FusionModule App User Manual (FusionModule2000) 2
FusionModule App User Manual (FusionModule2000) 2
V500R002C03
Product Description
Issue 05
Date 2020-03-06
and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.
Website: https://e.huawei.com
Purpose
The FusionModule2000 smart modular data center solution (FusionModule2000 for short)
includes smart modules A and B. This document describes the FusionModule2000 product
positioning, features, application scenarios, and system architecture, providing the systemic
information about the smart modular data center.
Intended Audience
This document is intended for:
Sales engineers
Technical support engineers
System engineers
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol Description
Indicates a hazard with a high level of risk which, if not
avoided, will result in death or serious injury.
Indicates a hazard with a medium level of risk which, if not
avoided, could result in death or serious injury.
Indicates a hazard with a low level of risk which, if not
avoided, could result in minor or moderate injury.
Indicates a potentially hazardous situation which, if not
avoided, could result in equipment damage, data loss,
performance deterioration, or unanticipated results.
NOTICE is used to address practices not related to personal
injury.
Supplements the important information in the main text.
NOTE is used to address information not related to personal
injury, equipment damage, and environment deterioration.
Change History
Changes between document issues are cumulative. The latest document issue contains all
updates made in previous issues.
Issue 05 (2020-03-06)
Updated the technical specifications of the integrated UPS.
Issue 04 (2020-01-14)
Updated the USB description.
Issue 03 (2019-12-04)
Updated the USB description.
Issue 02 (2019-03-10)
Updated the manual name and so on.
Issue 01 (2017-09-20)
This issue is the first release.
Contents
1 Positioning
The FusionModule2000 solution integrates the cabinet, power supply and distribution,
cooling, monitoring, and integrated cabling systems, achieves seamless integration of power
supply and distribution, cooling, and management systems, and enables the modular data
center to operate intelligently and efficiently. It can run network services alone or work as a
branch of a larger modular data center to run part of services.
The FusionModule2000 is designed for small- and medium-sized data center facilities. It
mainly applies to small- and medium-sized data centers for bank offices, governmental
agencies, small- and medium-sized enterprises (SMEs), education, and medical organizations.
The FusionModule2000 provides basic physical infrastructure for small- and medium-sized
data centers.
2 Features
The FusionModule2000 features high integration, outstanding security and reliability, space
saving, high energy efficiency, quick installation, optimal compatibility, fast and flexible
deployment, excellent monitoring, and stable cooling. It is a new-generation smart modular
data center solution.
High Integration
The smart module integrates a cabinet system, power supply and distribution system,
cooling system, facility management system, surge protection and grounding system,
auxiliary fire extinguishing system, and integrated cabling system. It provides an overall
solution.
The integrated power supply and distribution system have distributes power to
uninterruptible power systems (UPSs), smart cooling products, and IT equipment.
When the 380 V power supply is used and there are more than four battery cabinets or when the 480
power supply is used, battery racks are independently deployed.
Optimal Compatibility
The smart module supports class B environments, and smart cooling products support
class C environments.
Modular power distribution allows for smooth expansion to meet various requirements.
Excellent Monitoring
Various sensors monitor functional modules in the data center in real time.
The web-based monitoring system enables remote management of functional modules.
3 Application Scenarios
Scenario Figure
Single-row aisle containment
Scenario Figure
With a raised floor
Dual-row aisle
containment
Dual-row aisle
containment
Smart module A (UPS and smart cooling products deployed inside the module, batteries deployed
outside the module) and smart module B (smart cooling products deployed inside the module, UPS and
batteries deployed outside the module) are divided into two parts, which can be deployed in one room or
two rooms. If deployed in one room, the smart module adopts the hot aisle containment design to ensure
that the ambient temperature for batteries meets requirements.
4 Typical Configurations
The FusionModule2000 data center has two different architectures: smart modules A and B.
Typical configurations involve the single-row and dual-row 1200 mm wide aisle
containments.
Figure 4-4 Floor plan of the single-row 1200 mm wide aisle containment (PDC)
The PDC refers to the integrated UPS, integrated PDC, or precision PDC.
Figure 4-7 Floor plan of the dual-row 1200 mm wide aisle containment (PDC)
The PDC refers to the precision PDC, integrated UPS, or integrated PDC.
Figure 5-3 N+1 power supply and distribution system diagram (integrated PDC)
Figure 5-4 N+1 power supply and distribution system diagram (precision PDC or smart busway)
The wall-mounted PDB, but not the precision PDC or smart busway, supplies power to smart
cooling products.
Figure 5-5 2N power supply and distribution system diagram (integrated PDC)
Figure 5-6 2N power supply and distribution system diagram (precision PDC or smart busway)
The wall-mounted PDB, but not the precision PDC or smart busway, supplies power to smart
cooling products.
(1) Power input status indicator (2) Input circuit (3) Lighting circuit
breaker breaker
(4) Power distribution circuit breaker for (5) IT load circuit (6) UPS input circuit
the smart cooling product breaker breaker
(7) UPS maintenance bypass circuit (8) Control module (9) Bypass module
breaker
(10) Filler panel (11) Power module (12) Monitor display
unit (MDU)
(13) Power distribution monitoring board (14) UPS output
circuit breaker
(1) Power input (2) ATS drive module (3) ATS monitoring
status indicator module
(4) Lighting circuit (5) Power distribution circuit breaker (6) IT load circuit breaker
breaker for the smart cooling product
(7) UPS input (8) UPS maintenance bypass circuit (9) Control module
circuit breaker breaker
(10) Bypass module (11) Power module (12) ATS transfer switch
(13) ATS handle (14) Monitor display unit (MDU) (15) Power distribution
monitoring board
(16) UPS output
circuit breaker
(1) Positioning lock (2) Run indicator (3) Alarm indicator (4) Fault indicator
(5) Ready switch (6) Output port (7) Input port
Functions
The power module consists of a PFC rectifier and inverter. The power module performs
AC-DC or DC-DC conversion on the mains and battery inputs, and stabilizes the bus voltage.
The inverter converts DC inputs into AC sine wave outputs.
Specifications
Dimensions (H x W x D): 86 mm x 442 mm x 620 mm
Weight: < 21 kg
Rated output capacity: 25 kVA/25 kW
Power density: 17.2 W/inch3
(1) Positioning (2) Battery cold start (3) Run (4) Alarm indicator
lock button indicator
(5) Fault indicator (6) Ready switch (7) Signal port (8) Input and output
ports
Functions
The UPS is set to ECO mode and the bypass voltage is within the specified range.
The power module is overloaded for a period longer than the maximum allowed period.
Both the active and standby ECMs are abnormal.
The system fails to run properly and transfers to bypass mode.
A manual operation is performed to transfer to bypass mode.
Specifications
Dimensions (H x W x D): 130 mm x 442 mm x 500 mm
Weight < 25 kg
Maximum output power: 125 kW
(1) Ground terminal (2) Parallel port 1 (3) BSC port (4) Ready switch
1 on ECM 1
(5) Indicators for ECM 1 (6) Parallel port 2 (7) BSC port (8) Ready switch
2 on ECM 2
(9) Indicators for ECM 2 (10) Dry contact card (11) Dry (12) MDU port
contacts
(13) RS485 port (14) Fast Ethernet (FE) (15) COM2 (16) COM1 port
port port
(17) Battery temperature (18) Optional card
sensor port subrack cover
5.3.4.2 ECM
The control module consists of two ECMs that work in active/standby mode. Each card
provides two ports, that is, a BSC port in the upper part and a reserved parallel port in the
lower part.
The dry contact interface card takes effect only after it is set on the monitoring system. Set the
unused dry contact signal to the unused status.
Set the EPO port to NO or NC as required.
When multiple UPSs are paralleled, all dry contact signals to be used need to connect to each UPS.
Single cables require dual-insulated twisted cables. If the length of a power cable is within 25–50 m,
its cross-sectional area must be 0.5 mm2 to 1.5 mm2.
The FE port resembles the RS485 port. Follow the silk screen when connecting
communications cables as, if the RS485 port is mistaken for the FE port during cable
connection, the WebUI cannot be connected and MDU communication fails. Conversely, if
the FE port is mistaken for the RS485 port during cable connection, RS485
communication fails.
Only once being set will dry contact signals take effect. Set unused dry contact signals to
the unused state on the LCD.
In a parallel system, ensure that used dry contacts properly connect to each UPS.
The monitoring interface card provides external ports as well as monitoring and control
functions for the MDU. The ports include the ambient temperature and humidity sensor port,
FE port, battery temperature monitoring port, and network management port. MDU functions
include monitoring of the UPS, allowing users to set parameters, command delivery,
information reports, and UPS key information and parameters displayed on the LCD.
The maximum voltage and current of ports DO_1 to DO_4 are 30 V DC, 1 A or 60 V DC, 0.5 A
respectively.
Signal cables must be double-insulated twisted cables. If the cable length is 25–50 m, the
cross-sectional area must be 0.5–1.5 mm2.
RS485 cables and FE cables must be shielded cables.
Figure 5-16 and Figure 5-17 are recommended wiring methods for DO ports.
