NF20 Service Manual
NF20 Service Manual
User’s manual
1
Power Factor Controller
!
CAUTIONS:
1. High voltage !
3. Make sure that the discharge time set in controller matches capacitor
discharge time !
2
Power Factor Controller
CONTENTS
Section 1 General
Section 4 Terminals
Section 7 Keyboard
3
Power Factor Controller
4
Section1 General
Main features:
5
Recall function of recorded values
True RMS measurement upto 31st harmonics
Display of individual voltage and current harmonics in % upto 31 st
Display of voltage and current total harmonics distortion
Display and monitoring of temperature
Potential free contact alarm output , rtc (Optional)
NF20 96 Model
.
6
Section 2 Mechanical Dimensions :
96 mm
59 mm
NF20 96 model With Add On card (Relay + Modbus)
.
96 mm 51 mm
96 mm
75 mm
7
8
Panel Cutout for NF20 96 size model
92 mm + 0.8mm
92 mm + 0.8mm
Optional Pluggable Module (Relay + Modbus)
9
Section 2 Mechanical Dimensions : 144 size model
Panel Cutout
138mm
138mm
10
Section 3 Installation and connection of the controller
Mounting of the controller is featured with easy “Clip- in” mounting. Push the
meter in panel slot, it will click fit into panel with the four integral retention
clips on two sides of meter. If required, additional support is provided with
swivel screws as shown in Fig. 1 for NF20 96 Model. same is applicable for
NF20 144 MODEL
.
Before the controller is connected up, all leads and cables must be checked to
ensure that no current is flowing through them. Care should be taken to
ensure that the measuring voltage and current are in the correct phase
position. The connection should be set up as shown in Fig. 2. The specified
safety regulations must be observed.
The measuring voltage may lie in the range from 30 - 550 VAC and can be
connected between L - N or between L - L.
The auxilliary supply voltage is 110 to 550 VAC and can be connected
between L - N or L -L (depending of the grid).
11
Easy Clip in
Mounting
Swivel Screw
Fig 1: Installation
3.1 Alarm output / error messages
The alarm contact is open in normal operation and closed in the event of a
fault. The relevant fault is simultaneously shown on the display in plain text.
The following fault messages are displayed:
UNDERVOLTAGE Display and relay output
OVERVOLTAGE Display and relay output
UNDER FREQUENCY Display and relay output
OVER FREQUENCY Display and relay output
UNDER CURRENT Display and relay output
OVER CURRENT Display and relay output
VOLTAGE HARMONICS Display and relay output
CURRENT HARMONICS Display and relay output
OVER TEMPERATURE Display and relay output
OUT OF BANK Display and relay output
OVER COMPENSATION Display and relay output
12
Fig. 2: NF20 96 Model Electrical Connection
supply- meas. meas. current
voltage voltage Im (5A/1A) 1. capacitor-
VLL‘ branch
k l
L1 (R)
L2 (S)
L3 (T)
N
T 6,3A
T 2A
T 2A
For 8 Relays
Interface RS485
COM NO 1 2 3 4 5 6 7 8
alarm-
relay
capacitor capacitor
contactors 1-4 contactors 5-8
T 2A
Interface
a b VL VL‘ IL IL‘ P1 P2
K1
power factor
controller
NF20 144 MODEL
COM NO 1 2 3 4 5 6 7 8 9 10 11 12
alarm-
relay
capacitor capacitor
contactors 1-6 contactors 7-12
13
Section 4 Rear side Terminals
4.1 Without Add on Card (Relay + Modbus)
Measurement Measurement
Aux Supply Voltage Current
(110 to 550 VAC) (30 to 550 VAC) (1 / 5 Amp)
1 2 3 4 5 6 7
L N NC VL VL‘ IL IL‘
ALARM
COM C1 C2 C3 C4
NO COM
Common (Relay 1 to 4)
Incoming phase
Potential Free
Potential Free supply for
contactors. Relay Contacts
Alarm Contact
14
4.2 With Add on Card (Relay + Modbus)
Measurement Measurement
Aux Supply Voltage Current
(110 to 550 VAC) (30 to 550 VAC) (1 / 5 Amp)
1 2 3 4 5 6 7
L N NC VL VL‘ IL IL‘
B A G
COM C5 C6 C7 C8
RS 485
ALARM
COM C1 C2 C3 C4
NO COM
Common (Relay 1 to 8)
Incoming phase
supply for Potential Free
Potential Free
contactors. Relay Contacts
Alarm Contact
15
Section 4 NF20 144 Terminals
1 2 3 4 5 6 7 8 9
P1 K1 K2 K3 K4 K5 K6
(Relay 1 to 6)
Incoming phase
supply for Potential Free
contactors. Relay Contacts
16
Section 4 NF20 144 Terminals
1 2 3 4 5 6 7 8
P1 K1 K2 K3 K4 K5 K6
17
Section 5 Front Screen
PF 0,990 IND
18
Section 6 Front Screen capacitor symbols
PF 0,990 IND
X D
19
Section 7 Keyboard
Keyboard with soft touch keys are provided on the front fascia
of the controller. The various keys are:-
MENU Key. Pressing menu key will enter
M into main menu OR to exit from sub
menu.
