Multilin-EPM-9900P__03-10-2019

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

GE

Grid Solutions

Multilin EPM 9900P


High Performance Power Quality and Monitoring & Metering
Transient Recorder Meter • 0.06% Energy Accuracy (ANSI 0.2%)
• 50MHz Transient Recorder (over 800,000
The Multilin™ EPM 9900P is one of the most advanced monitoring products on the market today, providing
samples/cycle)
a comprehensive perspective of energy usage and power quality metrics for critical energy circuits.
• Harmonics to the 511th order
Features such as 0.06% accuracy, available high speed 50MHz Transient Recorder, advanced (Voltage,Current), 127th order in real time
communication interface/protocol capabilities, and up to 4GB of logging make the EPM 9900P perfect
• Voltage Sag/Swell, Current Fault and Transient
for industrial and utility substation automation applications where both power quality monitoring, high
Recording
accuracy and easy integration/commissioning are required.
• Up to 4 GB data logging
• Class A IEC 61000-4-30 Power Quality &
Key Benefits
EN50160 Reporting Support
• Ideal for revenue and power quality monitoring in applications such as of utility substations, advanced
industrial manufacturing, datacenters and hospitals with high resolution transient recording (up to
50Mhz) and high accuracy 0.06% Watt/Hr energy metering with demand and time of use capture. Advanced
• Constant Calibration metrology self calibrates every 10 seconds ensuring highly stable readings
Communications
• Large 4GB memory makes it possible to log years of captured data
• Modbus, DNP 3.0, IEC 61850 including high
• Easy integration with flexible communications options and protocols supporting simultaneous speed GOOSE messaging for cross triggering
Modbus, DNP and IEC 61850 communications data capture
• Standardize setup, commissioning, ongoing maintenance using IEC 61850 settings files • Standard Ethernet with dual Ethernet capability
• Upgradable for future requirements with modular communications I/O and software option upgrades • Port control to secure and disable services/ports
• Easy system integration supporting up to
Applications 32 Modbus TCP/IP sockets per Ethernet port
• Power quality event capture for utility or industrial event investigation/reconciliation and predictive and Up to 16 Relay Outputs/40 Digital Status
maintenance (Utility substation, Data Centers, Manufacturing, Hospitals) Inputs

• Revenue energy billing or reconciliation (demand, time of use) and for utility or industrial applications
• High speed data capture for external device control in applications such as generation or renewables Easy Setup and Use
• Specialized utility power quality reporting for EN50160 or IEC 61000-4-30 Class A standards • User friendly, color touchscreen display
• Software based setup with web server for
data visualization
• Prewired enclosure for safe retrofit/new
installations
EPM 9900P Advanced Power Quality Meter

High Performance Power Quality and Transient Meter for Utility or Industrial Applications
Providing high performance power quality analysis functions, the EPM 9900P
delivers high accuracy power quality monitoring and transient waveform
capture, and reporting data in compliance with IEC 61000-4-30 Class A and
EN 50160 international standards. This provides power system managers
with a deep understanding of each circuits’ power usage and reliability.

With up to 4GB of data logging, including 50 MHz transient capture, the EPM
9900P ensures that essential power quality data and events are captured,
stored, and time synchronized allowing for comprehensive analysis of
events. The EPM 9900P also supports a multitude of communications
protocols such as Modbus, DNP3 and 61850 making it easy to integrate
and retrieve data into a SCADA or data analysis system. The EPM 9900P is a
clear choice for applications where critical revenue accurate metering is an
Power Grid Commercial/
absolute necessity such as power utility or industrial applications. Generation Automation Industrial Data Center

Comprehensive Revenue Energy Metering and Monitoring


With ANSI Class 0.2% accuracy the EPM 9900P provides comprehensive Perpetual Time of Use for Complex Metering
measurements of energy and power quality values as well as monitoring
A new feature of the EPM 9900P is the perpetual Time of Use (TOU) calendar
of key electrical conditions to detect and proactively remedy issues to help
that only requires one time setup.
prevent outages or asset damage.
The TOU implementation allows the user to set up multiple tariffs to meet
• Full 4 quadrant metering
any contractual obligations. It also allows the user to customize any energy
• Energy load profiling: log virtually unlimited historical trending parameter for TOU. The 16 available TOU registers can be configured not
• Time of Use perpetual calendar that supports multiple tariffs only for TOU built-in energy readings, but also for any stored data from
• Transformer and Line Loss compensation: for both iron and copper and pulses or RTU Master readings that might need TOU functionality.
total substation losses
• CT and PT compensation: correct for errors in current and voltage
transformers
• Coincidental readings: e.g., PF or VARs at time of Peak Demand, to identify
number of capacitors needed, peak inefficiencies, etc.
• Load aggregation/universal metering: pulse inputs can be used to
aggregate or accumulate different loads such as utility products (Water,
Air, Gas, etc.)