Figure 5-18 and Table 5-5 describe the COM1 pin definitions.
Pin Description
1 GND
2 N/A
3 RS485-
4 RS485+
5 N/A
6 12V_PORT
Figure 5-19 and Table 5-6 describe the COM2 pin definitions.
Pin Description
1 RS485+
2 RS485-
3 N/A
4 RS485+
5 RS485-
6 GND
7 CANH0
8 CANL0
Figure 5-20 and Table 5-7 describe the RS485 pin definitions.
Pin Description
1 RS485_T+
2 RS485_T–
3 N/A
4 RS485_R+
5 RS485_R–
6 GND
7 N/A
8 N/A
5.3.5 MDU
Appearance
The indicator on the MDU panel is yellow when the bypass supplies power in non-ECO mode.
Functions
The monitor display unit (MDU) allows for general UPS operations, parameter setting,
viewing of running status and alarms, and so on.
Specifications
Dimensions (H x W x D): 175 mm x 264 mm x 40 mm
Item Specifications
Cable routing mode Routed in and out from the top
Routed in and out from the bottom (tail frame configured)
Protection level IP20
Dimensions (H x W x D) 2000 mm x 600 mm x 1100 mm
Communication Dry contacts, RS485, and SNMP
Item Specifications
Operating temperature 0°C to 40°C
Storage temperature –40°C to +70°C
Relative humidity 5%–95% RH (non-condensing)
Altitude 0–1000 m (When the altitude is greater than 1000 m and less
than 4000 m, the rated power should be derated. For details,
see the IEC62040-3.)
Item Specifications
Safety compliance EN62040-1, 2013
IEC62040-1, 2013
Electromagnetic EN/IEC62040-2
compatibility (EMC) IEC61000-2-2
IEC61000-4-2
EN61000-4-6: EN/IEC62040-2 2nd Ed (IEC61000-4-6)
EN61000-4-3: EN/IEC62040-2 2nd Ed (IEC61000-4-3)
EN/IEC62040-2 2nd Ed (IEC61000-4-4)
EN/IEC62040-2 2nd Ed (IEC61000-4-5)
IEC61000-4-8
IEC61000-4-11
Item Specifications
Input system Three-phase, four-wire, and PE
Rated input voltage 380 V AC/400 V AC/415 V AC (line voltage)
Input voltage range 80–280 V AC (phase voltage)
At 0–40°C: The UPS works at full load when the voltage is
176–280 V AC and is linear derated to 40% load when the
voltage is 176–80 V AC.
Input frequency range 40–70 Hz
Input power factor > 0.99 (full load); > 0.98 (half load)
THDi ≤ 3% (linear load; maximum: 3%); ≤ 5% (non-linear load;
maximum: 5%)
Item Specifications
Input system Three-phase, four-wire, and PE
Rated input voltage 380 V AC/400 V AC/415 V AC (line voltage)
Input frequency range 50/60 Hz ±6 Hz (adjustable with the tolerance of 0.5–6 Hz, ±2
Hz by default)
Item Specifications
Battery voltage 360–528 V DC (30–44 batteries, 32 by default; derated by 6%
when there are 30 batteries)
Battery management Intelligent battery management
Cold start When a mains outage occurs, batteries can start the UPS to
supply power to loads.
Charging voltage Equalized charging voltage: 2.3–2.4 V/cell, 2.35 V/cell by
default (30–42 batteries); 2.3–2.35 V/cell, 2.35 V/cell by
default (44 batteries)
Float charging voltage: 2.23–2.3 V/cell; 2.25 V/cell by
default (30–44 batteries)
Item Specifications
Item Specifications
System efficiency 96% (linear load)
Item Specifications
Current equalization 5%
specification
Item Specifications
Engineering Dimensions (H x W x D) Basic dimensions: 2000 x 600 x 1100,
features (mm) 2000 x 600 x 1200
Expanded dimensions: 2200 (including
a top frame) x 600 x 1200
Weight (kg) < 350
Enclosure protection level IP20
Cable routing Routed in and out from the top
Maintenance mode Operated from the front and maintained
from the rear
Item Specifications
Installation mode Installed on an ESD floor or concrete floor
Electrical Rated operating voltage (V 380/400/415
features AC)
Rated insulation voltage (V 690
AC)
Rated frequency (Hz) 50/60
IT power distribution input One 3-pole 160 A MCCB input
mode One 3-pole 250 A MCCB input
Two 3-pole 160 A MCCB inputs
Two 3-pole 250 A MCCB inputs
Smart cooling product One 3-pole 160 A MCCB input
power distribution input One 3-pole 250 A MCCB input
mode
Two 3-pole 160 A MCCB inputs
Two 3-pole 250 A MCCB inputs
Output switch (standard IT power distribution branch: a
configuration) maximum of 48 branches
(single-phase) or 16 branches
(three-phase), a maximum of 40 A
current for each branch
Smart cooling product power
distribution branch: a maximum of 16
branches (three-phase), a maximum of
63 A current for each branch
Lighting switch Smart cooling product with dual inputs:
six 1-pole 10 A switches
Smart cooling product with single input:
three 1-pole 10 A switches
Surge protection Class C; nominal discharge current In
(8/20 µs) = 20 kA, maximum discharge
current Imax (8/20 µs) = 40 kA; voltage
protection level Up (20 kA, 8/20 μs) ≤ 1.8
kV (L-N)/≤ 1.0 kV (N-PE)
Monitoring Detection items Three-phase input voltage, current,
function frequency, active power, reactive power,
electric energy, power factor, and
temperature
Communications mode Supports the Modbus TCP protocol and
Modbus RTU protocol.
(Optional) Branch temperature monitoring
Certifications CE, CCC
Item Specifications
Power distribution mains input Phase voltage, phase current, load rate, frequency,
power factor, total active power, total electric energy,
total apparent power, total reactive power, busbar
temperature, circuit breaker status, and surge
protection status
Power distribution branch output Phase current, active power, load rate, electric
energy, temperature, and circuit breaker status
Item Specifications
Dimensions (H x W x D) Basic dimensions: 2000 x 600 x 1100, 2000 x 600 x
(mm) 1200
Expanded dimensions: 2200 (including a top frame) x
600 x 1200
Weight (kg) < 400
Rated operating voltage (V) 380/400/415
Rated insulation voltage (V) 690
Rated frequency (Hz) 50/60
Rated operating current (A) 400/250/160
Enclosure protection level IP20
Output switch 40 A single-phase, maximum 144 routes (single-phase)
Surge protection Class C; nominal discharge current In (8/20 µs) = 20 kA,
maximum discharge current Imax (8/20 µs) = 40 kA;
voltage protection level Up (20 kA, 8/20 μs) ≤ 1.8 kV
(L-N)/≤ 1.0 kV (N-PE)
Cable routing Routed in and out from the top or bottom
Certifications CCC, CE
Environmental friendliness RoHS, REACH
Item Specifications
Power distribution mains Phase voltage, phase current, load rate, frequency, power
input factor, total active power, total electric energy, total
apparent power, total reactive power, busbar temperature,
circuit breaker status, and surge protection status
Power distribution branch Phase current, active power, load rate, electric energy,
output temperature, and circuit breaker status
Item Feature
High efficiency, Space saving: saves the IT cabinet space.
economical, and rapid
delivery Easy maintenance: short maintenance duration.
High scalability: Busbar trunking units can be added. Each
busbar trunking unit connects to one power distribution unit.
Long lifespan.
Power saving.
Safe, reliable, and flexible High reliability: uses a foolproof structure with installation
O&M position marks and spacing measures.
Easy O&M: can be easily maintained as the new main way is
highly reliable and allows users to replace power distribution
units.
Easy installation: short time to install the new main way.
Intelligent monitoring and Easy to network through an FE port to implement
flexible management teleindication, telemetering, and teleadjusting.
Flexible to manage and monitor the power usage effectiveness
(PUE) and maintenance.
Intelligently measures and monitors parameters such as
electricity, current, voltage, power factor, total active power,
total apparent power, total reactive power, and neutral wire
current.
Item Specifications
System type Three-phase, four-wire, and PE
Rated operating voltage 380 V AC, 400 V AC, or 415 V AC
Overvoltage type III
Rated operating current at 40°C 160 A/250 A
Input switch One 3-pole 160 A MCCB
One 3-pole 250 A MCCB
Output switch Six 1-pole 40 A MCBs
Rated transient withstand current 10 kA, 1s
Rated frequency 50/60 Hz
Protection level IP30
Electric shock protection type Type I
Electromagnetic compatibility (EMC) Level A
environment
Cabling mode Routed in from the end
Cable connection capacity 160 A rated current: 4 x 70 mm2 + 1 x
35 mm2
250 A rated current: 4 x 95 mm2 + 1 x
50 mm2
Item Specifications
Power distribution mains input Phase voltage, phase current, load rate, frequency,
power factor, total active power, total electric energy,
total apparent power, total reactive power, busbar
temperature, and circuit breaker status
Power distribution branch output Phase current, active power, load rate, electric
energy, temperature, and circuit breaker status
Table 5-28 Configuration scenarios (for both the main and auxiliary battery cabinets)
- - 40 38 36 34 32
26 Ah/40 Ah Layer 1 10 9 8 7 6
Layer 2 10 10 10 10 10
Layer 3 10 10 10 10 10
Layer 4 10 9 8 7 6
Table 5-29 Configuration scenarios (The main battery cabinet and auxiliary battery cabinet are
differentiated.)
