Control System Room
Control System Room
A. EXTERNAL LOAD
Wall Load
1. Boiler Room
North: No Wall Load
East:
2
A East =26.4 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
(
Qwall , East = 2.828854314
W
2
m −K )
( 26.4 m2 ) ( 13.1425 K )=981.5049505 W
South:
2
A South=28.5 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
a. Roof Load
No Roof Load
Glass Load
QG =QSG +QTH
QSG =(230)(0.55)(10.5)(0.83)
QSG =1102.4475 W
QTH =UAΔT
W
Q TH =(5.9 2
)(10.5)(36.12−23)
m −K
QTH =812.784 W
QG =1102.4475 W +812.784 W
QG =1915.2315W
b. Infiltration Load
no of air changes=a+ bV +c (t o−t i )
no of air changes=0.150+ 0.010(6.793)+(0.007)(36.12−23)
changes
no of air changes=0.30977
hr
No . of people=18
QS ,seated =gain per person× sensible heat gain × no . of people ×CLF
QS ,seated =150W × 0.50 ×18 ×0.59
QS ,seated =796.5W
Q L, seated =gain per person ×latent heat gain ×no . of people× CLF
Q L, seated =150 W ×0.5 × 18× 0.59
Q L, seated =796.5 W
No . of people=1
QS ,teaching =gain per person× sensible heat gain × no . of people ×CLF
QS ,teaching =175W × 0.50 ×1 ×0.59
QS ,teaching =51.625W
Q L,teaching =gain per person ×latent heat gain ×no . of people× CLF
Q L,teaching =175 W ×0.5 × 1× 0.59
Q L,teaching =51.625 W
c. Partition Load
North:
Qwall=UAΔT
2
A wall, North =32.7 m
1 1
U wall = =
Rtotal 0.3244
W
U wall =3.082614057 2
m −K
(
Qs , North = 3.082614057
W
m −K )
( 32.7 m2) (26−23)=302.404439W
2
West:
Qwall=UAΔT
2
A wall, North =26.4 m
1 1
U wall = =
Rtotal 0.3244
W
U wall =3.082614057 2
m −K
(
Qs , west = 3.082614057
W
2
m −K )
( 26.4 m2 ) (26−23)=244.1430333 W
2. Drafting Room
External Load
a. Wall Load
North: No Wall Load
East: No Wall Load
South:
2
A South=28.1 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
(
Qwall , South= 2.828854314 2
W
m −K )
( 28.1 m2 ) ( 13.1425 K )=872.6500W
West: No Wall Load
b. Roof Load
No Roof Load
c. Glass Load
QG =QSG +QTH
QSG =(230)(0.55)(10.5)(0.8)
QSG =1062.6 W
QTH =UAΔT
W
Q TH =(5.9 2
)(10.5)(36.12−23)
m −K
QTH =812.784 W
QG =1062.6 W +812.784 W
QG =1875.384 W
d. Infiltration Load
no of air changes=a+ bV +c (t o−t i )
no of air changes=0.150+ 0.010(6.793)+(0.007)(36.12−23)
changes
no of air changes=0.30977
hr
e. Ventilation Load
Q= A Or V r
Q=(63.69)(22/100)(4.72)
L
Q=66.135696
s
Internal Load
a. Lighting
QS =(Lamp Rating∈W )(F U )(F B)(CLF )
Q L, seated =gain per person ×latent heat gain ×no . of people× CLF
Q L, seated =100 W ×0.4 ×18 ×0.59
Q, L ,seated =354 W
No . of people=1
QS ,teaching =gain per person× sensible heat gain × no . of people ×CLF
QS ,teaching =175W × 0.50 ×1 ×0.59
QS ,teaching =51.625W
Q L,teaching =gain per person ×latent heat gain ×no . of people× CLF
Q L,teaching =175 W ×0.5 × 1× 0.59
Q L,teaching =51.625 W
c. Partition Load
North:
Qwall=UAΔT
2
A wall, North =32.3 m
1 1
U wall = =
Rtotal 0.3244
W
U wall =3.082614057 2
m −K
(
Qs , North = 3.082614057
W
m −K
2 )
( 32.3 m2 ) (26−23)=298.7053021 W
(
Qs , west = 3.082614057
W
2
m −K )
( 63.69 m2 ) (26−23)=588.9950679 W
d. Miscellaneous Load
QS =(rating)(Fu )(CLF )
QS , Loptop=(45)(1)(1)(1)=45 W
QS ,Projector =(50)(1)(1)(1)=50 W
QS ,Other Equipment =( 0)(1)(1)(1)=0 W
QS ,TOTAL=45 W +50 W +0 W =95 W
South:
2
