Lynx Plus Install
Lynx Plus Install
Security Systems
ARMED READY
OFF 1 2 3 STAY
ESCAPE RECORD VOLUME PLAY DELETE
AWAY 4 5 6 AUX
ADD LIGHTS ON TEST BYPASS SELECT
7 8 9
LIGHTS OFF CODE CHIME
0
STATUS NO DELAY FUNCTION
KITCHEN
BEDROOM BEDROOM TV ROOM KITCHEN DINING BDRM
DINING
LIVING ROOM
BDRM
BEDROOM BEDROOM
LIVING ROOM
TO
BEDROOM BR BEDROOM
KTCHN
GARAGE
LVNG RM . CLOSED
DOOR
BASEMENT
floor_plan-001-V1
-2-
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Table of Contents
SYSTEM FEATURES ..................................................................................................................................5
MOUNTING THE CONTROL.....................................................................................................................6
WIRING CONNECTIONS...........................................................................................................................7
CONNECTING/CONFIGURING COMMUNICATIONS DEVICES ........................................................9
AC POWER AND BACKUP BATTERY....................................................................................................11
INSTALLING WIRELESS ZONES...........................................................................................................13
MECHANICS OF PROGRAMMING ........................................................................................................16
ZONE RESPONSE TYPE DEFINITIONS ...............................................................................................18
DATA FIELD DESCRIPTIONS ................................................................................................................20
✻56 ENHANCED ZONE PROGRAMMING MODE ................................................................................38
✻80 DEVICE PROGRAMMING MENU MODE ......................................................................................43
✻81 ZONE LIST MENU MODE................................................................................................................47
✻83 ENHANCED SEQUENTIAL MODE ................................................................................................49
✻84 ASSIGN ZONE VOICE DESCRIPTORS ..........................................................................................52
✻85 RECORD CUSTOM VOICE DESCRIPTORS...................................................................................54
REMOTE PROGRAMMING/CONTROL (DOWNLOADING) ................................................................55
SYSTEM OPERATION..............................................................................................................................56
TESTING THE SYSTEM ..........................................................................................................................62
SYSTEM COMMUNICATION ..................................................................................................................63
TROUBLESHOOTING GUIDE ................................................................................................................65
PROGRAMMING DEFAULT TABLES....................................................................................................67
LYNX PLUS CONTROL DEFAULTS................................................................................................67
LYNXSIA PLUS CONTROL DEFAULTS .........................................................................................69
REGULATORY AGENCY STATEMENTS ..............................................................................................73
LIMITATIONS OF THIS SYSTEM STATEMENT..................................................................................75
UL NOTICES..............................................................................................................................................75
SIA QUICK REFERENCE GUDE ............................................................................................................75
SPECIFICATIONS.....................................................................................................................................76
CONTACTING TECHNICAL SUPPORT.................................................................................................76
WARRANTY INFORMATION .................................................................................................................76
INDEX.........................................................................................................................................................77
SUMMARY OF CONNECTIONS DIAGRAM ...........................................................................Rear Cover
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
-3-
-4-
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
System Features
The Lynx Plus Series control is a self-contained, rechargeable wireless control/communicator that features
easy installation and usage. A built-in speaker provides voice annunciation of system status along with voice
descriptors of each zone. An internal module (if provided) allows the Lynx Plus Series to communicate with
the Central Station via the Internet.
Lynx Plus Series is not intended for UL985 Household Fire applications unless a 24-hour backup battery
UL (P/N LYNXRCHKIT-HC or LYNXRCHKIT-SHA) is installed.
Powerline Carrier Devices have not been evaluated by UL.
Features
System Features Alarm Output
• Real-time clock display and 2 line by 16 • Built-in sounder
character alpha display • Bell output (120mA max.)
• Message center (for user recorded messages) • Steady output for burglary/panic
• Voice announcement of system and zone status • Temporal pulse output for fire and carbon
• Voice chime monoxide alarms
• Alarm clock • Long range radio/audio alarm verification
• Reminder Programming
• X10 scheduling • Options stored in EEROM
• Latch key reports • Can be downloaded or controlled via IBM-
• Automatic stay arming compatible computer using Compass
• Remote phone control downloader software and specified HAYES-
• Speaker phone operation compatible modem or via capable GSM or IP
• “Follow me” reminder and system announcements communications module
• 8 User Codes (Installer, Master, 5 Secondary, • Voice prompt programming mode
Duress) Other Features
• 3 Panic Functions • Exit error feature (detects difference between an
Zones and Devices actual alarm and exit alarm caused by leaving a
• 1 Hardwire zone door open after the exit delay expires)
• Up to 24 Wireless zones (5800 Series • Event log stores up to 84 events
transmitters) • Macro/ 1-button paging
• Up to 16 Wireless button zones • RF jam detection
• Up to 8 Powerline carrier devices • Compatible with encrypted (high-security)
• Supports wireless keypads devices
-5-
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
back case.
3. Feed the field wiring through the
appropriate openings in the back
case. Use tie-wraps to secure the
wiring to the built-in wire loops as ROTATE
FRONT CASE
needed. UPWARD
TO RELEASE
4. Mount the back case to a sturdy HOOKS
wall.
5. Attach the front and back cases by
connecting the hooks on the front FRONT
case to the attachments on the rear CASE
tabs.
Desktop Mounting
For desktop mounting, the optional
mounting base (model LYNXPLUS-
DM, purchased separately) must be
used.
ADD 5 6
PLAY
DELETE
LIGHTS
ON AUX
7 TEST
-6-
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
Wiring Connections
Wiring Overview
The following summarizes the connections required. Refer to the Wiring Connections paragraph and the
Summary of Connections diagram on the inside back cover when making connections. Ensure that the
battery cable is routed as shown in the figure below.
WIRE
ROUTING
TUNNELS
TIE-WRAP
POINT
MOUNTING
HOOK
TERMINAL
STRIP
MOUNTING
HOOK
TELEPHONE
CONNECTION
BATTERY
CABLE
LOCAL
SOUNDER
DISABLE
SWITCH
POWERLINE CARRIER
DEVICE CONNECTOR
1000-300-006-V2
Wiring Connections
1. Make Earth Ground Connection - The designated earth ground terminal (1) must be terminated in a good earth ground
for the lightning transient protective devices in this product to be effective. The following are examples of good earth
grounds available at most installations:
Metal Cold Water Pipe - Secure a non-corrosive metal strap (copper is recommended) to the pipe that is electrically
connected and secured to which the ground lead is electrically connected and secured.
AC Power Outlet Ground - Available from 3-prong, 120VAC power outlets only. To test the integrity of the ground
terminal, use a three-wire circuit tester with neon lamp indicators, such as the UL Listed Ideal Model 61–035, or
equivalent, available at most electrical supply stores.
a. Connect terminal 1 to a good earth ground.
2. Make Phone Line Connections - For local or full line seizure follow the appropriate steps below.
Local Seizure
a. Connect the incoming phone line to either the 8-position jack or terminals 2 (TIP) and 3 (RING) on the Lynx Plus.
b. Connect the handset phone lines to terminals 4 (TIP) and 5 (RING).
Full Line Seizure: The control must be placed in series with the incoming phone line. Plugging the Direct Connect Cord
directly into the RJ31X jack, allows the control to seize the phone line when an alarm occurs and normal phone line
usage by the premises phones if the plug needs to be removed.
a. Cut the incoming RING and TIP phone lines (typically red and green, respectively) and connect them to RJ31X
terminals 4 (red) and 5 (green).
b. Connect the premises end of the cut RING and TIP wires to RJ31X terminals 1 (grey) and 8 (brown) respectively.
-7-
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
Wiring Connections
c. Wire the flying leads of a Direct Connect Cord to the control’s phone terminals as shown in the diagram or plug into
the 8-position jack.
d. Plug the Direct Connect Cord into the RJ31X jack.
INCOMING
PHONE LINE
RING
TIP
RED 4 5 GREEN
3 6
TO
RJ31X PREMISES PHONES
RING
2 7 TIP
GREY 1 8 BROWN
DIRECT
CONNECT
CORD
OR
BROWN
GREEN
GREY
RED
8-POSITION
JACK
TIP RING TIP RING
}
}
INCOMING TO
PHONE LINE PREMISES
PHONES
01000-008-V0
LOCAL SOUNDER DISABLE: The Master Keypad’s built-in piezo sounder can be disabled by setting the
sounder disable switch to OFF. If disabled, however, no sounding will occur upon AC loss, since the
external sounder does not operate when AC power is lost.
HARDWIRED ZONE: If the EOLR is not at the end of the loop, the zone will not be properly supervised, and the
system may not respond to an open circuit on the zone.
Refer to the ✻80 Device Programming Menu Mode section to program the Powerline Carrier Devices.
-8-
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
The device must be registered before downloading or alarm reporting can take place.
-9-
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
* If the unit is in an area of known cellular coverage for 3 – 5 min and these conditions do not clear contact AlarmNet for
assistance.
- 10 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
Use only the provided ADEMCO K10145WH/K10145X10 or K10145CN Transformer. Wiring to the AC
Transformer must not exceed 300 feet using 16-gauge wire. The voltage reading between terminals 10 and
11 of the control must not fall below 9.00VAC.
Do not plug the transformer into the AC outlet until after all wiring connections have been made. Ensure the
cover is snapped closed prior to applying AC power
Backup battery
In the event of an AC power loss, the system is supported by a long life backup battery that is supervised for
connection and for low voltage conditions. If the battery is missing, or a low battery condition is detected, a
“low battery” message is displayed and a report is sent to the central station. In addition, the system will beep
once every 45 seconds to audibly indicate a low battery condition (press any key to stop the beeping).
AC Power and Rechargeable Backup Battery
Connecting AC Power and backup battery
1. Connect wires from the K10145WH or K10145X10 (K10145CN in Canada) AC Transformer to terminals 10 and 11 as
shown on the summary of connections diagram.
