CSC-103

Line Differential Protection

IED

Product Guide
CSC-103 Line Differential Protection IED

Version:V1.06

Issued Date:2020.08

Copyright owner: Beijing SIFANG Automation Co., Ltd

Note: the company reserves the right to amend the instruction. If equipment does not agree
with the instruction at anywhere, please contact our company in time. We will provide you
with corresponding service.

®
is registered trademark of Beijing SIFANG Automation Co., Ltd.

We reserve all rights to this document, even in the event that a patent is issued and a different commercial
proprietary right is registered. Improper use, in particular reproduction and dissemination to third parties, is
not permitted.

This document has been carefully checked. If the user nevertheless detects any errors, he is asked to notify
us as soon as possible.

The data contained in this manual is intended solely for the product description and is not to be deemed to
be a statement of guaranteed properties. In the interests of our customers, we constantly seek to ensure
that our products are developed to the latest technological standards as a result; it is possible that there
may be some differences between the hardware/software product and this information product.

Manufacturer: Beijing SIFANG Automation Co., Ltd.


Email: [email protected]
Website: http://www.sf-auto.com
Add: No.9, Shangdi 4th Street, Haidian District, Beijing, P.R.C.100085

2 / 51
CSC-103 Line Differential Protection IED

CSC-103 is selective, reliable and high speed protection IED for transmission line, with powerful
capabilities to cover following applications:

 For 35kV to 1000kV transmission lines, W/O serial compensation equipment for extra-long lines,
or W/O parallel lines, heavy load lines, extreme long line or short line;

 Up to 3 terminals.

 Support two groups of CT inputs of multi-breaker arrangement;

 Fully proven protection functions library;

 Customized protection function scheme, all in one or main protection unit only;

 Powerful scalable hardware capability, for present and future application

 Mixable CT&VT inputs / SV(Sampling Value) inputs or outputs;

 Mixable Binary inputs & output relays / GOOSE inputs or outputs;

 Robust hardware with excellent EMC performance and IP54 protection under -40℃ to
+70℃ operating temperature;

3 / 51
Application
BUS

52

74TC 86

* I VREF V

87L
21,21N

68, 78 FL

50/51, 46
50N/51N

67/67N 32
85-21,21N

50BF 49
85-67N

50STUB 81

50SOTF 27,59

50DZ, 47
62PD

46BC VT
Failure

50OL 25 79 - RS-485
- RJ45/FO
CT - IEC61850
Failure - IEC60870-5-103
- IEC62439-3 PRP

Fault recording
LINE

4 / 51
Application
BUS 1

* I1 VREF1
I2 V

52 FL
21,21N

68, 78 32

50/51, 87L
50N/51N
LINE 1
50BF
67/67N

50SOTF 85-21,21N

52 49
50DZ,
85-67N
62PD
50STUB

81
50OL

27,59
* 46BC
LINE 2 47 - RS-485
46 - RJ45/FO
VT - IEC61850
CT Failure - IEC60870-5-103
Failure - IEC62439-3 PRP
VREF2
25 79
52

Fault recording

VREF3

BUS 2

5 / 51
Function
Function ANSI Code Qty. Description

Line differential protection 87L 1 3 differential protection elements with different principle

1 5 zone + 1 extended zone


Polygonal characteristic and MHO characteristic
Distance protection 21/21N
Load encroachment
Power swing blocking
85-21/21N 1 PUTT, POTT, Blocking mode, DDT
Tele-protection scheme
85-67N Permissive and blocking mode, DTT
1 4 stages; Forward/reverse/non-directional; Definite time/
Directional overcurrent protection 50,51,67
Inverse time characteristic; Inrush block
1 4 stages; Forward/reverse/non-directional; Definite time/
50N, 51N,
Directional earth fault protection Inverse time characteristic; 3 phase current inputs or
67N
single current input
Negative sequence overcurrent 1
46 4 stages; Definite time/ Inverse time characteristic
protection

Thermal overload 49 1 2 stages for alarm; 1 stage for tripping

Overvoltage 59 1 4 stages; Definite time / Inverse time characteristic;

Undervoltage 27 1 4 stages; Definite time / Inverse time characteristic;

Negative sequence overvoltage 47 1 4 stages; Definite time / Inverse time characteristic

Overpower protection 32 1 2 stages

Out of step protection 78 1 1 stage for alarm; 1 stage for tripping

Under frequency protection 81U 1 4 stages;

Over frequency protection 81O 1 4 stages;

Frequency rate protection 81DF 1 4 stages;

Breaker failure protection 50BF 1 2 stages; DTT in stage 2;

Dead zone protection 50DZ 1 1 stage; DTT;

Poles discrepancy protection 62PD 1 1 stage;

Broken conductor detection 46BC 1 1 stage;

Synchro-check & Energizing 1


25
check

Auto-reclosing 79 2 4 shots;

Stub-bus overcurrent 50STUB 1 1 stage;

Switch-on-to-fault protection 50SOFT 1 1 stage;

CT secondary circuit supervision 1 Enable/ disable blocking differential protection

6 / 51
Function
VT secondary circuit supervision 97FF 1

Disturbance recording 1 Max. 20s in 1 recording;

Trip circuit supervision 74TC Selectable board

Programmable logic

Measurement V, I, F, COSΦ, P, Q, Wp, Wq

Automation

Note 1: the number in “Qty.” column is the maximum quantity of function module that can
be offered.

87L Line differential protection


 For HV and MV lines, and up to 3 terminals protection
line
This protection element calculates the fault
 Support dual CT inputs of multiple breaker current only, the sudden change variable
arrangement part of whole current. Without influence of
load current, the protection function has
 3 differential protection elements, which
high sensitivity, especially to the fault
coordinate with each other to achieve high
through arc resistance on heavy load line.
sensitivity and reliability with capacitive
charging-current compensation and strictly
ΔIDiff
phase selection during various system

 Phase segregated differential operating area


protection

K2
IDiff
ΔI_2Diff
operating area

K1
ΔI_1Diff
K2

I_2Diff ΔI_1Res ΔI_2Res ΔIRes

K1
I_1Diff  Zero-sequence current differential
protection function
I_1Res I_2Res IRes
As a complement to phase segregated
differential protection, the zero sequence
 Sudden-change current differential

7 / 51
Function
current differential protection is used to  CT saturation detection
enhance the protection sensitivity on the
Based on current waveform principle, the
earth fault through high arc resistance. It
protection can discriminate the CT
always clears the fault after a delay time.
saturation condition. Once under this
condition, the protection will use a new
I0Diff
differential and restraint characteristic
shown in the below to guarantee the
Operating area security of the protection.

 Differential protection CT failure detection

 Automatic CT ratio compensation;


K
 Long-term Differential current supervision

I_0Diff  Up to 8 binary inputs for remote


transmission command and one binary
I0Res input for remote tripping command

21 Distance protection
 Full scheme protection with all phase to X
Line
phase faults and phase to earth fault loops X_Zset
independently for each zones; Φ_Ztop

 5 zones + 1 extension zone

Line
X Φ_Zleft
Zone 5 Φ_Zright
Zone 4
Zone 3 R_Zset R
Zone 2
Φ_Zbottom
Zone Ext.

Zone 1

R  5 zones + 1 extension zone

Zone 3 Reverse
(optional)

Zone 4 Reverse
(optional)
Zone 5 Reverse
(optional)

 Polygon characteristic

8 / 51
Function
X
X
Zone 5
Zone 4

Zone 3
Zone 2

Zone Ext.

Zone 1

Zone 3 Reverse Φ_Load


(optional) R_Load
Zone 4 Reverse
(optional)
R
Zone 5 Reverse
(optional)

 MHO characteristic
jX
jX
Z ZD 0   30

Φ_Load
R_Load

R
 Load Area

R
ZS
 Power swing blocking logic, which
guarantee no wrong operating during
 Load Encroachment
power swing, and guarantee fast operating
while fault during power swing.

85-21,21N/67N Tele-protection
 Based on distance protection element and  DTT;
directional earth fault protection element.
 Work with line differential protection in two
The function employs power line carrier
modes:
(PLC)
 Work in parallel
 Support following principle
 Backup mode
 PUTT;
It is automatically enabled once line
 POTT;
differential protection out of service; and
 Blocking; automatically quit when line differential
protection is restored.

9 / 51
Function
50BF CB failure protection
 Two trip stages (local CB and surrounding  Single/ three phase CBF initiation
breaker tripping)
 Settable CB Aux contacts checking
 Transfer trip command to the remote line
 Current criteria checking (including phase
end in stage 2
current, zero and negative sequence
 Internal/ external initiation current)

50DZ Dead zone protection


 The IED provides dead zone protection to  Situation 2: With one line side CT.
protect the area between circuit breaker
When a fault occurs between CT and
and CT in the case that CB is open.
breaker, protection IED sends a transfer
 Internal/ external initiation trip to remote line end IED to isolate the
fault. Tripping logic is illustrated below.
 Self-adaptive for bus side CT or line side
CT

 Situation 1: With one bus side CT of feeder

Once a fault occurs between CT and Inter trip


Bus
breaker, the IED trips the relevant busbar
zone CBs, shown as below.

IFAULT
Trip
Bus
Line1 Line2 LineN

IFAULT Legend:
Trip Opened CB
Relay
Closed CB

Line1 Line2 LineN

Legend:

Opened CB
Closed CB

10 / 51
Function
50STUB STUB protection
 The protected zone is between the CTs
and the opening disconnector

 Condition 1: The line side disconnector is


open;

 Condition 2: Main line protection IED is out Bus A Relay trip Bus B
of service.

 The STUB protection is enabled when the


open position of the disconnector; IFAULT IFAULT

 1 definite time stage, which related concept


is shown below.