Test Mode and Energy Presets


The EPM 9900P meter offers a Test Mode for testing watt-hour and VAR-hour
meter accuracy without affecting the stored readings. Using Test Mode, users
can verify the meter’s readings over the lifespan of an installed meter without
having to reset energy or disturb the load profiling and demand recording.

The Energy Preset feature allows a user to program the energy accumulator Configure customized TOU tariff schedules
values upon exiting Test Mode. This lets the user compensate for
accumulations missed during testing time, or easily replace the meter
System Events Logging
during upgrade or maintenance.
The EPM 9900P logs system operations to detect settings changes and
unauthorized access by recording

• Programming changes
• Password access changes
• Time changes
• Resets/Power up/down
• Firmware changes

Test Mode to test accuracy without reset

2 GEGridSolutions.com
EPM 9900P Advanced Power Quality Meter

Class A Power Quality Reporting


The EPM 9900P captures and stores comprehensive power quality
information, including harmonics, sags, swells and transients providing a
clear perspective and log of faults and disturbances to allow for detailed
and extensive forensic engineering analysis.

IEC 61000-4-30 Class A Power Quality Meter


• Designed specifically to meet the rigorous IEC 61000-4-30 Class A
standard, the EPM 9900P measures and analyzes power quality metrics
precisely.
• All reporting is available via the EN 50160 reporting format which can be
further customized to meet the required application or regulatory needs.

IEC 61000-4-15 Class A Flicker Meter:


• Flicker compliant with the IEC 61000-4-15 Class A standard
• Operates on both 220 volt/50 Hz and 120 volt/60 Hz throughout standard
test points

IEC 61000-4-7 Class A Harmonics and Interharmonics Analysis:


• View harmonic magnitudes to the 511th order for each voltage and
current channel Extensive harmonics analysis capabilities

• Harmonic magnitudes and phase angles in real time are resolved to the
127th order
• Obtain %THD, TDD, and K-Factor
• Conduct power quality analysis at the high end of the harmonic
magnitude spectrum

Phasor Analysis:
The monitor reads a phase angle analysis between the voltage and current
channels, allowing you to analyze efficiency and system integrity.

High-speed Voltage Reliability Measurements:


The EPM 9900P meter provides industry leading voltage measurement.

• Real time single cycle RMS measurements


• Customizable high-speed readings – can be set from 2 to 20 cycles RMS

Set Limit Control:


Programmable setpoints allowing a user to configure the meter to be used RealComprehensive Phasor
Time Power Quality visualization
Compliance Report

as a control device for many applications, such as:

• Capacitor control EN50160 Individual Report Summary


• Load shedding Power Frequency (x.1) Pass

• Automatic transfer schemes Supply Voltage Variations (x.3.x) Pass

• Transformer monitoring & control Rapid Voltage Changes (x.4.1) Pass

Flicker PLT (x.4.2) Pass


• Redundant protection (not designed for primary over-current protection)
Flicker PST Pass
• Many other control functions
Supply Voltage Dips (x.5) Pass

Alarm Notification: Voltage Swells Pass

Short Interruption of Supply Voltage (x.6) Pass


The EPM 9900P meter lets you set multiple programmable limits for any
measured value, as well as those set up in a Boolean logic tree, and limits Long Interruption of Supply Voltage (x.7) Pass

set up in the IEC 61850 protocol implementation. Users can be notified of Temporary powerfrequency overvoltage (x.8) Pass

alarm conditions via email. Supply Voltage Unbalance (x.10) Pass

Harmonic Voltage (x.11) Pass

Mains Signaling Voltage (x.13) Pass

User-friendly reports illustrating PQ compliance

GEGridSolutions.com 3
EPM 9900P Advanced Power Quality Meter

16 Bit Waveform and Fault Recorder: Independent ITIC/CBEMA Log Plotting:


• Record up to 1024 samples per cycle; capture a transient at over 800,000 • Quickly view total surges, sags, and average duration in the independent
samples per cycle or at 50 MHz sampling speed ITIC/CBEMA log
• Voltage and current recording with pre and post-event analysis • SEMI F47 graphing for power quality compliance in semiconductor
• Fault recording offers 8 times full scale capture capability industry

• 16 bit A/D converter provides precise waveform resolution Compatible Waveform Formats
• Both hardware and software triggers are available Using GE Communicator software, the meter will provide all waveform data
via COMTRADE and PQDIF compatible formats. This allows the waveform PQ
High-speed Status Input Triggers:
and fault records to be read by most third-party waveform analysis software
• Waveforms are recorded at time of status change programs.
• Input change and waveform recording are time-stamped to a 100 micro • COMTRADE (common format for transient data exchange) is defined by
second resolution IEEE Std C37.111
• Inputs and waveforms can be displayed together to time breakers and relays • PQDIF (power quality data interchange format) is defined by IEEE Std
1159.3-2003
Subcycle 50 MHz Transient Recorder (Software Option C):
A user can define log sizes within the meter. Thus the full memory can be
allocated specifically to the desired function.

