scb-ul-791060701.1

Download as pdf or txt
Download as pdf or txt
You are on page 1of 23

Sponsor:

ROCKWOOL Limited
Pencoed
Bridgend
CF35 6NY
United Kingdom
www.rockwool.com

Prepared by:
UL International (UK) Ltd

Approved body No.:


0843

Product Name:
ROCKWOOL® SCB (Sleeved Cavity Barrier)

Project No.:
4791060701.1

Report No.:
4791060701.1-01

Issue number:
01

Date of Issue:
8th May 2024

Copyright © 2024 UL LLC.

UL International (UK) Ltd.


220, Cygnet Court, Centre Park, Warrington. WA1 1PP

This classification report consists of twenty-three pages and may only be used or reproduced in its
entirety.

4705
Report No.: 4791060701.1-01 Page 2

TABLE OF CONTENTS

1. Introduction .............................................................................................................................................. 3
2. Details of classification product ................................................................................................................ 3
3. Test reports in support of classification.................................................................................................... 3
4. Classification and field of application ....................................................................................................... 7
5. Limitations............................................................................................................................................... 23
6. Signatories............................................................................................................................................... 23
Report No.: 4791060701.1-01 Page 3

1. Introduction

This classification report defines the classification assigned to the element ROCKWOOL® SCB, in
accordance with the procedures given in BS EN 13501-2: 2016.

2. Details of classification product

2.1 General

The element, ROCKWOOL® SCB, is defined as a fire resisting linear joint seal to be used to seal joints,
voids, gaps or other discontinuities within one or between two or more construction elements.

ROCKWOOL® SCB is manufactured from non-combustible stone wool, encapsulated within a resilient
polythene sleeve which eliminates the need for weather protection during installation. The SCB’s are
designed for both vertical and horizontal installations within a range of supporting constructions. The
sleeves are installed under a compression fit of 10mm.

2.2 Product description

The element, ROCKWOOL® SCB, is fully described in the test reports provided in support of
classification detailed in clause 3.1.

3. Test reports in support of classification

3.1 Summary of test reports

Wall Tests

Name of Test
Name of laboratory Test Date Test method
sponsor Reference
Warringtonfire Testing and
Rockwool BS EN 1366-4
Certification Limited - 521258/R 24/11/2022
Limited 2021
Notified Body No. 1121
Warringtonfire Testing and
Rockwool BS EN 1366-4
Certification Limited - 521533/R 16/11/2022
Limited 2021
Notified Body No. 1121
Warringtonfire Testing and
Rockwool BS EN 1366-4
Certification Limited - 535662/R 30/08/2023
Limited 2021
Notified Body No. 1121
Warringtonfire Testing and
Rockwool BS EN 1366-4
Certification Limited - 535150/R 23/08/2023
Limited 2021
Notified Body No. 1121
Report No.: 4791060701.1-01 Page 4

Floor Tests

Name of Test
Name of laboratory Test Date Test method
sponsor Reference
Warringtonfire Testing and
Rockwool BS EN 1366-4
Certification Limited - 522758/R 11/09/2022
Limited 2021
Notified Body No. 1121
Warringtonfire Testing and
Rockwool BS EN 1366-4
Certification Limited - 521533/R 16/11/2022
Limited 2021
Notified Body No. 1121
Warringtonfire Testing and
Rockwool BS EN 1366-4
Certification Limited - 521529/R 30/09/2022
Limited 2021
Notified Body No. 1121
Warringtonfire Testing and
Rockwool BS EN 1366-4
Certification Limited - 537524/R 27/10/2023
Limited 2021
Notified Body No. 1121
Report No.: 4791060701.1-01 Page 5

3.2 Results

Summary of report No.: WF No. 521258/R

A fire resistance test in accordance with BS EN 1366-4: 2021, on wall mounted cavity barrier systems.

Integrity (minutes) Insulation


Specimen
Cotton pad Sustained flames (minutes)
A 69 69 54
B 69 69 55
C 46 46 46
D 69 69 57
E 69 69 58

Summary of report No.: WF No. 521533/R

A fire resistance test in accordance with BS EN 1366-4: 2021, on both wall mounted and floor mounted
cavity barrier systems.

