DRYPOINT_RS_1300-6000__manual_en_2019_10_00_01
DRYPOINT_RS_1300-6000__manual_en_2019_10_00_01
DRYPOINT_RS_1300-6000__manual_en_2019_10_00_01
2 Safety instructions 5
6 Transport 13
7 Storage 13
8 Installation 14
1 Name plate
The name plate is on the back of the dryer and comprises all primary data of the device. Always refer to these data
when contacting the manufacturer or the sales department.
All guarantee claims will expire in the event that the name plate is modified or removed.
The dryer model printed on the nameplate includes one or more suffixes that specify one or more features of dryer.
2 Safety instructions
Pos : 2 /Beko Tec hnisc he Dok um entati on/Gl obal e T exte/Allgemei ner Hi nw eis BM @ 0\m od_1183615737313_6.doc @ 4004
Pos : 3 /Beko Tec hnisc he Dok um entati on/Sic herheit/Hi nweis Anlei tung BEKO @ 0\m od_1184147787557_6.doc @ 5758
Please check whether or not these instructions correspond to the device type.
Please adhere to all advice given in these operating instructions. They include essential information
which must be observed during installation, operation and maintenance. Therefore, it must be ensured
that these operating instructions are read by the fitter and the responsible operator / certified skilled
personnel prior to installation, start-up and maintenance.
The operating instructions must be accessible at all times at the place of application of the DRYPOINT®
RS 1300-6000 HP45 high pressure compressed-air refrigeration dryer.
In addition to these operating instructions, local and national regulations need to be observed, where
required.
Ensure that operation of the DRYPOINT® RS 1300-6000 HP45 high pressure compressed-air
refrigeration dryer only takes place within the permissible limit values indicated on the name plate. Any
deviation from these limit values involves a risk for persons and for the material, and may result in
malfunction or a breakdown.
After installing the device correctly and in accordance with the instructions in this manual, the dryer is
ready to operate, further settings are not required. Operation is fully automatic and maintenance is
limited to several examinations and cleaning measures which are described in the following chapters.
This manual must be available at all times for future reference and is a constituent part of the dryer.
If you have any queries regarding these installation and operating instructions, please contact BEKO
TECHNOLOGIES GMBH.
Supply voltage
Hot surfaces
Non-breathable air
Maintenance works or controlling measures must only be carried out by qualified personnel 1
Do not smoke
Note
Pos : 4 /Beko Tec hnisc he Dok um entati on/Sic herheit/Gefahr Druckluft @ 0\m od_1184148143854_6.doc @ 577
6
ARIA
AIR
LUFT Connection point compressed-air inlet
AIR
ARIA
AIR
LUFT Connection point compressed-air outlet
AIR
1
Certified skilled personnel are persons who are authorised by the manufacturer, with experience and technical training, who are well-
grounded in the respective provisions and laws and capable of carrying out the required works and of identifying and avoiding any risks during
the machine transport, installation, operation and maintenance.
Qualified and authorised operators are persons who are instructed by the manufacturer regarding the handling of the refrigeration system, with
experience and technical training, and who are well-grounded in the respective provisions and laws.
Works can be carried out by the operator of the plant, provided that they are skilled accordingly 2.
NOTE: Text that contains important specifications to be considered – does not refer to safety precautions.
The device was carefully designed with particular attention paid to environmental protection:
CFC-free refrigerants
CFC-free insulation material
Energy-saving design
Limited acoustic emissions
Dryer and packaging comprise reusable materials
This symbol advises the user to observe the environmental aspects and comply with the recommendations
connected with this symbol.
2Certified skilled personnel are persons who are authorised by the manufacturer, with experience and technical training, who are well-
grounded in the respective provisions and laws and capable of carrying out the required works and of identifying and avoiding any risks during
the machine transport, installation, operation and maintenance.
Qualified and authorised operators are persons who are instructed by the manufacturer regarding the handling of the refrigeration system, with
experience and technical training, and who are well-grounded in the respective provisions and laws.
Imminent hazard
Danger!
Consequences of non-observance: serious injury or death
Potential hazard
Warning!
Consequences of non-observance: possible serious injury or death
Imminent hazard
Caution!
Consequences of non-observance: possible injury or property damage
Potential hazard
Notice!
Consequences of non-observance: possible injury or property damage
Additional advice, info, hints
Important!
Consequences of non-observance: disadvantages during operation and maintenance, no danger
Danger!
Compressed air!
Risk of serious injury or death through contact with quickly or suddenly escaping compressed
air or through bursting and/or unsecured plant components.
Compressed air is a highly dangerous energy source.
Never work on the dryer when the system is under pressure.
Never direct the compressed-air outlet or condensate drain hoses at persons.
The user is responsible for the proper installation of the dryer. Non-observance of the instructions in the
"Installation" chapter leads to the expiration of the guarantee. Improper installation may result in
dangerous situations for the personnel and/or the device.
Pos : 5 /Beko Tec hnisc he Dok um entati on/Sic herheit/M aß nahmen Dr uckl uft BM @ 0\m od_1184148284291_6.doc @ 5812
Pos : 6 /Beko Tec hnisc he Dok um entati on/Sic herheit/Gefahr N etzs pannung @ 0\mod_1184148186948_6.doc @ 5794
Danger!
Supply voltage!
Contact with non-insulated parts carrying supply voltage involves the risk of an electric shock
resulting in injuries and death.
Only qualified and skilled personnel are authorised to run electrically-operated devices. Prior to
undertaking maintenance measures at the device, the following requirements must be met:
Make sure that the power supply is switched off and that the device is off and marked for maintenance
measures. Please also ensure that the power supply cannot be re-established during the works.
Pos : 7 /Beko Tec hnisc he Dok um entati on/Sic herheit/M aß nahmen N etz spannung BM 31/32/33 @ 0 \mod_1216898430699_6.doc @ 11319
Caution!
