Module-6-Parallel-Generators-for-Student
Module-6-Parallel-Generators-for-Student
Parallel
Generators
1
Title: Direct Current Generator
Duration: 4 hrs
Objectives
1) Continuity of Service
2
2) Efficiency
Usually the load on the electrical power plant fluctuate its peal
value sometimes during the day and its minimum value during the late
night hours. Since generators operate most efficient when delivering full
load, it is economical to use a single small unit when the load is light. Then,
as the load demand increases, a large generator can be substituted for
the smaller one or another smaller unit can be connected to run in parallel
with one already in operation.
3
C. Connection of Parallel DC Generators
1. The generators in a power plant, connected by heavy thick copper
bars, called bus-bars which act as positive and negative terminals.
To connect the generators in parallel, Positive terminal of the
generators are connected to the positive terminal of the bus-bars
and negative terminals of generators are connected to negative
terminal of the bus-bars, as shown in the figure.
Moreover, paralleling a generator with reverse polarity
effectively short circuits it and results in damaged brushes, a
damaged commutator and a blocked-out power plant. Generators
that have been tripped off the bus – because of a heavy fault
current should always be checked for reverse polarity before
paralleling.
2. To connect the 2 generator with the 1 existing working generators,
first we have to bring the speed of the prime mover of the 2
generator to the rated speed. At this point switch S4 is closed.
3. The circuit breaker V2 (voltmeter) connected across the open
switch S2 is closed to complete the circuit. The excitation of the
generator 2 is increased with the help of field rheostat till it
generates voltage equal to the voltage of bus-bars.
4. The main switch S2 is then closed and the generator 2 is ready to
be paralleled with existing generator. But at this point of time
generator 2 is not taking any load as its induced e.m.f. is equal to
bus-bar voltage. The present condition is called floating, that
means ready for supply but not supplying current to the load.
5. In order to deliver current from generator 2, it is necessary that its
induced e.m.f. E should be greater than the bus-bars voltage V.
By strengthening the field current, the induced e.m.f. of generator
2 could be improved and the current supply will get started. To
maintain bus-bar voltage, the field of generator 1 is weakened so
that value remains constant.
𝐸−𝑉
𝐼=
𝑅𝑎
4
Fig. 1.38
Condition 1
The no-load voltage of the generators to be operated in parallel is the
same.
Condition 2
The no-load voltage of the generators to be operated in parallel is
unequal.
5
V is the voltage of the bus to which we will connect the DC generators.
Also, we consider the armature resistance of Generator 1 and 2 are R1 and
R2 respectively. The load delivered by generator 1 and generator 2 are,
𝐼1 𝑅1 = 𝐸 − 𝑉 𝑎𝑛𝑑 𝐼2 𝑅2 = 𝐸 − 𝑉
From these two equations, we can write,
𝐼1 𝑅1 = 𝐼2 𝑅2
𝐼1 𝑅2
=
𝐼2 𝑅1
1
𝐼∝
𝑅
6
In that case, let us consider E1 and E2 are the open circuit or no
load voltage of generator 1 and 2 respectively. Now we can write,
𝐸1 − 𝑉 = 𝑅1 𝐼1
𝐸1 − 𝑉
𝐼1 =
𝑅1
𝐸2 − 𝑉 = 𝑅2 𝐼2
𝐸2 − 𝑉
𝐼2 =
𝑅2
Now, by making ratio of I1 and I2 we get,
𝐼1 𝐸1 − 𝑉 𝑅2
= ×
𝐼2 𝐸2 − 𝑉 𝑅1
Again we know that, the no load voltage of a DC generator is
directly proportional to the field flux and speed of the prime mover. So,
we can write,
𝐸1 ∝ ∅1 𝑁1
Where, Φ1 and N1 are the field flux and RPM of generator 1. Now, we
can write,
𝐸1 = 𝐾1 ∅1 𝑁1
𝐸2 = 𝐾2 ∅2 𝑁2
7
true that during parallel operation of DC shunt generators, the voltage drop
across the armature would be such that it will cause same terminal voltage
for both the generators when running with loads. This online terminal
voltage will be exactly equal to the voltage of the bus to which we connect
the generator.
E. Load Sharing
The load sharing between shunt generators in parallel can be
easily regulated because of their drooping characteristics. The load may
be shifted from one generator to another merely by adjusting the field
excitation.
Thus the current output of the generators depends upon the values of
E1 and E3. These values may be changed by field rheostats. The
common terminal voltage (or bus-bars voltage) will depend upon
It is generally desired to keep the bus bars voltage constant. This can be
achieved by adjusting the field excitations of the generators operating
in parallel.
(1) two parallel shunt generators having equal no-load voltages share
the load in such a ration that the load current of each machine
produces the same drop in each generator.
8
(2) In the case of two shunt generators having unequal no-load
voltages, the load currents produce sufficient voltage drop in each
so as to keep their terminal voltage the same.
(3) The generator with the different power ratings but the same
voltage regulation will divide any oncoming bus load in direct
proportion to their respective power ratings.
F. Compound Generators in Parallel
9
It this condition may continue, at a time generator G1 takes the entire load,
and at that instant, the generator G2 will start working as a motor. This may
result in the opening of the circuit breakers of the generator and the entire
parallel operation will be stopped.
10
This condition can be prevented by placing an equalizing bar between
two generators because of which two machines passes similarly equal
currents to the load, the slight difference between the two currents are
adjusted in the loop is made by the armatures and the equalizer bar.
Self-Evaluation Test
11
Exercises:
1
2. Two shunt generators operating in parallel deliver a total current of
250A. One of the generators is rated 50 kW and the other 100 kW.
The voltage rating of both machine is 500 V and have regulations of
6 percent (smaller one) and 4 percent. Assuming linear
characteristics, determine: (a) the current delivered by each
machine, (b) the terminal voltage, (c) the output power of each
generator.
2
3. Two 220 V dc generators, each having linear external
characteristics operate in parallel. One machine has a terminal
voltage of 270 V on no-load and 220 V at a load current of 35 A,
while the other has a voltage of 280 V at no-load and 220 V at 50
A. Calculate the output current of each machine and the bus bar
voltage when the total load is 60 A. What is the kW output of each
machine?
3
4. Two generators, each having no-load voltage of 500 V, are connected
in parallel to a constant resistance load consuming 400 kw. The
terminal potential difference of one machine falls linearly to 470 V as
the load is increased to 850 A, while that of the other falls linearly to
460 V when the load is 600 A. Find the load current and voltage of
each generator. If the induced emf of one machine is increased to
share load equally, find the new load current and voltage
4
5. Two shunt generators and a battery are working in parallel. The open
circuit voltage, armature and field resistances of generators are 250
V, 0.24 Ω, 100 Ω and 248 V, 0.12 Ω and 100 Ω respectively. If the
generators supply the same current when the load current is 40A,
calculate the emf of the battery if its internal resistance is 0.172 Ω.
5
References:
https://engineeringinterviewquestions.com/dc-generators-electrical-
engineering-multiple-choice-questions-and-answer/
6
7