CMMB 1020
CMMB 1020
Models
CMMB1020
Description
The CMMB1020 extends your BACnet or Modbus network when
your application requires additional inputs and outputs on a physical
controller. Capitalizing on the high-density I/O point count of 30
universal inputs and 20 outputs enables the CMMB1020 to provide a
cost effective yet advanced integration capability.
Features CMMB1020
Technical Specifications
Specifications CMMB1020
Input Voltage 24 Vac/Vdc ±10%
Consumption 12VA
Universal Inputs 30 [0-10Vdc, 2-10Vdc, Thermistor, on/off (dry contact), 0-20mA, 4-20mA] / 16-bit resolution
Universal Outputs 4 [0-10Vdc, on/off] / 12-bit resolution
Analog Outputs 4 [0-10Vdc] / 12-bit resolution
Digital Relay Binary Outputs 12 [normally open, independent common per relay, 5A resistive]
Service Port BACnet® MS/TP @ 38400 bps
BACnet® MS/TP @ 9600, 19200, 38400, 76800 or 115000 bps (BAS-C).
Modbus RTU slave @ 9600, 19200, 38400 or 57600.
Selectable parity and stop bit configuration:
Communication Port
• No parity, 2 stop bit
• Even parity, 1 stop bit
• Odd parity, 1 stop bit
Communication Connections 24 AWG twisted-shield cable (Belden 9841 or equivalent)
Electrical Connections 0.8 mm2 [18 AWG] minimum
Operational Temperature 0ºC to 50ºC [32ºF to 122ºF]
Storage Temperature -30ºC to 50ºC [-22ºF to 122ºF]
Relative Humidity 5 to 95% non condensed
Weight 0.6 kg [1.3 lb]
Dimensions A C
A = 9.18” / 233 mm
B = 4.93” / 125 mm
C = 2.27” / 58 mm B
CMMB1020-211124-ESA Page | 1
Remote I/O Communication Module
Specification and Installation Instructions
Baud Rate | DS2 Network | DS2 MAC Address | DS1 UO1-UO4 Selector | JP3-JP6 End of Line | JP1-JP2
2 3 4 Result 1 Mode The 8 DIP switches represent a binary Analog Output 120 Ohms*
OFF OFF OFF Auto Detect OFF BACnet logic to calculate the MAC address. None
ON OFF OFF 9600 ON Modbus* * default setting
OFF ON OFF 19,200 * default setting Default = 101 Binary Output*
ON ON OFF 38,400
OFF OFF ON 57,600* BACnet all OFF = 0 * default setting
AI28 NO
BO10
AI29 COM
NO
AI30 BO11
COM
COM
NO
COM BO12
Power Input | TB18 COM
** 500mA max ** COM PCB POWER
www.neptronic.com Page | 2
Remote I/O Communication Module
Specification and Installation Instructions
FCC Compliance
WARNING: Changes or modifications not expressly approved by the party responsible for compliance could
void the user’s authority to operate the equipment.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can
radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
BACnet
• Highest MAC address is 254.
• Default is all switches OFF = MAC address 0
• If you do not change device instance in program mode, it will be automatically modified according to the MAC address.
MAC Address DS.1 = 1 DS.2 = 2 DS.3 = 4 DS.4 = 8 DS.5 = 16 DS.6 = 32 DS.7 = 64 DS.8 = 128 Default Device Instance
0 OFF OFF OFF OFF OFF OFF OFF OFF 153000
1 ON OFF OFF OFF OFF OFF OFF OFF 153001
2 OFF ON OFF OFF OFF OFF OFF OFF 153002
3 ON ON OFF OFF OFF OFF OFF OFF 153003
4 OFF OFF ON OFF OFF OFF OFF OFF 153004
… … … … … … … … … …
126 OFF ON ON ON ON ON ON OFF 153126
… … … … … … … … … …
254 OFF ON ON ON ON ON ON ON 153254
Modbus
• Highest MAC address is 247.