Refrigerant!
The compressed-air refrigeration dryer uses HFC-containing refrigerants as a coolant.
Please observe the corresponding paragraph entitled "Maintenance works at the refrigeration cycle".
Warning!
Refrigerant leak!
A refrigerant leak involves the danger of serious injury and damage to the environment.
The DRYPOINT® RS 1300-6000 HP45 high pressure compressed-air refrigeration dryer contains
fluorinated greenhouse gas/refrigerant.
Installation, repair and maintenance works at the refrigeration system must only be carried out by
certified skilled personnel (specialists). A certification in accordance with EC regulation 303/2008 must
be available.
The requirements of the EC 842/2006 directive must be met under all circumstances.
Please refer to the indications on the name plate as regards the type and amount of refrigerant.
Comply with the following protective measures and rules of conduct:
Storage: Keep the container tightly closed. Keep it in a cool and dry place. Protect it against heat
and direct sunlight. Keep it away from ignition sources.
Handling: Take measures against electrostatic charging. Ensure good ventilation/suction at the
workplace. Check fittings, connections and ducts for tightness. Do not inhale the gas. Avoid contact
with the eyes or the skin.
Prior to carrying out works on refrigerant-carrying parts, remove the refrigerant to such an extent that
safe working is possible.
Do not eat, drink or smoke during work. Keep out of the reach of children.
Breathing protection: ambient-air-independent respirator (at high concentrations).
Eye protection: sealing goggles.
Hand protection: protective gloves (e.g. made of leather).
Personal protection: protective clothing.
Skin protection: use protective cream.
In addition, the safety data sheet for the refrigerant needs to be observed!
Caution!
Hot surfaces!
During operation, several components can reach surface temperatures of more than +60°C.
There is the risk of burns.
All components concerned are installed inside of the closed housing. The housing must only be opened by
certified skilled personnel 3.
Caution!
Improper use!
The device is intended for the separation of water in compressed air. The dried compressed air cannot
be used for breathing-air purposes and is not suitable for the direct contact with food.
This dryer is not suitable for the treatment of contaminated air or of air containing solids.
3Certified skilled personnel are persons who are authorised by the manufacturer, with experience and technical training, who are well-
grounded in the respective provisions and laws and capable of carrying out the required works and of identifying and avoiding any risks during
the machine transport, installation, operation and maintenance.
Qualified and authorised operators are persons who are instructed by the manufacturer regarding the handling of the refrigeration system, with
experience and technical training, and who are well-grounded in the respective provisions and laws.
Note!
Contaminated intake air!
In the event that the intake air is strongly contaminated (ISO 8573.1 class 3.-3 or poorer quality), we recommend
the additional installation of a prefilter (e.g. CLEARPOINT HP50S040), to avoid clogging of the heat exchanger.
Caution!
Heating-up through fire!
In the event of a heating-up through fire, the containers and pipes of the refrigerant system can
burst.
In this case, please proceed as follows:
Containers and plants which are filled with refrigerant can burst violently in the event of fire.
The refrigerants themselves are incombustible, but they are degraded to very toxic products at high
temperatures.
Remove the container/plant from the fire zone, as there is the risk of bursting!
Cool down containers and bottles via a directed water jet from a safe position.
In the event of fire, please use an approved fire extinguisher. Water is not a suitable agent to
extinguish an electrical fire.
This must only be carried out by persons who are trained and informed about the hazards emanating
from the product.
Caution!
Unauthorised intervention!
Unauthorised interventions may endanger persons and plants and lead to malfunction.
Unauthorised interventions, modification and abuse of the pressure devices are prohibited.
Operators of the devices must observe the local and national pressure equipment regulations in the
country of installation.
Pos : 8 /Beko Tec hnisc he Dok um entati on/Sic herheit/Sicher heits hi nweis e, weitere BM (nic ht Ex) @ 0 \mod_1183616103770_6.doc @ 4009os : 9 /Beko Tec hnisc he D ok umentati on/Sic herheit/Z us atz Sic her hei tshi nw eise BM 33 @ 0\m od_1231926887620_6.doc @ 12829s: 10 /Beko Tec hnis che D ok umentati on/Sic her heit/Vorsic ht Fehlfunk tion @ 0\mod_1214378096290_6.doc @ 9359
Note!
Ambient conditions!
In the event that the dryer is not installed under suitable ambient conditions, the ability of the device to
condense refrigerant gas is impaired. This can result in a higher load of the refrigerating compressor,
and in a loss of efficiency and performance of the dryer.
This in turn leads to overheated condenser fan motors, to malfunction of electric components and to a
breakdown of the dryer. Failures of this type will affect warranty considerations.
Do not install the dryer in an environment in which chemicals with a corrosive effect, explosive gases,
toxic gases, evaporation heat, high ambient temperatures or extreme dust and dirt can be found.
Pos : 12 /Bek o T ec hnis che D ok umentati on/Übersc hriften/1/Bestimmungsgem äße Verwendung @ 0 \mod_1183637706293_6.doc @ 5383
3 Proper use
This dryer was designed, manufactured and tested to separate the moisture which normally exists in compressed air.
Any other use is considered improper.
The manufacturer shall not be liable for problems occurring as a consequence of improper use. The user alone is
responsible for any damage resulting from that.
Furthermore, the correct use includes the compliance with the installation instructions, in particular in respect of:
• The voltage and frequency of the main voltage supply.
• The pressure, temperature and flow rate of the inlet air.
• The pressure, temperature and cooling-water throughput (water-cooled).
• The ambient temperature.
When delivered, the dryer is tested and fully assembled. The customer only needs to connect the device to the system
in accordance with the instructions in the following chapters.
