SLC
Wiring Manual
ECN 07-838
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly. Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended. The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
Limit-C1-2-2007
The amount of smoke present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm. Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire. Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood. CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for operation at 0-49 C/32-120 F and at a relative humidity 93% 2% RH (noncondensing) at 32C 2C (90F 3F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27 C/60-80 F. Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Overtightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit. Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his or her own expense. Canadian Requirements This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications. Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
HARSH, NIS, Notifier Integrated Systems, and NOTIFIRENET are all trademarks; and Acclimate Plus, FlashScan, NION, NOTIFIER, ONYX, ONYXWorks, UniNet, VeriFire, and VIEW are all registered trademarks of Honeywell International Inc. Echelon is a registered trademark and LonWorks is a trademark of Echelon Corporation. ARCNET is a registered trademark of Datapoint Corporation. Microsoft and Windows are registered trademarks of the Microsoft Corporation. LEXAN is a registered trademark of GE Plastics, a subsidiary of General Electric Company. 2008 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us. Please include the following information:
Product name and version number (if applicable) Printed manual or online Help Topic Title (for online Help) Page number (for printed manual) Brief description of content you think should be improved or corrected Your suggestion for how to correct/improve documentation
Send email messages to: [email protected] Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
Table of Contents
Table of Contents
Section 1: Introduction............................................................................................................. 9
1.1: About This Manual ........................................................................................................................................9 1.2: UL 864 Compliance.....................................................................................................................................10 1.2.1: Products Subject to AHJ Approval....................................................................................................10 1.3: Reference Documentation ..........................................................................................................................10 1.4: SLC Overview .............................................................................................................................................12 1.5: Polling Protocols .........................................................................................................................................12 1.6: Devices .......................................................................................................................................................13 1.6.1: Monitor/Zone Interface Modules.......................................................................................................13 1.6.2: Control Modules ................................................................................................................................13 1.6.3: Isolator Modules ................................................................................................................................14 1.6.4: Relay Modules...................................................................................................................................14 1.6.5: Transponders .....................................................................................................................................14 1.6.6: Plug-in Detector Bases ......................................................................................................................14 1.6.7: Intelligent Detectors .........................................................................................................................14 1.6.8: Addressable Manual Pull Stations.....................................................................................................15 1.6.9: RFX Wireless Interface .....................................................................................................................15 1.6.10: ACPS-610/E Addressable Charger/Power Supply ..........................................................................16 1.6.11: ACPS-2406 Addressable Charger/Power Supply............................................................................16 1.6.12: AMPS-24/E Addressable Power Supply .........................................................................................16 1.7: SLC Capacity...............................................................................................................................................16 1.8: SLC Performance.........................................................................................................................................16 1.9: LED Operation.............................................................................................................................................17
Table of Contents
5.2: Fault Isolator Module...................................................................................................................................33 5.2.1: Wiring an Isolator Module.................................................................................................................34 5.3: Isolator Detector Bases ................................................................................................................................34 5.3.1: How an Isolator Base Works .............................................................................................................35 5.4: NFPA Style 4 SLC Using Isolator Modules ................................................................................................36 5.5: NFPA Style 6 SLC Using Isolator Modules ................................................................................................37 5.6: NFPA Style 7 SLC Using an Isolating Device.............................................................................................38
Appendix C: Terminal Conversion Charts for V-type and H-type Devices ...................... 76
C.1: FRM-1 .........................................................................................................................................................76
6 The SLC Wiring Manual P/N 51253:J 10/30/2007
Table of Contents
Table of Contents
Section 1: Introduction
1.1 About This Manual
This document covers the installation and wiring of various Signaling Line Circuit (SLC) devices, when used with the following Fire Alarm Control Panels1 (FACPs): AFP-100 AFP-200 AFP-300/AFP-400 AM2020/AFP1010 NFS-3030/NFS2-3030 NFS-640/E, NFS2-640/E, NFS-320/E/C System 5000 with AIM-200
This document also provides basic information that applies to Notifier SLC loops in general, such as the branch resistance measurements. See Section 2.4, Control Panel Terminal Blocks, on page 23 for basic panel-end SLC connections. Additional information about each control panel and the modules and detectors referenced in this document, and the part numbers for their manuals, can be found in the respective installation manual as listed in Section 1.3, Reference Documentation below. FlashScan modules are changing to a new format. Several models are now available in this new format and have replaced the old format illustrations in this manual. While the old format is no longer manufactured for these models, Appendix C has been provided for those who need that wiring information: it contains terminal conversion charts between the old and new formats. In this appendix, the modules are referred to as h-type (the new format, which has horizontal rotary dials) and v-type (the old format, which has vertical rotary dials). This naming convention is a convenient way to avoid confusion when referring to a particular model, as the name of the model does not indicate the format. Refer to Figure 1.1
Vertical rotary dials. Old-format FCM-1.
FCM-1
FCM-1
1. AFC-600 has been discontinued; to service existing installations of this panel, refer to the original manuals shipped with the panel.