Line Line
A B

Legend:
Closed CB

25 Synchro-check and energizing check


 Available for automatic reclosing (internally  Override
or externally request) and manual closing
 Energizing check modes:
 Based on voltage/ angle/ frequency
 Dead line and dead bus
difference
 Dead line and live bus
 Synchro-check modes:
 Live line and dead bus
 Synchronization check
 Synchro-check reference voltage
 Energizing check, and synch-check if
supervision
energizing check failure

11 / 51
Function
79 Auto-reclosing
 Up to 2 AR modules to support 2 CBs in  Single/ three phase AR operation
one IED
 CB position ready supervision
 4 shots automatic reclosing (selectable)
 CB Aux. contact supervision
 Individually settable dead time for three
 Cooperation with internal synch-check and
phase AR and single phase AR for each
energizing check function for reclosing
shot
command
 Internal/ external AR initiation

12 / 51
Communication
 Up to 2 fiber-optical remote communication Overhead Line or Cable

ports, work in the redundant transmission


route, with advantage of no time-delay
channel switch in case of the primary Channel A

channel broken o e
Digital
communication
e o

network
Flexible combinations of the 4 type Protection IED
Converter Converter
Protection IED
Channel B
communication modes with 2 channels

 Dual directly single mode fiber-optical


cable connection mode, duplex LC  1 single mode fiber-optical cable direct
plug connection and 1 multimode fiber-
optical cable connection, LC plug with
Overhead Line or Cable
IEEE C37.94 interface via SDH/PDH

Overhead Line or Cable

Channel A

Channel B

Protection IED Protection IED Channel A

Digital

 Single mode fiber-optical cable communication


network
Protection IED Protection IED

connection through dual Channel B

communication converter with G.703


or G.703E1 interface via SDH/PDH
 The distance options of directly single
Overhead Line or Cable
mode fiber-optical cable connection mode:

Channel A  < 40 km;


Digital
o e
 40 – 60 km;
communication
e network o
o e
Digital
e communication o
Protection IED converter
network
converter Protection IED  60 – 120km;
Channel B

 Communication for “T” connection line


 Single mode fiber-optical cable
connection, 1 direct connection and 1
converter connection

Protection IED Protection IED


A B

Protection IED
C

13 / 51
Automation
 Support SV, GOOSE service of process  MODBUS
layer application in accordance with
 IEC 61850-8-1
IEC61850-8-1, -9-2, -9-2LE,
 IEC 62439-3 PRP
 Support MMS, GOOSE service of station
layer and bay layer application in  Support several time synchronizing way,
accordance with IEC61850-8-1, include:

 Seamless communication by PRP.  IRIG-B modulated electrical/ optical;

 Adaption to the existing automation system  Pulse;


with 2 or 3 Ethernet ports or 2 serial
 SNTP;
communication ports RS-485 in one
module  IEEE 1588;

 Support all main protocols, include:  Proven technology from thousands of


operated digital substations;
 IEC 60870-5-103 serial or TCP/IP;

 DNP 3.0;

HMI

Switch

Protection
IED

Switch Switch
Indoor

Outdoor
SCU AMU+SCU AMU+SCU

Bay A Bay B Bay A Bay B Bay A Bay B Bay A Bay B

Station layer: MMS/GOOSE; PRP; Station layer: MMS/GOOSE; PRP; Station layer: MMS/GOOSE; PRP; Station layer: MMS/GOOSE; PRP;
Bay layer: GOOSE; PRP; Bay layer: GOOSE; PRP; Bay layer: GOOSE; PRP; Bay layer: GOOSE; PRP;
Process layer: Process bus, GOOSE; PRP; Process layer: SV/GOOSE; PRP; Process layer: Process bus, SV/GOOSE; PRP;

14 / 51
Tools
AESP tools
AESP tools is the user-friendly software tool sets.  Fault analysis with fault records in curves,
AESP covers all works for the whole life cycle of circle diagrams, vector diagrams, harmonic
protection IEDs, include, bar, and protection characteristic diagram
graphically and precise data in pointed
 Setting and parameter
instant.
 Disturbance analysis by Fisewave

 Monitoring

 Logic programming by Nuclide

 IED configuration by IO master;

 Single line diagram painter;

 IEC 61850 system engineering manager

Its features are as follows:

 Oriented to IEDs management of whole


substation with freely configurable
 With integrated logic, the user can set, via
hierarchies based on the substation
a graphic interface, specific functions for
topology in real project.
the automation of switchgear or substation.
 Intelligent validity checks and shadow
 Password-protected access for different
avoid incorrect input when setting and
operation and different roles;
programming

15 / 51
Hardware
 Up to 3 RJ45 Ethernet ports ;
 Up to 8 AC Current Inputs and 6 Voltage
Inputs, 1A/ 5A settable;  Up to 2 RS-485 ports;

 Up to 45 Binary Inputs, include  1 IRIG-B / Pulse time synchronization port;


independent BIs;
 1 RJ45 front test port
 Up to 92 Output relays, with 5 switchable
 22 programmable LED
NO/NC contacts;
 Up to 4 customer defined function key;
 Up to 7 Ethernet optical ports, for SV,
GOOSE, MMS and other automation  4U 19” or 4U 1/2 19” case;
services;

Front view of the 4U 19” case

Rear view of the 19” case

16 / 51
Hardware
A 177
E
C B 482.6

C 265
A
D 320

E 437.2
D
Unit mm
B

Dimension of the 4U 19” case

Front view of the 4U 1/2 19” case Rear view of the 4U 1/2 19” case

D
A 177

B 259.2

A C 286

D 226

Unit mm
C

Dimension of the 4U 1/2 19” case

17 / 51
Specification
Thermal withstand Vph-e 200V, continuously;
AC current measurement
IEC60255-27 400V for 60s.
Item Data
Rated current Ir 1/5 A, settable
Other measurement
IEC60255-1
Operating range of (0 ~ 100) Ir Item Data
protection CT Rated frequency 50/60Hz, settable
Measuring range of (0.05 ~ 40) Ir Measuring range of
protection CT (0.9~1.1) Fr
frequency
Reading accuracy for ±2.5% Ir or 0.02Ir, Reading accuracy of
protection CT at (0.05~40) Ir ±0.02 Hz
frequency
Thermal withstand of 4 Ir Continuously; Reading accuracy of ±1°, at rated AC voltage and
protection CT 30 Ir for 30s angle AC current
IEC60255-27 100 Ir for 1s
Reading accuracy of
Range for measuring CT (0.01 ~ 2) Ir 1%, at rated AC voltage and
active power and
AC current
Reading accuracy for ±0.5% Ir, at I>Ir reactive power
measuring CT ±0.5% Ir, at I≤Ir
Thermal overload 4 Ir Continuously;
Binary inputs
capacity of measuring CT 30 Ir for 30s
IEC60255-27 100 Ir for 1s Item Data
Measurement range for 0.005A ~ 1.2A Rated voltage Vr.aux 110/125/220/250 Vdc, settable;
high sensitive CT IEC60255-1 or 24/48Vdc settable;

Reading accuracy for ±0.5%Ir, at I>10%Ir Max. permissible 300V,


high sensitive CT ±0.5%Ir, at I≤10%Ir voltage at Vr.aux=110/125/220/250 Vdc;

Thermal withstand of high 3A continuously IEC60255-1 62V, at Vr.aux =24/48 Vdc;

sensitive CT 100A for 1s Operating threshold ≥70% Vr.aux, guarantee


IEC60255-27 IEC60255-1 operating

Burden for current (per ≤0.15VA at Ir=1A; ≤55% Vr.aux, guarantee not to

phase) ≤0.3VA at Ir=5A operating

Dynamic thermal 250 Ir for 1.5 cycle Pickup time Approx. 1ms, intrinsic

overload capacity Dropout time Approx. 2ms, intrinsic


Burden for binary input ≤0.25 W, at Vr.aux=110Vdc

AC voltage measurement IEC60255-1 ≤0.5 W, at Vr.aux=220Vdc

Item Data
Output relay
Rated voltage Vr.ph-ph 100/110Vac, settable;
IEC60255-1 Item Data

Measuring range of VT 0.4V ~ 180V Rated contact voltage 24/48/110/125/220/250Vdc

Vph-e IEC60255-1 100/220Vac

Reading accuracy for VT < ±2.5% setting or 1V Maximum contact voltage 250Vac/dc

Vph-ph IEC60255-1

Burden for voltage ≤ 0.05VA, at Vr. ph-ph = 110V Mechanical endurance Unload, 10000 times
IEC60255-1 IEC60255-1 Load,making, ≥ 1000 times

18 / 51
Specification
Load,breaking, ≥ 1000 times voltage )
Current carrying capacity General relay: IEC60255-1
IEC60255-1 5A continuous,
30A, 200ms on,15s off
Ethernet communication
Power relay:
10A continuous, Item Data
30A, 200ms on,15s off Max. ports number 3

Making capacity General relay: Electrical Ethernet port type RJ45


IEC60255-1 1000W, at Vr.aux=220Vdc Maximum transmission 100M
L/R=40ms distance of Ethernet cable
Power relay: Optical Ethernet port type LC
1250W, at Vr.aux=220Vdc Fiber optic cable type Multi-mode
L/R=40ms Optic wavelength 1310 nm
Breaking capacity General relay: Optic received sensitivity -33 dBm
IEC60255-1 30W, at Vr.aux=220Vdc, Emitter electric level >-20 dBm;
L/R=40ms; Maximum transmission 2kM 62.5/125μm MMF
0.4A, at Vr.aux=110Vdc,, distance of optical fiber
L/R≤40ms; Transmission rate for 100Mbit/s
Power relay: IEC61850
55W, at Vr.aux=220Vdc, Transmission rate for DNP 100Mbit/s
L/R=40ms; 3.0
0.45A, at Vr.aux=110Vdc,
L/R≤40ms;
Serial communication
Contact insulation test 2kVac, 1min
(AC dielectric voltage ) Item Data
IEC60255-1 Number 2
Pick up time ≤5ms Port type RS-485
IEC60255-1 Maximum transmission 1.0km
distance
Drop off time ≤10ms
IEC60255-1 Voltage withstand test 500V earthing AC voltage
Transmission rate for Default setting 9600 bps;
IEC60870-5-103 Minimum: 1200bps;
Auxiliary power maximum: 19200bps

Item Data
Rated voltage Vr.aux 110V to 250Vdc/ac Time synchronization
IEC60255-1 24/48Vdc
Item Data
Input voltage range (0.8~1.2) Vr.aux Synchronization mode SNTP
IEC60255-1 IRIG-B time sync
Burden for power supply ≤20W, at quiescent Minute or second Pulse
unit ≤30W, at 50% loaded IEEE 1588

