Product Manual: 2-Wire Programmable Transmitter

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

PERFORMANCE

MADE
SMARTER

Product manual
5333
2-wire programmable transmitter

T E M P E R AT U R E   |   I . S . I N T E R FA C E S   |   CO M M U N I C AT I O N I N T E R FA C E S   |   M U LT I F U N C T I O N A L   |   I S O L AT I O N   |   D I S P L AY

No. 5333V115- UK
From ser. no. 1320 9 4 0 01 - 1320 9 4 630
1411150 01 
6 Product Pillars
to meet your every need
Individually outstanding, unrivalled in combination
With our innovative, patented technologies, we make signal conditioning smarter and simpler. Our portfolio is composed of six
product areas, where we offer a wide range of analog and digital devices covering over a thousand applications in industrial
and factory automation. All our products comply with or surpass the highest industry standards, ensuring reliability in even
the harshest of environments and have a 5-year warranty for greater peace of mind.

Our range of temperature transmitters and sensors provides the highest level of signal integrity from the
measurement point to your control system. You can convert industrial process temperature signals to analog, bus or
digital communications using a highly reliable point-to-point solution with a fast response time, automatic self-
calibration, sensor error detection, low drift, and top EMC performance in any environment.

We deliver the safest signals by validating our products against the toughest safety standards. Through our
commitment to innovation, we have made pioneering achievements in developing I.S. interfaces with SIL 2 Full
Assessment that are both efficient and cost-effective. Our comprehensive range of analog and digital intrinsically
safe isolation barriers offers multifunctional inputs and outputs, making PR an easy-to-implement site standard.
Our backplanes further simplify large installations and provide seamless integration to standard DCS systems.

We provide inexpensive, easy-to-use, future-ready communication interfaces that can access your PR installed base
of products. All the interfaces are detachable, have a built-in display for readout of process values and diagnostics,
and can be configured via push-buttons. Product specific functionality includes communication via Modbus and
Bluetooth and remote access using our PR Process Supervisor (PPS) application, available for iOS and Android.

Our unique range of single devices covering multiple applications is easily deployable as your site standard. Having
one variant that applies to a broad range of applications can reduce your installation time and training, and greatly
simplify spare parts management at your facilities. Our devices are designed for long-term signal accuracy, low
power consumption, immunity to electrical noise and simple programming.

Our compact, fast, high-quality 6 mm isolators are based on microprocessor technology to provide exceptional
performance and EMC-immunity for dedicated applications at a very low total cost of ownership. They can be
stacked both vertically and horizontally with no air gap separation between units required.

Our display range is characterized by its flexibility and stability. The devices meet nearly every demand for display
readout of process signals, and have universal input and power supply capabilities. They provide a real-time
measurement of your process value no matter the industry, and are engineered to provide a user-friendly and
reliable relay of information, even in demanding environments.
2-wire programmable
transmitter
5333

Table of contents
Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Technical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Mounting / installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Electrical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Mechanical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Mounting of sensor wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
ATEX Installation Drawing - 5333A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
ATEX Installation Drawing - 5333D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
IECEx Installation Drawing - 5333A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
IECEx Installation Drawing - 5333D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
FM Installation Drawing - 5333D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
CSA Installation Drawing - 5333A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
CSA Installation Drawing - 5333D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
INMETRO Installation Drawing - 5333A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
INMETRO Installation Drawing - 5333D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Document history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

5333V115-UK 3
2-wire programmable transmitter
5333

• RTD or Ohm input


• High measurement accuracy
• 3-wire connection
• Programmable sensor error value
• For DIN form B sensor head mountings

Application Applications
• Linearised temperature measurement with Pt100...
Pt1000 or Ni100...Ni1000 sensor.
• Conversion of linear resistance variation to a standard 2-wire installation
in control room
analog current signal, for instance from valves or Ohmic RTD to 4...20 mA
level sensors.
Technical characteristics V+

