VRF

Technical
Data Book
DVM S2
(R410A, 50/60Hz, HP)

Model : Energy efficiency / Standard Type


AM***AXVANH*EA
2. Specification
Standard - 50/60Hz
Model Name AM080AXVANH/EA AM100AXVANH/EA AM120AXVANH/EA
Outdoor unit module 1 - - -
Outdoor unit module 2 - - -
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Power Supply Ø, #, V, Hz 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60
Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 8 10 12
Performance Cooling kW 22.4 28.0 33.6
Capacity
Heating kW 25.2 31.5 37.8
Maximum number of connectable indoor units EA 14 18 21

Total capacity of the connected Min. kW 11.2 14.0 16.8


Indoor Units Max. kW 29.1 36.4 43.7
Cooling kW 4.84 6.29 8.77
Power Input
Heating kW 4.80 6.30 8.90
Cooling A 7.60 9.90 13.80
Power Current Input
Heating A 7.50 9.90 14.10
MCA A 19.0 23.0 26.0
Current
MFA A 25 32 32
EER Cooling W/W 4.63 4.45 3.83
Efficiency
COP Heating W/W 5.25 5.00 4.25
Body - GI Steel Plate GI Steel Plate GI Steel Plate
Casing Material
Base - GI Steel Plate GI Steel Plate GI Steel Plate
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Type - Inverter Scroll x 1 Inverter Scroll x 1 Inverter Scroll x 1
Output kW x n 4.60 x 1 6.67 x 1 6.67 x 1

Model Name - DS2GR7046FV* x 1 DS4GR7066FV* x 1 DS4GR7066FV* x 1


Compressor
Type - PVE PVE PVE
Oil
Initial charge cc x n 900 x 1 1,100 x 1 1,100 x 1

Type - Propeller Propeller Propeller


Discharge direction - Top Top Top
Quantity EA 1 1 1
Fan ㎥/min 174 188 205
Air Flow Rate
l/s 2,906 3,138 3,425

External Static mmAq 11 11 8


Max.
Pressure Pa 110 110 80
Type - BLDC Motor BLDC Motor BLDC Motor
Fan Motor
Output Wxn 630 x 1 630 x 1 630 x 1
2. Specification
Standard - 50/60Hz
Model Name AM080AXVANH/EA AM100AXVANH/EA AM120AXVANH/EA
Outdoor unit module 1 - - -
Outdoor unit module 2 - - -
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Type Braze connection Braze connection Braze connection
Liquid Pipe
Φ, ㎜ (inch) 9.52 (3/8) 9.52 (3/8) 12.70 (1/2)
Type Braze connection Braze connection Braze connection
Gas Pipe
Φ, ㎜ (inch) 19.05 (3/4) 22.22 (7/8) 28.58 (1-1/8)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length Max. [Equiv.] m 200[220] 200[220] 200[220]
(ODU-IDU)

Piping Piping length Max. m 90 90 90


(1st Branch-IDU)
Connections
Total piping
Max. m 1,000 1,000 1,000
length (System)
Level difference
(ODU in highest Max. m 110 110 110
position)

Level difference Max. m 110 110 110


(IDU in highest position)

Level difference Max. m 50 50 50


(IDU-IDU)

Transmission Min. ㎟ 0.75 0.75 0.75


Wiring Cable Remark - F1, F2 F1, F2 F1, F2
connections
Both indoor and Both indoor and Both indoor and
Power supply intake -
outdoor unit outdoor unit outdoor unit
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 5.5 5.5 6.2
Sound Pressure (Cooling) dB(A) 55 56 60
Sound
Sound Power (Cooling) dB(A) 75 78 81
Net Weight kg 171 183 187
Shipping Weight kg 185 197 201
External
Dimension Net Dimensions (WxHxD) ㎜ 930 x 1,695 x 765 930 x 1,695 x 765 930 x 1,695 x 765

Shipping Dimensions (WxHxD) ㎜ 998 x 1,887 x 829 998 x 1,887 x 829 998 x 1,887 x 829

Operating Cooling ℃ -5 ~ 50 -5 ~ 50 -5 ~ 50
Temp. Range Heating ℃ -25 ~ 24 -25 ~ 24 -25 ~ 24