2. Remove battery retainer.
3. Insert battery pack into back plate.
4. Install battery retainer.
5. Secure battery retainer with the provided screw.
6. Connect battery pack connector to the receptacle on the PC board.
7. After all wiring connections have been made, snap the case closed and plug the transformer into a 24-hour, 110VAC
unswitched outlet.
Note: Rechargeable batteries may take up to 48-hours to fully charge. The “LOW BAT” message should clear within four
hours or by entering Test Mode.
SCREW
NOTE
WALYNXRCHKIT-SC
BATTERY PACK SHOWN
RETAINER
LYNXRCHKIT-SC
BATTERY PACK
1000-300-027-V0
- 11 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
SCREW SCREW
RETAINER RETAINER
LYNXRCHKIT-SHA/
LYNXRCHKIT-HC OR LYNXRCHKIT-SC
1000-300-010-V0
Ensure the control panel assembly is snapped closed prior to applying AC power.
- 12 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
For button transmitters (RF "keys") such as the 5804 and 5801, you must assign a unique zone number to
each individual button used on the transmitter. Each button on the transmitter also has a pre-designated
loop or input number, which is automatically displayed.
House Identification
If you are using a 5804BD/5804BDV Wireless Keypad with the system, you must program a House ID
Code (01–31) in field ✻24 to establish proper communication, and the keypad must be set to the same ID.
House ID 00 disables all wireless keypads. An RF House ID is not necessary for other 5800 Series
transmitters; the entry should be left at “00” (default) in those cases.
Transmitter Supervision
Except for some transmitters/keypads that may be carried off-premises (5804, 5804BD, 5804BDV, and
5804E), each transmitter is supervised by a check-in signal that is sent to the receiver at 70–90 minute
intervals. If at least one check-in is not received from each supervised transmitter within a 12-hour period,
the "missing" transmitter number(s) and "FAULT" will be displayed. Additionally, the panel will beep once
every 45 seconds until acknowledged. The supervision for a particular transmitter in the system that may
also be carried off the premises (5801, 5802MN) may be turned off by entering it as a "UR" (unsupervised
RF) type, as described in the ✻56 Enhanced Zone Programming Mode section. 5800 Series transmitters
have built-in tamper protection and dependant on system status, will annunciate as a fault or alarm
condition if covers are removed.
Transmitter Input Types
Each of the following transmitters has one or more unique factory-assigned input (loop) ID codes. Each of
the inputs requires a programming zone (e.g., a 5804's four inputs require four button zones). Transmitters can
be entered as one of the following types (see transmitter’s instructions for appropriate input type):
Type Description
"RF" (Supervised RF) Sends periodic check-in signals, as well as fault, restore, and low battery signals.
The transmitter must remain within the receiver's range.
"UR" (Unsupervised RF) Sends all the signals that the "RF" type does, but the control does not supervise the
check-in signals. The transmitter may therefore be carried off-premises.
"BR" (Unsupervised Button RF) These only send fault signals. They do not send low battery signals until they are
activated. The transmitter may be carried off-premises.
Transmitter Battery Life
• Batteries in the wireless transmitters may last from 4–7 years, depending on the environment, usage,
and the specific wireless device being used. Factors such as humidity, high or low temperatures, as well
as large swings in temperature may all reduce the actual battery life in a given installation. The wireless
system can identify a true low battery situation, thus allowing the dealer or user of the system time to
arrange a change of battery and maintain protection for that point within the system.
- 13 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 14 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
LOOP 1 LOOP 1
(LOW (LOW
SENSITIVITY SENSITIVITY
LOOP 3 LOOP 3
LOOP 2
LOOP 4 LOOP 4
YOU MUST ON LOOP 4
YOU MUST OFF
LOOP 2 YOU MUST
ENROLL LOOP 2 ENROLL
LOOP 1 THIS LOOP 1 ENROLL
THIS THIS BUTTON
BUTTON LOOP 1 LOOP 1 BUTTON
LOOP
3 ••
•
LOOP 1
•• •••
•
••• • •
••
• ••
LOOP 2
(REED)
ON LOOP 2
1
OF
F (REED)
2
LOOP 1 LOOP 1
LOOP 1 (TERMINALS) LOOP 1
3
4 (TERMINALS)
LOOP 1 ALTERNATE
POSITION
FOR LOOP 2
5805-6 5806/5806W3/5807 5809 5811 5814 5816 5816MN
ENROLL AS "BR" 5808/5808LST/5808W3 ENROLL AS "RF" ENROLL AS "RF" ENROLL ENROLL AS "RF" ENROLL AS "RF"
ENROLL AS "RF" AS "RF"
LOOP 1 LOOP 2
(PRIMARY) (REED) LOOP 2
(REED)
AR
ME
LOOP 2
D
LOOP 3 RE
AD
Y
(AUX. (TERMINALS)
MIC
MESS
(TEMP LOOP 1
LOOP 3 (TERMINALS) LOOP 1
SENSOR)
(AUX. (INTERNAL
RIGHT) LOOP 1 SHOCK
(TERMINALS) SENSOR
5816TEMP 5817 5818 5819 5819S (WHS & BRS) 5820/5820L 5821 5828/5828V
ENROLL AS "RF" ENROLL AS "RF" ENROLL AS "RF" ENROLL AS "RF" ENROLL AS "RF" ENROLL AS "RF" ENROLL AS "RF" P RO G R A M
HOUSE ID
SERIAL #1 LOOP 1
LOOP 1 LOOP 3 (MOTION)
(HIGH AW
AY SERIAL #1
SECURITY) SERIAL #1 ST
AY LOOP 2
LOOP 1 LOOP 4 1
(SOUND) LOOP 2 2
SERIAL #1
(STANDARD SERIAL #2 3
4 LOOP 1
SECURITY) LOOP 3
(G
ree
(R n)
ed
(Yell
)
SERIAL #2
LOOP 3 (TILT MODE)
ow
)
LOOP 2
5849 5850 (GBD) 5853 5870API LOOP 4 (TAMPER) 5878 5890/5890PI
ENROLL AS "RF" ENROLL AS "RF" ENROLL AS "RF" ENROLL AS "RF" ENROLL AS "BR" ENROLL AS "RF"
5800-002-V0
5894PI 5897
ENROLL AS "RF" ENROLL AS "RF"
Notes: (1) Loop 4 must be enrolled on the 5801, 5804, 5804BD, 5804BDV and 5804E transmitters, whether or not the
loop is used.
(2) 5804E encrypted (High-Security) devices must be activated while the system is in Go/No Go Test Mode. Refer
to the transmitter’s installation instructions for complete details. The system will confirm enrollment of the
encrypted device by beeping two times.
(3) The 5806W3 smoke detector must be used in SIA applications.
The 5800PIR, 5800PIR-RES, 5800PIR-COM, 5800PIR-OD, 5800RL, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV,
UL 5804E, 5811, 5814, 5816TEMP, 5819, 5819S(WHS & BRS), 5828/5828V, 5850(GBD) and 5870APIwireless
transmitters have not been evaluated by UL.
- 15 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
Mechanics of Programming
General Programming Information
Programming options are stored in non-removable, electrically erasable, nonvolatile EEROM memory. The
system can be programmed at any time, even at the installer's premises prior to the actual installation.
Simply apply power temporarily to the Control and then program the unit as desired. There are four
programming modes:
• Data field programming (used for setting various system options).
• Interactive menu mode programming (used for programming zone information, programming
Powerline Carrier Devices, and for entering transmitter serial numbers).
• Voice Prompt programming (used for setting various system options).
The system can also be programmed remotely, using an IBM PC compatible Personal Computer, and
Compass Downloader and modem or via capable GSM or IP communications modules. See the Remote
Programming/Control (Downloading) section.
Note: You may find it convenient to adjust the volume setting before entering the Program Mode. This will allow you to
clearly hear the feedback announcements or system beeps in the Programming Mode, of the system’s built-in
speaker. To adjust the volume, press FUNCTION + VOLUME+ [3] or [6]. Upon exiting the Program Mode, the
system will reset the volume to the default value (mid level).
If a different Installer Code has been programmed, use that code to enter the Programming mode.
3. Upon entering programming mode, the control will initially display “Entering Programming Mode”.
4. Once you have entered the Program mode, data field “20 INSTALLER CODE” (the first data field in
the system) will be displayed and both keypad LEDs will flash. If you have entered the Voice Prompt
Programming mode. “Pro” will be displayed and the system will announce “Programming, use arrows
to scroll choices. Press select to accept, press escape to quit”.
- 16 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
Mechanics of Programming
Interactive Menu Mode Programming (✻56, ✻80, ✻81, ✻83, ✻84, ✻85)
Press [✻] + interactive mode No. (i.e., ✻56). The keypad will display the first of a series of prompts. A detailed
procedure (with displays of prompts) is provided in later sections of this manual.
✻56 Enhanced Zone Programming Mode
Interactive menu mode used for programming zone attributes and report codes. Refer to the ✻56
Enhanced Zone Programming Mode section for procedure.
✻80 Device Programming Menu Mode
Interactive menu mode for programming Powerline Carrier Devices. Refer to the ✻80 Device
Programming Menu Mode section for detailed procedure.
✻81 Zone Lists Menu Mode
Interactive menu mode for programming zone lists for Powerline Carrier Devices. Refer to the ✻81
Zone List Menu Mode section for detailed procedure.
✻83 Enhanced Sequential Mode
Interactive menu mode used to enter RF transmitter serial numbers. Refer to the ✻83 Enhanced
Sequential Mode section for detailed procedure.
✻84 Assign Zone Voice Descriptors
Interactive menu mode used to assign descriptors to each zone. These descriptors will be announced
whenever the system announces an event involving a zone.
✻85 Record Custom Voice Descriptors
Interactive menu mode used to record custom descriptors for use with each zone.
✻96 Initialize Download ID and Subscriber Account Number for Downloading
Entering ✻96 resets all subscriber account numbers and CSID in preparation for an initial download.
