Automatic Start Unit Trans-MiniAUTO++ Manual en V13
Automatic Start Unit Trans-MiniAUTO++ Manual en V13
Automatic Start Unit Trans-MiniAUTO++ Manual en V13
1.Introduction....................................................................................................................................... Page 4
1.1 General Specifications.............................................................................................................. Page 4
1.2 Warranty.................................................................................................................................... Page 4
1.3 Maintenance ............................................................................................................................. Page 4
1.4 Order Information...................................................................................................................... Page 4
2.Installation......................................................................................................................................... Page 5
2.1 Unit Configuration...................................................................................................................... Page 5
2.2 Panel Mounting.......................................................................................................................... Page 5
Figure 2.1 Front View................................................................................................................ Page 5
Figure 2.2 Panel Cut-Out.......................................................................................................... Page 5
2.3 Electrical Connection................................................................................................................. Page 6
3.Definition Of Front Panel And Accessing To The Parameters...................................................... Page 7
3.1 Front Panel Description............................................................................................................. Page 7
3.2 Accessing To The Operator Parameters.................................................................................... Page 15
3.3 Accessing To The Technician Parameters................................................................................. Page 16
3.4 Changing And Saving Parameter Values ................................................................................. Page 21
4.Parameters........................................................................................................................................ Page 22
4.1 Operator Parameters................................................................................................................. Page 22
4.1.1 Generator......................................................................................................................... Page 22
4.2 Technician Parameters.............................................................................................................. Page 23
4.2.1 System............................................................................................................................. Page 23
4.2.2 Generator......................................................................................................................... Page 27
4.2.3 Engine.............................................................................................................................. Page 29
4.2.4 Inputs............................................................................................................................... Page 39
4.2.5 Outputs............................................................................................................................. Page 48
4.2.6 Timers.............................................................................................................................. Page 56
4.2.7 User Adjustment............................................................................................................... Page 58
5.Specifications.................................................................................................................................... Page 61
6.Other Informations............................................................................................................................. Page 62
2
EU DECLARATION OF CONFORMITY
The product(s) that are stated above are fully in conformity with the essential requirements of
Council Directives:
This declaration is based on the full compliance of the products with the following European
standards:
EN 61326-1:2013 Electrical Equipment for Measurement, Control and Laboratory Use - EMC
Requirements
3
1.Introduction
1.2 Warranty
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts from
the delivery date. This warranty is in force if duty and responsibilities which are determined in
warranty document and instruction manual performs by the customer completely.
1.3 Maintenance
Repairs should only be performed by trained and specialized personnel. Cut power to the device
before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of
these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl
alcohol or water to clean the external plastic case.
Note: Devices have time clock. If real time clock is needed, “RTC” expression must be added to end of order code.
Example: Trans-MiniAUTO++.MPU.RTC
4
2.Installation
Ýçindekiler
A visual inspection of this product for possible damage occured during shipment is
recommended before installation. It is your responsibility to ensure that qualified mechanical
and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit , power off
the system and seperate the electrical connection of the device from the system.
Keep the power off until all of the wiring is completed so that electric shock and trouble with
the unit can be prevented.
The unit can be programmed using the buttons and LCD display on the front panel or PC
Software.
The unit is designed for panel mounting. Fixing is by two screw fixings.
1- Insert the unit in the panel cut-out from the front.
2- Insert the fixings in the slotted at the corners of the unit and tighten the fixing screws to secure
the unit against the panel.
! During the equipment is putted in hole on the metal panel while mechanical
installation some metal burrs can cause injury on hands, you must be careful.
ü
81mm
70mm
RESET
AUTO
81mm
111mm
5
2.3 Electrical Connection
TRANS-MINIAUTO++ three phase connections schematic
BATTERY -
12 11
SCR L(-) H(+)
23 22 21
J1939 ECUs
+
! 1
FUSE-4
MPU
BATTERY +
!
3
2
-
SCR
N
L1
L2
L3
GENERATOR
17
Configurable Analog Input
*
4
18
3
Temperature Sender
*
or High Temperature Switch
2
19
Oil Pressure Sender
BY SELECTING
*
PARAMETERS
or Low Oil Pressure Switch
20
To Engine
*
Sender Common Earth
24 25 26 27
Max. 300VV
FUSE-3
FUSE-2
BATTERY -
FUSE-1
Configurable Input-3
13 14 15 16
Remote Start or
Configurable Input-2
FUSE-5 Emergency Stop or
30 31
Configurable Input-1
8A
D+(W.L.)
Generator Charge Alternator
Contactor
Relay
G
BATTERY +
Configurable Output-6
9 10
LOAD
TO
TRANSISTOR OUTPUTS
Configurable Output-5
Configurable Output-4
8
Configurable Output-3
7
MAX. 1 A
Crank Or
Configurable Output-2
6
Fuel Or
Configurable Output-1
5
FUSE-1, 2, 3 : 2 A. T
FUSE-4, 5 : 8 A. T
1- Connect the unit as shown in the appropriate diagram. Be sure to connect the battery supply the right
way round and battery negative should be grounded. External fuse is recommended. Stranded cable
cross section: 1,5mm2, Solid cable cross section: 2,5mm2, The stripping length is 7 to 9 mm. Supply
cables must comply with the requirements of IEC 60277 or IEC 60245.
c
2- The CAN interface requires that a 120 Ohms terminator is fitted to each end of the communications
link. This termination resistor is fitted internally into the unit. So it is not required externally. Screened
cable must be used for connecting the CAN, ensuring that the screen is grounded at one end ONLY.
3- Screened cable must be used for connecting the Magnetic Pickup, ensuring that the screen is
grounded at one end ONLY.
4- Current transformers secondary should be grounded. The CT of 5VA is recommended. The unit has a
burden of 0.5VA on the CT.
6
3. Front Panel Description And Accessing To The Parameters
1
ü
4
RESET
2 3
AUTO
5 6 7
Number Comment
1 This LED indicates that any alarm was detected.
2 This LED shows that the unit is in the AUTO mode.
3 In the Manual and Auto modes, this LED indicates that the engine is starting up or is running.
4 This button is used for showing next page in normal operation.In Programming mode it is
used for entering parameter edit section, saving parameter value and showing next
parameters on the currently selected page.This button will also silence the alarm horn after a
failure has been detected.
5 The RESET button will reset the controller after a failure has been detected.
The STOP button is used for changing operating mode of the unit to the Stop Mode.
The generator is stopped.
6 The AUTO button is used for changing operating mode of the unit to the Auto Mode.
In Programming mode, it operates as an Down button (changing cursor position) or Decrement
button (decrease parameter value).
7 The START button is used for starting the engine when the unit is in the Manual Mode.
In Programming mode, it operates as an Up button (changing cursor position) or Increment
button (increase parameter value).
7
LCD display Description
Generator Page1
Current page name
Measurement values
GENERATOR
V12: 380V V1: 220V
V23: 380V V2: 220V ü
V31: 380V V3: 220V
On load
Engine Status
or Error Messages RESET
AUTO
Use the Next button to select which Data display page (screen) is to be displayed.