+
• Within a few seconds the user can program PR5333 to
-
mA
measure temperatures within all RTD ranges defined by
the norms.
• The RTD and resistance inputs have cable compensation 2-wire installation
for 3-wire connection. in control room
Resistance to 4...20 mA
Mounting / installation
• For DIN form B sensor head mounting. In non-hazardous V+
+

areas the 5333 can be mounted on a DIN rail with the PR


-

fitting type 8421. mA

4 5333V115-UK
Order

Type Version

5333 Zone 2 / Div. 2 :A


Zone 0, 1, 2, 20, 21, 22, M1 / DIV. 1, DIV. 2 :D

Accessories

5909 = Loop Link USB interface and PReset Software

Electrical specifications

Environmental conditions:
Operating temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -40°C to +85°C
Calibration temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20...28°C
Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 95% RH (non-cond.)
Protection degree, enclosure / terminals . . . . . . . . . . . . . . . . . . . . . IP68 / IP00
Mechanical specifications:
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ø 44 x 20.2 mm
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 g
Max. wire size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 x 1.5 mm2 stranded wire
Screw terminal torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.4 Nm
Vibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IEC 60068-2-6
2...25 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±1.6 mm
25...100 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±4 g
Common specifications:
Supply voltage, DC
5333A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.0...35 VDC
5333D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.0...30 VDC
Internal power dissipation
5333A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 mW...0.8 W
5333D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 mW...0.7 W
Voltage drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.0 VDC
Warm-up time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 min.
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Loop Link
Signal / noise ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Min. 60 dB
Response time (programmable) . . . . . . . . . . . . . . . . . . . . . . . . . . 0.33...60 s
Signal dynamics, input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 bit
Signal dynamics, output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 bit
Effect of supply voltage variation . . . . . . . . . . . . . . . . . . . . . . . . . < 0.005% of span / VDC

Accuracy, the greater of general and basic values:

General values

Input type Absolute accuracy Temperature coefficient

All ≤ ±0.1% of span ≤ ±0.01% of span / °C

Basic values

Input type Basic accuracy Temperature coefficient

RTD ≤ ±0.3°C ≤ ±0.01°C/°C

Lin. R ≤ ±0.2 Ω ≤ ±20 mW / °C

EMC - immunity influence . . . . . . . . . . . . . . . . . . . . . . . . < ±0.5% of span

5333V115-UK 5
Electrical specifications, input:
RTD and linear resistance input:

RTD Min. Max. Min.


type value value span Standard
Pt100...Pt1000 -200°C +850°C 25°C IEC 60751
Ni100...Ni1000 -60°C +250°C 25°C DIN 43760
Linear resistance 0Ω 10000 Ω 30 Ω -----

Max. offset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50% of selec. max. value


Cable resistance per wire (max.) . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Ω
Sensor current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . > 0.2 mA, < 0.4 mA
Effect of sensor cable resistance (3-wire) . . . . . . . . . . . . . . . . . . . . < 0.002 Ω / Ω
Sensor error detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes

Output:
Current output:
Signal range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4...20 mA
Min. signal range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 mA
Updating time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135 ms
Load resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ (Vsupply - 8.0) / 0.023 [Ω]
Load stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < ±0.01% of span / 100 Ω
Sensor error detection:
Programmable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5...23 mA
Namur NE43 Upscale . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 mA
Namur NE43 Downscale . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5 mA

Of span = Of the presently selected range

Observed authority requirements:


EMC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2014/30/EU
RoHS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2011/65/EU
ATEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2014/34/EU
EAC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TR-CU 020/2011
EAC Ex . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TR-CU 012/2011
Marine approval:
DNV-GL, Ships & Offshore . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Standard for Certification No. 2.4
Ex / I.S. approvals:
ATEX:
5333A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KEMA 10ATEX0003 X
5333D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KEMA 03ATEX1535 X
IECEx . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DEK 13.0036 X
FM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FM17US0013X
CSA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1125003
INMETRO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DEKRA 16.0014 X
EAC Ex . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RU C-DK.GB08.V.00410

6 5333V115-UK
Connections

Input:
RTD, 2-wire RTD, 3-wire Resistance, 2-wire Resistance, 3-wire
3 4 6 3 4 6 3 4 6 3 4 6

Output:
2-wire installation
1 2

+ mA -

Block diagram

Supply +
1 8...35 VDC
DC
4 mA
Input + 6 DC

Lin.R
RTD C PU Comm.

