Sheets - Sheet (2) Power System Engineering
Sheets - Sheet (2) Power System Engineering
Q(1) For a given short transmission line of impedance (R+jX) Ω/ph, the SE and
RE voltages, 𝑉𝑆 and 𝑉𝑅; respectively are fixed. The maximum active power that
can be transmitted over the line can be determined from:
|𝑣𝑟|∗|𝑣𝑠|
1)𝑃𝑅 = |𝑧|
∠θ − δ
|𝑣𝑟|∗|𝑣𝑠| |vr|^2
2) 𝑃𝑅 = |𝑧|
∠θ − δ − |z|
|𝑣𝑟|∗|𝑣𝑠| |vr|^2
3) 𝑃𝑅 = |𝑧|
cos(θ − δ) − |z|
cos θ
|𝑣𝑟|∗|𝑣𝑠| |vr|^2
4) 𝑃𝑅 = |𝑧|
− |z|
cos θ
Q2) Two stations are connected by a 3-φ TL having resistance and inductive
reactance of 1 and 4 Ω/ph respectively. The bus-bar voltage is 33 kV between
phases at each station.
a) The maximum active power received is;
1) 200 MW 2) 123.5MW 3) 400kW 4)300 MW
b) The maximum reactive power received is :
1) 256.23 MVAr 2) 300.5 MVAr
3) 120 MVAr 4) 30 MVAr
1/5
3rd Year Electr. power & M/Cs
Zagazig University
Power System Engineering (1)
Faculty of Eng.
Course code: EPE321a
Dept. of Electr. Power & M/Cs
Sheet (2)
Q4) A long, symmetrical, 3- φ OHTL, open circuited at the load end, gave the
following test data (all per phase star, for the same phase): load voltage 200∠00
kV, sending voltage 180∠50 kV, sending current 200∠920 A, power and pf for a
load of 200 kV/ph, 40 MW/ph and UPF
a) Line constant A is :
1)1.23 ∠2.3 2) 2.5∠ 0.23 3) 0.9 ∠5 4) 0.558 ∠4.6
b) line constant C Is :
1) 1∠92 2) 52 ∠1.25 3) 0.985∠0.23 4) 2.546∠1.56
c) line constant B is:
1) 246.4∠53.2 2) 55.23∠60
3)125.12 ∠30 4) 220.23∠0.23
d) received end current (Ir) is:
1) 200 A 2) 100 A 3) 115.4 A 4) 150 A
e) sending end voltage (input voltage ) is :
1) 120∠30 2) 216∠15 3) 250 ∠30 4) 300∠60
f) sending end current is :
1) 276 ∠51 2)300∠30 3)150∠30 4) 210∠45
g) power factor at sending end is :
1) 0.802 lag 2)0.802 lead 3) unity 4)0.92 lag
h) sending power equal to :
1)47.89 KW 2)47.89 MW 3)143.67 MW 4) 143.67 kW
2/5
3rd Year Electr. power & M/Cs
Zagazig University
Power System Engineering (1)
Faculty of Eng.
Course code: EPE321a
Dept. of Electr. Power & M/Cs
Sheet (2)
Q6) A 50 Hz, 3-
3/5
3rd Year Electr. power & M/Cs
Zagazig University
Power System Engineering (1)
Faculty of Eng.
Course code: EPE321a
Dept. of Electr. Power & M/Cs
Sheet (2)
Q8) A 3-φ OHTL has resistance and reactance of 5 and 20 Ω, respectively. The
load at the RE is 30 MW, 0.85 power factor lagging at 33 kV. Find the voltage
at the SE.
a) The sending end voltage (phase )is :
1) 51.16 kV 2) 29.54 kV 3) 45.2 kV 4) 26.1 kV
b) the kVAr rating of the compensating equipment inserted at the RE so as
to maintain a voltage of 33 kV at each end.
1) 56.21 MVAr 2) 22.8 MVAr 3)38.81 MVAr 4) 66.5 MVAr
c) Maximum load can be transmitted is :
1) 25.5 MW 2) 36.25 MW 3)58 MW 4) 40.1 MW
Q9) A 3-φ OHTL has resistance and reactance per phase of 5 and 25 Ω,
respectively. The load at the receiving-end is 15 MW, 33 kV, 0.8 power factor
lagging.
a) The value of constant A equals :
1) 0.92∠0.25 2) 1∠0 3)1.48∠25.26 4)25.5∠78.7
b) The value of constant B equal to :
1) 0.92∠0.25 2) 1∠0 3)1.48∠25.26 4)25.5∠78.7
c) The reactive power at load side (QD) :
1)11.25 MVAr 2)-11.25 MVAr 3)15 MVAr 4)-15 MVAr
d) the value of angle δ (power angle) :
1)-68.12 deg 2)-21.88 deg 3)21.88 deg 4)68.12 deg
e) The received reactive power is (QR) :
1) 6.135 MVAr 2)-6.135 MVAr r
3)17.385 MVAr 4)-17.385 MVAr
f) The capacity of the compensation equipment needed to deliver this load
with a SE voltage of 33 kV
1) 6.135 MVAr 2)-6.135 MVAr
3) 17.385 MVAr 4)-17.385 MVAr
g) the extra load of 0.8 lagging power factor which can be delivered with the
compensating equipment (of capacity as calculated above) installed, if
the receiving-end voltage is permitted to drop to 28kv
4/5
3rd Year Electr. power & M/Cs
Zagazig University
Power System Engineering (1)
Faculty of Eng.
Course code: EPE321a
Dept. of Electr. Power & M/Cs
Sheet (2)
Q10) A 3-φ, 132 kV OHTL delivers 50 MVA at 132 kV and 0.8 power factor
lagging at its RE. The constants of the line are A= 0.98∠30 and B=110∠750
Ω/ph.
a) Received end current (Ir):
1) 120 A 2)219 3)300A 4)237 A
b) The sending end voltage (Vs) is :
1) 95.37 ∠11.34 kV 2) 95.37∠-11.34 kV
3) 165.2∠11.34 kV 4) 165.2∠-11.34 kV
c) the value of power angle (δ) is:
1)11.34 deg 2)-11.34 deg 3)36.87 deg 4)-36.87deg
d) Static compensator is installed at the RE to maintain a voltage of 132 kV
at each end
a) The received end active power (PR) is :
1) 50 MW 2) 40 MW 3) 20 MW 4)12.3 MW
b) The received end reactive power (QR) is :
1) 10.69 MVAr 2) -15.914MVAr
3)-18.9 MVAr 4) 18.9 MVAr
c) The demand reactive power (QD) is equal to :
1) 30 MVAr 2)15 MVAr
2) 3)-30 MVAr 4)-15 MVAr
d) The capacity of the compensator (Qc) is equal to :
1) 40.69 MVAr 2)45.914 MVAr
2) 3)-19.4 MVAr 4)3.9 MVAr
e) The maximum load can be transmitted equal :
1) 110.43 MW 2) 50.23MW
3) 146.23 MW 4) 30.25 M
5/5