2-3 EN LOGICA Digital Integration Guide Modbus
2-3 EN LOGICA Digital Integration Guide Modbus
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
Application
The LOGICA Digital is a digital actuator designed to optimize
energy usage in Heating, Ventilation and Air Conditioning
(HVAC) systems.
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
Overview
The flowchart below describes the complete actuator commissioning process. The guide starts by explaining the
basic communication settings and valve selection process. Then, an application example is provided for each step of
the flowchart and lastly, a complete register list is provided. Beside each step there is a reference such as Ex. 2.
This refers to an application example, so the example given is Application example 2 on page 5.
A basic commissioning can be done very quickly by jumping over the optional steps.
Commission
actuator
No
Commissioning
Actuator Select valve & actuator
configured characteristic
Commissioning
actuator - default
mode and settings
Manual Remote
Preset Preset
Flow limitation
Ex. 4 Ex. 2
Match actuator Select new max Ex. 3
preset to valve’s No flow in actuator
Install No
sensor(s)?
Ex. 5
Select sensor
type and
configuration P1
Ex. 5
Select sensor
type and
configuration P2
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
Overview (continued)
Select
operating
mode
Ex. 9
PI controller Ex. 10
settings Ex. 19
Advanced settings
Limitation?
No
Yes
Ex. 13
Scheduled No
Flushing?
Yes
Ex. 13
Scheduled No
exercise?
Yes
Actuator
configured
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
These and other parameters can be changed via the Modbus interface using any standard Modbus software.
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
Commissioning actuator
This basic setup prepares the valve and actuator to control the flow using algorithms. The actuator should be mounted on
a valve before starting this process. Given that the Modbus-address has already been setup using the DIP-switches shown
in the LOGICA Digital Technote, these registers are needed to setup the Modbus communication. In registers where “W” is
shown in the R/W column, values must be written into the registers. By default, the Modbus communication baud rate is
19200, with 8 databits, even parity, and 1 stop bit, shown as 19200 8-E-1.
To configure the communication settings, the following registers must be setup:
When the communication commissioning has been done, the examples on the following pages can be performed
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
Register 400: Input signal can vary from 0-100 % by the input signal from the BMS controller.
Operating mode 0xC8 200 Uint16 R/W 0: Control via external control signal -
Note: Register 401 can be used for estimated flow feedback in l/h or register 402 can be used for flow feedback in percentage.
Following examples uses external setpoint (register 200 = 0) unless otherwise stated.
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
Register 113: Change maximum flow to match manual preset. E.g. 1000 l/h.
Register 400: Input signal can vary from 0-100 % by the input from the BMS controller. E.g. 3000 (30 %).
Register 402: Estimated flow from actuator using the maximum flow found in register 113.
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
Actual thermal power 0x19A 410 Uint16 R Example: 105 = 10.5 kW* kW*10
Please note: If the minimum Delta T setpoint is set too high, the system can go into a deadlock. A minimum flow is
recommended when the Delta T algorithm is active. Please define minimum flow in register 312 E.g. 2000 (Minimum flow 20 %)
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
Source for supply and 0x82 130 Uint16 W 5: P1 for the return temperatur -
return temperature
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
Flush timer actual value 0x13F 319 Uint16 R Example: 253 = 253 hours -
Example:
Energy since 00:00 0x19B 411 Uint16 R kWh*10
745 = 74.5 kWh
Energy in the last 24 Example:
0x19C 412 Uint16 R kWh*10
hours 1481 = 148.1 kWh
Continous energy Example:
0x1A0 416 Uint16 R kWh
counter 34053 = 34053 kWh
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
Modbus register 318 returns a masked HEX value, depending on the status.