• Default is all switches OFF = MAC address 1.
• There is no device instance for Modbus.
MAC Address DS.1 = 1 DS.2 = 2 DS.3 = 4 DS.4 = 8 DS.5 = 16 DS.6 = 32 DS.7 = 64 DS.8 = 128
1 OFF OFF OFF OFF OFF OFF OFF OFF
1 ON OFF OFF OFF OFF OFF OFF OFF
2 OFF ON OFF OFF OFF OFF OFF OFF
3 ON ON OFF OFF OFF OFF OFF OFF
4 OFF OFF ON OFF OFF OFF OFF OFF
… … … … … … … … …
126 OFF ON ON ON ON ON ON OFF
… … … … … … … … …
247 ON ON ON OFF ON ON ON ON
www.neptronic.com Page | 3
Remote I/O Communication Module
Specification and Installation Instructions
LEDs
POWER
STATUS RXD Power
DS2 DS1
1
ON
1
ON On = Input voltage normal
JP1
2
3
2
3 Off = No power
4 4
5 5 TXD
6
7
6
7
RXD
Status
8 8
Flashing = Normal operation (watchdog)
JP2
RX/TX (BACnet)
TXD
Flashing = Receiving (RX) and/or transmitting (TX) data.
RX/TX (Modbus)
Flashing = Receiving (RX) and/or transmitting (TX) data.
Output Status
On = Activated
Off = Deactivated
JP3
Analog = When Universal and Analog outputs are set
to analog values (Vdc); the LED intensity
corresponds to the output value. For example:
JP4 At 10Vdc, the LED will be fully on. At 5Vdc, the
Output Status LEDs LED will be at 50% intensity. At 0 Vdc, the LED
(one per output) will be off.
JP5
JP6
AO1
AO2
AO COM -
AO3
AO4
10VDC
COM
JP3
NO
+
COM UO1 when used
JP4
NO as AO5
www.neptronic.com Page | 4
Remote I/O Communication Module
Specification and Installation Instructions
Cfg UI.x Mode Cfg UI.x Cfg UI.xLinear Cfg UI.x Min Cfg UI.x Max Cfg UI.x Min Cfg UI.x Max Cfg UI.x Linear
(Reg. # for UI1: Reading Bias Value Scale Voltage Voltage Linear Value Linear Value Value Bias
112/40113) (113/40114) (114/40115) (115/40116) (116/40117) (117/40118) (118/40119) (119/40120)
1= "0-10V" N/A 1 0 10000 0 100 0
2= "4-20mA" N/A 1 0 20000 0 100 0
3= "Dry Contact" N/A N/A N/A N/A N/A N/A N/A
4-8 = Thermistors 0 N/A N/A N/A N/A N/A N/A
www.neptronic.com Page | 5
Remote I/O Communication Module
Specification and Installation Instructions
1
ID is equal to ObjectType.Instance
www.neptronic.com Page | 6
Remote I/O Communication Module
Specification and Installation Instructions
www.neptronic.com Page | 7
Remote I/O Communication Module
Specification and Installation Instructions
Out of service
AO.7 AO7 Voltage* Voltage of analog output 7 0 to 10 Volt | Resolution 0.001 Volt
Present Value
Out of service
AO.8 AO8 Voltage* Voltage of analog output 8 0 to 10 Volt | Resolution 0.001 Volt
Present Value
0 to 100% or 0 to 806800 ohms
AV.1 UI1 Impedance Universal Input 1 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.2 UI2 Impedance Universal Input 2 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.3 UI3 Impedance Universal Input 3 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.4 UI4 Impedance Universal Input 4 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.5 UI5 Impedance Universal Input 5 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.6 UI6 Impedance Universal Input 6 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.7 UI7 Impedance Universal Input 7 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.8 UI8 Impedance Universal Input 8 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.9 UI9 Impedance Universal Input 9 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.10 UI10 Impedance Universal Input 10 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.11 UI11 Impedance Universal Input 11 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.12 UI12 Impedance Universal Input 12 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.13 UI13 Impedance Universal Input 13 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.14 UI14 Impedance Universal Input 14 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.15 UI15 Impedance Universal Input 15 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.16 UI16 Impedance Universal Input 16 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.17 UI17 Impedance Universal Input 17 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.18 