ADDRESSABLE FIRE ALARM SYSTEM BOQ
Short
Sl. No. Long Description Unit Qty Unit Rate Amount
Description
G ADDRESSABLE FIRE ALARM SYSTEM
Supply, fixing, testing and commissioning of the following number of Loops UL/FM approved Microprocessor based addressable
type Fire Control panel with LCD displays,Zonal Indications, front panel operation keyboard, Networkable with Extended panels,
1 Fire Alarm Panel on board/ attachable Ethernet Module, RS232 &RS458/422 communication port, Graphics system/BMS compatable along with Nos 1
bacnetOver IP, default mac outputs and with Battery Power Pack as per specifications
2 Loop fire alarm panel (with each loop supporting 256 Detectors & Devices).
Supply, Installation, Testing & Commissioning of remote annunciators / Repeater panel shall consists of network communication
card (over ethernet cable from MFAP) ,display board which shall be Liquid Crystal Display (LCD) . The annunciator/Repeater panel
2 Fire Alarm Panel Nos 1
shall have built in memory to record the alarm events and shall have standard buttons for alarm acknowledgement, alarm
silence, trouble acknowledgement. etc.
Supply, installation, testing and commissioning of addressable photoelectric smoke Detector. The rate shall include the cost of
3 Smoke Detector Nos RO
junction box & necessary fixing accessories as required. (UL listed)
4 RI Supply, installation, testing and commissioning of response indicator. Nos 10
Supply, installation, testing and commissioning of addressable Heat Detector (Rate of Rise and Fixed temperature) (UL listed).
5 Smoke Detector Nos 2
The rate shall include the cost of junction box & necessary fixing accessories as required.
Supply, installation, testing and commissioning of addressable photoelectric smoke Detector. The rate shall include the cost of
6 Smoke Detector Nos 60
junction box & necessary fixing accessories as required. Blinkbule
Supply, installation, testing and commissioning of Addressable Manual Call Point with LED indication, Plug in wiring Terminals. The
7 MCP Nos 7
rate shall include the cost of junction box & necessary fixing accessories as required.
8 Hooter Supply, installation of loop powered Hooter 24V, 100 db Nos 7
Supply, installation, testing and commissioning of Addressable control Module for hooter with LED indication. The rate shall
9 Modules include the cost of junction box & necessary fixing accessories as required. Nos 0
Supply, installation, testing and commissioning of Addressable fault isolator module. The rate shall include the cost of junction
10 Modules Nos 3
box & necessary fixing accessories as required.
Supply, installation, testing and commissioning of relay control module. (interface unit). The rate shall include the cost of junction
11 Modules Nos 0
box & necessary fixing accessories as required.
Supply, Installation, Testing & Commissioning of Analogue Addressable Monitor module having addressing system for
12 Modules Nos 2
monitoring the field devices like Panic Bar, water flow devices etc. including Junction Box, mounting accessories, etc.
Supply, wiring, testing and commissioning of ISI Certified 2Cx1.5 sq.mm, twisted shield, FRLS type, armored double insulated
13 Cables & Wires copper cable with Ferrules, Lugs, saddles, saddles base & other accessories complete as required. The cable M 400
specification shall meet FACP & detectors manufacturer requirement. (Including hooter & RI cabling)
Supply and laying of 2mm thick FRLS PVC conduit with all necessary accessories like junction boxes, pull boxes. G.I fish wires and
14 other fixing accessories as required. The rate shall also include chasing of walls, floor and plastering of the chased portion etc all
PVC Conduits complete as required.
a) 20mm dia M Ro
b) 25mm dia M 30
16 duct detectors Supply Installation testing and commissioning of duct detectors along with its fixing accessories Nos 20
Page 1 of 1