BHMY FlowMax IOM 19584F 0923 English
BHMY FlowMax IOM 19584F 0923 English
BHMY FlowMax IOM 19584F 0923 English
THE RIGHTS, OBLIGATIONS AND LIABILITIES OF BAKER HUGHES AND THE CUSTOMER/
OPERATOR ARE STRICTLY LIMITED TO THOSE EXPRESSLY PROVIDED IN THE CONTRACT
RELATING TO THE SUPPLY OF THE EQUIPMENT. NO ADDITIONAL REPRESENTATIONS OR
WARRANTIES BY BAKER HUGHES REGARDING THE EQUIPMENT OR ITS USE ARE GIVEN
OR IMPLIED BY THE ISSUE OF THESE INSTRUCTIONS.
ii | Baker Hughes Copyright 2023 Baker Hughes Company. All rights reserved.
Table Of Contents
Product Description...................................................................................................................1
Principles of Operation..............................................................................................................2
Nameplate Information...............................................................................................................3
Regulator Markings....................................................................................................................3
Hydrostatic Testing....................................................................................................................4
Installation...................................................................................................................................4
Piping Schematics.....................................................................................................................5
Start-up and Operation..............................................................................................................12
Maintenance ...............................................................................................................................15
Bolt Torque Specifications........................................................................................................26
Troubleshooting.........................................................................................................................27
Copyright 2023 Baker Hughes Company. All rights reserved. Mooney FlowMax Regulators Instruction Manual | 1
Specifications US units Metric units Principle of Operation
Sizes 2,3,4, and 6 inch DN 50, DN 80, DN
100, DN 150
(Refer to Figure 1)
When the downstream pressure is greater than the set point of
Body Style Single Port Single Port
the pilot, the pilot is closed, resulting in equal pressure above
End Connections 150 CL FF, 150 CL Contact Factory and below the main diaphragm. With a balancing diaphragm
RF,Flanged NPT area slightly larger than the seat area, the resulting closing force,
(2” Only) along with the force of the main spring, forces the plug against
Temperature -20°F to 150°F -29°C to 66°C the seat.
Working -40°F to 175°F -40°C to 80°C With an increase in demand, the outlet pressure will begin to
Emergency drop and decrease the pressure above the main diaphragm. The
Maximum 250 psi 17 bar drop of the outlet pressure below the pilot set point will cause the
Operating pilot to open.
Differential As the pilot opens, pressure increases underneath the main
Maximum Casing 250 psi 17 bar diaphragm faster than pressure can bleed through the internal
Pressure restrictor. The imbalance in pressure on the main diaphragm
overcomes the spring force and the additional closing force from
Minimum 3 psi 0.21 bar
the balancing diaphragm, causing the plug to rise off the seat
Differential(Fully and satisfy the flow demand.
Open)
Once the flow demand is satisfied and the downstream pressure
Outlet Series 20L: 5 in 0.01 - 0.55 bar
begins to increase, the pressure above the main diaphragm and
PressureRange w.c. to 8 psi 0..21 - 17 bar in the pilot sense cavity rises. This causes the pilot to close. The
Series 20: 3 - 248 pressure below the main diaphragm bleeds through the internal
psi restrictor until pressure equalizes above and below the main
Maximum Inlet 250 psi 17 bar diaphragm. The forces of the main spring and the oversized
Pressure balancing diaphragm then close the plug on the seat.
Pilot Supply One 1/4” - 18 NPT One 1/4” - 18 NPT
Body Tap
Sense Line Tap Two 1/2” - 14 NPT Two 1/2” - 14 NPT
Table 2 - Specifications
Balancing Diaphragm
Pilot Sense Regulator Sense Line
Figure 1
2 | Baker Hughes Copyright 2023 Baker Hughes Company. All rights reserved.
