PERHITUNGAN DINDING PENAHAN TANAH

0.50

5.50
7.00

0.50
1.00

1.00 1.00 3.00

5.00

1. Data Rencana Retaining Wall 1 (RW1)


Data Tanah
γ = 26,5 kN/m3
Beban Merata Atas Tanah
q = 10,0 kN/m2

2. Dimensi Dinding Penahan Tanah


Tinggi dari Permukaan Tanah (h1) = 5,50 m
Tinggi tanah di depan dinding (h2) = 1,50 m
Tebal Pelapak (h3) = 1,00 m
Tinggi Total (H) = 7,00 m
Lebar Toe (b1) = 1,00 m
Lebar Heel (b2) = 3,00 m
Tebal Dinding Atas (ba) = 0,50 m
Tebal Dinding Bawah (bb) = 1,00 m
Lebar Total (B) = 5,00 m

3. Menghitung Nilai Cohesi (c ) dan Sudut Geser Tanah(ϕ) Menggunakan data Sondir
∑qc rata-rata hingga kedalaman dinding tanah
qcr =
∑titik
2
=
1
2
= 2 kg/cm
2
= 20000 kg/m
c = 20000 kg/m2
= 200,00 kN/m2

Po' = γtanah x h
= 2650 x 7
= 21200 kg/m2
sehingga; Vb = qcr
Po'
= 20000
21200
= 0,943396
Selanjutnya, untuk mengapatkan sudut geser dalam, dapat melihat grafik hubungan Vb dengan ϕ
disamping. sehingga didapatkan nilai sudut geser dalam,

ϕ = 45 ⁰

4. Koefisien Tekanan Tanah (Teori Rankine)


Koefisien tekanan tanah aktif (Ka)
Ka = Tan2 (45 - ɸ/2)
= Tan2 (45 - 23 )
= tan2 (23) = 0,17

Koefisien Tekanan Tanah Pasif (Kp)


Kp = Tan2 (45 + ɸ/2)
Tan2 (45 + 23 )
tan2 (68) = 5,83
5. Tekanan Tanah Aktif

Pa1

Pa2

Pp

Akibat beban merata tambahan (Pa1)


hs = q 10
= = 0,38 m
γ 27
Pa1 = Ka . γ . hs . H
= 0,17 x 27 x 0,38 x 7,00
= 12,01 kN

Akibat Tanah dibelakang dinding


2
Pa2 = 1/2 . Ka . γ . H
= 0,09 x 27 x 5,50 x 5,50
= 68,77 kN

6. Tekanan Tanah Pasif


Pp = 1/2 . Kp . γ . (h2+h3) . (h2 +h3)
= 2,91 x 27 x 1,50 x 1,50
= 173,76 kN
7. Cek Terhadap Guling
Momen Penggulingan (Mo)
Mo = (Pa1 . H/2) + (Pa2 . H/3)
= 42,04 kNm + 126,08 kNm
= 168,11 kNm
Momen Penahan (Mb)
Berat Jenis Beton (γb) =24,0 kN/m3
Bidang 1
W1 = B. h . γb
= 1,00 x 5,00 x 24,00
= 120,00 kN
Bidang 2
W2 = B . h . γb
= 6,00 x 0,50 x 24,00
= 72,00 kN
Bidang 3
W3 = (b1xb2/2) . γb
= 1,50 x 24,00
= 36,00 kN
Beban Akibat Beban Merata
Wq = q . b2
= 10,00 x 3,00
= 30,00 kN

Komponen Berat (kN) xn (m) Momen (kNm)


W1 120,00 2,5 300
W2 72,00 1,75 126,00
W3 36,00 1,34 48,24
Wq 30,00 4,28 128,40
Jumlah R = 258,00 Mb = 602,64
0.50
5.50
7.00

