Flexible Duct
Flexible Duct
PROJECT : Manufacturer:
CLIENT : Supplier:
Sharjah
A/C CONTRACTOR :
+971 588917130
M/S ERGA ENGINEERING [email protected]
INDEX
1. PRODUCT CATALOGUE
2. COMPLIANCE STATEMENT
3. TEST REPORTS
6. COMPANY PROFILE
P.O.Box 50673, Dubai Investments Park 2. | www.rhira.com | E: [email protected] | T: +971 4 8848 414
PRODUCT CATALOGUE
P.O.Box 50673, Dubai Investments Park 2. | www.rhira.com | E: [email protected] | T: +971 4 8848 414
ASTM E84
10"w.g. - 4" - 16" 10"w.g. - 4" - 16" 10"w.g. - 4" - 16"
6"w.g. - 18" - 20" 6"w.g. - 18" - 20" 6"w.g. - 18" - 20"
P.O.Box 50673, Dubai Investments Park 2. | www.rhira.com | E: [email protected] | T: +971 4 8848 414
COMPLIANCE STATEMENT FOR AERODUCT FLEXIBLE DUCT
1
Insulated Flexible Duct ADI1M
Insulation Thickness 25 mm
Density 16 kg/m3
P.O.Box 50673, Dubai Investments Park 2. | www.rhira.com | E: [email protected] | T: +971 4 8848 414
Test Report No. 7191231221-MEC20/2-YWA
dated 23 Apr 2020
Note: This report is issued subject to the Testing and Certification Regulations of the TÜV SÜD Group and the
General Terms and Conditions of Business of TÜV SÜD PSB Pte Ltd. In addition, this report is governed by the
terms set out within this report.
SUBJECT:
Fire propagation test on Brand: “Aeroduct”, Model: “Aeroduct” Flexible Duct for
Central Airconditioning material submitted by Hira Industries LLC on 11 Mar 2020.
TESTED FOR:
DATE OF TEST:
07 Apr 2020
PURPOSE OF TEST:
The test was conducted at TÜV SÜD PSB’s fire test laboratory located at No. 10
Tuas Avenue 10, Singapore 639134.
DESCRIPTION OF SPECIMENS:
Brand “Aeroduct”
Model reference “Aeroduct”
Generic product name Flexible Duct
Overlapped Aluminium Foil / Glass Wool / Overlapped
Material composition Aluminium Foil
Country of Origin United Arab Emirates
Nominal thickness (mm) -
Nominal bulk density (kg/m3) -
Fire retardant -
Page 2 of 7
Test Report No. 7191231221-MEC20/2-YWA
dated 23 Apr 2020
TEST PROCEDURE:
Prior to test, the specimens were prepared and conditioned in accordance with
paragraph 4.4 of the standard.
Three specimens, backed with calcium silicate board, were tested with the
Aluminium Foil face exposed to the specified heating conditions, in an apparatus
conforming to paragraph 5 and illustrated in Figures 1 to 3 of the Standard.
The mean temperature rise above ambient obtained from three specimens is also
shown in Figure 1 (i.e. with the actual calibration curve). The mean temperature
readings for the material and the calibration curve were obtained at the following
intervals from the start of the test: at 1/2 minute intervals up to 3 minutes, at 1 minute
intervals from 4 to 10 minutes, and at 2 minutes intervals from 12 to 20 minutes.
Page 3 of 7
Test Report No. 7191231221-MEC20/2-YWA
dated 23 Apr 2020
From these readings, the index of performance for the material was determined as
follows:
t=3 s- c t = 10 s- c
s1 = ———; s2 = ———
t = 0.5 10t t=4 10t
t = 20 s- c
and s3 = ———;
t = 12 10t
S = s1 + s2 + s3
s- c
Page 4 of 7
Test Report No. 7191231221-MEC20/2-YWA
dated 23 Apr 2020
RESULTS OF TEST:
The following test results were obtained for each specimen tested:
CONCLUSION:
The test results obtained, as an average of the 3 samples tested are as follows:
Sub-index, i1 = 1.2
Sub-index, i2 = 2.1
Sub-index, i3 = 1.0
REMARKS:
The test results relate only to the behaviour of the test specimens of the product
under the particular conditions of test; they are not intended to be the sole criterion
for assessing the potential fire hazard of the product in use.
