AC024KN4DCH+(CNH244DK)_Submittal_CAC+360+CST_01152021

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

SUBMITTAL AC024KN4DCH/AA Page 1 of 5

Samsung 360 Cassette, Single Zone, Split System

Job Name Location


Purchaser Engineer
Submitted to Reference Approval Construction
Unit Designation Schedule #
Specifications
Indoor Unit Model Number (US Code) AC024KN4DCH/AA (CNH244DK)
Model
Outdoor Unit Model Number (US Code) AC024JXADCH/AA (CXH24ADJ)
Nominal Capacity Cooling / Heating (Btu/h) 24,000 / 27,000
Cooling (Btu/h) 7,000 - 27,000
Capacity Range
Heating (Btu/h) 5,200 - 31,000
SEER / EER 20.50 / 11.10
Performance Shown with PC4NUNMUN Shown with PC4NUDMUN
COP (nominal heating) 3.2 (open type panel) (ceiling type panel)
HSPF 10.0
AHRI Certification Number 8856687 General Information
Condensate (pints/h) 6.8 • The indoor unit shall be a round ceiling cassette with 360°, even air distribution
Voltage ø / V / Hz 1 / 208-230 / 60 • The outdoor unit shall supply power to indoor unit via 14 AWG X 3 power wire
Working Voltage Range (VAC) 176 - 254 (max. 3% deviation from each)
Operating Current Cooling (A) 2.80 / 9.80 / 12.00 • Auto-restart after power loss
Power
(min. / std. / max.) Heating (A) 2.50 / 11.60 / 14.50
Max. Breaker Amps 20 • The outdoor unit shall have a snow accumulation prevention option setting to prevent snow drifting
Min. Circuit Ampacity (A) against an idle outdoor unit.
12.06
WXHXD Indoor Unit 37 1/4 X 11 X 37 1/4 • The indoor unit shall have a removable EEPROM that stores system programming information, unit
(in.) Outdoor Unit 37 X 39 11/16 X 13 name, and other data
Dimensions
Weight Indoor Unit 46.3
(lbs.) • Electro-static, washable, pleated filter as standard (included with fascia panel).
Outdoor Unit 142.2
Sound Pressure Indoor Unit dB(A) L/M/H 29 / 33 / 36 • Built in condensate pump with maximum 29" lift from the bottom of the unit, check valve, and float
Level switch that disables indoor unit during overflow detection
Outdoor Unit dB(A) Cooling / Heating (high) 50 / 50
23 ~ 115°F (-5 ~ 46°C) • Knock-out for outside air capability (with booster fan connection)
Cooling
Operating Outdoor 0 ~ 115°F (-18 ~ 46°C) W/Baffle
• Pipe connections at the outdoor unit shall be made inside the unit chassis. Refrigerant pipes can
Temperatures Heating -4 ~ 75°F (-20 ~ 24°C)
exit through the front, side, rear, or bottom sides of the outdoor unit.
°F (°C) Cooling 61 ~ 90°F (16 ~ 32°C)
Indoor
Heating T ≤ 80°F (27°C) • Fascia panel shall have LED indicator lights and an infrared receiver
High side (flare) 1/4"
Indoor & Outdoor • The indoor unit shall not have air louvers or blades allowing full airflow without restriction. Air direction
Low side (flare) 5/8"
Pipe control shall be achieved by creating a low pressure area near air outlet causing discharge air to
Maximum (ft.) 164 change direction angle.
Connections
Maximum Vertical Separation (ft.) 98
Condensate Connection 1 1/4" OD, 1" ID • Fixed or auto-swing air direction shall be possible with wireless, touch, or premium wired controller
(10° ~ 60° angle)
Type R410A
Factory Charge oz. 74.08 • Independent air distribution control shall be possible with wireless or premium wired controller (three
Refrigerant
Charged for 25 ft directions, 10° ~ 60° angle)
Additional Refrigerant 0.11 oz./ft. over 25 ft
• The outdoor unit shall have a night time quiet mode option to reduce operating sound during the
Manufacturer Samsung night (automatic or manual activation with dry contact signal).
Compressor Type Inverter Driven, Twin BLDC Rotary
RLA Amps 9.0 Construction
The outdoor unit shall be galvanized steel with a baked on powder coated finish for durability
Type BLDC (1) With Turbo Type Fan (1)
Evaporator Air Volume CFM (L/M/H) 480 / 547 / 646 The indoor unit shall be have a galvanized steel frame with HIPS chassis and fascia panel certified to
Fan Output Watts 65 X 1 UL94 V0.
FLA Amps 0.33
Heat Exchanger
Condenser Motor BLDC With Axial Type Fan (1) The indoor unit heat exchanger shall be mechanically bonded aluminum fin to copper tube
Fan FLA / Watts / CFM (max.) 0.48 A / 125 W / 2,190 CFM
Ceiling Type LXWXH 39 3/8 X 39 3/8 X 2 5/8 The outdoor unit heat exchanger shall be aluminum, flat fin, micro channel
(Square) Weight 7.94
Fascia Panel Controls
Open Type Diameter X H 41 15/16 X 3 3/8 Control signal shall be a DDC type signal
(Round) Weight 5.95
The indoor unit shall have a 12VDC output that is interlocked with fan to activate external devices (fan
Certifications ETL (UL 1995)
ON = 12VDC ON, fan OFF = 12VDC OFF, pigtail adapter plug required)
PCB fuses, indoor unit terminal block thermal fuse, current
Safety
Devices transformer, over-voltage protection, crankcase heating, temperature Interconnect control wire between outdoor and indoor unit shall be 16AWG X 2 shielded
limit protection logic, compressor overload sensing
Wired or wireless controllers must be purchased separately
Certified in accordance with the AHRI Unitary Small Air-Source Heat Pumps (USHP) Certification Program which is based on
the latest edition of AHRI Standard 210/240.
No additional interface modules/adapters are required when connecting to Samsung NASA DVM S
Samsung HVAC maintains a policy of ongoing development, specifications are subject to change without notice.
Refer to www.AHRIdirectory.org for current reference numbers.
central control options.