M UX PGA A /D
Comp. + 4
3
Input - D /A

0...16
mA
E E PRO M
Supply -
2 mA
4...20 mA
5333

5333V115-UK 7
Programming
• Loop Link is a communications interface that is needed for programming 5333.
• For programming please refer to the drawing below and the help functions in PReset.
• Loop link is not approved for communication with modules installed in harzardous (Ex) areas.

Receiving
Disconnect Equipment
1 +Vsupply
Red * Yellow Input
2
Black * Green

5333

Connector

08:30:00
n Language O ption
O utput C om m unicatio
File Product Input PRetop 5331
2004-8-10
Date:
Serial no: 043201594
Tag no: PRelectronics

Analog output
Analog input O utput type: 4 - 20mA
Pt100 DIN/IEC
Input type: Sensor error: Upscale
0.00 - 50.00 C
Input range:
3-wire
C onnection:

L oop
p: ------
C old junction com
1.00 sec
Response time:

5909 - USB
L ink

* Connected only for


"on-line" programming

Mechanical specifications Mounting of sensor wires

+ -

+ -

Wires must be mounted


ø 6 mm between the metal plates.

33 mm 20.2 mm

ø 44 mm

8 5333V115-UK
5333QA02
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

ATEX Installation drawing


For safe installation of 5333A the following must be observed. The module shall only be installed
by qualified personnel who are familiar with the national and international laws, directives and
standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.

ATEX Certificate KEMA 10ATEX 0003X

Marking II 3 G Ex nA [ic] IIC T4 … T6 Gc


II 3 G Ex ic IIC T4…T6 Gc
II 3 D Ex ic IIIC Dc

Standards EN 60079-0 : 2012, EN 60079-11 : 2012, EN 60079-15 : 2010

T4: -40 ≤ Ta ≤ 85ºC Terminal: 3,4,6 Terminal: 1,2 Terminal: 1,2


T6: -40 ≤ Ta ≤ 60ºC Ex nA [ic] Ex nA Ex ic

Uo: 5V Umax. ≤ 35 VDC Ui = 35 VDC


Io: 4.0 mA Ii = 110mA
Po: 20 mW Li = 10 μH
Lo: 900 mH Ci = 1.0 nF
Co: 1000 μF

Special conditions for safe use

For type of protection Ex nA, the transmitter shall be mounted in a metal enclosure providing a
degree of protection of at least IP54 according to EN60529.

For use in the presence of combustible dusts the transmitter shall be mounted in an enclosure
providing a degree of protection of at least IP6X in accordance with EN60529, the surface
temperature of the outer enclosure is 20 K above the ambient temperature

For an ambient temperature ≥ 60ºC, heat resistant cables shall be used with a rating of at least
20 K above the ambient temperature.

Revision date: Version Revision Page:


2013-08-07 V2R0 1/1

5333V115-UK 9
5333QA01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

ATEX Installation drawing


For safe installation of 5333D the following must be observed. The module shall only be Installed by
qualified personnel who are familiar with the national and international laws, directives and
standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.

ATEX Certificate KEMA 03ATEX 1535 X

Marking
II 1 G Ex ia IIC T4...T6 Ga
II 1 D Ex ia IIIC Da
II 1 M Ex ia I Ma

Standards EN 60079-0 : 2012, EN 60079-11 : 2012, EN 60079-26 : 2007,


EN 60079-15 : 2010

Hazardous area
Zone 0, 1, 2, 20, 21, 22 Non Hazardous Area
T4: -40 ≤ Ta ≤ 85ºC
T5: -40 ≤ Ta ≤ 60ºC
T6: -40 ≤ Ta ≤ 60ºC

Terminal: 3,4,6 6
Uo: 30 VDC
Io: 8 mA 5 1+
Po: 60 mW
Lo: 35 mH 4 2 -
Co: 66 nF
3
5333D
Barrier

Terminal: 1,2
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10μH
Ci: 1.0nF

Revision date: Version Revision Page:


2013-08-07 V2R0 1/2

10 5333V115-UK
5333QA01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

Installation notes:

In a potentially explosive gas atmosphere, the transmitter shall be mounted in an enclosure in


order to provide a degree of protection of at least IP20 according to EN60529.

If the transmitter is installed in an explosive atmosphere requiring the use of equipment of


category 1 G, 1 M or 2 M, and if the enclosure is made of aluminum, if must be installed such,
that ignition sources due to impact and friction sparks are excluded.

