Power Cables
Power Cables
This Technical Information Sheet (TIS) covers Lifeline® RHW-2 Cables: UL Certified and Listed Two Hour Fire
Resistive Cable for use in EMT Conduit and BreathSaver® XW Phenolic Conduit
Prysmian Group
4 Tesseneer Drive, Highland Heights, KY 41076
+1-859-572-8000 / na.prysmiangroup.com
SPL-FPT-0013-Issued March 2022
Manufacturer’s Instructions for
Lifeline® Power Cables
Prysmian Group
4 Tesseneer Drive, Highland Heights, KY 41076
+1-859-572-8000 / na.prysmiangroup.com
SPL-FPT-0013-Issued March 2022
Lifeline® Power Cables: RHW-2 Fire Resistive Cables in
EMT Conduit and BreathSaver® XW Phenolic Conduit
UL 2196 Certified Fire Resistive Cable for Survivability in a Fire
• ST1
• IEEE 1202
• NFPA 70, NFPA 72, NFPA 101, NFPA 130 and NFPA 502 RoHS
COMPLIANT
LISTED
Prysmian Group
4 Tesseneer Drive, Highland Heights, KY 41076
+1-859-572-8000 / na.prysmiangroup.com
SPL-FPT-0013-Issued March 2022
Lifeline® Power Cables: RHW-2 Fire Resistive Cables in
EMT Conduit and BreathSaver® XW Phenolic Conduit
UL 2196 Certified Fire Resistive Cable for Survivability in a Fire
G30070 1/0 19 0.100 (2.5) 0.61 (15.5) 441 (656) 150 170
G30071 2/0 19 0.100 (2.5) 0.65 (16.6) 535 (796) 175 195
G30072 3/0 19 0.100 (2.5) 0.70 (17.9) 656 (976) 200 225
G30073 4/0 19 0.100 (2.5) 0.76 (19.2) 803 (1195) 230 260
G30074 250 37 0.130 (3.3) 0.86 (21.9) 987 (1469) 255 290
G31501 300 37 0.130 (3.3) 0.92 (23.4) 1160 (1726) 285 320
G30075 350 37 0.130 (3.3) 0.97 (24.7) 1306 (1943) 310 350
G31496 400 37 0.130 (3.3) 1.02 (25.9) 1500 (2232) 335 380
G30076 500 37 0.130 (3.3) 1.10 (27.9) 1820 (2708) 380 430
G30077 600 61 0.145 (3.7) 1.21 (30.6) 2199 (3272) 420 475
G30078 750 61 0.145 (3.7) 1.31 (33.3) 2699 (4016) 475 535
1
Ampacities are based on Table 310.16 of the National Electrical Code (NFPA 70) for 3 current carrying conductors at 30°C ambient.
The above dimensions are approximate and subject to normal manufacturing tolerances. Information subject to change without notice.
Prysmian Group
4 Tesseneer Drive, Highland Heights, KY 41076
+1-859-572-8000 / na.prysmiangroup.com
SPL-FPT-0013-Issued March 2022
Lifeline® Power Cables: RHW-2 Fire Resistive Cables in
EMT Conduit and BreathSaver® XW Phenolic Conduit
UL 2196 Certified Fire Resistive Cable for Survivability in a Fire
Conductor Horizontal Installation in EMT Conduit - Horizontal Installation in XW BreathSaver Conduit - Vertical Installation in XW BreathSaver Conduit -
Size Number of Conductors Number of Conductors Number of Conductors
1 2 3 4 1 2 3 4 1 2 3 4
6 3/4 1-1/4 1-1/4 1-1/2 3/4 1 1-1/4 1-1/4 1 1-1/2 2-1/2 2-1/2
1/0 1-1/4 2 2-1/2 2-1/2 1-1/4 1-1/2 2-1/2 2-1/2 2 3 3-1/2 3-1/2
3/0 1-1/2 2-1/2 2-1/2 3 1-1/4 1-1/2 2-1/2 2-1/2 2-1/2 3-1/2 4 4
For questions regarding installation and conduit size, including the use of ECG, contact the Lifeline team at Prysmian Cables & Systems USA, LLC (800) 333-4248 x2600.
Prysmian Group
4 Tesseneer Drive, Highland Heights, KY 41076
+1-859-572-8000 / na.prysmiangroup.com
SPL-FPT-0013-Issued March 2022
3/1/23, 8:26 PM FHIT.25C - Electrical Circuit Integrity Systems | UL Product iQ
https://iq.ulprospector.com/en/profile?e=34446 1/5
3/1/23, 8:26 PM FHIT.25C - Electrical Circuit Integrity Systems | UL Product iQ
Fig. 1
Two-piece Single-bolt Pipe Clamp
Fig. 2
Steel Strut Trapeze
1. Wall or Floor Assembly* — Minimum 2 hour fire rated concrete or masonry wall or concrete floor. Opening in wall or floor
through which raceway passes is to be sized to closely follow the contour of the raceway. Through opening in wall or floor to be
firestopped using a compatible firestop system.
See Through-penetration Firestop Systems (XHEZ) category for presently Certified firestop systems.
2. Raceway* — Reinforced Thermosetting Resin Conduit. Horizontal or Vertical installation; or EMT type steel conduit. Horizontal
installation.
FRE COMPOSITES INC — BreathSaver Brand Type XW Conduit and Type XW elbows as follows:
https://iq.ulprospector.com/en/profile?e=34446 2/5
3/1/23, 8:26 PM FHIT.25C - Electrical Circuit Integrity Systems | UL Product iQ
600 2-1/2 3 4 5 3 4 5 5
ALLIED TUBE & CONDUIT CORPORATION — Type EMT E-Z Pull Brand
4 1 1-1/4 1-1/2 2
3 1 1-1/4 1-1/2 2
2 1 1-1/4 1-1/2 2
1 1-1/4 2 2 2-1/2
4/0 2 2-1/2 3 3
250 2 2-1/2 3 3
400 2 3 4 4
https://iq.ulprospector.com/en/profile?e=34446 3/5
3/1/23, 8:26 PM FHIT.25C - Electrical Circuit Integrity Systems | UL Product iQ
600 2-1/2 3 4 —
RACO — Steel (all components) EMT Compression Couplings. Trade size to correspond with the EMT raceway size.