20
Section 8 Display of various electrical parameters:
REACTIVE POWER
21
LINE FREQUENCY It shows phase Frequency value
kWh EXPORT
It shows system active export
energy.
22
ACT IVE DEMAND IMPORT It shows system active import
demand power value.
It Displays temperature of
TEMPERATURE
Power Factor controller panel.
23
SYSTEM FAULTS-1 It Displays system present
faults.
SYSTEM FAULTS-2
It Displays system present
faults.
There are three main menus namely Basic Setting, Advanced Setting,
Service Modes.
Press Menu key to enter into main menus from display parameters.
Press Up / down key to scroll through main menus.
Press Enter key to enter into submenus.
24
Section 10 BASIC SETTINGS
Press ENTER key to enter into Basic setting.
ENTER PASSWORD : Password protection can be
enabled to prevent unauthorised access to basic
ENTER PASSWORD
setting’s sub-menues, by default password is set to
0000.
APFC allows user to set password in range 0000 to
9999. Password protection is enabled by selecting a
four digit number other than 0000.
Password Setting:
To change password please refer section 11.7
25
SYSTEM NOMINAL VOLTAGE :This is the system rated
voltage with respect to which the fault limits
are defined. Value is settable from 50 to 550 VAC.
SYS NOM VOLTAGE
Press ENTER key to edit system nominal value.
Pressing or key will increment or decrement
digit value. Then pressing ENTER key will advance to
next digit & confirm newly changed values.
BANKS IN USE : user can set banks from 1 to 4. If
Add on card with 4 relays are attached user can set
banks from 1 to 8 ( NF20 96 Model).
BANKS IN USE for NF20 144 Model it can be 1 to 12
Press ENTER key to edit banks in use.
Pressing or key will increment or decrement
digit value. Then pressing ENTER key will confirm newly
changed values.
BANK KVAR VALUES : user can program bank kvar
BANK1 KVAr VALUE
values in range 1 to 255 kVAr. Increments in steps of
0.5 kVAr. kVAr value with decimal digit is possible.
26
Section 11 ADVANCED SETTINGS
Press ENTER key to enter into Advance setting.
27
Section 11.1 : SYSTEM SETUP
This menu allows user to set one out of several system
SYSTEM SETUP
related setup parameters.
Press ENTER key to enter into system setup sub menues.
Pressing or key will scroll through submenus.
28
SWITCH OFF TIME :This parameter is the SWITCH-
SWITCH-OFF-TIME OFF time of individual capacitor bank. Switch off time
Value is settable from 10 to 1800 Sec.
Press ENTER key to edit Switch off time value.
Pressing or key will increment or decrement
digit value resp. Then pressing ENTER key will advance
to next digit & confirm newly changed values.
29
Threshold value is editable in range 30 to 100%.
Press ENTER key to edit threshold value.
Pressing or key will increment or decrement
digit value resp. Then pressing ENTER key will
advance to next digit & confirm newly changed
values.
SWITCHING OPERATION WARNING COUNT : After
an output has performed this number of switching
operations a warning message is displayed.
switching operation warning count is editable in
SWITCHING OPERATION range 10000 to 255000.
WARNING COUNT warning will get disappear if user resets switching
operation count.
Press ENTER key to edit switching operation count.
Pressing or key will increment or decrement
digit value resp. Then pressing ENTER key will
advance to next digit & confirm newly changed
values.
Capacitor Health Check : The kvar of the particular
CAP HEALTH CHECK
capacitor bank is calculated during each switching
operation and compared with stage output of
capacitor. If the result varies by 80% of nominal
value for a particular bank warning will be
displayed & if it goes below 70% of nominal value
that particular bank will get block. user can enable
or disable this feature. The number of attempts for
checking bank value are programable, refer “cap
test attempt” count.
30
Press ENTER key to edit cap health check.
Press or key to get available options (yes
/no) resp. Then pressing ENTER key will confirm
newly changed options.
SYSTEM FREQUENCY :
This parameter is settable as 50 or 60 Hz.
