Lift Specification
Lift Specification
lR;eso Tk;rs
Hkkjr ljdkj
jsy ea=ky;
GOVERNMENT OF INDIA
MINISTRY OF RAILWAYS
Amendment Revision
SN Reason
Number Date Number Date
1 1 24.11.15 - - Rly bd. Letter no. 2012/elect(G) /150/7 dated 02.09.2013
and SC Rly letter no. E.252/Lifts /2013-14 Dt.
10.02.2015.
Amdt. cl.: 2.3, 2.8, 2.9, 4.0, 5.8, 6.1.2.7, 6.2, 6.5.1, 6.5.3,
6.5.5, 6.6.2, 6.9.2.1, 6.9.5.2, 6.9.7.1, 6.10.3.2, 6.21.2,
6.21.3, 6.23.1, 6.23.4.1, 11.0 and annex-1.
Add. Cl.: 6.15.4, 6.22.6, 6.22.7, 6.22.11, 13.2.4, 19.2, 19.3
& 19.4.
Del. Cl.: 6.6.4, 6.9.1.4. & 6.9.6.3.
2 1 26.12.19 Rationalized the specification to improve its reliability and
clarity.
3 2 ----- Rationalized the specification in line with the current
technical upgradation and to improve its reliability and
clarity.
जारीकर्ाा ISSUED BY
ऊजाा एवं पर्ाावरण प्रबंधन पवार सप्लाई एवं ई एम र्ू ENERGY AND ENVIRONMENT MANAGEMENT POWER SUPPLY
AND EMU DIRECTORATE
ननदेशालर्
RESEARCH DESIGNS AND STANDARDS ORGANISATION
अनसु धं ान अनिकल्प एवं मानक सगं ठन
MANAK NAGAR, LUCKNOW-226011
मानक नगर लखनऊ & 226011
Approved by:
INDEX
1. FOREWORD
Elevators facilitate the vertical transportation of railway passengers
and others at railway stations and buildings. This specification will
facilitate the provision of safe and high quality elevators on the Indian
Railway (IR) network.
2. SCOPE
2.1. The specification seeks to define the objectives, guidelines and
requirements for design, manufacture, supply, installation, testing
and commissioning, preparation of maintenance/ operations manual
and imparting training to maintenance/ operations personnel in
respect of heavy duty elevators.
2.2. Elevators are required to be machine room-less & gear-less and the
same shall be suitable for railway stations, be they underground or
over ground (please refer item 10 of Annexure-1). In absence of any
specific mention to the contrary in the tender, it will be deemed that
the railway station is of overground type. The elevator should be fit for
use by elderly as well as differently abled passengers. Although focus
of the spec. is on vertical movement of passengers from Foot-over-
Bridge (FOB) to platform, concourse, circulating area, etc., the spec. is
equally suited for multi-storied buildings (please refer item 1 of
Annexure-1).
2.3. Elevators shall be heavy duty type and capable of operating safely and
smoothly at a rate of 180 motor starts per hour or above for a period
of not less than 20 hours per day, seven day a week. The elevators
should be designed for minimum 10,00,000 operations per year.
2.4. The Contractor shall be fully responsible for obtaining relevant safety
certificate or license or any other authorization required from
statutory authorities as a pre-requisite for taking up the work of
commissioning and regular operation of Machine-room less & Gear-
less Elevators. The firm shall also obtain the relevant safety certificate
from statutory authority in respect of individual elevators. Fee, if any,
for obtaining such license/ certificate shall be borne by the contractor.
The aforesaid provision shall be applicable to contractual warranty
period and (if applicable) AMC period also.
2.5. The Contractor shall submit to the railway, relevant safety and
clearance certificates for each equipment, as obtained from the
statutory authorities.
2.6. The Contractor shall be responsible to supply and install any signage/
graphics required for fulfillment of relevant statutory authority’s
norms, whether or not specifically mentioned in the spec.
2.7. Railways shall furnish the particulars of their specific requirements by
filling in all the entries, as per the format given in Annexure 1.
Prepared by: Checked by:
SSE/EM Dir/EM
Page 4 of 85 Effective from: ………. Spec No. RDSO/2013/EM/SPEC/0016 (Rev’1’)-2019
2.9.2 As for site preparation works (civil and electrical), with the exception
of items of works specifically kept under contractor’s scope by this
specification, all the other works shall automatically fall under
railways’ scope. The site preparation works to be undertaken by
railways may typically include: construction of the Elevator shaft
including pit; construction of FOB extension for connecting the main
passage to Elevator shaft; raised platform/profiling required for
prevention of ingress of water into the Elevator shaft; any
miscellaneous works (if required), to offer a clear site to the elevator
contractor; canopy above the landing doors (where required); provision
of architraves; provision of drain pipe in the lift well at slightly higher
level than main drain, so that the inflow of water from outside can be
avoided. The drain pipe to be connected to main drain a suitable
pump and sump at pit of the shaft to be provided to discharge water
in drain pipe; provision of earth pits for achieving an earth resistance
of max 1 ohm (for elevators, railways shall provide separate earthing
pits); making single phase and three phase LT power supply available
for the Elevator, etc.
2.9.3 Elevator shaft should preferably be of RCC. If brick construction is
used, then it is recommended that the minimum thickness of shaft
wall shall be 230 mm and RCC tie-beams shall be provided at the
bracket fixing levels and any other equipment fixing locations. The
location of the RCC tie-beams shall be provided by the Elevator
contractor.
2.9.4 Elevator contractor will provide communication port at ITB at machine
room and at SCR. The control wiring from machine room to SCR shall
be done by railway contractor. The elevator contractor will facilitate
the connection at ITBs.
2.9.5 Provision of CCTV surveillance system.
3. APPLICABLE STANDARDS
IS 14665 Specification for passengers lifts
BS EN-81-1 20 Safety Rules for the construction and
installation of lifts Part 1: Electrical Lifts
IEC 60364 Standard on Electrical installation for
building
IS 15330 Installation and maintenance of Lifts for
handicapped persons – Code of practice
IS 15785 Installation and maintenance of lift
without conventional machine rooms –
Code of practice
IS 8216 Guide for inspection of lift wire ropes
IS 14665: Part 1 Electric Traction Lifts – Part 1:
Guidelines for outline dimensions of
passenger, goods, service and hospital
lifts
IS 14665: Part 2: Sec 1 Electric Traction Lifts – Part 2: Code of
and 2 practice for installation, Operation and
maintenance:
Section 1: Passenger and goods lifts;
Section 2: Service Lifts
IS 14665: Part 3: Sec 1 Electric Traction Lifts – Part 3: Safety
and 2 rules:
Section 1: Passenger and goods lifts;
Section 2: Service Lifts
IS 14665: Part 4: Sec 1-9 Electric Traction Lifts – Part 4:
Components
IS 14665: Part 5 Electric Traction Lifts – Specification
Part 5: Inspection manual
IEC 60034: Part – 1 Rotating electrical machines - Rating
and performance
IEC 60034: Part – 2-1 Rotating electrical machines - Standard
methods for determining losses and
efficiency from tests (excluding machines
for traction vehicles)
BS EN 12385-5 Steel wire ropes. Safety. Stranded ropes
for lifts
BS EN 61000-6-3 Electromagnetic compatibility (EMC) -
Generic standards - Emission standard
for residential, commercial and light-
industrial environments
BS EN 61000-6-1 Electromagnetic compatibility (EMC) -
Generic standards - Immunity for
residential, commercial and light-
industrial environments
BS EN 12015 Electromagnetic compatibility - Product
family standard for Lifts, escalators and
passengers conveyors -Emission.
BS EN 12016 Electromagnetic compatibility - Product
family standard for Lifts, escalators and
passenger conveyors -Immunity.
ISO 7465 Passenger Lifts and service lifts. Guide
rails for car & counterweight – T type
BS EN ISO 1461 Hot dip galvanized coatings on
fabricated iron and steel articles.
