esm4410
esm4410
esm4410
Installation:
In this section, physical dimensions of the device, panel mounting, electrical wiring are
explained.
In this section, user interface of the device, how to access to the parameters, description
of the parameters are explained.
Control Algorithm:
Also in these sections, there are warnings to prevent serious injury while doing the
physical and electrical mounting or using the device.
Explanation of the symbols which are used in these sections are given below.
c This symbol is used for safety warnings. User must pay attention to these
warnings.
a
This symbol is used to determine the dangerous situations as a result of an electric
shock. User must pay attention to these warnings definitely.
i
This symbol is used to determine the important notes about functions and usage of
the device.
2.INSTALLATION.................................................................................................................................... Page 7
2.1 GENERAL DESCRIPTION
2.2 FRONT VIEW AND DIMENSIONS OF ESM-4410 TEMPERATURE CONTROLLER
2.3 PANEL CUT-OUT
2.4 ENVIRONMENTAL RATINGS
2.5 PANEL MOUNTING
2.6 INSTALLATION FIXING CLAMP
2.7 REMOVING FROM THE PANEL
5.PARAMETERS.................................................................................................................................... Page 27
5.1 SET PARAMETER
5.2 PROGRAM PARAMETERS
8.SPECIFICATIONS................................................................................................................................Page 30
Manufacturer Company Address: DOSAB, Karanfil Sokak, No:6, 16369 Bursa, Turkiye
The manufacturer hereby declares that the product conforms to the following
standards and conditions.
Product Category : Electrical equipment for measurement, control and laboratory use
EN 61010-1:2001 Safety Requirements for electrical equipment for measurement, control and
laboratory use
Standard
ESM-4410 230 V V (±%15) , 50/60 Hz
NTC
PTC
Temperature Input J or K Type TC
2 or 3 wire PT 100
Standard
Heating or Cooling
Output (Relay Control Output
Function
Output) Alarm Output
ON/OFF Operation
c
19 NTC (Note-1) -19.9°C 99.9°C
Z Þ Vdc,
Note-1 : If input type is selected PTC or NTC (BC = 12, 15, 18, 19 ),
Temperature sensor is given with the device. For this reason, W Þ Vacdc
If input type is selected as PTC, sensor type (V = 0,1 or 2) or
If input type is selected as NTC, sensor type (V = 0,3 or 4) must be
declared in ordering information.
E Output-1
1 Relay Output(7 A@250 V at resistive load, 1NO)
FG Output-2
00 None
4 NTC-M6L50.K1.5 (1.5
NTC Probe, stainless steel housing with
m cable for cooling application)
9 Customer
1.3 Warranty
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts from
the delivery date. This warranty is in force if duty and responsibilities which are determined in
warranty document and instruction manual performs by the customer completely.
1.4 Maintenance
Repairs should only be performed by trained and specialized personnel. Cut power to the device
before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of
these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl
alcohol or water to clean the external plastic case.
c
Before beginning installation of this product, please read the instruction
manual and warnings below carefully.
In package ,
- One piece unit
- Two pieces mounting clamps
- One piece instruction manual
A visual inspection of this product for possible damage occured during shipment is
recommended before installation. It is your responsibility to ensure that qualified
mechanical and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit, power
off the system and separate the electrical connection of the device from the system.
The unit is normally supplied without a power switch or a fuse. Use power switch and fuse
as required.
Be sure to use the rated power supply voltage to protect the unit against damage and to
prevent failure.
Keep the power off until all of the wiring is completed so that electric shock and trouble
with the unit can be prevented.
Never attempt to disassemble, modify or repair this unit. Tampering with the unit may
results in malfunction, electric shock or fire.
During the equipment is putted in hole on the metal panel while mechanical installation
some metal burrs can cause injury on hands, you must be careful.
Montage of the product on a system must be done with it’s own fixing clamps. Do not do
the montage of the device with inappropriate fixing clamps. Be sure that device will not fall
while doing the montage.
ESM-4
410
Mounting Clamp
Front Panel
IP65 protection
NEMA 4X Panel surface
(maximum thickness 5 mm / 0.2 inch)
ESM-4410
48 mm/ 1.89 inch
OUT PROG
SET
SET
P
Operating Conditions
Operating Temperature : 0 to 50 °C
Altitude : Up to 2000 m.
c
Forbidden Conditions:
Corrosive atmosphere
Explosive atmosphere
Home applications (The unit is only for industrial applications)
During installation into a metal panel, care should be taken to avoid injury from
c
metal burrs which might be present. The equipment can loosen from vibration
and become dislodged if installation parts are not properly tightened. These
precautions for the safety of the person who does the panel mounting.
10
1
2 The unit is designed for panel
mounting.
c
Montage of the unit to a system must be done with it’s own fixing clamps. Do
not do the montage of the device with inappropriate fixing clamps. Be sure
that device will not fall while doing the montage.
c
Before starting to remove the unit from panel, power off the unit and the
related system.
