Electrical Systems
Electrical Systems
Electrical Systems
3
Objectives
Introduction
It is important that project managers and superintendents have a basic understanding of the
fundamentals of electricity and how electrical systems work. You don’t have to be an electrician
or electrical engineer to understand how electrical systems work or to understand what is being
installed and why.
Like many fields electrical contracting is very broad and it is nearly impossible for an individual
to know everything, even after a lifetime of working in the industry, about electrical construction.
Changes in the industry do occur and new systems are continually on the horizon. However, the
principles on which all electrical systems work and the basics of electricity stay the same, even as
more sophisticated applications are developed and installed every day.
1
Fundamentals of Electricity
In order to understand electrical systems and to confidently coordinate with your subcontractors, it is
important that you have a working knowledge of the fundamentals of electricity.
For electricity to flow there needs to be a source, a load, and a completely closed path. Think about
what happens when you “flip” on your bedroom light switch. The switch when in the off position
opens the path and stops the source from being able to force the flow of electricity through the
load (the lightbulb). When the switch is closed, it completes the path from the service panel located
somewhere in your house that is energized by the local utility company, and current flows through
the load (the lightbulb). This system is a simple electrical circuit.
50W
120V
I
120 V
SW
Figure 1A: Simple Circuit - Switch Open
The Current (I) is zero I = 0 Amps
50W
120V
I
120 V
SW
Figure 1B: Simple Circuit - Switch Closed
The current (I) is calculated using the equation: Power = Current x Voltage (Watts Law) or P = I x E
I = P / E = 50 Watts ÷ 120 V = 0.4167 Amps
2
Circuits
A circuit is an arrangement of closed path(s) through which electricity (i.e., electrons) can travel. Most
complete circuits include an energy source, conductors, insulators, loads, a switch or other control
device, and a protective device (i.e., fuse).
A simple circuit consists of only one energy source, one conductor, and one load.
A series circuit has at least two loads. The conductor, loads, and control and protective devices are
connected end-to-end to make up a single path through which electricity can travel from and back to
the energy source. If a series circuit is interrupted at any point, electricity will not flow.
R1 R2
IT
Es
A parallel circuit has two or more independent paths. If one path is interrupted, electricity can still
flow through the remaining path(s).
IT
I1 I2
Es R1 R2
A series – parallel circuit has a combination of a series path and two or more independent parallel
paths. Depending on the arrangement of the loads and where a path interruption occurs the current
may or may not continue to flow through the loads.
R1
IT I2
I1
Es R2 R3
Current (I) is the rate at which electricity flows through a circuit. Current is measured in amperes or
amps.
Voltage (E) also called “electromotive force” or “emf” is the force that causes electricity to flow.
Voltage is measured in volts. In formulas, voltage is represented by either E or V. E will be used in
this course.
Resistance (R) Most materials making up a circuit resist the flow of electricity. The amount of this
resistance depends on the type of material and its dimensions. Resistance is measured in ohms. The
symbol for ohms is the Greek letter Omega (Ω).
Power is the rate at which electrical energy is transformed; it is the rate of doing work and is
measured in watts.
Direct Current
Direct current (DC) is the constant flow of electricity through a conductor in one direction. A dry-cell
battery connected to a light bulb is an example of a simple DC circuit.
Ohm’s Law
Ohm’s Law states the relationship between the current, voltage, and resistance of a simple DC circuit.
Watt’s Law
The basic form of Watt’s Law states that the electrical power (P) in a simple dc circuit is the product of
current and voltage.
P = I2 x R
P = E2 / R
Derivation P = I x E (Watt’s Law) and I = E/R (Ohm’s Law). Since I = E/R, substitute E/R for I in the
Watt’s Law formula: P = E/R x E = E2 / R.
Ohm’s Law and Watt’s Law problems involving simple, series, or parallel circuits usually consist of
calculating an unknown quantity (i.e., voltage) based on two or more known quantities (i.e. current,
resistance, or power).
Simple Circuits
The basic Ohm’s Law and Watt’s Law formulas can be applied directly to problems involving simple
DC circuits.
I R=3Ω
12 V
5
DC Series Circuits
Four rules apply to DC series circuits:
(1) The total voltage is the sum of the voltages across each load.
(2) The current is the same in all parts of the circuit.
(3) The total resistance is the sum of the individual load resistances.
(4) The total power is the sum of the powers used by the individual loads.
PROBLEM: In the DC series circuit illustrated in Figure 6, I = 6 amps, R1 = 4 ohms, and R2 = 2 ohms.
R1 R2
I
Et
6
DC Parallel Circuits
The rules for DC parallel circuits are:
(4) The total power is the sum of the powers used by the individual loads.
I R1 R2
Et
(b) According to Rule 1, the voltage across each load is the same. Apply Ohm’s Law
just as you would to a problem involving a simple dc circuit where I = 3 amps
and R = 0.8 ohm.
7
Alternating Current
Alternating current (AC) is the flow of electricity back and forth in a conductor at regular intervals.
The rate of flow reversal is called “frequency”. Nearly all AC power systems in the United States
operate at a frequency of 60 cycles per second. This means that the electricity flows in one direction
for 1/120 of a second and then in the other direction for 1/120 of a second. The current makes one
complete cycle in 1/60 of a second or 60 complete cycles in one second.
The sine wave is commonly used to illustrate alternating current. The graph below shows the sine
wave for a single-phase (1ϕ) AC current. The complete AC cycle is divided into two half cycles - - the
first is given a positive value and the second a negative value. The first half cycle (+) begins at zero
and rises to a peak value before returning to zero, at which point the second half cycle (-) peaks and
returns to zero again.
The disadvantage of single-phase AC is that the electrical power is cut off each time the current
reaches “0”. This problem can be avoided with three-phase (3ϕ) ac systems that provides overlapping
cycles. The power supplied to a motor or other device is never cut off because when one phase
reaches “0”, the other two phases are either positive or negative.
8
In-Phase AC Circuits
The voltage and current of an AC circuit can be depicted on the same graph as separate sine waves.