Nameplate Information Item Definition
FlowMax Trademarked name
S/N Serial number assigned to regulator
FM # FlowMax product identification
Size/End Conn Line size of body and type of end
connection
Max Inlet/Outlet Maximum inlet or outlet pressure
Pressure psig (bar)
Cap % Percent capacity of maximum for the
regulator
Mfg. Date Date of manufacture
Figure 2 - Nameplate Min. Differential Minimum differential required to fully
open regulator
Regulator Markings Max
Temperature
Maximum operating temperature in
degrees Fahrenheit
Loading Port
Inlet
Inlet Port
Sense Ports
1. American National Standards Institute (ANSI) pressure class rating of the regulator.
2. Line size of body.
3. ANSI pressure class rating of the flange.
4. Indication that the regulator has been hydrostatically tested according to code requirements.
5. The Serial Number is stamped on the spring case, spacer, and Body.
6. The Nameplate location.
Copyright 2023 Baker Hughes Company. All rights reserved. Mooney FlowMax Regulators Instruction Manual | 3
Hydrostatic Testing Installation
Installation and testing of the FlowMax Regultor Personal injury, equipment damage, or leakage due to
should be made by trained, qualified personnel explosion of accumulated gas or bursting of pressure
familiar with high-pressure piping and pilot-operated containing parts, may result if this regulator is over-
regulators. pressured, or is installed where service conditions
could exceed the limits given in the specification of
this manual, or on the nameplate, or where conditions
All FlowMax regulators are hydrostatically tested at the factory
exceed any ratings of the adjacent piping or piping
prior to shipment according to ISA-S75.19-1989 and MSS-SP-61
connections. Verify the limitations of both regulator
standards. If it is necessary to retest the Regulator body, follow
and pilot to ensure neither device is overpressured.
the procedures listed below.
To reduce the chances of such injury or damage,
Note: This Procedure applies to the regulator body only. If provide pressure relieving or pressure limiting de-
actuator retesting is required, contact the factory for proper vices (as required by the U.S. code of Federal Regula-
procedures. tions, by the National Fire Codes of the National Fire
1. Disconnect and remove the pilot inlet and actuator sense Protection Association, or by other applicable codes),
control line(s). to prevent service conditions from exceeding those
limits. Additionally, physical damage to the regulator,
2. Remove the body-to-actuator bolts and remove the actuator pilot, or tubing can cause personal injury and/or prop-
and pilot. erty damage due to explosion of accumulated gas. To
reduce the chances of such injury and damage, install
the regulator in a safe location.
4 | Baker Hughes Copyright 2023 Baker Hughes Company. All rights reserved.
4. langed End Regulators: Use suitable line gaskets and good
F
bolting practices with flanged bodies. Incremental tightening Piping Schematics
of the line bolts in a crisscross pattern is recommended. The following piping schematics are provided:
Note: Prior to commissioning, re-tighten actuator 1. Single Regulator with Single Pilot. Page 6
housing cap screws as they may become loose during
2. Standby Monitor set with differential pressure greater than
transit. See Page 26 for torque values.
10 psid (0.69 bar)(Monitor located downstream). Page 7
5. Orientation: The FlowMax regulator may be installed
3. Standby Monitor set with differential pressure less than 10
in any position – the best position being the one that
psid (0.69 bar)(Monitor located downstream). Page 8
provides easiest access for pilot adjustment and general
maintenance. 4. Standby Monitor set with differential pressure greater than
10 psid (0.69 bar)(Monitor located upstream). Page 9
6. Control Lines: Control sense lines should be run from the
actuator on the FlowMax regulator to a point 8 to 10 pipe 5. Standby Monitor set with differential pressure less than 10
diameters downstream from the regulator (refer to piping psid (0.69 bar)(Monitor located upstream). Page 10
schematics). Use Table 3 as a guide for the ideal tubing size 6. Working Monitor set. Page 11
to use. Reduce as necessary to connect the actuator.
All drawings show installations with the Series 20 Flowgrid pilot.
Outlet Pressure Consult factory for installation schematics of other manufacturer’s
pilot on the FlowMax regulator.
Pilot Less than 2 to 5 psi Greater than
Regulator 2 psi (0.14 (0.14 - 0.35 5 psi (0.35
with: bar) bar) bar)
Static Sense
1/2” Pipe
Line 1/2” Tubing 3/8” Tubing
minimum
(No Flow)1
Sense Line 3/4” to 1”
1/2” Pipe 1/2” Tubing
with Flow2 Pipe
1
The Flowgrid Series 20 Pilot has a static sense line.