- - 20 19 18 17 16 20 19 18 1 1
7 6
65 Ah/100 Ah Layer 1 5 4 3 2 1 5 4 3 2 1
Layer 2 5 5 5 5 5 5 5 5 5 5
Layer 3 5 5 5 5 5 5 5 5 5 5
Layer 4 5 5 5 5 5 5 5 5 5 5
5.9 rPDU
The rPDU uses IEC sockets by default. GB sockets are also supported.
The figures are for reference only. The actual products prevail.
6 Structural System
Figure 6-1 Components of the single-row 1200 mm wide cold aisle containment (PDC)
(1) End door (2) Flat or rotating skylight (3) Control skylight
(4) Cable trough (5) Smart ETH gateway (6) Cabinet
(7) Alarm beacon (8) Pad (9) Access control device
Figure 6-2 Components of the single-row 1200 mm wide cold aisle containment (smart busway)
(1) General input unit (2) Control skylight (3) Alarm beacon
(4) Power distribution unit (5) Busbar trunking unit (6) Flat or rotating skylight
(7) Cable trough (8) Cabinet (9) Pad
(10) Access control device (11) End door
Figure 6-3 Components of the dual-row 1200 mm wide cold aisle containment (power supply and
distribution cabinet)
(1) End door (2) Flat or rotating skylight (3) Control skylight
(4) Cable trough (5) Smart ETH gateway (6) Cabinet
(7) Alarm beacon (8) Pad (9) Access control device
Figure 6-4 Components of the dual-row 1200 mm wide cold aisle containment (smart busway)
(1) General input unit (2) Control skylight (3) Alarm beacon
(4) Power distribution unit (5) Busbar trunking unit (6) Flat or rotating skylight
(7) Cable trough (8) Cabinet (9) Pad
(10) Access control device (11) End door
6.4 IT Cabinet
An IT cabinet used in the smart module complies with the International Electrotechnical
Commission (IEC) 60297-1 standard and provides stable installation space for servers,
thereby ensuring safe operation of servers.
The cabinet dimensions are unified, and both front and rear air channels are designed.
6.5 Skylight
Skylights are used for sealing an aisle containment. Skylights are classified as control
skylights, rotating skylights, and flat skylights.
The 300 mm wide flat skylight is used with a 300 mm wide smart cooling product.
(1) Skylight connective plate (2) Control skylight panel (3) Cable separation panel
Control skylights are installed on both ends of an aisle and used to install monitoring components
such as the camera, multi-functional sensor, and smoke detector.
If the smart module is longer than 7 m, add one control skylight in the middle of the smart module
for installing a multi-functional sensor or smoke detector.
(1) Magnetic lock fixing base (2) Skylight connective plate (3) Flat skylight panel
A rotating skylight is designed with an eccentric structure. When the trigger is activated, a rotating
skylight falls under gravity. When a magnetic lock is triggered, the rotating skylight falls under
gravity.
The BOM numbers of 600 mm wide rotating and flat skylights are the same (21501038). The
rotating skylight requires a magnetic lock but the flat skylight does not.
(1) Magnetic lock fixing base (2) Skylight connective plate (3) Rotating skylight panel
The BOM numbers of 800 mm wide rotating and flat skylights are the same (21501039). The rotating
skylight requires a magnetic lock but the flat skylight does not.
Sliding Door
Sliding doors can be opened only sideways, and therefore may involve risks during fire extinguishing
system acceptance.
Revolving Door
The double revolving door is an outward opening door with an opening angle of 90 degrees. It
ensures that the aisle containment is properly sealed and separated.
Type Dimensions
600 mm wide smart cooling Height (adjustable): 270 mm ≤ H ≤ 410 mm; depth
product, PDC, IT cabinet, (adjustable): 1000 mm, 1100 mm, or 1200 mm
battery cabinet, or network
cabinet base Height (adjustable): 410 mm ≤ H ≤ 700 mm; depth
(adjustable): 1000 mm, 1100 mm, or 1200 mm
300 mm wide smart cooling Height (adjustable): 270 mm ≤ H ≤ 410 mm; depth
product base (adjustable): 1000 mm, 1100 mm, or 1200 mm
Height (adjustable): 410 mm ≤ H ≤ 700 mm; depth
(adjustable): 1000 mm, 1100 mm, or 1200 mm
800 mm wide IT or network Height (adjustable): 270 mm ≤ H ≤ 410 mm; depth
cabinet base (adjustable): 1000 mm, 1100 mm, or 1200 mm
Height (adjustable): 410 mm ≤ H ≤ 700 mm; depth
(adjustable): 1000 mm, 1100 mm, or 1200 mm
Fixed Bases
The fixed bases for the FusionModule2000 are classified into cabinet bases (600 mm wide),
smart cooling product bases (300 mm wide), smart cooling product and PDC bases (600 mm
wide), and cabinet bases (800 mm wide).
Type Dimensions (H x W x D)
600 mm wide IT, battery, or network 250 mm x 600 mm x 1200 mm
cabinet base
300 mm wide smart cooling product base 250 mm x 300 mm x 1200 mm
600 mm wide smart cooling product or 250 mm x 600 mm x 1200 mm
PDC base
800 mm wide IT or network cabinet base 250 mm x 800 mm x 1200 mm
Cable Manager
A cable manager is used to manage cables inside a cabinet horizontally.
Cable Ring
A cable ring is installed on a side post in the cabinet to secure vertically routed cables.
Cable Tray
A cable tray is used for forward and backward cabling. It uses mounting ears to facilitate
device installation.
The installation positions for cable management devices are for reference only. Determine the
installation positions based on the actual situation.
Components
The indoor unit of the NetCol5000-A consists of a compressor, oil separator, fan, heat
exchanger, electronic expansion valve, one-way valve, filter dryer, sight glass, electric heater
(optional), electrode humidifier (optional), wet film humidifier (optional), water pump
(optional), and so on.
Compressor
The DC variable-frequency compressor provides the cooling capacity ranging from 20%
to 100% to meet partial load requirements.
Oil separator
It is an oil-gas separator that separates lubricant from the exhaust of the compressor and
brings back the separated lubricant to the compressor.
EC fan
The EC fan implements stepless speed adjustment.
Heat exchanger
The efficient finned evaporator, an important part in the cooling system, absorbs heat
from indoor air to ensure that the indoor temperature and humidity meet requirements.
Electronic expansion valve
The flow regulator uses a micro controller to control the motor operation, thereby
changing the pass-through area of the valve to precisely regulate the flow of refrigerant.
One-way valve
The one-way valve efficiently controls backflow of gas or liquid.
Filter dryer
The filter dryer absorbs moisture from refrigerant pipes and filters out foreign matter,
which reduces the component damage probability and ensures efficient and reliable
operating of components.
Sight glass
The sight glass allows you to observe the refrigerant flow and the content of gas and
liquid for easy maintenance and optimization.
Electric heater
The PTC heater features quick start, large heating capacity, and even heat dissipation. It
has multiple protection mechanisms to ensure the secure and stable running of the
equipment.
Humidifier
The electrode or wet film humidifier can be used to precisely control the equipment
room humidity.
Water pump
The water pump provides power for top drainage with a maximum lift of 4 meters.
7.2.2 Controller
7.2.2.1 Appearance and Ports
Appearance
The controller provides a 7-inch true color touchscreen and man-machine interfaces for query,
setting, monitoring, and maintenance.
The indicator on the panel displays operating status of the smart cooling product. Figure 7-2
shows the position of the indicator. Table 7-1 describes the mapping between indicators,
buzzers, and alarms. If alarms of different severities (critical, major, minor, or warning) are
raised simultaneously, the indicator status corresponds to the alarm with the highest severity
level and the buzzer status corresponds to the unacknowledged alarm with the highest severity
level.
Ports
1 MUS05A Reserved
2 FE (fast Ethernet) communications port
3 CAN communications port for the main control board and
LCD
4 RS485_1 Reserved
5 USB Host After installing the WiFi module, locally connect to
the smart cooling product over the Service Expert
Function
Single unit control: Provides logic control for the components of a single smart cooling
product to ensure that the indoor temperature and humidity meet requirements.
Display operation: Provides a 7-inch touchscreen for you to set parameters for the smart
cooling product and query its status.
Teamwork control: Enables multiple smart cooling products to work cooperatively,
distributes thermal loads in an optimal way to dramatically reduce power consumption,
and provides multiple standby smart cooling products to improve the reliability.
The smart cooling product has the following four remote functions.
− Telemetry: supply air temperature, return air temperature, supply air humidity,
return air humidity, and working status of the smart cooling product.
− Teleindication: startup/shutdown states, overvoltage/overcurrent,
undervoltage/undercurrent, return air overtemperature/undertemperature, return air
overhumidity/underhumidity, filter normal/blocked, and fan normal/faulty.
