CW 100-485 communication protocol

2018 -10 -30

1. CW 100, Communication data can be divided into functional code data and
non-functional code data, the latter includes running command, running
status, operation parameters, alarm information, etc.
I .1 CW 100 functional code data
Function code data is the important setting parameters of the frequency
converter, as follows:
CW 100 Group P 0、P 1、P 2、P 3、P 4、P 5、P 6、P 7、P 8
FC P 、P 9 、PA 、PB
data (readabl
e)
Group A 0、A 1、A 2、A 5、A 6、A 7、A 8、A 9、
A AA 、AB 、AC
(readabl
e and
written)

The function code data mailing address is defined as follows:


1. When reading the functional code data for the communication
For the functional code data of P 0 ~ PF and A 0~AF groups, the higher
communication address directly indicates the functional group number, and
the lower 16 functional code directly indicates the serial number in the
functional group. The examples are as follows:

1) P 0-16 functional parameters, whose communication address is F


010H, where F 0H represents the functional parameters of P 0
group and 10H represents the hexadecheal data format of the
function number 16 in the functional group

2) AC-08 function parameters, whose mailing address is AC 08, where


ACH represents the function parameter of AC group and 08H
represents the hexadecimal data format of function number 8 in
the function group
2, when writing for communication, into the functional code data
For the function code data of P 0 ~ PF group, its communication
address is 16 points high, and according to whether EEPROM is
written, it is divided into 00~0F or F 0~FF. 16 points low is
directly the serial number of the function code in the function
group. The examples are as follows:
1) Write the function parameters P 0-16
With ou t writi n g to the EEPR O M , its mai li ng add re ss is 001 0H
Wh e n EE P RO M ne e d s to wr i t e , it s ma i l i ng ad d r e s s is F 01 0 H
For the function code data of A 0 to AF group, its communication address is
16 years high, which is divided into 40 to 4 F or A 0 to AF according to
whether EEPROM is required. 16 years low is directly the serial number of
the function code in the function group. The examples are as follows:
2) Write the functional parameters AC-08
Wh e n wr i t i n g to a EE P R O M is no t re q u i r e d , it s ma i li n g ad d r e ss is
4C 08 H
W h e n E E P R O M n e e d s t o w r i t e , i t s m a i l i n g ad d r e s s i s AC 08 H

I .2 CW 100 non-functional code data


CW 100 Status Monitoring parameters of U group, fault description of
NOT"functi Data converter and operating status of converter
on (read-
Code data only)
Control Control command, communication set point, digital output
paramet terminal control, analog output AO1 control, analog
ers output AO 2 control, high-speed pulse (FMP) output
(write- control, and parameter initialization
only)
1. Status data
Status data is divided into U group monitoring parameters, converter
fault description and converter operating status
1) U group parameter monitoring parameters
For the description of the monitoring data of group U, see the
relevant descriptions in Chapter 5 and Chapter 6. The address of group
U is defined as follows: U 0 ~ UF is 70~7F, and the lower mailing
address of group group 16 is the serial number of the monitoring
parameters in the group. The example is as follows: U011, whose
mailing address is 700 BH
2) Failure description of the frequency converter
When reading the fault description of the converter, the communication
address is fixed to 8000H. By reading the address data, the upper
computer can obtain the fault code of the current converter. The
description of the fault code is defined in Chapter 5 F 9-14 function
code
3) Operation status of the frequency converter
When the communication reads the operating state of the inverter, the
communication address is fixed to 3000H. By reading the address data, the
upper computer can obtain the operating state information of the current
operation of the inverter, which is defined as follows:
Frequter operating status Read the state word definition
address
1: Is running
3000H 2: Reverse operation
3: Downtime

2. Control the parameters


The control parameters are divided into control command, digital output
terminal control, analog output AO1 control, analog output AO2 control,
and high-speed pulse (FMP) output control
1) Control the command
When F0-02 (command source) is selected as 2: communication control, the
upper computer can realize the relevant command control of the start and
stop of the inverter through the communication address. The control
command is defined as follows:
Control the command Command function
mailing address
1: Is running
2: Reverse operation
3: Positive, turn the point to
2000H move
4: Reverse point movement
5: Free shutdown
6: reduce, speed stop
7: Therefore, the obstacle is
reset

