Structural Concrete - 2020 - Haavisto - Compressive strength of core specimens drilled from concrete test cylinders
Structural Concrete - 2020 - Haavisto - Compressive strength of core specimens drilled from concrete test cylinders
Structural Concrete - 2020 - Haavisto - Compressive strength of core specimens drilled from concrete test cylinders
DOI: 10.1002/suco.202000428
TECHNICAL PAPER
KEYWORDS
air-entrained, concrete, compressive, strength, core, cylinder, size effect, testing
specimen10 and the cut aggregate particles may pop out lower compressive strength values.1 This has partly been
of the specimen during compression.11 It has also been explained by the drying shrinkage. As a result of the dry-
suggested that drilling as a destructive method would ing of the hardened cement paste, the surface tension in
cause microcracking in the cement matrix and weaken- small pores increases, which makes the cement gel more
ing of the bond between the aggregate particles and the compact.16 Another suggestion has been that under com-
hydrated cement.12 In addition, different compaction pression, the increase in the internal pressure on the
methods are used between the structures and the test water-filled capillary pores causes lower compressive
specimens, which might also influence on the compres- strengths. It has also been suggested that this effect
sive strength. applies only to the fully saturated specimens. On the
other hand, due to the deformations caused by the com-
pression, the partially saturated specimen may also
2.4 | Size effect become fully saturated during the compression test.17
lcore 2
F l=d = 1 − ðβ −α f core Þ 2 − , ð2Þ
dcore
The moisture content factor in ACI Guide 214.4R-1018 is The slenderness factors given in the above-mentioned
Fmc = 1.09 if the testing of the cores is preceded by 48 hr guidelines are summarized in Figure 2. To facilitate the
of water soaking, and Fmc = 0.96 if testing is preceded by comparison, all factors are presented in the same format
storage for 7 days at a temperature of 16–21 C and below as in ACI Guide 214.4R-10 (2010) and adjusted to have
60% relative humidity. The factor Fmc = 1.00 is used if the length-to-diameter ratio of 2.0 as a reference case
the storage of the cores before testing has been in accor- (Fl/d = 1.00).
dance with the ASTM standard C42 (2020), that is, stor-
ing in a sealed bag or similar for at least 5 days after
moisture exposure caused by the preparation of the speci- 3.4 | Other effects
mens. European standards have specified that cores
should be tested primarily in an air-dried condition (DIN In addition, a conversion factor to take into account the
EN 13791 / A20:2017–02; EN 13791:2019; SS 13 72 possibility of the lateral reinforcement in the core has
07:2005). been given in BS EN 12054–1 (2009),23 and a conversion
17517648, 2021, S1, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/suco.202000428 by Cochrane Peru, Wiley Online Library on [24/10/2024]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
HAAVISTO ET AL. E687
TABLE 2 The results of the fresh concrete tests (at the beginning of the casting/at the midpoint of the casting)
Slump test (mm) Flow table test (mm) Air content (%)
Concrete mixture The first batch The second batch The first batch The second batch The first batch The second batch
Mix 1 130 / 70 160 / 90 490 / 430 470 / 400 4.1 / 4.2 5.6 / 5.2
Mix 2 180 / 180 160 / 120 530 / 530 520 / 470 3.9 / 5.3 4.4 / 4.9
Mix 3 180 / 200 200 / 190 480 / 490 540 / 480 4.0 / 5.6 3.8 / 5.6
Ref mix 180 / 160 120 / 110 500 / 510 460 / 460 1.8 / 1.9 1.8 / 2.6
TABLE 3 The compressive strength and density test results for each specimen type and concrete mix
FIGURE 4 The different stages of the experimental programme: compaction (a), storing (b), drilling (c) and testing (d)
The air content of the concrete was determined by the (2012).31 Compression tests were made at the age of
water column method according to EN 12350–7 (2019).29 3 months in accordance with EN 12390–3 (2019)26 and
The results in Table 2 show that concrete slowly stiffens EN 12504–1 (2019)32 (Figure 4d).
during the casting, but for Mix 1 there was a significant Local density differences were examined from two
difference between these two measurements. 150 × 300 mm cylinders for each concrete mix from three
For practical reasons, all specimens were cast on one height locations. Perpendicularly drilled cores of 50 mm
layer. The compaction of concrete was carried out with a in diameter were cut into five specimens, as shown in
vibrating table according to standard EN 12390–2 Figure 6. The density was determined from these water-
(2019)30 (Figure 4a). The molds were covered with a plas- saturated specimens by dividing their mass by its volume
tic film for 46 to 50 hr before demoulding, followed by as determined by the water-displacement method.33 The
soaking in the water tanks until the age of 28 days. The samples were combined to give a density result from
temperature of the water tanks varied between 18 to three different depths from each height location.