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
Linear 0 --
Actuating control curve 0x67 103 Uint16 R/W
Equal percentage (EQ %) 1 --
Default 19200 0
9600 1
19200 2
57600 4
76800 5
115200 6
1 stop bit 1
RS485 stop bits 0x6A 106 Uint16 R/W --
2 stop bits 2
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
None 0
Odd 2
Region of control signal
Close when adjusting where the end positions 0 - 500
in which the actuator 0x6D 109 Uint16 R/W %*100
range (30 Default)
stays in position
Linear (Default) 0
OPTIMA Compact Low 1
2.5 DN10/15 30-200 l/h
OPTIMA Compact Low 2
5.0 DN10/15 65-370 l/h
OPTIMA Compact High 3
2.5 DN15/20 100-575 l/h
Select valve type OPTIMA Compact High
5.0 DN15/20 220-1330 l/h 0x6E 110 Uint16 R/W 4 --
(DN10-32)
OPTIMA Compact High 5
5.5 DN20 300-1800 l/h
OPTIMA Compact low 5.5 6
DN25 280-1800 l/h
OPTIMA Compact High 7
5.5 DN25L 600-3609 l/h
OPTIMA Compact 5.5 8
DN32 550-4001 l/h
Linear (Default) 0
OPTIMA Compact DN40 1
1370-9500 l/h
OPTIMA Compact DN50 2
1400-11500 l/h
OPTIMA Compact DN50 3
flanged LF 2.5-15.0 m3/h
OPTIMA Compact DN50 4
flanged HF 3.9-24.0 m3/h
OPTIMA Compact DN65 5
flanged LF 4.4-25.0 m3/h
OPTIMA Compact DN65 6
Select valve type flanged HF 5.9-35.0 m3/h
OPTIMA Compact DN80
(DN40-50) 7
flanged LF 5.3-34.0 m3/h
(DN50-80 flanged) OPTIMA Compact DN80 0x6E 110 Uint16 R/W --
(DN50-100 Ultra) 8
flanged HF 7.0-43.0 m3/h
OPTIMA Compact DN50 9
Ultra HF 1.4-11.5 m3/h
OPTIMA Compact DN65 10
Ultra LF 3.0-16.0 m3/h
OPTIMA Compact DN65 11
Ultra HF 4.2-24.0 m3/h
OPTIMA Compact DN80 12
Ultra LF 4.4-25.0 m3/h
OPTIMA Compact DN80 13
Ultra HF 6.0-35.0 m3/h
OPTIMA Compact DN100 14
Ultra LF 5.3-34.0 m3/h
OPTIMA Compact DN100 15
Ultra HF 7.0-43.0 m3/h
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
Direct 0
Inversion of the valve 0x78 120 Uint16 R/W --
actuating direction
Inverted 1
LED off 0
Normal: 22 s/mm 0
Fast: 16 s/mm 2
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
Off 0
Binary input 1
Sensor type P1 0x7B 123 Uint16 R/W --
0-10 V input 2
Pt1000 6
Direct 0
P1 inversion 0x7C 124 Uint16 R/W --
(Binary input)
Inverted 1
Correction value P1 Offset of sensor value P1 0x7D 125 Int16 R/W -50 to +50 °K*10
Off 0
Binary input 1
0-10 V input 2
Sensor/output type P2 0x7E 126 Uint16 R/W --
Pt1000 6
0-10 V output 8
register 126
0-10 V Y position 9
feedback register 401
Direct 0
P2 inversion
(Binary input) 0x7F 127 Uint16 R/W --
Inverted 1
Correction value P2 Offset of sensor value P2 0x80 128 Int16 R/W -50 to +50 °K*10
Direct 0
P2 inversion 0x81 129 Uint16 R/W --
(Analog output)
Inverted 1
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
2 P2
Configuration of timer
Flush timer value. Function inactive 0x84 132 Uint16 R/W 0 - 4320 Hours
if timer = "0"
No change 0
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
Reserved 0x2000
Reserved 0x8000
Operating hours Total operating time of 0x141 321 Uint32 R 0 - 4294967295 Seconds
the actuator
Overall distance covered
Distance counter by the actuator since 0x143 323 Uint32 R 0 - 4294967295 mm*10
manufacturing
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
No warning 0
Warning: Leak detected Leak detected 0x197 407 Uint16 R --
Differential temperature 1
over 8 °K while valve is
closed for over 6 hours
Off 0
Binary input P1 0x198 408 Uint16 R --
On 1
Off 0
Binary input P2 0x199 409 Uint16 R --
On 1
Actual value of thermal Current thermal power
calculated 0x19A 410 Uint16 R 0 - 65535 kW*10
power
Thermal power since
Energy since 00:00 midnight (Based on the 0x19B 411 Uint16 R 0 - 65535 kWh*10
internal RTC time)
Energy in the last 24 h Energy in the last 24 0x19C 412 Uint16 R 0 - 65535 kWh*10
hours
Off (shut-off ) 0
Status HVAC mode Heating 0x19D 413 Uint16 R 1 --
(Changeover)
Cooling 2
Current active limitation,
Actual flow rate limitation dependent on heating or 0x19E 414 Uint16 R 50 - 50000 l/h
cooling mode
PI controller output value PI controller output 0x19F 415 Uint16 R 0 - 100 %
Continuous energy Calculated value of
counter energy (Write 0 to reset) 0x1A0 416 Uint16 R/W 0 - 65500 kWh*10
Target position Current target in mm for 0x1A2 418 Uint16 R 0 - 150 mm*10
the stem
Actual position Actual position of the 0x1A3 419 Uint16 R 0 - 150 mm*10
stem
LOGICA Digital
Energy-series DN10-DN80 (DN100 Ultra) Modbus Integration Guide
0/1 0/1
0/1 0/1
0 - 1000 %*10
Measured value at input
Analog Input P2 P2. Unit dependent on 0x1A9 425 Int16 R
selected sensor type
-500 to +1500 °C*10
Frese A/S assumes no responsibility for errors, if any, in catalogues, brochures, and other Frese A/S
printed matter. Frese A/S reserves the right to modify its products without prior notice,
including already ordered products, if this does not alter existing specifications. All registered
Tel: +45 58 56 00 00
trademarks in this material are the property of Frese A/S. All rights reserved. [email protected]