Integrity (minutes) Insulation


Specimen
Cotton pad Sustained flames (minutes)
A 91 91 76
B 91 91 73
C 91 91 91
D 91 91 59
E 91 91 77
F 85 85 39
G 86 86 49
H 91 91 48
I 91 91 12

Summary of report No.: WF No. 535662/R

A fire resistance test in accordance with BS EN 1366-4: 2021, on wall mounted cavity barrier systems.

Integrity (minutes) Insulation


Specimen
Cotton pad Sustained flames (minutes)
A 145 145 145
B 145 145 145
C 142 142 127
Report No.: 4791060701.1-01 Page 6

Summary of report No.: WF No. 535150/R

A fire resistance test in accordance with BS EN 1366-4: 2021, on wall mounted cavity barrier systems.

Integrity (minutes) Insulation


Specimen
Cotton pad Sustained flames (minutes)
A 132 132 132
B 132 132 132
C 132 132 132
D 113 113 113
E 132 132 132
F 132 132 103
G 132 132 132

Summary of report No.: WF No. 522758/R

A fire resistance test in accordance with BS EN 1366-4: 2021, on floor mounted cavity barrier systems.

Integrity (minutes) Insulation


Specimen
Cotton pad Sustained flames (minutes)
A 23 25 18
B 25 25 25
C 66 66 26
D 66 66 30
E 66 66 33
F 66 66 35
G 66 66 20

Summary of report No.: WF No. 521529/R

A fire resistance test in accordance with BS EN 1366-4: 2021, on floor mounted cavity barrier systems.

Integrity (minutes) Insulation


Specimen
Cotton pad Sustained flames (minutes)
A 132 132 50
B 132 132 44
C 132 132 32
D 93 93 22
E 69 69 39
F 93 93 9
G 123 123 16
Report No.: 4791060701.1-01 Page 7

Summary of report No.: WF No. 537524/R

A fire resistance test in accordance with BS EN 1366-4: 2021, on floor mounted cavity barrier systems.

Integrity (minutes) Insulation


Specimen
Cotton pad Sustained flames (minutes)
A 132 132 49
B 118 132 55

4. Classification and field of application

4.1 Reference of classification

This classification has been carried out in accordance with Clause 7 of EN 13501-2:2016.

4.2 Classification

The element, ROCKWOOL® SCB is classified according to the following combinations of performance
parameters and classes as appropriate.

R E I W t t - M C S IncSlow sn ef r
Report No.: 4791060701.1-01 Page 8

Considering the tests submitted for classification, ROCKWOOL® SCB provides the following classification
for the tested seal type:

Horizontally oriented ROCKWOOL® SCB in 50 – 100 mm wide cavities

Product: ROCKWOOL® SCB - 110mm

1. ROCKWOOL® SCB
2. AAC Concrete
3. 9mm thick OSB board
4. 9mm thick Cement particle board
Horizontally oriented ROCKWOOL® SCB - 110mm
Thickness Compression
Element of construction Classification
of Product (Minimum)
E 120 – H – X – F – W 50 to W 100
110 mm 10mm Aerated concrete / Aerated concrete
EI 45 – H – X – F – W 50 to W 100
E 60 – H – X – F – W 50 to W 100
110 mm 10mm Aerated concrete / Timber (OSB)
EI 45 – H – X – F – W 50 to W 100
E 90 – H – X – F – W 50 to W 100
110 mm 10mm Aerated concrete / SFS (CP board)
EI 45 – H – X – F – W 50 to W 100
ROCKWOOL® SCB compress fitted into the gap/joint, with a minimum compression as shown above.
Report No.: 4791060701.1-01 Page 9

Horizontally oriented ROCKWOOL® SCB in 101 – 290 mm wide cavities

Product: ROCKWOOL® SCB - 110mm

1. ROCKWOOL® SCB
2. AAC Concrete
3. 9mm thick OSB board
4. 9mm thick Cement particle board
5. 50mm thick stone mineral wool insulation (60kg/m3)
Horizontally oriented ROCKWOOL® SCB - 110mm
Thickness Compression
of Product (Minimum) Element of construction Classification

