Commissioning Liquefier Machine Record

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 6

LINDE GAS (THAILAND) LTD.

Seting parameter for EKC.315 Danfoss Tag.no : 4EA1


Factory Default
Function Parameter Min Max
Setting Setting

Normal display
Show the actual supperheat/valve's operat - K K
Define veiw in O17
If you wish to see the expansion valve's ac - % %
,give the lower buttom a brief push (1s) define view in O17
Referance
Set the requirede set point - -60C' 50C'
Differantial r01 0.1K 10.0K 2.00
Units (0=C' +bar/1=F'+pisg) r05 0 1 C-b
External contribution to the referance r06 -50 K 50 K 00.0
Correction of signal from S2 r09 -1.0 K 1.0 K 00.0
Correction of signal from S3 r10 -10 K 10 K 00.0
Start/stop of refrigeration r12 OFF ON ON
Define thermostat function
(0=no thermostat function , 1=On/off therm r14 0 1 000
Alarm
Upper deviation (above the themperature se A01 0K 50K 5.0
Lower deviation (above the themperature se A02 0K 50K 3.0
Alarm's time delay A03 0 min 90 min 030
Regulating parameters
P: Amplification factor Kp n04 0.5 20 03.0
I : Integration time T n05 30S 600S 120
D: Differentiation time Td (0=off) n06 0S 90S Off
Max.value of superheat reference n09 2K 15K 006
Min.value of superheat reference n10 1K 12K 004
MOP (max=off) n11 0.0bar60 bar Off
Period time (only when AKV/A valve is used n13 3S 10S 006
Stability factor for superheat control.
Changes should only be made by trained sta n18 0 10 005
Damping of amplification around referance valve
Changes should only be made by trained sta n19 0.2 1 00.3
Amplification factor for superheat
Changes should only be made by trained sta n20 0 10 00.4
LINDE GAS (THAILAND) LTD.

Seting parameter for EKC.315 Danfoss Tag.no : 4EA1


Factory Default
Function Parameter Min Max
Setting Setting

Definition of superheat control 1=mss,2= n21 1 2 001


Value of min.superheat referance for loads n22 1 15 002
Standby temperature when valve closed (TQ valve only)
Changes should only be made by trained sta n26 -15K 20K 000
Standby temperature when valve open (TQ valve only)
Changes should only be made by trained sta n27 5K 50K 020
Max.opening degree
Changes should only be made by trained sta n32 0 100 100
Miscellaneous
Controller's address o03* 1 60
ON/OFF switch (service-pin message) o04* - -
Define valve and output signal:
0=off
1:TQ.AO : 0-20mA
2:TQ.AO : 4-20mA o09 0 5 000
3:AKV.AO : 0-20mA
4:AKV.AO : 4-20mA
5:AKV.AO : EKC 347-slave
Define input signal on the analoge input AIA
0: no signal
1: Temperature setpoint . 0-20 mA
2: Temperature setpoint . 4-20 mA o10 0 4 000
3: Displacement of superheat referance 0-20 mA
4: Displacement of superheat referance 4-20 mA
Set supply voltage freguency o12 50Hz 60Hz 50
Select display for " nornal pictures:
1: Superheat
2: Valve's opening degree o17 1 3 001
3: Air temperature
Manual control of outputs
Off : no manual control
1: Relay for solenoid valve : select ON o18 Off 3 000
2: AKV/A Output : select ON
LINDE GAS (THAILAND) LTD.

Seting parameter for EKC.315 Danfoss Tag.no : 4EA1


Factory Default
Function Parameter Min Max
Setting Setting

3: Alarm relay activated (cut out)


Working range for pressure transmitter-min o20 -1bar 60 bar -01.0
Working range for pressure transmitter-max o21 -1bar 60 bar 12.0
Seting for the fuction o09
Set temperature vallue or opening degree o27 -70 C'160 C' -35.0
signal must be minimum (0 or 4 mA)
Set temperature vallue or opening degree o28 -70 C' 160 C' 15.0
signal must be maximum (20 mA)
Refrigerance seting o30 0 29 000
R404a ; 19
Service
TQ valve actuator u04 C'
Referance of the valve actuator temperatur u05 C'
Analog input AIA (18-19) u06 mA
Analog output AO (2-5) u08 mA
Read status of input DI u10 on/off
Thermostate cut-in time u18 min.
Temperature at S2 sensor u20 C'
Superheat u21 K
Superheat referance u22 K
Read AKV valve opening degree u24 C'
Read evaporating pressure u25 bar
Read evaporating temperature u26 C'
Temperature at S3 sensor u27 C'
Temperature referance u28 C'
Read signal at pressure transmitter input u29 mA
Remark
Factory setting
If you need to return to the factory-set values,it can be done in this way
- Cut out the supply voltage to the controller
- Keep both buttom depressed at the same time as you reconnect the supply

REV.0 Prepared by QE/EN


LINDE GAS (THAILAND) LTD.

Seting parameter for EKC.315 Danfoss Tag.no : 4EA1


Factory Default
Function Parameter Min Max
Setting Setting

12/11/2006