Based on Function
Primary Instruments: Directly measure a physical quantity without the aid of any other
instrument. Examples include thermometers, ammeters, and voltmeters.
Secondary Instruments: Measure a physical quantity indirectly by converting it into a
more convenient form and then using a primary instrument to measure the converted
quantity. Examples include pressure transducers and thermocouples.
Types of Transducers
There are many types of transducers, each designed to convert a specific physical quantity. Here
are some common examples:
Temperature Transducers:
o Thermocouples: Generate a voltage based on the temperature difference between
two dissimilar metals.
o Resistance Temperature Detectors (RTDs): Change resistance with temperature.
o Thermistors: Change resistance with temperature, often more sensitive than
RTDs.
Pressure Transducers:
o Strain Gauges: Measure strain (deformation) caused by pressure, and convert it to
an electrical signal.
o Piezoresistive Sensors: Utilize the change in resistance of a material due to
pressure.
o Capacitive Sensors: Detect changes in capacitance caused by pressure.
Displacement Transducers:
o Potentiometers: Measure linear or angular displacement by changing resistance.
o Linear Variable Differential Transformers (LVDTs): Measure displacement using
electromagnetic principles.
o Capacitive Sensors: Can also measure displacement by detecting changes in
capacitance.
Force Transducers:
o Load Cells: Measure force by converting it into a strain, which is then sensed by
strain gauges.
o Piezoelectric Sensors: Generate a voltage when subjected to mechanical stress.
Flow Transducers:
o Mass Flow Meters: Measure the mass flow rate of a fluid.
o Volume Flow Meters: Measure the volume flow rate of a fluid.
o Ultrasonic Flow Meters: Use sound waves to measure flow velocity.
Sensitivity: The ability of a transducer to produce a large output signal for a small
change in the input quantity.
Accuracy: The degree to which a transducer's output matches the true value of the input
quantity.
Linearity: The extent to which the transducer's output is a linear function of the input
quantity.
Repeatability: The ability of a transducer to produce the same output for the same input
under repeated conditions.
Range: The maximum and minimum values of the input quantity that the transducer can
measure.
Response Time: The time required for a transducer's output to stabilize after a change in
input.
1. U-Tube Manometer: The most basic type, with both ends open to the atmosphere. It
measures the gauge pressure of a fluid relative to atmospheric pressure.
2. Inverted U-Tube Manometer: The ends are sealed, with one end connected to the
pressure source and the other to a reference pressure. It measures absolute pressure.
3. Inclined Manometer: The tube is inclined to increase the sensitivity for measuring small
pressure differences.
4. Well-Type Manometer: One arm is much wider than the other, allowing for larger
pressure differences to be measured.
Working Principle
The liquid in the manometer will rise or fall in response to the pressure difference
between the two points being measured.
The difference in height between the liquid levels is directly proportional to the pressure
difference.
The pressure difference can be calculated using the formula:
Applications of Manometers
Manometers are a reliable and versatile tool for measuring pressure in many different
applications. Their simplicity and low cost make them a popular choice for pressure
measurement.
Vacuum Gauges
Bourdon tube gauge: A mechanical gauge that uses a curved tube that straightens out as
pressure increases.
Diaphragm gauge: Can also be used to measure absolute pressure.
Strain gauge pressure transducer: Converts pressure into an electrical signal using
strain gauges.
In summary:
Vacuum gauges are used in applications where pressures are significantly lower than
atmospheric, such as in vacuum chambers or vacuum pumps.
Absolute pressure gauges are used in applications where it is important to know the
total pressure of a gas, such as in chemical processes or medical devices.
Vacuum gauges are instruments used to measure pressures below atmospheric pressure.
They are often used in applications where a high vacuum is required, such as in scientific
research, semiconductor manufacturing, and vacuum coating.
Absolute Pressure Gauges
Absolute pressure gauges are instruments used to measure the total pressure of a gas,
including the atmospheric pressure. They provide a direct measurement of the pressure,
without reference to atmospheric pressure. This is particularly useful in applications
where the ambient pressure can fluctuate or is unknown.
In simpler terms:
1. Area-Velocity Meters:
o Venturi meter: Creates a constriction in the pipe, causing the liquid to accelerate
and the pressure to drop. The flow rate is calculated based on the pressure
difference and the cross-sectional areas of the pipe and the constriction.
o Orifice plate: Similar to a venturi meter, but uses a simple plate with a hole to
create the constriction.
o Nozzle meter: A more streamlined version of the orifice plate, designed to
minimize energy losses.