When the voltage and current begin and peak at exactly the same time, they are said to be “in phase”.
For all practical purposes, the “in phase” circuit consists of only resistance, the loads being devices
such as light bulbs, toasters, or heaters.
A simple capacitor consists of two conductor plates separated by a dielectric (insulator). Each plate
stores energy in the form of electric charges when electricity flows through the capacitor. One plate
becomes positively charged and the other negatively charged. The opposite charges on the plates
produce a voltage in the capacitor that opposes changes in the circuit voltage.
Because changes in the circuit voltage are opposed by capacitive reactance, the peak of the current
wave occurs ahead of the peak of the voltage wave. In other words, “Current leads voltage”.
Inductors are usually coils. The flow of electricity in an inductor produces a circular magnetic field
that is proportional to the current. When the current increases, the size of the magnetic field increases
and induces a voltage in the inductor. When the current decreases, the field collapses. The collapsing
field reverses the polarity of the induced voltage, which opposes the decrease in current.
Because the changes of current are opposed by inductive reactance, the peak of the current wave
is delayed and arrives after the peak of the voltage wave. In other words, “Current lags behind
voltage”.
9
Power Factor
The power factor (PF) is the ratio of the “true” power to the “apparent” power:
When a circuit is in phase, the true power equals the apparent power, which means that the power
measured by a wattmeter would be the same as the power calculated with the formula P = I x E. In
this case, the circuit is said to have a “unity” power factor or a power factor equal to 1 or 100%. If
the circuit is out of phase, the power measured by the wattmeter will be less than the apparent or
calculated power, and the power factor will be less than unity.
PROBLEM: An AC circuit draws 20 amps from a 240-volt source. The wattmeter measures
3,360 watts. What is the power factor?
If inductance or capacitive reactance puts the circuit out of phase, the power factor must be added to
the basic power formula:
P = I x E x PF
PROBLEM: A single-phase AC circuit draws 8 amps from a 120-volt source. If the power factor is
60%, what is the power rating in watts?
SOLUTION: (1) P = I x E x PF
The formula for a three-phase (3ϕ) system includes another term called the “three-phase factor”,
which is a constant equal to the square root of 3, or 1.73.
P3ϕ = I x E x PF x 1.73
PROBLEM: What is the power rating in watts of a 3ϕ circuit that draws 15 amps from a 120-volt
source if the power factor is 70%?
A transformer can be either a step-up transformer that receives power at a low voltage and delivers it
at a higher voltage, or a step-down transformer that receives power at a high voltage and delivers it
at a lower voltage.
The voltage of the primary winding will be the same as the source voltage. The voltage of the
secondary (ES) is equal to the primary voltage (EP) times the ratio of the number of turns (NS) in the
secondary to the number of turns (NP) in the primary.
PROBLEM: The primary and secondary windings of a step-up transformer are shown below. If a
voltage of 120 volts (EP) is applied across the primary, how many volts (ES) will be induced across the
secondary?
SOLUTION: (1) ES = EP x NS / NP
PROBLEM: The primary and secondary windings of a step-down transformer are shown below. If a
voltage of 120 volts (EP) is applied across the primary, how many volts (ES) will be induced across the
secondary?
SOLUTION: (1) ES = EP x NS / NP
11
The power of the primary winding equals the power of the secondary winding. Voltage and current
calculations are based on this principle.
PROBLEM: The primary of a step-down transformer has a voltage (EP) of 2,400 volts and a current
of 20 amps. If the voltage (ES) across the secondary is 240 volts, what is the current (IS)?
Transformers convert electricity from low to high voltage for long-distance transmission, then convert
it back to low voltage for use in homes and other facilities.
12
Power Distribution
Electrical Power Distribution will help you to understand how utility power is generated and
distributed and the main system components required to distribute power throughout a building.
Power distribution and connecting the building to its permanent power source are critical items that
must be considered early in the project design phase. HVAC equipment, elevators, motors, lighting,
fire protection, and numerous other systems cannot be tested and inspected until permanent power
has been connected. Working successfully with the electrical and mechanical superintendents
requires that you have a thorough understanding of the scope of work that must be accomplished
and that you are able to communicate with them efficiently.
When electrical power is distributed to its point of utilization, it is either in the form of single-
phase or three-phase AC voltage. Single-phase AC voltage is distributed into residences and other
small commercial buildings. Normally, three-phase AC voltage is distributed to larger commercial
buildings and industrial sites.
Energy means the capacity to do work. For example, the capacity to light a light bulb, to heat a home,
or to move something requires energy. Energy exists in many forms, such as electrical, mechanical,
chemical, and heat. Energy of an object in motion is called kinetic energy. Energy due to the position
of an object that is not yet moving is called potential energy.
Work is the transferring or transforming of energy. Work is done when a force is exerted to move
something over a distance against opposition, such as moving a desk from one side of a room to
the other. An electric motor used to drive an elevator cab performs work. Work is performed when
motion is accomplished against the action of a force that tends to oppose the motion. Work is also
done each time energy changes from one form into another.
Power is the rate at which work is done. It considers not only the work that is performed but the
amount of time in which the work is done. For instance, electrical power is the rate at which work is
done as electrical current flows through a wire. Mechanical power is the rate at which work is done as
an object is moved against opposition over a certain distance. Power is either the rate of production or
the rate of use of energy. The watt is the unit of measurement of electrical power.
13
Generation and Distribution of Electrical Power
Power is produced at a generating plant (source). Distribution occurs between the power generating
plant and the consumer by transmission lines and substations. Transformers are used to control the
voltage and current levels. Conversion of electrical power to another form (light, heat, mechanical)
occurs at the customer end.
Power provided from the U.S. electrical grid (the grid) is based on a frequency of 60 Hz.
Learn more about the “Grid” at the Department of Energy Web site.
14
Common Electrical Distribution Systems
120/240-Volt, Single-Phase, Three-Wire system is the
most common distribution method for residences.
Most appliances and home equipment use 120 V power
supplied to power receptacles. Dryers, ovens, hot water
heaters, hot tubs, and other higher current requiring
equipment may use the 240 V power.