8
Data display pages on the LCD display;
Generator Page1:
V12: Generator voltage L1-L2
GENERATOR V23: Generator voltage L2-L3
V12: 380V V1: 220V V31: Generator voltage L3-L1
V1: Generator voltage L1-N
V23: 380V V2: 220V V2: Generator voltage L2-N
V31: 380V V3: 220V V3: Generator voltage L3-N
On load
Generator Page2:
Fq: Generator frequency
GENERATOR
Fq:50.0Hz
On load
Generator Page3:
I1: Load Current L1
GENERATOR I2: Load Current L2
I1: 26A PF1: -0.84 I3: Load Current L3
PF1: Generator power factor L1
I2: 23A PF2: -0.80 PF2: Generator power factor L2
I3: 25A PF3: -0.82 PF3: Generator power factor L3
On load
Generator Page4:
P1: Generator active power L1
GENERATOR P2: Generator active power L2
P1: 170kW P3: Generator active power L3
P2: 170kW
P3: 170kW
On load
Generator Page5:
Q1: Generator reactive power L1
GENERATOR Q2: Generator reactive power L2
Q1: 40kVAr Q3: Generator reactive power L3
Q2: 40kVAr
Q3: 40kVAr
On load
Generator Page6:
S1: Generator apparent power L1
GENERATOR S2: Generator apparent power L2
S1: 210kVA S3: Generator apparent power L3
S2: 210kVA
S3: 210kVA
On load
9
Generator Page7:
SP: Generator total active power
GENERATOR SQ: Generator total reactive power
SP: 510kW SS: Generator total apparent power
SQ: 120kVAr
SS: 630kVA
On load
Generator Page8:
kWh: Generator active energy
GENERATOR KVArh: Generator reactive energy
kWh : 30600
kVArh: 7200
On load
Engine Page1:
Oil pressure: Oil pressure sender input value
ENGINE Temperature: Coolant temperature sender input value
Oil Pressure: 4.3bar Speed: Engine speed
Temperature : 30ºC
Speed : 1500rpm
On load
Engine Page2:
Conf. AI: Configurable Analog Input value
ENGINE Battery volt: Battery supply voltage
Conf.AI : 96% Gen.chg.volt: Charge generator voltage
Battery volt: 12.0Vdc
Gen.chg.volt: 11.8Vdc
On load
Engine Page3:
Run times: Number of generator runs
ENGINE Crank times: Number of generator cranks
Run times : 7 W.Hour_Min: Engine running time (Hour and Minute)
Crank times : 11
W.Hour_Min: 2_57
On load
10
J1939 Values Page1: *1
Engine speed: Engine speed via J1939
J1939 VALUES Oil pressure: Oil pressure via J1939
Engine speed: 1500rpm Coolant temp: Coolant temperature via J1939
Oil pressure: 4.0bar
Coolant temp: 27ºC
On load
15/02/2011
13:32:28
12
Example-1: Displaying all Data display pages.
*2 *2 *2
J1939 VALUES J1939 VALUES J1939 VALUES
Engine speed: 1500rpm Fuel rate: 12.50L/h Coolant level: 87.6%
Oil pressure: 4.0bar ü
Fuel tot.: 176L ü
Load at cur.spd: 25% ü
*2 *2 *2
J1939 VALUES J1939 VALUES J1939 DM1 FAULTS1
Oil temper.: 82.00ºC Int.man.temp.: 45ºC Spn:110
Act.engine torq: 75% ü
Pedal position: 50.0% ü
Fmi:0 Oc:1 ü
AUTO
Press Enter button AUTO AUTO
for 2 seconds to
access the menu
options.
Press Stop/Reset
button to exit event log
GENERATOR screen.
V12: 380V V1: 220V
V23: 380V V2: 220V
V31: 380V V3: 220V
On load
AUTO
Press Enter button AUTO AUTO
for 2 seconds to
access the menu
options.
Press Stop/Reset
English Display button to exit Chinese Display
language selection
GENERATOR screen. ·¢µç»ú×é
V12: 0V V1: 0V V12: 0V V1: 0V
V23: 0V V2: 0V V23: 0V V2: 0V
V31: 0V V3: 0V V31: 0V V3: 0V
Wait for start
14
3.2 Accessing To The Operator Parameters
PROGRAM OPERATOR SETTING OPERATOR SETTING GENERATOR GENERATOR VOLT LEVEL GENERATOR VOLT LEVEL GENERATOR VOLT LEVEL
Operator setting Password Generator Volt level Under volt shutdown Under volt shutdown Under volt shutdown
Technician setting ü ü ü Frequency level ü Under volt prealarm ü 320 Vac ü Under volt prealarm
Factory adjustment 0000 Current level Under volt reset Under volt reset
Power level Over volt shutdown Over volt shutdown
GENERATOR GENERATOR FREQ LEVEL GENERATOR FREQ LEVEL GENERATOR FREQ LEVEL
Volt level Under freq shutdown Under freq shutdown Under freq shutdown
Frequency level ü Under freq prealarm ü 43.0 Hz ü Under freq prealarm
Current level Under freq reset Under freq reset
Power level Over freq shutdown Over freq shutdown
AUTO AUTO
GENERATOR GENERATOR CUR LEVEL GENERATOR CUR LEVEL GENERATOR CUR LEVEL
Volt level Under cur set Under cur set Under cur set
Frequency level ü Under cur prealarm ü 20 A ü Under cur prealarm
Current level Under cur reset Under cur reset
Power level Over cur set Over cur set
AUTO AUTO
GENERATOR GEN POWER LEVEL GEN POWER LEVEL GEN POWER LEVEL
Volt level Under power shutdown Under power shutdown Under power shutdown
Frequency level ü Under power prealarm ü 150 kVA ü Under power prealarm
Current level Under power reset Under power reset
Power level Over power shutdown Over power shutdown
AUTO AUTO
GENERATOR GEN WORKING CALENDAR GEN WORKING CALENDAR GEN WORKING CALENDAR
Working calendar Disable/enable select Disable/enable select Disable/enable select
ü Start time on monday ü DISBL ü Start time on monday
Stop time on monday Stop time on monday
Start time on tues. Start time on tues.
AUTO AUTO
AUTO
15
3.3 Accessing To The Technician Parameters
PROGRAM TECHNICIAN SETTING TECHNICIAN SETTING SYSTEM SYSTEM NETWORK SYSTEM NETWORK SYSTEM NETWORK
Operator setting Password System Network CT ratio CT ratio CT ratio
Technician setting ü ü Generator ü Breakers ü PT ratio ü 500 A ü PT ratio
Factory adjustment 0000 Engine LCD display Type of AC system Type of AC system
Inputs Communication Generator kVA rating Generator kVA rating
AUTO AUTO
AUTO
AUTO AUTO
AUTO
SYSTEM DATE & TIME SET DATE & TIME SET DATE & TIME SET
Date & time set RTC RTC RTC
Default settings ü Year ü ENABL ü Year
Password Month Month
Day Day
AUTO AUTO
DATE & TIME SET DATE & TIME SET DATE & TIME SET
Week Week Week
Hour ü 1 ü Hour
Minute Minute
Second Second
AUTO
TECHNICIAN SETTING GENERATOR GENERATOR VOLT LEVEL GENERATOR VOLT LEVEL GENERATOR VOLT LEVEL
System Volt level Under volt shutdown Under volt shutdown Under volt shutdown
Generator ü Frequency level ü Under volt prealarm ü 320 Vac ü Under volt prealarm
Engine Current level & act. Under volt reset Under volt reset
Inputs Power level Over volt shutdown Over volt shutdown
GENERATOR GENERATOR FREQ LEVEL GENERATOR FREQ LEVEL GENERATOR FREQ LEVEL
Volt level Nominal frequency Nominal frequency Nominal frequency
Frequency level ü Under freq shutdown ü 50.0 Hz ü Under freq shutdown
Current level & act. Under freq prealarm Under freq prealarm
Power level Under freq reset Under freq reset
AUTO AUTO
GENERATOR GEN CUR LEVEL & ACT GEN CUR LEVEL & ACT GEN CUR LEVEL & ACT
Volt level Under cur. set Under cur. set Under cur. set
Frequency level ü Under cur. prealarm ü 20 A ü Under cur. prealarm
Current level & act. Under cur. reset Under cur. reset
Power level Under cur. act. Under cur. act.