UI18 Impedance Universal Input 18 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.19 UI19 Impedance Universal Input 19 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.20 UI20 Impedance Universal Input 20 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.21 UI21 Impedance Universal Input 21 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.22 UI22 Impedance Universal Input 22 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.23 UI23 Impedance Universal Input 23 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.24 UI24 Impedance Universal Input 24 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.25 UI25 Impedance Universal Input 25 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.26 UI26 Impedance Universal Input 26 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.27 UI27 Impedance Universal Input 27 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.28 UI28 Impedance Universal Input 28 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.29 UI29 Impedance Universal Input 29 Impedance Out of service
Resolution: 1% or 1 ohms
0 to 100% or 0 to 806800 ohms
AV.30 UI30 Impedance Universal Input 30 Impedance Out of service
Resolution: 1% or 1 ohms
www.neptronic.com Page | 8
Remote I/O Communication Module
Specification and Installation Instructions
Out of service
AV.31 Cfg AO1 Failsafe Preset Failsafe preset for analog output 1 0 to 10Volt | Resolution: 0.001Volt
Present Value
Out of service
AV.32 Cfg AO2 Failsafe Preset Failsafe preset for analog output 2 0 to 10Volt | Resolution: 0.001Volt
Present Value
Out of service
AV.33 Cfg AO3 Failsafe Preset Failsafe preset for analog output 3 0 to 10Volt | Resolution: 0.001Volt
Present Value
Out of service
AV.34 Cfg AO4 Failsafe Preset Failsafe preset for analog output 4 0 to 10Volt | Resolution: 0.001Volt
Present Value
Out of service
AV.35 Cfg AO5 Failsafe Preset* Failsafe preset for analog output 5 0 to 10Volt | Resolution: 0.001Volt
Present Value
Out of service
AV.36 Cfg AO6 Failsafe Preset* Failsafe preset for analog output 6 0 to 10Volt | Resolution: 0.001Volt
Present Value
Out of service
AV.37 Cfg AO7 Failsafe Preset* Failsafe preset for analog output 7 0 to 10Volt | Resolution: 0.001Volt
Present Value
Out of service
AV.38 Cfg AO8 Failsafe Preset* Failsafe preset for analog output 8 0 to 10Volt | Resolution: 0.001Volt
Present Value
Out of service 0 = Open
BO.1 BO1 State Binary Output 1 State
Present Value 1 = Closed
Out of service 0 = Open
BO.2 BO2 State Binary Output 2 State
Present Value 1 = Closed
Out of service 0 = Open
BO.3 BO3 State Binary Output 3 State
Present Value 1 = Closed
Out of service 0 = Open
BO.4 BO4 State Binary Output 4 State
Present Value 1 = Closed
Out of service 0 = Open
BO.5 BO5 State Binary Output 5 State
Present Value 1 = Closed
Out of service 0 = Open
BO.6 BO6 State Binary Output 6 State
Present Value 1 = Closed
Out of service 0 = Open
BO.7 BO7 State Binary Output 7 State
Present Value 1 = Closed
Out of service 0 = Open
BO.8 BO8 State Binary Output 8 State
Present Value 1 = Closed
Out of service 0 = Open
BO.9 BO9 State Binary Output 9 State
Present Value 1 = Closed
Out of service 0 = Open
BO.10 BO10 State Binary Output 10 State
Present Value 1 = Closed
Out of service 0 = Open
BO.11 BO11 State Binary Output 11 State
Present Value 1 = Closed
Out of service 0 = Open
BO.12 BO12 State Binary Output 12 State
Present Value 1 = Closed
Out of service 0 = Open
BO.13 BO13 State* Binary Output 13 State
Present Value 1 = Closed
Out of service 0 = Open
BO.14 BO14 State* Binary Output 14 State
Present Value 1 = Closed
Out of service 0 = Open
BO.15 BO15 State* Binary Output 15 State
Present Value 1 = Closed
Out of service 0 = Open
BO.16 BO16 State* Binary Output 16 State
Present Value 1 = Closed
Select the unit system to use on the 0= Celsius
BV.1 Cfg Temperature Units Present Value
device. 1= Fahrenheit
1= Custom
Out of service 2= Profile 1
MSV.0 Cfg IO Profile Select input/output profile.
