CURRENT TRANSFORMERS

MAK 140/80
For currents from 200 A to 2000 A
Type: ring / busbar
Standards: acc. to BS 3938, EN 60044-1

Technical data:
Class of accuracy: 0,2S … 3 (see table).
Rated burden: max. 60 VA (see table).
Rated voltage: 720 V.
Rated frequency: 50-60 Hz.
Rated sec. current: 5 A (or 1 A on request).
Security factor: FS 5 FS10
Working temperature range: -20 … +45°C.
High voltage test: 4 kVeff, 50 Hz, 1 min.
Insulation class: E (max. 120°C)
Protection: IP 00.
Case: non-flammable plastic, UL 94 V-0.

Outline drawing of MAK 140/80

Order specification:
Weight:: 1000...1200gr
-Ring-type current transformer.
-Class of accuracy: 0.5
-Rated primary current: 2000 A.
-Rated secondary current: 5 A.
-Rated burden: 30 VA
-Busbar dimension: 2x80x10 mm or ∅ 73 mm.
Note: -On request orders for types different from table are
accepted. MAK 140/80 2000/5 A Cl. 0,5 30VA

Different types of MAK140/80 current transformers see in the table on next page

43

E D. 09. 04. 08. 43-45. MAK140-80. DOC.


CURRENT TRANSFORMERS
Rated Type: MAK 140/80
primary Acc. Max. busbar hole dimension: 81x31 mm or ∅ 73 mm (see outline drawing)
current class Rated Burden (VA)
In 1.5 2.5 3.75 5 7.5 10 12.5 15 20 30 45 60
0.5 x
200 A 1 x
3 x
0.5 x
250 A 1 x x
3 x
0,2 x
0.5 x x
300 A 1 x x x
3
0,2S
0,5S x
0,2 x
400 A 0.5 x x
1 x x x
3 x x
0,2S x
0,5S x
500 A 0,2 x
0.5 x x x
1 x x x x
3 x
0,2S x
0,5S x
600 A 0,2 x x x
0.5 x x x
1 x x x x
3 x
0,2S x
0,5S x
750 A 0,2 x x
0.5 x x x
1 x x x x x
3 x
0,2S x
0,5S x
800 A 0,2 x x
0.5 x x x x
1 x x x x x x
3 x x
0,2S x x
0,5S x x
1000 A 0,2 x x x
0.5 x x x x
1 x x x x x
3 x
0,2S x x
0,5S x x x
1200 A 0,2 x x x
0,5 x x x x
1 x x x x x
0,2S x x
0,5S x x x
1250 A 0,2 x x x x
0,5 x x x x x
1 x x x x x
0,2S x x
0,5S x x x
1500 A 0,2 x x x x
0,5 x x x x x
1 x x x x x
0,2S x x
0,5S x x x
1600 A 0,2 x x x x
0,5 x x x x x
1 x x x x x
0,2S x x
0,5S x x x
2000 A 0,2 x x x x x
0,5 x x x x x
1 x x x x x

44

.
CURRENT TRANSFORMERS

MAK140/80d
These current transformers can be used two range
by re-switching the secondary windings.

Rated Type: MAK 140/80d

primary Acc. Busbar hole 81x31 mm (see fig.)

current cl. Rated burden (VA)

In 5-2,5 10-5 15-7,5 30-15


0,5
600-300A 1 X X
3
0,5 X
800-400A 1 X
3 X
0,5 X
1000-500A 1 X
3 X
0,5 X
1200-600A 1 X
3 X
0.5 X X
1600-800A 1 X
3
0.5 X X
2000-1000A 1 X
3

MAK140/80t
These current transformers can be used three range
by re-switching the secondary windings.

Rated Type: MAK 140/80t


primary Ac. Busbar hole 81x31mm (see fig.)

current cl. Rated burden (VA)


In 10-5-2,5 20-10-5 30-15-7,5
0,5 X
1200-600-300A 1 X
3 X
0,5 X
1600-800-400A 1 X X
3
0,5 X X
2000-1000-500A 1 X
3

Order specification:
-Ring-type current transformer. MAK 140/80d 1000-500/5 A Cl.0,5 10-5VA
-Class of accuracy: 0.5
-Rated primary current: 1000-500 A.
-Rated secondary current: 5 A.
-Rated burden: 10-5 VA
-Busbar dimension: 2x80x10 mm or ∅ 73 mm.