FusionModule2000 Smart Modular Data Center

V500R002C03
Product Description

Issue 05

Date 2020-03-06

HUAWEI TECHNOLOGIES CO., LTD.


Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China

Website: https://e.huawei.com

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. i


FusionModule2000 Smart Modular Data Center
Product Description About This Document

About This Document

Purpose
The FusionModule2000 smart modular data center solution (FusionModule2000 for short)
includes smart modules A and B. This document describes the FusionModule2000 product
positioning, features, application scenarios, and system architecture, providing the systemic
information about the smart modular data center.

Intended Audience
This document is intended for:
 Sales engineers
 Technical support engineers
 System engineers

Symbol Conventions
The symbols that may be found in this document are defined as follows.

Symbol Description
Indicates a hazard with a high level of risk which, if not
avoided, will result in death or serious injury.
Indicates a hazard with a medium level of risk which, if not
avoided, could result in death or serious injury.
Indicates a hazard with a low level of risk which, if not
avoided, could result in minor or moderate injury.
Indicates a potentially hazardous situation which, if not
avoided, could result in equipment damage, data loss,
performance deterioration, or unanticipated results.
NOTICE is used to address practices not related to personal
injury.
Supplements the important information in the main text.
NOTE is used to address information not related to personal
injury, equipment damage, and environment deterioration.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. ii


FusionModule2000 Smart Modular Data Center
Product Description About This Document

Change History
Changes between document issues are cumulative. The latest document issue contains all
updates made in previous issues.

Issue 05 (2020-03-06)
Updated the technical specifications of the integrated UPS.

Issue 04 (2020-01-14)
Updated the USB description.

Issue 03 (2019-12-04)
Updated the USB description.

Issue 02 (2019-03-10)
Updated the manual name and so on.

Issue 01 (2017-09-20)
This issue is the first release.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. iii


FusionModule2000 Smart Modular Data Center
Product Description Contents

Contents

About This Document .................................................................................................................... ii


1 Positioning...................................................................................................................................... 1
2 Features ........................................................................................................................................... 2
3 Application Scenarios .................................................................................................................. 4
4 Typical Configurations ................................................................................................................ 7
4.1 Single-Row 1200 mm Wide Aisle Containment ........................................................................................................... 8
4.2 Dual-Row 1200 mm Wide Aisle Containment ........................................................................................................... 10

5 Power Supply and Distribution System ................................................................................. 12


5.1 Power Supply and Distribution System for Smart Module A ..................................................................................... 12
5.2 Power Supply and Distribution System for Smart Module B ..................................................................................... 14
5.3 Integrated UPS (50 kVA, 125 kVA) ............................................................................................................................ 17
5.3.1 Product Structure ..................................................................................................................................................... 17
5.3.2 Power Module .......................................................................................................................................................... 20
5.3.3 Bypass Module ........................................................................................................................................................ 21
5.3.4 Control Module ........................................................................................................................................................ 22
5.3.4.1 Overview .............................................................................................................................................................. 22
5.3.4.2 ECM...................................................................................................................................................................... 22
5.3.4.3 Dry Contact Card .................................................................................................................................................. 24
5.3.4.4 Monitoring Interface Card .................................................................................................................................... 26
5.3.5 MDU ........................................................................................................................................................................ 30
5.3.6 Technical Specification ............................................................................................................................................ 32
5.4 Integrated PDC ........................................................................................................................................................... 35
5.5 Precision PDC............................................................................................................................................................. 37
5.6 New Main Way ........................................................................................................................................................... 39
5.7 Smart cooling product PDB ........................................................................................................................................ 40
5.8 Battery Cabinet ........................................................................................................................................................... 42
5.9 rPDU ........................................................................................................................................................................... 45
5.10 (Optional) Ground Copper Bar ................................................................................................................................. 46

6 Structural System ........................................................................................................................ 48


6.1 Single-Row 1200 mm Wide Aisle Containment ......................................................................................................... 48

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. iv


FusionModule2000 Smart Modular Data Center
Product Description Contents

6.2 Dual-Row 1200 mm Wide Aisle Containment ........................................................................................................... 49


6.3 Network Cabinet ......................................................................................................................................................... 51
6.4 IT Cabinet ................................................................................................................................................................... 53
6.5 Skylight ....................................................................................................................................................................... 55
6.6 Aisle End Door ........................................................................................................................................................... 58
6.7 Cabinet Bottom Sealing Plate ..................................................................................................................................... 59
6.8 Cabinet Enclosure Plate .............................................................................................................................................. 60
6.9 (Optional) Base ........................................................................................................................................................... 61
6.10 Cable Trough ............................................................................................................................................................ 62
6.11 (Optional) Cable Tray ............................................................................................................................................... 63
6.12 (Optional) Adaptive Frame ....................................................................................................................................... 63
6.13 Scenario with Columns ............................................................................................................................................. 64
6.14 Cable Management Devices ..................................................................................................................................... 65

7 Temperature Control System .................................................................................................... 69


7.1 System Overview ........................................................................................................................................................ 69
7.2 NetCol5000-A025 Smart Cooling Product ................................................................................................................. 69
7.2.1 Indoor Unit Components ......................................................................................................................................... 69
7.2.2 Controller ................................................................................................................................................................. 71
7.2.2.1 Appearance and Ports............................................................................................................................................ 71
7.2.2.2 Function and Features ........................................................................................................................................... 73
7.2.3 Application Environment ......................................................................................................................................... 74
7.2.4 Technical Specifications .......................................................................................................................................... 77
7.3 NetCol5000-A042 Smart Cooling Product ................................................................................................................. 79
7.3.1 Product Introduction ................................................................................................................................................ 79
7.3.1.1 Appearance ........................................................................................................................................................... 79
7.3.1.2 Cooling Components ............................................................................................................................................ 81
7.3.1.3 Controller .............................................................................................................................................................. 83
7.3.1.3.1 Appearance and Ports......................................................................................................................................... 83
7.3.1.3.2 Functions and Features ...................................................................................................................................... 86
7.3.2 Physical Ports........................................................................................................................................................... 87
7.3.3 Product Specifications ............................................................................................................................................. 88
7.4 NetCol500 Outdoor Unit ............................................................................................................................................ 90
7.4.1 Product Composition ............................................................................................................................................... 91
7.4.2 Technical Specifications .......................................................................................................................................... 92
7.4.3 (Optional) Low-Temperature Component................................................................................................................ 94
7.4.4 (Optional) Sunshade ................................................................................................................................................ 96
7.5 (Optional) Dehumidifier ............................................................................................................................................. 97
7.6 Smart Cooling Product Controller .............................................................................................................................. 98
7.7 L1/L2 Linkage (iCooling Function) .......................................................................................................................... 100

8 Facility Management System .................................................................................................. 101


8.1 NetEco6000 Intelligent Data Center Management System....................................................................................... 102

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. v


FusionModule2000 Smart Modular Data Center
Product Description Contents

8.2 ECC800 Core Controller .......................................................................................................................................... 103


8.3 (Optional) Tecal RH2288 V2 Server ......................................................................................................................... 106
8.4 (Optional) LAN Switch ............................................................................................................................................ 107
8.5 Pad ............................................................................................................................................................................ 108
8.6 Skylight Actuator ...................................................................................................................................................... 108
8.7 Data Collection System ............................................................................................................................................ 110
8.7.1 (Optional) Rack environment unit ......................................................................................................................... 110
8.7.2 Smart ETH Gateway .............................................................................................................................................. 111
8.7.3 WiFi Converter ...................................................................................................................................................... 113
8.8 Video Surveillance System ....................................................................................................................................... 114
8.8.1 IP Camera .............................................................................................................................................................. 114
8.8.2 VCN500 ................................................................................................................................................................. 116
8.9 Access Control System ............................................................................................................................................. 117
8.9.1 Access Actuator ..................................................................................................................................................... 117
8.9.2 (Optional) Aisle Access Control System ................................................................................................................ 120
8.9.3 (Optional) Cabinet Access Control System ........................................................................................................... 124
8.10 Environment Monitoring System ............................................................................................................................ 126
8.10.1 WLDS900 Water Sensor ...................................................................................................................................... 126
8.10.2 (Optional) Smoke Detector .................................................................................................................................. 127
8.10.3 (Optional) Temperature Sensor ............................................................................................................................ 128
8.10.4 Temperature and Humidity Sensor....................................................................................................................... 129
8.10.5 Multi-functional Sensor ....................................................................................................................................... 129
8.10.6 Alarm Beacon ...................................................................................................................................................... 131
8.11 Intelligent Battery Management Subsystem ........................................................................................................... 131
8.11.1 CIM ...................................................................................................................................................................... 133
8.11.2 BIM ...................................................................................................................................................................... 134

9 Lighting System......................................................................................................................... 137


9.1 AC Actuator .............................................................................................................................................................. 137
9.2 Aisle Light ................................................................................................................................................................ 138

10 Surge Protection and Grounding System ........................................................................... 140


11 Integrated Cabling System .................................................................................................... 143
A Acronyms and Abbreviations ................................................................................................ 145

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. vi


FusionModule2000 Smart Modular Data Center
Product Description 1 Positioning

1 Positioning

The FusionModule2000 solution integrates the cabinet, power supply and distribution,
cooling, monitoring, and integrated cabling systems, achieves seamless integration of power
supply and distribution, cooling, and management systems, and enables the modular data
center to operate intelligently and efficiently. It can run network services alone or work as a
branch of a larger modular data center to run part of services.
The FusionModule2000 is designed for small- and medium-sized data center facilities. It
mainly applies to small- and medium-sized data centers for bank offices, governmental
agencies, small- and medium-sized enterprises (SMEs), education, and medical organizations.
The FusionModule2000 provides basic physical infrastructure for small- and medium-sized
data centers.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 1


FusionModule2000 Smart Modular Data Center
Product Description 2 Features

2 Features

The FusionModule2000 features high integration, outstanding security and reliability, space
saving, high energy efficiency, quick installation, optimal compatibility, fast and flexible
deployment, excellent monitoring, and stable cooling. It is a new-generation smart modular
data center solution.

High Integration
 The smart module integrates a cabinet system, power supply and distribution system,
cooling system, facility management system, surge protection and grounding system,
auxiliary fire extinguishing system, and integrated cabling system. It provides an overall
solution.
 The integrated power supply and distribution system have distributes power to
uninterruptible power systems (UPSs), smart cooling products, and IT equipment.

When the 380 V power supply is used and there are more than four battery cabinets or when the 480
power supply is used, battery racks are independently deployed.

Outstanding Security and Reliability


 The smart module supports optional aisle and cabinet access control, which prevents
unauthorized personnel from entering the smart module and improves security.
 Rotating skylights open automatically in case of fire, and the emergency button opens
the door in case of emergency, which improves the data center safety.
 The smart module supports two power inputs.
 Each UPS is configured with a manual maintenance bypass switch. When the smart
module is working properly, the switch is locked to prevent misoperations.
 Modular UPSs work in N+1 redundancy mode to improve the reliability of the smart
module.
 Strong-current and weak-current cables, optical fibers, and network cables are routed
separately to minimize electromagnetic interference.
 The electronic expansion valve used in a smart cooling product has a backup power
module which ensures that the electronic expansion valve can be closed when the system
is powered off, thereby preventing compressor damage.
 The positive temperature coefficient (PTC) electric heater of the smart cooling product
provides dual protection functions: automatic reset and auto-recovery disabling.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 2


FusionModule2000 Smart Modular Data Center
Product Description 2 Features

Fast and Flexible Deployment


 The smart module can be placed in an altered room of an office building.
 The smart module can be directly installed on a concrete floor in a building, which
simplifies engineering.
 If the smart busway (optional) is configured, one or two cabinet places are saved.
 The smart module is delivered within a few days and can be quickly installed onsite.
 The design minimizes the workload of engineering.
 The standardized installation procedures reduce the installation time and workload.
 Single-row cabinets or dual-row cabinets are deployed based on the equipment room size,
power consumption of a single cabinet, and expansion requirements.
 IT cabinets are flexibly equipped with servers as well as storage and network equipment
to meet enterprise requirements for enterprise application and internal services.
 The 42 kW smart cooling product features a long pipeline, large height difference, and
small footprint.

High Energy Efficiency


 High-efficiency UPSs and DC variable frequency smart cooling products reduce power
consumption.

Optimal Compatibility
 The smart module supports class B environments, and smart cooling products support
class C environments.
 Modular power distribution allows for smooth expansion to meet various requirements.

Excellent Monitoring
 Various sensors monitor functional modules in the data center in real time.
 The web-based monitoring system enables remote management of functional modules.

Stable and Quiet Cooling


The NetCol5000-A features efficient cooling, low noise, effective energy saving, high
reliability, wide working conditions, wide power range, high compatibility, intelligent
monitoring, and easy maintenance.
 The 25 kW and 42 kW smart cooling products support L1/L2 linkage and teamwork of
indoor units.
 Teamwork control: Up to 32 smart cooling products can be networked for teamwork.
When multiple smart cooling products work cooperatively, heat load is optimally
distributed to reduce power consumption and backup is provided to improve reliability.
 The smart cooling products support T1 and T3 temperature environments and extremely
low-temperature environments.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 3


FusionModule2000 Smart Modular Data Center
Product Description 3 Application Scenarios

3 Application Scenarios

Table 3-1 Aisle effects

Scenario Figure
Single-row aisle containment

Dual-row aisle containment

Without a raised floor

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 4


FusionModule2000 Smart Modular Data Center
Product Description 3 Application Scenarios

Scenario Figure
With a raised floor

The smart module can be equipped with or without a raised floor.


 Without a raised floor: top cable routing + top pipe routing
 With a raised floor: top cable routing + bottom pipe routing

Table 3-2 Application scenarios

Scenario Type Figure


Smart module A Single-row aisle
(batteries, UPS, containment
and smart cooling
products deployed
inside the module)

Dual-row aisle
containment

Smart module A Single-row aisle


(UPS and smart containment
cooling products
deployed inside
the module,
batteries deployed
outside the
module)

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 5


FusionModule2000 Smart Modular Data Center
Product Description 3 Application Scenarios

Scenario Type Figure


Dual-row aisle
containment

Smart module B Single-row aisle


(smart cooling containment
products deployed
inside the module,
UPS and batteries
deployed outside
the module)

Dual-row aisle
containment

Smart module A (UPS and smart cooling products deployed inside the module, batteries deployed
outside the module) and smart module B (smart cooling products deployed inside the module, UPS and
batteries deployed outside the module) are divided into two parts, which can be deployed in one room or
two rooms. If deployed in one room, the smart module adopts the hot aisle containment design to ensure
that the ambient temperature for batteries meets requirements.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 6


FusionModule2000 Smart Modular Data Center
Product Description 4 Typical Configurations

4 Typical Configurations

The FusionModule2000 data center has two different architectures: smart modules A and B.
Typical configurations involve the single-row and dual-row 1200 mm wide aisle
containments.

Table 4-1 Typical configurations

Smart Inside Smart Module Outside Smart


Module Module
Scenario
Smart Integrated UPS, smart cooling product, and -
module A battery
Integrated UPS and smart cooling product Battery
Smart Integrated power distribution cabinet (PDC) and UPS and battery
module B smart cooling product
Precision PDC Battery, UPS, and smart
cooling product power
distribution equipment
(provided by the
customer, not included in
the power distribution
system of smart module
B)
Smart busway and wall-mounted power UPS and battery
distribution box (PDB) (distributes power to
smart cooling products and aisle lighting)
Precision PDC and wall-mounted PDB
(distributes power to smart cooling products and
aisle lighting)

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 7


FusionModule2000 Smart Modular Data Center
Product Description 4 Typical Configurations

4.1 Single-Row 1200 mm Wide Aisle Containment


Figure 4-2 Single-row aisle containment (PDC)

Figure 4-3 Single-row aisle containment (smart busway)

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 8


FusionModule2000 Smart Modular Data Center
Product Description 4 Typical Configurations

Figure 4-4 Floor plan of the single-row 1200 mm wide aisle containment (PDC)

The PDC refers to the integrated UPS, integrated PDC, or precision PDC.

Table 4-2 Key technical specifications

Item Technical Specifications


Number of IT 2–24 cabinets
cabinets
Equipment room  In the scenario (without bases) where the PDC is configured, the
space minimum area is 18 m2, and the minimum floor height is 2.6 m
when 2.0 m high IT cabinets are deployed and is 2.8 m when 2.2 m
high IT cabinets are deployed.
 In the scenario (without bases) where the smart busway is
configured, the minimum floor height is 2.8 m when 2.0 m high IT
cabinets are deployed and is 3.0 m when 2.2 m high IT cabinets are
deployed.
Cooling NetCol5000-A025 In-row Air Cooled Smart Cooling Product (300 mm
wide); NetCol5000-A042 In-row Air Cooled Smart Cooling Product
(600 mm wide)
Power Smart module A: integrated UPS
distribution Smart module B: integrated PDC or precision PDC + wall-mounted
PDB or smart busway + wall-mounted PDB
Aisle 1200 mm wide single-row cold or hot aisle containment

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 9


FusionModule2000 Smart Modular Data Center
Product Description 4 Typical Configurations

4.2 Dual-Row 1200 mm Wide Aisle Containment


Figure 4-5 Dual-row aisle containment (PDC)

Figure 4-6 Dual-row aisle containment (smart busway)

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 10


FusionModule2000 Smart Modular Data Center
Product Description 4 Typical Configurations

Figure 4-7 Floor plan of the dual-row 1200 mm wide aisle containment (PDC)

The PDC refers to the precision PDC, integrated UPS, or integrated PDC.

Table 4-3 Key technical specifications

Item Technical Specifications


Number of IT 6 to 48 cabinets (max. 24 cabinets in an N+1 system; max. 48 cabinets
cabinets in a 2N system; max. module length: 15 m)
Equipment room  In the scenario (without bases) where the PDC is configured, the
space minimum area is 18 m2, and the minimum floor height is 2.6 m
when 2.0 m high IT cabinets are deployed and is 2.8 m when 2.2 m
high IT cabinets are deployed.
 In the scenario (without bases) where the smart busway is
configured, the minimum floor height is 2.8 m when 2.0 m high IT
cabinets are deployed and is 3.0 m when 2.2 m high IT cabinets are
deployed.
Cooling  NetCol5000-A025 In-row Air Cooled Smart Cooling Product (300
mm wide)
 NetCol5000-A042 In-row Air Cooled Smart Cooling Product (600
mm wide)
Power  Smart module A: integrated UPS
distribution  Smart module B: integrated PDC or precision PDC + wall-mounted
PDB or smart busway + wall-mounted PDB
Aisle 1200 mm wide dual-row cold or hot aisle containment

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 11


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5 Power Supply and Distribution System

5.1 Power Supply and Distribution System for Smart


Module A
For smart module A, the power supply and distribution system diagrams are the same
regardless of whether battery cabinets are deployed inside or outside the module.

N+1 power supply and distribution system diagram

Figure 5-1 N+1 power supply and distribution system diagram

Network video recorder (NVR).