Loading Factory Defaults
If a default table is loaded, any data that has already been programmed into the system will be changed
according to the default table selected!
✻97 To load the factory defaults, enter ✻97, then press number 1, 2, 3, or 4 to select from default tables 1-4,
or press “0” if you are not selecting a default table. Refer to the Programming Default Tables section of this
manual to view the tables.
Exiting Program Mode
Do not exit Program Mode via *98 if you intend to enter LRR Communication Device Diagnostic Mode.
✻98 Exits program mode and inhibits re-entry into the Expert or Voice Prompt Programming modes using
the Installer Code.
✻99 Exits program mode but allows re-entry into the Expert Program mode using Installer Code (4112) +
800 or into the Voice Prompt Programming mode using Installer Code (4112) + 888.
Note: After exiting program mode (or upon power-up), the system takes up to a minute to reset. To bypass the reset
delay, press [#] + [0].
- 17 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 18 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
ZT16 is only available on the LynxSIA Plus version of the control panel.
Type 16 Zone type 16 can be assigned to any wireless zone. It can not be used with heat detectors,
Supervised Fire combination heat/smoke detectors, wireless sensors or fire pull stations. This zone type is always
with Verification active and can not be bypassed.
Zone Characteristics:
• Provides a fire alarm when zone is alarmed, but only after the alarm has been verified.
• System verifies alarm by delaying reporting and control panel alarm sounding for 30 seconds
after alarm is detected. If the zone remains faulted after 30 seconds a fire alarm is provided. If
any other fire zone is faulted during the 30 second delay window a fire alarm is immediately
provided for that zone. An alarm for original fire zone will also be provided if that zone is still
faulted afterward. If there are no fire alarms after the 30 second delay expires, the system will
open a 60 second window. If any fire zone is faulted during that window a fire alarm will
immediately be provided for that zone.
• Bell output will pulse following alarm verification
Type 20 Zone type 20 is a special-purpose zone type used with 5800 Series wireless pushbutton units.
Arm–Stay Zone Characteristics:
• Exit delay regardless of the arming mode selected.
• System is armed in the STAY mode when the zone is activated.
• Zone number is sent to the central station as a user number when arming or disarming.
Type 21 Zone type 21 is a special-purpose zone type used with 5800 Series wireless pushbutton units.
Arm–Away Zone Characteristics:
• System is armed in the AWAY mode when the zone is activated.
• Zone number is sent to the central station as a user number when arming or disarming.
Type 22 Zone type 22 is a special-purpose zone type used with 5800 series wireless pushbutton.
Disarm Zone Characteristics:
• Disarms the system when the zone is activated.
Type 23 Zone type 23 can be used on a zone when a Powerline Carrier Device (e.g., X10) action is desired,
No Alarm but with no accompanying alarm (e.g., front door light).
Response
Type 24 Zone type 24 is usually assigned sensors or contacts on exterior doors and windows where bells
Silent Burglary and/or sirens are NOT desired.
Zone Characteristics:
• Instant alarm, with NO audible indication when is armed in the AWAY, STAY, STAY NO
DELAY, or AWAY NO DELAY mode.
• Report sent to the central station.
Note: The Keypad beeps if the zone is faulted when system is disarmed and Chime mode is on.
- 19 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
Installer Code
20 The Installer Code is used to enter the 4-digit Master Security Code. See "Master Code"
INSTALLER CODE in the System Operation section for procedure.
Note: LynxSIA Plus does not allow duplication of Installer code. If a duplicate code is
entered the entry is rejected and LYNX issues single long beep indicating rejection.
The old installer code remains unchanged.
SELECTIONS
Enter 4 digits (0-9)
Quick Arm Enable
21 If enabled, security code is not required to arm the system. The user simply presses and
QUICK ARM ENABLE holds down the AWAY or STAY key to arm.
SELECTIONS
0 = do not allow quick arm
1 = allow quick arm
Keypad Backlight Timeout
22 This option allows the choice of either always backlighting the keypad or turning the
KEYP
EYPAD BACKLIGHT
ACKLIGHT backlighting off after 10 seconds of keypad inactivity.
SELECTIONS
0 = no timeout; always backlight keys
1 = turn backlighting off after inactivity
Forced Bypass
23 All zones bypassed by this function will be displayed after the bypass is initiated.
FORCED BYPASS UL installations: must be 0 (no forced bypass)
SELECTIONS
0 = no forced bypass
1 = provide automatic bypass of all open (faulted) zones
RF House ID Code
24 The House ID identifies receivers and wireless keypads. If a 5804BD/5804BDV
RF HOUSE ID CODE Transmitter is to be used, a House ID Code MUST be entered, and the keypad should
be set to the same ID.
SELECTIONS
00 = disable all wireless keypad usage
01-31 = House ID
- 20 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 21 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 22 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 23 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 24 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
All four digits of the Subscriber Account number must be entered in Fields ✻43 and ✻44. If ten-digit format is
selected in ✻48 (option 5), all ten digits of the Subscriber Account number must be entered.
Field ✻46: Enter up to 24 digits. Do not fill unused spaces. Enter 0-9, #+11 for ‘✻’; #+12 for’#’; #+13 for a
pause (2 seconds).
“Follow Me Reminder” Phone Number
46 This option allows the user to schedule a time driven message. When activated the
FOLLOW ME PHONE# system will dial the phone number programmed and deliver a voice message (custom
words 72, 73 and 74). This option is only supported when the follow me feature is
enabled in field ✻49 (option 6-9 or 10-13).
If using the Follow Me Reminder feature, enter the phone number here. If fewer than
24 digits are entered, exit by pressing [✻]. To clear entries from the field press ✻46✻.
The telephone message can be terminated (acknowledged) by pressing any key on the
telephone keypad. Pressing any key on the local Lynx Plus Series keypad will terminate
(acknowledge) both the follow me and the local reminder announcements.
Note: The follow me reminder announcement will be terminated if any other event requires
the system to dial out or if an audible alarm has occurred.
SELECTIONS
Enter up to 24 digits.
- 25 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 26 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
Split/Dual Reporting
49
This field is used to select a reporting option as follows:
SPLIT/DUAL REP Enter: 0 - 5 when reporting to telephone receivers.
6 - 9 when reporting to a pager is desired
10 - 13 when reporting to an aux telephone receiver.
Note: If you are installing a communications module that has voice communications
capability (i.e.; GSMVL), refer to Field ✻55 notes for additional information.
Pager Report Format
Options 6-9 send reports to the primary phone number, in a format defined in Field
✻48, and send reports to a pager, which has its phone number entered as the secondary
phone number in Field ✻42. The pager report is a 7-digit code, with optional 16-digit
prefix. For an explanation of the pager format, refer to the User Guide.
Follow Me System Report Format
Options 10-13 send reports to the primary phone number, in a format defined in Field
✻48, and sends voice message to the secondary phone number entered in Field ✻42.
The message is a repeatable system status announcement. If the manual paging option
has been programmed in Field ✻87, the message will repeat “system, system…..”. The
message can be terminated by pressing any key on the telephone keypad.
To Primary To Secondary
0 = All reports None, unless primary fails, then all
1 = Alarms, Restore, Cancel* Others
2 = All except Open/Close, Test Open/Close, Test
3 = Alarms, Restore, Cancel All
4 = All except Open/Close, Test All
5 = All reports All
To Primary To Paging Number
6= All reports except Open/Close Alarms, Open/Close ‡, Troubles
7= All reports Alarms, Troubles
8= All reports Alarms, Open/Close ‡, Troubles
9= All reports except Open/Close Open/Close ‡,
To Primary To Follow Me System Phone Number
10= All reports except Open/Close Alarms, Open/Close ‡, Troubles
11 = All reports Alarms, Troubles
12= All reports Alarms, Open/Close ‡, Troubles
13= All reports except Open/Close Open/Close ‡
*Recent close report is sent to primary number (LynxSIA Plus only)
‡ Will report Users 0, 5-8, and, if using wireless button-type devices, will report the zone number of the
arm or disarm button 26-33. All other zones and users are not reported.
- 27 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 28 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
Field ✻55: If AAV is enabled in ✻91, depending on Communication Channels programmed in ✻55, only the Reporting
options from the table below are available. They should be programmed as described in Dynamic Signaling (field ✻77). If
AAV is disabled in field ✻91, reporting option 5 is not available.
If Follow Me System of Pager features are selected, AAV will not be available even if enabled in ✻91 UNLESS
option 5 is selected in ✻55 (Radio only). If option 5 is selected in ✻55, AAV will be established on the primary
channel because Follow me System and Pager are not available on the radio’s audio channel.
The following table shows the only valid combinations of communication channels and reporting options. It is the
responsibility of the installer to ensure that a valid combination is programmed.
AAV
Reporting Option Enabled? ✻55 Communication Channel
Primary Phone only Y/N 0 = Telco Line only (no radio) (see Note 1)
Redundant reports to both channels Y/N 1 = LRR/IP (Digital Communication only) and Telco Line (see Note 1)
Primary Phone is the preferred channel Y/N 1 = LRR/IP (Digital Communication only) and Telco Line (see Note 1)
LRR/IP is the preferred channel Y/N 1 = LRR/IP (Digital Communication only) and Telco Line (see Note 1)
LRR/IP Only N 3 = LRR/IP (Digital Communication only) (no Telco Line) (see Notes 2 & 3)
Y 5 = LRR/IP (Digital Communication w/AAV) (Telco Line connections for 2-way
voice session only, if applicable) (see Notes 2, 3, 4)
NOTES
1. AAV mode can be established only on Telco Line.
2. Follow me System and Follow me Reminder and Pager features are not supported. These features will not work if
selected in ✻49.
3. Speaker Phone and Remote Phone Access are not available. These features should be disabled in ✻47 and ✻91.
Download over the Phone Line feature is also unavailable.