Most commercial and industrial buildings use three
phase power. The most commonly used incoming service
voltage system is the 277/480 V Three Phase Four Wire
(WYE Connected). A step-down transformer is needed
to reduce the voltage to 120/208 for receptacles and other
lower voltage equipment.
15
16
Power Distribution System Equipment
Power distribution systems are used in every residential, commercial, and industrial building to
safely control the distribution of electrical power throughout the facility.
The power is then distributed by a load center to various branch circuits for lighting, appliances, and
electrical outlets.
17
Commercial and Industrial Power Distribution
Power distribution systems used in commercial and industrial facilities are more complex than
those used in single-family homes and must be capable of handling higher levels of current and
voltage. Although some small facilities usually do not require switchboards, medium and large
facilities commonly use switchboards to safely distribute power to transformers, panelboards, control
equipment, and, ultimately, to system loads.
Switchgear
A coordinated design consisting of switching and interrupting devices and associated equipment
such as control and protective devices and metering.
Switchboard
A large panel or assembly of panels containing switches, overcurrent protective devices, buses, and
associated instruments. Unlike panelboards, switchboards sometimes must be mounted away from a
wall to allow access to rear-mounted equipment.
18
Panelboard
A panelboard is a type of enclosure for overcurrent protection devices and the busses and
connections that provide power to these devices and their associated circuits. According to the
National Electrical Code® (NEC®), a panelboard is:
• Used to control light, heat, or power circuits
• Placed in a cabinet or cutout box
• Mounted in or against a wall
• Accessible only from the front
For additional information, refer to National Electrical Code® Article 408, Switchboards and
Panelboards.
19
In a Main Circuit Breaker (MCB) panelboard
the entire panel can be de-energized by
switching the main breaker off.
Fuse - A device designed to open a circuit when its rated current is exceeded. This is usually
accomplished when a metal link in the fuse melts. Renewable fuses allow the user to replace the link
and non-renewable fuses do not. Fuses are available in various sizes and types. Some have a time
delay.
Fuse Class - A letter designation given to a fuse to identify its operating and construction
characteristics.
Circuit Breaker - A device that can be used to open or close a circuit manually and also opens a circuit
automatically when it senses an overcurrent.
20
Single-Phase Main Breaker Panelboard
21
Grounding and Bonding
Grounding is the action of electrically connecting something
to a grounding electrode, which is a conductive object used to
create a direct connection to ground--typically a ground rod.
In a building, there are typically a number of services other than electrical supply that employ
metallic connections in their design. These include water piping, gas piping, HVAC ducting, and
so on. A building may also contain steel structures in its construction. There is thus a possibility
that a dangerous potential may develop between the conducting parts of non-electrical systems
including building structures and the external conducting parts of electrical installations as well as
the surrounding earth. This may give rise to undesirable current flow through paths that are not
normally designed to carry current (such as joints in building structures) and also cause hazardous
situations of indirect shock.
It is therefore necessary that all such parts are bonded to the electrical service earth point of the
building to ensure safety of occupants. This is called equipotential bonding. There are two aspects
to equipotential bonding: the main bonding where services enter the building and supplementary
bonding within rooms, particularly kitchens and bathrooms.
23
Components of an Effective Grounding System
An effective grounding system is one of the most important aspects of ensuring lightning protection.
The purpose of this system is to provide a pathway for the lightning energy to safely flow to earth,
as if this is not effective the extreme current -given the conditions- can find alternate pathways. If the
current does deviate, the damage can range from electromagnetic interference on sensitive equipment
and overloading circuits to electrical fires, arc flash and electrocution. For this reason, it is crucial to
consult professionals when implementing one of these systems.
1. Earthing network conductor. Conductor must have the current carrying capacity for the
maximum fault current for the total clearing time of the fault. Copper or copper-bonded steel
conductors are characteristically used for this purpose. WAPP offers various types of conductors
for earth grids and bonding ranging from flat copper tape, various copper earth cables to
proprietary ERICO Smoothweave cables.
2. Interconnecting Joints. Connections between grounding conductors are essential to the
functionality and reliability of the system, this is how the elements of the grounding system tie
together. Exothermically welding the connections, by use of CADWELD provides a superior bond
on a molecular level ensuring that it will never corrode or loosen which would otherwise damage
the integrity of the electrical continuity. A more economical and procedurally simple alternative
are mechanical connectors, these are of bolted, wedge and crimp type which, rely on the physical
surface contact to maintain electrical connection. For above ground connections (e.g. fence
clamps), this is an acceptable way of bonding.
24
3. Grounding Electrode. The grounding electrode (or
sometimes referred to as rod/stake provides electrical
connection to the ground and acts to dissipate current
to it. Electrodes can be categorised as either “natural” or
“made”. A natural electrode is intrinsic to the structure
this could be metal underground water piping, effectively
grounded metal framework of the facility, and/or the
steel in reinforced concrete foundations. An electrode is
considered made when it is implemented for the express
function of improving the performance a grounding
system this includes buried metal plates, buried mesh
conductor and rods or pipes driven into the ground.
25
Electrical Material
An electrical contractor is a business person or firm that performs specialized construction work
related to the design, installation, and maintenance of electrical and communication systems.
An electrician is someone trained (and usually licensed) to perform electrical work. Electrical work is
a highly technical profession that requires a thorough understanding of how electricity works and the
materials and components used to deliver power, as well as electrical safety and standards.
To organize an electrical estimate and efficiently order and supply the correct material needed for a
job, electrical material is typically categorized.
NECA members are electrical contractors who work in all aspects of electrical construction. While
most qualify as small businesses, large, multi-area electrical contracting firms are also members of the
association.
NECA contractors are the technical professionals responsible for the most innovative and safest
electrical construction in the U.S. They hold a high standard for superior performance and are
committed to delivering quality results.
