RAC Assignments
RAC Assignments
3. One TR is:
a. 3.5 kW b. 4.5 kW
c. 5.5 kW d. none of these
A low temperature is maintained so that heat can flow from the external fluid
Protect evaporator
Domestic refrigerators
Cold storages
Before compression
Before throttling
After compression
After throttling
22 One ton of refrigeration is equal to
2.11 kW
2.5 kW
3.5 kW
3.1 kW
23 The refrigerant leaving the throttle valve is
saturated vapour
saturated liquid
superheated vapour
wet vapour
24 Reducing suction pressure in refrigeration cycle
none
25 For domestic refrigerator the following type of expansion valve is economically
suitable
capillary tube
plastic tube
none of above
1 A 5 TR, R12 refrigeration plant has a saturated suction temperature of -50C. The
condensation takes place at 320C and there is no under cooling of refrigerant
liquid. Assuming isentropic compression calculate:
a. COP of plant, b. Mass flow rate of refrigerant, c. Power required to run the
compressor in KW.. Take Cp of superheated vapour as 0.615KJ/Kgk
T[0C] P[Bar] Hf[KJ/Kg] Hg[KJ/Kg] Sg[KJ/Kgk]
-5 2.61 - 249.3 1.557
32 7.85 130.5 264.5 1.542
i) COP of the refrigerator, ii) the temperature at which the heat is rejected,
iii) the amount of heat rejected in kJ/min., and iv) COP, if the cycle is used as a heat
pump.
3 A refrigerator produces 20 tons of ice per day from and at 0°C. The
there is no undercooling of the liquid refrigerant. The actual COP is 70% of the
theoretical COP. Determine :
i) The rate of refrigerant circulation, ii) The size of single acting compressor when
running at 240 rpm assuming, L = D and volumetric efficiency of 80%.
Take, hfg (fusion of ice) =335 kJ/kg., Use the following properties of the refrigerant
4 A Bell – Coleman cycle works between 1 bar and 6 bar. Compression follows PV1.25
= C and expansion follows PV1.3 = C. Find COP and capacity of unit in tons of
refrigeration, if the air flow is 0.5 kg/s. Assume compression and expansion begins
at 7°C and 37°C respectively.
5 A refrigerator working on Bell-Coleman cycle operates between pressure limits of
1.05 bar and 8.5 bar. Air is drawn from the cold chamber at 10°C, compressed and
then it is cooled to 30°C before entering the expansion cylinder. The expansion and
compression follows the law pv1.3 = constant. Determine the COP of the system.
6 The temperature limits of an ammonia refrigerating system are 25°C and – 10°C. If
the gas is dry at the end of compression calculate the coefficient of performance of
the cycle, assuming no under cooling of the liquid ammonia.
Use the following table for the properties of ammonia.
Temp. (°C) Liquid Heat Latent Liquid
(kJ/kg) Heat Entropy(kJ/kgK)
(kJ/kg)
25 298.9 1166.94 1.1242
–10 135.37 1297.68 0.5443
7 An ammonia ice plant operates between a condenser temperature of 35°C
Cp = 2.763 kJ/kgK.
Tset P(bar) vf vg hf hg sf sg
8 A dense air refrigeration system of 10 ToR capacity works between 4 bar and 16
bar. The air leaves the cold chamber at 0°C and discharges air at 25°C to the
expansion cylinder after air cooler. The expansion and compression cylinders are
double acting. The mechanical efficiency of compressor and expander are 85%
and 80% resp. The compressor speed is 250 rpm and has stroke of 250 mm.
Determine
i) COP
iii) HP per TR
iv) COP
1 Enumerate the various methods of air refrigeration systems & explain any one.
1 Explain Need of Refrigeration System in Aircraft
2 Enumerate the various methods of aircraft refrigeration system and explain
regenerative air cooling system.
3 Describe with neat sketch a boot strap air refrigeration system.
4 Discuss the limitations of Reversed Carnot Cycle with vapor as Refrigerant.
5 Explain Effect of change in evaporator & condenser pressure on COP of VCC.
6 Draw neat diagram of Regenerative air cooling system for air craft refrigeration
and explain it with the help of its T-S diagram.
