Product Manual: 2-Wire Programmable Transmitter
Product Manual: 2-Wire Programmable Transmitter
Product Manual: 2-Wire Programmable Transmitter
MADE
SMARTER
Product manual
5333
2-wire programmable transmitter
T E M P E R AT U R E | I . S . I N T E R FA C E S | CO M M U N I C AT I O N I N T E R FA C E S | M U LT I F U N C T I O N A L | I S O L AT I O N | D I S P L AY
No. 5333V115- UK
From ser. no. 1320 9 4 0 01 - 1320 9 4 630
1411150 01
6 Product Pillars
to meet your every need
Individually outstanding, unrivalled in combination
With our innovative, patented technologies, we make signal conditioning smarter and simpler. Our portfolio is composed of six
product areas, where we offer a wide range of analog and digital devices covering over a thousand applications in industrial
and factory automation. All our products comply with or surpass the highest industry standards, ensuring reliability in even
the harshest of environments and have a 5-year warranty for greater peace of mind.
Our range of temperature transmitters and sensors provides the highest level of signal integrity from the
measurement point to your control system. You can convert industrial process temperature signals to analog, bus or
digital communications using a highly reliable point-to-point solution with a fast response time, automatic self-
calibration, sensor error detection, low drift, and top EMC performance in any environment.
We deliver the safest signals by validating our products against the toughest safety standards. Through our
commitment to innovation, we have made pioneering achievements in developing I.S. interfaces with SIL 2 Full
Assessment that are both efficient and cost-effective. Our comprehensive range of analog and digital intrinsically
safe isolation barriers offers multifunctional inputs and outputs, making PR an easy-to-implement site standard.
Our backplanes further simplify large installations and provide seamless integration to standard DCS systems.
We provide inexpensive, easy-to-use, future-ready communication interfaces that can access your PR installed base
of products. All the interfaces are detachable, have a built-in display for readout of process values and diagnostics,
and can be configured via push-buttons. Product specific functionality includes communication via Modbus and
Bluetooth and remote access using our PR Process Supervisor (PPS) application, available for iOS and Android.
Our unique range of single devices covering multiple applications is easily deployable as your site standard. Having
one variant that applies to a broad range of applications can reduce your installation time and training, and greatly
simplify spare parts management at your facilities. Our devices are designed for long-term signal accuracy, low
power consumption, immunity to electrical noise and simple programming.
Our compact, fast, high-quality 6 mm isolators are based on microprocessor technology to provide exceptional
performance and EMC-immunity for dedicated applications at a very low total cost of ownership. They can be
stacked both vertically and horizontally with no air gap separation between units required.
Our display range is characterized by its flexibility and stability. The devices meet nearly every demand for display
readout of process signals, and have universal input and power supply capabilities. They provide a real-time
measurement of your process value no matter the industry, and are engineered to provide a user-friendly and
reliable relay of information, even in demanding environments.
2-wire programmable
transmitter
5333
Table of contents
Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Technical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Mounting / installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Electrical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Mechanical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Mounting of sensor wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
ATEX Installation Drawing - 5333A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
ATEX Installation Drawing - 5333D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
IECEx Installation Drawing - 5333A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
IECEx Installation Drawing - 5333D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
FM Installation Drawing - 5333D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
CSA Installation Drawing - 5333A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
CSA Installation Drawing - 5333D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
INMETRO Installation Drawing - 5333A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
INMETRO Installation Drawing - 5333D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Document history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5333V115-UK 3
2-wire programmable transmitter
5333
Application Applications
• Linearised temperature measurement with Pt100...
Pt1000 or Ni100...Ni1000 sensor.
• Conversion of linear resistance variation to a standard 2-wire installation
in control room
analog current signal, for instance from valves or Ohmic RTD to 4...20 mA
level sensors.
Technical characteristics V+
+
• Within a few seconds the user can program PR5333 to
-
mA
measure temperatures within all RTD ranges defined by
the norms.
• The RTD and resistance inputs have cable compensation 2-wire installation
for 3-wire connection. in control room
Resistance to 4...20 mA
Mounting / installation
• For DIN form B sensor head mounting. In non-hazardous V+
+
4 5333V115-UK
Order
Type Version
Accessories
Electrical specifications
Environmental conditions:
Operating temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -40°C to +85°C
Calibration temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20...28°C
Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 95% RH (non-cond.)