4. AAV mode can be established only on LRR/IP (Digital Communication with AAV Capabilities)
Legend
LRR/IP (Digital Communication only) = Digital GSM Communication Channel
LRR/IP (Digital Communication with AAV) = GSM Communication Channel with voice capabilities (a radio with voice capabilities is required
to use the voice capabilities)
Telco Line = Land Phone Line
Reporting Channels
55 This option is used to enable/disable Central Station reporting via the LRR/IP
REPORT CHANNELS Communications Device (See Field ✻77). Upload/ download via the Internet IP module
is not affected by this entry. The option specifies the channel that the control will use
when sending reports to the Central Station (Follow Me Phone and Pager). Select some
or all channels as required.
IMPORTANT NOTE: Make sure that selected channels are physically available and
functional.
SELECTIONS
0 = Telco Line (no Radio)
1 = LRR/IP(Digital Communication only) and Telco Line
3 = LRR/IP (Digital Communication only) (no Telco Line)
5 = LRR/IP (Digital Communication with AAV) (Telco Line Connections for 2-way voice
session only, if applicable)
- 29 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 30 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
For the LynxSIA Plus control, the ✻59 Exit Error Report Code and ✻68 Cancel Report Code options are
always enabled. A report code can be entered if reporting formats other than Contact ID ® are used.
- 31 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
To ensure that the Lynx Plus Series properly transmits its reports to the Central Station via the proper channel you must
program a Primary Phone Number in Field ✻41 and/or activate/deactivate the LRR/IP Communications Module in Field ✻55.
The 15-Second Dialer Delay (Burglary), programmed in Field in ✻50 is independent of the delay selected in Field ✻77 and
applies to both telephone and communications device.
- 33 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 34 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 35 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 36 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 37 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
Zone Number
A01 Enter the 2-digit zone number to be programmed and the Voice Descriptor for the selected
ZONE NUMBER zone number will be announced, if it is programmed. Press [✻] to advance to the next
field. Pressing 00 exits mode, upon which the prompt “56” blinks, indicating the mode is
inactive. Press [✻] + any field number to go to that field.
SELECTIONS
00 = Exit Zone Programming 26-41 = Button zones (only)
01 = Hardwire Zone 92 = Duress
02-25 = RF zones (only) 95, 96, 99 = Panic zones
Zone Type
b Each zone must be assigned to a 2-digit zone type, which defines the way in which the
ZONE TYPE system responds to faults in that zone. Press [✻] to advance to the next field or [#] to
return to previous prompt.
Notes: (1) ZT16 is only available on the LynxSIA Plus version
(2) ZT16 is not for use with manually actuated devices including fire, keypad or key
fob zones, or fire pull stations, or for heat detectors.
(3) If 00 is accepted as a zone type, save the 00 zone type and advance to the
confirm delete prompt (F).
SIA ZT 16 must be used in SIA fire applications.
SELECTIONS
00 = Not Used 09 = Fire without verification
01 = Entry/Exit #1 10 = Interior w/Delay
02 = Entry/Exit #2 14 = Carbon Monoxide
03 = Perimeter 16 = Fire with verification
04 = Interior Follower 20 = Arm–Stay
05 = Trouble Day/Alarm Night 21 = Arm–Away
06 = 24 Hr Silent 22 = Disarm
07 = 24 Hr Audible 23 = No Alarm Response
08 = 24 Hr Aux 24 = Silent Burglary
-
Report Code
C Enter the report code for this zone. The report code consists of 2 hexadecimal digits, each
REPORT CODE in turn consisting of 2 numerical digits. For example, for a report code of "3C", enter
[0][3] for "3" and [1][2] for "C". If this is Zone 95, 96 or 99, the system skips to the VOICE
DESCRIPTOR prompt (1C). Press [✻] to advance to the next field or [#] to return to
previous prompt.
Note: If “00” is entered as the first digit, there will be no report for that zone.
SELECTIONS
00-09 = 0-9 12 = C 14 = E
10 = A 13 = D 15 = F
11 = B
- 38 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 39 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 40 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
Descriptor 2
IE
This prompt is used to enter a Voice Descriptor. Enter [#] + 2-digit vocabulary index
number † of second descriptor word for this zone. Use the [6] or [8] key to advance to
Note: System displays 2- descriptor 2 or to next zone. To change the entered index number before pressing [6] or
digit selection & [8], simply press [#] + desired 2-digit vocabulary index number. If descriptor 2 is not
alpha descriptor OR desired, enter [#] + 99 (blank), then press [8] to return to zone number prompt.
99 “No selection” † see ✻84 Assign Zone Voice Descriptors section for vocabulary index
SELECTIONS
Enter [#] + 2-digit vocabulary index number † of first descriptor word for this zone.
6 = accept word and advance to descriptor 2 (descriptor 2 will be announced)
8 = accept word and advance to next zone (prompt A) – entire zone descriptor will be announced
Press any other key to repeat the selected word
- 41 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 42 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 43 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
ZT16 is only available on the LynxSIA Plus version of the control panel.
- 44 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 45 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 46 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 47 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 48 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
Zone Number
A02
A02 Enter the 2-digit zone number of the first transmitter to have its serial number entered.
ZONE NUMBER The system will announce the Voice Descriptor for the selected zone number, if it is
programmed.
Press [✻] to continue. Starting with this zone number, the system will search for the first
transmitter that has all of the following attributes pre-programmed in ✻56 ENHANCED
ZONE PROGRAMMING:
a) The appropriate input type was selected in ✻56 (RF, UR, or BR programmed)
b) The appropriate loop number was selected in ✻56.
c) No serial number has been programmed
d) Zone type
If the first zone number entered does not have one or more of the above attributes, the
system will search its database for the first zone that does, and will display it at the
enroll SERIAL NUMBER prompt (1b).
Enter 00 to exit. Prompt “83” blinks, indicating the mode is inactive.
Note: Two exceptions to the requirement above exist for keys. Four zone button type
devices (zone numbers 26, 30, 34, and 38) will be stopped only if there are no serial
numbers enrolled in all 4 zones of the key, regardless of the attributes that have been
entered. In addition, zone types are not required to be present. In this case, 1A,
Option 4 must be selected prior to “Learn”.
SELECTIONS
Enter 2-digit zone number.
[✻] = continue; system searches for zones not yet entered (for zones 2 through 25 a zone
type must be entered), then advances to ENROLL SERIAL NUMBER prompt “1b”
00 = exit Sequential mode
- 49 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 50 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
Note: In Enhanced Sequential Learn Mode, 4 button type keys will always be learned simultaneously. They will be stopped at
the 4 button boundaries of 26, 30, 34 and 38, provided the zone is free of a serial number. If the first zone of the key
has a serial number learned, the remaining keys cannot be programmed in sequential learn mode. In addition, if the
zone has not been set up (duplicate loop, missing zone type, etc.) only entries 0 (skip to the next zone) and 4 (copy
the key template) will be allowed.
- 51 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 52 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
Notes: (1) If button type device is used to Arm Away, Arm Stay, and disarm the system it is recommended to assign
“Check” and “Zones” voice descriptors to each of the three zones. This will allow the system to announce
“Check Zones” “Low Battery” if the button device has a low battery.
(2) If a Wireless Keypad is being installed along with this system, not all the voice descriptors shown on this list can
be announced by keypad. (Refer to the Wireless Keypad documentation for further information).
- 53 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 54 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
Multiple security levels protect remote programming against compromise by attempts to defeat the system.
1. Security Code Handshake: An 8-digit download ID code must be matched between the Control and
downloader.
2. Site-Initiated Remote Programming: The installer or subscriber initiates the call from the subscriber
premises by entering the Installer Code + # + 1, while the system is disarmed. All parameters can then be
downloaded via the phone lines using a personal computer.
3. Station-Initiated Remote Programming: The operator calls the site from your office to initiate the
download call. The Control hangs up and then calls back the PC via the preprogrammed telephone
number. The unit can then be uploaded, downloaded, or controlled from your office.
4. Telco Handoff: The installer or subscriber performs a download session on the call initiated from the
site or from local laptop computer by entering the Installer or Master Code + # + 1 at the control panel.
5. Data Encryption: Data passed between the PC and the Control is encrypted for security so that it is
very difficult for a foreign device tapped into the phone line to take over communication and substitute
system-compromising information.
Equipment required to download to a system at the premises
• An IBM PC compatible computer and appropriate interconnecting cables.
• Either a HAYES brand SMARTMODEM 1200 (Level 1.2 or higher external or Level 1.1 or higher [with 4
position DIP switch] internal style), a HAYES brand Optima 336 external, a HAYES brand Optima 24
Plus FAX96, or an Ademco CIA Modem or via a capable GSM or IP communications device.
• Compass Downloader for Windows (at revision level supporting Lynx Plus Series).
Initial Download: Enter Installer Code + # + 5. This sets field ✻95 to 4 rings, and system to “no call-back”
option. The download computer can then call the subscriber, make connection, and download all
programming data.
Flexible Callback: If enabled in field ✻93, the download operator can temporarily change the last 1, 2, or 3
digits (depending on selection) of the call back number. This allows the control to call back a computer other
than the one programmed, which may be helpful at times of high computer traffic. Refer to 93 Flexible
Callback programming field for additional information.
Remote Programming Information
If using Remote Programming, the Lynx Plus Series must be connected to the telephone line or to the
Internet, as applicable.
The downloading system can perform many functions when in communication with the Control. Besides
uploading and downloading, the status of the system can be observed and various commands can be
initiated, as follows:
• Arm the system in the away mode; disarm the system.
• Bypass a zone.
• Force the system to accept a new program download.
• Shut down communication functions (for nonpayment of monitoring fees in an owned system).
• Shut down all security system functions (for nonpayment for a leased system).
• Inhibit local keypad programming (prevents account takeover).
• Command the system to upload a copy of its resident program to the office.