Present Value 3= Profile 2
4= Profile 3
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.1 Cfg UI1 Mode Select universal input 1 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
www.neptronic.com Page | 9
Remote I/O Communication Module
Specification and Installation Instructions
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.2 Cfg UI2 Mode Select universal input 2 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.3 Cfg UI3 Mode Select universal input 3 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.4 Cfg UI4 Mode Select universal input 4 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.5 Cfg UI5 Mode Select universal input 5 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.6 Cfg UI6 Mode Select universal input 6 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.7 Cfg UI7 Mode Select universal input 7 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.8 Cfg UI8 Mode Select universal input 8 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.9 Cfg UI9 Mode Select universal input 9 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.10 Cfg UI10 Mode Select universal input 10 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
www.neptronic.com Page | 10
Remote I/O Communication Module
Specification and Installation Instructions
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.11 Cfg UI11 Mode Select universal input 11 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.12 Cfg UI12 Mode Select universal input 12 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.13 Cfg UI13 Mode Select universal input 13 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.14 Cfg UI14 Mode Select universal input 14 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.15 Cfg UI15 Mode Select universal input 15 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.16 Cfg UI16 Mode Select universal input 16 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.17 Cfg UI17 Mode Select universal input 17 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.18 Cfg UI18 Mode Select universal input 18 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.19 Cfg UI19 Mode Select universal input 19 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
www.neptronic.com Page | 11
Remote I/O Communication Module
Specification and Installation Instructions
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.20 Cfg UI20 Mode Select universal input 20 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.21 Cfg UI21 Mode Select universal input 21 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.22 Cfg UI22 Mode Select universal input 22 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.23 Cfg UI23 Mode Select universal input 23 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.24 Cfg UI24 Mode Select universal input 24 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.25 Cfg UI25 Mode Select universal input 25 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.26 Cfg UI26 Mode Select universal input 26 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.27 Cfg UI27 Mode Select universal input 27 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.28 Cfg UI28 Mode Select universal input 28 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
www.neptronic.com Page | 12
Remote I/O Communication Module
Specification and Installation Instructions
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.29 Cfg UI29 Mode Select universal input 29 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
1= 0-10V
2= 4-20mA
3= Dry Contact
Out of service 4= 10K Type3/G/4A1
MSV.30 Cfg UI30 Mode Select universal input 30 mode
Present Value 5= 10K Type2/3A1/NTC(Danfoss)
6= 10K_ NTC Carel
7= 20K Type6A1
8= 30K Type6A1
Selected analog output 1 failsafe Out of service 1= Last State