B Refrigerants
1. Ammonia is one of the oldest refrigerants, which is still used widely, because
It is a natural refrigerant
It is inexpensive
It is odorless
3. Sulphur dioxide was mainly used in small refrigeration systems, because
It is expensive
Expensive
5. The chemical formula of refrigerant R11 is
CCl3F CClF3
CClHF CHF
6. Which of the following refrigerants are phased-out due to Montreal protocol on
ozone layer depletion
R22 R11
R134a R141b
8. For ammonia refrigerating systems, the tubes of a shell and tube condenser are
made of
copper aluminum
steel brass
9. The freon group of refrigerants are
halo-carbon refrigerants
azeotrope refrigerants
inorganic refrigerants
hydro-carbon refrigerants
1 Which of the following statement is correct for ammonia as a refrigerant?
all of these
1 ODP value of R11 is
A) 0 B) 1 C) 2 D) 3
1 Which of the following refrigerants has highest freezing point ?
ammonia
carbon dioxide
sulphur dioxide
R–12
Unit 2
Vapour compression cycle
All of above
Refrigerant mass flow rates in both low and high stage compressors are
equal
Mass flow rates in low and high stage compressors are equal if the
pressure ratios are equal
2 The natural Refrigerant CO2 has a Fairly low critical Temperature find
the high temperature, the condensing temperature and the COP. If it
is used in a standard cycle with high and low pressure of 6 and 3
MPa. [45.90C, 220C, 6.2]
3 A heat pump for heat upgrade uses ammonia with a low temperature
of 250C and high pressure of 5000 kPa. If it receives 1MW of soft
work what is the rate of heat transfer at the high temperature?
[4386 KW]
d) COP (4.167)
t ht hg Sf
400C 371.5 1473 1.36
-100C 135.4 1433 0.544
5 Draw schematic diagram of two stage compression system with flash gas
removal & flash gas intercooling, explain it with the help of P-H diagram.
B) Multi-pressure systems
Multiple Choice Questions
Ans.: a) and c)
Ans.: a) , c) and d)
3
Using intercooling in multi-stage compression systems:
Ans.: b)
4
External intercooling of refrigerant vapour:
a) Is feasible for ammonia based systems
Ans.: a) and b)
Ans.: a) , c) and d)
6
Using intercooling in multi-stage compression systems:
Ans.: b)
7
External intercooling of refrigerant vapour:
Ans.: a) and b)
9
7. Refrigeration system with liquid subcooler is used to:
a) Refrigerant mass flow rates in both low and high stage compressors
are equal
d) Mass flow rates in low and high stage compressors are equal if the
pressure ratios are equal
Ans.: b)
11
9. Use of flash tank for intercooling:
Ans.: b) and c)
12
Multi-evaporator systems are:
Ans.: a) and b)
13
2. Multi-evaporator systems with a single compressor and a pressure
reducing valve:
Ans.: d)
15
Compared to individual expansion valves, multiple expansion valves:
Ans.: a) and d)
16
Compared to multi-evaporator and single compressor systems,
multi-evaporator
Ans.: a) and b)
17
In multi-stage systems:
a) The refrigerant used should have high critical temperature and high
freezing point
b) The refrigerant used should have high critical temperature and low
freezing point
18
6. In cascade systems:
19
Cascade systems are widely used for:
Ans.: b)
20
For a two-stage cascade system working on Carnot cycle and between
low and high
a) –20oC
b) –30oC
c) –67oC
d) 0oC
Ans.: b)
21
In a two stage, auto-cascade system:
Ans.: c)
22
In a two stage, auto-cascade system:
6 What are the methods of improving COP of VCRs ? Explain with line
diagram Cascade refrigeration system.
10 Explain with sketch, two stage compression system with flash gas removal.
Also show the process on P-H Diagram.
Assignment 04
a) Higher COPs
Ans.: c)
7
Absorption of the refrigerant by the absorbent in a vapour absorption
refrigeration system is accompanied by:
8
An absorption system consisting of only two closed vessels:
Ans. b) and c)
9
The conventional, continuously operating single stage vapour absorption
refrigeration system:
Ans. b) and d)
10
For an ideal refrigerant-absorbent mixture:
d) Obeys Raoult’s law in liquid phase and Dalton’s law in vapour phase
Ans. a) and d)
11
For a refrigerant-absorbent mixture with a negative deviation from Raoult’s law:
c) The actual equilibrium temperature will be less than that predicted by Raoult’s
law
12
Refrigerant-absorbent pairs used in vapour absorption refrigeration systems
should:
13
Which of the following statements are true:
Ans. a) and c)
14
Vapour absorption refrigeration systems using water-lithium bromide:
15
For a required refrigeration capacity, the solution heat exchanger used in
waterlithium bromide systems:
16
In water-lithium bromide systems:
Ans. a) and d)
17
4. In commercial water-lithium bromide systems
18
5. Commercial multi-effect absorption systems:
Ans. a) and d)
19
6. In water-lithium bromide systems:
a) The required heat source temperature should be higher than minimum heat
generation temperature
increases
c) The required heat source temperature is higher for air cooled condensers,
compared to water cooled condensers
20
In commercial water-lithium bromide systems, the system capacity is regulated
by:
21
Presence of water vapour in the refrigerant circuit of a NH3-H2O system:
22
Compared to H2O-LiBr systems, a NH3-H2O system:
23
Which of the following statements regarding the definition of concentration are
TRUE:
Ans. b) and c)
24
Which of the following statements regarding NH3-H2O solution are TRUE:
a) The bubble point temperature is always higher than dew point temperature
b) The bubble point temperature is always lower than dew point temperature
c) At a given pressure, the bubble point and dew point temperatures are higher
than the saturation temperature of NH3 but lower than the saturation
temperature of H2O
d) At a given pressure, the bubble point and dew point temperatures are lower
than the saturation temperature of NH3 but higher than the saturation
temperature of H2O
Ans.: b) and c)
25
For NH3-H2O solution at equilibrium, which of the following statements are
FALSE:
26
When a binary solution of NH3-H2O is throttled adiabatically:
Ans.: b) and d)
27
In an ammonia-water system a rectification column is used mainly to:
28
In a reflux condenser:
Ans.: a)
29
Due to the requirement of rectification:
30
In pumpless vapour absorption refrigeration systems:
31
Which of the following statements regarding pumpless systems are TRUE:
32
Compared to compression systems, the performance of absorption systems:
33
Compared to compression systems, absorption systems:
