EASY LOGIC POWER AND ENERGY METERS Functions and Characteristics

EasyLogic
PM2000 series
The EasyLogic™ PM2000 multi-function power and energy meter

Offering all the measurement capabilities required to monitor and electrical installation in a single 96 x 96 mm unit, with LED or
LCD display options.

Applications
Cost management applications

• Bill checking to verify that you are only charged for the energy you use
• Aggregation of energy consumption, including WAGES, and cost allocation per area, per usage, per shift or
per time within the same facility
• Energy cost and usage analysis per zone, per usage or per time period to optimise energy usage

Network management applications

• Metering of electrical parameters to better understand the behaviour of your electrical distribution system
• Power quality analysis
PB115532

PLSED309005EN 1
EASY LOGIC POWER AND ENERGY METERS Functions and Characteristics

Introducing EasyLogic PM2000 series, next generation power meter which offers all
PB114325

the measurement capabilities required to monitor an electrical installation in a single


96 x 96 mm unit. PM2000 meters are available in LED and LCD display variants.

• PM2100 series:
–– LED display type: Intuitive navigation with self-guided, three buttons,
bright red colour LEDs of 14.2 mm height. Two columns of LEDs, one
on each side of the meter’s front panel indicates the parameter name
chosen for display

• PM2200 series:
–– LCD display type: Monochrome graphical LCD of 128 x 128 resolution
with viewable area of 67 x 62.5 mm lets the users read all three phase
measured values simultaneously. The bright anti-glare display features
large characters and powerful backlighting for easy reading even in
extreme lighting conditions and viewing angles. Intuitive menus, multi-
language text, icons and graphics create a friendly environment to
PM2000 series LED display meter
learn about your electrical network.

• Applications
–– Cost management:
–– Electrical installation remote monitoring
–– Energy accounting and balancing
–– Tenant and sub-billing
–– Panel instrumentation
–– Energy management

• Network management:
–– Power quality analysis: THD % and individual harmonics up to 15th and 31st
order
–– Measurement of True PF and Displacement PF
–– Recording Min/Max values of instantaneous parameters with date &
timestamp
–– Optional IO modules comprising either 2 Digital Inputs and 2 Outputs, or 2
Analogue Inputs and 2 Outputs for comprehensive WAGES monitoring
–– Calculates % unbalance for voltage & current
–– Embedded 2 digital inputs and 2 digital outputs in PM2125 and PM2225
meters
Feature selection
• Main characteristics:
Commercial ref. number Model
–– Easy to install: Mounts using two clips, no tools are required. Compact meter
METSEPM2110 PM2110
with 54 mm depth, connectable up to 480 ±10% AC Volts L-L without voltage
METSEPM2120 PM2120 transformers for installations compliant with measurement category III, and
METSEPM2125C PM2125+1 double insulated.
–– Easy to operate: Intuitive navigation with self guided menus and test LED at
METSEPM2130 PM2130
the front panel used for test and calibration of the meter on site or laboratory.
METSEPM2210 PM2210 Heart-beat LED indicates normal functioning and communication status if
METSEPM2220 PM2220 connected to RS-485 network.

METSEPM2225C PM2225+1
–– Product standard compliance
–– Active energy Class 1.0 as per IEC 62053-21
METSEPM2230 PM2230
–– Active energy Class 0.5S as per IEC 62053-22 (partial compliance for
METSEPM2KDGTLIO22 PM2K2DIDO
active energy test clause only)
METSEPM2KANLGIO22 PM2K2AIAO
–– Reactive energy Class 1.0 as per IEC 62053-24 (partial compliance for
METSEPM2KANLGIO11 PM2K1AIAO reactive energy test clause only)

See your Schneider Electric representative for complete


ordering information.