3. Fire Resistive Cables* — The hourly fire rating applies to cable passing completely through a fire zone and terminating a minimum
of 12 inches beyond the fire rated wall or floor bounding the fire zone.
PRYSMIAN CABLES AND SYSTEMS USA LLC — Type RHW-2 Lifeline Brand of the following part numbers: G300 followed by 64, 65, 66, 67, 68,
69, 70, 71, 72, 73, 74, 75, 76, 77, 78; or G31501 or G31496. To be installed as described herein and in accordance with the manufacturer's
installation instructions SPL-FPT-0013 (TIS301H) dated Sep 2020, SPL-FPT-0012 dated March 2022.
4. Supports — (Figure 1) — Min 12 gauge, by 1-1/2 in. wide or 1-5/8 in wide, painted or unpainted, slotted steel channels with
hemmed flange edges. Channel bottom with or without holes. Lengths of slotted steel channels 5 ft and less shall be secured to the
wall or floor with a min of two 1/4 in. diameter (or larger) by 2-1/4 in. min long concrete screws, or 1/4 in. diameter (or larger) by 1-
3/4 in. long min steel masonry anchors. One screw or anchor to be located at each end of the slotted steel channel. Lengths of slotted
steel channel in excess of 5 ft require a min of three screws or anchors, one at each end of the channel and one centrally located
within the length of the channel. The supports shall be spaced a maximum of 5 ft. OC. When installing cable(s) in vertical runs, the
maximum distance of cable within raceway shall be 24 ft.
4A. Trapeze-type Supports — (Figure 2) — The raceways shall be installed on/from trapeze-type supports. The trapeze-type supports
shall be secured from the surface of the floor. The supports shall be spaced a maximum of 5 ft. OC.
5. Clamps — Steel 1-1/4 in. wide two-piece single-bolt pipe clamps. Size to correspond with the outside diameter of the raceway and
as follows: Trade size 3/4-2 in. conduit, min 14-gauge; Trade size 2-1/2 in. conduit, min 12-gauge; Trade size 3 in. and larger conduit,
min 11-gauge.
6. Pulling Lubricant — (Not Shown) — When installing cables within a raceway, the cables shall be coated with pulling lubricant.
AMERICAN POLYWATER CORP — Polywater LZ
7. Pull Box — (Optional Not Shown) — Cables installed in the horizontal or vertical orientation within type XW raceway, or in the
horizontal orientation within EMT raceway, may utilize a Resolve One NEMA-4X stainless steel industrial control panel enclosure. Refer
to the manufacturer's installation instructions, for additional details.
8. Pull Box — (Optional Not Shown) — Cables installed in the horizontal orientation within EMT raceway may utilize a Wiegmann
NEMA-3R steel cutout box enclosure. Refer to the manufacturer's installation instructions, for additional details.
9. Insulating Bushing — For installation with item 8A. Prysmian P/N CUSEMT. Refer to the manufacturer's installation instructions, for
additional details.
https://iq.ulprospector.com/en/profile?e=34446 4/5
3/1/23, 8:26 PM FHIT.25C - Electrical Circuit Integrity Systems | UL Product iQ
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL Solutions' Follow - Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL
Solutions' Follow - Up Service. Always look for the Mark on the product.
UL Solutions permits the reproduction of the material contained in Product iQ subject to the following conditions: 1. The Guide Information,
Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading manner,
without any manipulation of the data (or drawings). 2. The statement "Reprinted from Product iQ with permission from UL Solutions" must appear
adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "©2023 UL LLC."
https://iq.ulprospector.com/en/profile?e=34446 5/5
SPECIFICATION FOR CERTIFIED
XW FOR CORROSION PROOF
2-HOUR RATED CABLE SYSTEM (UL 2196 | FHIT 25C)
75 Wales, Saint-André-d’Argenteuil, Québec, CANADA J0V 1X0 | +1 450 537-3311 | Fax: +1 450 537-3415
60 Greenhorn Drive, Pueblo, Colorado, 81004, USA | +1 719 565-3311 | Fax: +1 719 564-3415
Toll free: +1 888 849-9909 | frecomposites.com
F1RST
IN THE1: DESCRIPTION & LISTING
SECTION
FIELD ®
1.1 Description
This specification outlines the requirements for the design, construction and performance of the Extra Heavy Wall (XW) BreathSaver Reinforced Thermosetting
®
1.3 Materials
Conduits and fittings shall consist of continuous E or E-CR glass roving in a cured corrosion resistant phenolic resin system pigmented with UV inhibiting
carbon black dispersed homogeneously manufactured for use at temperatures ranging from –40 °F (-40 °C) to 1850 °F (1010 °C). No resorcinol resin
based system shall be allowed.
Phenolic resin system shall be impervious to a wide spectrum of chemicals. Conduit shall contain no halogens as chlorine and shall not contain other toxic
materials in excess of trace levels limits compliant with OSHA requirements.
1.4 Joining Method
Each length of conduit is supplied with an integral bell on one end and spigot on the other end. All joints shall be adhesive bonded inside a bell end of even
socket depth through out the raceway. Adhesive shall be supplied by the manufacturer of the conduit and shall have a minimum joint pull out load of 1
000 lb, (454 kg) per inch diameter trade size.
1.5 Fittings
All fittings, adapters and elbows shall be constructed in the same manner as the conduit (filament wound) and shall have a socket depth and an inside bell
design consistent with the conduit.
SECTION 2: DIMENSIONS
2.1 Sizes & wall thicknesses
Conduits and fittings shall be manufactured with nominal wall thicknesses as outlined below:
SECTION 3: REQUIREMENTS
3.1 Workmanship
Conduits and fittings shall be free from defects and commercially practicable in color, opacity, density and other physical properties. The exterior surface
finish shall be smooth per acceptable industry practices.
3.2 Marking
Conduits and fittings shall be marked with a suitable identifying mark printed on the outside of the product. Such marking shall contain:
(1) RTRC (2) for use -40 °F (40 °C) to 1850 °F (1010 °C) (3) trade size (4) manufacturer’s name or trademark (5) part number (6) degrees and radii (elbows
only) (7) date of manufacture.
Rev.3 | 04/19
3.3 Specifications
All Conduits and Fittings are UL listed against UL 2515A following tests made in laboratory by Underwriters Laboratories (UL file #E53373).
