P-21133-D6-R1
P-21133-D6-R1
P-21133-D6-R1
Project:
INSTALLATION
Client: MAERSK
Vessel: CAP SAN NICOLAS
Class: ABS
Prepared: FB KMT
Reviewed AK ARK
Approved: JJ JJ
Date: 16/10/2021 23/05/2019
Consultant
ACE MARINE & ENGINEERING
SERVICES PTE. LTD.
FEASIBILITY STUDY REPORT
#14-03, Raffles City Tower,
250 North Bridge Road,
Singapore 179101
Telephone : +65 6832 8054
Fax : +65 6826 4120
Email: [email protected]
Web : www.acesingapore.com
REVISION HISTORY: 4
1. INTRODUCTION 5
7.3.1 Proposed Tap -Out Location from Ballast pumps to filter inlet 35
7.3.2 Pipe Line from Filter Outlet to UV Inlet 37
7.3.3 Pipe Line from UV Outlet to OVBD/Tank-In Line. 39
7.3.4 Pipe Line from Filter to Back Flush Pump 41
7.3.5 Pipe Line from Back flush Pump to OVBD Chest 43
7.3.6 System Bypass 45
7.3.7 Eductor Drive Line 47
7.3.8 Eductor Tap-In Line 49
7.3.9 Filter Bypass Line 51
7.3.10 Overall View 53
7.4 PIPE SPOOL MATERIAL TAKE-OFF 55
11. CONCLUSION 86
3
REVISION HISTORY:
4
1. INTRODUCTION
This booklet is prepared to report the feasibility study conducted for the installation of Ballast Water
Treatment System onboard the vessel CAP SAN NICOLAS. The intended ballast water treatment
system which is to be installed onboard is OPTIMARIN 1000 - 1274 Bk3 (1 Set). The main objective of
this report is to capture the findings of the feasibility study for the installation of BWTS equipment at
intended location and integration of the same with the vessels existing systems. Optimum placement of
equipment has been done based on space constraints, easiness for system integration and pressure
drop calculations. Detailed Material Take off for the piping spools, estimated foundation weights, Power
requirement of newly installed BWTS equipment & Modified ballast system pressure drop calculation is
also included in this feasibility report.
Location of new BWTS unit is proposed to be at the FWD of Engine at floor deck as highlighted in
Section 7.2 & 8. Even the existing BWTS Mahle is not working, we have not considered to remove this
BWTS skid from its existing position. Owner can decide later whether to remove the existing BWTS
equipment or to keep the same in original position. Equipment placement and pipe modification study
was conducted based on the 3D scan output of vessel.
Only 1 Set of Optimarin system has been considered even though the vessel is having 2 nos of
800m3/hr capacity Ballast pumps. Hence only one pump can be used at a time while Ballasting and De-
ballasting after the installation of BWTS system.
Reference Information: - The below listed drawings / documents are referred for the generation of this
feasibility study report.
5
2. MAIN PARTICULARS OF THE VESSEL
Class ABS
6
3. MAIN PARTICULARS OF OPTIMARIN BWTS USED ONBOARD
Manufacturer Optimarin
Model 1000/1274BK3
Ballast Pumps Capacity 800 m³/hr. at 40 MTH for each Ballast pump.
Qty 2 nos.
7
5. BASIC INFORMATION REGARDING OPTIMARIN BWTS.
The Optimarin Ballast Water Management System (OBS) is known for its simple and flexible assembly
of components. The system has been duly tested, evaluated and subsequently approved in accordance
to both IMO and USCG requirements for ballast water management systems (BWMS).
The OBS does not utilize any chemical or toxic agents for the treatment process and no free radicals are
left in the treated ballast water. Thus, the water treated in the OBS will have no more harmful effect on
tanks, coatings, structure, pipes and pumps than the ambient water itself. The treatment is based on
filtration and UV-treatment. The Optimarin BWTS has been tested successfully with all three salinities -
brackish, fresh and sea water.
The OBS is a component based system. That means that the system is based upon many different
components set up to work together to obtain a common task – clean and disable life in the ballast
water. The following will describe each individual main component. All components are tied together
with a control system.
Filter
The filter is removing the particles from the seawater during intake. It is therefore only in use
during ballasting. The filter screen is 40μm. The filter has a self-cleaning function by reversing
the flow direction and flushing the dirty water back into the sea.
Fig: - UV Chamber
The lamp cables are part of the lamp and will be replaced together with the lamp. Length of the
lamp cable is 3 meter.
The ballast water will flow through the inlet manifold, the UV chambers and out through the outlet
manifold. To ensure equal flow through each UV chamber, the inlet and outlet of the manifolds are
placed diagonally to each other. See examples below.
Fig: - UV Unit
9
MAIN COMPONENTS (FLEXIBLY PLACED)
Instruments: (a) Pressure transmitter [PT01] & (b) Flow meter [FM01]
The pressure transmitter is used to control the pressure during back-flushing of the filter.
The Flow meter monitors total flow through the ballast system.
• Signal from the flow meter is utilized by the PLC to control FPV.
• If flow failure, alarm and BWTS shut down will occur.
10
Manifold Ventilation Shut Off Valve
The manual valve shall stay open during operation. This will prevent air to accumulate in the UV-
chamber. Air displaces the water and may lead to insufficient cooling of the UV-lamps and pursuant
overheating.
11
UV Power cabinet (+UVPxx)
Each UV power cabinets provide power (up to 35kW) to one UV lamp. Terminals for connecting the
high voltage UV lamp (operational voltage: 2150VAC)
12
6. GENERAL INFORMATION OF VESSELS EXISTING BALLAST SYSTEM
13
7. FEASIBILITY USING OPTIMARIN 1000/1274 BK3 BALLAST SYSTEM
Sea water that enters the ballast system should be treated to required discharge standards to comply
with D-2 regulation as per IMO Ballast water management convention. UV treatment is applied during
uptake and discharge of ballast water in order to meet the proper D-2 discharge standards. Optimarin
Ballast system(1000 m3/s) used for this water treatment is to be properly integrated with the vessels
existing Ballast system. Below mentioned modifications to be made on the system
Treated ballast water from the BWTS system is Tie-in to tank-in / OVBD manifold of 450A pipe after
valves BA-41 and BA-38.