Record and Analyze Waveform Fault and Transient Data

4 GEGridSolutions.com
EPM 9900P Advanced Power Quality Meter

Easy System Integration and Available IEC 61850 Solution

Software options B and above offer an embedded IEC 61850 Protocol Server Software Options
for seamless integration with substation automation and industrial 61850
The EPM 9900P Software options lets you upgrade meter functionality even
applications.
after installation. This means you can purchase what you need now and then
• The IEC 61850 Protocol Server allows up to 6 simultaneous MMS clients. upgrade in the future for the additional needs.
• Either Ethernet port can be configured for IEC 61850 (only one port at a Feature A B C
time can run IEC 61850)
Basic Measurements * * *
• GOOSE publisher/subscriber functionality is supported. Memory 512 MB 1 GB 4 GB
• Buffered and unbuffered reports are supported for the following triggers: Sampling Speed 512 1024 Up to 800,000
general meter interrogation, for example, the report is generated in 50 MHz Transients *
response to a query; meter integrity, for example, the report is generated EN61000-4-30 Class A * * *
according to a programmed interval; and data change, for example, the IEC 61850 Server * *
report is generated due to a change in the contents of a dataset. IEC 61850 GOOSE * *

• File transfer is supported


• Embedded Web Protocol Server support is available for IEC 61850 CID file Unique GOOSE Cross Trigger:
uploading, IEC 61850 Protocol Server status and for displaying incoming • Fault-based cross trigger of waveform based on GOOSE message
and outgoing GOOSE messages. • Provides system-wide distribution fault analysis on an event
• Multiple Logical Nodes, which map flicker, harmonics, digital inputs/ • Timing better than 200 microseconds is typical
outputs, limit state, voltage, current, energy and other data, are supported.
• Many different circuits can be viewed after an event occurred
• Waveform capture can be triggered by status input data inside GOOSE
messages. The user can program up to 16 status inputs that will trigger
a waveform capture when the information is received via a GOOSE
message. The status inputs include digital inputs, limit states, and any
other status input supported by the meter.

Intelligent Substation IEC 61850 Design


Cross Trigger Fault Readings for Simultaneous Station-wide Fault Analysis

GEGridSolutions.com 5
EPM 9900P Advanced Power Quality Meter

Flexible Communications Options Ethernet Communication Port Capabilities:


The EPM 9900P meter offers up to 6 simultaneous communication ports and • 2 Ethernet ports provide multiple simultaneous communication
multiple protocols to meet almost every need. • Each port has separate MAC address and IP address
• Supports Modbus TCP/IP, DNP 3.0 and IEC 61850
Hardware Features:
• GOOSE messaging protocol supported for IEC 61850
• 2 optional RS485 ports speaking Modbus and/or DNP 3.0
• Up to 32 Modbus TCP/IP sockets per Ethernet port
• USB front panel port
• Highly secure port control to disable unneeded services and ports
• ANSI optical front panel port
• Email Function - SMTP email to client on alarm
• 2 separately addressable Ethernet ports
• Precise Time Synchcronization - SNTP Time Sync protocol
• Optional Fiber or RJ45 media on one Ethernet port
• File Transfer Protocol - High-speed file data transfer
8 Built-in Digital High-speed Status Inputs:
VAUX Input:
• Inputs automatically sense whether the circuit is externally wetted
• Neutral to ground or aux voltage readings
• If externally wetted, input up to 150 VDC is accepted
• Synchronizing schemes, for example, obtaining the frequency, magnitude,
• If internally wetted, the meter supplies the necessary voltage for the
and phase angle on both sides of a switch or between generator and bus
control application
voltage

Watt/hr Pulse

ANSI Optical Port Backlight Button

256-Color LCD Display


Touch-screen Overlay
VAR/hr Pulse

Optional Upgrade Cards


Standard 10/100
BaseT Ethernet RJ45 Port 2-ports: RS485 and 4
(Auto-detecting Tx and Rx) Pulse Outputs