− Telecontrol: smart cooling product startup/shutdown.
− Teleadjusting: temperature, humidity, and alarm threshold.
Remote management: You can monitor, manage, and upgrade one or more smart cooling
products using the remote management function provided by Huawei.
Faults and alarms are recorded and stored. Up to 1500 historical fault and alarm records
can be stored.
Access logs can be traced back. Historical user login and setting records can be
displayed. Up to 1000 historical records can be stored.
Features
The display panel provides a touchscreen with a concise user-friendly interface.
The controller controls the indoor temperature precisely and responds quickly.
The controller is protected by a multi-level password protection mechanism, avoiding
misoperations.
Password verification is required upon the first startup to ensure the system security. No
password verification is required for subsequent startup if the first verification succeeds.
The display panel displays the operating status and duration of the smart cooling product
components in real time.
The fault diagnosis system automatically displays the information about current faults,
which facilitates the maintenance.
The controller provides a variety of external ports including a fast Ethernet (FE) port and
universal serial bus (USB) port that is protected by a security mechanism.
Do not install the smart cooling product near a noise-sensitive place such as an office or a
conference room.
Table 7-3–Table 7-7 describe the operating environment, physical ports, installation
requirements, and water quality requirements of the NetCol5000-A.
Environmental Specifications
Item Specifications
Operating temperature 18–45°C
Operating humidity 20%–80% RH
Storage temperature –40°C to +70°C
Storage humidity 5%–95% RH (non–condensing)
Outdoor temperature Working with the NetCol500–A032 (including
low–temperature components): –40°C to +45°C
Working with the NetCol500–A036 (including
low–temperature components): –40°C to +55°C
Working with the NetCol500–A036: –20°C to +55°C
Working with the NetCol500-A026SC11E0: –20°C to
+45°C
Working with the NetCol500-A0265S11E0: –20°C to
+55°C
Working with the NetCol500-A0265S11E0 (including
low–temperature components): –40°C to +45°C
Protection level Indoor unit: IP20
Outdoor unit: IPX5
Item Specifications
Altitude 0–1000 m. When the altitude is greater than 1000 meters, the
cooling capacity is derated. The maximum operating altitude is
4000 meters. For the detailed derated data, reference the Table
7-4.
Physical Ports
Item Specifications
Refrigerant liquid pipe Copper pipe, with an outer diameter of 5/8 inch (15.88 mm)
and thickness of 1.0 mm, withstanding a pressure not smaller
than 4.5 MPa, welding
Refrigerant gas pipe Copper pipe, with an outer diameter of 3/4 inch (19.05 mm)
and thickness of 1.0 mm, withstanding a pressure not smaller
than 4.5 MPa, welding
Water inlet pipe to the G 1/2 inch inner screw thread
humidifier
Installation Requirements
When the total load power of servers corresponding to a single smart cooling product is less
than 5 kW or the equipment room airtightness is not satisfactory, the indoor humidity might
be relatively high, which is not a product quality issue. You are advised to install a
dehumidifier in the equipment room in this case.
Item Specifications
Equipment room door Width ≥ 0.9 m; height ≥ 2.3 m
Floor Bearing capacity ≥ 350 kg/m2; height of the raised floor ≥ 250
mm
Installation mode Installed on a concrete floor, a base, or an ESD floor
Pipe and cable routing Cables and pipes can be routed from the top or bottom
Equivalent length of ≤ 80 m
one-way pipe
Height difference If the outdoor unit is placed higher than the indoor unit, the
between the indoor and maximum vertical distance between them is 20 m.
outdoor units If the indoor unit is placed higher than the outdoor unit, the
maximum vertical distance between them is 5 m.
Thickness of the thermal ≥ 13 mm
insulation foam
Inner diameter of the Liquid pipe: 16 mm
thermal insulation foam Gas pipe: 19 mm
Drainage Drainpipes can withstand a high temperature greater than or
equal to 85°C (for the smart cooling products configured with
electrode humidifiers)
Power supply Leakage switches are not recommended for the main circuit. If
leakage switches are required by the customer or local
regulations, use the residual current circuit breaker (RCCB)
that is insensitive to the single-phase DC pulses and transient
current pulses
Note: If some conditions are not met, contact Huawei technical support.
If the inlet water contains large granules, install a water filtering device at the inlet port to
prevent pipe blockage.
The inlet water pressure should be in the range of 0.1–0.7 MPa (A reducing valve must be
installed if the inlet water pressure exceeds 0.7 MPa.), and the temperature should be in the
range of 1°C–40°C.
Item Specifications
Cooling mode Air cooled
Refrigerant R410A
Air flow mode Horizontal air flow
Dimensions (H x W x D) 2000 mm x 300 mm x 1100 mm (cabinet)
2000 mm x 300 mm x 1200 mm (cabinet with an
enclosure frame)
2200 mm x 300 mm x 1100 mm (cabinet with an
enclosure frame, customizable)
2200 mm x 300 mm x 1200 mm (cabinet with top and
enclosure frames)
Net weight 230 kg
Environmental friendliness REACH, RoHS
For a smart cooling product with heating and humidification functions, the general switch
is a 40 A, feature C switch that does not derate at 45°C. If the switch derates largely when
the temperature changes, verify that the switch can work at 40 A for a long time at 45°C.
For a smart cooling product without heating and humidification functions, the general
switch is a 32 A, feature C switch that does not derate at 45°C. If the switch derates largely
when the temperature changes, verify that the switch can work at 25 A for a long time at
45°C.
(1) Cabinet connecting kit (2) Controller panel (3) Door lock (4) Front door
(5) Mounting hole (6) Side panel (7) Rear door (8) Anchor
D in the figure stands for the cabinet depth, which can be 1100 mm or 1200 mm. Table 7-10 shows the
available cabinet dimensions.
(1) Power cable hole (Φ28 mm) on the top (2) Humidifier water inlet hole (Φ43 mm) on
the top
(3) Signal cable hole (Φ28 mm) on the (4) Refrigerant gas pipe hole (Φ43 mm) on
skylight the top
(5) Refrigerant liquid pipe hole (Φ43 mm) (6) Drainpipe hole (Φ43 mm) on the top
on the top
(7) Signal cable holes (Φ28 mm) on the top (8) Power cable hole (Φ28 mm) at the
bottom
(9) Humidifier water inlet hole (Φ43 mm) (10) Refrigerant gas pipe hole (Φ60 mm) at
at the bottom the bottom
(11) Drainpipe hole (Φ60 mm) at the (12) Refrigerant liquid pipe hole (Φ60 mm)
bottom at the bottom
(13) Signal cable hole (Φ28 mm) at the
bottom
(1) Fan (2) Electric heater (3) Condensate pump (4) Drainage check
valve
(5) Strong-current (6) Evaporator (7) Wet film (8) Water inlet
box humidifier solenoid valve
(9) Humidifier (10) Differential (11) Signal cable (12) Compressor
pump pressure switch terminal block driver
(13) Weak-current (14) T/H sensor (15) Discharge pipe (16) EEV
box
(17) Oil separator (18) Sight glass (19) Compressor (20) Filter dryer
Compressor
− The NetCol5000-A uses a DC variable-frequency compressor that features compact
size, light weight, long service life, low noise, easy installation as well as high
reliability, stability, and energy efficiency.
− The wet film humidifier has low water quality requirements and high environment
adaptability.
− The wet film humidifier has a simple structure and is easy to remove, clean, and
maintain.
− The wet film humidifier can quickly start and generate huge humidification
capacity.
− The wet film humidifier consumes less power, saving more than 95% of energy
compared with a traditional electrode humidifier.
− Compared with a traditional electrode humidifier, the wet film humidifier has a
longer service life and maintenance interval.
Condensate pump
The water pump provides power for top drainage with a maximum lift of 4 m.
Check valve
The check valve effectively prevents gas or liquid backflow.
Differential pressure switch
When the air filter is dirty or blocked, the differential pressure switch triggers an alarm,
prompting for air filter replacement.
Differential pressure sensor
− It adjusts air volume based on the differential pressure to ensure precise air supply.
No excessive adjustment helps save energy and reduce power consumption.
− The air supply volume is also sufficient, which helps eliminate hotspots and
improves reliability.
T/H sensor
Six built-in negative temperature coefficient (NTC) temperature sensors and one return
air T/H sensor are provided.
7.3.1.3 Controller
7.3.1.3.1 Appearance and Ports
Appearance
The controller provides a 7-inch true color touchscreen and man-machine interfaces for query,
setting, monitoring, and maintenance.
The indicator on the panel displays operating status of the smart cooling product. Figure 7-7
shows the position of the indicator. Table 7-11 describes the mapping between indicators,
buzzers, and alarms. If alarms of different severities (critical, major, minor, or warning) are
raised simultaneously, the indicator status corresponds to the alarm with the highest severity
level and the buzzer status corresponds to the unacknowledged alarm with the highest severity
level.
Ports
Functions
Each smart cooling product has an independent control system, LCD, electric heater,
humidifier, and T/H sensor to ensure its normal operating in high-precision mode.