c) Offer less noise and vibration d) Are compact for large capacities
a. Absorber b. Rectifier
Cryogenics
1 In cascade systems
a) Correct b) incorrect
3 Explain two stage cascade refrigeration system with its P-h diagram.
6
Explain cryogenics.
7
Describe Linde system.
8
Describe applications of cryogenics.
Experiment:06
Psychometry
Multiple Choice Questions
6 Moist air is :
a. water vapour b. dry air
c. mixture of water vapour and dry air d. none of these
2
Specific humidity of atmospheric air at 27.5 oC is 0.016 kg/kg d.a Find
partial pressure of water vapor , relative humidity DPT.[Pv=0.02675 bar,
Φ= 72.87%, DPT=21.38 oC].
3
Calculate the specific volume of an air-vapor mixture in cubic meter per
kilogram of dry air when the following condition prevail: DBT=30 oC,
w=0.015mg/kgda, total pressure (p)= 90kpa[ Pv= 0.0212bar,
µ=µv+µa=99.09]
4
A sample of moist air has a DBT of 43 oC and a WBT of 29 oC. calculate
the following without making use of the psychrometric chart: i) Pv, ii) w
iii) Rtc, iv) DPT , v) Humaid specific heat vi) enthalpy vii) dgree of
saturation [Pv= 0.03064 bar, w= 0.016 kgdov/kgda, Φ=35.47% DPT=
o
24.43 C, humaid sp.heat sp heat , Cp= cpa=wcpv=1.0407,
h=97.58k3/kg]
5
The barometric reading is 680 mm of Hg DBT=35 oC WBT= 25 oC.
Determine i) щ ii) sp. volume , iii) h1 & iv) RH P= or b= 680 mmHg X
133.3=90644h/m 2
=0.90644 bar. [ Pv= 0.02578 bar, щ= 0.0182
kgwv/kgda, Φ= 49.86
6
Moist air has DBT= 25 oC and degree of saturation 30%, the boromatric
pressure is 2.01325 bar calculate enthalphy and volume per kg of air
relative humidity saturated pressure of steam as 3.17 k/m2 at 25 oC
1
Short note on psychrometric chart
2
Describe Dry bulb temperature, Wet bulb temperature, Specific humidity,
Relative humidity, SHF.
3
What is adiabatic saturation/saturator.
4
Describe an air washer.
5
Describe bi-pass factor.
1
The DBT & DPT of atmospheric air are 300C and 140C resply. If the
barometer reading is 758 mm of Hg determine humidity ratio.
2
Find the absolute humidity of the air sample which has a DPT of 160C.
3
For a DBT of 250C ps a RH of 50% calculate the following for air when the
borometric pr. is 740 mm of Hg. Find without using psychrometric chart
(a) partial pr. of water vapor and dry air (b) DPT (c) specific humidity (d)
specific volume (e) enthalpy.
4
A sample of moist air has a dbt of 430C & WBT of 290C Calculate the
following without chart (a)partial pr. of water vapour (b) sp. humidity (c)
RH (d) DPT (e) humaid sp. heat (f) enthalpy (g) Degree of saturation (h)
Sigma heat function.
5
A sample of air has DBT & WBT of 35 0C & 25 0C respectively. The barometric
pr. is 760 mm of Hg Calculate (a) humidity ratio, RH enthalpy of the
sample (b) humidity ratio, RH & enthalpy, if the air were adiabatically
saturated.
6
Investigate the effect of humidity on the density of moist air by computing
the vapor density for an air water vapor mixture at 26 0C & RH of 0,50 &
1005 also , for each core, compere the value of the degree of saturation of
the value of RH.
7
Air at a condition of 300C DBT & 170C WBT & a barometric pr. Of 1050 mbar
enters an equipment where it undergoes a process of adiabatic
saturation the air leaving with a moisture content of 5g/kg higher than
what it was while entering . Calculate the following (a)moisture content
of the air entering the equipment (b) DBT & enthalpy of the air leaving
the equipment.
8
(a) Moist air is at 25 0C its DPT is 200C. The barometric pr. Is 755 mm of
Hg. What are the value of specific and relative humidities of the air ?
(b) if this air is cooled to 150C DBT & 50% RH what will be the
amount of total heat removed per unit mass of dry air? What will be the
corresponding amount of moisture removed?