Refrigerant System
The compressor shall be hermetically sealed, inverter controlled, twin BLDC Rotary
Refrigerant flow shall be controlled by an electronic expansion valve at outdoor unit
Soft-start to reduce current demand during compressor start
Warranty
10 Years compressor, 10 years parts, 1 year limited labor when registered

© 2021 Samsung HVAC


SHA-CAC-01152021 www.SamsungHVAC.com
Page 2 of 5
SUBMITTAL AC024KN4DCH/AA
Samsung 360 Cassette, Single Zone, Split System
AC024KN4DCH/AA Accessories

Required Accessories
Ceiling Type (square, white) PC4NUDMUN
Ceiling Type (square, black) PC4NBDMUN
Fascia Panel
Open Type (round, white) PC4NUNMUN
Open Type (round, black) PC4NBNMUN
*A fascia panel is required for cassette unit operation and is sold separately.

Optional Accessories
Simplified Touch Controller MWR-SH11UN
Wired Controller
Advanced Wired Controller MWR-WG00UN
Wi-Fi Adapter MIM-H04UN
External Temperature Sensor MRW-TA
Wireless Controller AR-KH03U
External Contact Control MIM-B14
Wall Bracket (for outdoor unit) CKN-250
Front WBF-2M-B
Wind Baffles
Back WBB-3M
25' - ILS-2509
Line Sets - insulated and flared, interconnect cables included
50' - ILS-5009
Thermostat Adaptor (for connection to a standard 24VAC thermostat) MIM-A60UN
Motion Detection Sensor MCR-SME

888-699-6067
www.SamsungHVAC.com
Page 3 of 5
SUBMITTAL AC024KN4DCH/AA
Samsung 360 Cassette, Single Zone, Split System
AC024KN4DCH/AA Dimensional Drawing With Ceiling Type Fascia Panel
Units: mm [inches]

No. Description No. Description


1 Refrigerant Gas Pipe 7 Suction rim for air direction booster fan
2 Refrigerant Liquid Pipe 8 Decoration fascia panel
3 Condensate drain 9 Drain hose
4 Power and wiring entry 10 Fresh air knockout hole
5 Air discharge opening 11 Status display
6 Air suction grille 12 Infrared receiver

888-699-6067
www.SamsungHVAC.com
Page 4 of 5
SUBMITTAL AC024KN4DCH/AA
Samsung 360 Cassette, Single Zone, Split System
AC024KN4DCH/AA Dimensional Drawing With Open Type Fascia Panel

Units: mm [inches]

No. Description No. Description


1 Refrigerant Gas Pipe 7 Suction rim for air direction booster fan
2 Refrigerant Liquid Pipe 8 Decoration fascia panel
3 Condensate drain 9 Drain hose
4 Power and wiring entry 10 Fresh air knockout hole
5 Air discharge opening 11 Status display
6 Air suction grille 12 Infrared receiver

888-699-6067
www.SamsungHVAC.com
Page 5 of 5
SUBMITTAL AC024KN4DCH/AA
Samsung 360 Cassette, Single Zone, Split System
AC024JXADCH/AA Dimensional Drawing

4 - ø15/32"

14 3/16"

15 1/8"
13"

37 1/8"

TOP

37" 11 9/32"
38 11/16"

39 11/16"
25 3/4"

27 1/16"
19 5/16"
FRONT FRONT WITHOUT SERVICE COVER
24 7/16"

No. Description
1 Suction service valve
2 Liquid service valve
3 Drainage hole
4 Power and communication conduit openings

888-699-6067
www.SamsungHVAC.com

You might also like