Ref: Comments on Protective setting calculations and relay setting schedule 33 & 11kV System
Page 1 of 2
resistor as 450 Ohm? What is design
margin standard
16 MVA Transformer Secondary cables
and 500 kVA Transformer cables entering The same is included in sectional arrangement
2
slope details like sectional drawing to be drawing. Refer Section E-E & Section M-M.
shown in the drawing.
D Bus Bar Differential protection
why you select 1500 ohm instead of 600
D.1 Noted. The same is revised in document
ohm
E Grid OG breaker OC & EF settings
Noted. However it shall be noted that due to this
limitation, required time grading of 0.3 sec
We are restricted by the OETC incomers between all concerned breakers is not possible,
E.1 Noted Noted
hence keep TMS = 0.3 for OC & EF hence to achieve minimum discrimination we
have sacrificed grading between Grid OG –
PSS IC breakers.
F Distance Protection of feeder-I
As per attached SLD, only yellow highlighted
conductor is Poplar and remaining is Panther,
'3.55 kM of OHL is poplar type see
F.1 In attached SLD, Yellow highlighted part is
attached SLD.
indicated only in feeder-2, Hence it is not
considered for Feeder-1.
Page 2 of 2
CALCULATION SHEETS
LIST OF CONTENTS
1. OBJECTIVES: ............................................................................................................................................. 3
1. OBJECTIVES:
These calculations are for the determination of Protection Settings and Relay Co-ordination for the
Electrical System of 33/11 kV, Shinas Grid substation Outgoing feeders to Rumailah Grid station.
2. NETWORK CONDITIONS AND ASSUMPTIONS:
2.1 The fault currents used for the protection settings calculation are based upon the maximum 3-Phase &
1-Phase Phase fault levels at 33kV bus of Shinas Grid substation, the data is provided by client. The
fault currents are as follows :
Sr. No. Source Grid station & Bus 3-Ph fault current in kA 1-Ph fault current in kA
2.2 Independent operation of 33kV Incomer feeders from Shinas Grid substation & Rumailah Substation is
considered on 33kV side whereas for 11kV bus parallel operation of 2 x 20 MVA Transformer is
considered for protective relay settings. This operating philosophy is confirmed by client.
2.3 It is assumed that in 33kV Switchgear Panel, Incomer-1 &2 connected with Bus A & B respectively and
bus coupler will be in open.
2.4 The fault current on 11kV bus is calculated considering single as well as double feed circuit, however
for the purpose of protective relay settings maximum fault current with independent operation of
transformers and single feed operation of 33kV incoming source is considered.
2.5 For over current co-ordination IEC defined Standard Inverse (SI) curve is used.
The equation of the curve is,
0.14
Operating time, t (sec.) = TMS
(PSM)0.02 - 1
2.6 Setting of instantaneous overcurrent element for transformer feeders shall be greater than
a) 1.3 x transformer maximum symmetrical through fault current, and
b) Maximum magnetising inrush current to avoid any undesirable tripping during switching.
Where manufacturer’s data is not available, magnetising inrush current is generally assumed to be 10 x
full load current for 100 msecs.
2.7 Minimum grading margin of 0.3 sec. is considered between the two relays for proper coordination.
2.8 The overcurrent & earth fault relay make and model number for 33kV outgoing feeder at Shinas Grid
Substation is assumed to be Siemens 7SJ8021.
33kV Bus Coupler at New 1-1 400/1A 33/√3/.110/√3 kV 51/51N/50/50N Siemens 7SR1103
4
Rumailah PSS
1-2 1-1 400/1A 33/√3/.110/√3 kV 25 Siemens 7SG1172
20 MVA Transformer Outgoing at 1-1 400 /1A 87T Siemens 7SR2423
5
Rumailah PSS 2-2 1200/1A 50/51/50N/51N Siemens 7SR1103
1-2 1-2 11/√3/.110/√3 kV 67/67N Siemens 7SR1206
-- SBEF # Siemens 7SR1101
6 11kV Incomer at Rumailah PSS
-- 87NL (LV) # Siemens 7SR1103
2-2 1200 /1A 87T Siemens 7SR2423
7 11kV Bus Coupler Rumailah PSS 1-2 1200 /1 A 50/51/50N/51N Siemens 7SR1102
I. Fault Level Calculations for 2X20 MVA, 33/11kV Primary substation at Rumailah with incoming feed from 132/33kV Shinas Grid
station - Single Feed.