NOTE
• Specification may be subject to change without prior notice.
1) Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°CDB, 19°CWB, Outdoor temperature 35°CDB, 24°CWB
- Heating : Indoor temperature 20°CDB, 15°CWB, Outdoor temperature 7°CDB, 6°CWB
- Equivalent refrigerant pipe length 5m, Level differences 0m
2) Performance of Multiple Module Outdoor unit is weighted average of Single Module outdoor units.
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
4. Dimensional Drawing
Outdoor unit

• AM080/100AXVANH/EA Unit: mm (inches)

NOTE

1 Detail A and SECTION B-B indicate the dimension


after fixing the attached piping.
2 Item 3-6: Knock-out hole
3 View C indicate the dimension of knock-out hole
(bottom)
4 Pipe [Ø, mm(inch)]: Brazing connection

HP Liquid pipe Gas pipe


8 9.52(3/8) 19.05(3/4)
10 9.52(3/8) 22.22(7/8)

NO Table of descriptions Remark NO Table of descriptions Remark


1 Gas Ref.pipe See NOTE 4. 5 Knock-out Hole for Ref.Piping (bottom)
2 Liquid Ref.pipe See NOTE 4. 6 Knock-out Hole for Ref.Piping (front)
3 Power wiring conduit Ø44
4 Communication wiring conduit Ø34
Page 1 of 2
SUBMITTAL AM048JNCDCH/AA
Samsung DVM S Series, Ceiling Mounted, Indoor Unit

Job Name Location


Purchaser Engineer
Submitted to Reference Approval Construction
Unit Designation Schedule #

Specifications
Nominal Cooling (Btu/h) 48,000
Performance
Capacity 1 Heating (Btu/h) 54,000

Voltage (ø/V/Hz) 1 / 208 - 230 / 60


Current Input Cooling/Heating (A) 1.45 / 1.45
Power
MCA 1.4 • Compatible with Samsung DVM S, DVM S Water, and DVM Eco
MOP 15 systems (AM**********AA).

Type • Washable electro-static filter as standard (included with unit)


Sirocco X 4
Fan Type BLDC • High-voltage terminal block temperature sensor to disable unit in
Motor the event overheating of power connection.
Output (W) 355 X 1
• Power and pipe connections are easily accessible from one side
Airflow CFM (UL) L/M/H 918/ 1,088 / 1,286 of the unit for simple installation and service.

Type R410A • Powerful air throw for large areas


Refrigerant
Control Method Electronic Expansion Valve • Fresh air inlet to allow simple introduction of outside air.

Liquid (flare) Inches 3/8 Construction


Piping HIPS chassis certified to UL94 V0 with a galvanized steel base.
Suction (flare) Inches 5/8
Connections
Heat Exchanger
Drain Inches VP25 (OD 1 1/4, ID 1)
The heat exchanger shall be mechanically bonded fin to copper
tube
Unit WXHXD Inches 64 15/16 X 9 1/4 X 26 9/16
Dimensions Weight lbs. 93.7 Indoor Fan
Indoor fan shall be sirocco type (4)
Sound Level L/M/H dB 38 / 43 / 46
Three fan speed settings and auto setting
External Temperature Sensor MRW-TA Controls
External Contact Control MIM-B14 The unit shall be operated via a wireless or wired remote control
with DDC type signal
Wireless Controller AR-EH03U
Accessories
Aspen Maxi Orange ASP-MAXO-UNIV The unit shall integrate with the Samsung NASA Controls Network
Condensate
Solution
Pump Blue Diamond BD-BLUE230
Controls shall integrate with a BMS system
CN83 Pigtail (for external float switch connection) DB39-01263A
Control wiring shall be 2 X 16 AWG shielded wire
Safety Certifications ETL (UL 1995)
1
Nominal cooling capacities are based on: Indoor temperature: 80 ⁰F DB, 67⁰F WB. Outdoor temperature: 95⁰F DB, 75⁰F WB.
Nominal heating capacities are based on: Indoor temperature: 70 ⁰F DB, 60⁰F WB. Outdoor temperature: 47⁰F DB, 43⁰F WB.
Samsung HVAC maintains a policy of ongoing development, specifications are subject to change without notice.

www.SamsungHVAC.com
© 2021 Samsung HVAC
SHA-DVMS-03302021 888-699-6067
Page 2 of 2
SUBMITTAL AM048JNCDCH/AA
Samsung DVM S Series, Ceiling Mounted, Indoor Unit

64 15/16"
26 9/16"

10 11/16"
9 1/4"
60 7/16"

10 1/4"

 

6 11/16"
1" 62 15/16"