26
Labor Units Defined
All labor data in this manual are in units of man-hours. Each table of labor units indicates whether
the labor units are for the installation of:
E = One, or per each item
C = Per hundred items or per hundred linear feet of the item
M = Per thousand items or per thousand linear feet of the item
LF = Linear Foot
CY = Cubic Yard
29
The NECA labor unit tables include three different labor units for each item:
NECA 1 Normal N
NECA 2 Difficult D
NECA 3 Very Difficult VD
Normal Installation Conditions – When all of the conditions associated with the installation of an
item will permit the maximum productivity of the electricians on a project, these “normal” column
labor units are applicable.
Examples of these normal conditions might include the installation of surface mounted items up to a
height of ten feet above the floor, the use of a rolling scaffold or six-foot ladders, a repetitive layout,
a minimum of required measurements, a minimum of interference by structural or mechanical
obstacles, etc.
Occasionally there are unusual installation conditions when a labor unit that is less than the “normal”
column labor unit is justified. For example, when an abnormally large quantity of parallel conduits,
without bends or offsets, are to be installed on trapeze hangers, labor units slightly smaller than the
“normal” column labor units might be appropriate.
Difficult Installation Conditions – When one or more of the conditions associated with the
installation of an item will permit less than maximum productivity of the electricians on a typical
project, these “difficult” column labor units are applicable.
Examples of the difficult conditions might include the installation of surface mounted items up to a
height of twenty feet from the floor, the use of fixed scaffolding installed by others, the use of ten-
foot ladders, a non-repetitive layout, a moderate amount of interference by structural or mechanical
obstacles, etc.
Users of this manual are also encouraged to consider using labor units whose magnitude are
somewhere between the normal column labor units and the difficult column labor units when
conditions justify this consideration.
Very Difficult Installation Conditions – When one or more of the conditions associated with the
installation of an item will permit substantially less than maximum productivity of the electricians on
a typical project, these “very difficult” column labor units are applicable.
Examples of the very difficult conditions might include the installation of surface mounted items
greater than the height of twenty feet above the floor, the use of fixed scaffolding installed by others,
the use of man-lifts, an individual location of each item, a substantial amount of interference by
structural or mechanical items, a difficult fastening method, etc.
Users of this manual are also encouraged to consider using labor units whose magnitude are
somewhere between the difficult column labor units and the very difficult column labor units when
the conditions justify this consideration. It is also essential that users of this manual select labor
units that are greater than the very difficult column labor unit when conditions justify the need.
For more information on adjusting labor units and how to use the guide see: Introduction to the
NECA Manual of Labor Units, in the NECA 2019-2020 MLU.
30
NECA Categories of Work
Prior to 2018 the NECA Manual of Labor Units was organized into 14 categories of electrical material.
SECTION TITLE
01 Integrated Building Systems
02 Conduit, Raceways, Fittings, & Related Items
03 Wire, Cable, Lugs, Terminations, Busway & Bus Duct
04 Switchboards, MCC’s, Panelboards, & Power Equipment
05 Lighting Fixtures, Poles, Parking Lot Lighting
06 Wiring Devices
07 Hazardous Systems
08 Grounding & Lighting Protection Systems
09 Heating Equipment Connections
10 Temporary Power & Lighting
11 Outdoor Overhead and Underground Systems
12 Equipment Installation and Connections
13 Industrial Control and Instrumentation
14 Alternative Energy Systems
Many electrical contractors use a different breakdown of electrical material for estimating purposes.
The beginning estimator should consult with the chief estimator and follow the system established by
their company for preparing their estimates.
The same information can be found in the newer version (NECA Manual of Labor Units 2019-2020
Edition) under the Construction Specification Institute’s MasterFormat, 2018 Edition. For example,
Section 06 Wiring Devices can now be found in Section 8: Division 26 - Electrical: 26 27 00: Low-
Voltage Distribution Equipment.
Section 8: Division 26 - Electrical addresses labor units related to general electrical workings as well
as more specific areas of electrical construction. Labor units in this Division were previously found in
nearly all sections of the previous versions of the NECA Manual of Labor Units.
31
NECA Manual of Labor Units
2015-2016 Edition
6
Split Wired Receptacle - Straight Blade
15 Amp 3 Wire 35.00 43.75 52.50 C
20 Amp 3 Wire 40.00 50.00 60.00 C
Plugtail Connectors
6" angle solid wire 10.00 12.50 15.00 C
6" stranded wire 10.00 12.50 15.00 C
6" angle solid wire with wago connector 10.00 12.50 15.00 C
6" angle stranded wire with wago connector 10.00 12.50 15.00 C
32
NECA Manual of Labor Units
2019-2020 Edition
8
Plugtail Wired Switches
15 Amp 1 Pole 10.00 12.50 15.00 C
20 Amp 1 Pole 15.00 18.75 22.50 C
15 Amp 2 Pole 20.00 25.00 30.00 C
20 Amp 2 Pole 25.00 31.25 37.50 C
15 Amp 3 Way 25.00 31.25 37.50 C
20 Amp 3 Way 30.00 37.50 45.00 C
15 Amp 4 Way 30.00 37.50 45.00 C
20 Amp 4 Way 35.00 43.75 52.50 C
Plugtail Connectors
6-inch Angle Solid Wire 10.00 12.50 15.00 C
6-inch Stranded Wire 10.00 12.50 15.00 C
6-inch Angle Solid Wire with Wago Connector 10.00 12.50 15.00 C
6-inch Angle Stranded Wire with Wago Connector 10.00 12.50 15.00 C
33
Section 8: Division 26 - Electrical
26 05 33: Raceway and Boxes for Electrical Systems
General Information
Conduit, Raceways, Fittings and Related Items
• Measuring, cutting, threading and handling conduit
• Material assembly and installation
• Conduit offset bending
Electrical conduits are used to protect and provide the route of electrical wiring. Electrical conduits
(ECs) are made of metal, plastic, or fiber and can be rigid or flexible. The National Electric Code
(NEC) sets standards for the installation for conduits and other raceways.
Other Trade Names: Galvanized Rigid Conduit (GRC), Galvanized Rigid Steel (GRS)
34
Intermediate Metal Conduit (IMC)
IMC was developed in the 1970s as a thin-wall alternative to
rigid metal conduit (RMC) that weighs about one-third less.