________________ _____________
Ye Wint Aung Ong Kian Huat
Higher Associate Engineer Assistant Manager
Fire Property
Mechanical
Page 5 of 7
Test Report No. 7191231221-MEC20/2-YWA
dated 23 Apr 2020
400
Calibration Curve
300
TEMPERATURE RISE (deg C)
250
200
150
100
50
0
0 2 4 6 8 10 12 14 16 18 20
TIME(min)
Page 6 of 7
Test Report No. 7191231221-MEC20/2-YWA
dated 23 Apr 2020
Please note that this Report is issued under the following terms :
1. This report applies to the sample of the specific product/equipment given at the time of its testing/calibration. The results are not used to
indicate or imply that they are applicable to other similar items. In addition, such results must not be used to indicate or imply that TÜV SÜD
PSB approves, recommends or endorses the manufacturer, supplier or user of such product/equipment, or that TÜV SÜD PSB in any way
“guarantees” the later performance of the product/equipment. Unless otherwise stated in this report, no tests were conducted to determine
long term effects of using the specific product/equipment.
2. The sample/s mentioned in this report is/are submitted/supplied/manufactured by the Client. TÜV SÜD PSB therefore assumes no responsibility for
the accuracy of information on the brand name, model number, origin of manufacture, consignment or any information supplied.
3. Nothing in this report shall be interpreted to mean that TÜV SÜD PSB has verified or ascertained any endorsement or marks from any other
testing authority or bodies that may be found on that sample.
4. This report shall not be reproduced wholly or in parts and no reference shall be made by the Client to TÜV SÜD PSB or to the report or
results furnished by TÜV SÜD PSB in any advertisements or sales promotion.
5. Unless otherwise stated, the tests were carried out in TÜV SÜD PSB Pte Ltd, No.1 Science Park Drive Singapore 118221.
July 2011
Page 7 of 7
Test Report No. 7191231221-MEC20/1-YWA
dated 23 Apr 2020
Note: This report is issued subject to the Testing and Certification Regulations of the TÜV SÜD Group and the
General Terms and Conditions of Business of TÜV SÜD PSB Pte Ltd. In addition, this report is governed by the
terms set out within this report.
SUBJECT:
Surface spread of flame test on Brand: “Aeroduct”, Model: “Aeroduct” Flexible Duct
for Central Airconditioning material submitted by Hira Industries LLC on 11 Mar 2020.
TESTED FOR:
DATE OF TEST:
01 Apr 2020
PURPOSE OF TEST:
The test was conducted at TÜV SÜD PSB’s fire test laboratory located at No. 10
Tuas Avenue 10, Singapore 639134.
DESCRIPTION OF SPECIMENS:
Brand “Aeroduct”
Model reference “Aeroduct”
Generic product name Flexible Duct
Overlapped Aluminium Foil / Glass Wool / Overlapped
Material composition Aluminium Foil
Country of Origin United Arab Emirates
Nominal thickness (mm) -
Nominal bulk density (kg/m3) -
Fire retardant -
Page 2 of 6
Test Report No. 7191231221-MEC20/1-YWA
dated 23 Apr 2020
TEST PROCEDURE:
Prior to test, the specimens were prepared and conditioned in accordance with
paragraphs 5.3 to 5.6 of the standard and secured to a specimen holder as
described in paragraph 6.3.
Six specimens, backed with calcium silicate board, were tested with the Aluminium Foil
face exposed to the specified thermal radiation from the apparatus described in paragraph
6.1 of the standard. The intensity of the radiated heat incident on the specimen varies with
distance from the hotter end, so that when the specified calibration panel is mounted in the
place to be occupied by the specimen, the irradiance of the radiometer is as given in Table
1. The test was terminated when the flame front reached the 825mm reference line, or after
10 minutes has elapsed, whichever is the shorter.