2) Communication setting point


Communication set value In CW 100, frequency source, torque ceiling
source, VF separation voltage source, PID given source and PID feedback
source select the given data of communication set timing. The
corresponding address is 1000H, and when the host corresponding address
value is set, the data range is-10000~10000, corresponding to the given
value-100.00%~100.00%

3) Digital output terminal control


When the digital output terminal function is selected as 20: communication
control, the upper computer can change through the communication address
Control of the digital output terminal of the frequency device, defined as
follows:

The digital output terminal Command content


controls the mailing
address
BIT 0: DO 1 output control
BIT 1: DO 2 output control
BIT 2: RELAY 1 output control
BIT 3: RELAY 2 output control
2001H BIT 4: FMR output control
BIT 5:VDO 1
BIT 6:VDO 2
BIT 7:VDO 3
BIT 8:VDO 4
BIT 9:VDO 5

4) Analog output AO 1, AO 2, high-speed pulse output FMP


control
When the analog output is AO 1 and AO 2, and the high speed pulse output
FMP output function is selected as 12: communication setting, the upper
computer computer can control the inverter analog output and high speed
pulse output through the communication address, which is defined as
follows:

Output control mailing Command content


address
AO 1 2002H 0 ~ 7 FFF indicates
AO 2 2003H between 0%
F MP 2004H and 100%

5) Parameter initialization
This function is required when the parameter initialization of the
inverter is required through the upper computer.

If FP-00 (, user password) is not 0, the password needs to be verified


through communication first. After the verification, the upper computer
will initialize the parameter within 30 seconds.

The communication address for user password verification is 1F 00H. If the


correct user password is written to the address, the password verification
can be completed
The address is 1F 01H and its data content is defined as follows:

The parameter initializes Command function


the mailing address
1: Restore the factory parameters
2: Clear and record the information
1F 01H
4: Restore the user backup
parameters
501: Backup user current
parameters
2. CW 100 Modbus Communication protocol

The CW 100 se ries inverte r provides RS 485 communication


interfa ce an d supports Modbus-RTU sl ave station communication
protoco l. Users can realize centralized control through the computer or
PLC, set the frequency converter operation command through the
communication protocol, modify or read the function code parameters, and
read the working state and fault information of the frequency converter.
.12 Agreement content
The serial communication protocol defines the information content and usage
format transmitted in the serial communication. This includes: host polling
(or broadcast) format; host coding method, including: required action
function code, transmission data and error check. The response of the slave
also adopts the same structure, including: action confirmation, return data
and error verification, etc. If the slave has an error while receiving the
information, or cannot complete the action required by the host, it will
organize a failure information and feedback to the host in response.
.12.1 Application mode
The frequency converter is connected to the "single-master and multi-slave"
PC / PLC control network with RS 485 bus, serving as the communication slave.
.1.22 Bus structure
1. Hardware interface
Insert RS 485 into the inverter and expand the card MD 38TX 1 hardware.
2, extension, pu structure single host multiple slave system. Each
communication device in the network has a unique slave station address,
with a device serving as a pass
The host (often flat PC host, PLC, HMI, etc.), actively initiate communication,
read or write the slave parameters, other devices are in the communication slave,
in response to the host's inquiry or communication operation. Only one device can
send the data at the same time, while the other devices are in the receiving state.
The setting range of the slave address is 1~247,0 is the broadcast communication
address. The slave address in the network must be unique.3, the communication
transmission mode of asynchronous serial, half-duplex transmission mode. In the
process of serial asynchronous communication, data sends one frame of data at a
time in the form of packets. It is agreed in the MODBUS-RTU protocol that when the
idle time of no data on the communication data line is greater than that
3.5 Transmission time of Byte, indicating the start of a new communication frame.