IMC ships with either a straight-tapped or integral coupling.
It features a galvanized OD and corrosion-resistant ID
coating.
Electrical Code Compliance
IMC is covered under Article 342 in the NEC®.
IMC Sizing
IMC is available in trade sizes 1/2 through 4, and 10′ lengths. Threads on the uncoupled end are
covered by industry color-coded thread protectors to protect the threads, keep them clean and sharp,
and aid in trade size recognition. Thread protectors for trade sizes 1, 2, 3 and 4 are color-coded
orange; trade sizes 1/2, 1 1/2, 2 1/2 and 3 1/2 are yellow; and trade sizes 3/4 and 1 1/4 are green.
EMT Sizing
EMT is available in trade sizes 1/2 through 4, and 10′ and 20′
lengths. Some manufacturers also produce EMT in a range
of colors for easy system identification.
35
Rigid Aluminum Conduit (RAC)
Rigid aluminum conduit provides lightweight, nonmagnetic
wiring solutions for dry, wet, exposed, concealed or
hazardous locations that comply with the National Electric
Code® (NEC).
36
Plastic Conduits
Rigid PVC pipe, electrical nonmetallic tubing (ENT), and
liquid-tight flexible nonmetallic conduit (LFNC) are the
most likely plastic conduits to be found in a residential,
commercial, and industrial installations.
37
Electrical Non-Metallic Flexible Tubing (ENT)
ENT, or “Smurf tube” (nicknamed because of its light-blue
color), is a corrugated, flexible PVC plastic tubing used
mostly for dry interior work or in certain places, such as
a basement or crawlspace, where moisture exists on the
interior of a building.
38
Other Raceways
Surface Metal Raceways
Nonmetallic Surface Raceways
Metal Wireway
Underfloor Duct
Trench Duct
Cable Tray
Steel
Aluminum
Fiberglass
Metal Boxes
Metal boxes are typically used with metal raceway mainly
as a place to pull wires, splice wires, and install devices. The
types of available boxes are their applications are numerous.
For example, a 4-inch square metal box with knockouts
(concentric circles that can be removed for installing conduit)
is used extensively for installing power devices - receptacles
and lighting devices - switches, and as a back box for light
fixtures and fire alarm devices. Metal boxes come in a variety
of shapes: square, octagon, and round.
Plastic Boxes
Nonmetallic boxes are typically used with nonmetallic
sheathed cable or nonmetallic raceways. They come in many
different shapes and types depending on the application.
39
Section 8: Division 26 - Electrical
26 05 19: Low-Voltage Electrical Power Conductors and Cables
General Information
• Wire, Cable, Lugs, Terminations, Busway and Bus DuctPulling cable, including set-up and
removing jacks, sheaves and cable pullers
• Testing circuits for continuity only
Building Wire
A wire is an electrical conductor made from a conductive material like copper or aluminium that is
covered with a protective insulation to prevent contact with other conductors or objects. If the wire is
bare it is being used as a grounding wire.
Single-conductor wire can be either solid or stranded. Solid wire consists of a single strand or core
of wire that is insulated with non-conductive material. Typically you will find solid core wire in
situations where the wire is not designed to be continuously flexed (i.e. your house electrical wiring,
wires for breadboards, etc.)
Stranded wire consists of a bundle of small gauge wires compressed and insulated with non-
conductive material. Typically you will find stranded wires in situations where the wire needs to be
routed through tight spaces or experiences frequent flexing/vibration (i.e. headphone cables, speaker
wire, automotive wire, appliance cables, etc.)
The AWG - American Wire Gauge - is used as a standard method denoting wire diameter, measuring
the diameter of the conductor (the bare wire) with the insulation removed. AWG is sometimes also
known as Brown and Sharpe (B&S) Wire Gauge.
The higher the number - the thinner the wire. Typical household wiring is AWG number 12 or 14.
Telephone wire is typical AWG 22, 24, or 26.
THHN Wire
T Thermoplastic
HH Hot Hot (90 degrees Celcius)
N Nylon Outer Covering
XHHW-2
X Cross Linked Polyethelyne
HH Hot Hot (90 degrees Celcius)
W Wet Locations
-2 90 degrees wet or dry locations
RHW
R Rubber
H Hot (75 degrees Celcius)
W Wet
40
Cable
Cable is a group of two or more wires wrapped in a nonmetallic sheath (NM) or an armored or
metal clad (AC, MC) protective flexible housing. Cable is both the conductor “wire” and the sheath
“conduit” fabricated together. Installation is typically faster than installing conduit “pipe” and
conductors “wire” since once installed, no additional labor is required to pull the wires through the
housing.
There are many different types of cable available to meet various installation requirements. Indoor,
outdoor, and direct burial are just a few options.
The most common cable used in residential installations is Romex®. The Romex® brand of Non-
Metallic Building Wire (“NM”) originated in 1922 with its development by the former Rome Wire
Company, a predecessor to General Cable Corporation.
41
Section 8: Division 26 - Electrical
26 27 00: Low-Voltage Distribution Equipment
General Information
The labor units in this section include the installation of the wiring device in a box already in place
and the termination of copper conductors on the wiring device. The labor units for wiring devices
which are factory mounted in enclosures include the installation of the enclosure and the termination
of copper conductors. When aluminum conductors are terminated on wiring devices the labor units
in this section must be increased.
Devices
Device. A unit of an electrical system that carries or controls electric energy as its principal function.
NEC 100. The most common example of devices used everyday are switches and receptacles.
Devices are typically selected based on the rated amperage and voltage. Exceeding either of these
values can lead to early failure or a potential hazard.
Receptacle outlets are available in a number of options: general-purpose grade, specification (spec)
grade, and hospital grade as well as a few others. The National Electrical Manufacturers Association
(NEMA) has created standards that receptacles and plugs are built to.
GFCI receptacles provide ground-fault circit interruption. Class A GFCA devices will open the circuit
if a ground fault of 4-6 milliamperes or more occurs. GFCI receptacles are less expensive than GFCI
circuit breakers. NEC 210.8 lists the locations that are required to have GFCI protection, such as
bathroom and kitchen outlets near water.