E 60 – H – X – F – W 101 to W 290
110 mm 10 mm Aerated concrete / Aerated concrete
EI 30 – H – X – F – W 101 to W 290
E 120 – H – X – F – W 101 to W 290
110 mm 10 mm Aerated concrete / Timber OSB*
EI 45 – H – X – F – W 101 to W 290
E 60 – H – X – F – W 101 to W 290
110 mm 10 mm Aerated concrete / SFS (CP board)
EI 20 – H – X – F – W 101 to W 290
ROCKWOOL® SCB compress fitted into the gap/joint, with a minimum compression as shown above.
*Minimum 50 mm thick stone mineral wool insulation with a minimum density of 60 kg/m3 installed above
and below the cavity barrier adjacent to the OSB board, continuing a minimum of 190 mm above the cavity
and 350 mm below the cavity.
Report No.: 4791060701.1-01 Page 10

Horizontally oriented ROCKWOOL® SCB in 50 – 290 mm wide cavities

Product: ROCKWOOL® SCB - 150mm

1. ROCKWOOL® SCB
2. AAC Concrete
3. 9mm thick OSB board
4. 9mm thick Cement particle board
5. 50mm thick stone mineral wool insulation (60kg/m3)
Horizontally oriented ROCKWOOL® SCB - 150mm
Thickness Compression
Element of construction Classification
of Product (Minimum)
E 60 – H – X – F – W 50 to W 290
150 mm 10 mm Aerated concrete / Aerated concrete
EI 30 – H – X – F – W 50 to W 290
E 90 – H – X – F – W 50 to W 290
150 mm 10 mm Aerated concrete / OSB*
EI 45 – H – X – F – W 50 to W 290
E 60 – H – X – F – W 50 to W 290
150 mm 10 mm Aerated concrete / SFS (CP board)
EI 30 – H – X – F – W 50 to W 290
ROCKWOOL® SCB compress fitted into the gap/joint, with a minimum compression as shown above.
*Minimum 50 mm thick stone mineral wool insulation with a minimum density of 60 kg/m3 installed above
and below the cavity barrier adjacent to the OSB board, continuing a minimum of 150 mm above the cavity
and 350 mm below the cavity.
Report No.: 4791060701.1-01 Page 11

Vertically oriented ROCKWOOL® SCB in 50 – 55 mm wide cavities

Product: ROCKWOOL® SCB - 65mm

1. ROCKWOOL® SCB
2. AAC Concrete
3. 9mm thick OSB board
4. 9mm thick Cement particle board
Vertically oriented ROCKWOOL® SCB - 65mm
Thickness Compression
Element of construction Classification
of Product (Minimum)
E 90 – V – X – F – W 50 to W 55
65 mm 10 mm Aerated concrete / Aerated concrete
EI 60 – V – X – F – W 50 to W 55
E 90 – V – X – F – W 50 to W 55
65 mm 10 mm Aerated concrete / Timber (OSB)
EI 60 – V – X – F – W 50 to W 55
E 90 – V – X – F – W 50 to W 55
65 mm 10 mm Aerated concrete / SFS (CP board)
EI 60 – V – X – F – W 50 to W 55
ROCKWOOL® SCB compress fitted into the gap/joint, with a minimum compression as shown above.
Report No.: 4791060701.1-01 Page 12

Vertically oriented ROCKWOOL® SCB in 56 – 100 mm wide cavities

Product: ROCKWOOL® SCB - 110mm

1. ROCKWOOL® SCB
2. AAC Concrete
3. 9mm thick OSB board
4. 9mm thick Cement particle board
5. 50mm thick stone mineral wool insulation (60kg/m3)
Vertically oriented ROCKWOOL® SCB - 110mm
Thickness Compression
Element of construction Classification
of Product (Minimum)
E 90 – V – X – F – W 56 to W 100
110 mm 10mm Aerated concrete / Aerated concrete
EI 45 – V – X – F – W 56 to W 100
110 mm 10mm Aerated concrete / Timber (OSB) EI 45 – V – X – F – W 56 to W 100

E 60 – V – X – F – W 56 to W 100
110 mm 10mm Aerated concrete / SFS (CP board)*
EI 45 – V – X – F – W 56 to W 100
ROCKWOOL® SCB compress fitted into the gap/joint, with a minimum compression as shown above.
*Minimum 50 mm thick stone mineral wool insulation with a minimum density of 60 kg/m3 continuing a
minimum of 195mm from the unexposed face of the cavity barrier adjacent to the OSB board.
Report No.: 4791060701.1-01 Page 13

