CONTENTS
Pages
1. HVAC 4
1.1. APPLICABLE CODES, REGULATIONS AND STANDARDS 4
1.2. DESIGN CRITERIA 4
1.2.1. OUTSIDE WEATHER CONDITIONS 4
1.2.2. INDOOR DESIGN CONDITIONS 5
1.2.3. OCCUPANCY ESTIMATE 5
1.2.4. LIGHTING POWER DENSITY (LPD) AND DEVICES 5
1.3. VENTILATION AND FRESH AIR RATES 6
1.4. INTERNAL HEAT GAIN 6
1.5. NOISE CRITERIA 7
1.6. COOLING LOAD ESTIMATE 7
1.7. HVAC SYSTEM DESCRIPTION 8
1.7.1. HVAC SYSTEM DESCRIPTION FOR EACH BUILDING 8
1.7.2. EMERGENCY POWER SUPPLY AND REDUNDANCY 9
The design of the Heating, Ventilation and Air-Conditioning systems (HVAC) shall be
designed in accordance with NEOM NEOM-NEN-SCH-005- List of technical codes and
standards in addition to the latest editions’ requirements and recommendations of the below:
HVAC load calculations shall be done on the following design data for Aqaba city, which is
the nearest city to magna pressure tank:
Latitude: 29.612 N
Longitude: 35.018 E
Elevation: 53 M
The following table represents the indoor design condition that shall be met for
Summer/Winter seasons:
Summer Winter
Space Dry Bulb Temp. (°C)Relative Humidity (%) Dry Bulb Temp.
(°C)
Office 23 50 21
Corridors 23 50 21
Control Rooms 22 40 - 50 21
Laboratory 23 50 21
Battery room 26 50 -
Electrical room 22 - -
Notes:
Tolerances: Temperature: +/- 1 °C
Relative Humidity: +/- 5%
The occupancy rates used in the preliminary calculations shall be on the latest edition of
ASHRAE Standard 62.1,the final occupancy figures shall be validated from NEOM
Water/ETSD.
The lighting and devices shall be calculated according to given data from Electrical
department or as per ASHRAE STANDARD 90.1-latest version and operator guide as follows.
The ventilation rate shall be based on the ASHRAE standards 62.1 (2019)
Area Rate
Space
L/s per m2
Sum pit 5
Locker Rooms 2.5
Toilets—Private 25 L/s/WC
Shower 25 L/s/unit
Battery room 10 ACH
Laboratory 5.1
Fresh air intake louvers shall be of sand trap and sized on maximum face velocity of 1 m\s
with respect to the net area.
Exhaust air discharge shall be sized on face velocities of 2 m\s with respect to the net area.
The Lighting Loads: The lighting load used in the preliminary calculations shall be done on
the latest edition of ASHRAE Standard 90.1 space by space method, final figures shall be
verified on the actual interior lighting layouts.
Equipment Loads: Equipment load shall be allowed for in the air-conditioning load estimate
and shall include heat emissions from the computer terminals and printers in the office
areas and any other ancillary equipment used for a specific application, heat dissipation
rates shall base on ASHRAE handbook recommendations
The preliminary HVAC equipment load for control building has been estimated at
approximately about 53 KW as follow:
Battery room: Estimated load 2.8 KW, air flow 186 l/s, fresh air 0 l/s
Control room: Estimated load 29.8 KW, air flow 2513 l/s, fresh air 80 l/s
Corridor: Estimated load 4.8 KW, air flow 255 l/s, fresh air 35 l/s
Laboratory: Estimated load 4.6 KW, air flow 132 l/s, fresh air 55 l/s
Office: Estimated load 4.3 KW, air flow 203 l/s, fresh air 35 l/s
UPS: Estimated load 6.8 KW, air flow 672 l/s, fresh air 0 l/s
HVAC systems shall be selected and designed taking into consideration the selection of
optimum and most efficient systems in relation with function and application for each space.
All spaces within magna pressure tank shall be served by means of a standalone DX system
meeting sustainability requirement as described in sustainability sections and as per SBC
601/602, SBC 1001 and ASHRAE 90.1
Outdoor equipment shall be located outside at building surface or any area opened to sky.
Different areas shall be served by means of individual DX Split Heat pumps for standalone
Units,
DX Split decorative cooling unit shall be used for battery room, or similar areas without
reflected ceiling.
Indoor units shall be installed in BOH areas where possible as per actual architecture
layout to reduce accessibility for these units from front of house areas.
In case selected Heat Pump or DX with integrated heating coil cannot cater for the heating
load, then duct mounted electric coil shall be considered to offset the heating load.
a) Control building:
Control building shall be served by DX systems using separated concealed split units.
