FusionModule App User Manual (FusionModule2000) (2)
FusionModule App User Manual (FusionModule2000) (2)
FusionModule App User Manual (FusionModule2000) (2)
Issue 01
Date 2024-01-05
and other Huawei trademarks are the property of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei
Digital Power Technologies Co., Ltd. and the customer. All or part of the products, services and features
described in this document may not be within the purchase scope or the usage scope. Unless otherwise
specified in the contract, all statements, information, and recommendations in this document are
provided "AS IS" without warranties, guarantees or representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.
Website: https://digitalpower.huawei.com
Purpose
This document describes the functions of the FusionModule app and provides
solutions to common faults.
Intended Audience
The document is intended for:
● Commissioning engineers
● Maintenance engineers
● Technical support engineers
Symbol Conventions
The symbols that may be found in this manual are defined as follows.
Symbol Description
Change History
Issue Date Description
Issue 01 (2024-01-05) Copyright © Huawei Digital Power Technologies Co., Ltd. iii
FusionModule App
User Manual (FusionModule2000) Contents
Contents
3 FAQs..........................................................................................................................................70
3.1 What Do I Do If Login Fails?............................................................................................................................................. 70
3.2 What Do I Do If the Power Distribution View Does Not Display the Circuit Diagram?...............................71
3.3 What Do I Do If the U Space Proportion Is Not Displayed on the App?...........................................................72
3.4 What Do I Do If a Smoke Sensor or Water Sensor Is Not Displayed on the App?........................................ 72
Home
● Home: Displays the smart module layout information, including the power,
cooling capacity, space, resources, energy efficiency, environment, and alarm
overview.
● Active Alarms: Displays the statistics and list of active alarms of the current
device. You can acknowledge and clear active alarms.
● Historical Alarms: Displays the list of all handled alarms. You can sort alarms
by alarm generation time or alarm severity, and filter alarms by alarm
generation time or alarm severity.
iPower
iPower: Displays the power distribution link diagram of the smart module. You
can view the device information and parameters of power distribution devices.
Cooling
iCooling: Displays the cooling full link diagram. You can view the device
information and parameter information of cooling devices and track the energy
efficiency of cooling devices.
More
● More: Displays more functions. You can perform monitoring and maintenance
operations on devices, such as device monitoring, software upgrade,
parameter synchronization, and layout adjustment.
● Monitor: Displays the categories and lists of all devices. You can view real-
time data or active alarms of a device, such as basic information, running
information, and temperature information.
Setting
b. Open the Huawei AppGallery app, search for FusionModule, and tap
Install.
● Scan the QR code to download and install the app.
Scan the QR code on Maintenance > APP Obtaining on the ECC800-pro
WebUI, and download and install the app as prompted.
1. Obtain the app software installation package from Huawei technical support
website.
– For enterprise users:
i. Log in to https://support.huawei.com/enterprise.
ii. Search for DP*fm.apk.
iii. Choose Software & Tools.
iv. Download the DP_VxxxRxxxSPCxxx_fm.apk installation package of
the latest version.
– For carriers:
i. Log in to https://support.huawei.com.
ii. Search for DP*fm.apk.
iii. Click the Software & Tools tab, and then select Product Software
under Filter by Document Type.
iv. Download the DP_VxxxRxxxSPCxxx_fm.apk installation package of
the latest version.
On the Software tab page, download the app software and digital signature
file.
After the downloading is complete, use the digital certificate and verification
tool available at Huawei technical support website to verify the digital
signature of the software package.
a. Contact technical support to obtain the OpenPGP Signature Verification
Guide package.
Prerequisites
You have obtained the Wi-Fi SSID, Wi-Fi password, and WLAN IP address of the
ECC800-Pro.
Procedure
1. On the PAD screen, tap the app icon.
NOTE
If you log in to the app for the first time, select I have read and accept to the above
statement carefully in the Privacy Statement dialog box, and click Accept.
2. On the app login screen, choose Setting > Network Connection. Select the
WiFi SSID set on the ECC800-Pro WebUI, and enter WiFi Password to log in.