31
SYSTEM TYPE :
This parameter is settable as 1 phase or 3 phase.
SYSTEM TYPE Press ENTER key to edit parameter.
Press or key to get available options (1PH
/3PH) resp. Then pressing ENTER key will confirm
newly changed option.
32
PHASE CURRENT PHASE VOLTAGE
IL2 L2 - N - 0
IL2 L2 - L3 - 30
Il2 ( k <- > l ) L3 - N - 60
IL2 L1 - L3 - 90
IL2 L1 - N - 120
IL2 L1 - L2 - 150
Il2 ( k <- > l ) L2 - N - 180
Il2 ( k <- > l ) L2 - L3 - 210
IL2 L3 - N - 240
Il2 ( k <- > l ) L3 - L1 - 270
Il2 ( k <- > l ) L1 - N - 300
Il2 ( k <- > l ) L1 - L2 - 330
33
ENERGY DEMAND INTEGRATION TIME :
This parameter is used to set the period over which
current and power readings are to be integrated.
The Unit of displayed values is minutes. time is
ENERGY DEMAND settable as 8,15,20,30 min resp.
INTEGRATION TIME
Press ENTER key to edit parameter.
Pressing or key will increment or decrement
digit value resp. Then pressing ENTER key will
advance to next digit & confirm newly changed
values.
ENERGY UNIT :
This parameter allows user to set energy in terms
ENERGY UNIT of Wh / kWh / MWh as per the requirement. Same
is applicable to all types of energy.
34
Press ENTER key to edit parameter.
Pressing or key will scroll between the
available options. Then pressing ENTER key will
confirm the newly selected option.
35
DEFAULT SYSTEM VALUES :
This menu allows user to reset NF20 to factory
default setting.(Refer section 14 )
DEFAULT SYSTEM VALUES Press ENTER key to edit parameter.
Press or key to get available options. Then
press ENTER key to confirm newly changed option.
During factory reset meter will display “WAIT”
message on second row then NF20 will reset to factory
default settings.
36
Section 11.2 :MANUAL SETUP :
This menu allows user to test or set the bank
MANAUL SETUP operating mode.
BANK ON / OFF MANUALLY :
This menu allows user to ON / OFF banks set in Auto
mode only.
BANK ON / OFF Press ENTER key to ON/OFF Bank manually.
( MANUALLY )
Press or key to get available options as ON /
OFF. Then press ENTER to ON / OFF bank manually.
Note : - APFC allows to ON / OFF Banks set in Auto
mode only. If fault is present APFC does not allow to
ON/OFF Banks manually. On exit from manual mode
all the banks enter into Auto mode.
BANKS FUNCTION :
This parameter allows to set individual bank
operating mode.
Press ENTER key to edit parameter.
Press or key to get available options as AUTO
/ FIXED / OFF. Then press ENTER to confirm individual
BANKS FUNCTIONS AS
bank operating mode.
AUTO / FIXED / FAULTY Auto : Automatic Operation
It is displayed as capacitor symbol if connected.
37
Section 11.3 :ALARM SETUP :
This menu allows user to set one out of several alarm
ALARM SETUP
related parameters.
Press ENTER key to enter into alarm setup sub menues.
Pressing or key will scroll through submenus.
38
Note 2: - Relay will reset at 3% of voltage nominal value
plus trip value.
Reset point is factory set, not editable.
39
FREQUENCY FAULT : It is for frequency protection against
FREQUENCY FAULT
frequency condition in phase.
Note : -
1. Frequency fault will occur at nominal frequency minus or
plus of trigger point of nominal frequency.
1. If fault occurs APFC will Switch off all banks including
fixed banks one after the other with a delay of 1sec between
the banks when fault occurs.
2.Relay will reset at 1% of Nominal frequency value plus OR
minus trip value resp. Reset point is factory set, not
editable.
40
UNDER CURRENT : It is for under current protection
UNDER CURRENT
against under current condition in phase.
(1 - 3 %)
Press ENTER key to edit trigger value.
Pressing or key will increment or decrement digit
value. Then pressing ENTER key will advance to next digit &
confirm newly changed values.
41
OVER CURRENT : It is for over current protection against
OVER CURRENT
over current condition in phase.
42
VOLTAGE THD : When voltage THD is more
VOLTAGE THD
than set limit then PF controller will operate relay
( 1 - 25 % )
Press ENTER key to edit trigger value.
Pressing or key will increment or decrement digit
value. Then pressing ENTER key will advance to next digit &
confirm newly changed values.
43
CURRENT THD : When current THD is more
CURRENT THD
than set limit then PF controller will operate relay
44
Temperature : When cabinet temperature exceeds above
TEMPERATURE the 55 deg celsius APFC displays warning message and if
temperature exceeds above 60 deg celsius APFC
disconnects all the capacitor banks and activates the
relay if enabled.