Protection degree, enclosure / terminals . . . . . . . . . . . . . . . . . . . . . IP68 / IP00
Mechanical specifications:
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ø 44 x 20.2 mm
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 g
Max. wire size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 x 1.5 mm2 stranded wire
Screw terminal torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.4 Nm
Vibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IEC 60068-2-6
2...25 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±1.6 mm
25...100 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±4 g
Common specifications:
Supply voltage, DC
5333A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.0...35 VDC
5333D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.0...30 VDC
Internal power dissipation
5333A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 mW...0.8 W
5333D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 mW...0.7 W
Voltage drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.0 VDC
Warm-up time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 min.
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Loop Link
Signal / noise ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Min. 60 dB
Response time (programmable) . . . . . . . . . . . . . . . . . . . . . . . . . . 0.33...60 s
Signal dynamics, input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 bit
Signal dynamics, output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 bit
Effect of supply voltage variation . . . . . . . . . . . . . . . . . . . . . . . . . < 0.005% of span / VDC
General values
Basic values
5333V115-UK 5
Electrical specifications, input:
RTD and linear resistance input:
Output:
Current output:
Signal range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4...20 mA
Min. signal range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 mA
Updating time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135 ms
Load resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ (Vsupply - 8.0) / 0.023 [Ω]
Load stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < ±0.01% of span / 100 Ω
Sensor error detection:
Programmable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5...23 mA
Namur NE43 Upscale . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 mA
Namur NE43 Downscale . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5 mA
6 5333V115-UK
Connections
Input:
RTD, 2-wire RTD, 3-wire Resistance, 2-wire Resistance, 3-wire
3 4 6 3 4 6 3 4 6 3 4 6
Output:
2-wire installation
1 2
+ mA -
Block diagram
Supply +
1 8...35 VDC
DC
4 mA
Input + 6 DC
Lin.R
RTD C PU Comm.
M UX PGA A /D
Comp. + 4
3
Input - D /A
0...16
mA
E E PRO M
Supply -
2 mA
4...20 mA
5333
5333V115-UK 7
Programming
• Loop Link is a communications interface that is needed for programming 5333.
• For programming please refer to the drawing below and the help functions in PReset.
• Loop link is not approved for communication with modules installed in harzardous (Ex) areas.
Receiving
Disconnect Equipment
1 +Vsupply
Red * Yellow Input
2
Black * Green
5333
Connector
08:30:00
n Language O ption
O utput C om m unicatio
File Product Input PRetop 5331
2004-8-10
Date:
Serial no: 043201594
Tag no: PRelectronics
Analog output
Analog input O utput type: 4 - 20mA
Pt100 DIN/IEC
Input type: Sensor error: Upscale
0.00 - 50.00 C
Input range:
3-wire
C onnection:
L oop
p: ------
C old junction com
1.00 sec
Response time:
5909 - USB
L ink
+ -
+ -
33 mm 20.2 mm
ø 44 mm
8 5333V115-UK
5333QA02
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
For type of protection Ex nA, the transmitter shall be mounted in a metal enclosure providing a
degree of protection of at least IP54 according to EN60529.
For use in the presence of combustible dusts the transmitter shall be mounted in an enclosure
providing a degree of protection of at least IP6X in accordance with EN60529, the surface
temperature of the outer enclosure is 20 K above the ambient temperature
For an ambient temperature ≥ 60ºC, heat resistant cables shall be used with a rating of at least
20 K above the ambient temperature.
5333V115-UK 9
5333QA01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Marking
II 1 G Ex ia IIC T4...T6 Ga
II 1 D Ex ia IIIC Da
II 1 M Ex ia I Ma
Hazardous area
Zone 0, 1, 2, 20, 21, 22 Non Hazardous Area
T4: -40 ≤ Ta ≤ 85ºC
T5: -40 ≤ Ta ≤ 60ºC
T6: -40 ≤ Ta ≤ 60ºC
Terminal: 3,4,6 6
Uo: 30 VDC
Io: 8 mA 5 1+
Po: 60 mW
Lo: 35 mH 4 2 -
Co: 66 nF
3
5333D
Barrier
Terminal: 1,2
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10μH
Ci: 1.0nF
10 5333V115-UK
5333QA01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Installation notes:
For installation in a potentially explosive dust atmosphere, the following instructions apply:
The transmitter shall be mounted in a metal enclosure form B that is providing a degree of
protection of at least IP6X according to EN60529, that is suitable for the application and
correctly installed.
Cable entries and blanking elements shall be used that are suitable for the application and
correctly installed.