9
(a) The Temp. of air entering an adiabatic saturator is 420C & that of air
leaving is 300C compute the humidity ratio & RH of the entering air.
(b) The conditions inside a room are 250C & 50% degree of
saturation. The inside surface temp of glass window is 100C will the
moisture condense from the room air upon the window glass?
10
On a particular day the atm air was found to have a DBT of 300C & WBT of
180C. The barometric pr. Was observed to be 756 mm of Hg. Obtain the
following value (a) RH (b) Sp humidity (c) DPT (d) enthalpy of air/kg of
dry air (e) volume of moisture per kg of dry air.
11
Obtain all psychrometric properties of air at 360C DBT & 200C WBT.
12
Determine the absolute humidity of the sample air having a DPT of 180C.
13
The DBT & DPT of ambient air are 400C & 140C reply. Determine the degree
of saturation of air also determine the RH.
1
The atm air is at 38 0C DBT & 1.01325 bar. If its thermodynamics WBT is 24 0C
determine: (a) the humidity ratio (sp.humidity) (b)sp. Enthalpy (c) DPT (d) RH
(e) sp. Volume.
2
Moist air , saturated at 10 0C flows over a heating coil at the rate of 500
m3/hr. Air leaves the coil at 40 0C. Plot the process on psychrometric chart &
determine (a) WBT of air (b) the sensible heat transferred in kw (c) the
total heat transferred in kw
3
Moist air of above example is poned over a heating coil having mean
effective temp of coil surface on 43 0C calculate the bypass factor of heating
coil.
4
. Moist air having DBT & WBT of 40°c & 20°c Respectively. flows over a
cooling coil at the rate of 7000 m²/hr. Finally it is cooled to 26°C DBT. Plot
the process on chart & determine (a) Final WBT of air (b) the total heat
transferred in kw. It the cooling coil surface temp is 22°c, find the bypass
factor of the coil.
5. Moist air at 32°c DBT & 50% RH enters a cooling coil at 10000 m³/hr. It is
desired that the air leaving the coil has a DBT of 20°C & WBT of 18°C.
Determine the following (a) mean effective surface temp of the coil. (b)
Bypass factor of the coil (c) sensible heat factor of the coil (d) total heat
removed per kg of air (e) mass of vapour condensed.
6
Air enters a chamber at 10°C DBT & 5° C thermodynamic WBT at a rate of 100
cubic metre per min (cmm). The barometer reads a pr. of 1. 01325 bar.
While passing thro the chamber, the air absorbs sensible heat at the rote of
40 kw & picks up 45 kg/hr of saturated steam at 105°C. Determine the dry
& wet bulb temps. of the air leaving the chamber.
7
An air stream of 7000 m³/hr at a DBT of 27°C & humidity ratio of 0.010 kg / kg
of dry air is adiabatically mixed with 20,000 m³/hr of air having 35°C DBT
& 55% RH. Find DBT & WBT of the resulting mixture.
8
300 m³/min of moist air enters a refrigeration coil at 35°C DBT & 50% RH. The
ADP of the coil is 10°c ( the bypass factor is 0.15. Determine (a) the outlet
stock of moist air & (b) the cooling capacity of coil in TR.
9
500 m³/min of fresh air at 30° DBT & 50% RH is adiabatically mixed with 1000
m³/min of recirculated air at 22°C DBT & 10°C DPT. Calculate the enthalpy,
sp. volume, humidity ratio & final DBT of the mixture.
10
In a cooling application, moist air enters a refrigeration coil at the rate of 100
kg of air at 35°C DBT and 50% RH. The ADP of the coil is 5°C & bypass factor
is 0.15. Determine (a) the outlet state of moist air (b) the cooling capacity of
coil in TR.
11
Room air at 20°C DBT & 60% RH is mixed with outdoor air at 40°C DBT & 40%
RH in the ratio 4:1 The mixture is passed throl a Cooling coil whose temp is
maintained at 9°C & whose bypass factor is 0.25. Find the following (a)
condition of air entering the coil (b) condition of air leaving the coil (c) If
250 m³/min of air is supplied to the room, find the refrigeration load on the
cooling coil.
12
A sling psychrometer reads 40°C DBT 28°C WBT, when atm pr. is 75 cm of Hg.
Calculate the following. (a) sp. humidity (b) Relative humidity (c) Dew point
temp (d) enthalpy (e) vapour density.
Experiment 06:
Comfort
1
Describe humab comfort.
2
Explain comfort. chart.
3
Describe the thermoregulatory system of humans.
d) In a 100% re-circulation system, the coil ADP is less than room ADP
2. State which of the following statements are TRUE?
b) In a system with outdoor air for ventilation, the load on building is greater
than the load on
coil
c) In a system with outdoor air for ventilation, the load on building is less than the
load on coil
d) In a system with outdoor air for ventilation, the Coil ADP is less than room ADP
3. Which of the following statements are TRUE?
a) Systems with reheat are used when the Room Sensible Heat Factor is low
b) Systems with reheat are used when the Room Sensible Heat Factor is high
c) When reheat coils are used, the required coil ADP can be increased
d) When reheat coils are used, the required supply airflow rate increase
4. Which of the following statements are TRUE?
a) b)
c) d)
6. The conditioned air supplied to the room must have the capacity to take up
1
Describe SHF, RHSF, GSHF
2
Explain bypass factor.