22 C during the curing. Specimens were then stored in
laboratory conditions at temperatures of 19 to 22 C and
an of average 60% relative humidity until testing 5 | RESULTS A ND DISCUSSION
(Figure 4b).
The core specimens were drilled with the water- The mean and SD values of compressive strengths and
cooled diamond core drill bits (Figure 4c). Drilling was densities are presented in Table 3. The strength results
made parallel to the casting direction and centrally are obtained directly as a quotient of the ultimate load
through a 150 × 300 mm cylinder. Several core speci- divided by the cross-sectional area, without any conver-
mens were taken from the cylinder as shown in sion factors.
Figure 5. The cores were cut using a water-cooled dia- Figure 7 shows the relationship between the average
mond saw and both ends of the cores were grinded to strength obtained from each specimen type to the soaked
meet the requirements of standard EN 12390–1 150 × 300 mm cylinder's average strength. The widely
17517648, 2021, S1, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/suco.202000428 by Cochrane Peru, Wiley Online Library on [24/10/2024]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
E690 HAAVISTO ET AL.
F I G U R E 7 The
comparison of average
compressive strength and
standard deviation of each
specimen type to the
compressive strength average
obtained from the soaked
150 × 300 mm cylinders
concrete mixes, the strength ratio of 100 × 100 mm cores between different concrete types in the above-mentioned
and air-cured 150 × 300 mm cylinders was on average 0.85, ratios. It is noteworthy here that cubes are the only speci-
while the ratio was 0.81 between 100 × 100 mm cores and men type in this study, which was tested perpendicular
soaked 150 × 300 mm cylinders. These ratios are of the to the casting direction. Therefore, when comparing the
same order as the conversion factor 0.82 between 1.0 and strength obtained from other specimens with the cube
2.0 length-to-diameter ratios presented in EN13791 strength, the effect of the testing direction is also
(2019).40 However, there were significant differences in the included in the test results. It is more significant in con-
above-mentioned ratios depending on the concrete type. crete types, which are more sensitive to segregation.
The ratio between the 100 mm core strength and the air-
cured 150 × 300 mm cylinder strength varied from 0.78 to
0.93 depending on the concrete type, while the ratio 5.3 | Drilling effect
between the 100 mm core strength and the soaked
150 × 300 mm cylinder strength varied from 0.74 to 0.88. The ratios between cylinder strength and core specimen
Since the mix proportions between Mix 1 and Mix strength are shown in Figure 8 for 100 × 100 mm and
3 were almost equal except for the silica fume, which was 150 × 300 mm specimens. The curing, compaction and
included in Mix 3, the results give some indications that the storing of test specimens as well as moisture conditions
use of the silica fume might have an advantageous effect on during the compression test were similar between cylin-
the compressive strength in test specimens, with the length- der specimens and cores. Thus, the difference in the
to-diameter ratio of 1.0 compared with the strength of the strength between them is mainly caused by the different
specimens with a l/d-ratio of 2.0. One explanation for this surfaces of the specimens. Based on the test results, dril-
phenomenon could be possible differences in the effect of ling seems to have a clear weakening effect on the com-
silica on the compressive and splitting tensile strength prop- pressive strength. Similar findings have been achieved in
erties of concrete. This has been referred to, for example, in several other studies.36,44,45 In the current investigation,
the results of the studies by Amudhavalli & Mathew41 and drilling had more of an effect on compressive strength for
Jaber, Gorgis & Hassan.42 The splitting tensile strength 100 × 100 mm specimens than for 150 × 300 mm speci-
value could be expected to be of greater importance in the mens. This may be due in part to the smaller size of the
compressive strength tests of slender specimens due to the specimen, which results in the ratio of the drilled surface
lesser effect of the end friction. area to the specimen volume being much bigger on the
The strength ratio between 100 × 100 mm cores and 100 × 100 mm specimen than the 150 × 300 mm speci-
air-cured 150 mm cubes was on average 1.01 for all con- men. A difference in slenderness might also have an
crete mixes, while the strength ratio of air-cured 150 × influence.