For an ambient temperature ≥ 60ºC, heat resistant cables shall be used with a rating of at least
20 K above the ambient temperature.
The surface temperature of the enclosure is equal to the ambient temperature plus 20 K, for a
dust layer with a thickness up to 5 mm
5333V115-UK 11
5333QI02
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Standards IEC 60079-0 : 2011, IEC 60079-11 : 2011, IEC 60079-15 : 2010
Terminal Ex nA [ic] Ex ic
1,2 Umax = 35V Ui : 35V, Ii:110mA, Ii:10µH, Ci:1,0nF
3,4,6 Uo: 5V, Io: 4mA, Po: 20mW, Lo: 900mH, Co: 1000µF
Installation note:
For installation in a potentialy explosive gas atmosphere, the following instructions apply:
For nA installation the transmitter must be installed in an metal enclosure e.g. a form B
enclosure, providing a degree of protection of at least IP54 according to IEC60529 or in an
enclosure with type of protection Ex n or Ex e.
Cable entry devices and blanking elements shall fulfill the same requirements
For an ambient temperature ≥ 60ºC, heat resistant cables shall be used with a rating of at
least 20 K above the ambient temperature.
For installation in a potentially explosive dust atmposphere, the following instructions apply:
The surface temperature of the enclosure is equal to the ambient temperature plus 20 K, for a
dust layer with a thickness up to 5 mm.
The transmitter must be mounted in a enclosure according to DIN 43729 that provides a
degree of protection of at least IP6X according to IEC60529, and that is suitable for the
application. Cable entry devices and blanking elements shall fulfill the same requirements.
12 5333V115-UK
5333QI01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Hazardous area
Zone 0, 1, 2, 20, 21, 22, M1 Non Hazardous Area
6
Terminal: 3,4,6
Uo: 30 VDC 5 1+
Io: 8 mA
Po: 60 mW 4 2 -
Lo: 35 mH 5333D
Co: 66 nF 3
5343B
Barrier
Terminal: 1,2
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10μH
Ci: 1.0nF
5333V115-UK 13
5333QI01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Installation notes.
In a potentially explosive gas atmosphere, the transmitter shall be mounted in a metal form B
enclosure in order to provide a degree of protection of at least IP20 according to IEC60529. If
however the environment requires a higher degree of protection, this shall be taken into
account.
For installation in a potentially explosive dust atmosphere, the following instructions apply:
For explosive dust atmospheres, the surface temperature of the outer enclosure is 20 K above
the ambient temperature.
The transmitter shall be mounted in a metal enclosure form B according to DIN43729 that is
providing a degree of protection of at least IP6X according to IEC60529, that is suitable for the
application and correctly installed.
Cable entries and blanking elements shall be used that are suitable for the application and
correctly installed.
For an ambient temperature ≥ 60ºC, heat resistant cables shall be used with a rating of at least
20 K above the ambient temperature.
14 5333V115-UK
5300Q502
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
FM Installation Drawing
5333V115-UK 15
5300Q502
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Equipment that is FM-approved for intrinsic safety may be connected to barriers based on the ENTITY
CONCEPT. This concept permits interconnection of approved transmitters, meters and other devices in
combinations which have not been specifically examined by FM, provided that the agency's criteria are
met. The combination is then intrinsically safe, if the entity concept is acceptable to the authority having
jurisdiction over the installation.
The entity concept criteria are as follows:
The intrinsically safe devices, other than barriers, must not be a source of power.
The maximum voltage Ui(VMAX) and current Ii(IMAX), and maximum power Pi(Pmax), which the device can
receive and remain intrinsically safe, must be equal to or greater than the voltage (Uo or VOC or Vt) and
current (Io or ISC or It) and the power Po which can be delivered by the barrier.
The sum of the maximum unprotected capacitance (Ci) for each intrinsically device and the interconnect-
ing wiring must be less than the capacitance (Ca) which can be safely connected to the barrier.
The sum of the maximum unprotected inductance (Li) for each intrinsically device and the interconnecting
wiring must be less than the inductance (La) which can be safely connected to the barrier.
The entity parameters Uo,VOC or Vt and Io,ISC or It, and Ca and La for barriers are provided by the barrier
manufacturer.
Terminal 1 , 2
Vmax : 35 V
Ci: 1.0 nF 1 2
Li:10 uH
SENSOR
16 5333V115-UK
CSA Installation drawing 5333QC02
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
For safe installation of the 5333A the following must be observed. The module shall only be installed by
qualified personnel who are familiar with the national and international laws, directives and standards that
apply to this area.