If the enclosure is made of non-metallic materials, electrostatic charging shall be avoided.

For installation in a potentially explosive dust atmosphere, the following instructions apply:

The transmitter shall be mounted in a metal enclosure form B that is providing a degree of
protection of at least IP6X according to EN60529, that is suitable for the application and
correctly installed.

Cable entries and blanking elements shall be used that are suitable for the application and
correctly installed.

For an ambient temperature ≥ 60ºC, heat resistant cables shall be used with a rating of at least
20 K above the ambient temperature.

The surface temperature of the enclosure is equal to the ambient temperature plus 20 K, for a
dust layer with a thickness up to 5 mm

Revision date: Version Revision Page:


2013-08-07 V2R0 2/2

5333V115-UK 11
5333QI02
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

IECEx Installation drawing


For safe installation of 5333A or 5343A the following must be observed. The module shall only be
installed by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.

Certificate IECEx DEK 13.0036X

Marking Ex nA [ic] IIC T6..T4 Gc T4: -40 ≤ Ta ≤ 85ºC


Ex ic IIC T6..T4 Gc T6: -40 ≤ Ta ≤ 60ºC
Ex ic IIIC Dc

Standards IEC 60079-0 : 2011, IEC 60079-11 : 2011, IEC 60079-15 : 2010

Terminal Ex nA [ic] Ex ic
1,2 Umax = 35V Ui : 35V, Ii:110mA, Ii:10µH, Ci:1,0nF
3,4,6 Uo: 5V, Io: 4mA, Po: 20mW, Lo: 900mH, Co: 1000µF

Installation note:

For installation in a potentialy explosive gas atmosphere, the following instructions apply:

For nA installation the transmitter must be installed in an metal enclosure e.g. a form B
enclosure, providing a degree of protection of at least IP54 according to IEC60529 or in an
enclosure with type of protection Ex n or Ex e.

For ic installation the transmitter must be installed in enclosure providing a degree of


protection of at least IP20 according to IEC60529 and that is suitable for the application.

Cable entry devices and blanking elements shall fulfill the same requirements

For an ambient temperature ≥ 60ºC, heat resistant cables shall be used with a rating of at
least 20 K above the ambient temperature.

For installation in a potentially explosive dust atmposphere, the following instructions apply:
The surface temperature of the enclosure is equal to the ambient temperature plus 20 K, for a
dust layer with a thickness up to 5 mm.
The transmitter must be mounted in a enclosure according to DIN 43729 that provides a
degree of protection of at least IP6X according to IEC60529, and that is suitable for the
application. Cable entry devices and blanking elements shall fulfill the same requirements.

Revision date: Version Revision Page:


2013-06-03 V1R0 1/1

12 5333V115-UK
5333QI01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

IECEx Installation drawing


For safe installation of 5333D or 5343B the following must be observed. The module shall only be
installed by qualified personnel who are familiar with the national and international laws, directives
and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.

Certificate IECEx DEK 13.0036X

Marking Ex ia IIC T4…T6 Ga


Ex ia IIIC Da
Ex ia I Ma

Standards IEC 60079-0 : 2011, IEC 60079-11 : 2011, IEC 60079-26:2006

Hazardous area
Zone 0, 1, 2, 20, 21, 22, M1 Non Hazardous Area

T4: -40 ≤ Ta ≤ 85ºC


T5: -40 ≤ Ta ≤ 60ºC
T6: -40 ≤ Ta ≤ 45ºC

6
Terminal: 3,4,6
Uo: 30 VDC 5 1+
Io: 8 mA
Po: 60 mW 4 2 -
Lo: 35 mH 5333D
Co: 66 nF 3
5343B
Barrier
Terminal: 1,2
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10μH
Ci: 1.0nF

Revision date: Version Revision 0Page:


2013-06-03 V1R0 1/2

5333V115-UK 13
5333QI01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

Installation notes.

In a potentially explosive gas atmosphere, the transmitter shall be mounted in a metal form B
enclosure in order to provide a degree of protection of at least IP20 according to IEC60529. If
however the environment requires a higher degree of protection, this shall be taken into
account.

If the transmitter is installed in an explosive atmosphere requiring the use of equipment


protection level Ga, Ma and Mb, and if the enclosure is made of aluminum, it must be installed
such, that ignition sources due to impact and friction sparks are excluded.