2
The Sense line of the FlowMax actuator has flow.
Copyright 2023 Baker Hughes Company. All rights reserved. Mooney FlowMax Regulators Instruction Manual | 5
Piping Schematics (cont’d)
1. S
ingle Regulator/Single Pilot
(Pressure Reducing Regulator)
1. Pilot supply tubing from filter OUTLET connection to the Series 20 pilot INLET port.
2. Type 30 filter mounted in inlet piping.
3. OUTLET port of Series 20 pilot connected to Loading connection on the actuator housing of the FlowMax regulator
4. Sense line connecting the SENSE Port on the Series 20 pilot to the sense port on the FlowMax actuator.
(Refer to Table 3 on Page 5 for sense piping recommendations)
5. Sense line connecting the FlowMax regulator to the downstream piping.
6. Series 20 pilot with pilot cartridge in PRV mode. Pilot LOADING port is plugged.
6 | Baker Hughes Copyright 2023 Baker Hughes Company. All rights reserved.
Piping Schematics (cont’d)
2. S
tandby Monitor with Differential Pressure Greater than 10 psid (0.69 bar)
(Monitor located downstream)
Operating
Regulator
Monitor
Regulator
1. Pilot supply tubing from filter OUTLET to Series 20 pilot INLET port.
2. Type 30 Filter mounted in inlet piping.
3. OUTLET Port of Series 20 pilot connected to the loading connection on the actuator housing of the FlowMax regulator.
4. Sense line connecting the SENSE port on the Series 20 pilot to the sense port on the FlowMax actuator.
(Refer to Table 3 on Page 5 for sense piping recommendations)
5. Sense line connecting the FlowMax regulator to the downstream piping.
6. Series 20 pilot with pilot cartridge in PRV mode. Pilot LOADING port is plugged.
7. Pilot supply tubing from filter OUTLET to Series 20 pilot INLET port.
8. Type 30 filter mounted in inlet piping.
9. OUTLET port of Series 20 pilot connected to the Loading connection on the actuator housing of the FlowMax regulator.
(Same as #3, See Typical Top View)
10. Sense line connecting the SENSE port on the Series 20 pilot to the sense port on the FlowMax actuator.
11. Sense line connecting the FlowMax actuator to the downstream piping.
12. Series 20 pilot with pilot cartridge in PRV mode. Pilot LOADING port is plugged.
Copyright 2023 Baker Hughes Company. All rights reserved. Mooney FlowMax Regulators Instruction Manual | 7
Piping Schematics (cont’d)
3. S
tandby Monitor with Differential Pressure Less than 10 psid (0.69 bar)
(Monitor located downstream)
VentValve
SenseValve
Operating
Regulator
Monitor Regulator
1. Pilot supply tubing from filter OUTLET connection to Series 20 pilot INLET port.
2. Type 30 filter mounted in inlet piping.
3. OUTLET port of Series 20 pilot connected to the loading connection on the actuator housing of the FlowMax regulator.
4. Sense line connecting the SENSE port on the Series 20 pilot to the sense port on the FlowMax actuator.
(Refer to Table 3 on Page 5 for sense piping recommendations)
5. Sense line connecting the FlowMax regulator to the downstream piping.
6. Series 20 pilot with pilot cartridge in PRV mode. Pilot LOADING port is plugged.
7. Pilot supply tubing from filter OUTLET connection on the upstream piping connected to Series 20 pilot INLET port.
8. Type 30 filter mounted in the upstream inlet piping.
9. OUTLET port of Series 20 pilot connected to loading connection on the actuator housing of the FlowMax regulator.
(Same as #3, See typical top view)
10. Sense line connecting SENSE port on Series 20 pilot to sense port on the FlowMax actuator.
11. Sense line connecting the FlowMax actuator to the downstream piping.
12. Series 20 pilot with pilot cartridge in PRV mode. Pilot LOADING port is plugged.
8 | Baker Hughes Copyright 2023 Baker Hughes Company. All rights reserved.