11
You must ensure that the device is correctly configured for your application.
c
Incorrect configuration could result in damage to the temperature being
controlled, and/or personal injury. It is your responsibility, as the installer, to
ensure that the configuration is correct.
Device parameters has factory default values. These parameters must be set
according to the system’s needs.
c
Only qualified personnel and technicians should work on this equipment. This
equipment contains internal circuits with voltage dangerous to human life.
There is severe danger for human life in the case of unauthorized intervention.
c
Be sure to use the rated power supply voltage to protect the unit against
damage and to prevent failure.
c Keep the power off until all of the wiring is completed so that electric shock and
trouble with the unit can be prevented.
12
c
Electrical wiring of the device must be the same as ‘Electrical Wiring Diagram’
below to prevent damage to the process being controlled and personnel
injury.
1 2 3 4 5
a7
6
L N
(+) (-)
Temperature Input
(TC, PT-100, PTC or NTC)
Supply Voltage Input
230 V V (±15%) 50/60 Hz - 3 VA
115 V V (±15%) 50/60 Hz - 3 VA
24 V V (±15%) 50/60 Hz - 3 VA
24 V W ( - %15, + %10 ) 50/60 Hz - 3 VA
Relay Output (It must be determined in order)
13
c a Y CAT II c a Y CAT II
P/N : ESM - 4410 - 5.09.0.1/00.00/2.0.0.0 P/N : ESM - 4410 - 5.03.0.1/00.00/2.0.0.0
mPt-100
230 VV ± 15%
OUTPUT 50/60 Hz - 3VA
7A@250VV
mPt-100 7A@250VV
230 VV ± 15%
OUTPUT 50/60 Hz - 3VA
(-19.9 ; +99.9) Scale (0 ; 400) Scale
L N L N
C NO C NO
1 2 3 4 5 6 7 1 2 3 4 5 6 7
Rear label appearance of the device Rear label appearance of the device
that have PTC (-19.9oC ; + 99.9oC) Scale that have PTC (-50oC ; 150oC) Scale
c a Y CAT II c a Y CAT II
P/N : ESM - 4410 - 5.15.0.1/00.00/2.0.0.0 P/N : ESM - 4410 - 5.12.0.1/00.00/2.0.0.0
mPTC
230 VV ± 15%
OUTPUT 50/60 Hz - 3VA mPTC
230 VV ± 15%
OUTPUT 50/60 Hz - 3VA
7A@250VV
7A@250VV
(-19.9 ; +99.9) Scale (-50 ; 150) Scale
L N L N
R W C NO R W C NO
1 2 3 4 5 6 7 1 2 3 4 5 6 7
Rear label appearance of the device Rear label appearance of the device
that have J Type Thermocouple that have K Type Thermocouple
o o o o
( 0 C ; 800 C ) Scale ( 0 C ; 999 C ) Scale
c a Y CAT II c a Y CAT II
P/N : ESM - 4410 - 5.05.0.1/00.00/2.0.0.0 P/N : ESM - 4410 - 5.10.0.1/00.00/2.0.0.0
m
J TYPE TC
230 VV ± 15%
OUTPUT 50/60 Hz - 3VA
7A@250VV
m
K TYPE TC 7A@250VV
230 VV ± 15%
OUTPUT 50/60 Hz - 3VA
14
Note-1
L aN Note-2
6 7
External
Note-3
Fuse
(1 A T)
Power
Supply
Switch
c
Supply Voltage
230 V V ( ± %15 ) 50/60 Hz
115 V V ( ± %15 ) 50/60 Hz
24 V V ( ± %15 ) 50/60 Hz
24 V W ( - %15, + %10 ) 50/60 Hz
Make sure that the power supply voltage is the same indicated on the
c
instrument.
Switch on the power supply only after that all the electrical connections have
been completed.
Supply voltage range must be determined in order. While installing the unit,
supply voltage range must be controlled and appropriate supply voltage must
be applied to the unit. Controlling prevents damages in unit and system and
possible accidents as a result of incorrect supply voltage.
There is no power supply switch on the device. So a power supply switch must
c
be added to the supply voltage input. In accordance with the safety regulations,
the power supply switch shall bring the identification of the relevant
instrument.Power supply switch shall be easily accessible by the user.
Power switch must be two poled for seperating phase and neutral. On/Off
condition of power switch is very important in electrical connection. On/Off
condition of power switch must be signed for preventing the wrong connection.
c
The instrument is protected with an internal fuse (Please refer to Note-1 for
information). In case of failure it is suggested to return the instrument to the
manufacturer for repair.
15
TC Connect the wires with the polarity as shown in the figure at left.
1 2 3
3.5.2 RTD Connections
PT-100 PT-100
Note 1 Note 2
1 2 3 1 2 3
3-wire PT-100 connection 2-wire PT-100 connection
(with line compensation) (without line compensation)
(Max. Line impedance is 10 W)
Note 1 : In 3-wire system, use always cables of the same diameter (min 1mm²)
Its necessary to use cable in the same gauge and type for doing the line compensation
properly.