1.1
The Three Phase Fault & Single Phase Earth Fault current on 33kV Bus at Source i.e. Existing 132/33 kV Shinas Grid Grid Station:
Three Phase Fault Current = 19.41 kA (Data received from client via mail)
Single Phase Earth Fault Current = 3 kA (Data received from client via mail)
1.2 3 Phase Fault at 33kV switchgear Bus at Rumailah Substation when Feed from Existing 132/33kV Shinas Grid Station is
operating (i.e. Single circuit operation - Feeder-1) :
Maximum 3 Phase Fault Current at Existing 132/33kV Grid Station (i.e. on 33kV Side)
= 19.41 kA (Data received from client via mail)
Assumptions :-
Base kV = 33.00 kV
Base MVA = 20.00 MVA
Source Impedance, ZS (i.e. upto 33kV side) = 33/(sqrt(3)*Iks)
ZS = 0.000 + j 0.982 ohm
Zs = 0.982 ohm
Base Impedance = (Base kV2 / Base MVA) = Zb = 54.45 ohm (33kV2/20MVA)
= 33/(sqrt(3)*ZT1) kA
3 Ph. bolted fault current at 33kV bus of Rumailah S/S = 4.23 kA
1.3 1 Phase Fault at 33kV bus of Rumailah Substation fed from Existing Grid Station
Maximum Single Phase Fault Current at Existing Grid Station
= 3 kA
(i.e. on 33kV Side)
Total positive sequence Impedance of the line Z1L1 = 1.692 +j 3.201 ohm
Total negative sequence Impedance of the line Z2L1 = 1.692 +j 3.201 ohm
Total zero sequence Impedance of the line Z0L1 = 5.116 +j 9.660 ohm
Reference bus
Source
U0=1 pu
ZS Z1L1
Z2L1
Z0L1
Incomer-2
Type of incoming line = Cu/ XLPE/ SWA/ PVC Cable
= 33/(sqrt(3)*ZT1) kA
3 Ph. bolted fault current at 33kV bus of Rumailah S/S = 4.210 kA
1.5 1 Phase Fault at 33kV bus of Rumailah Substation fed from Existing Grid Station
Total positive sequence Impedance of the line Z1L1 = 1.700 +j 3.214 ohm
Total negative sequence Impedance of the line Z2L1 = 1.700 +j 3.214 ohm
Total zero sequence Impedance of the line Z0L1 = 5.143 +j 9.702 ohm
Reference bus
Source
U0=1 pu
ZS Z1L1
Z2L1
Z0L1
II. Fault Level Calculations at 11kV Bus for 33/11kV Indoor Rumailah Primary Substation
2.1 3 Phase Fault at 11kV Bus when 20 MVA Transformer-1 is operating with Feeder-1 as source of supply and 11kV
bus coupler is in Open condition.
System Voltage = 33 kV
Fault on 11kV Bus is calculated considering Feeder-1 is supplying to 33kV Bus with two incomers operating independently.
Max. 3 Phase Fault current on 33kV Bus, Ikr = 4.23 kA
Base kV (kVb) = 11 kV
2
Base Impedance (Zb) = 6.05 ohm (11kV /20MVA)
Equivalent fault impedance (On 20 MVA Base) upto fault (Ignoring cable impedance as it is
= Zeq
location very small in length )
= Zs + ZT1
= 0.199 pu
Base MVA
Fault level in MVA at 11kV Bus =
Total fault impedance Zeq
= 100.51 MVA
3 Phase Fault current at 11kV Bus, Ikr = Fault MVA/(Sqrt(3)*11)
= 5.28 kA
2.2 1 Phase-Earth Fault at 11kV Bus when 20 MVA Transformer-1 is operating with Feeder-1 as source of supply and
11kV Bus coupler is in open condition.
Transformer Impedance with negative tolerance = 0.116 pu
(Z1T = Z2T = Z0T)
Source impedance upto transformer primary = 9.026 ohm (Impedance considering
(Z1S = Z2S) independent operation )
= 9.026/54.45 (Actual Value / Base Impedance)
= 0.166 pu
Reference bus
Source
U0=1 pu
ZS Z0T
Z1T
Z2T
Total Impedance for Ground fault Zgt = Zs1+ Zs2 + Z1T + Z2T + Z0T
= 0.17 + 0.116 + 0.116 + 0.116
= 0.514 pu
Zgt (ohms) = 3.108 ohm
Line to Ground fault current = 3VL-N/Zgt
= 6.13 kA
2.3 3 Phase Fault at 11kV Bus when 20 MVA Transformer-2 is operating with Feeder-2 as source of supply and bus coupler
on 11kV bus is in open condition.
System Voltage = 33 kV
Fault on 11kV Bus is calculated considering Feeder-2 is supplying to 33kV Bus with two incomers operating independently.
2.4 1 Phase-Earth Fault at 11kV Bus when 20 MVA Transformer-2 is operating with Feeder-2 as source of supply with bus
coupler on 11kV Bus is in open condition.
Transformer Impedance with negative tolerance = 0.116 pu
(Z1T = Z2T = Z0T)
Source impedance upto transformer primary = 9.056 ohm
(Z1S = Z2S) independent operation )
= 4.528/54.45 ohm (Actual Value / Base Impedance)
= 0.166 pu
Reference bus
Source
U0=1 pu
ZS Z0T
Z1T
Z2T
Total Impedance for Ground fault Zgt = Zs1+ Zs2 + Z1T + Z2T + Z0T
= 0.17 + 0.116 + 0.116 + 0.116
= 0.514 pu
Zgt (ohms) = 3.112 ohm
Line to Ground fault current = 3VL-N/Zgt
= 6.13 kA
2.5 3 Phase bolted fault at 11kV Bus with Bus coupler on 11kV bus in closed condition.
