Spec Tech C1100D5
Spec Tech C1100D5
Spec Tech C1100D5
Standby Standby
Fuel consumption kVA (kW) kVA (kW)
Ratings 1133 (906) 1029 (823)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
gph 13.4 24.0 36.7 50.1 14.3 24.8 35.4 45.9
L/hr 60.80 109.30 167.10 228.00 65.00 113.00 161.00 209.00
Fuel flow
Maximum fuel flow, L/hr 428
Maximum fuel inlet restriction, mm Hg 203
Maximum fuel inlet temperature (°C) 70
©2011 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
Document no. DS372-CPGK-RevC - 3/1/2012
Air Standby Rating Standby Rating
Combustion air, m 3/min 72.80 68.40
Maximum air cleaner restriction, kPa 6.2
Exhaust
Exhaust gas flow at set rated load, m3/min 198.5 183.0
Exhaust gas temperature, °C 513 499
Maximum exhaust back pressure, kPa 10
Genset outline
Open set
Enclosed set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
©2011 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
Document no. DS372-CPGK-RevC - 3/1/2012
Alternator data
Connection 1 Temp rise °C Duty2 Alternator Voltage
Wye, 3 Phase 150/125C S/P HC6K 380-440V
11000V
Wye, 3 Phase 150/105C S/P/C LVP7F 380-440V
Ratings definitions
Emergency Standby Limited-Time running Prime Power (PRP) Base Load (Continuous)
Power (ESP) Power (LTP): Power (COP)
Applicable for supplying power to Applicable for supplying power to a Applicable for supplying power to Applicable for supplying power
varying electrical load for the constant electrical load for limited varying electrical load for unlimited continuously to a constant electrical
duration of power interruption of a hours. Limited Time Running Power hours. Prime Power (PRP) is in load for unlimited hours. Continuous
reliable utility source. Emergency (LTP) is in accordance with ISO accordance with ISO 8528. Ten Power (COP) in accordance with ISO
Standby Power (ESP) is in 8528. percent overload capability is 8528, ISO 3046, AS 2789, DIN 6271
accordance with ISO 8528. Fuel available in accordance with ISO and BS 5514.
Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS
3046, AS 2789, DIN 6271 and BS 5514.
5514.
©2011 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
Document no. DS372-CPGK-RevC - 3/1/2012
Specification sheet
Diesel
generator set
KTA38 series
engine
900 kVA - 1132 kVA 50 Hz
810 kW - 1020 kW 60 Hz
Description
®
This Cummins commercial generator set is a Cooling system - Standard integral set-
fully integrated power generation system, mounted radiator system, designed and tested
providing optimum performance, reliability, and for rated ambient temperatures, simplifies facility
versatility for stationary Standby, Prime Power, design requirements for rejected heat.
and Continuous duty applications. ®
Control system - Standard PowerCommand
Features electronic control provides total system
integration including remote start/stop, precise
Cummins heavy-duty engine - Rugged 4-cycle
frequency and voltage regulation, alarm and
industrial diesel delivers reliable power, low TM
status message display, AmpSentry
emissions and fast response to load changes.
protection, output metering, auto-shutdown.
Permanent Magnet Generator (PMG) - Offers
Enclosures - Optional containerized version
enhanced motor starting and fault clearing short
available.
circuit capability.
Warranty and service - Backed by a
Alternator - Several alternator sizes offer
comprehensive warranty and worldwide
selectable motor starting capability with low
distributor network.
reactance 2/3 pitch windings; low waveform
distortion with non-linear loads, fault clearing
short-circuits capability, and class H insulation.
power.cummins.com
©2017 Cummins Inc. | SS15-CPGK (07/17)
Generator set specifications
Governor regulation class ISO 8528 G3*
Voltage regulation, no load to full load ± 0.5%
Random voltage variation ± 0.5%
Frequency regulation Isochronous
Random frequency variation ± 0.25%
EMS compatibility EN61000-6-4/EN61000-6-2
*ISO 8528 G2 for C900D6B, C1000D6B
Engine specifications
Design 4 cycle, in-line, turbocharged and after cooled
Bore 159 mm (6.25 in.)
Stroke 159 mm (6.25 in.)
Displacement 38 L (2300 in3)
Cylinder block 12 cylinder vee formation, direct injection, four-cycle diesel engine
Battery capacity 890 amps at ambient temperature 32 °F (0 °C)
Battery charging alternator 55 amps
Starting voltage 24 volts, negative ground
Fuel system Direct injection
Fuel filter Dual spin on paper element fuel filters with standard water separator
Air cleaner type Dry replaceable element
Lube oil filter type(s) Spin-on paper element full flow and bypass lube oil filters
Standard cooling system 104 ºF (40 ºC) ambient radiator
Alternator specifications
Design Brushless, 4 pole, drip-proof revolving field
Stator 2/3 pitch
Rotor Direct coupled by flexible disc
Insulation system Class H
Standard temperature rise 150 °C Standby
Exciter type Permanent Magnet Generator (PMG)
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform Total Harmonic Distortion (THDV) No load < 1.5%. Non distorting balanced linear load < 5%
Telephone Influence Factor (TIF) < 50%
Telephone Harmonic Factor (THF) < 2%
Available voltages
50 Hz Line – Neutral/Line – Line 60 Hz Line – Neutral/Line – Line
127/220 240/416 120/208 230/400 225/440
230/400 220/380*
*Derate may be applicable at this voltage. Please consult factory for details.