Piping Schematics (cont’d)
4. S
tandby Monitor with Differential Pressure Greater than 10 psid (0.69 bar)
(Monitor located upstream)
Monitor
Regulator
Operating
Regulator
1. Pilot supply tubing from filter OUTLET connection to Series 20 pilot INLET port.
2. Type 30 filter mounted in inlet piping.
3. OUTLET port of Series 20 pilot connected to the Loading connection on the actuator housing of the FlowMax regulator.
4. Sense line connecting the SENSE port on the Series 20 pilot to downstream of the operating regulator.
(Refer to Table 3 on Page 5 for sense piping recommendations)
5. Sense line connecting the FlowMax regulator to the interstage piping.
6. Series 20 pilot with pilot cartridge in PRV mode. Pilot LOADING port is plugged.
7. Pilot supply tubing from filter OUTLET connection to Series 20 Pilot INLET port.
8. Type 30 filter mounted in inlet piping.
9. OUTLET port of Series 20 pilot connected to Loading connection on the actuator housing of the FlowMax regulator.
(Same as #3, See Typical Top View)
10. Sense line connecting SENSE port on Series 20 pilot to sense port on the FlowMax actuator.
11. Sense line connecting the FlowMax actuator to the downstream piping.
12. Series 20 pilot with pilot cartridge in PRV mode. Pilot LOADING port is plugged.
Copyright 2023 Baker Hughes Company. All rights reserved. Mooney FlowMax Regulators Instruction Manual | 9
Piping Schematics (cont’d)
5. S
tandby Monitor with Differential Pressure Less than 10 psid (0.69 bar)
(Monitor located upstream)
Monitor
Regulator
Operating
Regulator
1. Pilot supply tubing from filter OUTLET connection to Series 20 pilot INLET port.
2. Type 30 filter mounted in inlet piping.
3. OUTLET port of Series 20 pilot connected to the loading connection on the actuator housing of the FlowMax regulator.
4. Sense line connecting the Pilot SENSE port to downstream of the operating regulator.
(Refer to Table 3 on Page 5 for sense piping recommendations)
5. Sense line connecting the FlowMax regulator to the interstage piping.
6. Series 20 pilot with pilot cartridge in PRV mode. Pilot LOADING port is plugged.
7. Pilot supply tubing from filter OUTLET connection on the upstream piping to pilot INLET port connection.
8. Type 30 filter mounted in inlet piping.
9. OUTLET port of Series 20 pilot connected to loading connection on the actuator housing of the FlowMax regulator.
(Same as #3, See Typical Top View)
10. Sense line connecting SENSE port on Series 20 pilot to sense port on the FlowMax actuator.
11. Sense line connecting the FlowMax actuator to the downstream piping.
12. Series 20 pilot with pilot cartridge in PRV mode. Pilot LOADING port is plugged.
10 | Baker Hughes Copyright 2023 Baker Hughes Company. All rights reserved.
Piping Schematics (cont’d)
6. Working Monitor Set
1. Pilot supply tubing from filter OUTLET connection to Series 20 pilot (#1) LOADING port.
2. Pilot #1 OUTLET port connected to pilot #2 INLET port.
3. Pilot #2 OUTLET port connected to the loading connection on the actuator housing of the FlowMax regulator.
4. Sense line connecting the 1st stage FlowMax regulator to the interstage piping.
(Refer to Table 3 on Page 5 for sense piping recommendations)
5. Sense line connecting SENSE port on Series 20 pilot (#2) to the sense port on the FlowMax actuator.
6. INLET port on the monitor Series 20 pilot (#1) is plugged.*
7. LOADING port on the Series 20 pilot (#2) is plugged.*
8. Sense line connecting the SENSE port on the monitor pilot (#1) to the downstream piping.
9. Type 30 filter mounted in the inlet piping.
10. Pilot supply tubing from filter OUTLET connection to Series 20 pilot (#3) INLET port.
11. LOADING port on the Series 20 pilot (#3) is plugged.
12. Sense line connecting SENSE port on Series 20 pilot (#3) to the sense port on the FlowMax actuator.
13. OUTLET port of Series 20 pilot (#3) connected to the loading connection on the actuator housing of the FlowMax regulator.