Control room shall be served by four concealed splits DX Heat pumps with one standby
to achieve air flow.
Battery room shall be served by dedicated of two hi-wall split DX cooling only (one
standby) and ventilated with two dedicated inline exhaust fans one (stand by) at outdoor
area opened to sky at rate not less than (5.1 l/s/m2) of floor area of room interfaced
with H2 sensors at the room to control H2 emissions rates. The maximum concentration
of H2 shall be limited to one percent of the total volume of the room.
the battery room shall be maintained at negative pressure and equipped with an
explosion-proof fan and motor..
Office and corridor shall be served by separated concealed split DX Heat pumps.
Laboratory shall be served by concealed split DX heat pumps and ventilated by dedicated
inline exhaust fan at outdoor area opened to sky for dilution ventilation.
The laboratory shall be maintained at negative pressure.
Design Parameters:
G02-CONTROL ROOM
1. General Details:
Floor Area ......................................................... 36.0 m²
Avg. Ceiling Height ............................................. 3.3 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 80.0 L/s
OA Requirement 2 .............................................. 0.0 L/s
Space Usage Defaults ....... ASHRAE Std 62.1-2016
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 15.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.25 Sensible ............................................................ 71.8 W/person
Schedule .................................... Sample Schedule Latent ............................................................... 60.1 W/person
Schedule .................................... Sample Schedule
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 10.0 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 36.0 0 0
5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 36.0 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.568 W/(m²·K)
Floor Depth ......................................................... 2.5 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m
7. Partitions:
(No partition data).
G03-ELECTRICAL ROOM
1. General Details:
Floor Area ......................................................... 19.0 m²
Avg. Ceiling Height ............................................. 3.3 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ....... ASHRAE Std 62.1-2016
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage .......................................................... 10.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.25 Sensible ............................................................ 71.8 W/person
Schedule .................................... Sample Schedule Latent ............................................................... 60.1 W/person
Schedule .................................... Sample Schedule
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 8.0 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 19.0 0 0
5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 19.0 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.568 W/(m²·K)
Floor Depth ......................................................... 2.5 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m
7. Partitions:
(No partition data).
G04&G09-CORIDDOR
1. General Details:
Floor Area ......................................................... 25.0 m²
Avg. Ceiling Height ............................................. 3.3 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 35.0 L/s
OA Requirement 2 .............................................. 0.0 L/s
Space Usage Defaults ....... ASHRAE Std 62.1-2016
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage .......................................................... 12.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.25 Sensible ............................................................ 71.8 W/person
Schedule .................................... Sample Schedule Latent ............................................................... 60.1 W/person
Schedule .................................... Sample Schedule
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 25.0 0 0
5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 25.0 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.568 W/(m²·K)
Floor Depth ......................................................... 2.5 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 50.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 39.5 °C
Ambient at Space Max Temp ............................ 44.5 °C
Uncondit. Space Min Temp ............................... 10.5 °C
Ambient at Space Min Temp ............................... 5.5 °C
G05-BATTERY ROOM
1. General Details:
Floor Area ......................................................... 26.0 m²
Avg. Ceiling Height ............................................. 3.3 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ....... ASHRAE Std 62.1-2016
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage .......................................................... 10.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.25 Sensible ............................................................ 71.8 W/person
Schedule .................................... Sample Schedule Latent ............................................................... 60.1 W/person
Schedule .................................... Sample Schedule
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 9.0 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 26.0 0 0
5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 26.0 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.568 W/(m²·K)
Floor Depth ......................................................... 2.5 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 12.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 39.5 °C
Ambient at Space Max Temp ............................ 44.5 °C
Uncondit. Space Min Temp ............................... 10.5 °C
Ambient at Space Min Temp ............................... 5.5 °C
G06-LABORATORY
1. General Details:
Floor Area ......................................................... 12.0 m²