45
OVER COMPENSATION : In Auto mode if all banks are
OVER COMPENSATION
ON (except Fixed banks) and if Diff. to PF exceeds
threshold of lower bank kvar value APFC will activate
relay if enabled.
Press ENTER key to enter into over compensation sub
setup.
Pressing or key will scroll through submenus.
46
Press ENTER key to edit option.
Press or key to get available options. Then
press ENTER key to confirm newly changed option.
Note : - Relay will reset if target PF is achieved.
47
Section 11.4 : RESET VALUES :
This menu allows user to reset one out of several
parameters.
RESET VALUES
Press ENTER key to enter into reset values sub menues.
Pressing or key will scroll through submenus.
RESET ENERGY : Press ENTER key to reset all energy
RESET ENERGY related parameters.
After resetting APFC will show “DONE” message on
display.
RESET DEMAND : Press ENTER key to reset all demand
RESET DEMAND related parameters.
After resetting APFC will show “DONE” message on display.
48
RESET INTERRUPT : Press ENTER key to reset
RESET INTERRUPT power down interrupt count.
After resetting APFC will show “DONE” message on
display.
RESET BANK SWITCHING COUNT : Press ENTER
RESET BANK SW ITCHING
key to entered into submenus.. Then press
COUNT ( INDIVIDUAL / ALL ) or key get available options. Then pressed
ENTER key to reset individual, all bank switching
count.
After resetting APFC will show “DONE” message on
display.
RESET BANK OPERATION TIME : Press ENTER key
RESET BANK OPERATION to entered into submenus.. Then press
TIME ( INDIVIDUAL / ALL ) or key get available options. Then pressed
ENTER key to reset individual, all bank operation
count.
After resetting APFC will show “DONE” message on
display.
49
Section 11.5 : MODBUS SETUP :
This menu allows user to set modbus related setup.
MODBUS SETUP
Press ENTER key to enter into modbus setup sub menus.
Pressing or key will scroll through submenus.
50
Section 11.6 : DISPLAY SETUP :
This menu allows user to set display related submenus.
DISPLAY SETUP
Press ENTER key to enter into display setup sub menues.
Pressing or key will scroll through submenus.
51
Section 11.7 :CHANGE PASSWORDS:
To change Basic setting’s password and Advanced
setting’s password enter correct password of
CHANGE PASSWORD
Advanced Setting.
After entering Advanced Setting’s correct password,
APFC enters into advanced setting’s sub-menues.
Pressing or key will scroll through Advanced
setting’s sub-menues. Select “CHANGE PASSWORDS”
sub-menu, Press ENTER key to enter into Change
Password’s sub menus. Pressing or key will
scroll through Basic password, Advanced Password
menu.
BASIC PASSWORD:
Press ENTER key to edit basic password.
BASIC PASSWORD Pressing or key will increment or decrement
digit value. Then pressing ENTER key will advance to
next digit & confirm newly changed password.
To re-edit password, follow the same procedure as
mentioned.
ADVANCE PASSWORD:
Press ENTER key to edit advanced password.
ADVANCE PASSWORD Pressing or key will increment or decrement
digit value. Then pressing ENTER key will advance to
next digit & confirm newly changed password.
To re-edit password, follow the same procedure as
mentioned.
52
Section 12 : SERVICE MODE :
Press ENTER key to entered into service sub menus.
SERVICE MODE Pressing or key will scroll through submenus.
The following sub menus will be available in service sub
menus : -
1. V -MIN V-MAX
2. I -MIN I -MAX
3. Frequency- MIN MAX
4. Temperature Min MAX
5. Maximum V THD I THD
6. Maximum Import Power
7. Maximum Export Power
8. Maximum Capacitive power
9. Maximum Inductive power
10. Maximum Apparent power
11. Maximum Import demand
12. Maximum Export demand
13. Maximum Apparent demand
14. Maximum Ampere demand
15. C1 to C8* Switching count
16. C1 to C8* Operation time
17. C1 to C8* Bank Kvar value
18 TEST RUN
53
TEST RUN:
This menu point allows the user to check the settings of the NF20 controller.
After activation of the test run, the controller switches each stage on and off
successively and calculates the output of the capacitors connected (this
procedure is done three times to eliminate possible errors). The values
calculated are stored and can be retrieved in the following menu item (C-
BANK kVar).