The 7-inch display panel with the true-color touchscreen allows you to set parameters for
the smart cooling product and query its status.
The smart cooling product has the following four remote functions.
− Telemetry: supply air temperature, return air temperature, supply air humidity,
return air humidity, and working status of the smart cooling product
− Teleindication: startup/shutdown states, overvoltage/overcurrent,
undervoltage/undercurrent, return air overtemperature/undertemperature, return air
overhumidity/underhumidity, filter normal/blocked, and fan normal/faulty
− Telecontrol: smart cooling product startup/shutdown
− Teleadjusting: temperature, humidity, and alarm threshold
When multiple smart cooling products work cooperatively, the controller optimally
distributes the heat load to reduce power consumption and provides backup to improve
reliability.
− When a smart cooling product in the group is faulty, the backup smart cooling
product starts to operate automatically to improve the reliability of the smart
cooling product system.
− Each smart cooling product enters the active mode one by one periodically.
− The number of operating smart cooling products varies depending on the thermal
load in the equipment room to meet requirements promptly, eliminate hot spots, and
save energy.
− A mechanism is adopted to prevent the smart cooling products in the same
equipment room operating in opposite status (such as cooling and heating, or
humidification and dehumidification), in order to save energy.
− Autonomous group networking: If a communication cable in the group control
network is disconnected, two group control network forms, and the group which has
no host smart cooling product can automatically recommend a host and continue the
group networking.
You can monitor, manage, and upgrade one or more smart cooling products using the
remote management software provided by Huawei.
1500 historical alarms can be stored.
Access logs can be traced back. 1000 historical login and setting logs can be stored.
The controller can display 30 days' temperature and humidity in colored curves and 30
days' differential pressure of supply air and return air (differential pressure control
function required) in colored curves. O&M personnel can view the smart cooling product
operating status onsite.
Features
The controller provides a touchscreen with a user-friendly interface.
The controller controls the indoor temperature precisely and responds quickly.
The controller is protected by a multi-level password protection mechanism, avoiding
misoperations.
Password verification is required upon the first startup to ensure the system security. No
password verification is required for subsequent startup if the first verification succeeds.
The controller provides multiple protection functions, such as abnormal power-off
self-recovery and water leakage detection, ensuring system reliability.
The cooling capacity, air volume, as well as the operating status and time of each
component in the smart cooling product are displayed on the LCD in real time.
The controller provides abundant external ports such as RS485 ports, CAN ports, FE
ports, and USB ports that are protected by a security mechanism. These ports flexibly
meet the communication requirements and feature good electrical isolation.
The controller provides multi-language display, such as Chinese, English, French,
Spanish, Russian, and so on.
O&M personnel can export fault records in one-click mode, making it easy to operate the
smart cooling product and know the running status of the smart cooling product.
The smart cooling product supports communications protocols such as Modbus RTU,
Modbus TCP, and SNMP, facilitating connection to the network management system.
The controller intelligently identifies abnormal parameter settings (incorrect commands)
and rejects them automatically.
If the indoor temperature fluctuates beyond the normal range, an audible and visible
alarm signal is sent automatically.
Item Specifications
Item Specifications
Humidifier water inlet pipe G 1/2 inch inner screw thread
(humidifier hose is provided for
the smart cooling product)
G 3/4 inch outer screw thread
(humidifier hose is not provided
for the smart cooling product)
Drainpipe BSPP 1/2 inch inner screw
thread
Outdoor unit Refrigerant liquid pipe Outer diameter of 5/8 inch
(15.88 mm), welding
Refrigerant gas pipe Outer diameter of 7/8 inch
(22.22 mm), welding
water cooling module Refrigerant liquid pipe Outer diameter of 5/8 inch
(15.88 mm), welding
Refrigerant gas pipe Outer diameter of 7/8 inch
(22.22 mm), welding
Low-temperature Connecting to indoor unit Outer diameter of 5/8 inch
component (optional liquid pipe (15.88 mm), welding
component)
Connecting to indoor unit Outer diameter of 7/8 inch
gas pipe (22.22 mm), welding
Connecting to outdoor unit Outer diameter of 5/8 inch
liquid pipe (15.88 mm), welding
Connecting to outdoor unit Outer diameter of 7/8 inch
gas pipe (22.22 mm), welding
Item Specifications
Refrigerant R410A
Cooling capacitya 42 kW
Air supply mode Horizontal flow
Airflow 8600 m3/h
Dimensions (H x W x D) 2000 mm x 600 mm x 1100 mm (cabinet dimensions)
2000 mm x 600 mm x 1200 mm (including an enclosure
frame)
Item Specifications
2200 mm x 600 mm x 1100 mm (including a top frame)
2200 mm x 600 mm x 1200 mm (including an enclosure
frame and a top frame)
Net weight/Gross weight 305 kg/342 kg
(full configuration)
Certification CQC, CE, RoHS, REACH, WEEE, and IEC
a: Test condition is rated condition (Indoor dry-bulb temperature: 37.8°C. Relative
humidity: 20%. Outdoor temperature: 35°C).
Operating Specifications
temperature
Operating Specifications
temperature
Applicable outdoor Work with NetCol500-A036: –20°C to +45°C
temperature Work with NetCol500-A036 (including a low-temperature
component): –40°C to +45°C
Work with NetCol500-A072: –5°C to +55°C
Protection level IP20
Installation mode ESD floor-mounted: pipes and cables routed from the top or
bottom
Floor: pipes and cables routed from the top
Altitude 0–4000 m. When the altitude exceeds 1000 m, the power
should be derated. For detailed derating data, see Table 7-17.
In the following chapters, outdoor unit photos are taken from the NetCol500-A072 as examples and are
for reference only.
Components
The NetCol500 outdoor unit consists of a condenser, electric control box, rack, and fans.
Outdoor unit installation environments are classified as follows based on the harshness:
Class A (controlled environment): indoor environments where the ambient temperature and humidity
are controlled, including rooms where people live
Class B (uncontrollable environment): indoor environments where the ambient temperature and
humidity are not controlled or general outdoor environments with simple shielding measures where
the humidity sometimes reaches 100%
Class C (harsh environment): marine environments within 3.7 km from the coast or outdoor land
environments with simple shielding measures within 1.2 km from a pollution source
Class D (marine environment): environments within 500 m from the coast
The NetCol500-A0365S11E0 and NetCol500-A0265S11E0 outdoor units must not be installed in class
D environments, and other outdoor units must not be installed in class C or class D environments.
A low-temperature component is mandatory when the outdoor ambient temperature may drop
to –20ºC.
Item Specifications
Heater power supply 220–240 V AC, 1 Ph, 50 Hz or 60 Hz
Heater power supply voltage tolerance Rated voltage ±10%
Heater power supply frequency Rated frequency ±3 Hz
tolerance
Refrigerant R410A
Liquid pipe outer diameter 5/8 inch (15.88 mm)
Gas pipe outer diameter 7/8 inch (22.22 mm)
HxWxD 632 mm x 944 mm x 507 mm (with package)
470 mm x 828 mm x 300 mm (without package)
Item Specifications
Expansion bolt hole M12x60
Storage temperature –40°C to +70°C
Storage humidity 5%–95% RH (non-condensing)
Maximum operating pressure 4.35 MPa
If the previous three conditions are met but no sunshade is installed, the smart cooling product
will shut down because the components are applied beyond specifications.
Item Specifications
Dimensions (H x W x D) 598 mm (14 U) x 491 mm x 410 mm
Weight 30 kg
Power system 220–240 V 50 Hz
Rated input current 5.9 A
Rated input power 1250 W
Dehumidification capacity 45 L/day
Appearance
The 7-inch true color-sensitive LCD offers a user-friendly interface for you to perform query,
settings, monitoring, and maintenance.
Functions
Single unit control: When only one unit is running, the controller provides logic control
over components in the unit to meet the indoor temperature and humidity requirements.
Display and operations: The 7-inch touchscreen of the controller allows you to set
parameters for the device and query the device status.
Teamwork control: When multiple units work cooperatively, the controller optimally
distributes the heat load to reduce power consumption and provides backup to improve
reliability.
Remote management: You can monitor, manage, and upgrade one or more units using
the remote management software provided by Huawei.
Benefits
The controller provides a touchscreen with a user-friendly interface.
The controller is highly precise and responsive.
The three-level password protection mechanism prevents misoperations.
The controller protects the smart cooling product from overvoltage, undervoltage,
abnormal power failures, and water leaks, ensuring system reliability.
The touchscreen of the controller displays the operating status and time of the
temperature control components in real time.
The controller provides a professional fault diagnosis system which automatically
displays fault information, facilitating maintenance.
The controller provides various external ports such as RS485 ports, FE ports, and USB
ports that are protected by a security mechanism.
Linkage Logic
1. Collect information about layouts, temperature and humidity, and power of all devices in
the smart module.
2. Correlate cabinets with smart cooling products in terms of airflow organization based on
the smart module layout.
3. Calculate heat dissipation of all devices in the smart module by using the equipment
power, after which the basic requirements of the cooling capacity can be determined.
Then roughly adjust the operating status of the smart cooling products (determine the
number of operating smart cooling products and initial rotational speed of the
compressors).