The SLC Wiring Manual P/N 51253:J 10/30/2007 9
Introduction
UL 864 Compliance
AFP-100 AFP-200 AFP-300/AFP-400 AIM-200 AM2020/AFP1010 BGX-101L CMX-1 CMX-2 FFT-7/FFT-7S LIB-400 MMX-1 MMX-101 MMX-2 MPS-24A/E MPS-24B/E
MPS-400 NCA NFS-3030 with CPU-3030 NFS-640/E System 5000 XP Series (XPP-1, XPC-8, XPM-8 & XPR-8) XP5-C XP5-M ACPS-2406 B224RB B501BH B501BHT FCPS-24/E
Reference Documentation
Introduction
Voice Alarm System Manual FireVoice-25/50 & FireVoice-25/50ZS Manual DVC Digital Voice Command Manual DAA Digital Audio Amplifier Manual AA-series Audio Amplifier Manual AM2020/AFP1010 Installation Manual System 5000 Installation, Operations, and Programming Manuals System 5000 with AIM-200: Refer to the AIM-200 Manual Power Supplies, Auxiliary Power Supplies & Battery Chargers ACPS-610/E Installation Manual ACPS-2406 Installation Manual AMPS-24/E Power Supply Manual FCPS-24 Field Charger/Power Supply Manual FCPS-24S6/FCPS-24S8 Field Charger/Power Supply System Components RA400Z Remote LED Annunciator Installation Document RFX Wireless Interface Manual XP Transponder Manual XP10-M Installation Document XP5 Series Manual XP6-C Installation Document XP6-MA Installation Document XP6-R Installation Document XPIQ Audio Transponder Manual SLC Loop Devices B224BI Isolator Base Installation Document (FlashScan/CLIP) B224RB Relay Base Installation Document B501 Standard Base Installation Document B501BH Sounder Base Installation Document B501BHT Temporal Sounder Base Installation Document B710HD HARSH Base Installation Document B710LP Flanged Base Installation Document FAPT-751 Acclimate Plus Multi-Sensor Detector Installation Document FAPT-851: See document for FSP-851, FSP-851T and FAPT-851 FCM-1 Control Module Installation Document FDM-1 Dual Monitor Module Installation Document FMM-1 Monitor Module Installation Document FMM-101 Mini Monitor Module Installation Document FRM-1 Relay Module Installation Document FSB-200, FSB-200S Single-ended Reflected Type Projected Beam Smoke Detector FSD-751PL Low-flow Duct Detector
51252 52290 52411 52410 52526 15088 15583, 15581, 15584 15949 Document Number 53018 51304 51907 50059 51977 Document Number I56-508 51012 15888 I56-1803 50786 I56-1805 I56-1806 I56-1804 51013 Document Number I56-725 I56-659 I56-357 I56-0491 I56-1367 I56-1252 I56-637 I56-0002
11
Introduction
SLC Overview
FSD-751RPL Low-flow Duct Detector with Relay FSD-751P Duct Detector Installation Document FSD-751RP Duct Detector Installation Document FSH-751 HARSH Installation Document FSI-751 Ion Detector Installation Document FSI-851 Ion Detector Installation Document FSL-751 Laser Detector Installation Document FSP-751 & FSP-751T Photo Installation Document FSP-851, FSP-851T and FAPT-851 Photoelectric Detectors Installation Document FST-751 Thermal Detector Installation Document FST-751R Rate of Rise Sensor Installation Document FST-851, FST-851R, and FST-851H Thermal Detectors Installation Document FTM-1 Firephone Control Module FZM-1 Zone Interface Module Installation Document HPX-751 HARSH Installation Document ISO-X Isolator Module Installation Document LPX-751 Laser Detector Installation Document LPX-751L Laser Detector Installation Document NBG-12LX Pull Station Installation Document NBG-12LXSP Spanish-/English-Labeled Addressable Manual Pull Station NBG-12LXP Portuguese-Labeled Addressable Manual Pull Station Note: Refer to the Device Compatibility Document for compatible conventional devices.
I56-1979 I56-1523 I56-1571 I56-054 I56-1249 I56-1924 I56-057 I56-1230 I56-1925 I56-1234 I56-1242 I56-1926 I56-1391 I56-1172 I56-1250 I56-1380 I56-748 I56-1793 51093 I56-2769 (English) I56-2797 (Spanish) I56-2272
12
Devices
Introduction
Many FlashScan devices can be programmed to run in either CLIP or FlashScan mode. Use one of the following three options with SLC loops: 1. 2. Program all modules and detectors on an SLC as FlashScan. Program all modules and detectors on an SLC as CLIP.
CAUTION: Do not program more than 99 addresses on a CLIP-mode SLC loop, because this will slow the system down and compromise the response time of the panel to display off-normal events.
3.
CAUTION: Do not program modules as CLIP and detectors as FlashScan on the same SLC. This combination does not work.
1.6 Devices
1.6.1 Monitor/Zone Interface Modules
These addressable modules allow the control panel to monitor entire circuits of conventional alarm initiating devices, such as manual pull stations, smoke detectors, heat detectors, waterflow and supervisory devices. FMM-1 Monitor Module; FlashScan or CLIP mode. (An earlier module named MMX-1 was CLIP mode only.) FDM-1 Dual Monitor Module; FlashScan or CLIP mode. FMM-101 Addressable Mini-Monitor Module; FlashScan or CLIP mode. (An earlier module named MMX-101 was CLIP mode only.) FZM-1 Zone Interface Module; FlashScan or CLIP mode. (An earlier module named MMX-2 was CLIP mode only). XP5-M Supervises five Class-B addressable Initiating Device Circuits (IDC) which monitor normally open contact initiating devices. Supports FlashScan or CLIP mode. This module is capable of participating in degraded mode where supported by the FACP. (See the XP5 Series Manual) XP6-MA Allows an intelligent alarm system to monitor six zones of conventional two-wire detectors; FlashScan or CLIP mode. XP10-M Supervises ten Class-B addressable Initiating Device Circuits (IDC) which monitor normally open contact initiating devices; FlashScan or CLIP mode. This module is capable of participating in degraded mode where supported by the FACP.
Introduction
Devices
1.6.5 Transponders
XPIQ An integrated, multiple channel audio amplification and distribution subsystem remotely controlled by the FACP. It can direct up to four low level audio signals from risers to up to four audio amplifiers, which are then directed to up to four integrated, continuously supervised speaker circuits. The XPIQ is FlashScan capable (only). XP Series (XPP-1, XPC-8, XPM-8 & XPR-8) Provides the FACP with an efficient multiplex subsystem capability. It communicates with the FACP and functions as a data-gathering panel for alarm Initiating Device Circuits and as a remote switching center for Notification Appliance Circuits (NAC), telephone circuits or relays. Not FlashScan capable.
For information on connecting these transponders to the SLC, refer to the XP Transponder Manual or the XPIQ Manual.
14
Devices
Introduction
FSI-851 Addressable, intelligent smoke detector that incorporates an ionization sensing chamber. Designed to provide open area protection. FlashScan-capable. (An earlier model named FSI-751 was also FlashScan capable. Earlier models named CPX-751 and CPX-551 were CLIP mode only.) FSP-851 Analog, addressable intelligent smoke detector that uses a photoelectric sensing chamber. Listed for use in ducts. Designed to provide open area protection. The FSP-851T adds thermal sensors that will alarm at a fixed temperature of 135 F (57.2C). Both models support FlashScan or CLIP mode. (Earlier versions named FSP-751 and FSP-751T also supported FlashScan or CLIP mode, but were not listed for use in ducts. Earlier models named SDX-551, SDX-751 and SDX551TH were CLIP mode only.) FST-851 Intelligent thermistor sensing circuit for fast response. Designed to provide open area protection with 50 foot spacing capability. A fixed temperature sensor with 135F (57.2C) fixed temperature alarm. The FST-851R incorporates a thermal rate of rise of 15F (8.3C). The FST851H is a high temperature sensor with 190F (87.8C) fixed temperature alarm. Both models models support FlashScan or CLIP mode. (Earlier versions named FST-751 and FST-751R also supported FlashScan or CLIP mode. Earlier models named FDX-551 and FDX-551R were CLIP mode only.) FSD-751P Photoelectric Duct Detector. The FSD-751RP includes an alarm relay. Both models support FlashScan or CLIP mode. FSD-751PL Low-flow Photoelectric Duct Detector, with extended speed range of 1004000 FPM (0.5 m/s to 20.3 m/s). FSD-751RPL adds a relay. Both models support FlashScan or CLIP mode. FSH-751 (HARSH) A special smoke detector that provides early warning smoke detection in hostile environments where traditional smoke detectors are not practical. Supports FlashScan or CLIP mode. (An earlier model named HPX-751 was CLIP mode only.) FSL-751 VIEW An advanced intelligent photoelectric detector that uses a laser diode, special optics, and signal processing to obtain extremely high sensitivity. Supports FlashScan and CLIP mode; compatible with AFP-300/AFP-400, NFS-640, NFS2-640, NFS-320 and NFS-3030/NFS23030 only. LPX-751L is compatible with AFP-200 and AM2020/AFP1010; CLIP mode only. (An earlier version named LPX-751 was CLIP mode only and compatible with AFP-300/AFP-400.)