14
Back flush line is connected to the Existing Overboard chest through 100A pipe line before valve 109V.
Another Tie-out (of DN125) is taken from filter outlet and Tie-in to educator driving force line(125A)
before valve 103V (for educator drive water filtration) and Tie-out (200A) is taken from the educator
discharge line to filter outlet line for UV treatment.
Sampling point is provided at outlet line as per IMO requirement to take samples of the ballast water
coming from the UV Unit after treatment. Existing sampling point in the OVBD is to be replaced with new
sampling sets as per the details mentioned in Optimarin installation manual, makes it possible to take
the samples of water.
15
Fig : Sampling Device after the water treatment (Port side)
16
Clarification required from Vessel
Confirmation required whether the existing 150A pipe connected between BWTS inlet line and Tank
inlet line need to be removed or not .Approximate length of the existing pipe is 2.2m
17
7.1.3 Integrated Ballast System P&ID
18
7.2 PROPOSED LOCATION FOR THE BWTS EQUIPMENTS ONBOARD
Location of new BWTS unit is proposed to be at the FWD of Engine at floor deck as highlighted in
below snapshot. Even the existing BWTS Mahle is not working, we have not considered to remove
this BWTS skid from its existing position. Owner can decide later whether to remove the existing
BWTS equipment or to keep the same in original position.
PROPOSED
LOCATION
FOR
FILTER
PROPOSED
LOCATION
FOR FILTER
Fig: - Proposed location for Filter at Tank top FWD of Engine Room
20
PROPOSED LOCATION
FOR BACKFLUSH PUMP
Fig: - Proposed location for Back flush pump at Tank top FWD of Engine room
PROPOSED
LOCATION FOR
BACKFLUSH
PUMP
Fig: - Proposed location for Back flush pump at Tank top FWD of Engine room
21
Fig: - Proposed location for Filter & Back Flush Pump at Tank top FWD of Engine room.
22
7.2.2 Proposed Location for UV unit
PROPOSED
LOCATION FOR UV
UNIT
Fig: - Proposed location for UV Unit at Tank top FWDof Engine room
PROPOSED
LOCATION FOR
UV UNIT
Fig: - Proposed location for UV Unit at Tank top FWD of Engine room
23
Fig: - Proposed location for UV Unit at Tank top FWD of Engine room.
24
7.2.3 Proposed Location for Control Panel, Filter Control Panel and Interlock Panel
Fig: - Proposed location for Control Panel, Filter Control Panel & Interlock Panel at Tank Top FWD of
Engine room.
Fig: - Proposed location for Control Panel, Filter Control Panel & Interlock Panel at Tank Top FWD of
Engine room.
25
PROPOSED LOCATION FOR CONTROL PANEL, FILTER
CONTROL PANEL & INTERLOCK PANEL
Fig: - Proposed location for Control Panel, Filter Control Panel & Interlock Panel at Tank top FWD of
Engine room
Fig: - Proposed location for Control Panel, Filter Control Panel & Interlock Panel at Tank top FWD of
Engine room
26
7.2.4 Proposed location For UV Power Cabinet (6 nos)
PROPOSED LOCATION
FOR UV POWER
CABINETS
Fig: - Proposed location for UV Power Cabinet at Tank top FWD of Engine room
Fig: - Proposed location for UV Power Cabinet at Tank top FWD of Engine room
27
PROPOSED LOCATION FOR UV
POWER CABINETS
Fig: - Proposed location for UV Power Cabinet at Tank top FWD of Engine room
Fig: - Proposed location for UV Power Cabinet at Tank top FWD of Engine room
28
7.2.5 Proposed Location for Sensor Box and Terminal Box
PROPOSED LOCATION
FOR SENSOR BOX AND
TERMINAL BOX
Fig: - Proposed location for Sensor Box and Terminal Box at Tank Top FWD of Engine room.
29
Fig: - Proposed location for Sensor Box and Terminal Box at Tank Top FWD of Engine room.
30
7.2.6 Proposed Location for OBS Touch Panels
PROPOSED
LOCATION FOR OBS
TOUCH PANEL
PROPOSED
LOCATION FOR OBS
TOUCH PANEL
The proposed location for OBS Touch Panel at Navigation Deck requires confirmation from vessel