Pos : 15 /Bek o T ec hnis che D ok umentati on/Übersc hriften/1/Aussc hluss v om Anw endungs ber eich @ 0\m od_1236003439359_6.doc @ 13709
Note!
Improper use!
The device is intended for the separation of water in compressed air. The dried compressed air
cannot be used for breathing-air purposes and is not suitable for the direct contact with food.
This dryer is not suitable for the treatment of contaminated air or of air containing solids.
For the examination prior to the start-up and for periodic inspections, the national regulations need to be observed,
such as the industrial safety regulation in the Federal Republic of Germany. In countries outside the EU, the respective
regulations in force there need to be adhered to.
The proper use of pressure devices is the basic requirement for safe operation. As regards pressure devices, the
following points need to be observed:
• The DRYPOINT® RS 1300-6000 HP45 high pressure compressed-air refrigeration dryer must only be employed
within the pressure and temperature range limits indicated by the manufacturer on the name plate.
• No welding must be carried out on the pressure parts.
• The DRYPOINT® RS 1300-6000 HP45 high pressure compressed-air refrigeration dryer must neither be installed in
insufficiently ventilated rooms nor near heat sources or inflammable substances.
• To avoid fractures resulting from material fatigue, the refrigeration dryer should not be exposed to vibrations
during operation.
• The maximum operating pressure indicated by the manufacturer on the name plate must not be exceeded. It is
the installer's responsibility to install the appropriate safety and control devices. Prior to the start-up of the
DRYPOINT® RS 1300-6000 HP45 high pressure compressed-air refrigeration dryer, the connected pressure
generator (compressor etc.) must be set to the max. permissible operating pressure. The integrated safeguard
needs to be checked by an approved inspection agency.
• The documents related to the DRYPOINT® RS 1300-6000 HP45 high pressure compressed-air refrigeration dryer
(manual, operating instructions, manufacturer's declaration etc.) must be kept safe for future reference.
• No objects whatsoever must be installed at or placed on the DRYPOINT® RS 1300-6000 HP45 high pressure
compressed-air refrigeration dryer and the connecting lines.
• Operation of the plant is only permissible with fully closed and intact housing and cover panels. Operation of the
plant with damaged housing/cover panels is prohibited.
6 Transport
Check the packaging for visible loss or damage. If no visible damage can be ascertained, place the unit in close
proximity to the place of installation and unpack the device.
During this procedure, the dryer must always remain in an upright position. The components may be damaged when
the unit is tilted or turned upside down.
Store the device in a dry environment and do not expose it to extreme weather conditions.
Handle with care. Strong shocks can cause irreparable damage.
7 Storage
Keep the device away from extreme weather conditions
even when packaged.
Keep the dryer in an upright position, also while it is
stored. Tilting the device or turning it upside down can
cause irreparable damage to some components.
When the dryer is not in use, it can be stored in its
packaging in a dust-free and protected place at a
temperature of +1°C … +50°C and at a specific humidity
of max. 90%. If the storage period exceeds 12 months,
you should contact the manufacturer.
SCC0001
The packaging material is recyclable. Dispose of the material in accordance with the
directives and provisions in force in the country of destination
8 Installation
8.1 Place of installation
Note!
Ambient conditions!
In the event that the dryer is not installed under suitable ambient conditions, the ability of the device to
condense refrigerant gas is impaired. This can result in a higher load of the refrigerating compressor, and
in a loss of efficiency and performance of the dryer.
This in turn leads to overheated condenser fan motors, to malfunction of electric components and to a
breakdown of the dryer. Failures of this type will affect warranty considerations.
Do not install the dryer in an environment in which chemicals with a corrosive effect, explosive gases,
toxic gases, evaporation heat, high ambient temperatures or extreme dust and dirt can be found.
1 Air compressor
2 Aftercooler
3 Condensate separator
4 Prefilter
5 Bypass group
6 Dryer
7 Compressed-air tank
8 Final filter
9 BEKOMAT condensate drain
Installation type A is recommended when the total consumption corresponds to the throughput rate of the
compressor.
Installation type B is recommended when the air consumption constantly varies, with peak values which considerably
exceed the throughput rate of the compressor. The storage capacity of the tank must be dimensioned in such a way
that a possible short-term high air demand (peak air consumption) can be compensated.
Note!
Contaminated intake air!
In the event that the intake air is strongly contaminated (ISO 8573.1 class 3.-3 or poorer quality), we recommend
the additional installation of a prefilter (e.g. CLEARPOINT HP50S040), to avoid clogging of the heat exchanger.
Actual air throughput = air throughput acc. to planning x factor (F1) x factor (F2) x factor (F3) x factor (F4)
Example:
The DRYPOINT RS 2300 HP45 has a planned nominal capacity of 2280 m³/h. The highest achievable
air mass under the following operating conditions is:
Air inlet pressure = 35 bar(g) Factor (F1) = 0.94
Ambient temperature = 35°C Factor (F2) = 0.90
Air inlet temperature = 45°C Factor (F3) = 0.69
Pressure dew point = 10°C Factor (F4) = 1.37
Every function parameter corresponds to a numerical factor which, multiplied by the planned nominal capacity,
determines the following:
Actual air throughput = 2280 x 0.94 x 0.90 x 0.69 x 1.37 = 1823 m³/h
1823 m³/h is the maximum air mass of the dryer under the aforementioned operating conditions.
Selection of the best suitable model in accordance with the operating conditions:
To find out the correct dryer version, the required air mass must be divided by the correction factors of the
parameters indicated above:
16 DRYPOINT® RS 1300-6000 HP45
Installation
The air temperature and the air flow at the inlet of the dryer must lie within the limit values indicated on the name plate.
The connecting lines must be free from dust, iron rust, shards and other contaminations and correspond to the flow
rate of the dryer. Should air with a very high temperature be treated, the installation of an aftercooler may be
necessary. For the implementation of maintenance works, the installation of a bypass system is recommended.