System Voltage = 33 kV
Total Impedance of Circuit-1 upto fault location = Source Impedance of + Transformer-1 Impedance
Feeder-1 upto 33kV Bus ( with -ve) tolerance
= 0.199 pu
Source Impedance of Transformer-2 Impedance
Total Impedance of Circuit-2 upto fault location = +
Feeder-2 upto 33kV Bus ( with -ve) tolerance
= 0.2 pu
Base MVA (MVAb) = 20 MVA
(Transformer MVA is considered as Base MVA)
Base KV (kVb) = 11 kV
Base Impedance (Zb) = 6.05 ohm
2.6 1 Phase-Earth Fault Current at 11kV Bus with Bus coupler on 11kV Bus in closed condition.
= 10.87 MVA
3 Phase Fault current at 415V Bus, Ikr = Fault MVA/(Sqrt(3)*0.415)
= 15.13 kA
3.2 1 Phase-Earth fault at 415V Bus when single 500kVA Transformer is operating
Transformer Impedance ( with -ve tolerance) = 0.043 pu (as calculated above)
(Z1T = Z2T = Z0T)
Source impedance upto transformer primary at 500 kVA = 0.199 pu
(Z1S = Z2S)
Converting source impedance on 500kVA base = 0.005 pu (0.199*0.5/20)
Total Impedance for Ground fault Zgt = Zs1+Zs2+Z1+Z2+Z0
= 0.134 pu
Zgt (ohms) = 0.046 ohm
Line to Ground fault current = 3VL-N/Zgt
= 15.58 kA
Note :- Following are the assumptions considered for the purpose of relay co-ordination :
1. For Purpose of relay co-ordination 19.41 kA & 3 kA fault level is used at Shinas Substation
2. For 33kV Incomer/bus coupler and Outgoing feeders 4.23 kA & 1.59 kA fault level is used.
3. For 11kV Incomer and Bus coupler relaying, individual fault level is used whereas for outgoing feeders 10.53 kA & 14.61 kA fault level is used.
Hence summarising,
Curve = SI
PS = 0.30 In
TMS = 0.15
High set element is set greater than transformer inrush current or 1.3 times Transformer
Through Fault Current.
1.3 x Transformer Through fault current = 1.3 x 571 A
= 742 A
Transformer inrush current, I = 10 x IFLC
= 262 A
Since 1.3 x Tx through fault current is greater than transformer inrush current, I>>
setting is selected to be greater than 1.3 x Transformer through fault current.
Selected setting = 7.5 In
Hence summarising,
PS = 7.5 In
Time delay = 0.10 sec
= 12.253 kA
Max 1PH fault current at 11kV side when
20MVA transformers operating in parallel
Io setting (PS) = 0.2 Ien
Apprx. Operating time = 0.05 sec
Hence summarising,
Curve = SI
Current setting, Io (PS) = 0.20 Ien
TMS = 0.025
Instantaneous setting = Blocked
Hence summarising,
Curve = SI
PS = 1.00 In
TMS = 0.05
Instantaneous setting = Blocked
Hence summarising,
Curve = SI
Current setting, Io (PS) = 0.20 Ien
TMS = 0.025
Instantaneous setting = Blocked
Curve = SI
Max 3 PH fault current at 11kV side = 10.530 kA
when 20MVA transformers operating in
parallel
PS = 1.0 In
Maximum operating time of
downstream 11kV Feeders for above
fault = 0.113 sec (Data confimred by client)
11kV OG Feeder required operating
= Operating time of OG breaker + 0.3 sec (grading time)
time
= 0.413 sec
PSM = {Fault Current / (PS x CT Ratio)}
PSM = {(10.53 x 1000) / (1 x 400)}
PSM = 26.33
PSM = 20 (Limited to 20)
For Overcurrent Curve co-ordination, IEC defined SI curve is used.
Operating Time = TMS { 0.14/ ( (PSM)0.02 -1) }
TMS = 0.182
Selected TMS = 0.1 ( As per next available setting) B
Hence actual operating time = 0.23 sec
Hence summarising,
Curve = SI
PS = 1.00 In
TMS = 0.1
Instantaneous setting = Blocked
Curve = SI
Max 1PH fault current at 11kV side = 12.253 kA
when 1 transformers is operating
Io setting (PS) = 0.2 Ien
Maximum operating time of
downstream 11kV Feeders for above = 0.1 sec (Data confimred by client)
fault
11kV OG Feeder required operating
= Operating time of OG breaker + 0.3 sec (grading time)
time
= 0.4 sec
Bus Section CB operating time required = Operating time of 11kV Feeder CB + 0.3 sec
(Grading margin)
= 0.53 sec
B
PSM = {Fault Current / (PS x CT Ratio)}
PSM = {(5.28 x 1000) / (1 x 1200)}
PSM = 4.4
For Overcurrent Curve co-ordination, IEC defined SI curve is used.