3. On the app login screen, choose Setting > Communication IP Setting, set
the WLAN IP address of the ECC800-Pro, and tap OK.
NOTE
The default IP address is 192.168.245.10. Enter the actual WLAN IP address of the
ECC800-Pro.
Prerequisites
● You have obtained the user name and password for ECC800-Pro WebUI login.
● The PAD is connected to the ECC800-Pro over WiFi.
Procedure
1. On the app login screen, set User Name and Password, and tap Log In.
NOTE
● The user name and password for logging in to the app are the same as those for
logging in to the ECC800-Pro WebUI.
● After logging in to the app for the first time, change the initial password and keep
the password secure. You are advised to change the password periodically (every
three months) according to the password requirements.
● A maximum of three users can log in to the ECC800-Pro at the same time. If you
need to log in to the ECC800-Pro WebUI and app at the same time, you are
advised to use different user names to log in. Otherwise, you will be forced to log
out of either of them.
Prerequisites
● You have logged in to the app as an administrator. For details, see 1.2.2.2
Logging In to the App Using the Account and Password.
● Before recording face data by importing a file, you need to obtain the face
data file.
Procedure
● The face data is used only for the facial recognition function and will not be used
for other purposes. The face data is encrypted during transmission in the ECC800-
Pro to ensure that the personal data of users is fully protected.
● You can tap to modify associated users and tap to delete face data.
Prerequisites
You have recorded your facial data. For details, see 1.2.2.3.1 Recording Facial
Information.
Procedure
NOTE
● If facial recognition is performed by default when you log in to the app, you can
tap Password Login in the lower right corner of the facial recognition screen to
switch to the password login mode.
Prerequisites
● You have recorded your facial data. For details, see 1.2.2.3.1 Recording Facial
Information.
● Enable Default Facial Recognition Login if needed. For details, see 1.2.2.3.2
(Optional) Enabling Default Facial Recognition Login.
Procedure
1. On the app login screen, tap Face Login, and align your face with the circle
on the app screen. After the recognition is successful, log in to the app.
Prerequisites
You have recorded face data as an administrator.
Procedure
On the home screen of the app, tap in the upper left corner, choose Face in
the lower right corner, and align your face with the circle on the screen. After the
recognition is successful, the access control system is opened.
Prerequisites
● You have logged in to the app as an administrator.
● The AC actuator and FusionModule actuator have been connected to the
ECC800-Pro and are running properly.
Procedure
1. Choose More > Monitor.
2. On the Monitor screen, perform related steps based on the device type.
– AC actuator:
i. Choose Aisle > AC Actuator Group, select an AC actuator, and tap
Operation Control.
ii. On the Operation Control tab, set Route 1 control mode to Light,
and Set light Mode to Manual. Tap Submit.
– FusionModule actuator:
Choose Aisle > FusionModule Actuator Group, select a FusionModule
actuator, and tap Light Control.
NOTE
This operation can be performed only when Set light Mode of the FusionModule
actuator has been set to Manual on the ECC800-Pro WebUI.
Prerequisites
● You have logged in to the app as an administrator.
● The skylight actuator and FusionModule actuator have been connected to the
ECC800-pro and are running properly.
Procedure
1. Choose More > Monitor.
2. On the Monitor screen, choose Aisle > Skylight Actuator Group or Aisle >
FusionModule Actuator Group. Select a skylight actuator or FusionModule
actuator, and tap Remote Scuttle Opening.
3. In the dialog box that is displayed, enter the password for the current
administrator and tap Confirm.
NOTE
Prerequisites
● You have logged in to the app as an administrator.
● The access actuator and FusionModule actuator have been connected to the
ECC800-Pro and are running properly.
Procedure
1. Choose More > Monitor.
2. On the Monitor screen, choose Aisle > Access Actuator Group or Aisle >
FusionModule Actuator Group. Select an access actuator or FusionModule
actuator, and tap Remote Door Opening.
3. In the dialog box that is displayed, enter the password for the current
administrator and tap Confirm.
NOTE
Prerequisites
● You have logged in to the app as an administrator.
● The smart cooling device has been connected to the ECC800-Pro and is
running properly.