Note!
Pulsation and vibrations!
Pulsations and vibrations must be eliminated from the compressed air and IN/OUT piping to avoid
possible fatigue failure.
Do not use the dryer to treat air containing corrosive substances for copper and its alloys..
CAUTION!
During the piping of the dryer, the inlet and outlet connections need to be supported as is shown in the
illustration.
Non-observance will cause damage.
Note!
Contaminated intake air!
In the event that the intake air is strongly contaminated (ISO 8573.1 class 3.-3) or poorer quality, we
recommend the additional installation of a prefilter (e.g. CLEARPOINT HP50S040), to avoid clogging of
===== Ende der Stüc kliste =====
the heat exchanger.
The temperature and the amount of cooling water need to correspond to the limit values indicated on the name plate.
The cross-section of the connecting lines, which should preferably be flexible, must be free from dust, iron rust, shards
and other contaminations. We recommend employing connecting lines (flexible hoses, vibration-inhibiting fittings etc.)
which protect the dryer against possible vibrations in the pipework.
Note!
Contaminated intake water!
In the event that the intake water is strongly contaminated we recommend the additional installation of a
prefilter (500 micron), to avoid clogging of the heat exchanger.
Delivery pressure > 3 bar (2) (3) Cl- <50 mg/l or ppm
Note: (1) – Other temperatures upon request – check the data on the name plate.
(2) – Other pressures upon request – check the data on the name plate.
(3) – Pressure difference at the water connection of the dryer at maximum water flow.
Other delivery pressures upon request.
CAUTION!
During the piping of the dryer, the inlet and outlet connections need to be supported as is shown in the
illustration.
Non-observance will cause damage.
Danger!
Supply voltage!
The connection to the electric mains should only be carried out by qualified skilled personnel and must
correspond to the legal provisions in force in your region.
Prior to connecting the device, please check the name plate to avoid exceeding the indicated values. The voltage
tolerance is +/- 10%.
The installer is responsible for supplying and installing the power cable. Be sure to provide the proper fuses or
breakers based on the data information located on the nameplate.
LGT0039
RS 1300-2300 RS 2400-6000
QS
LGT0028
CAUTION!
In this system, the direction of rotation of the compressor is supervised by a reverse-phase protector
(RPP).
When this guard is triggered, the DMC24 goes into alarm mode (the alarm LED flashes and the
display of the DMC24 shows and ). In the event that the compressor does not run, the
direction of rotation must be changed by interchanging two phases. These modifications must only be
20 DRYPOINT® RS 1300-6000 HP45
Start-up
Do not by-pass the RPP protector: If the device is operated with the incorrect direction of rotation,
the compressor will fail immediately. This will void the guarantee.
Danger!
Supply voltage and missing earth connection!
Danger!
Compressed air and condensate under pressure!
The dryer is delivered with an already integrated electronically level-controlled BEKOMAT condensate drain. Connect
the condensate drain with a collection system or container by properly screwing it on.
Do not connect the drain with pressure plants.
It is advisable to install a water-oil separator, to which the total amount of condensate from the
compressors, dryers, tanks, filters etc. is supplied.
We recommend ÖWAMAT oil-water separators for dispersed compressor condensate and BEKOSPLIT
emulsion-splitting plants for emulsified condensate.
9 Start-up
9.1 Preliminary stages
Note!
Exceeding of the operating parameters!
Ensure that the operating parameters comply with the nominal values indicated on the name plate of the
dryer (voltage, frequency, air pressure, air temperature, ambient temperature etc.).
Prior to delivery, this dryer was thoroughly tested, packed and checked. Please verify the soundness of the dryer
during the initial start-up and check the perfect functioning during the first operating hours.
The operator and the user must ensure that the dryer is not operated without panels.
Note!
The dryer must not be started up more than six times an hour. Wait at least five minutes prior to
every restart.
The user is responsible for the compliance with these provisions. Irreparable damage can be caused by
starting up the device too often.
The method below should be applied during the first start-up, after longer downtimes or subsequent to
maintenance works.
The start-up must be carried out by certified skilled personnel.
Ensure that all steps of the "Installation" chapter have been carried out.
Ensure that the connection to the compressed-air system is in accordance with the provisions and that the lines are
fixed and supported properly.
Ensure that the condensate drain pipe is fixed in accordance with the provisions and that it is connected with a
collection system or a container.
Ensure that the bypass system (if available) is open and that the dryer is isolated.
Ensure that the manual valve of the condensate outlet is open.
Ensure that the cooling-water flow and the temperature are in accordance with the provisions (water-cooled).
Remove any packaging material and other items which may block the space around the dryer.
Switch on the main switch.
• Switch on the main switch on the control panel (pos. 1).
• When the alarm LED flashes and the display of the DMC24 shows and , the current phases are
not connected correctly. Change two of the three phases at the supply mains (see Section 8.7).
• Wait at least two hours before starting the dryer (the crankcase heater of the compressor needs to heat up the
compressor oil).
• Press the button for at least two seconds to start the dryer: If the compressor was out of operation for a
sufficient period of time, it will start immediately. If this is not the case, the display shows the countdown of the
seconds until the compressor restarts and the LED flashes (max. delay five minutes).
Make sure that the consumption complies with the values of the name plate.
• Ensure that the direction of rotation of the fan corresponds to the arrows on the condenser (air-cooled).
• Slowly close the central bypass valve of the system (if installed).
• Ensure that the drain discharges at regular intervals – wait for the first interventions.
CAUTION!
In this system, the direction of rotation of the compressor is supervised by a reverse-phase protector
(RPP).
When this guard is triggered, the alarm will be activated at the DMC24 (the alarm LED flashes and
the display of the DMC24 shows and ). In the event that the compressor does not run, the
direction of rotation must be changed by interchanging two phases. These modifications must only be
carried out by a qualified electrician.