2. Variable Area Meters:
o Rotameter: A vertical tube with a tapered inner section. A float rises or falls
within the tube, depending on the flow rate. The position of the float indicates the
flow rate.
3. Ultrasonic Flow Meters:
o Transit time method: Measures the time it takes for an ultrasonic pulse to travel
through the liquid, both upstream and downstream. The difference in travel time
is used to calculate the flow velocity.
o Doppler method: Measures the frequency shift of an ultrasonic signal reflected
from suspended particles in the liquid. This shift is related to the flow velocity.
4. Magnetic Flow Meters:
o Electromagnetic induction: A magnetic field is applied perpendicular to the
flow direction. As the liquid flows through the field, a voltage is induced that is
proportional to the flow velocity.
Advantages and Disadvantages of Liquid Level Flow Meters
Advantages:
Disadvantages:
Choosing the right liquid level flow meter depends on factors such as:
Primary Measurements
Secondary Measurements
Derived from Primary Standards: Secondary measurements are derived from primary
standards through calibration or indirect comparison. They often involve the use of
secondary standards or calibrated instruments.
Intermediate Accuracy: Secondary measurements offer a level of accuracy that is
typically lower than primary measurements but still sufficient for many applications.
Examples:
o Using a calibrated thermometer to measure temperature.
o Measuring pressure using a calibrated manometer.
o Determining electrical current using a calibrated ammeter.
Tertiary Measurements
In summary:
Primary measurements are the most accurate and precise, directly linked to primary
standards.
Secondary measurements are derived from primary standards and offer intermediate
accuracy.
Tertiary measurements are derived from secondary standards and have lower accuracy,
suitable for routine applications.
A half bridge circuit consists of two switches (transistors or diodes) and a capacitor. The
switches are connected in a way that allows them to control the flow of current through the
capacitor. When one switch is turned on and the other is turned off, the capacitor charges to the
DC supply voltage. When the switches are reversed, the capacitor discharges, creating an AC
voltage.
Opens in a new window www.build-electronic-
circuits.com
half bridge circuit
A full bridge circuit consists of four switches (transistors or diodes) and a capacitor. The
switches are connected in a way that allows them to control the flow of current through the
capacitor in both directions. When two opposite switches are turned on, the capacitor charges to
the DC supply voltage. When the switches are reversed, the capacitor discharges in the opposite
direction, creating an AC voltage with a higher amplitude than a half bridge circuit.
Key Differences
Output Voltage: Full bridge circuits produce a higher amplitude AC voltage compared
to half bridge circuits for the same DC input voltage.
Efficiency: Full bridge circuits are generally more efficient than half bridge circuits due
to the lower conduction losses in the switches.
Complexity: Full bridge circuits are more complex to control and require more
components than half bridge circuits.
Applications
Inverters: Both half bridge and full bridge circuits are used in inverters to convert DC
voltage to AC voltage for powering AC loads.
Motor Drives: Full bridge circuits are commonly used in motor drives to control the
speed and direction of motors.
DC-to-DC Converters: Both half bridge and full bridge circuits can be used in DC-to-
DC converters to convert a DC voltage to a different DC voltage.
The choice between a half bridge and full bridge circuit depends on the specific requirements of
the application, such as the desired output voltage, efficiency, and complexity.
Types of Thermistors
Working Principle
The resistance of a thermistor changes due to changes in the material's crystal structure.
In NTC thermistors, as temperature increases, the crystal lattice expands, making it easier
for electrons to move through the material, reducing resistance.
In PTC thermistors, as temperature increases, the crystal lattice becomes distorted,
making it more difficult for electrons to move through the material, increasing resistance.
Applications of Thermistors
Advantages of Thermistors
1. Pressure-Based Methods:
o Differential Pressure (DP) Transmitters: Measure the pressure difference
between the top and bottom of the liquid column. This pressure difference is
directly related to the liquid level.
o Static Pressure Transmitters: Measure the pressure at the bottom of the liquid
column. This pressure is proportional to the liquid level, assuming constant liquid
density.
2. Ultrasonic Level Sensors:
o Time-of-Flight Method: Emit an ultrasonic pulse and measure the time it takes
to return after reflecting off the liquid surface. The level can be calculated based
on the speed of sound and the travel time.
o Doppler Method: Measure the frequency shift of an ultrasonic signal reflected
from the liquid surface. This shift is related to the velocity of the liquid, which
can be used to infer the level.