Specifications and test methods
BS 5655: Part 10 Lifts and service lifts – Specification for
the testing and examination of Lifts and
service lifts
EN 81 – 71 Safety rules for the construction and
installation of lifts — Particular
applications to passenger lifts and goods
passenger lifts — Vandal resistant lifts
IEC 60227 - 6 Polyvinyl chloride insulated cables of
5. GENERAL REQUIREMENTS
5.1 The construction of all Elevators shall conform to latest editions of
IS-14665, IS 15785, IS-15330, and EN 81-1 20.
5.2 Each Elevator shall have its own driving machine. The method of drive
shall be Electric Traction with gearless motor having a provision of
VVVF Control; regenerative drive shall be provided, if specifically
asked for by the purchaser (please refer item 8, Annexure - 1). In
absence of any mention to the contrary in the tender, it will be deemed
that regeneration feature is not required. The system, including all
sub-systems and equipments shall be of proven design.
5.3 The design of the Elevators shall be such that no major repair shall be
necessary for a period of 20 years from the date of issue of Certificate
of Taking Over. This of course is based on the assumption that
prescribed inspections are carried out periodically and routine
maintenance as well as cleaning is carried out. The term ‘Major repair’
shall mean replacement of car frame, car enclosure, car and landing
doors, Elevator shaft wiring (except travelling cables), guide rails, drive
machine, and driving sheave; parts attached to these components,
which are subjected to normal wear and tear, are excluded.
5.4 The design of Elevators shall take into consideration fire prevention,
elimination of dust and dirt traps, and easy accessibility for cleaning
and routine maintenance.
5.5 The gearless drive machine shall be mounted on guide rails
accommodated within the Elevator shaft. The power switchgear and
main control equipment can be located suitably inside or near the
Elevator shaft. Location of the same is to be decided in coordination
with the railway and railway appointed civil contractor. No separate
machine-room will be provided for machine room-less and Gear-less
Elevators.
5.6 Elevators are critical to vertical transportation of passengers and staff
and particularly so for the differently abled and elderly. So, elevator
reliability is very important for IR. The reliability, availability and
maintainability of equipment/ components shall be judged on the
basis of Call Out Ratio (COR) i.e. engineer visits to the site for
unscheduled maintenance of an elevator. Firms should endeavor that
the COR does not exceed 2.5 per elevator per year. Railways should
consider levying a penalty on firms, in event of the COR exceeding 2.5.
Relevant penalty provisions, if any, shall be incorporated by the
railways in their special conditions of tender. In absence of such
penalty provision in the special conditions of tender, no penalty shall
be levied on the firm; even if COR are in excess of 2.5.
5.7 Elevator Speed:
5.7.1 For transfers between FOB and platform level, the nominal speed for
elevators in either direction shall be 1.0 m/s. The spec does not
permit the railways any other option in the matter of speed of Elevator
for transfers between FOB and platform level at railway stations.
5.7.2 In respect of applications other than transfers between FOB and
platform level, unless otherwise specified in the tender, the nominal
speed for Elevators in either direction shall be: 1.0 m/s for up to 6
stops; and 1.5 m/s for 7 to 13 stops. Should the railway have valid
reasons to specify a speed different from the aforesaid, then it can
indicate the same at item 3 of Annexure-1.
5.8 The elevator capacity and the outline dimensions viz car size, shaft
dimensions, Entrance, overhead, pit depth, car door & landing door
etc. should be as per the recommended dimensions given in IS 14665.
If necessitated by the site conditions, railways can specify any other
dimensions but these should fulfill the conditions of variation given in
the IS Standard Elevator car and shaft dimensions for 13/20/26
persons capacity Elevators have been specified in Cl. 11. Railways
must choose one of the three aforesaid Elevator capacities (refer item
2 of Annexure-1). Although the standard shaft and pit sizes prescribed
The elevator shall comprise of all parts and accessories, which are
necessary for its efficient operation, whether specifically mentioned or
not. The key parts and accessories along with their functions and
features are listed as follows:
6.1 Traction Drive System
6.1.1 Motor
6.1.1.1 Driving motor shall be of AC permanent magnet synchronous type
(with no slip rings) designed for special duty cycles required for
Elevator operation. It should have a high starting torque, high
power factor, high efficiency and low energy consumption. The
efficiency of driving motor shall not be less than 85%. The motor
should conform to IEC 60034: Part 1 & 2.
6.1.1.2 The motor shall be capable of not less than 180 starts per hour
without excessive temperature rise.
6.1.1.3 The maximum temperature rise of the winding shall not exceed
500C above ambient temperature when operated under normal
condition.
6.1.1.4 Provision shall be made to enable the speed to be checked at main
Control cubicle. The device for speed checking itself has been
included in the scope through Cl. 6.28 (e).
6.1.1.5 The motor shall carry a nameplate giving full details of its ratings
and characteristics.
6.1.1.6 The motor used shall have Class ‘F’ insulation with IP-21
protection and shall be designed for 110% of rated load.
6.1.1.7 The motor shall be designed to conform to S5 – 60% CDF (cyclic
duration factor). Duty cycles are defined as per IEC duty cycles for
non peak and peak period of operation.
6.1.2 Brake
6.1.2.1 The Electro-magnetic brake shall be of the spring applied and
electrically released type.
6.1.2.2 The brake shall be capable of stopping and holding the Elevator car
in its downward travel to rest (with 125% of its rated load) from the
maximum rated speed. In this condition, the retardation of the Car
shall not exceed that resulting from the operation of the Safety gear
or stopping on the buffer.
6.1.2.3 Springs used to apply the brake shoes (two nos.) shall be in
compression and adequately supported. Powder coating or other
alternative Anti-corrosion measures to be ensured.
6.1.2.4 Brake linings shall be of renewable, incombustible, non-asbestos
materials and shall be secured to the brake shoes so that normal
wear shall not weaken their fixings. Band brakes shall not be used.
6.4.1 The top clearance of the car and counterweight shall be as stated in IS
Standards.
6.4.2 The bottom run by of car and counterweight shall be as per relevant
IS Standards.
6.4.3 When the car rests on its fully compressed buffer, there shall be a
vertical clearance of at least 600 mm between the pit floor and the
lowest structural or mechanical part, equipment or device installed
beneath the car platform except:
i) Guide shoes, safety-jaw assemblies and platform aprons, guards
or other equipment located within 300mm, measured
horizontally from the sides of the car platform.
ii) Compensating sheaves
However, when the car rests on its fully compressed buffer, there shall
be a vertical clearance of not less than 50mm between any part of the
car and any obstruction of device mounted on the pit.
6.4.4 The clearance between the car/counterweight and the hoist-way
enclosure shall be at least 20 mm except on the side for loading and
unloading.
6.4.5 The clearance between the car and the counterweight shall be at least
40mm. The clearance between the counterweight and the
counterweight screen shall be at least 20 mm.
6.5 Guides and Fixings
6.5.1 Planed steel tees shall be provided as guides for the Elevator car and
counterweight, as appropriate, erected plumb and fixed securely to the
Elevator shaft by steel brackets. The bracket shall be solidly fixed with
the RCC beam/RCC slab. The guide rails shall be connected by steel
fish plates. Details of guides and associated items shall be scrutinized
and finalized at detailed design stage.
6.5.2 The rail contact surfaces of the connecting rail plates and back of the
guide rail ends shall be accurately machined and fitted at site to form
smooth joints.
6.5.3 The strength of the guides, their attachments and joints shall comply
IS 14665 part 4.
6.5.4 The stem sections of all guides shall be tongued and grooved to
provide matched joints. The guides and their fixings shall be able to
withstand the forces imposed by a fully loaded car travelling at
tripping speed of the governor, due to the application of the safety
gear, without permanent deformation or bending due to the uneven
loading of the car. The guide rail brackets shall be designed for 20
years life.
6.5.5 Guide rail brackets shall be of steel and bolted securely to the building
or structure steelworks. The brackets shall be designed and located
such that the rail will not deflect more than 5 mm under normal and
Safety Gear operation. There shall be a minimum of two brackets per
Prepared by: Checked by:
SSE/EM Dir/EM
Page 14 of 85 Effective from: ………. Spec No. RDSO/2013/EM/SPEC/0016 (Rev’1’)-2019
piece of guide rail and the distance between brackets shall not be
more than half the length of each piece of guide rail. The bracket
should be fixed to RCC beams/RCC slab using chemical bolts of Hiliti
make or other EOTA approved brand of fasteners manufactured as per
ETGA document no. 001TR029 with cold forming process. This
particular requirement is to be ensured during interface with
designated civil contractor. It is the sole responsibility of the Elevator
Contractor to check the strength of the shaft wall and get it certified
from the railway appointed civil Contractor.