A South=27.5 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
(
Qwall , South= 2.828854314 2
W
m −K )
( 27.5 m2 ) ( 11.628 K )=904.5826 W
QSG =(230)(0.55)(10.5)(0.83)
QSG =1102.4475 W
QTH =UAΔT
W
QTH =(5.9 2
)(10.5)(36.12−23)
m −K
QTH =812.784 W
QG =1102.4475 W +812.784 W
QG =1915.2315W
d. Infiltration Load
no of air changes=a+ bV +c (t o−t i )
no of air changes=0.150+ 0.010(6.793)+(0.007)(36.12−23)
changes
no of air changes=0.30977
hr
e. Ventilation Load
Q= A Or V r
Q=(62.7)(27 /100)(4.72)
L
Q=79.90488
s
Internal Load
a. Lighting
QS =(Lamp Rating∈W )(F U )(F B)(CLF )
b. Occupant
No . of people=17
QS ,seated =gain per person× sensible heat gain × no . of people ×CLF
QS ,seated =150W × 0.6 ×17 × 0.59
QS ,seated =752.3W
Q L, seated =gain per person ×latent heat gain ×no . of people× CLF
Q L, seated =150 W ×0.5 × 17 ×0.59
Q L, seated =752.25 W
No . of people=1
QS ,teaching =gain per person× sensible heat gain × no . of people ×CLF
QS ,teaching =175W × 0.50 ×1 ×0.59
QS ,teaching =51.625W
Q L,teaching =gain per person ×latent heat gain ×no . of people× CLF
Q L,teaching =175 W ×0.5 × 1× 0.59
Q L,teaching =51.625 W
c. Partition Load
North:
Qwall=UAΔT
2
A wall, North =31.7 m
1 1
U wall = =
Rtotal 0.3244
W
U wall =3.082614057 2
m −K
(
Qs , North = 3.082614057
W
2
m −K )
( 31.7 m2) (26−23)=293.1565968W
d. Miscellaneous Load
QS =(rating)(Fu )(CLF )
QS , Loptop=(45)(3)(1)(1)=135 W
QS ,Projector =(50)(1)(1)(1)=50 W
QS ,Other Equipment =(500)(1)(1)(1)=500W
QS ,TOTAL=45 W +50 W +600 W =685 W
4. Laboratory Room 3
External Load
f. Wall Load
South:
2
A South=27.5 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
QSG =(230)(0.55)(10.5)(0.83)
QSG =1102.4475 W
QTH =UAΔT
W
Q TH =(5.9 2
)(10.5)(36.12−23)
m −K
QTH =812.784 W
QG =1102.4475 W +812.784 W
QG =1915.2315W
i. Infiltration Load
no of air changes=a+ bV +c (t o−t i )
no of air changes=0.150+ 0.010(6.793)+(0.007)(36.12−23)
changes
no of air changes=0.30977
hr
j. Ventilation Load
Q= A Or V r
Q=(62.7)(27 /100)(4.72)
L
Q=79.90488
s
Internal Load
e. Lighting
QS =(Lamp Rating∈W )(F U )(F B)(CLF )
f. Occupant
No . of people=17
QS ,seated =gain per person× sensible heat gain × no . of people ×CLF
QS ,seated =150W × 0.6 ×17 × 0.59
QS ,seated =752.25 W
Q L, seated =gain per person ×latent heat gain ×no . of people× CLF
Q L, seated =150 W ×0.5 × 17 ×0.59
Q L, seated =752.25 W
No . of people=1
QS ,teaching =gain per person× sensible heat gain × no . of people ×CLF
QS ,teaching =175W × 0.50 ×1 ×0.59
QS ,teaching =51.625W
Q L,teaching =gain per person ×latent heat gain ×no . of people× CLF
Q L,teaching =175 W ×0.5 × 1× 0.59
Q L,teaching =51.625 W
g. Partition Load
North:
Qwall=UAΔT
2
A wall, North =31.7 m
1 1
U wall = =
Rtotal 0.3244
W
U wall =3.082614057 2
m −K
(
Qs , North = 3.082614057
W
2
m −K )
( 31.7 m2) (26−23)=293.1565968W
East:
Qwall=UAΔT
2
A wall, North =26.4 m
1 1
U wall = =
Rtotal 0.3244
W
U wall =3.082614057 2
m −K
(
Qs , North = 3.082614057
W
m −K )
( 26.4 m2 ) (26−23)=2 44.14303 W
2
West: No Partition Load
South: No Partition Load
Qs , Total =293.1565968+2 44.14303 W
Qs , Total =537.29963 W
h. Miscellaneous Load
QS =(rating)(Fu )(CLF )
QS , Loptop=(45)(3)(1)(1)=135 W
QS ,Projector =(50)(1)(1)(1)=50 W
QS ,Other Equipment =(500)(1)(1)(1)=500W