3
Write different loads acting on air conditioning systems.
IV. Enthalpy.
Determine
a. RSHF
9 In an air- conditioning system, air at 28°C & 1.013 bar is drawn into
a building with a percentage saturation of 50%. It is required to
maintain the air in the building at 20°c & 40% RH. The total heat
gains to the room are 15 kw, & latent heat gains are 3 kw.
Calculate the temp to which the inlet air should be coded at the
cooling coil (assume a coil bypass factor of 0.2), the refrigerating
load & the heat input to the heater. The system requires 5 m³ of
fresh air per second & no air is recirculated.
10 Air initially at g°c dbt & -3°c dpt is heated to 17°C. It then flows
through an air washer in which Water continuously recirculates
without being heated or cooled. After leaving the air washer the
air is reheated to final conde of 19°c dbt & 12°C WBT, Find (a)
wbt, & dbt for air leaving the water (b) healing req in each coil
per kg of dry air (c) by pass factor of air washer, & (d) efficiency
of the air washer.
12
One stream of air at 55 m³/min at 15°C & 60% flows into another
stream of an 35m³/min at 25°C & 70%. Calculate for the mixture
(a) dbt (b) wbt (c)Q & (d) w.
14
In a bathroom, the water tap is accidentally left open & the room is
flooded with water. The air inside the room becomes saturated with
water vapour. It the air is at 40°c & I atm pr. determine (a) the
partial pr. of Water vapour in air (b) the humidity ratio of the air
inside the room & (c) dpt of air-water vapour mixture.
1
An auditorium seats 1000 people. The space design conditions are
25°C and 50% RH. & outdoor design conditions 35°C DBT & 24°C
WBT. What is the cooling load due to ventilation? Assume
ventilation air per person to be 0.424 cmm
2
A hair salon shop has a sensible cooling load of 16 kW and latent
cooling load of 6.5 kW. The room conditions are to be maintained
at 25°C DBT 50% RH. If 56 cmm of supply air is furnished,
determine the required supply air DBT & WBT.
3
A Shop has a sensible Cooling load of 13.15 kw latent cooling load
of 4.4 kw. The shop is maintained at 25°C DBT 45% RH. Draw the
RSHF Line.
4
In an auditorium which is to be maintained at a temp not
exceeding 24°C & a RH not more than 60%, a sensible heat load of
132kw & 84 kg/hr of moisture have to be removed. Air is supplied
to the auditorium at 15°C. (a) how many kg of air per hour, must
be supplied (b) what is DPT of supply air & what is its RH?
5
(a) 28.5 cmm of 200m air at 25.5° (DBT 50% RH is mixed with
28.5 cmm of outside air at 38°C DBT and 27°C WBT. find the
ventilation load & the condition of air after mixing. (b)The above
mixed air is panned over a refrigerating coil. If the wet bulb temp
of air after equipment is 14.5 °C, determine the heat removed by
the equipment.
6
Room cond²: 26°C DBT, 19°C WAT Outside cand: 35°C DBT, 27°C
WBT. Room heat gains. Sensible heat. 11.1 kw, latent heat 3.9 kw.
The conditioned air supplied to the 200m is 50 cmm & 25% fresh
air & 75% recirculated zoom air. Find (a) DBT WBT of supply air
(b) DBT LWBT of mixed fresh and recirculated air before the
cooling coil (c) ADP & bypass factor of the coil. (d) the
refrigeration load on the cooling coil and the moisture removed by
the coil.
7
500 kg of air is supplied per min to an auditorium maintained at
21°C & 40%. R.M. The outside air at 5°C DBT & 60% RH is first
passed over heating coils and heated until its WBT is equal to the
room WBT. It is then passed through' an adiabatic Saturator & is
finally heated to 45°C before being supplied to room. Find: (a) the
heat added to both the heating coils. (b) the mass of water
evaporated in the air washer.
8
An air-conditioned space is maintained at 25°C DBT & 50%. RH.
The outside conditions are 40°C DBT & 25°C WBT The space has a
sensible heat gain of 24.5 kw. Conditioned air is supplied to the
space as saturated air at 10°c. The equipment consists of an air
washer. The air entering the air washer comprises 25%. outside
air. Calculate: (a) Volume flow rate of air supplied to space. (b)
latent heat gain of space. (c) cooling load of air Washer.
9
Data! Room conditions 26.5°C DBT & 50% RH. Room Sensible heat
gain = 26.3 kw, RSHF = 0.82. Find (a) the room latent heat gain (6)
ADP (c) cmm of air if it is supplied to the room at ADP (d) cmm &
sp. humidity of air if it is supplied to the room at 17°C.