IEC60255-1 IRIG-B signal format IRIG-B000

Insulation test (AC dielectric 2kVac, 1min IRIG-B Port type Twisted-pair connection

19 / 51
Specification
or multi-mode optical fiber ANSI/IEEE C37.90 port;
IRIG-B signal voltage level Differential signal input/ GB/T15145-2001 Enclosure port;
modulated DL/T478-2013 Input and output ports;
Functional earth port;

Inter-substation communication 500V, 50Hz, at rated


voltage ≤63V,
Item Data Tested on:
Ports number 1~2 Communication port;
Fiber optic cable type Single-mode or multi-mode Impulse voltage 5kV, at rated voltage>60V,
Optic wavelength 1310 nm, single-mode IEC60255-1 Tested on:
850 nm, multi-mode IEC60255-27 Auxiliary power supply
Optic received -34 dBm EN60255-5 port;
sensitivity ANSI/IEEE C37.90 Current and voltage
Emitter electric level >-11 dBm, at length <40 kM GB/T15145-2001 transformer ports;
>-4 dBm, at length 40~60 kM DL/T478-2013 Input and output ports;
>-5 dBm, at length 60~80 kM Functional earth ports;
>-3 dBm, at length 80~100 kM 1kV, at rated voltage≤60V,
>-0 dBm, at length 100~120 tested on:
kM CPU ports;
Fiber optic connector LC Insulation resistance ≥550MΩ, 500Vdc
type IEC60255-1
Data transmission rate 64 kbit/s, G703 IEC60255-27
2,048 kbit/s, G703-E1 EN60255-5
N*64kbps, N=1~12, C37.94 ANSI/IEEE C37.90
Max. transmission 120 kM 62.5/125μm MMF GB/T15145-2001
distance DL/T478-2013
Protective bonding ≤0.1Ω

Product safety test resistance


IEC60255-27
Item Data
Fire withstand/flammability Class V0
Over voltage category Category III IEC60255-27
IEC60255-27
Pollution degree Degree 2
EMC test
IEC60255-27
Insulation type Basic insulation Item Data
IEC60255-27 Electrostatic discharge Criteria A;
Degree of protection (IP) Front plate: IP54 immunity test Level IV;
IEC60255-27 Side plate:IP52 IEC60255-26 ±6kV contact discharge;
IEC60529 Rear plate: IP30 IEC61000-4-2 ±8kV air gap discharge;
Power frequency high 2kV, 50Hz, at rated Radiated interference Criteria A;
voltage withstand test voltage > 63V, radio-frequency Class IV;
IEC60255-5 Tested on: electromagnetic field 10 V/m, 80%,AM (1 kHz)
EN60255-5 Auxiliary power supply immunity test Frequency sweep:

20 / 51
Specification
IEC60255-26 80 MHz ~1 GHz; 1.4 GHz ~2.7 Power frequency Criteria A
IEC61000-4-3 GHz magnetic field immunity 100 A/m Continuous;
spot frequencies (MHz): test Criteria B
80; 160; 380; 450; 900; 1850; IEC60255-26 1000 A/m, 3s;
2150. IEC61000-4-8
Electrical fast Class A Power frequency Zone A
transient/burst immunity 4kV peak voltage; immunity test 300V, CM; 150V, DM;
test Tested on: IEC60255-26 Test on:
IEC60255-26 Auxiliary power supply IEC61000-4-16 Binary input ports;
IEC61000-4-4 port; Slow damped oscillatory Class III
ANSI/IEEE C37.90 Current and voltage wave immunity test 2.5 kV CM ; 1 kV DM;
transformer ports; (1MHz) Tested on:
Input and output ports; IEC60255-26 Auxiliary power supply
Functional earth port; IEC61000-4-18 port;
2kV peak voltage; ANSI/IEEE C37.90 Current and voltage
Tested on: transformer ports;
Communication port; Input and output ports;
Surge (impact) immunity Class A,Level IV 1 kV CM; 0 kV DM;
test 4.0kV, Line-to-earth; Tested on:
IEC60255-26 2.0kV, Line-to-line; Communication ports
IEC61000-4-5 Tested on: Fast damped oscillatory Level 4
Auxiliary power supply wave immunity test 4 kV, at 3MHz, 10MHz,
port; IEC61000-4-18 30MHz.
Current and voltage Tested on:
transformer ports; Auxiliary power supply
Input and output ports; port;
Functional earth port; Current and voltage
4.0kV, Line-to-earth; transformer ports;
Tested on: Input and output ports;
Communication ports; Pulse magnetic field Class V
Test for immunity to 10 V/m, 80% AM (1 kHz) immunity test 1000A/m
conducted disturbances, Frequency sweep: 150kHz– IEC61000-4-9
induced by radio- 80MHz Damped oscillation Class V
frequency fields Spot frequencies: 27MHz and magnetic field immunity 100A/m
IEC60255-26 68MHz; test
IEC61000-4-6 Tested on: IEC61000-4-10
Auxiliary power supply Conducted emission Class A;
port; IEC60255-1 0.15MHz to 0.50MHz;
Current and voltage IEC60255-26 0.50MHz to 30MHz;
transformer ports; CISPR 11, CISPR 22 Tested on:
Input and output ports; Auxiliary power supply port;
Functional earth port; Communication ports
Communication ports; Radiated emission Class A;

21 / 51
Specification
IEC 60255-1 30MHz to 230MHz; Vibration endurance test Class 1
IEC60255-26 230MHz to 1GHz; IEC 60255-21-1 Relay non-energized
CISPR 11, CISPR 22 Tested on: EN 60255-21-1 10 to 150 Hz: 1 g acceleration
Auxiliary power supply port; 20 sweep cycles in each axis,
Voltage dips and voltage Criteria A 3 axis
interruptions on DC 150 ms at 0% residual Shock response test Class 1
power supply voltage; IEC 60255-21-2 Relay energized
IEC 60255-26 200 ms at 40% residual EN 60255-21-2 Duration 11 ms :
IEC 61000-4-11 voltage; 5 g acceleration
IEC 61000-4-29 500 ms at 70% residual 6 shocks in each axis, 3 axis
voltage; Shock withstand test Class 1
5s at 0% residual voltage IEC 60255-21-2 Relay non-energized
Voltage dips and voltage Criteria A EN 60255-21-2 Duration 11 ms :
interruption on AC power At 50 Hz: 15 g acceleration
supply 5 cycles at 0% residual 6 shocks in each axis, 3 axis
IEC 60255-26 voltage; Bump test Class 1
IEC 61000-4-11 10 cycles at 40% residual IEC 60255-21-2 Relay non-energized
IEC 61000-4-29 voltage,; EN 60255-21-2 Duration 16 ms :
25 cycles at 70% residual 10 g acceleration
voltage; 2000 bumps in each axis, 3
250 cycles at 0% residual axis
voltage Sinusoidal sweep Class 1
Voltage ripple on DC 15% at twice rated frequency; seismic test Relay energized
power supply IEC 60255-21-3 1-8 Hz: ± 3.5 mm amplitude
IEC 60255-26 (horizontal axis)
IEC 61000-4-17 1-8 Hz: ± 1.5 mm amplitude
Gradual shutdown/ start- 5 min power off (vertical axis)
up for power supply 42VDC at 60 s shut down ramp 8-35 Hz: 1g acceleration
IEC60255-26 78VDC at 60 s start-up ramp (horizontal axis)
Reversal of DC power 60 s 8-35 Hz: 0,5g acceleration
supply (vertical axis)
IEC 60255-27 Frequency sweep:
1 sweep cycle in each axis, 3
Mechanical test axis

Item Data
Vibration response test Class 1 Environmental test
IEC 60255-21-1 Relay energized
Item Data
EN 60255-21-1 10-60 Hz: ± 0.035 mm
Cold test - operational -40°C, 96 hours,
amplitude
IEC 60255-27 relay energized
60-150 Hz: 0,5 g acceleration
IEC 60068-2-1
Frequency sweep:
Cold test – Storage -40°C, 96 hours,
1 sweep cycle in each axis,
IEC 60255-27 relay non-energized
3 axis

22 / 51
Specification
IEC 60068-2-1 IEC 60068-2-78
Dry heat test – operational +70°C, 96 hours, Cyclic temperature with +55°C, 93% r.h. 6 cycles,
IEC 60255-27 relay energized humidity test relay energized
IEC 60068-2-2 IEC 60255-27
Dry heat test – Storage +70°C, 96 hours, IEC 60068-2-30
IEC 60255-27 relay non-energized
IEC 60068-2-2 CE Certification
Change of temperature -40°C / +70°C, 6 cycles
IEC 60255-27 relay energized Item Data

IEC 60068-2-14 EMC EN 61000-6-2 and EN 61000-6-4


(EMC steering committee
Damp heat steady-state test +40°C, 93% r.h. 10 days,
2004/108/EC)
IEC 60255-27 relay energized
LVD EN 60255-27(LVD 2006/95EC)

23 / 51
Specification
87L, Line Differential Protection 85, Tele-protection scheme

Item Data Item Data


Phase segregated 0.1 Ir to 20.00 Ir Minimum operation ≤25 ms Permission mode for
differential protection ≤ ±3% or ±0.02 Ir time 21/21N/67N, when fault at the
current; Sudden-change middle of the transmission line.
differential protection Operation time 25 ms typically
current
Operating time 25ms typically 50, 51, 67, Directional overcurrent
Minimum operating time ≤ 20ms, at 700% setting, protection
and Idiff > 2Ires
Item Data
Differential current of zero 0.05Ir to 20.00Ir
Definite time characteristic
sequence differential ≤±3% or ±0.02Ir
0.05 Ir to 40.00 Ir
protection Current
≤ ±2.5% setting or ±0.02 Ir
Time delay of zero 0.00s to 10.00s, step 0.01s 0.00s to 100.00s, step 0.01s
Time delay of definite
≤ ±1% setting or ≤ +40ms, at
sequence differential ≤±1% or +130ms time characteristic
200% operating setting
protection Reset ratio ≥ 0.95
Reset time ≤ 40ms

