Protection TSS
Protection TSS
RAILWAY
TRACTION SUB STATION
2
3
132 / 25 KV TRACTION SUBSTATION LAYOUT PLAN
PROTECTION RAILWAY
TRACTION SUB STATION
TRANSFORMER PROTECTION
LIGHTNING ARRESTORS – HV & LV SIDE
EARTH FAULT RELAYS - HV & LV SIDE (REF)
INSTANTANEOUS OVER CURRENT RELAY –
HV SIDE (OCR1-I)
IDMT OCR RELAY – HV SIDE (OCR1-T)
TRASFORMER OVER LOAD PROTECTION,
3 STAGE RELAY – HV & LV SIDE
PROTECTION RAILWAY
TRACTION SUB STATION
TRANSFORMER PROTECTION
IDMT OCR RELAY – LV SIDE (OCR-2)
TRANSFORMER DIFFERENTIAL RELAY
(DFR)
TRANSFORMER BUCHOLZ RELAY
TRANSFORMER PRESURE RELAESE
DEVICE (PRD)
TRASFORMER WINDING TEMPERATURE
PROTECTION RELAY (WTI)
PROTECTION RAILWAY
TRACTION SUB STATION
TRANSFORMER PROTECTION
LOCAL BREAKER BACKUP PROTECTION --
LV SIDE (LBB)
TRANSFORMER OIL TEMPERATURE RELAY (OTI)
TRANSFORMER MINIMUM OIL GAUGE / RELAY
(MOG)
TRANSFORMER ARCING HORNS – HV & LV SIDES
TRANSFORMER ONLOAD TAP CHANGER
PROTECTION – HV & LV SIDE
TRASFORMER AIR BALOON & SILICA GEL
PROTECTION
PROTECTION RAILWAY
TRACTION SUB STATION
TRANSFORMER PROTECTION
TRANSFORMER FIRE PROTECTION
SYSTEM
TRANSFORMER INTER TRIP RELAY (ITR)
CIRCUIT BREAKER TRIP CIRCUIT
SUPERVISION SYSTEM
CIRCUIT BREAKER LOW GAS & AIR
PRESSURE RELAYS
PROTECTION RAILWAY
TRACTION SUB STATION
FEEDER PROTECTION
INSTANTANEOUS OVER CURRENT RELAY
(OCR3)
WRONG PHASE COUPLING RELAY (WPC)
DISTANCE PROTECTION RELAY (DPR)
VETORIAL DELTA -I RELAY
PANTO FLASHOVER RELAY
AUTO RECLOSE LOCKOUT RELAY
PT FUSE FAILURE INDICATION
PROTECTION RAILWAY
TRACTION SUB STATION
TSS PROTECTION
DC voltage monitoring relay to be provided on
control and relay panel to monitor the DC and AC
voltage.
DC UV Alarm – 100 VDC, Op. Time- 30 Sec.
DC UV Trip – 82 VDC, Op. Time -0.5 Sec.
DC OV Alarm – 140 VDC , Op. Time -30 Sec.
AC OV Alarm – 270 VAC, Op. Time -30 Sec.
AC UV Alarm – 170 VAC, Op. Time -30 Sec.
PROTECTION RAILWAY TRACTION SUB STATION
10
PRINCIPAL
OF RELAY
OPERATION
11
12
PROTECTION IN RAILWAY TRACTION SUB STATION
13
Transformer
Protection
14
HV Side protection
LIGHTNING ARRESTORS
- 60 KV LA For 66 KV System
15
Instruction No. TI/IN/0022
(February/2010) & Rev. on 19/07/2012
• OVER CURRENT
• IDMT OCR1 (T) = 190 % of IP FL
TMS = Such that relay operation must be
in between 500 to 600 msec for a
fault occurring on LV Bus.
18
HV Side protection
PRIMARY SIDE CURRENT
19
HV Side protection
PRIMARY SIDE CURRENT
Definite Time Over current Relay
(Rev. issued on 19/07/2012)
• HV side
OL1 = 130% of IP FL 15 min = 900 Sec
OL2 = 150% of IP FL 12 min = 720 Sec
OL3 = 180% of IP FL 05 min = 300 Sec
Repeated Over load protection Relay
POL = 110% of IP FL
TMS = 70 Sec.
POST OVERLOAD TIME RESET SETTING = 3 Hrs. 20
Incoming HV Side Protection
OCR-1 (I) & (T), REF RELAY OPERATION
CT CT
Stabilizing
Resistance
Inst IDMT
REF relay
O/C Relay
Trn – HV side
21
HV Side protection Transformer
22
HV Side protection Transformer
23
LV Side protection
LIGHTNING ARRESTORS
• LA - 42 KV LA For 25 KV System
24
LV Side protection
SECONDARY SIDE CURRENT
• RESTRICTED EARTH FAULT
• REF2 = 10% of IS FL
WHERE IS FL = SECONDARY FULL LOAD CURRENT
• OVER CURRENT
• IDMT OCR2 (T) = 180 % of IS FL
TMS = Such that relay operation must be in
between 250 to 300 msec for a fault
occurring on LV Bus. 25
LV Side Protection
SECONDARY SIDE CURRENT
Definite Time Over current Relay
(Rev. issued on 19/07/2012)
• LV side
OL1 = 120% of IS FL 14 min = 840 Sec
OL2 = 140% of IS FL 10 min = 600 Sec
OL3 = 170% of IS FL 04 min = 240 Sec
Repeated Over load protection Relay
POL = 100% of IS FL
TMS = 60 Sec.