32
7.2.7 Preliminary BWTS arrangement
33
7.3 TAPPING LOCATIONS AND ROUTING OF NEW PIPE
7.3.1 Proposed Tap -Out Location from Ballast pumps to filter inlet
FILTER
SYSTEM BYPASS
FILTER
BALLAST PUMPS
SYSTEM BYPASS
35
FILTER
FILTER
BYPASS SYSTEM BYPASS
36
7.3.2 Pipe Line from Filter Outlet to UV Inlet
FILTER
UV UNIT
FILTER BYPASS
FLOW METER
Fig: - Line from Filter outlet to UV Inlet
FILTER
UV UNIT
FILTER BYPASS
FLOW METER
37
FILTER
UV UNIT
FILTER BYPASS
FLOW METER
38
7.3.3 Pipe Line from UV Outlet to OVBD/Tank-In Line.
UV UNIT
OVBD/TANK-IN LINE
SYSTEM BYPASS
LINE
UV UNIT
EXISTING TANK-
IN/OVBD LINE
SYSTEM BYPASS
39
UV UNIT
CONNECTED
TO EXISTING
SYSTEM BYPASS OVBD LINE
40
7.3.4 Pipe Line from Filter to Back Flush Pump
FILTER
BACKFLUSH
PUMP
FILTER
BACKFLUSH
PUMP
41
FILTER
BACKFLUSH
PUMP
42
7.3.5 Pipe Line from Back flush Pump to OVBD Chest
BACKFLUSH
PUMP
BACKFLUSH
PUMP
43
CONNECTED TO
EXISTING 100A
OVBD LINE
BACKFLUSH LINE
BACKFLUSH
PUMP
44
7.3.6 System Bypass
FILTER
UV UNIT
SYSTEM
BYPASS LINE
FROM BALLAST
PUMPS
FILTER
UV UNIT
SYSTEM
BYPASS LINE
45
FILTER
UV UNIT
CONNECTED
TO EXISTING
OVBD LINE
SYSTEM
BYPASS LINE
Fig: - System Bypass line
46
7.3.7 Eductor Drive Line
FILTER
OUTLET
LINE
CONNECTED TO
FILTER
EXISTING
EDUCTOR DRIVE
LINE
FILTER
OUTLET
LINE
FILTER
EXISTING
EDUCTOR
DRIVE LINE
FILTER
CONNECTED
FROM EXISTING
EDUCTOR DRIVE
LINE
`
Fig: - Eductor Drive line
48
7.3.8 Eductor Tap-In Line
UV UNIT
FILTER
OULTLET TO
UV INLET LINE FROM
EXISTING
EDUCTOR
DISCHARGE
LINE
FILTER
FROM
EXISTING
EDUCTOR
DISCHARGE
LINE
UV UNIT
FILTER
49
FROM EXISTING
EDUCTOR
UV UNIT DISCHARGE LINE
FILTER OULTLET TO
UV INLET LINE
FILTER
50
7.3.9 Filter Bypass Line
FILTER
FILTER
OUTLET
LINE
FILTER
INLET LINE
FILTER
FILTER
OUTLET
LINE
FILTER
INLET LINE
51
FILTER
OUTLET
FILTER LINE
FILTER
INLET LINE
52
7.3.10 Overall View
FILTER
FILTER OUTLET
LINE
BACK FLUSH
PUMP
UV UNIT
FILTER
OUTLET LINE
UV OUTLET
LINE
FILTER
BACK
FLUSH EDUCTOR
PUMP DISCHARGE
LINE
53
FILTER INLET LINE
FILTER
FILTER
OUTLET
LINE
UV OUTLET LINE
BACK
FLUSH
PUMP
`
Fig: - Overall View
FILTER
UV OUTLET
LINE
EDUCTOR
DRIVE
LINE
EDUCTOR SYSTEM
DISCHARGE BYPASS LINE
LINE
54
7.4 PIPE SPOOL MATERIAL TAKE-OFF
Detailed spool weight summary, Gasket and Bolt MTO & Piping BOM are appended here with.
55
CAP SAN NICOLAS- BWTS SPOOL DETAILS - SUMMARY
Line Weight
No. Line Number Material Standard /
Pipe Weight Flange Dia Reducer Weight Weight (Kg)
Dia (mm) Length (m) Flange Type Pressure Qty Weight (kg) Elbow Type Angle Dia (mm) Qty Weight (kg) Size (mm) Qty Dia (mm) Qty Inside Outside
(kg) (mm) Type (kg) (kg)
rating
Additional Fittings
BLIND PLATES,
9 SLIP ON , FF JIS 5K 450 2 64.000 150 2 5.200 Galvanized Galvanized 140.980
FLANGES
No. Line Number Bolt & Nut Type Bolt Size Qty Gasket type Standard Pressure rate Gasket Dia Qty
PIPE LINE FROM HEX BOLT & NUT M20X110 112 FF DIN PN10 50 1
TAP-OUT
1 HEX BOLT & NUT M20X190 48 FF DIN PN10 350 13
MANIFOLD TO
FILTER INLET HEX BOLT & NUT M16X80 4
SYSTEM BYPASS
4 HEX BOLT & NUT M20X190 16 FF DIN PN10 350 4
LINE
EDUCTOR DRIVE HEX BOLT & NUT M16X75 40 FF DIN PN10 125 7
6
LINE HEX BOLT & NUT M16X135 8
PIPE LINE FROM HEX BOLT & NUT M16X85 12 FF DIN PN10 80 1
7 FILTER TO BACK
FLUSH PUMP HEX BOLT & NUT M16X140 8 FF DIN PN10 100 3
7 ELBOW 90-LR DN100 6 GALVANIZED PIPE, STPG 370-E, SCH 40 Approx Weight is 23.04
8 ELBOW 90-SR DN100 1 GALVANIZED PIPE, STPG 370-E, SCH 40 Approx Weight is 2.56
9 ELBOW 90-LR DN125 6 GALVANIZED PIPE, STPG 370-E, SCH 40 Approx Weight is 38.88
TO BE GALVANIZED
10 ELBOW 90-SR DN125 4 GALVANIZED PIPE, STPG 370-E, SCH 40 Approx Weight is 17.28
BOTH INSIDE AND
11 ELBOW 90-LR DN200 3 GALVANIZED PIPE, STPG 370-E, SCH 40 Approx Weight is 60.3
OUTSIDE
12 ELBOW 90-SR DN200 5 GALVANIZED PIPE, STPG 370-E, SCH 40 Approx Weight is 67
13 ELBOW 90- SR DN350 12 GALVANIZED PIPE, ERWS 370,THK9.5 Approx Weight is 543.6
14 ELBOW 90- LR DN350 2 GALVANIZED PIPE, ERWS 370,THK9.5 Approx Weight is 135.8