QS ,TOTAL=45 W +50 W +600 W =685 W
5. Room 37
External Load
a. Wall Load
East:
2
A East =26.4 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
(
Qwall , East = 2.828854314 2
W
m −K )
( 26.4 m2 ) ( 13.1425 K )=981.5048 W
South:
2
A South=26.3 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
(
Qwall , South= 2.828854314 2
W
m −K )
( 26.3 m2 ) ( 11.628 K )=865.1099 W
b. Roof Load
2
A Roof =60.72 m
W
U wall =0.7182463298 2
m −K
(
Q Roof = 0.7182463298 2
W
m −K )
( 60.72 m2 ) ( 9.8 K )=427.396788 W
c. Glass Load
QG =QSG +QTH
QSG =(230)(0.55)(10.5)(0.83)
QSG =1102.4475 W
QTH =UAΔT
W
Q TH =(5.9 2
)(10.5)(36.12−23)
m −K
QTH =812.784 W
QG =1102.4475 W +812.784 W
QG =1915.2315W
d. Infiltration Load
no of air changes=a+ bV +c (t o−t i )
no of air changes=0.150+ 0.010(6.793)+(0.007)(36.12−23)
changes
no of air changes=0.30977
hr
e. Ventilation Load
Q= A Or V r
Q=(60.72)(70/100)(3.54)
L
Q=150.46416
s
QS =1.23 Q(t o−t i)
L
QS =1.23(150.46416 )(36.12−23)
s
QS =2428.130428 W
Internal Load
a. Lighting
QS =(Lamp Rating∈W )(F U )(F B)(CLF )
Q L, seated =gain per person ×latent heat gain ×no . of people× CLF
Q, seated L =100 W ×0.4 ×43 × 0.59
Q L, seated =1014.8 W
No . of people=1
QS ,teaching =gain per person× sensible heat gain × no . of people ×CLF
QS ,teaching =175W × 0.50 ×1 ×0.59
QS ,teaching =51.625W
Q L,teaching =gain per person ×latent heat gain ×no . of people× CLF
Q L,teaching =175 W ×0.5 × 1× 0.59
Q L,teaching =51.625 W
Qwall=UAΔT
2
A wall, North =33.65 m
1 1
U wall = =
Rtotal 0.3244
W
U wall =3.082614057 2
m −K
( W
Qs , North = 3.082614057
m −K )
( 33.65 m2 ) (26−23)=311.1898891W
2
d. Miscellaneous Load
QS =(rating)(Fu )(CLF )
QS , Loptop=(45)(3)(1)(1)=135 W
QS ,Projector =(50)(1)(1)(1)=50 W
QS ,Other Equipment =(0)(1)(1)(1)=0 W
QS ,TOTAL=45 W +50 W +0 W =185 W
6. Room 11
External Load
f. Wall Load
East:
2
A East =26.4 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
(
Qwall , East = 2.828854314 2
W
m −K )
( 26.4 m2 ) ( 13.1425 K )=981.5048 W
South:
2
A South=26.3 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
(
Qwall , South= 2.828854314 2
W
m −K )
( 26.3 m2 ) ( 11.628 K )=865.1099 W
g. Roof Load
No Roof Load
h. Glass Load
QG =QSG +QTH
QSG =(230)(0.55)(10.5)(0.83)
QSG =1102.4475 W
QTH =UAΔT
W
Q TH =(5.9 2
)(10.5)(36.12−23)
m −K
QTH =812.784 W
QG =1102.4475 W +812.784 W
QG =1915.2315W
i. Infiltration Load
no of air changes=a+ bV +c (t o−t i )
no of air changes=0.150+ 0.010(6.793)+(0.007)(36.12−23)
changes
no of air changes=0.30977
hr
j. Ventilation Load
Q= A Or V r
Q=(60.72)(70/100)(3.54)
L
Q=150.46416
s
QS =1.23 Q(t o−t i)
L
QS =1.23(150.46416 )(36.12−23)
s
QS =2428.130428 W
Internal Load
e. Lighting
QS =(Lamp Rating∈W )(F U )(F B)(CLF )
Q L, seated =gain per person ×latent heat gain ×no . of people× CLF
Q L, seated =100 W ×0.4 ×43 × 0.59
Q L, seated =1014.8 W
No . of people=1
QS ,teaching =gain per person× sensible heat gain × no . of people ×CLF
QS ,teaching =175W × 0.50 ×1 ×0.59
QS ,teaching =51.625W
Q L,teaching =gain per person ×latent heat gain ×no . of people× CLF
Q L,teaching =175 W ×0.5 × 1× 0.59
Q L,teaching =51.625 W
g. Partition Load
Qwall=UAΔT
2
A wall, North =33.65 m
1 1
U wall = =
Rtotal 0.3244
W
