2383 - Projet - ANNEXE1 - Modbus Communication Schedule.

xlsx SPCU 19/04/2024

Validation Date Tag Name Address index Data Type Client Access Scan Rate Description
MCS.HeartBeat_A 300001 Word RO 1000 PCU Cabinet A Heartbeat
MCS.HeartBeat_B 300002 Word RO 1000 PCU Cabinet B Heartbeat
MCS.STATUS.KEY_MCS 300003 0 Boolean RO 1000 MCS only in Control (Keyswitch)
MCS.STATUS.KEY_BOTH 300003 1 Boolean RO 1000 MCS & ICSS in Control (Keyswitch)
MCS.STATUS.MASTER 300003 2 Boolean RO 1000 MCS Master - This is the Master MCS
MCS.STATUS.FLT_MODEM_1A 300003 3 Boolean RO 1000 Modem 1A Fault - MCS unable to comm with the Topside Modem
MCS.STATUS.FLT_MODEM_1B 300003 4 Boolean RO 1000 Modem 1B Fault - MCS unable to comm with the Topside Modem
MCS.STATUS.FLT_HB_PLCA 300003 5 Boolean RO 1000 MCS PLC Heartbeat Fault - MCS unable to communicate with the MCS
MCS.STATUS.FLT_HB_SOM1A 300003 6 Boolean RO 1000 SOM-1A Heartbeat Fault - MCS unable to communicate with SOM-1A
MCS.STATUS.FLT_HB_PLCB 300003 7 Boolean RO 1000 MCS PLC Heartbeat Fault - MCS unable to communicate with the MCS
MCS.STATUS.FLT_HB_SOM1B 300003 8 Boolean RO 1000 SOM-1B Heartbeat Fault - MCS unable to communicate with SOM-1B
MCS.STATUS.FLT_ACCA 300003 9 Boolean RO 1000 MCS-A AC Circuit Breaker Open or Tripped
MCS.STATUS.FLT_ACCB 300003 10 Boolean RO 1000 MCS-A AC Circuit Breaker Open or Tripped
MCS.STATUS.FLT_DCCA 300003 11 Boolean RO 1000 MCS-A DC Circuit Breaker Open or Tripped
MCS.STATUS.FLT_DCCB 300003 12 Boolean RO 1000 MCS-A DC Circuit Breaker Open or Tripped
MCS.STATUS.FLT_DCCAB 300003 13 Boolean RO 1000 MCS-A+B DC Circuit Breaker Open or Tripped
MCS.STATUS.FLT_FAN 300003 14 Boolean RO 1000 MCS Fan Fault
MCS.STATUS.FLT_KVM 300003 15 Boolean RO 1000 MCS KVM Fault
MCS.ESD-E.PSD_TRIG_TRIP 300004 0 Boolean RO 1000 PCU Cabinet ESD Echo Platform Status Word - PSD Trigger Tripped - Hardwired Input Signal Tripped
MCS.ESD-E.PSD_TRIG_ACT 300004 1 Boolean RO 1000 PCU Cabinet ESD Echo Platform Status Word - PSD Trigger Active - PSD is the Highest Priority Input Tripped
MCS.ESD-E.PSD_SHUTIN 300004 2 Boolean RO 1000 PCU Cabinet ESD Echo Platform Status Word - PSD Shut-In Sequence Complete
MCS.ESD-E.ESD_TRIG_TRIP 300004 4 Boolean RO 1000 PCU Cabinet ESD Echo Platform Status Word - ESD Trigger Tripped
MCS.ESD-E.ESD_TRIG_ACT 300004 5 Boolean RO 1000 PCU Cabinet ESD Echo Platform Status Word - ESD Trigger Active
MCS.ESD-E.ESD_TEST_ACT 300004 6 Boolean RO 1000 PCU Cabinet ESD Echo Platform Status Word - ESD Test Activated
MCS.ESD-E.TSE_TRIG_TRIP 300004 7 Boolean RO 1000 PCU Cabinet ESD Echo Platform Status Word - TSE Trigger Tripped
MCS.ESD-E.TSE_TRIG_ACT 300004 8 Boolean RO 1000 PCU Cabinet ESD Echo Platform Status Word - TSE Trigger Active
MCS.ESD-E.ESDTSE_SHUTIN 300004 9 Boolean RO 1000 PCU Cabinet ESD Echo Platform Status Word - ESD/TSE Shut-In Sequence Complete
MCS.ESD-F.PSD_TRIG_TRIP 300006 0 Boolean RO 1000 PCU Cabinet ESD froxtrot Platform Status Word - PSD Trigger Tripped - Hardwired Input Signal Tripped
MCS.ESD-F.PSD_TRIG_ACT 300006 1 Boolean RO 1000 PCU Cabinet ESD froxtrot Platform Status Word - PSD Trigger Active - PSD is the Highest Priority Input Tripped
MCS.ESD-F.PSD_SHUTIN 300006 2 Boolean RO 1000 PCU Cabinet ESD froxtrot Platform Status Word - PSD Shut-In Sequence Complete
MCS.ESD-F.ESD_TRIG_TRIP 300006 4 Boolean RO 1000 PCU Cabinet ESD froxtrot Platform Status Word - ESD Trigger Tripped
MCS.ESD-F.ESD_TRIG_ACT 300006 5 Boolean RO 1000 PCU Cabinet ESD froxtrot Platform Status Word - ESD Trigger Active
MCS.ESD-F.ESD_TEST_ACT 300006 6 Boolean RO 1000 PCU Cabinet ESD froxtrot Platform Status Word - ESD Test Activated
MCS.ESD-F.TSE_TRIG_TRIP 300006 7 Boolean RO 1000 PCU Cabinet ESD froxtrot Platform Status Word - TSE Trigger Tripped
MCS.ESD-F.TSE_TRIG_ACT 300006 8 Boolean RO 1000 PCU Cabinet ESD froxtrot Platform Status Word - TSE Trigger Active
MCS.ESD-F.ESDTSE_SHUTIN 300006 9 Boolean RO 1000 PCU Cabinet ESD froxtrot Platform Status Word - ESD/TSE Shut-In Sequence Complete
MCS.ALOG.VI_A.SCALED 300007 Float RO 1000 PCU Cabinet MCS Input Voltage-A
MCS.ALOG.VI_A.STATUS.OVR_ACT 300009 0 Boolean RO 1000 PCU CABINET MCS INPUT VOLTAGE-A STATUS WORD - OVERRIDE ACTIVE
MCS.ALOG.VI_A.STATUS.UNKNOWN_A 300009 1 Boolean RO 1000 PCU CABINET MCS INPUT VOLTAGE-A STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
MCS.ALOG.VI_A.STATUS.UNKNOWN_B 300009 2 Boolean RO 1000 PCU CABINET MCS INPUT VOLTAGE-A STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
MCS.ALOG.VI_A.STATUS.UN_RANGE 300009 3 Boolean RO 1000 PCU CABINET MCS INPUT VOLTAGE-A STATUS WORD - UNDERRANGE
MCS.ALOG.VI_A.STATUS.OV_RANGE 300009 4 Boolean RO 1000 PCU CABINET MCS INPUT VOLTAGE-A STATUS WORD - OVERRANGE
MCS.ALOG.VI_A.STATUS.LOLO 300009 8 Boolean RO 1000 PCU CABINET MCS INPUT VOLTAGE-A STATUS WORD - LOLO
MCS.ALOG.VI_A.STATUS.LO 300009 9 Boolean RO 1000 PCU CABINET MCS INPUT VOLTAGE-A STATUS WORD - LO
MCS.ALOG.VI_A.STATUS.HI 300009 10 Boolean RO 1000 PCU CABINET MCS INPUT VOLTAGE-A STATUS WORD - HI
MCS.ALOG.VI_A.STATUS.HIHI 300009 11 Boolean RO 1000 PCU CABINET MCS INPUT VOLTAGE-A STATUS WORD - HIHI
MCS.ALOG.VI_B.SCALED 300010 Float RO 1000 PCU Cabinet MCS Input Voltage-B
MCS.ALOG.VI_B.STATUS.OVR_ACT 300012 0 Boolean RO 1000 PCU CABINET MCS INPUT VOLTAGE-B STATUS WORD - OVERRIDE ACTIVE
MCS.ALOG.VI_B.STATUS.UNKNOWN_A 300012 1 Boolean RO 1000 PCU CABINET MCS INPUT VOLTAGE-B STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
MCS.ALOG.VI_B.STATUS.UNKNOWN_B 300012 2 Boolean RO 1000 PCU CABINET MCS INPUT VOLTAGE-B STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
MCS.ALOG.VI_B.STATUS.UN_RANGE 300012 3 Boolean RO 1000 PCU CABINET MCS INPUT VOLTAGE-B STATUS WORD - UNDERRANGE
MCS.ALOG.VI_B.STATUS.OV_RANGE 300012 4 Boolean RO 1000 PCU CABINET MCS INPUT VOLTAGE-B STATUS WORD - OVERRANGE
MCS.ALOG.VI_B.STATUS.LOLO 300012 8 Boolean RO 1000 PCU CABINET MCS INPUT VOLTAGE-B STATUS WORD - LOLO
MCS.ALOG.VI_B.STATUS.LO 300012 9 Boolean RO 1000 PCU CABINET MCS INPUT VOLTAGE-B STATUS WORD - LO
MCS.ALOG.VI_B.STATUS.HI 300012 10 Boolean RO 1000 PCU CABINET MCS INPUT VOLTAGE-B STATUS WORD - HI
MCS.ALOG.VI_B.STATUS.HIHI 300012 11 Boolean RO 1000 PCU CABINET MCS INPUT VOLTAGE-B STATUS WORD - HIHI
MCS.ALOG.II_A.SCALED 300013 Float RO 1000 PCU Cabinet MCS Input Current-A
MCS.ALOG.II_A.STATUS.OVR_ACT 300015 0 Boolean RO 1000 PCU CABINET MCS INPUT CURRENT-A STATUS WORD - OVERRIDE ACTIVE

Page 1 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx SPCU 19/04/2024

Validation Date Tag Name Address index Data Type Client Access Scan Rate Description
MCS.ALOG.II_A.STATUS.UNKNOWN_A 300015 1 Boolean RO 1000 PCU CABINET MCS INPUT CURRENT-A STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
MCS.ALOG.II_A.STATUS.UNKNOWN_B 300015 2 Boolean RO 1000 PCU CABINET MCS INPUT CURRENT-A STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
MCS.ALOG.II_A.STATUS.UN_RANGE 300015 3 Boolean RO 1000 PCU CABINET MCS INPUT CURRENT-A STATUS WORD - UNDERRANGE
MCS.ALOG.II_A.STATUS.OV_RANGE 300015 4 Boolean RO 1000 PCU CABINET MCS INPUT CURRENT-A STATUS WORD - OVERRANGE
MCS.ALOG.II_A.STATUS.LOLO 300015 8 Boolean RO 1000 PCU CABINET MCS INPUT CURRENT-A STATUS WORD - LOLO
MCS.ALOG.II_A.STATUS.LO 300015 9 Boolean RO 1000 PCU CABINET MCS INPUT CURRENT-A STATUS WORD - LO
MCS.ALOG.II_A.STATUS.HI 300015 10 Boolean RO 1000 PCU CABINET MCS INPUT CURRENT-A STATUS WORD - HI
MCS.ALOG.II_A.STATUS.HIHI 300015 11 Boolean RO 1000 PCU CABINET MCS INPUT CURRENT-A STATUS WORD - HIHI
MCS.ALOG.II_B.SCALED 300016 Float RO 1000 PCU Cabinet MCS Input Current-B
MCS.ALOG.II_B.STATUS.OVR_ACT 300018 0 Boolean RO 1000 PCU CABINET MCS INPUT CURRENT-B STATUS WORD - OVERRIDE ACTIVE
MCS.ALOG.II_B.STATUS.UNKNOWN_A 300018 1 Boolean RO 1000 PCU CABINET MCS INPUT CURRENT-B STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
MCS.ALOG.II_B.STATUS.UNKNOWN_B 300018 2 Boolean RO 1000 PCU CABINET MCS INPUT CURRENT-B STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
MCS.ALOG.II_B.STATUS.UN_RANGE 300018 3 Boolean RO 1000 PCU CABINET MCS INPUT CURRENT-B STATUS WORD - UNDERRANGE
MCS.ALOG.II_B.STATUS.OV_RANGE 300018 4 Boolean RO 1000 PCU CABINET MCS INPUT CURRENT-B STATUS WORD - OVERRANGE
MCS.ALOG.II_B.STATUS.LOLO 300018 8 Boolean RO 1000 PCU CABINET MCS INPUT CURRENT-B STATUS WORD - LOLO
MCS.ALOG.II_B.STATUS.LO 300018 9 Boolean RO 1000 PCU CABINET MCS INPUT CURRENT-B STATUS WORD - LO
MCS.ALOG.II_B.STATUS.HI 300018 10 Boolean RO 1000 PCU CABINET MCS INPUT CURRENT-B STATUS WORD - HI
MCS.ALOG.II_B.STATUS.HIHI 300018 11 Boolean RO 1000 PCU CABINET MCS INPUT CURRENT-B STATUS WORD - HIHI
MCS.ALOG.VI_1A.SCALED 300019 Float RO 1000 PCU Cabinet SOM 1A Output Voltage
MCS.ALOG.VI_1A.STATUS.OVR_ACT 300021 0 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT VOLTAGE STATUS WORD - OVERRIDE ACTIVE
MCS.ALOG.VI_1A.STATUS.UNKNOWN_A 300021 1 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT VOLTAGE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
MCS.ALOG.VI_1A.STATUS.UNKNOWN_B 300021 2 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT VOLTAGE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
MCS.ALOG.VI_1A.STATUS.UN_RANGE 300021 3 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT VOLTAGE STATUS WORD - UNDERRANGE
MCS.ALOG.VI_1A.STATUS.OV_RANGE 300021 4 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT VOLTAGE STATUS WORD - OVERRANGE
MCS.ALOG.VI_1A.STATUS.LOLO 300021 8 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT VOLTAGE STATUS WORD - LOLO
MCS.ALOG.VI_1A.STATUS.LO 300021 9 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT VOLTAGE STATUS WORD - LO
MCS.ALOG.VI_1A.STATUS.HI 300021 10 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT VOLTAGE STATUS WORD - HI
MCS.ALOG.VI_1A.STATUS.HIHI 300021 11 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT VOLTAGE STATUS WORD - HIHI
MCS.ALOG.II_1A.SCALED 300022 Float RO 1000 PCU Cabinet SOM 1A Output Current
MCS.ALOG.II_1A.STATUS.OVR_ACT 300024 0 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT CURRENT STATUS WORD - OVERRIDE ACTIVE
MCS.ALOG.II_1A.STATUS.UNKNOWN_A 300024 1 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT CURRENT STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
MCS.ALOG.II_1A.STATUS.UNKNOWN_B 300024 2 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT CURRENT STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
MCS.ALOG.II_1A.STATUS.UN_RANGE 300024 3 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT CURRENT STATUS WORD - UNDERRANGE
MCS.ALOG.II_1A.STATUS.OV_RANGE 300024 4 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT CURRENT STATUS WORD - OVERRANGE
MCS.ALOG.II_1A.STATUS.LOLO 300024 8 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT CURRENT STATUS WORD - LOLO
MCS.ALOG.II_1A.STATUS.LO 300024 9 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT CURRENT STATUS WORD - LO
MCS.ALOG.II_1A.STATUS.HI 300024 10 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT CURRENT STATUS WORD - HI
MCS.ALOG.II_1A.STATUS.HIHI 300024 11 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT CURRENT STATUS WORD - HIHI
MCS.ALOG.JI_1A.SCALED 300025 Float RO 1000 PCU Cabinet SOM 1A Output Power
MCS.ALOG.JI_1A.STATUS.OVR_ACT 300027 0 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT POWER STATUS WORD - OVERRIDE ACTIVE
MCS.ALOG.JI_1A.STATUS.UNKNOWN_A 300027 1 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT POWER STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
MCS.ALOG.JI_1A.STATUS.UNKNOWN_B 300027 2 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT POWER STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
MCS.ALOG.JI_1A.STATUS.UN_RANGE 300027 3 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT POWER STATUS WORD - UNDERRANGE
MCS.ALOG.JI_1A.STATUS.OV_RANGE 300027 4 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT POWER STATUS WORD - OVERRANGE
MCS.ALOG.JI_1A.STATUS.LOLO 300027 8 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT POWER STATUS WORD - LOLO
MCS.ALOG.JI_1A.STATUS.LO 300027 9 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT POWER STATUS WORD - LO
MCS.ALOG.JI_1A.STATUS.HI 300027 10 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT POWER STATUS WORD - HI
MCS.ALOG.JI_1A.STATUS.HIHI 300027 11 Boolean RO 1000 PCU CABINET SOM 1A OUTPUT POWER STATUS WORD - HIHI
MCS.ALOG.VI_1B.SCALED 300028 Float RO 1000 PCU Cabinet SOM 1B Output Voltage
MCS.ALOG.VI_1B.STATUS.OVR_ACT 300030 0 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT VOLTAGE STATUS WORD - OVERRIDE ACTIVE
MCS.ALOG.VI_1B.STATUS.UNKNOWN_A 300030 1 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT VOLTAGE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
MCS.ALOG.VI_1B.STATUS.UNKNOWN_B 300030 2 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT VOLTAGE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
MCS.ALOG.VI_1B.STATUS.UN_RANGE 300030 3 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT VOLTAGE STATUS WORD - UNDERRANGE
MCS.ALOG.VI_1B.STATUS.OV_RANGE 300030 4 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT VOLTAGE STATUS WORD - OVERRANGE
MCS.ALOG.VI_1B.STATUS.LOLO 300030 8 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT VOLTAGE STATUS WORD - LOLO
MCS.ALOG.VI_1B.STATUS.LO 300030 9 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT VOLTAGE STATUS WORD - LO
MCS.ALOG.VI_1B.STATUS.HI 300030 10 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT VOLTAGE STATUS WORD - HI

Page 2 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx SPCU 19/04/2024

Validation Date Tag Name Address index Data Type Client Access Scan Rate Description
MCS.ALOG.VI_1B.STATUS.HIHI 300030 11 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT VOLTAGE STATUS WORD - HIHI
MCS.ALOG.II_1B.SCALED 300031 Float RO 1000 PCU Cabinet SOM 1B Output Current
MCS.ALOG.II_1B.STATUS.OVR_ACT 300033 0 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT CURRENT STATUS WORD - OVERRIDE ACTIVE
MCS.ALOG.II_1B.STATUS.UNKNOWN_A 300033 1 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT CURRENT STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
MCS.ALOG.II_1B.STATUS.UNKNOWN_B 300033 2 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT CURRENT STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
MCS.ALOG.II_1B.STATUS.UN_RANGE 300033 3 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT CURRENT STATUS WORD - UNDERRANGE
MCS.ALOG.II_1B.STATUS.OV_RANGE 300033 4 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT CURRENT STATUS WORD - OVERRANGE
MCS.ALOG.II_1B.STATUS.LOLO 300033 8 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT CURRENT STATUS WORD - LOLO
MCS.ALOG.II_1B.STATUS.LO 300033 9 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT CURRENT STATUS WORD - LO
MCS.ALOG.II_1B.STATUS.HI 300033 10 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT CURRENT STATUS WORD - HI
MCS.ALOG.II_1B.STATUS.HIHI 300033 11 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT CURRENT STATUS WORD - HIHI
MCS.ALOG.JI_1B.SCALED 300034 Float RO 1000 PCU Cabinet SOM 1B Output Power
MCS.ALOG.JI_1B.STATUS.OVR_ACT 300036 0 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT POWER STATUS WORD - OVERRIDE ACTIVE
MCS.ALOG.JI_1B.STATUS.UNKNOWN_A 300036 1 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT POWER STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
MCS.ALOG.JI_1B.STATUS.UNKNOWN_B 300036 2 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT POWER STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
MCS.ALOG.JI_1B.STATUS.UN_RANGE 300036 3 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT POWER STATUS WORD - UNDERRANGE
MCS.ALOG.JI_1B.STATUS.OV_RANGE 300036 4 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT POWER STATUS WORD - OVERRANGE
MCS.ALOG.JI_1B.STATUS.LOLO 300036 8 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT POWER STATUS WORD - LOLO
MCS.ALOG.JI_1B.STATUS.LO 300036 9 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT POWER STATUS WORD - LO
MCS.ALOG.JI_1B.STATUS.HI 300036 10 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT POWER STATUS WORD - HI
MCS.ALOG.JI_1B.STATUS.HIHI 300036 11 Boolean RO 1000 PCU CABINET SOM 1B OUTPUT POWER STATUS WORD - HIHI
MCS.SOM1A.STATUS.TRIP_CMNFAIL 300040 0 Boolean RO 1000 PCU Cabinet Subsea Output Module 1A Status Word - Common Failure
MCS.SOM1A.STATUS.PWR_ON 300040 1 Boolean RO 1000 PCU Cabinet Subsea Output Module 1A Status Word - Power On
MCS.SOM1A.STATUS.ALM_LINEISO 300040 2 Boolean RO 1000 PCU Cabinet Subsea Output Module 1A Status Word - Line Iso Monitor Alm
MCS.SOM1A.STATUS.TRIP_LINEISO 300040 3 Boolean RO 1000 PCU Cabinet Subsea Output Module 1A Status Word - Line Iso Monitor Trip
MCS.SOM1A.STATUS.ALM_XMR_TAH 300040 4 Boolean RO 1000 PCU Cabinet Subsea Output Module 1A Status Word - Transformer Alarm High
MCS.SOM1A.STATUS.ALM_HI_VOLT 300040 5 Boolean RO 1000 PCU Cabinet Subsea Output Module 1A Status Word - Over Voltage Alarm
MCS.SOM1A.STATUS.ALM_LO_VOLT 300040 6 Boolean RO 1000 PCU Cabinet Subsea Output Module 1A Status Word - Under Voltage Alarm
MCS.SOM1A.STATUS.TRIP_SECCB 300040 7 Boolean RO 1000 PCU Cabinet Subsea Output Module 1A Status Word - Sec Circuit Brkr Tripped
MCS.SOM1A.STATUS.TRIP_HI_VOLT 300040 8 Boolean RO 1000 PCU Cabinet Subsea Output Module 1A Status Word - Over Voltage Trip
MCS.SOM1A.STATUS.TRIP_LO_VOLT 300040 9 Boolean RO 1000 PCU Cabinet Subsea Output Module 1A Status Word - Under Voltage Trip
MCS.SOM1B.STATUS.TRIP_CMNFAIL 300041 0 Boolean RO 1000 PCU Cabinet Subsea Output Module 1B Status Word - Common Failure
MCS.SOM1B.STATUS.PWR_ON 300041 1 Boolean RO 1000 PCU Cabinet Subsea Output Module 1B Status Word - Power On
MCS.SOM1B.STATUS.ALM_LINEISO 300041 2 Boolean RO 1000 PCU Cabinet Subsea Output Module 1B Status Word - Line Iso Monitor Alm
MCS.SOM1B.STATUS.TRIP_LINEISO 300041 3 Boolean RO 1000 PCU Cabinet Subsea Output Module 1B Status Word - Line Iso Monitor Trip
MCS.SOM1B.STATUS.ALM_XMR_TAH 300041 4 Boolean RO 1000 PCU Cabinet Subsea Output Module 1B Status Word - Transformer Alarm High
MCS.SOM1B.STATUS.ALM_HI_VOLT 300041 5 Boolean RO 1000 PCU Cabinet Subsea Output Module 1B Status Word - Over Voltage Alarm
MCS.SOM1B.STATUS.ALM_LO_VOLT 300041 6 Boolean RO 1000 PCU Cabinet Subsea Output Module 1B Status Word - Under Voltage Alarm
MCS.SOM1B.STATUS.TRIP_SECCB 300041 7 Boolean RO 1000 PCU Cabinet Subsea Output Module 1B Status Word - Sec Circuit Brkr Tripped
MCS.SOM1B.STATUS.TRIP_HI_VOLT 300041 8 Boolean RO 1000 PCU Cabinet Subsea Output Module 1B Status Word - Over Voltage Trip
MCS.SOM1B.STATUS.TRIP_LO_VOLT 300041 9 Boolean RO 1000 PCU Cabinet Subsea Output Module 1B Status Word - Under Voltage Trip

Page 3 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx EPU 19/04/2024

Validation Date Tag Name Address Data Type Client Access Scan Rate Description
EPU.STATUS.FLT_MODEM_1A 300001 0 Boolean RO 1000 Modem 1A Fault - MCS unable to comm with the Topside Modem
EPU.STATUS.FLT_MODEM_1B 300001 1 Boolean RO 1000 Modem 1B Fault - MCS unable to comm with the Topside Modem
EPU.STATUS.FLT_MODEM_2A 300001 3 Boolean RO 1000 Modem 2A Fault - MCS unable to comm with the Topside Modem
EPU.STATUS.FLT_MODEM_2B 300001 4 Boolean RO 1000 Modem 2B Fault - MCS unable to comm with the Topside Modem
EPU.STATUS.FLT_HB_PLCA 300001 5 Boolean RO 1000 EPU PLC Heartbeat Fault - MCS unable to communicate with the EPU
EPU.STATUS.FLT_HB_PLCB 300001 5 Boolean RO 1000 EPU PLC Heartbeat Fault - MCS unable to communicate with the EPU
EPU.STATUS.FLT_HB_SOM1A 300001 6 Boolean RO 1000 SOM-1A Heartbeat Fault - MCS unable to communicate with SOM-1A
EPU.STATUS.FLT_HB_SOM1B 300001 7 Boolean RO 1000 SOM-1B Heartbeat Fault - MCS unable to communicate with SOM-1B
EPU.STATUS.FLT_HB_SOM2A 300001 8 Boolean RO 1000 SOM-2A Heartbeat Fault - MCS unable to communicate with SOM-2A
EPU.STATUS.FLT_HB_SOM2B 300001 9 Boolean RO 1000 SOM-2B Heartbeat Fault - MCS unable to communicate with SOM-2B
EPU.STATUS.FLT_FAN 300001 10 Boolean RO 1000 EPU Fan Fault
EPU.STATUS.FLT_DCCA 300001 11 Boolean RO 1000 EPU-A DC Circuit Breaker Open or Tripped
EPU.STATUS.FLT_DCCB 300001 12 Boolean RO 1000 EPU-A DC Circuit Breaker Open or Tripped
EPU.STATUS.FLT_DCCAB 300001 13 Boolean RO 1000 EPU-A+B DC Circuit Breaker Open or Tripped
EPU.ALOG.VI_A.SCALED 300002 Float RO 1000 EPU Cabinet EPU Input Voltage-A
EPU.ALOG.VI_A.STATUS.OVR_ACT 300004 0 Boolean RO 1000 EPU CABINET EPU INPUT VOLTAGE-A STATUS WORD - OVERRIDE ACTIVE
EPU.ALOG.VI_A.STATUS.UNKNOWN_A 300004 1 Boolean RO 1000 EPU CABINET EPU INPUT VOLTAGE-A STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
EPU.ALOG.VI_A.STATUS.UNKNOWN_B 300004 2 Boolean RO 1000 EPU CABINET EPU INPUT VOLTAGE-A STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
EPU.ALOG.VI_A.STATUS.UN_RANGE 300004 3 Boolean RO 1000 EPU CABINET EPU INPUT VOLTAGE-A STATUS WORD - UNDERRANGE
EPU.ALOG.VI_A.STATUS.OV_RANGE 300004 4 Boolean RO 1000 EPU CABINET EPU INPUT VOLTAGE-A STATUS WORD - OVERRANGE
EPU.ALOG.VI_A.STATUS.LOLO 300004 8 Boolean RO 1000 EPU CABINET EPU INPUT VOLTAGE-A STATUS WORD - LOLO
EPU.ALOG.VI_A.STATUS.LO 300004 9 Boolean RO 1000 EPU CABINET EPU INPUT VOLTAGE-A STATUS WORD - LO
EPU.ALOG.VI_A.STATUS.HI 300004 10 Boolean RO 1000 EPU CABINET EPU INPUT VOLTAGE-A STATUS WORD - HI
EPU.ALOG.VI_A.STATUS.HIHI 300004 11 Boolean RO 1000 EPU CABINET EPU INPUT VOLTAGE-A STATUS WORD - HIHI
EPU.ALOG.VI_B.SCALED 300005 Float RO 1000 EPU Cabinet EPU Input Voltage-B
EPU.ALOG.VI_B.STATUS.OVR_ACT 300007 0 Boolean RO 1000 EPU CABINET EPU INPUT VOLTAGE-B STATUS WORD - OVERRIDE ACTIVE
EPU.ALOG.VI_B.STATUS.UNKNOWN_A 300007 1 Boolean RO 1000 EPU CABINET EPU INPUT VOLTAGE-B STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
EPU.ALOG.VI_B.STATUS.UNKNOWN_B 300007 2 Boolean RO 1000 EPU CABINET EPU INPUT VOLTAGE-B STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
EPU.ALOG.VI_B.STATUS.UN_RANGE 300007 3 Boolean RO 1000 EPU CABINET EPU INPUT VOLTAGE-B STATUS WORD - UNDERRANGE
EPU.ALOG.VI_B.STATUS.OV_RANGE 300007 4 Boolean RO 1000 EPU CABINET EPU INPUT VOLTAGE-B STATUS WORD - OVERRANGE
EPU.ALOG.VI_B.STATUS.LOLO 300007 8 Boolean RO 1000 EPU CABINET EPU INPUT VOLTAGE-B STATUS WORD - LOLO
EPU.ALOG.VI_B.STATUS.LO 300007 9 Boolean RO 1000 EPU CABINET EPU INPUT VOLTAGE-B STATUS WORD - LO
EPU.ALOG.VI_B.STATUS.HI 300007 10 Boolean RO 1000 EPU CABINET EPU INPUT VOLTAGE-B STATUS WORD - HI
EPU.ALOG.VI_B.STATUS.HIHI 300007 11 Boolean RO 1000 EPU CABINET EPU INPUT VOLTAGE-B STATUS WORD - HIHI
EPU.ALOG.II_A.SCALED 300008 Float RO 1000 EPU Cabinet EPU Input Current-A
EPU.ALOG.II_A.STATUS.OVR_ACT 300010 0 Boolean RO 1000 EPU CABINET EPU INPUT CURRENT-A STATUS WORD - OVERRIDE ACTIVE
EPU.ALOG.II_A.STATUS.UNKNOWN_A 300010 1 Boolean RO 1000 EPU CABINET EPU INPUT CURRENT-A STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
EPU.ALOG.II_A.STATUS.UNKNOWN_B 300010 2 Boolean RO 1000 EPU CABINET EPU INPUT CURRENT-A STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
EPU.ALOG.II_A.STATUS.UN_RANGE 300010 3 Boolean RO 1000 EPU CABINET EPU INPUT CURRENT-A STATUS WORD - UNDERRANGE
EPU.ALOG.II_A.STATUS.OV_RANGE 300010 4 Boolean RO 1000 EPU CABINET EPU INPUT CURRENT-A STATUS WORD - OVERRANGE
EPU.ALOG.II_A.STATUS.LOLO 300010 8 Boolean RO 1000 EPU CABINET EPU INPUT CURRENT-A STATUS WORD - LOLO
EPU.ALOG.II_A.STATUS.LO 300010 9 Boolean RO 1000 EPU CABINET EPU INPUT CURRENT-A STATUS WORD - LO
EPU.ALOG.II_A.STATUS.HI 300010 10 Boolean RO 1000 EPU CABINET EPU INPUT CURRENT-A STATUS WORD - HI
EPU.ALOG.II_A.STATUS.HIHI 300010 11 Boolean RO 1000 EPU CABINET EPU INPUT CURRENT-A STATUS WORD - HIHI
EPU.ALOG.II_B.SCALED 300011 Float RO 1000 EPU Cabinet EPU Input Current-B
EPU.ALOG.II_B.STATUS.OVR_ACT 300013 0 Boolean RO 1000 EPU CABINET EPU INPUT CURRENT-B STATUS WORD - OVERRIDE ACTIVE
EPU.ALOG.II_B.STATUS.UNKNOWN_A 300013 1 Boolean RO 1000 EPU CABINET EPU INPUT CURRENT-B STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
EPU.ALOG.II_B.STATUS.UNKNOWN_B 300013 2 Boolean RO 1000 EPU CABINET EPU INPUT CURRENT-B STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
EPU.ALOG.II_B.STATUS.UN_RANGE 300013 3 Boolean RO 1000 EPU CABINET EPU INPUT CURRENT-B STATUS WORD - UNDERRANGE
EPU.ALOG.II_B.STATUS.OV_RANGE 300013 4 Boolean RO 1000 EPU CABINET EPU INPUT CURRENT-B STATUS WORD - OVERRANGE
EPU.ALOG.II_B.STATUS.LOLO 300013 8 Boolean RO 1000 EPU CABINET EPU INPUT CURRENT-B STATUS WORD - LOLO
EPU.ALOG.II_B.STATUS.LO 300013 9 Boolean RO 1000 EPU CABINET EPU INPUT CURRENT-B STATUS WORD - LO
EPU.ALOG.II_B.STATUS.HI 300013 10 Boolean RO 1000 EPU CABINET EPU INPUT CURRENT-B STATUS WORD - HI
EPU.ALOG.II_B.STATUS.HIHI 300013 11 Boolean RO 1000 EPU CABINET EPU INPUT CURRENT-B STATUS WORD - HIHI