IRIG-B Satellite Clock: Optional Second


1 msec Time Sync Ethernet Port

Color-coded Voltage Inputs

8 High-Speed Status Inputs


Slots 3 and 4 Provide up
to 12 Relay Outputs

6 GEGridSolutions.com
EPM 9900P Advanced Power Quality Meter

Industry-Leading DNP 3.0 Level 2 Plus – Complies with DNP Level EXTERNAL I/O
1 and Level 2 Certification Requirements:
• Up to 136 measurements (64 Binary Inputs, 8 Binary Counters, 64 Analog
Analog Outputs:
Inputs) can be mapped to DNP static points • PL90001MAON4O00/PL90001MAON8O00: 4 or 8 Analog Outputs, 0-1 mA,
self-powered, scalable, bidirectional
• Up to 16 relays and 8 resets can be controlled through DNP
• PL90002OMAON400/PL90002OMAON800: 4 or 8 Analog Outputs, 4-20
• Report-by-exception processing (DNP Events) deadbands with unsolicited
mA, self-powered, scalable
response for serial communication
• Wiring: Common Mode
• 250 available events, in four event types (Binary Input Change, Frozen
Counter, Counter Change, and Analog Change) • Accuracy: 0.1% of Full Scale
• Calibration: Self-calibrating
Secure Communications
• Scaling: Programmable
The EPM 9990P offers 9 levels of password security to protect the meter
from unauthorized use. Each level can be configured to enable specific • Ordering: Up to 4 Analog Output modules
capabilities, so that a Utility can control access to functions according to
Analog Inputs:
the type of user. For example, one user level is able to create and change
TOU calendars, while a different user level is able to read TOU data, but not • PL90008AI100000: 8 Analog Inputs, 0±1 mA
change anything. • PL90008AI200000: 8 Analog Inputs, 4-20 mA
• PL90008AI300000: 8 Analog Inputs, 0±5 VDC
Expandible Inputs and Outputs • PL90008AI400000: 8 Analog Inputs, 0±20 VDC
• Wiring: Common Mode
INTERNAL I/O • Accuracy: 0.25% of Full Scale

Pulse Outputs: Relay Outputs: • Scaling: Programmable

S: Dual Serial RS485/Pulse Output Card R1: 6 Relay Output Card • Ordering: Up to 4 Analog Input modules

• 4 KYZ pulses - Solid State • 5 A, 250 VAC/30 VDC


• Pulse width: 5 ms • Form C (Latching) Digital Dry Contact Relay Outputs:
• Two RS485 ports • PL90004RO100000: 4 Relay Outputs, 5 A, 250 VAC/30 VDC,
Form-C Latching
Digital Input Status: • Ordering: 1 module in addition to internal modules
DI: 16 Status Inputs Card
Digital Solid State Pulse Outputs:
• Used for alarm detect or pulse accumulation
• PL90004PO100000: 4 Solid State Pulse Outputs, Form A or C KYZ pulses
• Up to 150 VDC wetted or non-wetted (24 VDC internally provided)
• Maximum Pulse Speed: 20 pulses per second
• Ordering: Up to 4 Digital Solid State Output modules

I/O Module Accessories (Required):


• PL9000PSIO00000: Power supply required when using an external
I/O module. EPM 9900P does not have internal power for external I/O
modules.
• PL9000MBIO00000: Mounting bracket for external I/O modules. Must be
ordered with external I/O module.

Note: The EPM 9900P provides one I/O slot for the S (Slot 1), and two I/O slots
for the R1 and DI (Slots 3 and 4).

GEGridSolutions.com 7
EPM 9900P Advanced Power Quality Meter

Color Touch Screen Display


The EPM 9900P meter features a touchscreen LCD color display which uses • Alarms
a bright TFT glass with a high temperature and long life LED backlight for • Phasor Analysis
increased usability and visibility. LED is superior to CCFL solutions due to
• Harmonic spectrum analysis and waveforms
better temperature and half-life specifications.
• Real time trending
Screen displays include:
• Log status
• Real-time viewing (voltage, current, power, demand)
• Configuration settings
• Accumulated energy and time of use readings
• Multi-language Support (English, Chinese, Hebrew, Portuguese, Spanish,
• Flicker readings French, Polish)

MAIN

TRENDS HOME ENERGY BAR GRAPH


REAL
TIME REAL TIME TOU RESETS
MAIN VOLTAGE PHASOR TRENDS

CURRENT HARMONICS LOG STATUS


ALARMS POWER
QUALITY POWER ALARMS VERSIONS

DEMAND FLICKER SETTINGS

2016-10-07 14:40:51 1 2016-10-07 14:57:38

PHASOR HARMONICS
300.0 %THD
270 Volts A 19.91
240 300 Volts B Mag 240.0 TDD 0.00
Volts C Freq(Hz) 56.864
Volts A 000.00 180.0 Volts A 120.68
210 Volts B 120.91 120.0
Volts C 240.02
Amps A 60.0 Volts B
Amps B Amps A 029.52
Amps B 150.47 0
Amps C 269.53 -60.0
180 0
Volts AB Volts AB 330.37 -120.0
Volts BC Volts BC 089.65
Volts CA Volts CA 210.39 -180.0
150 30 Freq(Hz) 60.001 -240.0
Hookup ABC -300.0
Wye
120 60 0 8 16 24 32 Spectrum
90 Phase Phasor PH-PH Time (ms)
g 2016-10-07 14:43:51 10 2016-10-07 14:43:51