6.5.6 The fixing of guide rails to their brackets and to the building structure
shall permit compensation, either automatically or by simple
adjustment, due to normal settling of the building or shrinkage of
concrete.
6.6 Buffer
6.6.1 Buffers shall be installed as a means of stopping the car and
counterweight at the extreme limits of travel.
6.6.2 Buffers shall be of spring type and the same shall comply IS: 14665
(part- 4, Sec. 1). If any manufacturer offers PU (polyurethane) type
buffer same may be accepted by consignee after evaluating the
supporting documents submitted by the manufacturer about the
performance of PU buffers.
6.6.3 Buffers in the pit shall be mounted on steel frame, which shall extend
between both the car and counterweight guide rails.
6.7 Governor
6.7.1 The speed governor shall be in accordance with IS: 14665 (part-4,
Sec.4) and shall be adjustable to actuate the safety gears, located
overhead and driven by governor rope suitably connected to the car
and mounted on its own pulleys.
6.7.2 Tripping speed of the over speed governor shall be chosen between:
115% to 140% in respect of 1m/sec; or 115% to 132% in respect of
1.5m/sec. The tripping of the over-speed governor for the safety gear
shall occur when the car speed exceeds the rated speed downwards.
6.7.3 A mechanically operated safety switch shall be provided to disconnect
the power supply to the motor when the governor is activated.
6.7.4 The governor shall be of “V” groove wheel design.
6.7.5 The governor rope shall be of steel and shall comply IS: 14665.
6.7.6 The rope shall be maintained in tension by means of weighted or
spring loaded tension sheaves located in the pit.
6.7.7 An over speed governor shall also be provided to the counterweight in
case of Hanging pit. The Contractor is required to interface with the
railway and railway appointed civil contractor for the requirements of
hanging pits.
6.8 Diverting pulleys
Prepared by: Checked by:
SSE/EM Dir/EM
Page 15 of 85 Effective from: ………. Spec No. RDSO/2013/EM/SPEC/0016 (Rev’1’)-2019
sheet with pilfer proof screws. If single sheet is not used, it can be
in two pieces fixed with pilfer-proof screws. The platform shall be
designed on the basis of the rated load evenly distributed with a
minimum safety factor of five (5). Design calculations shall be
submitted by the contractor at the design stage.
6.9.4.2 The car platform shall be insulated to prevent the transmission of
noise and vibration from the car frame to the platform.
6.9.6.3 Fan shall automatically start on registering the command. The car
ventilation fan shall be switched off within a period which shall be
adjustable from 5 to 15 minutes after the last registered call is
answered. However, fan Switch shall be provided to disable auto-
starting of the Fan when not desired.
6.9.7 Car Interior and Elevator Finishes
6.9.7.1 Unless otherwise specified elsewhere in this specification, the
following finishes for the Elevator shall be complied with:
I. Landing Finishes:
i. Landing Plate, Scratch Resistant Stainless Steel
Indicators, MAP, etc.
ii. Landing Doors Scratch Resistant Stainless steel with fire
rating as per IS 14665 part-I
II. Car Finishes:
i. Car Transom Panels Scratch Resistant Stainless steel
ii. Car Wall:
a) Front Panels Scratch Resistant Stainless steel
b) Side Panels (incl. COP) Scratch Resistant Stainless steel
c) Back Panels Scratch Resistant Stainless steel
iii. Car Doors Scratch Resistant Stainless steel
iv. Car Floor finish 6 mm thick Aluminum Chequered plate
v. Car Ceiling Scratch Resistant Stainless steel panels
with sufficient LED down lights
vi. Car Kick-Plates and Scratch Resistant Stainless steel
skirting
vii. Hand/grip rail Hairline Finish Stainless steel of straight
through type and supported from min. 3
locations.
viii. Buffer rail Thermoplastic Elastomeric or suitable
material enclosed in Scratch resistant
stainless steel frame with minimum height
of 100mm x (width of the car minus
100mm) long shall be suitably fixed to take
the impact of wheel chair foot rest
III. Hall Button and Display Faceplate:
Scratch Resistant Stainless Steel
6.9.7.2 The contractor shall further note that:
(i) Wherever scratch resistant stainless steel has been asked finish
shall be honey comb or moon rock or hairline.
(i)
One or more switches whereby the following modes of operation
can be effected as desired:
(a) With Attendant
(b) Without Attendant
(c) Operation by Firemen in accordance with IS 14665 and
statutory requirements.
(ii) “UP/DOWN” buttons which shall cause a car to travel in the
desired direction. These buttons shall be operative only during
the “Attendant” operation.
6.15.4 A switch should be provided in accordance with IS 14665-1 part 2
for operation by fireman.
6.16 Car Position Indicator
6.16.1 The car position indicators shall be provided inside the car and also
on each landing in the Hall-way. These indicators shall not be part
of COP inside the car or Call buttons (in the Hall way). The location
of the indicators shall be above the door.
6.16.2 The faceplate of the car position indicator shall be made of stainless
steel grade 304. The Stainless steel plate should be minimum 2 mm
thick and its mounting arrangement should have two sunken
screws. This plate should be pilfer-proof. Floor numbers shall be
digitally displayed using minimum 5 x 7 square dot matrix LED.
There shall also be an arrow in motion vividly and dynamically
indicating car movement and direction. It shall also be capable of
displaying/ scrolling (at least 8 characters) simple message such as:
floor names e.g. ‘Concourse’/ ‘Platform’/ ‘Foot Over bridge’; ‘Out of
service’; ‘Under Maintenance’; ‘Firemen’; etc. which may be decided
based on mutual agreement between the railway and the contractor.
The surface of the display unit shall be non-glare type.
6.17 Elevator Inter-Communication System
6.17.1 The Contractor shall provide an Elevator inter-communication
between the Elevator Car, main control cubicle and SCR room
consisting of master and slave stations. The Contractor shall offer
the system from a proven vendor and provide details thereof during
design approval stage.
6.17.2 All stations shall be equipped with handsets except those slave
stations installed inside the Elevator cars, which shall be of the
hands free type.
6.17.3 The handsets/ intercoms shall be supplied from a UPS power
supply so that the intercom’s working remains unaffected in event of
failure of mains power supply.
6.17.4 A master station shall be supplied and installed in the Station
Control Room (SCR). A single intercom system shall be installed to
handle calls from all Elevators and it shall be handset type with
caller identification facility.
6.17.5 A slave station shall be supplied and installed in the main control
cubicle and also in each Elevator car. The loudspeaker and
microphone unit of the slave station shall be concealed in the car
operating panel. The necessary cabling, conduits including from
SCR room to main control cubicle etc. shall be provided by the
Contractor (please refer item 12 of Annexure-1). Routing shall be
finalized in consultation with the railways. It should be possible to
decipher the identity of calling Elevator at the SCR room. For easy
identification, elevators should be numbered inside the car as well
as at each landing.
6.18 Certificate Holder
A framed and glazed panel made of stainless steel of minimum 2mm
thickness, suitable to display the Elevator certificate shall be
provided above the car operating panel. This shall be got approved
at design stage.
6.19 Hallway Equipment
6.19.1 Hall Call Buttons
One (1) set of hall call buttons shall be provided for each Elevator at
every floor served. The set of buttons shall be installed on the wall
adjacent to each Elevator landing. The faceplate shall be made of
stainless steel grade 304 with hairline finish. The Stainless steel
plate for mounting the indicators and landing call buttons should be
minimum 2 mm thick and its mounting arrangement should have
two Sunken Screws. This plate should be pilfer-proof. All buttons
shall be vandal resistant as per EN 81-120 with designations and
Braille marked on it. The hall call buttons shall be micro-push type
and suitable for heavy duty. The response light of the call buttons
shall be orange or red, when illuminated. When a Elevator arrives at
the hall, the illumination shall cease.