0.50
1.00

1.00 1.00 3.00

5.00

1.34

1.75

2.50

4.28

Mb 602,64
FS = = = 3,58 >2 OK
Mo 168,11

8. Cek Terhadap Geser


Gaya Geser (Vo)
Vo = Pa1 + Pa2
= 12,01 kN + 68,77 kN
= 80,78 kN

Gaya Penahan (Vb)


Vb = (µ . R) + Pp
= 154,80 kN + 173,76 kN
= 328,56 kN

Cek Terhadap Geser (Fsmin = 1,5)


Vb 328,56
FS = = = 4,07 > 1,5 OK
Vo 80,78
9. Cek Terhadap Daya Dukung Tanah
Eksentrisitas (e)
B Mb - Mo B
e = - <
2 R 5
5,00 602,64 - 168,11 5,00
= - <
2 258,00 5
= 2,5 - 1,68 < 1,00
= 0,82 < 1,00 OK

Kapasitas Ultimate Tanah (Qu)


Untuk tanah dengan ɸ = 45 ° didapatkan:
Nq = 134,88
Nc = 133,88
Nγ = 271,76

q = γ . (h2 + h3)
= 27 x 1,50 + 1,00
= 66,25 kN/m2
B' = B - 2e
= 5,00 - 1,63
= 3,37 m
β = tan−1(𝑃𝑎 cos 𝛼 )
𝑅
80,78 0,53
= tan -1
[ 258,00 ]
= 9,34

Faktor Bentuk:
𝐵 𝑁𝑞
𝐹𝑐𝑠 = 𝑥 +1
𝐿 𝑁𝑐
= 0,714285714 x 1,01 +1
= 1,72
𝐵
𝐹𝑞𝑠 = 𝑥 tan 𝜑 + 1
𝐿
= 0,714285714 x 1,00 +1
= 1,71
𝐵
𝐹𝛾𝑠 = 1 − 𝑥 0,4
𝐿
= 1- ( 0,71 x 0,40 )
= 0,71

Faktor Kedalaman:
ℎ2 + ℎ3
𝐹𝑐𝑑 = 1 + 0,4 𝑥
𝐵
2,50
= [ 5,00
x 0,4 ] +1
= 1,20
ℎ2 + ℎ3
𝐹𝑞𝑑 = 1 + 2 . tan 𝜑 . 1 − sin 𝜑 2 )𝑥
𝐵
2,50
1 + ( 2,00 x 0,09 x )
= 5,00
= 1,09
Fγd = 1

Faktor Inklinasi
2
𝛽
𝐹𝑐𝑖 = 1 −
90
9,34
= 1- [ 90,00 ] 2

= 0,989229817
2
2
𝛽
𝐹𝑞𝑖 = 1 −
90
9,34
= 1- [ 90,00 ] 2

= 0,989229817
2
𝛽
𝐹𝛾𝑖 = 1 −
𝜑
9,34
= 1- [ 45,00 ] 2

= 0,956919267

Kapasitas Ultimate Tanah (Qu)


Qu = (c . Nc . Fcs . Fcd . Fci) + (q . Nq . Fqs . Fqd . Fqi) + (0,5 . γ . B . Nγ . Fγs . Fγd . Fγi)
= 69447,99 kN/m2

Kapasitas Izin Tanah (Qa)


Faktor Aman (Fs) = 3
Qa = Qu 69447,99
= = 23149 kN/m2
Fs 3,00

Tegangan Tanah di bawah dinding (Qtoe dan Qheel)


𝑅 6𝑒
𝑄𝑡𝑜𝑒 = 𝑥 1+
𝐵 𝐵
258,00 4,89
= x(1 + )
5,00 5,00
= 102,1 kN/m2 < Qa = 23149,3 kN/m2 OK