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 12


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

2N power supply and distribution system diagram

Figure 5-2 2N power supply and distribution system diagram

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 13


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.2 Power Supply and Distribution System for Smart


Module B
N+1 Power Supply and Distribution System Diagram

Figure 5-3 N+1 power supply and distribution system diagram (integrated PDC)

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 14


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-4 N+1 power supply and distribution system diagram (precision PDC or smart busway)

The wall-mounted PDB, but not the precision PDC or smart busway, supplies power to smart
cooling products.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 15


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

2N Power Supply and Distribution System Diagram

Figure 5-5 2N power supply and distribution system diagram (integrated PDC)

Figure 5-6 2N power supply and distribution system diagram (precision PDC or smart busway)

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 16


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

The wall-mounted PDB, but not the precision PDC or smart busway, supplies power to smart
cooling products.

5.3 Integrated UPS (50 kVA, 125 kVA)


5.3.1 Product Structure

 The appearance of the UPS5000-E-125K-HABBS (02311FTD-002, 02311FTD-007) is similar to


that of the UPS5000-E-50K-HABBS (02311FTB-001, 02311FTB-009).
 The appearance of the UPS5000-E-125K-HASBS (02311FTE-002) is similar to that of the
UPS5000-E-50K-HASBS (02311FTC-001).
 The appearance of the UPS5000-E-125K-HASBS (02311FTE-004, 02311FTE-006) is similar to that
of the UPS5000-E-50K-HASBS (02311FTC-004, 02311FTC-006).

Figure 5-7 UPS5000-E-50K-HABBS (02311FTB-001) front view

(1) Power input status indicator (2) Input circuit (3) Lighting circuit
breaker breaker
(4) Power distribution circuit breaker for (5) IT load circuit (6) UPS input circuit
the smart cooling product breaker breaker

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 17


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

(7) UPS maintenance bypass circuit (8) Control module (9) Bypass module
breaker
(10) Filler panel (11) Power module (12) Monitor display
unit (MDU)
(13) Power distribution monitoring board (14) UPS output
circuit breaker

Figure 5-8 UPS5000-E-125K-HASBS (02311FTE-002) front view

(1) Power input status (2) ATS (3) Lighting circuit


indicator breaker
(4) ATS handle (5) Power distribution circuit breaker (6) IT load circuit
installation slot for the smart cooling product breaker
(7) UPS input circuit (8) UPS maintenance bypass circuit (9) Control module
breaker breaker
(10) Bypass module (11) Power module (12) Monitor display
unit (MDU)
(13) Power distribution (14) UPS output circuit breaker
monitoring board

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 18


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-9 UPS5000-E-125K-HASBS (02311FTE-004) front view

(1) Power input (2) ATS drive module (3) ATS monitoring
status indicator module
(4) Lighting circuit (5) Power distribution circuit breaker (6) IT load circuit breaker
breaker for the smart cooling product
(7) UPS input (8) UPS maintenance bypass circuit (9) Control module
circuit breaker breaker
(10) Bypass module (11) Power module (12) ATS transfer switch
(13) ATS handle (14) Monitor display unit (MDU) (15) Power distribution
monitoring board
(16) UPS output
circuit breaker

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 19


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.3.2 Power Module


Appearance

Figure 5-10 Power module

(1) Positioning lock (2) Run indicator (3) Alarm indicator (4) Fault indicator
(5) Ready switch (6) Output port (7) Input port

Functions
The power module consists of a PFC rectifier and inverter. The power module performs
AC-DC or DC-DC conversion on the mains and battery inputs, and stabilizes the bus voltage.
The inverter converts DC inputs into AC sine wave outputs.

Specifications
 Dimensions (H x W x D): 86 mm x 442 mm x 620 mm
 Weight: < 21 kg
 Rated output capacity: 25 kVA/25 kW
 Power density: 17.2 W/inch3

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 20


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.3.3 Bypass Module


Appearance

Figure 5-11 Bypass module

(1) Positioning (2) Battery cold start (3) Run (4) Alarm indicator
lock button indicator
(5) Fault indicator (6) Ready switch (7) Signal port (8) Input and output
ports

Functions
The UPS is set to ECO mode and the bypass voltage is within the specified range.
The power module is overloaded for a period longer than the maximum allowed period.
Both the active and standby ECMs are abnormal.
The system fails to run properly and transfers to bypass mode.
A manual operation is performed to transfer to bypass mode.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 21


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Specifications
 Dimensions (H x W x D): 130 mm x 442 mm x 500 mm
 Weight < 25 kg
 Maximum output power: 125 kW

5.3.4 Control Module


5.3.4.1 Overview
In a standard configuration, the control module consists of two ECMs, one dry contact card,
and one monitoring interface card (from left to right). The four cards are hot swappable. One
subrack is reserved above the dry contact card. A backfeed protection card or dry contact
extended card can be inserted into this subrack.

Figure 5-12 Signal panel on the control module

(1) Ground terminal (2) Parallel port 1 (3) BSC port (4) Ready switch
1 on ECM 1
(5) Indicators for ECM 1 (6) Parallel port 2 (7) BSC port (8) Ready switch
2 on ECM 2
(9) Indicators for ECM 2 (10) Dry contact card (11) Dry (12) MDU port
contacts
(13) RS485 port (14) Fast Ethernet (FE) (15) COM2 (16) COM1 port
port port
(17) Battery temperature (18) Optional card
sensor port subrack cover

Ports are protected by a security mechanism.

5.3.4.2 ECM
The control module consists of two ECMs that work in active/standby mode. Each card
provides two ports, that is, a BSC port in the upper part and a reserved parallel port in the
lower part.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 22


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-13 ECM

Table 5-1 Ports on the ECM

Silk Screen Description


PARALLEL The PARALLEL port transmits parallel signals.
BSC The BSC port is used in a dual-bus system to synchronize
output frequencies and phases between UPS systems,
ensuring that two buses can switch with each other.
BSC cables are hot-swappable.

Table 5-2 Indicator description

Indicator Color Status Description

NORMAL Green Steady on This ECM is the active ECM.


Blinking at 0.5 This ECM is the standby ECM and it is
Hz ready.
Off This ECM is not ready or the CPLD of
this ECM is being upgraded.
Blinking at 4 Hz The DSP of the ECM is being upgraded or
not configured.
ALM Yellow Steady on The ECM has a minor alarm, but it does
not need to be replaced.
Off The ECM has no minor alarm or the DSP
of the ECM is being upgraded.
FAULT Red Steady on The ECM has a critical alarm.
Off The ECM has no critical alarm or the DSP
of the ECM is being upgraded.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 23


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.3.4.3 Dry Contact Card


The dry contact card allows the UPS to detect and manage the switch status of the battery
system (including the external battery switch) and implement remote emergency power-off
(EPO).

Figure 5-14 Dry contact card

Table 5-3 Ports on the dry contact card

Silk Screen Description Status Initial


Status

BTG Port for detecting  Connected: Disconnected


battery grounding battery
faults grounding fault
 Disconnected:
0V Port for signal ground
no battery
grounding fault
GEN Port for detecting  Connected: Disconnected
diesel generator D.G. mode
(D.G.) mode  Disconnected:
0V Port for signal ground non-D.G. mode

BCB_OL Port for detecting the  Grounded: Grounded


BCB box BCB box
connected
 Disconnected:
BCB box not
connected
BCB_STA Port for monitoring  Connected: Disconnected
the battery switch battery switch
ON
 Disconnected:
battery switch
OFF
BCB_DRV Controls battery  0 V: battery 0V
circuit breaker trip. switch not
When the voltage is tripped
+12 V, the circuit  12 V: battery
breaker trips. switch tripped
BCB_0V Port for signal ground

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 24


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Silk Screen Description Status Initial


Status

EPO_NO Emergency power-off If the normally Disconnected


(EPO) port open (NO) port is
connected to the
EPO_12V +12 V EPO_12V port,
EPO is triggered.
EPO_NC EPO port If the normally Connected
closed (NC) port is
EPO_12V +12 V disconnected from
the EPO_12V port,
EPO is triggered.
SWITCH STATUS_OUT Port for monitoring  Connected: Connected
the UPS output circuit circuit breaker
breaker ON
 Disconnected:
SWITCH STATUS_0V Port for signal ground
circuit breaker
OFF
SWITCH STATUS_MT Port for monitoring  Disconnected: Disconnected
the maintenance circuit breaker
circuit breaker ON
 Connected:
SWITCH STATUS_0V Port for signal ground
circuit breaker
OFF
SWITCH STATUS_BP Port for monitoring  Connected: Connected
the bypass input circuit breaker
circuit breaker ON
 Disconnected:
SWITCH STATUS_0V Port for signal ground
circuit breaker
OFF
SPD Port for monitoring  Connected: Connected
the input AC surge SPD enabled
protective device  Disconnected:
(SPD) SPD disabled
0V Port for signal ground

 The dry contact interface card takes effect only after it is set on the monitoring system. Set the
unused dry contact signal to the unused status.
 Set the EPO port to NO or NC as required.
 When multiple UPSs are paralleled, all dry contact signals to be used need to connect to each UPS.
 Single cables require dual-insulated twisted cables. If the length of a power cable is within 25–50 m,
its cross-sectional area must be 0.5 mm2 to 1.5 mm2.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 25


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.3.4.4 Monitoring Interface Card

 The FE port resembles the RS485 port. Follow the silk screen when connecting
communications cables as, if the RS485 port is mistaken for the FE port during cable
connection, the WebUI cannot be connected and MDU communication fails. Conversely, if
the FE port is mistaken for the RS485 port during cable connection, RS485
communication fails.
 Only once being set will dry contact signals take effect. Set unused dry contact signals to
the unused state on the LCD.
 In a parallel system, ensure that used dry contacts properly connect to each UPS.

The monitoring interface card provides external ports as well as monitoring and control
functions for the MDU. The ports include the ambient temperature and humidity sensor port,
FE port, battery temperature monitoring port, and network management port. MDU functions
include monitoring of the UPS, allowing users to set parameters, command delivery,
information reports, and UPS key information and parameters displayed on the LCD.

Figure 5-15 Monitoring interface card

The maximum voltage and current of ports DO_1 to DO_4 are 30 V DC, 1 A or 60 V DC, 0.5 A
respectively.

Table 5-4 Ports on the monitoring interface card

Port Silk Screen Description

DO_1 NO DO_1 is used to output alarms and indicates critical


alarms by default. It can be set to indicate minor
COM alarms, bypass mode, battery mode, or low battery
voltage.
DO_2 NO DO_2 is used to output alarms and indicates minor
alarms by default. It can be set to indicate critical
COM alarms, bypass mode, battery mode, or low battery
voltage

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 26


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Port Silk Screen Description


DO_3 NO DO_3 is used to output alarms and indicates bypass
mode by default. It can be set to indicate critical
COM alarms, minor alarms, battery mode, or low battery
voltage.
DO_4 NO DO_4 is used to output alarms and indicates battery
mode by default. It can be set to indicate critical
COM alarms, minor alarms, bypass mode, or low battery
voltage.
DB26 MDU Provides FE, RS485, I2C, and CAN signals.
Battery B_TEMP Connects to an indoor battery temperature sensor.
temperature sensor
port
Southbound COM1  Supported protocol: Modbus-RTU.
communications  Connects to an ambient temperature and
port 1 humidity sensor over two wires.
Southbound COM2  Supported protocol: Modbus-RTU.
communications  Connects to a southbound device.
port 2
Network port FE  Supported protocols: Modbus-TCP, HTTPS, and
SNMP.
 Connects to the network port on a PC.
Northbound RS485  Supported protocol: Modbus-RTU.
communications  Connects to a northbound network management
port device over two wires.

 Signal cables must be double-insulated twisted cables. If the cable length is 25–50 m, the
cross-sectional area must be 0.5–1.5 mm2.
 RS485 cables and FE cables must be shielded cables.

Figure 5-16 and Figure 5-17 are recommended wiring methods for DO ports.

Figure 5-16 Wiring method 1

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 27


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-17 Wiring method 2

Figure 5-18 and Table 5-5 describe the COM1 pin definitions.

Figure 5-18 COM1 pins

Table 5-5 COM1 pin definition

Pin Description
1 GND
2 N/A
3 RS485-
4 RS485+
5 N/A
6 12V_PORT

Figure 5-19 and Table 5-6 describe the COM2 pin definitions.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 28


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-19 COM2 pins

Table 5-6 COM2 pin definition

Pin Description

1 RS485+
2 RS485-
3 N/A
4 RS485+
5 RS485-
6 GND
7 CANH0
8 CANL0

Figure 5-20 and Table 5-7 describe the RS485 pin definitions.

Figure 5-20 RS485 pins

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 29


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-7 RS485 pin definition

Pin Description
1 RS485_T+
2 RS485_T–
3 N/A
4 RS485_R+
5 RS485_R–
6 GND
7 N/A
8 N/A

If cables are prepared onsite, follow the three methods below:


 Connect pin 1 and pin 2. Pin 1 connects to RS485+ and pin 2 connects to RS485–.
 Connect pin 4 and pin 5. Pin 4 connects to RS485+ and pin 5 connects to RS485–.
 Connect pins 1, 2, 4, and 5. Twist cables to pin 1 and pin 4 into one cable and then connect it to
RS485+. Twist cables to pin 2 and pin 5 into one cable and then connect it to RS485–.

5.3.5 MDU
Appearance

Figure 5-21 MDU

(1) Status indicator (2) LCD touchscreen

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 30


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-8 Status indicator

Status Color Meaning


On Red A critical alarm has been generated, and the buzzer sounds
continuously.
Yellow A minor alarm has been generated, and the buzzer buzzes at 2 Hz.
Green The UPS is running properly or a warning has been generated.
Off N/A The MDU is powered off.

The indicator on the MDU panel is yellow when the bypass supplies power in non-ECO mode.

Figure 5-22 MDU ports

Table 5-9 Description of MDU ports

No. Port Name Description

1 MUS05A Connects to the MDU and monitoring interface card


(DB26)
2 FE Network port
3 CAN Reserved
4 RS485_1 Reserved
5 USB Host  After installing the WiFi module, locally connect to the
UPS over the Service Expert app. Obtain the initial
startup password during deployment. View or obtain
UPS running information during preventive
maintenance.
NOTE
Only Huawei service engineers or authorized service engineers are
allowed to use the WiFi module. To ensure security, remove the

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 31


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

No. Port Name Description


WiFi module immediately after use.
 Insert the USB flash drive, import and export the
configuration file, export run logs, and upgrade software.
6 RST Restart switch for the MDU
7 SD Reserved
8 DIP switch Implements specific functions by using the DIP switch and
specific buttons; controls the CAN communication build-out
resistor in a parallel system

Functions
The monitor display unit (MDU) allows for general UPS operations, parameter setting,
viewing of running status and alarms, and so on.

Specifications
Dimensions (H x W x D): 175 mm x 264 mm x 40 mm

5.3.6 Technical Specification


Table 5-10 Physical specifications

Item Specifications
Cable routing mode Routed in and out from the top
Routed in and out from the bottom (tail frame configured)
Protection level IP20
Dimensions (H x W x D) 2000 mm x 600 mm x 1100 mm
Communication Dry contacts, RS485, and SNMP

Table 5-11 Environmental specifications

Item Specifications
Operating temperature 0°C to 40°C
Storage temperature –40°C to +70°C
Relative humidity 5%–95% RH (non-condensing)
Altitude 0–1000 m (When the altitude is greater than 1000 m and less
than 4000 m, the rated power should be derated. For details,
see the IEC62040-3.)

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 32


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-12 Safety and EMC

Item Specifications
Safety compliance EN62040-1, 2013
IEC62040-1, 2013
Electromagnetic EN/IEC62040-2
compatibility (EMC) IEC61000-2-2
IEC61000-4-2
EN61000-4-6: EN/IEC62040-2 2nd Ed (IEC61000-4-6)
EN61000-4-3: EN/IEC62040-2 2nd Ed (IEC61000-4-3)
EN/IEC62040-2 2nd Ed (IEC61000-4-4)
EN/IEC62040-2 2nd Ed (IEC61000-4-5)
IEC61000-4-8
IEC61000-4-11

Table 5-13 Mains Input electrical specifications

Item Specifications
Input system Three-phase, four-wire, and PE
Rated input voltage 380 V AC/400 V AC/415 V AC (line voltage)
Input voltage range 80–280 V AC (phase voltage)
At 0–40°C: The UPS works at full load when the voltage is
176–280 V AC and is linear derated to 40% load when the
voltage is 176–80 V AC.
Input frequency range 40–70 Hz
Input power factor > 0.99 (full load); > 0.98 (half load)
THDi ≤ 3% (linear load; maximum: 3%); ≤ 5% (non-linear load;
maximum: 5%)

Table 5-14 Bypass Input electrical specifications

Item Specifications
Input system Three-phase, four-wire, and PE
Rated input voltage 380 V AC/400 V AC/415 V AC (line voltage)
Input frequency range 50/60 Hz ±6 Hz (adjustable with the tolerance of 0.5–6 Hz, ±2
Hz by default)

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 33


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-15 Battery specifications

Item Specifications
Battery voltage 360–528 V DC (30–44 batteries, 32 by default; derated by 6%
when there are 30 batteries)
Battery management Intelligent battery management
Cold start When a mains outage occurs, batteries can start the UPS to
supply power to loads.
Charging voltage  Equalized charging voltage: 2.3–2.4 V/cell, 2.35 V/cell by
default (30–42 batteries); 2.3–2.35 V/cell, 2.35 V/cell by
default (44 batteries)
 Float charging voltage: 2.23–2.3 V/cell; 2.25 V/cell by
default (30–44 batteries)

Table 5-16 Output electrical specifications

Item Specifications

Output system Three-phase, four-wire, and PE


Voltage 380 V AC/400 V AC/415 V AC (line voltage)
Output voltage precision ±1% (balanced load)
Output power factor 1
Transfer time  Uninterruptible transfer: 0 ms
 Interruptible transfer: ≤ 20 ms
Output voltage imbalance Voltage imbalance: ±3%; phase imbalance: 120±2°
Overload capability Inverter overload capability:
 100% < load ≤ 110%: transfer to bypass mode after 60
minutes
 110% < load ≤ 125%: transfer to bypass mode after 10
minutes (tolerance ±0.1 minute)
 125% < load ≤ 150%: transfer to bypass mode after 1
minute
 Load > 150% or a short circuit occurs: run for 200 ms
Derating coefficient of  40 A circuit breaker: 0.75
output circuit breakers  63 A circuit breaker: 0.7

Table 5-17 System electrical specifications

Item Specifications
System efficiency 96% (linear load)

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 34


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Specifications
Current equalization 5%
specification

5.4 Integrated PDC


Figure 5-23 Integrated PDC

Table 5-18 Technical specifications of the integrated PDC

Item Specifications
Engineering Dimensions (H x W x D)  Basic dimensions: 2000 x 600 x 1100,
features (mm) 2000 x 600 x 1200
 Expanded dimensions: 2200 (including
a top frame) x 600 x 1200
Weight (kg) < 350
Enclosure protection level IP20
Cable routing Routed in and out from the top
Maintenance mode Operated from the front and maintained
from the rear