● The permission to control smart cooling devices has been enabled. For details,
see 1.2.7.2 Enabling the Permission to Control Smart Cooling Devices.
Procedure
1. Choose More > Monitor.
2. On the Monitor screen, tap Cooling, select a smart cooling device, and tap
ON or OFF.
3. In the dialog box that is displayed, enter the password for the current
administrator and tap Confirm.
NOTE
Prerequisites
● You have logged in to the app as an administrator.
● In the busway power distribution scenario, the general input unit or power
distribution unit of the busway has been connected to the ECC800-Pro. The
power supply branch has been configured and associated, and is running
properly.
Procedure
1. Choose More > Monitor.
2. On the Monitor screen, tap Power Distribution, select the general input unit
or power distribution unit, and tap Running Parameters.
3. On the Running Parameters screen, set parameters and tap SUBMIT.
Prerequisites
● You have logged in to the app as an administrator.
● The subrack information has been created on the ECC800-Pro, and the device
layout is configured.
NOTE
● The initial layout of the iFind depends on the floor layout of the ECC800-Pro home
screen.
● The iFind layout adjustment function can be used to adjust device positions but cannot
be used to add or delete device information.
● Administrators can use the editing function of the iFind to adjust the device location
and power configuration in the plan view. Operators can only view the iFind layout and
operate devices in blink mode.
Procedure
1. Choose More > iFind.
2. On the iFind screen, perform operations as required.
– Select a device and tap Blink to perform blink control.
– Tap Edit in the upper right corner, adjust the device location, change the
device name, and configure the battery level. Tap Save.
NOTE
Prerequisites
● You have logged in to the app as an administrator.
● The upgrade software package has been uploaded to the PAD or USB flash
drive.
NOTE
Procedure
1. Choose More > Software Upgrade.
2. On the Software Upgrade tab, tap Create Tasks.
3. On the Create Tasks screen, select the upgrade mode, select the device
upgrade software package in File Upload, and tap Upload.
● You can select a feature or Board Support Package (BSP) program to upgrade it
separately.
● If an upgrade feature package is not required, tap Delete in the Operation column
to delete it.
● The ECC800-Pro upgrade package includes the ECC800 software upgrade program
and BSP software upgrade program. After the upgrade using the ECC800 upgrade
package, the ECC800-Pro system will restart.
Prerequisites
● You have logged in to the app as an administrator.
● Devices that can store data locally, such as the integrated PDF, integrated
UPS, and smart cooling product, have been connected.
Procedure
1. Choose More > Export Data.
2. On the Export Data screen, tap Device Data, Configuration File, Historical
Data, or Device Log, set parameters as prompted, and tap Export.
NOTE
● To ensure data security, you need to enter the encryption password. Keep the
password secure so that the data package can be decompressed properly.
● If a USB flash drive is inserted into the ECC800-Pro, you can select the USB flash
drive as the export location and save the exported data to the USB flash drive.
Device logs can only be exported locally.
3. After the export is successful, tap Confirm in the dialog box that is displayed.
NOTE
If device logs are exported, you can tap Share to share the exported device logs with
other terminals.
Prerequisites
● You have logged in to the app as an administrator.
● The configuration file has been exported. For details, see 1.2.5.3 Exporting
System Data.
Procedure
1. Choose More > Import Data.
2. On the Import Data screen, set parameters related to data import and tap
Import.
NOTE
The encryption password is set during data export. Therefore, when selecting a
configuration file, you need to enter the encryption password of the configuration file
so that the configuration file can be imported.
3. After the import is successful, tap CONFIRM in the dialog box that is
displayed.
NOTE
The ECC800-Pro will restart after you import the configuration file.
Prerequisites
● You have logged in to the app as an administrator.
● The ECC800-Pro and devices have been powered on and are running properly.
● The target device has been replaced and is displayed in the device monitoring
list.
Procedure
1. Choose More > Parameter Sync.
2. On the Parameter Sync screen, select the source device and target device,
and tap Confirm.
NOTICE
Prerequisites
● You have logged in to the app as an administrator.
● Devices of the smart modules, PowerPODs, and preset modules have been
connected to the corresponding ECC800-Pro.
