Eaton-256276-EASY822-DC-TCX-en_GB

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

DATASHEET - EASY822-DC-TCX

Control relay, 24 V DC, 12DI(4AI), 8DO-Trans, 1AO, time, expandable,


easyNet

Part no. EASY822-DC-TCX


Catalog No. 256276

EL-Nummer 4520972
(Norway)
Delivery program
Basic function easy800 (expandable, easyNet)

Description Expandable: Digital/analog inputs/outputs and AS-Interface, PROFIBUS-DP,


CANopen®, DeviceNet bus systems
Bus system easyNet on board
customized laser inscription or delivery with user program possible with EASY-
COMBINATION-* product (article No. 2010781)

Inputs
Digital 12

of which can be used as analog 4

Outputs
Outputs Number 9

Transistor 8

Additional features
Real time clock #

Expansions Expandable
Networkable (easyNet)

Supply voltage 24 V DC

Software EASY-SOFT-PRO

Technical data
General
Standards EN 55011, EN 55022, IEC/EN 61000-4, IEC 60068-2-6, IEC 60068-2-27

Approvals CSA
UL
EAC

Dimensions (W x H x D) mm 107.5 x 90 x 72 (6 PE)

Weight kg 0.3

Mounting Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1
(accessories)
Terminal capacities
Solid mm
2 0.2/4 (AWG 22 - 12)

Flexible with ferrule mm


2 0.2/2.5 (AWG 22 - 12)

Standard screwdriver mm 0.8 x 3.5

Max. tightening torque Nm 0.6


Climatic environmental conditions
Operating ambient temperature °C In accordance with IEC 60068-2-1, -25 - +55

Condensation Take appropriate measures to prevent condensation

Storage ϑ °C In accordance with IEC 60068-2-1, -2, -14


-40 - +70

relative humidity % in accordance with IEC 60068-2-30, IEC 60068-2-78


5 - 95

Air pressure (operation) hPa 795 - 1080


Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4) IP20

Vibrations Hz In accordance with IEC 60068-2-6


constant amplitude 0.15 mm: 10 - 57
constant acceleration 2 g: 57 - 150

Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms Impacts 18

Drop to IEC/EN 60068-2-31 Drop height mm 50

Free fall, packaged (IEC/EN 60068-2-32) m 1

11/04/2019 Eaton 256276 ED2019 V61.0 EN 1/8


Mounting position Vertical or horizontal
Electromagnetic compatibility (EMC)
Overvoltage category/pollution degree III/2

Electrostatic discharge (ESD)

applied standard according to IEC EN 61000-4-2

Air discharge kV 8

Contact discharge kV 6

Electromagnetic fields (RFI) to IEC EN 61000-4-3 V/m 0.8 - 1.0 GHz: 10


1.4 - 2 GHz: 3
2.0 - 2.7 GHz: 1

Radio interference suppression EN 55011 Class B

Burst kV according to IEC/EN 61000-4-4

power pulses (Surge) according to IEC/EN 61000-4-5


1 kV (supply cables, symmetrical)

Immunity to line-conducted interference to (IEC/EN 61000-4-6) V 10


Insulation resistance
Clearance in air and creepage distances EN 50178, UL 508, CSA C22.2, No. 142

Insulation resistance EN 50178


Back-up of real-time clock
Back-up of real-time clock

① Backup time (hours) with fully charged double layer capacitor


② Service life (years)

Accuracy of real-time clock to inputs s/day typ. ± 2 (± 0.2 h⁄Year)

depending on ambient air temperature fluctuations of up to ± 5 s/day (± 0.5 h⁄year)


are possible
Repetition accuracy of timing relays
Accuracy of timing relays (of values) % ± 0.02

Resolution

Range “S” ms 5

Range “M:S” s 1

Range “H:M” min 1


Retentive memory
Write cycles of the retentive memory 12
10 (read⁄write cycles)
Power supply
Rated operational voltage Ue V 24 DC (-15/+20%)

Permissible range Ue 20.4 - 28.8 V DC

Residual ripple % ≦5

Siemens MPI, (optional) yes

Input current 140 mA at Ue

Voltage dips ms ≤ In accordance with IEC 61131-2


≤ 20

Fuse A ≧ 1A (T)