Vertically oriented ROCKWOOL® SCB in 101 – 290 mm wide cavities

Product: ROCKWOOL® SCB - 110mm

6. ROCKWOOL® SCB
7. AAC Concrete
8. 9mm thick OSB board
9. 9mm thick Cement particle board
10. 50mm thick stone mineral wool insulation (60kg/m3)
Vertically oriented ROCKWOOL® SCB - 110mm
Thickness Compression
Element of construction Classification
of Product (Minimum)
E 60 – V – X – F – W 101 to W 290
110 mm 10 mm Aerated concrete / Aerated concrete
EI 45 – V – X – F – W 101 to W 290
110 mm 10 mm Aerated concrete / Timber (OSB) EI 45 – V – X – F – W 101 to W 290
E 60 – V – X – F – W 101 to W 290
110 mm 10 mm Aerated concrete / SFS (CP board)*
EI 45 – V – X – F – W 101 to W 290
ROCKWOOL® SCB compress fitted into the gap/joint, with a minimum compression as shown above.
*Minimum 50 mm thick stone mineral wool insulation with a minimum density of 60 kg/m3 continuing a
minimum of 195mm from the unexposed face of the cavity barrier adjacent to the OSB board.
Report No.: 4791060701.1-01 Page 14

Vertically oriented ROCKWOOL® SCB in 101 – 290 mm wide cavities

Product: ROCKWOOL® SCB - 150mm

1. ROCKWOOL® SCB
2. AAC Concrete
3. 9mm thick OSB board
4. 9mm thick Cement particle board
Vertically oriented ROCKWOOL® SCB - 150mm
Thickness Compression
Element of construction Classification
of Product (Minimum)
E 60 – V – X – F – W 101 to W 290
150 mm 10 mm Aerated concrete / Aerated concrete
EI 45 – V – X – F – W 101 to W 290
150 mm 10 mm Aerated concrete / Timber (OSB) EI 45 – V – X – F – W 101 to W 290

E 60 – V – X – F – W 101 to W 290
150 mm 10 mm Aerated concrete / SFS (CP board)
EI 45 – V – X – F – W 101 to W 290
ROCKWOOL® SCB compress fitted into the gap/joint, with a minimum compression as shown above.
Report No.: 4791060701.1-01 Page 15

Vertically oriented ROCKWOOL® SCB in 50 – 60 mm wide cavities

Product: ROCKWOOL® SCB - 200mm

1. ROCKWOOL® SCB
2. AAC Concrete
3. 9mm thick OSB board
4. 50mm thick stone mineral wool insulation (60kg/m3)
Vertically oriented ROCKWOOL® SCB - 200mm
Thickness Compression
Element of construction Classification
of Product (Minimum)
200 mm 5 mm Aerated concrete / Aerated concrete EI 120 – V – X – F – W 50 to W 60

200 mm 5 mm Aerated concrete / 60kg Stone mineral


EI 120 – V – X – F – W 50 to W 60
wool over timber (OSB)
200 mm 10 mm Aerated concrete / Timber (OSB) EI 120 – V – X – F – W 50 to W 55
ROCKWOOL® SCB compress fitted into the gap/joint, with a minimum compression as shown above.
Report No.: 4791060701.1-01 Page 16

Vertically oriented ROCKWOOL® SCB in 61 – 150 mm wide cavities

Product: ROCKWOOL® SCB - 200mm

1. ROCKWOOL® SCB
2. AAC Concrete
3. 50mm thick stone mineral wool insulation (60kg/m3)
Vertically oriented ROCKWOOL® SCB - 200mm
Thickness Compression
Element of construction Classification
of Product (Minimum)
200 mm 10 mm Aerated concrete / Aerated concrete EI 120 – V – X – F – W 61 to W 150
200 mm 10 mm Aerated concrete / Aerated concrete* EI 120 – V – X – F – W 61 to W 150
ROCKWOOL® SCB compress fitted into the gap/joint, with a minimum compression as shown above.
*Minimum 50 mm thick stone mineral wool insulation with a minimum density of 60 kg/m3 installed to both
faces of the cavity barrier adjacent to the OSB board, continuing through the cavity.
Report No.: 4791060701.1-01 Page 17