Do not by-pass the RPP protector: If the device is operated with the incorrect direction of rotation, the
compressor will fail immediately. This will void the guarantee.
During short-term shut down (max. two to three days), it is advisable to leave the dryer and the control
panel connected to the supply current circuit. Otherwise, it would be necessary at a restart of the dryer to
wait two hours, until the oil in the compressor has reached the specified operating temperature.
• Ensure that the dew point temperature indicated on the DMC24 is within the permissible range.
• Switch the dryer off after several minutes by pressing the button on the DMC24 for at least two seconds. The
display then shows .
Only use potential-free contacts that are suitable for low voltage. Ensure the sufficient insulation of
potentially dangerous voltage-carrying components.
CAUTION!
Automatic restart / remote control ON/OFF. The unit may start up without any active influence!
The user will be responsible for the installation of proper protections for possible
sudden power restoration to the dryer.
Note!
A dew point between 0°C and +10°C displayed on the control unit is considered to be correct according
to the possible operating conditions (flow rate, air inlet temperature, ambient temperature etc.).
During the operation, the refrigerating compressor runs continuously. The dryer needs to be switched on during the
entire compressed-air usage time, even if the compressed-air compressor works periodically.
Note!
The dryer must not be started up more than six times an hour. Wait at least five minutes prior to
every restart.
The user is responsible for the compliance with these provisions. Irreparable damage can be caused
when starting up the device too often.
10 Technical data
10.1 Technical data DRYPOINT RS 1300-6000 HP45 3/400/50
reset
log
ESC
info
set
3
K
T4 T3
T2
T1
PQS0060
1 Main switch
2 Electronic control unit DMC 24
3 Air and refrigerant-gas flow chart
Refrigeration cycle – The refrigerant is conducted through the compressor and reaches a condenser under high
pressure. There, cooling-down takes place, making the refrigerant condense to a liquid state which is under high
pressure. The liquid is pressed through a capillary tube where the resulting pressure drop ensures that the refrigerant
evaporates at a defined temperature. The liquid refrigerant which is under low pressure is led into the heat
exchanger, where it expands. The cold resulting from the expansion serves to cool down the compressed air
in the heat exchanger. During this process, the refrigerant evaporates. The low-pressure gas is resupplied to
the compressor, where it is compressed again. It then re-enters the cycle. In phases of a reduced
compressed-air load, the excess refrigerant is resupplied automatically to the compressor via the hot gas
bypass valve.
Technical description
2 4 37
T2
P< 12.3 12.4 P> P
12.2 mA
T3 T4
6
36
25
8
7 9 M
1a 1b
1
12.1
20
T1 11 / 35 10
DGF0103
1c
ELD
21
13
2 4 37
T2
P< 12.3 12.4 P> P
12.2 mA
T3 T4
6
36
25
7 18
1a 1b
1
19
12.1
T1 11 / 35 10 20
DGF0104
1c
ELD
21
13
8 mm
2x 5/16 in.
A
A +
4 mm
5/32 in.
-
VLY0001
VLY0003
LPS : Low-pressure appliance on the suction side of the compressor, which is triggered when the pressure dros
below the predetermined value. The values are reset automatically as soon as the nominal conditions are re-
established.
Note!
The heating resistor needs to be switched on at least two hours prior to the start-up of the refrigerant
compressor.
reset
log
ESC
info
PQS0046
set
DISPLAY
LED BUTTON
Compressor ON - green ON
Pressure in bar(g)
Pressure in psi(g)
The DMC24 controls all operations, alarms and instrument settings of the dryer. The display and the LEDs indicate all
operating conditions.
During normal operation, the display shows the dew point temperature.
The condensate drain test is always possible via the ESC button.
• Press the button for at least two seconds to start the dryer: If the compressor was out of operation for a
sufficient period of time, it will start immediately. If this is not the case, the display shows the countdown of the
seconds until the compressor restarts and the LED flashes (max. delay five minutes).
Access to the Info menu is indicated on the display by the message (first parameter of the menu). Use the
info
and arrows to move to the next or previous point. Press to have the value of the selected parameter
info
displayed. Press again to return to the list of displayable parameters.
Press ESC to leave the Info menu (if, after a period of two minutes, no button is pressed, the menu is exited
automatically).
Info Description
HP – Condensation pressure HP
The total operating hours and the hours until the next maintenance are indicated in the field 0...999 hours,
and in thousand hours from 1.0 hours onwards (example: when the display shows 35, this means 35 hours
and when the display shows 3.5, this means 3,500 hours).
When a service warning is active, the LED flashes. When the service warning was automatically reset, it has been
stored and the LED is continuously on.
In both cases the display shows the dew point temperature and the service warnings which are active or which are no
longer active but not yet reset.
Service warnings are not automatically reset (except for which can be put on automatic reset).
reset
log
To RESET the service warning, simultaneously press the buttons for three seconds. Only the stored service
warning will be reset. Service warnings which are still active continue to be indicated by the flashing LED.
NOTE: the operator/service technician must check the dryer and eliminate the problem that led to the activation of
the service warning.
HdP – High dew point: dew point too high, higher than the adjusted HdA value.
Setting T1< -1°C (30°F) delay five minutes / reset T1> 0°C (32°F)
drn - Drain: failure condensate drain (opening of the DRN contact – see electric diagram) -
delay 20 minutes
dt – Outlet temperature: compressor outlet temperature (probe T4) outside the normal
values but within the safety limits
Setting T4> 90°C (194°F) delay three minutes / reset T4< 85°C (185°F)
HCP – High condensation pressure: condensation pressure (transformer HP) outside the
normal values but within the safety limits
Setting HP> 28barg (406psig) delay three minutes / reset HP< 25barg (363psig)
NOTE: when the dryer is switched on but no system pressure is applied, the drain trouble indication may
appear.