Any discrepancies in bank parameters found are evaluated and displayed in
plain text. The following errors can be displayed:
- No Input voltage
- Under Voltage
- Over Voltage
- Check number of Banks
- Wrong power input
Note: The results displayed are messages intended to help the user trace the
cause of the error. Final evaluation remains the responsibility of the user.
Under complicated (high load fluctuations) grid conditions, 100% error
recognition cannot be guaranteed.
54
Section 13 : TECHNICAL DATA :
- Large and multifunctional LCD
Display (2 × 16 characters)
- Graphic and alphanumeric
- LCD illumination
- Line voltage (V AC)
System parameters displayed - Reactive power (VAr)
- Active power (W)
- Frequency (Hz)
- Apparent power (VA)
- Line current (A)
- Temperature (°C)
- Real-time cos phi
- Diff to PF
- THD – V / THD - I in % upto 31st
- Individual Harmonics in % upto
31st for V & I
- Energy kWh (Import/ Export)
- Energy kVAh
- Energy kVARh (Ind /Cap)
- Demand kVA/Current/kW (Imp /
Exp)
- Run Hour
- On Hour
- No of interruption
- RTC time.
- System Fault 1/2.
- System Warning
55
Alarm output - Out of Bank (Under
Compensation)
- Overcompensation
- Under Voltage
- Over Voltage
- Undercurrent
- Overcurrent
- Over temperature
- Under / Over Frequency
- Excess Harmonics ( V-THD / I-
THD)
Recall recorded values - Maximum / Minimum Voltage
- Maximum / Minimum Current
- Maximum / Minimum Frequency
- Maximum Active Power (Import
/ Export)
- Maximum Apparent Power
- Maximum Capacitive Power
- Maximum Inductive Power
- Maximum Active Import Demand
- Maximum Active Export Demand
- Maximum Apparent Demand
- Maximum Ampere Demand
- Maximum / Minimum
Temperature
- Maximum THD(V/I)
- Switching count of Capacitor
- Operation time of capacitor
56
- Capacitor switching count exceed
the limit (OSC - Over Switching
Count)
- Capacitor kVAr value between 70
Warning Messages to 80% (CVAL)
- Ambient temperature between
55 to 60 Degree Cel. (TMP)
- RTC Battery Low (BAT)
(Only applicable for RTC module)
57
Operation
- Auxiliary Supply voltage 110 V AC – 550 V AC
- Auxiliary Supply Frequency 40 to 70 Hz
- Target cos phi 0.8 ind. … 0.8 cap.
- Switching On & Off 10 s … 30 min
- Discharge Time 60 s … 30 min
Control modes self-optimized intelligent control
mode
Measurement
- Measurement voltage range 30 ... 550 V AC (L–L / L–N)
- Fundamental frequency 50 / 60 Hz
- Measurement current (CT) x/5 and x/1 Ampere onsite
programmable
- Minimum operating current 2 mA
- Maximum current 6 A (sinusoidal)
Accuracy Current, voltage: 0.5% of nominal
value
Active, Apparent, Reactive power:
1% of nominal value
Active Energy : 1%
Apparent Energy : 1%
Reactive Energy : 2%
THD : ± 4%
Switching outputs 4 / 6 / 8 steps available (NF20 96
Relay outputs model)
- Number of outputs 6/ 8/12 steps available (NF20 144
- Switching voltage/Power model)
Max. 250 VAC / 1000W
CT Seconadry 5 Amp
System frequency 50 Hz
System type 3 Phase
Node address 1
59
Section 14 : FACTORY DEFAULT SETTING :
Autoscroll OFF
Backlite ON/OFF ON
Contrast_level 5
60
Description Default value
Switch_operation_warning 50000
61
Fault Description Default
Enable Parameter (*) Enable
Trip Value 85%
Under Voltage 5 Sec
Trip Delay (*)
Hysteresis (*) 3%
Relay Yes
Enable Parameter (*) Enable
Trip Value 110%
Over Voltage Trip Delay (*) 5 Sec
Hysteresis (*) 2%
Relay Yes
Enable Parameter Disable
Trip Value 6%
Under Frequency
Trip Delay (*) 5 Sec
Hysteresis (*) 1%
Relay No
Enable Parameter Disable
Trip Value 6%
Over Frequency
Trip Delay (*) 5 Sec
Hysteresis (*) 1%
Relay No
*Note : - Parameters are not editable, Factory set.
62
Fault Description Default
Enable Parameter (*) Enable
Trip Value 2%
Under Current
Trip Delay (*) 5 Sec
Hysteresis (*) 1%
Relay Yes
Enable Parameter (*) Enable
Trip Value 110%
Over Current Trip Delay (*) 5 Sec
Hysteresis (*) 1%
Relay Yes
Enable Parameter (*) Enable
Trip Value 7%
V THD
Trip Delay (*) 30 Sec
Hysteresis (*) 2%
Relay Yes
Enable Parameter (*) Enable
Trip Value 50%
I THD
Trip Delay (*) 30 Sec
Hysteresis (*) 45%
Relay Yes
*Note : - Parameters are not editable, Factory set.