Power loss P W Normally 3.4


Digital inputs 24 V DC
Number 12

Inputs can be used as analog inputs 4 (I7, I8, I11, I12)

Potential isolation from power supply: no


between digital inputs: no
from the outputs: yes
to interface/memory card: no
to easyLink: no
to easyNet: yes

Rated operational voltage Ue V DC 24

Input voltage V DC Signal 0: ≦ 5 (I1 - I6, I9, I10, ≦ 8 (I7, I8, I11, I12)
Signal 1: ≧ 15 (I1 - I6, I9, I10), ≧ 8 (I7, I8, I11, I12)

Input current at signal 1 mA I1 - I6, I9, I10: 3.3 (at 24 V DC)


I7, I8, I11, I12: 2.2 (at 24 V DC)

Deceleration time ms 20 (0 -> 1/1 -> 0, Debounce ON)


normally 0.025 (0 -> 1/1 -> 0, Debounce OFF, I1 - I4)
normally 0.25 (0 -> 1/1 -> 0, Debounce OFF, I5, I6, I9, I10)
normally 0.15 (0 -> 1/1 -> 0, Debounce OFF, I7, I8, I11, I12)

11/04/2019 Eaton 256276 ED2019 V61.0 EN 2/8


Cable length m 100 (unshielded)

Frequency counter

Number 4 (I1, I2, I3, I4)

Counter frequency kHz ≦5

Pulse shape Square

Pulse pause ratio 1:1

Cable length m ≦ 20 (screened)

Incremental counter

Number of counter inputs 2 (I1 + I2, I3 + I4)

Counter frequency kHz ≦3

Pulse shape Square

Signal offset 90°

Pulse pause ratio 1:1

Rapid counter inputs

Number 4 (I1, I2, I3, I4)

Cable length m ≦ 20 (screened)

Counter frequency kHz ≦5

Pulse shape Square

Pulse pause ratio 1:1


Analog inputs
Number 4 (I7, I8, I11, I12)

Potential isolation from power supply: no


between digital inputs: no
from the outputs: yes
to interface/memory card: no
to easyLink: no
to easyNet: yes

Input type DC voltage

Signal range 0-10 V DC

Resolution 0.01 V analog


0.01 V digital
10 Bit (value 0 - 1023)

Input impedance kΩ 11.2

Accuracy of actual value

two devices from series % ±3

Within a single device % ± 2, (I7, I8, I11, I12) ± 0.12 V

Conversion time, analog/digital ms each CPU cycle

Input current mA <1

Cable length m ≦ 30, screened


Analog outputs
Number 1

Potential isolation from power supply: no


To the digital inputs: no
From the digital outputs: yes
to interface/memory card: yes
to easyNet: yes
to easyLink: yes

Output type DC voltage

Signal range 0-10 V DC

Max. output current A 0.01

Load resistance 1 kΩ

Overload and short-circuit protection Yes

Resolution 0.01 V DC analog


10 Bit (value 0 - 1023) digital

Recovery time µs 100

Accuracy

-25 °C - 55 °C % 2

25°C % 1

Conversion time, analog/digital ms each CPU cycle


Transistor outputs
Number 8

11/04/2019 Eaton 256276 ED2019 V61.0 EN 3/8


Rated operational voltage Ue V DC 24

Permissible range Ue 20.4 - 28.8 V DC

Residual ripple % 5

Supply current mA Norm./max. 18/32 at signal 0


24/44 at signal 1

Potential isolation from power supply: yes


From the inputs: yes
between digital inputs: no
to the interface: yes
to easyLink: yes
to easyNet: yes

Rated operational current at signal „1” DC per channel Ie A max. 0.5

Lamp load without Rv per channel W 3 (Q1 - Q4)


5 (Q5 - Q8)

Residual current on 0 signal per channel mA < 0.1

Max. output voltage V 2.5 (signal 0 at external load < 10 MΩ)


U = Ue - 1 V (signal 1 at Ie = 0.5 A)

Short-circuit protection Yes, electronic (Q1 - Q4), thermal (Q5 - Q8)

Short-circuit tripping current for Ra ≦ 10 mΩ A 0.7 ≦ Ie ≦ 2 per output


depending on number of active channels and their load

Total short-circuit current A 8

Peak short-circuit current A 16

Thermal cutout Yes

Max. operating frequency with constant resistive load Operations/


40000
h

Parallel connection of outputs

With resistive load, inductive load with external suppressor circuit, Group 1: Q1 to Q4
combination within a group Group 2: Q5 - Q8