𝑅 6𝑒
𝑄ℎ𝑒𝑒𝑙 = 𝑥 1−
𝐵 𝐵
258,00 4,89
= x(1 - )
5,00 5,00
= 1,1 kN/m2 >0 OK

10. Desain Penulangan Retaining Wall


Desain Tulangan Lentur
a. Desain Tulangan Lentur untuk H1
Tebal Dinding (Bb) = 500,0 mm
Selimut Beton (Ts) = 40,0 mm
Tebal Efektif (d) = 500,0 - 40,0 - (1/2 x 16,0 )
= 452,0 mm = 0,45 m
Lebar Ditinjau (b) = 1000,0 mm = 1,00 m
Mutu Beton (fc') = 35,0 MPa
Mutu Baja (fy) = 420,0 MPa
Diameter Tulangan = 16,0 mm
= 12,56 mm2

Momen Ultimate (Mu)


P1 = 1,6 . Ka . 𝛾 . hs . (h1+h2)
= 1,6 x 0,17 x 27 x 0,38 x ( 5,50 + 1,50 )
= 19,22 kN
P2 = 0,5 . 1,6 . Ka . 𝛾 . (2(h1+h2))
= 0,5 . 1,6 . 0,2 . 27 . ( 2,00 x ( 5,50 + 1,50 ))
= 50,92 kN
P1 x (h1+h2) P2 x (h1+h2)
Mu = +
2 3
134,51 356,46
= +
2,00 3,00
= 186,08 kNm
Tulangan yang diperlukan (As)
Mu 186,08
Rn = = = 1012 = 1,0120 N/mm2
Ɵbd2 0,18

ρb = 0,85 fc β 600
fy 600 + fy
= 0,85 35,0 7,00 600
420,0 600 + 420,0
= 0,291667

ρmax = 0,75 x ρb = 0,75 x 0,29167


= 0,21875

ρmin = 1,4 = 1,4 = 0,003333333


fy 420,0

ρ pakai = 0,0033

m = fy = 420,0
0,85 x fc 0,85 x 35,0
= 14,12

ρ = 1 1 1- 2m x Rn
m fy
= 1 1 1- 28,24 x 1,01
14,12 420,0
= 0,0025

ρmax = 0,21875
ρ pakai = 0,0033
ρ = 0,0025

ρ < ρmax → ρ pakai = 0,0033


ρ < ρmin pakai

As perlu = ρbd
= 0,0033 x 1000,0 x 452,0
= 1506,67 mm2

Digunakan Tulangan ф 16,0 mm = 200,96 mm2


Jumlah Tulangan (n) = 1506,67 = 7,50 → 8 buah
200,96
Jarak Tulangan Dalam 1 m = 1000,0 = 125,00 mm 150 mm
8

Menurut SNI 2847:2013 pasal 10.5.4 hal 76 disebutkan sebagai berikut:


Jarak Tulangan ≤ 3 x Tebal Dinding, atau 450 mm
Jarak ≤ 3 x Tebal Dinding
150 ≤ 3 x 500,0
150 ≤ 1500 (OK)

As jadi = n x 1 x π x ф2
4
= 8 x 0,25 x 3,14 x 256,0

= 1608 mm2 > 1506,67 mm2 → (OK)

Maka dipakai tulangan = ф 16 - 150,00 mm

• Kontrol Kekuatan
Mn = As x fy x dx - a
2
dengan a = As x fy
0,85 x f'c x b

= 1607,68 x 420
0,85 x 35,0 x 1000,0

= 675225,6
29750

= 22,70 mm

Mn = 1608 x 420,00 x 452,00 - 22,70


2
= 297539288,66 Nmm

ф x Mn = Mu
0,80 x 297.539.289 Nmm = 186.076.502 Nmm

238.031.431 Nmm > 186.076.502 Nmm → (OK)

b. Desain Tulangan Lentur untuk H


Tebal Dinding (Bb) = 1000,0 mm
Selimut Beton (Ts) = 30,0 mm
Tebal Efektif (d) = 1000,0 - 30,0 - (1/2 x 16,0 )
= 962,0 mm = 0,96 m
Lebar Ditinjau (b) = 1000,0 mm = 1,00 m
Mutu Beton (fc') = 35,0 MPa
Mutu Baja (fy) = 420,0 MPa
Diameter Tulangan = 16,0 mm
= 12,56 mm2