Procedure
1. Choose More > Perf Data.
2. On the Perf Data screen, choose the Battery Cure, Bat Discharge Curve, or
General performance data tab.
3. On the Battery Cure, Bat Discharge Curve, or General performance data
tab, tap Setting Query Condition or in the upper right corner, set
search criteria, and tap OK.
Prerequisites
● You have logged in to the app as an administrator.
● An access control device, cabinet electronic lock, or fingerprint lock has been
connected, and access user management and access permission management
have been configured on the ECC800-Pro WebUI.
Procedure
1. Choose More > Operation Log.
2. On the Operation Log screen, view operation logs.
Prerequisites
● You have logged in to the app.
● An access control device, cabinet electronic lock, or fingerprint lock has been
connected, and access user management and access permission management
have been configured on the ECC800-Pro WebUI.
Procedure
1. Choose More > Access Event.
2. On the Access Event screen, view access control events.
Prerequisites
● You have logged in to the app as an administrator.
● The ECC800-Pro and devices have been powered on and are running properly.
Procedure
1. Choose More > Asset Details.
2. On the Asset Details screen, view device asset details such as e-labels of
system devices and other devices.
NOTE
To view details about the e-label of a device, tap E-label of the device.
Prerequisites
● You have logged in to the app.
● The ECC800-Pro and devices have been powered on and are running properly.
Procedure
1. Choose More > Device Version Info.
2. On the Device Version Info screen, view the hardware version and software
version of the device.
Prerequisites
You have logged in to the app as an administrator.
Procedure
1. Choose More > Network Parameter.
2. On the Network Parameter screen, view the network parameters of the PAD.
Procedure
CAUTION
If the PAD is steady on, the PAD screen and battery lifespan will be shortened.
Correctly set this parameter.
Prerequisites
You have logged in to the app as an administrator.
Procedure
3. In the Switch Control Center dialog box, tap on the right of High-
Risk Permission.
4. In the dialog box that is displayed, tap OK.
NOTE
● After the High-Risk Permission switch is turned on, if an administrator logs out of
the app and then logs in again, the switch is turned off by default.
Procedure
Prerequisites
Before turning on the iCooling switch, ensure that the smart module meets the
following configuration requirements:
● A cabinet-level temperature sensor has been installed.
● Electrical energy has been configured for the IT cabinet, network cabinet, and
smart cooling product.
● At least one cold aisle T/H sensor is installed for each smart cooling product.
Procedure
Procedure
Home
Display the smart module layout information, including the power, power
consumption, environment, cooling capacity, PUE, load rate, space, temperature,
power distribution, cooling, and alarm overview.
Device Monitoring
Setting
Procedure
1. On the smart screen, choose Settings > More > Languages.
1. Install the Huawei AppGallery app. If you have installed the app, go to 2.
2. Open the Huawei AppGallery app, search for FusionModule, and tap Install.
1. Obtain the app software installation package from Huawei technical support
website.
– For enterprise users:
i. Log in to https://support.huawei.com/enterprise.
ii. Search for DP*fm.apk.
iii. Choose Software & Tools.
iv. Download the DP_VxxxRxxxSPCxxx_fm.apk installation package of
the latest version.
– For carriers:
i. Log in to https://support.huawei.com.
ii. Search for DP*fm.apk.
iii. Click the Software & Tools tab, and then select Product Software
under Filter by Document Type.
iv. Download the DP_VxxxRxxxSPCxxx_fm.apk installation package of
the latest version.
On the Software tab page, download the app software and digital signature
file.
After the downloading is complete, use the digital certificate and verification
tool available at Huawei technical support website to verify the digital
signature of the software package.
a. Contact technical support to obtain the OpenPGP Signature Verification
Guide package.
Procedure
1. On the home smart screen, choose Settings > More > Ethernet.
2. On the Ethernet screen, turn on the switch on the right of Ethernet and set
the smart screen IP address.
Prerequisites
You have obtained the NetEco NMS IP address and ECC800-Pro WLAN IP address.