+1
Available in China only

2 PLSED309005EN
EASY LOGIC POWER AND ENERGY METERS Functions and Characteristics

• Main characteristics: (cont'd)


PB115531

–– Tested in accordance with IEC 62052-11 standard for


–– 5 A, I-nominal
–– 1 A, I-nominal (field settable).
–– Power quality analysis: The PM2000 offers THD % measurements and
Individual harmonics up to15th order in PM2x20 variants and up to 31st in
PM2x30 variants.
–– Load management: Simultaneous display of peak, present, predicted &
rising demands of all the four demand parameters (W, VA, VAR, Amps)
–– Billing: Tenant billing/utility meter cross check (where local regulations are
not applicable).
–– Timer: Active load timer, Meter operation timer and Run hours timer. These
features help advise maintenance requirements and scheduling.
–– Password: Field configurable password for securing set up information and
PM2000 LCD display prevent tampering of integrated values.
–– Cyber security: Option for disabling RS-485 port through front panel
keys against unauthorized access. It helps during installation and trouble
shooting of communication network.
–– LED display: Auto scaling, 9+3 digits for energy, 4 digits for other
parameters.
–– LCD display: 5 digits for energy, 5 or 6 digits for other parameters, with auto
scaling.
–– 12am snap shot: The values from summary page will be stored as snap shot
and refreshed by next day 12am.
–– Rate counters: 2 configurable counters display values in custom specified
units based on energy recorded (e.g., kgCO2 carbon emission or energy
cost).
–– Energy preset feature: For retrofit application.

PLSED309005EN 3
EASY LOGIC POWER AND ENERGY METERS Functions and Characteristics

PM2000 technical specifications


PB114317

General
Use on LV and MV systems with onsite programmable PT/CT ratio
Basic metering with THD %, Individual Harmonics, RTC and min/max readings
Instantaneous rms values
Current Average line current of 3-phase, per-phase, and calculated
neutral current
Voltage Average voltage of L-L, L-N parameters, and per-phase
Frequency Any available line
Real, reactive, and apparent power Total and per-phase value
Displacement power factor Average and per-phase signed, four quadrant
True Power Factor Average and per-phase signed, four quadrant
% Unbalance Among the phase for Amps, V L-N, V L-L
Energy values stored in non-volatile memory
Four quadrant measurement for Accumulated energy values for Active, Reactive & Apparent
Rear of PM2000 closed Delivered (Forward or Import) and Energy parameters, quadrant basis
Received (Reverse or Export) energy Net & Total (absolute) values
Timer Accumulated time counters for active load timer, meter
operation timer, run hours and power outage counter
Old Registers Facilitates retrieval of last cleared energy values
PB114318

Demand values
Current average Present, Last, Predicted, Peak, and Peak Date Time
Active power Present, Last, Predicted, Peak, and Peak Date Time
Reactive power Present, Last, Predicted, Peak, and Peak Date Time
Apparent power Present, Last, Predicted, Peak, and Peak Date Time
Demand sync methods Thermal, Timed, Command Sync, and Clocked Sync
Demand calculation mode Sliding, fixed and rolling block
Demand intervals Settable from 1 to 60 minutes, in the step of 1 minute
Display
PM2100 series Bright red colour LED display, 7 segment LED, ~ 14.2 mm
height, 3 rows with 4 digits per row, Auto range
PM2200 series Full scape, monochrome graphical LCD of 128 x 128 resolution
with viewable area of 67 x 62.5 mm
Visualization mode for signs IEC or IEEE type in LCD display meter
Communication
Rear of PM2000 open RS-485 serial Channel connection Industry standard Modbus RTU
protocol
Integration with software SCADA/ DCS/ PMS/ EMS/ BAS/ BMS software
Native Plug and Play support Schneider Electric energy management system software -
StruxureWare Power Monitoring Expert, StruxureWare
PB114321

PowerSCADA Expert along with ION Setup programming support


Min/Max values
Minimum & Maximum value For 8 parameters, viz., V L-L, V L-N, Amps, PF, Hz, W, VA,
recording of 3-ph average or total VAR with date and time stamp, resettable separately
through set up mode
Alarms
Alarming with time stamping in A different combination of set point driven alarms and
PM2x30 meters digital alarms with 1 s time stamping. The alarms can be
programmed and combined to trigger digital outputs, the
meter keeps an alarm logs with the active and historical
alarms with date and time stamping in 40 registers
Diagnostics
Diagnostic page Indicates LED/LCD status, sl number, diag pages, OS & RS
version
Lock/ Un-Lock
Page Lock & Unlock (PM2100 series) Unique feature to ensures that commonly referred page is
Rear of PM2000 without I/O module restored in 4 minutes of inactive time
Rate 1 counter +2
kgCO2 emission (example) Rate counter can be configured to display the CO2 emission
in kgCO2 format based on the kWh measured either in
delivered or received direction.
Rate 2 counter+2
Tariff counter (example) Rate counter can also be configured to calculate the
electricity cost based on the energy consumption in
customized currency format.
12am snap shot
12am snap shot+2 Snap shot of Avg Voltage, Avg Current, Total Active Power &
Energy delivered as measured by the meter at 12am. The
static page will be refreshed with new values by 12am next day
+2
Available in PM2220/PM2230 (LCD) meters