300 mm cylinders and 150 mm cubes was on average Compressive strength of the 150 × 300 mm cores was
0.85, which agreed with the ratios 0.82–0.85 reported by on average 7%–8% lower than the strength of the cylinder
Zabihi & Eren.43 There were also clear differences specimens of the same size, while with the most common
17517648, 2021, S1, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/suco.202000428 by Cochrane Peru, Wiley Online Library on [24/10/2024]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
E692 HAAVISTO ET AL.
F I G U R E 8 Ratios of compressive strength mean values obtained from different specimen types and comparison to the ratios provided
by the different codes
core specimen size – 100 × 100 mm – that ratio was 11% difference observed between the air-entrained concrete
excluding Mix 2, which had a 17% ratio. These ratios are types and the reference concrete.
higher than the correction factors for the drilling effect The observed difference is slightly higher than that in
proposed by Bartlett & MacGregor.46 Li's48 study of 0.45 water/cement ratio concrete (4%), but
Based on the results, the effect of drilling on air- is considerably lower than the difference in 0.65 water/
entrained concrete did not differ from that of nonair- cement ratio concrete (16%). It is noteworthy that Li used
entrained concrete, and the magnitude of the drilling smaller 100 × 200 mm cylinder specimens in his study,
effect seems to be independent of the concrete mix. so the saturation rate can be assumed to be higher.
Bisher47 had previously observed that concrete age, the The differences in the compressive strength between
amount of cement or the type of aggregate did not have soaked and air-dried cores in various studies are signifi-
significant influence on drilling effect. cantly higher than those obtained for the cylinder speci-
mens in this study. Bartlett & MacGregor49 put together
data from several different studies and concluded that
5.4 | Effect of the moisture content the strength obtained from air-dried cores was on average
during compression test 14% higher than the strength obtained from the cores
that had been soaked for at least 40 hr. Khoury et al.34
The effect of the specimen moisture content during test- came to a very similar conclusion in their recent study.
ing was studied by comparing the compressive strength
values of 72 hr-soaked and air-dried 150 × 300 mm cylin-
der specimens. Figure 8 reveals that the compressive 5.5 | Strength and density differences in
strength average of the air-dried 150 × 300 mm cylinders test specimens
was 5%–6% higher than that of the same sized 72 hr-
soaked test specimens. The ratio seems to be independent Differences in density and compressive strength values in
of the concrete mix and there was no significant different parts of 150 × 300 mm cylinders were clarified by
17517648, 2021, S1, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/suco.202000428 by Cochrane Peru, Wiley Online Library on [24/10/2024]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
HAAVISTO ET AL. E693
comparing the results of the core specimens taken from dif- 6 | CONCLUSIONS
ferent height positions. In addition, differences in density in
the transverse direction of the cylinder were studied. This paper presents the compressive strength results
It can be seen from Figure 9 that the compressive obtained from different types of concrete specimens with
strength increased in most test specimens from the casting similar compaction and curing conditions. The influence
surface to the bottom. This finding is in agreement with of the size of the core specimens, the correlation between
the findings of Moccia et al. (2020).50 A similar phenome- the core strength and the same size cylinder specimen
non is also seen in density results in Figure 9, but with the strength, the effect of the moisture condition during test-
difference that the cores taken closest to the casting sur- ing, as well as the correlation between the core strength
face in many cases have a higher density than the next and the strength obtained from the standard specimens
core below. Results also show that with the reference mix, were studied with more than 650 test specimens made
the density is almost independent of the height position. with four different concrete types. The conclusions of this
This indicates that the entrained air voids may not be study can be presented as follows:
evenly distributed in air-entrained concrete mixes. The
results of the horizontal density differences at different 1. The influence of the specimen size on the concrete
height positions are shown in Figure 10. compressive strength with drilled cores as well as the
correlation between core strength and standard speci-
men strength is dependent on the concrete mix. It is
recommended that a similar study with a larger num-
ber of different concrete mixes be conducted in order
to determine the effect of the different components
and properties of the concrete on the strength ratios
between different specimen types.