• Set the time
• View/Modify
• X10/ Scheduling
- 55 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 56 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
System Operation
Keypad Operation
The keypad allows the user to arm and disarm the system, and perform other system functions, such as
bypassing zones. Zone and system conditions (ALARM, trouble, bypass) are displayed on the keypad. When
an alarm occurs, keypad sounding and external sounding will occur, and the zone(s) in alarm will be
displayed on the keypad. Pressing any key will silence the keypad sounder for 10 seconds (only once).
Disarming the system will silence both keypad and external sounders. When the system is disarmed, any
zones that were in an alarm condition during the armed period will be displayed (memory of alarm). To
clear this display, simply repeat the disarm sequence by entering the Security Code and pressing the OFF
key. The keypad also features chime annunciation, and 3 panic key pairs for silent, audible, fire or personal
emergency alarms. These keys can notify the central station of an alarm condition, if that service is
connected.
Panic Keys
There are three panic key pairs that, if programmed, can be used to manually initiate alarms and send a
report to the central station. Each can be individually programmed for 24-hour silent, audible, personal or
fire emergency responses. The panic function is activated when both keys of the appropriate key pair are
pressed at the same time. The panic functions are identified by the system as follows:
Keys Displayed as Zone
[1] & [✻] 95 Important: For the silent panic functions
to be of practical value, the system must be
[✻] & [#] 99 connected to a central station.
[3] & [#] 96
Security Codes
Installer Code
The installer programs the 4-digit Installer Code initially as part of the programming procedure. The
factory default Installer Code is 4-1-1-2, but may be changed in field ✻20. The Installer Code is the
only code that allows entry into Programming mode and also, in normal operation mode, is used to
enter the Master Code, which allows access to the normal functions of the system.
Master Code
In normal operation mode, the Installer Code is used to enter the 4-digit Master Security Code.
Enter/change the Master code by installer.
At the keypad enter: Installer Code + [CODE key] + [02] + desired 4-digit Master Code
Change the Master code by master user.
At the keypad enter: Current Master Code + [CODE key] + [02] + new Master Code + new Master Code
again
Secondary User Codes
In normal operation mode, the Master Security Code can be used to assign up to 6 secondary 4-digit security
codes, including a Babysitter Code and a Duress Code. The Master Code can also be used to remove
secondary codes from the system (individually).
Assign (or change) a secondary security code.
At the keypad enter: Master Code + [CODE key] + User # (03–08) + desired Secondary Code
The system will emit a single beep when each secondary code has been successfully entered.
Delete a secondary security code.
At the keypad enter: Master Code + [CODE key] + User # (03–08)
- 57 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
System Operation
Security Code Notes
• The Master and Secondary security codes permit access to the system for arming, disarming, etc.
• The Installer Code can disarm the system only if it was used to arm it. In addition, the Installer Code cannot
disarm the system if it was armed by pressing and holding a Quick-Arm button.
• The Babysitter Code (User Code No. 7) can disarm the system only if it was used to arm it. In addition, the
Babysitter Code cannot disarm the system if it was armed by pressing and holding a Quick-Arm button.
• Duress code (User Code No. 8) sends a special code to the monitoring station when used to perform any system
operation. Instruct users to be careful not to use this code for normal usage. If the duress code is programmed, you
must enter a report code for Zone 92 (duress).
• If a secondary code is inadvertently repeated for different users, the lower user number will take priority.
• Opening/closing reports are sent for the Installer Code as No. 01, with the appropriate subscriber number. Master
Code and set of secondary user codes are sent as Nos. 02 and 03–08, respectively, in Contact ID® format (with the
appropriate user number); in 4 + 2, it is 1–8. Quick arming (and open/close executed by downloader) is reported as
user 00.
- 58 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
System Operation
Exit Error Alarm Displays
The system will display the following if programmed in Field *59. Entering a second Code + OFF sequence will
clear the display.
Display Meaning
Appears along with a zone indication if an exit or interior zone contained a fault during
CA
closing at the time the exit delay ended (e.g., exit door left open), but the system was
Alarm Cancelled
disarmed during the entry delay time. The alarm sounder and keypad sound
continuously, but stop when the system is disarmed. No message will be transmitted to the
central station.
Appears along with a zone indication if an exit or interior zone contained a fault during
EA
closing when the exit delay ended, but the system was NOT disarmed during the entry
Exit Error
delay time. The alarm sounder and keypad sound continuously until the system is disarmed
(or timeout occurs). An Exit Alarm message is sent to the central station. OR if an alarm
from an exit or interior zone occurs within two minutes after the end of an exit delay
System Displays
Display Meaning
Remote Phone Control feature is active (Appears in place of the clock).
PC
Remote Phone
System Speaker Phone mode is active (Appears in place of the clock).
PH
Speakerphone
Displayed when an invalid entry is made.
EE
Invalid Entry
Displayed when programming a Follow Me Phone Number.
Phn
Follow Me Phone#
EE Data entry error (invalid field number entered while programming. Re-enter a valid field
Invalid Entry number).
d1 Displayed approximately 4 seconds after power-up. After approximately 1 minute* the green
StandBy “READY” LED should light and the real-time clock will appear. If the “d1” remains displayed
for more than 1 minute, the system is disabled.
*To bypass the 1-minute delay, press [#] + [0].
Important: Do not try to bypass 1minute delay before “d1” is displayed!
FC Appears when a communication failure has occurred. This message clears only when the
Comm Fail system is subsequently armed.
90 Appears when the system has detected an RF jamming condition or excessive interference.
RF Jam
- 59 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
System Operation
The following words or phrases define conditions on specific zones or individually displayed system status
conditions.
Display Meaning
Fault A malfunction is discovered in the system; or an open is detected in a fire zone; or a fault
in a day/night burglary zone is discovered during a disarmed period. Accompanied by a
display of the zone number in trouble. The fault condition may also be caused by some
change in the environment that prevents the built-in receiver from receiving signals from
a particular wireless sensor.
After correcting the problem, the display can be cleared by entering the security code plus
the OFF key twice.
Fault 103 Indicates one of the following:
• control panel lost communication with the communications module
• communications module tamper detected (cover removed)
• primary communications path failure
• radio is not registered; account not activated
• primary power loss
• secondary communications path failure
• battery charger failure
• low battery
ALARM System is armed and an intrusion has been detected (also appears during a Fire Alarm or
audible emergency alarm). Accompanied by the protection zone that is in alarm.
FIRE A Fire Alarm or Fire Fault is present. Accompanied by a display of the zone that
is in alarm
CO Displayed when a Carbon Monoxide Alarm or Fault is present.
No AC AC power is not present. If displayed, the system is operating on backup battery power.
Stay Perimeter Burglary zones, such as protected windows and doors, are armed
Away All burglary zones, interior and perimeter, are armed.
StayInst or AwayInst Entry delay is turned off.
Bypass One or more burglary protection zones have been bypassed.
Chime Chime feature is active (displayed only when the system is disarmed)
Lowbat Displayed with no zone number indicates that the system’s backup battery is weak.
Displayed with a zone number and a once-per-45 seconds “beeping” at the keypad indicates
that a low battery condition exists in the wireless sensor displayed (zone “00” indicates a
wireless button/keypad). If the battery is not replaced within 30 days, a “FAULT” display
may occur.
Msg A message has been recorded and has not yet been played back.
Rec The system is in Recording mode.
Test in Progress System is in Test mode.
4 Hr End of Test LynxSIA Plus Only – Displayed during the final five minutes of the system test.
Ready or NotReady System status displayed only when the system is disarmed
Exit Now System has been armed and the exit delay is active
bF Indicates Communications Module failure (displayed on RF Keypad only)
- 60 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
System Operation
UL Audio alarm verification has not been evaluated by UL.
The Lynx Plus Series sends the “alarm message” followed by a “Listen-in-to-Follow message” (Contact ID®
code 606) to the Central Station. The Listen-in-to-Follow message causes the Central Station’s digital
receiver to temporarily hold the phone line for approximately 1-minute. When the Lynx Plus Series receives
the “kissoff” from the central station, indicating that the alarm message has been received, the Two-Way
Voice (AAV) feature is activated in the (default) “Listen Mode” and sirens and keypad sounds are
discontinued. The Lynx Plus Series transmits a beep acknowledgment to the Central Station, once per
second. The beep alternates between two tones and indicates that the Lynx Plus Series is waiting for a
session command from the Central Station operator. Once a command is issued the beep acknowledgement
is discontinued, however, if a command is not issued within two minutes the system will “time out” and the
call will be terminated.
Operator Commands
The Central Station operator begins the session, which last 5 minutes, by entering one of the valid AAV
commands shown in the table below. The session may be extended 5 minutes, without changing the
operating mode, by pressing the [7] key on the touch-tone phone. Selecting another operating mode also
resets the session an additional 5 minutes. During the last minute of the 5 minute, session, the Lynx Plus
Series generates two beeps every 30 seconds to alert the Central Station operator that the session is about to
time out. The Central Station operator may then extend the session by pressing the [7] key on the touch-tone
phone. If the session is not extended the phone line is disconnected, and the session is ended. Sessions may
be ended at any time by pressing the [9] key on the touch-tone phone. The AAV modes are described as
follows:
Note: When entering AAV commands make sure the Central Station receiver has been disconnected from the
phone line, otherwise AAV commands may not go through.
Key Function
1 Talk Mode: Pressing the [1] key on the touch tone phone, enables one-way voice communication from the
central station to the violated premises, and allows the operator to talk communicate through the Lynx Plus
Series speaker. In this mode the ARMED (red) and READY (green) LEDs blink alternately.
2 VOX (Voice) Mode: Pressing the [2] key on the touch-tone phone, enables two-way voice communications
between the central station and the violated premises. In this mode the ARMED (red) and READY (green)
LEDs blink alternately.
3 Listen Mode: Pressing the [3] key on the touch-tone phone, enables one-way audio from the violated premises
to the central station. The Listen Mode is the start up default mode of the voice feature and allows the
operator to listen through the Lynx Plus Series microphone. This mode does not affect the existing LED
pattern.