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 35


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Specifications
Installation mode Installed on an ESD floor or concrete floor
Electrical Rated operating voltage (V 380/400/415
features AC)
Rated insulation voltage (V 690
AC)
Rated frequency (Hz) 50/60
IT power distribution input  One 3-pole 160 A MCCB input
mode  One 3-pole 250 A MCCB input
 Two 3-pole 160 A MCCB inputs
 Two 3-pole 250 A MCCB inputs
Smart cooling product  One 3-pole 160 A MCCB input
power distribution input  One 3-pole 250 A MCCB input
mode
 Two 3-pole 160 A MCCB inputs
 Two 3-pole 250 A MCCB inputs
Output switch (standard  IT power distribution branch: a
configuration) maximum of 48 branches
(single-phase) or 16 branches
(three-phase), a maximum of 40 A
current for each branch
 Smart cooling product power
distribution branch: a maximum of 16
branches (three-phase), a maximum of
63 A current for each branch
Lighting switch Smart cooling product with dual inputs:
six 1-pole 10 A switches
Smart cooling product with single input:
three 1-pole 10 A switches
Surge protection Class C; nominal discharge current In
(8/20 µs) = 20 kA, maximum discharge
current Imax (8/20 µs) = 40 kA; voltage
protection level Up (20 kA, 8/20 μs) ≤ 1.8
kV (L-N)/≤ 1.0 kV (N-PE)
Monitoring Detection items Three-phase input voltage, current,
function frequency, active power, reactive power,
electric energy, power factor, and
temperature
Communications mode Supports the Modbus TCP protocol and
Modbus RTU protocol.
(Optional) Branch temperature monitoring
Certifications CE, CCC

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 36


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-19 Monitoring specifications

Item Specifications
Power distribution mains input Phase voltage, phase current, load rate, frequency,
power factor, total active power, total electric energy,
total apparent power, total reactive power, busbar
temperature, circuit breaker status, and surge
protection status
Power distribution branch output Phase current, active power, load rate, electric
energy, temperature, and circuit breaker status

5.5 Precision PDC


Figure 5-24 Precision PDC

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 37


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-20 Precision PDC technical specifications

Item Specifications
Dimensions (H x W x D)  Basic dimensions: 2000 x 600 x 1100, 2000 x 600 x
(mm) 1200
 Expanded dimensions: 2200 (including a top frame) x
600 x 1200
Weight (kg) < 400
Rated operating voltage (V) 380/400/415
Rated insulation voltage (V) 690
Rated frequency (Hz) 50/60
Rated operating current (A) 400/250/160
Enclosure protection level IP20
Output switch 40 A single-phase, maximum 144 routes (single-phase)
Surge protection Class C; nominal discharge current In (8/20 µs) = 20 kA,
maximum discharge current Imax (8/20 µs) = 40 kA;
voltage protection level Up (20 kA, 8/20 μs) ≤ 1.8 kV
(L-N)/≤ 1.0 kV (N-PE)
Cable routing Routed in and out from the top or bottom
Certifications CCC, CE
Environmental friendliness RoHS, REACH

Table 5-21 Monitoring specifications

Item Specifications
Power distribution mains Phase voltage, phase current, load rate, frequency, power
input factor, total active power, total electric energy, total
apparent power, total reactive power, busbar temperature,
circuit breaker status, and surge protection status
Power distribution branch Phase current, active power, load rate, electric energy,
output temperature, and circuit breaker status

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 38


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.6 New Main Way


Figure 5-25 New main way

The new main way does not support a three-phase rPDU.

Table 5-22 New main way features

Item Feature
High efficiency, Space saving: saves the IT cabinet space.
economical, and rapid
delivery Easy maintenance: short maintenance duration.
High scalability: Busbar trunking units can be added. Each
busbar trunking unit connects to one power distribution unit.
Long lifespan.
Power saving.
Safe, reliable, and flexible High reliability: uses a foolproof structure with installation
O&M position marks and spacing measures.
Easy O&M: can be easily maintained as the new main way is
highly reliable and allows users to replace power distribution
units.
Easy installation: short time to install the new main way.
Intelligent monitoring and Easy to network through an FE port to implement
flexible management teleindication, telemetering, and teleadjusting.
Flexible to manage and monitor the power usage effectiveness
(PUE) and maintenance.
Intelligently measures and monitors parameters such as
electricity, current, voltage, power factor, total active power,
total apparent power, total reactive power, and neutral wire
current.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 39


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-23 Technical specifications

Item Specifications
System type Three-phase, four-wire, and PE
Rated operating voltage 380 V AC, 400 V AC, or 415 V AC
Overvoltage type III
Rated operating current at 40°C 160 A/250 A
Input switch  One 3-pole 160 A MCCB
 One 3-pole 250 A MCCB
Output switch Six 1-pole 40 A MCBs
Rated transient withstand current 10 kA, 1s
Rated frequency 50/60 Hz
Protection level IP30
Electric shock protection type Type I
Electromagnetic compatibility (EMC) Level A
environment
Cabling mode Routed in from the end
Cable connection capacity  160 A rated current: 4 x 70 mm2 + 1 x
35 mm2
 250 A rated current: 4 x 95 mm2 + 1 x
50 mm2

Table 5-24 Monitoring specifications

Item Specifications
Power distribution mains input Phase voltage, phase current, load rate, frequency,
power factor, total active power, total electric energy,
total apparent power, total reactive power, busbar
temperature, and circuit breaker status
Power distribution branch output Phase current, active power, load rate, electric
energy, temperature, and circuit breaker status

5.7 Smart cooling product PDB


The smart cooling product PDB supplies power to smart cooling products and aisle lighting in
precision PDC or new main way scenarios.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 40


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-26 Appearance

Table 5-25 Technical specifications

Item Technical Specifications


Rated operating voltage 380 V/400 V/415 V
Rated frequency 50/60 Hz
Rated operating current 160 A/250 A/400 A
Input switch 160 A/3P MCCB, 250 A/3P MCCB, 400 A/3P MCCB
Output switch  Rated current 160 A: 8 x 40 A/3P + 2 x 10 A/1P + 1 x 32
A/1P MCB
 Rated current 250 A/400 A: 8 x 63 A/3P + 2 x 10 A/1P + 1
x 32 A/1P MCB
IP rating IP20
Surge protection level Level C SPD
Certification CE, CCC
Installation mode Wall-mounted
Flame spread rating Fire-retardant materials with a flame spread rating of V0 are
used. The heat shrink tubing is at least 1 mm thick.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 41


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.8 Battery Cabinet


A maximum of two battery groups and up to four battery cabinets (in 2N scenario) can be
deployed inside the smart module. If many batteries are configured, they can be deployed
outside the smart module.
 If the configured batteries can be placed in four or fewer battery cabinets, it is
recommended that battery cabinets be deployed inside the smart module (smart module
A). Battery cabinets or racks can also be deployed with UPS batteries outside smart
module A (batteries deployed outside) or smart module B.
 If the number of configured batteries exceeds the capacity of four battery cabinets, it is
recommended that battery racks be deployed outside smart module A (batteries deployed
outside) or the smart module B. Battery cabinets can also be deployed with UPS batteries
outside smart module A (batteries deployed outside) or smart module B.
The battery cabinets provide space for installation and cabling of batteries and the iBattery
intelligent battery management system for the smart module.

Figure 5-27 Battery cabinet

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 42


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-28 Battery cabinet components

(1) BIB (battery control I/O board) (2) iBOX (CIM)


(3) Batteries (4) Circuit breaker

Table 5-26 Battery cabinet technical specifications

Item Technical Specifications


External dimensions  Basic dimensions: 2000 mm x 600 mm x 1100 mm
(H x W x D)  Dimensions after expansion: 2200 mm x 600 mm x 1100 mm
(with the top frame)
 Basic dimensions: 2000 mm x 600 mm x 1200 mm
 Dimensions after expansion: 2200 mm x 600 mm x 1200 mm
(with the top frame)
Color Black (PANTONE426C/RAL9005)
Material High-intensity class A carbon cold rolled steel plate and
zinc-coated steel plate
Air channel Front and rear air channels
Installation space 42 U
Installation mode Installed on a concrete floor or ESD floor
Door opening mode The front door is a single door, and the rear door is a double one.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 43


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Technical Specifications


Weight 128 kg (excluding batteries)
Protection level IP20

Shoto and Enersys batteries are supported.

Table 5-27 Maximum number of batteries inside a battery cabinet

Battery Specifications Maximum Number of Batteries


Inside a Battery Cabinet
26 Ah 40
40 Ah
65 Ah 20
100 Ah

Table 5-28 Configuration scenarios (for both the main and auxiliary battery cabinets)

Battery Layer (from Top Number of Batteries


Specifications to Bottom)

- - 40 38 36 34 32
26 Ah/40 Ah Layer 1 10 9 8 7 6
Layer 2 10 10 10 10 10
Layer 3 10 10 10 10 10
Layer 4 10 9 8 7 6

Table 5-29 Configuration scenarios (The main battery cabinet and auxiliary battery cabinet are
differentiated.)

Battery Layer Main Battery Cabinet Auxiliary Battery


Specifications (from (Number of Batteries) Cabinet (Number of
Top to Batteries)
Bottom)

- - 20 19 18 17 16 20 19 18 1 1
7 6
65 Ah/100 Ah Layer 1 5 4 3 2 1 5 4 3 2 1
Layer 2 5 5 5 5 5 5 5 5 5 5

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 44


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Battery Layer Main Battery Cabinet Auxiliary Battery


Specifications (from (Number of Batteries) Cabinet (Number of
Top to Batteries)
Bottom)

Layer 3 5 5 5 5 5 5 5 5 5 5
Layer 4 5 5 5 5 5 5 5 5 5 5

5.9 rPDU
The rPDU uses IEC sockets by default. GB sockets are also supported.

Figure 5-29 Full-height rPDU

Figure 5-30 Half-height rPDU

The figures are for reference only. The actual products prevail.

A three-phase rPDU cannot be used with the smart busway.

Table 5-30 rPDU specifications

Type Model Output Port


IEC PDU2000-32-1PH-9/3-B1 9 x C13 + 3 x C19
(half height)
PDU2000-32-1PH-20/4-B9 20 x C13 + 4 x C19
(full height)
PDU2000-32-3PH-12/9-B2 12 x C13 + 9 x C19
(full height)
GB PDU2000-32-1PH-9/3-B2 GB 10 A: 9
(half height) GB 16 A: 3

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 45


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Type Model Output Port


PDU2000-32-1PH-20/4-B2 GB 10 A: 20
(full height) GB 16 A: 4
PDU2000-32-3PH-12/9-B3 GB 10 A: 12
(full height) GB 16 A: 9

5.10 (Optional) Ground Copper Bar


Ground copper bars can be horizontal and vertical. Vertical ground copper bars are longer
than horizontal ones. Ground copper bars are used to ground cabinets. Ground copper bars are
installed in the battery cabinet or IT cabinet closest to the PDC.

Figure 5-31 Horizontal ground bar

Figure 5-32 Vertical ground bar

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 46


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-33 Installation position for a horizontal ground copper bar

Figure 5-34 Installation positions for vertical ground copper bars

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 47


FusionModule2000 Smart Modular Data Center
Product Description 6 Structural System

6 Structural System

6.1 Single-Row 1200 mm Wide Aisle Containment


The single-row 1200 mm wide aisle containment can be a cold or hot aisle containment that
involves the following components: IT cabinet, network cabinet, PDC, smart cooling product,
battery cabinet, skylight, end door, and cable trough. A cold aisle containment is used as an
example.

Figure 6-1 Components of the single-row 1200 mm wide cold aisle containment (PDC)

(1) End door (2) Flat or rotating skylight (3) Control skylight
(4) Cable trough (5) Smart ETH gateway (6) Cabinet
(7) Alarm beacon (8) Pad (9) Access control device

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 48


FusionModule2000 Smart Modular Data Center
Product Description 6 Structural System

Figure 6-2 Components of the single-row 1200 mm wide cold aisle containment (smart busway)

(1) General input unit (2) Control skylight (3) Alarm beacon
(4) Power distribution unit (5) Busbar trunking unit (6) Flat or rotating skylight
(7) Cable trough (8) Cabinet (9) Pad
(10) Access control device (11) End door

6.2 Dual-Row 1200 mm Wide Aisle Containment


The dual-row 1200 mm wide aisle containment can be a cold or hot aisle containment that
involves the following components: IT cabinet, network cabinet, PDC, smart cooling product,
battery cabinet, skylight, end door, and cable trough. A cold aisle containment is used as an
example.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 49


FusionModule2000 Smart Modular Data Center
Product Description 6 Structural System

Figure 6-3 Components of the dual-row 1200 mm wide cold aisle containment (power supply and
distribution cabinet)

(1) End door (2) Flat or rotating skylight (3) Control skylight
(4) Cable trough (5) Smart ETH gateway (6) Cabinet
(7) Alarm beacon (8) Pad (9) Access control device

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 50


FusionModule2000 Smart Modular Data Center
Product Description 6 Structural System

Figure 6-4 Components of the dual-row 1200 mm wide cold aisle containment (smart busway)

(1) General input unit (2) Control skylight (3) Alarm beacon
(4) Power distribution unit (5) Busbar trunking unit (6) Flat or rotating skylight
(7) Cable trough (8) Cabinet (9) Pad
(10) Access control device (11) End door

6.3 Network Cabinet


The network cabinet provides the smart module with the space for integrated cabling and the
cable management interface.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 51


FusionModule2000 Smart Modular Data Center
Product Description 6 Structural System

Figure 6-5 Network cabinet

Table 6-1 Network cabinet technical specifications

Item Technical Specifications


External dimensions (H x  2000 mm x 600 mm x 1100 mm (with castors)
W x D)  2000 mm x 600 mm x 1200 mm (with castors)
 2000 mm x 800 mm x 1100 mm (with castors)
 2000 mm x 800 mm x 1200 mm (with castors)
 2200 mm x 600 mm x 1200 mm (without castors)
 2200 mm x 800 mm x 1200 mm (without castors)
Color Black (PANTONE426C/RAL9005)
Material High-intensity class A carbon cold rolled steel plate and
zinc-coated steel plate
Air channel Front and rear air channels
Installation space  A 2000 mm high cabinet provides 42 U available space.
 A 2200 mm high cabinet provides 47 U available space.
 The distance between the front and rear mounting bars
can be adjusted by the step of 25 mm. Positions behind
the cabinet are reserved for installing two rPDUs.
Installation mode Installed on a concrete floor, a base, or an ESD floor

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 52


FusionModule2000 Smart Modular Data Center
Product Description 6 Structural System

Item Technical Specifications


Door opening mode The front door is a single door, and the rear door is a double
one.
Weight of an empty  2000 mm x 600 mm x 1200 mm: 128 kg
cabinet  2000 mm x 800 mm x 1200 mm: 153 kg
The weight of an empty  2200 mm x 600 mm x 1200 mm: 137 kg
cabinet includes the weight
 2200 mm x 800 mm x 1200 mm: 164 kg
of the front and rear doors.
 2000 mm x 600 mm x 1100 mm: 110 kg
 2000 mm x 800 mm x 1100 mm: 135 kg
Protection level IP20

6.4 IT Cabinet
An IT cabinet used in the smart module complies with the International Electrotechnical
Commission (IEC) 60297-1 standard and provides stable installation space for servers,
thereby ensuring safe operation of servers.
The cabinet dimensions are unified, and both front and rear air channels are designed.

Figure 6-6 IT cabinet

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 53


FusionModule2000 Smart Modular Data Center
Product Description 6 Structural System

The cabinet provides the following features:


 The ventilation rate of the front and rear doors is at least 70%.
 Two rack power distribution units (rPDUs) can be vertically installed at the rear inside
the cabinet.
 The position of each U is marked on the vertical mounting bars.
 The front and rear doors are locked and can be unlocked only with dedicated keys.
 The cabinet supports a door status sensor and electronic access control.
 The maximum static load of the cabinet is 1800 kg.

Table 6-2 Cabinet technical specifications

Item Technical Specifications


External  2000 mm x 600 mm x 1100 mm (with castors)
dimensions (H x W  2000 mm x 600 mm x 1200 mm (with castors)
x D)
 2000 mm x 800 mm x 1100 mm (with castors)
 2000 mm x 800 mm x 1200 mm (with castors)
 2200 mm x 600 mm x 1200 mm (without castors)
 2200 mm x 800 mm x 1200 mm (without castors)
Color Black (PANTONE426C/RAL9005)
Material High-intensity class A carbon cold rolled steel plate and zinc-coated
steel plate
Air channel Front and rear air channels
Installation space  A 2000 mm high cabinet provides 42 U available space.
 A 2200 mm high cabinet provides 47 U available space.
 The distance between the front and rear mounting bars can be
adjusted for every 25 mm.
− For a 1200 mm deep cabinet: The maximum depth for
installing devices inside the cabinet is 750 mm and can be
extended to 850 mm by adjusting the mounting bars.
− For a 1100 mm deep cabinet: The maximum depth for
installing devices inside the cabinet is 700 mm and can be
extended to 750 mm by adjusting the mounting bars.
 Positions for vertically installing two rPDUs are provided in the
rear of the cabinet.
Installation mode Installed on a concrete floor, a base, or an ESD floor
Door opening mode The front door is a single door, and the rear door is a double one.
Weight of an empty  2000 mm x 600 mm x 1200 mm: 128 kg
cabinet  2000 mm x 800 mm x 1200 mm: 153 kg
The weight of an  2200 mm x 600 mm x 1200 mm: 137 kg
empty cabinet
 2200 mm x 800 mm x 1200 mm: 164 kg
includes the weight
of the front and rear  2000 mm x 600 mm x 1100 mm: 110 kg
doors.  2000 mm x 800 mm x 1100 mm: 135 kg

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 54


FusionModule2000 Smart Modular Data Center
Product Description 6 Structural System

Item Technical Specifications


Protection level IP20
Optional cabinet Cable ring, bottom sealing plate, guide rail, tray, side door panel,
accessories and bottom plate

6.5 Skylight
Skylights are used for sealing an aisle containment. Skylights are classified as control
skylights, rotating skylights, and flat skylights.

Table 6-3 Skylight technical specifications

Item Dimensions (H x W x D) Applicable Cabinet Dimensions


(H x W x D)

Control skylight 341 mm x 605 mm x 1334 mm  2000 mm x 600 mm x 1200 mm


 2000 mm x 600 mm x 1100 mm
 2200 mm x 600 mm x 1200 mm
341 mm x 805 mm x 1334 mm  2000 mm x 800 mm x 1200 mm
 2000 mm x 800 mm x 1100 mm
 2200 mm x 800 mm x 1200 mm
300 mm wide 341 mm x 305 mm x 1334 mm  2000 mm x 300 mm x 1200 mm
flat skylight  2000 mm x 300 mm x 1100 mm
 2200 mm x 300 mm x 1200 mm
600 mm wide 341 mm x 605 mm x 1334 mm  2000 mm x 600 mm x 1200 mm
flat or rotating  2000 mm x 600 mm x 1100 mm
skylight
 2200 mm x 600 mm x 1200 mm
800 mm wide 341 mm x 805 mm x 1334 mm  2000 mm x 800 mm x 1200 mm
flat or rotating  2000 mm x 800 mm x 1100 mm
skylight
 2200 mm x 800 mm x 1200 mm

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 55


FusionModule2000 Smart Modular Data Center
Product Description 6 Structural System

Figure 6-7 300 mm wide flat skylight

(1) Skylight connective plate (2) Flat skylight panel

The 300 mm wide flat skylight is used with a 300 mm wide smart cooling product.