3. Radar Level Sensors:
o Time-of-Flight Method: Similar to ultrasonic sensors, but use electromagnetic
waves instead of sound waves.
o Frequency Modulation Continuous Wave (FMCW) Method: Transmit a
continuous wave and measure the frequency shift of the reflected signal. This
shift is related to the distance to the liquid surface.
4. Capacitance Level Sensors:
o Measure the capacitance between a probe and the liquid. The capacitance changes
with the level of the liquid, as the dielectric constant of the liquid is different from
that of air.
5. Hydrostatic Level Sensors:
o Use a pressure transducer to measure the hydrostatic pressure exerted by the
liquid at a specific depth. This pressure is directly related to the liquid level.
Non-contact Measurement: Many indirect methods do not require physical contact with
the liquid, reducing the risk of contamination or damage to the sensor.
Suitable for Harsh Environments: Some indirect methods can be used in harsh
environments, such as high temperatures, corrosive liquids, or high pressures.
Accurate and Reliable: Many indirect methods offer high accuracy and reliability,
especially when properly calibrated and maintained.
The choice of indirect liquid level measurement method depends on factors such as:
By understanding the different methods of indirect liquid level measurement, you can select the
most appropriate technique for your specific application.
Working Principle
Working Principle
1. Resistance Variation: An RTD is made of a pure metal, typically platinum, nickel, or
copper. The electrical resistance of these metals changes predictably with temperature.
As the temperature of the RTD increases, the atoms in the metal vibrate more vigorously,
which increases the resistance to the flow of electrical current.
2. Wheatstone Bridge: RTDs are often used in a Wheatstone bridge circuit to measure the
change in resistance. A Wheatstone bridge is a network of four resistors arranged in a
diamond shape. One of the resistors is the RTD, while the others are known resistors.
3. Voltage Measurement: When a voltage is applied across the bridge, a current flows
through each resistor. The voltage difference between the two diagonally opposite
corners of the bridge is measured. If the RTD's resistance changes due to a change in
temperature, the voltage difference will also change.
4. Temperature Calculation: By knowing the initial resistance of the RTD and the change
in voltage difference, the temperature can be calculated using a calibration curve or
equation.
Advantages of RTDs
High Accuracy: RTDs offer high accuracy and precision in temperature measurement.
Wide Temperature Range: They can measure a wide range of temperatures, from very
low to very high.
Excellent Stability: RTDs are highly stable over time and can maintain their calibration
for long periods.
Repeatability: They provide consistent and repeatable measurements.
Disadvantages of RTDs
Slower Response Time: RTDs may have a slower response time compared to other
temperature sensors, such as thermocouples.
Higher Cost: RTDs can be more expensive than some other temperature sensors.
RTDs are widely used in industrial process control, laboratory applications, and other
fields where accurate and reliable temperature measurement is required.
Contact-Based Methods
Thermometers:
o Glass thermometers (mercury, alcohol)
o Digital thermometers (thermocouples, RTDs, thermistors)
Thermocouples: Junctions of two dissimilar metals generate a voltage based on
temperature difference.
Resistance Temperature Detectors (RTDs): Resistance changes with temperature.
Thermistors: Semiconductor devices whose resistance changes significantly with
temperature.
Non-Contact Methods
Other Methods
Types of Tachometers
1. Mechanical Tachometers:
o Centrifugal Tachometers: Use centrifugal force to move a pointer or dial,
indicating the rotational speed.
o Magnetic Tachometers: Use a magnetic field generated by the rotating object to
induce a voltage in a stationary coil. The voltage is proportional to the rotational
speed.
2. Optical Tachometers:
o Stroboscopic Tachometers: Use a flashing light to create a stroboscopic effect.
By adjusting the flash rate, the rotational speed can be determined when the
rotating object appears stationary.
o Laser Tachometers: Use a laser beam to measure the time it takes to reflect off a
rotating object. The rotational speed can be calculated based on the distance and
time.
3. Digital Tachometers:
o Contact Tachometers: Use a contact probe to sense the rotation of a shaft or
gear. The probe generates a pulse for each rotation, which is counted by a digital
counter.
o Non-Contact Tachometers: Use optical, magnetic, or ultrasonic sensors to
measure rotation without physical contact.
Applications of Tachometers
Automotive Industry: Measuring engine speed, wheel speed, and transmission speed.
Industrial Machinery: Monitoring the speed of motors, pumps, and other rotating
equipment.