Momen Ultimate (Mu)


P1 = 1,6 . Ka . 𝛾 . hs . ((h1+h2)/2)
= 1,6 x 0,17 x 27 x 0,38 x ((5,50 + 1,50 )/2)
= 9,61 kN
P2 = 0,5 . 1,6 . Ka . 𝛾 . (2(h1+h2))
= 0,5 . 1,6 . 0,17 . 27 . ( 2,00 x ((5,50 + 1,50 )/2)
= 25,46 kN
P1 x (h1+h2) P2 x (h1+h2)
Mu = +
4 6
67,26 178,23
= +
2,00 3,00
= 93,04 kNm

Tulangan yang diperlukan (As)


Mu 93,04
Rn = = = 112 kN/m2 = 0,1117 N/mm2
Ɵbd2 0,83

ρb = 0,85 fc β 600
fy 600 + fy
= 0,85 35,0 7,00 600
420,0 600 + 420,0
= 0,291667
ρmax = 0,75 x ρb = 0,75 x 0,29167
= 0,21875

ρmin = 1,4 = 1,4 = 0,003333333


fy 420,0

ρ pakai = 0,0033
m = fy = 420,0
0,85 x fc 0,85 x 35,0
= 14,12

ρ = 1 1 1- 2m x Rn
m fy
= 1 1 1- 28,24 x 0,11
14,12 420,0
= 0,0000

ρmax = 0,21875
ρ pakai = 0,0033
ρ = 0,0000

ρ < ρmax → ρ pakai = 0,0033


ρ < ρmin pakai

As perlu = ρbd
= 0,0033 x 1000,0 x 962,0
= 3206,67 mm2

Digunakan Tulangan ф 16,0 mm = 200,96 mm2


Jumlah Tulangan (n) = 3206,67 = 15,96 → 16 buah
200,96
Jarak Tulangan Dalam 1 m = 1000,0 = 62,5 → 150,00 mm
16

Menurut SNI 2847:2013 pasal 10.5.4 hal 76 disebutkan sebagai berikut:


Jarak Tulangan ≤ 3 x Tebal Dinding, atau 450 mm
Jarak ≤ 3 x Tebal Dinding
150 ≤ 3 x 1000,0
150 ≤ 3000 (OK)
As jadi = n x 1 x π x ф2
4
= 16 x 0,25 x 3,14 x 256,0

= 3215 mm2 > 3206,67 mm2 → (OK)

Maka dipakai tulangan = ф 16 - 150,00 mm

• Kontrol Kekuatan
Mn = As x fy x dx - a
2

dengan a = As x fy
0,85 x f'c x b

= 3215,36 x 420
0,85 x 35,0 x 1000,0
= 1350451,2
29750
= 45,39 mm

Mn = 3215 x 420,00 x 962,00 - 45,39


2
= 1268483324,26 Nmm

ф x Mn = Mu
0,80 x 1.268.483.324 Nmm = 93.038.251 Nmm

1.014.786.659 Nmm > 93.038.251 Nmm → (OK)

c. Perhitungan Tulangan Bagi


• Tulangan Bagi
Dalam SNI - 2847 - 2020, dalam arah tegak lurus terhadap tulangan utama harus disediakan tulangan
pembagi. Luas tulangan pembagi bagi untuk fy = 420 Mpa dapat dicari dengan rumus sebagai berikut:
As bagi = 0,25 x b x ba
100
= 0,25 x 1000 x 500
100
= 1250 mm2

As Tulangan (Ø) 13 mm = 132,79 mm2


Jumlah Tulangan(n) = As bagi
As Ø
= 1250
132,79
= 9,41 buah
Jumlah Tulangan Pakai = 10 buah
Jarak Tulangan tiap m = 1000
10
= 100 mm