- 61 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
TO THE INSTALLER
Regular maintenance and inspection (at least annually) by the installer and frequent testing by the user are vital to continuous satisfactory
operation of any alarm system.
The installer should assume the responsibility of developing and offering a regular maintenance program to the user as well as
acquainting the user with the proper operation and limitations of the alarm system and its component parts. Recommendations must be
included for a specific program of frequent testing (at least weekly) to ensure the system’s proper operation at all times.
- 62 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
System Communication
This section provides an explanation of formats this system accommodates for reporting alarms and other
system conditions to the central station. The process of a successful transmission consists of both the
method of communication between the control panel and the central station receiver, and the actual way the
information is sent and displayed at the central station.
Communication Overview
When the panel calls the central station receiver, it waits to hear a “handshake” frequency from the receiver
to confirm that the receiver is on-line and ready to receive its message. Once the panel hears the handshake
it is programmed to listen for, it sends its message. The panel then waits for a “kissoff” frequency from the
receiver acknowledging that the message was received and understood.
If the handshake frequency is not given or is not understood by the panel, the panel will not send its
message. Once the handshake frequency is received and understood by the panel, the panel will send its
message. If there is an error in the transmission (the receiver does not receive a “valid” message), the kissoff
frequency will not be given by the central station receiver.
The panel will make eight attempts to the primary telephone number and eight attempts to the secondary
telephone number (if programmed) to get a valid message through. If the panel is not successful after its
numerous attempts, the keypad will display “FC Comm Failure.” If the secondary number is a pager, “FC
Comm Failure” displays after the first 8 attempts to the primary number.
The following chart defines the (handshake/kissoff) frequencies that the panel supports, and the different
formats that can be sent for each.
FORMAT HANDSHAKE TRANSMITS DATA KISSOFF TRANSMIT TIME
Low Speed 1400Hz 1900Hz (10PPS) 1400Hz Under 15 seconds
3+1, 4+1, 4+2 (Standard report)
Sescoa/Radionics 2300Hz 1900Hz (20PPS) 2300Hz Under 10 seconds
3+1, 4+1, 4+2 (Standard report)
Express 1400–2300Hz DTMF (10 cps) 1400Hz Under 3 seconds
4+2
Contact ID® 1400–2300Hz DTMF (10 cps) 1400Hz Under 3 seconds
- 63 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
System Communication
.
ADEMCO Contact ID® Reporting takes the following format: CCCC Q EEE GG ZZZ where:
CCCC = Customer (subscriber) ID
Q = Event qualifier, where: E = new event, and R = restore
EEE = Event code (3 hex digits) (for a complete list of event codes, refer to the central office receiver manual)
GG = Always “00”
ZZZ = Zone/Contact ID® number reporting the alarm, or user number for open/close reports. System status
messages (AC Loss, Walk Test, etc.) contain zeroes in the ZZZ location.
- 64 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
Troubleshooting Guide
Trouble Conditions
The word “Fault” on the keypad’s display, accompanied by a rapid “beeping” at the keypad, indicates that
there is a trouble condition in the system. Pressing any key can silence the audible warning sound. Instruct
users to call for service immediately upon seeing any “Fault” messages.
System (including Wireless)
SYMPTOM POSSIBLE CAUSE REMEDY
1. Transmitter signal 1a. Transmitter not properly powered. 1a Check or change transmitter's battery.
not received at 1b. Transmitter is located too far from RF 1b. Move transmitter or RF receiver.
control. receiver.
1c. There is metal shielding between 1c. Check for large metal obstructions, then relocate
transmitter and RF receiver. transmitter if necessary.
1d. Transmitter is malfunctioning. 1d. Verify by activating control with another,
similar transmitter. If O.K. now, return
defective transmitter.
1e. Transmitter No. (zone) is not 1e. Verify programming.
programmed.
2. Transmitter zone 2a. Transmitter zone type (ZT) is set to 00 2a. Set ZT to a valid active zone type in field ✻56.
number appears (Not Used).
during Transmitter 2b. Transmitter battery not installed. 2b. Install proper battery.
Sniffer mode, but 2c. 5800 System transmitter not "enrolled" 2c. "Enter" unit in field ✻56 or ✻83.
does not clear. in system.
3. Low battery message
on keypad.
3a. "Low Bat" (no zone Nos.) 3a. System battery is low or missing. 3a. Replace system battery.
3b. "Low Bat" + "00". 3b. Remote RF keypad/button battery is low. 3b. Replace battery in the RF keypad.
3c. "Low Bat" + "nn". 3c. Transmitter for zone “nn” has a low 3c. Replace the battery in the displayed
battery. transmitter.
3d. Standard- or High-Capacity battery 3d. Ensure that battery is properly connected.
connected to wrong receptacle.
4. Periodic beep(s) from 4a. System is in Test mode. 4a. Enter Code + OFF to exit Test mode.
keypad. 4b. A transmitter low battery has occurred 4b. Enter Code + OFF and replace the battery.
and is displayed.
4c. A supervision fault has occurred. 4c. Check the transmitter indicated. Restore
communication to the receiver to cancel the
condition.
4d. System low battery 4d. Replace system battery
5. There is no response Put control in Test mode. If zone does not
to a transmitter in respond, try operating the tamper switch or
normal operation, another input to the transmitter.
although zone 5a. If another input causes the zone to be 5a. Delete input's serial number (not the zone), and
number clears during displayed, the wrong input was "entered" enter the proper input (see field ✻56).
Transmitter Sniffer when programming.
mode. 5b. If no response at all from this 5b. Determine which transmitter is programmed for
transmitter, this physical transmitter this zone and reprogram as necessary.
has not been entered by the system.
Transmitter Sniffer display is being
cleared by another unit programmed for
this zone.
6. Nuisance or phantom 6a. Sensors not properly installed, wired, or 6a. Check installation to see if in accordance with
alarm. monitored. established procedure.
6b. Universal transmitter (5817) 6b. Check programming switches on transmitter.
programmed wrong.
7. Intrusion alarm for 7a. Protected door or window opened while 7a. Check with all occupants of protected home.
no apparent reason. system armed.
7b. Improper user operation of exit/entry 7b. Check setting of entry and exit delays.
delays.
7c. Magnets located too far from switches, 7c. Check all openings for proper switch and
and/or doors and windows not properly magnet orientation.
aligned.
- 65 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
Troubleshooting Guide
Control
SYMPTOM POSSIBLE CAUSE REMEDY
1. “No AC” is displayed. 1a. Interrupted AC power supply. 1a. Check transformer connection and
powerline circuit breaker.
2. Digital communicator 2a. System in Test mode. 2a. Remove from Test mode.
message not being 2b. Telephone connection not secure. 2b. Check all connections.
received. 2c. Digital communicator malfunctioning. 2c. Check with a different CONTROL PANEL.
2d. Telephone number in program needs 2d. Program prefix or access code into the
prefix or access code. CONTROL PANEL.
2e. Telephone call to central monitoring 2e. System cannot work in this situation.
station requires operator assistance.
3. Does not arm 3a. Open or faulted zone(s) 3a. Check for faulted zones and make intact, or
properly. READY light use Bypass arming, if desired.
not on.
4. System doesn't
respond to keystrokes
on keypad.
4a. "CC" displayed. 4a. System is in communication with 4a. Wait until download session is finished.
downloader at central station.
4b. "d1" displayed. 4b. System has just been powered and is in 4b. Wait for initialization to finish, or bypass
its one minute initialization. this time by pressing '#' + '0.'
Smoke Detectors
SYMPTOM POSSIBLE CAUSE REMEDY
1. Detector alarms, no 1a. Dust, dirt in sensing chamber. 1a. Clean unit's sensing chamber with vacuum
apparent reason. cleaner per unit's instructions.
1b. Improper location. 1b. See unit's instructions for locations to avoid.
Relocate as necessary.
1c. Unit malfunctioning. 1c. Replace detector.
2. Detector's siren 2a. Unit not receiving required power. 2a. Check for proper installation of battery. Try new
sounds. battery.
2b. Unit malfunctioning. 2b. Replace detector.
- 66 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 67 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 68 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 69 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 70 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 71 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
- 72 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
FCC STATEMENTS
Federal Communications Commission (FCC) Part 15 Statement
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual.
Unauthorized changes or modifications could void the user's authority to operate the equipment.
Industry Canada
NOTICE: The Industry Canada Label identifies certified equipment. This certification means that the equipment meets
telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment
Technical Requirements document(s). The Department does not guarantee the equipment will operate to the user’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local
telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer
should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alterations made
by the user to this equipment, or equipment malfunctions, may give the telecommunications company to request the user to
disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal
metallic water pipe system, if present, are connected together, This precaution may be particularly important in rural areas.
Caution: Users should not attempt to make such connections themselves but should contact appropriate electric inspection
authority, or electrician, as appropriate.
- 73 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
WARNING
THE LIMITATIONS OF THIS ALARM SYSTEM
While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or
other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a
variety of reasons. For example:
• Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor or
disconnect an alarm warning device.
• Intrusion detectors (e.g., passive infrared detectors), smoke detectors, and many other sensing devices will not work
without power. Battery-operated devices will not work without batteries, with dead batteries, or if the batteries are not put
in properly. Devices powered solely by AC will not work if their AC power supply is cut off for any reason, however briefly.
• Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if the
signal path has been recently checked during a weekly test, blockage can occur if a metal object is moved into the path.
• A user may not be able to reach a panic or emergency button quickly enough.