Figure 6-8 Control skylight

(1) Skylight connective plate (2) Control skylight panel (3) Cable separation panel

 Control skylights are installed on both ends of an aisle and used to install monitoring components
such as the camera, multi-functional sensor, and smoke detector.
 If the smart module is longer than 7 m, add one control skylight in the middle of the smart module
for installing a multi-functional sensor or smoke detector.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 56


FusionModule2000 Smart Modular Data Center
Product Description 6 Structural System

Figure 6-9 600 mm wide flat or rotating skylight

(1) Magnetic lock fixing base (2) Skylight connective plate (3) Flat skylight panel

 A rotating skylight is designed with an eccentric structure. When the trigger is activated, a rotating
skylight falls under gravity. When a magnetic lock is triggered, the rotating skylight falls under
gravity.
 The BOM numbers of 600 mm wide rotating and flat skylights are the same (21501038). The
rotating skylight requires a magnetic lock but the flat skylight does not.

Figure 6-10 800 mm wide flat or rotating skylight

(1) Magnetic lock fixing base (2) Skylight connective plate (3) Rotating skylight panel

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 57


FusionModule2000 Smart Modular Data Center
Product Description 6 Structural System

The BOM numbers of 800 mm wide rotating and flat skylights are the same (21501039). The rotating
skylight requires a magnetic lock but the flat skylight does not.

6.6 Aisle End Door


End doors are classified into sliding doors and revolving doors. End doors are installed on
both ends of the aisle containment, which makes the module independent, improves
equipment efficiency, and helps onsite personnel or devices move into or out of the aisle
containment.

Sliding Door

Figure 6-11 Sliding door

The dimensions of sliding doors are as follows:


2000 mm high cabinet: H x W x D = 2300 mm x 1400 mm x 54 mm
2200 mm high cabinet: H x W x D = 2500 mm x 1400 mm x 54 mm

Sliding doors can be opened only sideways, and therefore may involve risks during fire extinguishing
system acceptance.

Revolving Door
The double revolving door is an outward opening door with an opening angle of 90 degrees. It
ensures that the aisle containment is properly sealed and separated.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 58


FusionModule2000 Smart Modular Data Center
Product Description 6 Structural System

Figure 6-12 Double revolving door

The dimensions of double revolving doors are as follows:


2000 mm high cabinet: H x W x D = 2300 mm x 1400 mm x 80 mm
2200 mm high cabinet: H x W x D = 2500 mm x 1400 mm x 80 mm

6.7 Cabinet Bottom Sealing Plate


Cabinet sealing plates are used to seal the space under cabinets to ensure that an aisle is
airtight.

Table 6-4 Cabinet bottom sealing plate specifications

Installation Position Type Notice


Middle cabinet 300 mm wide front and rear Apply to 300 mm wide
sealing plates smart cooling products.
600 mm wide front and rear Apply to cabinets that are
sealing plates 600 mm wide and 2000 mm
high.
800 mm wide front and rear Apply to cabinets that are
sealing plates 800 mm wide and 2000 mm
high.
End cabinet Bottom sealing plate Apply to end cabinets that
assembly: Front and rear are 2000 mm high.
sealing plates + side sealing
plate (assembled by five
components)
Cabinets on both sides of a Combined lower part: Front Apply to cabinets that are
column (for scenarios with and rear sealing plates + located on both sides of a
columns) side sealing plate column and are 2000 mm
(assembled by five high.
components)

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 59


FusionModule2000 Smart Modular Data Center
Product Description 6 Structural System

Figure 6-13 Bottom sealing plate assembly

(1) Side sealing plate (2) Front or rear sealing plate

Figure 6-14 600 mm/800 mm wide bottom sealing plate

Figure 6-15 300 mm wide bottom sealing plate

6.8 Cabinet Enclosure Plate


Enclosure plates are used for sealing an aisle. They can be 300 mm, 600 mm, and 800 mm
wide and apply only to a single row of cabinets.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 60


FusionModule2000 Smart Modular Data Center
Product Description 6 Structural System

Figure 6-16 Cabinet enclosure plate

6.9 (Optional) Base


Adjustable Bases
An adjustable base for the FusionModule2000 can be 300 mm, 600 mm, or 800 mm wide.
The minimum adjustment range is 1 mm.

Table 6-5 Base specifications

Type Dimensions
600 mm wide smart cooling Height (adjustable): 270 mm ≤ H ≤ 410 mm; depth
product, PDC, IT cabinet, (adjustable): 1000 mm, 1100 mm, or 1200 mm
battery cabinet, or network
cabinet base Height (adjustable): 410 mm ≤ H ≤ 700 mm; depth
(adjustable): 1000 mm, 1100 mm, or 1200 mm
300 mm wide smart cooling Height (adjustable): 270 mm ≤ H ≤ 410 mm; depth
product base (adjustable): 1000 mm, 1100 mm, or 1200 mm
Height (adjustable): 410 mm ≤ H ≤ 700 mm; depth
(adjustable): 1000 mm, 1100 mm, or 1200 mm
800 mm wide IT or network Height (adjustable): 270 mm ≤ H ≤ 410 mm; depth
cabinet base (adjustable): 1000 mm, 1100 mm, or 1200 mm
Height (adjustable): 410 mm ≤ H ≤ 700 mm; depth
(adjustable): 1000 mm, 1100 mm, or 1200 mm

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 61


FusionModule2000 Smart Modular Data Center
Product Description 6 Structural System

Fixed Bases
The fixed bases for the FusionModule2000 are classified into cabinet bases (600 mm wide),
smart cooling product bases (300 mm wide), smart cooling product and PDC bases (600 mm
wide), and cabinet bases (800 mm wide).

Table 6-6 Base specifications

Type Dimensions (H x W x D)
600 mm wide IT, battery, or network 250 mm x 600 mm x 1200 mm
cabinet base
300 mm wide smart cooling product base 250 mm x 300 mm x 1200 mm
600 mm wide smart cooling product or 250 mm x 600 mm x 1200 mm
PDC base
800 mm wide IT or network cabinet base 250 mm x 800 mm x 1200 mm

6.10 Cable Trough


Cabinet cable troughs are categorized into signal cable troughs and power cable troughs,
which are used to route signal cables and power cables respectively. This ensures that weak
current cables are separated from strong current cables.
A cable trough consists of several parts that are clamped together. A cable trough is assembled
using two brackets, one supporting plate, and one partition plate (used to separate
weak-current optical fibers from weak-current network cables and separate strong-current
route A from strong-current route B).
A cable trough is 170 mm high and 310 mm long.

Figure 6-17 300 mm wide cable trough

(1) Bracket (2) Supporting plate


(3) Partition plate

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 62


FusionModule2000 Smart Modular Data Center
Product Description 6 Structural System

Figure 6-18 600 mm or 800 mm wide cable trough

(1) Bracket (2) Supporting plate


(3) Partition plate (4) Position for the smart ETH gateway

6.11 (Optional) Cable Tray


Cable trays are used to route cables across two rows of cabinets in the smart module. If two
rows of cabinets are deployed, route strong-current and weak-current cables over the control
skylight at either end of the rows preferentially. If there are more than 24 cabinets, install one
cable tray on the top of end cabinets for routing power cables as there are many cables to be
routed.
A cable tray is 2.5 m long.

Figure 6-19 Cable tray

(1) Cable ladder support (2) Cable ladder

6.12 (Optional) Adaptive Frame


To meet requirements for cabinet height and depth in different scenarios, tail frames, top
frames, and smart cooling product adaptive frames can be installed. In this way, all cabinets in
the smart module can have the same height and depth and the two rows of cabinets can have
the same length.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 63


FusionModule2000 Smart Modular Data Center
Product Description 6 Structural System

Table 6-7 Adaptive frame specifications

Component Width Depth Height Remarks


(mm) (mm) (mm)

PDC tail frame 600 100 2000/2200 Increases the cabinet


depth by 100 mm.
300 mm wide smart 300 100 2000/2200 Increases the cabinet
cooling product depth by 100 mm.
enclosure frame
600 mm wide smart 600 100 2000/2200
cooling product
enclosure frame
300 mm wide top 300 1200 200 Increases the cabinet
frame height by 200 mm.
600 mm wide top 600 1200 200
frame
300 mm smart 300 1100 2000 When there is an odd
cooling product number of 300 mm
adaptive frame 300 1200 2000 smart cooling products,
use the adaptive frame
to supplement the
opposite position to
ensure that the two
rows of cabinets have
the same length.

6.13 Scenario with Columns


The FusionModule2000 can be used in the scenario with columns if the following conditions
are met:
 The maximum dimensions of a column in the data center are 1100 mm x 1100 mm.
 There are fewer than two columns in the aisle width direction.
 If a column is located at an end of the smart module, the smart module supports only the
revolving door.
 If a column in the data center is irregular, ensure that the maximum cross section of the
column does not interfere with cabinets.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 64


FusionModule2000 Smart Modular Data Center
Product Description 6 Structural System

Figure 6-20 Scenario with columns

For more information, see the FusionModule2000 configuration manual.

6.14 Cable Management Devices


Cables inside cabinets are sorted by cable managers, cable rings, and cable trays. Cable
managers route cables horizontally, cable rings on the cabinet side route cables vertically, and
cable trays route cables from the cabinet front to cabinet rear.

Cable Manager
A cable manager is used to manage cables inside a cabinet horizontally.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 65


FusionModule2000 Smart Modular Data Center
Product Description 6 Structural System

Figure 6-21 Cable manager

Table 6-8 1 U cable manager specifications

Dimensions (H x W x D) Weight Space Occupied


43.6 mm x 482.6 mm x 91 mm 0.56 kg 1U

Cable Ring
A cable ring is installed on a side post in the cabinet to secure vertically routed cables.

Figure 6-22 Cable ring

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 66


FusionModule2000 Smart Modular Data Center
Product Description 6 Structural System

Table 6-9 Cable ring specifications

Name Dimensions (H x W x D) Weight


Standard cable ring 55 mm x 48 mm x 188.6 mm 0.163 kg
Small cable ring 55 mm x 48 mm x 44 mm 0.096 kg

Cable Tray
A cable tray is used for forward and backward cabling. It uses mounting ears to facilitate
device installation.

Figure 6-23 Cable tray

Table 6-10 Cable tray specifications

Dimensions (H x W x D) Weight Space Occupied


43.6 mm x 482.6 mm x 250 mm 1.89 kg 1U

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 67


FusionModule2000 Smart Modular Data Center
Product Description 6 Structural System

Figure 6-24 Installation positions for cable management devices

(1) Cable rack (2) Cable ring (3) Cable tray

The installation positions for cable management devices are for reference only. Determine the
installation positions based on the actual situation.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 68


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

7 Temperature Control System

7.1 System Overview


The cooling system uses in-row air cooled smart cooling products and an aisle containment
for cooling. The in-row air cooled smart cooling products and equipment cabinets form an
aisle containment to separate hot air from cold air.
An in-row air cooled smart cooling product works as follows: After the unit starts, the
low-pressure refrigerant vapor in the refrigerating system is suctioned into the compressor,
compressed into high-pressure vapor, and discharged to the condenser. The outdoor air drawn
in by the axial flow fan flows through the condenser and carries away the heat emitted from
the refrigerant so that the high-pressure refrigerant vapor condenses into high-pressure liquid.
The high-pressure liquid passes through the filter and flow regulating mechanism and then is
ejected to the evaporator. Then the liquid vaporizes at low pressure and absorbs ambient heat.
The cross-flow fan draws air into the fins in the evaporator to exchange heat and discharges
cooled air to the cold aisle. The indoor air flows cyclically to decrease the temperature.
In-row smart cooling products are close to heat sources, which shortens the air supply
distance, reduces airflow pressure loss and cold air loss, and maximizes the use of cooling
capacity.

7.2 NetCol5000-A025 Smart Cooling Product


This section describes the components, operating environment, and technical specifications of
the NetCol5000-A025 In-row Air Cooled Smart Cooling Product (25 kW smart cooling
product for short).

7.2.1 Indoor Unit Components


Dimensions
Dimensions (H x W x D) of the NetCol5000-A in standard configurations are 2000 mm x 300
mm x 1100 mm, as shown in Figure 7-1. The equipment depth can be extended to 1200 mm
by adding an enclosure frame to the front door.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 69


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Figure 7-1 Dimensions (unit: mm)

Components
The indoor unit of the NetCol5000-A consists of a compressor, oil separator, fan, heat
exchanger, electronic expansion valve, one-way valve, filter dryer, sight glass, electric heater
(optional), electrode humidifier (optional), wet film humidifier (optional), water pump
(optional), and so on.
 Compressor
The DC variable-frequency compressor provides the cooling capacity ranging from 20%
to 100% to meet partial load requirements.
 Oil separator
It is an oil-gas separator that separates lubricant from the exhaust of the compressor and
brings back the separated lubricant to the compressor.
 EC fan
The EC fan implements stepless speed adjustment.
 Heat exchanger
The efficient finned evaporator, an important part in the cooling system, absorbs heat
from indoor air to ensure that the indoor temperature and humidity meet requirements.
 Electronic expansion valve
The flow regulator uses a micro controller to control the motor operation, thereby
changing the pass-through area of the valve to precisely regulate the flow of refrigerant.
 One-way valve
The one-way valve efficiently controls backflow of gas or liquid.
 Filter dryer

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 70


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

The filter dryer absorbs moisture from refrigerant pipes and filters out foreign matter,
which reduces the component damage probability and ensures efficient and reliable
operating of components.
 Sight glass
The sight glass allows you to observe the refrigerant flow and the content of gas and
liquid for easy maintenance and optimization.
 Electric heater
The PTC heater features quick start, large heating capacity, and even heat dissipation. It
has multiple protection mechanisms to ensure the secure and stable running of the
equipment.
 Humidifier
The electrode or wet film humidifier can be used to precisely control the equipment
room humidity.
 Water pump
The water pump provides power for top drainage with a maximum lift of 4 meters.

7.2.2 Controller
7.2.2.1 Appearance and Ports

Appearance
The controller provides a 7-inch true color touchscreen and man-machine interfaces for query,
setting, monitoring, and maintenance.
The indicator on the panel displays operating status of the smart cooling product. Figure 7-2
shows the position of the indicator. Table 7-1 describes the mapping between indicators,
buzzers, and alarms. If alarms of different severities (critical, major, minor, or warning) are
raised simultaneously, the indicator status corresponds to the alarm with the highest severity
level and the buzzer status corresponds to the unacknowledged alarm with the highest severity
level.

Figure 7-2 Display panel

(1) Indicator (2) Display panel

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 71


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Table 7-1 Indicator and buzzer status description

Alarm Status Indicator Buzzer


The device is operating properly, or a Green No buzzing
warning is generated.
There is an unacknowledged major Yellow Intermittent buzzing
alarm.
There is an unacknowledged critical Red Constant buzzing
alarm.

Ports

Figure 7-3 Controller side ports

Table 7-2 Ports

No. Name Note

1 MUS05A Reserved
2 FE (fast Ethernet) communications port
3 CAN communications port for the main control board and
LCD
4 RS485_1 Reserved
5 USB Host  After installing the WiFi module, locally connect to
the smart cooling product over the Service Expert

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 72


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

No. Name Note


app. Obtain the initial startup password during
deployment. View or obtain the running information
about the smart cooling product during preventive
maintenance. (Applicable to V200R001C20 and later
versions)
NOTE
Only Huawei service engineers or authorized service engineers
are allowed to use the WiFi module. To ensure security, remove
the WiFi module immediately after use.
 Insert the USB flash drive, import and export the
configuration file, export run logs, and upgrade
software.
6 RST restart switch for the display
7 SD Reserved
8 SW1-4 Dual in-line package (DIP) switch on LCD

7.2.2.2 Function and Features

Function
 Single unit control: Provides logic control for the components of a single smart cooling
product to ensure that the indoor temperature and humidity meet requirements.
 Display operation: Provides a 7-inch touchscreen for you to set parameters for the smart
cooling product and query its status.
 Teamwork control: Enables multiple smart cooling products to work cooperatively,
distributes thermal loads in an optimal way to dramatically reduce power consumption,
and provides multiple standby smart cooling products to improve the reliability.
 The smart cooling product has the following four remote functions.
− Telemetry: supply air temperature, return air temperature, supply air humidity,
return air humidity, and working status of the smart cooling product.
− Teleindication: startup/shutdown states, overvoltage/overcurrent,
undervoltage/undercurrent, return air overtemperature/undertemperature, return air
overhumidity/underhumidity, filter normal/blocked, and fan normal/faulty.
− Telecontrol: smart cooling product startup/shutdown.
− Teleadjusting: temperature, humidity, and alarm threshold.
 Remote management: You can monitor, manage, and upgrade one or more smart cooling
products using the remote management function provided by Huawei.
 Faults and alarms are recorded and stored. Up to 1500 historical fault and alarm records
can be stored.
 Access logs can be traced back. Historical user login and setting records can be
displayed. Up to 1000 historical records can be stored.

Features
 The display panel provides a touchscreen with a concise user-friendly interface.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 73


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

 The controller controls the indoor temperature precisely and responds quickly.
 The controller is protected by a multi-level password protection mechanism, avoiding
misoperations.
 Password verification is required upon the first startup to ensure the system security. No
password verification is required for subsequent startup if the first verification succeeds.
 The display panel displays the operating status and duration of the smart cooling product
components in real time.
 The fault diagnosis system automatically displays the information about current faults,
which facilitates the maintenance.
 The controller provides a variety of external ports including a fast Ethernet (FE) port and
universal serial bus (USB) port that is protected by a security mechanism.

7.2.3 Application Environment

Do not install the smart cooling product near a noise-sensitive place such as an office or a
conference room.

Table 7-3–Table 7-7 describe the operating environment, physical ports, installation
requirements, and water quality requirements of the NetCol5000-A.

Environmental Specifications

Table 7-3 Environmental specifications

Item Specifications
Operating temperature 18–45°C
Operating humidity 20%–80% RH
Storage temperature –40°C to +70°C
Storage humidity 5%–95% RH (non–condensing)
Outdoor temperature  Working with the NetCol500–A032 (including
low–temperature components): –40°C to +45°C
 Working with the NetCol500–A036 (including
low–temperature components): –40°C to +55°C
 Working with the NetCol500–A036: –20°C to +55°C
 Working with the NetCol500-A026SC11E0: –20°C to
+45°C
 Working with the NetCol500-A0265S11E0: –20°C to
+55°C
 Working with the NetCol500-A0265S11E0 (including
low–temperature components): –40°C to +45°C
Protection level  Indoor unit: IP20
 Outdoor unit: IPX5

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 74


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Item Specifications
Altitude 0–1000 m. When the altitude is greater than 1000 meters, the
cooling capacity is derated. The maximum operating altitude is
4000 meters. For the detailed derated data, reference the Table
7-4.