When the alarm is active, the LED flashes. When the alarm was not automatically reset, it is stored and the
LED is on (in any case, the dryer remains OFF).
When the LED flashes, the message and the active alarms will appear in sequence on the display.
When the LED is on, the message and the alarms which triggered and which need to be reset will appear
in sequence on the display.
reset
log
The alarms are not automatically reset. To RESET an alarm, the LED needs to be on and the buttons
must be pressed simultaneously for at least three seconds.
The dryer will not start automatically subsequent to the reset of the alarms.
NOTE: the operator/service technician must check the dryer and eliminate the problem that led to the activation of
the alarm.
Alarm Description
HP – High pressure: the refrigerant high-pressure guard HPS has triggered (note: the pressure switch
has a reset button)
COn - Compressor: the compressor protection and/or the reverse-phase protector RPP have
triggered
Hdt – High outlet temperature: compressor outlet temperature outside the safety limit
Setting T4> 100°C (212°F) delay one minute / reset T4< 90°C (194°F)
ICE - ICE / Icing: Temperature in the exchanger (probe T1) is too low and leads to icing of the
condensate.
Setting T1< -3°C (27°F) delay one minute / reset T1> 0°C (32°F)
The access to the log menu is confirmed on the display by the message (L01) (first parameter of the menu).
Use the and arrows to move to the next or previous point (L01 … L10). Press log to have the selected log
value displayed. Alternatively, the parameter that triggered the alarm and the operating hours of the machine at the
moment of the alarm activation are indicated. Press log again to return to the log list.
Press ESC to leave the log menu (if, after a period of two minutes, no button is pressed, the menu is exited
automatically).
Close the contact between terminals 2 and 3 to enable the remote control. The LED lights up and it is no
longer possible to switch the dryer on or off from the local control panel (the condensate drain test is possible and
you have access to the info and log menus).
When the contact between terminals 2 and 3 is closed, close the second contact between terminals 1 and 2 to switch
on the dryer. Open the contact between terminals 1 and 2 to switch off the dryer.
Only use potential-free contacts that are suitable for low voltage. Ensure the sufficient insulation of
potentially dangerous voltage-carrying components.
CAUTION!
Automatic restart / remote control ON/OFF. The unit may start up without any active influence!
The user will be responsible for the installation of proper protections for possible
sudden power restoration to the dryer.
Dryer is switched on, no service warning and no alarm (active and not yet reset) indicated.
4 5 6
Dryer is off or a service warning or alarm (active and not yet reset) is indicated.
4 5 6
For further information, please contact your retailer or your service centre.
Only qualified personnel must be allowed to access to the setup menu. The manufacturer is not
responsible for malfunctioning or failure due to modification to the operating parameters.
info
With dryer ON or OFF and not in other menus, simultaneously press buttons set for at least 5 seconds to enter
the setup menu.
Access to the info menu is confirmed by message on the display (first parameter of menu). Use arrows and
to move to following/previous one.
Keep info pressed to display the value of the selected parameter and use arrows and to change the value.
Release the button info to confirm the value and skip to following parameter.
Press ESC to exit setup menu (if no button is pressed after 2 minutes the menu is exited automatically).
Standard
ID Description Limits Resolution
setup
0.5 °C 20
HdA - High DewPoint Alarm : Alarm threshold for a high 0.0…25.0 °C or
DewPoint (the alarm disappears when the temperature or or
drop 1°C / 2°F below alarm point) 32 … 77 °F
1 °F 68
SrV - Service Setting: setting of service warning timer. 0.0 … 9.0 0.5
8.0
00 = service warning timer disabled. (x 1000) hours (x1000) hours
AS = YES - CAUTION -
THE DRYER MAY POWER UP WITHOUT BEING ACTED UPON.
THE USER WILL BE RESPONSIBLE FOR THE INSTALLATION OF PROPER PROTECTIONS
FOR POSSIBLE SUDDEN POWER RESTORATION TO THE DRYER.
Note!
These BEKOMAT condensate drains were designed in particular for the operation in a DRYPOINT RS
HP45 refrigeration dryer. The installation in other compressed-air processing systems or the replacement
with another drain brand can lead to malfunction. The maximum operating pressure (see name plate)
must not be exceeded!
Ensure that the upstream valve is open when the dryer starts operation.
For safe operation, the device must only be installed and operated in accordance with the indications in
the operating instructions. In addition, the national and operational statutory provisions and safety
regulations, as well as the accident prevention regulations required for the respective case of
application, need to be observed during employment. This applies accordingly when accessories are
used
Danger!
Compressed air!
Risk of serious injury or death through contact with quickly or suddenly escaping compressed
air or through bursting and/or unsecured plant components.
Compressed air is a highly dangerous energy source.
Never work on the dryer when the system is under pressure.
Never direct the compressed-air outlet or condensate drain hoses at persons.
The user is responsible for the proper maintenance of the dryer. Non-observance of the instructions in
the "Installation" and "Maintenance, troubleshooting, spare parts and dismantling" chapters leads to the
expiration of the guarantee. Improper maintenance may result in dangerous situations for the personnel
and/or the device.
Danger!
Supply voltage!
Contact with non-insulated parts carrying supply voltage involves the risk of an electric shock
resulting in injuries and death.
Only qualified and skilled personnel are authorised to run electrically-operated devices. Prior to
undertaking maintenance measures at the device, the following requirements must be met:
Make sure that the power supply is switched off and that the device is off and marked for maintenance
measures. Please also ensure that the power supply cannot be re-established during the works.
Prior to carrying out maintenance works at the dryer, switch it off and wait for at least 30 minutes.
Caution!
Hot surfaces!
During operation, several components can reach surface temperatures of more than +60°C.
There is the risk of burns.