• While smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not
activate or provide early warning for a variety of reasons in as many as 35% of all fires, according to data published by the
Federal Emergency Management Agency. Some of the reasons smoke detectors used in conjunction with this System may
not work are as follows. Smoke detectors may have been improperly installed and positioned. Smoke detectors may not
sense fires that start where smoke cannot reach the detectors, such as in chimneys, in walls, or roofs, or on the other side of
closed doors. Smoke detectors also may not sense a fire on another level of a residence or building. A second floor detector,
for example, may not sense a first floor or basement fire. Finally, smoke detectors have sensing limitations. No smoke
detector can sense every kind of fire every time. In general, detectors may not always warn about fires caused by
carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable
materials, overloaded electrical circuits, children playing with matches, or arson. Depending on the nature of the fire
and/or location of the smoke detectors, the detector, even if it operates as anticipated, may not provide sufficient warning to
allow all occupants to escape in time to prevent injury or death.
• Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their
installation manual. Passive Infrared Detectors do not provide volumetric area protection. They do create multiple beams
of protection, and intrusion can only be detected in unobstructed areas covered by those beams. They cannot detect motion
or intrusion that takes place behind walls, ceilings, floors, closed doors, glass partitions, glass doors, or windows.
Mechanical tampering, masking, painting or spraying of any material on the mirrors, windows or any part of the optical
system can reduce their detection ability. Passive Infrared Detectors sense changes in temperature; however, as the
ambient temperature of the protected area approaches the temperature range of 90° to 105°F (32° to 40°C), the detection
performance can decrease.
• Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the
other side of closed or partly open doors. If warning devices are located on a different level of the residence from the
bedrooms, then they are less likely to waken or alert people inside the bedrooms. Even persons who are awake may not
hear the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by passing
traffic. Finally, alarm warning devices, however loud, may not warn hearing-impaired people.
• Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or
temporarily out of service. Telephone lines are also subject to compromise by sophisticated intruders.
• Even if the system responds to the emergency as intended, however, occupants may have insufficient time to protect
themselves from the emergency situation. In the case of a monitored alarm system, authorities may not respond
appropriately.
• This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to
last as long as 10 years, the electronic components could fail at any time.
The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This
alarm system should be tested weekly to make sure all sensors and transmitters are working properly. The security keypad
(and remote keypad) should be tested as well.
Wireless transmitters (used in some systems) are designed to provide long battery life under normal operating conditions.
Longevity of batteries may be as much as 4 to 7 years, depending on the environment, usage, and the specific wireless device
being used. External factors such as humidity, high or low temperatures, as well as large swings in temperature, may all reduce
the actual battery life in a given installation. This wireless system, however, can identify a true low battery situation, thus
allowing time to arrange a change of battery to maintain protection for that given point within the system.
Installing an alarm system may make the owner eligible for a lower insurance rate, but an alarm system is not a substitute for
insurance. Homeowners, property owners and renters should continue to act prudently in protecting themselves and continue to
insure their lives and property.
We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and their loved ones
to learn about these developments.
- 74 -
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Lynx Plus Series Installation and Setup Guide
UL NOTICES
1. For UL Residential Burglar Alarm installations with line security, total exit delay time must
not exceed 60 seconds. For UL Burglar Alarm installations without line security, total exit
delay time must not exceed 120 seconds.
2. Periodic testing (see scheduling mode) must be at least every 24 hours.
3. Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL
installations (Aux power 500mA max.).
4. Remote downloading without an alarm company technician on-site (unattended
downloading) is not permissible for UL installations.
5. Auto-disarming is not a UL Listed feature.
6. As SIA limits for delay of alarm reporting and sounding can exceed UL limits for commercial
and residential applications, the following UL requirements per UL681 are provided:
The maximum time that a control unit shall be programmed to delay the transmission of a
signal to a remote monitoring location, or to delay the energizing of a local alarm sounding
device to permit the alarm system user to enter and disarm the system, or to arm the system
and exit shall not exceed:
a) 60 seconds for a system with standard line security or encrypted line security,
b) 120 seconds for a system without standard line security or encrypted line security, or
c) 120 seconds for a system that does not transmit an alarm signal to a remote monitoring
location.
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
- 75 -
Lynx Plus Series Installation and Setup Guide
Specifications
Lynx Plus Series Security Controls
1. Physical: 8-3/4” W x 6-3/4” H x 1-3/4” D
2. Electrical:
VOLTAGE INPUT: 9VAC from plug-in 25VA transformer.
RECHARGEABLE BACKUP BATTERY: Nickel-metal hydride battery pack rated at 7.7Vdc.
ALARM SOUNDER: Bell = 6-14VDC, 120mA max (e.g., ADEMCO’s WAVE2EX).
3. Communication:
FORMATS SUPPORTED:
ADEMCO Express, 10 characters/sec, DTMF (TouchTone) Data Tones, 1400/2300Hz ACK, 1400Hz
KISSOFF.
ADEMCO Contact ID® Reporting, 10 characters/sec., DTMF (TouchTone) Data Tones, 1400/2300Hz
ACK, 1400Hz KISSOFF.
ADEMCO Low Speed, 10 pulses/sec, 1900Hz Data Tone,
1400Hz ACK/KISSOFF.
Radionics/SESCOA, 20 pulses/sec, 1800Hz Data Tone, 2300Hz ACK/KISSOFF. Can report 0–9, B–F.
Line Seize: Double Pole
Ringer Equivalence: 0.6B
FCC Registration No.: 5GBUSA-25623-AL-E
WARRANTY INFORMATION
Fort the latest warranty information, please go to:
www.honeywell.com/security/hsc/resources/wa
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
- 76 -
Lynx Plus Series Installation and Setup Guide
– Index –
*56 Enhanced zone programming mode...............13, 17, 38 Change the master code ...........................................................57
*80 Device programming menu mode ...................... 17, 43 Chime mode ..............................................................................21
*81 Zone list menu mode ........................................... 17, 47 Chime-by-zone ....................................................................67, 69
*83 Enhanced sequential mode ......................17, 38, 40, 49 Closing report ...........................................................................23
*84 Assign zone voice descriptors.............17, 41, 42, 52, 53 Communication overview .........................................................63
*85 Record custom voice descriptors ......................... 17, 54 Confirmation of arming ding..............................................67, 69
*96 Initialize download ID and subscriber account Connecting/configuring communication modules ................9, 10
number for downloading.............................................. 17 Contact ID event codes.............................................................64
15 Second dialer delay ..........................................28, 30, 67 Contact ID format.....................................................................31
24-Hour audible alarm..................................................... 18 Contact ID reporting ..........................................................64, 76
24-Hour carbon monoxide monitor .................................. 19 Contacting technical support ...................................................76
24-Hour silent alarm ................................................. 18, 57 Custom voice descriptors....................................................17, 54
5800 Series transmitters ................................................. 13
5800RL ............................................................................. 13 D
5801.................................................................................. 13 Data encryption ........................................................................55
5802MN...................................................................... 13, 14 Data field ..................................................................................16
5802MN2.......................................................................... 14 Data field descriptions .............................................................20
5804............................................................................ 13, 14 Daylight savings time start/end.........................................67, 69
5804BD..................................................................13, 14, 20 Default master code............................................................68, 70
5804BDV ...............................................................13, 14, 20 Delete a secondary security code..............................................57
5804E ......................................................................... 13, 14 Delete zone parameters confirmation ......................................40
5806.................................................................................. 15 Desktop mounting ......................................................................6
5816.................................................................................. 13 Dip switches .............................................................................13
5817.................................................................................. 13 Disable local sounder..................................................................8
5827.................................................................................. 13 Disarm ......................................................................................19
Download phone number....................................................68, 70
A Download, initial ......................................................................55
AC loss report code ............................................................ 67, 69 Downloader...............................................................................35
AC power............................................................................ 11, 12 Duress code...............................................................................57
AC power and rechargeable backup battery ........................... 12 Dynamic signaling delay ....................................................33, 34
AC power loss........................................................................... 11 Dynamic signaling priority ......................................................33
AC restore report code ....................................................... 67, 69
Ademco express.................................................................. 27, 76 E
Ademco low speed .............................................................. 27, 76 Encrypted (high-security) devices ................................14, 15, 39
Alarm bell timeout............................................................. 67, 69 Enter/change the master code..................................................57
Alarm restore codes ........................................................... 67, 69 Entering program mode ...........................................................16
Alarm sounder ......................................................................... 76 Entry delay .........................................................................67, 69
Arm away/stay report code ................................................ 67, 69 Entry/exit burglary...................................................................18
Arm–away ................................................................................ 19 Error code 374 ..........................................................................31
Armed system test ................................................................... 62 Event log 80% full report code ...........................................68, 70
Arm–stay.................................................................................. 19 Event logging................................................................35, 68, 70
Assign (or change) a secondary security code.......................... 57 Exit alarm.................................................................................31
Assign zone voice descriptors ...................................... 52, 67, 70 Exit delay......................................................................23, 67, 69
Audible exit warning/quick exit......................................... 67, 69 Exit door ...................................................................................22
Audio alarm verification (two-way voice feature) ................... 61 Exit error alarm displays .........................................................59
Aux function/1-button paging ............................................ 68, 70 Exit error report code .........................................................67, 69
Aux key .................................................................................... 35 Exit warning.............................................................................23
Exiting program mode..............................................................17
B Expert programming ................................................................16
Babysitter code ........................................................................ 57 External sounder ......................................................................22
Backlighting............................................................................. 20 External sounder connections ....................................................8
Backup battery................................................................... 11, 12 Fault ...................................................................................60, 65
Backup reporting ..................................................................... 25
Battery life ............................................................................... 13 F
Bell ........................................................................................... 76 FC .............................................................................................63
BR....................................................................................... 13, 39 FCC statement .........................................................................73
Burglary zones ......................................................................... 21 Features......................................................................................5
Busy-standby ........................................................................... 59 Fire sounder timeout..........................................................67, 69
Button transmitters........................................................... 13, 14 First test report offset ........................................................67, 69
