ELECTRICAL GENERAL NOTES:
1. ALL ELECTRICAL INSTALLATIONS HEREIN AND OTHER RELATED WORKS TO BE DONE IN THIS BUILDING SHALL
e BE IN ACCORDANCE WITH THE PROVISIONS AND STANDARDS OF THE FOLLOWING:
1.1 THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE.
1.2 REPUBLIC ACT 7926 OTHERWISE KNOWN AS THE NEW ELECTRICAL ENGINEERING LAW
1.3 THE NATIONAL BUILDING CODE OF THE PHILIPPINES.
1.4 FIRE CODE OF THE PHILIPPINES.
3.00 f g 1.5 1.5 EXISTING RULES AND REGULATION OF THE LOCAL POWER UTILITY COMPANY.
1.6 THE EXISTING CITY/MUNICIPAL ORDINANCES AND,
Sf Sg 1.7 THE BUREAU OF LABOR STANDARDS.
2. ALL ELECTRICAL INSTALLATIONS HEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY
Sde REGISTERED ELECTRICAL ENGINEER. HE SHALL BE RESPONSIBLE IN THE INTERPRETATION OF THE PLANS
AND SPECIFICATION AND THE REQUIRED STANDARDS OF THE ELECTRICAL CODE.
d 3. MATERIALS AND EQUIPMENT TO BE USED SHALL HAVE INSPECTED COMMODITY CLEARANCE (ICC) LABEL FOR
FOREIGN MADE PRODUCTS AND P.S. MARK FOR LOCAL IN NATURE OF THE BUREAU OF PRODUCT STANDARD
(BPS).
4. PROVIDE GROUNDING WIRE TO ALL OUTLETS AND LIGHTING CIRCUITS, ALL NON CURRENT CARRYING METAL
6.00 PARTS SHALL BE GROUNDED AND BOBDED INCLUDING FENCE AND GATE.
5. ALL PANEL BOARDS, MAIN DISTRIBUTION PANELS, ETC., SHALL HAVE GROUNDING BUS FOR BRANCH
Sc CIRCUITS AND SUB FEEDER GROUNDING SYSTEM SHALL BE BONDED TO THE NEAREST METAL WATER PIPE.
6. MOUNTING HEIGHT FOR ALL WIRING DEVICES AND PANEL BOARDS SHALL BE.
6.1 LIGHTING OUTLETS 1.40M ABOVE FLOOR FINISH.
6.2 CONVENIENCE OUTLETS 0.30M ABOVE FLOOR FINISH.
6.3 TELEPHONE OUTLETS 0.30M ABOVE FLOOR FINISH.
6.4 PANEL BOARDS & CABINETS 1.40M ABOVE FLOOR FINISH.
7. WIRING METHODS SHALL BE AS FOLLOWS:
Sab b c
7.1
CONDUIT (IMC).
SERVICE ENTRANCE RESISTS INTERMEDIATE METALLIC
3.00 a 7.2 LIGHTING AND POWER SYSTEM POLYVINYL CHLORIDE (PVC).
7.3 TELEPHONE OUTLETS POLYVINYL CHLORIDE (PVC).
7.4 ALL VIBRATING EQUIPMENTS LIQUID TIGHT FLEXIBLE METAL
CONDUIT.
8. NO CHANGES OR MODIFICATION SHALL BE MADE WITHOUT THE DESIGNERS WRITTEN CONSENT.
C1 9. ALL WORKS SHALL BE EXECUTED IN A WORKMANSHIP MANNER AND SHALL PREVENT A NEAT AND ORDERLY
PB C2 ACCEPTANCE. ALL WIRING SHALL BE CONCEALED IN THE LEAST POSSIBLE WAY.