MSV.31 Cfg AO1 Failsafe Mode
mode Present Value 2= Preset
Selected analog output 2 failsafe Out of service 1= Last State
MSV.32 Cfg AO2 Failsafe Mode
mode Present Value 2= Preset
Selected analog output 3 failsafe Out of service 1= Last State
MSV.33 Cfg AO3 Failsafe Mode
mode Present Value 2= Preset
Selected analog output 4 failsafe Out of service 1= Last State
MSV.34 Cfg AO4 Failsafe Mode
mode Present Value 2= Preset
Selected analog output 5 failsafe Out of service 1= Last State
MSV.35 Cfg AO5 Failsafe Mode*
mode Present Value 2= Preset
Selected analog output 6 failsafe Out of service 1= Last State
MSV.36 Cfg AO6 Failsafe Mode*
mode Present Value 2= Preset
Selected analog output 7 failsafe Out of service 1= Last State
MSV.37 Cfg AO7 Failsafe Mode*
mode Present Value 2= Preset
Selected analog output 8 failsafe Out of service 1= Last State
MSV.38 Cfg AO8 Failsafe Mode*
mode Present Value 2= Preset
1= Last State
Selected binary output 1 failsafe Out of service
MSV.39 Cfg BO1 Failsafe Mode 2= Open
mode Present Value
3= Closed
1= Last State
Selected binary output 2 failsafe Out of service
MSV.40 Cfg BO2 Failsafe Mode 2= Open
mode Present Value
3= Closed
1= Last State
Selected binary output 3 failsafe Out of service
MSV.41 Cfg BO3 Failsafe Mode 2= Open
mode Present Value
3= Closed
1= Last State
Selected binary output 4 failsafe Out of service
MSV.42 Cfg BO4 Failsafe Mode 2= Open
mode Present Value
3= Closed
1= Last State
Selected binary output 5 failsafe Out of service
MSV.43 Cfg BO5 Failsafe Mode 2= Open
mode Present Value
3= Closed
1= Last State
Selected binary output 6 failsafe Out of service
MSV.44 Cfg BO6 Failsafe Mode 2= Open
mode Present Value
3= Closed
1= Last State
Selected binary output 7 failsafe Out of service
MSV.45 Cfg BO7 Failsafe Mode 2= Open
mode Present Value
3= Closed
1= Last State
Selected binary output 8 failsafe Out of service
MSV.46 Cfg BO8 Failsafe Mode 2= Open
mode Present Value
3= Closed
1= Last State
Selected binary output 9 failsafe Out of service
MSV.47 Cfg BO9 Failsafe Mode 2= Open
mode Present Value
3= Closed
1= Last State
Selected binary output 10 failsafe Out of service
MSV.48 Cfg BO10 Failsafe Mode 2= Open
mode Present Value
3= Closed
1= Last State
Selected binary output 11 failsafe Out of service
MSV.49 Cfg BO11 Failsafe Mode 2= Open
mode Present Value
3= Closed
www.neptronic.com Page | 13
Remote I/O Communication Module
Specification and Installation Instructions
1= Last State
Selected binary output 12 failsafe Out of service
MSV.50 Cfg BO12 Failsafe Mode 2= Open
mode Present Value
3= Closed
1= Last State
Selected binary output 13 failsafe Out of service
MSV.51 Cfg BO13 Failsafe Mode** 2= Open
mode Present Value
3= Closed
1= Last State
Selected binary output 14 failsafe Out of service
MSV.52 Cfg BO14 Failsafe Mode** 2= Open
mode Present Value
3= Closed
1= Last State
Selected binary output 15 failsafe Out of service
MSV.53 Cfg BO15 Failsafe Mode** 2= Open
mode Present Value
3= Closed
1= Last State
Selected binary output 16 failsafe Out of service
MSV.54 Cfg BO16 Failsafe Mode** 2= Open
mode Present Value
3= Closed
* Only available when JP3 - JP6 jumpers (UO1 - UO4 selector) are set to AO5 - AO8.
** Only available when JP3 - JP6 jumpers (UO1 - UO4 selector) are set to BO13 - BO16.
www.neptronic.com Page | 14
Remote I/O Communication Module
Specification and Installation Instructions
Modbus Registers
• Register address
o As per protocol base (base 0); for PLC add 1 to protocol base.
o As per holding register (base 40001)
• Functions :
o 03 Read Holding Register
o 06 Write Single Register
o 16 Write Multiple Registers
• Error Codes :
o 02 Illegal Data Address
o 03 Illegal Value
o 06 Slave Device Busy
• W = Writable register, RO = read only.
