Unit-0i Psoc
Unit-0i Psoc
CONTROL
(R2041021)
Presented by
J SURESH M.Tech
ASSISTANT PROFESSOR
DEPARTMENT OF EEE
POWER SYSTEM OPERATION AND
CONTROL
Text Books:
1. Power Generation, Operation and Control by Allen J Wood, Bruce F WollenBerg 3rd
Edition, Wiley Publication 2014.
2.Electric Energy systems Theory – by O.I.Elgerd, Tata McGraw–hill Publishing
Company Ltd., Second
edition.
3.Modern Power System Analysis – by I.J.Nagrath&D.P.Kothari Tata McGraw Hill
Publishing Company
Ltd, 2nd edition.
SYLLABUS
1.2. HEAT RATE CURVE – COST CURVE – INCREMENTAL FUEL AND PRODUCTION
COSTS –
INPUT–OUTPUT CHARACTERISTICS.
LINE LOSSES .
without losses.
After the completion of the course the student should be able to compute optimal
scheduling of Generators.
1.1. OPTIMAL OPERATION OF GENERATORS IN
THERMAL
POWER STATIONS
OPTIMAL OPERATION OF GENERATORS IN THERMAL POWER STATIONS
Optimal Means minimum utilisation of the resources to get the max output power.
Practically we have have different types of generating plants, such as coal fired
thermal plants, hydel plants, nuclear plants, oil and natural gas units etc.
Fuel cost is different from different locations under normal condition generating capacity is
PG>PD+PL
The factors influencing the cost of generation are the generator
efficiency, fuel cost and
transmission losses.
For interconnected system Real Power (P) & Reactive Power(Q) is scheduled for each
2. Fuel cost-The location at which the most efficient generator we installed but fuel cost we
10MW
G1 G2
1.25Rs/Watt
10MW
1.5Rs/Watt 10MW
G3
2Rs/Watt
The most efficient generator may not give minimum cost, since it may be
located in a place where fuel cost is high. Further, if the plant is located far
from the load centers, transmission losses may be high and running the
The first problem in the power system is unit commitment (UC) problem
and the second
problem is load scheduling (LS) problem.
Main aim in the economic dispatch problem is to minimize the total cost
Unit commitment (UC) is a popular problem in electric power system that aims at
Limited
OR
or
Hot Gasses to Cblzriney
Bo:ler
Coal
hopped
Turbine
Pulverizer
Aly Ash
hopper
Feedwater
Condenser
Pump Cooling Tower
Water
Storage
This unit has to supply power not only to the load connected to the power
system but also to the local needs for the auxiliaries in the station, which may
The power requirements for station auxiliaries are necessary to drive boiler feed
pumps, fans
input–output curve of a generating unit. For each generating unit there shall be a
Pi min Pi max
1.2.2 HEAT RATE CURVE:
The heat rate characteristics obtained from the plot of the net heat rate in
kcal/kWh versus
The thermal unit is most efficient at a minimum heat rate, which corresponds
to a particular
generation PG. The curve indicates an increase in heat rate at low and high
power limits.
From the input –output curves, the incremental fuel cost (IFC) curve can
= Δ F / Δ PG
The sum of real-power generation of all the various units must always be equal to the total
Similarly, the limits may also have to be considered over the range of reactive-power
capabilities of the generator unit requiring that:
2. Voltage magnitude and phase-angle constraints: For maintaining better
voltage profile and limiting overloadings, it isessential that the bus voltage
magnitudes and phase angles at various buses should vary within the limits.
These can be illustrated by imposing the inequality constraints on bus voltage
magnitudes and their phase angles.
3 or••amic consWaints: These constants may consider when fast
changes in generation are required for picking up the shedding down
or increasing of load demand. These constraints are of the form:
LOSSES NEGLECTED
or
ΣPG ≥ PD----------------------ii
Where PG is power capacity of generating power plant
iii
iv
PG1 PG2 PG3 PGn
G1 G2 G3 Gn
-------
BUS BAR
LOAD
This is a constrained Optimization problem .The loading of each generator is
constrained
By the inequality constrained of equation –iii is not effective ,the problem can be
solved by the method of LAGRANGE MULTIPLIER
L=CTOTAL+ λ(PD - z- ) or
-
L[PG1,PG2,--PGn,PD, λ]=CTOTAL- λ( - PD)------------------------v
TO MINIMIZATION IS ACHIEVED BY THE CONDITION
λ ∂ L/ ∂ PGi =0
The overall cost is summation of cost of each generating unit.
vi
decrease in cost than the increase in cost of adding the same output reduction to units with
lower incremental costs. Therefore, all units must run with same incremental operating costs.
After getting the optimal solution, in the case that the generation of any one unit is below its
minimum capacity or above its maximum capacity, then its generation becomes the
corresponding limit.