20A, 120V
GFCI
42
Switches
Switches open and close electrical circuits, allowing power to flow through lights and appliances. The
switch used should match the amperage and voltage for the circuit they serve. Switches designated
“CU-AL” are compatible for both copper and aluminum wiring. Be sure to select compatible
switches, otherwise, they can present a fire hazard.
The simplest and most common switch is a Single Pole Single Throw Switch (SPST) used frequently
for controlling lights. Flipping the switch up completes the circuit, turning lights or appliances on,
and flipping it down breaks (opens) the circuit, turning the lights or receptacle off. A single-pole
switch has two brass terminal screws on the side that receive the black and white wires of the circuit.
(The number of terminal screws identifies the type of switch.) Modern single-pole switches also have
a green grounding screw (not shown) that connects to the circuit’s ground wire.
A switch that can operate hallway lights from either end of the hallway is called a three-way switch ;
it has an extra terminal.
Occupancy Sensors
• A occupancy sensor automatically turns the lights ON upon detection of motion and turns the
lights OFF automatically after the area is vacated
• Occupancy sensors may offer the option to switch the sensor from automatically turning the lights
ON to requiring manual button press from the occupant (Manual/Vacancy Mode)
Vacancy Sensors
• A vacancy sensor requires manual activation of the lights by the occupant, then turns the lights
OFF automatically soon after the area is vacated
• A vacancy sensor does not offer an option of automatically turning the lights ON
43
Section 8: Division 26 - Electrical
26 51 00: Interior Lighting, 26 52 00: Safety Lighting, 26 54 00: Classified Location Lighting, 26
55 00: Special Purpose Lighting, 26 56 00: Exterior Lighting
General Information
• Lighting Fixtures, Poles and Parking Lot Lighting
• Fixture installation
• Power and grounding conductor terminations
• Original installation of lamps and fluorescent tubes, covers and lenses in new lighting fixture
installation
• Verification of fixture operation
Light Fixtures
The appropriate type of light fixture required depends on several factors; where it is installed,
purpose for lighting the area, cost, and other considerations. Most lighting designers categorize
lighting fixtures into three types: ambient, task, and accent.
Ambient light is fundamental light that brightens up a whole area. A ceiling light fixture is an
excellent example of normal lighting. An ambient light fixture may usually be able to handle light
bulbs with larger wattages than process or accent accessories.
Task lighting is the lighting you utilize to do tasks, hence the name! A desk lamp is just a excellent
example of the task light installation as it can be used especially to do work. Activity lighting tends to
be focused on small areas such as for example end tables or desks but does provide a small number of
ambient lighting.
Accent lighting is just as the name implies used to provide feature illumination. A light fixture
employed for accent lighting won’t be bright enough to provide sufficient background or task
lighting. This sort of light is used to display artwork or to enhance the atmosphere of any room.
Fixture Lamp Types
A light fixture or luminaire is a technical and professional term for the electrical fixtures used to hold
a lamp—a light bulb—the light source. Common lamps types include: Incandescent (INC), Halogen,
Fluorescent (FL), High Intensity Discharge (HID), Light Emitting Diode (LED).
44
Fixture Mounting Methods
Troffer
A troffer is a rectangular or square light fixture that fits into
a modular dropped ceiling grid (i.e. 2' by 2' or 2' by 4').
Surface
Surface mounted fixtures are usually mounted indoors on
ceilings and walls and outdoors on the exterior of buildings.
Suspended
Fixtures can be suspended by pendant, stem, aircraft cable,
swival and canopy, wire, chain, cable, cords, or other similar
methods.
Recessed
Flush mounted fixtures are recessed into surfaces such as
gypsum board or hard lid ceilings. When installed they are
flush with the surface and blend in with the surroundng
area. Round recessed lights are called downlights or can
lights.
High-Bay
High bay lighting fixtures are designed for applications of
20 feet or more. A wide range of indoor lighting fixtures
provide specific light patterns for high bay lighting
applications, including maintenance lighting, warehouse
lighting, recreation center lighting, hangar lighting and
storage lighting.
Low-Bay
Used to light areas with lower ceilings 20 feet or less. Low
bay lighting options have diffusers at the bottom of the
fixtures. These diffuse the light, cutting down on the harsh
reflections that lower ceilings can cause. The result is a
more natural, pleasing light in rooms with low ceilings. The
applications for this technology are endless, and they are the
perfect option for any tight space.
45
Section 8: Division 26 - Electrical
26 12 00: Medium-Voltage Transformers, 26 13 00: Medium-Voltage Switchgear, 26 21 00:
Low-Voltage Electrical Service Entrance, 26 22 00: Low-Voltage Transformers, 26 24 00:
Switchboards and Panelboards
General Information
Switchboards, MCC’s, Panelboards and Power Equipment
• Rigging for reasonable lifting and hoisting
• Moving, handling and placing in position, bolting sections/bussing together and factory harness
• wiring for fans, heaters and controls.
Several pages in these sections contain labor units for handling electrical equipment and exclude the
labor for conductor terminations. The labor for conductor terminations must be added separately for
these items. When labor units in this section do include the conductor terminations, the labor units
are based on the minimum sizes of copper conductors allowed by the National Electrical Code.
Material found in these sections was covered earlier in the Power Distribution section.
46
Electrical Plans
Electrical plans or electrical drawings are created by a design team to illustrate for the electrical
installer (electrician) how the electrical systems are to be installed preconstruction. The final set of
electrical drawings illustrating how the systems were actually installed are commonly referred to as
“as-built drawings”.
Electrical Symbols
The NEIS NECA 100 - 2006 Symbols for Electrical Construction Drawings publication describes
graphic symbols used to represent electrical wiring and equipment on construction drawings. In this
publication, the term “electrical” is used to include electrical, electronic, and communications systems
covered by the National Electrical Code (NFPA 70). This publication also summarizes recommended
drawing practices for electrical construction drawings.