10
A hall is to be maintained at 24°C DBT & 60% RH under the
following conditions. Outdoor cond: 38°c DBT, 28°c WBT. Room
SH load 46.4kw, Room LH load = 11.6 kw. Quantity of infiltration =
1200 m³/hr, ADP = 10°c, Quantity of recirculated air = 60%.. If the
quantity of recirculated air is mixed with conditioned air after the
coding load, find the following SH gain from other sources air
infiltration air = 15w21. If 25%. of fresh air & 75%. recirculated
air is mixed and passed wi thro' the conditioner coil, find the
following (a) condition of air leaving the coil (b) cond of air
entering the hall (c) the mass flow rate of air entering the cooler
(d) the mass flow rate of total are passing thro the hall (e) bypass
factor (f) the refrigeration load on the cooling coil in TR.
11
An are conditioning system is to be designed for a restaurant with
the following data: Outside design cond² = 40°C OBT, 28°C WBT
Inside design cond² = 25°C DBT, 50% RH, Solar heat goi's third
walls, roof, floor = 5.87 kw Solar heat gain through glass = 5.52kw,
Occupants = 25. SH gain per person = 58W, Lt gain per person =
60w Internal lighting load = 15 lamps of room & 10 tubes of 80w.
cond of supply ate to the room (c) the amount of total air required
in m³/hr (d) the capacity of the conditioning plant.”
1. An air conditioning System is designed for industrial process for hot & wet
summer conditions:
Assuming 40% fresh air and 60% re-circulated air passing through the
evaporator coil and the bypass factor of 0.15, find the dew point temperature of
the coil.
3. A building has the following calculated cooling loads
RSH=310 KW,RLH=100KW
Outdoor air is at 280C and 50% RH. and 10% of air by mass is supplied to the
building is out door air.
If the air supplied to the space is not to be at a temperature lower that 180C Find,
3. Bypass factor.
Experiment:08
Air distribution system
The metabolic rate depends mainly on the activity level of the human being
The metabolic rate depends mainly on the sex of the human being
To maintain thermal comfort, the DBT of air should be increased as its moisture
content increases
To maintain thermal comfort, the DBT of air should be decreased as air velocity
increases
a) Effective temperature combines the affects of dry bulb temperature and air
velocity into a single index
b)Effective temperature combines the affects of dry bulb temperature and wet
bulb temperature into a single index
c) Mean radiant temperature combines the affects of dry bulb temperature and
surrounding surface temperature into a single index
d) Operative temperature combines the affects of dry bulb temperature and mean
radiant temperature into a single index
5 Which of the following statements are TRUE?
a) In winter air conditioning systems, heated and dehumidified air is
supplied to the
conditioned space
b) In winter air conditioning systems, heated and humidified air is supplied
to the conditioned space
c) A pre-heater is recommended in winter air conditioning systems to
improve overall efficiency of the system
d) A pre-heater is recommended in winter air conditioning systems to
prevent freezing of water in the humidifier and for better control
a) Under ideal conditions, the static pressure through an air conditioning duct
remains constant
b) Under ideal conditions, the total pressure through an air conditioning duct
remains constant
b) In a duct of uniform cross section, the static pressure decreases along length
c) In a duct of uniform cross section, the total pressure decreases along length
a) For a given flow rate, the pressure drop is less compared to a circular duct
b) For a given pressure drop, it requires less material compared to a circular duct
2
Explain Duct design method, Equal friction method, Velocity reduction
method, Static regain method.
3
Types of fans used in Air conditioner
4
Short note on Grills, Register, Diffuser.
a.Aspect Ratio
b. Equivalent Diameter
c. Dynamic Pressure
d. Draft
9 Describe (write a note on) the thermal exchange of human body &
Environment.
10 Discuss the factors affecting thermal balance between human body &
environments
.
1 Explain with necessary conditions comfort chart.
4 What do you understand by cooling load and heating load ? Explain the
7 What are the different methods of duct design ? Explain velocity reduction
method in details.
8 What are the different factors considered in load estimation sheet for
comfort application?
9 What is effective temperature? Explain factors affecting it.
10 Describe the different methods of air conditioning duct design. Why are
dampers required in some systems ?
EXTRA
1. Show the state of atm air on psychrometric Chart and read all those properties which
can be read from this Chart when air is at (a) t=32°C & Q = 0.6 (b) t =32°c & dew pt
temp = 10°C 8 (c) t=32°c & h= 50 kr/kg. Also Compare these values with those obtained
from mathematical relations. Assume barometric pr. Is std atm pr, 1.01325 bar.
2. Moist air enters a refrigeration coil at 30°C dbt & 60% RH at the rate of 200 m³/min at
std atm. pr. It leaves the Coil at 25°C. Calculate the tons of refrigeration required and the
final Q
3. Air initially at g°c dbt & -3°c dpt is heated to 17°C. It then flows through an air washer in
which Water continuously recirculates without being heated or cooled. After leaving the
air washer the air is reheated to final conde of 19°c dbt & 12°C WBT, Find (a) wbt, & dbt
for air leaving the water (b) healing req in each coil per kg of dry air (c) by pass factor of
air washer, & (d) efficiency of the air washer.
