TYCO Safety Products Technical Support
April 9, 2012
TSW Revision 2.04
Functional Changes PHASE 2 DONGLE (741-779 or 741-780) IS REQUIRED FOR PHASE
and Enhancements: 2 TSW SOFTWARE. SEE DONGLE UPGRADE PROCEDURE TO
ORDER THE COMPATIBLE DONGLE AND FEATURE CODE.
• Integrated Automatic Email
• WAV file support for alarm categories
• Vectored Supervised Client support
• Increased number of Clients to 20 any combination
supervised/unsupervised
• Increased Active List size to 2900 for all alarm categories
• Allow Cancel on job Upgrade
• Allow Temperature Display in Celsius
• Support for 4 simultaneous monitors
Repaired Defects: • 276947 4190 DAT files fail to import in Graphics Editor.
• 276949 Objects in Graphics Editor always shift when clicked on
with Snap-To-Grid enabled.
• 276950 Double-clicking on a class in the list of “Do not act on
class”, class names of a command link moves several classes to
the “Act on class” list.
• 276951 Web Browser command window does not restore location
properly after initial close.
• 276954 Some types of non-zoomable objects are not positioned
correctly at runtime.
• 276956 Object enabled as “Primary screen for this point” does not
override an object of the same point on another graphics screen.
• 276960 CTRL-O opens a window to enter URL on Web Browser
invoked by a graphics Command Button.
• 277058 Imported 16 bit DOC file does not appear as the original
when imported.
• 277095 Graphics Editor crashes when objects are moved around
in the Dedicated Area.
• 277131 Edge of TSW screen is displayed on the second monitor.
• 277353 Non-zoomable buttons change font and location after a
paste and screen is re-opened.
• 277754 TSW Configurator crash if the user deletes any network
card from loop 4 to loop 7 in a 7 loop configuration.
• 277916 277725 External DACR point does not show as
unacknowledged at an external node if it re-alarms.
• 277917 277728 Issue updating text from specific screen.
• 278160 TSW runtime should not allow window to maximize or
restore when access level is below required level.
• 278171 Operator Note does not format properly.
• 278369 Wrong Current Status for a List that contains external
points.
• 278462 Changing location of Report target file never prompts a
request to delete or append file if file already exists at location.
• 278475 TSW graphics screens show IDNet Isolator points as RED
when in Normal state (ON).
.
Installation IMPORTANT!
Procedure for • Use “Customer PC” download
• Click Start, Settings, Control Panel, Add/Remove Programs to remove
TSW PC:
existing TSW programmer THEN REBOOT THE COMPUTER before
installing new TSW software.
• Run the install and follow the instructions carefully, being sure to reboot
the PC when prompted.
o if necessary, install will prompt you to install Microsoft .NET
Framework 3.5 Service Pack 1
• Requires New Network Programmer version 1.03.09 or newer
• Requires Security Service software version 1.02.02 or newer
• TSW Runtime (Client and Server) now supported for Windows 7
only. Using Windows XP and Vista may still work as long as you
are not using any of the new 2.04 features.
• TSW Configurator still supported on Windows XP or Windows
Vista and Windows 7.
• PCI network card requires PCI Driver version 4.01.01.00 or newer
to run on Windows 7 platform. This version is installed by the
TSW software install beginning with version 1.01.04.F1 TSW.
Installation • A complete TSW software installation of any version must have been
Procedure for done before using this utility.
• Use “TSWREV’s” download
Service Laptop PC
• Download the desired version of the TSWREV software to the PC, then
GCCREV utility: double click on the file to install the new version software to the
GCCREV’s folder.
• To install as the active programmer version click Start, Programs,
Simplex, TrueSite,TSW, GCC Revs, Change to 2.04.
• Note: All existing versions of TSWREV’s for TSW have been redone to
accommodate major differences between phase 1 and phase 2 TSW.
Redownload existing TSWREV versions before changing between
phase 1 and phase 2 versions for the first time.