21, Distance protection Inverse time characteristic


0.05 Ir to 40.00 Ir
Current
Item Data ≤ ±2.5% setting or ±0.02Ir
5 zones Time delay IEC Inverse Normal inverse;
Number of zones
IEC 60255-151 Very inverse;
Distance characteristic Polygonal and MHO
Extremely inverse;
Resistance setting range 0.05 / Ir ~ 600 / Ir Ω, step 0.01
Long time inverse
Ω, when Ir = 5 A / 1 A
≤ ±5% or ≤ +40ms , at 2
Reactance setting range 0.05 / Ir ~ 600 / Ir Ω, step 0.01
<I/ISETTING < 20
Ω, when Ir = 5 A / 1 A
Time delay IEEE/ ANSI Inverse;
Delay time of distance 0.00s~60.00 s, step 0.01 s
Inverse Short time inverse;
zones ≤±1% or ≤+20 ms, at setting
IEEE/ ANSI C37.112 Long time inverse;
time > 60 ms
Moderately inverse;
Minimum operating time ≤20 ms, zone 1 at fault
Very inverse;
within 64% operating zone
Extremely inverse;
Operation time 22 ms typically, zone 1 at
Definite time inverse
fault within 70% operating
≤ ±5% setting or ≤ +40ms, at
zone
2 <I/ISETTING < 20
Dynamic overreaching for ≤±5%, at 0.5< SIR <30
Time delay user-defined A
zone 1 T=( i + B) k
inverse (
I_SET
)P −1
Measuring tolerance of ≤+3% when fault current is
IEEE/ANSI C37.112 ≤ ±5% setting or ≤ + 40ms, at
fault locator (not including greater than 0.01 Ir at metal
2 <I/ISETTING < 20
errors caused by factors fault, error will become
Time factor of 0.001 to 1000.0s, step 0.001s
outside product) bigger when fault occurs
characteristic, A
with greater transition
Time delay of 0.00s to 100.00s, step 0.01s
resistance
characteristic, B

25 / 51
Specification
Index of characteristic, P 0.01 to 10.00, step 0.01 inverse Short time inverse;
Time constant of 0.025 to 1.50, step 0.001 IEEE/ANSI C37.112 Long time inverse;
characteristic, k Moderately inverse;
Min inverse operate time Instantaneous Very inverse;
Reset ratio ≥ 0.95 Extremely inverse;
Reset time ≤ 40ms Definite inverse
Directional element ≤ ±5% setting or ≤ + 40ms, at
Angle range of operating 170° 2 <I/ISETTING < 20
area Time delay user- A
T=( + B) k
Characteristic angle 0° to 90°, step 1° defined inverse (
i
I_SET
)P −1
≤ ±1°, at phase to phase
voltage >2V IEEE/ANSI C37.112 ≤ ±5% setting or ≤ + 40ms, at
Inrush current blocking element 2 <I/ISETTING < 20
Max. current setting 0.05 Ir to 40.00 Ir Time factor of 0.001 to 1000.0s, step 0.001s
≤ ±2% setting or ±0.02Ir
without inrush current characteristic, A
blocking Time delay of 0.00s to 100.00s, step 0.01s
Ratio of second 0.07 to 0.50, step 0.01 characteristic, B
harmonics to Index of characteristic, 0.01 to 10.00, step 0.01
fundamental current P
Time period of cross 0.00s to 100.00s, step 0.01s Time constant of 0.025 to 1.500, step 0.001
≤ ±1% setting or ≤+40ms
phases blocking characteristic, k
Min inverse operate
instantaneous
time
50N, 51N, 67N Directional earth fault
Reset ratio ≥ 0.95
protection Reset time ≤ 40ms
Zero sequence directional element
Item Data
Three phase currents or Operating area range 160°;
Current inputs
single current 0° to 90°, step 1°
Characteristic angle
Definite time characteristic ≤ ±1°, at 3U0≥1V
0.05 Ir to 40.00 Ir Negative sequence directional element
Current
≤ ±2.5% setting or ±0.02 Ir Operating area range 160°
0.00s to 100.00s, step 0.01s
Time delay ≤ ±1% setting or ≤ +40ms, at 0° to 90°, step 1°
Characteristic angle
200% operating setting ≤ ±1°, at 3U2≥2V
Reset ratio ≥ 0.95
Reset time ≤ 40ms 46, Negative-sequence overcurrent
Inverse time characteristic protection
0.05 Ir to 40.00 Ir
Current
≤ ±2.5% setting or ±0.02Ir Item Data
Time delay IEC Inverse Normal inverse; Definite time characteristic
IEC 60255-151 Very inverse; 0.05 Ir to 40.00 Ir
Current
≤ ±2.5% setting or ±0.02 Ir
Extremely inverse;
0.00s to 100.00s, step 0.01s
Short time inverse Time delay ≤ ±1% setting or ≤ +40ms, at
Long time inverse 200% operating setting
Reset ratio ≥ 0.95
≤ ±5% setting or ≤ + 40ms, at
Reset time ≤ 40ms
2 <I/ISETTING < 20
Inverse time characteristic
Time delay IEEE/ANSI Inverse;
Current 0.05 Ir to 40.00 Ir

26 / 51
Specification
≤ ±2.5% setting or ±0.02Ir
 I eq2  I P2 
Time delay IEC Inverse Normal inverse;
IEC high temperature
t   ln  2 2
 I eq  I  
curve
IEC 60255-151 Very inverse; IEC 60255-149
≤ ±5% setting or ≤+40ms
Extremely inverse;
Short time inverse
59, Overvoltage protection
Long time inverse
≤ ±5% setting or ≤+ 40ms, at Item Data
2 <I/ISETTING < 20 Voltage input Phase to phase voltage or
Time delay IEEE/ANSI Inverse; phase to earth voltage
inverse Short time inverse; Definite time characteristic
IEEE/ANSI C37.112 Long time inverse; phase-to-earth voltages 40.0V to 100.0 V, step 0.01 V
Moderately inverse; ≤ ±2.5% setting or ± 1V
Very inverse;
Phase to phase voltage 80.0V to 200.0 V, step 0.01 V
Extremely inverse;
≤ ± 2.5% setting or ± 1V
Definite inverse
Reset ratio 0.95 to 1, step 0.01
≤ ±5% setting or ≤ +40ms, at
≤ ±3 % setting
2 <I/ISETTING < 20,
Time delay 0.00s to 120.00s, step 0.01s
Time delay user-defined A
T=( i + B) k ≤ ±1 % setting or ≤ +50ms,
inverse (
I_SET
)P −1
at 120% voltage setting
IEEE/ANSI C37.112 ≤ ±5% setting or ≤ + 40ms, at
Reset time ≤ 40ms
2 <I/ISETTING < 20
Inverse time characteristic
Time factor of 0.001 to 1000.0s, step 0.001s
phase-to-earth voltages 40.0V to 100.0 V, step 0.01 V
characteristic, A
≤ ±2.5% setting or ± 1V
Time delay of 0.00s to 100.00s, step 0.01s
Phase to phase voltage 80.0V to 200.0 V, step 0.01 V
characteristic, B
≤ ±2.5% setting or ± 1V
Index of characteristic, P 0.01 to 10.00, step 0.01
Time delay IEC Inverse Normal inverse;
Time constant of 0.025 to 1.500, step 0.001
IEC 60255-127 Very inverse;
characteristic, k
Extremely inverse;
Min inverse operate time instantaneous
Short time inverse;
Reset ratio ≥ 0.95
Long time inverse;
Reset time ≤ 40 ms
≤ ±5% setting or ≤ + 50ms, at
2 <U/Uset < 20
49, Thermal overload protection
Time delay IEEE/ANSI Inverse;
Item Data inverse Short time inverse;
0.05 Ir to 40.00 Ir IEEE/ANSI C37.112 Long time inverse;
Current
≤ ±2.5% setting or ±0.02Ir
Moderately inverse;
Heating time constant 6-9999 s
Very inverse;
Cooling time constant 0.1-10
Extremely inverse;
 I eq2  Definite inverse
IEC low temperature
t   ln  2 2 
curve
IEC 60255-149  I eq  I   ≤ ±5% setting or ≤ +50ms, at
≤ ±5% setting or ≤+40ms 2 <U/Uset < 20

27 / 51
Specification
Time delay user-defined   Moderately inverse;
 
 A
inverse t  B T Very inverse;
  U  P

IEEE/ANSI C37.112 
   1  Extremely inverse;
 Uset 
≤ ±5% setting or ≤ +50ms, at Definite inverse
2 <U/Uset < 20. ≤ ±1% setting or ≤ +50ms, at
Time factor of 0.001 to 10.000, step 0.001 120% voltage setting
characteristic, A Time delay user-defined  
 
A
Time delay of 0.00s to 100.00s, step 0.01s inverse t  B T
  U  P

characteristic, B IEEE/ANSI C37.112   1 
  Uset  
Index of characteristic, P 0.01 to 10.00, step 0.01 ≤ ±1% setting or ≤ +50ms, at
Time constant of 0.025 to 1.500, step 0.001 120% voltage setting
characteristic, T Time factor of 0.001 to 10.000, step 0.001
Min inverse operate time instantaneous characteristic, A
Reset ratio ≥ 0.95 Time delay of 0.00s to 100.00s, step 0.01s
Reset time ≤ 40ms characteristic, B
Index of characteristic, P 0.01 to 10.00, step 0.01
47, Negative-sequence overvoltage Time constant of 0.025 to 1.500, step 0.001
protection characteristic, T
Min inverse operate time instantaneous
Item Data
Reset ratio ≥ 0.95
Voltage input Calculated from 3 phase to
Reset time ≤ 40ms
earth voltages
Definite time characteristic 27, Undervoltage protection
Voltage 40 to 100 V, step 0.01 V
≤ ±2.5% setting or ± 1V Item Data