63
Fault Description Default
Enable Parameter (*) Enable
Trip Value (*) 60 Degree
Temperature
Trip Delay (*) 10 Sec
Hysteresis (*) 55 Degree
Relay Yes
Enable Parameter (*) Enable
Out Of bank Trip Delay (*) 10 Sec
Relay Yes
Enable Parameter (*) Enable
OverCompensation Trip Delay (*) 10 Sec
Relay Yes
64
BASIC SUB MENU
OR
No
PASSWORD CORRECT
D Q
YES
OR
M
Edit CT PRIMARY BASIC SETTINGS
OR
M
Edit CT SECONDARY BASIC SETTINGS
OR
M
Edit SYSNOM VOLTAGE BASIC SETTINGS
OR
M
Edit BANKS IN USE BASIC SETTINGS
OR
M
BANK1 KVAr VALUE BASIC SETTINGS
Edit
OR
M
BANK2 KVAr VALUE BASIC SETTINGS
Edit
OR
M
BANK3 KVAr VALUE BASIC SETTINGS
Edit
OR
M
Edit BANK4 KVAr VALUE BASIC SETTINGS
D Q
Note :- Depending on no. of banks configured Bank KVAr screen will shown upto that bank.
65
Section 15 : OPERATING DIAGRAM :
M Menu Key
Enter Key
Up Key
Down Key
Main Menu
U V
Display M
BASIC SETTINGS BASIC SUB MENU
Parameters
Display M
ADVANCE SETTINGS ADVANCE SUB
Parameters
MENU
Display M
SERVICE MODE SERVICE SUB MENU
Parameters
U V
66
ADVANCE SUB MENU
OR
No
PASSWORD CORRECT
F E
YES
M
System Sub Setup SYSTEM SETUP ADVANCE SETTING
M
MANUAL SETUP ADVANCE SETTING
Manual Sub Setup
M
Alarm Sub Setup ALARM SETUP ADVANCE SETTING
M
Reset Sub Setup RESET VALUES ADVANCE SETTING
M
Modbus Sub Setup MODBUS SETUP ADVANCE SETTING
M
Display Sub Setup DISPLAY SETUP ADVANCE SETTING
M
Change Password CHANGE PASSWORDS ADVANCE SETTING
Sub Setup
F E
67
System Sub Setup
G J
OR
M
Edit TARGET PF SYSTEM SETUP
OR
M
Edit SWITCH-IN-TIME SYSTEM SETUP
OR
M
Edit SWITCH-O FF-TIME SYSTEM SETUP
OR
M
Edit DISCHARGE TIME SYSTEM SETUP
OR
M
THRESHOLD SYSTEM SETUP
Edit
OR
SWITCHING OPERATION
M
Edit SYSTEM SETUP
WARNING COUNT
OR
M
Edit CAP HEALTH CHECK SYSTEM SETUP
OR
CAPACITOR TEST M
Edit SYSTEM SETUP
ATTEMPTS COUNT
OR
SYSTEM FREQUENCY M
Edit SYSTEM SETUP
OR
M
Edit SYSTEM TYPE SYSTEM SETUP
I H
68
I H
OR
M
Edit * INPUT PHASE CURRENT SYSTEM SETUP
OR
M
Edit * INPUT PHASE VOLTAGE SYSTEM SETUP
OR
ENERGY DEMAND
M
Edit
SYSTEM SETUP
INTEGRATION TIME
OR
M
Edit ENERGY UPDATE RATE SYSTEM SETUP
OR
M
Edit ENERGY UNIT SYSTEM SETUP
OR
ENERGY OVERFLOW M
Edit
SYSTEM SETUP
COUNT
OR
M
Edit #RTC DATE , TIME SYSTEM SETUP
OR
M