Operating Time = TMS { 0.14/ (PSM)0.02 -1) }
Since the 67 relays will be operational only when both transformers will be in parallel, they shall operate
in minimum time for fault current when looking into transformer.
The fault contribution (total) when both = 10.53 kA (As per Fault Level Calculation)
20MVA transformers are in operation
(estimated)
PS desirable = 0.5 In
Since the 67N relays will be operational only when both transformers will be in parallel, they shall
operate in minimum time for fault current when looking into transformer.
The fault contribution (total) when both = 12.25 kA (As per Fault Level Calculation)
20MVA transformers are in operation
(estimated)
PS = 0.2 Ien
PSM = {Fault Current / (PS x CT Ratio)}
Actual Operating time with TMS of 0.05 = 0.14 x 0.05 / (20 ^ 0.02 - 1)
Operating time = 0.113 sec
TMS = 0.05
PS = 0.20 Ien
Instantaneous setting = Blocked
Direction of operation ….. looking into 20MVA Transformer
RCA recommended ….. -45º (Inductive)
Operating time required = 11kV Bus CB Operating Time + 0.3 (Grading margin)
= 0.88 sec
PSM = {Fault Current / (PS x CT Ratio)} B
PSM = {6.13 x 1000 / (0.2 x 1200)}
PSM = 25.541667 (Limited to 20)
= 20
For Earth Fault Protection, IEC defined SI curve is used.
Operating Time = TMS { 0.14/ (PSM0.02-1) }
Actual Operating time with TMS of 0.5 = 0.14 x 0.4 / (20 ^ 0.02 - 1)
Operating time = 0.907 sec
Hence summerising,
Curve = SI
Current setting, Io (PS) = 0.20 Ien
TMS = 0.400 B
Instantaneous setting = Blocked
Actual Operating time with TMS of 0.2 = 0.14 x 0.2 / (4.4 ^ 0.02 - 1)
Operating time = 0.931 sec
11kV side Standby Earth fault protection should be co-ordinated with the overcurrent protection
(unbalance) on the transformer primary (33kV) (Delta) side of a transformer, because an earth fault on
the secondary (star) side would appear on the primary side as 1/sqrt(3) p.u. fault current in two phases.
Selected setting = 9 In
Hence summarising,
Curve = SI
PS = 1.00 In
TMS = 0.200
Instantaneous setting = 9 In
Time = 0.01 sec
Operating Time of 33kV Transformer Incomer needs to be graded with 33kV incomer-1 feeder
Fault level at 33kV Bus A - with Feeder-1
= 4230 A
acting as source
The above fault current is greater than Instanteneous element pick up value, Hence the relay will operate
instanteneously for a fault current of 4230A.
Hence summarising,
Curve = SI
Current setting, Io (PS) = 0.2 Ien
TMS = 0.025
Instantaneous setting = Blocked
Hence summarising,
Curve = NI
Current setting, Io (PS) = 0.20 Ien
TMS = 0.300
Instantaneous setting = Blocked
A HV Interposing CT Multiplier
Transformer Primary Load Current (HV Side) at mid
= (20 x 1000) / (√3 x 33 x 0.95)
tap (-5%)
= 369 A
Corresponding CT secondary current = 369 ÷ 400 / 1
= 0.923 A
HV Interposing CT multiplier = 1/ 0.923
= 1.09
B HV Interposing CT Connection
Yy0 (0º)
C LV Interposing CT Multiplier
Transformer Primary Load Current (LV Side) = 1049 A (Refer above calculation)
Corresponding CT secondary current = 1049 ÷ 1200 / 1
= 0.875
LV Interposing CT multiplier = 1 / 0.875
= 1.15
D LV Interposing CT Connection
Yd1 (-30º)
Transformer Details
Rating : 20 MVA
Primary side Voltage (HV) : 33 kV
Secondary side Voltage (LV) : 11.5 kV
% Impedance : 12.5 %
Vector Group : DYn11
Tapping details : -15% to +5% in steps of 1.667%
Relay used : 7SR1103
Transformer Impedance with negative tolerance:
IEC applicable Impedance Tolerance : ± 7.5 %
Therefore Transformer Minimum Impedance : 11.57 % (with -ve tolerance)
where,
Itf = Through fault current for Transformer
Short circuit MVA of Transformer = Transformer MVA ÷ %Z (-ve Tolerance)
= 20 / 11.57
= 172.87 MVA
Through fault current for Transformer = 172.87 x 1000000 / (1.732 x 11.5 x 1000)
= 8678.83
The max developed voltage across relay circuit Vp = 2 x (SQRT(2Vk x (Vf + Vk)))
where, Vf = If*1/CTR*(Rct+2Rl+Rs)
= 1671 V
hence, Vp = 2763.26 V
Since the Peak voltage is lower than 3000V, non linear resistor is not required, though the same shall be
verified by vendor.