4. To meet temperature requirements for the smart module, slightly adjust the operating
status of smart cooling products according to the deviation of cooling requirements
calculated by using the data of temperature distribution in the smart module.
5. When distributing cooling requirements for each smart cooling product, minimize the
power consumption of the cooling system in the smart module with the help of energy
efficiency features of smart cooling products.
In the figure, RF_Z indicates wireless networking. RF_Z(1) devices can communicate with the
ECC800 in wireless mode. The RF_Z(2) BIM and CIM communicate with each other in wireless
mode. RF_Z(1) and RF_Z(2) devices use different protocols and are isolated from each other.
Wireless communication is automatically established after the access actuator, skylight actuator, and
multi-functional sensor successfully connect to and communicate with the ECC800 through PoE.
skylight actuator, AC actuator, multi-functional sensor, and access actuator) can be connected
by RF_Z wireless networking.
The management system provides a GUI to implement comprehensive management functions
based on requirements. The system can monitor the following equipment:
Power equipment, including precision smart cooling products, integrated PDCs, UPSs,
and ATSs
Environment monitoring equipment, including multi-functional sensors, and water
sensors, and so on.
Video equipment, including cameras and network video recorders VCN500
Access control equipment: A standard access management system is integrated to
manage and monitor key information such as door status, card swiping, and permission
setting.
Standard network management interface: The NetEco provides SNMP interfaces to
communicate with third-party NMSs. The system can be customized to support other
protocols for the access from different devices.
(1) PSU (optional) (2) PSU (optional) (3) Status (4) 3G/4G
indicator antenna port
(5) FE ports (WAN_1–WAN_2 (6) AI/DI_1–6 sensor (7) RF_Z (8) SW
and LAN_1–LAN_2) input ports antenna port button
(9) DO_1–2 dry contact outputs (10) RS485 port (11) Default (12) USB
(COM1–4/12 V) button port
(13) ECC800 main control
module
ECC800 Specifications
Item Specifications
Operating temperature –20°C to +50°C
Storage temperature –40°C to +70°C
Humidity 5%–95% RH (non-condensing)
Altitude 0-4000 m (When the altitude is between 3000 m and 4000 m,
the temperature decreases by 1°C for each additional 200 m.)
Item Specifications
Dimensions (H x W x D) 43.6 mm x 442 mm x 330 mm
Color Black
Installation requirements Installed in a standard 1 U cabinet
Installed in a 19-inch rack
Environmental protection requirements RoHS5
Item Specifications
Power input Two AC inputs
Rated operating voltage: 200–240 V AC or 100–120 V AC
Rated operating frequency: 50/60 Hz
Power output Output voltage: 42–58 V DC (rated voltage: 53.5 V DC)
Output power of two power supplies: 2000 W (176–300 V AC);
940 W (linear derating at 85-175 V AC)
Output power of a single power supply: 1000 W (176–300 V
AC); 470 W (linear derating at 85–175 V AC)
FE port expansion Supports two WAN ports and two LAN ports with the 10/100M
communications rate.
RS485 serial port Four RS485 ports with the default communications rate of 9600
expansion bit/s
Each port provides 12 V DC power with the rated current of 450
mA.
AI/DI expansion Supports six AI/DI ports to connect to sensors such as smoke,
(RJ45) water, and temperature sensors.
Each port provides 12 V DC power with the rated current of 85
mA.
DO expansion Two DO ports both supporting active and passive DO
(RJ45) Supports passive (dry contact) DO port with contact point
capacity of 20 W, maximum withstand voltage of 60 V DC, and
rated current of 500 mA.
Supports the active DO port with an output voltage of 12 V DC
and output current of 450 mA.
Wireless Wireless communication that complies with IEEE802.15.4
communication
3G (optional) Supports 3G (WCDMA) communication and is compatible with 2G
(GSM) communication. A standard SIM card slot is provided.
NOTE
The prerequisite for using a SIM card is that the site has signal coverage.
Item Specifications
USB After installing the WiFi module, connect the WiFi module to
the ECC800 using the app on the mobile phone or tablet
computer to view the basic information about the smart module,
such as layout, resources, energy efficiency, environment, and
alarms.
Insert a USB flash drive to export historical data, device data,
fault information, and configuration files, and import or export
the device configuration data and historical data.
Button SW: wireless network pairing button
Default: button for restoring the default IP address
Item Specifications
Equipment 2 U, H x W x D: 87.5 mm x 447 mm x 740 mm
Can be installed in a standard cabinet that is 19 inches
wide and 1000 mm deep or deeper
Main board Central One or two
processing unit
(CPU)
Item Specifications
CPU model Intel®Xeon® E5-2600 (Romely-EP) series 4C/6C/8C
processor; maximum configuration: 135 W processor of
3.3 GHz dominant frequency and the L3 cache of 20 MB
for a CPU
Memory 24 DIMMs slots, supports RDIMM/LRDIMM memory of
DDR3, a maximum of 768 GB
Hard drive Supports eight 2.5-inch 6 Gbit/s hot-swappable
SAS/SATA/SSD hard drives, or twelve 3.5-inch 6 Gbit/s
hot-swappable SAS/SATA hard drives and two 2.5-inch
built-in 6 Gbit/s hot-swappable SAS/SATA/SSD hard
drives.
Expansion Supports six expansion slots for PCIe 3.0 cards: one slot
for PCIe3.0 x 16, four slots for PCIe3.0 x 8, and one
dedicated slot for RAID.
Item Specifications
External dimensions (H x W x D) 44.4 mm x 442 mm x 420 mm
Maximum power (full configuration) 913 W (power consumption: 173 W; PoE:
740 W)
Weight ≤ 8 kg
DC input voltage Rated voltage: –48 V DC to –60 V DC
Voltage range: –36 V DC to –72 V DC
AC input voltage Rated voltage: 100–240 V AC
Voltage range: 90–264 V AC
Temperature Operating temperature: 0°C to +50°C
NOTE
When the altitude ranges from 1800 m to 5000
m, the highest temperature decreases by 1°C for
each additional 220 m.
Item Specifications
Storage temperature: –40°C to +70°C
Humidity 5%–95% RH (non-condensing)
Altitude Non-PoE device:
− With DC power: 0–2000 m
− With AC power: 0–5000 m
PoE device: 0–5000 m
8.5 Pad
The pad, a control panel, allows wireless access to the data center facility management system.
You can monitor the equipment in the data center and environmental parameters in real time
over the app.
(1) LOCK/GND (2) BUTTON/GND (3) AI/DI_1 sensor (4) AI/DI_2 sensor
magnetic lock DO window open button DI input port input port
output port input port
(5) BLINK button (6) Status indicator (7) Address DIP (8) COM1 RS485
switch port
(9) COM2 RS485 (10) PoE port (11) 48 V power
port port
Specifications
Item Specifications
Power input DC input: Terminal, with input voltage of 36–60 V DC
PoE input: One PoE port that complies with IEEE802.3at.
PoE port FE communication with the rate of 10/100M
Wireless One wireless port that complies with IEEE802.15.4, mutual backup
communication with FE communication
AI/DI port Two AI/DI ports for detecting equipment room fire extinguishing
linkage signals; smoke detection signals also supported
DO output One 12 V DC power output for controlling the skylight magnetic
lock; driving six skylight magnetic locks simultaneously
Item Specifications
DI input One DI input port for connecting to the skylight open button
BLINK button Press the button for less than 1s to start blinking.
Hold down the button for 1–5s to search for a network and start
networking.
Hold down the button for more than 6s to clear network
parameters.
Address DIP 4-pin address DIP switch
switch
E-label Supported
(1) Ground port (2) 48 V DC power (3) PoE port (4) COM1/12V port
input port
(5) COM2/12V port (6) COM3 port (7) COM4 port (8) NTC1–3 ports
(9) NTC4–6 ports (10) AI/DI_1 port (11) AI/DI_2 port (12) 12V_1 port
(13) 12V_2 port (14) BLINK button (15) Status indicator
Specifications
Item Specifications
Power input DC input: Phoenix terminal, with an input voltage range of
Item Specifications
36–60 V DC
PoE input: One PoE port that complies with IEEE802.3at.
12 V power output Two 12 V DC power outputs with the rated output current of 250
mA
FE port FE communication with the rate of 10/100M
RS485 serial port Four RS485 ports with the default communications rate of
expansion 9600 bit/s
Among the four RS485 ports, two support 12 V DC power
output with the rated current of 400 mA.
The other two are isolated, with the default communications
rate of 9600 bit/s, and do not support power output.
AI/DI input Two active 12 V DC, 200 mA (rated) AI/DI input ports
Temperature sensor Provides two RJ45 ports to connect to six temperature sensors,
port each RJ45 port connecting to three temperature sensors.
BLINK button Supports the blinking function.