Furthermore, products comply with the NFPA 130 as well as NFPA 502 for exposed installations, FT4 rated (CSA). Product identified in Section 2.1 with “*”
is not UL Listed as 8” is not a recognized trade size dimension per National Electric Code (NEC) and Canadian Electric Code (CEC).
SECTION 5: MANUFACTURER
Conduits and fittings shall be manufactured by FRE Composites. No substitute shall be accepted.
This document is the property of FRE Composites Inc. (“FRE Composites”). It shall not be used, reproduced, copied or transmitted to other persons without written authorization.
composites.com
Rev.3 | 04/19
EMT and Color EMT
Submittal Sheet
in trade sizes ½–4, in a variety its EMT for weld strength, bendability,
plating thickness, all dimensions,
of colors. and uniform smoothness of the
interior coating.
1/2 16 0.706 0.622 0.042 0.30 100 700 7000 2100 Black
3/4 21 0.922 0.824 0.049 0.46 100 500 5000 2300 Red
1 27 1.163 1.049 0.057 0.67 100 300 3000 2010 Blue
1 1/4 35 1.510 1.380 0.065 1.01 50 200 2000 2020 Red
1 1/2 41 1.740 1.610 0.065 1.16 50 150 1500 1740 Black
2 53 2.197 2.067 0.065 1.48 50 120 1200 1776 Blue
2 1/2 63 2.875 2.731 0.072 2.16 - 61 610 1318 Black
3 78 3.500 3.356 0.072 2.63 - 51 510 1341 Blue
3 1/2 91 4.000 3.834 0.083 3.49 - 37 370 1291 Black
4 103 4.500 4.334 0.083 3.93 - 30 300 1179 Blue
Master bundle quantities conform to NEMA Standard RN-2. All Western Tube conduit is UL Listed.
information
Submittal Information
LOCATIONS: COMMENTS:
WTE-111617
Project Information
Company Name:
Address:
City:
State & Zip:
Phone:
Project Name:
City:
State: www.alliedeg.com
Electrical Metallic Tubing (EMT) and True Color™ EMT
FEATURES & SPECIFICATIONS
Manufactured for Long Life Codes & Standards Compliance
Allied Tube & Conduit® EMT is precision manufactured Allied EMT is listed to Underwriters Laboratories Safety
from high grade mild strip steel for exceptional durability Standard UL 797 and meets ANSI C80.3. These standards
and long-lasting life. Allied EMT is hot galvanized using a have been adopted as federal specifications in lieu of WWC
patented inline Flo-Coat® process. This process combines 563. EMT is recognized as an equipment grounding conductor
zinc, a conversion coating, and a clear organic polymer by NEC Section 250-118. Documentation for compliance with
topcoat to form a triple layer of protection against corrosion NEC Article 250 is also available in the GEMI (Grounding and
and abrasion. Electro-Magnetic Interference) analysis software and related
research studies found at the www.alliedeg.com website.
E-Z Pull® EMT combines strength with ductility, providing easy
bending, cutting and joining while resisting flattening, kinking and Installation of EMT shall be in accordance with the National
splitting. Available in sizes 1/2 (16) - 4 (103). Electrical Code and the UL listing information. Allied EMT is
listed in category FJMX. Master bundles conform to NEMA
Coatings Standard RN2.
Allied’s EMT (Electrical Metallic Tubing) has a special low
friction ID coating called E-Z Pull that greatly improves the slip Specification Data
properties between conduit and wire. With To specify Allied EMT, include the following: Electrical Metallic
E-Z Pull EMT, wire pulls through the EMT smoothly and easily, Tubing shall be equal to that manufactured by Allied Tube &
making installation easier and faster. Conduit Corporation. EMT shall be hot galvanized steel O.D.
with an organic corrosion resistant I.D. coating, and shall
EMI Shielding be listed to UL Safety Standard 797 and manufactured in
Allied EMT is very effective in reducing electromagnetic accordance with ANSI C80.3.
field levels for encased power distribution circuits, shielding
computers and other sensitive electronic equipment from the
effects of electromagnetic interference.
For more information on EMT shielding, visit
www.alliedeg.com to obtain the GEMI (Grounding and Electro-
Magnetic Interference) software analysis program.
in mm in mm lb kg ft m ft m
1/2 16 0.706 17.93 0.042 1.07 30 13.6 7000 2135 3500 1066.8
3/4 21 0.922 23.42 0.049 1.24 46 20.9 5000 1525 2500 762.0
1 27 1.163 29.54 0.057 1.45 67 30.4 3000 915 1500* 457.2
1-1/4 35 1.510 38.35 0.065 1.65 101 45.8 2000 610 2000 609.6
1-1/2 41 1.740 44.20 0.065 1.65 116 52.6 1500 457.5 1500 457.2
2 53 2.197 55.80 0.065 1.65 148 67.1 1200 366.0 1200 365.7
2-1/2 63 2.875 73.03 0.072 1.83 216 98.0 610 186.1 610 185.9
3 78 3.500 88.90 0.072 1.83 263 119.3 510 155.6 510 155.4
3-1/2 91 4.000 101.60 0.083 2.11 349 158.3 370 112.9 370 112.7
4 103 4.500 114.30 0.083 2.11 393 178.3 300 91.5 300 91.5
1
Outside diameter tolerances: +/- .005 in. (.13mm) for trade sizes 1/2 (16mm) *Blue trade size 1 master bundle size: 3000 ft / 915 m
through 2 (53mm); ** Other Color Trade Sizes 2 - 4 are available thru special order
+/- .010 in. (.25mm) for trade sizes 2-1/2 (63mm); NOTE: Length = 10 ft. (3.05m) with a tolerance of +/- .25 in. (6.35 mm)
+/- .015 in. (.38mm) for trade size 3 (78mm);
+/- .020 in. (.51mm) for trade sizes 3-1/2 (91mm) and 4 (103mm).