User Friendly Color Touch Screen Display

8 GEGridSolutions.com
EPM 9900P Advanced Power Quality Meter

Software
GE Communicator Software EnerVista™ Launchpad
This software connects remote meters via Serial, Ethernet or Modem. It EnerVista Launchpad is a powerful software package that provides users a
allows users to view real time metered data, configure and analyze collected platform to access all of the setup and support tools needed for configuring
information from remote EPM power meters. and maintaining GE Multilin products.

GE Communicator displays real-time data from supported meters. The data EnerVista Launchpad allows configuration of devices in real-time by
is presented in a simple and powerful graphical format so that laymen communicating using RS232, RS485, Ethernet or modem connections. Using
access data easily. The software offers many screens, including: Launchpad as the single interface to the setup and analysis software makes
it easy to enter set points, read metered values, monitor status and evaluate
• Voltage, Current, Power & Energy
power quality.
• Time of Usage & Accumulations
Included in EnerVista Launchpad is a document archiving and management
• Power Quality
system that ensures critical documentation is up-to-date and available
• Harmonics Visualization when needed by automatically checking for and downloading new versions
• Actual Real time Waveform Scopes of manuals, applications notes, specifications and service bulletins.
• Alarms & Limits
• Max. & Min. for Each Parameter
• I/O Device Information

EnerVista Integrator
EnerVista Integrator is a toolkit that allows seamless integration of GE Multilin
devices into new or existing automation systems by sending GE device data
to HMI, DCS and SCADA systems. Included in EnerVista Integrator is:

• OPC/DDE Server
• GE Multilin Drivers
• Automatic Event Retrieval
• Automatic Waveform Retrieval

GEGridSolutions.com 9
EPM 9900P Advanced Power Quality Meter

Multilin Meter Enclosure Pre-Wired, Configured and Economical Solution for


Expanding existing switchgear or installing new metering capability can Retrofit and Small Metering Systems
be challenging due to space limitations, downtime and installation and
equipment costs. GE’s Multilin Meter Enclosure is a pre-wired configured,
Easy and Rapid Installation
economical solution for both retrofit expansions and small scale meter • Factory pre-wired, installation-ready GE metering solution eliminates
installations that allows the expansion of existing switchgear capability wiring and associated errors for rapid installation
without expensive and time-consuming design.
• Extend metering capability with new systems and existing switchgear
When ordered as a meter option the enclosure provides a factory pre-wired, without system installation downtime
installation-ready metering solution that further drives energy cost savings,
by enabling the measurement of key energy usage information along Cost-Effective Retrofit Solution
multiple metering points for new or existing systems. Ordering the enclosure • Save up to 200% versus the addition of a new switchgear cabinet
is simple when selected as an option during meter configuration, ensuring
• Compact footprint makes effective use of existing allocated space
correct pre-wired meter-compatible delivery.
• Allows new installations or the expansion of existing switchgear capability
without expensive, time-consuming designs, eliminating system downtime

Reliable and Compatible


• Backed by a 10 year warranty

• Simple meter option ordering ensures compatibility with GE EPM 9900P meters

• Comprehensive factory testing of both meter and enclosure together

• NEMA1 tested and UL/CUL certified

Applications (New and Retrofit installations)


• Utility/Indusrial Power Quality Studies

• Healthcare Institutions

• Government Buildings

• Manufacturing

• Educational Campuses

• Data Centers

Meter Enclosure Assembly


The installation of the GE’s Multilin Meter Enclosure is simple, safe and
eliminates downtime through simple mounting and wiring. The enclosure is
UL/CUL certified and NEMA 1 rated making it ideal for indoor environments.

It is provided in two voltage configurations (120-240V and 277V) to ensure


compatibility with customer installations. The standard equipment includes
voltage fuses; a shorting block for current transformers; and a control power
transformer for 277V power systems that are pre-wired and configured to
ensure safety, quality and long-term reliability.