14. Sense line connecting the 2nd stage FlowMax regulator to the downstream piping.
Note: The INLET and LOADING ports form a common port on the Series 20 pilot
Copyright 2023 Baker Hughes Company. All rights reserved. Mooney FlowMax Regulators Instruction Manual | 11
Start-up and Operation Standby Monitor
The following procedures are suggested for start up of the
FlowMax regulator equipped with Series 20 pilots. Start up of
(Upstream Operating Regulator
the FlowMax regulator should be made by trained, qualified Configuration)
personnel familiar with high pressure systems and pilot-operated
regulators. This procedure is based on the first regulator being the Operating
regulator and the second regulator being the Monitor regulator.
Note: In this configuration, installation of a shut-off valve
and a vent valve are required in the sense line of the
operating regulator to facilitate testing of the monitor
The instruction manual for the PILOT(S) being used regulator performance. See Pages. 8 and 9.
should be consulted to insure that the installation and
start up instructions for the pilot are followed. Some 1. If necessary, purge any pressure in the station.
pilots can be damaged if not installed and put into 2. Set operating regulator pilot (#1) spring at the MAXIMUM
operation correctly. setting. The sense line shut-off valve should be closed and
the sense line vent valve should be open.
Single Pressure Reducing Regulator 3. Set monitor pilot (#2) spring to the MINIMUM (zero) setting.
1. Back off the pilot adjusting screw to fully remove the spring 4. Slowly open the inlet block valve. Full inlet pressure should
compression. be present at the monitor regulator and the Monitor regulator
should be closed.
2. Slowly open the upstream block valve to pressurize the
FlowMax regulator and pilot system. The FlowMax regulator 5. Open any hand valve(s) in the pilot supply lines on both
should lock up (shut off) with zero pressure downstream. regulators. The sense line shut-off valve should remain
closed and the sense line vent valve should remain open
3. Fully open any hand valve(s) in the control line(s) and the (Refer to page 8).
pilot supply line.
6. Open a vent or downstream block valve.
4. Slightly open a downstream block valve or open a vent in
piping downstream of the FlowMax regulator. 7. Increase the pilot spring setting of the monitor regulator until
the desired monitor override setting is reached. Lock in the
5.
Slowly increase the pilot spring setting until the desired pilot setting.
downstream pressure is achieved.
8. With some flow going through the station, close the vent
6. Slowly close the downstream block valve or vent to check valve on the operating regulator sense line and open the
the FlowMax regulator for lockup (shutoff). shut-off valve on the same line. Start to lower the Pilot setting
7. Slowly open the downstream block valve to allow full flow. of the operating regulator until the desired outlet pressure is
achieved.
ote: When the set point of the operating regulator
N
becomes less than the set point of the monitor regulator,
the interstage pressure will drop from approximately
full inlet pressure to 2-4 psi (0.14-0.28 bar) above the
outlet pressure at low flow rates.
12 | Baker Hughes Copyright 2023 Baker Hughes Company. All rights reserved.
Standby Monitor Working Monitor
1. Purge any pressure in the station.
(Upstream Monitor Regulator
2. Set pilots #1 and #2 to a setting above the desired set points.
Configuration) 3. Set the pilot (#3) at a zero setting.
This procedure is based on the first stage regulator being the
4. Slowly open the inlet block valve to station. The s e c o n d
Monitor regulator and the second stage regulator being the
stage regulator should remain closed as a result of the pilot
Operating regulator.
#3 being set to zero.
1. If necessary, purge any pressure in the station.
5. Fully open any hand valve(s) in the control line(s) and the
2. Set first stage monitor regulator pilot spring at the MAXIMUM pilot supply line.
setting.
6. Open an outlet block valve or vent to allow flow through the
3.
Set second stage operating regulator pilot spring to the station.
MINIMUM (zero) setting.