Approximate D
Trade Metric Standard
Radius (A)1 Offset (B)2 Straight (D)1 Weight Per
Size Designator Package
100 Pieces
A
in mm in mm in mm lb kg
in mm in mm in mm lb kg B
3 78 15 381 24 1/4 616 9 1/4 235 921 417.8 D
3 78 18 457 27 7/8 708 9 7/8 251 1052 477.2
3 78 24 610 34 5/8 879 10 5/8 270 1293 586.5 B
3 78 30 762 41 1041 11 279 1512 685.8
3 78 36 914 46 3/4 1187 10 3/4 273 1710 775.7
3 78 42 1067 54 1372 12 305 1973 895.0
3 78 48 1219 60 1/4 1530 12 1/4 311 2192 994.3
3 1/2 91 18 457 27 7/8 708 9 7/8 251 1396 633.2
3 1/2 91 24 610 34 5/8 879 10 5/8 270 1716 778.4
3 1/2 91 30 762 41 1041 11 279 2007 910.4
3 1/2 91 36 914 46 3/4 1187 10 3/4 273 2269 1029.2
3 1/2 91 42 1067 54 1372 12 305 2618 1187.5
3 1/2 91 48 1219 60 1/4 1530 12 1/4 311 2908 1319.1
4 103 24 610 34 5/8 879 10 5/8 270 1932 876.4
4 103 30 762 41 1041 11 279 2260 1025.1
4 103 36 914 46 3/4 1187 10 3/4 273 2555 1158.9
4 103 42 1067 54 1372 12 305 2948 1337.2
4 103 48 1219 60 1/4 1530 12 1/4 311 3275 1485.5
2
For information only, not a requirement as per UL Standard
Sizes 2-1/2 (63) and larger shipped in palletized cartons or bulk.
Also available in the following Degrees (60°, 45°, 30°, 22-1/2°, 15° & 11-1/4°)
5F
breather/drains NEMA 4X
IP66
Features:
• International Ex approvals
• IP66, CSA enclosure type (NEMA) 4X
• Available in two thread lengths: 10mm two drain holes or 15mm
three drain holes
• Available in brass, stainless steel and glass-filled nylon
• Metric and NPT threads available
Standard materials:
• Brass CZ121
• 316 stainless steel
• Aluminum
• Glass-filled nylon
Ordering information:
DP E 3 0 29 S3
Certification Material Thread type Thread length
DESCRIPTION
Polywater LZ Lubricant is a high-performance,
cable pulling lubricant. Polywater LZ is compatible
with a broad variety of LSZH/LSHF compounds.
Polywater LZ is also compatible with other high-
performance cable jackets. It provides excellent
tension reduction and is recommended for all types
of cable pulling.
Polywater LZ is slow drying and leaves a thin,
slippery film that retains its lubricity for months after
use. Polywater LZ does not sustain flame when
used with fire-retardant cables and systems. Its
dried residue is nonconductive and
noncombustible.
Polywater LZ is a stringy gel. It can be applied by
hand or using Polywater’s LP-D5 Pump. It is also
available in the unique Front End Pack Polywater LZ is a specification grade lubricant
prelubrication bags. PRODUCT FEATURES
FRICTION TESTING • Low Friction Coefficient: Maximum tension
reduction on all types of cable jackets.
Lubricity: Polywater LZ shows superior friction
reduction on a variety of jacket types. Typical • Universal: Suitable for all types of jackets and
friction coefficients at 200 lbs/ft (2.91 kN/m) normal cable, including power, control, and
pressure are shown. Test results are based on the instrumentation cable.
method described in the white paper, “Coefficient of • Low-Smoke Zero Halogen (LSZH/LSHF)
Friction Measurement on Polywater’s Friction Compatible: Extensively tested on LSZH/LSHF
Table, 2007” (polywater.com/FTable.pdf). Values thermoplastic and thermoset jackets.
are averages based on cable jacket and conduit
materials from multiple manufacturers.
END USE
CABLE CONDUIT TYPE
JACKET Polywater LZ is a specification grade lubricant that
STEEL FRP HDPE PVC EMT
meets the performance requirements of:
LSZH .16 .17 .07 .08 .21
CSPE .21 .24 .12 .16 .24 • Nuclear and other generation plants
CPE .15 .19 .09 .10 .17 • Mass transit systems and airports
XLPE .13 .12 .06 .06 .12
• Oil and petrochemical
LLDPE .10 .11 .05 .06 .13
60%
A six-inch length (152 mm) of a one-inch (25 mm)
diameter cable will hold at least 35 grams of
40% Polywater LZ for one minute when held vertically at
70°F (21°C).
20%
Coatability:
0% Coatability is a measure of the lubricant’s ability to
Tensile vs Tensile vs Elongation Elongation Tensile vs Elongation
NonAged, Water, vs vs Water, Water, vs Water,
coat the jacket as a thin film for continued lubricity
100° C 100° C NonAged, 100° C 50°C 50° C on longer pulls.
100° C
Polywater LZ will wet out evenly on cable jacket
Polyethylene Stress Cracking: surfaces. It will not bead up or rub off the jacket
Polywater LZ shows no stress cracking on LDPE, sample. A one-inch (25 mm) diameter XLPE cable
MDPE, or HDPE cable jackets when tested per dipped six inches (152 mm) into Polywater LZ, then
IEEE Standard 12101. withdrawn and held vertically, will retain at least 25
Volume Resistivity: grams of Polywater LZ for one minute at 70°F
There are no significant changes in the conductive (21°C).
properties of XLPE and EPR semi-conducting Combustibility:
compounds when volume resistivity is tested Combustibility is a measure of combustion
according to IEEE Standard 12101. properties of the lubricant residue in a fire situation
Building Wire Testing: (with an impinging heat flux).
THHN and XLPE building wire meet UL tensile, Polywater LZ has no flash point and its dried
elongation, and voltage withstand requirements residue will not support combustion and spread
after exposure to Polywater LZ as tested by UL flame. A 15-gram sample of the Polywater LZ,
requirements2. when placed in a one-foot, split, metal conduit and
Cable Approvals: fully dried for 24 hours at 105°C, will not ignite and
Polywater LZ is approved by many cable spread a flame more than three inches beyond the
manufacturers. Contact American Polywater for point of ignition when subjected to a continuous
details. heat flux of 85 kW/m2. The total test time was 30
1
minutes.
IEEE Std 1210-2004; IEEE Standard Tests for Determining
Compatibility of Cable-Pulling Lubricants with Wire and Cable. Test method described in “Fire Parameters and Combustion Properties
of Cable Pulling Compound Residues,” presented to the International
2
UL Subject 267, Investigation for Wire-Pulling Compounds. Wire & Cable Symposium, 1987.