Lockable Hinge

Door Gasket

Fused Voltage Inputs


Current Input
Shorting Block Control Power Transformer

10 GEGridSolutions.com
EPM 9900P Advanced Power Quality Meter

Wiring Drawings - EPM 9900P Meter

B C N A B C N
A B C N A
A B
B C
C N
N A B C N

A B C N A B C N A B C N A B C N

* * * *
CT CT CT CT
Shorting Shorting Shorting Shorting
Block Block N/U N/U Block Block N/U
Va Va Va Va
Vb Vb Vb Vb
Earth Earth Earth Earth
*
CTs
CTsGround * Ground Vc Vc CTsCTs CTs
* Ground * Ground Vc Vc
CT CT Vn Vn CT CT Vn Vn
Shorting Shorting Shorting Shorting
Vaux Vaux Vaux Vaux
Block Block N/U N/U Block Block N/U
Va Va Va Va
Vb Vb Vb Vb
Earth Earth Earth Earth
CTs Ground Ground Vc Vc CTs CTs Ground Ground Vc Vc
Vn Vn Vn Vn
Vaux Vaux Vaux Vaux

Vn Vn Vn Vn
PTs PTs Vc Vc Vc Vc
Vb Vb Vb Vb
Va Va Va Va

Fuses 3 x 0.1A Fuses 3 x 0.1A Fuses


Vn Vn Vn 3 x 0.1A Fuses 3 x 0.1A
Vn
PTs Earth Ground PTs Earth Ground
Vc Vc Vc Vc
Vb Vb Vb Vb
B C N A
A B
B C
C N
N A B
B C
C N
N A B C N Va Va
Va Va

4-Wire Wye, 3 Element with 4 CTs and Fuses


3 PTs3 x 0.1A Fuses 3 x 0.1A 4-Wire Wye, 3 Element with 4 CTs and no PTs Fuses 3 x 0.1A Fuses 3 x 0.1A
EarthCurrent
*Note: Optional CT for Ground Measurement
Earth GroundOnly *Note: Optional CT for Current Measurement Only

A B B C CN N A B C N A BA CB NC NA A B B C C N N

A B C N A
A B
B C
C N
N
AA B C N A B C N
B C N
CT CT CT CT
Shorting Shorting Shorting Shorting
Block Block Block Block

N/U N/U N/U


Va Va Va Va
Earth Earth Earth Earth
Ground Ground Vb Vb Ground Ground Vb Vb

CTsCT
Shorting
CT
Shorting
Vc Vc CTs CTs CT
Shorting
CT
Shorting
Vc Vc
Vn Vn Block Block Vn Vn
Block Block
Vaux Vaux Vaux Vaux
N/U N/U N/U
Va Va Va Va
Earth Earth Earth Earth
Ground Ground Vb Vb Ground Ground Vb Vb

CTs
CTs Vc Vc CTs
CTs CTs Vc Vc
Vn Vn Vn Vn
Vaux Vaux Vaux Vaux

Vn Vn
PTs PTs Vc Vc Vc Vc
Vn Vn
Va Va Va Va

Earth Ground FusesEarth Ground Fuses


2 x 0.1A Fuses 2 x 0.1A Vn 2 x 0.1A VnFuses 2 x 0.1A
PTs PTs Vc Vc Vc Vc
Vn Vn
B C N A B C N Va Va
A B C N A B C N Va Va

Earth Ground Earth2 Ground


Fuses x 0.1A Fuses 2 x 0.1A Fuses 2 x 0.1A Fuses 2 x 0.1A

A B
A B C N A B C
C N
N AA B
B C
C N
N A B C N
4-Wire Wye, 2.5 Element, 3 CTs and 2 PTs 3-Wire, 2 Element Delta Direct with 2 CTs

GEGridSolutions.com 11
EPM 9900P Advanced Power Quality Meter

Dimensional Drawings - EPM 9900P Meter


5.04”
6.91” [12.80cm]
10.74” [17.55cm]
1.87” 5.73”
[27.28cm] [4.75cm] [14.55cm

6.74” [17.12cm]
6.96” [17.68cm]
Front
5.04”
6.91” [12.80cm]
.55cm]
5.73”
[14.55cm] 7.49”/19.02cm
4.44” [11.28cm]

4. 44”/11. 28 cm
5.94” [15.09cm]

Back

5.04”
6.91” [12.80cm]
[17.55cm]
1.87” 5.73”
[4.75cm] [14.55cm] 7.49”/19.02cm
4.44” [11.28cm]
6.74” [17.12cm]
6.96” [17.68cm]

5.94” [15.09cm]

Side

12 GEGridSolutions.com
EPM 9900P Advanced Power Quality Meter

Dimensional Drawings - EPM 9900P Enclosure


12.09” (307.09 mm) 14.28” (362.71 mm)
10.29” (261.37 mm) 12.00” (304.80 mm)
4 x 0.31" 4 x 0.31"
( 7.87 mm) ( 7.87 mm)