U wall =3.082614057 2
m −K
(
Qs , North = 3.082614057
W
m −K )
( 33.65 m2 ) (26−23)=311.1898891W
2
h. Miscellaneous Load
QS =(rating)(Fu )(CLF )
QS , Loptop=(45)(3)(1)(1)=135 W
QS ,Projector =(50)(1)(1)(1)=50 W
QS ,Other Equipment =( 0)(1)(1)(1)=0 W
QS ,TOTAL=45 W +50 W +0 W =185 W
7. Room 32-36
External Load
a. Wall Load
South:
2
A South=17.5 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
(
Qwall , South= 2.828854314 2
W
m −K )
( 17.5 m2) ( 11.628 K )=575.6435 W
b. Roof Load
2
A Roof =46.2 m
W
U Roof =0.7182463298 2
m −K
(
Q Roof = 0.7182463298 2
W
m −K )
( 46.2m2 ) ( 9.8 K )=325.1932083 W
c. Glass Load
QG =QSG +QTH
QSG =(230)(0.55)(10.5)(0.83)
QSG =1102.4475 W
QTH =UAΔT
W
QTH =(5.9 2
)(10.5)(36.12−23)
m −K
QTH =812.784 W
QG =1102.4475 W +812.784 W
QG =1915.2315W
d. Infiltration Load
no of air changes=a+ bV +c (t o−t i )
no of air changes=0.150+ 0.010(6.793)+(0.007)(36.12−23)
changes
no of air changes=0.30977
hr
e. Ventilation Load
Q= A Or V r
Q=(46.2)(70 /100)(3.54)
L
Q=114.4836
s
Q L, seated =gain per person ×latent heat gain ×no . of people× CLF
Q L, seated =100 W ×0.4 ×33 ×0.59
Q L, seated =778.8 W
No . of people=1
QS ,teaching =gain per person× sensible heat gain × no . of people ×CLF
QS ,teaching =175W × 0.50 ×1 ×0.59
QS ,teaching =51.625W
Q L,teaching =gain per person ×latent heat gain ×no . of people× CLF
Q L,teaching =175 W ×0.5 × 1× 0.59
Q L,teaching =51.625 W
c. Partition Load
North:
Qwall=UAΔT
2
A wall, North =26.425 m
1 1
U wall = =
Rtotal 0.3244
W
U wall =3.082614057 2
m −K
(
Qs , north= 3.082614057
W
m −K )
( 26.425 m2 ) (26−23)=244.3742294 W
2
d. Miscellaneous Load
QS =(rating)(Fu )(CLF )
QS , Loptop=(45)(3)(1)(1)=135 W
QS ,Projector =(50)(1)(1)(1)=50 W
QS ,Other Equipment =(0)(1)(1)(1)=0 W
QS ,TOTAL=45 W +50 W +0 W =185 W
8. Room 12-16
External Load
f. Wall Load
South:
2
A South=17.5 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
(
Qwall , South= 2.828854314 2
W
m −K )
( 17.5 m2) ( 11.628 K )=575.6435 W
QSG =(230)(0.55)(10.5)(0.83)
QSG =1102.4475 W
QTH =UAΔT
W
Q TH =(5.9 2
)(10.5)(36.12−23)
m −K
QTH =812.784 W
QG =1102.4475 W +812.784 W
QG =1915.2315W
i. Infiltration Load
no of air changes=a+ bV +c (t o−t i )
no of air changes=0.150+ 0.010(6.793)+(0.007)(36.12−23)
changes
no of air changes=0.30977
hr
j. Ventilation Load
Q= A Or V r
Q=(46.2)(70 /100)(3.54)
L
Q=114.4836
s
Q, seated L =gain per person ×latent heat gain ×no . of people× CLF
Q L, seated =100 W ×0.4 ×33 ×0.59
Q L, seated =778.8 W
No . of people=1
QS ,teaching =gain per person× sensible heat gain × no . of people ×CLF
QS ,teaching =175W × 0.50 ×1 ×0.59
QS ,teaching =51.625W
Q L,teaching =gain per person ×latent heat gain ×no . of people× CLF
Q L,teaching =175 W ×0.5 × 1× 0.59
Q L,teaching =51.625 W
g. Partition Load
North:
Qwall=UAΔT
2
A wall, North =26.425 m
1 1
U wall = =
Rtotal 0.3244
W
U wall =3.082614057 2
m −K
(
Qs , north= 3.082614057
W
m −K )
( 26.425 m2 ) (26−23)=244.3742294 W
2
h. Miscellaneous Load
QS =(rating)(Fu )(CLF )
QS , Loptop=(45)(3)(1)(1)=135 W
QS ,Projector =(50)(1)(1)(1)=50 W
QS ,Other Equipment =( 0)(1)(1)(1)=0 W
QS ,TOTAL=45 W +50 W +0 W =185 W
9. Room 31
External Load
a. Wall Load
South:
2
A South=26.4 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