Button type .............................................................................. 39 Flexible callback ...........................................................55, 68, 70
Bypass ...................................................................................... 60 Follow me reminder feature.....................................................58
Bypass report code ............................................................. 67, 69 Follow me system announcement ............................................58
Bypass restore report code................................................. 67, 69 Forced bypass .....................................................................67, 69
Full line seizure..........................................................................7
C
Call waiting disable ................................................................. 24 G
Callback number...................................................................... 37 General programming information ..........................................16
Cancel report code.............................................................. 67, 69 Go/no go test .............................................................................14
Canceled alarm ........................................................................ 31
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM - 77 -
Lynx Plus Series Installation and Setup Guide
H Q
Handshake frequency .............................................................. 63 Quick arm enable ............................................................... 67, 69
Hardwired zone connections...................................................... 8 Quick exit .................................................................................23
Hayes ....................................................................................... 55
House ID .................................................................................. 20 R
House identification................................................................. 13 Radionics ..................................................................................27
Radionics/sescoa .......................................................................76
I Range........................................................................................13
Input type .......................................................................... 13, 39 Real-time clock display ...................................................... 67, 69
Installer code ................................................................57, 67, 69 Rec ............................................................................................60
Interactive menu mode programming..................................... 17 Redundant reporting/dynamic signaling delay ................. 67, 69
Interior with delay................................................................... 19 Remote phone control...............................................................58
Remote programming...............................................................55
K Remote programming/control ..................................................55
K10145WH/K10145X10........................................................... 11 Replacing the rechargeable battery .........................................12
K10145CN................................................................................ 11 Report code formats .................................................................63
Keypad backlight timeout ................................................. 67, 69 Report codes .............................................................................30
Keypad operation..................................................................... 57 Report format ..................................................................... 67, 69
Keys ......................................................................................... 13 RF .............................................................................................39
Kissoff frequency ..................................................................... 63 RF (supervised RF) ..................................................................13
RF house ID code................................................................ 67, 69
L RF transmitter low battery report code............................. 67, 69
Loading factory defaults.......................................................... 17 RF transmitter low battery restore.................................... 67, 69
Local seizure .............................................................................. 7 Ring detect count for downloading..................................... 68, 70
Long range radio and internet communication devices ............ 9
Loop and serial number........................................................... 39 S
Loop number............................................................................ 39 Scheduling ................................................................................55
Low battery report code..................................................... 67, 69 Secondary phone number................................................... 67, 69
Low battery restore report code ........................................ 67, 69 Secondary subscriber account number .............................. 67, 69
LYNXRCHKIT-HC .................................................................. 12 Secondary user codes ...............................................................57
LYNXRCHKIT-SC................................................................... 12 Security code handshake..........................................................55
LYNXRCHKIT-SHA................................................................ 12 Security codes..................................................................... 20, 57
Serial number............................................................... 17, 38, 40
M Sescoa/radionics select ....................................................... 67, 69
Macro function ......................................................................... 35 SH10A ......................................................................................44
Master code.............................................................................. 57 Silent burglary .........................................................................19
Master security code................................................................ 20 Single alarm sounding per zone......................................... 67, 69
Memory of alarm ..................................................................... 57 Siren/horn.................................................................................44
Message.................................................................................... 60 Site-initiated remote programming .........................................55
Smartmodem 1200 ...................................................................55
N Sniffer mode ................................................................. 14, 62, 65
No alarm response ................................................................... 19 Split/dual reporting............................................................ 67, 69
Number of reports in armed period......................................... 68 Start by zone type ....................................................................43
Station-initiated remote programming....................................55
O Supervised fire .........................................................................19
Open report code................................................................ 67, 69 Supervised fire with verification..............................................19
Operator commands ................................................................ 61 Supervised RF .................................................................... 13, 39
Optima 24 plus fax96 modem.................................................. 55 System battery .........................................................................65
System communication ............................................................63
P System displays........................................................................59
PABX access code .........................................................24, 67, 69 System features..........................................................................5
Pager characters ................................................................ 68, 70 System operation.......................................................... 43, 57, 72
Pager message ......................................................................... 35 System words ...........................................................................53
Pager report format ................................................................. 27
Paging feature ......................................................................... 35 T
Panic keys ................................................................................ 57 Technical support.....................................................................76
Perimeter burglary .................................................................. 18 Telco handoff ............................................................................55
Periodic test report ............................................................ 67, 69 Temporal pulse.........................................................................21
Phone system select........................................................... 67, 69 Test mode ..................................................................... 62, 65, 66
Plug-in transformer ................................................................. 11 Test report code.................................................................. 67, 69
Power up in previous state ................................................ 67, 69 Test restore report code...................................................... 67, 69
Powerline carrier device .........................................21, 43, 67, 69 Testing the system ...................................................................62
Powerline carrier device connections ........................................ 8 Transmitter loop numbers .......................................................15
Powerline carrier device house code.................................. 67, 69 Transmitter supervision ..........................................................13
Powerline carrier device programming ................................... 44 Transmitters ............................................................................13
Primary phone number ..................................................... 67, 69 Trouble by day/.........................................................................18
Primary subscriber account number ................................. 67, 69 Trouble conditions....................................................................65
Programming default tables.............................................. 67, 69 Trouble report code ............................................................ 67, 69
Trouble restore report code ................................................ 67, 69
Troubleshooting guide..............................................................65
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM - 78 -
Lynx Plus Series Installation and Setup Guide
U X
Unsupervised button RF.......................................................... 13 X10......................................................................................43, 55
Unsupervised RF ..................................................................... 13
Ur (unsupervised RF) ........................................................ 13, 39 Z
Zone entry to list ......................................................................47
V Zone list .................................................................. 17, 67, 69, 72
Voice descriptor.................................................................. 38, 52 Zone number.............................................................................38
Voice prompt programming mode ........................................... 16 Zone programming .............................................................67, 69
Voltage input............................................................................ 76 Zone response type ...................................................................18
Zone type ..................................................................................38
W
Wall mounting ........................................................................... 6
WAVE2EX................................................................................ 76
Wireless buttons ...................................................................... 13
Wireless transmitter................................................................ 32
Wireless zones.......................................................................... 13
Wiring connections..................................................................... 7
World wide web address .......................................................... 76
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM - 79 -
UL INSTALLATIONS
THE MINIMUM WIRE
SIZE USED FOR EXTERNAL SOUNDERS AND POWERLINE CARRIER DEVICES HAVE NOT BEEN EVALUATED BY UL.
TELEPHONE
INSTALLATIONS
MUST BE #26 GAGE
POWER SHUTDOWN NOTE: AT 6.0VDC THE SYSTEM WILL NOT OPERATE.
TO 24HR 110VAC
HARD 6-14VDC UNSWITCHED
800-03857V1
WARNING
TO PREVENT RISK OF WIRED 120mA max. OUTLET
SHOCK, DISCONNECT ZONE
TELEPHONE LINE K10145WH/K10145X10
AT TELECOM JACK 2k OR K10145CN PLUG-IN
BEFORE SERVICING EARTH OHMS BELL
GROUND TRANSFORMER
THIS UNIT EOLR
9VAC, 25VA
INCOMING
TELEPHONE PREMISES
LINE TELEPHONE NOTE
USE ONLY THE
K10145WH/K10145X10
12/09 Rev. A
OR K10145CN CLASS 2
RING TIP RING TRANSFORMERS
TIP
PROVIDED
8 SOUND
T R T R HWZ OUT AC AC
POS SUPER HIGH-CAPACITY
JACK BATTERY CONNECTOR
1 2 3 4 5 6 7 8 9 10 11
STANDARD/HIGH-CAPACITY
BATTERY CONNECTOR
INCOMING
GSML/GSMVL
Ê800-03857V1lŠ
PHONE EARTH PHONE ZONE SOUNDERS AC
GROUND COMMUNICATIONS PORT
LINE
WWW.DIYALARMFORUM.COM
ON
85dB
SIREN
DISABLE ALL OUTPUT CIRCUITS ARE POWER LIMITED.
SWITCH
WARNING
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES. THE LYNX PLUS SERIES CONTROLS ARE
COMPATIBLE WITH THE FOLLOWING THIS UNIT MAY BE PROGRAMMED TO INCLUDE AN ALARM
OPERATION IS SUBJECT TO THE FOLLOWING TWO
INTEGRAL RECHARGEABLE BATTERY PACKS: VERIFICATION FEATURE THAT WILL RESULT IN A DELAY OF THE
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
SYSTEM ALARM SIGNAL FROM THE INDICATED FIRE CIRCUITS.
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY P/N LYNXRCHKIT-SC THE TOTAL DELAY (CONTROL UNIT PLUS SMOKE DETECTORS)
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE P/N LYNXRCHKIT-HC SHALL NOT EXCEED 60 SECONDS. NO OTHER INITIATING
THAT MAY CAUSE UNDESIRED OPERATION. P/N LYNXRCHKIT-SHA DEVICES SHALL BE CONNECTED TO THESE CIRCUITS UNLESS
WEEKLY TESTING IS
WWW.DIYALARMFORUM.COM
REPLACE EVERY FOUR YEARS APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION.
REQUIRED TO ENSURE
PROPER OPERATION CIRCUIT CONTROL UNIT SMOKE DETECTOR
LYNX PLUS SERIES ALSO COMPLIES WITH THE FOLLOWING: OF THIS SYSTEM (ZONE) DELAY-SEC MODEL DELAY-SEC
CANADIAN STANDARDS ASSOCIATION (CSA) C22.1, 02 - 25 30 seconds 5806 10 seconds
CANADIAN ELECTRICAL CODE, PART 1, SAFETY STANDARD ZT16
FOR ELECTRICAL INSTALLATIONS AND CAN/ULC-S540
emergency number. The System must be checked by a qualified technician once every three years
INSTALLATION OF RESIDENTIAL FIRE WARNING SYSTEMS.
approval of the local authority having jurisdiction. The burglar alarm signal shall not be connected to a police
Notes: Connection of the fire alarm signal to a fire alarm headquarters or a central station shall be permitted with the
www.honeywell.com/security
P.O. Box 9040, Melville, NY 11747
Copyright © 2009 Honeywell International Inc.
2 Corporate Center Drive, Suite 100