APPLICATION PROPERTIES DIRECTIONS FOR USE
Application Systems: Polywater LZ can be hand applied or pumped onto
Polywater LZ has a stringy gel consistency that the cable as it enters the conduit.
makes it easy to lift, carry, and hand apply.
For long pulls, place approximately two-thirds of the
Polywater LZ can also be pumped directly into the recommended quantity of lubricant into the conduit
conduit or onto the cable using the Polywater using the Front End Packs or by pumping.
LP-D5 specialty lubricant pump. This allows
For Front End Packs use, attach the packs of
hands-free transfer and consistent application of
Polywater LZ to the winch line or pulling rope in
lubricant. Polywater’s low-shear pump will not
front of the cable by using tape or cable ties. Start
change the gel character of Polywater LZ. The
the pull and slit open the entire length of the pack(s)
LP-D5 pump applies lubricant at a rate of 1–2
with a sharp knife as it enters the conduit.
gallons (4–8 liters) per minute.
Supplement with direct jacket lubrication as the
Polywater LZ Front End Packs are bag packages
cable enters the conduit.
that “prelubricate” the head end of the cable during
the pull. The Front End Pack attaches to the winch Clean up by wiping off any excess lubricant with a
line and prelubricates as it goes through the rag.
conduit. Two sizes are available to fit 2” and larger
conduits.
Pull-Planner™ Tension Calculation Software is
available from Polywater. Pulling tension
estimations can ensure the use of appropriate Recommended Lubricant Quantity:
pulling equipment and that the cable is installed
within safe limits. Q=kXLXD
Polywater LZ is also available in a special-order, Where:
pourable version (lower viscosity) called Polywater Q = quantity in gallons (liters)
PLZ.
L = length of conduit run in feet (meters)
Temperature Use Range:
Polywater LZ: D = ID of the conduit in inches (mm)
20°F to 120°F (-5°C to 50°C). k = 0.0015 (0.0008 if metric units)
Polywater WLZ (Winter Grade version):
-20°F to 120°F (-30°C to 50°C) The quantity that is appropriate for any given pull
can vary from this recommendation by 50%,
Temperature Stability: depending on the complexity of the pull. Consider
Polywater LZ will not phase-out or separate after the following factors:
five freeze/thaw cycles or 5-day exposure at 120°F
Cable weight and stiffness
(50°C).
(Increase quantity for stiff, heavy cable)
Cleanup:
Conduit condition
Polywater LZ is nonstaining. Complete cleanup is
(Increase quantity for old, dirty, or rough conduits)
possible with water.
Conduit fill
Storage and Shelf Life:
(Increase quantity for high percent conduit fill)
Store Polywater LZ in a tightly sealed container
away from direct sunlight. Lubricant shelf life is 24 Number of bends
months. (Increase quantity for pulls with several bends)
Pulling environment
(Increase quantity for high temperatures)
MODEL SPECIFICATION ORDER INFORMATION
The statement below may be inserted into a CAT # PACKAGE DESCRIPTION
specific job specification to help maintain LZ-55 ½-gal. bag in a box (1.9 liters)
engineering standards and ensure project 6/case
integrity. LZ-110 ½-gal. bag in a pail (1.9 liters)
10/pail
LZ-35 1-qt. squeeze bottle (.95 liter)
The cable pulling lubricant shall be Polywater LZ 12/case
Lubricant. The cable pulling lubricant shall provide LZ-128 1-gal. pail (3.78 liter) 4/case
excellent friction reduction with good cling and
wetting through long pulls and multiple bends. The LZ-640 5-gal. pail (18.9 liter)
lubricant shall leave minimal, noncombustible
LZ-DRUM 55-gal. drum (208 liter)
residue. It shall be compatible with most cable
jacket materials and be extensively tested on a Winter Grade
broad variety of low smoke, halogen-free cable
jacket materials. WLZ-55 ½-gal. bag in a box (1.9 liters)
Cable jacket compatibility shall be tested with the 6/case
specific LSZH jacket material used on the cable. WLZ-110 ½-gal. bag in a pail (1.9 liters)
10/pail
Test data shall be provided by the cable
WLZ-35 1-qt. squeeze bottle (.95 liter)
manufacturer or the lubricant manufacturer. It shall 12/case
not stress crack polyethylene per ASTM Standard WLZ-128 1-gal. pail (3.78 liter) 4/case
1693. There shall be no significant changes in the
conductive properties of XLPE and EPR semi- WLZ-640 5-gal. pail (18.9 liter)
conducting compounds when the lubricant’s effect
on volume resistivity is tested according to IEEE
Standard 1210.
A 15-gram sample of the lubricant, when placed in
a one-foot, split metal conduit and fully dried for 24
hours at 105 degrees C, shall not spread a flame
more than three inches beyond a point of ignition
at a continued heat flux of 85 kW/meter2. Total
time of test shall be 30 minutes.
CONTACT US
1-800-328-9384 Toll Free | 1-651-430-2270 Main | 1-651-430-3634 Fax | email: [email protected]
IMPORTANT NOTICE: The statements here are made in good faith based on tests and observations we believe to be reliable. However, the completeness and accuracy of the information is not
guaranteed. Before using, the end-user should conduct whatever evaluations are necessary to determine that the product is suitable for the intended use.
American Polywater expressly disclaims any implied warranties and conditions of merchantability and fitness for a particular purpose. American Polywater’s only obligation shall be to
replace such quantity of the product proven to be defective. Except for the replacement remedy, American Polywater shall not be liable for any loss, injury, or direct, indirect,
or consequential damages resulting from product’s use, regardless of the legal theory asserted.
The installation of the “Insulating Bushing” is required as part of FHIT 25C, Item 9; and
within TIS 301H (Manufacturers Installation Instructions), Item 5.
The Insulation Bushings are only required when installing the Lifeline® RHW-2 system with
the approved EMT conduits/connectors. The bushings are designed to be placed inside
the inner diameter of the connector from inside an enclosure after the Lifeline® RHW-2
cables have been installed. The purpose of these bushings is to prevent the cable from
shorting to the connector during a fire event. Occasionally, during very high temperature
fires, EMT conduits can become malleable and begin to sag which creates tension on the
cables inside the conduits/enclosures. This added tension may lead to the ceramified
insulation on the wires to rub against the connector body as the wires exit (into the
enclosure) the connector. Generally, this happens when the wires in the enclosure are bent
causing each wire to move to one side of the connector housing. Tension may cause the
wire(s) to rub on the connector side they are closest to.
