Current Transformers: Technical Data
Current Transformers: Technical Data
MAK 140/80
For currents from 200 A to 2000 A
Type: ring / busbar
Standards: acc. to BS 3938, EN 60044-1
Technical data:
Class of accuracy: 0,2S … 3 (see table).
Rated burden: max. 60 VA (see table).
Rated voltage: 720 V.
Rated frequency: 50-60 Hz.
Rated sec. current: 5 A (or 1 A on request).
Security factor: FS 5 FS10
Working temperature range: -20 … +45°C.
High voltage test: 4 kVeff, 50 Hz, 1 min.
Insulation class: E (max. 120°C)
Protection: IP 00.
Case: non-flammable plastic, UL 94 V-0.
Order specification:
Weight:: 1000...1200gr
-Ring-type current transformer.
-Class of accuracy: 0.5
-Rated primary current: 2000 A.
-Rated secondary current: 5 A.
-Rated burden: 30 VA
-Busbar dimension: 2x80x10 mm or ∅ 73 mm.
Note: -On request orders for types different from table are
accepted. MAK 140/80 2000/5 A Cl. 0,5 30VA
Different types of MAK140/80 current transformers see in the table on next page
43
44
.
CURRENT TRANSFORMERS
MAK140/80d
These current transformers can be used two range
by re-switching the secondary windings.
MAK140/80t
These current transformers can be used three range
by re-switching the secondary windings.
Order specification:
-Ring-type current transformer. MAK 140/80d 1000-500/5 A Cl.0,5 10-5VA
-Class of accuracy: 0.5
-Rated primary current: 1000-500 A.
-Rated secondary current: 5 A.
-Rated burden: 10-5 VA
-Busbar dimension: 2x80x10 mm or ∅ 73 mm.
45