Avg. Ceiling Height ............................................. 3.3 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 55.0 L/s
OA Requirement 2 .............................................. 0.0 L/s
Space Usage Defaults ....... ASHRAE Std 62.1-2016
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage .......................................................... 16.50 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.25 Sensible ............................................................ 71.8 W/person
Schedule .................................... Sample Schedule Latent ............................................................... 60.1 W/person
Schedule .................................... Sample Schedule
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 5.0 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 12.0 0 0
5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 12.0 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.568 W/(m²·K)
Floor Depth ......................................................... 2.5 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 14.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 39.5 °C
Ambient at Space Max Temp ............................ 44.5 °C
Uncondit. Space Min Temp ............................... 10.5 °C
Ambient at Space Min Temp ............................... 5.5 °C
G08-OFFICE
1. General Details:
Floor Area ......................................................... 25.0 m²
Avg. Ceiling Height ............................................. 3.3 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 35.0 L/s
OA Requirement 2 .............................................. 0.0 L/s
Space Usage Defaults ....... ASHRAE Std 62.1-2016
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage .......................................................... 12.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.25 Sensible ............................................................ 71.8 W/person
Schedule .................................... Sample Schedule Latent ............................................................... 60.1 W/person
Schedule .................................... Sample Schedule
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 7.0 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 25.0 0 0
5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 25.0 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.568 W/(m²·K)
Floor Depth ......................................................... 2.5 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 39.5 °C
Ambient at Space Max Temp ............................ 44.5 °C
Uncondit. Space Min Temp ............................... 10.5 °C
Ambient at Space Min Temp ............................... 5.5 °C
WALL CONSTRUCTION
Wall Details
Outside Surface Color ................................ Medium
Absorptivity ..................................................... 0.675
Overall U-Value .............................................. 1.663 W/(m²·K)
ROOF CONSTRUCTION
Roof Details
Outside Surface Color ................................ Medium
Absorptivity ..................................................... 0.675
Overall U-Value .............................................. 0.363 W/(m²·K)
1. General Details:
Air System Name ................................. CONTROL BUILDING DX SYSTEM
Equipment Type .................................................................. Terminal Units
Air System Type .............................................................. Split DX Fan Coil
Number of zones ....................................................................................... 6
Ventilation ................................................. Dedicated Outdoor Air System
% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54
% Airflow 40 30 20 10 0
% kW 46 40 33 27 21
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
G05-BATTERY ROOM x1
Zone 2: Zone 2
G02-CONTROL ROOM x1
Zone 3: Zone 3
G04&G09-CORIDDOR x1
Zone 4: Zone 4
G06-LABORATORY x1
Zone 5: Zone 5
G08-OFFICE x1
Zone 6: Zone 6
G03-ELECTRICAL ROOM x1
T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 25.0 27.0 21.1 18.3 0.83
2 21.0 23.0 20.0 18.3 0.83
3 22.0 24.0 21.1 18.3 0.83
4 22.0 24.0 21.1 18.3 0.83
5 22.0 24.0 21.1 18.3 0.83
6 21.0 23.0 20.1 18.3 0.83
Cooling Coil:
Design Supply Temp. ........................................................................... 12.8 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source .................................................................... Air-Cooled DX
Schedule ........................................................................ JFMAMJJASOND
Heating Coil:
Design Supply Temp. ........................................................................... 30.0 °C
Heating Source ....................................................... Air Source Heat Pump
Schedule ........................................................................ JFMAMJJASOND
Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Ceiling supply /
1 Fan coil Not Used - 0.00 L/s/person 50 Pa 50 % -
ceiling return
Ceiling supply /
2 Fan coil Not Used - 0.00 L/s/person 50 Pa 50 % -
ceiling return
Ceiling supply /
3 Fan coil Not Used - 0.00 L/s/person 50 Pa 50 % -
ceiling return
Ceiling supply /
4 Fan coil Not Used - 0.00 L/s/person 50 Pa 50 % -
ceiling return
Ceiling supply /
5 Fan coil Not Used - 0.00 L/s/person 50 Pa 50 % -
ceiling return
Ceiling supply /
6 Fan coil Not Used - 0.00 L/s/person 50 Pa 50 % -
ceiling return
Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ......................................................................................... 10 %
Heating ...................................................................................................... 5 %
Calculation Months ................................ Jan to Dec Zone L/s Sizing ................. Sum of space airflow rates
Sizing Data ............................................ Calculated Space L/s Sizing ............. Individual peak space loads
Actual max L/s ................................................... 205 L/s Fan motor BHP ....................................................... 0.12 BHP