Page 4 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx EPU 19/04/2024

Validation Date Tag Name Address Data Type Client Access Scan Rate Description
EPU.ALOG.VI_1A.SCALED 300014 Float RO 1000 EPU Cabinet SOM 1A Output Voltage
EPU.ALOG.VI_1A.STATUS.OVR_ACT 300016 0 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT VOLTAGE STATUS WORD - OVERRIDE ACTIVE
EPU.ALOG.VI_1A.STATUS.UNKNOWN_A 300016 1 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT VOLTAGE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
EPU.ALOG.VI_1A.STATUS.UNKNOWN_B 300016 2 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT VOLTAGE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
EPU.ALOG.VI_1A.STATUS.UN_RANGE 300016 3 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT VOLTAGE STATUS WORD - UNDERRANGE
EPU.ALOG.VI_1A.STATUS.OV_RANGE 300016 4 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT VOLTAGE STATUS WORD - OVERRANGE
EPU.ALOG.VI_1A.STATUS.LOLO 300016 8 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT VOLTAGE STATUS WORD - LOLO
EPU.ALOG.VI_1A.STATUS.LO 300016 9 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT VOLTAGE STATUS WORD - LO
EPU.ALOG.VI_1A.STATUS.HI 300016 10 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT VOLTAGE STATUS WORD - HI
EPU.ALOG.VI_1A.STATUS.HIHI 300016 11 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT VOLTAGE STATUS WORD - HIHI
EPU.ALOG.II_1A.SCALED 300017 Float RO 1000 EPU Cabinet SOM 1A Output Current
EPU.ALOG.II_1A.STATUS.OVR_ACT 300019 0 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT CURRENT STATUS WORD - OVERRIDE ACTIVE
EPU.ALOG.II_1A.STATUS.UNKNOWN_A 300019 1 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT CURRENT STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
EPU.ALOG.II_1A.STATUS.UNKNOWN_B 300019 2 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT CURRENT STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
EPU.ALOG.II_1A.STATUS.UN_RANGE 300019 3 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT CURRENT STATUS WORD - UNDERRANGE
EPU.ALOG.II_1A.STATUS.OV_RANGE 300019 4 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT CURRENT STATUS WORD - OVERRANGE
EPU.ALOG.II_1A.STATUS.LOLO 300019 8 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT CURRENT STATUS WORD - LOLO
EPU.ALOG.II_1A.STATUS.LO 300019 9 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT CURRENT STATUS WORD - LO
EPU.ALOG.II_1A.STATUS.HI 300019 10 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT CURRENT STATUS WORD - HI
EPU.ALOG.II_1A.STATUS.HIHI 300019 11 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT CURRENT STATUS WORD - HIHI
EPU.ALOG.JI_1A.SCALED 300020 Float RO 1000 EPU Cabinet SOM 1A Output Power
EPU.ALOG.JI_1A.STATUS.OVR_ACT 300022 0 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT POWER STATUS WORD - OVERRIDE ACTIVE
EPU.ALOG.JI_1A.STATUS.UNKNOWN_A 300022 1 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT POWER STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
EPU.ALOG.JI_1A.STATUS.UNKNOWN_B 300022 2 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT POWER STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
EPU.ALOG.JI_1A.STATUS.UN_RANGE 300022 3 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT POWER STATUS WORD - UNDERRANGE
EPU.ALOG.JI_1A.STATUS.OV_RANGE 300022 4 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT POWER STATUS WORD - OVERRANGE
EPU.ALOG.JI_1A.STATUS.LOLO 300022 8 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT POWER STATUS WORD - LOLO
EPU.ALOG.JI_1A.STATUS.LO 300022 9 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT POWER STATUS WORD - LO
EPU.ALOG.JI_1A.STATUS.HI 300022 10 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT POWER STATUS WORD - HI
EPU.ALOG.JI_1A.STATUS.HIHI 300022 11 Boolean RO 1000 EPU CABINET SOM 1A OUTPUT POWER STATUS WORD - HIHI
EPU.ALOG.VI_1B.SCALED 300023 Float RO 1000 EPU Cabinet SOM 1B Output Voltage
EPU.ALOG.VI_1B.STATUS.OVR_ACT 300025 0 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT VOLTAGE STATUS WORD - OVERRIDE ACTIVE
EPU.ALOG.VI_1B.STATUS.UNKNOWN_A 300025 1 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT VOLTAGE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
EPU.ALOG.VI_1B.STATUS.UNKNOWN_B 300025 2 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT VOLTAGE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
EPU.ALOG.VI_1B.STATUS.UN_RANGE 300025 3 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT VOLTAGE STATUS WORD - UNDERRANGE
EPU.ALOG.VI_1B.STATUS.OV_RANGE 300025 4 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT VOLTAGE STATUS WORD - OVERRANGE
EPU.ALOG.VI_1B.STATUS.LOLO 300025 8 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT VOLTAGE STATUS WORD - LOLO
EPU.ALOG.VI_1B.STATUS.LO 300025 9 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT VOLTAGE STATUS WORD - LO
EPU.ALOG.VI_1B.STATUS.HI 300025 10 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT VOLTAGE STATUS WORD - HI
EPU.ALOG.VI_1B.STATUS.HIHI 300025 11 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT VOLTAGE STATUS WORD - HIHI
EPU.ALOG.II_1B.SCALED 300026 Float RO 1000 EPU Cabinet SOM 1B Output Current
EPU.ALOG.II_1B.STATUS.OVR_ACT 300028 0 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT CURRENT STATUS WORD - OVERRIDE ACTIVE
EPU.ALOG.II_1B.STATUS.UNKNOWN_A 300028 1 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT CURRENT STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
EPU.ALOG.II_1B.STATUS.UNKNOWN_B 300028 2 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT CURRENT STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
EPU.ALOG.II_1B.STATUS.UN_RANGE 300028 3 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT CURRENT STATUS WORD - UNDERRANGE
EPU.ALOG.II_1B.STATUS.OV_RANGE 300028 4 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT CURRENT STATUS WORD - OVERRANGE
EPU.ALOG.II_1B.STATUS.LOLO 300028 8 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT CURRENT STATUS WORD - LOLO
EPU.ALOG.II_1B.STATUS.LO 300028 9 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT CURRENT STATUS WORD - LO
EPU.ALOG.II_1B.STATUS.HI 300028 10 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT CURRENT STATUS WORD - HI
EPU.ALOG.II_1B.STATUS.HIHI 300028 11 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT CURRENT STATUS WORD - HIHI
EPU.ALOG.JI_1B.SCALED 300029 Float RO 1000 EPU Cabinet SOM 1B Output Power
EPU.ALOG.JI_1B.STATUS.OVR_ACT 300031 0 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT POWER STATUS WORD - OVERRIDE ACTIVE
EPU.ALOG.JI_1B.STATUS.UNKNOWN_A 300031 1 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT POWER STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
EPU.ALOG.JI_1B.STATUS.UNKNOWN_B 300031 2 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT POWER STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B

Page 5 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx EPU 19/04/2024

Validation Date Tag Name Address Data Type Client Access Scan Rate Description
EPU.ALOG.JI_1B.STATUS.UN_RANGE 300031 3 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT POWER STATUS WORD - UNDERRANGE
EPU.ALOG.JI_1B.STATUS.OV_RANGE 300031 4 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT POWER STATUS WORD - OVERRANGE
EPU.ALOG.JI_1B.STATUS.LOLO 300031 8 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT POWER STATUS WORD - LOLO
EPU.ALOG.JI_1B.STATUS.LO 300031 9 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT POWER STATUS WORD - LO
EPU.ALOG.JI_1B.STATUS.HI 300031 10 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT POWER STATUS WORD - HI
EPU.ALOG.JI_1B.STATUS.HIHI 300031 11 Boolean RO 1000 EPU CABINET SOM 1B OUTPUT POWER STATUS WORD - HIHI
EPU.ALOG.VI_2A.SCALED 300032 Float RO 1000 EPU Cabinet SOM 2A Output Voltage
EPU.ALOG.VI_2A.STATUS.OVR_ACT 300034 0 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT VOLTAGE STATUS WORD - OVERRIDE ACTIVE
EPU.ALOG.VI_2A.STATUS.UNKNOWN_A 300034 1 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT VOLTAGE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
EPU.ALOG.VI_2A.STATUS.UNKNOWN_B 300034 2 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT VOLTAGE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
EPU.ALOG.VI_2A.STATUS.UN_RANGE 300034 3 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT VOLTAGE STATUS WORD - UNDERRANGE
EPU.ALOG.VI_2A.STATUS.OV_RANGE 300034 4 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT VOLTAGE STATUS WORD - OVERRANGE
EPU.ALOG.VI_2A.STATUS.LOLO 300034 8 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT VOLTAGE STATUS WORD - LOLO
EPU.ALOG.VI_2A.STATUS.LO 300034 9 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT VOLTAGE STATUS WORD - LO
EPU.ALOG.VI_2A.STATUS.HI 300034 10 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT VOLTAGE STATUS WORD - HI
EPU.ALOG.VI_2A.STATUS.HIHI 300034 11 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT VOLTAGE STATUS WORD - HIHI
EPU.ALOG.II_2A.SCALED 300035 Float RO 1000 EPU Cabinet SOM 2A Output Current
EPU.ALOG.II_2A.STATUS.OVR_ACT 300037 0 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT CURRENT STATUS WORD - OVERRIDE ACTIVE
EPU.ALOG.II_2A.STATUS.UNKNOWN_A 300037 1 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT CURRENT STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
EPU.ALOG.II_2A.STATUS.UNKNOWN_B 300037 2 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT CURRENT STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
EPU.ALOG.II_2A.STATUS.UN_RANGE 300037 3 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT CURRENT STATUS WORD - UNDERRANGE
EPU.ALOG.II_2A.STATUS.OV_RANGE 300037 4 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT CURRENT STATUS WORD - OVERRANGE
EPU.ALOG.II_2A.STATUS.LOLO 300037 8 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT CURRENT STATUS WORD - LOLO
EPU.ALOG.II_2A.STATUS.LO 300037 9 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT CURRENT STATUS WORD - LO
EPU.ALOG.II_2A.STATUS.HI 300037 10 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT CURRENT STATUS WORD - HI
EPU.ALOG.II_2A.STATUS.HIHI 300037 11 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT CURRENT STATUS WORD - HIHI
EPU.ALOG.JI_2A.SCALED 300038 Float RO 1000 EPU Cabinet SOM 2A Output Power
EPU.ALOG.JI_2A.STATUS.OVR_ACT 300040 0 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT POWER STATUS WORD - OVERRIDE ACTIVE
EPU.ALOG.JI_2A.STATUS.UNKNOWN_A 300040 1 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT POWER STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
EPU.ALOG.JI_2A.STATUS.UNKNOWN_B 300040 2 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT POWER STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
EPU.ALOG.JI_2A.STATUS.UN_RANGE 300040 3 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT POWER STATUS WORD - UNDERRANGE
EPU.ALOG.JI_2A.STATUS.OV_RANGE 300040 4 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT POWER STATUS WORD - OVERRANGE
EPU.ALOG.JI_2A.STATUS.LOLO 300040 8 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT POWER STATUS WORD - LOLO
EPU.ALOG.JI_2A.STATUS.LO 300040 9 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT POWER STATUS WORD - LO
EPU.ALOG.JI_2A.STATUS.HI 300040 10 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT POWER STATUS WORD - HI
EPU.ALOG.JI_2A.STATUS.HIHI 300040 11 Boolean RO 1000 EPU CABINET SOM 2A OUTPUT POWER STATUS WORD - HIHI
EPU.ALOG.VI_2B.SCALED 300041 Float RO 1000 EPU Cabinet SOM 2B Output Voltage
EPU.ALOG.VI_2B.STATUS.OVR_ACT 300043 0 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT VOLTAGE STATUS WORD - OVERRIDE ACTIVE
EPU.ALOG.VI_2B.STATUS.UNKNOWN_A 300043 1 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT VOLTAGE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
EPU.ALOG.VI_2B.STATUS.UNKNOWN_B 300043 2 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT VOLTAGE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
EPU.ALOG.VI_2B.STATUS.UN_RANGE 300043 3 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT VOLTAGE STATUS WORD - UNDERRANGE
EPU.ALOG.VI_2B.STATUS.OV_RANGE 300043 4 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT VOLTAGE STATUS WORD - OVERRANGE
EPU.ALOG.VI_2B.STATUS.LOLO 300043 8 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT VOLTAGE STATUS WORD - LOLO
EPU.ALOG.VI_2B.STATUS.LO 300043 9 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT VOLTAGE STATUS WORD - LO
EPU.ALOG.VI_2B.STATUS.HI 300043 10 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT VOLTAGE STATUS WORD - HI
EPU.ALOG.VI_2B.STATUS.HIHI 300043 11 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT VOLTAGE STATUS WORD - HIHI
EPU.ALOG.II_2B.SCALED 300044 Float RO 1000 EPU Cabinet SOM 2B Output Current
EPU.ALOG.II_2B.STATUS.OVR_ACT 300046 0 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT CURRENT STATUS WORD - OVERRIDE ACTIVE
EPU.ALOG.II_2B.STATUS.UNKNOWN_A 300046 1 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT CURRENT STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
EPU.ALOG.II_2B.STATUS.UNKNOWN_B 300046 2 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT CURRENT STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
EPU.ALOG.II_2B.STATUS.UN_RANGE 300046 3 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT CURRENT STATUS WORD - UNDERRANGE
EPU.ALOG.II_2B.STATUS.OV_RANGE 300046 4 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT CURRENT STATUS WORD - OVERRANGE
EPU.ALOG.II_2B.STATUS.LOLO 300046 8 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT CURRENT STATUS WORD - LOLO
EPU.ALOG.II_2B.STATUS.LO 300046 9 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT CURRENT STATUS WORD - LO

Page 6 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx EPU 19/04/2024

Validation Date Tag Name Address Data Type Client Access Scan Rate Description
EPU.ALOG.II_2B.STATUS.HI 300046 10 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT CURRENT STATUS WORD - HI
EPU.ALOG.II_2B.STATUS.HIHI 300046 11 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT CURRENT STATUS WORD - HIHI
EPU.ALOG.JI_2B.SCALED 300047 Float RO 1000 EPU Cabinet SOM 2B Output Power
EPU.ALOG.JI_2B.STATUS.OVR_ACT 300049 0 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT POWER STATUS WORD - OVERRIDE ACTIVE
EPU.ALOG.JI_2B.STATUS.UNKNOWN_A 300049 1 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT POWER STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
EPU.ALOG.JI_2B.STATUS.UNKNOWN_B 300049 2 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT POWER STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
EPU.ALOG.JI_2B.STATUS.UN_RANGE 300049 3 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT POWER STATUS WORD - UNDERRANGE
EPU.ALOG.JI_2B.STATUS.OV_RANGE 300049 4 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT POWER STATUS WORD - OVERRANGE
EPU.ALOG.JI_2B.STATUS.LOLO 300049 8 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT POWER STATUS WORD - LOLO
EPU.ALOG.JI_2B.STATUS.LO 300049 9 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT POWER STATUS WORD - LO
EPU.ALOG.JI_2B.STATUS.HI 300049 10 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT POWER STATUS WORD - HI
EPU.ALOG.JI_2B.STATUS.HIHI 300049 11 Boolean RO 1000 EPU CABINET SOM 2B OUTPUT POWER STATUS WORD - HIHI
EPU.SOM1A.STATUS.TRIP_CMNFAIL 300050 0 Boolean RO 1000 EPU Cabinet Subsea Output Module 1A Status Word - Common Failure
EPU.SOM1A.STATUS.PWR_ON 300050 1 Boolean RO 1000 EPU Cabinet Subsea Output Module 1A Status Word - Power On
EPU.SOM1A.STATUS.ALM_LINEISO 300050 2 Boolean RO 1000 EPU Cabinet Subsea Output Module 1A Status Word - Line Iso Monitor Alm
EPU.SOM1A.STATUS.TRIP_LINEISO 300050 3 Boolean RO 1000 EPU Cabinet Subsea Output Module 1A Status Word - Line Iso Monitor Trip
EPU.SOM1A.STATUS.ALM_XMR_TAH 300050 4 Boolean RO 1000 EPU Cabinet Subsea Output Module 1A Status Word - Transformer Alarm High
EPU.SOM1A.STATUS.ALM_HI_VOLT 300050 5 Boolean RO 1000 EPU Cabinet Subsea Output Module 1A Status Word - Over Voltage Alarm
EPU.SOM1A.STATUS.ALM_LO_VOLT 300050 6 Boolean RO 1000 EPU Cabinet Subsea Output Module 1A Status Word - Under Voltage Alarm
EPU.SOM1A.STATUS.TRIP_SECCB 300050 7 Boolean RO 1000 EPU Cabinet Subsea Output Module 1A Status Word - Sec Circuit Brkr Tripped
EPU.SOM1A.STATUS.TRIP_HI_VOLT 300050 8 Boolean RO 1000 EPU Cabinet Subsea Output Module 1A Status Word - Over Voltage Trip
EPU.SOM1A.STATUS.TRIP_LO_VOLT 300050 9 Boolean RO 1000 EPU Cabinet Subsea Output Module 1A Status Word - Under Voltage Trip
EPU.SOM1B.STATUS.TRIP_CMNFAIL 300051 0 Boolean RO 1000 EPU Cabinet Subsea Output Module 1B Status Word - Common Failure
EPU.SOM1B.STATUS.PWR_ON 300051 1 Boolean RO 1000 EPU Cabinet Subsea Output Module 1B Status Word - Power On
EPU.SOM1B.STATUS.ALM_LINEISO 300051 2 Boolean RO 1000 EPU Cabinet Subsea Output Module 1B Status Word - Line Iso Monitor Alm
EPU.SOM1B.STATUS.TRIP_LINEISO 300051 3 Boolean RO 1000 EPU Cabinet Subsea Output Module 1B Status Word - Line Iso Monitor Trip
EPU.SOM1B.STATUS.ALM_XMR_TAH 300051 4 Boolean RO 1000 EPU Cabinet Subsea Output Module 1B Status Word - Transformer Alarm High
EPU.SOM1B.STATUS.ALM_HI_VOLT 300051 5 Boolean RO 1000 EPU Cabinet Subsea Output Module 1B Status Word - Over Voltage Alarm
EPU.SOM1B.STATUS.ALM_LO_VOLT 300051 6 Boolean RO 1000 EPU Cabinet Subsea Output Module 1B Status Word - Under Voltage Alarm
EPU.SOM1B.STATUS.TRIP_SECCB 300051 7 Boolean RO 1000 EPU Cabinet Subsea Output Module 1B Status Word - Sec Circuit Brkr Tripped
EPU.SOM1B.STATUS.TRIP_HI_VOLT 300051 8 Boolean RO 1000 EPU Cabinet Subsea Output Module 1B Status Word - Over Voltage Trip
EPU.SOM1B.STATUS.TRIP_LO_VOLT 300051 9 Boolean RO 1000 EPU Cabinet Subsea Output Module 1B Status Word - Under Voltage Trip
EPU.SOM2A.STATUS.TRIP_CMNFAIL 300052 0 Boolean RO 1000 EPU Cabinet Subsea Output Module 2A Status Word - Common Failure
EPU.SOM2A.STATUS.PWR_ON 300052 1 Boolean RO 1000 EPU Cabinet Subsea Output Module 2A Status Word - Power On
EPU.SOM2A.STATUS.ALM_LINEISO 300052 2 Boolean RO 1000 EPU Cabinet Subsea Output Module 2A Status Word - Line Iso Monitor Alm
EPU.SOM2A.STATUS.TRIP_LINEISO 300052 3 Boolean RO 1000 EPU Cabinet Subsea Output Module 2A Status Word - Line Iso Monitor Trip
EPU.SOM2A.STATUS.ALM_XMR_TAH 300052 4 Boolean RO 1000 EPU Cabinet Subsea Output Module 2A Status Word - Transformer Alarm High
EPU.SOM2A.STATUS.ALM_HI_VOLT 300052 5 Boolean RO 1000 EPU Cabinet Subsea Output Module 2A Status Word - Over Voltage Alarm
EPU.SOM2A.STATUS.ALM_LO_VOLT 300052 6 Boolean RO 1000 EPU Cabinet Subsea Output Module 2A Status Word - Under Voltage Alarm
EPU.SOM2A.STATUS.TRIP_SECCB 300052 7 Boolean RO 1000 EPU Cabinet Subsea Output Module 2A Status Word - Sec Circuit Brkr Tripped
EPU.SOM2A.STATUS.TRIP_HI_VOLT 300052 8 Boolean RO 1000 EPU Cabinet Subsea Output Module 2A Status Word - Over Voltage Trip
EPU.SOM2A.STATUS.TRIP_LO_VOLT 300052 9 Boolean RO 1000 EPU Cabinet Subsea Output Module 2A Status Word - Under Voltage Trip
EPU.SOM2B.STATUS.TRIP_CMNFAIL 300053 0 Boolean RO 1000 EPU Cabinet Subsea Output Module 2B Status Word - Common Failure
EPU.SOM2B.STATUS.PWR_ON 300053 1 Boolean RO 1000 EPU Cabinet Subsea Output Module 2B Status Word - Power On
EPU.SOM2B.STATUS.ALM_LINEISO 300053 2 Boolean RO 1000 EPU Cabinet Subsea Output Module 2B Status Word - Line Iso Monitor Alm
EPU.SOM2B.STATUS.TRIP_LINEISO 300053 3 Boolean RO 1000 EPU Cabinet Subsea Output Module 2B Status Word - Line Iso Monitor Trip
EPU.SOM2B.STATUS.ALM_XMR_TAH 300053 4 Boolean RO 1000 EPU Cabinet Subsea Output Module 2B Status Word - Transformer Alarm High
EPU.SOM2B.STATUS.ALM_HI_VOLT 300053 5 Boolean RO 1000 EPU Cabinet Subsea Output Module 2B Status Word - Over Voltage Alarm
EPU.SOM2B.STATUS.ALM_LO_VOLT 300053 6 Boolean RO 1000 EPU Cabinet Subsea Output Module 2B Status Word - Under Voltage Alarm
EPU.SOM2B.STATUS.TRIP_SECCB 300053 7 Boolean RO 1000 EPU Cabinet Subsea Output Module 2B Status Word - Sec Circuit Brkr Tripped
EPU.SOM2B.STATUS.TRIP_HI_VOLT 300053 8 Boolean RO 1000 EPU Cabinet Subsea Output Module 2B Status Word - Over Voltage Trip
EPU.SOM2B.STATUS.TRIP_LO_VOLT 300053 9 Boolean RO 1000 EPU Cabinet Subsea Output Module 2B Status Word - Under Voltage Trip

Page 7 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx G19 19/04/2024

Validation Date Tag Name Address Data Type Client Access Scan Rate Description
G19.STATUS.SEMA_ONSCAN 300001 0 Boolean RO 1000 WELL G-19 - MCS ON SCAN WITH SCM VIA CHA
G19.STATUS.SEMB_ONSCAN 300001 1 Boolean RO 1000 WELL G-19 - MCS ON SCAN WITH SCM VIA CHB
G19.STATUS.FLT_SEMA 300001 2 Boolean RO 1000 WELL G-19 - MCS UNABLE TO COMM WITH SCM VIA CHA
G19.STATUS.FLT_SEMB 300001 3 Boolean RO 1000 WELL G-19 - MCS UNABLE TO COMM WITH SCM VIA CHB
G19.STATUS.WELL_FLOWING 300001 4 Boolean RO 1000 WELL G-19 - WELL IS FLOWING
G19.STATUS.SMART 300001 5 Boolean RO 1000 WELL G-19 - SMART WELL FEATURES ENABLED
G19.STATUS.SCM_DIAG_ALM 300001 6 Boolean RO 1000 WELL G-19 - SCM DIAGNOSTIC ALARM ACT&UNACK
G19.ILOCK.SEQ_COND 300002 0 Boolean RO 1000 WELL G-19 I-LOCK - SEQUENCE COND
G19.ILOCK.SEQ_TRIP 300002 1 Boolean RO 1000 WELL G-19 I-LOCK - SEQUENCE COND - PSD/ESD/TSE TRIP ACTIVE
G19.ILOCK.KEY_MCS 300002 2 Boolean RO 1000 WELL G-19 I-LOCK - MCS ONLY IN CONTROL (KEYSWITCH)
G19.ILOCK.KEY_DCS 300002 3 Boolean RO 1000 WELL G-19 I-LOCK - DCS ONLY IN CONTROL (KEYSWITCH)
G19.ILOCK.NO_SCM 300002 4 Boolean RO 1000 WELL G-19 I-LOCK - SCM NOT INSTALLED - ALL CTRL DISABLED
G19.ILOCK.SCM_OFF_SCAN 300002 5 Boolean RO 1000 WELL G-19 I-LOCK - SCM OFF SCAN - ALL CTRL DISABLED
G19.ILOCK.TOT_COMM_LOSS 300002 6 Boolean RO 1000 WELL G-19 I-LOCK - TOTAL COMM LOSS
G19.ILOCK.WORKOVER 300002 7 Boolean RO 1000 WELL G-19 I-LOCK - WELL IN WORKOVER - ALL CTRL DISABLED
G19.ILOCK.MAXSOLS 300002 8 Boolean RO 1000 WELL G-19 I-LOCK - MAX SOLENOIDS ENERGIZED
G19.ILOCK.DV_DEFLOW 300002 9 Boolean RO 1000 WELL G-19 I-LOCK - DUMP VALVE DEENERGIZED - LP OPS I-LOCK
G19.ILOCK.HPHDR_LO 300002 10 Boolean RO 1000 WELL G-19 I-LOCK - HP HEADER LO PRESS - HP OPS I-LOCK
G19.ILOCK.HPHDR_UNK 300002 11 Boolean RO 1000 WELL G-19 I-LOCK - HP HEADER UNKNOWN PRESS - HP OPS I-LOCK
G19.ILOCK.LPHDR_LO 300002 12 Boolean RO 1000 WELL G-19 I-LOCK - LP HEADER LO PRESS - LP OPS I-LOCK
G19.ILOCK.LPHDR_UNK 300002 13 Boolean RO 1000 WELL G-19 I-LOCK - LP HEADER UNKNOWN PRESS - LP OPS I-LOCK
G19.ILOCK.MAXLP 300002 14 Boolean RO 1000 WELL G-19 I-LOCK - MAX LP VALVE PRESS IS EXCEEDED
G19.ILOCK.VALUE 300002 Word RO 1000 G19 Well Interlock Word
G19.ALOG.LPHPT.SCALED 300003 Float RO 1000 G19 Well LP Header Pressure
G19.ALOG.LPHPT.STATUS.OVR_ACT 300005 0 Boolean RO 1000 G19 WELL LP HEADER PRESSURE STATUS WORD - OVERRIDE ACTIVE
G19.ALOG.LPHPT.STATUS.UNKNOWN_A 300005 1 Boolean RO 1000 G19 WELL LP HEADER PRESSURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
G19.ALOG.LPHPT.STATUS.UNKNOWN_B 300005 2 Boolean RO 1000 G19 WELL LP HEADER PRESSURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
G19.ALOG.LPHPT.STATUS.UN_RANGE 300005 3 Boolean RO 1000 G19 WELL LP HEADER PRESSURE STATUS WORD - UNDERRANGE
G19.ALOG.LPHPT.STATUS.OV_RANGE 300005 4 Boolean RO 1000 G19 WELL LP HEADER PRESSURE STATUS WORD - OVERRANGE
G19.ALOG.LPHPT.STATUS.LOLO 300005 8 Boolean RO 1000 G19 WELL LP HEADER PRESSURE STATUS WORD - LOLO
G19.ALOG.LPHPT.STATUS.LO 300005 9 Boolean RO 1000 G19 WELL LP HEADER PRESSURE STATUS WORD - LO
G19.ALOG.LPHPT.STATUS.HI 300005 10 Boolean RO 1000 G19 WELL LP HEADER PRESSURE STATUS WORD - HI
G19.ALOG.LPHPT.STATUS.HIHI 300005 11 Boolean RO 1000 G19 WELL LP HEADER PRESSURE STATUS WORD - HIHI
G19.ALOG.HPHPT.SCALED 300006 Float RO 1000 G19 Well HP Header Pressure
G19.ALOG.HPHPT.STATUS.OVR_ACT 300008 0 Boolean RO 1000 G19 WELL HP HEADER PRESSURE STATUS WORD - OVERRIDE ACTIVE
G19.ALOG.HPHPT.STATUS.UNKNOWN_A 300008 1 Boolean RO 1000 G19 WELL HP HEADER PRESSURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
G19.ALOG.HPHPT.STATUS.UNKNOWN_B 300008 2 Boolean RO 1000 G19 WELL HP HEADER PRESSURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
G19.ALOG.HPHPT.STATUS.UN_RANGE 300008 3 Boolean RO 1000 G19 WELL HP HEADER PRESSURE STATUS WORD - UNDERRANGE
G19.ALOG.HPHPT.STATUS.OV_RANGE 300008 4 Boolean RO 1000 G19 WELL HP HEADER PRESSURE STATUS WORD - OVERRANGE
G19.ALOG.HPHPT.STATUS.LOLO 300008 8 Boolean RO 1000 G19 WELL HP HEADER PRESSURE STATUS WORD - LOLO
G19.ALOG.HPHPT.STATUS.LO 300008 9 Boolean RO 1000 G19 WELL HP HEADER PRESSURE STATUS WORD - LO
G19.ALOG.HPHPT.STATUS.HI 300008 10 Boolean RO 1000 G19 WELL HP HEADER PRESSURE STATUS WORD - HI
G19.ALOG.HPHPT.STATUS.HIHI 300008 11 Boolean RO 1000 G19 WELL HP HEADER PRESSURE STATUS WORD - HIHI
G19.ALOG.UPPT.SCALED 300009 Float RO 1000 G19 Well Upstream Production Pressure
G19.ALOG.UPPT.STATUS.OVR_ACT 300011 0 Boolean RO 1000 G19 WELL UPSTREAM PRODUCTION PRESSURE STATUS WORD - OVERRIDE ACTIVE
G19.ALOG.UPPT.STATUS.UNKNOWN_A 300011 1 Boolean RO 1000 G19 WELL UPSTREAM PRODUCTION PRESSURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
G19.ALOG.UPPT.STATUS.UNKNOWN_B 300011 2 Boolean RO 1000 G19 WELL UPSTREAM PRODUCTION PRESSURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
G19.ALOG.UPPT.STATUS.UN_RANGE 300011 3 Boolean RO 1000 G19 WELL UPSTREAM PRODUCTION PRESSURE STATUS WORD - UNDERRANGE
G19.ALOG.UPPT.STATUS.OV_RANGE 300011 4 Boolean RO 1000 G19 WELL UPSTREAM PRODUCTION PRESSURE STATUS WORD - OVERRANGE
G19.ALOG.UPPT.STATUS.LOLO 300011 8 Boolean RO 1000 G19 WELL UPSTREAM PRODUCTION PRESSURE STATUS WORD - LOLO
G19.ALOG.UPPT.STATUS.LO 300011 9 Boolean RO 1000 G19 WELL UPSTREAM PRODUCTION PRESSURE STATUS WORD - LO
G19.ALOG.UPPT.STATUS.HI 300011 10 Boolean RO 1000 G19 WELL UPSTREAM PRODUCTION PRESSURE STATUS WORD - HI
G19.ALOG.UPPT.STATUS.HIHI 300011 11 Boolean RO 1000 G19 WELL UPSTREAM PRODUCTION PRESSURE STATUS WORD - HIHI
G19.ALOG.UPTT.SCALED 300012 Float RO 1000 G19 Well Upstream Production Temperature
G19.ALOG.UPTT.STATUS.OVR_ACT 300014 0 Boolean RO 1000 G19 WELL UPSTREAM PRODUCTION TEMPERATURE STATUS WORD - OVERRIDE ACTIVE
G19.ALOG.UPTT.STATUS.UNKNOWN_A 300014 1 Boolean RO 1000 G19 WELL UPSTREAM PRODUCTION TEMPERATURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
G19.ALOG.UPTT.STATUS.UNKNOWN_B 300014 2 Boolean RO 1000 G19 WELL UPSTREAM PRODUCTION TEMPERATURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
G19.ALOG.UPTT.STATUS.UN_RANGE 300014 3 Boolean RO 1000 G19 WELL UPSTREAM PRODUCTION TEMPERATURE STATUS WORD - UNDERRANGE