• No Real number in Modbus register, use scale to calculate real number. Register = Real number * Scale => Real number = Register / Scale. Scale could be 1, 10 or 100
• Attention when writing a register that contains a bit string. If bit is writable (conditional or not), the write will always be accepted. If bit is reserved or not writable, the write will be ignored and
will keep its actual state.
• Use READ-MODIFY-WRITE sequence.
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
Unsigned [1..247]
0 40001 MAC Address W 101
Scale 1 * MAC address is 1 if all DIP switches of DS1 are OFF.
Unsigned
1 40002 Firmware Version 1.00 RO
Scale 100
2 40003 Serial Number (characters 0 & 1) ASCII MSB = char 0, LSB = char 1 RO
3 40004 Serial Number (characters 2 & 3) ASCII MSB = char 2, LSB = char 3 RO
4 40005 Serial Number (characters 4 & 5) ASCII MSB = char 4, LSB = char 5 RO
5 40006 Serial Number (characters 6 & 7) ASCII MSB = char 6, LSB = char 7 RO
6 40007 Serial Number (characters 8 & 9) ASCII MSB = char 8, LSB = char 9 RO
7 40008 Serial Number (characters 10 & 11) ASCII MSB = char 10, LSB = char 11 RO
8 40009 Serial Number (characters 12 & 13) ASCII MSB = char 12, LSB = char 13 RO
9 40010 Serial Number (characters 14 & 15) ASCII MSB = char 14, LSB = char 15 RO
0 = Operational 3 = download-in-progress
10 40011 System Status Unsigned 1 = Operational-read-only 4 = non-operational RO
2 = download-required 5 = backup-in-progress
www.neptronic.com Page | 15
Remote I/O Communication Module
Specification and Installation Instructions
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
www.neptronic.com Page | 16
Remote I/O Communication Module
Specification and Installation Instructions
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
www.neptronic.com Page | 17
Remote I/O Communication Module
Specification and Installation Instructions
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
49 40050 Binary Output States** Bit String B4: Binary Output 5 State B12: Binary Output 13 State** W 0
0 = Open, 1 = Closed 0 = Open, 1 = Closed
www.neptronic.com Page | 18
Remote I/O Communication Module
Specification and Installation Instructions
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
www.neptronic.com Page | 19
Remote I/O Communication Module
Specification and Installation Instructions
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
www.neptronic.com Page | 20
Remote I/O Communication Module
Specification and Installation Instructions
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
115 40116 Universal Input 1 Minimum Voltage 0-10V, 4-20mA: Type: Unsigned, Scale:1000, Unit: Volt, Range: 0.00 - 65.535V W N/A
116 40117 Universal Input 1 Maximum Voltage 0-10V, 4-20mA: Type: Unsigned, Scale:1000, Unit: Volt, Range: 0.00 - 65.535V W N/A
0-10V: Type: Signed, Scale: 1, Unit: Volt, Range: -32768 - 32767V
117 40118 Universal Input 1 Minimum Linear Value W N/A
4-20mA: Type: Signed, Scale: 1, Unit: mA, Range: -32768 - 32767mA
0-10V: Type: Signed, Scale: 1, Unit: Volt, Range: -32768 - 32767V
118 40119 Universal Input 1 Maximum Linear Value W N/A
4-20mA: Type: Signed, Scale: 1, Unit: mA, Range: -32768 - 32767mA
0-10V: Type: Signed, Scale: 1, Unit: Volt, Range: -32768 - 32767V
119 40120 Universal Input 1 Linear Value Bias W N/A
4-20mA: Type: Signed, Scale: 1, Unit: mA, Range: -32768 - 32767mA
1= 0-10V 5= 10K Type2/3A1/NTC(Danfoss)
2= 4-20mA 6= 10K NTC Carel