2. Drilling has a clear weakening effect on the com-
pressive strength of the test specimen. Based on the
test results, the authors propose a multiplying factor
of 1.09 for 150 × 300 mm core size and a factor of
1.12 for 100 × 100 mm core size for concrete types
with maximum aggregate size of Dmax = 16 mm if
the compressive strength obtained from the cores is
needed to convert to a compressive strength that
F I G U R E 9 The comparison of average density (a) and average corresponds of the same sized cylinders under simi-
compressive strength (b) at different height locations (c) of each specimen lar moisture conditions. Air-entrained concrete does
type to the total average values obtained from the same size cores not seem to differ in terms of drilling effect from the
F I G U R E 1 0 Density
results (kg/m3) at the different
height and depth locations of
150 × 300 mm cylinder
17517648, 2021, S1, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/suco.202000428 by Cochrane Peru, Wiley Online Library on [24/10/2024]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
E694 HAAVISTO ET AL.
nonair-entrained concrete. Further tests are 7. Al-Neshawy F, Ojala T, Punkki J. Stability of air content in
required to estimate the drilling effect for concrete fresh concretes with PCE-based superplasticizers. Nordic Con-
types with maximum aggregate sizes different to crete Res. 2019;60(1):145–158. https://doi.org/10.2478/ncr-
2019-0093.
those used in this study.
8. Choi S, Thienel KC, Shah SP. Strain softening of concrete in
3. The compressive strength of the air-dried 150 × 300 compression under different end constraints. Magazine Con-
mm cylinders was found to be on average 5%–6% crete Res. 1996;48(2):103–115. https://doi.org/10.1680/macr.
higher than the compressive strength of the same size 1996.48.175.103.
cylinders with a 72 hr soaking period prior to the test- 9. Suprenant, B. A. (1995). Core strength variation of in-place
ing, regardless of the concrete mixes. concrete. In The Aberdeen Group
4. The SD of the compressive strength results obtained 10. Kopf RJ, Cooper CG, Williams FW. In situ strength evaluation
of concrete case histories and laboratory investigations. Con-
from 50 × 50 mm cores was clearly higher than in
crete Int. 1981;3(3):66–71.
other core sizes. The authors propose avoiding the
11. Bartlett FM, MacGregor JG. Effect of core diameter on concrete
50 × 50 mm core size for determining the compressive core strengths. ACI Mater J. 1994b;91(5):460–469.
strength of concrete with maximum aggregate size of 12. McIntyre M, Scanlon A. Interpretation and application of core
Dmax = 16 mm, or alternatively to use a significantly test data in strength evaluation of existing concrete bridge
larger number of specimens. structures. Canadian J Civil Eng. 1990;17(3):471–480. https://
5. The effect of the silica fume was not within the scope of doi.org/10.1139/l90-051.
this study, but the results give some indications that the 13. Weibull W. A Statistical Theory Of The Strength Of Materials.
Stockholm: Ingeniörsvetenskapsakademiens handlingar, nr,
use of silica fume might have an advantageous effect on
1939;p. 151.
specimens with a l/d-ratio of 1.0 when compressive 14. Tucker J. Effect of dimensions of specimens upon the precision
strength is compared with specimens with a l/d-ratio of of strength data. ASTM Proc. 1945;45:952–960.
2.0. The effect of the cement replacement materials on 15. Hansen H, Kielland A, Nielsen KEC, Thaulow S. Compressive
the compressive strength ratios between different speci- strength of concrete - cube or cylinder? Bullletin (RILEM,
men types will require further investigation. Paris). 1962;17:23–30.
16. Wittmann FH. Surface tension skrinkage and strength of hard-
A C K N O WL E D G M E N T S ened cement paste. Mater Struct. 1968;1(6):547–552. https://
doi.org/10.1007/BF02473643.