15 Flange, Slip On(Flat Face) DN50 1 CARBON STEEL PN10 DIN Approx Weight is 2.4
16 Flange, Slip On(Flat Face) DN65 1 CARBON STEEL PN10 DIN Approx Weight is 3.1
17 Flange, Slip On(Flat Face) DN80 1 CARBON STEEL PN10 DIN Approx Weight is 3.8
18 Flange, Slip On(Flat Face) DN100 18 CARBON STEEL PN10 DIN Approx Weight is 77.4
TO BE GALVANIZED
19 Flange, Slip On(Flat Face) DN125 20 CARBON STEEL PN10 DIN Approx Weight is 116
BOTH INSIDE AND
20 Flange, Slip On(Flat Face) 150A 2 CARBON STEEL 5K JIS Approx Weight is 14.2
OUTSIDE
21 Flange, Slip On(Flat Face) 200A 2 CARBON STEEL 5K JIS Approx Weight is 12.66
22 Flange, Slip On(Flat Face) 200A 11 CARBON STEEL PN10 DIN Approx Weight is 108.9
23 Flange, Slip On(Flat Face) DN350 36 CARBON STEEL PN10 DIN Approx Weight is 802.8
24 Flange, Slip On(Flat Face) 450A 2 CARBON STEEL 5K JIS Approx Weight is 64
TO BE GALVANIZED
25 CON RED DN100X65 1 GALVANIZED STPG370E , SCH40, AS PER JIS BOTH INSIDE AND Approx Weight is 1.45
OUTSIDE
TO BE GALVANIZED
26 CON RED DN100X80 1 GALVANIZED STPG370E , SCH40, AS PER JIS BOTH INSIDE AND Approx Weight is 1.45
OUTSIDE
27 Blind Plate (15mm Thick) 100A 2 CARBON STEEL Approx Weight is 2.32
TO BE GALVANIZED
28 Blind Plate (15mm Thick) 150A 2 CARBON STEEL BOTH INSIDE AND Approx Weight is 5.2
OUTSIDE
29 Blind Plate (15mm Thick) 350A 3 CARBON STEEL Approx Weight is 42.6
NOTES:-
ADDITIONAL PIPE MATERIAL TO BE CONSIDERED AS PER STANDARD YARD PRACTICE
7.5 PRESSURE DROP CALCULATION
60
CALCULATION OF HEAD LOSS - BALLASTING THROUGH NO.1 BALLAST PUMP
61
Segment 3 - From Tap out to Filter inlet
Friction
Pipe
Loss Head
Flow Inner
Sl Length values Velocity Loss
Pipe Fittings (m3/hr) Quantity (ƒ or Dia
No. (hf)
(D)
K)
m m m/s m
1 DN 350 Pipe 800 7.4 - 0.0140 0.35 2.3093 0.0807
Stub in(No-Thru ) DN
2 800 - 1 0.7800 0.35 2.3093 0.2120
350
3 DN 350 Butterfly Valve 800 - 2 0.3500 0.35 2.3093 0.1903
Elbow DN350 (90 SR
4 800 - 6 0.3900 0.35 2.3093 0.6360
Bend)
Total Head Loss = 1.11899
Dynamic Pressure Loss = 0.110 bar
Difference in Height = 2.076m
Static Pressure loss due to difference in height = 0.204bar
Total Head Loss in Segment 3 =0.313bar
62
Segment 6 - From Tap in No:1 LS & DB WBT
Friction
Pipe
Loss Head
Flow Inner
Sl Length values Velocity Loss
Pipe Fittings (m3/hr) Quantity (ƒ or Dia
No. (hf)
(D)
K)
m m m/s m
1 350A Pipe 800 205 - 0.0140 0.35 2.3093 2.2354
2 450A Pipe 800 7.205 - 0.0140 0.45 1.3970 0.0223
3 Stub in(No-Thru ) 350A 800 - 2 0.7800 0.35 2.3093 0.4240
4 Stub in(No-Thru ) 450A 800 - 2 0.7200 0.45 1.3970 0.1432
5 350A Butterfly Valve 800 - 1 0.3500 0.35 2.3093 0.0951
6 Elbow 450A (90 SR Bend) 800 - 1 0.3600 0.45 1.3970 0.0358
Total Head Loss = 2.95591
Dynamic Pressure Loss = 0.290 bar
Total Head Loss in Segment 6 = 0.290 bar
Total calculated pressure loss = 0.86 bar
Total head loss for Ballasting while using No.1 Ballast pump= 1.39bar
63
CALCULATION OF HEAD LOSS DE- BALLASTING THROUGH NO.1 BALLAST PUMP
64
Segment 3 - From Tap out to UV inlet
Friction
Pipe
Loss Head
Flow Inner
Sl Length values Velocity Loss
Pipe Fittings (m3/hr) Quantity (ƒ or Dia
No. (hf)
(D)
K)
m m m/s m
1 DN 350 Pipe 800 8.4 - 0.0140 0.35 2.3093 0.0916
2 Stub in(No-Thru ) DN 350 800 - 2 0.7800 0.35 2.3093 0.4240
3 DN 350 Butterfly Valve 800 - 2 0.3500 0.35 2.3093 0.1903
Elbow DN350 (90 SR
4 800 - 5 0.3900 0.35 2.3093 0.5300
Bend)
Total Head Loss = 1.23590
Dynamic Pressure Loss = 0.121 bar
Difference in Height = 1.414m
Static Pressure loss due to difference in height = 0.139bar
Total Head Loss in Segment 3 = 0.260bar
Total head loss for De-ballasting while using No.1 Ballast pump= 0.91bar
66
POSITIVE SUCTION HEAD CALCULATION
Minimum Loadline draft of 6.83 (Ballast Condition Arrival) is taken for head calculation
Static Head = LWL - Height from Base line to pump suction = 6.83 -3.3m
S = Static
Height 3.53 m 0.35 bar
Head of Ballast pump together with positive suction head is higher than Total head loss using No.1 ballast
pump.