Symbol Groups (From: NEIS NECA 100 - 2006 Symbols for Electrical Construction Drawings)
Group Descrption
1.0 Wiring Methods
1.1 Raceways—Indicators
1.2 Raceways—Boxes and Busways
2.0 Luminaire (Lighting Fixtures)
2.1 Luminaire Fixtures—Basic Modifiers Mounting
2.2 Luminaire Fixtures—Basic Modifiers Orientation
2.3 Luminaire Fixtures—Basic Modifiers Emergency
2.4 Luminaire Fixtures—Extended Fixtures
3.0 Outlets and Receptacles
4.0 Switches and Sensors
5.0 Motors—Controls
5.1 Motorized & HVAC Equipment
6.0 Security
7.0 Fire Alarm Communications & Panels
7.1 Fire Alarm Indicators
7.2 Fire Alarm Sensors
8.0 Distribution Equipment
9.0 Communications—Teledata
9.1 Communications—Audio/Visual
9.2 Communications—Equipment
10.0 Site Work
11.0 Schematic Fault Circuit Interrupter, Personal Protection
11.1 One-Line Diagram Symbols—Switchboard Meters
11.2 Schematic and One-Line Diagram Symbols—Switches
12.0 Miscellaneous
13.0 Abbreviations
14.0 Nurse Call System
47
Example Pages from NEIS NECA 100 - 2006 Symbols for Electrical Construction Drawings
NECA 100 Symbols for Electrical Construction Drawings
2.010 Tw i n l u m i n a i r e p o l e m o u n t e d s i t e l u m i n a i r e f i x -
ture.
■ 10
48
Symbols for Electrical Construction Drawings NECA 100
Recessed fixture.
Wa l l m o u n t e d f i x t u r e .
2.200 A c c e n t / d i r e c t i o n a l a r r o w, w i t h o r w i t h o u t t a i l .
(Drawn from photometric center in direction of
optics or photometric orientation.)
Tr a c k m o u n t e d ; l e n g t h , l u m i n a i r e t y p e s a n d
q u a n t i t i e s a s s h o w n . ( Tr a c k l e n g t h d r a w n t o
scale.)
11 ■
49
NECA 100 Symbols for Electrical Construction Drawings
NOTE: M o d i f i e r s a r e s h o w n w i t h s p e c i f i c b a s e s y m b o l s f o r c l a r i t y.
Each modifier can be used with any of the base symbols.
2.403 Louvers.
■ 12
50
Common Electrical Systems
There are many different electrical systems in a typical commercial, residential, or industrial building.
Listed below are examples of some of the most common electrical systems.
Numbering the systems is often used by an electrical contractor for organizing the electrical estimate
into categories or systems.
System Estimate Scope of Work
06 FIXTURES Interior building fixtures (Typically estimated by floor)
07 LIGHTING BRANCH Conduit, hangers, boxes, etc. for the lighting branch circuits
08 DEVICES - LIGHTING Lighting devices, such as switches and occupancy sensors
39 LIGHTING CONTROL/DIMMING Lighting control systems / panels
43 SITE LIGHTING Parking lot lights, bollards, etc.
51
Electrical Estimating
Quantity Takeoff
The process of counting and measuring items depicted in the electrical drawings such as; light
fixtures, receptacles, conduit runs, panels and switchgear.
For example, conduit in a slab versus conduit in the wall or fastened to a steel beam are installed
differently.
52
Conduit in a slab can often use the shortest run from point A to point B and runs under the slab do
not have to be installed parallel or orthogonal to the building walls or framing.
Conduit runs in a slab are “stubbed-Up” to the device, panel, box, or location it is being connected to.
The requirement for the stub-ups is given in the specifications.
PVC Conduit Stubbed-Up with GRS Elbows PVC 90’s? Aren’t you concerned about your jet line/rope cutting through them
when you pull the wires? We always use rigid 90’s underground.
Typical Specification
Working With EMT - ELECTRICAL METALLIC TUBING and What Electricians Should Know
53
The isometric drawing below (not to scale) illustrates the horizontal and vertical installation of
conduit intalled in a ceiling (Lighting Branch) and in a slab (Power Branch).
Drop
Vertical conduit dropping
down from above is
referred to as a “drop”.
Stub-Up
Vertical conduit coming
up from below a slab is
referred to as a “Stub-up”.
Plan View
54
Takeoff Sheet
Totals of each item to be installed are organized and recorded in a takeoff sheet.
Example: Takeoff Sheet for Light Fixtures (Waste Management Hauling Facility)
Before counting or measuring items the first step is to prepare a takeoff sheet for the system to be
counted such as, light fixtures, or measured, such as Branch Lighting. Then, using the corresponding
drawing for the system to be counted or measured, count or measure all items for each drawing
where they are shown to be installed and record on the takeoff sheet. Continue until all those items
for each drawing where they are shown are counted before moving to the next item. If you find
something you missed earlier, immediately count it and adjust your previously noted quantity. Most
companies have a Takeoff Color Code for marking the items counted on the plans.
For example, color all light fixtures with a yellow highlighter and emergency fixtures with an orange
highlighter. Lighting devices (switches, etc.) color with a blue highlighter.
55
Take Off Color Code
To have a consistent process for estimating the scope of work for the different electrical systems and
indicating on plans that the components have been accounted for a take off color code is helpful.
The take off color code below shows the different color highlighters used for each system. For
example, use the pink highlighter to count power devices, such as, receptacles.
Colored pencils are used for coloring conduits that have been measured, such as, Lighting Branch,
Power Branch, Fire Alarm Branch, and Feeders.