AUTO AUTO
GEN CUR LEVEL & ACT GEN CUR LEVEL & ACT GEN CUR LEVEL & ACT
Under act. delay time Under act. delay time Under act. delay time
Over cur. set ü 2 SEC ü Over cur. set
Over cur. prealarm Over cur. prealarm
Over cur. reset Over cur. reset
AUTO
16
GEN CUR LEVEL & ACT GEN CUR LEVEL & ACT GEN CUR LEVEL & ACT
Over cur. act. Over cur. actions Over cur. act.
Over act. delay time ü DISBL ü Over act. delay time
Short circuit cur. Short circuit cur.
GENERATOR GEN POWER LEVEL GEN POWER LEVEL GEN POWER LEVEL
Volt level Under power shutdown Under power shutdown Under power shutdown
Frequency level ü Under power prealarm ü 150 kVA ü Under power prealarm
Current level & act. Under power reset Under power reset
Power level Over power shutdown Over power shutdown
AUTO AUTO
AUTO
GENERATOR GEN WORKING CALENDAR GEN WORKING CALENDAR GEN WORKING CALENDAR
Working calendar Disable/enable select Disable/enable select Disable/enable select
General ü Start time on monday ü DISBL ü Start time on monday
Stop time on monday Stop time on monday
Start time on tues. Start time on tues.
AUTO AUTO
AUTO
AUTO
*3
GENERATOR GENERATOR GENERAL GENERATOR GENERAL GENERATOR GENERAL
Working calendar Sens.option gen.freq Sens.option gen.freq Sens.option gen.freq
General ü Sens.opt.pickup&flywh ü DISBL ü Sens.opt.pickup&flywh
All warning are latch All warning are latch
TECHNICIAN SETTING ENGINE ENGINE START OPTIONS ENGINE START OPTIONS ENGINE START OPTIONS
System Starting options Horn prior start Au. alarm prior start Horn prior start
Generator ü Crank disconnect ü No. of start attemp ü DISBL ü No. of start attemp
Engine Speed settings Cranking time Cranking time
Inputs Plant battery Crank rest time Crank rest time
*3
ENGINE START OPTIONS ENGINE START OPTIONS ENGINE START OPTIONS
Pickup fail delay Pickup fail delay Pickup fail delay
ü 1.0 sec ü
AUTO AUTO
ENGINE ENGINE SPEED SETS ENGINE SPEED SETS ENGINE SPEED SETS
Starting options Nominal speed Nominal speed Nominal speed
Crank disconnect ü Under speed shutdown ü 1500 RPM ü Under speed shutdown
Speed settings Under speed prealarm Under speed prealarm
Plant battery Under speed reset Under speed reset
AUTO AUTO
ENGINE ENGINE PLANT BATTERY ENGINE PLANT BATTERY ENGINE PLANT BATTERY
Starting options Under volt Under voltage Under volt
Crank disconnect ü Under volt reset ü 10.0 Vdc ü Under volt reset
Speed settings Under volt delay Under volt delay
Plant battery Over volt Over volt
AUTO AUTO
Note: *3 = “Sens.opt.pickup&flywh” and “Pickup fail delay” parameters are only available at Trans-MiniAUTO++.MPU
17
*4 *4
ENGINE CANBUS ECU CANBUS ECU CANBUS ECU
CanBus ECU Baud rate Baud rate Baud rate
CanBus error set ü J1939 ECU type ü 4 ü J1939 ECU type
Maintenance Device address Device address
Load test Engine cont. address Engine cont. address
AUTO AUTO
*4
CANBUS ECU CANBUS ECU CANBUS ECU
ECU remote control ECU remote control ECU remote control
Speed control enable ü DISBL ü Speed control enable
Oil Pres cont. enab Oil Pres cont. enab
Temp. control enable Temp. control enable
AUTO
*4
CANBUS ECU CANBUS ECU CANBUS ECU
Speed set point Speed set point Speed set point
Speed correction ü 1500 RPM ü Speed correction
*4 *4
ENGINE CANBUS ERROR SET CANBUS ERROR SET CANBUS ERROR SET
CanBus ECU CAN fault actions CAN fault actions CAN fault actions
CanBus error set ü CAN fault activation ü DISBL ü CAN fault activation
Maintenance CAN fault delay CAN fault delay
Load test Amber warn.actions Amber warn.actions
AUTO AUTO
*4
CANBUS ERROR SET CANBUS ERROR SET CANBUS ERROR SET
Amber warn.activation Amber warn.activation Amber warn.activation
Amber warn.delay ü 2 ü Amber warn.delay
Red stop actions Red stop actions
Red stop activation Red stop activation
AUTO
*4
CANBUS ERROR SET CANBUS ERROR SET CANBUS ERROR SET
Red stop delay Red stop delay Red stop delay
ü 2 SEC ü
*4
ENGINE ENGINE MAINTENANCE ENGINE MAINTENANCE ENGINE MAINTENANCE
CanBus ECU Running hour interval Running hour interval Running hour interval
CanBus error set ü Maint.date interval ü 5000 HOUR ü Maint.date interval
Maintenance Eng. stop when maint Eng. stop when maint
Load test Eng.running hour(lsb) Eng.running hour(lsb)
AUTO AUTO
*4
ENGINE LOAD TEST LOAD TEST LOAD TEST
CanBus ECU Disable/enable select Disable/enable select Disable/enable select
CanBus error set ü ü DISBL ü
Maintenance
Load test
AUTO
AUTO
AUTO
AUTO
AUTO
AUTO AUTO
Note: *4 = “CanBus ECU” and “CanBus error set” parameter pages are only available at Trans-MiniAUTO++.CAN
18
SENDER LINEARISATION SENDER LINEARISATION SENDER LINEARISATION
Oil pressure sender 3 Oil pressure sender 3 Oil pressure sender 3
Oil pressure 3 ü 62 R ü Oil pressure 3
Oil pressure sender 4 Oil pressure sender 4
Oil pressure 4 Oil pressure 4
AUTO
AUTO
AUTO
AUTO
AUTO
AUTO
AUTO
AUTO
AUTO
AUTO
AUTO
AUTO
AUTO
AUTO
AUTO AUTO
AUTO AUTO
19
CONF. INPUT-2 CONF. INPUT-2 CONF. INPUT-2
Select from list Select from list Select from list
Active delay ü 25-HIGH TEMPERATURE ü Active delay
AUTO AUTO
AUTO AUTO
AUTO
TECHNICIAN SETTING USER ADJUSTMENT GEN. VOLTAGE OFFSET GEN. VOLTAGE OFFSET GEN. VOLTAGE OFFSET
Outputs Gen. voltage offset Gen. V1 offset Gen. V1 offset Gen. V1 offset
Timers ü Current offset ü Gen. V2 offset ü 0 Vac ü Gen. V2 offset
User adjustment Battery&chrg gen.vol Gen. V3 offset Gen. V3 offset
Sender inputs offset
AUTO
AUTO
AUTO
USER ADJUSTMENT SENDER INPUTS OFFSET SENDER INPUTS OFFSET SENDER INPUTS OFFSET
Gen. voltage offset Oil pressure offset Oil pressure offset Oil pressure offset
Current offset ü Temperature offset ü 0.0 Bar ü Temperature offset
Battery&chrg gen.vol Conf. AI1 offset Conf. AI1 offset
Sender inputs offset
20
3.4 Changing And Saving Parameters Values
Operation Screen
GENERATOR PROGRAM
V12: 380V V1: 220V Program Operator setting ü
ü
V23: 380V V2: 220V Language ü Technician setting
V31: 380V V3: 220V Event log Factory adjustment
On load
RESET RESET RESET
Press Enter button When the Enter button is Press the Up or Down
for 2 seconds to pressed, the parameters buttons to select
access the menu options. section is asked for the section you wish
accessing to parameters. to view/change.