15
Introduction
SLC Capacity
Single Open Single Ground Short Short and open Short and ground Open and ground Communications loss
Alarm, Trouble Alarm, Trouble (ground) Trouble Trouble Trouble Alarm, Trouble Trouble
Alarm, Trouble Alarm, Trouble (ground) Alarm, Trouble Trouble Alarm, Trouble Alarm, Trouble Trouble
Trouble - The control panel will indicate a trouble condition for this type of fault. Alarm - The control panel must be able to process an alarm input signal in the presence of this type of fault.
Table 1.2 SLC Circuit Configuration and Performance: Style 4, Style 6, Style 7
16
LED Operation
Introduction
AFP-300/AFP-400
NOTE: In CLIP mode, the LPX-751 and HPX-751 blink GREEN in standby and stay RED when activated.
17
Introduction
LED Operation
18
To maximize distance on the SLC loop, use the recommended type of wire. Using other wiring types makes the SLC circuit more susceptible to electrical interference and thus reduces its maximum loop length.
FACP: Wire Type and Limitations* Recommended Max. Distance Wire Gauge
LIB-200A or LIB-400 on AM2020/AFP1010 (See Table 2.2 for LIB-200.) RECOMMENDED: Twisted unshielded pair, 12 to 18 AWG (3.31 mm to 0.82 mm). 50 ohms max per length of Style 6 and 7 loops. 50 ohms per branch max for Style 4 loops 12,500 ft. (3,810 m) 9,500 ft. (2,895.6 m) 6,000 ft. (1,828.8 m) 3,700 ft. (1,127.76 m) 12 AWG/3.31 mm 14 AWG/2.08 mm 16 AWG/1.31 mm 18 AWG/0.82 mm
NOTE: Twisted-shielded pair or untwisted unshielded wire is not recommended for use with LIB-200A or LIB-400.
NFS-640 and LEM-320 on NFS-640 RECOMMENDED: Twisted-unshielded pair, 12 to 18 AWG (3.31 mm to 0.82 mm). 50 ohms maximum per length of Style 6 & 7 loops. 50 ohms per branch maximum for Style 4 loop. Untwisted, unshielded wire, in conduit or outside of conduit. 12,500 ft. (3,810 m) 9,500 ft. (2,895.6 m) 6,000 ft. (1,828.8 m) 3,700 ft. (1,127.76 m) 12 AWG (3.31 mm) 14 AWG (2.08 mm) 16 AWG (1.31 mm) 18 AWG (0.82 mm)
Note: Twisted-shielded pair is not recommended for use with this panel. Note: Maximum total capacitance of all SLC wiring (both between conductors and from any conductor to ground) should not exceed 0.5 microfarads.
NFS-320, NFS2-640, LEM-320 on NFS2-640, LCM-320/LEM-320 on NFS-3030/NFS2-3030 RECOMMENDED: Twisted-unshielded pair, 12 to 18 AWG (3.31 mm to 0.82 mm). 50 ohms, maximum per length of Style 6 & 7 loops. 50 ohms per branch maximum for Style 4 loop. Untwisted, unshielded wire, in conduit or outside of conduit. Twisted, shielded pair
Note: Shields must be isolated from ground. Shields should be broken at each device.
12,500 ft. (3,810 m) 9,500 ft. (2,895.6 m) 6,000 ft. (1,828.8 m) 3,700 ft. (1,127.76 m)
12 AWG (3.31 mm) 14 AWG (2.08 mm) 16 AWG (1.31 mm) 18 AWG (0.82 mm)
5,000 ft. (1,524 m) 3,700 ft. (1,127.76m) 5,000 ft. (1,524 m) 3,700 ft. (1,127.76m)
12 to 16 AWG (3.31 mm to 1.31 mm) 18 AWG (0.82 mm) 12 to 16 AWG (3.31 mm to 1.31 mm) 18 AWG (0.82 mm)
Note: Maximum total capacitance of all SLC wiring (both between conductors and from any conductor to ground) should not exceed 0.5 microfarads.
Table 2.1 Wiring Recommendations: NFS-320, NFS2-640, NFS-640, NFS2-3030, NFS-3030, LCM320, LEM-320, LIB-200A, and LIB-400
19
Wiring Requirements
XPIQ-SLI is an SLC device that provides an additional local SLC loop. This local SLC loop should use the same type of wire recommended for the FACP controlling the main SLC loop. Maximum resistance of the local SLC (from any device to FACP): 50 ohms. Maximum resistance of the local SLC (from any device to XPIQ-SLI): 20 ohms. (Maximum number of detectors and modules = 64) Maximum SLC local branch current degraded mode: 20 mA. Maximum distance of local loop: 2,000 ft. (600 m). Recommended wire: 12 AWG (3.31 mm) Notifier brand cable is recommended; see the product catalog available from Paige Electric. Recommended Max. Distance
FACP: Wire Type and Limitations AFP-100 Twisted, shielded pair, 40 ohms maximum per length of Style 6 and 7 loops. 40 ohms per branch maximum for Style 4 loops. Untwisted, Unshielded
Wire Gauge
10,000 ft. (3,000 m) 8,000 ft. (2,400 m) 4,875 ft. (1,450 m) 3,225 ft. (980 m) 1,000 ft. (300 m)
12 AWG (3.31 mm) 14 AWG (2.08 mm) 16 AWG (1.31 mm) 18 AWG (0.82 mm) 12-18 12 to 18 AWG (3.31 mm to 0.82 mm)
Note: Twisted-unshielded pair wire is not recommended for use with this panel.