PB
6.8 DESIGN ANALYSIS
7.00 COMPUTATION OF LOAD:
SHORT CIRCUIT ANALYSIS
FLOOR AREA : 7m x 6m = 42 sq. m LINE TO NUETRAL FAULT @230V-X1
SCHEDULE OF LOADS LIGTHTING OUTLET = 42 sq. m x 24 VA / sq. m= 1008 VA FAULT X1
Transformer Volt - Ampere
CIRCUIT BREAKER PROTECTION STEP 1: lsec = Secondary Voltage
CKT. NO. LOAD DESCRIPTION QTY. VA VOLTS AMPERE
AMPERE FRAME KAIC AMPERE TRIP
SIZE OF WIRE AND CONDUIT CONVENINCE OUTLET = 1800 VA (consider 1 CB 15amp rating)
1 LIGHTING OUTLET 7 1008 230 3.48 100 10 20 = 25,000
2 CONVENIENCE OUTLET 7 230 2.61 100 10 20
USE: 2-3.5 mm2 & 1-2.0 mm2 THW 20mm dia PVC PIPE
1 HP = 8 A 230
1800 USE: 2-3.5 mm2 & 1-2.0 mm2 THW 20mm dia PVC PIPE
3 1 hp AIR CONDITIONING UNIT 7 1840 230 2.61 100 10 30 USE: 2-5.5 mm2 & 1-5.5 mm2 THW 20mm dia PVC PIPE = 230 V x 8 A = 1840 VA = 108.7 Amps
4 REFRIGERATOR 1hp 1 1840 230 8 100 10 30 USE: 2-5.5 mm2 & 1-5.5 mm2 THW 20mm dia PVC PIPE Isec
STEP 2: Isc (sym)= %Z
5 FUTURE LOAD 1 1840 230 8 100 10 30 USE: 2-5.5 mm2 & 1-5.5 mm2 THW 20mm dia PVC PIPE
TOTAL CONNECTION LOAD 6488 22.09 TOTAL CURRENT = 5176/230 = 22.09 A = 108.7
0.2
FULL LOAD CURRENT @ 80% DEMAND FACTOR:
= 543.47
SINGLE LINE DIAGRAM
IFL = (22.09-10)0.80 = 9.672 + 30 = 39.672 A
USE: 1-125 AT/225 AF, 60Hz, SINGLE PHASE, 1P, MCB SAY, 10 kAIC MAIN CKT. BREAKER
USE: 2- 38 mm2 THW CU. WIRE + 1-14.0 mm2 GROUND WIRE @ 35 mm RSC
SERVICE VOLTAGE DROP CALCULATION:
LEGEND ENTRANCE (a) VOLTAGE DROP FOR SERVICE DROP WIRE,
LOCATION MAP USE: 2-38 mm2 & 1-14 mm2
THW CU. WIRE in 35 mm dia
2
RSC
VD= 2 X L X Z X I
PINES HOUSE 1000
Sudapin- Luvimin Rd = 2 X 50 X 0.808 X 39.672
1000
2 GANG CONVENIENCE OUTLET CIRCUIT BREAKER
KILOWATTHOUR METER = 3.20
M
2
3 GANG CONVENIENCE OUTLET CIRCUIT HOME-RUN 3.20 X 100
%VD= 230
3
ACU AIR-CONDITIONING = 1.39%
RANGE OUTLET UNIT
Kidapawan-Ilomavis Tourist Rd R
USE: 1-125 AT/225
AF, 60 Hz, SINGLE (b) VOLTAGE DROP FOR SERVICE ENTRANCE,
PHASE, 1P, MCB 2
VD= 2 X L X Z X I
30 AT
DISHWASHER OUTLET S SINGLE GANG SWITCH
D
1000
DOUBLE GANG SWITCH = 2 X 15 X 1.26 X 39.672
REFRIGERATOR OUTLET S2 1 20 AT 20 AT
2 1000
RE 3 30 AT 30 AT
4
PANEL BOARD = 1.49
FLUORESCENT 5 30 AT
M KILOWATT HOUR METER 1.49
INCANDESCENT LAMP %VD= 230 X 100
UTILITY POLE = 0.65%
SERVICE ENTRANCE GROUND
PREPARED / DESIGNED BY: PRC LICENSE #: PROJECT TITLE / LOCATION: CONFORMED BY: SHEET CONTENTS: SCALE: SHEET NO:
DATE OF EXPIRY:
PTR #: LIGHTING LAY-OUT SINGLE LINE DIAGRAM 1:100
PINES, LESLIE L. PEE ISSUED AT: PINES RESIDENCE ELECTRICAL PLAN LESLIE L. PINES POWER LAY-OUT LOCATION MAP
DATE DRAWN:
E
01
ISSUED ON:
PROFESSIONAL ELECTRICAL ENGINEER DESIGN ANALYSIS LEGEND
TIN #: OWNER
ISSUED AT: ADDRESS: PRK. 7A, BRGY SUDAPIN KIDAPAWAN CITY SCHEDULE OF LOADS SEPTEMBER 26, 2024