The built-in communication protocol of CW 100 series inverter is Modbus-RTU


slave communication protocol, which can respond to the "query / command" of
the host, or make corresponding actions according to the "query / command" of
the host, and communicate the data response. Host can refer to personal
computer (PC), industrial control equipment or programmable logic
controller (PLC),
The host can communicate with a single plane and publish broadcast
information to all lower planes. For the separate access query / command
of the host, the visited slave returns a reply frame; for the broadcast
information, the host needs no feedback response to the host.
2.2 Communication data structure
The Modbus protocol communication data format of CW 100 series frequency
converter is as follows. frequency converter only supports reading or writing of
Word parameters, the corresponding communication read command is Ox 03; write
command is 0x06, and byte or bit reading is not supported:
In theory, the upper computer can read several consecutive function codes
at a time (that is, n can be up to 12), but it should be noted that it can
not cross the last function code of this function code group, otherwise
the reply will be wrong.
If the communication frame error is detected by the machine or causes
unsuccessful reading and writing for other reasons, the error frame will
be answered.
1. Description of the data frame field:

Frame-head More than 3.5 characters of the transfer time is


START idle
Deliver Address address range: 1 ~ 247; 0 = Broadcast
address ADR address
command 03: Read the slave parameters; 06: Write the slave
code CMD parameters
Function code The parameter address inside the inverter is
address H indicated in 16 system; it is divided into
Function code functional codes and non-functional codes (such
address L as running status parameters, running commands,
etc.), see the address definition for details.
When transmitting, high bytes are in front and
low bytes are back.
The number of If the number of functional codes read in
functional this frame is 1 indicates that one functional
codes, H
code is read. When transmitting, high bytes
The number of
functional are in front and low bytes are back.
codes, L This agreement can only rewrite one function code
at a time, without this field.
data H Answer data, or data to be written, is
data L transmitted with high bytes before and low
bytes behind.
CRC CHK Low level Detection value: CRC 16 check value. When
CRC CHK High transmitting, low byte in front, high word
level After the festival. The calculation method is
described in this section of CRC calibration for
details.
END At the time of 3.5 characters

2. CRC calibration mode:


The CRC (Cyclical Redundancy Check) uses the RTU frame format,
and the message includes an error detection domain based on the
CRC method. The CRC domain detects the content of the entire message. The
CRC domain is two bytes containing a 16-bit binary value, which is added
to the message after calculated by the transmission device. The receiving
device recalculates the CRC of the received message and compares the value
with the received CRC domain, and if two CRC values are not equal, there
is a transmission error. CRC is done by first saving 0xFFFF and then
calling a process to process the continuous 8-bit bytes in the message
with the value in the current register. Only 8 Bit data in each character
is valid for CRC, and both start and stop bits and parity bits are invalid.
During CRC generation, each 8-bit character is different from the register
content (XOR), and the result is different to the lowest effective bit, and
not if the LSB is 0. The entire procedure was repeated 8 times. After the
last digit (8th digit) is completed, the next 8-bit byte is separately
different from the current value of the register. The value in the final
register is the CRC value after all bytes in the message.
When CRC is added to the message, low bytes join first, then high bytes.

Address definition of the communication parameter


Read and write function code parameters (some function codes cannot be
changed and are only for manufacturers or monitoring):

2.3 Function code parameter address marking rules


Represent the rule with the function code group number and the reference
code as the parameter address:
High bytes: F 0~FF (Group P), A 0~AF (Group A), 70~7F (Group U)
Low Bytes: 00 to FF
For example, for the range function code F 3-12, the access address of the
function code is expressed as
0xF 30C; Note:
1) PF group: neither read parameters nor change parameters;
2) U group: can only be read, can not change the parameters.
Some parameters cannot be changed when the frequency converter is in operation;
some parameters cannot be changed; change the function code parameters, note the
parameter range, units, and relevant instructions.