AFP-200 Twisted-shielded pair. 40 ohms maximum per length of Style 6 and 7 loops. 40 ohms per branch maximum for Style 4 loops Untwisted, unshielded wire, in conduit or outside of conduit 10,000 ft. (3,048 m) 8,000 ft. (2,438.4 m) 4,875 ft. (1,485.9 m) 3,225 ft. (982.98 m) 1,000 ft. (304.8 m) 12 AWG (3.31 mm) 14 AWG (2.08 mm) 16 AWG (1.31 mm) 18 AWG (0.82 mm) 12 to 18 AWG (3.31 mm to 0.82 mm)
Note: Twisted-unshielded pair wire is not recommended for use with this panel. Note: Maximum total capacitance of all SLC wiring (both between conductors and from any conductor to earth) should not exceed 0.5 microfarads. AFP-300/AFP-400 Twisted-shielded pair, 12 to 18 AWG. 40 ohms, maximum per length of Style 6 and 7 loops. 40 ohms per branch maximum for Style 4 loops. Untwisted, unshielded wire, in conduit or outside of conduit. 10,000 ft. (3,048 m) 8,000 ft. (2,438.4 m) 4,875 ft. (1,485.9 m) 3,225 ft. (982.98 m) 1,000 ft. (304.8 m) 12 AWG (3.31 mm) 14 AWG (2.08 mm) 16 AWG (1.31 mm) 18 AWG (0.82 mm) 12 to 18 AWG (3.31 mm to 0.82 mm)
Note: Twisted-unshielded pair wire is not recommended for use with this panel. LIB-200 on AM2020/AFP1010 (See Table 2.1 for LIB-200A or LIB-400.) Twisted-shielded pair. Maximum loop resistance is 40 ohms. Maximum length is 10,000 ft. per channel (NFPA Style 4) or 10,000 ft. total twisted pair length (NFPA Style 6 and 7). Maximum loop current is 200 mA (short circuit) or 100 mA (normal). 10,000 ft. (3,048 m) 8,000 ft. (2,438.4 m) 4,875 ft. (1,485.9 m) 3,225 ft. (982.98 m) 12 AWG (3.31 mm) 14 AWG (2.08 mm) 16 AWG (1.31 mm) 18 AWG (0.82 mm)
*If the wiring connected to the LIB-200 leaves the building it must be in conduit. It can not exceed 1000 m (1093 yards), must not cross any power lines, and must not be in the vicinity of any high voltage. These outdoor wiring restrictions do not apply to the LIB200A or the LIB-400.
System 5000 with AIM-200 Twisted-shielded pair. Maximum loop resistance: 40 ohms. Maximum loop voltage: 27.6 VDC. Maximum loop current: 200 mA (short circuit) or 100 mA (normal operation). 10,000 ft. (3,048 m) 8,000 ft. (2,438.4 m) 4,875 ft. (1,485.9 m) 3,225 ft. (982.98 m) 12 AWG (3.31 mm) 14 AWG (2.08 mm) 16 AWG (1.31 mm) 18 AWG (0.82 mm)
20
Wiring Requirements
Measure DC resistance as detailed and shown below: 1. 2. With power removed, short the termination point of one branch at a time and measure the DC resistance from the beginning of the SLC to the end of that particular branch. Repeat this procedure for all remaining branches in the SLC.
In Figure 2.1, Branches A, B, and C all begin at the SLC terminal, even though Branch B is T-tapped.
Branch A Branch B Branch C
SLC-meas5.cdr
SLC Out
B+
Segment Five
Segment Four
Segment One
Segment Two
SLC-meas2.cdr
Segment Three
21
Wiring Requirements
Measure DC resistance as detailed and shown below: 1. 2. 3. Disconnect the SLC channel B (Out) and SLC channel A (Return) at the control panel. Short the SLC at the last device and measure the resistance at SLC Out. Record resistance and remove the short. Short the SLC at the first device and measure the resistance at SLC return. Record resistance and remove the short.
SLC Out
STEP 2 Last Device SLC Return Short Point SLC Out First Device STEP 3 SLC Return Last Device
SLC-meas5.cdr
22
Wiring Requirements
B+ A+ B- A- TB1
TB16
NFS2640-SLC-TB.wmf, LEM320-SC-tb.wmf
LEM320-SLC-TB.cdr
23
Wiring Requirements
2.4.4 AFP-100
AFP-100 supports one SLC loop; the loop is CLIP mode only. The SLC loop connects to TB6.
2.4.5 AFP-200
AFP-200 supports one SLC loop; the loop is CLIP mode only. The SLC loop connects to TB5.
2.4.6 AFP-300/AFP-400
AFP-300 supports one SLC loop; AFP-400 supports two SLC loops. The loops are CLIP mode only. SLC loops connect to TB6 on AFP-300; SLC loops connect to TB5 and TB6 on AFP-400.
slc-300.wmf, slc-400.wmf
24
slc-200.wmf
slc-100.wmf
Wiring Requirements
Pin 3 SLC Loop Port APin 5 SLC Loop Port B+ Pin 7 SLC Loop Port BPin 8 Earth Ground LIB-200A
Pin 3 SLC Loop Port APin 5 SLC Loop Port B+ Pin 7 SLC Loop Port BPin 8 Earth Ground LIB-400
NOTE: AFC-600 has been discontinued; to service existing installations of this panel, refer to the original manuals shipped with the panel.
slc-lib-200a.wmf,slc-lib-400.wmf
25
Wiring Requirements
26
Shielding of the SLC is not recommended for use with NFS-320/E/C, NFS2-640/E, NFS-640/E, NFS2-3030, NFS-3030, LCM-320, LEM-320, LIB-200A or LIB-400. If twisted-shielded wire is used in one of these installations, use a floating shield to terminate the wire as shown in Section 3.5, Floating Shield, on page 29. Use of good wiring practice consistent with local electrical codes is expected.
3.2 No Conduit
For use with AFP-100, AFP-200, AFP-300/400, LIB-200, and AIM-200 only Scrape the paint on the cabinet to bare metal to provide a good electrical connection. Fold the foil and drain wire back over the cable jacket. Slide the cable into the connector clamp and secure. The drain wire should be connected to the connector screw. Do not allow the shield drain wire or foil to enter the system cabinet.