Maka dipakai = ф 13 - 100 mm

d. Desain Tulangan Bagian Heel & Toe


Geser Ultimate (Vu) = (1,2 ( 𝑏2 . ℎ1 + ℎ2 . 𝛾 + 𝑏2 . ℎ3 . 24) + (1,6 (𝑏2 . ℎ𝑠 . 𝑞))
= 685,91 kN

ƟVc = Ɵ (0,17 . λ . √fc' . b . d)


= 0,75 x ( 0,17 x 1,00 x 5,92 x 1000 x 962,00
= 725,64 kN > Vu = 685,91 kN OK
Mu = Vu . (0,5 b2)
= 685,91 kN x 1,5
= 1028,87 kNm

Tulangan yang diperlukan (As)


Mu 1028869811,32
Rn = = = 1,2353 N/mm2
Ɵbd2 832899600,00

ρb = 0,85 fc β 600
fy 600 + fy
= 0,85 35,0 3,00 600
420,0 600 + 420,0
= 0,125000

ρmax = 0,75 x ρb = 0,75 x 0,125


= 0,09375

ρmin = 1,4 = 1,4 = 0,003333333


fy 420,0

ρ pakai = 0,0033

m = fy = 420,0
0,85 x fc 0,85 x 35,0
= 14,12

ρ = 1 1 1- 2m x Rn
m fy
= 1 1 1- 28,24 x 1,24
14,12 420,0
= 0,0030

ρmax = 0,09375
ρ pakai = 0,0033
ρ = 0,0030

ρ < ρmax → ρ pakai = 0,0030

As perlu = ρbd
= 0,0030 x 1000,0 x 962,0
= 2890,71 mm2
Digunakan Tulangan ф = 19,0 = 283,385 mm2
Jumlah Tulangan (n) = 2890,71 = 10,20 → 14 buah
283,39
Jarak Tulangan Dalam 1 m = 1000,0 = 150,00 mm
14
Menurut SNI 2847:2013 pasal 10.5.4 hal 76 disebutkan sebagai berikut:
Jarak Tulangan ≤ 3 x Tebal Dinding, atau 450 mm
Jarak ≤ 3 x Tebal Dinding
150 ≤ 3 x 1000,0
150 ≤ 3000 (OK)
As jadi = n x 1 x π x ф2
4
= 14 x 0,25 x 3,14 x 361,0
= 3967 mm2 > 2890,71 mm2 → (OK)

Maka dipakai tulangan = ф 19 - 150,00 mm

• Kontrol Kekuatan
Mn = As x fy x dx - a
2

dengan a = As x fy
0,85 x f'c x b

= 3967,39 x 420
0,85 x 35,0 x 1000,0

= 1666303,8
29750

= 56,01 mm

Mn = 3967 x 420,00 x 962,00 - 56,01


2
= 1556319241,25 Nmm

ф x Mn = Mu
0,80 x 1.556.319.241 Nmm = 1.028.869.811 Nmm

1.245.055.393 Nmm > 1.028.869.811 Nmm → (OK)

11. Rekapitulasi Penulangan Retaining Wall


Penulangan Lentur Bawah D 16 - 150 mm
Penulangan Lentur Atas D 16 - 150 mm
Tulangan Bagi ф 13 - 100 mm
Penulangan Bagian Heel D 19 - 150 mm
Penulangan Bagian Toe D 19 - 150 mm
0.50

Beton fc' 35 MPa

D16-150 D16-150
6.00

D13-100 D13-100
7.00

D19-150 D19-150 D13-100


1.00
0.50

Beton fc' 35 MPa

D16-150 D16-150

6.00
D13-100 D13-100
7.00

D19-150 D19-150 D13-100


1.00

Beton fc 35 MPa
D13-100 D19-150

1.00 1.00 3.00

5.00