Procedure
1. On the home smart screen, tap the app icon.
NOTE
If you log in to the app for the first time, select I have read and accept to the above
statement carefully in the Privacy Statement dialog box, and click Accept.
2. On the app login screen, choose Setting > Communication IP Setting.
3. In the Communication IP Setting dialog box, set the NetEco NMS IP address,
large screen name, and ECC800-Pro WLAN IP address, and tap Confirm.
NOTE
The default IP address is 192.168.245.10. Enter the actual WLAN IP address of the
ECC800-Pro.
Prerequisites
● You have obtained the NetEco NMS IP address and ECC800-Pro WLAN IP
address.
● You have obtained the predefined large-screen information created on the
NetEco and the user name and password for accessing the third-party system.
Procedure
1. On the home smart screen, tap the app icon.
NOTE
If you log in to the app for the first time, select I have read and accept to the above
statement carefully in the Privacy Statement dialog box, and click Accept.
2. On the app login screen, choose Setting > Communication IP Setting.
3. In the Communication IP Setting dialog box, set the NetEco NMS IP address
and screen name.
4. Tap Select the NMS. In the Use a third party NMS account to log in dialog
box, enter the third-party username and password created on the NetEco, and
tap CONFIRM.
5. In the Please choose NMS large screen dialog box, select one of the
predefined large-screen lists configured on the NetEco, and tap CONFIRM.
6. Add a smart module based on site requirements and set the IP address for the
smart module to connect to the corresponding ECC800.
NOTE
● The default IP address is 192.168.245.10. Enter the actual WLAN IP address of the
ECC800-Pro.
7. Tap in the lower left corner of the home screen. In the displayed device
floating disk, tap the corresponding smart module and NetEco predefined
large screen to switch between the display screens.
NOTE
Each time you switch to a screen, the corresponding login screen is automatically
displayed.
8. On the displayed login screen, enter the user name and password of the
ECC800 or log in to the ECC800 using facial recognition to view the smart
module information.
NOTE
● When you log in to the NetEco predefined large screen for the first time, you need
to enter the user name and password for logging in to the NetEco WebUI.
● When a user records the same face in multiple smart modules, the user can log in
to one smart module and then switch to the other smart module without login
again.
Prerequisites
The smart screen has been connected to the ECC800-Pro over a network cable.
Procedure
1. On the smart screen, tap the app icon.
NOTE
If you log in to the app for the first time, select I have read and accept to the above
statement carefully in the Privacy Statement dialog box, and click Accept.
2. On the app login screen, choose Setting > Greeting Settings.
3. In the Greeting Settings dialog box, enter the greeting information, and then
tap OK.
Prerequisites
● You have obtained the user name and password for ECC800-Pro WebUI login.
● The smart screen has been connected to the ECC800-Pro over a network
cable.
Procedure
1. On the app login screen, set User Name and Password, and tap Log In.
NOTE
● The user name and password for logging in to the app are the same as those for
logging in to the ECC800-Pro WebUI.
● After logging in to the app for the first time, change the initial password and keep
the password secure. You are advised to change the password periodically (every
three months) according to the password requirements.
● A maximum of three users can log in to the ECC800-Pro at the same time. If you
need to log in to the ECC800-Pro WebUI and app at the same time, you are
advised to use different user names to log in. Otherwise, you will be forced to log
out of either of them.
Prerequisites
● You have logged in to the app as an administrator. For details, see 2.2.3.2
Logging In to the App Using the Account and Password.
● Before recording face data by importing a file, you need to obtain the face
data file.
Procedure
5. In the Enroll Face dialog box, select a recording mode based on site
requirements.
● The facial data is used only for configuring the facial recognition function and is
not used for other purposes. The facial data is encrypted during transmission in the
ECC800-Pro to ensure that the personal data of users is fully protected.
● You can tap to modify associated users and tap to delete facial data.
Prerequisites
You have recorded your facial data. For details, see 2.2.3.3.1 Recording Facial
Information.
Procedure
3. In the Switch Control Center dialog box, tap on the right of Default
Facial Recognition Login.
NOTE
● If facial recognition is performed by default when you log in to the app, you can
tap Password Login in the lower right corner of the facial recognition screen to
switch to the password login mode.