4. A classroom for 60 students is to be air conditioned to 22°c dbt & 55% &, first by
chemical dehumidification, & then cooling it by passing it over a cooling coil. The
outdoor conditions are 32°C dbt & 22°C dpt. The quantity of fresh air read is 0.5
m³/min/student, find (a) dbt of air after dehumidifier (b) capacity of the dehumidifier
(C) ADP of cooling coil, assuming a bypass factor of 0.3 (d) Capacity of the cooling coil.
5. One stream of air at 55 m³/min at 15°C & 60% flows into another stream of an
35m³/min at 25°C & 70%. Calculate for the mixture (a) dbt (b) wbt (c)Q & (d) w.
7. In a bathroom, the water tap is accidentally left open & the room is flooded with water.
The air inside the room becomes saturated with water vapour. It the air is at 40°c & I
atm pr. determine (a) the partial pr. of Water vapour in air (b) the humidity ratio of the
air inside the room & (c) dpt of air-water vapour mixture.
8. In an air- conditioning system, air at 28°C & 1.013 bar is drawn into a building with a
percentage saturation of 50%. It is required to maintain the air in the building at 20°c &
40% RH. The total heat gains to the room are 15 kw, & latent heat gains are 3 kw.
Calculate the temp to which the inlet air should be coded at the cooling coil (assume a
coil bypass factor of 0.2), the refrigerating load & the heat input to the heater. The
system requires 5 m³ of fresh air per second & no air is recirculated
9. An auditorium of dimension 20x40x6 m has air with RH 60%. at l atm and 30°C.
Determine (a) the partial pr. of water vapour in the air (b) the sp. humidity of air. (e) the
mars of water vapour in the auditorium &(d) the dpt. the Saturation pr. of water at 20°C,
25°C 30°c are 2.339, 3.169, 4.246 kpa respectively
10. An air conditioner delivers 2 m³ of air at 5%, which is completely saturated with water
vapour. If this air is mixed with 5m³ of air at 35°C & 40% RH in a room, determine the
temp, sp. humidity and RH of air after mixing.
Absorber
Generator
Pump
Higher COPs
Absorption of heat
Release of heat
No thermal effects
Reduction in volume
5 Presence of water vapour in the refrigerant circuit of a NH3-H2O system
c) Offer less noise and vibration d) Are compact for large capacities
9 In aqua-ammonia and Lithium-bromide water absorption refrigeration systems,
the refrigerants are respectively
Aqua
Ammonia
Air
none
1 How many refrigerants are used in Two stage Cascade refrigeration systems ?
one
two
three
four
1 Which is the three fluid vapour absorption system ?
Aqua-Ammonia
Li Br-Aqua
Electrolux
Kelvinator
05. PSYCHROMETRY
a) The maximum amount of moisture air can hold depends upon its temperature
and barometric pressure
b) Perfect gas model can be applied to air-water mixtures when the total pressure
is high
b) All specific psychrometric properties of moist air are based on unit mass of
water vapour
c) All specific psychrometric properties of moist air are based on unit mass of dry
air
d) All specific psychrometric properties of moist air are based on unit mass of
moist air
3. Which of the following statements are TRUE?
c) Under no circumstances, dry bulb and wet bulb temperatures are equal
d) Wet bulb temperature is always lower than dry bulb temperature, but higher
than dew point temperature
4. Which of the following statements are TRUE?
a) During sensible cooling of air, both dry bulb and wet bulb temperatures
decrease
b) During sensible cooling of air, dry bulb temperature decreases but wet bulb
temperature remains constant
c) During sensible cooling of air, dry and wet bulb temperatures decrease but
dew point temperature remains constant
d) During sensible cooling of air, dry bulb, wet bulb and dew point temperatures
decrease
5. Which of the following statements are TRUE?
d) Sensible heat factor is low for air conditioning plants operating in humid
climates
6. Which of the following statements are TRUE?
a) As the by-pass factor (BPF) of the cooling coil increases, temperature difference
between air at the outlet of the coil and coil ADP decreases
b) The BPF of the coil increases as the velocity of air through the coil increases
d) The BPF of the coil decreases as the number of rows in the flow direction
increase
7. Which of the following statements are TRUE?
During cooling and humidification process, the enthalpy of air remains constant
During cooling and humidification process, the enthalpy of air may increase,
decrease or remain constant depending upon the temperature of the wet surface
8. Which of the following statements are TRUE?
a) Evaporative cooling systems are attractive for hot and humid climates
b) Evaporative cooling systems are attractive for hot and dry climates
conditioned space
a) When humidification is done using an air washer, the temperature of air drops
during humidification
b)When humidification is done using an air washer, the temperature of air rises
during humidification
c)When humidification is carried out by adding dry steam, the temperature of air
remains close to the WBT of entering air
d)When humidification is carried out by adding dry steam, the temperature of air
remains close to the DBT of entering air
1 The air flow rate in air-conditioning is controlled by
register
dampers
grills
none of above
1 The temperature at which moist air starts condensing is known as
sensible heating
humidification
dehumidification
none
1 The wet bulb temperature during sensible heating of air
remains constant
increases
decreases
Can’t Predict
1 The difference between dry bulb temperature and wet bulb temperature, is called
dry bulb depression
degree of saturation
2 In laboratory test a psychrometer recorded dry bulb temperature as 350C & Wet
bulb temperature 280C. Calculate-
a. Vapour Pressure
b. R.H.