The authors gratefully acknowledge the financial support
17. Popovics S. Effect of curing method and final moisture condi-
provided by the Finnish Transport Agency, the Finnish tion on compressive strength of concrete. J American Concrete
Concrete Industry and Rudus Oy. The authors would also Inst. 1986;83(4):650–657. https://doi.org/10.14359/10658.
like to thank Mr. Heikki Alho and Mr. Kasperi Pirttikoski 18. ACI 214.4R-10. Guide For Obtaining Cores And Interpreting
for their assistance in the laboratory phase of this study. Compressive Strength Results. Farmington Hills, Michigan,
USA: American Concrete Institute, 2010.
DATA AVAILABILITY STATEMENT 19. SFS 7022:2019. Concrete. Application of standard SFS-EN
206 in Finland. Finnish Standards Association SFS, 2019
The data that supports the findings of this study are avail-
20. SS 13 72 07: Betongprovning - Hårdnad betong -
able in the supplementary material of this article.
Tryckhållfasthet - Omräkningsfaktorer. Stockholm, Sweden:
ORCID Swedish Standards Institute, 2005
21. DIN EN 13791 / A20:2017–02. Bewertung der Druckfestigkeit von
Jukka Haavisto https://orcid.org/0000-0003-0083-0701
Beton in Bauwerken oder in Bauwerksteilen; Änderung A20. Ber-
lin, Germany: Deutsches Institut für Normung e. V, 2017.
R EF E RE N C E S 22. ASTM C42/C42M-20. Standard test method for obtaining and
1. Neville AM. Properties of Concrete. 4th ed. Essex, England: testing drilled cores and sawed beams concrete (2020). https://
Longman Group Limited, 1995. doi.org/10.1520/C0042
2. Breysse, D. (2012). Non-destructive assessment of concrete 23. BS EN 12504–1:2009. Testing Concrete In Structures, Part 1:
structures: reliability and limits of single and combined tech- Cored Specimens – Taking, Examining and Testing In Com-
niques https://doi.org/10.1007/978-94-007-2736-6 pression. London: British Standard Institution, 2009;p. 16.
3. Neville AM. Core tests: Easy to perform, not easy to interpret. 24. BS EN 12504–1:2019. Testing Concrete in Structures, Part 1:
Concrete Int. 2001;23(11):59–68. Cored Specimens – Taking, Examining and Testing in Com-
4. Moccia F, Kubski X, Fernández Ruiz M, Muttoni A. The influ- pression. London: British Standard Institution, 2019;p. 19.
ence of casting position and disturbance induced by reinforce- 25. BS 6089:2010. Assessment Of In-Situ Compressive Strength –
ment on the structural concrete strength. Struct Concrete. Complementary Guidance to that given in BS EN 13791. Lon-
2020;1–28. https://doi.org/10.1002/suco.201900562. don: British Standard Institution, 2010.
5. Pigeon M, Pleau R. Durability of concrete in cold climates. 26. SFS-EN 12390–3: Testing hardened concrete. Part 3: Compres-
New York: E & FN Spon, 1995. sive strength of test specimens. European Committee for Stan-
6. Rauhanen M, Kuusela K. Taitorakenteiden erikoistarkastusten dardization, 2019
laatuvaatimukset - Sillat, Liikenneviraston ohjeita 28/2018. 27. SFS-EN 12350–2: Testing fresh concrete. Part 2: Slump test.
Helsinki: Liikennevirasto, 2018. European Committee for Standardization, 2019
17517648, 2021, S1, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/suco.202000428 by Cochrane Peru, Wiley Online Library on [24/10/2024]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
HAAVISTO ET AL. E695
28. SFS-EN 12350–5: Testing fresh concrete. Part 5: Flow table test. 47. Bisher H. Relationship between cylinder and core compressive
European Committee for Standardization, 2019 strength. J Sci Tech. 2010;15(1):26–31.
29. SFS-EN 12350–7: Testing fresh concrete. Part 7: Air content. Pres- 48. Li, G. (2004). The effect of moisture content on the tensile strength
sure methods. European Committee for Standardization, 2019 properties of concrete (M Sc. Thesis). University of Florida
30. SFS-EN 12390–2: Testing hardened concrete. Part 2: Making 49. Bartlett FM, MacGregor JG. Effect of moisture condition on
and curing specimens for strength tests. European Committee concrete cores strengths. ACI Mater J. 1994c;91(3):227–236.
for Standardization, 2019 https://doi.org/10.14359/4042.