Connector Screw Shield Drain Wire Foil
SLC-swterm1.cdr
Cabinet
27
Full Conduit
Conduit Tape over foil. Cabinet Example at right illustrates shield drain wire connection to an SLC terminal block without a reference or shield connection. Foil Shield Drain Wire
Shield2.wmf, SLC-swterm2a.wmf SLC-swterm3.cdr
Conduit
NOTE: For Style 6 or Style 7 SLC wiring, connect one end of the shield to the reference/negative side of the respective channel
Conduit
28
Floating Shield
NOTE: Using shielded wire in applications where it is not recommended will reduce the maximum SLC length. If shielded wire must be used where not recommended, failing to float the ends will reduce the maximum SLC length even further.
SLC-swterm4.cdr
29
Addressable Module
T-tapped Circuits
30
SLC Out
B+ B
NOTE: T-tapping of the SLC wiring is NOT allowed for Style 6 configuration.
31
32
A Fault Isolator Module on both sides of a device, or the combination of an Isolator Base and Isolator Module are required to comply with NFPA Style 7 requirements.
CAUTION: If relay or sounder bases are not used, a maximum of 25 addressable devices can be connected between Isolator Modules and/or Bases. When relay or sounder bases are used, the maximum number of addressable devices that can be connected between Isolators is reduced to seven. Isolator modules will not function properly when these limits are exceeded. When more than 100 Isolator Modules and/or Isolator Bases are connected from the AFP-300 or AFP-400 to an SLC loop, the address capacity of the loop is reduced by two (2) addresses for every isolator device in excess of 100. The address capacity of the loop is reduced by two (2) addresses for every isolator device in excess of 200 when the Isolator Modules and/or Isolator Bases are connected to the SLC loop from the NFS-320/E/C, NFS2-640/E, NFS2-3030, NFS-3030, NFS-640/E, AFP-100 or AFP-200.
33
IN IN OUT
SLC-isowire.cdr
OUT
SLC
34
Detector 1 Z
Detector 2 Y
Detector 5
Detector 3
SLC-isowork.wmf
Control Panel
Isolator Base
Non-Isolating Device
Short-circuit path
NOTE: For information on wiring an isolator base, refer to Figure 9.3, Wiring an Isolator Base on page 59.
35
36
SLC-style4iso.cdr
B B+
Isolator Module
Isolator Module
Section C
Section A
Isolator Module
Additional isolator module required when first device in the section is more than 20 feet from the control panel.
Isolator Module
Isolator Module
The first isolator module on SLC Out and SLC Return is optional for NFS-320, NFS2-640, AFP-300, AFP-400, NFS-640/E, or NFS-3030/NFS2-3030 because the panels provide the functionality. SLC Out SLC Return
Isolator Module
AFP-100, AFP-200, AM2020/AFP1010, System 5000 with AIM-200: The first isolator module on SLC Out and SLC Return must be contained within the same enclosure as the FACP, or these isolator modules must be connected within 20 ft. (6.1 m) of the FACP enclosure in conduit.
Control Panel
SLC-style6iso.cdr
37
Isolator Module
Isolator Module
Addressable Detector
Isolator Module
Isolator Module
Isolator Module
The first isolator module on SLC Out and SLC Return is optional for NFS-320, NFS2-640, AFP-300, AFP-400, NFS-640/E, or NFS-3030/NFS2-3030 because the panels provide the functionality. SLC Out SLC Return
Isolator Module
Control Panel
38
SLC-style7iso.cdr
AFP-100, AFP-200, AM2020/AFP1010, System 5000 with AIM-200: The first isolator module on SLC Out and SLC Return must be contained within the same enclosure as the FACP, or these isolator modules must be connected within 20 ft. (6.1 m) of the FACP enclosure in conduit.
39
SLC SLC+
Rotary Switches
24 VDC 24 VDC + IDC Return IDC Return + IDC Out + IDC Out
SLC SLC+
Rotary Switches
40
FZMtpH.wmf
FMMtpH.wmf
Description
Monitor Modules
{ {
9 H 8 H+ 7L+ 6L
ADDRESS LOOP
0 1 2 3 4 5
Label Use to record the device address and SLC number. SLC (+) Red
FMM-101.cdr
9 8 7 6
TENS
ONES
SLCDualMod-simplified.wmf
SLC SLC+
41
Monitor Modules
Breakaway Tab - Modules come with a raised breakaway tab on the TENS rotary switch. This tab must be removed when the module is on an FACP that uses more than 99 addresses.
Dual monitor modules: On dual monitor modules, only even numbers appear on the ONES rotary switch. The module takes both the selected address and the next-higher address.
42
SLC-setadd.cdr,SLC-setaddtpH.wmf, SLCbrktabs.wmf
Monitor Modules
Refer to the Device Compatibility Document for compatible smoke detectors. See Power Considerations on page 63 for information on supervising 24 VDC power.
From Supply
SLC-idcB1tpH.wmf
IDC
43
Monitor Modules
3. 4.
Manual pull station To Next IDC or Supervision Device SLC Heat detector FMM-1
IDC
44
SLC-idcD1tpH.wmf
Monitor Modules
3.
45
Monitor Modules
3.
24 VDC Resettable power. 90 mA External 24 volt supply required (Resettable power is not necessary for NFS320/E/C, NFS2-640/E, NFS-640/E, NFS23030, or NFS-3030 when operating in FlashScan mode.) 3.9K ELR (supplied with module)
SLC
FZM-1
46
SLC-idcB2tpH.wmf
IDC
Monitor Modules
3.
24 VDC Resettable power. 90 mA External 24 volt supply required (Resettable power is not necessary for NFS-320/E/C, NFS2-640/E, NFS-640/E, NFS2-3030, or NFS-3030 when operating in FlashScan mode.) SLC FZM-1
IDC
SLC-idcD2tpH.wmf
Figure 6.10 Typical Style D IDC Wiring with the FZM-1 Figure 6.11
47
Monitor Modules
48
Refer to the Device Compatibility Document for a list of compatible UL Listed Fire Alarm Releasing Solenoids. For more information on the module specifications refer to the Installation Instructions provided with these devices. Setting an SLC Address Each module is factory preset with an address of 00. To set an SLC address refer to Setting SLC Address on Module on page 42.
24 VDC Nonresettable Power ()* 24 VDC Nonresettable Power (+)* Style Z NAC (+) Style Z NAC () Style Y/Z NAC () Style Y/Z NAC (+) NOTE: Module polarities are shown in alarm condition. *Can also be used in audio/voice and fire-fighters telephone applications (70.7 VRMS audio or telephone); refer to the Voice Alarm System Manual, FireVoice 25/50 Manual, DVC Manual, or DAA Manual as appropriate for your equipment.