Time delay 0.00s to 100.00s, step 0.01s Voltage input Phase to phase voltages or

≤ ±1 % setting or ≤ +50ms, at phase to earth voltages

120% voltage setting Permitted current setting 0.04-40.00 Ir, step 0.01A

Reset ratio ≥ 0.95 ≤ ±2.5% setting or ±0.02Ir

Reset time ≤ 40ms Definite time characteristic

Inverse time characteritic phase-to-earth voltages 5.0 to 75.0 V, step 0.1 V

Voltage 1 to 100 V, step 0.01 V ≤ ±2.5% setting or ± 1 V

≤ ±2.5% setting or ± 1V Phase to phase voltage 10.0 to 150.0 V, step 0.1 V

Time delay IEC Inverse Normal inverse; ≤ ±2.5% setting or ±1 V

IEC 60255-127 Very inverse; Reset ratio 1.00 to 2.00, step 0.01

Extremely inverse; Time delay 0.00s to 120.00s, step 0.01s


Short time inverse; ≤ ±1 % setting or ≤ +50ms,
Long time inverse; at 80% voltage setting
≤ ±1% setting or ≤ + 50ms, at Reset time ≤ 40ms
120% voltage setting Inverse time characteritic
Time delay IEEE/ANSI Inverse; phase-to-earth voltages 5.0 to 75.0 V, step 0.1 V
inverse Short time inverse; ≤ ±2.5% setting or ± 1V
IEEE/ANSI C37.112 Long time inverse; Phase to phase voltage 10.0 to 150.0 V, step 0.1 V

28 / 51
Specification
≤ ±2.5% setting or ± 0.1V Time delay of stage 2 0.00s to 100.00 s, step 0.01s
Time delay IEC Inverse Curve 1 ≤ ±1% setting or ≤ +40 ms, at
IEC 60255-127 Curve 2 200% operating setting
Curve 3 Reset ratio ≥ 0.95
≤ ±1 % setting or ≤ +50ms, Reset time ≤ 40ms
at 80% voltage setting
Time delay user-defined 


 50DZ, Dead zone protection
A
curve t  B T
  U 
P

1    Item Data
IEC 60255-127   Uset  
≤ ±1 % setting or ≤ +50ms, Current 0.05 Ir to 40.00 Ir

at 80% voltage setting ≤ ±2.5% setting or ±0.02Ir

Time factor of 0.001 to 10.000, step 0.001 Time delay 0.00s to 100.00s, step 0.01s

characteristic, A ≤ ±1% setting or ≤ +40 ms, at

Time delay of 0.00s to 100.00s, step 0.01s 200% operating setting


Reset ratio ≥ 0.95
characteristic, B
Index of characteristic, P 0.010 to 10.000, step 0.005 Reset time ≤ 40ms

Time constant of 0.025 to 1.500, step 0.001


characteristic, T 50STUB, STUB protection
Min inverse operate time instantaneous
Item Data
Reset ratio 1.00 to 2.00, step 0.01
Current 0.05 Ir to 40.00 Ir
Reset time ≤ 40ms
≤ ±2.5% setting or ±0.02Ir
Time delay 0.00s to 100.00s, step 0.01s
32, Directional overpower protection
≤ ±1% setting or ≤ +40 ms, at
Item Data 200% operating setting
Power 0W to 500W Reset ratio ≥ 0.95
≤ ±3% setting or ±0.5Pn Reset time ≤ 40ms
Time delay 0.00s to 100.00s, step 0.01s
≤ ±1 % setting or ≤ +40ms 62PD, Pole discrepancy protection
at 120% operating setting
Reset time ≤ 55ms Item Data
Current 0.05 Ir to 40.00 Ir

50CBF, Circuit breaker failure ≤ ±2.5% setting or ±0.02Ir

protection Time delay 0.00s to 100.00s, step 0.01s


≤ ±1% setting or ≤ +40 ms, at
Item Data 200% operating setting
Phase current 0.05 Ir to 40.00 Ir Reset ratio ≥ 0.95
Negative sequence ≤ ±2.5% setting or ±0.02Ir Reset time ≤ 40ms
current
Zero sequence current
46BC, Broken conductor protection
Time delay of stage 1 0.00s to 100.00 s, step 0.01s
≤ ±1% setting or ≤ +40 ms, at Item Data
200% operating setting Current 0.05 Ir to 40.00 Ir

29 / 51
Specification
≤ ±2.5% setting or ±0.02Ir 81DF, Frequency change rate
Time delay 0.00s to 100.00s, step 0.01s protection
≤ ±1% setting or ≤ +40 ms, at
Item Data
200% operating setting
Reset ratio 0.3 to 20Hz/s
≥ 0.95 Change of rate Δf/Δt
≤± 0.5 Hz/s
Reset time ≤ 40ms
0.1s to 100.00s, step 0.01s
Time delay
≤ ±1.5% setting or ≤ +60 ms
81U, Under frequency protection
Upper limit of frequency 0.1 to 50Hz/s
Item Data change rate ≤±0.5Hz/s
45.00 to 50.00Hz, step Lower limit of frequency 0.1 to 50Hz/s
0.01Hz at Fr = 50Hz change rate ≤±0.5Hz/s
Frequency 54.00 to 60.00Hz, step 10 to 120V, step 0.01V
voltage
0.01Hz at Fr = 60Hz ≤±2.5% setting or ± 1V
≤ ± 20mHz
0.1s to 100.00 s, step 0.01s 50SOTF, Switch onto fault protection
Time delay ≤ ±1.5% setting or ≤+60 ms,
at 80% setting Item Data

Reset Δf =︱fset - freset︱ Approx. 20mHz Current 0.05 Ir to 40.00 Ir

0.3 to 20Hz/s ≤ ±2.5% setting or ±0.02Ir


Change of rate Δf/Δt Time delay 0.00s to 100.00s, step 0.01s
≤±0.5Hz/s
10 to 120V, step 0.01V ≤ ±1% setting or ≤ +40 ms, at
Voltage 200% operating setting
≤±2.5% setting or ± 1V
Reset ratio ≥ 0.95
0 to 10Ir
Current Reset time ≤ 40ms
≤±2.5% setting or +0.01Ir

81O, Over frequency protection 25, Synchro-check & energizing


check
Item Data
50.00 to 55.00Hz, step Item Data
Modes of Synchro-check  Synchronization check
0.01Hz at Fr = 50Hz  Energizing check, and
Frequency 60.00 to 66.00Hz, step synchronous check after
energizing check
0.01Hz at Fr = 60Hz failure
≤ ± 20mHz  Override
Modes of Energizing  Dead line & dead bus
0.1s to 100.00 s, step 0.01s check  Live line & dead bus
Time delay ≤ ±1.5% setting or ≤ +60 ms,  Dead line & live bus
Max dead voltage 10V to 50 V, step 0.01 V
at 80% setting setting at energizing
Reset Δf =︱fset - freset︱ Approx. 20mHz check mode ≤ ±2.5% setting or ± 1V
(Phase to earth voltage)
10 to 120V, step 0.01V Min live voltage setting
Voltage 30V to 65 V, step 0.01 V
≤±2.5% setting or ± 1V at synchronization check
mode ≤ ±2.5% setting or ± 1V
(Phase to earth voltage)
∆V- voltage difference 1V to 40 V, step 0.01 V
(Phase to earth voltage)
≤ ±2.5% setting or ± 1V

30 / 51
Specification
Δf- frequency difference 0.02 to 2.00Hz, step 0.01Hz Equal breaking time 0.10 s~100.00s, step of 0.01 s
(f2>f1; f2<f1)
≤ ±20mHz ≤ ±1% setting or ≤ +50 ms
Δα- angle difference 1 °to 80 °, step of 0.01 ° Disable 0.05s to 100.00 s, step 0.01s
(α2>α1; α2<α1)
≤ ±3° synchronization check ≤ ±1% setting or ≤ +50 ms
Maximum synchronous 0.02s to 100.00 s, step 0.01s time
check broadening time
≤ ±1.5% setting or ≤ +60 ms

Disable synchronization 0.05s to 100.00 s, step 0.01s 97FF, VT secondary circuit


check time ≤ ±1% setting or ≤ +50 ms supervision

Item Data
79, Auto-reclosing
Phase current 0.05 Ir to 1.0 Ir, step 0.01A
Item Data ≤ ±3% setting or ±0.02 Ir
Shots of reclosing 1 to 4 Zero or negative 0.05 Ir to 1.0 Ir, step 0.01A
Reclosing initiated Internal protection startups sequence current ≤ ±5% setting or ±0.02 Ir
inputs External binary input Phase to earth voltage 7.0V to 20.0V, step 0.01V
Dead time for each 0.05s~600.00s, step of 0.01 s ≤ ±3% setting or ± 1 V
shot of reclosing ≤ ±1% setting or ≤ +50 ms Phase to phase voltage 10.0V to 30.0V, step 0.01V
Reclosing 0.10 s~100.00s, step of 0.01 s ≤ ±3% setting or ± 1 V
confirmation time ≤ ±1% setting or ≤ +40 ms Operating phase to 40.0V to 65.0V, step 0.01V
Reclosing charging 0.05 s~100.00s, step of 0.01 s earth voltage ≤ ±3% setting or ± 1 V
time ≤ ±1% setting or +50 ms

31 / 51
Ordering Code
Product type

CSC-103-EB line differential protection IED

Hardware architecture

AR CT/VT Input / BIO/ GOOSE IO

DA SV Input / GOOSE IO

AG CT/VT Input / GOOSE IO

AD CT/VT Input / BIO / SV OUT / GOOSE IO

Language

EC English + Chinese

RE Russian + English + Chinese;

FE French + English + Chinese;

PE Portuguese + English + Chinese;

SE Spain + English + Chinese;

Protocols

X Null

1 IEC61850

2 IEC61870-5-103

3 MODBUS

4 DNP 3.0

Typical function groups of CSC-103

Typical function groups of CSC-103-00201


For 150KV and above,Overhead line or cable, As main protection IED;

87L: Line Differential Protection;