120 40121 Universal Input 2 Mode Unsigned W 6
3= Dry Contact 7= 20K Type6A1
4= 10K Type3/G/4A1 8= 30K Type6A1
10K NTC Carel, 10K Type 2/3A1/NTC(Danfoss), 20K Type 6AI, 30K Type 6AI, 10K Type 3/G/4A1:
121 40122 Universal Input 2 Reading Bias Type: Signed, Scale:100, Unit: ºC, Range: -327.68 - 327.67ºC W 0ºC
Type: Signed, Scale:100, Unit: ºF, Range: -557.82 - 621.08 ºF
122 40123 Universal Input 2 Linear Value Scale 0-10V, 4-20mA: Type: Unsigned, Scale:1000, Unit: No Unit, Range: 0.001, 0.01, 0.1, 1 or 10 W N/A
123 40124 Universal Input 2 Minimum Voltage 0-10V, 4-20mA: Type: Unsigned, Scale:1000, Unit: Volt, Range: 0.00 - 65.535V W N/A
124 40125 Universal Input 2 Maximum Voltage 0-10V, 4-20mA: Type: Unsigned, Scale:1000, Unit: Volt, Range: 0.00 - 65.535V W N/A
0-10V: Type: Signed, Scale: 1, Unit: Volt, Range: -32768 - 32767V
125 40126 Universal Input 2 Minimum Linear Value W N/A
4-20mA: Type: Signed, Scale: 1, Unit: mA, Range: -32768 - 32767mA
0-10V: Type: Signed, Scale: 1, Unit: Volt, Range: -32768 - 32767V
126 40127 Universal Input 2 Maximum Linear Value W N/A
4-20mA: Type: Signed, Scale: 1, Unit: mA, Range: -32768 - 32767mA
0-10V: Type: Signed, Scale: 1, Unit: Volt, Range: -32768 - 32767V
127 40128 Universal Input 2 Linear Value Bias W N/A
4-20mA: Type: Signed, Scale: 1, Unit: mA, Range: -32768 - 32767mA
1= 0-10V 5= 10K Type2/3A1/NTC(Danfoss)
2= 4-20mA 6= 10K NTC Carel
128 40129 Universal Input 3 Mode Unsigned W 6
3= Dry Contact 7= 20K Type6A1
4= 10K Type3/G/4A1 8= 30K Type6A1
10K NTC Carel, 10K Type 2/3A1/NTC (Danfoss), 20K Type 6AI, 30K Type 6AI, 10K Type 3/G/4A1:
129 40130 Universal Input 3 Reading Bias Type: Signed, Scale:100, Unit: ºC, Range: -327.68 - 327.67ºC W 0ºC
Type: Signed, Scale:100, Unit: ºF, Range: -557.82 - 621.08 ºF
130 40131 Universal Input 3 Linear Value Scale 0-10V, 4-20mA: Type: Unsigned, Scale:1000, Unit: No Unit, Range: 0.001, 0.01, 0.1, 1 or 10 W N/A
131 40132 Universal Input 3 Minimum Voltage 0-10V, 4-20mA: Type: Unsigned, Scale:1000, Unit: Volt, Range: 0.00 - 65.535V W N/A
132 40133 Universal Input 3 Maximum Voltage 0-10V, 4-20mA: Type: Unsigned, Scale:1000, Unit: Volt, Range: 0.00 - 65.535V W N/A
www.neptronic.com Page | 21
Remote I/O Communication Module
Specification and Installation Instructions
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
www.neptronic.com Page | 22
Remote I/O Communication Module
Specification and Installation Instructions
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
www.neptronic.com Page | 23
Remote I/O Communication Module
Specification and Installation Instructions
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
www.neptronic.com Page | 24
Remote I/O Communication Module
Specification and Installation Instructions
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
www.neptronic.com Page | 25
Remote I/O Communication Module
Specification and Installation Instructions
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
www.neptronic.com Page | 26
Remote I/O Communication Module
Specification and Installation Instructions
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
www.neptronic.com Page | 27
Remote I/O Communication Module
Specification and Installation Instructions
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
www.neptronic.com Page | 28
Remote I/O Communication Module
Specification and Installation Instructions
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
www.neptronic.com Page | 29