67
Updated H-Q curve of Ballast Pump
68
7.6 APPROXIMATE CABLE LENGTH REQUIRED
69
CAP SAN NICOLAS- ELECTRICAL CABLE SCHEDULE
From To
Estimated
Terminal
Sl.No No Name Supply/Device/Cabinet Gland size Gland range Device/Cabinet Gland size Gland range Voltage Conductor Note Cable
capacity
Length(m)
1 W 0000 Profibus Cable Cabinet M20 7-13 mm Cabinet M20 7-13 mm N/A N/A 2 SIENOPYR-FR-PROFIBUS-M-02Y(ST)CHX 20
2 W 0001 Power supply Control Panel (+CP) 440V Feeder Panel Yard - Control Panel (+CP) M25 9-17 mm 3x440 VAC Max 2.5 mm2 3 59
3 W 0004 Local audible and visible alarm 1 (AHL01) Control Panel (+CP) M20 7-13 mm Local audible and visible alarm 1 (AHL01) - 7-15 mm 24 VDC Max 1.5 mm2 4 Cable entry 3
4 W 0004B Local audible and visible alarm 2 (AHL02) Local audible and visible alarm 1 (AHL01) - 7-15 mm Local audible and visible alarm 2 (AHL02) - 7-15 mm 24 VDC Max 1.5 mm2 4 Cable entry 3
5 W 0010 Profinet Cable Cabinet M16 4.5-10 mm Cabinet M16 4.5-10 mm N/A N/A 4 L-9YH (ST) CH 2x2x0, 34/1, 5-100 GN VZN FRNC SF/UTP 26
6 W 0011 Power supply Filter Control (+FC) 440V Feeder Panel Yard - Filter Control (+FC) M32 11-21 mm 3x440 VAC Max 10mm2 3 62
7 W 0013 Filter Gear Motor (FGM01) Filter Control (+FC) M25 9-17 mm Filter Gear Motor (FGM01) M20 6-12 mm 3x440 VAC Max 2.5 mm2 3 24
8 W 0014 Back Flush Pump (BFP01) Filter Control (+FC) M32 11-21 mm Back Flush Pump (BFP01) M32 11-21 mm 3x440 VAC Max 10mm2 3 25
9 W 0020.1 Communication between +CP and +RCP (CCR) Control Panel (+CP) M16 4.5-10 mm Remote control panel (CCR) M16 4.5-10 mm N/A N/A 4TP Ethernet-min. CAT5E cable Max. 100m (Reffer Note 1) 224
10 W 0020.2 Communication between +CP and +RCP (Nav. Bridge) Control Panel (+CP) M16 4.5-10 mm Remote control panel(Nav. Bridge) M16 4.5-10 mm N/A N/A 4TP Ethernet-min. CAT5E cable Max. 100m (Reffer Note 1) 255
11 W 0021 Pressure Transmitter signal (PT01) Pressure Transmitter signal (PT01) MPM 6-12 mm Filter Control (+FC) M20 7-13 mm 4-20 mA Max 1.5 mm2 2 EMC gland, use shielded cable 32
12 W 0022 Flow Meter signal (FM01) Flow Meter (FM01) M20 7-13 mm Filter Control (+FC) M20 7-13 mm 4-20 mA Max 1.5 mm2 4 EMC gland, use shielded cable 30
13 W 0023 Filter signals (DPS) Filter Control (+FC) M25 9-17 mm Filter DPS M20 6-12 mm 24 VDC Max 1.5 mm2 4 24
14 W 0031 Filter Inlet Valve (FIV01) Filter Control (+FC) M20 7 -13 mm Filter Inlet Valve (FIV01) M20 7-13 mm 24 VDC Max 1.5 mm2 6 24
15 W 0032 Filter Outlet Valve (FOV01) Filter Control (+FC) M20 7 -13 mm Filter Outlet Valve (FOV01) M20 7-13 mm 24 VDC Max 1.5 mm2 6 24
16 W 0033 Filter Bypass Valve (FBV01) Filter Control (+FC) M20 7 -13 mm Filter Bypass Valve (FBV01) M20 7-13 mm 24 VDC Max 1.5 mm2 6 24
17 W 0034 Optimarin Bypass Valve (OBV01) Filter Control (+FC) M20 7 -13 mm Optimarin Bypass Valve (OBV01) M20 7-13 mm 24 VDC Max 1.5 mm2 6 27
18 W 0035 Filter Flush Valve (FFV01) Filter Control (+FC) M20 7 -13 mm Filter Flush Valve (FFV01) M20 7-13 mm 24 VDC Max 1.5 mm2 6 24
19 W 0036 Drive Water Valve (DWV01) Filter Control (+FC) M20 7 -13 mm Drive Water Valve (DWV01) M20 7-13 mm 24 VDC Max 1.5 mm2 6 25
20 W 0037 Mixed Water Valve (MWV01) Filter Control (+FC) M20 7 -13 mm Mixed Water Valve (MWV01) M20 7-13 mm 24 VDC Max 1.5 mm2 6 25
21 W 0041 Power supply Sensor Box 1 (+SB1) 440V Feeder Panel Yard - Sensor Box 1 (+SB1) M25 9-17 mm 3x440 VAC Max 2.5 mm2 3 55
22 W 0042 Power supply Sensor Box 2 (+SB2) 440V Feeder Panel Yard - Sensor Box 2 (+SB2) M25 9-17 mm 3x440 VAC Max 2.5 mm2 3 55
23 W 0060 Flow Pressure Valve Power supply Sensor Box 1 (+SB1) M20 7 -13 mm FPV01 Position supply M20 7-13 mm 2x230 VAC + G Max 1.5 mm2 3 20
24 W 0061 Flow Pressure Valve Position signal Sensor Box 1 (+SB1) M20 7 -13 mm FPV01 Position signal M20 7-13 mm 4-20 mA Max 1.5 mm2 2 EMC gland, use shielded cable 20
25 W 0062 Water Sensor signal (WS01) Water Sensor (WS01) ISO 4,5-7 mm Sensor Box 1 (+SB1) M20 7-13 mm 24 VDC Max 1.5 mm2 3 ISO Plugg 4400 40
26 W 0063 Air Release Valve (ARV01) Air Release Valve (ARV01) M20 6-12 mm Sensor Box 1 (+SB1) M20 7-13 mm 24 VDC Max 1.5 mm2 4 40
27 W 0101 Power supply UV Power cabinet 01 (UVP01) 440V Feeder Panel Yard - UV Power cabinet 01 (+UVP01) M40 19-28 mm 3x440 VAC Max 35 mm2 3 59
28 W 0104 UV Lamp supply UV Power cabinet 01 (+UVP01) M40 19-28 mm Terminal Box 01 (+TB01) M40 19-28 mm max 5000VAC Max 10 mm2 2 Ref OBS Installation manual 24