Page 3 of 6
Test Report No. 7191231221-MEC20/1-YWA
dated 23 Apr 2020
RESULTS OF TEST:
Specimen No. 1 2 3 4 5 6
Spread of flame at
first 1½ minutes (mm) 75-165 75-165 75-165 165-190 75-165 75-165
Distance (mm) Time of spread of flame to indicated distance
(minutes seconds)
Start of flaming 0.05 0.06 0.07 0.05 0.06 0.05
75 0.07 0.11 0.10 0.09 0.10 0.09
165 - - *0.15 0.14 *0.14 *0.15
190 - *0.16 - *0.16
215 - -
240
265
290
375
455
500
525
600
675
710
750
785
825
865
Time of maximum
spread of flame 0.07 0.11 0.10 0.14 0.10 0.09
(minutes seconds)
Distance of maximum
spread of flame (mm) 75-165 75-165 75-165 165-190 75-165 75-165
Comments 1. * - indicates flaming was observed above the horizontal reference line.
2. For specimen 1, 2, 3, 4, 5 and 6, the maximum flame time was 12 seconds,
14 seconds, 20 seconds, 21 seconds, 28 seconds and 21 seconds
respectively.
Page 4 of 6
Test Report No. 7191231221-MEC20/1-YWA
dated 23 Apr 2020
CONCLUSION:
In accordance with the class definitions specified in the Standard, the test results
show that the sample tested has a Class 1 Surface Spread of Flame.
REMARKS:
The test results relate only to the behaviour of the test specimens of the product
under the particular conditions of test; they are not intended to be the sole criterion
for assessing the potential fire hazard of the product in use.
______________ _____________
Ye Wint Aung Ong Kian Huat
Higher Associate Engineer Assistant Manager
Fire Property
Mechanical
Page 5 of 6
Test Report No. 7191231221-MEC20/1-YWA
dated 23 Apr 2020
Please note that this Report is issued under the following terms :
1. This report applies to the sample of the specific product/equipment given at the time of its testing/calibration. The results are not used to
indicate or imply that they are applicable to other similar items. In addition, such results must not be used to indicate or imply that TÜV SÜD
PSB approves, recommends or endorses the manufacturer, supplier or user of such product/equipment, or that TÜV SÜD PSB in any way
“guarantees” the later performance of the product/equipment. Unless otherwise stated in this report, no tests were conducted to determine
long term effects of using the specific product/equipment.
2. The sample/s mentioned in this report is/are submitted/supplied/manufactured by the Client. TÜV SÜD PSB therefore assumes no responsibility for
the accuracy of information on the brand name, model number, origin of manufacture, consignment or any information supplied.
3. Nothing in this report shall be interpreted to mean that TÜV SÜD PSB has verified or ascertained any endorsement or marks from any other
testing authority or bodies that may be found on that sample.
4. This report shall not be reproduced wholly or in parts and no reference shall be made by the Client to TÜV SÜD PSB or to the report or
results furnished by TÜV SÜD PSB in any advertisements or sales promotion.