17.52” (445.01 mm)


16.77” (425.96 mm)
16.28” (413.50 mm)
Va
Va VbVb Vc
Vc Vn
Vn

Earth
Ground

*Optional In
CT

Ic

Ib

Ia

Earth
Ground

Earth
Ground

AA BB CC N
N

LOAD
LOAD

4 Wire WYE 3 PT Hookup, 3 Element

4 Wire WYE 3 PT Hookup, 3 Element

GEGridSolutions.com 13
EPM 9900P Advanced Power Quality Meter

Technical Specifications
INPUT VOLTAGE RANGE SENSING METHOD COMMUNICATION FORMAT
• (5-347)VAC, Line to Neutral • Up to 1024 Samples per Cycle (Programmable) • Programmable parity and stop bits
• (10-600)VAC, Line to Line • 16 Bit A/D Resolution – Multiple Converters • Communication Protocols: Modbus TCP/IP, ASCII/
• True RMS RTU, DNP 3.0, IEC 61850 (Software Option B or C)
VOLTAGE INPUT WITHSTAND CAPABILITY • Constant CalibrationTM technology • ANSI Optical Port
• Voltage Inputs isolated to 2500VAC • Transient at 50 million samples per second • USB 1.1/2.0 Virtual COM Port
• RJ45 Ethernet Port 10/100BaseT
INPUT CURRENT RANGE ACCURACY RATING • Standard RJ45 Ethernet Port 10/100BaseT
• Programmable to any CT radio • ANSI C12.20 (Class 0.2) and IEC 62053-22 (Class • Optional Serial RS485 Ports (Meter, I/O card)
• Class 2: Nominal 1 A, with 2 times over range 0.2S) Accuracy, 0.06% Energy measurement • Optional 2nd Ethernet port - RJ45 Ethernet or
• Class 2: fault current recording to +/- 16 A peak accuracy Fiber Optic
• Class 20: Nominal 5 A, with 4 times over range • Full accuracy specifications available in User
Manual SHIPPING
• Class 20: fault current recording to +/- 80 A peak
• Time clock: 3.5 ppm for -40 to +85°C - less than Total shipping weight: approx. 6.5 lbs (2.9 kgs)
10 seconds drift per month on crystal sync; 2.0 Shipping container dimensions:
CURRENT INPUT WITHSTAND CAPABILITY (AT 23°C) ppm Typical from 0 - +40°C - less than 6 seconds 16” x 15.5” x 11.5”
• 100 Amps for 10 Seconds per month drift (40.64 am x 39.37 cm x 29.21 cm)
• 300 Amps for 3 Seconds
• 500 Amps for 1 Second UPDATE TIME COMPLIANCE
• 1 Second — Revenue Accurate Readings • ANSI C12.20 (Class 0.2) and IEC 62053-22 (0.2S
BURDEN • 1 Cycle — Faster updated readings Class) Accuracy
• Voltage Inputs: 0.072 VA/Phase Max at 600 Volts, • Customizable high-speed readings from 2 to 20 • ANSI C12.1 (Code for Electricity Metering)
0.003W/Phase Max at 120 Volts cycles RMS • ANSI C62.14 (Burst)
• Current Inputs: 0.008 VA per Phase Max at 20 • ANSI/IEEE C37.90.1 - Surge Withstand
Amps CONTROL POWER REQUIREMENTS • FCC Part 15, Subpart B, Class A
• HI Option: (100-240)VAC @50/60 Hz or (100-240) • IEC 61000-4-2 - ESD
ISOLATION VDC
• IEC 61000-4-3 - Radiant Immunity
All inputs to outputs are isolated to 2500 VAC • AC Option: (100-240)VAC @50/60 Hz
• IEC 61000-4-4 - Fast Transient
• LD Option: (18-60)VDC (24-48 VDC Systems)
• IEC 61000-4-5 - Surge Immunity
TEMPERATURE RATING • Burden: 25 VA Max
• IEC 61000-4-6 - Conducted Immunity
• Operating Temperature: (-20 to +70)°C
• IEC 61000-4-7 - Harmonics
• Humidity: Up to 95% RH Non-condensing FREQUENCY RANGE
• IEC 61000-4-15 - Flicker Meter
• Storage Temperature: (-30 to +80)°C 45Hz–69.9Hz
• IEC 61000-4-30 - Class A
• IEC 32052-11 - General Requirements
• IEC/CISPR 14-1 - Continuous EM Disturbance
• CE Marked
• UL and cUL Listed

Note: Please see product User Manual for


comprehensive specifications.