21&21N: Line Distance Protection, Quadrilateral characteristic, Full scheme, 5 zones + 1
extension;
21&21N: Line Distance Protection, MHO characteristic, Full scheme, 5 zones + 1 extension;
68: Power Swing detection;
85 – 21&21N: Tele-protection based on Distance Protection-Contact interface ;
85 – 67N: Tele-protection based on Directional Earth Fault Protection-Contact interface ;
A 50, 51&67: Directional Overcurrent Protection, 4 stages, DT/INVT, Directional element,
composite voltages block, Inrush block;
50N,51N&67N: Directional Earth-Fault Protection, 4 stages, DT/INVT, Directional element,
Inrush block;
46: Negative-Sequence Overcurrent Protection, 4 stages, DT/INVT;
49: Thermal Overload Protection, 3 Stages, 2 of 3 stages for alarm, 1 of 3 stages for tripping,
for cable;
50SOTF: Switch-Onto-Fault Protection, 1 stage, DT;
46BC: Broken Conductor Protection, 1 stage;
97FF: Symmetrical and asymmetrical VT Fuse Fail Detection;

32 / 51
Ordering Code
CTFF: CT-Secondary Current Supervision ;
DR: Disturbance recorder;
FP: Faulty phase indication;
FL: Fault Locator (FL),with parallel line compensation for transmission line;
94-1/3: Single- and/or three-pole tripping logic;

Typical function groups of CSC-103-00202


For 66-132KV, Overhead line or cable, As main protection IED;

87L: Line Differential Protection;


21&21N: Line Distance Protection, Quadrilateral characteristic, Full scheme, 5 zones + 1
extension;
21&21N: Line Distance Protection, MHO characteristic, Full scheme, 5 zones + 1 extension;
68: Power Swing detection;
50, 51&67: Directional Overcurrent Protection, 4 stages, DT/INVT, Directional element,
composite voltages block, Inrush block;
50N,51N&67N: Directional Earth-Fault Protection, 4 stages, DT/INVT, Directional element,
Inrush block;
B 46: Negative-Sequence Overcurrent Protection, 4 stages, DT/INVT;
49: Thermal Overload Protection, 3 Stages, 2 of 3 stages for alarm, 1 of 3 stages for tripping,
for cable;
50SOTF: Switch-Onto-Fault Protection, 1 stage, DT;
46BC: Broken Conductor Protection, 1 stage;
97FF: Symmetrical and asymmetrical VT Fuse Fail Detection;
CTFF: CT-Secondary Current Supervision ;
DR: Disturbance recorder;
FP: Faulty phase indication;
FL: Fault Locator (FL),with parallel line compensation for transmission line;

94-1/3: Single- and/or three-pole tripping logic;

Current protection function group

X No Current protection function group

50, 51&67: Directional Overcurrent Protection, 4 stages, DT/INVT, Directional element,


composite voltages block, Inrush block;
50N,51N&67N: Directional Earth-Fault Protection, 4 stages, DT/INVT, Directional element,
A
Inrush block;
46: Negative-Sequence Overcurrent Protection, 4 stages, DT/INVT;

Voltage protection function group

X No Voltage protection function group

59: Overvoltage Protection, 4 stages, DT/INVT;


A 27: Undervoltage Protection, 4 stages, DT/INVT;

Power protection function group

X No Power protection function group

33 / 51
Ordering Code
32OD: Directional overpower protection, 2 stages, forward/reverse ;
A

Out of step protection function

X Without Out of step protection function

78: Out of step protection;


A

Frequency protection function group

X No Frequency protection function group

81O: Overfrequency, 4 stages;


81U: Underfrequency, 4 stages;
A
81DF: df/dt Protection, 4 stages;

Breaker protection function group

X No Breaker protection function group

50BF: Circuit-Breaker Failure Protection, 2 stages, single/three-pole operating;


A

50BF: Circuit-Breaker Failure Protection, 2 stages, single/three-pole operating;


B 50DZ: Dead Zone Protection/End-fault protection, 1 stage, DT;

50BF: Circuit-Breaker Failure Protection, 2 stages, single/three-pole operating;


50DZ: Dead Zone Protection/End-fault protection, 1 stage, DT;
C
62PD: Pole-Discrepancy Protection, 1 stage, DT;

50BF: Circuit-Breaker Failure Protection, 2 stages, single/three-pole operating;


D 50STB: STUB protection, 1 stage, DT;

Autoreclosing & Synchronization function group

X No Autoreclosing & Synchronization function group

79: Single and/or Three-Pole AutoReclosing, 4 shots;


A

25: Synchro-Check with Live/Dead Line/Bus Measurement ;


B 79: Single and/or Three-Pole AutoReclosing, 4 shots;

25: Synchro-Check with Live/Dead Line/Bus Measurement ;


C

Control function

X No Control function

CB control;
Isolator control;
A Programmable Interlock logic;
Remote/local control switch;

_ 分隔符

Case

34 / 51
Ordering Code
Width of CASE :19" ;
1
Qty. of Slot :17;

Width of CASE :1/2 19";


2
Qty. of Slot :9;

Power Supply

H Voltage range of auxiliary power supply: DC/AC250-110V;

L Voltage range of auxiliary power supply: DC 24-48V;

Communication port for SAS

Application 1:Support optical channel for protection;


RJ45 for SAS:3;
A RS485/IRIG-B:1;
RS485:1;
RS232-Printer port:1;

Application 1:Support optical channel for protection;


RJ45 for SAS:1;
Optical Ethernet port for SAS:2;
RS485/IRIG-B:1;
RS485:1;
RS232-Printer port:1;
B
Type of fiber: Multi mode;
Wave length (nm):1310;
Type of port: LC;
Communication rate (MB/s):100;
Transmitting distance (kM):2;
TD/RD:1/1;

Application 1:Support dual CT input of line;


Application 2:Support optical channel for protection;
RJ45 for SAS:3;
C
RS485/IRIG-B:1;
RS485:1;
RS232-Printer port:1;

Application 1:Support dual CT input of line;


Application 2:Support optical channel for protection;
RJ45 for SAS:1;
Optical Ethernet port for SAS:2;
RS485/IRIG-B:1;
RS485:1;
D
RS232-Printer port:1;
Optical Ethernet port for extension:2;
Type of fiber: Multi mode;
Wave length (nm):1310;
Type of port: LC;
Communication rate (MB/s):100;

35 / 51
Ordering Code
Transmitting distance (kM):2;
TD/RD:1/1;

Communication port 1 for protection

X NULL-Communication port 1 for protection

Qty. of optical Ethernet port for SAS:1;


Qty. of optical Ethernet port for IED connection:1;
Type of fiber: Multi mode;
A Wave length (nm):1310;
Type of port: LC;
Communication rate (MB/s):100;
Transmitting distance (kM):2;

Qty. of optical communication ports for protection:1;


Application: PROT;
Type of fiber: Single Mode;
B Wave length (nm):1310;
Type of port: LC;
Communication rate (MB/s):0.064 to 50;
Transmitting distance (kM):40;

Qty. of optical communication ports for protection:1;


Application: PROT;
Type of fiber: Single Mode;
C Wave length (nm):1310;
Type of port: LC;
Communication rate (MB/s):0.064 to 50;
Transmitting distance (kM):40 to 60;

Qty. of optical communication ports for protection:1;


Application: PROT;
Type of fiber: Single Mode;
D Wave length (nm):1310;
Type of port: LC;
Communication rate (MB/s):0.064 to 50;
Transmitting distance (kM):60 to 120;

Communication port 2 for protecttion

X NULL-Communication port 2 for function

Qty. of optical Ethernet port for SAS:1;


Qty. of optical Ethernet port for IED connection:1;
Type of fiber: Multi mode;
A Wave length (nm):1310;
Type of port: LC;
Communication rate (MB/s):100;
Transmitting distance (kM):2;

36 / 51
Ordering Code
Qty. of optical communication ports for protection:1;
Application: PROT;
Type of fiber: Single Mode;
B Wave length (nm):1310;
Type of port: LC;
Communication rate (MB/s):0.064 to 50;
Transmitting distance (kM):40;

Qty. of optical communication ports for protection:1;


Application: PROT;
Type of fiber: Single Mode;
C Wave length (nm):1310;
Type of port: LC;
Communication rate (MB/s):0.064 to 50;
Transmitting distance (kM):40 to 60;

Qty. of optical communication ports for protection:1;


Application: PROT;
Type of fiber: Single Mode;
D Wave length (nm):1310;
Type of port: LC;
Communication rate (MB/s):0.064 to 50;
Transmitting distance (kM):60 to 120;

Transformer inputs module 1

Ip (1A&5A, 40Ir):5;
1
U (180V,star):4;

2 Im(2Ir) :3;

Ip (1A&5A, 40Ir):6;
3
U (180V,star):3;

Transformer inputs module 2

X NULL-Transformer inputs module 2

Ip (1A&5A, 40Ir):5;
1
U (180V,star):4;

2 Im(2Ir) :3;

Ip (1A&5A, 40Ir):3;
3
U (180V,star):1;

Binary inputs & output module 1

Qty. of BIs with common terminal:6;


Qty. of General output relay C, 1 NO:11;
A
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 110-220V;

37 / 51
Ordering Code
Qty. of BIs with common terminal:6;
Qty. of General output relay C, 1 NO:11;
B
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 24-48V;

Qty. of Power output relay, 1 NO + TCS:1;


Qty. of Power output relay, 1 NO:1;
C Qty. of General output relay A, 2 NO:1;
Qty. of General output relay B, 1 NO + 1 NC:1;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of General output relay C, 1 NO:8;


D
Qty. of General output relay F, 1 NO Latched:7;

Binary inputs & output module 2

5 Blank plate 5TE

Qty. of BIs with common terminal:6;


Qty. of General output relay C, 1 NO:11;
E
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:6;


Qty. of General output relay C, 1 NO:11;
F
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 24-48V;

Qty. of Power output relay, 1 NO + TCS:1;


Qty. of Power output relay, 1 NO:1;
G Qty. of General output relay A, 2 NO:1;
Qty. of General output relay B, 1 NO + 1 NC:1;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:26;


H Qty. of independent BIs :2;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:26;


I Qty. of independent BIs :2;
Voltage range of auxiliary power supply: DC 24-48V;

J Qty. of General output relay C, 1 NO:16;

Qty. of General output relay C, 1 NO:15;


K
Qty. of General output relay D, 1 NO/NC :1;

Binary inputs & output module 3

X Null

5 Blank plate 5TE

Qty. of BIs with common terminal:6;