● To disable the Default Facial Recognition Login function, tap on the right
of Default Facial Recognition Login.
4. In the Switch Control Center dialog box, tap OK.
Prerequisites
● You have recorded your facial data. For details, see 2.2.3.3.1 Recording Facial
Information.
● Enable Default Facial Recognition Login if needed. For details, see 2.2.3.3.2
(Optional) Enabling Default Facial Recognition Login.
Procedure
1. On the app login screen, tap Face Login, and align your face with the circle
on the app screen. After the recognition is successful, log in to the app.
Prerequisites
● Multiple modules have been configured to share the smart screen. For details,
see 2.2.3.1.3 Setting the Communication IP Address (Smart Screen Shared
by Multiple Modules).
● You have logged in to the app.
Procedure
1. On the home smart screen, tap in the lower left corner.
2. In the displayed device floating disk, tap the corresponding smart module and
NetEco predefined large screen to switch between the display screens.
NOTE
Each time you switch to a screen, the corresponding login screen is automatically
displayed.
3. On the displayed login screen, enter the user name and password of the
ECC800-Pro. The corresponding smart module information is displayed.
NOTE
● When you log in to the NetEco predefined large screen for the first time, you need
to enter the user name and password for logging in to the NetEco WebUI.
● When a user records the same face in multiple smart modules, the user can log in
to one smart module and then switch to the other smart module without login
again.
Prerequisites
● You have logged in to the app as an administrator.
● The AC actuator and FusionModule actuator have been connected to the
ECC800-Pro and are running properly.
Procedure
1. On the home screen, tap Monitor in the lower right corner.
2. On the Monitor screen, perform related steps based on the device type.
– AC actuator:
i. Choose Aisle > AC Actuator Group, select an AC actuator, and tap
Runing Parameters on the right of the AC actuator.
ii. On the Operation Control tab, set Route 1 control mode to Light,
and Set light Mode to Manual. Tap Submit.
This operation can be performed only when Set light Mode of the FusionModule
actuator has been set to Manual on the ECC800-Pro WebUI.
Prerequisites
● You have logged in to the app as an administrator.
● The skylight actuator and FusionModule actuator have been connected to the
ECC800-pro and are running properly.
Procedure
1. On the home screen, tap Monitor in the lower right corner.
2. On the Monitor screen, choose Aisle > Skylight Actuator Group or Aisle >
FusionModule Actuator Group. Select a skylight actuator or FusionModule
actuator, and tap Remote Scuttle Opening.
3. In the dialog box that is displayed, enter the password for the current
administrator and tap Confirm.
NOTE
Prerequisites
● You have logged in to the app as an administrator.
● The access actuator and FusionModule actuator have been connected to the
ECC800-Pro and are running properly.
Procedure
1. On the home screen, tap Monitor in the lower right corner.
2. On the Monitor screen, choose Aisle > Access Actuator Group or Aisle >
FusionModule Actuator Group. Select an access actuator or FusionModule
actuator, and tap Remote Door Opening.
3. In the dialog box that is displayed, enter the password for the current
administrator and tap Confirm.
NOTE
2.2.5.4 Unlocking
If O&M personnel forget to bring the cabinet lock keys and need to open the
cabinet electronic lock, administrators can unlock the cabinet electronic lock.
Unlocking will open the electronic lock of the cabinet. Exercise caution when
performing this operation.
Prerequisites
● You have logged in to the app as an administrator.
● The access actuator and FusionModule actuator have been connected to the
ECC800-Pro and are running properly.
Procedure
1. On the home screen, tap Monitor in the lower right corner.
2. On the Monitor screen, choose Cabinet > IT Cabinet > Cabinet Electronic
Lock, select the cabinet electronic lock, and tap Remote Unlocking.
3. In the dialog box that is displayed, enter the password for the current
administrator and tap Confirm.
NOTE
Prerequisites
● You have logged in to the app as an administrator.
● The smart cooling device has been connected to the ECC800-Pro and is
running properly.
● The permission to control smart cooling devices has been enabled. For details,
see 2.2.8.1 Enabling the Permission to Control Smart Cooling Devices.