For installation in a potentially explosive dust atmosphere, the following instructions apply:

For explosive dust atmospheres, the surface temperature of the outer enclosure is 20 K above
the ambient temperature.

The transmitter shall be mounted in a metal enclosure form B according to DIN43729 that is
providing a degree of protection of at least IP6X according to IEC60529, that is suitable for the
application and correctly installed.

Cable entries and blanking elements shall be used that are suitable for the application and
correctly installed.

For an ambient temperature ≥ 60ºC, heat resistant cables shall be used with a rating of at least
20 K above the ambient temperature.

Revision date: Version Revision 0Page:


2013-06-03 V1R0 2/2

14 5333V115-UK
5300Q502
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

FM Installation Drawing

Model 5331D, 5332D, 5333D and 5343B

Hazardous (Classified) Location Non Hazardous Location


Class I,Division1, Groups, A,B,C,D T4..T6
Class I, Zone 0, AEx ia IIC T4..T6 Associated Apparatus
or Barrier
+ with
Ambient temperature limits
T4: ‐40 to + 85 deg. Celcius
entity Parameters:
T6: ‐40 to + 60 deg. Celcius
UM < 250V
‐ Voc or Uo < Vmax or Ui
Terminal 1 , 2 Isc or Io < Imax or Ii
Vmax or Ui: 30 V Po < Pi
Imax or Ii: 120 mA Ca or Co > Ci + Ccable
Pmax or Pi: 0.84 W 1 2 La or Lo > Li + Lcable
Ci: 1 nF
Li:10 uH

Terminal 3,4,5,6 6 3 This device must not be connected


Vt or Uo: 9.6 V to any associated apparatus which
5 4
It or Io: 28 mA uses or generates more than 250
Pt or Po: 67.2 mW VRMS
Ca or Co: 3.5 uF
La or Lo: 35 mH SENSOR

Model 5335D, 5337D

Hazardous (Classified) Location Non Hazardous Location


Class I,Division1, Groups, A,B,C,D T4..T6
Class I, Zone 0, AEx ia IIC T4..T6 Associated Apparatus
or Barrier
+ with
Ambient temperature limits
T4: ‐40 to + 85 deg. Celcius
entity Parameters:
T6: ‐40 to + 60 deg. Celcius
UM < 250V
‐ Voc or Uo < Vmax or Ui
Terminal 1 , 2 Isc or Io < Imax or Ii
Vmax or Ui: 30 V Po < Pi
Imax or Ii: 120 mA Ca or Co > Ci + Ccable
Pmax or Pi: 0.84 W 1 2 La or Lo > Li + Lcable
Ci: 1 nF
Li:10 uH

Terminal 3,4,5,6 6 3 This device must not be connected


Vt or Uo: 9.6 V to any associated apparatus which
5 4
It or Io: 28 mA uses or generates more than 250
Pt or Po: 67.2 mW VRMS
Ca or Co: 3.5 uF
La or Lo: 35 mH SENSOR

Revision date: Version Revision Page:


2018-08-27 V3R0 1/2

5333V115-UK 15
5300Q502
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

The entity concept


The Transmitter must be installed according to National Electrical Code (ANSI-NFPA 70) and shall be
installed with the enclosure, mounting, and spacing segregation requirement of the ultimate application.

Equipment that is FM-approved for intrinsic safety may be connected to barriers based on the ENTITY
CONCEPT. This concept permits interconnection of approved transmitters, meters and other devices in
combinations which have not been specifically examined by FM, provided that the agency's criteria are
met. The combination is then intrinsically safe, if the entity concept is acceptable to the authority having
jurisdiction over the installation.
The entity concept criteria are as follows:
The intrinsically safe devices, other than barriers, must not be a source of power.
The maximum voltage Ui(VMAX) and current Ii(IMAX), and maximum power Pi(Pmax), which the device can
receive and remain intrinsically safe, must be equal to or greater than the voltage (Uo or VOC or Vt) and
current (Io or ISC or It) and the power Po which can be delivered by the barrier.

The sum of the maximum unprotected capacitance (Ci) for each intrinsically device and the interconnect-
ing wiring must be less than the capacitance (Ca) which can be safely connected to the barrier.