6.19.2 Hall Position Indicator
6.19.2.1 The faceplate of the car position indicator shall be made of scratch-
resistant stainless steel grade 304. The Stainless steel plate should
be minimum 2 mm thick and its mounting arrangement should
have two Sunken screws. This plate should be pilfer proof. Floor
numbers shall be digitally displayed using minimum 5x7 square
dot matrix LED. There shall also be an arrow in motion vividly and
dynamically indicating car movement and direction. It shall also be
capable of displaying/ scrolling (at least 8 characters) simple
message such as: floor names e.g. ‘Concourse’/ ‘Platform’/ ‘Foot
Over bridge’; ‘Out of service’; ‘Under Maintenance’; ‘Firemen’; etc.
which may be decided based on mutual agreement between the
railway and the contractor. The surface of the display unit shall be
non-glare type.
6.19.2.2 In case of Elevators for buildings, one set of Hall lanterns shall be
provided for each Elevator at every floor served. The set of lanterns
put on the walls of shaft and car top. The ends of the
trunking/conduits shall be sealed to prevent ingress.
6.21.7 Maintenance Access Panel (MAP) should preferably be located at
top floor level. All controller enclosure shall be pilfer proof and have
ingress protection rating as specified in Clause 11 of the spec.
6.21.8 The design of contactors and relay contacts shall be such that the
break and make contacts shall not be closed at the same time at
any position of the armature. The operating conditions shall be as
follows:
(a) If, one of the break contacts (i.e. normally closed) is closed, all
the make contacts are open.
(b) If, one of the make contacts (i.e. normally open) is closed, all
the break contacts are open.
6.21.9 In the control and safety circuits, the mean value of operating
voltage (in case of direct current) or the r.m.s. value (in case of
alternating current), between conductors or between conductor and
earth shall not exceed 250V.
6.21.10 In event of failure of normal electric supply, the supply to alarm
bell system, intercom system, emergency car lighting and 50%
ventilation fans shall be automatically switched to a UPS with
battery backup. The battery shall be of sealed maintenance free
type with total capacity sufficient to maintain the operation of
above equipment for at least 2 hours. The rating of UPS and
battery shall be scrutinized and finalized during design approval.
6.21.11 The insulation of all wiring including those within the controller
shall be of flame retardant, low smoke halogen free (FRLSZH) type
for underground stations only and FRLS for over ground stations
and service buildings, complying with the special cable
requirement of this Specification.
6.21.12 All field wiring shall be multi-strand copper conductor type. No
joints shall be permitted in any cables or wires in any location.
6.21.13 All wires shall be run in galvanized conduit or steel trunking. All
conduit outlets shall be bushed with insulating bushes of accepted
pattern. All wiring connections to switches shall be provided in
such a way to suit the device. All conduits shall be provided with IP
54 glands.
6.21.14 The arrangements of terminals at either end of flexible trailing
cables shall be identical and the terminal blocks marked to identify
the cables connected to them. The cable boxes and wiring for the
car light and the alarm bell shall be entirely independent of the
Elevator control wiring. Flexible trailing cables shall be securely
clamped at each end so that the weight is not supported by any
fixing of the various cores. The outer sheath of these cables shall
be of waterproof and flame retardant material. A total of 10 or 10%
of the total number of wires used (whichever is more) and 2 spare
Pressed” turn ON. The audible buzzer shall turn OFF with the
pressing of “Alarm Accept Button” but the visual indication shall
persist until the fault is cleared.
6.22.6 It may be possible from RMS to switch off the lift for parking, the
elevator shall complete the last landing or car call, if any and return
to the designated landing and stop there with both the car and
landing doors open for 15 - 20 seconds with audio announcement
that lift is going to be shut down and then door should get close.
The “Not in service” indicator shall be illuminated on the landing
indicator automatically for a pre - determined time and then
extinguished. The car light and ventilation fan shall be switched off
automatically at the same time. The essential buttons e.g. door
open, intercom and alarm bell etc. on the car operating panels shall
be remained functional and illuminated when the elevators have
been parked and locked out.
6.22.7 Upon actuation by RMS for non - parking, the elevator shall be
switched back to normal operation and both the car light and
ventilation fan shall be switched on automatically.
6.22.8 Each colour LED should be circular in shape with a diameter of
28.5 mm and text should be in black colour English Words with
Arial Font of size 20.
6.22.9 A prototype of ESDP should be installed in the Station Control Room
(SCR) at one station, before taking up mass implementation for all
stations.
6.22.10 The contractor shall provide all wiring and apparatus, suitable for
the specified electrical supply and the same shall be approved
during design stage. Insulation of all wiring, including those within
the Elevator shaft, shall be of flame retardant, low smoke, halogen
free (FRLSZH) type for underground stations only and FRLS for
overground stations and service buildings, complying with the
special cable requirement of this Specification. The purchaser shall
furnish the approximate cabling distance from Elevator to SCR
(please refer item 12 of Annexure-1).
6.22.11 Elevator contractor will provide communication port at ITB, at
machine room and at SCR. The control wiring from machine room to
SCR shall be done by railway contractor. The elevator contractor will
facilitate the connection at ITBs.
6.23 Special Emergency Operations for Elevators
The Elevator operation system shall be designed to provide the
following emergency operations. The Elevator Contractor shall
provide the Interface terminal boards (ITBs) with terminals for
terminating the fire and power failure signals to be provided by the
railways. The Elevator Contractor shall provide the cabling up to the
ITB.
6.23.1 Emergency Operation of Elevators in the Event of Power
Failure:
In event of power failure or power interruption or single phasing (or
any problem in the power supply system which affects the normal
operation of the Elevators), the Automatic Rescue Device (ARD) shall
act and complete its operation. After power supply) resumes elevator
should automatically return to its normal mode operation. .
6.23.2 Emergency Operation of Elevators in the Event of Fire
In the event of fire when any fire detection device is activated, all
Elevators shall automatically be brought to the designated floor (to
be designated during design approval stage) and be parked there
with the doors open for 15-20 seconds and thereafter the doors
would close. All Elevators shall be automatically rendered
inoperative after they have been brought to the designated floor. The
essential buttons such as “Door Open”, intercom and alarm bell,
etc. on the car operating panels shall remain functional and
illuminated. Normal operation of the Elevators shall be manually
reset by the operation of a reset key switch.
6.23.3 Emergency Operation of Elevators in the Event of Power
Failure and Fire
In the event of power failure and fire, the operation of the Elevators
shall be in accordance with the “Emergency Operation of Elevators
in the Event of fire” and in such event, DG set power supply/ other
alternate source (if any) shall be fed to the elevator. If such a power
supply is non-existent or non-functional, then the Automatic
Rescue Device shall act and rescue the passengers inside the
elevator.
6.23.4 Automatic Rescue Device
6.23.4.1 Features
a. A battery back-up based device shall be provided to bring the
Elevators to one of the nearest landings in the event of power
failure. The rescue device shall be able to move the Elevators
with any load from no load to full load at reduced speed to one
of the nearest landings and shall open the doors upon reaching
the landing. Thereafter, the Elevator doors shall remain closed
until resumption of power supply, at which point the Elevators
shall automatically reset to normal.
b. The direction of travel shall depend upon the load in the
Elevator.
c. During this operation, all safety features of the Elevator shall
remain operational. In case of Power failure (including single
phasing / unbalanced phase) elevator should operate with the
Automatic Rescue Device (ARD) and Electronic Rescue Tool
(ERT) mode immediately. The software for providing this feature
is subject to the Employer’s acceptance.
working area.
6.25 Pit Facilities
6.25.1 Buffers shall be provided in the Elevator pit.
6.25.2 A safety switch to prevent the car from moving when the governor
rope tension weight is out of position, shall be provided.
6.25.3 Fixed cat ladders shall be provided between the bottom landing and
the pit floor by the Contractor.
6.25.4 Two stop switches, one at bottom landing level in the shaft and the
other in the pit shall be provided, which when in the “STOP”
position shall prevent any movement of the Elevator car including
movement during inspection/ test operation, until both the switches
are set to “RUN” position. Further details in respect of the switches
are as follows:
(i) The switch shall have a mushroom head (red). It shall be locked
off when pushed and reset manually.