POST OVERLOAD TIME RESET SETTING = 3 Hrs.
26
25 kV/LV Side
Protection TFR
CT
28
LV Side protection Transformer
29
Transformer Differential protection
Biased differential protection: Guidelines
(a) The percentage biased setting should be so chosen
that the relay remains inoperative on differential
currents resulting from
(1) tap changing of traction transformer,
(2) mismatch in CT ratios &
(3) difference in CT saturation levels under through
fault conditions.
Percentage mismatches resulting from factors
(1) and (2) may be calculated from actual data
and an allowance of 7.5 to 15% may be made
for factor (3). 30
Transformer Differential protection
Biased differential protection: Guidelines
(b) The operating current setting may
be taken as 40%. If mal operations
of the relay are observed on through
faults and magnetizing inrush
(switching in of power transformer),
a higher setting may be considered.
31
Transformer Differential protection
32
Transformer Differential protection
Restraining
Coil Opt Coil
Differential
relay
33
Transformer Protection
34
Transformer Protection
35
TRANSFORMER
PROTECTION
FEEDER
PROTECTION
36
37
TRANSFORMER IN BUILT PROTECTION
1. Arcing horn gap
2. PRD / Diaphragm
3. Buchhloz relay----
--- Stage 1 - alarm
--- stage 2 - tripping
4. OTI ------
--- Stage 1 - alarm
--- stage 2 - tripping (85°c)
38
TRANSFORMER IN BUILT PROTECTION
5. WTI ---------
--Stage 1 - Alarm
--Stage 2 - Tripping (95°C)
6. Low Oil Level Alarm
40
41
42
43
44
I
T
R
45
Inter tripping of 132 kV and
25 kV Transformer CB
• Operation of the following relays result in
inter tripping of the transformer CBs on
primary as well as on the secondary sides.
• Differential relay.
• REF relay on HV or LV.
• Buchholz relay (Trip)
• WTI (trip)
• OTI (trip)
• PRD (trip)
46
CIRCUIT BREAKER TRIP
CIRCUIT SUPERVISION SYSTEM
• The RELAY is having 2 separate digital opto-
coupler status input which can be used to
continuously monitor continuity of trip circuit.
• Relay monitor Trip coil continuity through CB
NO during close condition and through CB
NC during Open condition. If any
discontinuity observed it generate Alarm
signal. The output marked as TCF (Trip
Circuit Faulty) is become close.
47
Feeder Protection
48
As per RDSO specs TI/SP/PSI/PROTCT/5070.
49
Asida Relay ADR219A
• Protection Features:
• Digital Distance
• Instantaneous Over-Current Protection.
• PT Fuse Monitoring.
• Auto Re-closer Relay.
• Breaker Failure detection.
• In-built CB Trip Circuit monitoring during
close as well as open condition
• Switch On to Fault. (SOTF) 50
Asida Relay ADR219A
• Protection Features:
• Password Protection for all setting
• Disturbance Recorder. 50 cycles of actual
waveform of voltage & current are
captured & saved in the built-in memory
with date time stamping, for analyzing fault
condition & fault location.
• • IEC standard open protocol.
51
52
LBB - Feeder breaker back up
protection feature
• This feature monitors the status of
Feeder CB or magnitude of fault current
after issue of trip command to feeder
CB and issues a trip command for
LVCB’s after a lapse of set time delay,
if either Feeder CB fails to open or fault
current is not falling below the actuating
value. 53
RDSO DETAILS
INSTRUCTIONS
54
RDSO DETAILS
INSTRUCTIONS
57
20205 Overload Capacity of Traction Transformers
Traction transformers usually have the following overload capacity:
1. Overload rating : (a) 50% overload for 15 min. and (b) 100%
overload for a period of 5 min.: after the transformer has attained
steady temperature on continuous operation at full load.
2. Over an ambient temperature of 45 degree C the maximum
permissible temperature rise shall be as under:
(a) Winding = 50degree C (by resistance method)
23
(b) Oil = 40 degree C ( by thermometer)
(c ) Current carrying parts = 35 degree C ( BY THERMOMETER)
3. The hot-spot temperature after 50 % overload for 15 min, or
100% overload for 5 min. shall not exceed 100 degree C for an
ambient temperature of 45 degree C.
4. Interval of time permissible between two successive overloads (
after continuous working at maximum ambient temperature of 45
degree C is 3 hours for both 50% overload for 15 min. and 100%
overload for 5 min.
58
Thank you
for
Attention
59