Hence Summarizing,
Fault current setting Is = 0.2
Stabilizing resistors Rs = 275 ohms
10.3 33kV Bus Bar Differential Protection (Main & Check Zone)
Relay used Siemens 7SG1211
CT data
CT primary current Ip = 1200 A
CT secondary current Is = 1 A
CT ratio N = 1200
Accuracy class Cl. = X
Knee point voltage Vk > 788 V
Magnetising current Im < 30 mA at Vk/2
CT internal resistance Rct < 5 Ω
Connected burden
4 sq mm Copper Lead (Assumed)
Unit lead resistance @ 90oC = 5.88 Ω/km
Lead length (two way) = 0.05 km (Assumed)
Total lead resistance @ 90oC RL = 5.88x0.05 Ω
RL = 0.294 Ω
Check for through fault stability
Voltage developed across the relay Vs = Imax/N x (Rct + 2RL)
where,
Imax = SWGR through fault rating
= 25000 A (Refer SLD)
Therefore, Vs = (25000/1200)x(5 + 2x0.294)
= 117 V
Say, Vs = 120 V
Fault Setting
Minimum fault current at 33kV Bus ( 1-phase fault = 1580 A (Refer Appendix-3)
current at 33kV PSS bus with Feeder-2 in operation)
The Primary Operating current Iop = (nIe + Is) x N
where,
n = No of CT's in parallel
Ie = Magnetising current at Vs
Is = Relay setting current
Magnetising current at setting voltage Ie = 9.14 mA @ 120V
No of Cts in parallel n = 5
Adopted relay setting current is Is = 0.2 A
Max.Voltage across relay ckt during through fault = 7.36 V
Imag at Vs = 0.0005602 A
Relay setting current will be 200mA = 0.20 A
Therefore, the Primary Operating current = 294.84 A
The operating current setting shall be 10-30% of the minimum fault current. In this case it is
around 19%, hence the above adopted current setting is found to be OK.
Stabilizing Resistor
Stabilizing resistor Rstab = Vs / Is
= 120V / 0.2A
= 600 Ω
Stabilizing Resistor Power Rating
PCONT ≥ IS2 x RSTAB
= 24 Watts
Non Linear Resistor requirement
The peak voltage VP = 2 x ( SQRT(2Vk x (Vf - Vk))
Where, Vf = Imax/N x Rstab
= 12500 V
Therefore, VP : 8593 V
Since the Peak voltage is more than 3000V non-linear resistor shall be required.
Setting Summary:
Current setting Is : 0.20
Stabilizing resistors Rs : 600 Ω
Say Rs : 600 Ω A
I) Overcurrent and Earth fault Protection at Shinas Grid station O/G Feeder
33kV Feeder Cable Differential Protection (87C) with Backup Distance Protection (21) for Shinas
II)
Grid O/G Feeder
2.1 Outgoing Feeder to Rumailah from Shinas Grid station :
Cable Differential Protection Setting (87C)
Type of Relay = 7SD522 *
Relay Location = --
CT Ratio (N) = 400 /1 A
For the setting with primary values at least double the value is to be set i.e.
Setting value I-DIFF> = 28
As per Siemens manual the pick value should not be less than 15% of the full scale current
15% of full scale current = 0.15 x 400
= 60 A
Converting into secondary = 60 / 400
= 0.15
Hence considering the default setting i.e.
I-DIFF> = 0.2 A (As per Client Comments)
D I>RELEASE DIFF
As per Siemens manual it is desired that a TRIP command is generated in the event of an
internal fault only if simultaneously the current of the local line end has exceeded a specific
quantity, then this current threshold can be set for enabling the differential protection TRIP.
Hence,
I>RELEASE DIFF = 0.00 A (Min. local current to release DIFF-Trip)
E Ic-comp. = OFF
H INRUSH RESTRAINT
Set
INRUSH REST = OFF
J CROSS BLOCK = NO
III) 33kV Feeder Distance Protection (21) for Feeder-II at shinas Grid station.
Protection Relay Type = Siemens, 7SA6101
CT Ratio = 400 / 1 A
VT Ratio = 33/√3 / 0.11/√3 kV
= 300 V
Total route length = 9.98 km
Line conductor type = Panther
OHL Length = 5.935 km
Line conductor type = Poplar
OHL Length = 3.556 km
Cable size = 33 kV, 3C x 300 Sqmm
Incomer Cable Length = 0.487 km
Impedance of OHL and Cable
Panther Conductor :
OHL +ve sequence impedance / km = 0.1750 +j 0.3330 Ω/kM
Total OHL +ve sequence impedance = 1.04 +j 1.98 Ω
3Cx300 sq.mm Cable:
Cable +ve sequence impedance / km = 0.079 +j 0.106 Ω/kM
Total cable +ve sequence impedance = 0.04 +j 0.05 Ω
Zone-1 reach (complex) of line (phase) referred to = 0.8 x (1.7 + j 3.21) x 400/300
secondary = 1.81 +j 3.43 Ω
Zone-1 reach (complex) of line (earth) referred to = 0.8 x (9.92 + j 18.79) x 400/300
secondary = 10.59 +j 20.05 Ω
Hence RE/RL (for zone 1) = 1/3 x ( R0/R1 - 1)
= 1/3 x (10.59/1.81 - 1)
= 1.62
Zone-2 reach (complex) of line (phase) referred to = 1.2 x (1.7 + j 3.21) x 400/300
secondary based on 120% of line length = 2.72 +j 5.14 Ω
Zone-2 reach (complex) of line (earth) referred to = 1.2 x (9.92 + j 18.79) x 400/300
secondary based on 120% of line length = 15.88 +j 30.07 Ω
Z3 setting is 100% of protected line length & portion of remote end transformer (fed through
longest line) Shinas Grid station to Rumailah
Resistance Reach calculations including arc resistance, etc. for phase faults
As per the calculation guidelines indicated in Siemens 7SA6 manual, a maximum arc voltage of 8kV can
be assumed for phase faults, which corresponds to the minimum to 4.8 Ω for the relay, as per Siemens
manual.