DEFAULT SYSTEM VALUES
Edit SYSTEM SETUP
OR
M
Edit MAX SWITCH POWER SYSTEM SETUP
69
Network Table :-
PHASE CURRENT PHASE VOLTAGE
IL1 L1 - N - 0
IL1 L1 - L2 - 30
IL1 ( k <- > l ) L2 - N - 60
IL1 L3 - L2 - 90
IL1 L3 - N - 120
IL1 L3 - L1 - 150
Il1 ( k <- > l ) L1 - N - 180
Il1 ( k <- > l ) L1 - L2 - 210
IL1 L1 - N - 240
Il1 ( k <- > l ) L2 - L3 - 270
Il1 ( k <- > l ) L3 - N - 300
Il1 ( k <- > l ) L3 - L1 - 330
IL2 L2 - N - 0
IL2 L2 - L3 - 30
IL2 ( k <- > l ) L3 - N - 60
IL2 L1 - L3 - 90
IL2 L1 - N - 120
IL2 L1 - L2 - 150
IL2 ( k <- > l ) L2 - N - 180
Il2 ( k <- > l ) L2 - L3 - 210
IL2 L3 - N - 240
IL2 ( k <- > l ) L3 - L1 - 270
Il2 ( k <- > l ) L1 - N - 300
Il2 ( k <- > l ) L1 - L2 - 330
70
PHASE CURRENT PHASE VOLTAGE
IL3 L3 - N - 0
IL3 L3 - L1 - 30
Il3 ( k <- > l ) L1 - N - 60
IL3 L2 - L1 - 90
IL3 L2 - N - 120
IL3 L2 - L3 - 150
Il3 ( k <- > l ) L3 - N - 180
Il3 ( k <- > l ) L3 - L1 - 210
IL3 L1 - N - 240
Il3 ( k <- > l ) L1 - L2 - 270
Il3 ( k <- > l ) L2 - N - 300
Il3 ( k <- > l ) L2 - L3 - 330
71
M anual Sub Setup
OR
M
BANK ON / OFF MANUAL SETUP
Edit
( MANUALLY )
OR
BANKS FUNCTIONS AS
Edit
AUTO / FIXED / FAULTY
MANUAL SETUP
72
A larm sub setup
L K
M
Sub Menu #1 UNDER VOLTAGE ALARM SETUP
M
Sub Menu #2 OVER VOLTAGE ALARM SETUP
M
Sub Menu #3 FREQUENCY FAULT ALARM SETUP
M
Sub Menu #4 UNDER CURRENT ALARM SETUP
M
Sub Menu #5 OVER CURRENT ALARM SETUP
M
Sub Menu #6 VOLTAGE THD ALARM SETUP
M
Sub Menu #7 CURRENT THD ALARM SETUP
M
Sub Menu #8 TEMPERATURE ALARM SETUP
M
Sub Menu #9 OVERCOMPENSATION ALARM SETUP
M
Sub Menu #10 OUT OF BANKS ALARM SETUP
M
Sub Menu #11 *BATT. LOW FAULT ALARM SETUP
73
Sub Menu #1
OR M
Under Voltage
TRIGGERVALUE
Edit
( 75 TO 90% )
OR
Under Voltage
Sub Menu #2
OR M
OR
Over Voltage
74
Sub Menu #3
OR M
Frequency Fault
TRIGGERVALUE
Edit
( 2 TO 10% )
OR
Frequency Fault
Sub Menu #4
M
OR
Under Current
TRIGGER VALUE
Edit
( 1 TO 3% )
OR
Under Current
75
Sub Menu #5
OR M
Over Current
TRIGGER VALUE
Edit
( 60 TO 120% )
OR
Over Current
Sub Menu #6
OR M
Voltage THD
TRIGGER VALUE
Edit
( 1 TO 25% )
OR
Voltage THD
76
Sub Menu #7
OR M
Current THD
TRIGGER VALUE
Edit
(1 TO 99% )
OR
Current THD
Sub Menu #8
OR
Edit M
RELAY ACTIVATION Temperature.