Number of outputs max. 4

Max. total current A Group 1: Q1 - Q4

Inductive load to EN 60947-5-1

Without external suppressor circuit

T0.95 = 1 ms, R = 48 Ω, L = 16 mH

Utilization factor g 0.25

Duty factor % DF 100

Max. switching frequency f = 0.5 Hz (max. DF = 50 %) Operations1500

DC-13, T0.95 = 72 ms, R = 48 Ω, L = 1.15 H

Utilization factor g 0.25

Duty factor % DF 100

Max. switching frequency f = 0.5 Hz (max. DF = 50 %) Operations1500

T0.95 = 15 ms, R = 48 Ω, L = 0.24 H

Utilization factor g 0.25

Duty factor % DF 100

Max. switching frequency f = 0.5 Hz (max. DF = 50 %) Operations1500

With external suppressor circuit

Utilization factor g 1

Duty factor % DF 100

Max. switching frequency, max. duty factor OperationsDepending on the suppressor circuit
Supply voltage UAux
Power loss P W 3.4
Network easyNet
Data transfer rate/distance 1000 KBit/s, 6 m
500 KBit/s, 25 m
250 Kbit/s, 40 m
125 Kbit/s, 300 m
50 KBit/s, 300 m
20 KBit/s, 700 m
10 KBit/s, 1000 m
Lengths from 40 m can be obtained only with cables with reinforced cross-section
and terminal adapter.

Potential isolation from power supply POW: yes


From the inputs: yes
from the outputs: yes
to easyLink: yes
to the interface: yes

11/04/2019 Eaton 256276 ED2019 V61.0 EN 4/8


Bus termination (first and last station) yes

Terminal types RJ45, 8-polig

Terminal capacity up to 1000 m, < 16 mΩ/m: 1.5 (AWG: 16)


up to 600 m, < 26 mΩ/m: 0.75 - 0.8 (AWG: 18)
up to 600 m, < 26 mΩ/m: 0.5 - 0.6 (AWG: 20, 19)
up to 400 m, < 40 mΩ/m: 0.34 - 0.5 (AWG: 22, 21, 20)
up to 250 m, < 60 mΩ/m: 0.25 - 0.34 (AWG: 23, 22)
up to 175 m, < 70 mΩ/m: 0.13 (AWG: 26)
up to 40 m, < 140 mΩ/m: 1.5 (AWG: 16)

Design verification as per IEC/EN 61439


Technical data for design verification

Rated operational current for specified heat dissipation In A 0

Heat dissipation per pole, current-dependent Pvid W 0

Equipment heat dissipation, current-dependent Pvid W 0

Static heat dissipation, non-current-dependent Pvs W 3.4

Heat dissipation capacity Pdiss W 0

Operating ambient temperature min. °C -25

Operating ambient temperature max. °C 55

IEC/EN 61439 design verification

10.2 Strength of materials and parts

10.2.2 Corrosion resistance Meets the product standard's requirements.

10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.

10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.

10.2.3.3 Verification of resistance of insulating materials to abnormal heat Meets the product standard's requirements.
and fire due to internal electric effects

10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.

10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.

10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.

10.2.7 Inscriptions Meets the product standard's requirements.

10.3 Degree of protection of ASSEMBLIES Meets the product standard's requirements.

10.4 Clearances and creepage distances Meets the product standard's requirements.

10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.

10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.

10.7 Internal electrical circuits and connections Is the panel builder's responsibility.

10.8 Connections for external conductors Is the panel builder's responsibility.

10.9 Insulation properties

10.9.2 Power-frequency electric strength Is the panel builder's responsibility.

10.9.3 Impulse withstand voltage Is the panel builder's responsibility.

10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.

10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.

10.11 Short-circuit rating Is the panel builder's responsibility.

10.12 Electromagnetic compatibility Is the panel builder's responsibility.

10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.