Page 8 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx G19 19/04/2024

Validation Date Tag Name Address Data Type Client Access Scan Rate Description
G19.ALOG.UPTT.STATUS.OV_RANGE 300014 4 Boolean RO 1000 G19 WELL UPSTREAM PRODUCTION TEMPERATURE STATUS WORD - OVERRANGE
G19.ALOG.UPTT.STATUS.LOLO 300014 8 Boolean RO 1000 G19 WELL UPSTREAM PRODUCTION TEMPERATURE STATUS WORD - LOLO
G19.ALOG.UPTT.STATUS.LO 300014 9 Boolean RO 1000 G19 WELL UPSTREAM PRODUCTION TEMPERATURE STATUS WORD - LO
G19.ALOG.UPTT.STATUS.HI 300014 10 Boolean RO 1000 G19 WELL UPSTREAM PRODUCTION TEMPERATURE STATUS WORD - HI
G19.ALOG.UPTT.STATUS.HIHI 300014 11 Boolean RO 1000 G19 WELL UPSTREAM PRODUCTION TEMPERATURE STATUS WORD - HIHI
G19.ALOG.APT.SCALED 300015 Float RO 1000 G19 Well Annulus Pressure
G19.ALOG.APT.STATUS.OVR_ACT 300017 0 Boolean RO 1000 G19 WELL ANNULUS PRESSURE STATUS WORD - OVERRIDE ACTIVE
G19.ALOG.APT.STATUS.UNKNOWN_A 300017 1 Boolean RO 1000 G19 WELL ANNULUS PRESSURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
G19.ALOG.APT.STATUS.UNKNOWN_B 300017 2 Boolean RO 1000 G19 WELL ANNULUS PRESSURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
G19.ALOG.APT.STATUS.UN_RANGE 300017 3 Boolean RO 1000 G19 WELL ANNULUS PRESSURE STATUS WORD - UNDERRANGE
G19.ALOG.APT.STATUS.OV_RANGE 300017 4 Boolean RO 1000 G19 WELL ANNULUS PRESSURE STATUS WORD - OVERRANGE
G19.ALOG.APT.STATUS.LOLO 300017 8 Boolean RO 1000 G19 WELL ANNULUS PRESSURE STATUS WORD - LOLO
G19.ALOG.APT.STATUS.LO 300017 9 Boolean RO 1000 G19 WELL ANNULUS PRESSURE STATUS WORD - LO
G19.ALOG.APT.STATUS.HI 300017 10 Boolean RO 1000 G19 WELL ANNULUS PRESSURE STATUS WORD - HI
G19.ALOG.APT.STATUS.HIHI 300017 11 Boolean RO 1000 G19 WELL ANNULUS PRESSURE STATUS WORD - HIHI
G19.ALOG.DPPT.SCALED 300021 Float RO 1000 G19 Well Downstream Production Pressure
G19.ALOG.DPPT.STATUS.OVR_ACT 300023 0 Boolean RO 1000 G19 WELL DOWNSTREAM PRODUCTION PRESSURE STATUS WORD - OVERRIDE ACTIVE
G19.ALOG.DPPT.STATUS.UNKNOWN_A 300023 1 Boolean RO 1000 G19 WELL DOWNSTREAM PRODUCTION PRESSURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
G19.ALOG.DPPT.STATUS.UNKNOWN_B 300023 2 Boolean RO 1000 G19 WELL DOWNSTREAM PRODUCTION PRESSURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
G19.ALOG.DPPT.STATUS.UN_RANGE 300023 3 Boolean RO 1000 G19 WELL DOWNSTREAM PRODUCTION PRESSURE STATUS WORD - UNDERRANGE
G19.ALOG.DPPT.STATUS.OV_RANGE 300023 4 Boolean RO 1000 G19 WELL DOWNSTREAM PRODUCTION PRESSURE STATUS WORD - OVERRANGE
G19.ALOG.DPPT.STATUS.LOLO 300023 8 Boolean RO 1000 G19 WELL DOWNSTREAM PRODUCTION PRESSURE STATUS WORD - LOLO
G19.ALOG.DPPT.STATUS.LO 300023 9 Boolean RO 1000 G19 WELL DOWNSTREAM PRODUCTION PRESSURE STATUS WORD - LO
G19.ALOG.DPPT.STATUS.HI 300023 10 Boolean RO 1000 G19 WELL DOWNSTREAM PRODUCTION PRESSURE STATUS WORD - HI
G19.ALOG.DPPT.STATUS.HIHI 300023 11 Boolean RO 1000 G19 WELL DOWNSTREAM PRODUCTION PRESSURE STATUS WORD - HIHI
G19.ALOG.DPTT.SCALED 300024 Float RO 1000 G19 Well Downstream Production Temperature
G19.ALOG.DPTT.STATUS.OVR_ACT 300026 0 Boolean RO 1000 G19 WELL DOWNSTREAM PRODUCTION TEMPERATURE STATUS WORD - OVERRIDE ACTIVE
G19.ALOG.DPTT.STATUS.UNKNOWN_A 300026 1 Boolean RO 1000 G19 WELL DOWNSTREAM PRODUCTION TEMPERATURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
G19.ALOG.DPTT.STATUS.UNKNOWN_B 300026 2 Boolean RO 1000 G19 WELL DOWNSTREAM PRODUCTION TEMPERATURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
G19.ALOG.DPTT.STATUS.UN_RANGE 300026 3 Boolean RO 1000 G19 WELL DOWNSTREAM PRODUCTION TEMPERATURE STATUS WORD - UNDERRANGE
G19.ALOG.DPTT.STATUS.OV_RANGE 300026 4 Boolean RO 1000 G19 WELL DOWNSTREAM PRODUCTION TEMPERATURE STATUS WORD - OVERRANGE
G19.ALOG.DPTT.STATUS.LOLO 300026 8 Boolean RO 1000 G19 WELL DOWNSTREAM PRODUCTION TEMPERATURE STATUS WORD - LOLO
G19.ALOG.DPTT.STATUS.LO 300026 9 Boolean RO 1000 G19 WELL DOWNSTREAM PRODUCTION TEMPERATURE STATUS WORD - LO
G19.ALOG.DPTT.STATUS.HI 300026 10 Boolean RO 1000 G19 WELL DOWNSTREAM PRODUCTION TEMPERATURE STATUS WORD - HI
G19.ALOG.DPTT.STATUS.HIHI 300026 11 Boolean RO 1000 G19 WELL DOWNSTREAM PRODUCTION TEMPERATURE STATUS WORD - HIHI
G19.ALOG.DHPT1.SCALED 300033 Float RO 1000 G19 Well Downhole Pressure-1
G19.ALOG.DHPT1.STATUS.OVR_ACT 300035 0 Boolean RO 1000 G19 WELL DOWNHOLE PRESSURE-1 STATUS WORD - OVERRIDE ACTIVE
G19.ALOG.DHPT1.STATUS.UNKNOWN_A 300035 1 Boolean RO 1000 G19 WELL DOWNHOLE PRESSURE-1 STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
G19.ALOG.DHPT1.STATUS.UNKNOWN_B 300035 2 Boolean RO 1000 G19 WELL DOWNHOLE PRESSURE-1 STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
G19.ALOG.DHPT1.STATUS.UN_RANGE 300035 3 Boolean RO 1000 G19 WELL DOWNHOLE PRESSURE-1 STATUS WORD - UNDERRANGE
G19.ALOG.DHPT1.STATUS.OV_RANGE 300035 4 Boolean RO 1000 G19 WELL DOWNHOLE PRESSURE-1 STATUS WORD - OVERRANGE
G19.ALOG.DHPT1.STATUS.LOLO 300035 8 Boolean RO 1000 G19 WELL DOWNHOLE PRESSURE-1 STATUS WORD - LOLO
G19.ALOG.DHPT1.STATUS.LO 300035 9 Boolean RO 1000 G19 WELL DOWNHOLE PRESSURE-1 STATUS WORD - LO
G19.ALOG.DHPT1.STATUS.HI 300035 10 Boolean RO 1000 G19 WELL DOWNHOLE PRESSURE-1 STATUS WORD - HI
G19.ALOG.DHPT1.STATUS.HIHI 300035 11 Boolean RO 1000 G19 WELL DOWNHOLE PRESSURE-1 STATUS WORD - HIHI
G19.ALOG.DHTT1.SCALED 300036 Float RO 1000 G19 Well Downhole Temperature-1
G19.ALOG.DHTT1.STATUS.OVR_ACT 300038 0 Boolean RO 1000 G19 WELL DOWNHOLE TEMPERATURE-1 STATUS WORD - OVERRIDE ACTIVE
G19.ALOG.DHTT1.STATUS.UNKNOWN_A 300038 1 Boolean RO 1000 G19 WELL DOWNHOLE TEMPERATURE-1 STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
G19.ALOG.DHTT1.STATUS.UNKNOWN_B 300038 2 Boolean RO 1000 G19 WELL DOWNHOLE TEMPERATURE-1 STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
G19.ALOG.DHTT1.STATUS.UN_RANGE 300038 3 Boolean RO 1000 G19 WELL DOWNHOLE TEMPERATURE-1 STATUS WORD - UNDERRANGE
G19.ALOG.DHTT1.STATUS.OV_RANGE 300038 4 Boolean RO 1000 G19 WELL DOWNHOLE TEMPERATURE-1 STATUS WORD - OVERRANGE
G19.ALOG.DHTT1.STATUS.LOLO 300038 8 Boolean RO 1000 G19 WELL DOWNHOLE TEMPERATURE-1 STATUS WORD - LOLO
G19.ALOG.DHTT1.STATUS.LO 300038 9 Boolean RO 1000 G19 WELL DOWNHOLE TEMPERATURE-1 STATUS WORD - LO
G19.ALOG.DHTT1.STATUS.HI 300038 10 Boolean RO 1000 G19 WELL DOWNHOLE TEMPERATURE-1 STATUS WORD - HI
G19.ALOG.DHTT1.STATUS.HIHI 300038 11 Boolean RO 1000 G19 WELL DOWNHOLE TEMPERATURE-1 STATUS WORD - HIHI
G19.ALOG.DHPT2.SCALED 300039 Float RO 1000 G19 Well Downhole Pressure-2
G19.ALOG.DHPT2.STATUS.OVR_ACT 300041 0 Boolean RO 1000 G19 WELL DOWNHOLE PRESSURE-2 STATUS WORD - OVERRIDE ACTIVE
G19.ALOG.DHPT2.STATUS.UNKNOWN_A 300041 1 Boolean RO 1000 G19 WELL DOWNHOLE PRESSURE-2 STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A

Page 9 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx G19 19/04/2024

Validation Date Tag Name Address Data Type Client Access Scan Rate Description
G19.ALOG.DHPT2.STATUS.UNKNOWN_B 300041 2 Boolean RO 1000 G19 WELL DOWNHOLE PRESSURE-2 STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
G19.ALOG.DHPT2.STATUS.UN_RANGE 300041 3 Boolean RO 1000 G19 WELL DOWNHOLE PRESSURE-2 STATUS WORD - UNDERRANGE
G19.ALOG.DHPT2.STATUS.OV_RANGE 300041 4 Boolean RO 1000 G19 WELL DOWNHOLE PRESSURE-2 STATUS WORD - OVERRANGE
G19.ALOG.DHPT2.STATUS.LOLO 300041 8 Boolean RO 1000 G19 WELL DOWNHOLE PRESSURE-2 STATUS WORD - LOLO
G19.ALOG.DHPT2.STATUS.LO 300041 9 Boolean RO 1000 G19 WELL DOWNHOLE PRESSURE-2 STATUS WORD - LO
G19.ALOG.DHPT2.STATUS.HI 300041 10 Boolean RO 1000 G19 WELL DOWNHOLE PRESSURE-2 STATUS WORD - HI
G19.ALOG.DHPT2.STATUS.HIHI 300041 11 Boolean RO 1000 G19 WELL DOWNHOLE PRESSURE-2 STATUS WORD - HIHI
G19.ALOG.DHTT2.SCALED 300042 Float RO 1000 G19 Well Downhole Temperature-2
G19.ALOG.DHTT2.STATUS.OVR_ACT 300044 0 Boolean RO 1000 G19 WELL DOWNHOLE TEMPERATURE-2 STATUS WORD - OVERRIDE ACTIVE
G19.ALOG.DHTT2.STATUS.UNKNOWN_A 300044 1 Boolean RO 1000 G19 WELL DOWNHOLE TEMPERATURE-2 STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
G19.ALOG.DHTT2.STATUS.UNKNOWN_B 300044 2 Boolean RO 1000 G19 WELL DOWNHOLE TEMPERATURE-2 STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
G19.ALOG.DHTT2.STATUS.UN_RANGE 300044 3 Boolean RO 1000 G19 WELL DOWNHOLE TEMPERATURE-2 STATUS WORD - UNDERRANGE
G19.ALOG.DHTT2.STATUS.OV_RANGE 300044 4 Boolean RO 1000 G19 WELL DOWNHOLE TEMPERATURE-2 STATUS WORD - OVERRANGE
G19.ALOG.DHTT2.STATUS.LOLO 300044 8 Boolean RO 1000 G19 WELL DOWNHOLE TEMPERATURE-2 STATUS WORD - LOLO
G19.ALOG.DHTT2.STATUS.LO 300044 9 Boolean RO 1000 G19 WELL DOWNHOLE TEMPERATURE-2 STATUS WORD - LO
G19.ALOG.DHTT2.STATUS.HI 300044 10 Boolean RO 1000 G19 WELL DOWNHOLE TEMPERATURE-2 STATUS WORD - HI
G19.ALOG.DHTT2.STATUS.HIHI 300044 11 Boolean RO 1000 G19 WELL DOWNHOLE TEMPERATURE-2 STATUS WORD - HIHI
G19.ALOG.CPI.SCALED 300065 Float RO 1000 G19 Well Choke Position Indicator
G19.ALOG.CPI.STATUS.OVR_ACT 300067 0 Boolean RO 1000 G19 WELL CHOCKE POSITION INDICATOR STATUS WORD - OVERRIDE ACTIVE
G19.ALOG.CPI.STATUS.UNKNOWN_A 300067 1 Boolean RO 1000 G19 WELL CHOCKE POSITION INDICATOR STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
G19.ALOG.CPI.STATUS.UNKNOWN_B 300067 2 Boolean RO 1000 G19 WELL CHOCKE POSITION INDICATOR STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
G19.ALOG.CPI.STATUS.UN_RANGE 300067 3 Boolean RO 1000 G19 WELL CHOCKE POSITION INDICATOR STATUS WORD - UNDERRANGE
G19.ALOG.CPI.STATUS.OV_RANGE 300067 4 Boolean RO 1000 G19 WELL CHOCKE POSITION INDICATOR STATUS WORD - OVERRANGE
G19.ALOG.CPI.STATUS.LOLO 300067 8 Boolean RO 1000 G19 WELL CHOCKE POSITION INDICATOR STATUS WORD - LOLO
G19.ALOG.CPI.STATUS.LO 300067 9 Boolean RO 1000 G19 WELL CHOCKE POSITION INDICATOR STATUS WORD - LO
G19.ALOG.CPI.STATUS.HI 300067 10 Boolean RO 1000 G19 WELL CHOCKE POSITION INDICATOR STATUS WORD - HI
G19.ALOG.CPI.STATUS.HIHI 300067 11 Boolean RO 1000 G19 WELL CHOCKE POSITION INDICATOR STATUS WORD - HIHI
G19.VALVE.AMV.STATUS.OPEN 300071 0 Boolean RO 1000 G19 WELL ANNULUS MASTER VALVE STATUS WORD - IS OPEN
G19.VALVE.AMV.STATUS.CLOSED 300071 1 Boolean RO 1000 G19 WELL ANNULUS MASTER VALVE STATUS WORD - IS CLOSED
G19.VALVE.AMV.STATUS.MOVING 300071 2 Boolean RO 1000 G19 WELL ANNULUS MASTER VALVE STATUS WORD - IS MOVING
G19.VALVE.AMV.STATUS.ALM_DISC 300071 3 Boolean RO 1000 G19 WELL ANNULUS MASTER VALVE STATUS WORD - DISCREPENCY
G19.VALVE.AMV.STATUS.ALM_FLTOMOV 300071 4 Boolean RO 1000 G19 WELL ANNULUS MASTER VALVE STATUS WORD - FAILED TO OPEN
G19.VALVE.AMV.STATUS.ALM_FBIGNORE 300071 5 Boolean RO 1000 G19 WELL ANNULUS MASTER VALVE STATUS WORD - FEEDBACK IS IGNORED
G19.VALVE.AMV.STATUS.OK_TO_OPN 300071 6 Boolean RO 1000 G19 WELL ANNULUS MASTER VALVE STATUS WORD - OK TO OPEN
G19.VALVE.AMV.STATUS.OK_TO_CLS 300071 7 Boolean RO 1000 G19 WELL ANNULUS MASTER VALVE STATUS WORD - OK TO CLOSE
G19.VALVE.AMV.STATUS.OPN_ILOCK_DFT 300071 8 Boolean RO 1000 G19 WELL ANNULUS MASTER VALVE STATUS WORD - OPEN ILOCK DEFEATABLE
G19.VALVE.AMV.STATUS.CLS_ILOCK_DFT 300071 9 Boolean RO 1000 G19 WELL ANNULUS MASTER VALVE STATUS WORD - CLOSE ILOCK DEFEATABLE
G19.VALVE.AMV.ILOCK.ROV_OPN 300072 0 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - ROV Override Open
G19.VALVE.AMV.ILOCK.ROV_CLSD 300072 1 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - ROV Override Closed
G19.VALVE.AMV.ILOCK.LPHDR_LO 300072 2 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - LP Header Low
G19.VALVE.AMV.ILOCK.LPHDR_UNK 300072 3 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - LP Header Unknown
G19.VALVE.AMV.ILOCK.LPHDR_OVR 300072 4 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - LP Header Override
G19.VALVE.AMV.ILOCK.HPHDR_LO 300072 5 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - HP Header Low
G19.VALVE.AMV.ILOCK.HPHDR_UNK 300072 6 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - HP Header Unkonwn
G19.VALVE.AMV.ILOCK.HPHDR_OVR 300072 7 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - HP Header Override
G19.VALVE.AMV.ILOCK.LPHPPRS_LO 300072 8 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - Out of service OPEN
G19.VALVE.AMV.ILOCK.LPHPPRS_UNK 300072 9 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - Out of service CLOSE
G19.VALVE.AMV.ILOCK.OOS_OPN 300072 10 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - Out of service OPEN
G19.VALVE.AMV.ILOCK.OOS_CLS 300072 11 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - Out of service CLOSE
G19.VALVE.AMV.ILOCK.CE_AMVPMV_OPN 300072 12 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - AMV and PMV are open - C&E 1a
G19.VALVE.AMV.ILOCK.CE_XOVPWV_OPN 300072 13 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - XOV and PWV are open - C&E 1B
G19.VALVE.AMV.ILOCK.CE_AMVXOV_OPN 300072 14 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - AMV and XOV are open - C&E 1C & 1D
G19.VALVE.AMV.ILOCK.CE_EQUALIZE 300072 15 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - Equalize before opening - C&E 4a
G19.VALVE.AMV.ILOCK.VALUE 300072 DWord RO 1000 G19 Well Annulus Master Valve Interlock Word
G19.VALVE.AMV.ILOCK.CE_PMVXOV_OPN 300073 0 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - PMV and XOV are open - C&E 1E
G19.VALVE.AMV.ILOCK.CE_PWVAMV_OPN 300073 1 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - PWV and AMV not closed - C&E 1F
G19.VALVE.AMV.ILOCK.CE_PCV_NOTCL 300073 2 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - PCV not closed - C&E 2
G19.VALVE.AMV.ILOCK.CE_PMVPWV_NOTCL 300073 3 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - PMV or PWV not closed - C&E 4b

Page 10 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx G19 19/04/2024

Validation Date Tag Name Address Data Type Client Access Scan Rate Description
G19.VALVE.AMV.ILOCK.CE_PWV_NOTCL 300073 4 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - PWV not closed - C&E 5
G19.VALVE.AMV.ILOCK.CE_XOV_OPN 300073 5 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - XOV open - C&E 8
G19.VALVE.AMV.ILOCK.CE_GLV_OPN 300073 6 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - GLV open - C&E 9
G19.VALVE.AMV.ILOCK.CE_PMVPWV_NOTCL1 300073 9 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - PMV or PWV not Closed - C&E 4b
G19.VALVE.AMV.ILOCK.CE_PWV_NOTCL1 300073 10 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - PWV not closed - C&E 6
G19.VALVE.AMV.ILOCK.CE_PCVPWV_NOTCL 300073 11 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - PCV and PWV not closed - C&E 7a
G19.VALVE.AMV.ILOCK.CE_PCVPMV_NOTCL 300073 12 Boolean RO 1000 G19 Well Annulus Master Valve Interlock Word - PCV and PMV not Closed - C&E 7b
G19.VALVE.GLV.STATUS.OPEN 300074 0 Boolean RO 1000 G19 WELL GAS LIFT ISOLATION VALVE STATUS WORD - IS OPEN
G19.VALVE.GLV.STATUS.CLOSED 300074 1 Boolean RO 1000 G19 WELL GAS LIFT ISOLATION VALVE STATUS WORD - IS CLOSED
G19.VALVE.GLV.STATUS.MOVING 300074 2 Boolean RO 1000 G19 WELL GAS LIFT ISOLATION VALVE STATUS WORD - IS MOVING
G19.VALVE.GLV.STATUS.ALM_DISC 300074 3 Boolean RO 1000 G19 WELL GAS LIFT ISOLATION VALVE STATUS WORD - DISCREPENCY
G19.VALVE.GLV.STATUS.ALM_FLTOMOV 300074 4 Boolean RO 1000 G19 WELL GAS LIFT ISOLATION VALVE STATUS WORD - FAILED TO OPEN
G19.VALVE.GLV.STATUS.ALM_FBIGNORE 300074 5 Boolean RO 1000 G19 WELL GAS LIFT ISOLATION VALVE STATUS WORD - FEEDBACK IS IGNORED
G19.VALVE.GLV.STATUS.OK_TO_OPN 300074 6 Boolean RO 1000 G19 WELL GAS LIFT ISOLATION VALVE STATUS WORD - OK TO OPEN
G19.VALVE.GLV.STATUS.OK_TO_CLS 300074 7 Boolean RO 1000 G19 WELL GAS LIFT ISOLATION VALVE STATUS WORD - OK TO CLOSE
G19.VALVE.GLV.STATUS.OPN_ILOCK_DFT 300074 8 Boolean RO 1000 G19 WELL GAS LIFT ISOLATION VALVE STATUS WORD - OPEN ILOCK DEFEATABLE
G19.VALVE.GLV.STATUS.CLS_ILOCK_DFT 300074 9 Boolean RO 1000 G19 WELL GAS LIFT ISOLATION VALVE STATUS WORD - CLOSE ILOCK DEFEATABLE
G19.VALVE.GLV.ILOCK.ROV_OPN 300075 0 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - ROV Override Open
G19.VALVE.GLV.ILOCK.ROV_CLSD 300075 1 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - ROV Override Closed
G19.VALVE.GLV.ILOCK.LPHDR_LO 300075 2 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - LP Header Low
G19.VALVE.GLV.ILOCK.LPHDR_UNK 300075 3 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - LP Header Unknown
G19.VALVE.GLV.ILOCK.LPHDR_OVR 300075 4 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - LP Header Override
G19.VALVE.GLV.ILOCK.HPHDR_LO 300075 5 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - HP Header Low
G19.VALVE.GLV.ILOCK.HPHDR_UNK 300075 6 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - HP Header Unkonwn
G19.VALVE.GLV.ILOCK.HPHDR_OVR 300075 7 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - HP Header Override
G19.VALVE.GLV.ILOCK.LPHPPRS_LO 300075 8 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - Out of service OPEN
G19.VALVE.GLV.ILOCK.LPHPPRS_UNK 300075 9 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - Out of service CLOSE
G19.VALVE.GLV.ILOCK.OOS_OPN 300075 10 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - Out of service OPEN
G19.VALVE.GLV.ILOCK.OOS_CLS 300075 11 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - Out of service CLOSE
G19.VALVE.GLV.ILOCK.CE_AMVPMV_OPN 300075 12 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - AMV and PMV are open - C&E 1a
G19.VALVE.GLV.ILOCK.CE_XOVPWV_OPN 300075 13 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - XOV and PWV are open - C&E 1B
G19.VALVE.GLV.ILOCK.CE_AMVXOV_OPN 300075 14 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - AMV and XOV are open - C&E 1C & 1D
G19.VALVE.GLV.ILOCK.CE_EQUALIZE 300075 15 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - Equalize before opening - C&E 4a
G19.VALVE.GLV.ILOCK.VALUE 300075 DWord RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word
G19.VALVE.GLV.ILOCK.CE_PMVXOV_OPN 300076 0 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - PMV and XOV are open - C&E 1E
G19.VALVE.GLV.ILOCK.CE_PWVAMV_OPN 300076 1 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - PWV and AMV not closed - C&E 1F
G19.VALVE.GLV.ILOCK.CE_PCV_NOTCL 300076 2 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - PCV not closed - C&E 2
G19.VALVE.GLV.ILOCK.CE_PMVPWV_NOTCL 300076 3 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - PMV or PWV not closed - C&E 4b
G19.VALVE.GLV.ILOCK.CE_PWV_NOTCL 300076 4 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - PWV not closed - C&E 5
G19.VALVE.GLV.ILOCK.CE_XOV_OPN 300076 5 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - XOV open - C&E 8
G19.VALVE.GLV.ILOCK.CE_GLV_OPN 300076 6 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - GLV open - C&E 9
G19.VALVE.GLV.ILOCK.CE_PMVPWV_NOTCL1 300076 9 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - PMV or PWV not Closed - C&E 4b
G19.VALVE.GLV.ILOCK.CE_PWV_NOTCL1 300076 10 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - PWV not closed - C&E 6
G19.VALVE.GLV.ILOCK.CE_PCVPWV_NOTCL 300076 11 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - PCV and PWV not closed - C&E 7a
G19.VALVE.GLV.ILOCK.CE_PCVPMV_NOTCL 300076 12 Boolean RO 1000 G19 Well Gas Lift Isolation Valve Interlock Word - PCV and PMV not Closed - C&E 7b
G19.VALVE.PMV.STATUS.OPEN 300077 0 Boolean RO 1000 G19 WELL PRODUCTION MASTER VALVE STATUS WORD - IS OPEN
G19.VALVE.PMV.STATUS.CLOSED 300077 1 Boolean RO 1000 G19 WELL PRODUCTION MASTER VALVE STATUS WORD - IS CLOSED
G19.VALVE.PMV.STATUS.MOVING 300077 2 Boolean RO 1000 G19 WELL PRODUCTION MASTER VALVE STATUS WORD - IS MOVING
G19.VALVE.PMV.STATUS.ALM_DISC 300077 3 Boolean RO 1000 G19 WELL PRODUCTION MASTER VALVE STATUS WORD - DISCREPENCY
G19.VALVE.PMV.STATUS.ALM_FLTOMOV 300077 4 Boolean RO 1000 G19 WELL PRODUCTION MASTER VALVE STATUS WORD - FAILED TO OPEN
G19.VALVE.PMV.STATUS.ALM_FBIGNORE 300077 5 Boolean RO 1000 G19 WELL PRODUCTION MASTER VALVE STATUS WORD - FEEDBACK IS IGNORED
G19.VALVE.PMV.STATUS.OK_TO_OPN 300077 6 Boolean RO 1000 G19 WELL PRODUCTION MASTER VALVE STATUS WORD - OK TO OPEN
G19.VALVE.PMV.STATUS.OK_TO_CLS 300077 7 Boolean RO 1000 G19 WELL PRODUCTION MASTER VALVE STATUS WORD - OK TO CLOSE
G19.VALVE.PMV.STATUS.OPN_ILOCK_DFT 300077 8 Boolean RO 1000 G19 WELL PRODUCTION MASTER VALVE STATUS WORD - OPEN ILOCK DEFEATABLE
G19.VALVE.PMV.STATUS.CLS_ILOCK_DFT 300077 9 Boolean RO 1000 G19 WELL PRODUCTION MASTER VALVE STATUS WORD - CLOSE ILOCK DEFEATABLE
G19.VALVE.PMV.ILOCK.ROV_OPN 300078 0 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - ROV Override Open
G19.VALVE.PMV.ILOCK.ROV_CLSD 300078 1 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - ROV Override Closed
G19.VALVE.PMV.ILOCK.LPHDR_LO 300078 2 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - LP Header Low

Page 11 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx G19 19/04/2024

Validation Date Tag Name Address Data Type Client Access Scan Rate Description
G19.VALVE.PMV.ILOCK.LPHDR_UNK 300078 3 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - LP Header Unknown
G19.VALVE.PMV.ILOCK.LPHDR_OVR 300078 4 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - LP Header Override
G19.VALVE.PMV.ILOCK.HPHDR_LO 300078 5 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - HP Header Low
G19.VALVE.PMV.ILOCK.HPHDR_UNK 300078 6 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - HP Header Unkonwn
G19.VALVE.PMV.ILOCK.HPHDR_OVR 300078 7 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - HP Header Override
G19.VALVE.PMV.ILOCK.LPHPPRS_LO 300078 8 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - Out of service OPEN
G19.VALVE.PMV.ILOCK.LPHPPRS_UNK 300078 9 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - Out of service CLOSE
G19.VALVE.PMV.ILOCK.OOS_OPN 300078 10 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - Out of service OPEN
G19.VALVE.PMV.ILOCK.OOS_CLS 300078 11 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - Out of service CLOSE
G19.VALVE.PMV.ILOCK.CE_AMVPMV_OPN 300078 12 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - AMV and PMV are open - C&E 1a
G19.VALVE.PMV.ILOCK.CE_XOVPWV_OPN 300078 13 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - XOV and PWV are open - C&E 1B
G19.VALVE.PMV.ILOCK.CE_AMVXOV_OPN 300078 14 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - AMV and XOV are open - C&E 1C & 1D
G19.VALVE.PMV.ILOCK.CE_EQUALIZE 300078 15 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - Equalize before opening - C&E 4a
G19.VALVE.PMV.ILOCK.VALUE 300078 DWord RO 1000 G19 Well Production Master Valve Interlock Word
G19.VALVE.PMV.ILOCK.CE_PMVXOV_OPN 300079 0 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - PMV and XOV are open - C&E 1E
G19.VALVE.PMV.ILOCK.CE_PWVAMV_OPN 300079 1 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - PWV and AMV not closed - C&E 1F
G19.VALVE.PMV.ILOCK.CE_PCV_NOTCL 300079 2 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - PCV not closed - C&E 2
G19.VALVE.PMV.ILOCK.CE_PMVPWV_NOTCL 300079 3 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - PMV or PWV not closed - C&E 4b
G19.VALVE.PMV.ILOCK.CE_PWV_NOTCL 300079 4 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - PWV not closed - C&E 5
G19.VALVE.PMV.ILOCK.CE_XOV_OPN 300079 5 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - XOV open - C&E 8
G19.VALVE.PMV.ILOCK.CE_GLV_OPN 300079 6 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - GLV open - C&E 9
G19.VALVE.PMV.ILOCK.CE_PMVPWV_NOTCL1 300079 9 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - PMV or PWV not Closed - C&E 4b
G19.VALVE.PMV.ILOCK.CE_PWV_NOTCL1 300079 10 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - PWV not closed - C&E 6
G19.VALVE.PMV.ILOCK.CE_PCVPWV_NOTCL 300079 11 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - PCV and PWV not closed - C&E 7a
G19.VALVE.PMV.ILOCK.CE_PCVPMV_NOTCL 300079 12 Boolean RO 1000 G19 Well Production Master Valve Interlock Word - PCV and PMV not Closed - C&E 7b
G19.VALVE.PWV.STATUS.OPEN 300080 0 Boolean RO 1000 G19 WELL PRODUCTION WING VALVE STATUS WORD - IS OPEN
G19.VALVE.PWV.STATUS.CLOSED 300080 1 Boolean RO 1000 G19 WELL PRODUCTION WING VALVE STATUS WORD - IS CLOSED
G19.VALVE.PWV.STATUS.MOVING 300080 2 Boolean RO 1000 G19 WELL PRODUCTION WING VALVE STATUS WORD - IS MOVING
G19.VALVE.PWV.STATUS.ALM_DISC 300080 3 Boolean RO 1000 G19 WELL PRODUCTION WING VALVE STATUS WORD - DISCREPENCY
G19.VALVE.PWV.STATUS.ALM_FLTOMOV 300080 4 Boolean RO 1000 G19 WELL PRODUCTION WING VALVE STATUS WORD - FAILED TO OPEN
G19.VALVE.PWV.STATUS.ALM_FBIGNORE 300080 5 Boolean RO 1000 G19 WELL PRODUCTION WING VALVE STATUS WORD - FEEDBACK IS IGNORED
G19.VALVE.PWV.STATUS.OK_TO_OPN 300080 6 Boolean RO 1000 G19 WELL PRODUCTION WING VALVE STATUS WORD - OK TO OPEN
G19.VALVE.PWV.STATUS.OK_TO_CLS 300080 7 Boolean RO 1000 G19 WELL PRODUCTION WING VALVE STATUS WORD - OK TO CLOSE
G19.VALVE.PWV.STATUS.OPN_ILOCK_DFT 300080 8 Boolean RO 1000 G19 WELL PRODUCTION WING VALVE STATUS WORD - OPEN ILOCK DEFEATABLE
G19.VALVE.PWV.STATUS.CLS_ILOCK_DFT 300080 9 Boolean RO 1000 G19 WELL PRODUCTION WING VALVE STATUS WORD - CLOSE ILOCK DEFEATABLE
G19.VALVE.PWV.ILOCK.ROV_OPN 300081 0 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - ROV Override Open
G19.VALVE.PWV.ILOCK.ROV_CLSD 300081 1 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - ROV Override Closed
G19.VALVE.PWV.ILOCK.LPHDR_LO 300081 2 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - LP Header Low
G19.VALVE.PWV.ILOCK.LPHDR_UNK 300081 3 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - LP Header Unknown
G19.VALVE.PWV.ILOCK.LPHDR_OVR 300081 4 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - LP Header Override
G19.VALVE.PWV.ILOCK.HPHDR_LO 300081 5 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - HP Header Low
G19.VALVE.PWV.ILOCK.HPHDR_UNK 300081 6 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - HP Header Unkonwn
G19.VALVE.PWV.ILOCK.HPHDR_OVR 300081 7 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - HP Header Override
G19.VALVE.PWV.ILOCK.LPHPPRS_LO 300081 8 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - Out of service OPEN
G19.VALVE.PWV.ILOCK.LPHPPRS_UNK 300081 9 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - Out of service CLOSE
G19.VALVE.PWV.ILOCK.OOS_OPN 300081 10 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - Out of service OPEN
G19.VALVE.PWV.ILOCK.OOS_CLS 300081 11 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - Out of service CLOSE
G19.VALVE.PWV.ILOCK.CE_AMVPMV_OPN 300081 12 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - AMV and PMV are open - C&E 1a
G19.VALVE.PWV.ILOCK.CE_XOVPWV_OPN 300081 13 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - XOV and PWV are open - C&E 1B
G19.VALVE.PWV.ILOCK.CE_AMVXOV_OPN 300081 14 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - AMV and XOV are open - C&E 1C & 1D
G19.VALVE.PWV.ILOCK.CE_EQUALIZE 300081 15 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - Equalize before opening - C&E 4a
G19.VALVE.PWV.ILOCK.VALUE 300081 DWord RO 1000 G19 Well Production Wing Valve Interlock Word
G19.VALVE.PWV.ILOCK.CE_PMVXOV_OPN 300082 0 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - PMV and XOV are open - C&E 1E
G19.VALVE.PWV.ILOCK.CE_PWVAMV_OPN 300082 1 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - PWV and AMV not closed - C&E 1F
G19.VALVE.PWV.ILOCK.CE_PCV_NOTCL 300082 2 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - PCV not closed - C&E 2
G19.VALVE.PWV.ILOCK.CE_PMVPWV_NOTCL 300082 3 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - PMV or PWV not closed - C&E 4b
G19.VALVE.PWV.ILOCK.CE_PWV_NOTCL 300082 4 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - PWV not closed - C&E 5
G19.VALVE.PWV.ILOCK.CE_XOV_OPN 300082 5 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - XOV open - C&E 8