SLCModule-simplified.wmf
49
Control Modules
Rear View
Jumper J1 must be removed when using the FCM-1 on an FFT-7 or FFT-7S telephone circuit (see the Voice Alarm System Manual, FireVoice 25/50 Manual, DVC Manual, or DAA Manual as appropriate for your equipment) and when supervising 24VDC NAC power using the no-relay alternative wiring (see Appendix A.2.3, Using the Addressable Control Module Without Relay).
FCMBackJump.wmf, FCMBackJumpcl.wmf
Prying tool
To remove J1 from the FCM-1: 1. Insert a small prying tool, such as a screwdriver or probe, behind J1. Using the tip of the prying tool, slide J1 toward the rear of the FCM-1 so that it exits from the slot in the back.
2.
J1
NOTE: When using NFS2-3030/NFS-3030 and the Control type ID, do not remove jumper J1.
50
Control Modules
4. 5. 6. 7.
51
Control Modules
4. 5. 6.
52
SLC-nacZtpH.wmf
A power supervision relay is required only on the last module of the power. (only: If using one of thes FlashScan type IDs that provide built-in power supervision, no relay is required.)
Control Modules
Non-resettable 24 VDC power (-) Module polarities are shown in alarm condition. All wiring shown is supervised and power-limited. (+) SLC (-) SLC (+)
Compatible UL-listed 24 VDC releasing device. One (1) 24 VDC device maximum or Two (2) 12 VDC wired in series. FCM-1
When using the FCM-1 for Style Y (Class B) applications, remove jumper J1.
Module polarities are shown in alarm condition. All wiring shown is supervised and power-limited.
(-) (+)
FCM-1
Figure 7.7 NPFA Style Z (Class A) Wiring of the FCM-1 Critical Requirements. When connecting a releasing device to the FCM-1 module, note the following: 1. 2. 3. 4. See Power Considerations on page 52 for information on monitoring 24 VDC power. Do not T-tap or branch a Style Y or Style Z circuit. Only one (1) 24V solenoid or two (2) 12V solenoids in series can be connected to the FCM-1. Do not loop wiring under the screw terminals. Break the wire run to provide supervision of connections.
53
Control Modules
5.
All applications using the FCM-1 are power-limited: a. b. Program the releasing circuit for Type Code REL CKT ULC or RELEASE CKT. Circuits are supervised against opens and shorts.
6.
Refer to your FACPs Programming Manual for instructions on setting the Soak Timer.
The FCM-1 module must be programmed with the correct releasing type code listed in your FACPs Programming Manual.
54
For more information on the module specifications refer to the Installation Instructions provided with this device. For information on transponders, refer to the specific transponder manual. Setting an SLC Address Each relay module is factory preset with an address of 00. To set an SLC address refer to Section 6.2, Setting an SLC Address for a Module, on page 42.
C NC NO
C
NC NO
SLC-frmCtpH.wmf
55
Relay Module
56
NOTE: The B710LP base wiring is identical to the B501, except there is no shield terminal.
SLC-B501wire.wmf
57
Figure 9.2 shows typical wiring of the B710HD detector base (for use with a HARSH detector) connected to an SLC. An optional RA400Z Remote LED Annunciator is shown connected to the base.
SLC To next device on SLC
NOTE: Use a spade lug to wire the Remote LED Annunciator () to Terminal 2 ().
58
SLC In
Conduit
SLC-224BIwire.wmf
SLC
b224rb.wmf
59
4 5 3
IN -3
21
External supply 2 +1
Class A Optional Wiring Optional Sounder Interconnect* SLC B+ UL-listed Compatible FACP SLC B-
(-) Power
B501BHWiring.wmf
60
+
SLC
SLC-nbg12.cdr
61
62
Where: Rmax = maximum resistance of the 24 VDC wires Vms = minimum supply voltage (see Table A.1 below) Vom = minimum operating voltage of the detector or end-of-line relay, whichever is greater, in volts N = total number of detectors on the 24 VDC supply circuit Is = detector current in standby Na = number of detectors on the 24 VDC power circuit which must function at the same time in alarm Ia = detector current in alarm Ir = end-of-line relay current Nb = number of Notification Appliance Devices Ib = Notification Appliance current when activated
NOTE: This simplified equation assumes that the devices are at the end of a long wire run.
The minimum supply voltages produced by Notifier power supplies are listed below:
FACP AFP-100 AFP-200 NFS-640/E KAPS-24 on NFS2-640 or NFS-320 Vms 18.1 19.4 19.15 20.16V Power Supply FCPS-24/E FCPS-24S6/FCPS-24S8 MPS-24A/E MPS-24B/E MPS-400 ACPS-2406 AMPS-24/E ACPS-610/E Vms 19.1 19.1 19.6 20.1 19.23 19.8 20.27 19.4
63
Power Considerations
A.2.1 Using Type Codes with Built-In Power Supervision on NFS2-3030 and NFS-3030
With LCM-320 revision 2.0 and higher, certain FlashScan type codes have external power supervision built into the software. For details, refer to Devices Requiring External Power Supervision in the NFS2-3030 Installation Manual or the NFS-3030 Installation Manual.
64
Power Considerations
24 VDC Power from Control Panel or Power Supply FCM-1 ELR 47K Power Supervision Relay (EOLR-1)
ELR 47K
FMM-1
SLC-psr-2addresstpH.wmf
65
Power Considerations
Note: Drawing shows power wiring only; SLC Wiring not shown.
66
SLC-nacY1tpH.wmf
Power Considerations
FCM-1
FCM-1
Note: Drawing shows power wiring only; SLC Wiring not shown.
SLC-nacZ1tpH.wmf
67
Power Considerations
68
Secondary Surge Protectors: DTK-2LVLP-F: Diversified Technology Group, Inc. (DITEK) 1720 Starkey Rd. Largo, FL 33771 (800) 753-2345. SLCP-30: EDCO 1805 N.E. 19th Ave. Ocala, FL 34470 (352) 732-3029 PLP-42N: Northern Technologies, Inc. 23123 E. Madison Ave. Liberty Lake, WA 99019 (800) 727-9119
NOTE: For detailed information refer to the installation documentation supplied with the unit.
One primary surge protector must be used with each SLC wiring pair whenever SLC wiring runs outside the building. Install primary protection only as shown in this document. Refer to NEC Article 800 and local building code requirements.
