Data Sheet 750gpm@8bar
Data Sheet 750gpm@8bar
Data Sheet 750gpm@8bar
Product Schedule
Qty/
Article No Description
Set
Tag # : Electrical Pump Set [ Pump For Duty Point 750 USGPM @ 8 bar, Listed Rated point : 750.0 USGPM @ 8.0 bar]
Pump NF-S-125-245 1
Tag # : Diesel Fire Pump Set [ Pump For 750 USGPM @ 8 bar]
Pump NF-S-150-170 1
Qty/
Article No Description
Set
Tag # : Diesel Fire Pump Set [ Pump For 750 USGPM @ 8 bar]
30504010348 Diesel Engine FD 140 H, 127 HP, 2,900 RPM 1
Manufacturer FIRE DRIVER / Factory Choice Power 127 HP Speed 2,900 RPM
Cooling Heat Exchanger Cooled Certification UL & FM
- Industrial Muffler 1
Make FACTORY CHOICE Type CALCIUM LEAD GRID Set(s) Config 24 VDC,2# (=12 VDC,4#)
Single Battery 12 V DC No Of Batteries 4 Capacity Hour 20 Hr
Tag # : Jockey Pump Set [ Pump For 52.69 USGPM @ 8.5 bar]
Pump NF-VLS 8-80 1
Qty/
Article No Description
Set
Tag # : Jockey Pump Set [ Pump For 52.69 USGPM @ 8.5 bar]
Manufacturer Naffco Power 5.5 Kw Speed 3,500 RPM
Frequency 60 Hz Pole 2 Mounting V1
Specification TEFC Enclosure Phase 3 PH LineVoltage 380 V
Certification NON-CERTIFIED
Speed (RPM) Driver PumpModel NF-S-125-245 Pump Test Std ANSI/HI 14.6-2011
3550 Motor Duty Flow 750.0 USGPM Duty Head 8.0 bar Stage 1 Impeller Dia 211.0 mm
Duty Power 55.92 kW 74.96 HP 150% of Flow 1125 USGPM Size Pump Nozzle
Peak Power 62.15 kw 83.31 HP Shut Off Head 9.42 bar Discharge In 3
Driver Power 100.0 HP CQ= 1 CH= 1
Prepared By Sindha Azarudeen
Tag Number Electrical Pump Set Offer No NAFF-KSA-237
Date 29/01/2024
In line with Manufacturer policy for continuous product development, Manufacturer has the right to change specifications without prior notice
Actual pump performance and impeller diameter values may vary ± 5% which is within normal permissible / expected range Reference: NF-S-125-245-3550
Technical Data Sheet
Operating Conditions
Fluid Fresh water
Specific Gravity 1
Temperature -
Viscosity 0 Cst
Speed 3550 RPM
Duty Flow (Q) 750.0 USGPM
Duty Head (H) 8.0 bar
Suction Pressure 0.3 bar
Pump Test Std ANSI/HI 14.6-2011
140% limit of H at shut-off 11.2 bar
65% limit of H @150% of Q 5.2 bar
Notes:
In line with Manufacturer policy for continuous product development, Manufacturer has the right to change specifications without prior notice
Actual pump performance and impeller diameter values may vary ± 5% which is within normal permissible / expected range
Block 16, Reemas Ind. City, Istanbul Road (South), Exit 18, As Sulay
Diesel Pump Set - Technical Documents
Performance Chart
Project 750 GPM@8BAR Liquid Fresh water
Consultant - Specific Gravity 1
Purchaser SAMPLE Viscosity - Cst
Contractor - Fluid Temperature - Deg C
Speed (RPM) Driver PumpModel NF-S-150-170 Pump Test Std ANSI/HI 14.6-2011
2900 Engine Duty Flow 750.0 USGPM Duty Head 8.0 bar Stage 1 Impeller Dia 271.0 mm
Duty Power 52.69 kW 70.63 HP 150% of Flow 1125 USGPM Size Pump Nozzle
Peak Power 63.37 kw 84.95 HP Shut Off Head 9.6 bar Discharge In 4
Driver Power 127.0 HP CQ= 1 CH= 1
Pump Model :
NF-S-150-170
Operating Conditions Liquid
Certified Rated Flow 750.0 USGPM Temperature 20 °C
Certified Rated Head 8.0 bar Liquid Type Clear
Duty Flow 750.0 USGPM Fluid Selection Fresh water
Duty Head 8.0 bar Fluid density 998.2067 kg/m³
Suction Size 6 In Viscosity 1.0034 mm²/s
Discharge Size 4 In Specific Gravity 1
Pump Test Std. ANSI/HI 14.6-2011
Performance Performance Limits as Per NFPA 20
Impeller Diameter 271.0 mm 140% Limit of H at Shut-off 11.2 bar
Shut off Pressure 9.6 bar 65% Limit of H at 150% of Q 5.2 bar
Stage 1
Speed 2900 RPM Constructional Features
Duty Power 52.69 kW Mounting Horizontal
Peak Efficiency 76.41 % Bearing Type Ball Bearing
Peak Power 63.37 kW Rotation CW
Flow @ 150% of Rated 1125 USGPM Bearing Lubrication Grease
Pressure @ 150% of Rated 6.28 bar Flange type -
Power @ 150% of Rated 61.18 kW Shaft Sealing Gland Packing
Performance Curve
Note:
In line with Manufacturer policy for continuous product development, Manufacturer has the right to change specifications without prior notice.
Actual pump performance and impeller diameter values may vary ± 5% which is within normal permissible / expected range.
Jockey Pump Set - Technical Documents
Performance Chart
Speed (RPM) Driver PumpModel NF-VLS 8-80 Pump Test Std ANSI/HI 14.6-2011
3500 Motor Duty Flow 52.69 USGPM Duty Head 8.5 bar Stage 8
Peak Power 4.75 kw 6.37 HP Shut Off Head 11.44 bar Discharge In 2
Driver Power 7.5 HP CQ= 1 CH= 1
Prepared By Sindha Azarudeen
Tag Number Jockey Pump Set Offer No NAFF-KSA-237
Date 29/01/2024
In line with Manufacturer policy for continuous product development, Manufacturer has the right to change specifications without prior notice
Actual pump performance and impeller diameter values may vary ± 5% which is within normal permissible / expected range Reference: VLS-8-60-N
Technical Data Sheet
Operating Conditions
Fluid Fresh water
Specific Gravity 1
Temperature -
Viscosity 0 Cst
Speed 3500 RPM
Duty Flow (Q) 52.69 USGPM
Duty Head (H) 8.5 bar
Suction Pressure 0.3 bar
Pump Test Std ANSI/HI 14.6-2011
Notes:
In line with Manufacturer policy for continuous product development, Manufacturer has the right to change specifications without prior notice
Actual pump performance and impeller diameter values may vary ± 5% which is within normal permissible / expected range
Block 16, Reemas Ind. City, Istanbul Road (South), Exit 18, As Sulay