5. Unless otherwise stated, the tests were carried out in TÜV SÜD PSB Pte Ltd, No.1 Science Park Drive Singapore 118221.
July 2011
Page 6 of 6
PROJECT REFERENCE LIST
P.O.Box 50673, Dubai Investments Park 2. | www.rhira.com | E: [email protected] | T: +971 4 8848 414
PROJECT REFERENCE LIST
Region : United Arab Emirates
Page 1 of 4
Project Name
Contractor Consultant
The Emerald Palace Residential
Al Habtoor Engineering ATKINS
& Hotel Project
B+G+3 Storey Offices Building Pluto Ele/Mech
at Al Mamzar Al Gurg Consultants
2B+G+7 Hotel Bldg. At
Galadari Electromechanical ARCHGROUP Consultant
Mankhool, Dubai
Al Bateen @ Jumeriah Towers
Commodore Contracting National Engineering Bureau
Bab Al Bahr A luxury collection Architectural & Engineering
Trans Gulf Electromechanical
Hotel Consultants
Dubai Mixed Use Arabian Construction Co. / MAPCO KEO International
Grand Hotel Efeco ATKINS
Juma Al Majid Electromechanical
Al Wahda Mall 2 Khatib & Alami
Works
Sheikh Khalifa Specialist
Emirates Trading Agency Al Bayaty Architects
Hospital (RAK – UAE)
Shams Gateway Towers 3 to 8 Thermo Khatib & Alami
Sinogulf Tower Group 3 Woods Bagot
Corporate Towers @
National Projects & Construction LLC National Engineering Bureau
Al Reem Island
City of Lights @
China State Construction P & T Architects & Engineers
Al Reem Island
Infinity Tower Drake & Scull Khatib & Alami
Qasr Al Sarab Resort & SPA Al Jaber Engineeering Halcrow
Paris Sorbone University Al Habtoor Specon Parsons
Central Market Development MAPCO BDSP
Dalma Mall Hastie International DIAR
Wahat Hili Mall & Hotel MAPCO ACG
Park Rotana Mixed Use
Drake & Scull Al Salam
Development
Mist 1 A Project STS Abu Dhabi PHA
Al Ain Water Resort & Water
Al Sabbah K&A
Park
Al Ain University Hastie International AECOM
Al Muneera – Al Raha Beach
Drake & Scull Waterman Emirates
Development
Mangrove Palace Drake & Scull UPA
Cleveland Clinic @ AbuDhabi Emirates Trading Agency AECOM
Ruwais Housing Complex‐II SK Eng / Sigma Eng APG
Officers Accommodation @ Al
Al Oboor / Climacond Secure
Forsan site
BMW Showroom & workshop Tawazun Construction Al Rawasi Consulting Engineers
Nilona Tower Marriott Hotel Al Rostamani Pagel Arif Bintoak
Page 2 of 4
PROJECT APPROVALS
P.O.Box 50673, Dubai Investments Park 2. | www.rhira.com | E: [email protected] | T: +971 4 8848 414
SUBMITTAL COVER SHEET
Comments :
ENGINEER’S SIGNATURE
EX2020-LP/PM/02
~ AF~
MANUFACTURER/SUPPLIER DELIVERY
Company Name : Menasco Mechanical Contracting Country of Origin : AERODUCT/UAE
·--······ ----·-··---··--··-·--
..
Ramesh Hira LLC Availability Locally Manufactured []
Address Hira Industries C.C.A.S.G. Manufactured [J
--····-···---·------···--·-·-·-·-
______ __________
.. _____
,..... ,_,,,, Manufacture Production Period [_]
Delivery Ex-Works [_]
Local Agent __ -
Menasco Mechanical Contracting
.....,_. ,.................... ............................... Total delivery time [_]
Overland [1
Sea Freight
Total Freight
I [c 1i
PROGRAMME Date material required on site
Engineer's Comments :
Estimated date of arrival on site Signature: A
. 111~
Refer to the attached sheet for the comments.
~ 12/04/2020
Engineer's Comments:-
1. Insulation thickness and density shall be as per project specification.
2. Contractor to comply with the consultant comments.
Approval Status
A. Approved [ I I B. A(!(!roved with Comm!:lot:i -.JI
.., C. Rejected Revise & Resubm it [ I D. For Information [ 1
,,/
RESIDENT ENGINEER <\()~~ Date:
.. " -- ("
=-<:_)-
Distribution:
P.O.Box 50673, Dubai Investments Park 2. | www.rhira.com | E: [email protected] | T: +971 4 8848 414
® ®
1200
‘Hira Industries’ is dedicated to provide customers ‘Hira Industries’ aim’s to be a Global Leader in
in the Construction Sector with products of the niche products in building product industry. We
highest quality, by developing a successful aim to be the Market Leaders in the segments and
partnership with them, exceeding their expectations the regions we choose to compete in.
and gaining their trust through outstanding
performance by every member of our team. We
provide work environments where our employees
can meet their potential and thrive in an atmosphere
of professionalism. Our aim is to become the
“Employer of Choice” within the Building Product
HVAC Acessories
Industry.
thermal
Air Ducts
Used for hot, chilled water pipes and air conditioning applications with
minimal cost of installation.