Page 12 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx G19 19/04/2024

Validation Date Tag Name Address Data Type Client Access Scan Rate Description
G19.VALVE.PWV.ILOCK.CE_GLV_OPN 300082 6 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - GLV open - C&E 9
G19.VALVE.PWV.ILOCK.CE_PMVPWV_NOTCL1 300082 9 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - PMV or PWV not Closed - C&E 4b
G19.VALVE.PWV.ILOCK.CE_PWV_NOTCL1 300082 10 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - PWV not closed - C&E 6
G19.VALVE.PWV.ILOCK.CE_PCVPWV_NOTCL 300082 11 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - PCV and PWV not closed - C&E 7a
G19.VALVE.PWV.ILOCK.CE_PCVPMV_NOTCL 300082 12 Boolean RO 1000 G19 Well Production Wing Valve Interlock Word - PCV and PMV not Closed - C&E 7b
G19.VALVE.SCSSV.STATUS.OPEN 300083 0 Boolean RO 1000 G19 WELL DOWNHOLE SAFETY VALVE (SCSSV) STATUS WORD - IS OPEN
G19.VALVE.SCSSV.STATUS.CLOSED 300083 1 Boolean RO 1000 G19 WELL DOWNHOLE SAFETY VALVE (SCSSV) STATUS WORD - IS CLOSED
G19.VALVE.SCSSV.STATUS.MOVING 300083 2 Boolean RO 1000 G19 WELL DOWNHOLE SAFETY VALVE (SCSSV) STATUS WORD - IS MOVING
G19.VALVE.SCSSV.STATUS.ALM_DISC 300083 3 Boolean RO 1000 G19 WELL DOWNHOLE SAFETY VALVE (SCSSV) STATUS WORD - DISCREPENCY
G19.VALVE.SCSSV.STATUS.ALM_FLTOMOV 300083 4 Boolean RO 1000 G19 WELL DOWNHOLE SAFETY VALVE (SCSSV) STATUS WORD - FAILED TO OPEN
G19.VALVE.SCSSV.STATUS.ALM_FBIGNORE 300083 5 Boolean RO 1000 G19 WELL DOWNHOLE SAFETY VALVE (SCSSV) STATUS WORD - FEEDBACK IS IGNORED
G19.VALVE.SCSSV.STATUS.OK_TO_OPN 300083 6 Boolean RO 1000 G19 WELL DOWNHOLE SAFETY VALVE (SCSSV) STATUS WORD - OK TO OPEN
G19.VALVE.SCSSV.STATUS.OK_TO_CLS 300083 7 Boolean RO 1000 G19 WELL DOWNHOLE SAFETY VALVE (SCSSV) STATUS WORD - OK TO CLOSE
G19.VALVE.SCSSV.STATUS.OPN_ILOCK_DFT 300083 8 Boolean RO 1000 G19 WELL DOWNHOLE SAFETY VALVE (SCSSV) STATUS WORD - OPEN ILOCK DEFEATABLE
G19.VALVE.SCSSV.STATUS.CLS_ILOCK_DFT 300083 9 Boolean RO 1000 G19 WELL DOWNHOLE SAFETY VALVE (SCSSV) STATUS WORD - CLOSE ILOCK DEFEATABLE
G19.VALVE.SCSSV.ILOCK.ROV_OPN 300084 0 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - ROV Override Open
G19.VALVE.SCSSV.ILOCK.ROV_CLSD 300084 1 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - ROV Override Closed
G19.VALVE.SCSSV.ILOCK.LPHDR_LO 300084 2 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - LP Header Low
G19.VALVE.SCSSV.ILOCK.LPHDR_UNK 300084 3 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - LP Header Unknown
G19.VALVE.SCSSV.ILOCK.LPHDR_OVR 300084 4 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - LP Header Override
G19.VALVE.SCSSV.ILOCK.HPHDR_LO 300084 5 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - HP Header Low
G19.VALVE.SCSSV.ILOCK.HPHDR_UNK 300084 6 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - HP Header Unkonwn
G19.VALVE.SCSSV.ILOCK.HPHDR_OVR 300084 7 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - HP Header Override
G19.VALVE.SCSSV.ILOCK.LPHPPRS_LO 300084 8 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - Out of service OPEN
G19.VALVE.SCSSV.ILOCK.LPHPPRS_UNK 300084 9 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - Out of service CLOSE
G19.VALVE.SCSSV.ILOCK.OOS_OPN 300084 10 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - Out of service OPEN
G19.VALVE.SCSSV.ILOCK.OOS_CLS 300084 11 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - Out of service CLOSE
G19.VALVE.SCSSV.ILOCK.CE_AMVPMV_OPN 300084 12 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - AMV and PMV are open - C&E 1a
G19.VALVE.SCSSV.ILOCK.CE_XOVPWV_OPN 300084 13 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - XOV and PWV are open - C&E 1B
G19.VALVE.SCSSV.ILOCK.CE_AMVXOV_OPN 300084 14 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - AMV and XOV are open - C&E 1C & 1D
G19.VALVE.SCSSV.ILOCK.CE_EQUALIZE 300084 15 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - Equalize before opening - C&E 4a
G19.VALVE.SCSSV.ILOCK.VALUE 300084 DWord RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word
G19.VALVE.SCSSV.ILOCK.CE_PMVXOV_OPN 300085 0 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - PMV and XOV are open - C&E 1E
G19.VALVE.SCSSV.ILOCK.CE_PWVAMV_OPN 300085 1 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - PWV and AMV not closed - C&E 1F
G19.VALVE.SCSSV.ILOCK.CE_PCV_NOTCL 300085 2 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - PCV not closed - C&E 2
G19.VALVE.SCSSV.ILOCK.CE_PMVPWV_NOTCL 300085 3 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - PMV or PWV not closed - C&E 4b
G19.VALVE.SCSSV.ILOCK.CE_PWV_NOTCL 300085 4 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - PWV not closed - C&E 5
G19.VALVE.SCSSV.ILOCK.CE_XOV_OPN 300085 5 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - XOV open - C&E 8
G19.VALVE.SCSSV.ILOCK.CE_GLV_OPN 300085 6 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - GLV open - C&E 9
G19.VALVE.SCSSV.ILOCK.CE_PMVPWV_NOTCL1 300085 9 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - PMV or PWV not Closed - C&E 4b
G19.VALVE.SCSSV.ILOCK.CE_PWV_NOTCL1 300085 10 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - PWV not closed - C&E 6
G19.VALVE.SCSSV.ILOCK.CE_PCVPWV_NOTCL 300085 11 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - PCV and PWV not closed - C&E 7a
G19.VALVE.SCSSV.ILOCK.CE_PCVPMV_NOTCL 300085 12 Boolean RO 1000 G19 Well Downhole Safety Valve (SCSSV) Interlock Word - PCV and PMV not Closed - C&E 7b
G19.VALVE.XOV.STATUS.OPEN 300086 0 Boolean RO 1000 G19 WELL CROSSOVER VALVE STATUS WORD - IS OPEN
G19.VALVE.XOV.STATUS.CLOSED 300086 1 Boolean RO 1000 G19 WELL CROSSOVER VALVE STATUS WORD - IS CLOSED
G19.VALVE.XOV.STATUS.MOVING 300086 2 Boolean RO 1000 G19 WELL CROSSOVER VALVE STATUS WORD - IS MOVING
G19.VALVE.XOV.STATUS.ALM_DISC 300086 3 Boolean RO 1000 G19 WELL CROSSOVER VALVE STATUS WORD - DISCREPENCY
G19.VALVE.XOV.STATUS.ALM_FLTOMOV 300086 4 Boolean RO 1000 G19 WELL CROSSOVER VALVE STATUS WORD - FAILED TO OPEN
G19.VALVE.XOV.STATUS.ALM_FBIGNORE 300086 5 Boolean RO 1000 G19 WELL CROSSOVER VALVE STATUS WORD - FEEDBACK IS IGNORED
G19.VALVE.XOV.STATUS.OK_TO_OPN 300086 6 Boolean RO 1000 G19 WELL CROSSOVER VALVE STATUS WORD - OK TO OPEN
G19.VALVE.XOV.STATUS.OK_TO_CLS 300086 7 Boolean RO 1000 G19 WELL CROSSOVER VALVE STATUS WORD - OK TO CLOSE
G19.VALVE.XOV.STATUS.OPN_ILOCK_DFT 300086 8 Boolean RO 1000 G19 WELL CROSSOVER VALVE STATUS WORD - OPEN ILOCK DEFEATABLE
G19.VALVE.XOV.STATUS.CLS_ILOCK_DFT 300086 9 Boolean RO 1000 G19 WELL CROSSOVER VALVE STATUS WORD - CLOSE ILOCK DEFEATABLE
G19.VALVE.XOV.ILOCK.ROV_OPN 300087 0 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - ROV Override Open
G19.VALVE.XOV.ILOCK.ROV_CLSD 300087 1 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - ROV Override Closed
G19.VALVE.XOV.ILOCK.LPHDR_LO 300087 2 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - LP Header Low
G19.VALVE.XOV.ILOCK.LPHDR_UNK 300087 3 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - LP Header Unknown
G19.VALVE.XOV.ILOCK.LPHDR_OVR 300087 4 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - LP Header Override

Page 13 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx G19 19/04/2024

Validation Date Tag Name Address Data Type Client Access Scan Rate Description
G19.VALVE.XOV.ILOCK.HPHDR_LO 300087 5 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - HP Header Low
G19.VALVE.XOV.ILOCK.HPHDR_UNK 300087 6 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - HP Header Unkonwn
G19.VALVE.XOV.ILOCK.HPHDR_OVR 300087 7 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - HP Header Override
G19.VALVE.XOV.ILOCK.LPHPPRS_LO 300087 8 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - Out of service OPEN
G19.VALVE.XOV.ILOCK.LPHPPRS_UNK 300087 9 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - Out of service CLOSE
G19.VALVE.XOV.ILOCK.OOS_OPN 300087 10 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - Out of service OPEN
G19.VALVE.XOV.ILOCK.OOS_CLS 300087 11 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - Out of service CLOSE
G19.VALVE.XOV.ILOCK.CE_AMVPMV_OPN 300087 12 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - AMV and PMV are open - C&E 1a
G19.VALVE.XOV.ILOCK.CE_XOVPWV_OPN 300087 13 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - XOV and PWV are open - C&E 1B
G19.VALVE.XOV.ILOCK.CE_AMVXOV_OPN 300087 14 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - AMV and XOV are open - C&E 1C & 1D
G19.VALVE.XOV.ILOCK.CE_EQUALIZE 300087 15 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - Equalize before opening - C&E 4a
G19.VALVE.XOV.ILOCK.VALUE 300087 DWord RO 1000 G19 Well Crossover Valve Interlock Word
G19.VALVE.XOV.ILOCK.CE_PMVXOV_OPN 300088 0 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - PMV and XOV are open - C&E 1E
G19.VALVE.XOV.ILOCK.CE_PWVAMV_OPN 300088 1 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - PWV and AMV not closed - C&E 1F
G19.VALVE.XOV.ILOCK.CE_PCV_NOTCL 300088 2 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - PCV not closed - C&E 2
G19.VALVE.XOV.ILOCK.CE_PMVPWV_NOTCL 300088 3 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - PMV or PWV not closed - C&E 4b
G19.VALVE.XOV.ILOCK.CE_PWV_NOTCL 300088 4 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - PWV not closed - C&E 5
G19.VALVE.XOV.ILOCK.CE_XOV_OPN 300088 5 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - XOV open - C&E 8
G19.VALVE.XOV.ILOCK.CE_GLV_OPN 300088 6 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - GLV open - C&E 9
G19.VALVE.XOV.ILOCK.CE_PMVPWV_NOTCL1 300088 9 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - PMV or PWV not Closed - C&E 4b
G19.VALVE.XOV.ILOCK.CE_PWV_NOTCL1 300088 10 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - PWV not closed - C&E 6
G19.VALVE.XOV.ILOCK.CE_PCVPWV_NOTCL 300088 11 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - PCV and PWV not closed - C&E 7a
G19.VALVE.XOV.ILOCK.CE_PCVPMV_NOTCL 300088 12 Boolean RO 1000 G19 Well Crossover Valve Interlock Word - PCV and PMV not Closed - C&E 7b
G19.VALVE.AMON.STATUS.OPEN 300089 0 Boolean RO 1000 G19 WELL ANNULUS MONITOR VALVE STATUS WORD - IS OPEN
G19.VALVE.AMON.STATUS.CLOSED 300089 1 Boolean RO 1000 G19 WELL ANNULUS MONITOR VALVE STATUS WORD - IS CLOSED
G19.VALVE.AMON.STATUS.MOVING 300089 2 Boolean RO 1000 G19 WELL ANNULUS MONITOR VALVE STATUS WORD - IS MOVING
G19.VALVE.AMON.STATUS.ALM_DISC 300089 3 Boolean RO 1000 G19 WELL ANNULUS MONITOR VALVE STATUS WORD - DISCREPENCY
G19.VALVE.AMON.STATUS.ALM_FLTOMOV 300089 4 Boolean RO 1000 G19 WELL ANNULUS MONITOR VALVE STATUS WORD - FAILED TO OPEN
G19.VALVE.AMON.STATUS.ALM_FBIGNORE 300089 5 Boolean RO 1000 G19 WELL ANNULUS MONITOR VALVE STATUS WORD - FEEDBACK IS IGNORED
G19.VALVE.AMON.STATUS.OK_TO_OPN 300089 6 Boolean RO 1000 G19 WELL ANNULUS MONITOR VALVE STATUS WORD - OK TO OPEN
G19.VALVE.AMON.STATUS.OK_TO_CLS 300089 7 Boolean RO 1000 G19 WELL ANNULUS MONITOR VALVE STATUS WORD - OK TO CLOSE
G19.VALVE.AMON.STATUS.OPN_ILOCK_DFT 300089 8 Boolean RO 1000 G19 WELL ANNULUS MONITOR VALVE STATUS WORD - OPEN ILOCK DEFEATABLE
G19.VALVE.AMON.STATUS.CLS_ILOCK_DFT 300089 9 Boolean RO 1000 G19 WELL ANNULUS MONITOR VALVE STATUS WORD - CLOSE ILOCK DEFEATABLE
G19.VALVE.AMON.ILOCK.ROV_OPN 300090 0 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - ROV Override Open
G19.VALVE.AMON.ILOCK.ROV_CLSD 300090 1 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - ROV Override Closed
G19.VALVE.AMON.ILOCK.LPHDR_LO 300090 2 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - LP Header Low
G19.VALVE.AMON.ILOCK.LPHDR_UNK 300090 3 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - LP Header Unknown
G19.VALVE.AMON.ILOCK.LPHDR_OVR 300090 4 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - LP Header Override
G19.VALVE.AMON.ILOCK.HPHDR_LO 300090 5 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - HP Header Low
G19.VALVE.AMON.ILOCK.HPHDR_UNK 300090 6 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - HP Header Unkonwn
G19.VALVE.AMON.ILOCK.HPHDR_OVR 300090 7 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - HP Header Override
G19.VALVE.AMON.ILOCK.LPHPPRS_LO 300090 8 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - Out of service OPEN
G19.VALVE.AMON.ILOCK.LPHPPRS_UNK 300090 9 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - Out of service CLOSE
G19.VALVE.AMON.ILOCK.OOS_OPN 300090 10 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - Out of service OPEN
G19.VALVE.AMON.ILOCK.OOS_CLS 300090 11 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - Out of service CLOSE
G19.VALVE.AMON.ILOCK.CE_AMVPMV_OPN 300090 12 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - AMV and PMV are open - C&E 1a
G19.VALVE.AMON.ILOCK.CE_XOVPWV_OPN 300090 13 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - XOV and PWV are open - C&E 1B
G19.VALVE.AMON.ILOCK.CE_AMVXOV_OPN 300090 14 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - AMV and XOV are open - C&E 1C & 1D
G19.VALVE.AMON.ILOCK.CE_EQUALIZE 300090 15 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - Equalize before opening - C&E 4a
G19.VALVE.AMON.ILOCK.VALUE 300090 DWord RO 1000 G19 Well Annulus Monitor Valve Interlock Word
G19.VALVE.AMON.ILOCK.CE_PMVXOV_OPN 300091 0 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - PMV and XOV are open - C&E 1E
G19.VALVE.AMON.ILOCK.CE_PWVAMV_OPN 300091 1 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - PWV and AMV not closed - C&E 1F
G19.VALVE.AMON.ILOCK.CE_PCV_NOTCL 300091 2 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - PCV not closed - C&E 2
G19.VALVE.AMON.ILOCK.CE_PMVPWV_NOTCL 300091 3 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - PMV or PWV not closed - C&E 4b
G19.VALVE.AMON.ILOCK.CE_PWV_NOTCL 300091 4 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - PWV not closed - C&E 5
G19.VALVE.AMON.ILOCK.CE_XOV_OPN 300091 5 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - XOV open - C&E 8
G19.VALVE.AMON.ILOCK.CE_GLV_OPN 300091 6 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - GLV open - C&E 9
G19.VALVE.AMON.ILOCK.CE_PMVPWV_NOTCL1 300091 9 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - PMV or PWV not Closed - C&E 4b

Page 14 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx G19 19/04/2024

Validation Date Tag Name Address Data Type Client Access Scan Rate Description
G19.VALVE.AMON.ILOCK.CE_PWV_NOTCL1 300091 10 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - PWV not closed - C&E 6
G19.VALVE.AMON.ILOCK.CE_PCVPWV_NOTCL 300091 11 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - PCV and PWV not closed - C&E 7a
G19.VALVE.AMON.ILOCK.CE_PCVPMV_NOTCL 300091 12 Boolean RO 1000 G19 Well Annulus Monitor Valve Interlock Word - PCV and PMV not Closed - C&E 7b
G19.VALVE.CIV.STATUS.OPEN 300092 0 Boolean RO 1000 G19 WELL CHEMICAL INJECTION VALVE STATUS WORD - IS OPEN
G19.VALVE.CIV.STATUS.CLOSED 300092 1 Boolean RO 1000 G19 WELL CHEMICAL INJECTION VALVE STATUS WORD - IS CLOSED
G19.VALVE.CIV.STATUS.MOVING 300092 2 Boolean RO 1000 G19 WELL CHEMICAL INJECTION VALVE STATUS WORD - IS MOVING
G19.VALVE.CIV.STATUS.ALM_DISC 300092 3 Boolean RO 1000 G19 WELL CHEMICAL INJECTION VALVE STATUS WORD - DISCREPENCY
G19.VALVE.CIV.STATUS.ALM_FLTOMOV 300092 4 Boolean RO 1000 G19 WELL CHEMICAL INJECTION VALVE STATUS WORD - FAILED TO OPEN
G19.VALVE.CIV.STATUS.ALM_FBIGNORE 300092 5 Boolean RO 1000 G19 WELL CHEMICAL INJECTION VALVE STATUS WORD - FEEDBACK IS IGNORED
G19.VALVE.CIV.STATUS.OK_TO_OPN 300092 6 Boolean RO 1000 G19 WELL CHEMICAL INJECTION VALVE STATUS WORD - OK TO OPEN
G19.VALVE.CIV.STATUS.OK_TO_CLS 300092 7 Boolean RO 1000 G19 WELL CHEMICAL INJECTION VALVE STATUS WORD - OK TO CLOSE
G19.VALVE.CIV.STATUS.OPN_ILOCK_DFT 300092 8 Boolean RO 1000 G19 WELL CHEMICAL INJECTION VALVE STATUS WORD - OPEN ILOCK DEFEATABLE
G19.VALVE.CIV.STATUS.CLS_ILOCK_DFT 300092 9 Boolean RO 1000 G19 WELL CHEMICAL INJECTION VALVE STATUS WORD - CLOSE ILOCK DEFEATABLE
G19.VALVE.CIV.ILOCK.ROV_OPN 300093 0 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - ROV Override Open
G19.VALVE.CIV.ILOCK.ROV_CLSD 300093 1 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - ROV Override Closed
G19.VALVE.CIV.ILOCK.LPHDR_LO 300093 2 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - LP Header Low
G19.VALVE.CIV.ILOCK.LPHDR_UNK 300093 3 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - LP Header Unknown
G19.VALVE.CIV.ILOCK.LPHDR_OVR 300093 4 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - LP Header Override
G19.VALVE.CIV.ILOCK.HPHDR_LO 300093 5 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - HP Header Low
G19.VALVE.CIV.ILOCK.HPHDR_UNK 300093 6 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - HP Header Unkonwn
G19.VALVE.CIV.ILOCK.HPHDR_OVR 300093 7 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - HP Header Override
G19.VALVE.CIV.ILOCK.LPHPPRS_LO 300093 8 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - Out of service OPEN
G19.VALVE.CIV.ILOCK.LPHPPRS_UNK 300093 9 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - Out of service CLOSE
G19.VALVE.CIV.ILOCK.OOS_OPN 300093 10 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - Out of service OPEN
G19.VALVE.CIV.ILOCK.OOS_CLS 300093 11 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - Out of service CLOSE
G19.VALVE.CIV.ILOCK.CE_AMVPMV_OPN 300093 12 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - AMV and PMV are open - C&E 1a
G19.VALVE.CIV.ILOCK.CE_XOVPWV_OPN 300093 13 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - XOV and PWV are open - C&E 1B
G19.VALVE.CIV.ILOCK.CE_AMVXOV_OPN 300093 14 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - AMV and XOV are open - C&E 1C & 1D
G19.VALVE.CIV.ILOCK.CE_EQUALIZE 300093 15 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - Equalize before opening - C&E 4a
G19.VALVE.CIV.ILOCK.VALUE 300093 DWord RO 1000 G19 Well Chemical Injection Valve Interlock Word
G19.VALVE.CIV.ILOCK.CE_PMVXOV_OPN 300094 0 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - PMV and XOV are open - C&E 1E
G19.VALVE.CIV.ILOCK.CE_PWVAMV_OPN 300094 1 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - PWV and AMV not closed - C&E 1F
G19.VALVE.CIV.ILOCK.CE_PCV_NOTCL 300094 2 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - PCV not closed - C&E 2
G19.VALVE.CIV.ILOCK.CE_PMVPWV_NOTCL 300094 3 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - PMV or PWV not closed - C&E 4b
G19.VALVE.CIV.ILOCK.CE_PWV_NOTCL 300094 4 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - PWV not closed - C&E 5
G19.VALVE.CIV.ILOCK.CE_XOV_OPN 300094 5 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - XOV open - C&E 8
G19.VALVE.CIV.ILOCK.CE_GLV_OPN 300094 6 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - GLV open - C&E 9
G19.VALVE.CIV.ILOCK.CE_PMVPWV_NOTCL1 300094 9 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - PMV or PWV not Closed - C&E 4b
G19.VALVE.CIV.ILOCK.CE_PWV_NOTCL1 300094 10 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - PWV not closed - C&E 6
G19.VALVE.CIV.ILOCK.CE_PCVPWV_NOTCL 300094 11 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - PCV and PWV not closed - C&E 7a
G19.VALVE.CIV.ILOCK.CE_PCVPMV_NOTCL 300094 12 Boolean RO 1000 G19 Well Chemical Injection Valve Interlock Word - PCV and PMV not Closed - C&E 7b
G19.VALVE.DHCV1.STATUS.OPEN 300095 0 Boolean RO 1000 G19 WELL DOWNHOLE CHEMICAL INJECTION VALVE #1 STATUS WORD - IS OPEN
G19.VALVE.DHCV1.STATUS.CLOSED 300095 1 Boolean RO 1000 G19 WELL DOWNHOLE CHEMICAL INJECTION VALVE #1 STATUS WORD - IS CLOSED
G19.VALVE.DHCV1.STATUS.MOVING 300095 2 Boolean RO 1000 G19 WELL DOWNHOLE CHEMICAL INJECTION VALVE #1 STATUS WORD - IS MOVING
G19.VALVE.DHCV1.STATUS.ALM_DISC 300095 3 Boolean RO 1000 G19 WELL DOWNHOLE CHEMICAL INJECTION VALVE #1 STATUS WORD - DISCREPENCY
G19.VALVE.DHCV1.STATUS.ALM_FLTOMOV 300095 4 Boolean RO 1000 G19 WELL DOWNHOLE CHEMICAL INJECTION VALVE #1 STATUS WORD - FAILED TO OPEN
G19.VALVE.DHCV1.STATUS.ALM_FBIGNORE 300095 5 Boolean RO 1000 G19 WELL DOWNHOLE CHEMICAL INJECTION VALVE #1 STATUS WORD - FEEDBACK IS IGNORED
G19.VALVE.DHCV1.STATUS.OK_TO_OPN 300095 6 Boolean RO 1000 G19 WELL DOWNHOLE CHEMICAL INJECTION VALVE #1 STATUS WORD - OK TO OPEN
G19.VALVE.DHCV1.STATUS.OK_TO_CLS 300095 7 Boolean RO 1000 G19 WELL DOWNHOLE CHEMICAL INJECTION VALVE #1 STATUS WORD - OK TO CLOSE
G19.VALVE.DHCV1.STATUS.OPN_ILOCK_DFT 300095 8 Boolean RO 1000 G19 WELL DOWNHOLE CHEMICAL INJECTION VALVE #1 STATUS WORD - OPEN ILOCK DEFEATABLE
G19.VALVE.DHCV1.STATUS.CLS_ILOCK_DFT 300095 9 Boolean RO 1000 G19 WELL DOWNHOLE CHEMICAL INJECTION VALVE #1 STATUS WORD - CLOSE ILOCK DEFEATABLE
G19.VALVE.DHCV1.ILOCK.ROV_OPN 300096 0 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - ROV Override Open
G19.VALVE.DHCV1.ILOCK.ROV_CLSD 300096 1 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - ROV Override Closed
G19.VALVE.DHCV1.ILOCK.LPHDR_LO 300096 2 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - LP Header Low
G19.VALVE.DHCV1.ILOCK.LPHDR_UNK 300096 3 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - LP Header Unknown
G19.VALVE.DHCV1.ILOCK.LPHDR_OVR 300096 4 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - LP Header Override
G19.VALVE.DHCV1.ILOCK.HPHDR_LO 300096 5 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - HP Header Low
G19.VALVE.DHCV1.ILOCK.HPHDR_UNK 300096 6 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - HP Header Unkonwn

Page 15 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx G19 19/04/2024

Validation Date Tag Name Address Data Type Client Access Scan Rate Description
G19.VALVE.DHCV1.ILOCK.HPHDR_OVR 300096 7 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - HP Header Override
G19.VALVE.DHCV1.ILOCK.LPHPPRS_LO 300096 8 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - Out of service OPEN
G19.VALVE.DHCV1.ILOCK.LPHPPRS_UNK 300096 9 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - Out of service CLOSE
G19.VALVE.DHCV1.ILOCK.OOS_OPN 300096 10 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - Out of service OPEN
G19.VALVE.DHCV1.ILOCK.OOS_CLS 300096 11 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - Out of service CLOSE
G19.VALVE.DHCV1.ILOCK.CE_AMVPMV_OPN 300096 12 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - AMV and PMV are open - C&E 1a
G19.VALVE.DHCV1.ILOCK.CE_XOVPWV_OPN 300096 13 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - XOV and PWV are open - C&E 1B
G19.VALVE.DHCV1.ILOCK.CE_AMVXOV_OPN 300096 14 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - AMV and XOV are open - C&E 1C & 1D
G19.VALVE.DHCV1.ILOCK.CE_EQUALIZE 300096 15 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - Equalize before opening - C&E 4a
G19.VALVE.DHCV1.ILOCK.VALUE 300096 DWord RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word
G19.VALVE.DHCV1.ILOCK.CE_PMVXOV_OPN 300097 0 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - PMV and XOV are open - C&E 1E
G19.VALVE.DHCV1.ILOCK.CE_PWVAMV_OPN 300097 1 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - PWV and AMV not closed - C&E 1F
G19.VALVE.DHCV1.ILOCK.CE_PCV_NOTCL 300097 2 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - PCV not closed - C&E 2
G19.VALVE.DHCV1.ILOCK.CE_PMVPWV_NOTCL 300097 3 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - PMV or PWV not closed - C&E 4b
G19.VALVE.DHCV1.ILOCK.CE_PWV_NOTCL 300097 4 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - PWV not closed - C&E 5
G19.VALVE.DHCV1.ILOCK.CE_XOV_OPN 300097 5 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - XOV open - C&E 8
G19.VALVE.DHCV1.ILOCK.CE_GLV_OPN 300097 6 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - GLV open - C&E 9
G19.VALVE.DHCV1.ILOCK.CE_PMVPWV_NOTCL1 300097 9 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - PMV or PWV not Closed - C&E 4b
G19.VALVE.DHCV1.ILOCK.CE_PWV_NOTCL1 300097 10 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - PWV not closed - C&E 6
G19.VALVE.DHCV1.ILOCK.CE_PCVPWV_NOTCL 300097 11 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - PCV and PWV not closed - C&E 7a
G19.VALVE.DHCV1.ILOCK.CE_PCVPMV_NOTCL 300097 12 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #1 Interlock Word - PCV and PMV not Closed - C&E 7b
G19.VALVE.DHCV2.STATUS.OPEN 300098 0 Boolean RO 1000 G19 WELL DOWNHOLE CHEMICAL INJECTION VALVE #2 STATUS WORD - IS OPEN
G19.VALVE.DHCV2.STATUS.CLOSED 300098 1 Boolean RO 1000 G19 WELL DOWNHOLE CHEMICAL INJECTION VALVE #2 STATUS WORD - IS CLOSED
G19.VALVE.DHCV2.STATUS.MOVING 300098 2 Boolean RO 1000 G19 WELL DOWNHOLE CHEMICAL INJECTION VALVE #2 STATUS WORD - IS MOVING
G19.VALVE.DHCV2.STATUS.ALM_DISC 300098 3 Boolean RO 1000 G19 WELL DOWNHOLE CHEMICAL INJECTION VALVE #2 STATUS WORD - DISCREPENCY
G19.VALVE.DHCV2.STATUS.ALM_FLTOMOV 300098 4 Boolean RO 1000 G19 WELL DOWNHOLE CHEMICAL INJECTION VALVE #2 STATUS WORD - FAILED TO OPEN
G19.VALVE.DHCV2.STATUS.ALM_FBIGNORE 300098 5 Boolean RO 1000 G19 WELL DOWNHOLE CHEMICAL INJECTION VALVE #2 STATUS WORD - FEEDBACK IS IGNORED
G19.VALVE.DHCV2.STATUS.OK_TO_OPN 300098 6 Boolean RO 1000 G19 WELL DOWNHOLE CHEMICAL INJECTION VALVE #2 STATUS WORD - OK TO OPEN
G19.VALVE.DHCV2.STATUS.OK_TO_CLS 300098 7 Boolean RO 1000 G19 WELL DOWNHOLE CHEMICAL INJECTION VALVE #2 STATUS WORD - OK TO CLOSE
G19.VALVE.DHCV2.STATUS.OPN_ILOCK_DFT 300098 8 Boolean RO 1000 G19 WELL DOWNHOLE CHEMICAL INJECTION VALVE #2 STATUS WORD - OPEN ILOCK DEFEATABLE
G19.VALVE.DHCV2.STATUS.CLS_ILOCK_DFT 300098 9 Boolean RO 1000 G19 WELL DOWNHOLE CHEMICAL INJECTION VALVE #2 STATUS WORD - CLOSE ILOCK DEFEATABLE
G19.VALVE.DHCV2.ILOCK.ROV_OPN 300099 0 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - ROV Override Open
G19.VALVE.DHCV2.ILOCK.ROV_CLSD 300099 1 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - ROV Override Closed
G19.VALVE.DHCV2.ILOCK.LPHDR_LO 300099 2 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - LP Header Low
G19.VALVE.DHCV2.ILOCK.LPHDR_UNK 300099 3 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - LP Header Unknown
G19.VALVE.DHCV2.ILOCK.LPHDR_OVR 300099 4 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - LP Header Override
G19.VALVE.DHCV2.ILOCK.HPHDR_LO 300099 5 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - HP Header Low
G19.VALVE.DHCV2.ILOCK.HPHDR_UNK 300099 6 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - HP Header Unkonwn
G19.VALVE.DHCV2.ILOCK.HPHDR_OVR 300099 7 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - HP Header Override
G19.VALVE.DHCV2.ILOCK.LPHPPRS_LO 300099 8 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - Out of service OPEN
G19.VALVE.DHCV2.ILOCK.LPHPPRS_UNK 300099 9 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - Out of service CLOSE
G19.VALVE.DHCV2.ILOCK.OOS_OPN 300099 10 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - Out of service OPEN
G19.VALVE.DHCV2.ILOCK.OOS_CLS 300099 11 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - Out of service CLOSE
G19.VALVE.DHCV2.ILOCK.CE_AMVPMV_OPN 300099 12 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - AMV and PMV are open - C&E 1a
G19.VALVE.DHCV2.ILOCK.CE_XOVPWV_OPN 300099 13 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - XOV and PWV are open - C&E 1B
G19.VALVE.DHCV2.ILOCK.CE_AMVXOV_OPN 300099 14 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - AMV and XOV are open - C&E 1C & 1D
G19.VALVE.DHCV2.ILOCK.CE_EQUALIZE 300099 15 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - Equalize before opening - C&E 4a
G19.VALVE.DHCV2.ILOCK.VALUE 300099 DWord RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word
G19.VALVE.DHCV2.ILOCK.CE_PMVXOV_OPN 300100 0 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - PMV and XOV are open - C&E 1E
G19.VALVE.DHCV2.ILOCK.CE_PWVAMV_OPN 300100 1 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - PWV and AMV not closed - C&E 1F
G19.VALVE.DHCV2.ILOCK.CE_PCV_NOTCL 300100 2 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - PCV not closed - C&E 2
G19.VALVE.DHCV2.ILOCK.CE_PMVPWV_NOTCL 300100 3 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - PMV or PWV not closed - C&E 4b
G19.VALVE.DHCV2.ILOCK.CE_PWV_NOTCL 300100 4 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - PWV not closed - C&E 5
G19.VALVE.DHCV2.ILOCK.CE_XOV_OPN 300100 5 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - XOV open - C&E 8
G19.VALVE.DHCV2.ILOCK.CE_GLV_OPN 300100 6 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - GLV open - C&E 9
G19.VALVE.DHCV2.ILOCK.CE_PMVPWV_NOTCL1 300100 9 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - PMV or PWV not Closed - C&E 4b
G19.VALVE.DHCV2.ILOCK.CE_PWV_NOTCL1 300100 10 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - PWV not closed - C&E 6
G19.VALVE.DHCV2.ILOCK.CE_PCVPWV_NOTCL 300100 11 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - PCV and PWV not closed - C&E 7a

