Handbook For Electricity Metering
Handbook For Electricity Metering
1 3
HANDBOOK
FOR
ELECTRICITY
METERING
ELEVENTH EDITION
COPYRIGHT 2014 BY EDISON ELECTRIC INSTITUTE
701 Pennsylvania Avenue, N.W. Washington, D.C. 20004-2696
Eighth, Ninth, and Tenth editions entitled Handbook for Electricity Metering
Copyright 1981, 1992, 2002 and 2014 by the Edison Electric Institute
iii
iv STAFF
Randy Graham, Project Manager, Edison Electric Institute
HANDBOOK FOR ELECTRICITY METERING
Chapters 1–4
Reginald Murchison, Alabama Power Company
Darla Adams, Alabama Power Company (Assistant to Reginald Murchison)
Thomas Held, P.E., We Energies
Ken Dimpfl, American Electric Power
Gordon Belcher, Northeast Utilities
Harley Gilleland, The HarGil Group
Gary Hendley, Oncor Electric Delivery
James “Jim” West, Ameren Corp.
Terry Bates, Oncor Electric Delivery
Chapter 5
Ken Dimpfl, American Electric Power
Jerome Peplinski, P.E., MGE
Kathy Crouse, ITRON
Larry Waters, GE
Len Peaslee, SEMPRA
Lou Santilli, ITRON
Scott Weikel, Elster
Steve Wright, ITRON
Chapters 6 & 8
Tony Osmanski, PPL Utilities
Michael Anderson, Landis+Gyr
Arlin Rummel, Sensus
Brad Johnson, Oncor
Joseph Chunko, PPL Utilities
Curt Crittenden, GE
Harley Gilleland, The HarGil Group
Scott Weikel, Elster
Joe Chunko, PPL Utilities
Arlin Rummel, Sensus
Chapter 7 v
Terry Bates, Oncor
Tony Osmanski, PPL Utilities
Chapter 9
Tom Lawton, TESCO
Rob Reese, TESCO
William Hardy, PhD, PowerMeasurements
Gordon Belcher, Northeast Utilities
Chapter 10
Jim West, Ameren
Steve Bell, PPL Utilities
Russell Borchardt, Xcel Energy
Jim DeMars, Florida Power & Light
Bob Dunbar, Knopp Inc.
David Ellis, Public Service Electric & Gas
Scott Flowers, Ritz Instrument Transformers, Inc.
Harley Gilleland, The HarGil Group
Mike Haas, GE
Tim Morgan, Duke Energy
Randy Mullikin, ABB
Rudy Ogajanov, ABB
Andre Rotterbacher, Ritz Instrument Transformers, Inc.
Bryan Sonnenberg, GE
Dylan Stewart, Alstom Grid
Marcus Zickefoose, Radian Research, Inc.
Chapters 11 & 12
Thomas S. Held, P.E., We Energies
Russell Borchardt, Xcel Energy
Brian C. Teddy, P.E., Wisconsin Public Service
John Schroeder, Alliant Energy
Jerome Peplinski, P.E., Madison Gas and Electric
Robert C. Stabe, Xcel Energy
vi Chapters 13 & 14
Gordon Belcher, Northeast Utilities
Brad Johnson, Oncor
HANDBOOK FOR ELECTRICITY METERING
Chapter 15
Dan Gunderson, ALLETE – Minnesota Power
Shannon Edwards, Radian Research, Inc.