Table 7-4 Altitude table

Height 0 1000 1500 2000 2500 3000 3500 4000


Density correction 1 0.887 0.835 0.785 0.737 0.692 0.649 0.608
Air volume correction 1 0.887 0.835 0.785 0.737 0.692 0.649 0.608
Refrigeration volume 1 0.940 0.909 0.878 0.846 0.815 0.784 0.753
correction

Physical Ports

Table 7-5 Physical ports

Item Specifications
Refrigerant liquid pipe Copper pipe, with an outer diameter of 5/8 inch (15.88 mm)
and thickness of 1.0 mm, withstanding a pressure not smaller
than 4.5 MPa, welding
Refrigerant gas pipe Copper pipe, with an outer diameter of 3/4 inch (19.05 mm)
and thickness of 1.0 mm, withstanding a pressure not smaller
than 4.5 MPa, welding
Water inlet pipe to the G 1/2 inch inner screw thread
humidifier

Installation Requirements

When the total load power of servers corresponding to a single smart cooling product is less
than 5 kW or the equipment room airtightness is not satisfactory, the indoor humidity might
be relatively high, which is not a product quality issue. You are advised to install a
dehumidifier in the equipment room in this case.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 75


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Table 7-6 Installation requirements

Item Specifications
Equipment room door Width ≥ 0.9 m; height ≥ 2.3 m
Floor Bearing capacity ≥ 350 kg/m2; height of the raised floor ≥ 250
mm
Installation mode Installed on a concrete floor, a base, or an ESD floor
Pipe and cable routing Cables and pipes can be routed from the top or bottom
Equivalent length of ≤ 80 m
one-way pipe
Height difference  If the outdoor unit is placed higher than the indoor unit, the
between the indoor and maximum vertical distance between them is 20 m.
outdoor units  If the indoor unit is placed higher than the outdoor unit, the
maximum vertical distance between them is 5 m.
Thickness of the thermal ≥ 13 mm
insulation foam
Inner diameter of the Liquid pipe: 16 mm
thermal insulation foam Gas pipe: 19 mm
Drainage Drainpipes can withstand a high temperature greater than or
equal to 85°C (for the smart cooling products configured with
electrode humidifiers)
Power supply Leakage switches are not recommended for the main circuit. If
leakage switches are required by the customer or local
regulations, use the residual current circuit breaker (RCCB)
that is insensitive to the single-phase DC pulses and transient
current pulses
Note: If some conditions are not met, contact Huawei technical support.

Water Quality Requirements for Wet Film Humidifiers


The inlet water pressure should be in the range of 0.1–0.7 MPa (A reducing valve must be
installed if the inlet water pressure exceeds 0.7 MPa.), and the temperature should be in the
range of 1°C–40°C.
The wet film humidifier should use tap water (no water treatment facility needed for the inlet
water) that meets the following requirements:
 Non-freezing and nephelometric turbidity units (NTU): < 3
 No visible substances
 6.5 ≤ pH value ≤ 8.5
 Total hardness (in CaCO3): ≤ 450 mg/L

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 76


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Water Quality Requirements for Electrode Humidifiers

If the inlet water contains large granules, install a water filtering device at the inlet port to
prevent pipe blockage.

The inlet water pressure should be in the range of 0.1–0.7 MPa (A reducing valve must be
installed if the inlet water pressure exceeds 0.7 MPa.), and the temperature should be in the
range of 1°C–40°C.

Table 7-7 Water quality requirements for electrode humidifiers

Item Requirement Unit


Hydrogen ion 7–8.5 pH
Conductivity at 20°C (σ20)a 125–1250 µS/cm
Inlet water hardness specificationsb ≤ 100 mg/L
a: When σ20 is less than 125 µS/cm, the first vapor exhausting duration of the humidifier is
long; when σ20 greater than 1250 µS/cm, the humidifier service life is affected.
b: A water softener needs to be installed if the inlet water hardness exceeds 100 mg/L
(CaCO3).

7.2.4 Technical Specifications


Table 7-8 and Table 7-9 describe the general and optional specifications of the NetCol5000-A.

Table 7-8 General specifications

Item Specifications
Cooling mode Air cooled
Refrigerant R410A
Air flow mode Horizontal air flow
Dimensions (H x W x D)  2000 mm x 300 mm x 1100 mm (cabinet)
 2000 mm x 300 mm x 1200 mm (cabinet with an
enclosure frame)
 2200 mm x 300 mm x 1100 mm (cabinet with an
enclosure frame, customizable)
 2200 mm x 300 mm x 1200 mm (cabinet with top and
enclosure frames)
Net weight 230 kg
Environmental friendliness REACH, RoHS

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 77


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

 For a smart cooling product with heating and humidification functions, the general switch
is a 40 A, feature C switch that does not derate at 45°C. If the switch derates largely when
the temperature changes, verify that the switch can work at 40 A for a long time at 45°C.
 For a smart cooling product without heating and humidification functions, the general
switch is a 32 A, feature C switch that does not derate at 45°C. If the switch derates largely
when the temperature changes, verify that the switch can work at 25 A for a long time at
45°C.

Table 7-9 Optional specifications

Item NetCol5 NetCol5 NetCol5 NetCol5 NetCol5 NetCol5


000-A02 000-A02 000-A02 000-A02 000-A02 000-A02
5H412D 5H412D 5H412D 5H412D 5H4WE2 5H4WE0
20020E1/ 2E120E1 20020E0/ 2E120E0
NetCol5 NetCol5
000-A02 000-A02
5H40E2 5H40E0
Power supply Dual Dual Single Single Dual Single
mode power power power power power power
supplies supplies supply supply supplies supply
Maximum 20 A 30 A 20 A 30 A 30 A 30 A
current
Power system Supports the 380–415 V, 3PH+N+PE, 50 Hz/60 Hz power system, and
applies to scenarios where the voltage range is 342–457 V and
frequency range is 47–63 Hz.
Voltage If upstream voltage fluctuation exceeds the rated voltage±10%, you are
advised to add a voltage regulator. Otherwise, the smart cooling product
may generate alarms frequently and fail to work properly.
Heating No Yes No Yes Yes Yes
Humidification No Yes No Yes Yes Yes
Pipe routing Top and bottom pipe Bottom pipe routing Top and Bottom
routing bottom pipe
pipe routing
routing
Condensate Yes No Yes No
pump
Water pump lift 4m N/A 4m N/A
In the preceding table, No indicates that the corresponding model does not provide the
function.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 78


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

7.3 NetCol5000-A042 Smart Cooling Product


This section describes the components, operating environment, and technical specifications of
the NetCol5000-A042 In-row Air Cooled Smart Cooling Product (42 kW smart cooling
product for short).

7.3.1 Product Introduction


7.3.1.1 Appearance

Figure 7-4 Dimensions (unit: mm)

(1) Cabinet connecting kit (2) Controller panel (3) Door lock (4) Front door
(5) Mounting hole (6) Side panel (7) Rear door (8) Anchor

D in the figure stands for the cabinet depth, which can be 1100 mm or 1200 mm. Table 7-10 shows the
available cabinet dimensions.

Table 7-10 Dimensions

Dimensions H x W x D (mm) Expansion Method


Standard dimensions 2000 x 600 x 1100 -
Expanded dimensions 2000 x 600 x 1200 Install an enclosure
frame.
2200 x 600 x 1100 Install a top frame.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 79


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Dimensions H x W x D (mm) Expansion Method


2200 x 600 x 1200 Install an enclosure
frame and a top frame.

Figure 7-5 Holes in the smart cooling product

(1) Power cable hole (Φ28 mm) on the top (2) Humidifier water inlet hole (Φ43 mm) on
the top
(3) Signal cable hole (Φ28 mm) on the (4) Refrigerant gas pipe hole (Φ43 mm) on
skylight the top
(5) Refrigerant liquid pipe hole (Φ43 mm) (6) Drainpipe hole (Φ43 mm) on the top
on the top
(7) Signal cable holes (Φ28 mm) on the top (8) Power cable hole (Φ28 mm) at the
bottom
(9) Humidifier water inlet hole (Φ43 mm) (10) Refrigerant gas pipe hole (Φ60 mm) at
at the bottom the bottom
(11) Drainpipe hole (Φ60 mm) at the (12) Refrigerant liquid pipe hole (Φ60 mm)
bottom at the bottom
(13) Signal cable hole (Φ28 mm) at the
bottom

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 80


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

7.3.1.2 Cooling Components


The NetCol5000-A mainly consists of a DC variable-frequency compressor, EC fan,
evaporator, electronic expansion valve (EEV), oil separator, sight glass, filter dryer, air filter,
electric heater (optional), wet film humidifier (optional), condensate pump, check valve,
differential pressure switch, differential pressure sensor (optional), and temperature and
humidity sensor (T/H sensor).

Figure 7-6 Components

(1) Fan (2) Electric heater (3) Condensate pump (4) Drainage check
valve
(5) Strong-current (6) Evaporator (7) Wet film (8) Water inlet
box humidifier solenoid valve
(9) Humidifier (10) Differential (11) Signal cable (12) Compressor
pump pressure switch terminal block driver
(13) Weak-current (14) T/H sensor (15) Discharge pipe (16) EEV
box
(17) Oil separator (18) Sight glass (19) Compressor (20) Filter dryer

 Compressor
− The NetCol5000-A uses a DC variable-frequency compressor that features compact
size, light weight, long service life, low noise, easy installation as well as high
reliability, stability, and energy efficiency.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 81


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

− The high-precision drive automatically adapts to the system pressure fluctuations.


− The drive conducts precision self-check. Compressor and drive faults can be stored
in separate zones.
 EC fan
− The energy-efficient EC fan that supports stepless speed adjustment is used to
reduce the energy efficiency of the fan.
− There are ten EC fans in total. The smart cooling product will not shut down when a
single fan fails.
− Fans can be maintained with power-on. You can replace one faulty fan without
shutting down the smart cooling product.
 Evaporator
− The evaporator adopts the inner threaded copper pipe and blue hydrophilic
aluminum foil to prevent water blowing due to condensate water accumulation and
improve heat exchange performance. The V-type evaporator optimizes the airflow
pattern and reduces the air resistance.
− The finned-tube evaporator with a high cooling efficiency adopts the synergy field
principle and computational fluid dynamics (CFD) to optimize the flow path design,
which greatly improves the heat exchange efficiency.
− The small diameter evaporator is adopted to enhance the heat exchange
performance, a 10%+ increase in heat exchange efficiency compared with a
traditional solution.
− The designed pressure bearing capacity of the heat exchange coil is 1.6 MPa, an
excellent pressure bearing capacity.
 EEV
− The flow regulator uses a miniature controller to control the operation of the step
motor, thereby changing the pass-through area of the valve to regulate the flow of
refrigerant.
− The EEV is equipped with an energy storage unit that prevents slugging due to
migration of refrigerant when the smart cooling product is powered off abnormally.
 Oil separator
It is an oil-gas separator which separates the lubricant brought out due to exhaustion of
the compressor and brings back the separated lubricant to the compressor.
 Sight glass
It allows you to observe the refrigerant flow and gas content for easy maintenance and
optimization.
 Filter dryer
It absorbs water from the refrigerant pipes and filters the foreign matter, which reduces
component damage rates and improves operating efficiency and reliability.
 Air filter
The G4 air filter is used, and the F5 air filter is customizable. The air filter meets the
relevant requirements of the China National Standard GB/T 14295-2008.
 Electric heater
− The positive temperature coefficient (PTC) electric heater automatically adjusts
heating capacity and provides multiple protection measures to ensure secure and
reliable operating.
− The heater features quick start, large heating capacity, and even heating.
 Wet film humidifier

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 82


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

− The wet film humidifier has low water quality requirements and high environment
adaptability.
− The wet film humidifier has a simple structure and is easy to remove, clean, and
maintain.
− The wet film humidifier can quickly start and generate huge humidification
capacity.
− The wet film humidifier consumes less power, saving more than 95% of energy
compared with a traditional electrode humidifier.
− Compared with a traditional electrode humidifier, the wet film humidifier has a
longer service life and maintenance interval.
 Condensate pump
The water pump provides power for top drainage with a maximum lift of 4 m.
 Check valve
The check valve effectively prevents gas or liquid backflow.
 Differential pressure switch
When the air filter is dirty or blocked, the differential pressure switch triggers an alarm,
prompting for air filter replacement.
 Differential pressure sensor
− It adjusts air volume based on the differential pressure to ensure precise air supply.
No excessive adjustment helps save energy and reduce power consumption.
− The air supply volume is also sufficient, which helps eliminate hotspots and
improves reliability.
 T/H sensor
Six built-in negative temperature coefficient (NTC) temperature sensors and one return
air T/H sensor are provided.

7.3.1.3 Controller
7.3.1.3.1 Appearance and Ports

Appearance
The controller provides a 7-inch true color touchscreen and man-machine interfaces for query,
setting, monitoring, and maintenance.
The indicator on the panel displays operating status of the smart cooling product. Figure 7-7
shows the position of the indicator. Table 7-11 describes the mapping between indicators,
buzzers, and alarms. If alarms of different severities (critical, major, minor, or warning) are
raised simultaneously, the indicator status corresponds to the alarm with the highest severity
level and the buzzer status corresponds to the unacknowledged alarm with the highest severity
level.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 83


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Figure 7-7 Display panel

(1) Indicator (2) Display panel

Table 7-11 Indicator and buzzer status description

Alarm Status Indicator Buzzer


The device is operating properly, or a Green No buzzing
warning is generated.
There is an unacknowledged major Yellow Intermittent buzzing
alarm.
There is an unacknowledged critical Red Constant buzzing
alarm.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 84


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Ports

Figure 7-8 Controller side ports

Table 7-12 Ports

No. Name Note


1 MUS05A Reserved
2 FE (fast Ethernet) communications port
3 CAN communications port for the main control board and
LCD
4 RS485_1 Reserved
5 USB Host  After installing the WiFi module, locally connect to
the smart cooling product over the Service Expert
app. Obtain the initial startup password during
deployment. View or obtain the running information
about the smart cooling product during preventive
maintenance. (Applicable to V200R001C20 and later
versions)
NOTE
Only Huawei service engineers or authorized service engineers
are allowed to use the WiFi module. To ensure security, remove
the WiFi module immediately after use.
 Insert the USB flash drive, import and export the
configuration file, export run logs, and upgrade
software.
6 RST restart switch for the display

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 85


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

No. Name Note


7 SD Reserved
8 SW1-4 Dual in-line package (DIP) switch on LCD

7.3.1.3.2 Functions and Features

Functions
 Each smart cooling product has an independent control system, LCD, electric heater,
humidifier, and T/H sensor to ensure its normal operating in high-precision mode.
 The 7-inch display panel with the true-color touchscreen allows you to set parameters for
the smart cooling product and query its status.
 The smart cooling product has the following four remote functions.
− Telemetry: supply air temperature, return air temperature, supply air humidity,
return air humidity, and working status of the smart cooling product
− Teleindication: startup/shutdown states, overvoltage/overcurrent,
undervoltage/undercurrent, return air overtemperature/undertemperature, return air
overhumidity/underhumidity, filter normal/blocked, and fan normal/faulty
− Telecontrol: smart cooling product startup/shutdown
− Teleadjusting: temperature, humidity, and alarm threshold
 When multiple smart cooling products work cooperatively, the controller optimally
distributes the heat load to reduce power consumption and provides backup to improve
reliability.
− When a smart cooling product in the group is faulty, the backup smart cooling
product starts to operate automatically to improve the reliability of the smart
cooling product system.
− Each smart cooling product enters the active mode one by one periodically.
− The number of operating smart cooling products varies depending on the thermal
load in the equipment room to meet requirements promptly, eliminate hot spots, and
save energy.
− A mechanism is adopted to prevent the smart cooling products in the same
equipment room operating in opposite status (such as cooling and heating, or
humidification and dehumidification), in order to save energy.
− Autonomous group networking: If a communication cable in the group control
network is disconnected, two group control network forms, and the group which has
no host smart cooling product can automatically recommend a host and continue the
group networking.
 You can monitor, manage, and upgrade one or more smart cooling products using the
remote management software provided by Huawei.
 1500 historical alarms can be stored.
 Access logs can be traced back. 1000 historical login and setting logs can be stored.
 The controller can display 30 days' temperature and humidity in colored curves and 30
days' differential pressure of supply air and return air (differential pressure control
function required) in colored curves. O&M personnel can view the smart cooling product
operating status onsite.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 86


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

 A comprehensive power monitoring function is provided. Faults such as power reverse


phase, open phase, overvoltage, undervoltage, high frequency, and low frequency are
diagnosed and appropriate alarms are reported and recorded. Automatic protection,
recovery, and restart are also provided.
 The operating status and alarms of the outdoor unit are monitored using the touchscreen
controller on the indoor unit. Audible and visual alarms are supported and alarms can be
uploaded to the upstream element management system (EMS) for centralized
management.
 Alarms about the condensate pump are monitored using the touchscreen controller on the
indoor unit. Audible and visual alarms are supported and alarms can be uploaded to the
upstream EMS for centralized management, which helps locate faults accurately and
improve the drainage reliability.

Features
 The controller provides a touchscreen with a user-friendly interface.
 The controller controls the indoor temperature precisely and responds quickly.
 The controller is protected by a multi-level password protection mechanism, avoiding
misoperations.
 Password verification is required upon the first startup to ensure the system security. No
password verification is required for subsequent startup if the first verification succeeds.
 The controller provides multiple protection functions, such as abnormal power-off
self-recovery and water leakage detection, ensuring system reliability.
 The cooling capacity, air volume, as well as the operating status and time of each
component in the smart cooling product are displayed on the LCD in real time.
 The controller provides abundant external ports such as RS485 ports, CAN ports, FE
ports, and USB ports that are protected by a security mechanism. These ports flexibly
meet the communication requirements and feature good electrical isolation.
 The controller provides multi-language display, such as Chinese, English, French,
Spanish, Russian, and so on.
 O&M personnel can export fault records in one-click mode, making it easy to operate the
smart cooling product and know the running status of the smart cooling product.
 The smart cooling product supports communications protocols such as Modbus RTU,
Modbus TCP, and SNMP, facilitating connection to the network management system.
 The controller intelligently identifies abnormal parameter settings (incorrect commands)
and rejects them automatically.
 If the indoor temperature fluctuates beyond the normal range, an audible and visible
alarm signal is sent automatically.

7.3.2 Physical Ports


Table 7-13 Physical ports

Item Specifications

Indoor unit Refrigerant liquid pipe Outer diameter of 5/8 inch


(15.88 mm), welding
Refrigerant gas pipe Outer diameter of 7/8 inch
(22.22 mm), welding

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 87


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Item Specifications
Humidifier water inlet pipe G 1/2 inch inner screw thread
(humidifier hose is provided for
the smart cooling product)
G 3/4 inch outer screw thread
(humidifier hose is not provided
for the smart cooling product)
Drainpipe BSPP 1/2 inch inner screw
thread
Outdoor unit Refrigerant liquid pipe Outer diameter of 5/8 inch
(15.88 mm), welding
Refrigerant gas pipe Outer diameter of 7/8 inch
(22.22 mm), welding
water cooling module Refrigerant liquid pipe Outer diameter of 5/8 inch
(15.88 mm), welding
Refrigerant gas pipe Outer diameter of 7/8 inch
(22.22 mm), welding
Low-temperature Connecting to indoor unit Outer diameter of 5/8 inch
component (optional liquid pipe (15.88 mm), welding
component)
Connecting to indoor unit Outer diameter of 7/8 inch
gas pipe (22.22 mm), welding
Connecting to outdoor unit Outer diameter of 5/8 inch
liquid pipe (15.88 mm), welding
Connecting to outdoor unit Outer diameter of 7/8 inch
gas pipe (22.22 mm), welding

7.3.3 Product Specifications


Table 7-14, Table 7-15, and Table 7-16 describe the technical specifications of the
NetCol5000-A in-row smart cooling product.