Automobile industries
Furniture packaging
Optical equipments
REFLECTIVE INSULATION
AeroReflect range is a thermal reflective insulation product which
prevents heat transfer by thermal radiations.
spaces.
www.hirawalraven.com
Diamond Tapes, the Adhesive Tapes Division of Hira
Legal Type Limited Liability Company - Single Owner)LLC - SO( ).م.م. الشخص الواحد (ذ- شركة ذات مسؤولية محدودة الشكل القانونى
Expiry Date 19/08/2025 تاريخ النتهاء Issue Date 20/08/2002 تاريخ الصدار
D&B D-U-N-S ® N 561246349 الرقم العالمي Main License No 536867 رقم الرخصة الم
Register No. 1753156 رقم السجل التجارى DCCI No. 72664 عضوية الغرفة
100.00% Shares Owner / مالك British Virgin Islands / جزر هيرا هولدينج كومباني ليمتد 554141
حصص العذراء البريطانية
HIRA HOLDING COMPANY LTD
Manager / مدير India / الهند بريان بيريرا 1128510
BRYAN PEREIRA
Print Date 19/08/2024 13:31 تاريخ الطباعة Receipt No. 15950266 رقم اليصال
)اتصالت/ (دو6969 أرسل رقم الرخصة إلى،يمكنك الن تجديد رخصتك التجارية من خلل الرسائل النصية القصيرة
Get FREE access to
.للحصول على اذن الدفع
Zoho One for the first
Now you can renew your trade license by sending a text message )SMS(. Send your year
trade license number to 6969 )Du/ Etisalat( to receive payment voucher. - احصل على زوهو ون مجانا
للسنة الولى Zoho.com/det
لمراجعة صحة البيانات الواردة في الرخصة يرجي مسح رمزالستجابة السريعة. وثيقة إلكترونية معتمدة وصادرة بدون توقيع من دائرة القتصاد والسياحة في دبي
this is a certified e-document issued without signature by the department of Economy and Tourism .Kindly Scan the QR Code to
Verify the certificate
Address / العنوان
Phone No 971-4-8848414 تليفون P.O. Box 50673 صندوق بريد
Fax No 971-4-8848434 فاكس Parcel ID 0 رقم القطعة
Mobile No 971-55-1091958 هاتف متحرك [email protected] Email / البريد اللكتروني
Remarks / الملحظات
Print Date 19/08/2024 13:31 تاريخ الطباعة Receipt No. 15950266 رقم اليصال
)اتصالت/ (دو6969 أرسل رقم الرخصة إلى،يمكنك الن تجديد رخصتك التجارية من خلل الرسائل النصية القصيرة
Get FREE access to
.للحصول على اذن الدفع
Zoho One for the first
Now you can renew your trade license by sending a text message )SMS(. Send your year
trade license number to 6969 )Du/ Etisalat( to receive payment voucher. - احصل على زوهو ون مجانا
للسنة الولى Zoho.com/det
لمراجعة صحة البيانات الواردة في الرخصة يرجي مسح رمزالستجابة السريعة. وثيقة إلكترونية معتمدة وصادرة بدون توقيع من دائرة القتصاد والسياحة في دبي
this is a certified e-document issued without signature by the department of Economy and Tourism .Kindly Scan the QR Code to
Verify the certificate
شهادة شهر قيد شركة فى السجل التجارى
Commercial Register
Register Details / تفاصيل القــيد
Main Lice. Nr 536867 رقم الرخصة المRegister No. 1753156 رقم القيد
Print Date 19/08/2024 13:31 تاريخ الطباعة Receipt No. 15950266 رقم اليصال
)اتصالت/ (دو6969 أرسل رقم الرخصة إلى،يمكنك الن تجديد رخصتك التجارية من خلل الرسائل النصية القصيرة
Get FREE access to
.للحصول على اذن الدفع
Zoho One for the first
Now you can renew your trade license by sending a text message )SMS(. Send your year
trade license number to 6969 )Du/ Etisalat( to receive payment voucher. - احصل على زوهو ون مجانا
للسنة الولى Zoho.com/det
لمراجعة صحة البيانات الواردة في الرخصة يرجي مسح رمزالستجابة السريعة. وثيقة إلكترونية معتمدة وصادرة بدون توقيع من دائرة القتصاد والسياحة في دبي