(1) PWR_IN (2) FE_1 cascading (3) POE_1–2 (4) POE_3–4 ports
cascading power port signal port ports
(5) 48V_OUT1 (6) 48V_OUT2 (7) FE_2 (8) PWR_OUT
power output port power output port cascading signal cascading power port
port
(9) BLINK button (10) Status indicator
Specifications
Item Specifications
Power input PWR_IN D-type power input terminal, for power cascading, input voltage
range: 45–55 V DC
Power of a single smart ETH gateway: max (2.7 A , 48 V DC); power of
cascaded smart ETH gateways: max (25 A, 48 V DC)
Power output PWR_OUT D-type power output terminal, for power cascading, output
voltage range: 45–55 V DC
48V_OUT1 and 48V_OUT2, terminal (1 A,48 V DC), output voltage
range: 45–55 V DC
FE port Two FE ports, RJ45 terminal with an indicator, 10/100M communication
rate, for the cascading between smart ETH gateways and the
communication with the upper computer
POE port Four POE ports, RJ45 terminal with an indicator, 10/100M
communications rate, complying with IEEE802.3, IEEE802.3u,
IEEE802.3af/at
BLINK If you press the BLINK button, the RUN indicator blinks intermittently at
button super short intervals (blinking at super short intervals for 0.5s and then off
for 0.5s) for 5 seconds.
Indicators
(1) RF_1 antenna port (2) RF_2 antenna port (3) Reset button (4) WPS button
(5) Status indicator (6) 48 V power port (7) PoE port
Specifications
Item Specifications
Power input DC input: Phoenix terminal, with an input voltage range of 36–60 V
DC
PoE power supply: One PoE port, complying with IEEE802.3at,
25.5 W
WiFi function 2.4 GHz frequency, two antennas, supporting eight STA
connections, 50 m WiFi coverage (no blockage)
Supports the WPS button.
Reset button Press and hold down the button for more than 5s to restore the factory
settings of the WiFi converter.
WPS button Support fast WiFi access by WPS.
WPS function: When the WiFi is enabled, if you choose Advanced settings > WPS connection on the
WLAN of the intelligent device (such as a mobile phone and pad) and press the WPS button on the WiFi
converter at the same time, the intelligent device will quickly connect to the WiFi hotspot of the device.
8.8.1 IP Camera
The IPC6325-WD-VR IP camera (IPC6325 camera for short) is a two-megapixel wide
dynamic infrared zoom dome camera that can be wall-mounted or ceiling-mounted.
The camera monitors the module interior in real time, records videos, and implements 7x24h
storage.
Item Specifications
8.8.2 VCN500
Figure 8-14 VCN500
Item Specifications
Video input A VCN500 supports the access from a maximum of 32 cameras and
the maximum access bandwidth of 160 Mbit/s.
Video transfer A VCN500 supports the video transfer from 32 cameras or of 160
Mbit/s.
Storage A VCN500 supports the storage access from a maximum of 32
cameras and the maximum storage access bandwidth of 160 Mbit/s.
Video playback and A VCN500 supports video playback and download of 32 cameras
download or 160 Mbit/s.
Item Specifications
Hard drive slot Twelve 3.5-inch hard drive slots
Hard drive type and Twelve 4 TB SATA hard drives
quantity NOTE
The VCN500 supports hard drives at enterprise and monitoring
levels.
RAID control card The VCN500 does not have a RAID control card on its
mainboard.
CPU type and quantity 1 x 1 GHz, maximum 10 MB cache
Memory capacity 2 GB
I/O port Two service network ports, with RJ45 connectors and
LNK/ACT indicators
Power parameters Single power supply only
Maximum PSU power: 250 W
AC power input voltage range: 100–240 V AC
Item Specifications
AC power frequency range: 50–60 Hz
Weight (full configuration) ≤ 20 kg
Typical power 40 W
consumption (excluding
hard drives)
Maximum power 70 W
consumption (excluding
hard drives)
Typical power 170 W
consumption (including
monitoring-level hard
drives)
Maximum power 215 W
consumption (including
monitoring-level hard
drives)
Typical power 200 W
consumption (including
enterprise-level hard
drives)
Maximum power 250 W
consumption (including
enterprise-level hard
drives)
Dimensions (H x W x D) 86.1 mm x 447.0 mm x 470.0 mm
(1) 48 V power port (2) POE port (3) RS485 port COM2
(4) RS485 port COM1 (5) Address DIP switch (6) Status indicator
(7) BLINK button (8) WG_2 Wiegand (9) WG_1 Wiegand interface
interface
(10) AI/DI_2 dry (11) AI/DI_1 dry (12) LOCK/GND/GATE/COM door
contact (Reserved port contact (Reserved port status or magnetic lock port
for linkage control or for exit button)
third-party fire
extinguishing system
dry contacts)
Specifications
Item Specifications
Item Specifications
AI/DI port Two AI/DI ports, can connect to the fire alarm and exit button
DO/DI port One 12 V DC power output that controls magnetic locks,
terminal
One DI input port for connecting to the door status switch
RS485 serial port Two RS485 ports (one route) with the default communications rate
expansion of 9600 bit/s, physical port cascading supported (reserved function)
Wiegand interface Two Wiegand interfaces, 12 V DC card reader operating power
output; two routes of card readers (non-fingerprint readers) can
operate at the same time.
BLINK button Press the button for less than 1 second to start blinking.
Hold down the button for 1–5 seconds to search for a network
and start networking.
Hold down the button for more than 10 seconds to clear
network parameters.
Address DIP switch 4-pin address DIP switch
E-label Supported
Indicators
Communications Ports
The access actuator provides one DO port (LOCK/GND) and one DI port (GATE/COM).
Table 8-17 lists the LOCK/GND/GATE/COM port pin definitions.
Item Description
LOCK/GND (control magnetic locks) pin sequence LOCK 12V_OUT
GND GND
GATE/COM (door status) pin sequence GATE DI1
COM COM
The access control system is configured with an emergency button that can disconnect
the power supply to the magnetic lock to open the door.
Table 8-18 Specifications of the fingerprint and card reader with a keypad
Item Specifications
Dimensions (L x W x H) 156 mm x 53 mm x 38 mm
Rated operating voltage 12V DC±15%
Rated operating current 300mA±15%
Card type supported IC card
Authorized storage A maximum of 3000 authorized users, with a maximum of
6000 fingerprints
Communications mode RS485 and Wiegand communications ports
Working status Standby: The blue indicator is on, and the green
indicator for the fingerprint reader is steady on.
Fingerprint collection: The red indicator for the
fingerprint reader is on.
Unauthorized fingerprint collection: The buzzer sounds
twice, and the red and blue indicators blink twice.
Authorized fingerprint collection: The buzzer sounds
once, and the red and blue indicators blink once.
Card swiping: The buzzer sounds once, and the red and
blue indicators blink once.
Item Specifications
Dimensions (L x W x H) 156 mm x 53 mm x 38 mm
Operating voltage Rated voltage: 12 V DC ±5%
Operating current Rated current: 300 mA ±5%
Card type supported IC card
Authorized storage A maximum of 3000 authorized users, with a maximum
of 6000 fingerprints
Communications mode RS485 and Wiegand communications ports
Working status Standby: The blue indicator is on, and the green
indicator for the fingerprint reader is steady on.
Fingerprint collection: The red indicator for the
fingerprint reader is on.
Unauthorized fingerprint collection: The buzzer
sounds twice, and the red and blue indicators blink
twice.
Authorized fingerprint collection: The buzzer sounds
once, and the red and blue indicators blink once.
Card swiping: The buzzer sounds once, and the red
and blue indicators blink once.
Item Specifications
Dimensions (L x W x H) 114 mm x 63 mm x 25 mm
Operating voltage Operating voltage range: 10.8–13.2 V DC; rated voltage:
12 V DC
Operating current Static standby current 80 mA, dynamic operating current
(card swiping, key pressing) 150 mA, minimum input
current 12 V DC/300 mA
Communications mode Wiegand communications port
Magnetic Lock
Item Specifications
Rated input voltage 12V DC
Rated current 200–300 mA
Unlock mode Power on to unlock
Card type supported IC card
Mechanically unlock Supported
Features:
An IC card can be used after being authorized using software.
An IC card can be authorized for one lock or all locks.
Door opening information is recorded through a network.
The system displays the status of cabinet doors and locks in real time, and generates
alarms for unauthorized door opening.
The system supports remote door opening.
(1) Water detector (2) Conversion cable end A, connected (3) Conversion cable
to the water detector
(4) Conversion cable (5) Water detection cable end A, (6) Water detection
end B, connected to connected to the conversion cable cable
the water detection
cable
Item Specification
Operating voltage 12 V DC (9–16 V DC)
Operating temperature –20°C to +70°C
Storage temperature –40°C to +85°C
Humidity 10%–80% RH (non-condensing)
Item Specifications
Item Specifications
Temperature measurement range –20°C to +70°C
Measurement precision ±1°C
Operating temperature –10°C to +55°C
Operating voltage 10–16 V DC
Storage temperature –40°C to +70°C
Item Specifications
Measurement range –20°C to +70°C
Measurement precision ±1°C
Operating temperature –10°C to +55°C
Operating voltage 9–16 V DC
Storage temperature –40°C to +70°C
Specifications
Item Specifications
Temperature –40°C to 80°C.
monitoring
Humidity Precision ≤ ±5% RH (25°C, 20%–80% RH).
monitoring
Smoke Complies with Ul217. The smoke sensor generates an alarm when
monitoring testing 3.2% weak dust for each foot.