4 PLSED309005EN
EASY LOGIC POWER AND ENERGY METERS Functions and Characteristics

Electrical characteristics
PB114320

Type of measurement True RMS 64 samples per cycle


Measurement accuracy
Current, average & per-phase ±0.5 %
Voltage average & per-phase ±0.5 %
Frequency ±0.05 %
Power Factor, average & per-phase ±0.01
Power (W-Active, VA- Apparent) ±0.5 %
Power (VAR- Reactive) ±1.0 %
Real/ Active Energy (Wh) Class 0.5S as per IEC 62053-22 and Class 1.0 as per
IEC 62053-21 for both CT nominal of 5 A and 1 A+3

Reactive Energy Class 1.0 as per IEC 62053-24


Apparent Energy ±0.5 %
THD % and ±5 % FS for THD % & Individual harmonics
Individual Harmonics- V & A
Input-voltage
Rear of PM2000 with I/O module VT primary 999 kV L-L max, secondary voltage depends on VT ratio
U nominal 277 V L-N/480V L-L
Measured V with full range 20-277 V L-N/35 - 480 V L-L, cat III
20-347 V L-N/35 - 600 V L-L, cat II
Permanent overload 750 V AC L-L
Impedance => 5 MΩ
PB114319

Frequency nominal 50/60 Hz


VA burden < 0.2 VA at 240 V AC L-N
Input-current
CT ratings Primary adjustable 1 A to 32768 A
Secondary 1 A or 5 A I-nominal
Measured Amps with over 5 mA to 6 A
range & Crest Factor
Over current withstand Continuous 12 A, 10s/hr 50 A, 1s/hr 500 A
Impedance < 0.3 mΩ
Frequency nominal 50/60 Hz
VA Burden <0.024 VA at 6 A
Rear of PM2000 with I/O module disconnected AC control power
Operating range 44- 277 V AC ±10% (80-277 V AC ±10% with I/O card)
Burden <6 VA at 277 V AC L-N (<8 VA for PM2x30 and PM2x25C)
Frequency 45 to 65 Hz
Ride-through time 100 ms typical at 120 V AC and maximum burden (50 ms
with Analog IO card for PM2x30)
400 ms typical at 230 V AC and maximum burden (50 ms
with Analog IO card for PM2x30)
DC control power
Operating range 48-277 V DC ±10% (100-277 V AC ±10% with I/O card)
Burden < 2 W at 277 V DC (< 3.3 W for PM2x30 and PM2x25C)
Ride-through time 50 ms typical at 125 V DC and maximum burden
Real time clock
RTC with battery backup 3 years (when meter is in Power OFF condition)
Displays update
Instantaneous 1s
Demand 15 s
Harmonics 5s
Wiring configuration
User programmable 1ph, 2w, L-N
1ph, 2w, L-L
1ph, 3w, L-L with N (2phase)
3ph, 3w, Delta, Ungrounded
3ph, 3w, Delta, Corner Grounded+4
3ph, 3w, Wye, Ungrounded+4
3ph, 3w, Wye Grounded+4
3ph, 3w, Wye, Resistance Grounded+4
3ph, 4w, Open Delta, Center-Tapped+4
3ph, 4w, Delta, Center-Tapped+4
3ph, 4w, Wye, Ungrounded+4
3ph, 4w, Wye Grounded
3ph, 4w, Wye, Resistance Grounded+4

+3
For 1 A CT nominal, additional error of ±1 % from 50 mA to 150 mA, ±2 % for current > 10
mA to < 50 mA. Partial standard compliance for Class 0.5S meter type (energy test clause only)
+4
Through communication in PM2100 series meters