*Note: Some options may not be available on all models - consult factory for availability.
power.cummins.com
©2017 Cummins Inc. | SS15-CPGK (07/17)
PowerCommand 3.3 (MLD) control Load profile (operating hours at % load in 5% increments)
system Fault history
The PowerCommand 3.3 control system is an integrated Data logging and fault simulation (requires InPower)
microprocessor based generator set control system Standard control functions
providing voltage regulation, engine protection, alternator
Digital governing (optional)
protection, operator interface and isochronous governing.
Integrated digital electronic isochronous governor
AmpSentry – Includes integral AmpSentry protection,
which provides a full range of alternator protection Temperature dynamic governing
functions that are matched to the alternator provided. Digital voltage regulation
Power management – Control function provides battery Integrated digital electronic voltage regulator
monitoring and testing features and smart starting control 3-phase, 4-wire Line-to-Line sensing
system.
Configurable torque matching
Advanced control methodology – Three phase sensing,
AmpSentry AC protection
full wave rectified voltage regulation, with a PWM output for
stable operation with all load types. AmpSentry protective relay
Communications interface – Control comes standard with Over current and short circuit shutdown
PCCNet and Modbus interface. Over current warning
Regulation compliant – Prototype tested: UL, CSA and Single and three phase fault regulation
CE compliant. Over and under voltage shutdown
Service – InPower™ PC-based service tool available for
Over and under frequency shutdown
detailed diagnostics, setup, data logging and fault
simulation. Overload warning with alarm contact
Reliable design – The control system is designed for Reverse power and reverse Var shutdown
reliable operation in harsh environment. Field overload
Multi-language support Engine protection
Operator panel features Battery voltage monitoring, protection and testing
Operator panel features – The operator panel, in addition Over speed shutdown
to the alternator, displays the Utility/AC Bus data. Low oil pressure warning and shutdown
Operator/display functions High coolant temperature warning and shutdown
320 x 240 pixels graphic LED backlight LCD Low coolant level warning or shutdown
Auto, manual, start, stop, fault reset and lamp test/panel Low coolant temperature warning
lamp switches Fail to start (over crank) shutdown
Alpha-numeric display with pushbuttons Fail to crank shutdown
LED lamps indicating genset running, remote start, not in Cranking lockout
auto, common shutdown, common warning, manual run Sensor failure indication
mode, auto mode and stop
Low fuel level warning or shutdown
Paralleling control functions
Fuel-in-rupture-basin warning or shutdown
Digital frequency synchronization and voltage matching
Full authority electronic engine protection
Isochronous kW and kVar load sharing controls
Control functions
Droop kW and kVar control
Time delay start and cool down
Sync check
Real time clock for fault and event time stamping
Extended paralleling (Peak Shave/Base Lload)
Exerciser clock and time of day start/stop
Digital power transfer control (AMF) provides load
Data logging
transfer operation in open or closed transition or soft
(ramping) transfer mode Cycle cranking
Alternator data Load shed
Line-to-Neutral and Line-to-Line AC volts Configurable inputs and outputs (4)
3-phase AC current Remote emergency stop
Frequency Options
kW, kVar, power factor kVA (three phase and total) Auxiliary output relays (2)
Engine data Masterless Load Demand (MLD)
DC voltage Load dependent start/stop of multi-gen system
Engine speed Predictive load input
Lube oil pressure and temperature Run hour equalization
Coolant temperature
PowerCommand 3.3
Comprehensive FAE data (where applicable) control operator/display
Other data panel
Genset model data
Start attempts, starts, running hours, kW hours
power.cummins.com
©2017 Cummins Inc. | SS15-CPGK (07/17)
Emergency Standby Power (ESP):
Applicable for supplying power to varying electrical
load for the duration of power interruption of a
reliable utility source. Emergency Standby Power
(ESP) is in accordance with ISO 8528. Fuel Stop
power in accordance with ISO 3046, AS 2789,
DIN 6271 and BS 5514.
Limited-Time Running Power (LTP):
Applicable for supplying power to a constant
electrical load for limited hours. Limited-Time
This outline drawing is to provide representative configuration
Running Power (LTP) is in accordance with
details for model series only.
ISO 8528.
Prime Power (PRP): See respective model data sheet for specific model outline
drawing number.
Applicable for supplying power to varying electrical
load for unlimited hours. Prime Power (PRP) is in Do not use for installation design
accordance with ISO 8528. Ten percent overload
capability is available in accordance with ISO 3046,
AS 2789, DIN 6271 and BS 5514.
Base Load (Continuous) Power (COP):
Applicable for supplying power continuously to a
constant electrical load for unlimited hours.
Continuous Power (COP) in accordance with
ISO 8528, ISO 3046, AS 2789, DIN 6271 and
BS 5514.
Model Dim ‘A’ (mm) Dim ‘B’ (mm) Dim ‘C’ (mm) Set weight* dry (kg) Set weight* wet (kg)
C1100D5B 4470 1785 2229 7990 8380
C1000D6B 4470 1785 2229 7990 8380
C1000D5B 4470 1785 2229 7990 8380
C900D6B 4470 1785 2229 7990 8380
* Note: Weights represent a set with standard features. See outline drawings for weights of other configurations.
©2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
SS15-CPGK (07/17)