Remote I/O Communication Module
Specification and Installation Instructions
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
www.neptronic.com Page | 30
Remote I/O Communication Module
Specification and Installation Instructions
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
www.neptronic.com Page | 31
Remote I/O Communication Module
Specification and Installation Instructions
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
www.neptronic.com Page | 32
Remote I/O Communication Module
Specification and Installation Instructions
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
www.neptronic.com Page | 33
Remote I/O Communication Module
Specification and Installation Instructions
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
www.neptronic.com Page | 34
Remote I/O Communication Module
Specification and Installation Instructions
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
www.neptronic.com Page | 35
Remote I/O Communication Module
Specification and Installation Instructions
Protocol Holding
Base Register
Description Data Type Units/Values Writable Default Value
365 40366 Analog Output 7 Failsafe Mode*** Unsigned 1 = Last State | 2 = Preset W 2
Unsigned
366 40367 Analog Output 7 Preset*** Unit: Volt (V), Range: 0V to 10V, Value x 1000 (e.g. 2V = 2000) W 0V
Scale 1000
367 40368 Analog Output 8 Failsafe Mode*** Unsigned 1 = Last State | 2 = Preset W 2
Unsigned
368 40369 Analog Output 8 Preset*** Unit: Volt (V), Range: 0V to 10V, Value x 1000 (e.g. 2V = 2000) W 0V
Scale 1000
369 40370 Binary Output 1 Failsafe Mode Unsigned 1 = Last State | 2 = Open | 3 = Closed W 2
370 40371 Binary Output 2 Failsafe Mode Unsigned 1 = Last State | 2 = Open | 3 = Closed W 2
371 40372 Binary Output 3 Failsafe Mode Unsigned 1 = Last State | 2 = Open | 3 = Closed W 2
372 40373 Binary Output 4 Failsafe Mode Unsigned 1 = Last State | 2 = Open | 3 = Closed W 2
373 40374 Binary Output 5 Failsafe Mode Unsigned 1 = Last State | 2 = Open | 3 = Closed W 2
374 40375 Binary Output 6 Failsafe Mode Unsigned 1 = Last State | 2 = Open | 3 = Closed W 2
375 40376 Binary Output 7 Failsafe Mode Unsigned 1 = Last State | 2 = Open | 3 = Closed W 2
376 40377 Binary Output 8 Failsafe Mode Unsigned 1 = Last State | 2 = Open | 3 = Closed W 2
377 40378 Binary Output 9 Failsafe Mode Unsigned 1 = Last State | 2 = Open | 3 = Closed W 2
378 40379 Binary Output 10 Failsafe Mode Unsigned 1 = Last State | 2 = Open | 3 = Closed W 2
379 40380 Binary Output 11 Failsafe Mode Unsigned 1 = Last State | 2 = Open | 3 = Closed W 2
380 40381 Binary Output 12 Failsafe Mode Unsigned 1 = Last State | 2 = Open | 3 = Closed W 2
381 40382 Binary Output 13 Failsafe Mode**** Unsigned 1 = Last State | 2 = Open | 3 = Closed W 2
382 40383 Binary Output 14 Failsafe Mode**** Unsigned 1 = Last State | 2 = Open | 3 = Closed W 2
383 40384 Binary Output 15 Failsafe Mode**** Unsigned 1 = Last State | 2 = Open | 3 = Closed W 2
384 40385 Binary Output 16 Failsafe Mode**** Unsigned 1 = Last State | 2 = Open | 3 = Closed W 2
*** Only available when JP3 - JP6 jumpers (UO1 - UO4 selector) are set to AO5 - AO8.
**** Only available when JP3 - JP6 jumpers (UO1 - UO4 selector) are set to BO13 - BO16.
Recycling at end of life: please return this product to your Neptronic local distributor for recycling. If you need to find the nearest Neptronic authorized distributor, please consult www.neptronic.com.
www.neptronic.com Page | 36