Terminal: 6 Terminal:
3,4,6 1-2
Uo: 5 VDC 5 1+ Functional Ratings:
Io: 4 mA U nominal ≤ 35 VDC;
Po: 20 mW 4 2 - I nominal ≤ 3.5 - 23 mA
Lo: 900 mH
Co: 1000μF 3
Supply
NI Installation instructions
The transmitter must be installed in an enclosure providing a degree of protection of at least IP54
according to IEC60529 that is suitable for the application and is correctly installed. Cable entry
devices and blanking elements shall fulfill the same requirements.
If the enclosure is made of non-metallic materials or of painted metal, electrostatic charging shall
be avoided.
Use supply wires with a rating of at least 5 K above the ambient temperature.
Supply from a Class 2 Power Supply with Transient protection or equivalent.
5333V115-UK 17
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Hazardous area
Non Hazardous Area
T4: -40 ≤ Ta ≤ 85ºC
T6: -40 ≤ Ta ≤ 60ºC
Barrier
CLASS 2258 04 - PROCESS CONTROL EQUIPMENT - Intrinsically Safe Entity - For Hazardous
Locations
Class I, Division 1, Groups A, B, C and D
Ex ia IIC, Ga
CLASS 2258 84 - PROCESS CONTROL EQUIPMENT - Intrinsically Safe Entity - For Hazardous
Locations - Certified to US Standards
Class I, Division 1, Groups A, B, C and D
Class I, Zone 0, AEx ia IIC, Ga
Warning:
Substitution of components may impair intrinsic safety.
The transmitters must be installed in a suitable enclosure to meet installation codes stipulated in
the Canadian Electrical Code (CEC) or for US the National Electrical Code (NEC).
18 5333V115-UK
5333QB02
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Normas ABNT NBR IEC 60079-0 : 2013; ABNT NBR IEC 60079-11 : 2013
ABNT NBR IEC60079-15 : 2012
Terminais Ex nA [ic] Ex ic
1,2 U ≤ = 35V Ui : 35V, Ii:110mA, Ii:10µH, Ci:1,0nF
3,4,6 Uo: 5V, Io: 4mA, Po: 20mW, Lo: 900mH, Co: 1000µF
5333V115-UK 19
5333QB01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Normas ABNT NBR IEC 60079-0 : 2013; ABNT NBR IEC 60079-11 : 2013
Áreas Risco
Zona 0, 1, 2, 20, 21, 22, M1 Areas de não Risco
6
Terminais:
3,4,5,6 5 1+
Uo: 30 VDC
Io: 8 mA 4 2 -
Po: 60 mW 5333D
Lo: 35 mH 3
5343B
Co: 66 nF
Barrier
Terminais: 1,2
Ui: 30 VDC
Ii: 120 mA
Pi: 0,84 W
Li: 10 μH
Ci: 1,0 nF
20 5333V115-UK
5333QB01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Notas de Instalação.
O transmissor deve ser montado em invólucro de metal forma B de acordo com DIN43729 que
está fornecendo um grau de proteção de pelo menos IP6X de acordo com ABNT NBR
IEC60529. O invólucro deve ser adequado para aplicação e instalado corretamente.
As entradas dos cabos e os elementos de obturação que podem ser utilizados são adequados
para a aplicação e corretamente instalados.
Para temperatura ambiente >= 60ºC, fios de resistência ao calor devem ser usados com uma
faixa de pelo menos 20K acima da temperatura ambiente.
5333V115-UK 21
Document history
The following list provides notes concerning revisions of this document.
Rev. ID Date Notes
111 13/45 IECEx and INMETRO approvals added.
112 15/14 PESO/CCOE approval added.
GOST approval replaced with EAC approval.
113 17/07 FM installation drawing updated.
INMETRO installation drawings updated.
114 18/48 FM installation drawing updated.
115 19/35 CSA approval for 5333A received. Installation
drawing added.
CCOE approval discontinued.
22 5333V115-UK
We are near you,
all over the world
Our trusted red boxes are supported wherever you are
All our devices are backed by expert service and a 5-year business with a global reach. This means that we are
warranty. With each product you purchase, you receive always nearby and know your local markets well.
personal technical support and guidance, day-to-day We are committed to your satisfaction and provide
delivery, repair without charge within the warranty period PERFORMANCE MADE SMARTER all around the world.
and easily accessible documentation.
For more information on our warranty program, or to meet
We are headquartered in Denmark, and have offices and with a sales representative in your region, visit
authorized partners the world over. We are a local prelectronics.com.
Benefit today from
PERFORMANCE MADE SMARTER
Our innovative, patented technologies are derived from our extensive R&D facilities and
from having a great understanding of our customers’ needs and processes. We are guided
by principles of simplicity, focus, courage and excellence, enabling some of the world’s
greatest companies to achieve PERFORMANCE MADE SMARTER.