(
Qwall , South= 2.828854314 2
W
m −K )
( 26.4 m2 ) ( 13.848 K )=1632.729 W
West:
2
AWest =18.7 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
(
Qwall , West= 2.828854314 2
W
m −K )
( 18.7 m2 ) ( 13.848 K )=732.5532W
b. Roof Load
2
A Roof =48.18 m
W
U Roof =0.7182463298 2
m −K
(
Q Roof = 0.7182463298 2
W
m −K )
( 48.18 m2 ) ( 10.3 K )=356.4326141 W
c. Glass Load
QG =QSG +QTH
QSG =(230)(0.55)(10.5)(0.8)
QSG =1062.6 W
QTH =UAΔT
W
Q TH =(5.9 2
)(10.5)(36.12−23)
m −K
QTH =812.784 W
QG =1062.6 W +812.784 W
QG =1875.384 W
d. Infiltration Load
no of air changes=a+ bV +c (t o−t i )
no of air changes=0.150+ 0.010(6.793)+(0.007)(36.12−23)
changes
no of air changes=0.30977
hr
e. Ventilation Load
Q= A Or V r
Q=(48.18)(70 /100)(3.54 )
L
Q=119.39004
s
b. Occupant
No . of people=33
QS ,seated =gain per person× sensible heat gain × no . of people ×CLF
QS ,seated =100W × 0.6 ×33 × 0.59
QS ,seated =1168.2 W
Q, seated L =gain per person ×latent heat gain ×no . of people× CLF
Q L, seated =100 W ×0.4 ×33 ×0.59
Q L, seated =778.8 W
No . of people=1
QS ,teaching =gain per person× sensible heat gain × no . of people ×CLF
QS ,teaching =175W × 0.50 ×1 ×0.59
QS ,teaching =51.625W
Q L,teaching =gain per person ×latent heat gain ×no . of people× CLF
Q L,teaching =175 W ×0.5 × 1× 0.59
Q L,teaching =51.625 W
c. Partition Load
North:
Qwall=UAΔT
2
A wall, North =26.05 m
1 1
U wall = =
Rtotal 0.3244
W
U wall =3.082614057 2
m −K
(
Qs , North = 3.082614057
W
2
m −K )
( 26.05 m2 ) (26−23)=240.9062886W
d. Miscellaneous Load
QS =(rating)(Fu )(CLF )
QS , Loptop=(45)(3)(1)(1)=135 W
QS ,Projector =(50)(1)(1)(1)=50 W
QS ,Other Equipment =( 0)(1)(1)(1)=0 W
QS ,TOTAL=45 W +50 W +0 W =185 W
10. Room 17
External Load
f. Wall Load
South:
2
A South=26.4 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
(
Qwall , South= 2.828854314 2
W
m −K )
( 26.4 m2 ) ( 13.848 K )=1632.729 W
West:
2
AWest =18.7 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
(
Qwall , West= 2.828854314 2
W
m −K )
( 18.7 m2 ) ( 13.848 K )=732.5532W
g. Roof Load
No Roof Load
h. Glass Load
QG =QSG +QTH
QSG =(230)(0.55)(10.5)(0.8)
QSG =1062.6 W
QTH =UAΔT
W
Q TH =(5.9 2
)(10.5)(36.12−23)
m −K
QTH =812.784 W
QG =1062.6 W +812.784 W
QG =1875.384 W
i. Infiltration Load
no of air changes=a+ bV +c (t o−t i )
no of air changes=0.150+ 0.010(6.793)+(0.007)(36.12−23)
changes
no of air changes=0.30977
hr
j. Ventilation Load
Q= A Or V r
Q=(48.18)(70 /100)(3.54 )
L
Q=119.39004
s
f. Occupant
No . of people=33
QS ,seated =gain per person× sensible heat gain × no . of people ×CLF
QS ,seated =100W × 0.6 ×33 × 0.59
QS ,seated =1168.2 W
Q L, seated =gain per person ×latent heat gain ×no . of people× CLF
Q L, seated =100 W ×0.4 ×33 ×0.59
Q, seated L =778.8 W
No . of people=1
QS ,teaching =gain per person× sensible heat gain × no . of people ×CLF
QS ,teaching =175W × 0.50 ×1 ×0.59
QS ,teaching =51.625W
Q L,teaching =gain per person ×latent heat gain ×no . of people× CLF
Q L,teaching =175 W ×0.5 × 1× 0.59
Q L,teaching =51.625 W
g. Partition Load
North:
Qwall=UAΔT
2
A wall, North =26.05 m
1 1
U wall = =
Rtotal 0.3244
W
U wall =3.082614057 2
m −K
(
Qs , North = 3.082614057
W
2
m −K )
( 26.05 m2 ) (26−23)=240.9062886W