Technical data ETIM 7.0


PLC's (EG000024) / Logic module (EC001417)

Electric engineering, automation, process control engineering / Control / Programmable logic control (SPS) / Logic module ([email protected] [AKE539014])

Supply voltage AC 50 Hz V 0-0

Supply voltage AC 60 Hz V 0-0

Supply voltage DC V 20.4 - 28.8

Voltage type of supply voltage DC

Switching current A 0.5

Number of analogue inputs 4

Number of analogue outputs 1

Number of digital inputs 12

11/04/2019 Eaton 256276 ED2019 V61.0 EN 5/8


Number of digital outputs 8

With relay output No

Number of HW-interfaces industrial Ethernet 0

Number of interfaces PROFINET 0

Number of HW-interfaces RS-232 0

Number of HW-interfaces RS-422 0

Number of HW-interfaces RS-485 0

Number of HW-interfaces serial TTY 0

Number of HW-interfaces USB 0

Number of HW-interfaces parallel 0

Number of HW-interfaces Wireless 0

Number of HW-interfaces other 3

With optical interface No

Supporting protocol for TCP/IP No

Supporting protocol for PROFIBUS No

Supporting protocol for CAN No

Supporting protocol for INTERBUS No

Supporting protocol for ASI No

Supporting protocol for KNX No

Supporting protocol for MODBUS No

Supporting protocol for Data-Highway No

Supporting protocol for DeviceNet No

Supporting protocol for SUCONET No

Supporting protocol for LON No

Supporting protocol for PROFINET IO No

Supporting protocol for PROFINET CBA No

Supporting protocol for SERCOS No

Supporting protocol for Foundation Fieldbus No

Supporting protocol for EtherNet/IP No

Supporting protocol for AS-Interface Safety at Work No

Supporting protocol for DeviceNet Safety No

Supporting protocol for INTERBUS-Safety No

Supporting protocol for PROFIsafe No

Supporting protocol for SafetyBUS p No

Supporting protocol for other bus systems Yes

Radio standard Bluetooth No

Radio standard WLAN 802.11 No

Radio standard GPRS No

Radio standard GSM No

Radio standard UMTS No

IO link master No

Redundancy No

With display No

Degree of protection (IP) IP20

Basic device Yes

Expandable Yes

Expansion device No

With timer Yes

Rail mounting possible Yes

Wall mounting/direct mounting Yes

Front build in possible No

Rack-assembly possible No

Suitable for safety functions No

Category according to EN 954-1 None

SIL according to IEC 61508 None

11/04/2019 Eaton 256276 ED2019 V61.0 EN 6/8


Performance level acc. EN ISO 13849-1 None

Appendant operation agent (Ex ia) No

Appendant operation agent (Ex ib) No

Explosion safety category for gas None

Explosion safety category for dust None

Width mm 107.5

Height mm 90

Depth mm 72

Approvals
Product Standards IEC/EN see Technical Data; UL 508; CSA C22.2 No. 142-M1987; CSA C22.2 No. 213-
M1987; CE marking

UL File No. E135462

UL Category Control No. NRAQ

CSA File No. 012528

CSA Class No. 2252-01 + 2258-02

North America Certification UL listed, CSA certified

Degree of Protection IEC: IP20, UL/CSA Type: -

Dimensions

Assets (links)
Declaration of CE Conformity
00002536
Instruction Leaflets
IL05013012Z2018_02
Manuals
MN04902001Z_DE (German)
MN04902001Z_EN (English)

Additional product information (links)


Instruction leaflet "easy control relays" IL05013012Z (AWA2528-1979)

Instruction leaflet "easy control relays" ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL05013012Z2010_11.pdf


IL05013012Z (AWA2528-1979)

Instruction leaflet "easy control relays" ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL05013012Z2018_02.pdf


IL05013012Z (AWA2528-1979)

Manual "easy800 control relays" MN04902001Z (AWB2528-1423)

Handbuch „Steuerrelais easy800“ ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN04902001Z_DE.pdf


MN04902001Z (AWB2528-1423) - Deutsch

11/04/2019 Eaton 256276 ED2019 V61.0 EN 7/8


Manual "easy800 control relays" MN04902001Z ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN04902001Z_EN.pdf
(AWB2528-1423) - English

f1=1454&f2=1179;Labeleditor http://applications.eaton.eu/sdlc?LX=11&amp

11/04/2019 Eaton Industries GmbH 8/8


http://www.eaton.eu
© 10/2019 by Eaton Industries GmbH
Eaton 256276 ED2019 V61.0 EN

You might also like