1. CW 100, Communication data can be divided into functional code data and
non-functional code data, the latter includes running command, running
status, operation parameters, alarm information, etc.
I .1 CW 100 functional code data
Function code data is the important setting parameters of the frequency
converter, as follows:
CW 100 Group P 0、P 1、P 2、P 3、P 4、P 5、P 6、P 7、P 8
FC P 、P 9 、PA 、PB
data (readabl
e)
Group A 0、A 1、A 2、A 5、A 6、A 7、A 8、A 9、
A AA 、AB 、AC
(readabl
e and
written)
5) Parameter initialization
This function is required when the parameter initialization of the
inverter is required through the upper computer.
4, parameter lock password check: (if the return is 8888H, that is, the
password check passed)
8. P u l s e ( P U L S E ) O u t p u t c o n t r o l : ( w r i t e on l y )
command address Command content
2004H 0 ~ 7 FFF ind ic ate s
betwe en 0% and 100 %
This parameter is used to set the data transmission rate between the upper
computer computer and the frequency converter. Note that the baud rate set by the
upper computer and the inverter must be consistent, otherwise, the communication
cannot be carried out. The larger the port rate, the faster the communication
speed.
When the function code is set to a valid value, if the interval between one
communication and the next communication exceeds the communication timeout time,
the system will report the communication fault error (Err 16). Usually, it is
set to be invalid. If in a continuous communication system, you set the
secondary parameters, you can monitor the communication status.
3.3 Start-up
Send control code: 01 06 20 00 00 01 43 CA
3.5 Stop
Send control code: 01 06 20 00 00 06 02 08