SYSTEM HIGHLIGHTER
DEVICES
POWER PINK
LIGHTING BLUE
TELE/DATA GREEN
FIRE ALARM RED PENCIL
DISTRIBUTION EQUIP
REGULAR POWER BLUE
EMERGENCY POWER ORANGE
GROUNDING GREEN
PENCIL COLORS
NM Cable
FEEDERS EMT MC CABLE PVC GRC/IMC
BRANCH RED PINK GREEN BROWN
2. Review the Specifications - Thoroughly review the Division 01 general specifications in addition to the Division
26 specifications and pay close attention to contractor qualifications, payment terms, bonding capacity,
insurance requirements and make sure you can meet the qualifications and live with the legal language should
you win the construction project. When you are finished with the general specifications, it is time to move onto
the Division 26 specifications and make a note of the material grade, installation methodologies and
responsibilities of costs (who provides fire alarm, communications, etc.) Generally, the specs will determine the
quality of materials while the drawings determine quantities. It is important to highlight anything out of the
ordinary and make sure you include these items in your bid. I have seen many contractors take a black eye on an
otherwise profitable project because they bid a less expensive material grade only to find during the project
execution that it was significantly more expensive. If you intend to offer an alternate option, make sure it is
approved first and in writing because they will hold you to the specified material grades.
3. Review the Drawings - Look over the drawings at a high level to get an idea of the full scope of work. You should
review the architectural in addition to the electrical drawings to understand working heights and elevations that
will affect labor costs, material pricing and equipment requirements. Once you understand the general
construction (think birds eye view of the project) it is time to review the Division 26 drawings taking note of any
technical details that are depicted and watch for any discrepancies between the drawings and specifications and
write this down.
57
1
4. Perform a Quantity Takeoff - Pull out your highlighters, scale master or your favorite takeoff software to begin
the process of counting and measuring items depicted in the electrical drawings like light fixtures, receptacles,
conduit runs, panels and gear. Start with one item (we suggest light fixtures) and count all items sheet by sheet
keeping totals per sheet before moving to the next item. If you find something you missed earlier, immediately
count it and adjust your previously noted quantity. Now total your quantities for each sheet and move to a
quantity takeoff sheet, example excel sheet below. Note: Are you responsible for HVAC hookups or any low
voltage?
5. Request Supplier Quotes - One of the reasons we suggest getting your lighting counts first is to speed up
receiving a quote for these items because they are generally quoted independently of the rest of your materials.
A couple things to note, do not worry about getting the specifics on the light fixtures, rather note the
designations used to identify the fixtures on the plans i.e. A1, B1, C1, etc. The lighting firm will reference the
lighting schedule and look up the item details and provide a lump sum quote. It is in your best interest to build a
relationship with your local lighting firms to ensure you are getting competitive pricing in a timely manner.
6. Create your Estimate - Now that you have the quantities laid out, you will need to determine the unit cost for
each item. To accomplish this, you need to determine the material and labor costs associated with each task and
extend those out by the task quantity. Determining the material cost is simple, a quick call to your supplier or
pricing service can give you this data, but the labor cost requires that you know how long it takes to install the
material. This requires past production history and experience, or if you do not have past production history and
limited field experience we suggest purchasing NECA’s Manual of Labor Units to use as a guide. Once the labor
unit is determined you will multiply that by the burdened labor cost to determine the labor cost for the task. See
the simple excel example quantity takeoff sheet below that includes material and labor costs per task and the
totals summarized. Now you will want to summarize the total material cost and total labor hours for all the
items, and you’ll multiply the labor hours by your fully burdened hourly labor cost to get your total labor cost for
the task. Add these two numbers together to determine your total direct costs for the project and the basis for
your estimate. Keep in mind, you will need to add line items for any other direct costs required for the
installation like equipment rentals or subcontractors.
7. Add Overhead and Profit - Now that we have our estimated job cost (direct costs) we need to add profit and
overhead to those costs to arrive at our sales price. While profit is self-explanatory, overhead is not and is the
total of all the other indirect expenses that are required to run your business including your office lease,
estimating, sales, marketing, bookkeepers, and other expenses that must be paid to keep your business
operating smoothly. Like profit, overhead is a percentage that you add to the project costs to land at your sales
price. Small contractors commonly believe they do not have overhead and shouldn't charge for it and this is not
correct. You are leaving money on the table and it's in your best interest to figure out the overhead required to
run your small business with an accountant that specializes in construction.
8. Build your Proposal - Now that we have our sales price, we need to create a proposal that details what is
included in our bid in clear and concise terms. We suggest using similar language to what was used in the project
specifications and drawings. This makes it easier for the General Contractor reviewing your proposal to ensure
you have covered everything and that nothing major is missing and he can therefore trust your price. Electrical
contractors provide lump sum bids. This means you provide a fixed fee to cover everything outlined in your bid.
This is where it is important to clarify anything that you have included or excluded to avoid any confusion once
the project is awarded. Free Electrical Proposal Template Here
9. Double Check Takeoff Quantities & Estimate - It is always a good idea to get a second set of eyes from your
estimating team to review your work prior to submitting your bid to make sure you have not missed anything.
This review should involve a counterpart taking off the project’s major systems and ensuring that nothing was
missed during the original takeoff. We suggest keeping a bid log (simple excel spreadsheet) that shows recent
and successfully completed projects by type and size with the price per sq ft listed for reference. While you
should never bid projects this way, you can compare a previously completed project against your current project
58
2
to see if there is a large variance in price. If there is a big delta, it is worth looking into to figure out why. Note:
you can use this log to help with preliminary budget numbers.
10. Submit Bid - Once you have double checked your work it is time to submit your bid. Today, everyone submits
bids electronically either through the bid site that they received the bid or via email. We suggest that you read
the Division 01 specifications again and looking for any bid instructions and follow them to a tee.
11. Review the Results - In the beginning it can be tough to determine where you are in the mix compared to other
electrical contractors bidding the same work. Remember, General Contractors go with numbers from vendors
they trust, potentially years of experience working together, more than the low number, so it might take a
couple bids to gain a General Contractors trust. When you lose a project, it is always a good idea to ask the
General Contractor how you stack up against the competition, sometimes they will send you the bid tabs with
your competitors’ numbers and other times they will tell you that you are high or too low for comfort. Unless it
is a public bid, they are not required to provide this information, but if you ask in a respectful manner you will
receive feedback, and this will help you with adjusting on future bids. Note: It is a good idea to request bid tabs
on awarded projects as well to see if you are leaving money on the table by bidding too low.
59
3