PLSED309005EN 5
EASY LOGIC POWER AND ENERGY METERS Functions and Characteristics

PM2000 series
Mechanical characteristics
Weight ~ 300 gm
IP degree of protection IP54 front side, IP30 meter body as per IEC 60529
Material Polycarbonate meets UL 94V-0 flammability rating
Dimensions W x H x D 96 x 96 x 54 mm maximum (depth of the meter from housing mounting flange) and 13 mm (protrusion of meter
from housing flange). Meter depth with IO module is 74 mm
Mounting position Vertical
Panel thickness 5 mm maximum
Environmental characteristics
Operating temperature Meter -10 to +60 °C (14 to 140 °F)
Storage temperature Meter -25 to +70 °C (-13 to 158 °F)
Humidity rating 5 to 95% RH non condensing
Pollution degree 2
Altitude ≤ 2000 m (6562 ft) Category III
Product life Minimum 7 years
Electromagnetic compatibility (tested as per IEC 61326-1)
Electrostatic discharge IEC 61000-4-2
Immunity to radiated field IEC 61000-4-3
Immunity to fast transients IEC 61000-4-4
Immunity to impulse waves IEC 61000-4-5
Conducted immunity IEC 61000-4-6
Immunity to magnetic fields IEC 61000-4-8
Immunity to voltage dips IEC 61000-4-11
Emissions Emissions FCC Part 15 Class A/CE
Safety
Europe CE, as per IEC 61010-1 Ed-3
US and Canada cULus as per UL61010-1 and CAN/CSA-C22.2 No. 61010-1, for 600V AC
Measurement Category (Voltage CAT III up to 480 V L-L
and Current inputs) CAT II up to 600 V L-L
Overvoltage Category (Control power) CAT III up to 300 V L-N
Dielectric As per IEC/UL 61010-1 Ed-3
Protective Class II, Double insulated for user accessible parts
Green premium EOL, REACH, PEP, RoHS complied
Other certification RCM (Australia), EAC (Russia)
Communication
RS-485 port Modbus RTU: 2-Wires, with ground & shield, 4800, 9600, 19200 or 38400 baud, Parity - Even, Odd, None, 1 stop
bit if parity is Odd or Even, 2 stop bits if None
DLF3000: Firmware update through communication port
Pulse Output – POP Max 40 V DC, 20 mA 20 ms ON time
Configurable pulse weight from 1 to 9999000 pulses/k_h (kWh, kVAh, or kVARh)
Isolation 2.5 kV RMS, double insulated
Protection features Password protected for set-up & clearing energy and Min/Max data
Display language English, Spanish, French, Chinese, German, Portugese, Russian, Turkish
Technical publication Printed installation guide (IG) with the meter in multi language (EN,ES,FR,DE,PT, RU,TR,ZH)
Human machine interface
Display type LED display: 7 segment LED, ~ 14.2 mm height, 3 rows with 4 digits per row 2 columns of LEDs, one on each side
of the LED panel to indicate the parameters under measurement
LCD display: Monochrome graphical LCD of 128x128 mm resolution with viewable area of 67 x 62.5 mm
Keypad PM2100 series: 3 buttons for navigation & combination of 2 buttons for performing set-up, Lock/unlocking of page,
Diagnostic page operation
PM2200 series: 4 buttons for intuitive navigation of HMI/ UI pages
CAL LED Indicator Red colour, meter constant is configurable from 1 to 9999000 pulses/k_h (kWh, kVAh, or kVARh)
Comm. activity Green LED (for indicating RS-485 interface or heart beat pulse)

6 PLSED309005EN
EASY LOGIC POWER AND ENERGY METERS Functions and Characteristics

Electrical characteristics of IO modules


Status Inputs (Digital Inputs)
Voltage ratings 18.5 to 36 V DC, OFF 0 to 4 V DC
PB115529