AUTO
button. AUTO
21
4. Parameters
4.1 Operator Parameters
4.1.1 Generator
CT ratio
Load current transformers transfer ratio(Primary current/Secondary current) value must be entered to
this parameter.
Example:
If Current Transformer Primary=500A and Current Transformer Secondary=5A, Current Transformer
Ratio should be entered CT Primary/CT Secondary=100.
PT ratio
Defines the scaling factor applied to voltage readout and associated fault conditions.
This PT ratio is for additional voltage transformers mounted the unit.
2- User Configured: Gen breakers have only close drives, when want to breaker close, close breaker
output on and after 1 sec. open breaker output on and after breaker close pulse time open breaker
output will off. When want to breaker open close breaker output and open breaker output will off.
Parameters; GEN CLOSE BREAKER CONTACT TYPE, GEN CLOSE TIMER(if gen closed input
selected), GEN OPEN TIMER(if gen closed input selected), TRANSFER TIME.
Breaker close
pulse time
1s
Gen. Open Out.
(NO) t[s]
24
rtNB
brCP brCP brCP brCP brCP brCP brCP brCP brCP brCP
GCB close sPLD sPLD sPLD
command
t[s]
brOP GbCt GbCt brOP GbCt brOP GbCt GbCt GbCt GbCt
1s 1s 1s
GCB open
command
t[s]
Feedback
input
t[s]
GCB fail to
close alarm
t[s]
GCB close
command
t[s]
GbOt GbOt
GCB open brOP
command
t[s]
Feedback
input
t[s]
GCB fail to
open alarm
t[s]
25
Transfer Time
This is used to allow for fixed duration transfer breaks when switching from mains to generator and
back. It can be used to ensure that the supply is removed from the load for fixed period of time to allow
pumps/motors to come to rest etc.
Spring Loading Time
When the unit give open command to the breaker and after that the unit want to give close command
the same breaker, this time for between open and close commands, because if there is no delay
between open and close commands can be problem the motorized switches.
Retry Number
The unit try to close breaker number of this parameter. If each try there is no close feedback, after last
try the alarm will be activated.
Digital Contrast
It is used to change contrast of LCD Display.
4.2.2 Generator
GENERATOR VOLT LEVEL (Generator->Volt level) Min Max Default Unit
Under volt shutdown Generator Under Voltage Shutdown 60(dis) 600 320 VV
Under volt prealarm Generator Under Voltage Pre-Alarm 60(dis) 600 340 VV
Under volt reset Generator Under Voltage Pre-Alarm Reset 60 600 350 VV
Over volt shutdown Generator Over Voltage Shutdown 60 600 440 VV
Over volt prealarm Generator Over Voltage Pre-Alarm 60(dis) 600 420 VV
Over volt reset Generator Over Voltage Pre-Alarm Reset 60 600 400 VV
Shutdown delay time Generator Voltage Shutdown Delay Time 0.0 10.0 1.0 Sec
GEN CUR LEVEL & ACT (Generator->Current level & act.) Min Max Default Unit
Under cur. set Generator Under Current Set 0 9999 1 AV
Under cur. prealarm Generator Under Current Pre-Alarm 0(dis) 9999 dis AV
Under cur. reset Generator Under Current Pre-Alarm Reset 0 9999 5 AV
Under cur. act. Generator Under Current Actions 0(dis) 3 dis
0 - Disable
1 - Warning (Alarm Only, No Shutdown)
2 - Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
3 - Shutdown (Alarm And Shutdown)
Under act. delay time Generator Under Current Actions Delay Time 0 99 2 Sec
Over cur. set Generator Over Current Set 0 9999 9999 AV
Over cur. prealarm Generator Over Current Pre-Alarm 0(dis) 9999 9990 AV
Over cur. reset Generator Over Current Pre-Alarm Reset 0 9999 9980 AV
Over cur. act. Generator Over Current Actions 0(dis) 3 dis
0 - Disable
1 - Warning (Alarm Only, No Shutdown)
2 - Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
3 - Shutdown (Alarm And Shutdown)
Over act. delay time Generator Over Current Actions Delay Time 0 99 2 Sec
Short circuit cur. Generator Short Circuit Current Set 0 9999 9999 AV
28
GENERATOR GENERAL (Generator->General) Min Max Default Unit
Sens.option gen.freq Sensing Options Generator Frq En/Dis ENABL/DISBL ENABL
Sens.opt.pickup&flywh*7 Sensing Opt Pickup En/Dis & Flywheel 0(dis) 1000 DISBL
All warning are latch All Warnings Are Latched En/Dis ENABL/DISBL DISBL
4.2.3 Engine
The parameters in this page are used for engine started signals. If any of the selected signals appears,
the unit assumes that the engine has started.
Crank Disconnect On Gen. Frequency
If the generator frequency over than 30.0 Hz, the unit assumes that the engine has started and the unit
stop cranking.
Crank Disconnect On Engine RPM
If the generator speed over than 500 Rpm, the unit assumes that the engine has started and the unit
stop cranking.
Crank Disconnect On Gen. Voltage
If the generator voltage over than 300 Vac, the unit assumes that the engine has started and the unit
stop cranking.
Crank Disconnect On Charge Alt. Voltage
If the charge alternator voltage over than 6.1 Vdc, the unit assumes that the engine has started and
the unit stop cranking. Note: If the charge generator input (terminal #13) is disconnect, this parameter
selected as disabled (6.0 Vdc).
Crank Disconnect On Oil Pressure
If the oil pressure sender over than this value or the oil pressure digital input (terminal #15) is not
switched to -Battery, the unit assumes that the engine has started and the unit stops cranking.