c. Degree of Saturation
d. DPT
3 A sample of moist air has DBT of 430C & WBT of 290C.Calculate the following
making use of psychrometric Chart.
1. Partial Pressure of water vapour.
2. Specific Humidity.
3. Relative Humidity
4. Dew Point Temperature
5. Humid Specific Heat
6. Enthalpy.
4 A sling psychrometer records 35°C Dry Bulb Temperature (DBT) and
i) specific humidity,
iv) enthalpy
5 Atmospheric air at 40°C dry bulb temperature and 18°C weight bulb temperature
is flowing at the rate of 100 m3/min through the space. Water at 18°C is injected
into the air stream at the rate of 48 kg/hr. Determine the specific humidity and
enthalpy of the leaving air. Also determine the dry bulb, weight bulb temperature
and relative humidity of the leaving air.
6 A sample of air has DBT & WBT of 350 C & 250 C Respectively. The barometric
pressure is 760 mm of Hg. Determine-
b. Specific Humidity
c.DPT
d. Enthalpy.
7 A sample of moist air has DBT of 430C & WBT of 290C.Calculate the following
without making use of psychrometric Chart.
1. Partial Pressure of water vapour.
2. Specific Humidity.
3. Relative Humidity
4. Dew Point Temperature
5. Humid Specific Heat
6. Enthalpy.
8 A sample of air has DBT & WBT of 350 C & 250 C Respectively. The barometric
pressure is 760 mm of Hg.
Determine-
b. Specific Humidity
c.DPT
d. Enthalpy.
On a particular day, a sling psychrometer reads 30°C os dbt & 20°c as wbt.
Determine the humidity ratio.
9 On a particular day, the atmospheric air was found to have DBT of 30°C and WBT
of 18°C. The barometric pressure was observed to be 756 mm Hg.
Obtain following :
i) Relative humidity
iii) DPT
i) Bypass factor
ii) ADP
iii) SHF.
Short answer questions
1 For DBT of 38°C and RH of 70%, Calculate the following for air if barometric
pressure is 1 bar.
i. Specific Humidity
iii. DPT
Data :
f f g f f g
g g
30 0.04 125. 2430. 2556 0.4 8.016 8.45
25 8 1 .3 37 3
31 0.04 130. 2428. 2558 0.4 7.982 8.43
50 0 1 .1 51 3
32 0.04 134. 2425. 2559 0.4 7.948 8.41
76 2 7 .9 64 3
33 0.05 138. 2423. 2561 0.4 7.915 8.39
03 3 4 .7 78 3
38 0.06 159. 2411. 2570 0.5 7.749 8.29
63 2 5 .7 46 5
Moist air enters a refrigeration coil at 30°C dbt & 60% RH at the rate of 200
m³/min at std atm. pr. It leaves the Coil at 25°C. Calculate the tons of
refrigeration required and the final Q
1 Write a short note on-Bypass factor of the cooling coil.
1 Atmospheric air at 30°C DBT and 75% RH enters a cooling coil at the rate of 200
CMM. The coil dew point temperature is 14°C and bypass factor of coil is 0.1. Find :
1) Vapour pressure
2) Sp. Humidity
3) Relative Humidity
4) Vapour density.
1 Define Following terms-
a. DBT
b. WBT
c. Specific Humidity.
d. DPT
1 Define the following terms,
1) Bypass factor 2)ADP
3) Relative Humidity 4)Thermodynamic wet bulb temp.
1 Define the following terms :
I. Degree of saturation
a) Lower dry bulb temperatures and higher moisture content are recommended
for winter
b) Lower dry bulb temperatures and lower moisture content are recommended
for winter
c) Lower dry bulb temperatures and higher moisture content are recommended
for summer
d) Higher dry bulb temperatures and higher moisture content are recommended
for summer
1 State which of the following statements are TRUE?
a) The air conditioning duct should have high aspect ratio for good performance
b) If the air conditioning duct is diverging, then the angle of divergence should be
as small as possible to reduce pressure loss
c) To minimize noise and vibration, air should flow with a low velocity
a) High air velocity in ducts results in lower initial costs but higher operating
costs
If not done properly, the velocity method gives rise to large sized ducts
c) The effective draft temperature depends on dry bulb temperature and relative
humidity of air
d) The effective draft temperature depends on dry bulb temperature and velocity
of air
1
1
11.