To prevent the remote chance of an electrical short from occurring, Prysmian has selected
and tested a woven silica fabric that can withstand extremely high temperatures while
providing insulating properties. The approved woven silica fabric (called a tape by the
manufacturer) is AVSil Silica Woven Tape Type WT65CH. Prysmian supplies this silica
woven “tape” in lengths pre-cut for EMT connector sizes per the catalog numbers below:
While each bushings length is cut per the ID of the connector, the width is constant at 3
inches. This extra width allows for a minimum of ½ inch to overhang past the end of the
EMT connector.
To install the bushing, simply wrap the bushing around the exposed cables within the
enclosure and slide the bushing fabric 2½ inches into connector with ½ inch outside
connector. This may require some movement of the cables to ensure the bushing is in
place. Fold the ½ inch excess fabric (outside connector) over the threaded OD of the
The following pages will show technical data sheets and safety data sheets for the silica
woven tape as well as the 3M 69 Glass Cloth Tape.
A video tutorial on how to apply the Insulating Bushing can be found here: Link to Video
Colin Williams
Technical Account Manager
TDS-13
May 2019
AVSIL® SILICA WOVEN TAPES
Product Description
AVSil® WT19, WT180, WT36CH and WT65CH are “woven edge” silica tapes for protection of electrical lines,
piping and equipment from fire, extreme heat, welding splatter and molten metal. AVSil® WT19, WT180,
WT36CH and WT65CH represents four different thickness of silica tape, and all have the added benefit of
woven edges to prevent unraveling. AVSil® Silica Woven Tapes can withstand thermal temperatures up to
1800°F (982°C) for extended periods of time. These tapes are used in high temperature applications as
insulation or thermal protection over: electrical cabling, pipe, water jacketed tubing, cords, and hoses. AVSil®
Silica Woven Tapes are also used as “mop style” furnace curtains, furnace door gasketing, high temperature
seals, and as a replacement for refractory ceramic fiber tape. AVSil® Silica Woven Tapes are used
extensively in the Power Generation, Shipbuilding, Construction, Welding and Metal Processing industries.
Features Benefits
• Resists high temperature and penetration of • Protects cables, pipes, cords and other
molten metal weld “slag” equipment in the toughest welding applications
• Fireproof • Protects against hot work fires
• Woven edge • Does not unravel like slit tape
• Excellent insulating properties • Lower energy costs
• Can be used in fabrication • Reinforces edges of blankets & curtains
Technical Data
Typical Properties WT19 WT180 WT36CH WT65CH
Silicon Dioxide Content ≥96% ≥96% ≥96% ≥96%
Nominal Thickness (inches/mm) 0.015/0.381 0.250/6.35 0.062/1.57 0.125/3.17
Nominal Roll Length (feet/meters) 100/30.48 50/15.24 100/30.48 50/15.24
NOTES:
1. WT19 is available in 1.5” width only. WT180 is available in 1”, 2” and 3” width only. WT36CH and WT65CH
tapes are available in .5”, 1”, 1.5”, 2”, 3”, 4” and 6” width.
2. Rolls may consist of three pieces. Minimum piece length is 10 feet (3.09 meters).
3. Other roll lengths are available upon request.
4. Silica tapes are made of amorphous silica and contain no asbestos or ceramic fibers.
5. The melt point of all AVSil® Silica Woven Tapes is 3000°F (1648°C).
AVS Industries cannot predict all of the potential applications for which customers may attempt to use the AVSil® Silica Woven Tapes. AVSil® Silica
Woven Tapes will have varying degrees of effectiveness for each potential application depending on the maximum temperature attained, the length of
use, and the amount of temperature fluctuation. If the customer has any questions regarding the use of AVSil® Silica Woven Tapes in a particular
application, please contact AVS Industries at (302) 221-1720 and we will provide a sample of the AVSil® Silica Woven Tape for testing. This product is
not warranted against injuries or damages of any kind caused by uses for which this product was not designed, intended, or tested by AVS Industries.
________________________________________________________________________________________________________
AVS Industries, LLC ● 21 Bellecor Drive ● Unit C ● New Castle, Delaware 19720
Tel: (302) 221-1720 ● Fax: (302) 221-1721 ● www.avsind.com
WHEN THE HEAT IS ON, KEEP YOUR COOL WITH AVS!
Manufacturer:
AVS Industries LLC Phone Product Information (302) 221-1720
21 Bellecor Drive Revision Date: May 31, 2019
Unit C
New Castle, DE 19720
DESCRIPTION
No Hazard Rating is available for this Product
2. Hazard Identification
Emergency Overview
Off-White or tan colored flexible woven tape with no odor.
Effects of Overexposure:
Inhalation: Inhalation of airborne fibers may cause irritation to the mouth, nose and throat.
Ingestion: May cause temporary irritation of the digestive tract, but not an expected route of entry in industrial
uses.
Chronic Hazards: There are no known chronic health effects associated with the use of this product under normal
working conditions.
Primary Routes of Entry: Skin contact, inhalation, ingestion & eye contact.
Carcinogenicity Information: None of the components present in this material at concentrations equal to or
greater than 0.1% are listed by IARC, NTP, OSHA or ACGIH as a carcinogen.
SDS-103
Page 2 of 4
Product: AVSil® Silica Woven Tape
3. Composition and Information on Ingredients
Eye Contact: Flush eyes immediately with large amounts of water for at least 15 minutes holding eyelids open
while flushing. Seek medical attention promptly.
Skin Contact: Wash contaminated skin thoroughly with mild soap and cool water. Seek medical attention if
irritation persists.
Inhalation: Remove person from source of exposure and then seek medical attention immediately.
Extinguishing Media: Carbon dioxide, water, foam or dry chemical as suitable for type of surrounding fire.
Unusual Fire & Explosion Hazards: During sustained fire irritating and/or toxic gases may be generated by
combustion.
Fire Fighting Instructions: Wear full fire-fighting protective equipment including self-contained breathing
apparatus.
Dust or loose fibers can be vacuumed or swept with the aid of a dust suppressant.
Dispose according to federal, state, and local environmental regulations.
Particular care should be taken when working with “used” material to minimize dust. If exposure limits are
exceeded or if irritation is experienced, NIOSH approved respiratory protection should be worn.