30
CANBUS ECU (Engine->CanBus ECU)*8 Min Max Default Unit
Baud rate Baud Rate: 0 7 4 kBaud
0 - 20
1 - 50
2 - 100
3 - 125
4 - 250
5 - 500
6 - 800
7 - 1.000
J1939 ECU type J1939 ECU Type Selection: 0(dis) 11 0
0 - Disable
1 - Standard
2 - Volvo EMS1
3 - Volvo EMS2
4 - Volvo EMS2b
5 - Volvo EDC3
6 - Volvo EDC4
7 - Deutz EMR2
8 - Deutz EMR3
9 - Perkins 1300
10 - Perkins ADEM3
11 - Perkins ADEM4
Device address Device Address 0 255 17
Engine cont. address Engine Control Address 0 255 0
ECU remote control ECU Remote Control via J1939 ENABL/DISBL DISBL
Speed control enable Speed Control via J1939 ENABL/DISBL DISBL
Oil pres cont. enab Oil Pressure Control via J1939 ENABL/DISBL DISBL
Temp. control enable Coolant Temperature Control via J1939 ENABL/DISBL DISBL
Speed set point Speed Set Point Selection 1500 / 1800 1500 RPM
Speed correction Speed Correction Value 0 100 50 %
Baud Rate
It defines the used Baud rate.
Note: All participants on the CAN bus must use the same Baud rate.
J1939 ECU Type Selection
The J1939 interface of this unit can be operated with different ECUs. This parameter determines the
operating mode of the used ECUs. If this parameter is selected as “disable”, No messages will be sent
or received.
Note: Volvo EMS2 engine types: TAD734, TAD940, TAD941, TAD1640, TAD1641, TAD1642.
Volvo EDC3 engine types: TAD1240, TAD1241, TAD1242.
Volvo EDC4 engine types: TD520, TAD520, TD720, TAD720, TAD721, TAD722.
Perkins engines fitted with the ADEM3 / ADEM4: 2306, 2506, 1106, 2806.
Note: Changing above mentioned parameter becomes only effective after restarting the unit.
Volvo EMS1,
Volvo EDC4, Perkins 1300,
Volvo EMS2,
Parameter Deutz EMR2, Perkins ADEM3, Standard
Volvo EMS2b,
Deutz EMR3 Perkins ADEM4
Volvo EDC3
Remote Start Yes No No No
Remote Stop Yes No No No
50/60 Hz Yes No No No
Selection
Idle Mode Yes No No No
If this parameter is selected as “Disable”, The ECU remote control via the J1939 protocol will be
disabled.
Speed Control via J1939
If this parameter is selected as “Enable”, The speed sensing from J1939 ECU will be used for the
speed (Rpm) failures.
Oil Pressure Control via J1939
If this parameter is selected as “Enable”, The oil pressure sensing from J1939 ECU will be used for the
oil pressure failures and the engine started signal.
Coolant Temperature Control via J1939
If this parameter is selected as “Enable”, The coolant temperature sensing from J1939 ECU will be
used for the coolant temperature failures.
32
CANBUS ERROR SET (Engine->CanBus error set)*9 Min Max Default Unit
CAN fault actions Can Fault Actions:
0- Disable
1- Warning Non-Latching
2- Warning (Alarm Only, No Shutdown)
3- Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
4- Shutdown (Alarm And Shutdown) 0(dis) 4 0
Red stop delay J1939 Red Stop Lamp Delay 0 250 2 Sec
For example; if the engine running hours was changed 75112 hours, the values of these
parameters was calculated as follows;
Engine Running Hour (Lsb) = Intermediate Value – (Engine Running Hour * 256)
= 9576 – (37 * 256)
= 104
Ignition Delay
With gas engines often a purging operation is desired before starting. With the engaging of the starter
the ignition delay is started. If the 'min ignition speed' is reached after expiry of this time, the
configurable relay output 'ignition' is set.
Choke Time
This timer dictates that how long choke output will be active in gasoline engines.
35
tR Interval between 2 start attempts [s]
tID Ignition delay [s]
tGV Gas valve delay [s]
tD Engine delayed monitoring [s]
[RPM]
Rated speed
[1/min;RPM]
Minimum ignition speed
will not be reached
Crank disconnect
magnetic pick-up speed
t[s]
Start request
t[s]
Ignition tID 5s
t[s]
Starter tIT tR
t[s]
Engine
monitoring ON tD
t[s]
36
tPH Preheating time [s]
tCR Engagement time [s]
tR Interval between 2 start attempts [s]
tD Engine delayed monitoring [s]
[RPM]
Rated speed
[1/min;RPM]
Crank disconnect
magnetic pick-up speed
t[s]
Start request
t[s]
Pre-heat tPH tR
t[s]
2s
Starter tCR tCR
t[s]
Fuel relay
t[s]
Engine
monitoring ON tD
t[s]
37
tPH Preheating time [s]
tCR Engagement time [s]
tR Interval between 2 start attempts [s]
tD Engine delayed monitoring [s]
tCH Choke time [s]
[RPM]
Rated speed
[1/min;RPM]
Crank disconnect
magnetic pick-up speed
t[s]
Start request
t[s]
Pre-heat tPH tR
t[s]
2s
Starter tCR tCR
t[s]
Engine
monitoring ON tD
t[s]
38
4.2.4 Inputs
39
Conf. AI high reset Configurable Analog Input 0 3000 90 %
High Reset
Conf. AI high shutd. Configurable Analog Input 0 (dis) 3000 0 (dis) %
High Shutdown
Conf. AI control ON Configurable Analog Input 0 (dis) 3000 0 (dis) %
control ON
Conf. AI control OFF Configurable Analog Input 0 3000 75 %
control OFF
40
SENDER LINEARISATION (Inputs->Sender linearisation) Min Max Default Unit
Oil pressure sender 1 Oil Pressure Sender Point-1 0 1300 11 R
Oil pressure 1 Oil Pressure Point-1 0.0 30.0 0.0 BAR
Oil pressure sender 2 Oil Pressure Sender Point-2 0 1300 29 R
Oil pressure 2 Oil Pressure Point-2 0.0 30.0 0.5 BAR
Oil pressure sender 3 Oil Pressure Sender Point-3 0 1300 47 R
Oil pressure 3 Oil Pressure Point-3 0.0 30.0 1.0 BAR
Oil pressure sender 4 Oil Pressure Sender Point-4 0 1300 65 R
Oil pressure 4 Oil Pressure Point-4 0.0 30.0 1.5 BAR
Oil pressure sender 5 Oil Pressure Sender Point-5 0 1300 82 R
Oil pressure 5 Oil Pressure Point-5 0.0 30.0 2.0 BAR
Oil pressure sender 6 Oil Pressure Sender Point-6 0 1300 100 R
Oil pressure 6 Oil Pressure Point-6 0.0 30.0 2.5 BAR