Medical Equipment: Measuring the speed of rotating components in medical devices.
Research and Development: Measuring the rotational speed of experimental equipment.
Systematic Errors
Gross Errors
Export to Sheets
Minimizing Errors
By understanding these different types of errors and taking appropriate measures to minimize
them, you can improve the accuracy and reliability of your measurements.
Analog Measurement Systems: These systems use analog signals throughout the measurement
process. They often involve components such as potentiometers, amplifiers, and analog-to-
digital converters (ADCs).
Digital Measurement Systems: These systems use digital signals, which are more resistant to
noise and interference. They typically involve components such as microcontrollers, digital-to-
analog converters (DACs), and digital displays.
Smart Measurement Systems: These systems incorporate intelligence into the measurement
process, allowing for more advanced features such as self-calibration, data logging, and
communication with other systems.
Sensor: Converts the physical quantity into an electrical signal. Examples include
thermocouples, RTDs, pressure transducers, and photodiodes.
Signal Conditioning: Amplifies, filters, or converts the sensor signal to make it suitable for the
display or output device. This may involve components such as amplifiers, filters, and ADCs.
Display or Output Device: Presents the measured value in a human-readable format. Examples
include digital displays, analog meters, chart recorders, and data loggers.
Working Principle
1. Two Different Metals: The two metals used in a bimetallic thermometer have different
coefficients of thermal expansion. This means that they expand at different rates when heated.
2. Bending: When the temperature changes, the metal with the higher coefficient of thermal
expansion expands more than the other metal. This causes the bimetallic strip to bend.
3. Pointer Movement: The bending of the strip is often used to move a pointer or dial on a scale,
indicating the temperature.
Simple Construction: Bimetallic thermometers have a simple and rugged construction, making
them reliable and easy to use.
Low Cost: They are relatively inexpensive compared to other temperature measurement
devices.
Wide Temperature Range: Bimetallic thermometers can measure a wide range of temperatures.
No External Power Source: They do not require an external power source to operate.
Thermistor
Thermocouple
Principle: A thermocouple is a junction of two dissimilar metals that generates a voltage based
on the temperature difference between the two junctions.
Types: Various types, including Type K, Type J, Type T.
Advantages: Wide temperature range, rugged construction, fast response time.
Disadvantages: Lower sensitivity than thermistors, requires cold junction compensation.
Key Differences
Export to Sheets
The choice between a thermistor and a thermocouple depends on the specific requirements of the
application, such as:
Temperature range: Thermocouples are better suited for wider temperature ranges, while
thermistors are more sensitive at lower temperatures.
Accuracy: Thermistors generally offer higher accuracy, especially at lower temperatures.
Response time: Thermocouples have a faster response time.
Cost: Thermistors are generally more cost-effective.
In summary, both thermistors and thermocouples are valuable temperature sensors with
their own strengths and weaknesses. The best choice depends on the specific needs of the
application.
Principle: A magnetic field is applied perpendicular to the flow direction. As the conductive
liquid flows through the field, a voltage is induced that is proportional to the flow velocity.
Advantages:
o Non-invasive: No physical obstructions in the flow path.
o Suitable for a wide range of liquids, including slurries and corrosive fluids.
o High accuracy and repeatability.
o Low maintenance requirements.
Disadvantages:
o Requires a conductive liquid.
o May be affected by external magnetic fields.
Principle: A turbine rotor rotates as the liquid flows past it. The rotational speed of the turbine is
proportional to the flow velocity.
Advantages:
o Suitable for a wide range of liquids, including gases.
o High accuracy and repeatability.
o Relatively low cost.
Disadvantages:
o Requires a minimum flow rate to operate.
o May be affected by suspended solids or debris.
o May require regular maintenance.
Key Differences
Non-Invasive Yes No
Export to Sheets
The choice between a magnetic flow meter and a turbine ultrasonic flow meter depends on
factors such as:
Liquid Type: If the liquid is conductive, a magnetic flow meter is generally preferred. If the liquid
is non-conductive or contains suspended solids, a turbine ultrasonic flow meter may be more
suitable.
Flow Rate Range: Magnetic flow meters can measure a wider range of flow rates than turbine
ultrasonic flow meters.
Accuracy: Both types of flow meters can offer high accuracy, but magnetic flow meters may be
slightly more accurate in some applications.
Cost: Turbine ultrasonic flow meters are generally less expensive than magnetic flow meters.