Additional primary surge suppressors may be added as required by the NEC. Add these additional suppressors in series with the SLC wiring at the building entry/exit. Wiring connected to the surge suppressor output must remain within the building while wiring connected to the surge suppressor input may be routed outside the building as shown below.
Building #2 Building #1
P P = Primary S = Secondary P
Surge Suppressor
P FACP S P S
SLC-ssbuild1.cdr
69
Installation
B.2 Installation
Mounting of the secondary surge suppressor must be inside the FACP enclosure or in a separate enclosure listed for fire protective signaling use. Locate on an available stud and secure with nut. Unit is connected in series with the SLC Loop to protect the Control Panel. Provide a common ground to eliminate the possibility of a differential in ground potentials.
IN
OUT
SLC Loop
IN OUT
PLP-42N Connections
PLP-42N
GRND
L4 L4
OUTPUT
INPUT
L3
L2
L1
L1
L2
L3
OUTPUT
L3
INPUT
L2
L2
L3
+
SLC Loop
GRND
L4
L4
NOTE: Use 12 AWG (3.31 mm2) to 18 AWG (0.82 mm2) wire with crimp-on connectors to connect the units ground terminal to equipment ground. Wire length must be minimized to provide best protection.
70
SLC-plpn1.cdr
L1
L1
SLC-lvlp1.cdr
Installation
SLCP-30 Connections
SLCP-30
IN
OUT
SLC Loop +
SLC-slcp1.cdr
IN
OUT
IN
OUT
SLC Loop
IN OUT
PLP-42N Connections
PLP-42N
GRND
L4 L4
OUTPUT
INPUT
L3
L2
L1
L1
L2
L3
PLP-42N
OUTPUT
L3
INPUT
L2
L3
+
SLC Loop
GRND
L4
NOTE: Use 12 AWG (3.31 mm2) to 18 AWG (0.82 mm2) wire with crimp-on connectors to connect the units ground terminal to equipment ground. Wire length must be minimized to provide best protection
SLC-plpn2.cdr
L1
L1
L2
SLC-lvlp2.cdr
71
Installation
SLCP-30 Connections
SLCP-30
IN
OUT
SLC Loop +
SLCP-30
IN
OUT
+ + IN OUT
SLC-slcp2.cdr
NOTE: Do not connect shield (if present) to surge protector or fire panel.
PLP-42N Connections
PLP-42N
GRND
L4 L4
OUTPUT
L3
INPUT
SLC Loop
L2 L1
L1
L2
L3
NOTE: Use 12 AWG (3.31 mm2) to 18 AWG (0.82 mm2) wire with crimp-on connectors to connect the units ground terminal to equipment ground. Wire length must be minimized to provide best protection. Do not connect shield (if present) to surge protector or fire panel.
72
SLC-plpn3.cdr
SLC-lvlp3.cdr
Installation
SLCP-30 Connections
SLCP-30
SLC Loop
+ +
IN
OUT
NOTE: Do not connect shield (if present) to surge protector or fire panel.
+ + IN OUT
NOTE: Do not connect shield (if present) to surge protector or fire panel.
PLP-42N Connections
PLP-42N
GRND
L4 L4
OUTPUT
L3
INPUT
SLC Loop
L2 L1
L1
L2
L3
NOTE: Use 12 AWG (3.31 mm2) to 18 AWG (0.82 mm2) wire with crimp-on connectors to connect the units ground terminal to equipment ground. Wire length must be minimized to provide best protection. Do not connect shield (if present) to surge protector or fire panel.
SLCP-30 Connections
SLCP-30
SLC Loop
+ +
IN
OUT
NOTE: Do not connect shield (if present) to surge protector or fire panel.
SLC-slcp3.cdr
SLC-plpn3.cdr
SLC-lvlp3.cdr
SLC-slcp3.cdr
73
Notes
74
Notes
75
Type H
Terminal Function SLC SLC + Unused Normally Open (1) Normally Closed (1) Relay Common (1) Normally Open (2) Normally Closed (2) Relay Common (2) Unused Unused
76
SLC SLC +
Type V
Type H
Terminal Function SLC SLC + VDC VDC + Unused Solenoid B/A Solenoid B/A + Solenoid A + Solenoid A Unused Unused
77
FMM-1
C.3 FMM-1
Class A Supervision Class A Supervision+ Class A/B Supervision + Class A/B Supervision -
SLC SLC +
Class A Supervision Class A Supervision+ Class A/B Supervision + Class A/B Supervision -
SLC SLC +
Type V
Type H
Terminal Function SLC SLC + Unused Unused Unused Class A/B Supervision Class A/B Supervision + Class A Supervision + Class A Supervision Unused Unused
78
NumericsG
Numerics
24 VDC power 6366 alternate method of supervising 66 monitoring and switching NAC power 49
A
A77-716B Replaced by EOLR-1 See power supervision relay ACPS-2406 16, 63 ACPS-610/E 16, 63 address capacity 33 addressable devices 33 addressable modules 13, 40 AFC-600 Discontinued AFP-100 20, 24 AFP-200 20, 24 AFP-300/AFP-400 20, 24 AIM-200 20, 25 AM2020/AFP1010 19, 20, 25 AMPS-24/E 16, 63 analog intelligent devices 12 auxiliary devices 14
24 VDC 64 listing 15 devices addressable 33 auxiliary 14 isolator 33 maximum number between isolators 33 SLC capacity 16 supervised 64 dry contact ratings 55 dry-contact 14 DTK-2LVLP-F 69 dual monitor module 13, 41, 45 duplicate addressing 45
E
electrical interference 19 End-of-Line-Resistor 51, 66, 67 EOLR-1 See power supervision relay
F
FACP, see Fire Alarm Control Panels factory preset 42 FAPT-751 14 FAPT-851 14 fault 16, 35, 37 fault condition 33 Fault Isolator Module, see isolator module FCM-1 49, 51, 52, 53, 64, 66, 67 FCPS-24 63 FDM-1, see dual monitor module Fire Alarm Control Panels 9, 69 Fire alarm service 43, 44, 45, 46, 47 FlashScan 9, 12, 17, 34 floating segments 29 FMM-1, see monitor module FMM-101, see miniature monitor module Form-C contacts 55 four-wire configuration 52 FRM-1, see Relay modules FSB-200, FSB-200S 14 FSI-751 15 FSI-851 15 FSL-751 15 FSP-751/T 15 FSP-851/T 15 FST-751/R 15 FST-851/R 15 FTM-1 13 FZM-1, see zone interface module 40 FZM-1, see zone interface module
B
B224BI, see isolator bases B501 57 B710HD 14, 57 B710LP 57 bases 14 building entry/exit 69
C
cabinet 27 circuit fault 14 circuit, speaker/telephone 13 CLIP (Classic Loop Interface Protocol) 12, 17 coded output 66, 67 common ground 70 communications loop 34 conduit, types of 2729 connector screw 27 connectors, crimp-on 70, 71, 72, 73 control modules 13 CPX-551 15 CPX-751 15
D
DC resistance 21 degraded mode 13, 40 detector bases list of 14 see also isolator bases detectors
The SLC Wiring Manual P/N 51253:J 10/30/2007
G
general alarm 66, 67 ground terminal 70, 71, 72, 73