Oil pressure sender 7 Oil Pressure Sender Point-7 0 1300 117 R
Oil pressure 7 Oil Pressure Point-7 0.0 30.0 3.0 BAR
Oil pressure sender 8 Oil Pressure Sender Point-8 0 1300 134 R
Oil pressure 8 Oil Pressure Point-8 0.0 30.0 3.5 BAR
Oil pressure sender 9 Oil Pressure Sender Point-9 0 1300 151 R
Oil pressure 9 Oil Pressure Point-9 0.0 30.0 4.0 BAR
Oil pressure sender 10 Oil Pressure Sender Point-10 0 1300 184 R
Oil pressure 10 Oil Pressure Point-10 0.0 30.0 5.0 BAR
Temperature sender 1 Temperature Sender Point-1 0 1300 291 R
Temperature 1 Temperature Point-1 0 300 40 ºC
Temperature sender 2 Temperature Sender Point-2 0 1300 197 R
Temperature 2 Temperature Point-2 0 300 50 ºC
Temperature sender 3 Temperature Sender Point-3 0 1300 134 R
Temperature 3 Temperature Point-3 0 300 60 ºC
Temperature sender 4 Temperature Sender Point-4 0 1300 97 R
Temperature 4 Temperature Point-4 0 300 70 ºC
Temperature sender 5 Temperature Sender Point-5 0 1300 70 R
Temperature 5 Temperature Point-5 0 300 80 ºC
Temperature sender 6 Temperature Sender Point-6 0 1300 51 R
Temperature 6 Temperature Point-6 0 300 90 ºC
Temperature sender 7 Temperature Sender Point-7 0 1300 38 R
Temperature 7 Temperature Point-7 0 300 100 ºC
Temperature sender 8 Temperature Sender Point-8 0 1300 29 R
Temperature 8 Temperature Point-8 0 300 110 ºC
Temperature sender 9 Temperature Sender Point-9 0 1300 22 R
Temperature 9 Temperature Point-9 0 300 120 ºC
Temperature sender 10 Temperature Sender Point-10 0 1300 15 R
Temperature 10 Temperature Point-10 0 300 140 ºC
Conf. AI sender 1 Configurable Analog Input Sender Point-1 0 1300 10 R
Conf. AI value 1 Configurable Analog Input Point-1 0 3000 0 %
Conf. AI sender 2 Configurable Analog Input Sender Point-2 0 1300 30 R
Conf. AI value 2 Configurable Analog Input Point-2 0 3000 11 %
Conf. AI sender 3 Configurable Analog Input Sender Point-3 0 1300 50 R
Conf. AI value 3 Configurable Analog Input Point-3 0 3000 22 %
Conf. AI sender 4 Configurable Analog Input Sender Point-4 0 1300 70 R
Conf. AI value 4 Configurable Analog Input Point-4 0 3000 33 %
Conf. AI sender 5 Configurable Analog Input Sender Point-5 0 1300 90 R
Conf. AI value 5 Configurable Analog Input Point-5 0 3000 44 %
41
Conf. AI sender 6 Configurable Analog Input Sender Point-6 0 1300 110 R
Conf. AI value 6 Configurable Analog Input Point-6 0 3000 55 %
Conf. AI sender 7 Configurable Analog Input Sender Point-7 0 1300 130 R
Conf. AI value 7 Configurable Analog Input Point-7 0 3000 66 %
Conf. AI sender 8 Configurable Analog Input Sender Point-8 0 1300 150 R
Conf. AI value 8 Configurable Analog Input Point-8 0 3000 77 %
Conf. AI sender 9 Configurable Analog Input Sender Point-9 0 1300 170 R
Conf. AI value 9 Configurable Analog Input Point-9 0 3000 88 %
Conf. AI sender 10 Configurable Analog Input Sender Point-10 0 1300 190 R
Conf. AI value 10 Configurable Analog Input Point-10 0 3000 100 %
42
CONF. INPUT-1 (Inputs->Conf. input-1) Min Max Default Unit
Dis,user conf.or list 0- Disable 0(dis) 2 2
1- User Configured
2- Select From List
Polarity 0- Normally Open (Close To Activate) 0 1 1
1- Normally Close (Open To Activate)
Indication If User Configured 0 4 0
0- Status
1- Warning Non-Latching
2- Warning Latching
3- Electrical Trip
4- Shutdown
Activation If User Configured 0 2 2
0- Active From Starting
1- Active From Safety On
2- Always Active
Select from list If Select From List 0 28 27
0-Remote Start On Load
1-Remote Start Off Load
2-Reserved
3-Failures masked
4-Reserved
5-Reserved
6-Simulate Auto Button
7-Simulate Test Button
8-Reserved
9-Simulate Start Button
10-Simulate Stop Button
11-Generator Closed Auxiliary
12-Generator Load Inhibit
13-Reserved
14-Reserved
15-Auto Restore Inhibit
16-Auto Start Inhibit
17-Panel Lock
18-Reserved
19-Reserved
20-Reserved
21-Reserved
22-Remote Inhibit
23-Being Found Alive
24-Reserved
25-Low Oil Pressure
26-High Temperature
27-Emergency Stop
28-Low Oil Level
Active delay Input active delay 0 250 0 Sec
2 RESERVED
3 FAILURES MASKED
This input is used to prevent the engine stop when the shutdown fault was become. However the engine was
stopped when the overspeed fault was become.
4 RESERVED
5 RESERVED
8 RESERVED
14 RESERVED
46
17 PANEL LOCK
This input is used to provide security to the installation. If the panel lock input is active, the unit will not respond to
operation of the mode select or start buttons. This allows the unit to be placed into a spesific mode (such as
Auto) and than secured. The operation of the unit is not affected and the operator will still be able to view the
various instrumentation pages etc. Note: External control sources (i.e. Simulate Start Button) are not affected by
the panel lock input and will continue to operate normally.
18 RESERVED
19 RESERVED
20 RESERVED
21 RESERVED
22 REMOTE INHIBIT
In AUTO mode, if one of the configurable inputs are selected as 22 (Remote Inhibit) and this input is active, the
module will inhibit the generator for starting. In the other hand, if this input is active while the generator was
starting, the module will stop the generator.
23 BEING FOUND ALIVE
When this input is active, controlling the engine remotely is not possible.
24 RESERVED
25 LOW OIL PRESSURE
This input is used as the oil pressure failure input.
26 HIGH TEMPERATURE
This input is used as the temperature failure input.
27 EMERGENCY STOP
This input is used as the emergency stop input.