Table 7-14 General specifications

Item Specifications
Refrigerant R410A
Cooling capacitya 42 kW
Air supply mode Horizontal flow
Airflow 8600 m3/h
Dimensions (H x W x D)  2000 mm x 600 mm x 1100 mm (cabinet dimensions)
 2000 mm x 600 mm x 1200 mm (including an enclosure
frame)

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 88


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Item Specifications
 2200 mm x 600 mm x 1100 mm (including a top frame)
 2200 mm x 600 mm x 1200 mm (including an enclosure
frame and a top frame)
Net weight/Gross weight 305 kg/342 kg
(full configuration)
Certification CQC, CE, RoHS, REACH, WEEE, and IEC
a: Test condition is rated condition (Indoor dry-bulb temperature: 37.8°C. Relative
humidity: 20%. Outdoor temperature: 35°C).

Table 7-15 Optional specifications

Item NetCol5000- NetCol5000- NetCol5000- NetCol5000-


A042H412D2 A042H412D2 A042H412D2 A042H412D2
0020E1 0020E2 W120E1 W120E2

Power system 380–415 V AC, 50 Hz or 60 Hz 3Ph+N+PE


Tolerance: –10% to +10% of rated voltage, rated frequency±3 Hz
Power supply mode Single power Dual power Single power Dual power
supply supplies supply supplies
Max Current 40 A Active: 40 A 46 A Active: 46 A
Standby: 40 A Standby: 40 A
Condensate pump Yes Yes Yes Yes
Heating function No No Yes Yes
Humidification No No Yes Yes
function
Reheating capacity N/A N/A 6 kW 6 kW
Humidifying N/A N/A 3 kg/h 3 kg/h
capacity

Table 7-16 Application conditions

Operating Specifications
temperature

Operating temperature 18–45°C


Operating humidity 20%–80% RH
Storage temperature –40°C to +70°C
Storage humidity 5%–95% RH (non-condensing)

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 89


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Operating Specifications
temperature
Applicable outdoor  Work with NetCol500-A036: –20°C to +45°C
temperature  Work with NetCol500-A036 (including a low-temperature
component): –40°C to +45°C
 Work with NetCol500-A072: –5°C to +55°C
Protection level IP20
Installation mode  ESD floor-mounted: pipes and cables routed from the top or
bottom
 Floor: pipes and cables routed from the top
Altitude 0–4000 m. When the altitude exceeds 1000 m, the power
should be derated. For detailed derating data, see Table 7-17.

Table 7-17 Derating coefficients

Altitude 0 1000 1500 2000 2500 3000 3500 4000


(m)
Air volume 1 0.887 0.835 0.785 0.737 0.692 0.649 0.608
coefficient
Cooling 1 0.940 0.909 0.878 0.846 0.815 0.784 0.753
capacity
coefficient
The sensible heat ratio is all 100% in rated condition.

7.4 NetCol500 Outdoor Unit


Table 7-18 Mapping between indoor and outdoor units of smart cooling products

Indoor Unit Outdoor Unit


25 kW smart cooling NetCol500-A032, NetCol500-A036, NetCol500-A026SC11E0,
product NetCol500-A0265S11E0
42 kW smart cooling NetCol500-A036, NetCol500-A072
product

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 90


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

7.4.1 Product Composition


Appearance

Figure 7-9 Appearance

In the following chapters, outdoor unit photos are taken from the NetCol500-A072 as examples and are
for reference only.

Components
The NetCol500 outdoor unit consists of a condenser, electric control box, rack, and fans.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 91


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Figure 7-10 Components

(1) Condenser (2) Electric control box


(3) Rack (4) Fans

7.4.2 Technical Specifications


Figure 7-11 Dimensions of the NetCol500 outdoor unit

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 92


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Table 7-19 Technical specifications of the NetCol500 outdoor unit

Product Model NetCol500 NetCol500 NetCol500 NetCol500- NetCol500- NetCol50


-A026SC11 -A0265S11 -A0325C11 A0365C11E0 A0385C11E 0-A0725C
E0 E0 E0 /NetCol500- 0 11E0
A0365S11E0
Power system 220–240 V 380–480 V AC, 3 Ph/N/PEa, 50/60 Hz (If a low-temperature component is
AC, installed, the power system is 380–415 V AC, 3 Ph/N/PE, 50/60 Hz.)
L/N/PE, 50
Hz
Voltage tolerance Rated voltage ±10%b
Frequency Rated frequency ±3 Hz
tolerance
Maximum outdoor 3.3 2.5 2.5 2.5 2.5 4.5
unit current (A)
Air volume of fans 8000 12000 12000 12000 12000 26000
(m3/h)
Number of fans 1 1 1 1 1 2
Liquid pipe outer 5/8 inch 5/8 inch 5/8 inch 5/8 inch 5/8 inch 5/8 inch
diameter (15.88 mm) (15.88 mm) (15.88 mm) (15.88 mm) (15.88 mm) (15.88 mm)
Gas pipe outer 3/4 inch 3/4 inch 7/8 inch 7/8 inch 7/8 inch 7/8 inch
diameter (19.05 mm) (19.05 mm) (22.22 mm) (22.22 mm) (22.22 mm) (22.22 mm)
Dimensions H1 x 890 x 1110 920 x 1120 1160 x 1370 1160 x 1370 1160 x 1370 1100 x
W1 (W2) x D (985) x (985) x (1220) x (1220) x 1094 (1220) x 2200
(mm) 1094 1094 1094 1094 (2050) x
1094
Dimensions H2 x 590 x 1110 620 x 1120 714 x 1370 714 x 1370 714 x 1370 654 x 2200
W1 (W2) x D (985) x (985) x (1220) x (1220) x 1094 (1220) x (2050) x
(mm) 1094 1094 1094 1094 1094

Net weight (kg) 91 132 110 130/147 130 185


Certification RoHS, REACH, CE/CBc
Operating Depends on the indoor unit. For details, see the product overview in the indoor unit user
temperature manual.
Storage –40 to +70
temperature (°C)
Storage humidity 5%–95% RH (non-condensing)
Altitude 0–1000 m: normal use; above 1000 m: derating. For derating details, see the product
overview in the indoor unit user manual.
a: The neutral wire is not required when the NetCol500-A0265S11E0 works with the NetCol5000-A021H (208
V).
b: If the upstream voltage may fluctuate outside the voltage tolerance, install a voltage stabilizer; otherwise, the
smart cooling product may fail to run properly due to frequent alarms.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 93


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Product Model NetCol500 NetCol500 NetCol500 NetCol500- NetCol500- NetCol50


-A026SC11 -A0265S11 -A0325C11 A0365C11E0 A0385C11E 0-A0725C
E0 E0 E0 /NetCol500- 0 11E0
A0365S11E0
c: CE certification is required if the NetCol500-A026SC11E0 works with the NetCol5000-A025 (300 mm
wide). CB certification is required if it works with the NetCol5000-A021H (208 V). CE certification is required
for the other models.

Outdoor unit installation environments are classified as follows based on the harshness:
 Class A (controlled environment): indoor environments where the ambient temperature and humidity
are controlled, including rooms where people live
 Class B (uncontrollable environment): indoor environments where the ambient temperature and
humidity are not controlled or general outdoor environments with simple shielding measures where
the humidity sometimes reaches 100%
 Class C (harsh environment): marine environments within 3.7 km from the coast or outdoor land
environments with simple shielding measures within 1.2 km from a pollution source
 Class D (marine environment): environments within 500 m from the coast
The NetCol500-A0365S11E0 and NetCol500-A0265S11E0 outdoor units must not be installed in class
D environments, and other outdoor units must not be installed in class C or class D environments.

7.4.3 (Optional) Low-Temperature Component


Working Principle
When the outdoor temperature is below the operating temperature lower limit specified for the
product, the condensing pressure of the system for the outdoor unit condenser with natural
cooling may still stay below the safe operating pressure of the compressor. A low-temperature
component is required to address this issue.
The low-temperature component intelligently controls the condensing pressure to ensure that
the equipment can work safely and reliably at an outdoor ambient temperature as low as
–40ºC. When detecting that the outdoor condensing pressure is low, the pressure stabilizing
valve automatically opens to bypass hot gas to the liquid storage tank of the low-temperature
component, thereby ensuring that the condensing pressure stays within the range for safe and
reliable operation. When detecting that the condensing pressure exceeds the threshold, the
pressure stabilizing valve automatically closes the bypass.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 94


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Figure 7-12 Low-temperature component

(1) Safety valve (2) Connecting to indoor (3) Connecting to outdoor


unit liquid pipe unit liquid pipe
(4) Condensing pressure (5) Connecting to outdoor (6) Connecting to indoor unit
control valve unit gas pipe gas pipe

A low-temperature component is mandatory when the outdoor ambient temperature may drop
to –20ºC.

Table 7-20 Low-temperature component specifications

Item Specifications
Heater power supply 220–240 V AC, 1 Ph, 50 Hz or 60 Hz
Heater power supply voltage tolerance Rated voltage ±10%
Heater power supply frequency Rated frequency ±3 Hz
tolerance
Refrigerant R410A
Liquid pipe outer diameter 5/8 inch (15.88 mm)
Gas pipe outer diameter 7/8 inch (22.22 mm)
HxWxD 632 mm x 944 mm x 507 mm (with package)
470 mm x 828 mm x 300 mm (without package)

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 95


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Item Specifications
Expansion bolt hole M12x60
Storage temperature –40°C to +70°C
Storage humidity 5%–95% RH (non-condensing)
Maximum operating pressure 4.35 MPa

7.4.4 (Optional) Sunshade


When an outdoor unit is used in the T3 working condition (–5°C to +55°C), install a sunshade
if the following three conditions are met.
 The outdoor unit is installed horizontally.
 The ambient temperature exceeds 50°C.
 The outdoor unit is directly exposed to sunlight.

If the previous three conditions are met but no sunshade is installed, the smart cooling product
will shut down because the components are applied beyond specifications.

Figure 7-13 Sunshade appearance

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 96


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Figure 7-14 Sunshade dimensions (unit: mm)

Sunshades do not apply to the NetCol500-A026.

7.5 (Optional) Dehumidifier


If in-row air cooled smart cooling products are used in a smart module where the actual load
ratio is less than 10% of the smart cooling product cooling capacity, it is recommended that
one dehumidifier be installed for each module in the aisle containment at the bottom of a
server cabinet near smart cooling products.

Figure 7-15 Dehumidifier installation position

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 97


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Figure 7-16 Dehumidifier

(1) Mounting ear (2) Air filter (3) Control panel


(4) Castor (5) Water outlet (6) Handle
(A) Air intake vent (B) Air exhaust vent

Table 7-21 Dehumidifier specifications

Item Specifications
Dimensions (H x W x D) 598 mm (14 U) x 491 mm x 410 mm
Weight 30 kg
Power system 220–240 V 50 Hz
Rated input current 5.9 A
Rated input power 1250 W
Dehumidification capacity 45 L/day

7.6 Smart Cooling Product Controller


The controller for the NetCol5000–A in-row precision smart cooling product comprises an
LCD and main control board.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 98


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Appearance
The 7-inch true color-sensitive LCD offers a user-friendly interface for you to perform query,
settings, monitoring, and maintenance.

Figure 7-17 Appearance

(1) Indicator (2) Display panel

Functions
 Single unit control: When only one unit is running, the controller provides logic control
over components in the unit to meet the indoor temperature and humidity requirements.
 Display and operations: The 7-inch touchscreen of the controller allows you to set
parameters for the device and query the device status.
 Teamwork control: When multiple units work cooperatively, the controller optimally
distributes the heat load to reduce power consumption and provides backup to improve
reliability.
 Remote management: You can monitor, manage, and upgrade one or more units using
the remote management software provided by Huawei.

Benefits
 The controller provides a touchscreen with a user-friendly interface.
 The controller is highly precise and responsive.
 The three-level password protection mechanism prevents misoperations.
 The controller protects the smart cooling product from overvoltage, undervoltage,
abnormal power failures, and water leaks, ensuring system reliability.
 The touchscreen of the controller displays the operating status and time of the
temperature control components in real time.
 The controller provides a professional fault diagnosis system which automatically
displays fault information, facilitating maintenance.
 The controller provides various external ports such as RS485 ports, FE ports, and USB
ports that are protected by a security mechanism.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 99


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

7.7 L1/L2 Linkage (iCooling Function)


Features
 Energy saving: When the requirements of cooling capacity are determined, an optimal
operation mode for multiple smart cooling products can be adopted to minimize the total
cooling power consumption.
 Rapid elimination of hot spots: The power of equipment can be detected to accelerate the
response of smart cooling products and by using the air inlet temperature, the partial hot
spots that may exist in the smart module can be eliminated.
 Reliable operation: According to the load power, the number of operating smart cooling
products is minimized to avoid frequent startup and shutdown of smart cooling products
as well as temperature field fluctuation.

Linkage Logic
1. Collect information about layouts, temperature and humidity, and power of all devices in
the smart module.
2. Correlate cabinets with smart cooling products in terms of airflow organization based on
the smart module layout.
3. Calculate heat dissipation of all devices in the smart module by using the equipment
power, after which the basic requirements of the cooling capacity can be determined.
Then roughly adjust the operating status of the smart cooling products (determine the
number of operating smart cooling products and initial rotational speed of the
compressors).
4. To meet temperature requirements for the smart module, slightly adjust the operating
status of smart cooling products according to the deviation of cooling requirements
calculated by using the data of temperature distribution in the smart module.
5. When distributing cooling requirements for each smart cooling product, minimize the
power consumption of the cooling system in the smart module with the help of energy
efficiency features of smart cooling products.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 100


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

8 Facility Management System

Table 8-1 Management system configurations

Function ECC800 Web ECC800 App NetEco


Work order management No No Yes
Energy efficiency No No Yes
management
PUE statistics Yes Yes Yes
Capacity management No No Yes
Generating alarms for Yes No Yes
SNMP northbound
equipment
Monitoring data for Yes No Yes
SNMP northbound
equipment
Mobile app O&M Yes Yes Yes
Monitoring data/alarms Yes Yes Yes
for power supply and
distribution equipment
Monitoring data/alarms Yes Yes Yes
for cooling equipment
Monitoring data/alarms Yes Yes Yes
for environment
equipment
Monitoring data/alarms No No Yes
for fire extinguishing
equipment
Access control Yes Yes Yes
management
Intelligent lighting Yes Yes Yes

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 101


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Function ECC800 Web ECC800 App NetEco


View presetting Yes Yes No (manually drag)
Alarm notification by Yes No Optional
SMS or email
Battery monitoring Optional Optional Optional
Log recording Yes Yes Yes
Management range A single smart A single smart Multiple smart
module module modules
Configuration principle Mandatory Optional Optional

Figure 8-2 System network diagram

 In the figure, RF_Z indicates wireless networking. RF_Z(1) devices can communicate with the
ECC800 in wireless mode. The RF_Z(2) BIM and CIM communicate with each other in wireless
mode. RF_Z(1) and RF_Z(2) devices use different protocols and are isolated from each other.
 Wireless communication is automatically established after the access actuator, skylight actuator, and
multi-functional sensor successfully connect to and communicate with the ECC800 through PoE.

8.1 NetEco6000 Intelligent Data Center Management


System
With a flexible structure and modular design, the NetEco can manage infrastructure of a
single smart module or multiple smart modules in different areas in a centralized manner.
The FusionModule2000 provides WiFi and RF_Z wireless networking functions. The mobile
app can be connected by wireless networking. Certain southbound components (such as the

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 102


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

skylight actuator, AC actuator, multi-functional sensor, and access actuator) can be connected
by RF_Z wireless networking.
The management system provides a GUI to implement comprehensive management functions
based on requirements. The system can monitor the following equipment:
 Power equipment, including precision smart cooling products, integrated PDCs, UPSs,
and ATSs
 Environment monitoring equipment, including multi-functional sensors, and water
sensors, and so on.
 Video equipment, including cameras and network video recorders VCN500
 Access control equipment: A standard access management system is integrated to
manage and monitor key information such as door status, card swiping, and permission
setting.
 Standard network management interface: The NetEco provides SNMP interfaces to
communicate with third-party NMSs. The system can be customized to support other
protocols for the access from different devices.

8.2 ECC800 Core Controller


The ECC800 is the core component for local management. It is intelligent, flexible to deploy,
easy to maintain, and reliable. It adopts the PoE bus for expansion, and allows all intelligent
monitoring devices to be flexibly laid out so that it can manage the devices.

Figure 8-3 ECC800 (front view)

(1) PSU (optional) (2) PSU (optional) (3) Status (4) 3G/4G
indicator antenna port
(5) FE ports (WAN_1–WAN_2 (6) AI/DI_1–6 sensor (7) RF_Z (8) SW
and LAN_1–LAN_2) input ports antenna port button
(9) DO_1–2 dry contact outputs (10) RS485 port (11) Default (12) USB
(COM1–4/12 V) button port
(13) ECC800 main control
module

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 103


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Figure 8-4 ECC800 controller (rear view)

(1) 53.5V DC_OUT1 (2) 53.5V DC_OUT2 (3) AC_INPUT1


(4) AC_INPUT2

Figure 8-5 ECC800 main control module (side view)

(1) SIM card slot (2) Micro-SD card slot

ECC800 Specifications

Table 8-2 ECC800 environmental specifications

Item Specifications
Operating temperature –20°C to +50°C
Storage temperature –40°C to +70°C
Humidity 5%–95% RH (non-condensing)
Altitude 0-4000 m (When the altitude is between 3000 m and 4000 m,
the temperature decreases by 1°C for each additional 200 m.)

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 104


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Table 8-3 ECC800 structural specifications

Item Specifications
Dimensions (H x W x D) 43.6 mm x 442 mm x 330 mm
Color Black
Installation requirements  Installed in a standard 1 U cabinet
 Installed in a 19-inch rack
Environmental protection requirements RoHS5

Table 8-4 ECC800 technical specifications

Item Specifications
Power input  Two AC inputs
 Rated operating voltage: 200–240 V AC or 100–120 V AC
 Rated operating frequency: 50/60 Hz
Power output  Output voltage: 42–58 V DC (rated voltage: 53.5 V DC)
 Output power of two power supplies: 2000 W (176–300 V AC);
940 W (linear derating at 85-175 V AC)
 Output power of a single power supply: 1000 W (176–300 V
AC); 470 W (linear derating at 85–175 V AC)
FE port expansion Supports two WAN ports and two LAN ports with the 10/100M
communications rate.
RS485 serial port  Four RS485 ports with the default communications rate of 9600
expansion bit/s
 Each port provides 12 V DC power with the rated current of 450
mA.
AI/DI expansion  Supports six AI/DI ports to connect to sensors such as smoke,
(RJ45) water, and temperature sensors.
 Each port provides 12 V DC power with the rated current of 85
mA.
DO expansion Two DO ports both supporting active and passive DO
(RJ45)  Supports passive (dry contact) DO port with contact point
capacity of 20 W, maximum withstand voltage of 60 V DC, and
rated current of 500 mA.
 Supports the active DO port with an output voltage of 12 V DC
and output current of 450 mA.
Wireless Wireless communication that complies with IEEE802.15.4
communication
3G (optional) Supports 3G (WCDMA) communication and is compatible with 2G
(GSM) communication. A standard SIM card slot is provided.
NOTE
The prerequisite for using a SIM card is that the site has signal coverage.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 105


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Item Specifications
USB  After installing the WiFi module, connect the WiFi module to
the ECC800 using the app on the mobile phone or tablet
computer to view the basic information about the smart module,
such as layout, resources, energy efficiency, environment, and
alarms.
 Insert a USB flash drive to export historical data, device data,
fault information, and configuration files, and import or export
the device configuration data and historical data.
Button  SW: wireless network pairing button
 Default: button for restoring the default IP address

8.3 (Optional) Tecal RH2288 V2 Server


The Tecal RH2288 V2 rack server (RH2288 V2 for short) of Huawei features large capacity
and high performance. It serves as the monitoring host of the NetEco and is responsible for
data processing and analysis.
The server is a standard 2 U rack server, and supports standard rack mounting.