Note 2 : Install a jumper between terminals 2 and 3 when using a 2-wire RTD.
Note 3 : If the distance is longer than 10 meters, use 3-wire system.
PTC NTC
WHITE
RED
1 2 1 2
i While doing the PTC Probe connection, pay attention to the PTC Probe cable
colour.
16
2000V V 2000V V
4 4
Relay Output
5 5
2000V V
1 Analogue 1
3 Inputs 3
Device L N
7A V T Fuse
C
4
Last Control Element
(Contactor)
NO
5
c
Fuse
Load
17
ESM-4410
Led indication of
Output is active Displays
Temperature
Value,
Temperature Set
Value
and Parameters
OUT PROG
Led indication of
Led indication of SET Programming Mode
Output Set value is active
SET
P
Note-1
It is used to decrease the
value Note-1
It is used to increase the
value and access to the
parameter in programming
mode
It is used to change the Set
value, enter to and exit from
the programming mode It is used to change the Set
value and confirm the
parameter in programming
mode
Note-1: In Set value or programming mode while changing the parameter, if increment or
decrement button is pressed for 5 seconds continuously, increment and decrement number
become 10, if increment or decrement button is pressed for 10 seconds continuously, increment
and decrement number become 100.
18
ESM-4410
OUT PROG
“ r”Þ Revision Software
SET Revision
number
SET
P
ESM-4410
OUT PROG
SET
SET
P
c
If there is an unexpected situation while opening the device, power off the
device and inform a qualified personnel.
19
SET
SET
OUT PROG
SET
OUT PROG
SET
SET
SET
i
If no operation is done in programming or Set value mode for 20 seconds, device
turns back to main operation screen automatically.
20
SET SET
Press SET
SET
button to exit SET
programming
mode.
In password entering
screen, press SET
Press Enter
button to return the
button for
programming mode
accessing to the
entering screen
parameters
OUT PROG
SET
SET
Hysteresis Value
If Enter button is
pressed next
OUT PROG
parameter is shown.
In programming screen, SET
Programming Screen
Hysteresis
Value
SET SET
Press SET
SET SET
button to exit
from
programming Press SET button
mode. to turn to the
programming
screen without Press Enter
saving the button for saving
parameter. parameter
value.
OUT PROG
SET
SET
SET
SET
If Enter button is
OUT PROG pressed, next parameter
SET is shown.
Press SET button to turn
to the programming SET
Parameter can be
screen without saving changed with increment
the parameter. and decrement buttons.
Programming Screen
Process
Offset
Value
SET SET
Press SET
SET SET
button to exit
from
programming Press SET button
mode. to turn to the
programming
screen without Press Enter
saving the button for saving
parameter. parameter
value.
OUT PROG
SET
SET
Value of Minimum
Pulling Time for Output
If Enter button is
OUT PROG pressed, next parameter
Press SET button to SET is shown.
turn to the SET Parameter can be
programming screen changed with increment
without saving the and decrement buttons.
parameter.
Programming Screen
Value of
Minimum
Pulling
Time for
OUT PROG OUT PROG Output
SET SET
Press SET
SET SET
button to exit
from
programming Press SET button
mode. to turn to the
programming
screen without Press Enter
saving the button for saving
parameter. parameter
value.
OUT PROG
SET
SET
Programming Mode
Accessing Password
Value
OUT PROG
If Enter button is
pressed, next parameter
Press SET button to SET
is shown.
turn to the SET
programming screen Parameter can be
without saving the changed with increment
parameter. and decrement buttons.
Programming Screen
Programming
Mode
Accessing
Password
OUT PROG OUT PROG Value
SET SET
Press Enter
SET SET button for
saving
Press SET Press SET button to turn to parameter
button to exit the programming screen value.
from without saving the
programming parameter.
mode.
Programming Screen
Hysteresis
Parameter
It turns to
beginning of
OUT PROG OUT PROG
the
SET SET programming
SET SET
mode
SET value for Output. Control of output relay is done according to this value.
SET1 This value can be adjusted according to input type, minimum and maximum
of scale.
OUT PROG
SET
SET
P
28
In ON/OFF control algorithm, temperature value is tried to keep equal to set value by
opening or closing the last control element. ON/OFF controlled system, temperature value
oscillates continuously. Temperature value’s oscillation period or amplitude around set value
changes according to controlled system. For reducing oscillation period of temperature value,
a threshold zone is formed below or around set value and this zone is named hysteresis. Action
of control output is described with figures below.
Temperature
Temperature Hysteresis
Set Value
Time
Temperature
Control Output
ON
OFF
Time
7.1.1 ON/OFF Control in ESM-XX10 Temperature Controller
ON/OFF control algorithm in temperature control output which has heating function
Temperature
Control
Output Temperature
Set
ON
OFF
HYS
Temperature
ON/OFF control algorithm in temperature control output which has cooling function
Temperature
Control
Output Temperature
Set
ON
OFF
HYS
Temperature
29
30