29 W 0105 Temperature Switch (TS01) Temperature Switch (TS01) M12 6-8 mm UV Power cabinet 01 (+UVP01) M20 7-13 mm 24 VDC Max 2.5 mm2 2 25
30 W 0110 UV Intensity Sensor (UV01) UV Intensity Sensor (UV01) Plug - Sensor Box 1 (+SB1) M16 4,5-10 mm 4-20 mA Max 1.5 mm2 2 Optimarin supply 5m 3
31 W 0111 Temperature Transmitter (TT01) Temperature Transmitter (TT01) Plug - Sensor Box 1 (+SB1) M16 4,5-10 mm 4-20 mA Max 1.5 mm2 2 Optimarin supply 5m 3
32 W 0113 Terminal Box open signal (TB01) Terminal Box 01 (+TB01) M20 7-13 mm Sensor Box 1 (+SB1) M20 7-13 mm 24 VDC Max 1.5 mm2 2 2
33 W 0131 UV Chamber Valve Inlet (UVV01A) Sensor Box 1 (+SB1) M20 7-13 mm UV Chamber Valve Intlet (UVV01A) M20 7-13 mm 24 VDC Max 1.5 mm2 6 3
34 W 0132 UV Chamber Valve Outlet (UVV01B) Sensor Box 1 (+SB1) M20 7-13 mm UV Chamber Valve Outlet (UVV01B) M20 7-13 mm 24 VDC Max 1.5 mm2 6 3
35 W 0201 Power supply UV Power cabinet 02 (UVP02) 440V Feeder Panel Yard - UV Power cabinet 02 (+UVP02) M40 19-28 mm 3x440 VAC Max 35 mm2 3 60
36 W 0204 UV Lamp supply UV Power cabinet 02 (+UVP02) M40 19-28 mm Terminal Box 02 (+TB02) M40 19-28 mm max 5000VAC Max 10 mm2 2 Ref OBS Installation manual 24
37 W 0205 Temperature Switch (TS02) Temperature Switch (TS02) M12 6-8 mm UV Power cabinet 02 (+UVP02) M20 7-13 mm 24 VDC Max 2.5 mm2 2 25
38 W 0210 UV Intensity Sensor (UV02) UV Intensity Sensor (UV02) Plug - Sensor Box 1 (+SB1) M16 4,5-10 mm 4-20 mA Max 1.5 mm2 2 Optimarin supply 5m 3
39 W 0211 Temperature Transmitter (TT02) Temperature Transmitter (TT02) Plug - Sensor Box 1 (+SB1) M16 4,5-10 mm 4-20 mA Max 1.5 mm2 2 Optimarin supply 5m 3
40 W 0213 Terminal Box open signal (TB02) Terminal Box 02 (+TB02) M20 7-13 mm Sensor Box 1 (+SB1) M20 7-13 mm 24 VDC Max 1.5 mm2 2 2
41 W 0231 UV Chamber Valve Inlet (UVV02A) Sensor Box 1 (+SB1) M20 7-13 mm UV Chamber Valve Intlet (UVV02A) M20 7-13 mm 24 VDC Max 1.5 mm2 6 3
42 W 0232 UV Chamber Valve Outlet (UVV02B) Sensor Box 1 (+SB1) M20 7-13 mm UV Chamber Valve Outlet (UVV02B) M20 7-13 mm 24 VDC Max 1.5 mm2 6 3
43 W 0301 Power supply UV Power cabinet 03 (UVP03) 440V Feeder Panel Yard - UV Power cabinet 03 (+UVP03) M40 19-28 mm 3x440 VAC Max 35 mm2 3 60
44 W 0304 UV Lamp supply UV Power cabinet 03 (+UVP03) M40 19-28 mm Terminal Box 03 (+TB03) M40 19-28 mm max 5000VAC Max 10 mm2 2 Ref OBS Installation manual 24
45 W 0305 Temperature Switch (TS03) Temperature Switch (TS03) M12 6-8 mm UV Power cabinet 03 (+UVP03) M20 7-13 mm 24 VDC Max 2.5 mm2 2 25
46 W 0310 UV Intensity Sensor (UV03) UV Intensity Sensor (UV03) Plug - Sensor Box 1 (+SB1) M16 4,5-10 mm 4-20 mA Max 1.5 mm2 2 Optimarin supply 5m 3
47 W 0311 Temperature Transmitter (TT03) Temperature Transmitter (TT03) Plug - Sensor Box 1 (+SB1) M16 4,5-10 mm 4-20 mA Max 1.5 mm2 2 Optimarin supply 5m 3
48 W 0313 Terminal Box open signal (TB03) Terminal Box 03 (+TB03) M20 7-13 mm Sensor Box 1 (+SB1) M20 7-13 mm 24 VDC Max 1.5 mm2 2 2
49 W 0331 UV Chamber Valve Inlet (UVV03A) Sensor Box 1 (+SB1) M20 7-13 mm UV Chamber Valve Intlet (UVV03A) M20 7-13 mm 24 VDC Max 1.5 mm2 6 3
50 W 0332 UV Chamber Valve Outlet (UVV03B) Sensor Box 1 (+SB1) M20 7-13 mm UV Chamber Valve Outlet (UVV03B) M20 7-13 mm 24 VDC Max 1.5 mm2 6 3
51 W 0401 Power supply UV Power cabinet 04 (UVP04) 440V Feeder Panel Yard - UV Power cabinet 04 (+UVP04) M40 19-28 mm 3x440 VAC Max 35 mm2 3 60
52 W 0404 UV Lamp supply UV Power cabinet 04 (+UVP04) M40 19-28 mm Terminal Box 04 (+TB04) M40 19-28 mm max 5000VAC Max 10 mm2 2 Ref OBS Installation manual 24
53 W 0405 Temperature Switch (TS04) Temperature Switch (TS04) M12 6-8 mm UV Power cabinet 04 (+UVP04) M20 7-13 mm 24 VDC Max 2.5 mm2 2 25
54 W 0410 UV Intensity Sensor (UV04) UV Intensity Sensor (UV04) Plug - Sensor Box 2 (+SB2) M16 4,5-10 mm 4-20 mA Max 1.5 mm2 2 Optimarin supply 5m 3
55 W 0411 Temperature Transmitter (TT04) Temperature Transmitter (TT04) Plug - Sensor Box 2 (+SB2) M16 4,5-10 mm 4-20 mA Max 1.5 mm2 2 Optimarin supply 5m 3
56 W 0413 Terminal Box open signal (TB04) Terminal Box 04 (+TB04) M20 7-13 mm Sensor Box 2 (+SB2) M20 7-13 mm 24 VDC Max 1.5 mm2 2 2
57 W 0431 UV Chamber Valve Inlet (UVV04A) Sensor Box 2 (+SB2) M20 7-13 mm UV Chamber Valve Intlet (UVV04A) M20 7-13 mm 24 VDC Max 1.5 mm2 6 3