47
4.2.5 Outputs
CONF. OUTPUT-1 (Outputs->Conf. output-1) Min Max Default Unit
Polarity 0- Normally Open (Close To Activate) 0 1 0
1- Normally Close (Open To Activate)
Function 0-NOT USED
1-AIR FLAP CONTROL 0 122 43
2-ALARM RESET
3-AUDIBLE ALARM
4-AUTO START INHIBIT
5-RESERVED
6-BATTERY HIGH VOLTAGE
7-BATTERY LOW VOLTAGE
8-RESERVED
9-CAN ECU POWER (only available at Trans-MiniAUTO++.CAN)
10-CAN ECU STOP (only available at Trans-MiniAUTO++.CAN)
11-CHARGE ALTERNATOR FAILURE
12-COMMON ALARM
13-COMMON ELECTRICAL TRIP ALARM
14-COMMON SHUTDOWN ALARM
15-COMMON WARNING ALARM
16-COOLING FAN AFTER START
17-COOLING FAN AFTER STOP
18-COOLANT TEMPERATURE HIGH PRE-ALARM
19-COOLANT TEMPERATURE HIGH SHUTDOWN
20-COOLING DOWN TIMER IN PROGRESS
21-CRANK RELAY ENERGISED
22-DELAYED ALARMS ACTIVE
23-DIGITAL INPUT1 ALARM
24-DIGITAL INPUT2 ALARM
25-DIGITAL INPUT3 ALARM
26-RESERVED
27-RESERVED
28-RESERVED
29-RESERVED
30-RESERVED
31-RESERVED
32-RESERVED
33-RESERVED
34-RESERVED
35-RESERVED
36-RESERVED
37-RESERVED
38-RESERVED
39-EMERGENCY STOP
40-FAIL TO START ALARM
41-FAIL TO STOP ALARM
42-CONFIGURABLE ANALOG INPUT CONTROL
43-FUEL RELAY ENERGISED
44-GAS ENGINE IGNITION OUTPUT
45-GENERATOR AT REST
46-GENERATOR AVAILABLE
47-GENERATOR CLOSED AUXILIARY
48-GENERATOR FAILED TO CLOSE
49-GENERATOR FAILED TO OPEN
50-GENERATOR HIGH FREQUENCY PRE-ALARM
51-GENERATOR HIGH FREQUENCY SHUTDOWN
52-GENERATOR HIGH VOLTAGE PRE-ALARM
53-GENERATOR HIGH VOLTAGE SHUTDOWN
54-GENERATOR LOAD INHIBIT
55-GENERATOR LOW FREQUENCY PRE-ALARM
56-GENERATOR LOW FREQUENCY SHUTDOWN
57-GENERATOR LOW VOLTAGE PRE-ALARM
58-GENERATOR LOW VOLTAGE SHUTDOWN
59-GENERATOR STOPPING
60-GENERATOR OPEN BREAKER
61-HORN OUTPUT LATCHED
62-HORN OUTPUT PULSED
63-LAMP TEST
64-RESERVED
65-LOSS OF MAGNETIC PICK-UP SPEED SIGNAL (only available at Trans-MiniAUTO++.MPU)
66-LOW TEMPERATURE
67-MAINTENANCE DUE ALARM
68-RESERVED
69-RESERVED
70-RESERVED
71-RESERVED
72-RESERVED
73-RESERVED
74-RESERVED
75-RESERVED
76-RESERVED
77-RESERVED
78-NO LOADING COMMAND
79-OIL PRESSURE LOW PRE-ALARM
80-OIL PRESSURE LOW SHUTDOWN
81-CONFIGURABLE ANALOG INPUT HIGH PREALARM
82-CONFIGURABLE ANALOG INPUT HIGH SHUTDOWN
83-OVER CURRENT PRE-ALARM
84-OVER CURRENT
85-OVER POWER PRE-ALARM
86-OVER POWER SHUTDOWN
87-OVERSPEED PRE-ALARM
88-OVERSPEED SHUTDOWN
89-PANEL LOCK
90-PRE-HEAT(during preheat timer)
91-PRE-HEAT(until end of cranking)
92-PRE-HEAT(until end of warming)
93-PRE-HEAT(until end safety on)
94-REMOTE START PRESENT
95-REMOTE STOP DELAY IN PROGRESS
96-SHORT CIRCUIT
97-SMOKE LIMITING
98-STARTING ALARM
99-STARTING ALARMS ARMED
100-STOP RELAY ENERGISED
101-SYSTEM IN AUTO MODE
102-SYSTEM IN MANUAL MODE
103-SYSTEM IN STOP MODE
104-SYSTEM IN TEST MODE
105-UNDER CURRENT PRE-ALARM
106-UNDER CURRENT
107-UNDER POWER PRE-ALARM
108-UNDER POWER SHUTDOWN
109-UNDERSPEED PRE-ALARM
110-UNDERSPEED SHUTDOWN
111-WAITING FOR GENERATOR
112-REVERSE POWER
113-LOAD SUPPLY FROM GENERATOR
114-RESERVED
115-CONFIGURABLE ANALOG INPUT LOW PRE-ALARM
116-CONFIGURABLE ANALOG INPUT LOW SHUTDOWN
117-RESERVED
118-RESERVED
119-RESERVED
120-RESERVED
121-CHOKE ACTIVE
122-REMOTE CONTROL ACTIVE
48
CONF. OUTPUT-2 (Outputs->Conf. output-2) Min Max Default Unit
Polarity 0- Normally Open (Close To Activate) 0 1 0
1- Normally Close (Open To Activate)
Function The same as Configurable Output-1 options 0 122 21
49
CONFIGURABLE OUTPUTS SELECTIONS
0 NOT USED
Output is not used
2 ALARM RESET
The output indicates that an alarm reset being performed. Once the alarm reset has been completed, the output
become inactive again. The output could be used to give an external reset signal to external systems.
3 AUDIBLE ALARM
The output indicates that the internal sounder is operating. It may be use for external sounder.
5 RESERVED
8 RESERVED
12 COMMON ALARM
This output indicates that a warning, electrical trip or shutdown alarm has been activated.
50
18 COOLANT TEMPERATURE HIGH PRE-ALARM
This output indicates that a high engine coolant temperature warning (pre-alarm) has occurred.
26 RESERVED
27 RESERVED
28 RESERVED
29 RESERVED
30 RESERVED
31 RESERVED
32 RESERVED
33 RESERVED
34 RESERVED
35 RESERVED
36 RESERVED
37 RESERVED
38 RESERVED
39 EMERGENCY STOP
This output indicates that an emergency stop alarm has occurred.
51
44 GAS ENGINE IGNITION OUTPUT
With the engaging of the starter the ignition delay is started. If the ‘minimum ignition speed’ is reached after
expiry of this time, the configurable relay output ‘ignition’ is set. When the necessary engine shutdown process,
firstly gas valve is de-energised. Then ignition output is de-energised that after 5 seconds when the engine
speed become lower than ‘minimum ignition speed’
45 GENERATOR AT REST
The output indicates that the generator is not running.
46 GENERATOR AVAILABLE
This output indicates when the generator is ready to accept load, i.e. after safety on and warm up timers have
timed out.
59 GENERATOR STOPPING
This output indicates that the engine has been instructed to stop but has not come to rest.
63 LAMP TEST
This output indicates that the module is performing a lamp test.
64 RESERVED
52
65 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL(only available at Trans-MiniAUTO++.MPU)
This output indicates that the magnetic pick up signal is not sufficient to be used by the unit for speed monitoring.
The alarm can only operate if the speed signal fails to appearduring cranking. It is disabled if ‘multiple attempts to
engage’ is selected. If the MPU fails during engine running this would result in an under speed alarm.
66 LOW TEMPERATURE
This output indicates that a low temperature warning has occurred.
68 RESERVED
69 RESERVED
70 RESERVED
71 RESERVED
72 RESERVED
73 RESERVED
74 RESERVED
75 RESERVED
76 RESERVED
77 RESERVED
78 NO LOADING COMMAND
This output indicates that the unit is not calling of the generator contactor or breaker to be closed. Should the unit
close the generator contactor this output will become inactive.
53
89 PANEL LOCK
This output indicates that the unit ‘panel lock’ is active. If the panel lock input is active, the unit will not respond to
operation of the Mode select or start buttons. This allows the unit to be placed into a specific mode (such as
auto) and then secured.
96 SHORT CIRCUIT
This output indicates that the module has detected a short circuit on the generator output.
97 SMOKE LIMITING
This output is used to supply a smoke-limiting signal to an Electronic Governor to limit smoke emissions on start-
up. It is used in conjunction with the Smoke limit timer (Idle mode timer) settings. Once the timer has expired, the
Smoke limit output will cease to operate allowing the engine to accelerate to normal running speed.
98 STARTING ALARM
This output is used to supply an external sounder with a signal that the engine is about to start. The output will be
active during the start delay and pre-heat timer (if used).
54
107 UNDER POWER PRE-ALARM
This output indicates that the under power pre-alarm has been reached.