Vertically oriented ROCKWOOL® SCB in 56 – 150 mm wide cavities

Product: ROCKWOOL® SCB - 200mm

1. ROCKWOOL® SCB
2. AAC Concrete
3. 9mm thick OSB board
4. 12mm thick Cement particle board
5. 50mm thick stone mineral wool insulation (60kg/m3)
Vertically oriented ROCKWOOL® SCB - 200mm
Thickness Compression
Element of construction Classification
of Product (Minimum)
200 mm 10 mm Aerated concrete / SFS (CP Board)* EI 120 – V – X – F – W 56 to W 150
200 mm 10 mm Aerated concrete / Timber (OSB)** EI 120 – V – X – F – W 56 to W 150
ROCKWOOL® SCB compress fitted into the gap/joint, with a minimum compression as shown above.
*Minimum 50 mm thick stone mineral wool insulation with a minimum density of 60 kg/m3 installed to both
faces of the cavity barrier adjacent to the OSB board, continuing through the cavity.
**Minimum 100 mm thick stone mineral wool insulation with a minimum density of 60 kg/m3 installed to
both faces of the cavity barrier adjacent to the OSB board, continuing through the cavity.
Report No.: 4791060701.1-01 Page 18

Vertically oriented ROCKWOOL® SCB in 151 – 190 mm wide cavities

Product: ROCKWOOL® SCB - 200mm

1. ROCKWOOL® SCB
2. AAC Concrete
3. 12mm thick Cement particle board
4. 50mm thick stone mineral wool insulation (60kg/m3)
Vertically oriented ROCKWOOL® SCB - 200mm
Thickness Compression
Element of construction Classification
of Product (Minimum)
E 120 – V – X – F – W 151 to W 190
200 mm 10 mm Aerated concrete / Aerated concrete
EI 90 – V – X – F – W 151 to W 190
200 mm 10 mm Aerated concrete / SFS (CP Board)* EI 120 – V – X – F – W 151 to W 190
ROCKWOOL® SCB compress fitted into the gap/joint, with a minimum compression as shown above.
*Minimum 100 mm thick stone mineral wool insulation with a minimum density of 60 kg/m3 installed to
both faces of the cavity barrier adjacent to the OSB board, continuing through the cavity.
Report No.: 4791060701.1-01 Page 19

4.3 Field of Application – Linear Joint and Gap Seals

This classification is valid for the following end use applications (as defined in EN1366-4: 2021,
referencing the following appropriate clauses of EN1366-4: 2021).

13.1 Orientation

The field of application regarding the orientation of the linear joint is given in Table 2. The possible orientation
of linear joints (A to E) and of the specimens in the test (A to C) is illustrated in Figure 28.

Table 2 – Field of direct application regarding orientation

Table 2 only applies when both the supporting construction and the location of the seal within the linear joint
remain unchanged. See 13.3.
Report No.: 4791060701.1-01 Page 20

13.2 Supporting construction


Results obtained with autoclaved aerated concrete standard supporting constructions apply to aerated
concrete, concrete, blockwork and masonry separating elements of a thickness and density equal to or greater
than tested.

Test results obtained on a specific non-standard supporting construction apply only to that particular
construction.
Report No.: 4791060701.1-01 Page 21

13.3 Seal position


Test results are valid only for the position (see Figure 17) in which the seal was tested, except that where the
linear joint seal was fitted flush with the surface of the supporting construction and is exposed to the fire (see
Figure 17, position 2), the result may also be applied to linear joint seals with positions 3 and 5.
Report No.: 4791060701.1-01 Page 22

13.5 Dimensions
Linear joint seal made of mineral wool (faced)

The results of a seal compressed in the A<>A direction (see Figure 4) cover smaller joint width, provided the
degree of compression (%) exerted on the seal is equal to or greater than that used in the test.

The results of a seal compressed in the B<>B or C<>C directions (see Figure 4) cover smaller joint width and/or
higher compression, provided the compression applied is not sufficient to induce a mechanical failure of the
seal e.g. a de-lamination fracture of the mineral wool or facing.

The depth of a seal may be increased but not decreased.

In non-movement joints the density of the mineral wool may be increased.

If more than one layer of mineral wool strips has been used in the test the number of layers may be reduced
but not increased, provided the degree of compression (%) exerted on the seal is equal to or greater than that
used in the test.
Report No.: 4791060701.1-01 Page 23

5. Limitations

This classification report does not represent type approval or certification of the product.

6. Signatories

Report by: Reviewed by:

Chris Sweeney Chris Johnson


Project Engineer Senior Staff Engineer
Built Environment Built Environment

For and on behalf of UL International (UK) Ltd.