58 W 0432 UV Chamber Valve Outlet (UVV04B) Sensor Box 2 (+SB2) M20 7-13 mm UV Chamber Valve Outlet (UVV04B) M20 7-13 mm 24 VDC Max 1.5 mm2 6 3
59 W 0501 Power supply UV Power cabinet 05 (UVP05) 440V Feeder Panel Yard - UV Power cabinet 05 (+UVP05) M40 19-28 mm 3x440 VAC Max 35 mm2 3 60
60 W 0504 UV Lamp supply UV Power cabinet 05 (+UVP05) M40 19-28 mm Terminal Box 05 (+TB05) M40 19-28 mm max 5000VAC Max 10 mm2 2 Ref OBS Installation manual 24
61 W 0505 Temperature Switch (TS05) Temperature Switch (TS05) M12 6-8 mm UV Power cabinet 05 (+UVP05) M20 7-13 mm 24 VDC Max 2.5 mm2 2 25
62 W 0510 UV Intensity Sensor (UV05) UV Intensity Sensor (UV05) Plug - Sensor Box 2 (+SB2) M16 4,5-10 mm 4-20 mA Max 1.5 mm2 2 Optimarin supply 5m 3
63 W 0511 Temperature Transmitter (TT05) Temperature Transmitter (TT05) Plug - Sensor Box 2 (+SB2) M16 4,5-10 mm 4-20 mA Max 1.5 mm2 2 Optimarin supply 5m 3
64 W 0513 Terminal Box open signal (TB05) Terminal Box 05 (+TB05) M20 7-13 mm Sensor Box 2 (+SB2) M20 7-13 mm 24 VDC Max 1.5 mm2 2 2
65 W 0531 UV Chamber Valve Inlet (UVV05A) Sensor Box 2 (+SB2) M20 7-13 mm UV Chamber Valve Intlet (UVV05A) M20 7-13 mm 24 VDC Max 1.5 mm2 6 3
66 W 0532 UV Chamber Valve Outlet (UVV05B) Sensor Box 2 (+SB2) M20 7-13 mm UV Chamber Valve Outlet (UVV05B) M20 7-13 mm 24 VDC Max 1.5 mm2 6 3
2
67 W 0601 Power supply UV Power cabinet 06 (UVP06) 440V Feeder Panel Yard - UV Power cabinet 06 (+UVP06) M40 19-28 mm 3x440 VAC Max 35 mm 3 60
2
68 W 0604 UV Lamp supply UV Power cabinet 06 (+UVP06) M40 19-28 mm Terminal Box 06 (+TB06) M40 19-28 mm max 5000VAC Max 10 mm 2 Ref OBS Installation manual 24
2
69 W 0605 Temperature Switch (TS06) Temperature Switch (TS06) M12 6-8 mm UV Power cabinet 06 (+UVP06) M20 7-13 mm 24 VDC Max 2.5 mm 2 25
2
70 W 0610 UV Intensity Sensor (UV06) UV Intensity Sensor (UV06) Plug - Sensor Box 2 (+SB2) M16 4,5-10 mm 4-20 mA Max 1.5 mm 2 Optimarin supply 5m 3
2
71 W 0611 Temperature Transmitter (TT06) Temperature Transmitter (TT06) Plug - Sensor Box 2 (+SB2) M16 4,5-10 mm 4-20 mA Max 1.5 mm 2 Optimarin supply 5m 3
2
72 W 0613 Terminal Box open signal (TB06) Terminal Box 06 (+TB06) M20 7-13 mm Sensor Box 2 (+SB2) M20 7-13 mm 24 VDC Max 1.5 mm 2 2
2
73 W 0631 UV Chamber Valve Inlet (UVV06A) Sensor Box 2 (+SB2) M20 7-13 mm UV Chamber Valve Intlet (UVV06A) M20 7-13 mm 24 VDC Max 1.5 mm 6 3
2
74 W 0632 UV Chamber Valve Outlet (UVV06B) Sensor Box 2 (+SB2) M20 7-13 mm UV Chamber Valve Outlet (UVV06B) M20 7-13 mm 24 VDC Max 1.5 mm 6 3
2
75 W 2001 Power supply Interlock Panel 1 (+IP01) 440V Feeder Panel Yard - Interlock Panel 1 (+IP01) M25 9-17 mm 3x440 VAC Max 2.5 mm 3 61
2
76 W 2010 Interlock signal 00 (NO.1 Ballast Pump) GSP Yard - Interlock Panel 1 (+IP01) M20 7-13 mm 24 VDC Max 1.5 mm 2 20
2
77 W 2011 Interlock signal 01 (NO.2 Ballast Pump) GSP Yard - Interlock Panel 1 (+IP01) M20 7-13 mm 24 VDC Max 1.5 mm 2 20
2
78 W 2012 Interlock signal 02 (Valve BA-31) VRCS Yard - Interlock Panel 1 (+IP01) M20 7-13 mm 24 VDC Max 1.5 mm 2 75
2
79 W 2013 Interlock signal 03 (Valve BA-32) VRCS Yard - Interlock Panel 1 (+IP01) M20 7-13 mm 24 VDC Max 1.5 mm 2 75
2
80 W 2014 Interlock signal 04 (Valve BA-33) VRCS Yard - Interlock Panel 1 (+IP01) M20 7-13 mm 24 VDC Max 1.5 mm 2 75
2
81 W 2015 Interlock signal 05 (Valve BA-34) VRCS Yard - Interlock Panel 1 (+IP01) M20 7-13 mm 24 VDC Max 1.5 mm 2 75
2
82 W 2016 Interlock signal 06 (Valve BA-35) VRCS Yard - Interlock Panel 1 (+IP01) M20 7-13 mm 24 VDC Max 1.5 mm 2 75
2
83 W 2017 Interlock signal 07 (Valve BA-36) VRCS Yard - Interlock Panel 1 (+IP01) M20 7-13 mm 24 VDC Max 1.5 mm 2 75
2
84 W 2018 Interlock signal 08 (Valve BA-39) VRCS Yard - Interlock Panel 1 (+IP01) M20 7-13 mm 24 VDC Max 1.5 mm 2 75
2
85 W 2019 Interlock signal 09 (Valve BA-40) VRCS Yard - Interlock Panel 1 (+IP01) M20 7-13 mm 24 VDC Max 1.5 mm 2 75
2
86 W 2020 Interlock signal 10 (Valve BA-42) VRCS Yard - Interlock Panel 1 (+IP01) M20 7-13 mm 24 VDC Max 1.5 mm 2 75
2
87 W 2021 Interlock signal 11 (Valve BA-104) Limit Switch Yard - Interlock Panel 1 (+IP01) M20 7-13 mm 24 VDC Max 1.5 mm 2 28
2
88 W 2022 Interlock signal 12 (Valve BA-106) Limit Switch Yard - Interlock Panel 1 (+IP01) M20 7-13 mm 24 VDC Max 1.5 mm 2 28
2
89 W 2023 Interlock signal 13 (Valve BV01) Limit Switch Yard - Interlock Panel 1 (+IP01) M20 7-13 mm 24 VDC Max 1.5 mm 2 32