14 GEGridSolutions.com
EPM 9900P Advanced Power Quality Meter

Ordering
Base Meter ****** ** * ** * * ** ** ** Description
PL9900P
Enclosure ENC120 NEMA1 Rated - Indoor, Single Meter Enclosure, 120V
ENC277 NEMA1 Rated - Indoor, Single Meter Enclosure, 277V
XXXXXX None
Control Power AC 100-240VAC Power Supply
HI 90‐265VAC or 100‐240VDC
LD 18-60VDC (24-48VDC Systems)
Frequency 6 60 Hz
5 50 Hz
Current Inputs 5A 5A
1A 1A
Software A 512MB memory with 512 samples/cycle
B 1GB memory with 1024 samples/cycle, IEC 61850 Communications Protocol
C 4GB memory with 1024 samples/cycle, IEC 61850 Communications
Protocol and 50MHz Transient Recording
Slot 1 S 2-ports RS485 and 4 Pulse Outputs
X Empty Slot
Slot 2 E1 Second Ethernet Port - 10/100BaseTX, RJ45
E2 Second Ethernet Port - 100FX, Multimode ST Connector
XX Empty Slot
Slot 3 R1 6 Relay Outputs
D1 16 Status Inputs
XX Empty Slot
Slot 4 R1 6 Relay Outputs
D1 16 Status Inputs
XX Empty Slot

EPM 9900P Accessories


Internal Input/Output (I/O) Modules
Description
EPM 9900P Slot 1 PL9900P-ACC-SXX 2-ports RS485 and 4 Pulse Outputs
EPM 9900P Slot 2 PL9900P-ACC-E1X Second Ethernet Port, 10/100BaseTX, RJ45
PL9900P-ACC-E2X Second Ethernet Port, 100FX, Multimode, ST connector
EPM 9900P Slot 3 PL9900P-ACC-R1X 6 Relay Outputs
PL9900P-ACC-D1X 16 Status Inputs
EPM 9900P Slot 4 PL9900P-ACC-R1X (same as Slot 3) 6 Relay Outputs
PL9900P-ACC-D1X (same as Slot 3) 16 Status Inputs
Software upgrade PL9900P-ACC-SAB Upgrade Software option A to B:1GB memory with 1024 samples/cycle, IEC 61850 Communications Protocol
PL9900P-ACC-SAC Upgrade Software option A to C:4GB memory with 1024 samples/cycle, IEC 61850 Communications Protocol and 50MHz
Transient Recording
PL9900P-ACC-SBC Upgrade Software option B to C:4GB memory with 1024 samples/cycle, IEC 61850 Communications Protocol and 50MHz
Transient Recording
GE Communicator PLSOFT-COMS GE Communicator for Windows® Single User

External Input/Output (I/O) Modules


Analog Output Modules
PL9000-1MAON4O00 4 Channel 0-1 mA Analog Outputs
PL9000-1MAON8O00 8 Channel 0-1 mA Analog Outputs
PL9000-2OMAON400 4 Channel 4-20 mA Analog Outputs
PL9000-2OMAON800 8 Channel 4-20 mA Analog Outputs
Analog Input Modules
PL9000-8AI100000 8 Channel 0-1mA Analog Inputs
PL9000-8AI200000 8 Channel 4-20mA Analog Inputs
PL9000-8AI300000 8 Channel 0-5V DC Analog Inputs
PL9000-8AI400000 8 Channel 0-10 V DC Analog Inputs
Digital Dry Contact Relay/Solid State Pulse Outputs
PL9000-4RO100000 4 Relay Outputs, 5A, 250VAC/30 VDC, Form C Latching
PL9000-4PO100000 4 Solid State Pulse Outputs, Form A or C KYZ Pulses, 20 Pulses/sec. Max.
PL9000-PSIO00000 Auxiliary Power Supply (Required for External I/O Modules)
PL9000-MBIO00000 Auxiliary Mounting Bracket (Required for External I/O Modules)

GEGridSolutions.com 15
GE
650 Markland St.
Markham, ON
Canada L6C 0M1
Toll Free (NA Only): 1-800-547-8629
Tel: 905-927-7070
Fax: 905-927-5098

GEGridSolutions.com
IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered
trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark of
Schneider Automation. NERC is a registered trademark of North American Electric Reliability Council.
NIST is a registered trademark of the National Institute of Standards and Technology.
GE, the GE monogram, Multilin, FlexLogic, EnerVista and CyberSentry are trademarks of General Electric
Company.

GE reserves the right to make changes to specifications of products described at any time without notice
and without obligation to notify any person of such changes.

Copyright 2019, General Electric Company. All Rights Reserved. GEA-31996(E)


English
191003

You might also like