125949853
125949853
125949853
ABSTRACT
This study evaluates the performance of a residential air conditioner (A/C) using R32 as a retrofit for R410A. One of
the biggest challenges in the retrofitting is to determine the ideal mass of refrigerant, which eventually lead to optimum
performance of the system. The theoretical mass of refrigerant charging in this retrofitting analysis was determined
using the density ratio of alternative (R32) to the existing (R410A) refrigerants. To achieve the optimum performance,
the mass of refrigerant charging was varied between 90, 95, 100 and 105% from the theoretical mass of refrigerant
charging. The experiments were carried out using a 2.5 kW split type A/C. The results show that the replacement of
R410A with R32 decreases the COP at all refrigerants charging. The highest COP of A/C with R32 was achieved during
mass of refrigerant charging of 95%. In this condition, the COP only decreased by 5.1%. The decrement in COP is
caused by an increase in input power of the A/C. Consequently, it is not recommended replacing R410A with R32 in
the A/Cs that originally is designed for R410A.
they concluded that the replacement of R410A with R32 condition that is the indoor temperature does not change
in a domestic refrigerator decreased the system 0.3oC for 15 minutes.
performance. The cooling capacity and the input power are
Table 1. Refrigerant properties [1,2] calculated using equation:
Normal (1)
Critical GWP
Refrige- Boiling
Composition Temperature (100-
rant Point (2)
(oC) year)
(oC)
R22 Pure fluid -40.8 96.2 1700 where,
Q = cooling capacity, Kw
R32(50%):
R410A -51.5 72.5 1725
R125(50%) = mass flow rate of indoor air, kg/s
R134a Pure fluid -26.1 101.1 1430 h1 = specific enthalpy of indoor air, kJ/kg
R32 Pure fluid -48.3 78.1 675
h2 = specific enthalpy of leaving air on the
Different results obtained by Xu et al. [11]. They cooling coil, kJ/kg
reported that the use of R32 in a vapor-injected heat
W = input power, kW
pump increased the cooling capacity and the COP by
10% and 9% compared to R410A. Their study also V = electric voltage, V
concluded that to enhance the system performance, the
I = electric current, A
R32 can be utilized as a refrigerant alternative to replace
R410A on the heat pump. Furthermore, the coefficient of performance (COP) is
calculated using equation,
In spite of R32 has a low GWP, however scientific
papers that discuss R32 as a retrofit for R410A in
(3)
residential A/Cs are still limited. Therefore, it is the aim
of the study to obtain the ideal mass of refrigerant
charging of R32, when it is used as a retrofit for R410A The COP reduction due to drop-in replacement from
on the split-type A/C. R410A to R32 is calculated using equation,
(4)
2. METHODOLOGY
Experimental study was carried out on a split type air The values of h1 and h2 are obtained using
conditioner with the cooling capacity of 2.4 kW, which psychrometric chart as shown in Figure 1. Where, Tdb_1
originally was designed for R410A. The first test was and Tdb_1 are dry bulb temperatures of leaving air on the
carried out in the A/C with 750 grams of R410A. Then, cooling coil and indoor air, respectively.
the refrigerant of R410A was evacuated and replaced by
R32 for four different mass of refrigerant charging. Four
parameters will be measured during this experimental
study, i.e., temperature, pressure, electric voltage and
electric current.
Densities of R32 and R410A at temperature of 5oC on
the saturated vapor are 25.769 and 34.843 kg/m3,
respectively. As a result, the density ratio R32 to R410A
is 0.743. It means that when the R410A is replaced with
R32, the mass of refrigerant charging is 750 g × 0.743 =
557.3 g. The mass of refrigerant of 557.3 gram in this
study is defined as 100% of refrigerant charging or
theoretical refrigerant charging. Furthermore, the next
three masses of refrigerant charging of R32 with 90, 95
and 105% from theoretical value are calculated at 501.6,
529.4 and 585.2 grams, respectively.
Figure 1 Air process in the psychrometric chart to
During experiments, the indoor and outdoor
determine the cooling capacity
temperatures are kept constant, which is 5oC and 34oC,
respectively. The data are recorded at steady state
168
Advances in Engineering Research, volume 198
1,4
3. RESULTS AND DISCUSSION
1,3
Figure 2 illustrates the correlation between cooling
2,6
2,5 substitution of R410A with R32 reduces the COP due to
2,5
2,4 increase in input power. Although in Figure 2 shows that
2,4 at 95%, the cooling capacity of R32 is higher than that of
2,3 R410A, but the increment of input power at this charging
2,3
2,2 (95%) is higher than that of the increment of the cooling
2,1 2,2 capacity. It causes a decrease in COP.
2,0 30
85% 90% 95% 100% 105% 110%
Discharge Pressure (bar)
28
Refrigerant charge amount of R32 26 25,2
24,4
23,8
24 23
Figure 2 The variation of cooling capacity for various
mass of refrigerant charging of R32 22
20
18
85% 90% 95% 100% 105% 110%
169
Advances in Engineering Research, volume 198
2,8
25
170