Logical Relationships and Control Principles

1. Mode of operation
The system is divided into two operating modes, "automatic mode" and "manual mode",
in which the operator can operate each device, and all interlock conditions are not involved

in the control. In "Auto Mode", all interlock conditions participate in the control.

2. Reservoir state logic


There are five states of oil storage tanks: "Inlet", "Sedimentation", "Oil", "Isolation", and
"Maintenance".

 Oil feed state


When the system is in "manual mode", the operator can directly select the TANK111 as
the skimmer mode through the HMI, and when the system is in the "automatic mode", the
TANK-111 can only be selected as the skimmer mode when the liquid level value of the

TANK-111 is less than TANK111 allowable filling level value.


Sedimentation state
When the system is in "manual mode", the operator can select the TANK111 as the settling
mode directly through the HMI, and when the system is in the "automatic mode", the TANK-
111 can only be selected as the skimmer mode when the TANK-111 liquid level value must
be met ≥TANK111 the full tank level set value.

 Oily condition
"Oil" status: After the operator confirms that the oil has passed the inspection, the TANK-
111 is selected as the oil state.

 Quarantine status
"Isolated" status: After the operator confirms that the oil test fails, the TANK-111 is selected
as the isolation state.
 Maintenance status
The Maintenance status is confirmed by the operator.

3. Regulator pump start-up logic


When the system of the stabilizer pump is "manual mode", the operator can "start", "stop"
and "change the speed" of the upper computer
When the system is in "automatic mode", the system controls "start", "stop" and "change
speed" when the "stabilized pump" is the main pump.
The main pump selection is set by the operator, and only one of the two regulator pumps
can be the "main pump" at the same time, and if the regulator pump of the "main pump"
triggers a fault during system operation, the other regulator pump will automatically convert
to the "main pump".
The starting logic of the regulator pump starts when the pressure of the oil pipeline
network is detected to be lower than the set value, and the frequency of the regulator pump
is controlled by the PID output value. During the operation of the stabilizer pump, if it is
detected that the pressure of the oil line is higher than the set value, the stabilizer pump will
be stopped for a long time. If the pressure stabilizer pump reaches the maximum frequency
and the pressure of the oil pipeline network still does not reach the preset pressure value, the
transfer oil pump (the main oil pump with the oil sequence number of the transfer oil pump
is 1) will be delayed and the pressure stabilizer pump will be stopped.
4. Fuel pump start-stop logic
When the system of the oil pump is "manual mode", the operator can "start", "stop" and
"change the speed" operation on the host computer
When the system is in "automatic mode", the "oil pump" starts and stops successively
according to the pump start sequence after receiving the system command.

 Hair oil pump sequence


There are two types of hair oil sequences:
1 Manual mode: The starting sequence of each pump is unique according to the operator
who chooses the starting sequence of each pump.

2 Automatic mode: The system automatically sorts after each batch of refueling according
to the cumulative running time of each pump. The oil pump with the shortest running time is
serial number 1.
 Fuel pump maintenance mode
The operator can set the fuel pump to "maintenance mode" and automatically set the
failed pump to maintenance mode when the system detects a pump fault signal.
When the pump triggers the "maintenance mode", the oil sequence number of the faulty
pump will be set to "0", and the oil sequence of the other three oil pumps will be rearranged
to achieve the purpose of automatic switching. The principle of reordering is that the
sequence number of the oil pump greater than the sequence number of the faulty pump is
reduced by 1, and the sequence number of the oil pump that is smaller than the sequence
number of the faulty pump remains unchanged.
The motor winding of the oil pump, the motor housing is overheated, the motor bearing
is overheated, and the pump vibration coefficient is too high, all trigger the pump fault signal.

 System plus or minus pump logic


When the pressure of the stabilizer pump is in operation and reaches the maximum speed,
the pressure of the oil pipeline network is still lower than the "stable pressure set value", the
system delays the start of the oil pump with the oil generation sequence number 1 and stops
the operation of the stabilizer pump.

When the oil pump with oil sequence number 1 is running, if the flow rate of the oil pipeline
network does not reach the "set value of the operating flow of one pump", the oil pump with
oil sequence 2 will be started with a delay. If it is detected that the pressure of the oil pipeline
network is greater than the "stop pressure set value", the oil pump with oil generation
sequence number 1 will be stopped for a delay.

When there are two oil pumps running together, if it is detected that the flow rate of the
oil pipeline network does not reach the "two pumps operating flow set value", the oil pump
with oil sequence 3 will be started. If the flow rate of the detected oil pipeline network is

greater than the "two pumps operating flow set value", the oil pump with oil generation
sequence 2 will be stopped with a delay.

When the three oil pumps are running at the same time, if the flow rate of the oil pipeline
network is detected to be less than the "three pumps operating flow set value", the oil pump
with oil generation sequence of 4 will be started, and if the detected oil pipeline network flow
is greater than the "three pumps operating flow setting value", the oil production pump with
oil generation sequence of 3 will be stopped with delay.

When the four pumps are running at the same time, if the flow rate of the oil pipeline
network is detected to be less than the "four pumps operating flow set value", the alarm will
be prompted, and if the flow rate of the oil pipeline network is detected to be greater than
the "four pumps operating flow set value", the oil generation pump with the oil generation
sequence of 4 will be stopped with a delay.
5. Skimmer pump logic
When the system is in "manual mode", the operator can "start" and "stop" the skimmer
pump through SCADA. Not subject to interlock conditions.
Stop the CP-311 pump when FSLL311 trigger is detected when the system is in "Auto

Mode" or when the PT-311 pressure is detected to be too low.


6. XV1221, XV122 interlock shut-off valve
7. Pump stop interlock conditions