Lectures 23 and 24
Lectures 23 and 24
Week 12
Department of Mechatronics
College of Electrical and Mechanical
Engineering
Nonlinear Analysis of a Shunt DC Motor
❑ The flux and the internal generated voltage 𝐸𝐴 of a DC machine are nonlinear functions
of its mmf and must be determined based on the magnetization curve.
❑ Two main contributors to the mmf are its field current and the armature reaction (if
present).
❑ Since the magnetization curve is a plot of the generated voltage vs. field current, the
effect of changing the field current can be determined directly from the magnetization
curve.
❑ If a machine has armature reaction, its flux will reduce with increase in load. The total
mmf in this case will be
𝔉𝑛𝑒𝑡 = 𝑁𝐹 𝐼𝐹 − 𝔉𝐴𝑅
❑ It is customary to define an equivalent field current that would produce the same output
voltage as the net (total) mmf in the machine; 𝔉𝐴𝑅
∗
𝐼𝐹 = 𝐼𝐹 −
𝑁𝐹
Nonlinear Analysis of a Shunt DC Motor
❑ Conducting a nonlinear analysis to determine the internal generated voltage in a DC
motor, we may need to account for the fact that a motor can be running at a speed other
than the rated one.
𝐸𝐴 𝑛
=
𝐸𝐴0 𝑛0
❑ Where 𝐸𝐴0 and 𝑛0 represent the reference (rated) values of voltage and speed,
respectively. Therefore, if the reference conditions are known from the magnetization
curve and the actual 𝐸𝐴 is computed, the actual speed can be determined.
Example 8-2
❑ A 50-hp, 250-V, 1200 r/min dc shunt motor without compensating windings has an
armature resistance (including the brushes and interpoles) of 0.06 Ω. Its field circuit has
a total resistance Radj + RF of 50 , which produces a no-load speed of 1200 r/min. There
are 1200 turns per pole on the shunt field winding, and the armature reaction produces
a demagnetizing magnetomotive force of 840 A• turns at a load current of 200 A. The
magnetization curve of this machine is shown in Figure.
❑ The maximum power out of the motor is directly proportional to its speed.
❑ For the field resistance control, the maximum power out of a DC motor is
constant, while the maximum torque is reciprocal to the motor speed.
Speed Control of Shunt DC Motors
❑ Torque and power limits as functions of motor speed for a shunt (or separately
excited) DC motor.
Example 8.3
❑ A 100 hp, 250 V, 1200 rpm DC shunt motor with an armature resistance of 0.03
and a field resistance of 41.67 . The motor has compensating windings, so
armature reactance can be ignored. Mechanical and core losses may be ignored
also. The motor is driving a load with a line current of 126 A and an initial speed
of 1103 rpm. Assuming that the armature current is constant.
For the magnetization curve shown in figure, what is the
motor speed if the field resistance is increased to 50 ?
Example 8.4
❑ Assuming that the motor next is connected as a separately excited and is initially
running with 𝑉𝐴 = 250 𝑉,𝐼𝐴 = 120 𝐴 and at 𝑛 = 1103 𝑟𝑝𝑚 while supplying a
constant-torque load, estimate the motor speed if VA is reduced to 200 V.
The series DC motor
❑ A series DC motor is a DC motor whose field windings consists of a relatively few
turns connected in series with armature circuit.
❑ The terminal characteristic of a series DC motor is quite different from that of the
shunt motor since the flux is directly proportional to the armature current
(assuming no saturation). An increase in motor flux causes a decrease in its
speed; therefore, a series motor has a dropping torque-speed characteristic.
❑ The induced torque in a series machine is
𝜏𝑖𝑛𝑑 = 𝐾𝜙𝐼𝐴
❑ Since the flux is proportional to the
armature current: 𝜙 = 𝑐𝐼𝐴
❑ where c is a proportionality constant.
The series DC motor
❑ Therefore, the torque is 𝜏𝑖𝑛𝑑 = 𝐾𝑐𝐼𝐴2
❑ Torque in the motor is proportional to the square of its armature current. Series
motors supply the highest torque among the DC motors. Therefore, they are used
as car starter motors, elevator motors etc.
❑ Assuming first that the magnetization curve is linear and no saturation occurs,
flux is proportional to the armature current: 𝜙 = 𝑐𝐼𝐴
𝜏𝑖𝑛𝑑
❑ Since the armature current is: 𝐼𝐴 = and the armature voltage: 𝐸𝐴 = 𝐾𝜙𝜔
𝐾𝑐
❑ The speed of unsaturated series motor inversely proportional to the square root
of its torque.
The series DC motor
❑ One serious disadvantage of a series motor is that its speed goes to infinity for a
zero torque.
❑ In practice, however, torque never goes to zero because of the mechanical, core,
and stray losses. Still, if no other loads are attached, the motor will be running
fast enough to cause damage.
❑ Steps must be taken to ensure that a
series motor always has a load!
❑ Therefore, it is not a good idea to
connect such motors to loads by a belt
or other mechanism that could break.
Example 8.5
❑ A 250 V series DC motor with compensating windings has a total series resistance
RA + RS of 0.08 . The series field consists of 25 turns per pole and the
magnetization curve is shown in figure.
❑ Since the shunt mmf and series mmf subtract from each other in a differentially
compounded motor, increasing load increases the armature current 𝐼𝐴 and
decreases the flux.
❑ When flux decreases, the motor speed increases further increasing the load. This
results in an instability (much worse than one of a shunt motor) making
differentially compounded motors unusable for any applications.
❑ In addition to that, these motors are not easy to
start. The motor typically remains still or turns
very slowly consuming enormously high
armature current.
❑ Stability problems and huge starting armature
current lead to these motors being never used
intentionally.
Example 8.6
❑ A 100 hp, 250 V compounded DC motor with compensating windings has an
internal resistance, including the series winding of 0.04 . There are 1000 turns
per pole on the shunt field and 3 turns per pole on the series windings. The
magnetization curve is shown below. The field resistor has been adjusted for the
motor speed of 1200 rpm. The mechanical, core, and stray losses may be
neglected.
❑ Find the no-load shunt field current.
❑ If the motor is cumulatively compounded, find
its speed when 𝐼𝐴 = 200 𝐴.
❑ If the motor is differentially compounded, find
its speed when 𝐼𝐴 = 200 𝐴.
The Permanent Magnet DC Motor
❑ A permanent magnet DC (PMDC) motor is a motor whose poles are made out of
permanent magnets.
❑ Advantages
o Since no external field circuit is needed, there are no field circuit copper losses;
o Since no field windings are needed, these motors can be considerable smaller.
❑ Disadvantages
o Since permanent magnets produces weaker flux densities then externally supported
shunt fields, such motors have lower induced torque.
o There is always a risk of demagnetization from extensive heating or from armature
reaction effects (via armature mmf).
Questions?