Function code Communication Communication fies the


group number visit, ask for the function code address in
address RAM
From the P 0 to the 0xF 000 ~ 0xFEFF 0x 0000 ~ 0x 0EFF
PE group
From A 0 to AC 0xA 000 ~ 0xACFF 0x 4000 ~ 0x 4CFF
group
U 0 group 0x 7000 ~ 0x 70F F

Note that because EEPROM is frequently stored, it will reduce the


service life of EEPROM, so some function codes are not stored in
communication mode, just change the value in RAM.
1) If it is a P group parameter, to achieve the function, as long as the high F of
the function code address into 0.
2) If it is A group A parameter, to realize the function, just change the high A
of the address of the function code into 4
can realize. The corresponding function code address is indicated as follows:
High bytes: 00~0F (Group P), 40~4F (Group A)
Low Bytes: 00 to FF
in compliance with:
Function code P 3-12, not stored in EEPROM, the address is 030C;
Function code A 0-05, not stored in EEPROM, the address is 4005;
This address means that can only write RAM, can not read the action, read,
invalid address.
For all the parameters, this function can also be implemented using the command
code 07H.
The data is given by the host computer through the communication address 0x 1000.
The data format is the data with 2 decimal places, and the data range is-F 0-10~
+ F 0-10.
1. Stop / operation parameters:
Parameter parametric Parameter parametric description
address description address
1000H * Communication 1010H PID set up
Setpoint (decimal)
10000 ~ 10000
1001H running frequency 1011H PID feedback
1002H busbar voltage 1012H PLC step
1003H output voltage 1013H PULSE Input pulse frequency in
0.01kHz
1004H output 1014H Feedback speed in 0.1Hz
1005H output power 1015H The remaining running
time
1006H output torque 1016H AI 1 pre before voltage
1007H running speed 1017H AI 2 pre front voltage
1008H The DI input flag 1018H AI 3 pre front voltage
1009H Th e DO ou t pu t 1019H linear velocity
fl a g
100AH AI 1 voltage 101AH Current power-on time
100BH AI 2 voltage 101BH Current running time
100CH AI 3 voltage 101CH PULSE Input pulse frequency
in 1Hz
100DH Count the 101DH Communication set value
numerical input
100EH Length value input 101EH Actual feedback speed
100FH loading speed 101FH Main frequency X is
shown

– – 1020H Auxiliary frequency Y is


shown

pay attention to:


1) The communication set value is the percentage of the relative value, and
10000 corresponds to 100.00%, and-10000 corresponds to-100.00%.
2) For the data of frequency dimension, the percentage is the percentage of the
relative maximum frequency (F 0-10); for the data of torque dimension, the
percentage is F 2-10 and A 2-48 (the torque upper limit number is set,
corresponding to the first and second motors respectively).

2. Enter the control command to the frequency converter: (write only)


Command word Command function
address

0001: Forward turn operation

0002: reverse operation

0003: Positive turning point


2000H movement
0004: reverse point movement

0005: Free shutdown

0006: deceleration stop

0007: Fault is reset

3. Read the frequency converter status: (read-only)

status word State word function


address
0001: Forward turn
3000H operation
0002: reverse operation
0003: shut down

4, parameter lock password check: (if the return is 8888H, that is, the
password check passed)

Password address Enter the contents of


the password
1F 00H *****

5. Digital output terminal control: (write only)


command address Command content
BIT 0: DO 1 output control
BIT 1: DO 2 output control
BIT 2: RELAY 1 output control
BIT 3: RELAY 2 output control
BIT 4: FMR output control
2001H BIT 5:VDO 1
BIT 6:VDO 2
BIT 7:VDO 3
BIT 8:VDO 4
BIT 9:VDO 5

6. Analog output AO 1 control: (write only)


command address Command content
2002H 0 ~ 7 FFF ind ic ate s
betwe en 0% and 100 %

7. Simulated output AO 2 control: (write only)


command address Command content
2003H 0 ~ 7 FFF ind ic ate s
betwe en 0% and 100 %

8. P u l s e ( P U L S E ) O u t p u t c o n t r o l : ( w r i t e on l y )
command address Command content
2004H 0 ~ 7 FFF ind ic ate s
betwe en 0% and 100 %