PoE port One PoE port that complies with IEEE802.3AT
RS485 port One RS485 port is reserved.
DI input One DI input port, 12 V DC power input
BLINK button Wireless communication:
Press the button for less than 1s to start blinking.
Hold down the button for 1–5s to search for a network and start
networking.
Hold down the button for more than 6s to clear network parameters.
Smoke sensor Supports smoke sensor test.
test button
E-label Supported
The detected values of the multifunctional sensor and the T/H sensor in the smart cooling product aisle
are different (detecting positions are different).
Item Specifications
Dimensions (L x W x H) 130 mm x 75 mm x 55 mm
Installation requirements Installed on a wall
Protection level IP50
Environmental RoHS, REACH
protection requirements
Item Specifications
Power input RJ45 port; supports input voltage 9–16 V DC; operating current
≤ 400 mA
Acoustic pressure ≥ 100±3 dB/30 cm
Working duration ≥ 45 min
battery tripping management, and uploads data to the upper-level management unit through
COM or PoE ports.
The battery interface module (BIM) is a battery monitoring module that monitors the voltages,
internal resistances, and pole temperatures of batteries.
One CIM supports a maximum of 300 BIMs, and manages BIMs for a maximum of four battery
strings.
The BIM supports Shoto and Enersys batteries.
In the scenario with battery cabinets, the CIM is installed inside a battery cabinet of the
FusionModule2000 and the CIM communications cable connects to a smart ETH gateway in
this example. Figure 8-29 shows the CIM and BIM networking in the scenario with battery
cabinets.
Figure 8-30 CIM and BIM networking (in the scenario with battery cabinets)
When a battery system needs to be managed by multiple CIMs, the CIMs can be connected to
northbound devices using straight-through cables (the ECC supports four CIMs in parallel)
without cascading. Figure 8-30 shows the system networking.
Figure 8-31 CIM communications cable connecting to the smart ETH gateway
8.11.1 CIM
The CIM is a battery information collection module. It collects battery status data from the
downstream BIM groups through wireless communication, and sends the data to the ECC and
UPS through COM or PoE ports.
Features
Collects battery data detected by the BIM through wireless communication.
Each CIM can manage a maximum of four battery strings composed of 300 batteries.
An external Hall effect sensor is connected to monitor the current of each battery string.
Calculates the SOC and SOH of batteries and battery strings.
Accurately identifies batteries with lower voltages in a battery string.
Identifies loose battery terminals and battery terminal overtemperature, and controls
battery switch tripping.
Supports WebUI display and northbound communication over FE and RS485.
Allows the upper-level management unit to upgrade the CIM and BIM online.
If the upgrade package is transmitted to the CIM, the upgrade is complete. The BIM upgrade is finished
through the CIM at the back end.
Appearance
(1) –48 V 0.5 A port (2) PoE port (3) COM_IN port (RS485
(power input) communication input)
(4) COM_OUT port (5) DI and DO ports (6) HALL_1–HALL_8
(RS485 communication current monitoring ports
output)
(7) RF_Z antenna port (8) BCB_1–BCB_4 ports (9) BCB_OUT and BCB_IN
(BCB_2–BCB_4 reserved) ports
(10) Networking switch (11) PWR indicator (12) RUN indicator
8.11.2 BIM
The BIM is a battery monitoring module that supports 12 V power input and monitors the
voltages, internal resistances, and pole temperatures of batteries.
Features
Monitors the voltages, internal resistances, and pole temperatures of batteries.
Provides the hibernation function (when detecting that the battery voltage is low, it enters
low-power mode).
Uploads battery data to the CIM through wireless communication.
Appearance
(1) RUN/ALM indicator (2) Networking switch (3) Panel ports (4) Fastener
Panel Ports
Indicators
If an indicator blinks at long intervals, it is blinking on for 1s and then off for 1s.
If an indicator blinks at super short intervals, it is blinking at 10 Hz, that is, on for 0.05s and then off
for 0.05s.
If both the red and green indicators light up at the same time, orange effect may be generated.
Networking Switch
Button pressing Press the button for less Searches for and joins a network if there is no
than 5s. network. Initializes parameters of a network
if there is a network.
Button holding Hold down the button Clears the present network and resets the
down for more than 5s. wireless module.
9 Lighting System
The lighting system is composed of AC actuators and aisle lights. They can be configured
based on site requirements.
9.1 AC Actuator
The AC actuator is used in a smart module to control the lighting inside the smart module by
receiving commands from the access control system or host, infrared linkage information
(disabled by default), or signals from the light button. It also provides a charging port for the
pad. The AC actuator can connect to the ECC800 controller by wireless networking
(802.15.4).
(1) AC OUT2 port (2) AC OUT1 port (3) AC IN port (4) Status indicator
(5) BLINK button (6) AI/DI dry (7) COM1–2 RS485
contact port
Specifications
Item Specifications
Power input One AC input, 100–240 V AC.
Power output AC OUT1: two AC outputs, 100–240 V AC, maximum total
current: 5 A. The built-in relay can connect or disconnect the
circuit.
AC OUT2: one AC output, 100–240 V AC, maximum current: 5
A. Supplies power continuously.
Wireless One wireless communication port, complying with IEEE802.15.4
communication
RS485 port One route of dual RS485 ports, not isolated (reserved)
AI/DI detection Two AI/DI dry contact ports, which can connect to two light buttons
BLINK button Press the button for less than 1s to start blinking.
Hold down the button for 1–5s to search for a network and start
networking.
Hold down the button for more than 6s to clear network
parameters.
Item Specifications
Installation mode Ceiling installation
Light base requirement The light base and light are integrated.
Item Specifications
Protection level IP20
Electrical insulation class Class I
Standards compliance IEC 60598
Rated operating voltage 220–240 V AC (working normally in the
range of 198 V AC to 264 V AC)
Light color Daylight color
Luminous flux ≥ 900 lm
Rated power 10–16 W
The surge protection and grounding system consists of the surge protection solution and
grounding solution.
Grounding Solution
Figure 10-1 M-shaped (grid) grounding solution for a single-row aisle containment
Figure 10-2 M-shaped (grid) grounding solution for a dual-row aisle containment
1. Each cabinet in the smart module connects to the ground grid nearby using ground cables
with a minimum cross-sectional area of 16 mm2.
2. Use 100 mm x 0.3 mm copper foils or 25 mm2 braided copper strips for the equipotential
bonding grid, and use 30 mm x 3 mm red copper strips for the equipotential bonding bar
based on the customer's configurations.
.
Connect equipotential cables to metal components without carrying currents in the smart
module, such as metal doors and windows, cable trays, and ESD floor supports. Each
equipotential cable should have a minimum cross-sectional area of 6 mm2.
Figure 10-3 shows the equipotential cable connections for cabinets in a single-row aisle
containment.
In a dual-row aisle containment, two branch ground copper bars are used. The main ground
copper bar is in the PDC, and a branch ground copper bar is in the first IT cabinet near the
PDC.
Figure 10-4 Equipotential cable connections for dual-row cabinets (two branch ground copper
bars)
The integrated cabling system of the smart module mainly consists of cabling devices and
cables.
Cable Troughs
Cable troughs are installed on the top of cabinets for routing cables. There are two types of
cable troughs: signal cable troughs and power cable troughs.
If a dual-row aisle containment is equipped with one PDC and one network cabinet, power
cables need to be routed to the other end of the module through the control skylight on the top
of the PDC while signal cables need to be routed to the other end of the module through the
control skylight on the top of the network cabinet.
Cable
The power cables include power cables to the UPS, battery cabinet, smart cooling
product, and rPDU.
The ground cables include ground cables to the PDU8000, battery cabinet, and IT
cabinet.
The monitoring cables include monitoring cables to the smart cooling product, UPS, and
video devices, access control alarm cables, cables in the network cabinet, and various
sensor cables.
Cables to the fire extinguishing auxiliary components include cables to the alarm beacon
and skylight actuator.
A
AC alternate current
ATS automatic transfer switch
B
BCB battery circuit breaker
BIB battery control I/O board
BIM battery interface module
BSPP British Standard Pipe Parallel Thread
C
CAN controller area network
CE ConformitéEuropéenne
CFD computational fluid dynamics
CIM communication interface module
D
DC direct current
E
EC electronic commutation
ECC energy control center
ETH Ethernet
F
FE fast Ethernet
I
iBAT ibattery
IC integrated circuit
IDC Internet data center
IDS integrated data-center solution
IT Internet technology
L
LCD liquid crystal display
LED light emitting diode
M
MTBF mean time between failures
MTTR mean time to repair
N
NTC negative temperature coefficient
P
PDU power distribution unit
PE protective earthing
PoE power over Ethernet
PUE power usage effectiveness
R
RCCB residual current circuit breaker
S
SD secure digital memory
SIM subscriber identity module
U
USB Universal Serial Bus
UPS uninterruptible power system
V
VCN video cloud node
W
WiFi wireless fidelity