Figure 8-6 RH2288 V2 server

The RH2288 V2 server has the following features:


 The server has powerful computing, storage, and expansion capabilities.
 The server can be flexibly configured with value-added components to provide diverse
functions.

Table 8-5 RH2288 V2 server specifications

Item Specifications
Equipment 2 U, H x W x D: 87.5 mm x 447 mm x 740 mm
Can be installed in a standard cabinet that is 19 inches
wide and 1000 mm deep or deeper
Main board Central One or two
processing unit
(CPU)

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 106


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Item Specifications
CPU model Intel®Xeon® E5-2600 (Romely-EP) series 4C/6C/8C
processor; maximum configuration: 135 W processor of
3.3 GHz dominant frequency and the L3 cache of 20 MB
for a CPU
Memory 24 DIMMs slots, supports RDIMM/LRDIMM memory of
DDR3, a maximum of 768 GB
Hard drive Supports eight 2.5-inch 6 Gbit/s hot-swappable
SAS/SATA/SSD hard drives, or twelve 3.5-inch 6 Gbit/s
hot-swappable SAS/SATA hard drives and two 2.5-inch
built-in 6 Gbit/s hot-swappable SAS/SATA/SSD hard
drives.
Expansion Supports six expansion slots for PCIe 3.0 cards: one slot
for PCIe3.0 x 16, four slots for PCIe3.0 x 8, and one
dedicated slot for RAID.

8.4 (Optional) LAN Switch


Figure 8-7 S5320 LAN switch

Table 8-6 S5320 LAN switch specifications

Item Specifications
External dimensions (H x W x D) 44.4 mm x 442 mm x 420 mm
Maximum power (full configuration) 913 W (power consumption: 173 W; PoE:
740 W)
Weight ≤ 8 kg
DC input voltage Rated voltage: –48 V DC to –60 V DC
Voltage range: –36 V DC to –72 V DC
AC input voltage Rated voltage: 100–240 V AC
Voltage range: 90–264 V AC
Temperature  Operating temperature: 0°C to +50°C
NOTE
When the altitude ranges from 1800 m to 5000
m, the highest temperature decreases by 1°C for
each additional 220 m.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 107


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Item Specifications
 Storage temperature: –40°C to +70°C
Humidity 5%–95% RH (non-condensing)
Altitude  Non-PoE device:
− With DC power: 0–2000 m
− With AC power: 0–5000 m
 PoE device: 0–5000 m

8.5 Pad
The pad, a control panel, allows wireless access to the data center facility management system.
You can monitor the equipment in the data center and environmental parameters in real time
over the app.

Figure 8-8 Pad

The pad provides a capacitive multi-touch screen.


Huawei pad screen size is 8–12 inches. The pad uses Android 4.0 or later, and has a memory
of 2 GB or more.

If a non-standard pad is selected, confirm with Huawei engineers.

8.6 Skylight Actuator


The skylight actuator controls the rotating skylights on the aisle containment through the
alarm linkage information from the equipment room fire extinguishing system or the control
information from the upper host. The skylight actuator supports E-labels and wireless
networking (802.15.4).

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 108


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Figure 8-9 Skylight actuator

(1) LOCK/GND (2) BUTTON/GND (3) AI/DI_1 sensor (4) AI/DI_2 sensor
magnetic lock DO window open button DI input port input port
output port input port
(5) BLINK button (6) Status indicator (7) Address DIP (8) COM1 RS485
switch port
(9) COM2 RS485 (10) PoE port (11) 48 V power
port port

Specifications

Table 8-7 Skylight actuator technical specifications

Item Specifications
Power input  DC input: Terminal, with input voltage of 36–60 V DC
 PoE input: One PoE port that complies with IEEE802.3at.
PoE port FE communication with the rate of 10/100M
Wireless One wireless port that complies with IEEE802.15.4, mutual backup
communication with FE communication
AI/DI port Two AI/DI ports for detecting equipment room fire extinguishing
linkage signals; smoke detection signals also supported
DO output One 12 V DC power output for controlling the skylight magnetic
lock; driving six skylight magnetic locks simultaneously

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 109


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Item Specifications
DI input One DI input port for connecting to the skylight open button
BLINK button  Press the button for less than 1s to start blinking.
 Hold down the button for 1–5s to search for a network and start
networking.
 Hold down the button for more than 6s to clear network
parameters.
Address DIP 4-pin address DIP switch
switch
E-label Supported

8.7 Data Collection System


8.7.1 (Optional) Rack environment unit
The rack environment unit collects and controls the environmental data of IT cabinets.

Figure 8-10 Rack environment unit

(1) Ground port (2) 48 V DC power (3) PoE port (4) COM1/12V port
input port
(5) COM2/12V port (6) COM3 port (7) COM4 port (8) NTC1–3 ports
(9) NTC4–6 ports (10) AI/DI_1 port (11) AI/DI_2 port (12) 12V_1 port
(13) 12V_2 port (14) BLINK button (15) Status indicator

Specifications

Table 8-8 Technical specifications of the rack environment unit

Item Specifications
Power input  DC input: Phoenix terminal, with an input voltage range of

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 110


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Item Specifications
36–60 V DC
 PoE input: One PoE port that complies with IEEE802.3at.
12 V power output Two 12 V DC power outputs with the rated output current of 250
mA
FE port FE communication with the rate of 10/100M
RS485 serial port  Four RS485 ports with the default communications rate of
expansion 9600 bit/s
 Among the four RS485 ports, two support 12 V DC power
output with the rated current of 400 mA.
 The other two are isolated, with the default communications
rate of 9600 bit/s, and do not support power output.
AI/DI input Two active 12 V DC, 200 mA (rated) AI/DI input ports
Temperature sensor Provides two RJ45 ports to connect to six temperature sensors,
port each RJ45 port connecting to three temperature sensors.
BLINK button Supports the blinking function.

8.7.2 Smart ETH Gateway


A smart ETH gateway allows the extension of the 53.5 V DC power supply and FE
communication for the ECC800 and can be flexibly deployed in a smart module.

Figure 8-11 Smart ETH gateway

(1) PWR_IN (2) FE_1 cascading (3) POE_1–2 (4) POE_3–4 ports
cascading power port signal port ports
(5) 48V_OUT1 (6) 48V_OUT2 (7) FE_2 (8) PWR_OUT
power output port power output port cascading signal cascading power port
port
(9) BLINK button (10) Status indicator

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 111


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Specifications

Table 8-9 Technical specifications for a smart ETH gateway

Item Specifications
Power input PWR_IN D-type power input terminal, for power cascading, input voltage
range: 45–55 V DC
Power of a single smart ETH gateway: max (2.7 A , 48 V DC); power of
cascaded smart ETH gateways: max (25 A, 48 V DC)
Power output  PWR_OUT D-type power output terminal, for power cascading, output
voltage range: 45–55 V DC
 48V_OUT1 and 48V_OUT2, terminal (1 A,48 V DC), output voltage
range: 45–55 V DC
FE port Two FE ports, RJ45 terminal with an indicator, 10/100M communication
rate, for the cascading between smart ETH gateways and the
communication with the upper computer
POE port Four POE ports, RJ45 terminal with an indicator, 10/100M
communications rate, complying with IEEE802.3, IEEE802.3u,
IEEE802.3af/at
BLINK If you press the BLINK button, the RUN indicator blinks intermittently at
button super short intervals (blinking at super short intervals for 0.5s and then off
for 0.5s) for 5 seconds.

Indicators

Table 8-10 Indicators on a smart ETH gateway

Indicator Color Name Status Description


PWR Green Power input Steady on The power input is normal.
status
indicator Off There is no power input.

RUN Green Module Off The power supply is


running abnormal.
status
indicator Blinking at The smart ETH gateway
long intervals successfully registers with
the ECC800 and the software
runs properly (the indicator
blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at The smart ETH gateway
short intervals does not register with the
ECC800 (the indicator blinks
at 4 Hz, on for 0.125s and
then off for 0.125s).

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 112


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Indicator Color Name Status Description


Blinking The indicator blinks at super
short intervals for 0.5s
(blinking at 10 Hz, on for
0.05s and then off for 0.05s)
and then turns off for 0.5s.
The cycle lasts for 10s.
ALM Red Alarm Steady on A system failure alarm is
indicator generated.
Off No system alarm is
generated.

8.7.3 WiFi Converter


The WiFi converter converts PoE signals into WiFi signals for communicating with devices
such as the pad and mobile phone.

Figure 8-12 WiFi converter

(1) RF_1 antenna port (2) RF_2 antenna port (3) Reset button (4) WPS button
(5) Status indicator (6) 48 V power port (7) PoE port

Specifications

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 113


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Table 8-11 WiFi converter technical specifications

Item Specifications
Power input  DC input: Phoenix terminal, with an input voltage range of 36–60 V
DC
 PoE power supply: One PoE port, complying with IEEE802.3at,
25.5 W
WiFi function  2.4 GHz frequency, two antennas, supporting eight STA
connections, 50 m WiFi coverage (no blockage)
 Supports the WPS button.
Reset button Press and hold down the button for more than 5s to restore the factory
settings of the WiFi converter.
WPS button Support fast WiFi access by WPS.

WPS function: When the WiFi is enabled, if you choose Advanced settings > WPS connection on the
WLAN of the intelligent device (such as a mobile phone and pad) and press the WPS button on the WiFi
converter at the same time, the intelligent device will quickly connect to the WiFi hotspot of the device.

8.8 Video Surveillance System


The video surveillance subsystem consists of the cameras and VCN (a network video recorder)
and implements real-time monitoring, video storage, and video playback.

8.8.1 IP Camera
The IPC6325-WD-VR IP camera (IPC6325 camera for short) is a two-megapixel wide
dynamic infrared zoom dome camera that can be wall-mounted or ceiling-mounted.
The camera monitors the module interior in real time, records videos, and implements 7x24h
storage.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 114


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Figure 8-13 IPC6325 camera

Table 8-12 IPC6325 camera technical specifications

Item Specifications

Image sensor 1/2.7" two-megapixel progressive scan CMOS


Lowest illuminance  Color: 0.01 lux (F1.4, AGC ON)
 Black and white: 0.004 lux (F1.4, AGC ON)
0 lux (infrared enabled)
Wide dynamic range 120 dB
Focal length 2.8–12 mm manual zoom, 4.3x optical zoom
Video coding format H.265/H.264/MJPEG
Maximum resolution 1920x1080
Power supply PoE (802.3at/af), 24 V AC±25%, 24 V DC±25%, 12 V
DC±25% (polarity-insensitive DC power supply),
applicable to DC/AC adapter and PoE hot backup
Protection level IP66; complying with IEC 60529
Vandal-proof class IK10; complying with IEC 62262

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 115


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

8.8.2 VCN500
Figure 8-14 VCN500

Table 8-13 VCN500 performance specifications

Item Specifications
Video input A VCN500 supports the access from a maximum of 32 cameras and
the maximum access bandwidth of 160 Mbit/s.
Video transfer A VCN500 supports the video transfer from 32 cameras or of 160
Mbit/s.
Storage A VCN500 supports the storage access from a maximum of 32
cameras and the maximum storage access bandwidth of 160 Mbit/s.
Video playback and A VCN500 supports video playback and download of 32 cameras
download or 160 Mbit/s.

Table 8-14 VCN500 hardware specifications

Item Specifications
Hard drive slot Twelve 3.5-inch hard drive slots
Hard drive type and Twelve 4 TB SATA hard drives
quantity NOTE
The VCN500 supports hard drives at enterprise and monitoring
levels.

RAID control card The VCN500 does not have a RAID control card on its
mainboard.
CPU type and quantity 1 x 1 GHz, maximum 10 MB cache
Memory capacity 2 GB
I/O port Two service network ports, with RJ45 connectors and
LNK/ACT indicators
Power parameters Single power supply only
Maximum PSU power: 250 W
AC power input voltage range: 100–240 V AC

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 116


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Item Specifications
AC power frequency range: 50–60 Hz
Weight (full configuration) ≤ 20 kg
Typical power 40 W
consumption (excluding
hard drives)
Maximum power 70 W
consumption (excluding
hard drives)
Typical power 170 W
consumption (including
monitoring-level hard
drives)
Maximum power 215 W
consumption (including
monitoring-level hard
drives)
Typical power 200 W
consumption (including
enterprise-level hard
drives)
Maximum power 250 W
consumption (including
enterprise-level hard
drives)
Dimensions (H x W x D) 86.1 mm x 447.0 mm x 470.0 mm

8.9 Access Control System


8.9.1 Access Actuator
The access actuator is the control component for the aisle door in a smart module. It connects
to the ECC800 controller over FE port, wireless networking (802.15.4). It opens the magnetic
lock by detecting the card swiping information of the card reader, door open button
information, and fire linkage information. It has access right management, access event record,
and alarm record functions.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 117


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Figure 8-15 Access actuator

(1) 48 V power port (2) POE port (3) RS485 port COM2
(4) RS485 port COM1 (5) Address DIP switch (6) Status indicator
(7) BLINK button (8) WG_2 Wiegand (9) WG_1 Wiegand interface
interface
(10) AI/DI_2 dry (11) AI/DI_1 dry (12) LOCK/GND/GATE/COM door
contact (Reserved port contact (Reserved port status or magnetic lock port
for linkage control or for exit button)
third-party fire
extinguishing system
dry contacts)

Specifications

Table 8-15 Access actuator technical specifications

Item Specifications

Power input  DC input: Terminal, with input voltage of 36–60 V DC


 POE input: One POE port that complies with IEEE802.3at.
POE port FE communication, 10/100M communications rate
Wireless One wireless communication port that complies with
communication IEEE802.15.4, mutual backup with FE communication

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 118


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Item Specifications
AI/DI port Two AI/DI ports, can connect to the fire alarm and exit button
DO/DI port  One 12 V DC power output that controls magnetic locks,
terminal
 One DI input port for connecting to the door status switch
RS485 serial port Two RS485 ports (one route) with the default communications rate
expansion of 9600 bit/s, physical port cascading supported (reserved function)
Wiegand interface Two Wiegand interfaces, 12 V DC card reader operating power
output; two routes of card readers (non-fingerprint readers) can
operate at the same time.
BLINK button  Press the button for less than 1 second to start blinking.
 Hold down the button for 1–5 seconds to search for a network
and start networking.
 Hold down the button for more than 10 seconds to clear
network parameters.
Address DIP switch 4-pin address DIP switch
E-label Supported

Indicators

Table 8-16 Access actuator indicator description

Indicator Color Name Status


PWR Green Power input status  Steady on: The power input is
indicator normal.
 Off: There is no power input.
RUN Green Communication  Off: The power is abnormal or the
status indicator board program is loading.
 Blinking at long intervals: The access
actuator successfully registers with
the ECC800 and the software runs
properly (the indicator blinks at 0.5
Hz, on for 1s and then off for 1s).
 Blinking at short intervals: The
communication is disconnected or the
access actuator fails to register with
the ECC800 (the indicator blinks at 4
Hz, on for 0.125s and then off for
0.125s).
 Blinking: The indicator blinks at
super short intervals for 0.5s
(blinking at 10 Hz, on for 0.05s and
then off for 0.05s) and then turns off
for 0.5s. The cycle lasts for 10s.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 119


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Indicator Color Name Status


ALM Red Alarm indicator  Steady on: A system failure alarm is
generated.
 Off: No system alarm is generated.
RF_Z Green Wireless  Steady on: No network parameters
communication exist, or a network is to be created.
status indicator  Blinking at long intervals: A network
is set up, and no node access is
allowed (the indicator blinks at 0.5
Hz, on for 1s and then off for 1s).
 Blinking at super short intervals: A
network is set up, and node access is
allowed (the indicator blinks at 10
Hz, on for 0.05s and then off for
0.05s).
 Blinking intermittently at super short
intervals: The access actuator is
searching for a network (the indicator
blinks at super short intervals for 0.5s
and then turns off for 0.5s).

Communications Ports
The access actuator provides one DO port (LOCK/GND) and one DI port (GATE/COM).
Table 8-17 lists the LOCK/GND/GATE/COM port pin definitions.

Table 8-17 LOCK/GND/GATE/COM port pin definitions

Item Description
LOCK/GND (control magnetic locks) pin sequence LOCK 12V_OUT
GND GND
GATE/COM (door status) pin sequence GATE DI1
COM COM

8.9.2 (Optional) Aisle Access Control System


The aisle access control system is used in an aisle containment. It monitors and collects data
for devices and personnel moving into or out of the aisle containment. Diverse access control
devices such as the fingerprint and card reader with a keypad, fingerprint and card reader, and
card reader with a keypad are supported.
 The access control system applies to the equipment room, aisle containment, and cabinet
doors.
 The access control system consists of an access actuator, fingerprint reader with a
keypad, magnetic lock, and exit button.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 120


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

 The access control system is configured with an emergency button that can disconnect
the power supply to the magnetic lock to open the door.