Page 16 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx G19 19/04/2024

Validation Date Tag Name Address Data Type Client Access Scan Rate Description
G19.VALVE.DHCV2.ILOCK.CE_PCVPMV_NOTCL 300100 12 Boolean RO 1000 G19 Well Downhole Chemical Injection Valve #2 Interlock Word - PCV and PMV not Closed - C&E 7b
G19.VALVE.MIV.STATUS.OPEN 300101 0 Boolean RO 1000 G19 WELL METHANOL INJECTION VALVE STATUS WORD - IS OPEN
G19.VALVE.MIV.STATUS.CLOSED 300101 1 Boolean RO 1000 G19 WELL METHANOL INJECTION VALVE STATUS WORD - IS CLOSED
G19.VALVE.MIV.STATUS.MOVING 300101 2 Boolean RO 1000 G19 WELL METHANOL INJECTION VALVE STATUS WORD - IS MOVING
G19.VALVE.MIV.STATUS.ALM_DISC 300101 3 Boolean RO 1000 G19 WELL METHANOL INJECTION VALVE STATUS WORD - DISCREPENCY
G19.VALVE.MIV.STATUS.ALM_FLTOMOV 300101 4 Boolean RO 1000 G19 WELL METHANOL INJECTION VALVE STATUS WORD - FAILED TO OPEN
G19.VALVE.MIV.STATUS.ALM_FBIGNORE 300101 5 Boolean RO 1000 G19 WELL METHANOL INJECTION VALVE STATUS WORD - FEEDBACK IS IGNORED
G19.VALVE.MIV.STATUS.OK_TO_OPN 300101 6 Boolean RO 1000 G19 WELL METHANOL INJECTION VALVE STATUS WORD - OK TO OPEN
G19.VALVE.MIV.STATUS.OK_TO_CLS 300101 7 Boolean RO 1000 G19 WELL METHANOL INJECTION VALVE STATUS WORD - OK TO CLOSE
G19.VALVE.MIV.STATUS.OPN_ILOCK_DFT 300101 8 Boolean RO 1000 G19 WELL METHANOL INJECTION VALVE STATUS WORD - OPEN ILOCK DEFEATABLE
G19.VALVE.MIV.STATUS.CLS_ILOCK_DFT 300101 9 Boolean RO 1000 G19 WELL METHANOL INJECTION VALVE STATUS WORD - CLOSE ILOCK DEFEATABLE
G19.VALVE.MIV.ILOCK.ROV_OPN 300102 0 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - ROV Override Open
G19.VALVE.MIV.ILOCK.ROV_CLSD 300102 1 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - ROV Override Closed
G19.VALVE.MIV.ILOCK.LPHDR_LO 300102 2 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - LP Header Low
G19.VALVE.MIV.ILOCK.LPHDR_UNK 300102 3 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - LP Header Unknown
G19.VALVE.MIV.ILOCK.LPHDR_OVR 300102 4 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - LP Header Override
G19.VALVE.MIV.ILOCK.HPHDR_LO 300102 5 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - HP Header Low
G19.VALVE.MIV.ILOCK.HPHDR_UNK 300102 6 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - HP Header Unkonwn
G19.VALVE.MIV.ILOCK.HPHDR_OVR 300102 7 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - HP Header Override
G19.VALVE.MIV.ILOCK.LPHPPRS_LO 300102 8 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - Out of service OPEN
G19.VALVE.MIV.ILOCK.LPHPPRS_UNK 300102 9 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - Out of service CLOSE
G19.VALVE.MIV.ILOCK.OOS_OPN 300102 10 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - Out of service OPEN
G19.VALVE.MIV.ILOCK.OOS_CLS 300102 11 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - Out of service CLOSE
G19.VALVE.MIV.ILOCK.CE_AMVPMV_OPN 300102 12 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - AMV and PMV are open - C&E 1a
G19.VALVE.MIV.ILOCK.CE_XOVPWV_OPN 300102 13 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - XOV and PWV are open - C&E 1B
G19.VALVE.MIV.ILOCK.CE_AMVXOV_OPN 300102 14 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - AMV and XOV are open - C&E 1C & 1D
G19.VALVE.MIV.ILOCK.CE_EQUALIZE 300102 15 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - Equalize before opening - C&E 4a
G19.VALVE.MIV.ILOCK.VALUE 300102 DWord RO 1000 G19 Well Methanol Injection Valve Interlock Word
G19.VALVE.MIV.ILOCK.CE_PMVXOV_OPN 300103 0 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - PMV and XOV are open - C&E 1E
G19.VALVE.MIV.ILOCK.CE_PWVAMV_OPN 300103 1 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - PWV and AMV not closed - C&E 1F
G19.VALVE.MIV.ILOCK.CE_PCV_NOTCL 300103 2 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - PCV not closed - C&E 2
G19.VALVE.MIV.ILOCK.CE_PMVPWV_NOTCL 300103 3 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - PMV or PWV not closed - C&E 4b
G19.VALVE.MIV.ILOCK.CE_PWV_NOTCL 300103 4 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - PWV not closed - C&E 5
G19.VALVE.MIV.ILOCK.CE_XOV_OPN 300103 5 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - XOV open - C&E 8
G19.VALVE.MIV.ILOCK.CE_GLV_OPN 300103 6 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - GLV open - C&E 9
G19.VALVE.MIV.ILOCK.CE_PMVPWV_NOTCL1 300103 9 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - PMV or PWV not Closed - C&E 4b
G19.VALVE.MIV.ILOCK.CE_PWV_NOTCL1 300103 10 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - PWV not closed - C&E 6
G19.VALVE.MIV.ILOCK.CE_PCVPWV_NOTCL 300103 11 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - PCV and PWV not closed - C&E 7a
G19.VALVE.MIV.ILOCK.CE_PCVPMV_NOTCL 300103 12 Boolean RO 1000 G19 Well Methanol Injection Valve Interlock Word - PCV and PMV not Closed - C&E 7b
G19.VALVE.PLET.STATUS.OPEN 300104 0 Boolean RO 1000 G19 WELL PLET VALVE STATUS WORD - IS OPEN
G19.VALVE.PLET.STATUS.CLOSED 300104 1 Boolean RO 1000 G19 WELL PLET VALVE STATUS WORD - IS CLOSED
G19.VALVE.PLET.STATUS.MOVING 300104 2 Boolean RO 1000 G19 WELL PLET VALVE STATUS WORD - IS MOVING
G19.VALVE.PLET.STATUS.ALM_DISC 300104 3 Boolean RO 1000 G19 WELL PLET VALVE STATUS WORD - DISCREPENCY
G19.VALVE.PLET.STATUS.ALM_FLTOMOV 300104 4 Boolean RO 1000 G19 WELL PLET VALVE STATUS WORD - FAILED TO OPEN
G19.VALVE.PLET.STATUS.ALM_FBIGNORE 300104 5 Boolean RO 1000 G19 WELL PLET VALVE STATUS WORD - FEEDBACK IS IGNORED
G19.VALVE.PLET.STATUS.OK_TO_OPN 300104 6 Boolean RO 1000 G19 WELL PLET VALVE STATUS WORD - OK TO OPEN
G19.VALVE.PLET.STATUS.OK_TO_CLS 300104 7 Boolean RO 1000 G19 WELL PLET VALVE STATUS WORD - OK TO CLOSE
G19.VALVE.PLET.STATUS.OPN_ILOCK_DFT 300104 8 Boolean RO 1000 G19 WELL PLET VALVE STATUS WORD - OPEN ILOCK DEFEATABLE
G19.VALVE.PLET.STATUS.CLS_ILOCK_DFT 300104 9 Boolean RO 1000 G19 WELL PLET VALVE STATUS WORD - CLOSE ILOCK DEFEATABLE
G19.VALVE.PLET.ILOCK.ROV_OPN 300105 0 Boolean RO 1000 G19 Well PLET Valve Interlock Word - ROV Override Open
G19.VALVE.PLET.ILOCK.ROV_CLSD 300105 1 Boolean RO 1000 G19 Well PLET Valve Interlock Word - ROV Override Closed
G19.VALVE.PLET.ILOCK.LPHDR_LO 300105 2 Boolean RO 1000 G19 Well PLET Valve Interlock Word - LP Header Low
G19.VALVE.PLET.ILOCK.LPHDR_UNK 300105 3 Boolean RO 1000 G19 Well PLET Valve Interlock Word - LP Header Unknown
G19.VALVE.PLET.ILOCK.LPHDR_OVR 300105 4 Boolean RO 1000 G19 Well PLET Valve Interlock Word - LP Header Override
G19.VALVE.PLET.ILOCK.HPHDR_LO 300105 5 Boolean RO 1000 G19 Well PLET Valve Interlock Word - HP Header Low
G19.VALVE.PLET.ILOCK.HPHDR_UNK 300105 6 Boolean RO 1000 G19 Well PLET Valve Interlock Word - HP Header Unkonwn
G19.VALVE.PLET.ILOCK.HPHDR_OVR 300105 7 Boolean RO 1000 G19 Well PLET Valve Interlock Word - HP Header Override
G19.VALVE.PLET.ILOCK.LPHPPRS_LO 300105 8 Boolean RO 1000 G19 Well PLET Valve Interlock Word - Out of service OPEN

Page 17 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx G19 19/04/2024

Validation Date Tag Name Address Data Type Client Access Scan Rate Description
G19.VALVE.PLET.ILOCK.LPHPPRS_UNK 300105 9 Boolean RO 1000 G19 Well PLET Valve Interlock Word - Out of service CLOSE
G19.VALVE.PLET.ILOCK.OOS_OPN 300105 10 Boolean RO 1000 G19 Well PLET Valve Interlock Word - Out of service OPEN
G19.VALVE.PLET.ILOCK.OOS_CLS 300105 11 Boolean RO 1000 G19 Well PLET Valve Interlock Word - Out of service CLOSE
G19.VALVE.PLET.ILOCK.CE_AMVPMV_OPN 300105 12 Boolean RO 1000 G19 Well PLET Valve Interlock Word - AMV and PMV are open - C&E 1a
G19.VALVE.PLET.ILOCK.CE_XOVPWV_OPN 300105 13 Boolean RO 1000 G19 Well PLET Valve Interlock Word - XOV and PWV are open - C&E 1B
G19.VALVE.PLET.ILOCK.CE_AMVXOV_OPN 300105 14 Boolean RO 1000 G19 Well PLET Valve Interlock Word - AMV and XOV are open - C&E 1C & 1D
G19.VALVE.PLET.ILOCK.CE_EQUALIZE 300105 15 Boolean RO 1000 G19 Well PLET Valve Interlock Word - Equalize before opening - C&E 4a
G19.VALVE.PLET.ILOCK.VALUE 300105 DWord RO 1000 G19 Well PLET Valve Interlock Word
G19.VALVE.PLET.ILOCK.CE_PMVXOV_OPN 300106 0 Boolean RO 1000 G19 Well PLET Valve Interlock Word - PMV and XOV are open - C&E 1E
G19.VALVE.PLET.ILOCK.CE_PWVAMV_OPN 300106 1 Boolean RO 1000 G19 Well PLET Valve Interlock Word - PWV and AMV not closed - C&E 1F
G19.VALVE.PLET.ILOCK.CE_PCV_NOTCL 300106 2 Boolean RO 1000 G19 Well PLET Valve Interlock Word - PCV not closed - C&E 2
G19.VALVE.PLET.ILOCK.CE_PMVPWV_NOTCL 300106 3 Boolean RO 1000 G19 Well PLET Valve Interlock Word - PMV or PWV not closed - C&E 4b
G19.VALVE.PLET.ILOCK.CE_PWV_NOTCL 300106 4 Boolean RO 1000 G19 Well PLET Valve Interlock Word - PWV not closed - C&E 5
G19.VALVE.PLET.ILOCK.CE_XOV_OPN 300106 5 Boolean RO 1000 G19 Well PLET Valve Interlock Word - XOV open - C&E 8
G19.VALVE.PLET.ILOCK.CE_GLV_OPN 300106 6 Boolean RO 1000 G19 Well PLET Valve Interlock Word - GLV open - C&E 9
G19.VALVE.PLET.ILOCK.CE_PMVPWV_NOTCL1 300106 9 Boolean RO 1000 G19 Well PLET Valve Interlock Word - PMV or PWV not Closed - C&E 4b
G19.VALVE.PLET.ILOCK.CE_PWV_NOTCL1 300106 10 Boolean RO 1000 G19 Well PLET Valve Interlock Word - PWV not closed - C&E 6
G19.VALVE.PLET.ILOCK.CE_PCVPWV_NOTCL 300106 11 Boolean RO 1000 G19 Well PLET Valve Interlock Word - PCV and PWV not closed - C&E 7a
G19.VALVE.PLET.ILOCK.CE_PCVPMV_NOTCL 300106 12 Boolean RO 1000 G19 Well PLET Valve Interlock Word - PCV and PMV not Closed - C&E 7b
G19.VALVE.SWV1.STATUS.OPEN 300107 0 Boolean RO 1000 G19 WELL SWC1 - UPPER SLEEVE STATUS WORD - IS OPEN
G19.VALVE.SWV1.STATUS.CLOSED 300107 1 Boolean RO 1000 G19 WELL SWC1 - UPPER SLEEVE STATUS WORD - IS CLOSED
G19.VALVE.SWV1.STATUS.MOVING 300107 2 Boolean RO 1000 G19 WELL SWC1 - UPPER SLEEVE STATUS WORD - IS MOVING
G19.VALVE.SWV1.STATUS.ALM_DISC 300107 3 Boolean RO 1000 G19 WELL SWC1 - UPPER SLEEVE STATUS WORD - DISCREPENCY
G19.VALVE.SWV1.STATUS.ALM_FLTOMOV 300107 4 Boolean RO 1000 G19 WELL SWC1 - UPPER SLEEVE STATUS WORD - FAILED TO OPEN
G19.VALVE.SWV1.STATUS.ALM_FBIGNORE 300107 5 Boolean RO 1000 G19 WELL SWC1 - UPPER SLEEVE STATUS WORD - FEEDBACK IS IGNORED
G19.VALVE.SWV1.STATUS.OK_TO_OPN 300107 6 Boolean RO 1000 G19 WELL SWC1 - UPPER SLEEVE STATUS WORD - OK TO OPEN
G19.VALVE.SWV1.STATUS.OK_TO_CLS 300107 7 Boolean RO 1000 G19 WELL SWC1 - UPPER SLEEVE STATUS WORD - OK TO CLOSE
G19.VALVE.SWV1.STATUS.OPN_ILOCK_DFT 300107 8 Boolean RO 1000 G19 WELL SWC1 - UPPER SLEEVE STATUS WORD - OPEN ILOCK DEFEATABLE
G19.VALVE.SWV1.STATUS.CLS_ILOCK_DFT 300107 9 Boolean RO 1000 G19 WELL SWC1 - UPPER SLEEVE STATUS WORD - CLOSE ILOCK DEFEATABLE
G19.VALVE.SWV1.ILOCK.ROV_OPN 300108 0 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - ROV Override Open
G19.VALVE.SWV1.ILOCK.ROV_CLSD 300108 1 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - ROV Override Closed
G19.VALVE.SWV1.ILOCK.LPHDR_LO 300108 2 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - LP Header Low
G19.VALVE.SWV1.ILOCK.LPHDR_UNK 300108 3 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - LP Header Unknown
G19.VALVE.SWV1.ILOCK.LPHDR_OVR 300108 4 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - LP Header Override
G19.VALVE.SWV1.ILOCK.HPHDR_LO 300108 5 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - HP Header Low
G19.VALVE.SWV1.ILOCK.HPHDR_UNK 300108 6 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - HP Header Unkonwn
G19.VALVE.SWV1.ILOCK.HPHDR_OVR 300108 7 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - HP Header Override
G19.VALVE.SWV1.ILOCK.LPHPPRS_LO 300108 8 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - Out of service OPEN
G19.VALVE.SWV1.ILOCK.LPHPPRS_UNK 300108 9 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - Out of service CLOSE
G19.VALVE.SWV1.ILOCK.OOS_OPN 300108 10 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - Out of service OPEN
G19.VALVE.SWV1.ILOCK.OOS_CLS 300108 11 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - Out of service CLOSE
G19.VALVE.SWV1.ILOCK.CE_AMVPMV_OPN 300108 12 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - AMV and PMV are open - C&E 1a
G19.VALVE.SWV1.ILOCK.CE_XOVPWV_OPN 300108 13 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - XOV and PWV are open - C&E 1B
G19.VALVE.SWV1.ILOCK.CE_AMVXOV_OPN 300108 14 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - AMV and XOV are open - C&E 1C & 1D
G19.VALVE.SWV1.ILOCK.CE_EQUALIZE 300108 15 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - Equalize before opening - C&E 4a
G19.VALVE.SWV1.ILOCK.VALUE 300108 DWord RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word
G19.VALVE.SWV1.ILOCK.CE_PMVXOV_OPN 300109 0 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - PMV and XOV are open - C&E 1E
G19.VALVE.SWV1.ILOCK.CE_PWVAMV_OPN 300109 1 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - PWV and AMV not closed - C&E 1F
G19.VALVE.SWV1.ILOCK.CE_PCV_NOTCL 300109 2 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - PCV not closed - C&E 2
G19.VALVE.SWV1.ILOCK.CE_PMVPWV_NOTCL 300109 3 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - PMV or PWV not closed - C&E 4b
G19.VALVE.SWV1.ILOCK.CE_PWV_NOTCL 300109 4 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - PWV not closed - C&E 5
G19.VALVE.SWV1.ILOCK.CE_XOV_OPN 300109 5 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - XOV open - C&E 8
G19.VALVE.SWV1.ILOCK.CE_GLV_OPN 300109 6 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - GLV open - C&E 9
G19.VALVE.SWV1.ILOCK.CE_PMVPWV_NOTCL1 300109 9 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - PMV or PWV not Closed - C&E 4b
G19.VALVE.SWV1.ILOCK.CE_PWV_NOTCL1 300109 10 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - PWV not closed - C&E 6
G19.VALVE.SWV1.ILOCK.CE_PCVPWV_NOTCL 300109 11 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - PCV and PWV not closed - C&E 7a
G19.VALVE.SWV1.ILOCK.CE_PCVPMV_NOTCL 300109 12 Boolean RO 1000 G19 Well SWC1 - Upper Sleeve Interlock Word - PCV and PMV not Closed - C&E 7b
G19.VALVE.SWV2.STATUS.OPEN 300110 0 Boolean RO 1000 G19 WELL SWC2 - LOWER SLEEVE STATUS WORD - IS OPEN

Page 18 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx G19 19/04/2024

Validation Date Tag Name Address Data Type Client Access Scan Rate Description
G19.VALVE.SWV2.STATUS.CLOSED 300110 1 Boolean RO 1000 G19 WELL SWC2 - LOWER SLEEVE STATUS WORD - IS CLOSED
G19.VALVE.SWV2.STATUS.MOVING 300110 2 Boolean RO 1000 G19 WELL SWC2 - LOWER SLEEVE STATUS WORD - IS MOVING
G19.VALVE.SWV2.STATUS.ALM_DISC 300110 3 Boolean RO 1000 G19 WELL SWC2 - LOWER SLEEVE STATUS WORD - DISCREPENCY
G19.VALVE.SWV2.STATUS.ALM_FLTOMOV 300110 4 Boolean RO 1000 G19 WELL SWC2 - LOWER SLEEVE STATUS WORD - FAILED TO OPEN
G19.VALVE.SWV2.STATUS.ALM_FBIGNORE 300110 5 Boolean RO 1000 G19 WELL SWC2 - LOWER SLEEVE STATUS WORD - FEEDBACK IS IGNORED
G19.VALVE.SWV2.STATUS.OK_TO_OPN 300110 6 Boolean RO 1000 G19 WELL SWC2 - LOWER SLEEVE STATUS WORD - OK TO OPEN
G19.VALVE.SWV2.STATUS.OK_TO_CLS 300110 7 Boolean RO 1000 G19 WELL SWC2 - LOWER SLEEVE STATUS WORD - OK TO CLOSE
G19.VALVE.SWV2.STATUS.OPN_ILOCK_DFT 300110 8 Boolean RO 1000 G19 WELL SWC2 - LOWER SLEEVE STATUS WORD - OPEN ILOCK DEFEATABLE
G19.VALVE.SWV2.STATUS.CLS_ILOCK_DFT 300110 9 Boolean RO 1000 G19 WELL SWC2 - LOWER SLEEVE STATUS WORD - CLOSE ILOCK DEFEATABLE
G19.VALVE.SWV2.ILOCK.ROV_OPN 300111 0 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - ROV Override Open
G19.VALVE.SWV2.ILOCK.ROV_CLSD 300111 1 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - ROV Override Closed
G19.VALVE.SWV2.ILOCK.LPHDR_LO 300111 2 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - LP Header Low
G19.VALVE.SWV2.ILOCK.LPHDR_UNK 300111 3 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - LP Header Unknown
G19.VALVE.SWV2.ILOCK.LPHDR_OVR 300111 4 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - LP Header Override
G19.VALVE.SWV2.ILOCK.HPHDR_LO 300111 5 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - HP Header Low
G19.VALVE.SWV2.ILOCK.HPHDR_UNK 300111 6 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - HP Header Unkonwn
G19.VALVE.SWV2.ILOCK.HPHDR_OVR 300111 7 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - HP Header Override
G19.VALVE.SWV2.ILOCK.LPHPPRS_LO 300111 8 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - Out of service OPEN
G19.VALVE.SWV2.ILOCK.LPHPPRS_UNK 300111 9 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - Out of service CLOSE
G19.VALVE.SWV2.ILOCK.OOS_OPN 300111 10 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - Out of service OPEN
G19.VALVE.SWV2.ILOCK.OOS_CLS 300111 11 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - Out of service CLOSE
G19.VALVE.SWV2.ILOCK.CE_AMVPMV_OPN 300111 12 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - AMV and PMV are open - C&E 1a
G19.VALVE.SWV2.ILOCK.CE_XOVPWV_OPN 300111 13 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - XOV and PWV are open - C&E 1B
G19.VALVE.SWV2.ILOCK.CE_AMVXOV_OPN 300111 14 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - AMV and XOV are open - C&E 1C & 1D
G19.VALVE.SWV2.ILOCK.CE_EQUALIZE 300111 15 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - Equalize before opening - C&E 4a
G19.VALVE.SWV2.ILOCK.VALUE 300111 DWord RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word
G19.VALVE.SWV2.ILOCK.CE_PMVXOV_OPN 300112 0 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - PMV and XOV are open - C&E 1E
G19.VALVE.SWV2.ILOCK.CE_PWVAMV_OPN 300112 1 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - PWV and AMV not closed - C&E 1F
G19.VALVE.SWV2.ILOCK.CE_PCV_NOTCL 300112 2 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - PCV not closed - C&E 2
G19.VALVE.SWV2.ILOCK.CE_PMVPWV_NOTCL 300112 3 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - PMV or PWV not closed - C&E 4b
G19.VALVE.SWV2.ILOCK.CE_PWV_NOTCL 300112 4 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - PWV not closed - C&E 5
G19.VALVE.SWV2.ILOCK.CE_XOV_OPN 300112 5 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - XOV open - C&E 8
G19.VALVE.SWV2.ILOCK.CE_GLV_OPN 300112 6 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - GLV open - C&E 9
G19.VALVE.SWV2.ILOCK.CE_PMVPWV_NOTCL1 300112 9 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - PMV or PWV not Closed - C&E 4b
G19.VALVE.SWV2.ILOCK.CE_PWV_NOTCL1 300112 10 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - PWV not closed - C&E 6
G19.VALVE.SWV2.ILOCK.CE_PCVPWV_NOTCL 300112 11 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - PCV and PWV not closed - C&E 7a
G19.VALVE.SWV2.ILOCK.CE_PCVPMV_NOTCL 300112 12 Boolean RO 1000 G19 Well SWC2 - Lower Sleeve Interlock Word - PCV and PMV not Closed - C&E 7b
G19.VALVE.SWV3.STATUS.OPEN 300113 0 Boolean RO 1000 G19 WELL SWC3 - COMMON CLOSE STATUS WORD - IS OPEN
G19.VALVE.SWV3.STATUS.CLOSED 300113 1 Boolean RO 1000 G19 WELL SWC3 - COMMON CLOSE STATUS WORD - IS CLOSED
G19.VALVE.SWV3.STATUS.MOVING 300113 2 Boolean RO 1000 G19 WELL SWC3 - COMMON CLOSE STATUS WORD - IS MOVING
G19.VALVE.SWV3.STATUS.ALM_DISC 300113 3 Boolean RO 1000 G19 WELL SWC3 - COMMON CLOSE STATUS WORD - DISCREPENCY
G19.VALVE.SWV3.STATUS.ALM_FLTOMOV 300113 4 Boolean RO 1000 G19 WELL SWC3 - COMMON CLOSE STATUS WORD - FAILED TO OPEN
G19.VALVE.SWV3.STATUS.ALM_FBIGNORE 300113 5 Boolean RO 1000 G19 WELL SWC3 - COMMON CLOSE STATUS WORD - FEEDBACK IS IGNORED
G19.VALVE.SWV3.STATUS.OK_TO_OPN 300113 6 Boolean RO 1000 G19 WELL SWC3 - COMMON CLOSE STATUS WORD - OK TO OPEN
G19.VALVE.SWV3.STATUS.OK_TO_CLS 300113 7 Boolean RO 1000 G19 WELL SWC3 - COMMON CLOSE STATUS WORD - OK TO CLOSE
G19.VALVE.SWV3.STATUS.OPN_ILOCK_DFT 300113 8 Boolean RO 1000 G19 WELL SWC3 - COMMON CLOSE STATUS WORD - OPEN ILOCK DEFEATABLE
G19.VALVE.SWV3.STATUS.CLS_ILOCK_DFT 300113 9 Boolean RO 1000 G19 WELL SWC3 - COMMON CLOSE STATUS WORD - CLOSE ILOCK DEFEATABLE
G19.VALVE.SWV3.ILOCK.ROV_OPN 300114 0 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - ROV Override Open
G19.VALVE.SWV3.ILOCK.ROV_CLSD 300114 1 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - ROV Override Closed
G19.VALVE.SWV3.ILOCK.LPHDR_LO 300114 2 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - LP Header Low
G19.VALVE.SWV3.ILOCK.LPHDR_UNK 300114 3 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - LP Header Unknown
G19.VALVE.SWV3.ILOCK.LPHDR_OVR 300114 4 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - LP Header Override
G19.VALVE.SWV3.ILOCK.HPHDR_LO 300114 5 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - HP Header Low
G19.VALVE.SWV3.ILOCK.HPHDR_UNK 300114 6 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - HP Header Unkonwn
G19.VALVE.SWV3.ILOCK.HPHDR_OVR 300114 7 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - HP Header Override
G19.VALVE.SWV3.ILOCK.LPHPPRS_LO 300114 8 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - Out of service OPEN
G19.VALVE.SWV3.ILOCK.LPHPPRS_UNK 300114 9 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - Out of service CLOSE
G19.VALVE.SWV3.ILOCK.OOS_OPN 300114 10 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - Out of service OPEN

Page 19 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx G19 19/04/2024

Validation Date Tag Name Address Data Type Client Access Scan Rate Description
G19.VALVE.SWV3.ILOCK.OOS_CLS 300114 11 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - Out of service CLOSE
G19.VALVE.SWV3.ILOCK.CE_AMVPMV_OPN 300114 12 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - AMV and PMV are open - C&E 1a
G19.VALVE.SWV3.ILOCK.CE_XOVPWV_OPN 300114 13 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - XOV and PWV are open - C&E 1B
G19.VALVE.SWV3.ILOCK.CE_AMVXOV_OPN 300114 14 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - AMV and XOV are open - C&E 1C & 1D
G19.VALVE.SWV3.ILOCK.CE_EQUALIZE 300114 15 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - Equalize before opening - C&E 4a
G19.VALVE.SWV3.ILOCK.VALUE 300114 DWord RO 1000 G19 Well SWC3 - Common Close Interlock Word
G19.VALVE.SWV3.ILOCK.CE_PMVXOV_OPN 300115 0 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - PMV and XOV are open - C&E 1E
G19.VALVE.SWV3.ILOCK.CE_PWVAMV_OPN 300115 1 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - PWV and AMV not closed - C&E 1F
G19.VALVE.SWV3.ILOCK.CE_PCV_NOTCL 300115 2 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - PCV not closed - C&E 2
G19.VALVE.SWV3.ILOCK.CE_PMVPWV_NOTCL 300115 3 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - PMV or PWV not closed - C&E 4b
G19.VALVE.SWV3.ILOCK.CE_PWV_NOTCL 300115 4 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - PWV not closed - C&E 5
G19.VALVE.SWV3.ILOCK.CE_XOV_OPN 300115 5 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - XOV open - C&E 8
G19.VALVE.SWV3.ILOCK.CE_GLV_OPN 300115 6 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - GLV open - C&E 9
G19.VALVE.SWV3.ILOCK.CE_PMVPWV_NOTCL1 300115 9 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - PMV or PWV not Closed - C&E 4b
G19.VALVE.SWV3.ILOCK.CE_PWV_NOTCL1 300115 10 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - PWV not closed - C&E 6
G19.VALVE.SWV3.ILOCK.CE_PCVPWV_NOTCL 300115 11 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - PCV and PWV not closed - C&E 7a
G19.VALVE.SWV3.ILOCK.CE_PCVPMV_NOTCL 300115 12 Boolean RO 1000 G19 Well SWC3 - Common Close Interlock Word - PCV and PMV not Closed - C&E 7b
G19.VALVE.WOV.STATUS.OPEN 300116 0 Boolean RO 1000 G19 WELL WORKOVER VALVE STATUS WORD - IS OPEN
G19.VALVE.WOV.STATUS.CLOSED 300116 1 Boolean RO 1000 G19 WELL WORKOVER VALVE STATUS WORD - IS CLOSED
G19.VALVE.WOV.STATUS.MOVING 300116 2 Boolean RO 1000 G19 WELL WORKOVER VALVE STATUS WORD - IS MOVING
G19.VALVE.WOV.STATUS.ALM_DISC 300116 3 Boolean RO 1000 G19 WELL WORKOVER VALVE STATUS WORD - DISCREPENCY
G19.VALVE.WOV.STATUS.ALM_FLTOMOV 300116 4 Boolean RO 1000 G19 WELL WORKOVER VALVE STATUS WORD - FAILED TO OPEN
G19.VALVE.WOV.STATUS.ALM_FBIGNORE 300116 5 Boolean RO 1000 G19 WELL WORKOVER VALVE STATUS WORD - FEEDBACK IS IGNORED
G19.VALVE.WOV.STATUS.OK_TO_OPN 300116 6 Boolean RO 1000 G19 WELL WORKOVER VALVE STATUS WORD - OK TO OPEN
G19.VALVE.WOV.STATUS.OK_TO_CLS 300116 7 Boolean RO 1000 G19 WELL WORKOVER VALVE STATUS WORD - OK TO CLOSE
G19.VALVE.WOV.STATUS.OPN_ILOCK_DFT 300116 8 Boolean RO 1000 G19 WELL WORKOVER VALVE STATUS WORD - OPEN ILOCK DEFEATABLE
G19.VALVE.WOV.STATUS.CLS_ILOCK_DFT 300116 9 Boolean RO 1000 G19 WELL WORKOVER VALVE STATUS WORD - CLOSE ILOCK DEFEATABLE
G19.VALVE.WOV.ILOCK.ROV_OPN 300117 0 Boolean RO 1000 G19 Well Workover Valve Interlock Word - ROV Override Open
G19.VALVE.WOV.ILOCK.ROV_CLSD 300117 1 Boolean RO 1000 G19 Well Workover Valve Interlock Word - ROV Override Closed
G19.VALVE.WOV.ILOCK.LPHDR_LO 300117 2 Boolean RO 1000 G19 Well Workover Valve Interlock Word - LP Header Low
G19.VALVE.WOV.ILOCK.LPHDR_UNK 300117 3 Boolean RO 1000 G19 Well Workover Valve Interlock Word - LP Header Unknown
G19.VALVE.WOV.ILOCK.LPHDR_OVR 300117 4 Boolean RO 1000 G19 Well Workover Valve Interlock Word - LP Header Override
G19.VALVE.WOV.ILOCK.HPHDR_LO 300117 5 Boolean RO 1000 G19 Well Workover Valve Interlock Word - HP Header Low
G19.VALVE.WOV.ILOCK.HPHDR_UNK 300117 6 Boolean RO 1000 G19 Well Workover Valve Interlock Word - HP Header Unkonwn
G19.VALVE.WOV.ILOCK.HPHDR_OVR 300117 7 Boolean RO 1000 G19 Well Workover Valve Interlock Word - HP Header Override
G19.VALVE.WOV.ILOCK.LPHPPRS_LO 300117 8 Boolean RO 1000 G19 Well Workover Valve Interlock Word - Out of service OPEN
G19.VALVE.WOV.ILOCK.LPHPPRS_UNK 300117 9 Boolean RO 1000 G19 Well Workover Valve Interlock Word - Out of service CLOSE
G19.VALVE.WOV.ILOCK.OOS_OPN 300117 10 Boolean RO 1000 G19 Well Workover Valve Interlock Word - Out of service OPEN
G19.VALVE.WOV.ILOCK.OOS_CLS 300117 11 Boolean RO 1000 G19 Well Workover Valve Interlock Word - Out of service CLOSE
G19.VALVE.WOV.ILOCK.CE_AMVPMV_OPN 300117 12 Boolean RO 1000 G19 Well Workover Valve Interlock Word - AMV and PMV are open - C&E 1a
G19.VALVE.WOV.ILOCK.CE_XOVPWV_OPN 300117 13 Boolean RO 1000 G19 Well Workover Valve Interlock Word - XOV and PWV are open - C&E 1B
G19.VALVE.WOV.ILOCK.CE_AMVXOV_OPN 300117 14 Boolean RO 1000 G19 Well Workover Valve Interlock Word - AMV and XOV are open - C&E 1C & 1D
G19.VALVE.WOV.ILOCK.CE_EQUALIZE 300117 15 Boolean RO 1000 G19 Well Workover Valve Interlock Word - Equalize before opening - C&E 4a
G19.VALVE.WOV.ILOCK.VALUE 300117 DWord RO 1000 G19 Well Workover Valve Interlock Word
G19.VALVE.WOV.ILOCK.CE_PMVXOV_OPN 300118 0 Boolean RO 1000 G19 Well Workover Valve Interlock Word - PMV and XOV are open - C&E 1E
G19.VALVE.WOV.ILOCK.CE_PWVAMV_OPN 300118 1 Boolean RO 1000 G19 Well Workover Valve Interlock Word - PWV and AMV not closed - C&E 1F
G19.VALVE.WOV.ILOCK.CE_PCV_NOTCL 300118 2 Boolean RO 1000 G19 Well Workover Valve Interlock Word - PCV not closed - C&E 2
G19.VALVE.WOV.ILOCK.CE_PMVPWV_NOTCL 300118 3 Boolean RO 1000 G19 Well Workover Valve Interlock Word - PMV or PWV not closed - C&E 4b
G19.VALVE.WOV.ILOCK.CE_PWV_NOTCL 300118 4 Boolean RO 1000 G19 Well Workover Valve Interlock Word - PWV not closed - C&E 5
G19.VALVE.WOV.ILOCK.CE_XOV_OPN 300118 5 Boolean RO 1000 G19 Well Workover Valve Interlock Word - XOV open - C&E 8
G19.VALVE.WOV.ILOCK.CE_GLV_OPN 300118 6 Boolean RO 1000 G19 Well Workover Valve Interlock Word - GLV open - C&E 9
G19.VALVE.WOV.ILOCK.CE_PMVPWV_NOTCL1 300118 9 Boolean RO 1000 G19 Well Workover Valve Interlock Word - PMV or PWV not Closed - C&E 4b
G19.VALVE.WOV.ILOCK.CE_PWV_NOTCL1 300118 10 Boolean RO 1000 G19 Well Workover Valve Interlock Word - PWV not closed - C&E 6
G19.VALVE.WOV.ILOCK.CE_PCVPWV_NOTCL 300118 11 Boolean RO 1000 G19 Well Workover Valve Interlock Word - PCV and PWV not closed - C&E 7a
G19.VALVE.WOV.ILOCK.CE_PCVPMV_NOTCL 300118 12 Boolean RO 1000 G19 Well Workover Valve Interlock Word - PCV and PMV not Closed - C&E 7b
G19.CHOKE.PCV.CALC_POS 300119 Float RO 1000 G19 Well Production Choke Calculated Position
G19.CHOKE.PCV.SP_MCS 300121 Float RO 1000 G19 Well Production Choke Setpoint (MCS)
G19.CHOKE.PCV.STATUS.OPEN 300123 0 Boolean RO 1000 G19 WELL PRODUCTION CHOKE STATUS WORD - IS OPEN