SDS-103
Page 3 of 4
Product: AVSil® Silica Woven Tape
8. Exposure Controls and Personal Protection
ENGINEERING CONTROLS:
Ventilation: General ventilation and/or local exhaust ventilation are adequate.
Respiratory Protection: Respirators are not necessary under normal working conditions.
Eye Protection: Eye protection is not necessary under normal working conditions.
Protective Clothing: Protective Clothing is not necessary under normal working conditions.
EXPOSURE LIMITS:
Amorphous Silica
PEL (OSHA) 80mg/m³ ÷ % SiO2 or 20 mppcf
TLV (ACGIH) 10 mg/m³ (inhalable); 3 mg/m³ (respirable)
NIOSH 6 mg/m³
IDHL 3000 mg/m³
PHYSICAL DATA:
Boiling Point: 4046° F
Melting Point: >3000° F
Solubility in Water: Insoluble
Vapor Pressure: N.D.
Vapor Density: N.D.
Specific Gravity: 2.2
Color: Off-white or tan colored
Odor: None
Physical State: Woven Tape
Incompatibilities: Basic phosphates, hydrofluoric acid, and some oxides and hydroxides.
Hazardous Polymerization: Hazardous polymerization will not occur under normal conditions.
Hazardous Decomposition Products (Coating Only): Oxidation of the coating produces carbon monoxide and
carbon dioxide.
Material which has been subjected to elevated temperatures (>1800°F) may undergo partial conversion to
cristobalite, a form of crystalline silica, which may cause respiratory illness. The amount of cristobalite present will
depend on the temperature and length of service. The OSHA PEL for cristobalite is 0.05 mg/m³ (respirable).
No information is available; however, toxicity is expected to be low based on the insolubility in water of the
product.
SDS-103
Page 4 of 4
Product: AVSil® Silica Woven Tape
13. Disposal Considerations
Dispose of waste material in accordance with applicable federal, state, and local environmental regulations.
TSCA: The chemical substances in this product are on the TSCA Section 8 Inventory.
EXPORT NOTIFICATION: This product contains the following chemical substances subject to the reporting
requirements of TSCA 12(B) if exported from the United States: None
This Material Safety Data Sheet was revised in its entirety in May 2019.
ABBREVIATIONS:
1) ACGIH – American Conference of Governmental Industrial Hygienists
2) OSHA – Occupational Safety and Health Administration
3) NIOSH – National Institute of Occupational Safety and Health
4) IARC – International Agency for Research on Cancer
5) NTP – National Toxicology Program
6) TLV – Threshold Limit Value
7) PEL – Permissible Exposure Limit
8) TWA – Time Weighted Average
9) STEL – Short Term Exposure Limit
10) IDHL – Immediately Dangerous to Life or Health
11) N.A. – Not Applicable
12) N.D. – Not Determined
13) N.E. – Not Established
14) DSL – Domestic Substances List
THE ABOVE INFORMATION IS BELIEVED TO BE ACCURATE BASED ON THE MOST CURRENT DATA AVAILABLE. AVS INDUSTRIES MAKES
NO WARRANTY, EITHER EXPRESSED OR IMPLIED, WITH RESPECT TO SUCH INFORMATION, AND ASSUMES NO LIABILITY RESULTING
FROM ITS USE. USERS ARE ADVISED TO CONDUCT THEIR OWN TESTS TO DETERMINE THE SAFETY AND SUITABILITY OF EACH PRODUCT
OR PRODUCT COMBINATION FOR THEIR OWN PURPOSES. AVS INDUSTRIES SHALL NOT BE LIABLE FOR ANY CLAIMS, LOSSES, OR
DAMAGES OF ANY THIRD PARTY OR FOR LOST PROFITS OR INCIDENTAL OR CONSEQUENTIAL DAMAGES, HOWSOEVER ARISING EVEN IF
AVS INDUSTRIES HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES.
3M™ Glass Cloth Electrical Tape 69
with Silicone Pressure-Sensitive
Adhesive
Description 3M™ Glass Cloth Electrical Tape 69 is a white glass cloth tape with a high-temperature
thermosetting silicone pressure-sensitive adhesive. It is designed for use in 600-volt
dry location applications motors, and transformers with and without varnish coating.
Key attributes like high mechanical strength and resistance to high temperatures
provide excellent performance. The thermosetting adhesive provides an increased
bond once applied in areas of high ambient temperatures. The thermosetting
adhesive provides elevated temperature performance up to Class N 392°F (200° C)
temperature rating.
This tape provides insulation and solvent-resistant protection for use as coil cover,
anchor, banding and core, layer and crossover insulation. This tape features a non-
corrosive adhesive. It is conformable, printable and flame retardant.
Agency Approvals,
Self Certifications,
MIL Specs
Meets Requirements of:
• Military Specification No. Mil-1-19166C
• UL Recognized Component listing for 200° C (Guide OANZ2, File E17385)
• CSA Accepted Component 180° C, File LR93411
RoHS Compliant 2002/95/EC” means that the product or part (“Product”) does not contain any of the substances in excess of
the maximum concentration values in EU Directive 2002/95/EC, as amended by Commission Decision 2002/618/EC, unless
the substance is in an application that is exempt under RoHS. This information represents 3M’s knowledge and belief, which
may be based in whole or in part on information provided by third party suppliers to 3M.
3
1 of 3
3M™ Glass Cloth Electrical Tape 69
Typical Properties
Data is not for specifications. Values are typical and should not be considered minimum or maximum.
Properties measured at room temperature 73° F (~23° C) unless otherwise stated.
2 of 3
3M™ Glass Cloth Electrical Tape 69
Specifications 3M™ Glass Cloth Electrical Tape 69 is a glass cloth electrical tape with a rubber
thermosetting adhesive. The tape shall be white and 7 mils (0,177 mm) thick. The
tape shall be coated on one side with pressure-sensitive adhesive which shall not
require heat, moisture, or other preparation prior to or subsequent to application. The
adhesive coating shall be smooth and uniform, and be free of lumps and bare spots.
There shall be no separator between adjacent layers of the roll. The tape shall be UL
Recognized under UL Standard 510. The tape shall perform at a temperature of 392°
F (200° C) without loss of physical or electrical properties.