Input resistance 110 kW


Max Frequency 2 Hz (T ON min = T OFF min = 250 ms)
Detect Time 20 ms
Update time 1s
Isolation 2.5 kV RMS
Supported models Available as default feature in PM2125/ PM2225 and
Expandable option in PM2130/ PM2230 meter model
Application Integration of Breaker status or other non-electrical devices
like steam, water, gas meter through pulse inputs
Display support Available on PM2230/PM2225 (LCD type). In PM2130/
PM2125 meter, data is available through communication only.
Set up and configuration Through set-up software
Digital Outputs
Voltage ratings 40 V DC max, 20mA max
Rear of PM2200 with I/O On Resistance 50 W max
Meter constant Configurable from 1 to 9999000 k_h (kWh, kVARh, kVAh)
Pulse width 20 ms
Pulse frequency 25 Hz
Leakage current 1 micro Amps
Isolation 2.5 kV RMS
DIDOISO

Supported models Available as default feature in PM2125/ PM2225 and


Expandable option in PM2130/ PM2230 meter model
Alarm conditions 14 set point driven alarms, 4 Unary alarms, 2 Digital inputs
status
Application Pulse output: configurable for energies
upper / lower limit: configurable for 9 parameters with 14 set
point: V L-L, V L-N, Amps, F, V-THD %, W-tot, VA-tot, VAR-tot,
PF-avg http://69.195.124.174/~pilatfa7/temp/
Display support Available on PM2230/PM2225 (LCD type). In PM2130/
PM2125 meter, data is available through communication only
Set up and Configuration Through set-up software
Analogue inputs
Measurement scale 4-20 mA
Digital I/O module Input impedance =<300 W
Max source impedance >500 W
Update rate 1s
Accuracy 1 % of Full scale at ambient temp 0.1 %/K for de-rating
Voltage ratings Typical 12 V (max 30 V)
Power Consumption <1.5 Watts
PB115540

Isolation 2.5 kV RMS


Supported models Expandable option in PM2130/ PM2230 meter models
Application Configurable for inputs from flow rates, RPM, fluid level, oil
pressure, temperature measurement devices or transducers
with option of 81 different Uni code selection. Configuration
via set up software
Display Available on PM2230 (LCD type). In PM2130 meter, data is
available through communication only
Set up and configuration Through set up software
Analogue outputs
Scale 4-20 mA
Load impedance =<600 W
Analogue I/O module Update rate 1s
Accuracy 1 % of Full scale at ambient temp
Voltage ratings Typical 12 V (max 30 V)
Power Consumption <1.5 Watts
Isolation 2.5 kV RMS
Supported models Expandable option in PM2130/ PM2230 meter models
Application Analogue outputs can be associated to 40 different
instantaneous parameters
Display Available on PM2230 (LCD type). In PM2130 meter, data is
available through communication only
Set-up & configuration Through set-up software

PLSED309005EN 7
EASY LOGIC POWER AND ENERGY METERS Functions and Characteristics

PM2120/ PM2220/
Feature set summary PM2110 PM2130 PM2210 PM2230
PM2125 PM2225
Accuracy Class for Wh 1.0 0.5S 1.0 0.5S
Accuracy Class for VARh 1.0
Accuracy for VAh ±0.5 %
Amps, per-phase, average and calculated neutral current b
Voltage, V L-N, V L-L, per-phase and average b
True PF True PF
Power Factor True PF True PF
Displacement PF1 Displacement PF
Frequency, any available phase b
Power: W, VA, VAR: per-http://69.195.124.174/~pilatfa7/temp/
http://69.195.124.174/~pilatfa7/temp/ phase and total b