East: No Partition Load
West:
Qwall=UAΔT
2
A wall, North =26.4 m
1 1
U wall = =
Rtotal 0.3244
W
U wall =3.082614057 2
m −K
(
Qs , west = 3.082614057
W
2
m −K )
( 26.4 m2 ) (26−23)=244.1430333 W
h. Miscellaneous Load
QS =(rating)(Fu )(CLF )
QS , Loptop=(45)(3)(1)(1)=135 W
QS ,Projector =(50)(1)(1)(1)=50 W
QS ,Other Equipment =( 0)(1)(1)(1)=0 W
QS ,TOTAL=45 W +50 W +0 W =185 W
11. Room 20
External Load
a. Wall Load
North:
2
A North =26.3 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
(
Qwall , Nort h = 2.828854314 2
W
m −K )
( 26.3 m2 ) ( 7.793 K )=579.7903 W
East:
2
A East =26.4 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
(
Qwall , East = 2.828854314 2
W
m −K )
( 26.4 m2 ) ( 15.0925 K )=1127.134W
b. Roof Load
2
A Roof =60.72 m
W
U Roof =0.7182463298 2
m −K
(
Q Roof = 0.7182463298 2
W
m −K )
( 60.72 ) ( 8.8 K )=383.7848709 W
c. Glass Load
QG =QSG +QTH
QSG =(120)(0.55)(10.5)(0.86)
QSG =595.98 W
QTH =UAΔT
W
Q TH =(5.9 2
)(10.5)(36.12−23)
m −K
QTH =812.784 W
QG =595.98W +812.784 W
QG =1408.764 W
d. Infiltration Load
no of air changes=a+ bV +c (t o−t i )
no of air changes=0.150+ 0.010(6.793)+(0.007)(36.12−23)
changes
no of air changes=0.30977
hr
e. Ventilation Load
Q= A Or V r
Q=(60.72)(70/100)(3.54)
L
Q=150.46416
s
Internal Load
a. Lighting
QS =(Lamp Rating∈W )(F U )(F B)(CLF )
Q L, seated =gain per person ×latent heat gain ×no . of people× CLF
Q L, seated =100 W ×0.4 ×43 × 0.59
Q L, seated =1014.8 W
No . of people=1
QS ,teaching =gain per person× sensible heat gain × no . of people ×CLF
QS ,teaching =175W × 0.50 ×1 ×0.59
QS ,teaching =51.625W
Q L,teaching =gain per person ×latent heat gain ×no . of people× CLF
Q L,teaching =175 W ×0.5 × 1× 0.59
Q L,teaching =51.625 W
c. Partition Load
North:
Qwall=UAΔT
2
A wall, North =33.65 m
1 1
U wall = =
Rtotal 0.3244
W
U wall =3.082614057 2
m −K
(
Qs , North = 3.082614057
W
m −K )
( 33.65 m2 ) (26−23)=311.1898891W
2
(
Qs , west = 3.082614057
W
2
m −K )
( 26.4 m2 ) (26−23)=244.1430333 W
d. Miscellaneous Load
QS =(rating)(Fu )(CLF )
QS , Loptop=(45)(3)(1)(1)=135 W
QS ,Projector =(50)(1)(1)(1)=50 W
QS ,Other Equipment =(0)(1)(1)(1)=0 W
QS ,TOTAL=45 W +50 W +0 W =185 W
12. Room 1
External Load
f. Wall Load
North:
2
A North =26.3 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
(
Qwall , Nort h = 2.828854314 2
W
m −K )
( 26.3 m2 ) ( 7.793 K )=579.7903 W
East:
2
A East =26.4 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
(
Qwall , East = 2.828854314 2
W
m −K )
( 26.4 m2 ) ( 15.0925 K )=1127.134W
g. Roof Load
No Roof Load
h. Glass Load
QG =QSG +QTH
QSG =(120)(0.55)(10.5)(0.86)
QSG =595.98 W
QTH =UAΔT
W
QTH =(5.9 2
)(10.5)(36.12−23)
m −K
QTH =812.784 W
QG =595.98W +812.784 W
QG =1408.764 W
i. Infiltration Load
no of air changes=a+ bV +c (t o−t i )
no of air changes=0.150+ 0.010(6.793)+(0.007)(36.12−23)
changes
no of air changes=0.30977
hr
j. Ventilation Load
Q= A Or V r
Q=(60.72)(70/100)(3.54)
L
Q=150.46416
s
Internal Load
e. Lighting
QS =(Lamp Rating∈W )(F U )(F B)(CLF )
Q L, seated =gain per person ×latent heat gain ×no . of people× CLF
Q L, seated =100 W ×0.4 ×43 × 0.59
Q L, seated =1014.8 W
No . of people=1
QS ,teaching =gain per person× sensible heat gain × no . of people ×CLF