Fingerprint and Card Reader with a Keypad

Figure 8-16 Fingerprint and card reader with a keypad

Table 8-18 Specifications of the fingerprint and card reader with a keypad

Item Specifications

Dimensions (L x W x H) 156 mm x 53 mm x 38 mm
Rated operating voltage 12V DC±15%
Rated operating current 300mA±15%
Card type supported IC card
Authorized storage A maximum of 3000 authorized users, with a maximum of
6000 fingerprints
Communications mode RS485 and Wiegand communications ports
Working status  Standby: The blue indicator is on, and the green
indicator for the fingerprint reader is steady on.
 Fingerprint collection: The red indicator for the
fingerprint reader is on.
 Unauthorized fingerprint collection: The buzzer sounds
twice, and the red and blue indicators blink twice.
 Authorized fingerprint collection: The buzzer sounds
once, and the red and blue indicators blink once.
 Card swiping: The buzzer sounds once, and the red and
blue indicators blink once.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 121


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Fingerprint and Card Reader

Figure 8-17 Fingerprint and card reader

Table 8-19 Specifications of the fingerprint and card reader

Item Specifications
Dimensions (L x W x H) 156 mm x 53 mm x 38 mm
Operating voltage Rated voltage: 12 V DC ±5%
Operating current Rated current: 300 mA ±5%
Card type supported IC card
Authorized storage A maximum of 3000 authorized users, with a maximum
of 6000 fingerprints
Communications mode RS485 and Wiegand communications ports
Working status  Standby: The blue indicator is on, and the green
indicator for the fingerprint reader is steady on.
 Fingerprint collection: The red indicator for the
fingerprint reader is on.
 Unauthorized fingerprint collection: The buzzer
sounds twice, and the red and blue indicators blink
twice.
 Authorized fingerprint collection: The buzzer sounds
once, and the red and blue indicators blink once.
 Card swiping: The buzzer sounds once, and the red
and blue indicators blink once.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 122


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Card Reader with a Keypad

Figure 8-18 Card reader with a keypad

Table 8-20 Specifications of the card reader with a keypad

Item Specifications

Dimensions (L x W x H) 114 mm x 63 mm x 25 mm
Operating voltage Operating voltage range: 10.8–13.2 V DC; rated voltage:
12 V DC
Operating current Static standby current 80 mA, dynamic operating current
(card swiping, key pressing) 150 mA, minimum input
current 12 V DC/300 mA
Communications mode Wiegand communications port

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 123


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Magnetic Lock

Figure 8-19 Double door magnetic lock

Figure 8-20 Single door magnetic lock

Figure 8-21 Magnetic lock for a sliding door

8.9.3 (Optional) Cabinet Access Control System


The cabinet door access control system applies to cabinets in the aisle containment to ensure
data and device security.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 124


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Cabinet Electronic Lock

Figure 8-22 Cabinet electronic lock

Table 8-21 Cabinet electronic lock specifications

Item Specifications
Rated input voltage 12V DC
Rated current 200–300 mA
Unlock mode Power on to unlock
Card type supported IC card
Mechanically unlock Supported

Features:
 An IC card can be used after being authorized using software.
 An IC card can be authorized for one lock or all locks.
 Door opening information is recorded through a network.
 The system displays the status of cabinet doors and locks in real time, and generates
alarms for unauthorized door opening.
 The system supports remote door opening.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 125


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

(Optional) Mechanical Code Lock

Figure 8-23 Cabinet code lock

Functions and features


 The cabinet door can be opened with only the key and without the password.
 The cabinet door can be opened with only the password and without the key.
 The user can set a password.
 A password should only contain three digits.
 If a user forgot the password, he can reset it.

8.10 Environment Monitoring System


8.10.1 WLDS900 Water Sensor
The WLDS900 water sensor with the BOM number of 33010352 consists of a water detection
cable, a water detector, and a conversion cable.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 126


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Figure 8-24 WLDS900 water sensor

(1) Water detector (2) Conversion cable end A, connected (3) Conversion cable
to the water detector
(4) Conversion cable (5) Water detection cable end A, (6) Water detection
end B, connected to connected to the conversion cable cable
the water detection
cable

Table 8-22 WLDS900 water sensor specifications

Item Specification
Operating voltage 12 V DC (9–16 V DC)
Operating temperature –20°C to +70°C
Storage temperature –40°C to +85°C
Humidity 10%–80% RH (non-condensing)

8.10.2 (Optional) Smoke Detector


Smoke detectors are used to detect smoke in an aisle containment.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 127


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Figure 8-25 Smoke detector

Table 8-23 Smoke detector technical specifications

Item Specifications

Operating voltage 9–16 V DC


Quiescent current < 8 mA
Alarm current < 35 mA
Output mode Relay output
Output contact capacity 3 A 120 V AC or 3 A 24 V DC
Operating temperature –10°C to +50°C
Ambient humidity ≤ 95% RH
External dimensions Diameter: 112 mm; height: 41 mm

8.10.3 (Optional) Temperature Sensor


Figure 8-26 Temperature sensor

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 128


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Table 8-24 Temperature sensor specifications

Item Specifications
Temperature measurement range –20°C to +70°C
Measurement precision ±1°C
Operating temperature –10°C to +55°C
Operating voltage 10–16 V DC
Storage temperature –40°C to +70°C

8.10.4 Temperature and Humidity Sensor


Figure 8-27 Appearance

Table 8-25 Temperature and humidity sensor specifications

Item Specifications
Measurement range –20°C to +70°C
Measurement precision ±1°C
Operating temperature –10°C to +55°C
Operating voltage 9–16 V DC
Storage temperature –40°C to +70°C

8.10.5 Multi-functional Sensor


A multi-functional sensor integrates the smoke sensor and temperature and humidity sensor
and can connect to the ECC800 controller system over PoE or wireless communication.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 129


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Figure 8-28 Multi-functional sensor

Specifications

Table 8-26 Multi-functional sensor technical specifications

Item Specifications
Temperature –40°C to 80°C.
monitoring
Humidity Precision ≤ ±5% RH (25°C, 20%–80% RH).
monitoring
Smoke Complies with Ul217. The smoke sensor generates an alarm when
monitoring testing 3.2% weak dust for each foot.
PoE port One PoE port that complies with IEEE802.3AT
RS485 port One RS485 port is reserved.
DI input One DI input port, 12 V DC power input
BLINK button Wireless communication:
 Press the button for less than 1s to start blinking.
 Hold down the button for 1–5s to search for a network and start
networking.
 Hold down the button for more than 6s to clear network parameters.
Smoke sensor Supports smoke sensor test.
test button
E-label Supported

The detected values of the multifunctional sensor and the T/H sensor in the smart cooling product aisle
are different (detecting positions are different).

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 130


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

8.10.6 Alarm Beacon


The alarm beacon is installed outside an aisle containment. When fire or smoke is detected in
the smart module, the alarm beacon generates an audible alarm and blinks to inform operators
of fire and safety risks.

Figure 8-29 Alarm beacon

Table 8-27 Alarm beacon structural specifications

Item Specifications
Dimensions (L x W x H) 130 mm x 75 mm x 55 mm
Installation requirements Installed on a wall
Protection level IP50
Environmental RoHS, REACH
protection requirements

Table 8-28 Alarm beacon technical specifications

Item Specifications
Power input RJ45 port; supports input voltage 9–16 V DC; operating current
≤ 400 mA
Acoustic pressure ≥ 100±3 dB/30 cm
Working duration ≥ 45 min

8.11 Intelligent Battery Management Subsystem


The intelligent battery management subsystem consists of the CIM (CIM01C2) and BIM
(BIM01C3).
The communication interface module (CIM) is an intelligent battery management module
which collects wireless communication data from the downstream BIM groups, collects and
analyzes the operating data of battery strings, calculates state of charge (SOC) and state of
health (SOH) of batteries and battery strings, estimates the battery health status, supports

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 131


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

battery tripping management, and uploads data to the upper-level management unit through
COM or PoE ports.
The battery interface module (BIM) is a battery monitoring module that monitors the voltages,
internal resistances, and pole temperatures of batteries.

 One CIM supports a maximum of 300 BIMs, and manages BIMs for a maximum of four battery
strings.
 The BIM supports Shoto and Enersys batteries.

In the scenario with battery cabinets, the CIM is installed inside a battery cabinet of the
FusionModule2000 and the CIM communications cable connects to a smart ETH gateway in
this example. Figure 8-29 shows the CIM and BIM networking in the scenario with battery
cabinets.

Figure 8-30 CIM and BIM networking (in the scenario with battery cabinets)

When a battery system needs to be managed by multiple CIMs, the CIMs can be connected to
northbound devices using straight-through cables (the ECC supports four CIMs in parallel)
without cascading. Figure 8-30 shows the system networking.

Figure 8-31 CIM communications cable connecting to the smart ETH gateway

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 132


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

8.11.1 CIM
The CIM is a battery information collection module. It collects battery status data from the
downstream BIM groups through wireless communication, and sends the data to the ECC and
UPS through COM or PoE ports.

Features
 Collects battery data detected by the BIM through wireless communication.
 Each CIM can manage a maximum of four battery strings composed of 300 batteries.
 An external Hall effect sensor is connected to monitor the current of each battery string.
 Calculates the SOC and SOH of batteries and battery strings.
 Accurately identifies batteries with lower voltages in a battery string.
 Identifies loose battery terminals and battery terminal overtemperature, and controls
battery switch tripping.
 Supports WebUI display and northbound communication over FE and RS485.
 Allows the upper-level management unit to upgrade the CIM and BIM online.

If the upgrade package is transmitted to the CIM, the upgrade is complete. The BIM upgrade is finished
through the CIM at the back end.

Appearance

Figure 8-32 CIM front view

(1) –48 V 0.5 A port (2) PoE port (3) COM_IN port (RS485
(power input) communication input)
(4) COM_OUT port (5) DI and DO ports (6) HALL_1–HALL_8
(RS485 communication current monitoring ports
output)
(7) RF_Z antenna port (8) BCB_1–BCB_4 ports (9) BCB_OUT and BCB_IN
(BCB_2–BCB_4 reserved) ports
(10) Networking switch (11) PWR indicator (12) RUN indicator

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 133


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

(13) ALM indicator (14) RF_Z indicator (15) Delivered antenna

Figure 8-33 CIM bottom view

(1) Fastener (2) Micro SD card slot


(3) Default button (IP (4) ADDR dual in-line package (DIP) switch (RS485
reset) communications address)
(5) 12 V 2 A port (power
input)

8.11.2 BIM
The BIM is a battery monitoring module that supports 12 V power input and monitors the
voltages, internal resistances, and pole temperatures of batteries.

Features
 Monitors the voltages, internal resistances, and pole temperatures of batteries.
 Provides the hibernation function (when detecting that the battery voltage is low, it enters
low-power mode).
 Uploads battery data to the CIM through wireless communication.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 134


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Appearance

Figure 8-34 BIM

(1) RUN/ALM indicator (2) Networking switch (3) Panel ports (4) Fastener

Panel Ports

Figure 8-35 Port pins

Table 8-29 Port pin definitions

Pin Definition Description

1 GND BAT_V+ and BAT+ are


used for connecting red
2 NTCA wires to positive battery
terminals. BAT_V– and
3 NTCB
GND are used for
4 BAT+ connecting black wires to
negative battery terminals.
5 BAT_V–
6 NTCA1
7 NTCB1
8 BAT_V+

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 135


FusionModule2000 Smart Modular Data Center
Product Description 8 Facility Management System

Indicators

Table 8-30 Indicator description

Indicator Color Silk Status Description


Screen

Operating Green RUN Off  Power consumption is low.


 The BIM is not powered on.
Blinking at The networking has started but not
super short completed.
intervals
Blinking at The networking succeeds.
long intervals
Alarm Red ALM Off The BIM is normal.
Blinking at  Network parameters are being
super short cleared.
intervals  The BIM is blinking.
Steady on  The BIM is measuring the
battery internal resistance.
 The BIM is faulty.
 Communication with the CIM
times out.
 No network is connected. (The
BIM is waiting to connect to a
network.)

 If an indicator blinks at long intervals, it is blinking on for 1s and then off for 1s.
 If an indicator blinks at super short intervals, it is blinking at 10 Hz, that is, on for 0.05s and then off
for 0.05s.
 If both the red and green indicators light up at the same time, orange effect may be generated.

Networking Switch

Table 8-31 Networking switch description

Name Definition Function

Button pressing Press the button for less Searches for and joins a network if there is no
than 5s. network. Initializes parameters of a network
if there is a network.
Button holding Hold down the button Clears the present network and resets the
down for more than 5s. wireless module.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 136


FusionModule2000 Smart Modular Data Center
Product Description 9 Lighting System

9 Lighting System

The lighting system is composed of AC actuators and aisle lights. They can be configured
based on site requirements.

9.1 AC Actuator
The AC actuator is used in a smart module to control the lighting inside the smart module by
receiving commands from the access control system or host, infrared linkage information
(disabled by default), or signals from the light button. It also provides a charging port for the
pad. The AC actuator can connect to the ECC800 controller by wireless networking
(802.15.4).

Figure 9-1 AC actuator

(1) AC OUT2 port (2) AC OUT1 port (3) AC IN port (4) Status indicator
(5) BLINK button (6) AI/DI dry (7) COM1–2 RS485
contact port

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 137


FusionModule2000 Smart Modular Data Center
Product Description 9 Lighting System

Specifications

Table 9-1 AC actuator technical specifications

Item Specifications
Power input One AC input, 100–240 V AC.
Power output  AC OUT1: two AC outputs, 100–240 V AC, maximum total
current: 5 A. The built-in relay can connect or disconnect the
circuit.
 AC OUT2: one AC output, 100–240 V AC, maximum current: 5
A. Supplies power continuously.
Wireless One wireless communication port, complying with IEEE802.15.4
communication
RS485 port One route of dual RS485 ports, not isolated (reserved)
AI/DI detection Two AI/DI dry contact ports, which can connect to two light buttons
BLINK button  Press the button for less than 1s to start blinking.
 Hold down the button for 1–5s to search for a network and start
networking.
 Hold down the button for more than 6s to clear network
parameters.

9.2 Aisle Light


Light emitting diode (LED) lights are used for lighting in an aisle. The lights are installed on
the top at the two sides of the aisle.

Figure 9-2 LED light

Table 9-2 LED light technical specifications

Item Specifications
Installation mode Ceiling installation
Light base requirement The light base and light are integrated.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 138


FusionModule2000 Smart Modular Data Center
Product Description 9 Lighting System

Item Specifications
Protection level IP20
Electrical insulation class Class I
Standards compliance IEC 60598
Rated operating voltage 220–240 V AC (working normally in the
range of 198 V AC to 264 V AC)
Light color Daylight color
Luminous flux ≥ 900 lm
Rated power 10–16 W

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 139


FusionModule2000 Smart Modular Data Center
Product Description 10 Surge Protection and Grounding System

10 Surge Protection and Grounding


System

The surge protection and grounding system consists of the surge protection solution and
grounding solution.

Surge Protection Solution


SPDs are installed in front of the target equipment. The conducting wires to each SPD are
short (within 0.15 m) and straight. The SPD wires are copper wires with a minimum
cross-sectional area of 10 mm2, and the ground cables to SPDs are copper cables with a
minimum cross-sectional area of 16 mm2.

Grounding Solution

Solution 1: M-shaped (Grid) Grounding (Recommended)

Figure 10-1 M-shaped (grid) grounding solution for a single-row aisle containment

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 140


FusionModule2000 Smart Modular Data Center
Product Description 10 Surge Protection and Grounding System

Figure 10-2 M-shaped (grid) grounding solution for a dual-row aisle containment

1. Each cabinet in the smart module connects to the ground grid nearby using ground cables
with a minimum cross-sectional area of 16 mm2.
2. Use 100 mm x 0.3 mm copper foils or 25 mm2 braided copper strips for the equipotential
bonding grid, and use 30 mm x 3 mm red copper strips for the equipotential bonding bar
based on the customer's configurations.

Solution 2: S-shaped (Star) Grounding (Not Recommended)


 A main ground copper bar is installed inside the PDC and a branch ground copper bar is
installed inside the first battery cabinet or IT cabinet adjacent to the PDC. Ground
terminals of cabinets inside the module are connected to the branch ground copper bar
over ground cables with a minimum cross-sectional area of 16 mm2. The branch ground
copper bar connects to the main ground copper bar over a ground cable with a minimum
cross-sectional area of 25 mm2. The main ground copper bar connects to a floor earthing
bar (FEB) or collective ground bar (copper bar with an area of 25 mm x 3 mm routed
along a cable tray or wall in the equipment room).
 Metal components and parts of cabinets are properly connected. A structural connection
area is protected by paint or not and applied with antioxidants before connection. A
protected area should ensure that two metal components can be properly connected. The
DC resistance is within 0.1 ohm between any two connected metal components. Use a
ground cable to connect two metal components that cannot be directly connected, such as
cabinets and cabinet doors. The cable should have a minimum cross-sectional area of 6
mm2.
 A ground copper bar or main ground point is provided in each cabinet for equipment
grounding. These ground copper bars do not need to be insulated.
 The ground terminal should be greater than or equal to M8 in dimensions. A yellow
ground label is attached close to the main ground terminal for cabinets, as shown in

.
Connect equipotential cables to metal components without carrying currents in the smart
module, such as metal doors and windows, cable trays, and ESD floor supports. Each
equipotential cable should have a minimum cross-sectional area of 6 mm2.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 141


FusionModule2000 Smart Modular Data Center
Product Description 10 Surge Protection and Grounding System

Figure 10-3 shows the equipotential cable connections for cabinets in a single-row aisle
containment.

Figure 10-3 Equipotential cable connections for single-row cabinets

In a dual-row aisle containment, two branch ground copper bars are used. The main ground
copper bar is in the PDC, and a branch ground copper bar is in the first IT cabinet near the
PDC.

Figure 10-4 Equipotential cable connections for dual-row cabinets (two branch ground copper
bars)

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 142


FusionModule2000 Smart Modular Data Center
Product Description 11 Integrated Cabling System

11 Integrated Cabling System

The integrated cabling system of the smart module mainly consists of cabling devices and
cables.

Cable Troughs
Cable troughs are installed on the top of cabinets for routing cables. There are two types of
cable troughs: signal cable troughs and power cable troughs.
If a dual-row aisle containment is equipped with one PDC and one network cabinet, power
cables need to be routed to the other end of the module through the control skylight on the top
of the PDC while signal cables need to be routed to the other end of the module through the
control skylight on the top of the network cabinet.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 143


FusionModule2000 Smart Modular Data Center
Product Description 11 Integrated Cabling System

Figure 11-1 Cable routes through cable troughs

(1) Network cabinet (2) Optical fiber (3) Signal cable


(4) Smart ETH gateway (5) PDC (6) Power cable

Cable
 The power cables include power cables to the UPS, battery cabinet, smart cooling
product, and rPDU.
 The ground cables include ground cables to the PDU8000, battery cabinet, and IT
cabinet.
 The monitoring cables include monitoring cables to the smart cooling product, UPS, and
video devices, access control alarm cables, cables in the network cabinet, and various
sensor cables.
 Cables to the fire extinguishing auxiliary components include cables to the alarm beacon
and skylight actuator.

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 144


FusionModule2000 Smart Modular Data Center
Product Description A Acronyms and Abbreviations

A Acronyms and Abbreviations

A
AC alternate current
ATS automatic transfer switch

B
BCB battery circuit breaker
BIB battery control I/O board
BIM battery interface module
BSPP British Standard Pipe Parallel Thread

C
CAN controller area network
CE ConformitéEuropéenne
CFD computational fluid dynamics
CIM communication interface module

D
DC direct current

E
EC electronic commutation
ECC energy control center
ETH Ethernet

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 145


FusionModule2000 Smart Modular Data Center
Product Description A Acronyms and Abbreviations

F
FE fast Ethernet

I
iBAT ibattery
IC integrated circuit
IDC Internet data center
IDS integrated data-center solution
IT Internet technology

L
LCD liquid crystal display
LED light emitting diode

M
MTBF mean time between failures
MTTR mean time to repair

N
NTC negative temperature coefficient

P
PDU power distribution unit
PE protective earthing
PoE power over Ethernet
PUE power usage effectiveness

R
RCCB residual current circuit breaker

S
SD secure digital memory
SIM subscriber identity module

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 146


FusionModule2000 Smart Modular Data Center
Product Description A Acronyms and Abbreviations

SNMP Simple Network Management Protocol


SPD surge protective device

U
USB Universal Serial Bus
UPS uninterruptible power system

V
VCN video cloud node

W
WiFi wireless fidelity

Issue 05 (2020-03-06) Copyright © Huawei Technologies Co., Ltd. 147