As per Siemens setting guidelines, the line resistance itself can be ignored.
Hence,
R(Z1) phase = R(Z2) ph = R(Z3)ph= R(Z4) ph = 6.40 Ω secondary
Resistance Reach calculations including arc resistance, etc. for earth faults
As per Siemens Manual 7SA6 (C5300-G1176-C156-5) page No 102
"The resistance RL of the line itself can be ignored with SIPROTEC 4 devices. It is taken into account by
the shape of the polygon"
Hence as per Siemens recommendations , the setting must consider the fault resistance which appears as
an additional resistance at the fault location and is added to the impedance of the line. It comprises, for
example, the resistance in arcs, the earth distribution resistance of earth points and others.
The resistance RL of the line itself can be ignored with SIPROTEC 4 devices. It is taken into account by
the shape of the polygon, provided that the Inclination angle of the polygon Distance angle is not
greater than the Line angle.
(Note 1: In this case zone 2 impedance seen by the relay based on 120% of the protected length. Hence
tZ2 does not need any additional time delay. Grading margin for Zone-2 must take into account Circuit
Breaker operating time including spread of this tim
tZ3 setting is chosen at 1.2 sec, as the estimated max. time of operation of Grid end transformer
primary O/C relays is assumed as 1 sec.
In this case blocking scheme is not used and current reversal guard is not applicable and hence it may be
set to cover bus bar faults in the reverse direction.
7SR1206 51-4
8 33kV Incomer Feeder CTR: 400 / 1 A
(51 & 51N Protection) 51G-1>1 0.05 to 2.5 In (steps of 0.01In) 0.2 In
FUNCTION CONFIG>
Gn Differential Enabled, Disabled Enabled
Gn Inrush Detector Enabled, Disabled Enabled
DIFFERENTIAL PROT'N
Gn W1 ICT Multiplier 0.50, 0.51, ..1.49, 1.50 x 1.09
O
Primary Side : Gn W1 ICT Connection Yy0, Yd1, Yy2, Yd3, Yy4, Yd5, Yy6, Yy0 (-0 )
33/11kV, 20 MVA Yd7, Yy8, Yd9, Yy10, YD11, Ydy0
400/1A 7SR2423
10 Transformer Differential Gn W2 ICT Multiplier 0.50, 0.51, ..1.49, 1.50 x 1.15
Secondary Side : 87T
Protection
1200/1A
Gn W2 ICT Connection Yy0, Yd1, Yy2, Yd3, Yy4, Yd5, Yy6, Yd1 (-30O)
Yd7, Yy8, Yd9, Yy10, YD11, Ydy0
DIFFERENTIAL PROT'N
(87BD)
Gn 87 BD Element Enabled, Disabled Enabled
Gn 87BD Initial 10, 20, 30, 40, 50% of In 20%
Gn 87BD 1st Bias Slope off, 10, 20,…60, 70% of Irestrain 30%
Gn 87BD 1st Bias Slope Limit 2,3..19,20xIn 4 x In
Gn 87BD 2nd Bias Slope Type Line, Curve Line (Default Value)
Gn 87BD 2nd Bias Slope: 1, 1.05… 2x 1.5 x (Default Value)
Gn 87BD Delay 0, 0.005, …, 1s 0.005s
Gn 87BD Inrush Action Off, Inhibit Inhibit
Gn 87BD Overfluxing Action Off, Inhibit Off
SUPERVISION (INRUSH
DETECTOR)
Gn 87HBL2 Element Enabled, Disabled Enabled
Primary Side : Gn 87HBL2 Bias Phase, Cross, Sum Cross
33/11kV, 20 MVA
400/1A 7SR2423 Gn 87HBL2 Setting off, 15, 16, ..24,25% of Ioperate 20%
10 Transformer Differential
Secondary Side : 87T
Protection
1200/1A OUTPUT CONFIG
(output Matrix)
87BD Bon, Ln
87HS Bon, Ln
CT Input 1,5 A 1A
CT Ratio 5:0.2…5000:7 1200A
Siemens 7SG1211 87/50 Element Disabled, Enabled Enabled
Busbar Diff. Protection
0.005,0.006…0.100xIn
87/50 Setting 0.2
0.105,0.110…2.000xIn