Current Current
3-phase unbalance % Current Current
Voltage+4 Voltage
Demand parameters (Present, Last, Predicted and Peak for b b b b
W, VA, VAR, Amps)
Date and Time stamp for peak demand (no timestamp) (no timestamp)
Energy: Wh, VAh, VARh (4 quadrant)
Delivered, Received Delivered,
Delivered (Import or Forward), Received (Export or Reverse) Delivered, Delivered, Received
Total+4, Net+4, Received,
Received Total, Net, Last cleared3
Last cleared+4 Total, Net
Active load timer, meter operating timer, run hours and power Through com b
outage counter
THD %: Voltage L-N or L-L, Amps per phase b
Individual harmonics for Voltage, Current, per-phase+7 Up to 15th+4 Up to 31st+4 Up to 15th Up to 31st
Min/ Max with real time clock For avg or total of V L-L, V L-N, Through com b
Amps, PF, Hz, W, VA, VAR parameters with date and time
stamp of occurrence
RTC/battery2 NA b b NA b b
Communication Pulse Output RS-485 Pulse Output RS-485
Expandable Analogue IO module+5 b b
PM2K2AIAO: 2 input & 2 output channels
PM2K1AIAO: 1 input & 1 output channel
Expandable Digital IO module3 b b b b
PM2K2DIDO: 2 input & 2 output channels PM2125 PM2225
Customizable data logging up to 2 parameters. Option to b b
select Power (W,VA,VAR) Bi-directional energy (±Wh,
±VAh, ±VARh), Demand (W, VA,VAR) with configurable
interval and duration (e.g. 2 parameters for 60 days at 15
minutes interval)
Alarms: 14 set point driven alarms from 9 parameters (V L-L, b b b b
V L-N, Amps, F, V-THD %, W-tot, VA-tot, VAR-tot, PF-avg), 4 PM2125 PM2225
Unary alarms (meter power up, meter reset, meter diagnostic,
phase reversal) and 2 digital inputs status (with DI/DO card only)
12 am snap shot of Avg Voltage, Avg Current, Total active b
power & Energy delivered as measured every day at 12am+7 PM2225
Rate counters: 2 configurable counters to display values in b b b
customer specified units base on energy measured (e.g., PM2225
kgCO2 emission or energy cost)+7

+4
Through communication only
+5
Any one IO module can be used at a time with PM2130 or PM2230 meter. The control power range with IO module (including PM2125/ PM2225
references) shall be 72 to 304 V AC L-N or 90 to 304 V DC.
+6
Battery backup duration 3 years when meter is in Power OFF condition.
+7
Individual harmonics, 12am snap shot and rate counter features not available in PM2125/ PM2225 meters

8 PLSED309005EN
EASY LOGIC POWER AND ENERGY METERS DIMENSIONS AND CONNECTION

PM2000 LCD display legend description

A Menu selection buttons


PB115535

B Energy pulsing LED (red) Heartbeat / communications LED (green)

C Navigation or menu selections:

Exit screen and go up one level

Move cursor up list of options

Move cursor down, display more options

Move cursor one character to the left

Scroll right and display more menu items

+ Show next item in list or increase the highlighted value


_ Show previous item in list

D Maintenance & alarm notification area


PB115536

E Control power

F Voltage inputs

G Current inputs

H RS-485 / POP

I Gasket

J I/O channel slot - optional accessory for PM2230, embedded in PM2225 meter

PM2000 LED display legend description


A Phase measurements (VL-N, VL-L, I, kVA, kW, kVAR, PF, V-THD %, I-THD %)
PB115537

B Demand measurements (DM=Demand, PrsDM=Present demand,


PrdDM=Predictor demand, MD=Maximum demand))

C RTC Date & time

D Negative indicator

E Navigation key to navigate down

F Energy readings Apparent enegry, Active energy, Reactive energy

G Navigation key to navigate up

H OK Enter key

I Energy pulsing LED (red) Heartbeat / communications LED (green)

J x 1000 indicator
PB115538

K System measurements Vavg, kVA, F, lavg, kW, In, PFavg, kVAR, lunb

L Control power L1, L2

M Input voltage terminals V1, V2, V3, VN

N Input current terminals I1+, I1-, I2+, I2-, I3+, I3-

O RS-485 communications / POP terminals

P Gasket

Q I/O channel slot - optional accessory for PM2130, embedded feature in


PM2125 meter

PLSED309005EN 9
EASY LOGIC POWER AND ENERGY METERS DIMENSIONS AND CONNECTION

PM2000 meter rear view Meter installation


PB114323

PM2000 multi-function meter mechanical dimensions


PB114324

PM2000 Digital and Analogue IO module mechanical dimensions


PB115539

10 PLSED309005EN
Schneider Electric Industries SAS As standards, specifications and designs develop from time to time, please
35, Rue Joseph Monier, ask for confirmation of the information given in this document.
CS 30323
F - 92506 Rueil Malmaison Cedex
Design: Schneider Electric
RCS Nanterre 954 503 439 Photos: Schneider Electric
Capital social 896 313 776
www.schneider-electric.com Over 75 % of Schneider Electric products
have been awarded the Green Premium ecolabel
Product name
PLSED310091EN © 2017 - Schneider Electric - All rights reserved 04-2017

You might also like