Page 20 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx G19 19/04/2024

Validation Date Tag Name Address Data Type Client Access Scan Rate Description
G19.CHOKE.PCV.STATUS.CLOSED 300123 1 Boolean RO 1000 G19 WELL PRODUCTION CHOKE STATUS WORD - IS CLOSED
G19.CHOKE.PCV.STATUS.MOVING 300123 2 Boolean RO 1000 G19 WELL PRODUCTION CHOKE STATUS WORD - IS MOVING
G19.CHOKE.PCV.STATUS.ALM_DISC 300123 3 Boolean RO 1000 G19 WELL PRODUCTION CHOKE STATUS WORD - DISCREPENCY
G19.CHOKE.PCV.STATUS.ALM_FLTOCMD 300123 4 Boolean RO 1000 G19 WELL PRODUCTION CHOKE STATUS WORD - FAILED TO MOVE
G19.CHOKE.PCV.STATUS.ALM_FBIGNORE 300123 5 Boolean RO 1000 G19 WELL PRODUCTION CHOKE STATUS WORD - FEEDBACK IS IGNORED
G19.CHOKE.PCV.STATUS.OK_TO_MOVE 300123 6 Boolean RO 1000 G19 WELL PRODUCTION CHOKE STATUS WORD - OK TO MOVE
G19.CHOKE.PCV.STATUS.OK_TO_ABRT 300123 7 Boolean RO 1000 G19 WELL PRODUCTION CHOKE STATUS WORD - OK TO ABORT
G19.CHOKE.PCV.STATUS.MOV_ILOCK_DFT 300123 8 Boolean RO 1000 G19 WELL PRODUCTION CHOKE STATUS WORD - MOVE ILOCK DEFEATABLE
G19.CHOKE.PCV.STATUS.ABT_ILOCK_DFT 300123 9 Boolean RO 1000 G19 WELL PRODUCTION CHOKE STATUS WORD - ABORT ILOCK DEFEATABLE
G19.CHOKE.PCV.ILOCK.ROV_OPN 300124 0 Boolean RO 1000 G19 WELL PRODUCTION CHOKE INTERLOCK WORD - IS OPEN
G19.CHOKE.PCV.ILOCK.ROV_CLSD 300124 1 Boolean RO 1000 G19 WELL PRODUCTION CHOKE INTERLOCK WORD - IS CLOSED
G19.CHOKE.PCV.ILOCK.LPHDR_LO 300124 2 Boolean RO 1000 G19 WELL PRODUCTION CHOKE INTERLOCK WORD - LP HEADER PRESSURE LO
G19.CHOKE.PCV.ILOCK.LPHDR_UNK 300124 3 Boolean RO 1000 G19 WELL PRODUCTION CHOKE INTERLOCK WORD - LP HEADER PRESSURE UNKNOWN
G19.CHOKE.PCV.ILOCK.LPHDR_OVR 300124 4 Boolean RO 1000 G19 WELL PRODUCTION CHOKE INTERLOCK WORD - LP HEADER OVERRIDE
G19.CHOKE.PCV.ILOCK.OOS_OPN 300124 10 Boolean RO 1000 G19 WELL PRODUCTION CHOKE INTERLOCK WORD - OOS IN OPEN POSITION
G19.CHOKE.PCV.ILOCK.OOS_CLS 300124 11 Boolean RO 1000 G19 WELL PRODUCTION CHOKE INTERLOCK WORD - OOS IN CLOSE POSIION
G19.CHOKE.PCV.ILOCK.VALUE 300124 DWord RO 1000 G19 Well Production Choke Interlock Word
G19.SEQ.STEP 300125 Word RO 1000 G19 Well Sequences Sequence Step
G19.SEQ.TIME 300126 Word RO 1000 G19 Well Sequences Time Remaining
G19.CTRL.WORD 400001 Word R/W 1000 G19 Well Control Word
G19.VALVE.AMV.CTRL.WORD 400002 Word R/W 1000 G19 Well Annulus Master Valve Control Word
G19.VALVE.GLV.CTRL.WORD 400003 Word R/W 1000 G19 Well Gas Lift Isolation Valve Control Word
G19.VALVE.PMV.CTRL.WORD 400004 Word R/W 1000 G19 Well Production Master Valve Control Word
G19.VALVE.PWV.CTRL.WORD 400005 Word R/W 1000 G19 Well Production Wing Valve Control Word
G19.VALVE.SCSSV.CTRL.WORD 400006 Word R/W 1000 G19 Well Downhole Safety Valve (SCSSV) Control Word
G19.VALVE.XOV.CTRL.WORD 400007 Word R/W 1000 G19 Well Crossover Valve Control Word
G19.VALVE.AMON.CTRL.WORD 400008 Word R/W 1000 G19 Well Annulus Monitor Valve Control Word
G19.VALVE.CIV.CTRL.WORD 400009 Word R/W 1000 G19 Well Chemical Injection Valve Control Word
G19.VALVE.DHCV1.CTRL.WORD 400010 Word R/W 1000 G19 Well Downhole Chemical Injection Valve #1 Control Word
G19.VALVE.DHCV2.CTRL.WORD 400011 Word R/W 1000 G19 Well Downhole Chemical Injection Valve #2 Control Word
G19.VALVE.MIV.CTRL.WORD 400012 Word R/W 1000 G19 Well Methanol Injection Valve Control Word
G19.VALVE.PLET.CTRL.WORD 400013 Word R/W 1000 G19 Well PLET Valve Control Word
G19.VALVE.SWV1.CTRL.WORD 400014 Word R/W 1000 G19 Well SWC1 - Upper Sleeve Control Word
G19.VALVE.SWV2.CTRL.WORD 400015 Word R/W 1000 G19 Well SWC2 - Lower Sleeve Control Word
G19.VALVE.SWV3.CTRL.WORD 400016 Word R/W 1000 G19 Well SWC3 - Common Close Control Word
G19.VALVE.WOV.CTRL.WORD 400017 Word R/W 1000 G19 Well Workover Valve Control Word
G19.CHOKE.PCV.REM_SP 400020 Float R/W 1000 G19 Well Production Choke Remote Setpoint (ICSS)
G19.CHOKE.PCV.CTRL.VALUE 400022 Word R/W 1000 G19 Well Production Choke Control Word

Page 21 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx OF19 19/04/2024

Validation Date Tag Name Address index Data Type Client Access Scan Rate Description
OF19.STATUS.SEMA_ONSCAN 300001 0 Boolean RO 1000 WELL OF19 - MCS ON SCAN WITH SCM VIA CHA
OF19.STATUS.SEMB_ONSCAN 300001 1 Boolean RO 1000 WELL OF19 - MCS ON SCAN WITH SCM VIA CHB
OF19.STATUS.FLT_SEMA 300001 2 Boolean RO 1000 WELL OF19 - MCS UNABLE TO COMM WITH SCM VIA CHA
OF19.STATUS.FLT_SEMB 300001 3 Boolean RO 1000 WELL OF19 - MCS UNABLE TO COMM WITH SCM VIA CHB
OF19.STATUS.WELL_FLOWING 300001 4 Boolean RO 1000 WELL OF19 - WELL IS FLOWING
OF19.STATUS.SMART 300001 5 Boolean RO 1000 WELL OF19 - SMART WELL FEATURES ENABLED
OF19.STATUS.SCM_DIAG_ALM 300001 6 Boolean RO 1000 WELL OF19 - SCM DIAGNOSTIC ALARM ACT&UNACK
OF19.ILOCK.SEQ_COND 300002 0 Boolean RO 1000 WELL OF19 I-LOCK - SEQUENCE COND
OF19.ILOCK.SEQ_TRIP 300002 1 Boolean RO 1000 WELL OF19 I-LOCK - SEQUENCE COND - PSD/ESD/TSE TRIP ACTIVE
OF19.ILOCK.KEY_MCS 300002 2 Boolean RO 1000 WELL OF19 I-LOCK - MCS ONLY IN CONTROL (KEYSWITCH)
OF19.ILOCK.KEY_DCS 300002 3 Boolean RO 1000 WELL OF19 I-LOCK - DCS ONLY IN CONTROL (KEYSWITCH)
OF19.ILOCK.NO_SCM 300002 4 Boolean RO 1000 WELL OF19 I-LOCK - SCM NOT INSTALLED - ALL CTRL DISABLED
OF19.ILOCK.SCM_OFF_SCAN 300002 5 Boolean RO 1000 WELL OF19 I-LOCK - SCM OFF SCAN - ALL CTRL DISABLED
OF19.ILOCK.TOT_COMM_LOSS 300002 6 Boolean RO 1000 WELL OF19 I-LOCK - TOTAL COMM LOSS
OF19.ILOCK.WORKOVER 300002 7 Boolean RO 1000 WELL OF19 I-LOCK - WELL IN WORKOVER - ALL CTRL DISABLED
OF19.ILOCK.MAXSOLS 300002 8 Boolean RO 1000 WELL OF19 I-LOCK - MAX SOLENOIDS ENERGIZED
OF19.ILOCK.DV_DEFLOW 300002 9 Boolean RO 1000 WELL OF19 I-LOCK - DUMP VALVE DEENERGIZED - LP OPS I-LOCK
OF19.ILOCK.HPHDR_LO 300002 10 Boolean RO 1000 WELL OF19 I-LOCK - HP HEADER LO PRESS - HP OPS I-LOCK
OF19.ILOCK.HPHDR_UNK 300002 11 Boolean RO 1000 WELL OF19 I-LOCK - HP HEADER UNKNOWN PRESS - HP OPS I-LOCK
OF19.ILOCK.LPHDR_LO 300002 12 Boolean RO 1000 WELL OF19 I-LOCK - LP HEADER LO PRESS - LP OPS I-LOCK
OF19.ILOCK.LPHDR_UNK 300002 13 Boolean RO 1000 WELL OF19 I-LOCK - LP HEADER UNKNOWN PRESS - LP OPS I-LOCK
OF19.ILOCK.MAXLP 300002 14 Boolean RO 1000 WELL OF19 I-LOCK - MAX LP VALVE PRESS IS EXCEEDED
OF19.ILOCK.VALUE 300002 Word RO 1000 OF19 Well Interlock Word
OF19.ALOG.LPHPT.SCALED 300003 Float RO 1000 OF19 Well LP Header Pressure
OF19.ALOG.LPHPT.STATUS.OVR_ACT 300005 0 Boolean RO 1000 OF19 WELL LP HEADER PRESSURE STATUS WORD - OVERRIDE ACTIVE
OF19.ALOG.LPHPT.STATUS.UNKNOWN_A 300005 1 Boolean RO 1000 OF19 WELL LP HEADER PRESSURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
OF19.ALOG.LPHPT.STATUS.UNKNOWN_B 300005 2 Boolean RO 1000 OF19 WELL LP HEADER PRESSURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
OF19.ALOG.LPHPT.STATUS.UN_RANGE 300005 3 Boolean RO 1000 OF19 WELL LP HEADER PRESSURE STATUS WORD - UNDERRANGE
OF19.ALOG.LPHPT.STATUS.OV_RANGE 300005 4 Boolean RO 1000 OF19 WELL LP HEADER PRESSURE STATUS WORD - OVERRANGE
OF19.ALOG.LPHPT.STATUS.LOLO 300005 8 Boolean RO 1000 OF19 WELL LP HEADER PRESSURE STATUS WORD - LOLO
OF19.ALOG.LPHPT.STATUS.LO 300005 9 Boolean RO 1000 OF19 WELL LP HEADER PRESSURE STATUS WORD - LO
OF19.ALOG.LPHPT.STATUS.HI 300005 10 Boolean RO 1000 OF19 WELL LP HEADER PRESSURE STATUS WORD - HI
OF19.ALOG.LPHPT.STATUS.HIHI 300005 11 Boolean RO 1000 OF19 WELL LP HEADER PRESSURE STATUS WORD - HIHI
OF19.ALOG.LPHPT.STATUS.INVALID_A 300005 13 Boolean RO 1000 OF19 WELL LP HEADER PRESSURE STATUS WORD - SOURCE A INVALID
OF19.ALOG.LPHPT.STATUS.INVALID_B 300005 14 Boolean RO 1000 OF19 WELL LP HEADER PRESSURE STATUS WORD - SOURCE B INVALID
OF19.ALOG.LPHPT.STATUS.SEL_A_B 300005 15 Boolean RO 1000 OF19 WELL LP HEADER PRESSURE STATUS WORD - SOURCE SELECTION 0=A & 1=B
OF19.ALOG.HPHPT.SCALED 300006 Float RO 1000 OF19 Well HP Header Pressure
OF19.ALOG.HPHPT.STATUS.OVR_ACT 300008 0 Boolean RO 1000 OF19 WELL HP HEADER PRESSURE STATUS WORD - OVERRIDE ACTIVE
OF19.ALOG.HPHPT.STATUS.UNKNOWN_A 300008 1 Boolean RO 1000 OF19 WELL HP HEADER PRESSURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
OF19.ALOG.HPHPT.STATUS.UNKNOWN_B 300008 2 Boolean RO 1000 OF19 WELL HP HEADER PRESSURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
OF19.ALOG.HPHPT.STATUS.UN_RANGE 300008 3 Boolean RO 1000 OF19 WELL HP HEADER PRESSURE STATUS WORD - UNDERRANGE
OF19.ALOG.HPHPT.STATUS.OV_RANGE 300008 4 Boolean RO 1000 OF19 WELL HP HEADER PRESSURE STATUS WORD - OVERRANGE
OF19.ALOG.HPHPT.STATUS.LOLO 300008 8 Boolean RO 1000 OF19 WELL HP HEADER PRESSURE STATUS WORD - LOLO
OF19.ALOG.HPHPT.STATUS.LO 300008 9 Boolean RO 1000 OF19 WELL HP HEADER PRESSURE STATUS WORD - LO
OF19.ALOG.HPHPT.STATUS.HI 300008 10 Boolean RO 1000 OF19 WELL HP HEADER PRESSURE STATUS WORD - HI
OF19.ALOG.HPHPT.STATUS.HIHI 300008 11 Boolean RO 1000 OF19 WELL HP HEADER PRESSURE STATUS WORD - HIHI
OF19.ALOG.HPHPT.STATUS.INVALID_A 300008 13 Boolean RO 1000 OF19 WELL HP HEADER PRESSURE STATUS WORD - SOURCE A INVALID
OF19.ALOG.HPHPT.STATUS.INVALID_B 300008 14 Boolean RO 1000 OF19 WELL HP HEADER PRESSURE STATUS WORD - SOURCE B INVALID
OF19.ALOG.HPHPT.STATUS.SEL_A_B 300008 15 Boolean RO 1000 OF19 WELL HP HEADER PRESSURE STATUS WORD - SOURCE SELECTION 0=A & 1=B
OF19.ALOG.UPPT.SCALED 300009 Float RO 1000 OF19 Well Upstream Production Pressure
OF19.ALOG.UPPT.STATUS.OVR_ACT 300011 0 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION PRESSURE STATUS WORD - OVERRIDE ACTIVE
OF19.ALOG.UPPT.STATUS.UNKNOWN_A 300011 1 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION PRESSURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
OF19.ALOG.UPPT.STATUS.UNKNOWN_B 300011 2 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION PRESSURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
OF19.ALOG.UPPT.STATUS.UN_RANGE 300011 3 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION PRESSURE STATUS WORD - UNDERRANGE
OF19.ALOG.UPPT.STATUS.OV_RANGE 300011 4 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION PRESSURE STATUS WORD - OVERRANGE
OF19.ALOG.UPPT.STATUS.LOLO 300011 8 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION PRESSURE STATUS WORD - LOLO
OF19.ALOG.UPPT.STATUS.LO 300011 9 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION PRESSURE STATUS WORD - LO
OF19.ALOG.UPPT.STATUS.HI 300011 10 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION PRESSURE STATUS WORD - HI

Page 22 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx OF19 19/04/2024

Validation Date Tag Name Address index Data Type Client Access Scan Rate Description
OF19.ALOG.UPPT.STATUS.HIHI 300011 11 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION PRESSURE STATUS WORD - HIHI
OF19.ALOG.UPPT.STATUS.INVALID_A 300011 13 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION PRESSURE STATUS WORD - SOURCE A INVALID
OF19.ALOG.UPPT.STATUS.INVALID_B 300011 14 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION PRESSURE STATUS WORD - SOURCE B INVALID
OF19.ALOG.UPPT.STATUS.SEL_A_B 300011 15 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION PRESSURE STATUS WORD - SOURCE SELECTION 0=A & 1=B
OF19.ALOG.UPTT.SCALED 300012 Float RO 1000 OF19 Well Upstream Production Temperature
OF19.ALOG.UPTT.STATUS.OVR_ACT 300014 0 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION TEMPERATURE STATUS WORD - OVERRIDE ACTIVE
OF19.ALOG.UPTT.STATUS.UNKNOWN_A 300014 1 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION TEMPERATURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
OF19.ALOG.UPTT.STATUS.UNKNOWN_B 300014 2 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION TEMPERATURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
OF19.ALOG.UPTT.STATUS.UN_RANGE 300014 3 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION TEMPERATURE STATUS WORD - UNDERRANGE
OF19.ALOG.UPTT.STATUS.OV_RANGE 300014 4 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION TEMPERATURE STATUS WORD - OVERRANGE
OF19.ALOG.UPTT.STATUS.LOLO 300014 8 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION TEMPERATURE STATUS WORD - LOLO
OF19.ALOG.UPTT.STATUS.LO 300014 9 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION TEMPERATURE STATUS WORD - LO
OF19.ALOG.UPTT.STATUS.HI 300014 10 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION TEMPERATURE STATUS WORD - HI
OF19.ALOG.UPTT.STATUS.HIHI 300014 11 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION TEMPERATURE STATUS WORD - HIHI
OF19.ALOG.UPTT.STATUS.INVALID_A 300014 13 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION TEMPERATURE STATUS WORD - SOURCE A INVALID
OF19.ALOG.UPTT.STATUS.INVALID_B 300014 14 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION TEMPERATURE STATUS WORD - SOURCE B INVALID
OF19.ALOG.UPTT.STATUS.SEL_A_B 300014 15 Boolean RO 1000 OF19 WELL UPSTREAM PRODUCTION TEMPERATURE STATUS WORD - SOURCE SELECTION 0=A & 1=B
OF19.ALOG.APPT.SCALED 300015 Float RO 1000 OF19 Well Annulus Pressure
OF19.ALOG.APPT.STATUS.OVR_ACT 300017 0 Boolean RO 1000 OF19 WELL ANNULUS PRESSURE STATUS WORD - OVERRIDE ACTIVE
OF19.ALOG.APPT.STATUS.UNKNOWN_A 300017 1 Boolean RO 1000 OF19 WELL ANNULUS PRESSURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
OF19.ALOG.APPT.STATUS.UNKNOWN_B 300017 2 Boolean RO 1000 OF19 WELL ANNULUS PRESSURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
OF19.ALOG.APPT.STATUS.UN_RANGE 300017 3 Boolean RO 1000 OF19 WELL ANNULUS PRESSURE STATUS WORD - UNDERRANGE
OF19.ALOG.APPT.STATUS.OV_RANGE 300017 4 Boolean RO 1000 OF19 WELL ANNULUS PRESSURE STATUS WORD - OVERRANGE
OF19.ALOG.APPT.STATUS.LOLO 300017 8 Boolean RO 1000 OF19 WELL ANNULUS PRESSURE STATUS WORD - LOLO
OF19.ALOG.APPT.STATUS.LO 300017 9 Boolean RO 1000 OF19 WELL ANNULUS PRESSURE STATUS WORD - LO
OF19.ALOG.APPT.STATUS.HI 300017 10 Boolean RO 1000 OF19 WELL ANNULUS PRESSURE STATUS WORD - HI
OF19.ALOG.APPT.STATUS.HIHI 300017 11 Boolean RO 1000 OF19 WELL ANNULUS PRESSURE STATUS WORD - HIHI
OF19.ALOG.APPT.STATUS.INVALID_A 300017 13 Boolean RO 1000 OF19 WELL ANNULUS PRESSURE STATUS WORD - SOURCE A INVALID
OF19.ALOG.APPT.STATUS.INVALID_B 300017 14 Boolean RO 1000 OF19 WELL ANNULUS PRESSURE STATUS WORD - SOURCE B INVALID
OF19.ALOG.APPT.STATUS.SEL_A_B 300017 15 Boolean RO 1000 OF19 WELL ANNULUS PRESSURE STATUS WORD - SOURCE SELECTION 0=A & 1=B
OF19.ALOG.APTT.SCALED 300018 Float RO 1000 OF19 Well Annulus Temperature
OF19.ALOG.APTT.STATUS.OVR_ACT 300020 0 Boolean RO 1000 OF19 WELL ANNULUS TEMPERATURE STATUS WORD - OVERRIDE ACTIVE
OF19.ALOG.APTT.STATUS.UNKNOWN_A 300020 1 Boolean RO 1000 OF19 WELL ANNULUS TEMPERATURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
OF19.ALOG.APTT.STATUS.UNKNOWN_B 300020 2 Boolean RO 1000 OF19 WELL ANNULUS TEMPERATURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
OF19.ALOG.APTT.STATUS.UN_RANGE 300020 3 Boolean RO 1000 OF19 WELL ANNULUS TEMPERATURE STATUS WORD - UNDERRANGE
OF19.ALOG.APTT.STATUS.OV_RANGE 300020 4 Boolean RO 1000 OF19 WELL ANNULUS TEMPERATURE STATUS WORD - OVERRANGE
OF19.ALOG.APTT.STATUS.LOLO 300020 8 Boolean RO 1000 OF19 WELL ANNULUS TEMPERATURE STATUS WORD - LOLO
OF19.ALOG.APTT.STATUS.LO 300020 9 Boolean RO 1000 OF19 WELL ANNULUS TEMPERATURE STATUS WORD - LO
OF19.ALOG.APTT.STATUS.HI 300020 10 Boolean RO 1000 OF19 WELL ANNULUS TEMPERATURE STATUS WORD - HI
OF19.ALOG.APTT.STATUS.HIHI 300020 11 Boolean RO 1000 OF19 WELL ANNULUS TEMPERATURE STATUS WORD - HIHI
OF19.ALOG.APTT.STATUS.INVALID_A 300020 13 Boolean RO 1000 OF19 WELL ANNULUS TEMPERATURE STATUS WORD - SOURCE A INVALID
OF19.ALOG.APTT.STATUS.INVALID_B 300020 14 Boolean RO 1000 OF19 WELL ANNULUS TEMPERATURE STATUS WORD - SOURCE B INVALID
OF19.ALOG.APTT.STATUS.SEL_A_B 300020 15 Boolean RO 1000 OF19 WELL ANNULUS TEMPERATURE STATUS WORD - SOURCE SELECTION 0=A & 1=B
OF19.ALOG.DPPT.SCALED 300021 Float RO 1000 OF19 Well Downstream Production Pressure
OF19.ALOG.DPPT.STATUS.OVR_ACT 300023 0 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION PRESSURE STATUS WORD - OVERRIDE ACTIVE
OF19.ALOG.DPPT.STATUS.UNKNOWN_A 300023 1 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION PRESSURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
OF19.ALOG.DPPT.STATUS.UNKNOWN_B 300023 2 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION PRESSURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
OF19.ALOG.DPPT.STATUS.UN_RANGE 300023 3 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION PRESSURE STATUS WORD - UNDERRANGE
OF19.ALOG.DPPT.STATUS.OV_RANGE 300023 4 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION PRESSURE STATUS WORD - OVERRANGE
OF19.ALOG.DPPT.STATUS.LOLO 300023 8 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION PRESSURE STATUS WORD - LOLO
OF19.ALOG.DPPT.STATUS.LO 300023 9 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION PRESSURE STATUS WORD - LO
OF19.ALOG.DPPT.STATUS.HI 300023 10 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION PRESSURE STATUS WORD - HI
OF19.ALOG.DPPT.STATUS.HIHI 300023 11 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION PRESSURE STATUS WORD - HIHI
OF19.ALOG.DPPT.STATUS.INVALID_A 300023 13 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION PRESSURE STATUS WORD - SOURCE A INVALID
OF19.ALOG.DPPT.STATUS.INVALID_B 300023 14 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION PRESSURE STATUS WORD - SOURCE B INVALID
OF19.ALOG.DPPT.STATUS.SEL_A_B 300023 15 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION PRESSURE STATUS WORD - SOURCE SELECTION 0=A & 1=B
OF19.ALOG.DPTT.SCALED 300024 Float RO 1000 OF19 Well Downstream Production Temperature
OF19.ALOG.DPTT.STATUS.OVR_ACT 300026 0 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION TEMPERATURE STATUS WORD - OVERRIDE ACTIVE

Page 23 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx OF19 19/04/2024

Validation Date Tag Name Address index Data Type Client Access Scan Rate Description
OF19.ALOG.DPTT.STATUS.UNKNOWN_A 300026 1 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION TEMPERATURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
OF19.ALOG.DPTT.STATUS.UNKNOWN_B 300026 2 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION TEMPERATURE STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
OF19.ALOG.DPTT.STATUS.UN_RANGE 300026 3 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION TEMPERATURE STATUS WORD - UNDERRANGE
OF19.ALOG.DPTT.STATUS.OV_RANGE 300026 4 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION TEMPERATURE STATUS WORD - OVERRANGE
OF19.ALOG.DPTT.STATUS.LOLO 300026 8 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION TEMPERATURE STATUS WORD - LOLO
OF19.ALOG.DPTT.STATUS.LO 300026 9 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION TEMPERATURE STATUS WORD - LO
OF19.ALOG.DPTT.STATUS.HI 300026 10 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION TEMPERATURE STATUS WORD - HI
OF19.ALOG.DPTT.STATUS.HIHI 300026 11 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION TEMPERATURE STATUS WORD - HIHI
OF19.ALOG.DPTT.STATUS.INVALID_A 300026 13 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION TEMPERATURE STATUS WORD - SOURCE A INVALID
OF19.ALOG.DPTT.STATUS.INVALID_B 300026 14 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION TEMPERATURE STATUS WORD - SOURCE B INVALID
OF19.ALOG.DPTT.STATUS.SEL_A_B 300026 15 Boolean RO 1000 OF19 WELL DOWNSTREAM PRODUCTION TEMPERATURE STATUS WORD - SOURCE SELECTION 0=A & 1=B
OF19.ALOG.DHPT1.SCALED 300033 Float RO 1000 OF19 Well Downhole Pressure-1
OF19.ALOG.DHPT1.STATUS.OVR_ACT 300035 0 Boolean RO 1000 OF19 WELL DOWNHOLE PRESSURE-1 STATUS WORD - OVERRIDE ACTIVE
OF19.ALOG.DHPT1.STATUS.UNKNOWN_A 300035 1 Boolean RO 1000 OF19 WELL DOWNHOLE PRESSURE-1 STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
OF19.ALOG.DHPT1.STATUS.UNKNOWN_B 300035 2 Boolean RO 1000 OF19 WELL DOWNHOLE PRESSURE-1 STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
OF19.ALOG.DHPT1.STATUS.UN_RANGE 300035 3 Boolean RO 1000 OF19 WELL DOWNHOLE PRESSURE-1 STATUS WORD - UNDERRANGE
OF19.ALOG.DHPT1.STATUS.OV_RANGE 300035 4 Boolean RO 1000 OF19 WELL DOWNHOLE PRESSURE-1 STATUS WORD - OVERRANGE
OF19.ALOG.DHPT1.STATUS.LOLO 300035 8 Boolean RO 1000 OF19 WELL DOWNHOLE PRESSURE-1 STATUS WORD - LOLO
OF19.ALOG.DHPT1.STATUS.LO 300035 9 Boolean RO 1000 OF19 WELL DOWNHOLE PRESSURE-1 STATUS WORD - LO
OF19.ALOG.DHPT1.STATUS.HI 300035 10 Boolean RO 1000 OF19 WELL DOWNHOLE PRESSURE-1 STATUS WORD - HI
OF19.ALOG.DHPT1.STATUS.HIHI 300035 11 Boolean RO 1000 OF19 WELL DOWNHOLE PRESSURE-1 STATUS WORD - HIHI
OF19.ALOG.DHPT1.STATUS.INVALID_A 300035 13 Boolean RO 1000 OF19 WELL DOWNHOLE PRESSURE-1 STATUS WORD - SOURCE A INVALID
OF19.ALOG.DHPT1.STATUS.INVALID_B 300035 14 Boolean RO 1000 OF19 WELL DOWNHOLE PRESSURE-1 STATUS WORD - SOURCE B INVALID
OF19.ALOG.DHPT1.STATUS.SEL_A_B 300035 15 Boolean RO 1000 OF19 WELL DOWNHOLE PRESSURE-1 STATUS WORD - SOURCE SELECTION 0=A & 1=B
OF19.ALOG.DHTT1.SCALED 300036 Float RO 1000 OF19 Well Downhole Temperature-1
OF19.ALOG.DHTT1.STATUS.OVR_ACT 300038 0 Boolean RO 1000 OF19 WELL DOWNHOLE TEMPERATURE-1 STATUS WORD - OVERRIDE ACTIVE
OF19.ALOG.DHTT1.STATUS.UNKNOWN_A 300038 1 Boolean RO 1000 OF19 WELL DOWNHOLE TEMPERATURE-1 STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
OF19.ALOG.DHTT1.STATUS.UNKNOWN_B 300038 2 Boolean RO 1000 OF19 WELL DOWNHOLE TEMPERATURE-1 STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
OF19.ALOG.DHTT1.STATUS.UN_RANGE 300038 3 Boolean RO 1000 OF19 WELL DOWNHOLE TEMPERATURE-1 STATUS WORD - UNDERRANGE
OF19.ALOG.DHTT1.STATUS.OV_RANGE 300038 4 Boolean RO 1000 OF19 WELL DOWNHOLE TEMPERATURE-1 STATUS WORD - OVERRANGE
OF19.ALOG.DHTT1.STATUS.LOLO 300038 8 Boolean RO 1000 OF19 WELL DOWNHOLE TEMPERATURE-1 STATUS WORD - LOLO
OF19.ALOG.DHTT1.STATUS.LO 300038 9 Boolean RO 1000 OF19 WELL DOWNHOLE TEMPERATURE-1 STATUS WORD - LO
OF19.ALOG.DHTT1.STATUS.HI 300038 10 Boolean RO 1000 OF19 WELL DOWNHOLE TEMPERATURE-1 STATUS WORD - HI
OF19.ALOG.DHTT1.STATUS.HIHI 300038 11 Boolean RO 1000 OF19 WELL DOWNHOLE TEMPERATURE-1 STATUS WORD - HIHI
OF19.ALOG.DHTT1.STATUS.INVALID_A 300038 13 Boolean RO 1000 OF19 WELL DOWNHOLE TEMPERATURE-1 STATUS WORD - SOURCE A INVALID
OF19.ALOG.DHTT1.STATUS.INVALID_B 300038 14 Boolean RO 1000 OF19 WELL DOWNHOLE TEMPERATURE-1 STATUS WORD - SOURCE B INVALID
OF19.ALOG.DHTT1.STATUS.SEL_A_B 300038 15 Boolean RO 1000 OF19 WELL DOWNHOLE TEMPERATURE-1 STATUS WORD - SOURCE SELECTION 0=A & 1=B
OF19.ALOG.CPI.SCALED 300065 Float RO 1000 OF19 Well Choke Position Indicator
OF19.ALOG.CPI.STATUS.OVR_ACT 300067 0 Boolean RO 1000 OF19 WELL CHOCKE POSITION INDICATOR STATUS WORD - OVERRIDE ACTIVE
OF19.ALOG.CPI.STATUS.UNKNOWN_A 300067 1 Boolean RO 1000 OF19 WELL CHOCKE POSITION INDICATOR STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL A
OF19.ALOG.CPI.STATUS.UNKNOWN_B 300067 2 Boolean RO 1000 OF19 WELL CHOCKE POSITION INDICATOR STATUS WORD - FEEDBACK UNKNOWN ON CHANNEL B
OF19.ALOG.CPI.STATUS.UN_RANGE 300067 3 Boolean RO 1000 OF19 WELL CHOCKE POSITION INDICATOR STATUS WORD - UNDERRANGE
OF19.ALOG.CPI.STATUS.OV_RANGE 300067 4 Boolean RO 1000 OF19 WELL CHOCKE POSITION INDICATOR STATUS WORD - OVERRANGE
OF19.ALOG.CPI.STATUS.LOLO 300067 8 Boolean RO 1000 OF19 WELL CHOCKE POSITION INDICATOR STATUS WORD - LOLO
OF19.ALOG.CPI.STATUS.LO 300067 9 Boolean RO 1000 OF19 WELL CHOCKE POSITION INDICATOR STATUS WORD - LO
OF19.ALOG.CPI.STATUS.HI 300067 10 Boolean RO 1000 OF19 WELL CHOCKE POSITION INDICATOR STATUS WORD - HI
OF19.ALOG.CPI.STATUS.HIHI 300067 11 Boolean RO 1000 OF19 WELL CHOCKE POSITION INDICATOR STATUS WORD - HIHI
OF19.ALOG.CPI.STATUS.INVALID_A 300067 13 Boolean RO 1000 OF19 WELL CHOCKE POSITION INDICATOR STATUS WORD - SOURCE A INVALID
OF19.ALOG.CPI.STATUS.INVALID_B 300067 14 Boolean RO 1000 OF19 WELL CHOCKE POSITION INDICATOR STATUS WORD - SOURCE B INVALID
OF19.ALOG.CPI.STATUS.SEL_A_B 300067 15 Boolean RO 1000 OF19 WELL CHOCKE POSITION INDICATOR STATUS WORD - SOURCE SELECTION 0=A & 1=B
OF19.VALVE.AMV.STATUS.OPEN 300071 0 Boolean RO 1000 OF19 WELL ANNULUS MASTER VALVE STATUS WORD - IS OPEN
OF19.VALVE.AMV.STATUS.CLOSED 300071 1 Boolean RO 1000 OF19 WELL ANNULUS MASTER VALVE STATUS WORD - IS CLOSED
OF19.VALVE.AMV.STATUS.MOVING 300071 2 Boolean RO 1000 OF19 WELL ANNULUS MASTER VALVE STATUS WORD - IS MOVING
OF19.VALVE.AMV.STATUS.ALM_DISC 300071 3 Boolean RO 1000 OF19 WELL ANNULUS MASTER VALVE STATUS WORD - DISCREPENCY
OF19.VALVE.AMV.STATUS.ALM_FLTOMOV 300071 4 Boolean RO 1000 OF19 WELL ANNULUS MASTER VALVE STATUS WORD - FAILED TO OPEN
OF19.VALVE.AMV.STATUS.ALM_FBIGNORE 300071 5 Boolean RO 1000 OF19 WELL ANNULUS MASTER VALVE STATUS WORD - FEEDBACK IS IGNORED
OF19.VALVE.AMV.STATUS.OK_TO_OPN 300071 6 Boolean RO 1000 OF19 WELL ANNULUS MASTER VALVE STATUS WORD - OK TO OPEN
OF19.VALVE.AMV.STATUS.OK_TO_CLS 300071 7 Boolean RO 1000 OF19 WELL ANNULUS MASTER VALVE STATUS WORD - OK TO CLOSE