33kV Busbar Differential 87/50 Delay 0,0.01…60 s 0s
11.0 Protection 1200/1A
Stabilizing Resistor 600 ohms
(Main & Check Zone) A
50/51 O/C
FCT 50/51 ON, OFF ON
50-2 PICKUP 0.10…35.00A; ∞ ∞
50-2 DELAY 0.00…60.00S; ∞ ∞
50-1 PICKUP 0.10…35.00A; ∞ ∞
50-1 DELAY 0.00…60.00S; ∞ ∞
33kV Incomer feeder Siemens 51-PICKUP 0.10….4.00A (Step 0.01A) 1
1 400/1A 51 TIME DIAL 0.05…3.2S; ∞ (Step 0.01S) 0.3
from Grid station 7SJ8021
51-TOC Drop out Instantaneous, Disk Emulation Inst
Normal Inverse, Inverse, short Inverse,
51 IEC CURVE Long Inverses, Moderately Inverse, Normal Inverse
Extermly Inverse, Definite Inverse
50N/51N
FCT 50N/51N ON, OFF ON
50N-2 PICKUP 0.05…35.00A; ∞ ∞
50N-2 DELAY 0.00…60.00S; ∞ ∞
50N-1 PICKUP 0.05…35.00A; ∞ ∞
50N-1 DELAY 0.00…60.00S; ∞ ∞
51N-PICKUP 0.05….4.00A (Step 0.01A) 0.2
51N TIME DIAL 0.05…3.2; ∞ (Step 0.01) 0.3
51N- Drop out Instantaneous, Disk Emulation Inst
Normal Inverse, Inverse, short Inverse,
51N IEC CURVE Long Inverses, Moderately Inverse, Normal Inverse
Extermly Inverse, Definite Inverse
Device Configuration
State of Differential Protection ON/OFF ON
I-DIFF> 0.10 to 20.0A @ Is=1A 0.2 A
I-DIF> Switch ON 0.10 to 20.0A @ Is=1A 0.2 A
T-Delay I-DIFF> 0.00 to 60.00 sec 0
T310 1PHAS 0.00 to 50.00 sec 0.04
I>Release Diff 0.10 to 20.0A;0 @ Is=1A 0
33kV Incomer feeder-1 from
1 400/1A 7SD5221* Ic-Comp ON/OFF OFF
Grid Shinas station IcSTAB/IcN 2.0 to 4.0 2.5
I-DIFF> > 0.8 to 100.0A @ Is=1A 0.8 A
Inrush Rest. ON/OFF OFF
2nd Harmonic 10 to 45% 15%
Cross Block No/Yes No
Max Inrush Peak 1.1 to 25.0A @ Is=1A 15.0A
CROSSB 2HM 0.00 to 60.00 sec 0
87 of 131
Appendix-5A Relay setting schedule - Rev B
APPENDIX - 5A
2 X 20 MVA RUMAILAH SUBSTATION
RELAY SETTING SCHEDULE
33kV Outgoing Feeder - 2 at Shinas Grid station - Distance protection
CT Ratio : 400/1 A
Relay Type : 7SA6101
Forward
1301 Op. mode Z1 Reverse Non- Forward Operating mode Z1
Directional Inactive
1302 R(Z1) Ø-Ø 0.050 .. 600.000 Ω 6.4 Ω R(Z1), Resistance for ph-ph faults
1303 X(Z1) 0.050 .. 600.000 Ω 3.43 Ω X(Z1), Reactance
1304 RE(Z1) Ø-E 0.050 .. 600.000 Ω 53.13 Ω RE(Z1), Resistance for ph-e faults
1305 T1-1 phase 0.00 .. 30.00 sec;∞ 0.00 sec T1-1 phase, delay for single phase faults
1306 T1-multi-phase 0.00 .. 30.00 sec;∞ 0.00 sec T1 multi-ph, delay for multi phase faults
1307 Zone Reduction 0 .. 45° 0° Zone Reduction Angle (load compensation)
Forward
3 1311 Op. mode Z2 Reverse Non- Forward Operating mode Z2
Directional Inactive
1312 R(Z2) Ø-Ø 0.050 .. 600.000 Ω 6.4 Ω R(Z2), Resistance for ph-ph-faults
1313 X(Z2) 0.050 .. 600.000 Ω 5.14 Ω X(Z2), Reactance
1314 RE(Z2) Ø-E 0.050 .. 600.000 Ω 53.33 Ω RE(Z2), Resistance for ph-e faults
1315 T2-1phase 0.00 .. 30.00 sec;∞ 0.4 sec T2-1 phase, delay for single phase faults
1316 T2-multi-phase 0.00 .. 30.00 sec;∞ 0.4 sec T2 multi-ph, delay for multi phase faults
1317A Trip 1pole Z2 NO YES NO Single pole trip for faults in Z2
Forward
1321 Op. mode Z3 Reverse Forward Operating mode Z3
Non-Directional Inactive
1322 R(Z3) Ø-Ø 0.050 .. 600.000 Ω 6.4 Ω R(Z3), Resistance for ph-ph-faults
1323 X(Z3) 0.050 .. 600.000 Ω 13.03 Ω X(Z3), Reactance
1324 RE(Z3) Ø-E 0.050 .. 600.000 Ω 59.23 Ω RE(Z3), Resistance for ph-e faults