E
Qty. of General output relay C, 1 NO:11;

38 / 51
Ordering Code
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:6;


Qty. of General output relay C, 1 NO:11;
F
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 24-48V;

Qty. of Power output relay, 1 NO + TCS:1;


Qty. of Power output relay, 1 NO:1;
G Qty. of General output relay A, 2 NO:1;
Qty. of General output relay B, 1 NO + 1 NC:1;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:26;


H Qty. of independent BIs :2;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:26;


I Qty. of independent BIs :2;
Voltage range of auxiliary power supply: DC 24-48V;

J Qty. of General output relay C, 1 NO:16;

Qty. of General output relay C, 1 NO:15;


K
Qty. of General output relay D, 1 NO/NC :1;

Binary inputs & output module 4

X Null

5 Blank plate 5TE

Qty. of BIs with common terminal:6;


Qty. of General output relay C, 1 NO:11;
E
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:6;


Qty. of General output relay C, 1 NO:11;
F
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 24-48V;

Qty. of Power output relay, 1 NO + TCS:1;


Qty. of Power output relay, 1 NO:1;
G Qty. of General output relay A, 2 NO:1;
Qty. of General output relay B, 1 NO + 1 NC:1;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:26;


H Qty. of independent BIs :2;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:26;


I Qty. of independent BIs :2;
Voltage range of auxiliary power supply: DC 24-48V;

39 / 51
Ordering Code
J Qty. of General output relay C, 1 NO:16;

Qty. of General output relay C, 1 NO:15;


K
Qty. of General output relay D, 1 NO/NC :1;

Binary inputs & output module 5

X Null

5 Blank plate 5TE

Qty. of BIs with common terminal:6;


Qty. of General output relay C, 1 NO:11;
E
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:6;


Qty. of General output relay C, 1 NO:11;
F
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 24-48V;

Qty. of Power output relay, 1 NO + TCS:1;


Qty. of Power output relay, 1 NO:1;
G Qty. of General output relay A, 2 NO:1;
Qty. of General output relay B, 1 NO + 1 NC:1;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:26;


H Qty. of independent BIs :2;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:26;


I Qty. of independent BIs :2;
Voltage range of auxiliary power supply: DC 24-48V;

J Qty. of General output relay C, 1 NO:16;

Qty. of General output relay C, 1 NO:15;


K
Qty. of General output relay D, 1 NO/NC :1;

Binary inputs & output module 6

X Null

5 Blank plate 5TE

Qty. of BIs with common terminal:6;


Qty. of General output relay C, 1 NO:11;
E
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:6;


Qty. of General output relay C, 1 NO:11;
F
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 24-48V;

40 / 51
Ordering Code
Qty. of Power output relay, 1 NO + TCS:1;
Qty. of Power output relay, 1 NO:1;
G Qty. of General output relay A, 2 NO:1;
Qty. of General output relay B, 1 NO + 1 NC:1;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:26;


H Qty. of independent BIs :2;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:26;


I Qty. of independent BIs :2;
Voltage range of auxiliary power supply: DC 24-48V;

J Qty. of General output relay C, 1 NO:16;

Qty. of General output relay C, 1 NO:15;


K
Qty. of General output relay D, 1 NO/NC :1;

Binary inputs & output module 7

X Null

5 Blank plate 5TE

Qty. of BIs with common terminal:6;


Qty. of General output relay C, 1 NO:11;
E
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:6;


Qty. of General output relay C, 1 NO:11;
F
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 24-48V;

Qty. of Power output relay, 1 NO + TCS:1;


Qty. of Power output relay, 1 NO:1;
G Qty. of General output relay A, 2 NO:1;
Qty. of General output relay B, 1 NO + 1 NC:1;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:26;


H Qty. of independent BIs :2;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:26;


I Qty. of independent BIs :2;
Voltage range of auxiliary power supply: DC 24-48V;

J Qty. of General output relay C, 1 NO:16;

Qty. of General output relay C, 1 NO:15;


K
Qty. of General output relay D, 1 NO/NC :1;

Binary inputs & output module 8

X Null

41 / 51
Ordering Code
5 Blank plate 5TE

Qty. of BIs with common terminal:6;


Qty. of General output relay C, 1 NO:11;
E
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:6;


Qty. of General output relay C, 1 NO:11;
F
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 24-48V;

Qty. of Power output relay, 1 NO + TCS:1;


Qty. of Power output relay, 1 NO:1;
G Qty. of General output relay A, 2 NO:1;
Qty. of General output relay B, 1 NO + 1 NC:1;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:26;


H Qty. of independent BIs :2;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:26;


I Qty. of independent BIs :2;
Voltage range of auxiliary power supply: DC 24-48V;

J Qty. of General output relay C, 1 NO:16;

Qty. of General output relay C, 1 NO:15;


K
Qty. of General output relay D, 1 NO/NC :1;

Binary inputs & output module 9

X Null

5 Blank plate 5TE

Qty. of BIs with common terminal:6;


Qty. of General output relay C, 1 NO:11;
E
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:6;


Qty. of General output relay C, 1 NO:11;
F
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 24-48V;

Qty. of Power output relay, 1 NO + TCS:1;


Qty. of Power output relay, 1 NO:1;
G Qty. of General output relay A, 2 NO:1;
Qty. of General output relay B, 1 NO + 1 NC:1;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:26;


H Qty. of independent BIs :2;
Voltage range of auxiliary power supply: DC 110-220V;

42 / 51
Ordering Code
Qty. of BIs with common terminal:26;
I Qty. of independent BIs :2;
Voltage range of auxiliary power supply: DC 24-48V;

J Qty. of General output relay C, 1 NO:16;

Qty. of General output relay C, 1 NO:15;


K
Qty. of General output relay D, 1 NO/NC :1;

Binary inputs & output module 10

X Null

5 Blank plate 5TE

Qty. of BIs with common terminal:6;


Qty. of General output relay C, 1 NO:11;
E
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:6;


Qty. of General output relay C, 1 NO:11;
F
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 24-48V;

Qty. of Power output relay, 1 NO + TCS:1;


Qty. of Power output relay, 1 NO:1;
G Qty. of General output relay A, 2 NO:1;
Qty. of General output relay B, 1 NO + 1 NC:1;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:26;


H Qty. of independent BIs :2;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:26;


I Qty. of independent BIs :2;
Voltage range of auxiliary power supply: DC 24-48V;

J Qty. of General output relay C, 1 NO:16;

Qty. of General output relay C, 1 NO:15;


K
Qty. of General output relay D, 1 NO/NC :1;

Binary inputs & output module 11

X Null

5 Blank plate 5TE

Qty. of BIs with common terminal:6;


Qty. of General output relay C, 1 NO:11;
E
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 110-220V;

43 / 51
Ordering Code
Qty. of BIs with common terminal:6;
Qty. of General output relay C, 1 NO:11;
F
Qty. of General output relay D, 1 NO/NC :1;
Voltage range of auxiliary power supply: DC 24-48V;

Qty. of Power output relay, 1 NO + TCS:1;


Qty. of Power output relay, 1 NO:1;
G Qty. of General output relay A, 2 NO:1;
Qty. of General output relay B, 1 NO + 1 NC:1;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:26;


H Qty. of independent BIs :2;
Voltage range of auxiliary power supply: DC 110-220V;

Qty. of BIs with common terminal:26;


I Qty. of independent BIs :2;
Voltage range of auxiliary power supply: DC 24-48V;

J Qty. of General output relay C, 1 NO:16;

Qty. of General output relay C, 1 NO:15;


K
Qty. of General output relay D, 1 NO/NC :1;

Front plate

Width:19" ;
LCD: large;
1 Qty. of LEDs:24;
Qty. Configurable buttons:4;
Type of front test Port:RJ45;

Width:1/2 19";
LCD: Medium;
Qty. of LEDs:24;
2
Qty. CB operating buttons:2;
Qty. Configurable buttons:4;
Type of front test Port:RJ45;

44 / 51
Connection
Typical configure 1

A
B
C

-F CB

a2 X8 X5 a1
*
c2 BO1
IA 5' a2
a4 1' b1
c4 BO2
CSC-103 * a3
a6
IB 5' b2 CT for
c6 BO3
a8
1' b3 * * * protection
c8 BO4 19"/2 CASE * a4
a10 IC 5' a5
BO5 1' b4
c10
a12 * a6
CT for
c12 BO6 3I0 5' b5 * * * measurement
a14 1' b6
c14 BO7 a7
*
a16 I4 5' a8
c16 BO8 1' b7
a18
c18 BO9
* a10 *
a20 UA b10
c20 BO10
* a11 *
a22 UB b11
c22 BO11
* a12 *
a24 UC
BO12 b12
c24
* a9 *
a26 BI1
U4 b9
a28 BI2
a30 BI3
X3 a1
a32 COM- *
c26 BI4 ImA b1
c28 BI5 a3
*
c30 BI6 ImB b3
c32 COM- a4
*
ImC b4
X9
a2 BI1
a4 BI2 X7 a2
BO1 c2
a6 BI3 LINE
a8 BI4 a4
BO2 c4
a10 BI5
a6
a12 BI6 BO3 c6
c2 BI7 a8
c4 BI8 BO4 c8
c6 BI9 a10
c10 BI11 BO5 c10
c12 COM- a12
c14 COM1+ BO6 c12
c16 FAIL1 a14
c18 ALM1 BO7 c14
c20 BO3-1 a16
c22 BO4-1 BO8 c16
a14 COM2+ a18
a16 FAIL2 BO9 c18
a18 ALM2 a20
BO3-2 BO10 c20
a20
a22 BO4-2 a22
BO11 c22
a24 DC+ a32
BO12 c32
a28 DC-
BI1 a26
a32 BI2 a28
GND1 BI3 a30
COM- a32
BI4 c26
BI5 c28
BI6 c30
COM- c32
10 To printer

11
3

7
IRIG-B+ 1

IRIG-B- 2

RS485-A 5
6

RS232-TX 9
X1

RS485-B

RS485-GND

RS232-RX

RS232-GND

1) ETH1/ 2 are RJ45 or FO ,


ETH4
ETH2
RX ETH1

RX ETH2

ETH1

ETH3

RX CHN1

RX CHN2

optional.
2) ETH4 is front interface
TX
TX

TX

TX

for testing.