QS ,teaching =175W × 0.50 ×1 ×0.59
QS ,teaching =51.625W
Q L,teaching =gain per person ×latent heat gain ×no . of people× CLF
Q L,teaching =175 W ×0.5 × 1× 0.59
Q L,teaching =51.625 W
(
Qs , North = 3.082614057
W
m −K )
( 33.65 m2 ) (26−23)=311.1898891W
2
(
Qs , west = 3.082614057
W
2
m −K )
( 26.4 m2 ) (26−23)=244.1430333 W
h. Miscellaneous Load
QS =(rating)(Fu )(CLF )
QS , Loptop=(45)(3)(1)(1)=135 W
QS ,Projector =(50)(1)(1)(1)=50 W
QS ,Other Equipment =( 0)(1)(1)(1)=0 W
QS ,TOTAL=45 W +50 W +0 W =185 W
(
Qwall , North = 2.828854314 2
W
m −K )
( 17.5 m2 ) ( 10.393 K )=514.5049 W
b. Roof Load
2
A Roof =46.2 m
W
U Roof =0.7182463298 2
m −K
(
Q Roof = 0.7182463298 2
W
m −K )
( 46.2 )( 10.3 K )=341.7846985 W
c. Glass Load
QG =QSG +QTH
QSG =(120)(0.55)(10.5)(0.91)
QSG =630.63 W
QTH =UAΔT
W
Q TH =(5.9 2
)(10.5)(36.12−23)
m −K
QTH =812.784 W
QG =630.63 W +812.784 W
QG =1143.414W
d. Infiltration Load
no of air changes=a+ bV +c (t o−t i )
no of air changes=0.150+ 0.010(6.793)+(0.007)(36.12−23)
changes
no of air changes=0.30977
hr
Q L, seated =gain per person ×latent heat gain ×no . of people× CLF
Q L, seated =100 W ×0.4 ×33 ×0.59
Q L, seated =778.8 W
No . of people=1
QS ,teaching =gain per person× sensible heat gain × no . of people ×CLF
QS ,teaching =175W × 0.50 ×1 ×0.59
QS ,teaching =51.625W
Q L,teaching =gain per person ×latent heat gain ×no . of people× CLF
Q L,teaching =175 W ×0.5 × 1× 0.59
Q L,teaching =51.625 W
(
Qs , North = 3.082614057
W
m −K )
( 24.85 m2 ) (26−23)=229.8088779W
2
(
Qs , west = 3.082614057
W
m −K )
( 26.4 m2 ) (26−23)=244.1430333 W
2
d. Miscellaneous Load
QS =(rating)(Fu )(CLF )
QS , Loptop=(45)(3)(1)(1)=135 W
QS ,Projector =(50)(1)(1)(1)=50 W
QS ,Other Equipment =(0)(1)(1)(1)=0 W
QS ,TOTAL=45 W +50 W +0 W =185 W
14. Room 2-6
External Load
f. Wall Load
North:
2
A North =17.5 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
(
Qwall , North = 2.828854314 2
W
m −K )
( 17.5 m2 ) ( 10.393 K )=514.5049 W
g. Roof Load
No Roof Load
h. Glass Load
QG =QSG +QTH
QSG =(120)(0.55)(10.5)(0.91)
QSG =630.63 W
QTH =UAΔT
W
QTH =(5.9 2
)(10.5)(36.12−23)
m −K
QTH =812.784 W
QG =630.63 W +812.784 W
QG =1143.414W
i. Infiltration Load
no of air changes=a+ bV +c (t o−t i )
no of air changes=0.150+ 0.010(6.793)+(0.007)(36.12−23)
changes
no of air changes=0.30977
hr
Q L, seated =gain per person ×latent heat gain ×no . of people× CLF
Q L, seated =100 W ×0.4 ×33 ×0.59
Q L, seated =778.8 W
No . of people=1
QS ,teaching =gain per person× sensible heat gain × no . of people ×CLF
QS ,teaching =175W × 0.50 ×1 ×0.59
QS ,teaching =51.625W
Q L,teaching =gain per person ×latent heat gain ×no . of people× CLF
Q L,teaching =175 W ×0.5 × 1× 0.59
Q L,teaching =51.625 W
g. Partition Load
North:
Qwall=UAΔT
2
A wall, North =24.85 m
1 1
U wall = =
Rtotal 0.3244
W
U wall =3.082614057 2
m −K
(
Qs , North = 3.082614057
W
m −K )
( 24.85 m2 ) (26−23)=229.8088779W
2
(
Qs , west = 3.082614057
W
m −K )
( 26.4 m2 ) (26−23)=244.1430333 W
2
h. Miscellaneous Load
QS =(rating)(Fu )(CLF )
QS , Loptop=(45)(3)(1)(1)=135 W
QS ,Projector =(50)(1)(1)(1)=50 W
QS ,Other Equipment =( 0)(1)(1)(1)=0 W
QS ,TOTAL=45 W +50 W +0 W =185 W
15. Room 26
External Load
a. Wall Load
North:
2