In the solution of an optimization problem without considering the transmission losses, we make
use of equal incremental costs, i.e., the machines are so loaded that the incremental cost of
or
P, g PL
1
CONSIDER A POWER STATION HAVING n NUMBER OF UNITS
C=C1PG1+C2PG2+C2PG2+ +CnPGn
C= Cn(PGn) (1)
From the unit commitment table of a given plant, the fuel cost curve of the plant can be determined in
the form of a polynomial of suitable degree by the method of least squares fit.
If the transmission losses are neglected, the total system load can be optimally divided among the
It is, however, unrealistic to neglect transmission losses particularly when long distance transmission of
power is involved. A modem electric utility serves over a vast area of relatively low load density.
The transmission losses may vary from 5 to 15% of the total load, and therefore, it is essential to
It is obvious that when losses are present, we can no longer use the simple 'equal incremental cost'
criterion.
where
i=1 i=1
It will be shown later in tliis section that, if the power factor of load at each bus is assiuned to
reiiiain constant, the systems loss PL can be shown to be a fiinction of active power generation
at each plant. i.e.
To illustrate the point, consider a two-bus system with identical generators at
each bus (i.e. the same IC curves). Assume that the load is located near plant 1
and plant 2 has to deliver power via a loss line. Equal incremental cost criterion
would dictate that each plant should carry half the total load; while it is obvious in
this case that the plant 1 should cane a greater share of the load demand thereby
In this section, we shall investigate how the load should be shared among various
plants, when line losses are accounted for. The objective is to minimize the overall
cost of generation at any time under equality constraint of meeting the load
dispatch Eq. (2.6) together with the power balance Eq. (2.2). The partial derivative p i
termed to as the incremental transmission loss (ITL), associated with the ith generating plant.
necessary to compute ITL for each plant, and therefore we must determine
plants. There are several methods, approximate and exact, for developing a
transmission loss model. One of the most important, simple but approximate,
general form of the loss formula (derived later in this section) using B-
coefficients is
λ =Li. ∂ C/ ∂ PGi
λ =Li * ∂ Ci(PGi)/ ∂
PGi
plant and penalty factor ∂ PGi/ ∂ PDmeans PGi increment has a large portion
dissipated
as loss
R2
R1
I1 I2
G1 PL G1
I1+ I2
PD
R3
PL=I12R1+I22R2+( I1+ I2)2R3 LOAD
WHERE P=VICOSØ
I=P/V COSØ
Transmission loss PL IS EXPRESSED WITHOUT LOSS OF ACCURACY
(ii) All the lines in the system have same The ratio X / R is the same for all the network
branches
(iii) The magnitude and phase angle of voltages at each station remain constant
Consider the simple case of two generating plants connected to an arbitrary OR any
number of loads through a transmission network as shown in Fig a
Transmission system
(b)
Fig Twci plants ccintiected tc› a nurrit›er of lc›ads through a transrri issinn network
Current carried by that particular line i.e., I specified one of the line
whete Ig„ Ig, are the current supplied by planG 1 and 2 resp:ctive9, to meet flu
demand Io. Because of the assumptions ma&, lxi and In have same phase angle, as
do Ici and Ip Therefore, the cunent distrlbu?on facton are real nther than
complex. Rt
where zr, and u 2 are phase angles of Q, 2 «:a respect to a common reference. We
andpI
2
Np2 )fp,
+ 2$Np,|/ p,|cos‹r,N „| /, 2| cos‹r, + Ng,|J Is N rz oz1 sin zr,j
fly ) 2 = (N ; f ; ) coszr/ + JV¿2 )/G2 ) Cos« 2 )2 + (N ;)/ ) sin a/ + JV 2 )/ 2 |sin « 2 )2
2 z 2
N g, 2 ) Gf , -2 + sin
+ 2[Ng,|/„ | coszr, N, 2|f p2| COSW 2 -1- NSU! G | siR ‹r, N, 2 |fp 2| siR w2
=
, ,| 2 + N 2
| | 2 + 2Ng, Ng |fp,||SG2 | Cos(u , — cr2 )
NK 2
U G x 2 pf 2 2
and |f « 1
•,S|V,|cos#, •,S|V,|cos#2
where Pp„ Pc2 are three phase real power outputs of plantl and plant 2; V„ V, are
the line to line by voltages of iR plants and $, g2 are the power factor
angles.
The total tmnsmission loss in ie sysRm is given by
where the summation is taken over all branches of the network and Rx is the branch
resistance. Substituting we get
At consumer Premises
fi c,
6 + P4, -n v (°Ox — in @
Aow txis,+— ok gerievah’•p z, + tx
*^Kec ‹e
“ *'^ °‘° '^ °•°J 'u<h •• > fi<'2• nve i r› ri w
> ‹xt— < ee r+‹:u2 hoor k 1t*e °@j :: +oo yw
d‹m
Pp,_ ° ^fl4r +‹& ma/n,=,1
-o°• p*, + °i
°oejg,„,;pq
° ’**^° •'”' '•'' ° = */°• B••= ° °•-/›.
*‘°^° ^' QmemS <i *cha$til:rig
6 hou:d bx lA— ° °“
“ ! ^ P*ñ t 'J- 6 S I oo
pp gy
i zc+ioo — 8x io r<