7. Increase the setting of the second stage regulator, pilot (#3)
4. Slowly open the inlet block valve. Full inlet pressure should to the desired monitor over-ride pressure set point of the
be present at the second stage operating regulator and it station.
should be closed.
8.
Lower the setpoint of the first stage regulator pilot (#2)
5. Fully open any hand valve(s) in the control line(s) and the to the desired interstage pressure setting. The first stage
pilot supply line. regulator should begin to control the interstage pressure at
6. Open a vent or downstream block valve. the setpoint of Pilot #2.
7. Increase the set point of the second stage operating 9. Lower the setpoint of pilot #1 to take control of the system
regulator to the desired monitor over-ride set pressure. (a pressure that will be slightly lower than the final monitor
over-ride pressure).
8. Decrease the pilot spring setting of the first stage monitor
regulator until it take control at a set point just below the final 10. Raise the setpoint of pilot #3 to a maximum setting.
desired monitor over-ride set pressure. 11. Raise the setpoint of pilot #1 to maintain the exact monitor
9.
Increase the second stage operating regulator to the over-ride pressure set point.
maximum pilot setting. 12. Lower pilot #3 to the desired station outlet pressure.
10. Increase the first stage monitor regulator set pressure to the
final desired monitor over-ride set point.
11. Decrease the pilot spring setting of second stage operating
regulator until the final set point is achieved.
Note: When the set point of the operating regulator
becomes less than the set point of the monitor regulator,
the interstage pressure will rise to 2-4 psi (0.14-0.28 bar)
below the full inlet pressure (at low flows).
Copyright 2023 Baker Hughes Company. All rights reserved. Mooney FlowMax Regulators Instruction Manual | 13
14 | Baker Hughes Copyright 2023 Baker Hughes Company. All rights reserved.
Maintenance 2. Loosen and remove the cap screws securing the actuator
housing and remove the actuator from the body by lifting
straight up. DO NOT PRY.
Seat
Partial Disassembly for Stem/Plug/
Seat Inspection
1. Disconnect actuator control/sense and pilot supply lines to
the actuator.
O-Ring
Copyright 2023 Baker Hughes Company. All rights reserved. Mooney FlowMax Regulators Instruction Manual | 15
6” FlowMax Only Plug Seal
3. There is no body gasket in the 6” design. The cage needs
to be unscrewed for removal. The housing o-ring should be
removed and inspected.
Housing
O-Ring
Stem-
Bushing
16 | Baker Hughes Copyright 2023 Baker Hughes Company. All rights reserved.
Partial Assembly for 6. Ensure that the seat bore in the body is clean and install the
seat o-ring and seat into the bore in the body. Make sure that
Stem/Plug/Seat Inspection the chamfered edge of the seat is resting against the seat
o-ring and that the knife-edge sealing surface is facing up.
Note: Lightly lube o-rings before installation.
1. If the o-rings have been removed, reinstall the bushing
o-ring and the stem o-ring.
2. Screw the stem bushing into the bottom side of the lower
actuator housing until the bushing flange has bottomed on Plug
the housing. Do not over tighten.
3. Install a new o-ring in the internal plug groove. be removed
and inspected.
Seat
O-Ring
Plug
Grove Figure 14 - Proper seat orientation
7. Install the cage onto the seat. The cage should fit snugly
over the raised lip on the seat. Do not damage the seat
Figure 12 - Inspecting the plug o-ring sealing surface when installing the cage.
4. Install the plug onto the tapered end of the stem with the 8. Install the body gasket (2”, 3” & 4” models). The 6” FlowMax
plug seal facing away from the actuator. does not utilizes a body gasket.
5. Screw the stem nut on the bottom of the stem with the rubber
seal toward the plug to lock the plug assembly in place. Use Body
a wrench to hold the stem while tightening the stem nut. Gasket
Copyright 2023 Baker Hughes Company. All rights reserved. Mooney FlowMax Regulators Instruction Manual | 17
Partial Disassembly for Balancing
Diaphragm Inspection
1.
Disconnect control/sense and pilot supply lines to the
actuator.