Page 24 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx OF19 19/04/2024

Validation Date Tag Name Address index Data Type Client Access Scan Rate Description
OF19.VALVE.AMV.STATUS.OPN_ILOCK_DFT 300071 8 Boolean RO 1000 OF19 WELL ANNULUS MASTER VALVE STATUS WORD - OPEN ILOCK DEFEATABLE
OF19.VALVE.AMV.STATUS.CLS_ILOCK_DFT 300071 9 Boolean RO 1000 OF19 WELL ANNULUS MASTER VALVE STATUS WORD - CLOSE ILOCK DEFEATABLE
OF19.VALVE.AMV.ILOCK.ROV_OPN 300072 0 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - ROV Override Open
OF19.VALVE.AMV.ILOCK.ROV_CLSD 300072 1 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - ROV Override Closed
OF19.VALVE.AMV.ILOCK.LPHDR_LO 300072 2 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - LP Header Low
OF19.VALVE.AMV.ILOCK.LPHDR_UNK 300072 3 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - LP Header Unknown
OF19.VALVE.AMV.ILOCK.LPHDR_OVR 300072 4 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - LP Header Override
OF19.VALVE.AMV.ILOCK.HPHDR_LO 300072 5 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - HP Header Low
OF19.VALVE.AMV.ILOCK.HPHDR_UNK 300072 6 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - HP Header Unkonwn
OF19.VALVE.AMV.ILOCK.HPHDR_OVR 300072 7 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - HP Header Override
OF19.VALVE.AMV.ILOCK.LPHPPRS_LO 300072 8 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - Out of service OPEN
OF19.VALVE.AMV.ILOCK.LPHPPRS_UNK 300072 9 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - Out of service CLOSE
OF19.VALVE.AMV.ILOCK.OOS_OPN 300072 10 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - Out of service OPEN
OF19.VALVE.AMV.ILOCK.OOS_CLS 300072 11 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - Out of service CLOSE
OF19.VALVE.AMV.ILOCK.CE_AMVPMV_OPN 300072 12 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - AMV and PMV are open - C&E 1a
OF19.VALVE.AMV.ILOCK.CE_XOVPWV_OPN 300072 13 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - XOV and PWV are open - C&E 1B
OF19.VALVE.AMV.ILOCK.CE_AMVXOV_OPN 300072 14 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - AMV and XOV are open - C&E 1C & 1D
OF19.VALVE.AMV.ILOCK.CE_EQUALIZE 300072 15 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - Equalize before opening - C&E 4a
OF19.VALVE.AMV.ILOCK.VALUE 300072 DWord RO 1000 OF19 Well Annulus Master Valve Interlock Word
OF19.VALVE.AMV.ILOCK.CE_PMVXOV_OPN 300073 0 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - PMV and XOV are open - C&E 1E
OF19.VALVE.AMV.ILOCK.CE_PWVAMV_OPN 300073 1 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - PWV and AMV not closed - C&E 1F
OF19.VALVE.AMV.ILOCK.CE_PCV_NOTCL 300073 2 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - PCV not closed - C&E 2
OF19.VALVE.AMV.ILOCK.CE_PMVPWV_NOTCL 300073 3 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - PMV or PWV not closed - C&E 4b
OF19.VALVE.AMV.ILOCK.CE_PWV_NOTCL 300073 4 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - PWV not closed - C&E 5
OF19.VALVE.AMV.ILOCK.CE_XOV_OPN 300073 5 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - XOV open - C&E 8
OF19.VALVE.AMV.ILOCK.CE_GLV_OPN 300073 6 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - GLV open - C&E 9
OF19.VALVE.AMV.ILOCK.CE_PMVPWV_NOTCL1 300073 9 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - PMV or PWV not Closed - C&E 4b
OF19.VALVE.AMV.ILOCK.CE_PWV_NOTCL1 300073 10 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - PWV not closed - C&E 6
OF19.VALVE.AMV.ILOCK.CE_PCVPWV_NOTCL 300073 11 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - PCV and PWV not closed - C&E 7a
OF19.VALVE.AMV.ILOCK.CE_PCVPMV_NOTCL 300073 12 Boolean RO 1000 OF19 Well Annulus Master Valve Interlock Word - PCV and PMV not Closed - C&E 7b
OF19.VALVE.GLV.STATUS.OPEN 300074 0 Boolean RO 1000 OF19 WELL GAS LIFT ISOLATION VALVE STATUS WORD - IS OPEN
OF19.VALVE.GLV.STATUS.CLOSED 300074 1 Boolean RO 1000 OF19 WELL GAS LIFT ISOLATION VALVE STATUS WORD - IS CLOSED
OF19.VALVE.GLV.STATUS.MOVING 300074 2 Boolean RO 1000 OF19 WELL GAS LIFT ISOLATION VALVE STATUS WORD - IS MOVING
OF19.VALVE.GLV.STATUS.ALM_DISC 300074 3 Boolean RO 1000 OF19 WELL GAS LIFT ISOLATION VALVE STATUS WORD - DISCREPENCY
OF19.VALVE.GLV.STATUS.ALM_FLTOMOV 300074 4 Boolean RO 1000 OF19 WELL GAS LIFT ISOLATION VALVE STATUS WORD - FAILED TO OPEN
OF19.VALVE.GLV.STATUS.ALM_FBIGNORE 300074 5 Boolean RO 1000 OF19 WELL GAS LIFT ISOLATION VALVE STATUS WORD - FEEDBACK IS IGNORED
OF19.VALVE.GLV.STATUS.OK_TO_OPN 300074 6 Boolean RO 1000 OF19 WELL GAS LIFT ISOLATION VALVE STATUS WORD - OK TO OPEN
OF19.VALVE.GLV.STATUS.OK_TO_CLS 300074 7 Boolean RO 1000 OF19 WELL GAS LIFT ISOLATION VALVE STATUS WORD - OK TO CLOSE
OF19.VALVE.GLV.STATUS.OPN_ILOCK_DFT 300074 8 Boolean RO 1000 OF19 WELL GAS LIFT ISOLATION VALVE STATUS WORD - OPEN ILOCK DEFEATABLE
OF19.VALVE.GLV.STATUS.CLS_ILOCK_DFT 300074 9 Boolean RO 1000 OF19 WELL GAS LIFT ISOLATION VALVE STATUS WORD - CLOSE ILOCK DEFEATABLE
OF19.VALVE.GLV.ILOCK.ROV_OPN 300075 0 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - ROV Override Open
OF19.VALVE.GLV.ILOCK.ROV_CLSD 300075 1 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - ROV Override Closed
OF19.VALVE.GLV.ILOCK.LPHDR_LO 300075 2 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - LP Header Low
OF19.VALVE.GLV.ILOCK.LPHDR_UNK 300075 3 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - LP Header Unknown
OF19.VALVE.GLV.ILOCK.LPHDR_OVR 300075 4 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - LP Header Override
OF19.VALVE.GLV.ILOCK.HPHDR_LO 300075 5 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - HP Header Low
OF19.VALVE.GLV.ILOCK.HPHDR_UNK 300075 6 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - HP Header Unkonwn
OF19.VALVE.GLV.ILOCK.HPHDR_OVR 300075 7 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - HP Header Override
OF19.VALVE.GLV.ILOCK.LPHPPRS_LO 300075 8 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - Out of service OPEN
OF19.VALVE.GLV.ILOCK.LPHPPRS_UNK 300075 9 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - Out of service CLOSE
OF19.VALVE.GLV.ILOCK.OOS_OPN 300075 10 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - Out of service OPEN
OF19.VALVE.GLV.ILOCK.OOS_CLS 300075 11 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - Out of service CLOSE
OF19.VALVE.GLV.ILOCK.CE_AMVPMV_OPN 300075 12 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - AMV and PMV are open - C&E 1a
OF19.VALVE.GLV.ILOCK.CE_XOVPWV_OPN 300075 13 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - XOV and PWV are open - C&E 1B
OF19.VALVE.GLV.ILOCK.CE_AMVXOV_OPN 300075 14 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - AMV and XOV are open - C&E 1C & 1D
OF19.VALVE.GLV.ILOCK.CE_EQUALIZE 300075 15 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - Equalize before opening - C&E 4a
OF19.VALVE.GLV.ILOCK.VALUE 300075 DWord RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word
OF19.VALVE.GLV.ILOCK.CE_PMVXOV_OPN 300076 0 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - PMV and XOV are open - C&E 1E

Page 25 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx OF19 19/04/2024

Validation Date Tag Name Address index Data Type Client Access Scan Rate Description
OF19.VALVE.GLV.ILOCK.CE_PWVAMV_OPN 300076 1 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - PWV and AMV not closed - C&E 1F
OF19.VALVE.GLV.ILOCK.CE_PCV_NOTCL 300076 2 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - PCV not closed - C&E 2
OF19.VALVE.GLV.ILOCK.CE_PMVPWV_NOTCL 300076 3 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - PMV or PWV not closed - C&E 4b
OF19.VALVE.GLV.ILOCK.CE_PWV_NOTCL 300076 4 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - PWV not closed - C&E 5
OF19.VALVE.GLV.ILOCK.CE_XOV_OPN 300076 5 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - XOV open - C&E 8
OF19.VALVE.GLV.ILOCK.CE_GLV_OPN 300076 6 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - GLV open - C&E 9
OF19.VALVE.GLV.ILOCK.CE_PMVPWV_NOTCL1 300076 9 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - PMV or PWV not Closed - C&E 4b
OF19.VALVE.GLV.ILOCK.CE_PWV_NOTCL1 300076 10 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - PWV not closed - C&E 6
OF19.VALVE.GLV.ILOCK.CE_PCVPWV_NOTCL 300076 11 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - PCV and PWV not closed - C&E 7a
OF19.VALVE.GLV.ILOCK.CE_PCVPMV_NOTCL 300076 12 Boolean RO 1000 OF19 Well Gas Lift Isolation Valve Interlock Word - PCV and PMV not Closed - C&E 7b
OF19.VALVE.PMV.STATUS.OPEN 300077 0 Boolean RO 1000 OF19 WELL PRODUCTION MASTER VALVE STATUS WORD - IS OPEN
OF19.VALVE.PMV.STATUS.CLOSED 300077 1 Boolean RO 1000 OF19 WELL PRODUCTION MASTER VALVE STATUS WORD - IS CLOSED
OF19.VALVE.PMV.STATUS.MOVING 300077 2 Boolean RO 1000 OF19 WELL PRODUCTION MASTER VALVE STATUS WORD - IS MOVING
OF19.VALVE.PMV.STATUS.ALM_DISC 300077 3 Boolean RO 1000 OF19 WELL PRODUCTION MASTER VALVE STATUS WORD - DISCREPENCY
OF19.VALVE.PMV.STATUS.ALM_FLTOMOV 300077 4 Boolean RO 1000 OF19 WELL PRODUCTION MASTER VALVE STATUS WORD - FAILED TO OPEN
OF19.VALVE.PMV.STATUS.ALM_FBIGNORE 300077 5 Boolean RO 1000 OF19 WELL PRODUCTION MASTER VALVE STATUS WORD - FEEDBACK IS IGNORED
OF19.VALVE.PMV.STATUS.OK_TO_OPN 300077 6 Boolean RO 1000 OF19 WELL PRODUCTION MASTER VALVE STATUS WORD - OK TO OPEN
OF19.VALVE.PMV.STATUS.OK_TO_CLS 300077 7 Boolean RO 1000 OF19 WELL PRODUCTION MASTER VALVE STATUS WORD - OK TO CLOSE
OF19.VALVE.PMV.STATUS.OPN_ILOCK_DFT 300077 8 Boolean RO 1000 OF19 WELL PRODUCTION MASTER VALVE STATUS WORD - OPEN ILOCK DEFEATABLE
OF19.VALVE.PMV.STATUS.CLS_ILOCK_DFT 300077 9 Boolean RO 1000 OF19 WELL PRODUCTION MASTER VALVE STATUS WORD - CLOSE ILOCK DEFEATABLE
OF19.VALVE.PMV.ILOCK.ROV_OPN 300078 0 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - ROV Override Open
OF19.VALVE.PMV.ILOCK.ROV_CLSD 300078 1 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - ROV Override Closed
OF19.VALVE.PMV.ILOCK.LPHDR_LO 300078 2 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - LP Header Low
OF19.VALVE.PMV.ILOCK.LPHDR_UNK 300078 3 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - LP Header Unknown
OF19.VALVE.PMV.ILOCK.LPHDR_OVR 300078 4 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - LP Header Override
OF19.VALVE.PMV.ILOCK.HPHDR_LO 300078 5 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - HP Header Low
OF19.VALVE.PMV.ILOCK.HPHDR_UNK 300078 6 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - HP Header Unkonwn
OF19.VALVE.PMV.ILOCK.HPHDR_OVR 300078 7 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - HP Header Override
OF19.VALVE.PMV.ILOCK.LPHPPRS_LO 300078 8 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - Out of service OPEN
OF19.VALVE.PMV.ILOCK.LPHPPRS_UNK 300078 9 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - Out of service CLOSE
OF19.VALVE.PMV.ILOCK.OOS_OPN 300078 10 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - Out of service OPEN
OF19.VALVE.PMV.ILOCK.OOS_CLS 300078 11 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - Out of service CLOSE
OF19.VALVE.PMV.ILOCK.CE_AMVPMV_OPN 300078 12 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - AMV and PMV are open - C&E 1a
OF19.VALVE.PMV.ILOCK.CE_XOVPWV_OPN 300078 13 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - XOV and PWV are open - C&E 1B
OF19.VALVE.PMV.ILOCK.CE_AMVXOV_OPN 300078 14 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - AMV and XOV are open - C&E 1C & 1D
OF19.VALVE.PMV.ILOCK.CE_EQUALIZE 300078 15 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - Equalize before opening - C&E 4a
OF19.VALVE.PMV.ILOCK.VALUE 300078 DWord RO 1000 OF19 Well Production Master Valve Interlock Word
OF19.VALVE.PMV.ILOCK.CE_PMVXOV_OPN 300079 0 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - PMV and XOV are open - C&E 1E
OF19.VALVE.PMV.ILOCK.CE_PWVAMV_OPN 300079 1 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - PWV and AMV not closed - C&E 1F
OF19.VALVE.PMV.ILOCK.CE_PCV_NOTCL 300079 2 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - PCV not closed - C&E 2
OF19.VALVE.PMV.ILOCK.CE_PMVPWV_NOTCL 300079 3 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - PMV or PWV not closed - C&E 4b
OF19.VALVE.PMV.ILOCK.CE_PWV_NOTCL 300079 4 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - PWV not closed - C&E 5
OF19.VALVE.PMV.ILOCK.CE_XOV_OPN 300079 5 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - XOV open - C&E 8
OF19.VALVE.PMV.ILOCK.CE_GLV_OPN 300079 6 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - GLV open - C&E 9
OF19.VALVE.PMV.ILOCK.CE_PMVPWV_NOTCL1 300079 9 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - PMV or PWV not Closed - C&E 4b
OF19.VALVE.PMV.ILOCK.CE_PWV_NOTCL1 300079 10 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - PWV not closed - C&E 6
OF19.VALVE.PMV.ILOCK.CE_PCVPWV_NOTCL 300079 11 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - PCV and PWV not closed - C&E 7a
OF19.VALVE.PMV.ILOCK.CE_PCVPMV_NOTCL 300079 12 Boolean RO 1000 OF19 Well Production Master Valve Interlock Word - PCV and PMV not Closed - C&E 7b
OF19.VALVE.PWV.STATUS.OPEN 300080 0 Boolean RO 1000 OF19 WELL PRODUCTION WING VALVE STATUS WORD - IS OPEN
OF19.VALVE.PWV.STATUS.CLOSED 300080 1 Boolean RO 1000 OF19 WELL PRODUCTION WING VALVE STATUS WORD - IS CLOSED
OF19.VALVE.PWV.STATUS.MOVING 300080 2 Boolean RO 1000 OF19 WELL PRODUCTION WING VALVE STATUS WORD - IS MOVING
OF19.VALVE.PWV.STATUS.ALM_DISC 300080 3 Boolean RO 1000 OF19 WELL PRODUCTION WING VALVE STATUS WORD - DISCREPENCY
OF19.VALVE.PWV.STATUS.ALM_FLTOMOV 300080 4 Boolean RO 1000 OF19 WELL PRODUCTION WING VALVE STATUS WORD - FAILED TO OPEN
OF19.VALVE.PWV.STATUS.ALM_FBIGNORE 300080 5 Boolean RO 1000 OF19 WELL PRODUCTION WING VALVE STATUS WORD - FEEDBACK IS IGNORED
OF19.VALVE.PWV.STATUS.OK_TO_OPN 300080 6 Boolean RO 1000 OF19 WELL PRODUCTION WING VALVE STATUS WORD - OK TO OPEN
OF19.VALVE.PWV.STATUS.OK_TO_CLS 300080 7 Boolean RO 1000 OF19 WELL PRODUCTION WING VALVE STATUS WORD - OK TO CLOSE
OF19.VALVE.PWV.STATUS.OPN_ILOCK_DFT 300080 8 Boolean RO 1000 OF19 WELL PRODUCTION WING VALVE STATUS WORD - OPEN ILOCK DEFEATABLE
OF19.VALVE.PWV.STATUS.CLS_ILOCK_DFT 300080 9 Boolean RO 1000 OF19 WELL PRODUCTION WING VALVE STATUS WORD - CLOSE ILOCK DEFEATABLE

Page 26 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx OF19 19/04/2024

Validation Date Tag Name Address index Data Type Client Access Scan Rate Description
OF19.VALVE.PWV.ILOCK.ROV_OPN 300081 0 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - ROV Override Open
OF19.VALVE.PWV.ILOCK.ROV_CLSD 300081 1 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - ROV Override Closed
OF19.VALVE.PWV.ILOCK.LPHDR_LO 300081 2 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - LP Header Low
OF19.VALVE.PWV.ILOCK.LPHDR_UNK 300081 3 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - LP Header Unknown
OF19.VALVE.PWV.ILOCK.LPHDR_OVR 300081 4 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - LP Header Override
OF19.VALVE.PWV.ILOCK.HPHDR_LO 300081 5 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - HP Header Low
OF19.VALVE.PWV.ILOCK.HPHDR_UNK 300081 6 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - HP Header Unkonwn
OF19.VALVE.PWV.ILOCK.HPHDR_OVR 300081 7 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - HP Header Override
OF19.VALVE.PWV.ILOCK.LPHPPRS_LO 300081 8 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - Out of service OPEN
OF19.VALVE.PWV.ILOCK.LPHPPRS_UNK 300081 9 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - Out of service CLOSE
OF19.VALVE.PWV.ILOCK.OOS_OPN 300081 10 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - Out of service OPEN
OF19.VALVE.PWV.ILOCK.OOS_CLS 300081 11 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - Out of service CLOSE
OF19.VALVE.PWV.ILOCK.CE_AMVPMV_OPN 300081 12 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - AMV and PMV are open - C&E 1a
OF19.VALVE.PWV.ILOCK.CE_XOVPWV_OPN 300081 13 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - XOV and PWV are open - C&E 1B
OF19.VALVE.PWV.ILOCK.CE_AMVXOV_OPN 300081 14 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - AMV and XOV are open - C&E 1C & 1D
OF19.VALVE.PWV.ILOCK.CE_EQUALIZE 300081 15 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - Equalize before opening - C&E 4a
OF19.VALVE.PWV.ILOCK.VALUE 300081 DWord RO 1000 OF19 Well Production Wing Valve Interlock Word
OF19.VALVE.PWV.ILOCK.CE_PMVXOV_OPN 300082 0 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - PMV and XOV are open - C&E 1E
OF19.VALVE.PWV.ILOCK.CE_PWVAMV_OPN 300082 1 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - PWV and AMV not closed - C&E 1F
OF19.VALVE.PWV.ILOCK.CE_PCV_NOTCL 300082 2 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - PCV not closed - C&E 2
OF19.VALVE.PWV.ILOCK.CE_PMVPWV_NOTCL 300082 3 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - PMV or PWV not closed - C&E 4b
OF19.VALVE.PWV.ILOCK.CE_PWV_NOTCL 300082 4 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - PWV not closed - C&E 5
OF19.VALVE.PWV.ILOCK.CE_XOV_OPN 300082 5 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - XOV open - C&E 8
OF19.VALVE.PWV.ILOCK.CE_GLV_OPN 300082 6 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - GLV open - C&E 9
OF19.VALVE.PWV.ILOCK.CE_PMVPWV_NOTCL1 300082 9 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - PMV or PWV not Closed - C&E 4b
OF19.VALVE.PWV.ILOCK.CE_PWV_NOTCL1 300082 10 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - PWV not closed - C&E 6
OF19.VALVE.PWV.ILOCK.CE_PCVPWV_NOTCL 300082 11 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - PCV and PWV not closed - C&E 7a
OF19.VALVE.PWV.ILOCK.CE_PCVPMV_NOTCL 300082 12 Boolean RO 1000 OF19 Well Production Wing Valve Interlock Word - PCV and PMV not Closed - C&E 7b
OF19.VALVE.SCSSV.STATUS.OPEN 300083 0 Boolean RO 1000 OF19 WELL DOWNHOLE SAFETY VALVE (SCSSV) STATUS WORD - IS OPEN
OF19.VALVE.SCSSV.STATUS.CLOSED 300083 1 Boolean RO 1000 OF19 WELL DOWNHOLE SAFETY VALVE (SCSSV) STATUS WORD - IS CLOSED
OF19.VALVE.SCSSV.STATUS.MOVING 300083 2 Boolean RO 1000 OF19 WELL DOWNHOLE SAFETY VALVE (SCSSV) STATUS WORD - IS MOVING
OF19.VALVE.SCSSV.STATUS.ALM_DISC 300083 3 Boolean RO 1000 OF19 WELL DOWNHOLE SAFETY VALVE (SCSSV) STATUS WORD - DISCREPENCY
OF19.VALVE.SCSSV.STATUS.ALM_FLTOMOV 300083 4 Boolean RO 1000 OF19 WELL DOWNHOLE SAFETY VALVE (SCSSV) STATUS WORD - FAILED TO OPEN
OF19.VALVE.SCSSV.STATUS.ALM_FBIGNORE 300083 5 Boolean RO 1000 OF19 WELL DOWNHOLE SAFETY VALVE (SCSSV) STATUS WORD - FEEDBACK IS IGNORED
OF19.VALVE.SCSSV.STATUS.OK_TO_OPN 300083 6 Boolean RO 1000 OF19 WELL DOWNHOLE SAFETY VALVE (SCSSV) STATUS WORD - OK TO OPEN
OF19.VALVE.SCSSV.STATUS.OK_TO_CLS 300083 7 Boolean RO 1000 OF19 WELL DOWNHOLE SAFETY VALVE (SCSSV) STATUS WORD - OK TO CLOSE
OF19.VALVE.SCSSV.STATUS.OPN_ILOCK_DFT 300083 8 Boolean RO 1000 OF19 WELL DOWNHOLE SAFETY VALVE (SCSSV) STATUS WORD - OPEN ILOCK DEFEATABLE
OF19.VALVE.SCSSV.STATUS.CLS_ILOCK_DFT 300083 9 Boolean RO 1000 OF19 WELL DOWNHOLE SAFETY VALVE (SCSSV) STATUS WORD - CLOSE ILOCK DEFEATABLE
OF19.VALVE.SCSSV.ILOCK.ROV_OPN 300084 0 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - ROV Override Open
OF19.VALVE.SCSSV.ILOCK.ROV_CLSD 300084 1 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - ROV Override Closed
OF19.VALVE.SCSSV.ILOCK.LPHDR_LO 300084 2 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - LP Header Low
OF19.VALVE.SCSSV.ILOCK.LPHDR_UNK 300084 3 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - LP Header Unknown
OF19.VALVE.SCSSV.ILOCK.LPHDR_OVR 300084 4 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - LP Header Override
OF19.VALVE.SCSSV.ILOCK.HPHDR_LO 300084 5 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - HP Header Low
OF19.VALVE.SCSSV.ILOCK.HPHDR_UNK 300084 6 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - HP Header Unkonwn
OF19.VALVE.SCSSV.ILOCK.HPHDR_OVR 300084 7 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - HP Header Override
OF19.VALVE.SCSSV.ILOCK.LPHPPRS_LO 300084 8 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - Out of service OPEN
OF19.VALVE.SCSSV.ILOCK.LPHPPRS_UNK 300084 9 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - Out of service CLOSE
OF19.VALVE.SCSSV.ILOCK.OOS_OPN 300084 10 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - Out of service OPEN
OF19.VALVE.SCSSV.ILOCK.OOS_CLS 300084 11 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - Out of service CLOSE
OF19.VALVE.SCSSV.ILOCK.CE_AMVPMV_OPN 300084 12 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - AMV and PMV are open - C&E 1a
OF19.VALVE.SCSSV.ILOCK.CE_XOVPWV_OPN 300084 13 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - XOV and PWV are open - C&E 1B
OF19.VALVE.SCSSV.ILOCK.CE_AMVXOV_OPN 300084 14 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - AMV and XOV are open - C&E 1C & 1D
OF19.VALVE.SCSSV.ILOCK.CE_EQUALIZE 300084 15 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - Equalize before opening - C&E 4a
OF19.VALVE.SCSSV.ILOCK.VALUE 300084 DWord RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word
OF19.VALVE.SCSSV.ILOCK.CE_PMVXOV_OPN 300085 0 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - PMV and XOV are open - C&E 1E
OF19.VALVE.SCSSV.ILOCK.CE_PWVAMV_OPN 300085 1 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - PWV and AMV not closed - C&E 1F
OF19.VALVE.SCSSV.ILOCK.CE_PCV_NOTCL 300085 2 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - PCV not closed - C&E 2

Page 27 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx OF19 19/04/2024

Validation Date Tag Name Address index Data Type Client Access Scan Rate Description
OF19.VALVE.SCSSV.ILOCK.CE_PMVPWV_NOTCL 300085 3 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - PMV or PWV not closed - C&E 4b
OF19.VALVE.SCSSV.ILOCK.CE_PWV_NOTCL 300085 4 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - PWV not closed - C&E 5
OF19.VALVE.SCSSV.ILOCK.CE_XOV_OPN 300085 5 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - XOV open - C&E 8
OF19.VALVE.SCSSV.ILOCK.CE_GLV_OPN 300085 6 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - GLV open - C&E 9
OF19.VALVE.SCSSV.ILOCK.CE_PMVPWV_NOTCL1 300085 9 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - PMV or PWV not Closed - C&E 4b
OF19.VALVE.SCSSV.ILOCK.CE_PWV_NOTCL1 300085 10 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - PWV not closed - C&E 6
OF19.VALVE.SCSSV.ILOCK.CE_PCVPWV_NOTCL 300085 11 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - PCV and PWV not closed - C&E 7a
OF19.VALVE.SCSSV.ILOCK.CE_PCVPMV_NOTCL 300085 12 Boolean RO 1000 OF19 Well Downhole Safety Valve (SCSSV) Interlock Word - PCV and PMV not Closed - C&E 7b
OF19.VALVE.XOV.STATUS.OPEN 300086 0 Boolean RO 1000 OF19 WELL CROSSOVER VALVE STATUS WORD - IS OPEN
OF19.VALVE.XOV.STATUS.CLOSED 300086 1 Boolean RO 1000 OF19 WELL CROSSOVER VALVE STATUS WORD - IS CLOSED
OF19.VALVE.XOV.STATUS.MOVING 300086 2 Boolean RO 1000 OF19 WELL CROSSOVER VALVE STATUS WORD - IS MOVING
OF19.VALVE.XOV.STATUS.ALM_DISC 300086 3 Boolean RO 1000 OF19 WELL CROSSOVER VALVE STATUS WORD - DISCREPENCY
OF19.VALVE.XOV.STATUS.ALM_FLTOMOV 300086 4 Boolean RO 1000 OF19 WELL CROSSOVER VALVE STATUS WORD - FAILED TO OPEN
OF19.VALVE.XOV.STATUS.ALM_FBIGNORE 300086 5 Boolean RO 1000 OF19 WELL CROSSOVER VALVE STATUS WORD - FEEDBACK IS IGNORED
OF19.VALVE.XOV.STATUS.OK_TO_OPN 300086 6 Boolean RO 1000 OF19 WELL CROSSOVER VALVE STATUS WORD - OK TO OPEN
OF19.VALVE.XOV.STATUS.OK_TO_CLS 300086 7 Boolean RO 1000 OF19 WELL CROSSOVER VALVE STATUS WORD - OK TO CLOSE
OF19.VALVE.XOV.STATUS.OPN_ILOCK_DFT 300086 8 Boolean RO 1000 OF19 WELL CROSSOVER VALVE STATUS WORD - OPEN ILOCK DEFEATABLE
OF19.VALVE.XOV.STATUS.CLS_ILOCK_DFT 300086 9 Boolean RO 1000 OF19 WELL CROSSOVER VALVE STATUS WORD - CLOSE ILOCK DEFEATABLE
OF19.VALVE.XOV.ILOCK.ROV_OPN 300087 0 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - ROV Override Open
OF19.VALVE.XOV.ILOCK.ROV_CLSD 300087 1 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - ROV Override Closed
OF19.VALVE.XOV.ILOCK.LPHDR_LO 300087 2 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - LP Header Low
OF19.VALVE.XOV.ILOCK.LPHDR_UNK 300087 3 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - LP Header Unknown
OF19.VALVE.XOV.ILOCK.LPHDR_OVR 300087 4 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - LP Header Override
OF19.VALVE.XOV.ILOCK.HPHDR_LO 300087 5 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - HP Header Low
OF19.VALVE.XOV.ILOCK.HPHDR_UNK 300087 6 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - HP Header Unkonwn
OF19.VALVE.XOV.ILOCK.HPHDR_OVR 300087 7 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - HP Header Override
OF19.VALVE.XOV.ILOCK.LPHPPRS_LO 300087 8 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - Out of service OPEN
OF19.VALVE.XOV.ILOCK.LPHPPRS_UNK 300087 9 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - Out of service CLOSE
OF19.VALVE.XOV.ILOCK.OOS_OPN 300087 10 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - Out of service OPEN
OF19.VALVE.XOV.ILOCK.OOS_CLS 300087 11 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - Out of service CLOSE
OF19.VALVE.XOV.ILOCK.CE_AMVPMV_OPN 300087 12 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - AMV and PMV are open - C&E 1a
OF19.VALVE.XOV.ILOCK.CE_XOVPWV_OPN 300087 13 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - XOV and PWV are open - C&E 1B
OF19.VALVE.XOV.ILOCK.CE_AMVXOV_OPN 300087 14 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - AMV and XOV are open - C&E 1C & 1D
OF19.VALVE.XOV.ILOCK.CE_EQUALIZE 300087 15 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - Equalize before opening - C&E 4a
OF19.VALVE.XOV.ILOCK.VALUE 300087 DWord RO 1000 OF19 Well Crossover Valve Interlock Word
OF19.VALVE.XOV.ILOCK.CE_PMVXOV_OPN 300088 0 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - PMV and XOV are open - C&E 1E
OF19.VALVE.XOV.ILOCK.CE_PWVAMV_OPN 300088 1 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - PWV and AMV not closed - C&E 1F
OF19.VALVE.XOV.ILOCK.CE_PCV_NOTCL 300088 2 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - PCV not closed - C&E 2
OF19.VALVE.XOV.ILOCK.CE_PMVPWV_NOTCL 300088 3 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - PMV or PWV not closed - C&E 4b
OF19.VALVE.XOV.ILOCK.CE_PWV_NOTCL 300088 4 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - PWV not closed - C&E 5
OF19.VALVE.XOV.ILOCK.CE_XOV_OPN 300088 5 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - XOV open - C&E 8
OF19.VALVE.XOV.ILOCK.CE_GLV_OPN 300088 6 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - GLV open - C&E 9
OF19.VALVE.XOV.ILOCK.CE_PMVPWV_NOTCL1 300088 9 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - PMV or PWV not Closed - C&E 4b
OF19.VALVE.XOV.ILOCK.CE_PWV_NOTCL1 300088 10 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - PWV not closed - C&E 6
OF19.VALVE.XOV.ILOCK.CE_PCVPWV_NOTCL 300088 11 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - PCV and PWV not closed - C&E 7a
OF19.VALVE.XOV.ILOCK.CE_PCVPMV_NOTCL 300088 12 Boolean RO 1000 OF19 Well Crossover Valve Interlock Word - PCV and PMV not Closed - C&E 7b
OF19.VALVE.AAV.STATUS.OPEN 300089 0 Boolean RO 1000 OF19 WELL ANNULUS AUXILARY VALVE STATUS WORD - IS OPEN
OF19.VALVE.AAV.STATUS.CLOSED 300089 1 Boolean RO 1000 OF19 WELL ANNULUS AUXILARY VALVE STATUS WORD - IS CLOSED
OF19.VALVE.AAV.STATUS.MOVING 300089 2 Boolean RO 1000 OF19 WELL ANNULUS AUXILARY VALVE STATUS WORD - IS MOVING
OF19.VALVE.AAV.STATUS.ALM_DISC 300089 3 Boolean RO 1000 OF19 WELL ANNULUS AUXILARY VALVE STATUS WORD - DISCREPENCY
OF19.VALVE.AAV.STATUS.ALM_FLTOMOV 300089 4 Boolean RO 1000 OF19 WELL ANNULUS AUXILARY VALVE STATUS WORD - FAILED TO OPEN
OF19.VALVE.AAV.STATUS.ALM_FBIGNORE 300089 5 Boolean RO 1000 OF19 WELL ANNULUS AUXILARY VALVE STATUS WORD - FEEDBACK IS IGNORED
OF19.VALVE.AAV.STATUS.OK_TO_OPN 300089 6 Boolean RO 1000 OF19 WELL ANNULUS AUXILARY VALVE STATUS WORD - OK TO OPEN
OF19.VALVE.AAV.STATUS.OK_TO_CLS 300089 7 Boolean RO 1000 OF19 WELL ANNULUS AUXILARY VALVE STATUS WORD - OK TO CLOSE
OF19.VALVE.AAV.STATUS.OPN_ILOCK_DFT 300089 8 Boolean RO 1000 OF19 WELL ANNULUS AUXILARY VALVE STATUS WORD - OPEN ILOCK DEFEATABLE
OF19.VALVE.AAV.STATUS.CLS_ILOCK_DFT 300089 9 Boolean RO 1000 OF19 WELL ANNULUS AUXILARY VALVE STATUS WORD - CLOSE ILOCK DEFEATABLE
OF19.VALVE.AAV.ILOCK.ROV_OPN 300090 0 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - ROV Override Open
OF19.VALVE.AAV.ILOCK.ROV_CLSD 300090 1 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - ROV Override Closed