A North =18.7 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
(
Qwall , North = 2.828854314 2
W
m −K )
( 18.7 m2 ) ( 10.393 K )=549.7852 W
West:
2
A South=26.4 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
(
Qwall , West= 2.828854314 2
W
m −K )
( 26.4 m2 ) ( 18.9925 K )=1418.393 W
b. Roof Load
2
A Roof =48.18 m
W
U Roof =0.7182463298 2
m −K
c. Glass Load
QG =QSG +QTH
QSG =(120)(0.55)(10.5)(0.91)
QSG =630.63 W
QTH =UAΔT
W
QTH =(5.9 2
)(10.5)(36.12−23)
m −K
QTH =812.784 W
QG =630.63 W +812.784 W
QG =1143.414W
d. Infiltration Load
no of air changes=a+ bV +c (t o−t i )
no of air changes=0.150+ 0.010(6.793)+(0.007)(36.12−23)
changes
no of air changes=0.30977
hr
Q L, seated =gain per person ×latent heat gain ×no . of people× CLF
Q L, seated =100 W ×0.4 ×34 × 0.59
Q L, seated =802.4 W
No . of people=1
QS ,teaching =gain per person× sensible heat gain × no . of people ×CLF
QS ,teaching =175W × 0.50 ×1 ×0.59
QS ,teaching =51.625W
Q L,teaching =gain per person ×latent heat gain ×no . of people× CLF
Q L,teaching =175 W ×0.5 × 1× 0.59
Q L,teaching =51.625 W
c. Partition Load
North:
Qwall=UAΔT
2
A wall, North =26.05 m
1 1
U wall = =
Rtotal 0.3244
W
U wall =3.082614057 2
m −K
(
Qs , North = 3.082614057
W
2
m −K )
( 26.05 m2 ) (26−23)=240.9062886W
(
Qs , west = 3.082614057
W
2
m −K )
( 26.4 m2 ) (26−23)=244.1430333 W
d. Miscellaneous Load
QS =(rating)(Fu )(CLF )
QS , Loptop=(45)(3)(1)(1)=135 W
QS ,Projector =(50)(1)(1)(1)=50 W
QS ,Other Equipment =(0)(1)(1)(1)=0 W
QS ,TOTAL=45 W +50 W +0 W =185 W
16. Room 7
External Load
f. Wall Load
North:
2
A North =18.7 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
(
Qwall , South= 2.828854314 2
W
m −K )
( 18.7 m2 ) (10.393 K ) =549.7852W
West:
2
A South=26.4 m
1 1
U wall = =
Rtotal 0.3535
W
U wall =2.828854314 2
m −K
g. Roof Load
2
A Roof =48.18 m
W
U Roof =0.7182463298 2
m −K
(
Q Roof = 0.7182463298 2
W
m −K )
( 48.18 m2 ) ( 10.3 K )=356.4326141 W
h. Glass Load
QG =QSG +QTH
QSG =(120)(0.55)(10.5)(0.91)
QSG =630.63 W
QTH =UAΔT
W
QTH =(5.9 2
)(10.5)(36.12−23)
m −K
QTH =812.784 W
QG =630.63 W +812.784 W
QG =1143.414W
i. Infiltration Load
no of air changes=a+ bV +c (t o−t i )
no of air changes=0.150+ 0.010(6.793)+(0.007)(36.12−23)
changes
no of air changes=0.30977
hr
Q L, seated =gain per person ×latent heat gain ×no . of people× CLF
Q L, seated =100 W ×0.4 ×34 × 0.59
Q L, seated =802.4 W
No . of people=1
QS ,teaching =gain per person× sensible heat gain × no . of people ×CLF
QS ,teaching =175W × 0.50 ×1 ×0.59
QS ,teaching =51.625W
Q L,teaching =gain per person ×latent heat gain ×no . of people× CLF
Q L,teaching =175 W ×0.5 × 1× 0.59
Q L,teaching =51.625 W
g. Partition Load
North:
Qwall=UAΔT
2
A wall, North =26.05 m
1 1
U wall = =
Rtotal 0.3244
W
U wall =3.082614057 2
m −K
(
Qs , North = 3.082614057
W
2
m −K )
( 26.05 m2 ) (26−23)=240.9062886W
East: No Partition Load
West:
Qwall=UAΔT
2
A wall, North =26.4 m
1 1
U wall = =
Rtotal 0.3244
W
U wall =3.082614057 2
m −K
(
Qs , west = 3.082614057
W
2
m −K )
( 26.4 m2 ) (26−23)=244.1430333 W
h. Miscellaneous Load
QS =(rating)(Fu )(CLF )
QS , Loptop=(45)(3)(1)(1)=135 W
QS ,Projector =(50)(1)(1)(1)=50 W
QS ,Other Equipment =(0)(1)(1)(1)=0 W
QS ,TOTAL=45 W +50 W +0 W =185 W