9. Failure description of the frequency converter:


Fault address Inverter fault Inverter fault
of the information information
frequency
converter
0000: No fault 0015: abnormal parameter
0001: Hold on
read and write
0002: accelerated
overcurrent 0016: Frequency converter
0003: deceleration hardware failure
overcurrent 0017: Motor short circuit
0004: Constant-speed to ground fault
over-current 0018: Hold on
0005: accelerated 0019: Hold on
overvoltage 001A: Run time arrives
0006: decelerated 001B: User-defined fault
8000H 1
overvoltage
0007: Constant speed 001C: User-defined fault
overvoltage 2
0008: Buffered 001D: Power-on time
resistance overload arrives
fault 001E: drop load
0009: undervoltage 001F: PID feedback is
fault lost during runtime
000A: frequency 0028: Fast current limit
converter overload timeout fault
000B: Motor overload 0029: Switching motor
fault during operation
000C: Enter the 002A: Speed deviation is
missing phase too large
000D: output output 002B: Motor overspeed
phase 002D: Motor over
000E: the module is temperature
overheating 005A: Number of encoder
000F: External failure lines set correctly
0010: Communication is 005B: Encoder is missed
abnormal 005C: Initial position is
0011: Conactor abnormal wrong
0012: Current detection 005E: Speed feedback
fault error
0013: Motor tuning
fault
0014: Encoder / PG
card fault
2.4 Description of the FD group communication parameters

Baud rate Factory value 60 05


Fd -00
Individual bit: MODBUS baud rate
0:300BPS 5:9600BPS
Set the 1:600BPS 6:19200BPS
scope 2:1200BPS 7:38400BPS
3:2400BPS 8:57600BPS
4:4800BPS 9:115200BPS

This parameter is used to set the data transmission rate between the upper
computer computer and the frequency converter. Note that the baud rate set by the
upper computer and the inverter must be consistent, otherwise, the communication
cannot be carried out. The larger the port rate, the faster the communication
speed.

data format Factory value 0


0: No check: data format <8, N, 2>
Fd -01 1: even test: Data format <8, E, 1>
Set the scope 2: odd check: data format <8, O, 1>
3: No check: Data format <8-N-1>
The data format set by the upper computer and the inverter must be consistent,
otherwise, the communication cannot be carried out.

This machine Factory value 1


Fd -02 address
Set the scope 1~247,0-bit radio address
When the local address is set to 0, it is the broadcast address,
realizing the broadcasting function of the upper computer. The local
address is unique (except the broadcast address), which is the basis
of realizing the point-to-point communication between the upper
computer and the frequency converter.

Response delay Factory value 2ms


Fd -03
Set the scope 0~20ms
Response delay: refers to the intermediate interval between the end of the
inverter data acceptance and the data sent by the upward computer. If the
response delay is less than the processing time of the system, the response delay
shall be subject to the system processing time. If the response delay is longer
than the system processing time, the system shall process the data and delay
until the response delay time to send the data to the upper machine.

Communication Factory value 0.0 s


Fd -04 super, time
Set the scope 0.0s (invalid); 0.1~60.0s
The communication timeout time parameter is invalid when the function code is set
to 0.0s.

When the function code is set to a valid value, if the interval between one
communication and the next communication exceeds the communication timeout time,
the system will report the communication fault error (Err 16). Usually, it is
set to be invalid. If in a continuous communication system, you set the
secondary parameters, you can monitor the communication status.

Communication Factory value 0


Fd -05 association,
discuss the
selection
Set the scope 0: Non-standard Modbus protocol; 1: standard
Modbus protocol
Fd-05=1: the Modbus protocol for the selection criteria. Fd-05=0:
When reading the command, the number of returned bytes is one byte
more than the standard Modbus protocol, please see the "5
Communication Data Structure" section of this protocol.

Communication to Factory value 0


Fd -06 read the current
resolution
Set the scope 0:0.01A ;1:0.1A
Used to determine the output unit of the current value when the communication
reads the output current.

3. Actual use of the reference


Use 485 communication to stop the frequency, start and stop.
3.1. Set P002 to 2 and select the communication command channel
Send control code: 01 06 F 0 02 00 02 9A CB

3.2 Set P003 to 9, and select the main


frequency source for the given
communication transmission control code:
01 06 F 0 03 00 09 8A CC

3.3 Start-up
Send control code: 01 06 20 00 00 01 43 CA

3.4 Set the operating frequency to 32 HZ with two decimal


points, and the set value must be placed in the high
level to send the control code: 01 06 10 00 20 00 94 CA

3.5 Stop
Send control code: 01 06 20 00 00 06 02 08