(ii) First stop switch shall be accessible from the lower landing on
opening of the landing door and the second switch from the pit
floor.
(iii) A stainless steel faceplate of not less than 2mm in thickness,
indelibly marked “Pit Stop Switch” in both English, Hindi and
local vernacular language characters and with legends to show
the “STOP” and “RUN” positions shall be provided and fixed
immediately adjacent to the switch.
(iv) The knob of these switches or plate shall have fluorescent glow.
6.25.5 The Contractor shall liaise with the railway to ensure that the latter
(railway) makes a provision for proper drainage and pumping from
the Elevator pit as per clause no. 2.9.2. For elevator pits on railway
platforms, this may call for provision of pump, etc. by the railway. In
case of buildings or other applications, the need for such drainage
will be assessed by the contractor and railway; based on such
assessment, railway shall make the necessary provisions.
6.26 Corrosion Protection
The Contractor shall take into consideration, the corrosive effect of
the atmosphere in the Elevator design.
6.26.1 All steel components (5mm thick & above) shall be hot dipped
galvanized in accordance with BS EN ISO 1461, with minimum
thickness of 85 μm.
6.26.2 All parts constructed in sheet steel (less than 5mm) shall be either
galvanized by the hot dipped process or fabricated from hot dipped
galvanized sheet steel or spray galvanized and epoxy painted.
6.26.3 All mechanical and cast iron assemblies shall be cleaned and
painted. The running surfaces of car guides shall be treated with an
accepted rust preventive compound.
7. INTERFACES
7.1 The Contractor is required to interface with railway or civil contractor
appointed by railway in respect of the Elevator shaft requirement. The
Contractor shall co-ordinate with the railway or civil contractor
appointed by railway, to finalize all the details.
7.2 The Contractor shall co-ordinate with the railways and/ or railway
appointed civil contractor with regard to the following specific issues:
(a) space requirements, including tolerances to be complied by civil
engineering works.
(b) fixing requirements
(c) loads induced on the building, by the elevator
(d) interface with architectural finishes
(e) location for power supply termination point
(f) information on embedded parts, box-outs, etc. so as to enable
railway’s civil contractors to provide the necessary works.
(g) hanging pits (if any), including the shaft dimensions
(h) equipment access route
(i) scaffolding, lifting, etc. to be carried out by the elevator contractor
(only to the extent required for elevator installation)
(j) ventilation requirement
(k) integration with railway’s fire protection system (if any)
(l) provision of drainage with suitable pump and sump at the pit
8. ELECTROMAGNETIC COMPABILITY REQUIREMENT (EMC)
8.1 General
The contractor shall take adequate measures to reduce conducted,
induced, and radiated emissions, especially the levels of harmonics, to
acceptable values as specified by the relevant international standards
or by the concerned statutory authority.
8.2 Inter-System EMC
The Contractor shall ensure that all equipment supplied shall have
minimum Radio Frequency Interference introduced onto the main
network and comply with the Electromagnetic Compatibility (EMC)
requirements of the following standards: BS EN 61000-6-1, BS EN
61000-6-3, BS EN 12015 and BS EN 12016.
8.3 Harmonic distortion
The total harmonic distortion (THD) caused by the Elevator equipment
to the supply mains at the power supply input terminals of the
Elevator shall not exceed the following values when the Elevator is
travelling up at full load and rated speed:
Rated load Current (IL) THD (%)
Prepared by: Checked by:
SSE/EM Dir/EM
Page 41 of 85 Effective from: ………. Spec No. RDSO/2013/EM/SPEC/0016 (Rev’1’)-2019
2. Rated Speed (see Cl. 5.7) Refer cl. no. 5.7 1.0 m/s; 1.0 m/s; 1.0 m/s;
1.5 m/s 1.5 m/s 1.5 m/s
3. Standard Car Size As per IS 14665-1 As per IS 14665-1 As per IS 14665-1 As per IS 14665-1
(Width x Depth) (Metro Railway (Metro Railway may (Metro Railway may
(please refer item 5 of may adopt size as adopt size as per IS adopt size as per IS
Annexure-1 and cl. no. 5.8) per IS 14665-1 or 14665-1 or higher 14665-1 or higher as
higher as per as per requirement) per requirement)
requirement)
4. Car Height 2400 mm 2400 mm 2400 mm 2400 mm
6. Levelling Accuracy (Typical) ± 5 mm for normal ± 5 mm for normal ± 5 mm for ± 5 mm for normal
operation; operation; normal operation; operation;
± 10mm for ± 10mm for ± 10mm for ± 10mm for emergency
emergency rescue emergency rescue emergency rescue rescue mode
mode mode mode
7. Re-levelling Accuracy ± 15 mm ± 15 mm ± 15 mm ± 15 mm
(Typical)
8. Max. Sill Load (Car and 400 kg Aluminum/Stainle Aluminium/Stainle Aluminium/Stainless
Landing) ss steel with slots ss steel with slots steel with slots
Door sill load withstanding
Prepared by: Checked by:
SSE/EM Dir/EM
Page 45 of 85 Effective from: ………. Spec No. RDSO/2013/EM/SPEC/0016 (Rev’1’)-2019
capacity
9. Motor Insulation Class F F F F
B RIDE COMFORT
15. Acceleration/ Deceleration 0.5 m/s2 0.5 m/s2 0.5 m/s2 0.5 m/s2
Rate (Adjustable)
16. Max. Jerk 2 m/s3 2 m/s3 2 m/s3 2 m/s3
17. Max. Vertical Vibration In 20 Gal Pk - Pk 20 Gal Pk - Pk (1 - 20 Gal Pk -Pk (1 - 20 Gal Pk -Pk (1 -100
Car (1 -100 Hz ) 100 Hz ) 100 Hz ) Hz )
18. Max. Lateral Quaking 12 Gal Pk-Pk 12 Gal Pk-Pk 12 Gal Pk-Pk 12 Gal Pk-Pk
19. Noise In Car (with Fan in Max 55 dB(A) Max 55 dB(A) Max 55 dB (A) Max 55 dB (A)
operation)
C SHAFT EQUIPMENTS
20. Tentative size and weight of To be designed as per Should be design Should be design Should be design for life
Car Guide Rails IS 14665 for life of 20 years for life of 20 years of 20 years
21. Tentative size and weight of To be designed as per Should be design Should be design Should be design for life
Counterweight Guide Rails IS 14665 for life of 20 years for life of 20 years of 20 years
24. Car Sling Refer cl. no. 6.9.2 Fabricated from Fabricated from Fabricated from Sheet
Sheet steel. Cold sheet steel. Cold steel. Cold Rolled Steel
Rolled Steel up to Rolled steel up to upto 4mm and Hot
4mm and Hot 4mm and Hot
Rolled Sheets above 4
Rolled Sheets Rolled sheet above
above 4 mm thick 4 mm thick mm thick
25. Counterweight frame Fabricated from Sheet Fabricated from Fabricated from Fabricated from Sheet
steel. Cold Rolled Sheet steel. Cold sheet steel Cold steel. Cold Rolled Steel
Steel up to 4mm and Rolled Steel up to Rolled steel up to upto 4mm and Hot
Hot Rolled Sheets 4mm and Hot 4mm and Hot
Rolled Sheets above 4
above 4 mm thick Rolled Sheets Rolled sheet above
above 4 mm thick 4 mm thick mm thick
26. Over speed Governor with Centrifugally Centrifugally Centrifugally Centrifugally operated
test groove -Type operated operated operated
27. Car Safety Gear Progressive type Progressive type Progressive type Progressive type
28. Counterweight Safety Gear Progressive type Progressive type Progressive type Progressive type where
where ever applicable where ever where ever ever applicable (floating
(floating pit situation) applicable (floating applicable (floating pit situation)
pit situation) pit situation)
29. Over Speed Governor Required Required Required Required
tension weight switch
Prepared by: Checked by:
SSE/EM Dir/EM
Page 47 of 85 Effective from: ………. Spec No. RDSO/2013/EM/SPEC/0016 (Rev’1’)-2019
33. Guide shoes Sliding with Sliding with Sliding with Sliding with replaceable
replaceable liners replaceable liners replaceable liners liners
34. Car panel thickness Minimum 1.5mm Minimum 1.5mm 1.5mm thick 1.5mm thick
thick thick
35. Car Fan Refer cl. no. 6.9.6 Suitable Suitable ventilation Suitable ventilation
ventilation arrangement should arrangement should be
arrangement be made as per IS made as per IS 14665-
should be made as 14665-1
1
per IS 14665-1
36. Car Junction box Protection Refer cl. no. 6.9.5 IP 54 IP 54 IP 54
37. Car Handrail Refer cl. no. 6.9.3 On back On back On back side/lateral
side/lateral side of side/lateral side of side of car
car car
38. Buffer Rail On the rear side of On the rear side of On the rear side of On the rear side of car
car car car
39. Mirror (cl. 6.27- e) Required Required Required Required
E DOORS
40. Car Doors; clear opening Refer cl. no. 5.8 Centre opening Centre opening Centre Opening power
width and height of both the power doors as per power doors as per doors as per IS 14665-
car and landing entrance IS 14665-1. IS 14665-1. 1.