79
HR
H
HARSH 58
I
IDC, see Initiating Device Circuits Initiating Device Circuits 13, 4047 integral relay 33 IPX-751 Discontinued December 1, 2001 isolator bases 14, 33, 34, 38 how they work 35 wiring 59 isolator devices 33 isolator modules 14, 37, 38 how they work 33 wiring of 34
monitor module 13, 40, 43, 44 dual see dual monitor module miniature, see miniature monitor module zone interface see zone interface module MPS-24A 63 MPS-24B 63 MPS-400 63 multiplex subsystem 14
N
NAC 13 NAC power 49, 67 wiring 66 NAC terminal block 66 NBG-12LX 61 NC-100 53 NEC Article 800 69 NFPA Style 4 wiring 30 NFPA Style 6 wiring 31 with isolator modules 37 NFPA Style 7 33 with isolator device 38 NFPA Style B IDC wiring 43, 45, 46 NFPA Style D IDC wiring 44, 47 NFPA Style Y 49 wiring 51 NFPA Style Z 49 wiring 52 NFS2-3030/NFS-3030 23 NFS2-640 19 NFS-3030 19 NFS-320 19 NFS-640 19, 23 normally closed contacts 64 Notification Appliance Circuit 13, 66 see also NAC notification appliances 64
J
junction box 28
K
key-lock reset 61
L
LCM-320/LEM-320 19, 23 external power supervision 64 LED Annunciator, remote 57, 58 LED operation 17 LEM-320 on NFS-3030, see LCM-320/LEM-320 on NFS-640 19, 23 LIB-200 20 LIB-200A, LIB-400 19, 25 local building code 69 Loop Resistance 19, 20, 21 Style 6 & 7 22 loops 22 LPX-751/L 15
P M
metal conduit 28, 37 Miniature monitor module 41 module circuits, configuring 40 modules addressable 13 control 13 h-type 9, 78 isolator 14 monitor 13 relay 14 v-type 9, 78 PLP-42N 69 Polling Protocols 12 power run 63, 64 power supervision relay 51, 52, 64 power supplies 16, 63 power-limited 66 proper gauge wire 63 pull stations 15, 38 addressable manual, wiring 61
R
RA400Z 57, 58
The SLC Wiring Manual P/N 51253:J 10/30/2007
80
SZ
ratings, dry contact 55 relay bases 14, 33 relay module 14, 55 wiring 55 Releasing Device FCM-1 53 NC-100 53 remote switching center 14 RFX Wireless Interface (Discontinued as of Dec. 31, 2005) 15 rotary switches 9, 42, 45, 46, 47
V
VIEW 15
W
Waterflow alarm service, automatic and manual 43, 44, 45, 46, 47 wire length four-wire SLC 22 two-wire SLC 21 wire nuts 28 wire size 19, 20 wiring isolator bases 59 isolator modules 34 NACs 66 pull stations 61 relay modules 55 SLCs 43, 44, 45, 46, 47 wiring pair 69 wiring style requirements 16
S
SDRF-751 15 Security service 43, 44, 45, 46, 47 shield 73 shield drain wire 27 shielded wire 28 shield-termination 27 short circuit 33, 34 Signaling Line Circuit 12 see also SLC SLC capacity of devices 16 performance 16 setting an SLC address 42 terminal block 28 trouble conditions 16 wiring 43, 44, 45, 46, 47 SLC-30 69 sounder bases 14, 33 speaker circuit 13 Sprinkler supervision 43, 44, 45, 46, 47 standard bases 14 Style 4, Style 6, Style 7, Style B, Style D, Style Y, Style Z see NFPA Style 30 supervised circuits 64, 66 supervised devices 64 suppressors, surge 69 surge protector 12, 69 System 5000 with AIM-200 20, 25
X
XP Series Transponders 14 XP5-C Transponder 13 XP5-M Transponder 13
Z
zone interface module 13, 40, 46, 47
T
telephone circuit 13 terminal block, NAC 67 termination of shield 27 transponders 14 trouble conditions 16, 33 trouble warning 35 T-tapping 21, 30, 31, 37, 38 twisted shielded pair wiring 19, 20 twisted unshielded pair wiring 19, 20 twisted-pair wire 28 two-wire configuration 51 two-wire detectors 64
81
ZZ
82
Limited Warranty
Honeywell International Inc. warrants products manufactured by it to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date stamped at time of manufacture. The sole and exclusive obligation of Honeywell International Inc. is to repair or replace, at its option, free of charge for parts and labor, any part that is defective in materials or workmanship under normal use and service. All returns for credit are subject to inspection and testing at the factory before actual determination is made to allow credit. Honeywell International Inc. does not warrant products not manufactured by it, but assigns to the purchaser any warranty extended by the manufacturer of such products. This warranty is void if the product is altered or repaired by anyone other than Honeywell International Inc. or as expressly authorized by Honeywell International Inc. in writing, or is serviced by anyone other than Honeywell International Inc. or its authorized distributors. This warranty is also void if there is a failure to maintain the products and systems in which they operate in a proper and workable manner. In case of defect, secure a Return Material Authorization form from our Return Authorization Department. This writing constitutes the only warranty made by Honeywell International Inc., with respect to its products. Honeywell International Inc., does not represent that its products will prevent any loss by fire or otherwise, or that its products will in all cases provide the protection for which they are installed or intended. Buyer acknowledges that Honeywell International Inc., is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience, transportation damage, misuse, abuse, accident or similar incident. HONEYWELL INTERNATIONAL INC. GIVES NO WARRANTY, EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTENDS BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL HONEYWELL INTERNATIONAL INC. BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE HONEYWELL INTERNATIONAL INC.S PRODUCTS. FURTHERMORE, HONEYWELL INTERNATIONAL INC. SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS. This warranty replaces all previous warranties and is the only warranty made by Honeywell International Inc. No increase or alteration, written or verbal, of the obligation of this warranty is authorized.
Warn-HL-05-2007.fm