1325 T3 Delay 0.00 .. 30.00 sec;∞ 1.2sec T3 delay
Forward
1331 Op. mode Z4 Reverse Operating mode Z4
Non-Directional Inactive
Blocked
1332 R(Z4) Ø-Ø 0.050 .. 600.000 Ω R(Z4), Resistance for ph-ph-faults
1333 X(Z4) 0.050 .. 600.000 Ω X(Z4), Reactance
1334 RE(Z4) Ø-E 0.050 .. 600.000 Ω RE(Z4), Resistance for ph-e faults
3 1335 T4 Delay 0.00 .. 30.00 sec;∞ T4 delay
Fault Locator,
disturbance Recorder,
Event Recorder, Broken Enable / Disable Enable
Conductor, VT
Supervision
11kV Capacitor
33kV IC from 33kV IC-1 at 33kV B/C at 33kV, 20MVA Tx. 11kV Swgr B/C at 11kV OG feeder 500kVA Transformer
feeder at
Sr. No. Description Shinas Grid Rumailah Rumailah Feeder at Rumailah Rumailah at Rumailah feeder at Rumailah
Rumailah
Substation Substation Substation Substation Substation Substation Substation
Substation
1.0 CT Details
1.1 Primary rated Current , A 400 400 400 400 1200 400 400 100
1.2 Secondary rated Current , A 1 1 1 1 1 1 1 1
1.3 Set Current In 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0.30
Characteristic Curve as per IEC
1.4 SI SI SI SI SI SI SI SI
60255
B B
1.5 Time multiplier setting 0.300 0.300 0.200 0.200 0.125 B 0.1 0.050 0.150
1.6 Short Circuit Protection I>> Blocked Blocked Blocked 9 Blocked Blocked Blocked 7.5
1.7 Time multiplier setting Blocked Blocked Blocked 0.01 Blocked Blocked Blocked 0.01
Base voltage at which currents
1.8 33 33 33 33 33 33 33 33
are plotted kV
1 0.2
0.1
10
6
8 5
1
9 4
Time in Seconds
0.1
3
2
0.01
1 10 100 1000 10000
11kV OVERCURRENT
Current in Amp at 33kV PROTECTION CURVES
(1) - 11kV fault level on 33kV side for I/C & B/C (2) -500kVA Fault Level on 33kV Side
(3) - 11kV Fault Level of O/G & Cap Feeder (4) - OC Relay at 33kV BC
1 0.2
0.1
10
6
4
1
3
Time in Seconds
0.1
0.01
1 10 100 1000 10000 100000
33kV OVERCURRENT
Current in Amp at 33kV PROTECTION CURVES
(1) -33kV Grid Fault Level (2) -33kV Fault Level at Rumailah (3) - OC Relay at Grid OG
2.5 Time multiplier setting 0.300 0.300 0.175 0.025 0.400 B 0.250 B 0.100 B 0.250 0.025
2.6 Short Circuit Protection Io>> Blocked Blocked Blocked Blocked Blocked Blocked Blocked Blocked Blocked
2.7 Time multiplier setting Blocked Blocked Blocked Blocked Blocked Blocked Blocked Blocked Blocked
Base voltage at which currents are
2.8 33 33 33 33 11 11 11 11 11
plotted kV
3000 A at 33kV 1590 A at 33kV 1590 A at 33kV 1590 A at 33kV 6126A at 11kV 6126A at 11kV 12253A at 11kV 12253A at 11kV 12253A at 11kV
Line to Ground fault current Fault
2.9 bus of Shinas Grid bus of Rumailah bus of Rumailah bus of Rumailah bus of Rumailah bus of Rumailah bus of Rumailah bus of Rumailah bus of Rumailah
current for which relay is set, A
Substation Substation Substation Substation Substation Substation Substation Substation Substation
10
3
Time in Seconds
5
6
0.1
1 2
0.01
1 10 100 1000 10000 100000
Current in Amp at 11kV 11 kV Earth Fault Protection Curves
(1) - E/F level at 11kV bus (2) - EF Level at 11kV OG (3) - SBEF Relay
(4) - EF Relay at 11kV BC (5) - EF Relay at 11kV OG (6) - EF Relay at 11kV Cap fdr
10
Time in Seconds
5 4
0.1
2 1
0.01
1 10 100 1000 10000
Current in Amp at 33kV
(1) - Shinas Grid E/F level (2) - Rumailah Substation E/F level (3) - EF Relay at Grid OG