All components concerned are installed inside of the closed housing. The housing must only be opened
by certified skilled personnel.
Some components can reach high temperatures during operation. Avoid any contact until the system or
the component has cooled down.
4
Certified skilled personnel are persons who are authorised by the manufacturer, with experience and technical training, who are well-
grounded in the respective provisions and laws and capable of carrying out the required works and of identifying and avoiding any risks during
the machine transport, installation, operation and maintenance.
Qualified and authorised operators are persons who are instructed by the manufacturer regarding the handling of the refrigeration system, with
experience and technical training, and who are well-grounded in the respective provisions and laws.
DAILY:
• Check whether the dew point indicated on the electronics is correct.
• Ensure that the condensate drain system functions properly.
• Make sure that the condenser is clean.
EVERY 200 HOURS OR MONTHLY
• Clean the condenser using an air jet (max. 2 bar / 30 psig) inside out. Make
sure not to damage the aluminium lamellae of the cooling package.
• Finally, verify the operation of the device.
EVERY YEAR
• Clean housing and valve of BEKOMAT
• Replace BEKOMAT wearing parts
12.2 Troubleshooting
Danger!
Compressed air!
Risk of serious injury or death through contact with quickly or suddenly escaping compressed
air or through bursting and/or unsecured plant components.
Compressed air is a highly dangerous energy source.
Never work on the dryer when the system is under pressure.
Never direct the compressed-air outlet or condensate drain hoses at persons.
The user is responsible for the proper maintenance of the dryer. Non-observance of the instructions in
the "Installation" and "Maintenance, troubleshooting, spare parts and dismantling" chapters leads to the
expiration of the guarantee. Improper maintenance may result in dangerous situations for the personnel
and/or the device.
Danger!
Supply voltage!
Contact with non-insulated parts carrying supply voltage involves the risk of an electric shock resulting
in injuries and death.
Only qualified and skilled personnel are authorised to run electrically-operated devices. Prior to undertaking
maintenance measures at the device, the following requirements must be met:
Make sure that the power supply is switched off and that the device is off and marked for maintenance
measures. Please also ensure that the power supply cannot be re-established during the works.
Prior to carrying out maintenance works at the dryer, switch it off and wait for at least 30 minutes.
Caution!
Hot surfaces!
During operation, several components can reach surface temperatures of more than +60°C. There is
the risk of burns.
All components concerned are installed inside of the closed housing. The housing must only be opened
by certified skilled personnel.
Some components can reach high temperatures during operation. Avoid any contact until the system or
the component has cooled down.
The hot-gas bypass valve needs to be re-adjusted – contact a specialist for refrigerating
plants to have the nominal calibration re-established.
Refrigerant gas loss – contact a specialist for refrigerating plants.
◆ Dew point too low. The fan runs continuously – ensure perfect functioning of the fan power contactor (see
KV1/KV2 on the electric diagram) and/or of the pressure transducer (see BHP on the
electric diagram) – (air-cooled).
The ambient temperature is too low – re-establish the conditions indic.on the name
plate.
The hot-gas bypass valve needs to be re-adjusted – contact a specialist for
refrigerating plants to have the nominal calibration re-established.
◆ Extreme pressure The dryer does not discharge the condensate – see the corresponding paragraph.
drop in the dryer. The pressure dew point is too low – the condensate is frozen, therefore, air cannot
enter – see the corresponding paragraph.
Make sure that the connection hoses are not pinched off.
◆ The dryer does not The system pressure is too low and condensate is not discharged – re-establish the
drain the nominal conditions.
condensate. Valve for the condensate drainage is closed – open the valve.
Check the electric cabling.
Pressure dew point too low – the condensate is frozen – see the corresponding
paragraph.
BEKOMAT-discharge unit does not work properly (see BEKOMAT manual).
◆ The dryer BEKOMAT discharge unit is dirty (see BEKOMAT manual).
continuously
discharges
condensate.
◆ Water in the line. The dryer does not start – see the corresponding section.
If installed: untreated air flows through the bypass group - close it.
The dryer does not drain condensate – see the corresponding paragraph.
The pressure dew point is too high – see the corresponding paragraph.
◆ The high-pressure Check which of the following reasons is responsible for the triggering:
switch HPS has 1. The room temperature is too high or the air change insufficient – ensure sufficient
triggered. ventilation (air-cooled).
2. The condenser is dirty – please clean it (air-cooled).
3. The fan does not work – see the corresponding paragraph (air-cooled).
4. The cooling water is too hot – re-establish the operating conditions indic. on the name
plate (water-cooled).
5. Cooling-water flow insufficient - re-establish the operating conditions indic. on the name
plate (water-cooled).
Re-adjust the high-pressure switch, press the corresponding push button - check the
dryer for proper operation/function.
The HPS pressure failed or is defective – contact a specialist for refrigerating plants –
replace the high-pressure switch.
◆ The LPS low- Refrigerant gas loss – contact a specialist for refrigerating plants.
pressure switch was The low-pressure switch is automatically reset as soon as the nominal conditions are
re-established – check the dryer for proper functioning.
triggered.
◆ DMC24- LED is At a flashing LED: one or more alarms are active and the display shows
on. and the active alarms. When the LED is lit: one or more alarms need to be reset
and the display shows and the alarms which are no longer active but which still
need to be reset.
The alarms are indicated by the following messages:
1. : HPS pressure switch triggered (refrigerant high pressure) because the
condensation pressure is too high – see the corresponding paragraph (NOTE: press
the reset button on the HPS pressure switch when the problem is eliminated).
2. : LPS pressure switch triggered (low pressure) because the refrigerant pressure is
too low – see the corresponding paragraph.
3. : Con – The electrical protection of the compressor has triggered (see Q1/QC1
on the electric diagram) – reset and check the perfect functioning of the dryer.