Procedure
1. On the home screen, tap Monitor in the lower right corner.
2. On the Monitor screen, tap Cooling, select the smart cooling device, and tap
ON or OFF on the right of the smart cooling device.
3. In the dialog box that is displayed, enter the password for the current
administrator and tap Confirm.
NOTE
Prerequisites
● You have logged in to the app as an administrator.
● In the busway power distribution scenario, the general input unit or power
distribution unit of the busway has been connected to the ECC800-Pro. The
power supply branch has been configured and associated, and is running
properly.
Procedure
1. On the home screen, tap Monitor in the lower right corner.
2. On the Monitor screen, tap Power Distribution, select the general input unit
or power distribution unit, and tap Running Parameters.
3. On the Running Parameters screen, set parameters and tap SUBMIT.
Prerequisites
● You have logged in to the app as an administrator.
● The subrack information has been created on the ECC800-Pro, and the device
layout is configured.
NOTE
● The initial layout of the iFind depends on the floor layout of the ECC800-Pro home
screen.
● The iFind layout adjustment function can be used to adjust device positions but cannot
be used to add or delete device information.
● Administrators can use the editing function of the iFind to adjust the device location
and power configuration in the plan view. Operators can only view the iFind layout and
operate devices in blink mode.
Procedure
1. On the home screen, choose Functions > iFind in the lower right corner.
2. On the iFind screen, perform operations as required.
– Select a device and tap Blink to perform blink control.
– Tap Edit in the upper right corner, adjust the device location, change the
device name, and configure the battery level. Tap Save.
NOTE
Prerequisites
● You have logged in to the app as an administrator.
● The upgrade software package has been uploaded to the smart screen or USB
flash drive.
NOTE
Procedure
1. On the home screen, choose Functions > Upgrade in the lower right corner.
2. On the Create Tasks screen, select the upgrade mode, select the device
upgrade software package in File Upload, and tap Upload.
● You can select a feature or Board Support Package (BSP) program to upgrade it
separately.
● If an upgrade feature package is not required, tap Delete in the Operation column
to delete it.
● The ECC800-Pro upgrade package includes the ECC800 software upgrade program
and BSP software upgrade program. After the upgrade using the ECC800 upgrade
package, the ECC800-Pro system will restart.
Prerequisites
● You have logged in to the app as an administrator.
● Devices that can store data locally, such as the integrated PDF, integrated
UPS, and smart cooling product, have been connected.
Procedure
1. On the home screen, choose Functions > Export Data in the lower right
corner.
2. On the Export Data screen, tap Device Data, Configuration File, Historical
Data, or Device Log, set parameters as prompted, and tap Export.
NOTE
● To ensure data security, you need to enter the encryption password. Keep the
password secure so that the data package can be decompressed properly.
● If a USB flash drive is inserted into the ECC800-Pro, you can select the USB flash
drive as the export location and save the exported data to the USB flash drive.
Device logs can only be exported locally.
3. After the export is successful, tap Confirm in the dialog box that is displayed.
NOTE
If device logs are exported, you can tap Share to share the exported device logs with
other terminals.
Prerequisites
● You have logged in to the app as an administrator.
● The configuration file has been exported. For details, see 2.2.6.3 Exporting
System Data.
Procedure
1. On the home screen, choose Functions > Import Data in the lower right
corner.
2. On the Import Data screen, set parameters related to data import and tap
Import.
NOTE
The encryption password is set during data export. Therefore, when selecting a
configuration file, you need to enter the encryption password of the configuration file
so that the configuration file can be imported.
3. After the import is successful, tap CONFIRM in the dialog box that is
displayed.
NOTE
The ECC800-Pro will restart after you import the configuration file.
Prerequisites
● You have logged in to the app as an administrator.
● The ECC800-Pro and devices have been powered on and are running properly.
● The target device has been replaced and is displayed in the device monitoring
list.
Procedure
1. On the home screen, choose Functions > Synchronize in the lower right
corner.
2. On the Parameter Sync screen, select the source device and target device,
and tap Confirm.