31. SFS-EN 12390–1: Testing hardened concrete. Part 1: Shape, 50. Moccia F, Yu Q, Fernández Ruiz M, Muttoni A. Concrete com-
dimensions and other requirements for specimens and moulds. pressive strength: From material characterization to a struc-
European Committee for Standardization, 2012 tural value. Struct Concrete. 2020;1–21. https://doi.org/10.
32. SFS-EN 12504–1: Testing concrete in structures. Part 1: Cored 1002/suco.202000211.
specimens. Taking, examining and testing in compression.
European Committee for Standardization, 2019
AUTHOR BIOGRAPHIES
33. SFS-EN 12390–7: Testing hardened concrete. Part 7: Density of
hardened concrete. European Committee for Standardization, 2019
34. Khoury S, Aliabdo AA-H, Ghazy A. Reliability of core test – Jukka Haavisto, Researcher, Tam-
Critical assessment and proposed new approach. Alex Eng J. pere University, Unit of Concrete
2014;53(1):169–184. https://doi.org/10.1016/j.aej.2013.12.005. and Bridge Structures, PO Box
35. Tuncan M, Arioz O, Ramyar K, Karasu B. Assessing con-
600, FI-33014 Tampere University.
crete strength by means of small diameter cores. Construct
Build Mater. 2008;22(5):981–988. https://doi.org/10.1016/j.
conbuildmat.2006.11.020.
36. Al-Zharani TM, Demirboga R, Khushefati WH, Taylan O. Mea-
surement and prediction of correction factors for very high core
compressive strength by using the adaptive neuro-fuzzy tech-
niques. Construct Build Mater. 2016;122:320–331. https://doi. Ari Husso, Researcher, Tampere
org/10.1016/j.conbuildmat.2016.06.019. University, Unit of Concrete and
37. Arioz O, Ramyar K, Tuncan M, Tuncan A, Cil I. Some factors Bridge Structures, PO Box 600, FI-
influencing effect of core diameter on measured concrete com- 33014 Tampere University.
pressive strength. ACI Mater J. 2007;104(3):291–296.
38. Meininger RC. Effect of core diameter on measured concrete
strength. J Mater. 1968;3(2):320–336.
39. Yip WK, Tam CT. Concrete strength evaluation through the
use of small diameter cores. Magazine Concrete Res. 1988;40
(143):99–105.
Anssi Laaksonen, Professor, Tam-
40. SFS-EN 13791: Assessment of in-situ compressive strength in
structures and precast concrete components. European Com-
pere University, Unit of Concrete
mittee for Standardization, 2019 and Bridge Structures, PO Box
41. Amudhavalli NK, Mathew J. Effect of silica fume on strength 600, FI-33014 Tampere University.
and durability parameters of concrete. Int J Eng Sci Emerging
Tech. 2012;3(1):28–35.
42. Jaber A, Gorgis I, Hassan M. Relationship between splitting
tensile and compressive strengths for self-compacting concrete
containing nano- and micro silica. MATEC Web Conf. 2018;
162:1–8. https://doi.org/10.1051/matecconf/201816202013.
43. Zabihi N, Eren Ö. Compressive strength conversion factors of
concrete as affected by specimen shape and size. Res J Appl Sci
Eng Tech. 2014;7(20):4251–4257. https://doi.org/10.19026/ SU PP O R TI N G I N F O RMA TI O N
rjaset.7.796. Additional supporting information may be found online
44. Ergün A, Kürklü G. Assessing the relationship between the in the Supporting Information section at the end of this
compressive strength of concrete cores and molded specimens.
article.
Gazi University J Sci. 2012;25(3):737–750.
45. Ju M, Park K, Oh H. Estimation of compressive strength of
high strength concrete using non-destructive technique and How to cite this article: Haavisto J, Husso A,
concrete core strength. Appl Sci (Switzerland). 2017;7(12):1–16.
Laaksonen A. Compressive strength of core
https://doi.org/10.3390/app7121249.
46. Bartlett FM, MacGregor JG. Assessment of concrete strength in
specimens drilled from concrete test cylinders.
existing structures, Structural Engineering Report No. 198. Structural Concrete. 2021;22(Suppl. 1):E683–E695.
Edmonton: University of Alberta; 1994a. https://doi.org/10.1002/suco.202000428