2. Loosen the spring case cap and remove the main spring.
Housing
O-Ring
6” FlowMax Only
Note: The 6” FlowMax does not utilize a body gasket. There
should be no gap between the actuator and body.
Upper Nut Stem
18 | Baker Hughes Copyright 2023 Baker Hughes Company. All rights reserved.
Partial Assembly for Balancing 4. Install the washer in the piston counter bore and install
the upper stem nut. Use a wrench to hold the stem while
Diaphragm Inspection tightening the upper stem nut.
1. Install the balancing diaphragm onto the balancing
diaphragm retainer. Ensure that the diaphragm flange is Stem Nut
Washer
facing up. Once installed, the top diaphragm flange should
be pushed down flush with the counter bore surface of the
upper actuator housing.
Balancing Piston
Diaphragm
O-Ring
Balancing
Diaphragm
Retainer
Piston Ring
Washer
Copyright 2023 Baker Hughes Company. All rights reserved. Mooney FlowMax Regulators Instruction Manual | 19
5b. 3”, 4” & 6” FlowMax only: Lubricate and install the balancing 9. Lower the actuator assembly onto the regulator body. Use
diaphragm o-ring into the spring case groove. Place the caution not to pinch the housing o-ring during installation.
spring case onto the housing and install cap screws to the 10. Incrementally tighten the body cap screws to specified
proper torque (refer to Table 4, page 26). torque values. Table 4 Page 27.
3” - 6”
Balancing
Diaphragm
O-Ring
Figure 24b - Installing the balancing diaphragm o-ring on
the 3”, 4” & 6” FlowMax Figure 27 - Tightening the body cap screws
6. Insert the main spring into the piston counterbore and install
the spring case cap. Note that 6” FlowMax has an additional
2”, 3” & 4” FlowMax Only
washer between the spring and spring case cap. Note: The gap between the actuator and body shouldbe
approx. 1/16 in (1.59 mm).
6” FlowMax Only
Note: The 6” FlowMax does not utilize a body gasket. There
should be no gap between the actuator and body.
11.
Reconnect control/sense and pilot supply lines to the
actuator.
Housing
O-Ring
20 | Baker Hughes Copyright 2023 Baker Hughes Company. All rights reserved.
3. Remove the spring case cap and remove the main spring.
4. Remove the spring case capscrews and remove the spring
case.
5. Remove the upper stem nut and remove the piston from the
stem. Remove the balancing diaphragm. Use a wrench to
hold the stem while loosening the stem nut.
6. Remove the housing cap screws and remove the upper
actuator housing.
Copyright 2023 Baker Hughes Company. All rights reserved. Mooney FlowMax Regulators Instruction Manual | 21
4. Install the balancing diaphragm retainer o-ring side down,
over the stem and tighten. Use a wrench to hold the stem
while tightening the retainer. The 2” inch FlowMax retainer
is threaded and attached directly to the stem. The 3” - 6”
FlowMax regulators utilize a nut and washer to hold the
retainer in place.
5. Align the small hole on the main diaphragm flange with the
alignment pin in the lower actuator housing and bottom the
diaphragm on the housing flange.
O-Ring
Housing
Alignment Figure 35 - Install the remaining actuator cap screws
Pin 10. Install the balancing diaphragm onto the Balancing
O-Ring diaphragm Retainer. Ensure that the diaphragm flange is
Main facing up. Once installed, the diaphragm flange will need to
Diaphragm be pushed down so that it is flush with counter bore surface
of the upper actuator housing.
Balancing
Diaphragm
22 | Baker Hughes Copyright 2023 Baker Hughes Company. All rights reserved.