(Metro Railway
may adopt car door
of size 1000 mm
Wide)
41. Landing Doors Locking Both door panels Both door panels Both door panels Both door panels
mechanically locked mechanically mechanically locked mechanically locked
individually locked individually individually individually
42. Protection class for Car and IP20 IP20 IP20 IP20
Landing doors locking
device
43. Steel Door thickness Minimum 1.5 mm Minimum 1.5 mm Minimum 1.5 mm Minimum 1.5 mm
Stainless Steel sheet Stainless Steel Stainless Steel Stainless Steel sheet
sheet sheet
44. Fire rating of landing door As per IS 14665 As per IS 14665-1 As per IS 14665-1 As per IS 14665-1
45. Car door lock Electrical lock Electrical lock Electrical lock Electrical lock Required
Required Required Required
46. Door Safety Devices Refer cl. no. 6.10.3 2D Infrared 2D Infrared Curtain 2D Infrared Curtain of
Curtain of light & of light & light & Mechanical
For metro rail Mechanical Force Force Limiting Device.
application 3-D Limiting Device.
infra red curtain
may be provided if
purchaser specially
mention in the
tender documents.
F Machine
47. Machine Refer cl. no. 6.1 AC Permanent AC Permanent AC Permanent Magnet
Magnet Magnet Synchronous Axial type
Synchronous Axial Synchronous Axial Motor
type Motor type Motor
48. Motor-Insulation Class / Refer cl. no. 6.1 Class F / IP21 Class F / IP21 Class F / IP21
Type of Enclosure
G ELEVATOR MAJOR
COMPONENTS FINISH
49. Car panel Stainless steel Stainless steel Stainless steel Stainless steel Scratch
Scratch Resistant Scratch Resistant Scratch Resistant Resistant
50. Car entrance panel Stainless steel Stainless steel Stainless steel Stainless steel Scratch
Scratch Resistant Scratch Resistant Scratch Resistant Resistant
51. Car operating panel Stainless steel Stainless steel Stainless steel Stainless steel Scratch
Scratch Resistant Scratch Resistant Scratch Resistant Resistant
52. Car ceiling Stainless steel Stainless steel Stainless steel Stainless steel Scratch
Scratch Resistant Scratch Resistant Scratch Resistant Resistant
53. Handrail Stainless steel Stainless steel Stainless steel Stainless steel Hairline
Hairline Finish Hairline Finish Hairline Finish Finish
54. Car flooring Min 6 mm thick Min 6 mm thick Min 6 mm thick Min 6 mm thick
Aluminium Aluminium Aluminium Aluminium chequered
chequered plate chequered plate chequered plate plate
55. Landing entrance frame Stainless steel Stainless steel Stainless steel Stainless steel Scratch
Scratch Resistant Scratch Resistant Scratch Resistant Resistant
56. Doors-Car & Landing Stainless steel Stainless steel Stainless steel Stainless steel Scratch
Scratch Resistant Scratch Resistant Scratch Resistant Resistant
57. Guide Bracket Assembly Refer cl. no. 6.5 Should be Should be designed Should be designed for
designed for 20 for 20 years life 20 years life
years life
58. Car/ Counterweight guide Refer cl. no 6.5 Machined surfaces Machined surfaces Machined surfaces -
rail -Rust protective -Rust protective Rust protective Film;
Film; Other Film; Other Other Surfaces Epoxy
Surfaces Epoxy Surfaces Epoxy
painted.
painted. painted.
59. Counterweight Guard Refer cl. no. 6.3 GI / Spray GI/ Spray GI / Spray Galvanised
Galvanised With Galvanised with with Epoxy Painted
with Epoxy Painted Epoxy Painted
60. Counter weight frame Refer cl. no. 6.3 Hot dip Galvanised Hot dip Galvanised Hot dip Galvanised /
/ Spray Galvanised / Spray Galvanised Spray Galvanised with
with Epoxy Painted with Epoxy Painted Epoxy Painted
61. Filler Weight Refer cl. no. 6.3 Epoxy Painted. Epoxy Painted. Epoxy Painted.
62. Sling Hot dip Galvanised / Hot dip Galvanised Hot dip Galvanised Hot dip Galvanised
Spray Galvanised & /Spray Galvanised /Spray Galvanised /Spray Galvanised &
epoxy painted & epoxy painted & epoxy painted epoxy painted
63. Floor Assembly Spray Galvanised & Spray Galvanised Spray Galvanised & Spray Galvanised &
epoxy painted & epoxy painted epoxy painted epoxy painted
64. Roof Assembly Spray Galvanised & Spray Galvanised Spray Galvanised & Spray Galvanised &
epoxy painted & epoxy painted epoxy painted epoxy painted
H ELECTRICAL BUILDING
INTERFACE
65. Main Supply Voltage 400 Volt ± 10 %, 3- 415 VAC, 3 -phase 415 VAC, 3 -phase 415 VAC, 3 -phase
phase ±10% ±10% ±10%
66. Frequency 50 Hz ± 3% 50 Hz ± 3% 50 Hz ± 3% 50 Hz ± 3%
67. Main Fuses As per design 3x20 Amp 3 x 20 Amp. 3x20 Amp
requirement
68. Main Switch Rating As per design 32 Amp 32 Amp. 32 Amp
requirement
69. Main Switch Position Recommended on Recommended on Recommended on Recommended on Top
(External) Top most landing Top most landing Top most landing most landing
70. Shaft Lighting Refer cl. no. 6.21 Required as per IS Required as per IS Required as per IS
14665-1 14665-1 14665-1
71. ESDP (Elevator Status Refer cl. no. 6.22 LED based LED based Elevator LED based Elevator
Display Panel) (Optional Elevator Monitoring system Monitoring system with
item) Monitoring system with information of information of the
with information of the Elevators for
Elevators for their
the Elevators for their condition and
their condition and fault information condition and fault
fault information information
72. Signalization Voltage 12 to 30 VDC 12 to 30 VDC 12 to 30 VDC 12 to 30 VDC
I CIVIL BUILDING
INTERFACE
73. Head Room (Minimum) Refer cl. no. 5.8 For speeds upto 1 For speeds upto 1 For speeds upto 1 m/s:
m/s: 4250 mm; m/s: 4500mm; 4600mm;
For speeds above 1 For speeds above 1 For speeds above 1
m/s: As per IS m/s: As per IS
m/s: As per IS 14665
14665 (Part 1) 14665 (Part 1)
(Part 1)
74. Pit (Minimum) As per IS 14665 1600 mm 1800 mm 1850 mm
75. Shaft Size for Elevators with Refer cl. no. 5.8 2500 mm W X 2600 mm W X 2300 2950 mm W X 2350 mm
Counterweight safety 1900 mm D or in mm D or in D or in exceptional
exceptional cases, exceptional cases,
Prepared by: Checked by:
SSE/EM Dir/EM
Page 52 of 85 Effective from: ………. Spec No. RDSO/2013/EM/SPEC/0016 (Rev’1’)-2019
76. Control Type Full Collective Full Collective Full Collective Full Collective
77. Controller Refer cl. no. 6.11 Microprocessor Microprocessor Microprocessor based
based with Serial based with Serial with Serial
Communication. Communication. Communication.