77
Sub Menu #9
OR
Over Compensation
OR
Out of Banks
OR
M
Activate Warning BATT. LOW FAULT
Edit
OR
78
Reset Sub Setup
N M
M
DONE RESET ENERGY RESET VALUES
M
DONE RESET DEMAND RESET VALUES
M
DONE RESET MIN PARA RESET VALUES
M
DONE RESET MAX PARA RESET VALUES
M
DONE RESET ON-RUN HOUR RESET VALUES
M
DONE RESET PD INTERRUPT
RESET VALUES
DONE M
RESET BANK OPERATION
RESET VALUES
TIME ( INDIVIDUAL / ALL )
N M
79
MODBUS SETUP
X Y
OR
M
Edit SELECT BAUD RATE MODBUS SETUP
OR
M
Edit PARITY MODBUS SETUP
OR
M
STOP BITS MODBUS SETUP
Edit
OR
M
Edit DEVICE ADDRESS MODBUS SETUP
X Y
80
DISPLAY SETUP
OR M
DISPLAY SETUP
LCD BACKLIGHT
Edit
OR
M
Edit AUTOSCROLL DISPLAY SETUP
OR
M
CONTRAST DISPLAY SETUP
Edit
81
Change Password Sub Menu
OR
BASIC PASSWORDS
Edit
OR
ADVANCE
Edit
PASSWORDS
82
SERVICESUB MENU
P O
M
VOLTAGE MIN MAX SERVICEMODE
M
CURRENT MIN MAX SERVICE MODE
M
FREQUENCY MIN MAX SERVICE MODE
M
TEMPERATURE MIN MAX SERVICE MODE
M
MAX -VTHD % MAX -ITHD % SERVICEMODE
M
MAX ACTIVE IMPORT POWER SERVICE MODE
M
MAX ACTIVE EXPORT POWER SERVICE MODE
M
MAX REACTIVE CAPACITIVE POWER SERVICE MODE
M
MAX REACTIVE INDUCTIVE POWER SERVICE MODE
Q R
83
Q R
M
MAX APPERENT POWER SERVICE MODE
M
MAX ACTIVE POWER IMPORT DEMAND SERVICE MODE
M
MAX ACTIVE POWER EXPORT DEMAND SERVICE MODE
M
MAX APPARENT DEMAND POWER SERVICE MODE
M
MAX AMPERE DEMAND SERVICE MODE
M
BANK Operation Time SERVICE MODE
[1... Banks configured ]
M
BANK VALUE [1... Banks configured ] SERVICE MODE
M
TEST RUN SERVICE MODE
P O
84
DISPLAY PARAMETERS
C A
M
LINE VOLTAGE MAIN SCREEN-*
M
LINE CURRENT MAIN SCREEN-*
M
REACTIVE POWER MAIN SCREEN - *
M
ACTIVE POWER MAIN SCREEN - *
M
APPARENT POWER MAIN SCREEN -*
M
D IFF. TO PF MAIN SCREEN - *
LINE FREQUENCY
M
MAIN SCREEN - *
M
V-THD I-THD MAIN SCREEN-*
B S
85
B S
M
IND IVIDUAL VH%AND IH% # MAIN SCREEN - *
M
kWh IMPORT MAIN SCREEN-*
M
kWh EXPORT MAIN SCREEN-*
M
KVARh IND MAIN SCREEN-*
M
KVARh CAP
MAIN SCREEN-*
M
KVAh MAIN SCREEN-*
M
AMPERE DEMAND MAIN SCREEN-*
M
ACTIVE POWER DEMAND IMPORT MAIN SCREEN-*
M
ACTIVE POWER DEMAND EXPORT MAIN SCREEN-*
M
APPERANTPOWER DEMAND
MAIN SCREEN-*
M
TEMPERATURE MAIN SCREEN-*
T W
#Note : - Enter key at individual harmonics screen then press OR key to get next
individual harmonics count.
86
Power Factor Controller
T W
M
RUN H OUR [ HH.MM ] MAIN SCREEN-*
M
ON HO UR [ HH.MM ] MAIN SCREEN-*
M
^TIME, DATE MAIN SCREEN-*
M
SYSTEM
POWER WARNINGS
DOWN COUNT MAIN SCREEN-*
M
SYSTEM FAULTS-1 MAIN SCREEN-*
M
SYSTEM FAULTS-2 MAIN SCREEN-*
M
SYSTEM WARNING MAIN SCREEN-*
C A
87
Section16 Ordering codes
RS-485 modbus:
With RS-4852 R
Without RS-485 Z
Real Time Clock (RTC):
With RTC R
Without RTC Z
Adaptor plate:
Without Adaptor Plate 0
With Adaptor Plate 1
Version:
Standard 000
Language:
Polish P
English E
Acceptance tests:
without additional quality requirements 0
with an extra quality inspection certi cate 1
with a calibration certi cate 2
1
Limited availability, needs to be agreed with the manufacturer
2
Interface RS-485 available only for the controller with 8 relay outputs
88
Power factor controller NF20 B 1 H X A X X 0 000 X X controller execution 144x144 mm
Size:
144 x 144 B
Input voltage:
240V; 50/60Hz 1
Power supply:
110-550VAC H
Relay output:
6 Relay O/P 6
8 Relay O/P1 8
12 Relay O/P A
Alarm output:
With Alarm Output A
RS-485 Modbus:
With RS-4852 R
Without RS-485 Z
Real Time Clock (RTC):
With RTC R
Without RTC Z
Adaptor plate:
Without Adaptor Plate 0
Version:
Standard 000
Language:
Polish P
English E
Acceptance tests:
without additional quality requirements 0
with an extra quality inspection certi cate 1
with a calibration certi cate 2
89
90
91
92
LUMEL S.A.