114 RESERVED
117 RESERVED
118 RESERVED
119 RESERVED
120 RESERVED
55
4.2.6 Timers
START TIMERS (Timers->Start timers) Min Max Default Unit
Remote start delay Remote Start Delay 0 3600 4 Sec
Pre-heat Pre-Heat 0 250 3 Sec
Pre-heat bypass Pre-Heat Bypass 0 250 0 Min
Safety on delay Safety On Delay 0 99 5 Sec
Warming up time Warmup Time 0 250 3 Sec
Horn duration Horn Duration 0 (dis) 999 60 Sec
Chg. excitation time Charge Excitation Time 0 99(cont) 15 Sec
Cooling fan time Cooling Fan Time 0 250 180 Sec
Idle mode time Idle Mode Time (Smoke Limiting) 0 (dis) 3600 dis Sec
Idle mode time off Idle Mode Time Off (Smoke Limiting Off) 0 250 5 Sec
Periodic working time Periodic Working Time 0 (dis) 600 dis Min
Periodic waiting time Periodic Waiting Time 0 (dis) 600 dis Min
Remote Start Delay
This timer dictates how long the unit will wait after it has received a remote start signal before it will
attempt to start. This prevent un-necessary starting on a fluctuating mains supply etc.
Pre-Heat
This timer dictates the duration that the pre-heat output will be active before an attempt is made to
start the engine. Once this timer is expired cranking will commence.
Pre-Heat Bypass
This feature allows the unit to start a hot engine without performing an un-necessary pre-heat delay.
The bypass timer is triggered by the generator starting and actually being loaded. If the generator
started but does not achieve loading then the timer will not be triggered. The bypass timer is initiated
once the engine has come to rest. If any attempts to start are requested within the duration of the
bypass timer the start sequence will bypass the pre-heat timer.
Safety On Delay
This timer dictates how long the unit will ignore the Low Oil Pressure, High Engine Temperature,
Underspeed, Undervolts and any other inputs configured as active from safety on. It allows the values
such as oil pressure to rise to their operating values on starting without triggering an alarm. Once the
timer has expired all alarm conditions are monitored again. If configured to use 'fast loading', should all
the monitored conditions, such as oil pressure, come to expected state prior to the end of the safety on
timer, the timer will be terminated prematurely ensuring maximum protection as soon as possible.
Warmup Time
This timer is initiated once the engine is up and running. It delays loading the generator until it has
stabilised. Once this timer is expired the 'Close generator' signal will be given and the generator is
available to be loaded.
Horn Duration
This timer dictates how long the horn will work after the last error detected. Once after this timer ended
unit will do horn reset.
Charge Excitation Time
Charge excitation was selectable as momentary / continuous operation.This timer dictates how long
the Charge excitation will active.
56
Idle Mode Time (Smoke Limiting)
This is the amount of time that the smoke limiting output will remain active for once the engine has
started. While the smoke limiting output is active the engine will be held at a reduced speed to
minimise smoke emissions on start-up. (Only if fitted with an appropriate Electronic Control Module).
Once the timer has expired the engine will be allowed to accelerate up to its normal operating speed.
Cooling Timer
This is the time the generator is to run off-load once the load transfer signal has ceased. This gives the
engine time to cool down before shutdown.
GEN. VOLTAGE OFFSET (User adjustment->Gen. voltage offset) Min Max Default Unit
Gen. V1 offset Generator V1 Offset -20 20 0 VV
Gen. V2 offset Generator V2 Offset -20 20 0 VV
Gen. V3 offset Generator V3 Offset -20 20 0 VV
SENDER INPUTS OFFSET (User adjustment->Sender inputs offset) Min Max Default Unit
Oil Pressure offset Oil Pressure Offset -2.0 2.0 0.0 BAR
Temperature offset Coolant Temperature Offset -20 20 0 ºC
Conf. AI offset Configurable Analog Input Offset -200 200 0 %
58
Error Messages And Explanations:
59
Event Messages And Explanations:
60
5. Specifications
Equipment use : Electrical control equipment for generating sets.
Housing & Mounting :111 mm x 81 mm x 61 mm. (including connectors). Plastic
housing for panel mounting.
Panel Cut-Out : 81mm x 70mm.
Protection Against Mech. Impacts: 1Joule (IK06).
Protection Class : IP65 at front panel.
Weight : Approximately 0,3 Kg.
Environmental rating : Standard, indoor at an altitude of less then 2000 meters
with non-condensing humidity.
Operating/Storage Temperature : -20°C to +70°C / -30°C to +80°C
Operating/Storage Humidity : 95 % max. (non-condensing)
Vibration : EN 60068-2-6
Ten sweeps in each of three major axes
5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn.
Shock : EN 60068-2-27
Three shocks in each of three major axes
15gn in 11mS.
Installation Over Volt. Category : II Appliances, portable equipment
Pollution Degree : II, Normal office or workplace, non conductive pollution
Mode of Operation : Continuous.
Supply Voltage and Power : 8 to 32 VZ (Peak: 36 VZ) - 3.2W
Cranking Dropouts : Battery voltage can be “0” VDC for max. 50 ms during
cranking (battery voltage should be at least nominal
voltage before cranking).
Battery Voltage Measurement : 8 to 32 V Z, accuracy: 1 % FS, resolution: 0,1 V
Generator Voltage Measurement : 10 to 300 VAC Ph-N, 5 to 99.9 Hz. Accuracy: 1 % FS,
Resolution: 1 V, Harmonics: Up to 11th.
Generator Frequency : 5 to 99.9Hz (min. 20 VAC Ph-N) Accuracy: 0,25 % FS,
Resolution: 0,1 Hz.
Magnetic Pickup Input : 35 to 10000 Hz (4 to 35 volts peak continuously).
Accuracy: 0,25 % FS. (Only available at
Trans-MiniAUTO++.MPU devices)
CT secondary : 5A.
Charge Generator Excitation : 210mA @12V, 105mA @24V. Nominal 2.5W.
Charge Gen. Vol. Measurement : 8 to 32 V Z, accuracy: 1 % FS, resolution: 0,1 V.
Sender Measurement : 0 to 1300 ohm, accuracy: 1 % FS, resolution: 1 ohm.
Communication interface : RS-232, CanBus communication with 1939 ECU(Only
available at Trans-MiniAUTO++.CAN devices)
Relay Outputs : Generator contactor relay output 8A@250VV
61
Transistor Outputs : Fuel or Configurable output-1 1A at DC supply voltage
Crank or Configurable output-2 1A at DC supply voltage
Configurable output-3 1A at DC supply voltage
Configurable output-4 1A at DC supply voltage
Configurable output-5 1A at DC supply voltage
Configurable output-6 1A at DC supply voltage
All transistor ouputs supplied from DC supply terminal 12
Approvals :
, ,
6. Other Informations
Manufacturer Information:
Emko Elektronik Sanayi ve Ticaret A.Þ.
Bursa Organize Sanayi Bölgesi, (Fethiye OSB Mah.)
Ali Osman Sönmez Bulvarý 2. Sokak, No:3
16215 Nilüfer - BURSA / TÜRKÝYE
Phone : +90 224 261 19 00
Fax : +90 224 261 19 12
Thank you very much for your preference to use Emko Elektronik
Your Technology Partner Products.
www.emkoelektronik.com.tr
62