Controller in shaft Controller in shaft Controller in shaft and
and user interface and user interface user interface in landing
in landing in landing
78. Drive System Refer cl no. 6.12 VVVF Drive with VVVF Drive with VVVF Drive with
feedback control feedback control feedback control (closed
(closed loop) (closed loop) loop)
79. Power Factor 0.9 and above 0.9 and above 0.9 and above 0.9 and above
80. Auto Fan & Light Cut-Off Refer cl. no. 6.9.6 Automatically cuts Automatically cuts Automatically cuts off
off fan & light off fan & light when fan & light when there
when there is no there is no calls for is no calls for a set time
calls for a set time a set time
K CODES AND NORMS
81. Safety Codes EN81-20; IS:15785; EN81-1; IS:15785; EN81-1; IS:15785; EN81-1; IS:15785;
IS:15530 ; IS:14665, IS:15530 ; IS:15530 ; IS:15530 ; IS:14665; BS
BS EN 50126 IS:14665, BS EN IS:14665; BS EN EN 50126
50126 50126
82. Electromagnetic EN12015 (emission) EN12015 EN12015 (emission) EN12015 (emission)
Compatibility, EMC and EN12016 (emission) and and and
(immunity) EN12016 EN12016
Prepared by: Checked by:
SSE/EM Dir/EM
Page 53 of 85 Effective from: ………. Spec No. RDSO/2013/EM/SPEC/0016 (Rev’1’)-2019
83. Electrical Protection As per requirements Min. IP20 for Min. IP20 for Min. IP20 for
specified Panels/Boxes Panels/Boxes above Panels/Boxes above Top
above Top terminal Top terminal terminal Landing,
Landing, Landing,
Panels/Boxes mounted
Panels/Boxes Panels/Boxes
mounted on Car mounted on Car on Car and shaft
and shaft and shaft equipments and
equipments and equipments and Maintenance Access
Maintenance Maintenance Access Panel in Landing
Access Panel in Panel in Landing
Landing
84. Requirements For Physically As per requirements As per As per As per requirements
Challenged Use specified requirements requirements specified
specified specified
L PERIPHERAL FUNCTIONS
85. Communication System Refer cl. no. 6.17 3 station intercom 3 station intercom – 3 station intercom –
–Hands-free in Car Hands-free in Car Hands-free in Car (with
(with feed-back (with feed-back feed-back ),Handset in
),Handset in Main ),Handset in Main
Main Control Panel and
Control Panel and Control Panel and
SCR SCR SCR
86. Alarm In each landing and In each landing In each landing and In each landing and
SCR activated by and SCR activated SCR activated by SCR activated by Alarm
Alarm button in Car by Alarm button in Alarm button in Car button in Car
Car
87. Attendant Function Operated with Key Operated with Key Operated with Key Operated with Key
switch switch switch switch
88. EAS (Elevator Refer cl. no. 6.15.2 English; or English; or English; or
announcement system) English and Hindi English and Hindi English and Hindi
89. Load Weighing Device Refer cl. no. 6.20 Audio: English; or Audio: English; or Audio: English; or
(Overload) English and Hindi; English and English and
Visual: English Hindi; Hindi;
only Visual: English only Visual: English only
90. Full Load Bypass (For By passes landing By passes landing By passes landing By passes landing calls
Elevators serving more than calls when load in car calls when load in calls when load in when load in car
2 stops) exceeds 80% of rated car exceeds 80% of car exceeds 80% of exceeds 80% of rated
load rated load rated load
load
91. Automatic Rescue Device Refer cl. no. 6.23.4 Required. When Required. When the Required. When the
the Elevator stops Elevator stops in Elevator stops in
in between due to between due to between due to power
power supply power supply
supply failure or due to
failure or due to failure or due to
single phasing, single phasing, single phasing, battery
battery operated battery operated operated device drives
device drives the device drives the the Elevator to the
Elevator to the Elevator to the landing and opens the
landing and opens landing and opens door.
the door. the door.
92. Fireman elevator Refer cl no. 6.15 Required phase 2 Required phase2 Required phase 2
functionality
93. Surge Suppressor / Power Required Required Required Required
filters/ Over Voltage (to be provided
Protection separately for Control
Circuit also)
94. Surge Suppressor / Over Required separately Required Required separately Required separately for
Voltage Protection for Control Circuit separately for for Control Circuit Control Circuit also
also Control Circuit also
Prepared by: Checked by:
SSE/EM Dir/EM
Page 55 of 85 Effective from: ………. Spec No. RDSO/2013/EM/SPEC/0016 (Rev’1’)-2019
also
95. Anti Man-trap features As in Cl. 10.1 As in Cl. 10.1 As in Cl. 10.1 As in Cl. 10.1
M SIGNALISATION
96. Car Operating Panel Refer cl. no. 6.15 Including Including Including handicapped
handicapped handicapped feature with Braille
feature with Braille feature with Braille Buttons
Buttons Buttons
97. Car Indicator Refer cl. no. 6.16 Dot Matrix LED Dot Matrix LED Dot Matrix LED
Indicator / Indicator / Display Indicator / Display
Display
98. Landing Indicator Refer cl. no. 6.16 Dot Matrix LED Dot Matrix LED Dot Matrix LED
Indicator /Display Indicator / Display Indicator / Display
f) Output in KW
g) Weight
a) Make
b) Type 6.1.2.1
b) Weight (Approx.)
d) Acceleration
e) Retardation
f) Method of suspension
.5 Guide Rail:-
c) Spacing of intermediate
Supports
d) Method of lubrication 6.9.1.2
c. Spacing of intermediate
Supports
d. Method of lubrication 6.9.1.2
.6 Control Equipments:-
a. Type 10.14
a. No. of sections
d. Method of load
equalization of ropes/belts
.9 Finishing: 6.9.7
13.2 Submittals
13.2.1 The bidder must submit following documents along with the offer:
14.1.8 After successful conclusion of type test and scrutiny of test results,
RDSO shall issue a type test clearance certificate and direct the firm
to commence bulk manufacturing. Type test clearance granted to
the Contractor is liable to be withdrawn in the event that he carries
out any major change at a later date in the design or Bill of material
without RDSO's approval or if he supplies sub-assembly of inferior
specification/ quality, thus compromising on reliability.
14.2 Elevator Routine Testing
14.2.1 Routine testing relates to the bulk manufacturing stage.
14.2.2 Routine testing entails tests and inspections that are conducted at
the works of Elevator manufacturer and/or the works of its key sub-
suppliers, as per the relevant standards. These tests are required to
be carried out on each elevator as well as its sub-systems.
14.2.3 The railway representative/ inspection agency/ testing authority
would have the right at its discretion, to witness routine test(s) of
Elevator’s key sub-assemblies during the Elevator’s manufacturing
and/or accept the test results/ reports of respective
manufacturer’s/supplier’s in-house quality control (test reports
should be furnished for systems and sub-systems that are to
actually form a part of the Elevator to be supplied to IR), as
sufficient evidence that the routine tests have been carried out.
14.2.4 If the Product is being manufactured initially in a foreign country,
purchaser’s representative/ inspection agency/ testing authority at
its discretion, may like to visit and witness any of the routine tests,
at their own cost. The Contractor shall co-ordinate the program, in
such case.
14.2.5 At least 3 weeks’ notice shall be given to the railway representative/
inspection agency/ testing authority to be present for the routine
testing and inspection.
14.3 Elevator Pre-Dispatch Verification of Packing List
14.3.1 Before the ordered goods (complete Elevator system kits), as per the
offered dispatch lot are dispatched, purchaser’s representative/
inspection agency shall verify completeness of the dispatch lot as per
order details/ contractor’s packing list and if everything is in order,
issue the “Dispatch approval certificate”.
14.3.2 Thereafter, the Contractor can dispatch the goods to the consignee.
14.4 Elevator installation and Final Acceptance Testing
After installation, on-site acceptance tests shall be carried out on the
Elevator in the presence of railway’s representative/ inspection
agency/ testing authority. After satisfactory completion of inspection/
testing, the railway representative/ inspection agency/ testing
authority will authorize the commissioning of the Elevator for public
use by issuing an “Elevator installation final acceptance certificate”.
