Installation Data Sheet
Series: 1:1 Belt Drive AS.3 SFC
Document No.: TI-DATA-2014-SFC 18S 22S
Version: 1.4
Revision Date: 09/11/15
Model SFC 18S SFC 22S
Rated Pressure [psig] 110 125 145 160 190 217 110 125 145 160 190 217
Electrical data may vary in accordance with motor manufacturer's specifications. Motors are EISA
II. ELECTRICAL DATA compliant.
Drive Motor
Motor HP 25 30
NEMA Nominal Efficiency % 91.7% 91.7%
Service Factor 1.24 1.22
Enclosure Type TEFC/IP 55 TEFC/IP 55
Insulation Class F F
Standard Voltage 460V/3ph/60Hz 460V/3ph/60Hz
Full Load Amps [FLA] @ 460V/3ph/60 Hz/YD 29.5 33.5
FAN MOTOR (A/C)
Enclosure Type TEFC/IP 55 TEFC/IP 55
Insulation Class F F
Fan Motor [HP], oilcooler | aircooler 0.74 0.74
Nominal Efficiency %, oilcooler | aircooler 76.5% 76.5%
Full Load Amps [FLA] @ 460V/3ph/60 Hz/YD, oilcooler 1.62 1.62
TOTAL PACKAGE DATA (A/C)
Do NOT operate package on any unsymmetrical power supply. Also do NOT operate package on power supplies like, for example, a three-phase star three-phase star
three-phase (open) delta or three-phase start with non-grounded neutral. The machine requires a symmetrical three-phase power (wye); 4-wire; (wye); 3-wire;
supply transformer with a WYE configuration output as shown on the right. In a symmetrical three-phase supply the phase angles and grounded neutral grounded neutral
voltages are all the same. Other power supplies are not suitable.
Continuous Duty (Hours per day) 24 24
Control Cabinet Class [NEMA] 12 12
Short Circuit Current Rating (SCCR) [kA] @ 460V/3ph/60 Hz/YD 50 50
Package Full Load Amps @ 460V/3ph/60 Hz/YD (A/C) 45 45
Recommended Disconnect Fuse Size [Amps] @ Dual-element time-delay fuse; based on 2011 NEC 240.6, 430.52, and Tables 430.52, 430.148,and
430.150.4.
70 70
460V/3ph/60Hz/YD (A/C)
Based on 2011 NEC 110.14(C), 220.3, 310.15, Table 310.16, 430.6, 430.22, 430.24 and Tables
Recommended Disconnect Wire Size [AWG/kcmil] @ 430.148 and 430.150. Use multi-strand copper core wire. Size calculated based on 40 oC ambient
3 AWG per phase and ground 3 AWG per phase and ground
460V/3ph/60Hz/YD (A/C) temperature, with 60°C insulation rated wire if package FLA x 1.25 is less than 100A or 75°C
temperature rated wire for 100A and larger.