No. Name No. Name


1 Gas Pipe Opening 5 Air Inlet
2 Liquid Pipe Opening 6 Discharge Air
3 Drain Pipe Opening 7 Suspension Hook
4 Conduit Opening 8 Fresh Air Inlet (4")

www.SamsungHVAC.com
20/03/2023 1

Submittal MWR-SH11N Wired remote controller Latin America

Job Name Location


Purchaser Engineer
Submitted to Reference Approval Construction

Specifications
Model MWR-SH11N
Features Type Wired remote controller

Features
• Internal temperature sensor

• Backlight

• Built‐in infrared receiver to allow control of indoor unit wirelessly with AR‐EH03U or AR‐KH03U wireless controllers

• Indoor unit operation ON/OFF, operation mode, set temperature, louver position (cassette, ceiling, wall units), and fan
speed settings

Specifications
Specifications
• Error display
• Compatible with Samsung DVM S Systems (AM****X****/**,
AM0***XMDCH/**) and CAC systems (AC0***X**CH/**) only.
• Filter replacement alarm display and reset
• Can connect and control up to 16 indoor units on a single system or
across multiple systems (group control)
• Single indoor unit control or multiple unit control (maximum 16 units)
• 2 Conductor connection
• DC 12V power supplied by indoor unit
• All button lock (option)
• PLC (power line communication) is done on F3/F4 terminals.
• MWR‐SH11N has screw terminals for all wiring connections, wire is
• Partial controller button lock (ON/OFF, temperature setting, fan speed, timer function, louver swing, sleep function, quiet
not included
function, outing function, and operation mode buttons)
• 16 AWG X 2 shielded cable is necessary for proper operation
• Maximum wire length: 328' from MWR‐SH11N to farthest indoor unit.
• Upper and lower temperature setting restriction

• Heat, cool, dry, fan, and auto mode skip options (skips specified mode on wired controller)

• Restrict wireless controller signal (optional)

• Single event timer function (ON/OFF control, 30 minutes ‐ 24 hours timer setting options)

• System/indoor unit function and operation indication (defrost, error, restricted controller, central control, and SPi status)

• Service mode for connected indoor unit operation monitoring, addressing, and setup

• Can be used to specify "Mode Master" while connected to a single indoor unit when used with heat pump systems to
control system mode (heating or cooling)

• Outing function to keep a minimum heating (61~72°F) and cooling (77~86°F) temperature while you are away. When Outing
mode is activated, the unit will operate at the specified Outing temperature.
If indoor temperature is 9°F difference from desired Outing temperature, the indoor unit will turn on. If indoor temperature is
the same as desired Outing temperature, the indoor unit will turn off automatically. This is repeated depending on indoor
temperature for 12 hours. After 12 hours, Outing mode is released /canceled.

• Wind‐FreeTM Control (applies to supported models when using


the Wind‐FreeTM fascia panel)

• Long Reach Function (applies to supported models when using


the Wind‐FreeTM fascia panel)

English 1

Samsung maintains a policy of ongoing development, specifications are subject to change without notice.
20/03/2023 2

Submittal MWR-SH11N Wired remote controller Latin America

Specifications

English 2

Samsung maintains a policy of ongoing development, specifications are subject to change without notice.
25/07/2024 1

Submittal MXJ-YA1509M Y-joint Latin America

Job Name Location


Purchaser Engineer
Submitted to Reference Approval Construction

Specifications
Model MXJ-YA1509M
Features Type Y-joint

• Required component for Samsung DVM S and DVM Eco systems (AM****X****/**) with multiple evaporators and/or
Mode Change Units (MCU)
• Constructed of brazed copper or brass and copper
• Indoor unit Y-joint models include both liquid and suction fittings, insulation, and ties to secure insulation
• Heat recovery (HR) Y-joint models are required for branching the hot gas pipe throughout heat recovery systems (HR
systems only)
• Included insulation shall be polystyrene certified to UL94 V0, 5/8" wall thickness
• Inlet pipe shall be adjustable to facilitate different pipe sizes without having to braze additional fittings MWR-W
• Each model shall include adjustable reducers as noted in the table below

Specifications

English 1

Samsung maintains a policy of ongoing development, specifications are subject to change without notice.
25/07/2024 2

Submittal MXJ-YA1509M Y-joint Latin America

Specifications

English 2

Samsung maintains a policy of ongoing development, specifications are subject to change without notice.