The sum of the maximum unprotected inductance (Li) for each intrinsically device and the interconnecting
wiring must be less than the inductance (La) which can be safely connected to the barrier.

The entity parameters Uo,VOC or Vt and Io,ISC or It, and Ca and La for barriers are provided by the barrier
manufacturer.

NI Field Circuit Parameters

Model 5331D, 5332D, 5333D, 5335D, 5337D and 5343B

Hazardous (Classified) Location Non Hazardous Location


Class I,Division2, Groups, A,B,C,D T4..T6
Class I, Zone 2, IIC T4..T6 Associated Apparatus
or Barrier
+
Ambient temperature limits
T4: ‐40 to + 85 deg. Celcius
T6: ‐40 to + 60 deg. Celcius

Terminal 1 , 2
Vmax : 35 V
Ci: 1.0 nF 1 2
Li:10 uH

6 3 This device must not be connected


to any associated apparatus which
5 4
uses or generates more than 250
VRMS

SENSOR

Revision date: Version Revision Page:


2018-08-27 V3R0 2/2

16 5333V115-UK
CSA Installation drawing 5333QC02
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

For safe installation of the 5333A the following must be observed. The module shall only be installed by
qualified personnel who are familiar with the national and international laws, directives and standards that
apply to this area.

Marking Hazardous Area


Class I, Division 2, Group A,B,C,D T4..T6 CL I, Div 2, GP ABCD
Class I Zone 2 Ex/AEx nA[ic] IIC T4..T6 CL I, Zone 2, IIC
Class I Zone 2 Ex/AEx nA IIC T4..T6
NIFW Class I Division 2, Group A,B,C,D T4: -40ºC to 85 ºC
T6: -40ºC to 60 ºC

Terminal: 6 Terminal:
3,4,6 1-2
Uo: 5 VDC 5 1+ Functional Ratings:
Io: 4 mA U nominal ≤ 35 VDC;
Po: 20 mW 4 2 - I nominal ≤ 3.5 - 23 mA
Lo: 900 mH
Co: 1000μF 3

Supply

NI Installation instructions

The transmitter must be installed in an enclosure providing a degree of protection of at least IP54
according to IEC60529 that is suitable for the application and is correctly installed. Cable entry
devices and blanking elements shall fulfill the same requirements.
If the enclosure is made of non-metallic materials or of painted metal, electrostatic charging shall
be avoided.
Use supply wires with a rating of at least 5 K above the ambient temperature.
Supply from a Class 2 Power Supply with Transient protection or equivalent.

WARNING: Substitution of components may impair suitability for Class I, Division 2


AVERTISSEMENT: la substitution de composants peut nuire à l'aptitude à la Classe I, Division 2.
WARNING: Do not disconnect equipment unless power has been switched off or the area is known
to be safe.
AVERTISSEMENT: Ne débranchez pas l'équipement sauf si l'alimentation a été coupée ou si la
zone est connue pour être sûre.

Non Incendive field wiring installation


The non incendive field Wiring Circuit concept allows interconnection of Nonincendive Field wiring
Apparatus with Associated Nonincendive Field Wiring Apparatus or Assosicated Intrinsically Safe
Apparatus or Associated Apparatus not specially examined in combination as a syatem using any
of the wiring methods permitted for unclassified locations,
Voc < Vmax, Ca ≥ Ci + Ccable , La ≥ Li + Lcable.

Revision date: Version Revision Page:


2019-05-01 V1R0 1/1

5333V115-UK 17
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

CSA Installation drawing 533XQC03

Hazardous area
Non Hazardous Area
T4: -40 ≤ Ta ≤ 85ºC
T6: -40 ≤ Ta ≤ 60ºC

Module 5331D, 5333D 6


Terminal: 3,4,5,6 1+
5
Only passive, or non-energy
storing devices such as RTD’s 4 2 -
and Thermocouples may be
connected 3

Barrier

Module 5335D, 5336D and 5337D


Terminal: 3,4,5,6 Terminal: 1,2
Uo: 9.6 VDC Ui: 30 VDC
Io: 28 mA Ii: 120 mA
Po: 67.2 mW Pi: 0.84 W
Lo: 35 mH Li: 10 μH
Co: 2.5 μF Ci: 1.0 nF

CLASS 2258 04 - PROCESS CONTROL EQUIPMENT - Intrinsically Safe Entity - For Hazardous
Locations
Class I, Division 1, Groups A, B, C and D
Ex ia IIC, Ga

CLASS 2258 84 - PROCESS CONTROL EQUIPMENT - Intrinsically Safe Entity - For Hazardous
Locations - Certified to US Standards
Class I, Division 1, Groups A, B, C and D
Class I, Zone 0, AEx ia IIC, Ga

Warning:
Substitution of components may impair intrinsic safety.