45 / 51
Connection
Typical configure 2
A
B
C

-F CB

a2 X8 X5
* a1
c2 BO1 5' a2
IA
a4 1' b1
c4 BO2
CSC-103 * a3
a6
IB 5' b2
c6 BO3
1' b3
a8
c8 BO4 19"/2 CASE * a4 CT for
a10 IC 5' a5 * * * protection
BO5 1' b4
c10
a12 * a6
c12 BO6 3I0 5' b5
a14 1' b6
c14 BO7 a7
*
a16 I4 5' a8
c16 BO8 1' b7
a18
c18 BO9
* a10 *
a20 UA b10
c20 BO10
* a11 *
a22 UB b11
c22 BO11
* a12 *
a24 UC
BO12 b12
c24
* a9 *
a26 BI1
U4 b9
a28 BI2
a30 BI3 X4 a2
a32 COM- BO1 c2
c26 BI4 a4
c28 BI5 BO2 c4
c30 BI6 a6
c32 COM- BO3 c6
a8
X9 BO4 c8
a2 BI1 a10
a4 BI2 BO5 c10
a6 BI3 a12
a8 BI4 BO6 c12
a10 BI5 a14
a12 BI6 BO7 c14
c2 BI7 a16
c4 BI8 BO8 c16
c6 BI9 a18
BO9 c18
c10 BI11
a20
c12 COM- BO10 c20
c14 COM1+
FAIL1 a22
c16 BO11
ALM1 c22
c18
BO3-1 a32
c20 BO12
BO4-1 c32
c22
BI1 a26
a14 COM2+
FAIL2 BI2 a28
a16
ALM2 BI3 a30
a18
a20 BO3-2 COM- a32
a22 BO4-2 BI4 c26
BI5 c28
a24 DC+
BI6 c30
a28 DC- COM- c32

a32

GND1

46 / 51
Connection
X1 X7 a2
TX BO1 c2
RX ETH1 a4
IRIG-B+ 1
BO2
TX CSC-103 c4
IRIG-B- 2 a6
RX ETH2 BO3 c6
3 19"/2 CASE a8
BO4 c8
ETH1 4
a10
BO5 c10
RS485-A 5
a12
ETH2 BO6
6 c12
RS485-B
a14
7 BO7 c14
ETH3 RS485-GND
a16
8 BO8 c16
ETH4 a18
RS232-TX 9 BO9 c18
TX 10 To printer a20
RS232-RX BO10
RX CHN1 c20
11 a22
RS232-GND
TX BO11 c22
RX CHN2 a32
BO12 c32
BI1 a26
BI2 a28
1) ETH1/ 2 are RJ45 or FO , BI3 a30
optional. COM- a32
2) ETH4 is front interface BI4 c26
for testing. BI5 c28
BI6 c30
COM- c32

47 / 51
Connection
Typical configure 3
A
B
C

-F CB

a2 X8 X5
* a1
c2 BO1
IA 5' a2
a4 1' b1
c4 BO2
CSC-103 * a3
a6
IB 5' b2 CT for
c6 BO3
a8
1' b3 * * * protection
c8 BO4 19"/2 CASE * a4
a10 IC 5' a5
BO5 1' b4
c10
a12 * a6
CT for
c12 BO6 3I0 5' b5 * * * measurement
a14 1' b6
c14 BO7 a7
*
a16 I4 5' a8
c16 BO8 1' b7
a18
c18 BO9
* a10 *
a20 UA b10
c20 BO10
* a11 *
a22 UB b11
c22 BO11
* a12 *
a24 UC
BO12 b12
c24
* a9 *
a26 BI1
U4 b9
a28 BI2
a30 BI3
X3 a1
a32 COM- *
c26 BI4 ImA b1
c28 BI5 a3
*
c30 BI6 ImB b3
c32 COM- a4
*
ImC b4
X9
a2 BI1
a4 BI2
a6 BI3 LINE
a8 BI4 DC+ DC-
a10 BI5 MK
a12 BI6 X7 c2
c2 BI7 K1 52a TC
a2
c4 BI8 c4
c6 K2
BI9 a4 52b
c10 BI11 K1
K3 K2
c12 COM- a6
c14 COM1+ K3 a8
c16 FAIL1 c8
TCS
c18 ALM1 circuit
c20 BO3-1 R1-1 R1-2 a10
c22 BO4-1
R2-1 a12
a14 COM2+ a16
FAIL2 R2
a16 a14
ALM2 Power
a18 Relay
BO3-2 External
a20 R3-1 R3-2
BO4-2 a18 tripping
a22
R4-1 a20
CC
a24 DC+ a24 52b K86
R4
Power a22
a28 DC- Relay
External
a26
a32 BO1-1 closing
c26
GND1 a28
BO1-2 c28
a30
BO2-1 c30
a32
BO2-2 c32
10 To printer

11
4

8
IRIG-B+ 1

IRIG-B- 2
3

RS485-A 5
6

RS232-TX 9
X1

RS485-B

RS485-GND

RS232-RX

RS232-GND

1) ETH1/ 2 are RJ45 or FO ,


ETH4
RX ETH1

RX ETH2

ETH1

ETH2

ETH3

RX CHN1

RX CHN2

optional.
2) ETH4 is front interface
TX

TX

TX

TX

for testing.

48 / 51
Connection
Typical configure 4
A
B
C

a2 X10 X3
* a1
c2 BO1 5' a2
IA1 CB 1
a4 1' b1
c4 BO2
* a3
a6
CSC-103 IB1 5' b2
c6 BO3
1' b3
a8
BO4 * a4 CT for
c8
a10
19" CASE IC1 5' a5 * * * protection
BO5 1' b4
c10
a12 * a6
c12 BO6 IA2 5' b5
a14 1' b6
LINE 1
c14 BO7 * a7
a16 IB2 5' a8
c16 BO8 1' b7
a18 * a9
c18 BO9 5' b8
IC2
a20 1' b9
c20 BO10
* a10 *
a22 UA b10
c22 BO11
* a11 *
a24 UB
BO12 b11
c24 *
* a12
a26 UC
BO13 b12
c26
a28
c28 BO14 CB 2
a30
c30 BO15
a32
c32 BO16
X5 a1 CT for
*
a2 X11 5' a2 * * * protection
BO1 I01
c2 1' b1
a4 LINE 2
* a3
c4 BO2
I02 5' b2
a6
BO3 1' b3
c6
a8 * a4
U1
*
c8 BO4 b4
a10
* a6
c10 BO5
U2
*
b6
a12
c12 BO6 * a7 CB 3
U3 *
a14 b7
c14 BO7
a16
c16 BO8
a18 C
c18 BO9 B
a20
BO10 X9 a2 A
c20 BO1 c2
a22
BO11 a4
c22 BO2 c4
a24
BO12 a6
c24 BO3 c6
a26
BO13 a8
c26 BO4 c8
a28
BO14 a10
c28
BO5 c10
a30
BO15 a12
c30
BO6 c12
a32
BO16 a14
c32
BO7 c14
a16
BO8 c16
a18
BO9 c18
a20
BO10 c20
a22
BO11 c22
a24
BO12 c24
a26
BO13 c26
a28
BO14 c28
a30
BO15 c30
a32
BO16 c32

49 / 51
Connection
X14 X12 a2
a2 BI1
BO1 c2
a4 BI2
a4
a6 BI3 CSC-103 BO2 c4
a8 BI4 a6
a10 BI5 BO3 c6
a12 BI6 19" CASE a8
a14 BI7 BO4 c8
a16 BI8 a10
a18 BI9 BO5 c10
a20 BI10 a12
a22 BI12 BO6 c12
a26 BI13 a14
BO7 c14
a28 COM-
a16
c2 BI14 BO8 c16
c4 BI15 a18
c6 BI16 BO9 c18
c8 BI17 a20
c10 BI18 BO10 c20
c12 BI19 a22
c14 BI20 BO11 c22
c16 BI21 a24
BO12 c24
c18 BI22
c20 BI23 a26
BO13 c26
c22 BI24
a28
c24 BI25 BO14
c26 BI26 c28
a30
c28 COM- BO15 c30
a30 BI27
a32
a32 COM- BO16 c32
c30 BI28
c32 COM-
X13 a2
BO1 c2
a2 X15 a4
c2 BO1 BO2 c4
a4 a6
c4 BO2 BO3 c6
a6 a8
c6 BO3 BO4 c8
a8 a10
c8 BO4 BO5 c10
a10 a12
c10 BO5 BO6 c12
a12 a14
c12 BO6 BO7 c14
a14 a16
c14 BO7 BO8 c16
a16 a18
c16 BO8 BO9 c18
a18 a20
c18 BO9 BO10 c20
a20 a22
c20 BO10 BO11 c22
a22 a24
c22 BO11 BO12 c24
a24 a26
c24 BO12 BO13 c26
a26 BI1 a28
a28 BI2 BO14 c28
a30 BI3 a30
a32 COM- BO15 c30
c26 BI4 a32
BO16 c32
c28 BI5
c30 BI6
c32 COM-

50 / 51
Connection
X16 X1
a2 BI1 TX
a4 BI2 1 ETH1 RX
IRIG-B+
a6 BI3 CSC-103
2 TX
a8 BI4 IRIG-B- ETH2 RX
a10 BI5 19" CASE 3
a12 BI6
c2 BI7 4 ETH1
c4 BI8
c6 BI9 5 RS485-A
c10 BI11 ETH2
6
c12 COM- RS485-B
c14 COM1+ 7
RS485-GND ETH3
c16 FAIL1
c18 ALM1 8
c20 BO3-1
BO4-1 9 RS232-TX ETH4
c22
a14 COM2+ 10 TX
To printer RS232-RX
a16 FAIL2 CHN1 RX
a18 ALM2 11
RS232-GND
a20 BO3-2 TX
a22 BO4-2 CHN2 RX
a24 DC+

a28 DC-
1) ETH1/ 2 are RJ45 or FO ,
a32 optional.
2) ETH4 is front interface
GND1
for testing.

51 / 51