12. Install the piston onto the stem with the piston ring and 14a. 2” FlowMax only: Place the balancing diaphragm o-ring into
counter bore up. The bottom end of the piston should fit the counter bore in the upper actuator Housing and install
over the balancing diaphragm and hold it in place over the the spring case onto the housing. The o-ring can be lightly
balancing diaphragm Retainer. Note that 3” -6” FlowMax stretched for ease of assembly.
regulators utilize a nut to hold the balancing diaphragm
retainer in place. 2” Balancing
Diaphragm
Balancing Stem Nut O-Ring
Diaphragm
Retainer
Piston
Piston
3” - 6”Bal-
ancing
Diaphragm
O-Ring O-Ring
Washer
Copyright 2023 Baker Hughes Company. All rights reserved. Mooney FlowMax Regulators Instruction Manual | 23
6. Insert the main spring into the piston counterbore and 6” FlowMax Only
install the spring case cap. NOTE: The 6” FlowMax has an
additional washer between the spring and spring case cap. Note: The 6” FlowMax does not utilize a body gasket. There
should be no gap between the actuator and body.
20.
Reconnect control/sense and pilot supply lines to the
actuator.
Housing
O-Ring
24 | Baker Hughes Copyright 2023 Baker Hughes Company. All rights reserved.
5. Install the o-ring onto the indicator cover. Lightly lubricate
Stem the o-ring and threads. Screw the indicator cover into the
O-Ring spring case cap until bottomed.
Counterbore
Copyright 2023 Baker Hughes Company. All rights reserved. Mooney FlowMax Regulators Instruction Manual | 25
5. Use a socket wrench to tighten the stem nut back onto stem.
Use a wrench to hold the stem while tightening the stem nut.
6. Reassembly the actuator onto the regulator body. Refer to
steps 8-11 on pages 17 & 18.
Cleaning
1. DO NOT clean o-ring grooves with sharp metal tools.
The bottom of the grooves must have a smooth finish to
prevent leakage. The mating surface of adjacent parts must
also be smooth to prevent leakage.
Reduced Ca-
pacity Plug
Retainer
26 | Baker Hughes Copyright 2023 Baker Hughes Company. All rights reserved.
Troubleshooting
Problem Solution
The regulator will not shut-off 1. Verify the clearance between the actuator and body is even
2. Check actuator to body bolts - tighten if necessary
3. Check the pilot for excess friction (“sticking open”)
4. Check main spring
5. Check the plug seal for damage
6. Check the seat for any nicks or damage to the sealing surface
7. Check for damage to the seat o-ring
8. Check for obstructions in the stem hole
9. Check for failure of the balancing diaphragm
10. Check for blockage of the internal restrictor
Regulator will not open 1. Check if any valves in the sense line are not fully open
2. Check the pilot set point
3. Check that existing piping matches the piping schematics
4. Check for binding
5. Check the main diaphragm for damage
Erratic Behavior 1. Check the location of the sense line (away from pipes, fittings, and other turbulent
locations)
2. Check that the size of the sense line is adequate (refer to recommendations on page 5)
3. Check if any valves in the sense line are not fully open
4. Check the pilot for excess friction (“sticking”)
5. Check for excess friction in the actuator
Copyright 2023 Baker Hughes Company. All rights reserved. Mooney FlowMax Regulators Instruction Manual | 27
Notes
28 | Baker Hughes Copyright 2023 Baker Hughes Company. All rights reserved.
Notes
Copyright 2023 Baker Hughes Company. All rights reserved. Mooney FlowMax Regulators Instruction Manual | 29
Find the nearest local Channel Partner in your area:
valves.bakerhughes.com/contact-us
valves.bakerhughes.com
Copyright 2023 Baker Hughes Company. All rights reserved. Baker Hughes provides this information on
an “as is” basis for general information purposes. Baker Hughes does not make any representation as to
the accuracy or completeness of the information and makes no warranties of any kind, specific, implied or
oral, to the fullest extent permissible by law, including those of merchantability and fitness for a particular
purpose or use. Baker Hughes hereby disclaims any and all liability for any direct, indirect, consequential or
special damages, claims for lost profits, or third party claims arising from the use of the information, whether
a claim is asserted in contract, tort, or otherwise. Baker Hughes reserves the right to make changes in
specifications and features shown herein, or discontinue the product described at any time without notice or
obligation. Contact your Baker Hughes representative for the most current information. The Baker Hughes
logo, FlowMax and Mooney are trademarks of Baker Hughes Company. Other company names and product
names used in this document are the registered trademarks or trademarks of their respective owners.