Engineering/ All splices for 600-volt wire rated at 266° F (130° C) shall be insulated with a minimum
Architecture of two half-lapped layers of Scotch® Glass Cloth Electrical Tape 69.
Shelf Life & This product has a 5-year shelf life from date of manufacture when stored in a humidity
Storage controlled storage (50°F/10°C to 80°F/27°C and <75% relative humidity).
Availability 3M™ Glass Cloth Electrical Tape 69 is available in standard and custom lengths and
widths. Standard length is 36 yards.
For availability, please contact your local distributor. Names and addresses are
available from 3M.com/electrical [Where to Buy], or call 1-800-676-8381 or 1-800-245-
3573.
Important Notice All statements, technical information, and recommendations related to 3M’s products are based on
information believed to be reliable, but the accuracy or completeness is not guaranteed. Before using this
product, you must evaluate it and determine if it is suitable for your intended application. You assume all
risks and liability associated with such use. Any statements related to the product which are not contained
in 3M’s current publications, or any contrary statements contained on your purchase order shall have no
force or effect unless expressly agreed upon, in writing, by an authorized officer of 3M.
Warranty; Limited This product will be free from defects in material and manufacture at the time of purchase. 3M
Remedy; Limited MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED OF
Liability MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the
warranty period stated above, your exclusive remedy shall be, at 3M’s option, to replace or repair the 3M
product or refund the purchase price of the 3M product. Except where prohibited by law, 3M will not be
liable for any indirect, special, incidental or consequential loss or damage arising from this 3M
product, regardless of the legal theory asserted.
3M is a trademark of 3M Company.
3
Electrical Markets Division
6801 River Place Blvd.
Austin, TX 78726-9000
800 676 8381 or 800 245 3573 Please recycle.
FAX: 800 828 9329 or 800 245 0329 © 3M 2008 All rights reserved.
www.3M.com/electrical/oem 78-8111-0896-4_C
3 of 3
MATERIAL SAFETY DATA SHEET Scotch® Glass Cloth Tape 69 with Silicone Adhesive 10/23/12
This material safety data sheet (MSDS) is provided as a courtesy in response to a customer request. This product is not regulated
under, and a MSDS is not required for this product by the OSHA Hazard Communication Standard (29 CFR 1910.1200) because,
when used as recommended or under ordinary conditions, it should not present a health and safety hazard. However, use or
processing of the product not in accordance with the product's recommendations or not under ordinary conditions may affect the
performance of the product and may present potential health and safety hazards.
Product Use:
Intended Use: Electrical
SECTION 2: INGREDIENTS
Ingredient C.A.S. No. % by Wt
Glass Cloth 65997-17-3 50 - 75
Silicone Adhesive Mixture 25 - 50
_________________________________________________________________________________________________
Page 1 of 6
MATERIAL SAFETY DATA SHEET Scotch® Glass Cloth Tape 69 with Silicone Adhesive 10/23/12
accordance with the product's directions for use may affect the performance of the product and may present potential health and safety
hazards.
Skin Contact:
No health effects are expected.
Inhalation:
No health effects are expected.
Ingestion:
No health effects are expected.
Unusual Fire and Explosion Hazards: No unusual fire or explosion hazards are anticipated.
Note: See STABILITY AND REACTIVITY (SECTION 10) for hazardous combustion and thermal decomposition
information.
_________________________________________________________________________________________________
Page 2 of 6
MATERIAL SAFETY DATA SHEET Scotch® Glass Cloth Tape 69 with Silicone Adhesive 10/23/12
Clean-up methods
Not applicable.
7.1 HANDLING
This product is considered to be an article which does not release or otherwise result in exposure to a hazardous chemical under
normal use conditions.
7.2 STORAGE
Not applicable.
_________________________________________________________________________________________________
Page 3 of 6
MATERIAL SAFETY DATA SHEET Scotch® Glass Cloth Tape 69 with Silicone Adhesive 10/23/12
Hazardous Decomposition: Under recommended usage conditions, hazardous decomposition products are not expected. Hazardous
decomposition products may occur as a result of oxidation, heating, or reaction with another material.
_________________________________________________________________________________________________
Page 4 of 6
MATERIAL SAFETY DATA SHEET Scotch® Glass Cloth Tape 69 with Silicone Adhesive 10/23/12
ECOTOXICOLOGICAL INFORMATION
Not determined. Not applicable.
STATE REGULATIONS
Contact 3M for more information.
CHEMICAL INVENTORIES
The components of this product are in compliance with the chemical notification requirements of TSCA.
This product is an article as defined by TSCA regulations, and is exempt from TSCA Inventory listing requirements.
INTERNATIONAL REGULATIONS
Contact 3M for more information.
This MSDS has been prepared to meet the U.S. OSHA Hazard Communication Standard, 29 CFR 1910.1200.
_________________________________________________________________________________________________
Page 5 of 6
MATERIAL SAFETY DATA SHEET Scotch® Glass Cloth Tape 69 with Silicone Adhesive 10/23/12
National Fire Protection Association (NFPA) hazard ratings are designed for use by emergency response personnel to address the hazards that are
presented by short-term, acute exposure to a material under conditions of fire, spill, or similar emergencies. Hazard ratings are primarily based on the
inherent physical and toxic properties of the material but also include the toxic properties of combustion or decomposition products that are known to
be generated in significant quantities.
Revision Changes:
Section 1: Product name was modified.
Page Heading: Product name was modified.
Section 1: Initial issue message was modified.
DISCLAIMER: The information in this Material Safety Data Sheet (MSDS) is believed to be correct as of the date issued. 3M
MAKES NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY
OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR COURSE OF PERFORMANCE OR USAGE OF
TRADE. User is responsible for determining whether the 3M product is fit for a particular purpose and suitable for user's method of
use or application. Given the variety of factors that can affect the use and application of a 3M product, some of which are uniquely
within the user's knowledge and control, it is essential that the user evaluate the 3M product to determine whether it is fit for a
particular purpose and suitable for user's method of use or application.
3M provides information in electronic form as a service to its customers. Due to the remote possibility that electronic transfer may
have resulted in errors, omissions or alterations in this information, 3M makes no representations as to its completeness or accuracy.
In addition, information obtained from a database may not be as current as the information in the MSDS available directly from 3M
_________________________________________________________________________________________________
Page 6 of 6