Additional Notes
1. If cable length exceeds 100m, a switch(signal booster) needs to be installed after each 100 meters.
7.7 PRELIMINARY SLD
As per the feedback received two Optimarin OBS touch panels will be fitted onboard (one at CCR and
one at bridge). Kindly confirm whether the cable connections to these panels from main control cabinet
is connected in parallel or loop connection (from main panel to CCR remote panel and from CCR remote
panel to Bridge Remote Panel) to be provided.
72
7.8 STRUCTURAL WEIGHT ESTIMATION OF NEW FOUNDATION FOR BWTS EQUIPMENTS
(FOR 1000/1274BK3)
74
7.9 POWER REQUIREMENTS OF BWTS EQUIPMENTS
Optimarin1000/1274 BK3 system has estimated Power rating of 240kW. New Circuit breakers as per
Optimarin recommendation is to be provided at the 440V Feeder panel. Spare breakers are available
onboard the vessel. Existing spare breakers can be replaced with new breakers as per the required
current rating.
75
Clarification required from Vessel
As per the OPTIMARIN installation manual, 11 new circuit breakers need to be installed in 440 feeder
panel. Required confirmation from vessel whether all these 11 new circuit breakers can be fitted in the
existing 440V feeder panel.
If we do not have enough space, there is another option to install the new breakers in rear side of the
existing feeder panel.
76
7.9.1 Electric Load Analysis
Vessels existing electrical load analysis is recalculated to integrate the above mentioned BWTS
components in different vessels conditions. Below summary represents the percentage power
consumption at different vessel condition. As per existing Electrical Load Analysis, the ballast pump
operation is mentioned at Conditions Load / Unload in port. Updated Percentage consumption at these
conditions is provided below.
Without No No No
5*4320 1*4320 1*4320 68.20 63.30 37.40
Thruster Change Change Change
At Port In /
2
Out
With No No No
5*4320 2*4320 1*4320 86.40 77.00 25.90
Thruster Change Change Change
3 At Load / Unload 4*4320 1*4320 1*4320 79.60 40.80 21.70 80.70% 44.90 25.80
No
4 At Harbor 1*4320 28.40
Change
Black 32.40 No
1*4320
Out % Change
At
5
Emergency
No
Fire 1*4320 37.00
Change
77
8. ADDITIONAL MODIFICATIONS TO BE MADE ON SITE
New Check valve to be added on the eductor suction line as shown in below snap.
Fig: - CV01 (New Check Valve) Valve on Existing Eductor Suction Line
78
New Butterfly valve to be added on the eductor discharge line as shown in below snap.
Fig: - BV01 (New Butterfly Valve) Valve on Existing Eductor Discharge Line
Existing Check valve 107V at the overboard line is to be relocated on site as shown in below
picture
RELOCATED EXISTING
CHECK VALVE 107V
79
Existing sampling pipe in the OVBD pipe (350mm diameter) has to be removed and new
Optimarin supply has to be installed .
Sampling point is to be fitted such that there is enough space available for samples to be
collected and for that, the better option is to install the sampling tube in 90 degrees of the pipe
(towards FWD)
EXISTING SAMPLING
POINT ON OVBD
80
The line connecting to and from existing BWTS system needs to be blinded.
Fig: - Existing BWTS Back Flush Line to OVBD Chest Needs to be Blinded
81
Fig: - Existing connection between eductor suction Line & Existing BWTS System Line Needs to be
Blinded
82
9. ENGINE ROOM HATCH
All the BWTS equipments & spools can be lowered down to the engine room through engine room
hatch. Size of the hatch opening is approximately 2190x2240mm.
83
10. FEEDBACK RECEIVED FROM OPTIMARIN
4) GPS Integration
In given Installation manual the Integration of GPS to Optimarin Ballast system is not included. We have
asked Optimarin whether this is an optional integration and also to provide further details on this regard
if the vessel need to integrate the Optimarin BWTS system to vessels GPS
As per confirmation from Optimarin, integration with GPS is optional. It would cost additional 2511 EUR
for GPS junction box.
85
11. CONCLUSION
As per the feasibility study, placing of the Optimarin Ballast Water Treatment System OPTIMARIN
1000/1274 BK3 can be installed onboard the vessel CAP SAN NICOLAS with some structural & piping
modifications as shown in Section 7 & 8 of this report.
86
APPENDIX 1 – OPTIMARIN SCOPE OF SUPPLY
87