15. ACCESSIBILITY
15.1. The Elevator design shall allow easy and safe accessibility to
authorized persons for inspection, maintenance, repairs and cleaning.
15.2. Maintenance Access Panel (MAP) shall be lockable to avoid access to
unauthorized persons.
walls and floor openings, etc. Any error in the civil construction in so
far as they relate to the Works shall be immediately brought to the
attention of the “Engineer” and the Designated Contractor to allow
prompt rectification by the Designated Contractor so as to avoid
delays to the Works. The Elevator Contractor shall not be entitled to
claim for any additional costs incurred by him arising out of such
errors in the civil construction, if such additional costs could
reasonably have been avoided had the Elevator Contractor carried out
timely and proper setting out of the Works.
19.3 Once the elevator shaft is handed over to the contractor to commence
installation, they shall be responsible for providing fencing and
barricades to protect his working areas during the installation period
for the safety of his workers and other personnel working in the
station until the taking over of the lift by Railways.
19.4 The Elevator Contractor shall be responsible for the installation of all
guide rail brackets, separator, sill supports, hanger brackets including
drilling and all related materials. The Elevator contractor shall verify
and satisfy themselves in respect to the loading capability of the shaft
wall holding the bracket etc. If the Elevator Contractor feels that load
test is necessary/ required, then he can arrange the same in co-
ordination with civil contractor.
19.5 All equipment, sub-assemblies, structures, etc. shall be installed as
per the respective sub-contractor’s installation instructions.
19.6 Special care shall be taken for leveling/ plumbing, which shall be
done meticulously before any equipment, sub-assembly or structure is
fixed finally in position.
19.7 Adequate care shall also be taken during installation of the complete
Elevator to avoid damage to any equipment, sub-assembly or building
structure.
19.8 Railways will be responsible for the civil engineering works required
for installation and commissioning of elevator at the designated
locations. The Contractor will provide a terminal board near elevator
and Railways will provide electrical wiring and earthing upto this
terminal board. Railways will provide site assembly area with proper
power connection as per the extant rules. For more details on
railways’ scope of work, please see Cl. 2.9.
20. ON-SITE SUPPORT TO CONTRACTOR
20.1 The purchaser/ user railways would extend facilities on free-of-charge
basis, to the Contractor for storing: the product; and installation,
testing and commissioning equipment/ tools/ accessories, etc., at a
suitable location, as close as possible to the installation site.
20.2 This shall include providing a separate lockable/ secure material-
storage cum site office with electrical supply, light and fan fittings, etc.
21. AFTER SALES SERVICE
21.1 The bidder shall indicate in the offer, the facilities available with the
bidder or local agent for providing the required after sales service
during warranty and post warranty periods. The bidder will also
mention service organizations located in India and the availability of
trained staff and maintenance spares, etc.
21.2 The Contractor shall provide and ensure servicing facilities
throughout the warranty period of the system. After the warranty
period is over, the Contractor should give service support for trouble
shooting and for obtaining spare parts for AMC period.
21.3 The Contractor shall during the contractual warranty period and (if
applicable) AMC period, ensure that, in case a consignee reports a
failure, qualified service engineers visit the site within 24 hours from
the time of complaint. The firm should provide a toll free number for
registering complaints however firm should respond to any complain
registered by consignee via toll free number, fax, e-mail, per bearer at
address given by the Contractor or through any other means. The
responsibility to keep the current failure reporting address/contact
number/email address/fax number details will rest with the
consignee.
22. MAINTENANCE
22.1 The Contractor shall provide free-of-charge maintenance service (and
all the works specified) including required spares, for the specified
warranty period.
22.2 During the warranty period, the above maintenance service shall
include all preventive, scheduled and corrective maintenance and
additionally, all service-request calls made by the purchaser/ user
railways. For this, the Contractor would be required to provide a
comprehensive maintenance and service plan, for review and
acceptance by the purchaser or his authorized representative.
22.3 The maintenance work-system shall ensure safety of the personnel
and equipment.
22.4 In event of any failure, requiring design modifications, etc. in the
Elevator, the Contractor shall undertake to submit its details for a
review by the Purchaser or his authorized representative. On reaching
consensus and post-modification, the Contractor shall undertake
fresh testing and re-commissioning, if required.
22.5 Annual Maintenance Contract (AMC)
22.5.1 The bidder is required to quote separately for a comprehensive
annual maintenance contract (AMC) for the Elevator supplied
against the specification, which will be inclusive of all spares,
material and labour costs along with work schedule if required to do
so as per special condition of the tender documents.
22.5.2 The contractor shall be responsible to keep all the Elevators along
with all connected ancillary equipments/apparatus/ machines, as
have been stated under the scope of work and specification, in
ANNEXURE - 1
Note:
1. In respect of Sl. No. 3, in absence of any specific mention by the
purchaser, the requirement will be deemed to be 1 m/s for upto 6
stops and 1.5 m/s for 7 to 13 stops.
2. In respect of Sl. No. 7, in absence of any specific mention by the
purchaser, the requirement will be deemed to be 1 set of car doors.
3. In respect of Sl. No. 8, in absence of any specific mention by the
purchaser, it will be deemed that regenerative drive is not required.
4. In respect of Sl. No. 9, in absence of any specific mention by the
purchaser, it will be deemed that ESDP is not required.
5. In respect of Sl. No. 10, in absence of any specific mention by the
purchaser, the requirement will be deemed to be for overground
station.
6. In respect of Sl. No. 11, in absence of any specific mention by the
purchaser, it will be deemed that hanging pit is not involved.
ANNEXURE - 2
ANNEXURE-3
1. One complete Elevator shall be made available for type testing. The
selected Elevator shall be representative of the types to be supplied.
2. Complete Elevator system including traction drive system, in addition
to the controller, Elevator car enclosure, landing and car doors,
protection devices and call fixtures shall be assembled on a test rig or
inside a test tower to undergo comprehensive running and functional
testing to verify compliance with the Specification.
3. The tests shall include the following minimum requirements:
a) Verification of the suitability of the traction drive system;
b) Verification of the car operation and response to call fixtures, door
operation including the safety edges, all indications and signalling
features, and car top control features;
c) Full load tests on safety gear;
d) Measurement of electrical readings and verification of the operating
speed under various loading conditions;
e) Verification of riding comfort and levelling accuracy under various
load conditions.
f) Verification of the fault indication and fault diagnosis features.
g) Verification of the construction of the various control panels to the
specification shall be done. Insulation resistance and high voltage
tests shall be conducted in accordance with the test protocol.
h) Any additional testing as required by BS 5655 Part 10.
i) A 12-hour duty cycle test, during which the Elevator shall run
continuously with the contract load for 12 hours and shall travel
up and down with intermediate stops such that the number of
starts per hour as specified.
j) Complete functional tests on the isolating transformer and ripple
filter if provided
k) Operation of the battery back-up device and the battery operated
power supply.
l) Simulation of the emergency homing sequence during fire and
power failure.
m) Evidence in support of quality of welding and casting processes
(e.g. radiographic examination reports, etc)
# For certain tests, the type testing authority i.e. RDSO may choose to rely
upon previous type test reports/conformance certificates, as long as
they pertain to similar design and comparable rating. However, the
manufacturer cannot demand this as a matter of right
The type testing authority i.e. RDSO shall generally witness the
following set of type tests for the purpose of safety verification (the list
of tests can be enlarged, if required)
ANNEXURE - 3; contd…
Part B: Routine Tests
Annexure-3; contd…
ANNEXURE - 3; contd…
xix. Emergency Power and In event of power failure and/ or fire, the
Fire operation elevator should operate in a manner as
laid down in the spec.
xx. Functional tests of all
features and functions
not included in the
above but required as
per this specs and EN
81-120.
2. Twelve Hour Run Each Elevator shall run continuously with the
rated load for 12 hours and shall travel up
and down with intermediate stops such that
the number of max starts is as per the
specification. Railways shall arrange
uninterrupted power supply for the said
period. If uninterrupted supply is not
available, 12 running hours period shall be
ensured with minimum interruptions.
Modalities for the same may be worked out
between the contractor and the purchaser.