Standard L/s ...................................................... 204 L/s Fan motor kW ......................................................... 0.09 kW
Actual max L/(s·m²) .......................................... 1.43 L/(s·m²) Fan static ................................................................. 250 Pa
Calculation Months ................................ Jan to Dec Zone L/s Sizing ................. Sum of space airflow rates
Sizing Data ............................................ Calculated Space L/s Sizing ............. Individual peak space loads
Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
G05-BATTERY ROOM 1 2.7 Jul 1600 186 0.8 26.0 7.17
Zone 2
G02-CONTROL ROOM 1 24.7 Jun 2200 2513 0.5 36.0 69.80
Zone 3
G04&G09-CORIDDOR 1 2.8 Jul 1500 255 1.7 25.0 10.21
Zone 4
G06-LABORATORY 1 1.5 Jul 1500 132 0.7 12.0 10.99
Zone 5
Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
G08-OFFICE 1 2.2 Jul 1600 203 0.8 25.0 8.10
Zone 6
G03-ELECTRICAL ROOM 1 6.6 Jun 2200 672 0.3 19.0 35.36
1. Summary
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Design Ventilation Airflow Rate .............................................................. 205 L/s
TABLE 1.1.A. Component Loads For Space "G05-BATTERY ROOM" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.1 °C / 29.2 °C HEATING OA DB / WB 5.5 °C / 3.2 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 9 m² 460 - 9 m² 234 -
Roof Transmission 26 m² 61 - 26 m² 147 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 26 m² 0 - 26 m² 0 -
Partitions 12 m² 431 - 12 m² 361 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 325 W 227 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1300 W 1300 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 248 0 5% 37 0
>> Total Zone Loads - 2728 0 - 780 0
TABLE 1.1.B. Envelope Loads For Space "G05-BATTERY ROOM" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²·K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 9 1.663 - 460 - 234
H EXPOSURE
ROOF 26 0.363 - 61 - 147
TABLE 2.1.A. Component Loads For Space "G02-CONTROL ROOM" In Zone "Zone 2"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2200 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.9 °C / 27.3 °C HEATING OA DB / WB 5.5 °C / 3.2 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 10 m² 607 - 10 m² 241 -
Roof Transmission 36 m² 106 - 36 m² 190 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 36 m² 0 - 36 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 675 W 472 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 21000 W 20999 - 0 0 -
People 4 287 240 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2247 24 5% 22 0
>> Total Zone Loads - 24719 264 - 452 0
TABLE 2.1.B. Envelope Loads For Space "G02-CONTROL ROOM" In Zone "Zone 2"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²·K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 10 1.663 - 607 - 241
H EXPOSURE
ROOF 36 0.363 - 106 - 190
TABLE 3.1.A. Component Loads For Space "G04&G09-CORIDDOR" In Zone "Zone 3"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.5 °C / 29.3 °C HEATING OA DB / WB 5.5 °C / 3.2 °C
OCCUPIED T-STAT 22.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 25 m² 67 - 25 m² 142 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 25 m² 0 - 25 m² 0 -
Partitions 50 m² 2233 - 50 m² 1506 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 375 W 262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 256 0 5% 82 0
>> Total Zone Loads - 2818 0 - 1731 0
TABLE 3.1.B. Envelope Loads For Space "G04&G09-CORIDDOR" In Zone "Zone 3"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²·K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 25 0.363 - 67 - 142
TABLE 4.1.A. Component Loads For Space "G06-LABORATORY" In Zone "Zone 4"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.5 °C / 29.3 °C HEATING OA DB / WB 5.5 °C / 3.2 °C
OCCUPIED T-STAT 22.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 5 m² 277 - 5 m² 130 -
Roof Transmission 12 m² 32 - 12 m² 68 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 12 m² 0 - 12 m² 0 -
Partitions 14 m² 625 - 14 m² 422 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 248 W 173 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 132 18 5% 31 0
>> Total Zone Loads - 1456 198 - 651 0
TABLE 4.1.B. Envelope Loads For Space "G06-LABORATORY" In Zone "Zone 4"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²·K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 5 1.663 - 277 - 130
H EXPOSURE
ROOF 12 0.363 - 32 - 68
TABLE 5.1.A. Component Loads For Space "G08-OFFICE" In Zone "Zone 5"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.1 °C / 29.2 °C HEATING OA DB / WB 5.5 °C / 3.2 °C
OCCUPIED T-STAT 22.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 7 m² 393 - 7 m² 182 -
Roof Transmission 25 m² 67 - 25 m² 142 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 25 m² 0 - 25 m² 0 -
Partitions 15 m² 666 - 15 m² 452 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 375 W 262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 203 12 5% 39 0
>> Total Zone Loads - 2236 132 - 814 0
TABLE 5.1.B. Envelope Loads For Space "G08-OFFICE" In Zone "Zone 5"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²·K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 7 1.663 - 393 - 182
H EXPOSURE
ROOF 25 0.363 - 67 - 142
TABLE 6.1.A. Component Loads For Space "G03-ELECTRICAL ROOM" In Zone "Zone 6"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2200 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.9 °C / 27.3 °C HEATING OA DB / WB 5.5 °C / 3.2 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 8 m² 486 - 8 m² 194 -
Roof Transmission 19 m² 56 - 19 m² 101 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 19 m² 0 - 19 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 238 W 166 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 5300 W 5300 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 601 0 5% 15 0
>> Total Zone Loads - 6608 0 - 310 0
TABLE 6.1.B. Envelope Loads For Space "G03-ELECTRICAL ROOM" In Zone "Zone 6"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²·K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 8 1.663 - 486 - 194
H EXPOSURE
ROOF 19 0.363 - 56 - 101