The transmitters must be installed in a suitable enclosure to meet installation codes stipulated in
the Canadian Electrical Code (CEC) or for US the National Electrical Code (NEC).

Revision date: Version Revision Doc. No. Page:


2014-03-31 V4R0 533XQC03 1/1

18 5333V115-UK
5333QB02
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

Desenho de Instalação INMETRO


Para instalação segura do 5333A ou 5343A o seguinte deve ser observado. O modo deve
apenas ser instalado por pessoas qualificadas que são familiarizadas com as leis nacionais e
internacionais, diretrizes e padrões que se aplicam a esta área.
Ano de fabricação pode ser pego dos dois primeiros dígitos do número de série.

Certificado DEKRA 16.0014 X

Marcas Ex nA [ic] IIC T6..T4 Gc T4: -40 ≤ Ta ≤ 85ºC


Ex ic IIC T6..T4 Gc T6: -40 ≤ Ta ≤ 60ºC
Ex ic IIIC Dc

Normas ABNT NBR IEC 60079-0 : 2013; ABNT NBR IEC 60079-11 : 2013
ABNT NBR IEC60079-15 : 2012

Terminais Ex nA [ic] Ex ic
1,2 U ≤ = 35V Ui : 35V, Ii:110mA, Ii:10µH, Ci:1,0nF
3,4,6 Uo: 5V, Io: 4mA, Po: 20mW, Lo: 900mH, Co: 1000µF

Notas para instalação

Para a instalação em uma atmosfera de gás potencialmente explosivo, se aplicam as instruções a


seguir:
Para a instalação nA o transmissor deve ser instalado em um invólucro de metal, por exemplo,
gabinete em forma B que forneça um grau de proteção de pelo menos IP54 de acordo com IEC60529
ou em um invólucro com tipo de proteção Ex n ou Ex e.
Para a instalação Ex ic o transmissor deve ser instalado em um invólucro proporcionando um grau de
proteção de IP20, pelo menos, de acordo com a norma ABNT NBR IEC 60529. E o invólucro deve ser
adequado para a aplicação e corretamente instalado.
Dispositivos de entrada de cabos e elementos de supressão devem cumprir os mesmos requisitos.
Para temperatura ambiente >= 60ºC, fios de resistência ao calor devem ser usados com uma faixa de
pelo menos 20K acima da temperatura ambiente.
Para a instalação em uma atmosfera de poeira potencialmente explosiva , se aplicam as instruções a
seguir:
O transmissor deve ser montado em invólucro de metal forma B de acordo com DIN43729 que está
fornecendo um grau de proteção de pelo menos IP6X de acordo com ABNT NBR IEC60529.
O invólucro deve ser adequado para aplicação e instalado corretamente.
As entradas dos cabos e os elementos de obturação que podem ser utilizados são adequados para a
aplicação e corretamente instalados.
A temperatura da superfície do invólucro é igual à temperatura ambiente mais 20 K, para uma
camada de pó , com uma espessura até 5 mm.

Revision date: Version Revision Page:


2016-10-28 V2R0 1/1

5333V115-UK 19
5333QB01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

Desenho de Instalação InNMETRO


Para instalação segura do 5333D ou 5343B o seguinte deve ser observado. O modo deve apenas
ser instalado por pessoas qualificadas que são familiarizadas com as leis nacionais e
internacionais, diretrizes e padrões que se aplicam a esta área.
Ano de fabricação pode ser pego dos dois primeiros dígitos do número de série.