NOTICE
Prerequisites
● Devices of the smart modules, PowerPODs, and preset modules have been
connected to the corresponding ECC800-Pro.
● The policy for displaying performance data has been set. For details, see
2.2.8.5 Setting the Policy for Displaying Performance Data.
Procedure
1. On the home screen, choose Functions > Perf Data in the lower right corner.
2. On the Perf Data screen, tap on the right of General Performance Data,
Battery Discharge, or Battery Curve.
3. In the General Performance Data Setting, Battery Discharge Setting, or
Battery Curve Setting dialog box, set search criteria and tap FINISH.
Prerequisites
● You have logged in to the app as an administrator.
● The ECC800-Pro and devices have been powered on and are running properly.
Procedure
1. On the home screen, choose Functions > Asset&Version in the lower right
corner.
2. On the Asset&Version screen, view asset details and device version
information.
NOTE
To view details about the e-label of a device, tap E-label of the device.
Prerequisites
● You have logged in to the app as an administrator.
● An access control device, cabinet electronic lock, or fingerprint lock has been
connected, and access user management and access permission management
have been configured on the ECC800-Pro WebUI.
Procedure
1. On the home screen, choose Functions > Log&Access in the lower right
corner.
2. On the Log&Access screen, view operation logs and access control events.
Prerequisites
You have logged in to the app as an administrator.
Procedure
1. On the home screen, choose Functions > Energy in the lower right corner.
2. On the Energy screen, view the energy efficiency information of cabinets and
track the energy efficiency of devices.
Prerequisites
You have logged in to the app as an administrator.
Procedure
3. In the Switch Control Center dialog box, tap on the right of High-
Risk Permission.
NOTE
● After the High-Risk Permission switch is turned on, if an administrator logs out of
the app and then logs in again, the switch is turned off by default.
● To turn off the High-Risk Permission switch, tap on the right of High-
Risk Permission.
4. In the dialog box that is displayed, tap OK.
5. In the Switch Control Center dialog box, tap CONFIRM.
Prerequisites
Before turning on the iCooling switch, ensure that the smart module meets the
following configuration requirements:
Procedure
3. In the Switch Control Center dialog box, tap on the right of iCooling.
NOTE
Procedure
Procedure
Procedure
Prerequisites
You have obtained the NetEco NMS IP address and ECC800-Pro WLAN IP address.
Procedure
3. In the Communication IP Setting dialog box, set the NetEco NMS IP address,
large screen name, or ECC800-Pro WLAN IP address, and tap Confirm.
NOTE
The default IP address is 192.168.245.10. Enter the actual WLAN IP address of the
ECC800-Pro.
Procedure
3. In the Greeting Settings dialog box, enter the greeting information, and then
tap OK.
Procedure
3. In the Big Screen Location Setting dialog box, set the smart screen position
based on the actual installation position, and tap CONFIRM.
3 FAQs
Login failed because the The password has 1. Log in to the ECC800-
password has expired expired. Pro WebUI as an
administrator.
2. Choose Maintenance
> User Management.
The user
management page is
displayed.
3. Select the user to be
modified and click
Modify. On the page
that is displayed, reset
the login password.
Login failed The face token has Check whether the face
expired. data has been recorded
in the smart module.
Possible Causes
Two different types of power distribution devices are connected to the
FusionModule2000 or the current power distribution mode is a non-standard
power distribution solution. As a result, the power distribution link cannot be
properly displayed on the app.
Solution
Verify that only one type of power distribution device is connected to the
FusionModule2000 and the current power distribution mode is the standard power
distribution solution.
Possible Causes
Assets corresponding to U spaces are not allocated on the NetEco.
Solution
Allocate the assets of the corresponding U space on the NetEco. For details, see
"Allocating a Device" in NetEco Product Documentation (Data Center).
A
APP Application
B
BIM Battery Interface Module
BSP Board Support Package
E
ECC Energy Control Center
I
IP Internet Protocol
P
PDU Power Distribution Unit
PUE Power Usage Effectiveness
S
SSID Service Set Identifier
U
UPS Uninterruptible Power System
W
WiFi Wireless Fidelity