4. : Con – during first startup - The main electrical connection of the compressor
are connected incorrectly (see RPP on the electric diagram) – change the direction of
rotation and interchange two phases. These modifications must only be carried out
by a qualified electrician. DO NOT AVOID THE RPP PROTECTION: If the device is
operated with the incorrect direction of rotation, the compressor will fail
immediately. This will void the guarantee.
5. : Con – one phase of power supply of dryer is missing (see RPP on the electric
diagram) – restore the missing phase.
6. : Con – Reverse Phase Protector (RPP) is faulty – replace it.
7. : Con – If installed – Thermal protection inside the compressor tripped (see MC1
on wiring diagram) – wait 30 minutes and try again.
8. : FAn – The electrical protection of the fan has triggered (see QV1 on the electric
diagram) – reset and check the perfect functioning of the dryer (air-cooled).
9. : FAn – The thermal protection in the fan has triggered (see MF on the circuit
diagram – wait 30 minutes and retry (air-cooled).
10. : Hdt – The outlet temperature protection of the compressor has triggered as a
result of a very high temperature (probe T4) – see the corresponding paragraph.
11. : ICE – The temperature inside the exchanger (probe T1) is too low – the dew
point is too low – see the corresponding paragraph.
12. : LCP – The condensation pressure is too low – see the corresponding
paragraph.
13. : PF4 – Failure temperature probe T4 (compressor outlet) – check the electric
cabling and/or replace the probe.
14. : PFP – Failure pressure transducer BHP (condensation pressure) – check the
electric cabling and/or replace the transformer.
NOTE: The alarms need to be reset when the problem is eliminated (simultaneously press
reset
log
the buttons for three seconds).
◆ The DMC24- When the LED flashes, one or more service warnings are active. When the
LED is on. LED is lit: one or more service warnings need to be reset. The display shows the dew
point temperature and the service warning which is active or which is not yet reset.
The service warnings are indicated by the following messages:
1. : PF1 – Failure temperature probe T1 (dew point) – check the electric cabling
and/or replace the probe.
2. : PF2 – Failure temperature probe T2 (air IN) – check the electric cabling and/or
replace the probe.
3. : PF3 – Failure temperature probe T3 (compressor intake) – check the electric
cabling and/or replace the probe.
4. : Hdp – Dew point too high (higher than the adjusted alarm value) – see the
corresponding paragraph.
3. The ambient air temperature is too high or the room ventilation insufficient – ensure
sufficient ventilation.
6. The fan runs continuously – ensure perfect functioning of the power contactor of the
fan (see KV1/KV2 on the electric diagram) and/or of the pressure transducer (see BHP
on the electric diagram) – (air-cooled).
7. The hot-gas bypass valve needs to be re-adjusted – contact a specialist to have the
nominal calibration re-established.
8. The temperature of the cooling water is too low – re-establish the nominal conditions
(water-cooled).
9. The adjusting valve for the cooling-water flow needs to be re-adjusted - contact a
specialist to have the nominal calibration re-established (water-cooled).
3. The fan does not work – see the corresponding section (air-cooled).
4. The cooling water is too hot – re-establish the nominal conditions (water-cooled).
3. Air flows through the condenser although the fan is switched off – protect the dryer
against wind or external air flows (not caused by the fan of the dryer).
5. The adjusting valve for the cooling-water flow needs to be re-adjusted - contact a
technician for refrigeration plants to have the nominal calibration re-established
(water-cooled).
Caution!
Refrigerant!
Maintenance and repair works at refrigeration systems must only be carried out by BEKO service
technicians in accordance with the local provisions.
The total amount of refrigerant in the system must be collected for recycling purposes, resource recovery
or disposal.
The refrigerant must not be discharged into the environment.
When delivered, the dryer is ready to operate and filled with a refrigerant of the R407C type.
Should you detect a refrigerant leak, please contact a BEKO service technician. Prior to any intervention,
the room needs to be ventilated.
When the refrigeration cycle needs to be refilled, please also contact a BEKO service technician.
You will find the refrigerant type and amount on the name plate of the dryer.
Part Material
Pipe Copper
We recommend observing the safety provisions in force for the disposal of each material type.
The refrigerant contains lubricating-oil droplets which are released by the compressor.
The refrigerant must not be discharged into the environment. It must to be sucked off from the dryer
using a suitable device, and then needs to be supplied to a collection point.
13 Appendices
13.1 Dryer dimensions
21 BEKOMAT drain
MC : Compressor
MV : Condenser fan
NT2 : Check the transformer connections with regard to the supply voltage
BN = BROWN OR = ORANGE
BU = BLUE RD = RED
BK = BLACK WH = WHITE
YG = YELLOW/GREEN WH/BK = WHITE/BLACK
13.3.2 Electric diagrams DRYPOINT RS 1300-2300 HP45 - Electronic control unit DMC 24 Sheet 1/3
13.3.3 Electric diagrams DRYPOINT RS 1300-2300 HP45 - Electronic control unit DMC 24 Sheet 2/3
13.3.4 Electric diagrams DRYPOINT RS 1300-2300 HP45 - Electronic control unit DMC 24 Sheet 3/3
13.3.5 Electric diagrams DRYPOINT RS 2400-6000 HP45 - Electronic control unit DMC 24 Sheet 1/4
13.3.6 Electric diagrams DRYPOINT RS 2400-6000 HP45 - Electronic control unit DMC 24 Sheet 2/4
13.3.7 Electric diagrams DRYPOINT RS 2400-6000 HP45 - Electronic control unit DMC 24 Sheet 3/4
13.3.8 Electric diagrams DRYPOINT RS 2400-6000 HP45 - Electronic control unit DMC 24 Sheet 4/4
14 EC Declaration of conformity
EC declarations of dryers
DP RS 5000 HP45
and
DP RS 6000 HP45
will be issued individually