Certificado DEKRA 16.0014 X

Marcas Ex ia IIC T6…T4 Ga


Ex ia IIIC Da

Normas ABNT NBR IEC 60079-0 : 2013; ABNT NBR IEC 60079-11 : 2013

Áreas Risco
Zona 0, 1, 2, 20, 21, 22, M1 Areas de não Risco

T4: -40 ≤ Ta ≤ 85ºC


T5: -40 ≤ Ta ≤ 60ºC
T6: -40 ≤ Ta ≤ 45ºC

6
Terminais:
3,4,5,6 5 1+
Uo: 30 VDC
Io: 8 mA 4 2 -
Po: 60 mW 5333D
Lo: 35 mH 3
5343B
Co: 66 nF
Barrier
Terminais: 1,2
Ui: 30 VDC
Ii: 120 mA
Pi: 0,84 W
Li: 10 μH
Ci: 1,0 nF

Revision date: Version Revision Page:


2016-10-28 V2R0 1/2

20 5333V115-UK
5333QB01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

Notas de Instalação.

Em uma atmosfera de gás potencialmente explosiva, o transmissor deve ser montado em um


enclousure a fim de garantir um grau de proteção de no mínimo IP20 de acordo com ABNT
NBR IEC60529. Se contudo o ambiente requer um nível de proteção maior, isso deve ser
levado em conta

Se o transmissor é instalado em uma atmosfera explosiva exigindo o uso de equipamento de


proteção de nível Ga e se o invólucro é feito de alumínio, ele deve ser instalado de modo que,
mesmo em caso de avaria rara, fontes de ignição devido a impacto e fricção, faíscas são
eliminadas; Se o enclosure é feito de materiais não metálicos, cargas eletroestáticas devem
ser evitadas.
Se o enclosure é feito de materiais não metálicos, cargas eletroestáticas devem ser evitadas.

Para instalação em atmosfera de poeira potencialmente explosiva, as instruções a seguir:

O transmissor deve ser montado em invólucro de metal forma B de acordo com DIN43729 que
está fornecendo um grau de proteção de pelo menos IP6X de acordo com ABNT NBR
IEC60529. O invólucro deve ser adequado para aplicação e instalado corretamente.

As entradas dos cabos e os elementos de obturação que podem ser utilizados são adequados
para a aplicação e corretamente instalados.

Para temperatura ambiente >= 60ºC, fios de resistência ao calor devem ser usados com uma
faixa de pelo menos 20K acima da temperatura ambiente.

A temperatura da superfície do invólucro é igual à temperatura ambiente mais de 20 K, por


uma camada de pó, com uma espessura até 5 mm.

Revision date: Version Revision Page:


2016-10-28 V2R0 2/2

5333V115-UK 21
Document history
The following list provides notes concerning revisions of this document.
Rev. ID Date Notes
111 13/45 IECEx and INMETRO approvals added.
112 15/14 PESO/CCOE approval added.
GOST approval replaced with EAC approval.
113 17/07 FM installation drawing updated.
INMETRO installation drawings updated.
114 18/48 FM installation drawing updated.
115 19/35 CSA approval for 5333A received. Installation
drawing added.
CCOE approval discontinued.

22 5333V115-UK
We are near you,
all over the world
Our trusted red boxes are supported wherever you are

All our devices are backed by expert service and a 5-year business with a global reach. This means that we are
warranty. With each product you purchase, you receive always nearby and know your local markets well.
personal technical support and guidance, day-to-day We are committed to your satisfaction and provide
delivery, repair without charge within the warranty period PERFORMANCE MADE SMARTER all around the world.
and easily accessible documentation.
For more information on our warranty program, or to meet
We are headquartered in Denmark, and have offices and with a sales representative in your region, visit
authorized partners the world over. We are a local prelectronics.com.
Benefit today from
PERFORMANCE MADE SMARTER

PR electronics is the leading technology company specialized in making industrial process


control safer, more reliable and more efficient. Since 1974, we have been dedicated to
perfecting our core competence of innovating high precision technology with low power
consumption. This dedication continues to set new standards for products communicating,
monitoring and connecting our customers’ process measurement points to their process
control systems.

Our innovative, patented technologies are derived from our extensive R&D facilities and
from having a great understanding of our customers’ needs and processes. We are guided
by principles of simplicity, focus, courage and excellence, enabling some of the world’s
greatest companies to achieve PERFORMANCE MADE SMARTER.

www.prelectronics.com

You might also like