Page 28 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx OF19 19/04/2024

Validation Date Tag Name Address index Data Type Client Access Scan Rate Description
OF19.VALVE.AAV.ILOCK.LPHDR_LO 300090 2 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - LP Header Low
OF19.VALVE.AAV.ILOCK.LPHDR_UNK 300090 3 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - LP Header Unknown
OF19.VALVE.AAV.ILOCK.LPHDR_OVR 300090 4 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - LP Header Override
OF19.VALVE.AAV.ILOCK.HPHDR_LO 300090 5 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - HP Header Low
OF19.VALVE.AAV.ILOCK.HPHDR_UNK 300090 6 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - HP Header Unkonwn
OF19.VALVE.AAV.ILOCK.HPHDR_OVR 300090 7 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - HP Header Override
OF19.VALVE.AAV.ILOCK.LPHPPRS_LO 300090 8 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - Out of service OPEN
OF19.VALVE.AAV.ILOCK.LPHPPRS_UNK 300090 9 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - Out of service CLOSE
OF19.VALVE.AAV.ILOCK.OOS_OPN 300090 10 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - Out of service OPEN
OF19.VALVE.AAV.ILOCK.OOS_CLS 300090 11 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - Out of service CLOSE
OF19.VALVE.AAV.ILOCK.CE_AMVPMV_OPN 300090 12 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - AMV and PMV are open - C&E 1a
OF19.VALVE.AAV.ILOCK.CE_XOVPWV_OPN 300090 13 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - XOV and PWV are open - C&E 1B
OF19.VALVE.AAV.ILOCK.CE_AMVXOV_OPN 300090 14 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - AMV and XOV are open - C&E 1C & 1D
OF19.VALVE.AAV.ILOCK.CE_EQUALIZE 300090 15 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - Equalize before opening - C&E 4a
OF19.VALVE.AAV.ILOCK.VALUE 300090 DWord RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word
OF19.VALVE.AAV.ILOCK.CE_PMVXOV_OPN 300091 0 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - PMV and XOV are open - C&E 1E
OF19.VALVE.AAV.ILOCK.CE_PWVAMV_OPN 300091 1 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - PWV and AMV not closed - C&E 1F
OF19.VALVE.AAV.ILOCK.CE_PCV_NOTCL 300091 2 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - PCV not closed - C&E 2
OF19.VALVE.AAV.ILOCK.CE_PMVPWV_NOTCL 300091 3 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - PMV or PWV not closed - C&E 4b
OF19.VALVE.AAV.ILOCK.CE_PWV_NOTCL 300091 4 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - PWV not closed - C&E 5
OF19.VALVE.AAV.ILOCK.CE_XOV_OPN 300091 5 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - XOV open - C&E 8
OF19.VALVE.AAV.ILOCK.CE_GLV_OPN 300091 6 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - GLV open - C&E 9
OF19.VALVE.AAV.ILOCK.CE_PMVPWV_NOTCL1 300091 9 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - PMV or PWV not Closed - C&E 4b
OF19.VALVE.AAV.ILOCK.CE_PWV_NOTCL1 300091 10 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - PWV not closed - C&E 6
OF19.VALVE.AAV.ILOCK.CE_PCVPWV_NOTCL 300091 11 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - PCV and PWV not closed - C&E 7a
OF19.VALVE.AAV.ILOCK.CE_PCVPMV_NOTCL 300091 12 Boolean RO 1000 OF19 Well Annulus Auxilary Valve Interlock Word - PCV and PMV not Closed - C&E 7b
OF19.VALVE.AWV.STATUS.OPEN 300092 0 Boolean RO 1000 OF19 WELL ANNULUS WING VALVE STATUS WORD - IS OPEN
OF19.VALVE.AWV.STATUS.CLOSED 300092 1 Boolean RO 1000 OF19 WELL ANNULUS WING VALVE STATUS WORD - IS CLOSED
OF19.VALVE.AWV.STATUS.MOVING 300092 2 Boolean RO 1000 OF19 WELL ANNULUS WING VALVE STATUS WORD - IS MOVING
OF19.VALVE.AWV.STATUS.ALM_DISC 300092 3 Boolean RO 1000 OF19 WELL ANNULUS WING VALVE STATUS WORD - DISCREPENCY
OF19.VALVE.AWV.STATUS.ALM_FLTOMOV 300092 4 Boolean RO 1000 OF19 WELL ANNULUS WING VALVE STATUS WORD - FAILED TO OPEN
OF19.VALVE.AWV.STATUS.ALM_FBIGNORE 300092 5 Boolean RO 1000 OF19 WELL ANNULUS WING VALVE STATUS WORD - FEEDBACK IS IGNORED
OF19.VALVE.AWV.STATUS.OK_TO_OPN 300092 6 Boolean RO 1000 OF19 WELL ANNULUS WING VALVE STATUS WORD - OK TO OPEN
OF19.VALVE.AWV.STATUS.OK_TO_CLS 300092 7 Boolean RO 1000 OF19 WELL ANNULUS WING VALVE STATUS WORD - OK TO CLOSE
OF19.VALVE.AWV.STATUS.OPN_ILOCK_DFT 300092 8 Boolean RO 1000 OF19 WELL ANNULUS WING VALVE STATUS WORD - OPEN ILOCK DEFEATABLE
OF19.VALVE.AWV.STATUS.CLS_ILOCK_DFT 300092 9 Boolean RO 1000 OF19 WELL ANNULUS WING VALVE STATUS WORD - CLOSE ILOCK DEFEATABLE
OF19.VALVE.AWV.ILOCK.ROV_OPN 300093 0 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - ROV Override Open
OF19.VALVE.AWV.ILOCK.ROV_CLSD 300093 1 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - ROV Override Closed
OF19.VALVE.AWV.ILOCK.LPHDR_LO 300093 2 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - LP Header Low
OF19.VALVE.AWV.ILOCK.LPHDR_UNK 300093 3 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - LP Header Unknown
OF19.VALVE.AWV.ILOCK.LPHDR_OVR 300093 4 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - LP Header Override
OF19.VALVE.AWV.ILOCK.HPHDR_LO 300093 5 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - HP Header Low
OF19.VALVE.AWV.ILOCK.HPHDR_UNK 300093 6 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - HP Header Unkonwn
OF19.VALVE.AWV.ILOCK.HPHDR_OVR 300093 7 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - HP Header Override
OF19.VALVE.AWV.ILOCK.LPHPPRS_LO 300093 8 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - Out of service OPEN
OF19.VALVE.AWV.ILOCK.LPHPPRS_UNK 300093 9 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - Out of service CLOSE
OF19.VALVE.AWV.ILOCK.OOS_OPN 300093 10 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - Out of service OPEN
OF19.VALVE.AWV.ILOCK.OOS_CLS 300093 11 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - Out of service CLOSE
OF19.VALVE.AWV.ILOCK.CE_AMVPMV_OPN 300093 12 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - AMV and PMV are open - C&E 1a
OF19.VALVE.AWV.ILOCK.CE_XOVPWV_OPN 300093 13 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - XOV and PWV are open - C&E 1B
OF19.VALVE.AWV.ILOCK.CE_AMVXOV_OPN 300093 14 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - AMV and XOV are open - C&E 1C & 1D
OF19.VALVE.AWV.ILOCK.CE_EQUALIZE 300093 15 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - Equalize before opening - C&E 4a
OF19.VALVE.AWV.ILOCK.VALUE 300093 DWord RO 1000 OF19 Well Annulus Wing Valve Interlock Word
OF19.VALVE.AWV.ILOCK.CE_PMVXOV_OPN 300094 0 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - PMV and XOV are open - C&E 1E
OF19.VALVE.AWV.ILOCK.CE_PWVAMV_OPN 300094 1 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - PWV and AMV not closed - C&E 1F
OF19.VALVE.AWV.ILOCK.CE_PCV_NOTCL 300094 2 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - PCV not closed - C&E 2
OF19.VALVE.AWV.ILOCK.CE_PMVPWV_NOTCL 300094 3 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - PMV or PWV not closed - C&E 4b
OF19.VALVE.AWV.ILOCK.CE_PWV_NOTCL 300094 4 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - PWV not closed - C&E 5

Page 29 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx OF19 19/04/2024

Validation Date Tag Name Address index Data Type Client Access Scan Rate Description
OF19.VALVE.AWV.ILOCK.CE_XOV_OPN 300094 5 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - XOV open - C&E 8
OF19.VALVE.AWV.ILOCK.CE_GLV_OPN 300094 6 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - GLV open - C&E 9
OF19.VALVE.AWV.ILOCK.CE_PMVPWV_NOTCL1 300094 9 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - PMV or PWV not Closed - C&E 4b
OF19.VALVE.AWV.ILOCK.CE_PWV_NOTCL1 300094 10 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - PWV not closed - C&E 6
OF19.VALVE.AWV.ILOCK.CE_PCVPWV_NOTCL 300094 11 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - PCV and PWV not closed - C&E 7a
OF19.VALVE.AWV.ILOCK.CE_PCVPMV_NOTCL 300094 12 Boolean RO 1000 OF19 Well Annulus Wing Valve Interlock Word - PCV and PMV not Closed - C&E 7b
OF19.VALVE.CIDV.STATUS.OPEN 300095 0 Boolean RO 1000 OF19 WELL DOWNHOLE CHEMICAL INJECTION VALVE STATUS WORD - IS OPEN
OF19.VALVE.CIDV.STATUS.CLOSED 300095 1 Boolean RO 1000 OF19 WELL DOWNHOLE CHEMICAL INJECTION VALVE STATUS WORD - IS CLOSED
OF19.VALVE.CIDV.STATUS.MOVING 300095 2 Boolean RO 1000 OF19 WELL DOWNHOLE CHEMICAL INJECTION VALVE STATUS WORD - IS MOVING
OF19.VALVE.CIDV.STATUS.ALM_DISC 300095 3 Boolean RO 1000 OF19 WELL DOWNHOLE CHEMICAL INJECTION VALVE STATUS WORD - DISCREPENCY
OF19.VALVE.CIDV.STATUS.ALM_FLTOMOV 300095 4 Boolean RO 1000 OF19 WELL DOWNHOLE CHEMICAL INJECTION VALVE STATUS WORD - FAILED TO OPEN
OF19.VALVE.CIDV.STATUS.ALM_FBIGNORE 300095 5 Boolean RO 1000 OF19 WELL DOWNHOLE CHEMICAL INJECTION VALVE STATUS WORD - FEEDBACK IS IGNORED
OF19.VALVE.CIDV.STATUS.OK_TO_OPN 300095 6 Boolean RO 1000 OF19 WELL DOWNHOLE CHEMICAL INJECTION VALVE STATUS WORD - OK TO OPEN
OF19.VALVE.CIDV.STATUS.OK_TO_CLS 300095 7 Boolean RO 1000 OF19 WELL DOWNHOLE CHEMICAL INJECTION VALVE STATUS WORD - OK TO CLOSE
OF19.VALVE.CIDV.STATUS.OPN_ILOCK_DFT 300095 8 Boolean RO 1000 OF19 WELL DOWNHOLE CHEMICAL INJECTION VALVE STATUS WORD - OPEN ILOCK DEFEATABLE
OF19.VALVE.CIDV.STATUS.CLS_ILOCK_DFT 300095 9 Boolean RO 1000 OF19 WELL DOWNHOLE CHEMICAL INJECTION VALVE STATUS WORD - CLOSE ILOCK DEFEATABLE
OF19.VALVE.CIDV.ILOCK.ROV_OPN 300096 0 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - ROV Override Open
OF19.VALVE.CIDV.ILOCK.ROV_CLSD 300096 1 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - ROV Override Closed
OF19.VALVE.CIDV.ILOCK.LPHDR_LO 300096 2 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - LP Header Low
OF19.VALVE.CIDV.ILOCK.LPHDR_UNK 300096 3 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - LP Header Unknown
OF19.VALVE.CIDV.ILOCK.LPHDR_OVR 300096 4 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - LP Header Override
OF19.VALVE.CIDV.ILOCK.HPHDR_LO 300096 5 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - HP Header Low
OF19.VALVE.CIDV.ILOCK.HPHDR_UNK 300096 6 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - HP Header Unkonwn
OF19.VALVE.CIDV.ILOCK.HPHDR_OVR 300096 7 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - HP Header Override
OF19.VALVE.CIDV.ILOCK.LPHPPRS_LO 300096 8 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - Out of service OPEN
OF19.VALVE.CIDV.ILOCK.LPHPPRS_UNK 300096 9 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - Out of service CLOSE
OF19.VALVE.CIDV.ILOCK.OOS_OPN 300096 10 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - Out of service OPEN
OF19.VALVE.CIDV.ILOCK.OOS_CLS 300096 11 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - Out of service CLOSE
OF19.VALVE.CIDV.ILOCK.CE_AMVPMV_OPN 300096 12 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - AMV and PMV are open - C&E 1a
OF19.VALVE.CIDV.ILOCK.CE_XOVPWV_OPN 300096 13 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - XOV and PWV are open - C&E 1B
OF19.VALVE.CIDV.ILOCK.CE_AMVXOV_OPN 300096 14 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - AMV and XOV are open - C&E 1C & 1D
OF19.VALVE.CIDV.ILOCK.CE_EQUALIZE 300096 15 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - Equalize before opening - C&E 4a
OF19.VALVE.CIDV.ILOCK.VALUE 300096 DWord RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word
OF19.VALVE.CIDV.ILOCK.CE_PMVXOV_OPN 300097 0 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - PMV and XOV are open - C&E 1E
OF19.VALVE.CIDV.ILOCK.CE_PWVAMV_OPN 300097 1 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - PWV and AMV not closed - C&E 1F
OF19.VALVE.CIDV.ILOCK.CE_PCV_NOTCL 300097 2 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - PCV not closed - C&E 2
OF19.VALVE.CIDV.ILOCK.CE_PMVPWV_NOTCL 300097 3 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - PMV or PWV not closed - C&E 4b
OF19.VALVE.CIDV.ILOCK.CE_PWV_NOTCL 300097 4 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - PWV not closed - C&E 5
OF19.VALVE.CIDV.ILOCK.CE_XOV_OPN 300097 5 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - XOV open - C&E 8
OF19.VALVE.CIDV.ILOCK.CE_GLV_OPN 300097 6 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - GLV open - C&E 9
OF19.VALVE.CIDV.ILOCK.CE_PMVPWV_NOTCL1 300097 9 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - PMV or PWV not Closed - C&E 4b
OF19.VALVE.CIDV.ILOCK.CE_PWV_NOTCL1 300097 10 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - PWV not closed - C&E 6
OF19.VALVE.CIDV.ILOCK.CE_PCVPWV_NOTCL 300097 11 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - PCV and PWV not closed - C&E 7a
OF19.VALVE.CIDV.ILOCK.CE_PCVPMV_NOTCL 300097 12 Boolean RO 1000 OF19 Well Downhole Chemical Injection Valve Interlock Word - PCV and PMV not Closed - C&E 7b
OF19.VALVE.CITV1.STATUS.OPEN 300098 0 Boolean RO 1000 OF19 WELL TOPSIDE CHEMICAL INJECTION VALVE #1 STATUS WORD - IS OPEN
OF19.VALVE.CITV1.STATUS.CLOSED 300098 1 Boolean RO 1000 OF19 WELL TOPSIDE CHEMICAL INJECTION VALVE #1 STATUS WORD - IS CLOSED
OF19.VALVE.CITV1.STATUS.MOVING 300098 2 Boolean RO 1000 OF19 WELL TOPSIDE CHEMICAL INJECTION VALVE #1 STATUS WORD - IS MOVING
OF19.VALVE.CITV1.STATUS.ALM_DISC 300098 3 Boolean RO 1000 OF19 WELL TOPSIDE CHEMICAL INJECTION VALVE #1 STATUS WORD - DISCREPENCY
OF19.VALVE.CITV1.STATUS.ALM_FLTOMOV 300098 4 Boolean RO 1000 OF19 WELL TOPSIDE CHEMICAL INJECTION VALVE #1 STATUS WORD - FAILED TO OPEN
OF19.VALVE.CITV1.STATUS.ALM_FBIGNORE 300098 5 Boolean RO 1000 OF19 WELL TOPSIDE CHEMICAL INJECTION VALVE #1 STATUS WORD - FEEDBACK IS IGNORED
OF19.VALVE.CITV1.STATUS.OK_TO_OPN 300098 6 Boolean RO 1000 OF19 WELL TOPSIDE CHEMICAL INJECTION VALVE #1 STATUS WORD - OK TO OPEN
OF19.VALVE.CITV1.STATUS.OK_TO_CLS 300098 7 Boolean RO 1000 OF19 WELL TOPSIDE CHEMICAL INJECTION VALVE #1 STATUS WORD - OK TO CLOSE
OF19.VALVE.CITV1.STATUS.OPN_ILOCK_DFT 300098 8 Boolean RO 1000 OF19 WELL TOPSIDE CHEMICAL INJECTION VALVE #1 STATUS WORD - OPEN ILOCK DEFEATABLE
OF19.VALVE.CITV1.STATUS.CLS_ILOCK_DFT 300098 9 Boolean RO 1000 OF19 WELL TOPSIDE CHEMICAL INJECTION VALVE #1 STATUS WORD - CLOSE ILOCK DEFEATABLE
OF19.VALVE.CITV1.ILOCK.ROV_OPN 300099 0 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - ROV Override Open
OF19.VALVE.CITV1.ILOCK.ROV_CLSD 300099 1 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - ROV Override Closed
OF19.VALVE.CITV1.ILOCK.LPHDR_LO 300099 2 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - LP Header Low
OF19.VALVE.CITV1.ILOCK.LPHDR_UNK 300099 3 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - LP Header Unknown

Page 30 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx OF19 19/04/2024

Validation Date Tag Name Address index Data Type Client Access Scan Rate Description
OF19.VALVE.CITV1.ILOCK.LPHDR_OVR 300099 4 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - LP Header Override
OF19.VALVE.CITV1.ILOCK.HPHDR_LO 300099 5 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - HP Header Low
OF19.VALVE.CITV1.ILOCK.HPHDR_UNK 300099 6 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - HP Header Unkonwn
OF19.VALVE.CITV1.ILOCK.HPHDR_OVR 300099 7 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - HP Header Override
OF19.VALVE.CITV1.ILOCK.LPHPPRS_LO 300099 8 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - Out of service OPEN
OF19.VALVE.CITV1.ILOCK.LPHPPRS_UNK 300099 9 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - Out of service CLOSE
OF19.VALVE.CITV1.ILOCK.OOS_OPN 300099 10 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - Out of service OPEN
OF19.VALVE.CITV1.ILOCK.OOS_CLS 300099 11 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - Out of service CLOSE
OF19.VALVE.CITV1.ILOCK.CE_AMVPMV_OPN 300099 12 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - AMV and PMV are open - C&E 1a
OF19.VALVE.CITV1.ILOCK.CE_XOVPWV_OPN 300099 13 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - XOV and PWV are open - C&E 1B
OF19.VALVE.CITV1.ILOCK.CE_AMVXOV_OPN 300099 14 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - AMV and XOV are open - C&E 1C & 1D
OF19.VALVE.CITV1.ILOCK.CE_EQUALIZE 300099 15 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - Equalize before opening - C&E 4a
OF19.VALVE.CITV1.ILOCK.VALUE 300099 DWord RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word
OF19.VALVE.CITV1.ILOCK.CE_PMVXOV_OPN 300100 0 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - PMV and XOV are open - C&E 1E
OF19.VALVE.CITV1.ILOCK.CE_PWVAMV_OPN 300100 1 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - PWV and AMV not closed - C&E 1F
OF19.VALVE.CITV1.ILOCK.CE_PCV_NOTCL 300100 2 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - PCV not closed - C&E 2
OF19.VALVE.CITV1.ILOCK.CE_PMVPWV_NOTCL 300100 3 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - PMV or PWV not closed - C&E 4b
OF19.VALVE.CITV1.ILOCK.CE_PWV_NOTCL 300100 4 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - PWV not closed - C&E 5
OF19.VALVE.CITV1.ILOCK.CE_XOV_OPN 300100 5 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - XOV open - C&E 8
OF19.VALVE.CITV1.ILOCK.CE_GLV_OPN 300100 6 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - GLV open - C&E 9
OF19.VALVE.CITV1.ILOCK.CE_PMVPWV_NOTCL1 300100 9 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - PMV or PWV not Closed - C&E 4b
OF19.VALVE.CITV1.ILOCK.CE_PWV_NOTCL1 300100 10 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - PWV not closed - C&E 6
OF19.VALVE.CITV1.ILOCK.CE_PCVPWV_NOTCL 300100 11 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - PCV and PWV not closed - C&E 7a
OF19.VALVE.CITV1.ILOCK.CE_PCVPMV_NOTCL 300100 12 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #1 Interlock Word - PCV and PMV not Closed - C&E 7b
OF19.VALVE.CITV2.STATUS.OPEN 300101 0 Boolean RO 1000 OF19 WELL TOPSIDE CHEMICAL INJECTION VALVE #2 STATUS WORD - IS OPEN
OF19.VALVE.CITV2.STATUS.CLOSED 300101 1 Boolean RO 1000 OF19 WELL TOPSIDE CHEMICAL INJECTION VALVE #2 STATUS WORD - IS CLOSED
OF19.VALVE.CITV2.STATUS.MOVING 300101 2 Boolean RO 1000 OF19 WELL TOPSIDE CHEMICAL INJECTION VALVE #2 STATUS WORD - IS MOVING
OF19.VALVE.CITV2.STATUS.ALM_DISC 300101 3 Boolean RO 1000 OF19 WELL TOPSIDE CHEMICAL INJECTION VALVE #2 STATUS WORD - DISCREPENCY
OF19.VALVE.CITV2.STATUS.ALM_FLTOMOV 300101 4 Boolean RO 1000 OF19 WELL TOPSIDE CHEMICAL INJECTION VALVE #2 STATUS WORD - FAILED TO OPEN
OF19.VALVE.CITV2.STATUS.ALM_FBIGNORE 300101 5 Boolean RO 1000 OF19 WELL TOPSIDE CHEMICAL INJECTION VALVE #2 STATUS WORD - FEEDBACK IS IGNORED
OF19.VALVE.CITV2.STATUS.OK_TO_OPN 300101 6 Boolean RO 1000 OF19 WELL TOPSIDE CHEMICAL INJECTION VALVE #2 STATUS WORD - OK TO OPEN
OF19.VALVE.CITV2.STATUS.OK_TO_CLS 300101 7 Boolean RO 1000 OF19 WELL TOPSIDE CHEMICAL INJECTION VALVE #2 STATUS WORD - OK TO CLOSE
OF19.VALVE.CITV2.STATUS.OPN_ILOCK_DFT 300101 8 Boolean RO 1000 OF19 WELL TOPSIDE CHEMICAL INJECTION VALVE #2 STATUS WORD - OPEN ILOCK DEFEATABLE
OF19.VALVE.CITV2.STATUS.CLS_ILOCK_DFT 300101 9 Boolean RO 1000 OF19 WELL TOPSIDE CHEMICAL INJECTION VALVE #2 STATUS WORD - CLOSE ILOCK DEFEATABLE
OF19.VALVE.CITV2.ILOCK.ROV_OPN 300102 0 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - ROV Override Open
OF19.VALVE.CITV2.ILOCK.ROV_CLSD 300102 1 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - ROV Override Closed
OF19.VALVE.CITV2.ILOCK.LPHDR_LO 300102 2 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - LP Header Low
OF19.VALVE.CITV2.ILOCK.LPHDR_UNK 300102 3 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - LP Header Unknown
OF19.VALVE.CITV2.ILOCK.LPHDR_OVR 300102 4 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - LP Header Override
OF19.VALVE.CITV2.ILOCK.HPHDR_LO 300102 5 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - HP Header Low
OF19.VALVE.CITV2.ILOCK.HPHDR_UNK 300102 6 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - HP Header Unkonwn
OF19.VALVE.CITV2.ILOCK.HPHDR_OVR 300102 7 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - HP Header Override
OF19.VALVE.CITV2.ILOCK.LPHPPRS_LO 300102 8 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - Out of service OPEN
OF19.VALVE.CITV2.ILOCK.LPHPPRS_UNK 300102 9 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - Out of service CLOSE
OF19.VALVE.CITV2.ILOCK.OOS_OPN 300102 10 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - Out of service OPEN
OF19.VALVE.CITV2.ILOCK.OOS_CLS 300102 11 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - Out of service CLOSE
OF19.VALVE.CITV2.ILOCK.CE_AMVPMV_OPN 300102 12 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - AMV and PMV are open - C&E 1a
OF19.VALVE.CITV2.ILOCK.CE_XOVPWV_OPN 300102 13 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - XOV and PWV are open - C&E 1B
OF19.VALVE.CITV2.ILOCK.CE_AMVXOV_OPN 300102 14 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - AMV and XOV are open - C&E 1C & 1D
OF19.VALVE.CITV2.ILOCK.CE_EQUALIZE 300102 15 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - Equalize before opening - C&E 4a
OF19.VALVE.CITV2.ILOCK.VALUE 300102 DWord RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word
OF19.VALVE.CITV2.ILOCK.CE_PMVXOV_OPN 300103 0 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - PMV and XOV are open - C&E 1E
OF19.VALVE.CITV2.ILOCK.CE_PWVAMV_OPN 300103 1 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - PWV and AMV not closed - C&E 1F
OF19.VALVE.CITV2.ILOCK.CE_PCV_NOTCL 300103 2 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - PCV not closed - C&E 2
OF19.VALVE.CITV2.ILOCK.CE_PMVPWV_NOTCL 300103 3 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - PMV or PWV not closed - C&E 4b
OF19.VALVE.CITV2.ILOCK.CE_PWV_NOTCL 300103 4 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - PWV not closed - C&E 5
OF19.VALVE.CITV2.ILOCK.CE_XOV_OPN 300103 5 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - XOV open - C&E 8
OF19.VALVE.CITV2.ILOCK.CE_GLV_OPN 300103 6 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - GLV open - C&E 9

Page 31 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx OF19 19/04/2024

Validation Date Tag Name Address index Data Type Client Access Scan Rate Description
OF19.VALVE.CITV2.ILOCK.CE_PMVPWV_NOTCL1 300103 9 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - PMV or PWV not Closed - C&E 4b
OF19.VALVE.CITV2.ILOCK.CE_PWV_NOTCL1 300103 10 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - PWV not closed - C&E 6
OF19.VALVE.CITV2.ILOCK.CE_PCVPWV_NOTCL 300103 11 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - PCV and PWV not closed - C&E 7a
OF19.VALVE.CITV2.ILOCK.CE_PCVPMV_NOTCL 300103 12 Boolean RO 1000 OF19 Well Topside Chemical Injection Valve #2 Interlock Word - PCV and PMV not Closed - C&E 7b
OF19.VALVE.FLIV.STATUS.OPEN 300104 0 Boolean RO 1000 OF19 WELL FLOW LINE INJECTION VALVE STATUS WORD - IS OPEN
OF19.VALVE.FLIV.STATUS.CLOSED 300104 1 Boolean RO 1000 OF19 WELL FLOW LINE INJECTION VALVE STATUS WORD - IS CLOSED
OF19.VALVE.FLIV.STATUS.MOVING 300104 2 Boolean RO 1000 OF19 WELL FLOW LINE INJECTION VALVE STATUS WORD - IS MOVING
OF19.VALVE.FLIV.STATUS.ALM_DISC 300104 3 Boolean RO 1000 OF19 WELL FLOW LINE INJECTION VALVE STATUS WORD - DISCREPENCY
OF19.VALVE.FLIV.STATUS.ALM_FLTOMOV 300104 4 Boolean RO 1000 OF19 WELL FLOW LINE INJECTION VALVE STATUS WORD - FAILED TO OPEN
OF19.VALVE.FLIV.STATUS.ALM_FBIGNORE 300104 5 Boolean RO 1000 OF19 WELL FLOW LINE INJECTION VALVE STATUS WORD - FEEDBACK IS IGNORED
OF19.VALVE.FLIV.STATUS.OK_TO_OPN 300104 6 Boolean RO 1000 OF19 WELL FLOW LINE INJECTION VALVE STATUS WORD - OK TO OPEN
OF19.VALVE.FLIV.STATUS.OK_TO_CLS 300104 7 Boolean RO 1000 OF19 WELL FLOW LINE INJECTION VALVE STATUS WORD - OK TO CLOSE
OF19.VALVE.FLIV.STATUS.OPN_ILOCK_DFT 300104 8 Boolean RO 1000 OF19 WELL FLOW LINE INJECTION VALVE STATUS WORD - OPEN ILOCK DEFEATABLE
OF19.VALVE.FLIV.STATUS.CLS_ILOCK_DFT 300104 9 Boolean RO 1000 OF19 WELL FLOW LINE INJECTION VALVE STATUS WORD - CLOSE ILOCK DEFEATABLE
OF19.VALVE.FLIV.ILOCK.ROV_OPN 300105 0 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - ROV Override Open
OF19.VALVE.FLIV.ILOCK.ROV_CLSD 300105 1 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - ROV Override Closed
OF19.VALVE.FLIV.ILOCK.LPHDR_LO 300105 2 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - LP Header Low
OF19.VALVE.FLIV.ILOCK.LPHDR_UNK 300105 3 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - LP Header Unknown
OF19.VALVE.FLIV.ILOCK.LPHDR_OVR 300105 4 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - LP Header Override
OF19.VALVE.FLIV.ILOCK.HPHDR_LO 300105 5 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - HP Header Low
OF19.VALVE.FLIV.ILOCK.HPHDR_UNK 300105 6 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - HP Header Unkonwn
OF19.VALVE.FLIV.ILOCK.HPHDR_OVR 300105 7 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - HP Header Override
OF19.VALVE.FLIV.ILOCK.LPHPPRS_LO 300105 8 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - Out of service OPEN
OF19.VALVE.FLIV.ILOCK.LPHPPRS_UNK 300105 9 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - Out of service CLOSE
OF19.VALVE.FLIV.ILOCK.OOS_OPN 300105 10 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - Out of service OPEN
OF19.VALVE.FLIV.ILOCK.OOS_CLS 300105 11 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - Out of service CLOSE
OF19.VALVE.FLIV.ILOCK.CE_AMVPMV_OPN 300105 12 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - AMV and PMV are open - C&E 1a
OF19.VALVE.FLIV.ILOCK.CE_XOVPWV_OPN 300105 13 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - XOV and PWV are open - C&E 1B
OF19.VALVE.FLIV.ILOCK.CE_AMVXOV_OPN 300105 14 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - AMV and XOV are open - C&E 1C & 1D
OF19.VALVE.FLIV.ILOCK.CE_EQUALIZE 300105 15 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - Equalize before opening - C&E 4a
OF19.VALVE.FLIV.ILOCK.VALUE 300105 DWord RO 1000 OF19 Well Flow Line Injection Valve Interlock Word
OF19.VALVE.FLIV.ILOCK.CE_PMVXOV_OPN 300106 0 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - PMV and XOV are open - C&E 1E
OF19.VALVE.FLIV.ILOCK.CE_PWVAMV_OPN 300106 1 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - PWV and AMV not closed - C&E 1F
OF19.VALVE.FLIV.ILOCK.CE_PCV_NOTCL 300106 2 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - PCV not closed - C&E 2
OF19.VALVE.FLIV.ILOCK.CE_PMVPWV_NOTCL 300106 3 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - PMV or PWV not closed - C&E 4b
OF19.VALVE.FLIV.ILOCK.CE_PWV_NOTCL 300106 4 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - PWV not closed - C&E 5
OF19.VALVE.FLIV.ILOCK.CE_XOV_OPN 300106 5 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - XOV open - C&E 8
OF19.VALVE.FLIV.ILOCK.CE_GLV_OPN 300106 6 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - GLV open - C&E 9
OF19.VALVE.FLIV.ILOCK.CE_PMVPWV_NOTCL1 300106 9 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - PMV or PWV not Closed - C&E 4b
OF19.VALVE.FLIV.ILOCK.CE_PWV_NOTCL1 300106 10 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - PWV not closed - C&E 6
OF19.VALVE.FLIV.ILOCK.CE_PCVPWV_NOTCL 300106 11 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - PCV and PWV not closed - C&E 7a
OF19.VALVE.FLIV.ILOCK.CE_PCVPMV_NOTCL 300106 12 Boolean RO 1000 OF19 Well Flow Line Injection Valve Interlock Word - PCV and PMV not Closed - C&E 7b
OF19.CHOKE.PCV.CALC_POS 300119 Float RO 1000 OF19 Well Production Choke Calculated Position
OF19.CHOKE.PCV.SP_MCS 300121 Float RO 1000 OF19 Well Production Choke Setpoint (MCS)
OF19.CHOKE.PCV.STATUS.OPEN 300123 0 Boolean RO 1000 OF19 WELL PRODUCTION CHOKE STATUS WORD - IS OPEN
OF19.CHOKE.PCV.STATUS.CLOSED 300123 1 Boolean RO 1000 OF19 WELL PRODUCTION CHOKE STATUS WORD - IS CLOSED
OF19.CHOKE.PCV.STATUS.MOVING 300123 2 Boolean RO 1000 OF19 WELL PRODUCTION CHOKE STATUS WORD - IS MOVING
OF19.CHOKE.PCV.STATUS.ALM_DISC 300123 3 Boolean RO 1000 OF19 WELL PRODUCTION CHOKE STATUS WORD - DISCREPENCY
OF19.CHOKE.PCV.STATUS.ALM_FLTOCMD 300123 4 Boolean RO 1000 OF19 WELL PRODUCTION CHOKE STATUS WORD - FAILED TO MOVE
OF19.CHOKE.PCV.STATUS.ALM_FBIGNORE 300123 5 Boolean RO 1000 OF19 WELL PRODUCTION CHOKE STATUS WORD - FEEDBACK IS IGNORED
OF19.CHOKE.PCV.STATUS.OK_TO_MOVE 300123 6 Boolean RO 1000 OF19 WELL PRODUCTION CHOKE STATUS WORD - OK TO MOVE
OF19.CHOKE.PCV.STATUS.OK_TO_ABRT 300123 7 Boolean RO 1000 OF19 WELL PRODUCTION CHOKE STATUS WORD - OK TO ABORT
OF19.CHOKE.PCV.STATUS.MOV_ILOCK_DFT 300123 8 Boolean RO 1000 OF19 WELL PRODUCTION CHOKE STATUS WORD - MOVE ILOCK DEFEATABLE
OF19.CHOKE.PCV.STATUS.ABT_ILOCK_DFT 300123 9 Boolean RO 1000 OF19 WELL PRODUCTION CHOKE STATUS WORD - ABORT ILOCK DEFEATABLE
OF19.CHOKE.PCV.ILOCK.ROV_OPN 300124 0 Boolean RO 1000 OF19 WELL PRODUCTION CHOKE INTERLOCK WORD - IS OPEN
OF19.CHOKE.PCV.ILOCK.ROV_CLSD 300124 1 Boolean RO 1000 OF19 WELL PRODUCTION CHOKE INTERLOCK WORD - IS CLOSED
OF19.CHOKE.PCV.ILOCK.LPHDR_LO 300124 2 Boolean RO 1000 OF19 WELL PRODUCTION CHOKE INTERLOCK WORD - LP HEADER PRESSURE LO
OF19.CHOKE.PCV.ILOCK.LPHDR_UNK 300124 3 Boolean RO 1000 OF19 WELL PRODUCTION CHOKE INTERLOCK WORD - LP HEADER PRESSURE UNKNOWN

Page 32 de 36
2383 - Projet - ANNEXE1 - Modbus Communication Schedule.xlsx OF19 19/04/2024

Validation Date Tag Name Address index Data Type Client Access Scan Rate Description
OF19.CHOKE.PCV.ILOCK.LPHDR_OVR 300124 4 Boolean RO 1000 OF19 WELL PRODUCTION CHOKE INTERLOCK WORD - LP HEADER OVERRIDE
OF19.CHOKE.PCV.ILOCK.OOS_OPN 300124 10 Boolean RO 1000 OF19 WELL PRODUCTION CHOKE INTERLOCK WORD - OOS IN OPEN POSITION
OF19.CHOKE.PCV.ILOCK.OOS_CLS 300124 11 Boolean RO 1000 OF19 WELL PRODUCTION CHOKE INTERLOCK WORD - OOS IN CLOSE POSIION
OF19.CHOKE.PCV.ILOCK.VALUE 300124 DWord RO 1000 OF19 Well Production Choke Interlock Word
OF19.SEQ.STEP 300125 Word RO 1000 OF19 Well Sequences Sequence Step
OF19.SEQ.TIME 300126 Word RO 1000 OF19 Well Sequences Time Remaining
OF19.CTRL.WORD 400001 Word R/W 1000 OF19 Well Control Word
OF19.VALVE.AMV.CTRL.WORD 400002 Word R/W 1000 OF19 Well Annulus Master Valve Control Word
OF19.VALVE.GLV.CTRL.WORD 400003 Word R/W 1000 OF19 Well Gas Lift Isolation Valve Control Word
OF19.VALVE.PMV.CTRL.WORD 400004 Word R/W 1000 OF19 Well Production Master Valve Control Word
OF19.VALVE.PWV.CTRL.WORD 400005 Word R/W 1000 OF19 Well Production Wing Valve Control Word
OF19.VALVE.SCSSV.CTRL.WORD 400006 Word R/W 1000 OF19 Well Downhole Safety Valve (SCSSV) Control Word
OF19.VALVE.XOV.CTRL.WORD 400007 Word R/W 1000 OF19 Well Crossover Valve Control Word
OF19.VALVE.AAV.CTRL.WORD 400008 Word R/W 1000 OF19 Well Annulus Auxilary Valve Control Word
OF19.VALVE.AWV.CTRL.WORD 400009 Word R/W 1000 OF19 Well Annulus Wing Valve Control Word
OF19.VALVE.CIDV.CTRL.WORD 400010 Word R/W 1000 OF19 Well Downhole Chemical Injection Valve Control Word
OF19.VALVE.CITV1.CTRL.WORD 400011 Word R/W 1000 OF19 Well Topside Chemical Injection Valve #1 Control Word
OF19.VALVE.CITV2.CTRL.WORD 400012 Word R/W 1000 OF19 Well Topside Chemical Injection Valve #2 Control Word
OF19.VALVE.FLIV.CTRL.WORD 400013 Word R/W 1000 OF19 Well Flow Line Injection Valve Control Word
OF19.CHOKE.PCV.REM_SP 400020 Word R/W 1000 OF19 Well Production Choke Remote Setpoint (ICSS)
OF19.CHOKE.PCV.CTRL.VALUE 400022 Word R/W 1000 OF19 Well Production Choke Control Word