Tim Morgan, Duke Energy
Scott Weikel, Elster
Steve Schamber, Landis+Gyr
Chapter 16
Gordon Belcher, Northeast Utilities
Scott Bell, Southern Company
David Ellis, Public Service Electric & Gas
Harley Gilleland, The HarGil Group
John Grubbs, Southern Company
Vincent O’Connell, Northeast Utilities
Alan Salk, P.E., National Grid
Rick Hacket, Green Mountain Power
Chapter 17
Ellery Queen, Qtech Professional Services
David Scott, SAIC
Arlin Rummel, Sensus Metering
Ronnie Noble, Georgia Power Company
Russell Mullennix, Georgia Power Company
David Bernaudo, Southern California Edison
Mark Leach, Georgia Power Company
James Hancock, Georgia Power Company
Chapter 18
Tim Morgan, Duke Energy
David Wiseman, Duke Energy (retired)
William Hardy, PhD, Power Measurements
Alex Yan, Pacific Gas & Electric
David Ellis, Public Service Electric & Gas
Jim Thurber, Baltimore Gas & Electric Company
Shannon Edwards, Radian Research
Chapter 19 vii
Jim DeMars, Florida Power & Light
Young Nguyen, Pacific Gas & Electric
Chapter 21
Brad Johnson, Oncor
Dr. Aaron Snyder, EnerNex
Gordon Belcher, Northeast Utilities
Dan Gunderson, Minnesota Power
Contents
List of Figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xx
List of Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xxvi
List of Acronyms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xxviii
CHAPTER 1
INTRODUCTION TO THE METER DEPARTMENT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
The Electric Utility and the Community . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
The Duties of the Meter Department . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Customer Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Knowledge Required in Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Meter Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
CHAPTER 2
COMMON TERMS USED IN METERING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
CHAPTER 3
MATHEMATICS FOR METERING (A BRIEF REVIEW) . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Basic Laws of Equations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Parentheses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
The Graph . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
The Right Triangle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Trigonometric Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Scientific Notation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Complex Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Complex Numbers in Rectangular Form. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Addition and Subtraction of Complex Numbers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Multiplication of Complex Numbers in Rectangular Form. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Conjugation and Absolute Value of Complex Numbers in Rectangular Form . . . . . . . . . . . . . . 45
Division of Complex Numbers in Rectangular Form. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Complex Numbers Written in Polar Form. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Multiplication of Complex Numbers in Polar Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Division of Complex Numbers in Polar Form. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
ix
x Basic Computations Used in Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Calculating Percent Registration Using a Rotating Standard. . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Calculating Percent Registration Using Indicating Instruments. . . . . . . . . . . . . . . . . . . . . . . . . . 52
Register Formulas and Their Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
HANDBOOK FOR ELECTRICITY METERING
CHAPTER 4
ELECTRICAL CIRCUITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Direct Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Introduction to Direct Current Electric Circuits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Physical Basis for Circuit Theory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Resistance and Ohm’s Law as Applied to DC Circuits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Kirchhoff’s Current Law. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Kirchhoff’s Voltage Law . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Resistances Connected in Series. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Resistances Connected in Parallel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Resistances in Series–Parallel Circuits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Power and Energy in DC Circuits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Three-Wire Edison Distribution System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Summary of DC Circuit Formulas. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Alternating Current Single-Phase Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Introduction to Alternating Current Circuits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Sinusoidal Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Fundamental Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Phasors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Inductance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Capacitance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Resistance and Ohm’s Law as Applied to AC Circuits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Impedance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Power and Energy in Single-Phase AC Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Transformers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Harmonic Frequencies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Alternating Current Three-Phase Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Balanced Three-Phase Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Balanced Three-Phase Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Balanced Three-Phase Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Balanced Three-Phase Loads. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Per-Phase Equivalent Circuits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Power and Energy in Three-Phase AC Circuits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Power Triangle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Distribution Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Wye–Wye Transformer Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Wye–Delta Transformer Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Delta–Wye Transformer Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Delta–Delta Transformer Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
CHAPTER 5
SOLID-STATE ELECTRONICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
The Atom . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Semiconductor Electronics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Hole Current and Electron Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
N- and P-Type Materials. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
P–N Junction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Semiconductor Diode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Transistors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Digital Electronics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96 xi
Binary Digital Logic Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Memory Circuits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Microprocessors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
CONTENTS
CHAPTER 6
SERVICE SWITCH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Remote Service Switch—Introduction and Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Service Switch Features and Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Remote Service Switch Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Pre-Payment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Load Limiting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Load Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Other Benefits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Design Criteria for Internal Service Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Moving Condcutors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Electrical Contact Surfaces. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Actuators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Utility Acceptance Testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
ANSI Standard Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
CHAPTER 7
COMMUNICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Introduction—Communication Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
One-Way Communications Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Automated Meter Reading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Radio-Based Automated Meter Reading. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Network Meter Reading. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Telephone-Based Automated Meter Reading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Power Line Communications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Two-Way Communications Systems via Advanced Metering Infrastructure . . . . . . . . . . . . . . . . . 117
Power Line Communication (PLC) Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Typical Types of PLC Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Metering Substation Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Communications Media. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Protocols. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Access control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Communications to a Remote Terminal Unit (RTU). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Communications to a Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Host/Client Communications in the Substation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Home Area Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Communications Methods Used by a Home Area Network . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Applications for a Home Area Network. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Smart Energy Profile. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Head End System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Common Feature Sets and Issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
CHAPTER 8
THE SMART GRID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Smart Grid History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
19th Century . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
xii 20th Century . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
21st Century. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
What Makes a Grid “Smart?” . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
HANDBOOK FOR ELECTRICITY METERING
CHAPTER 9
INSTRUMENTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Electronic Digital Instruments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Transducers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Signal Conditioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Analog-to-Digital Converter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Common Instruments for Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
The Multimeter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Transformer Testers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Ratio Tester. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Burden Tester . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Admittance Tester. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Meter Accuracy Tester . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Communication Testing of Electric Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Meter Site Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
The Meter Site Analyzer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Instrument Transformer Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Ratio Testing with Applied Burden. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Burden-Only Testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Admittance Testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
PT Testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Meter Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
CHAPTER 10
INSTRUMENT TRANSFORMERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Conventional Instrument Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Basic Theory of Instrument Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
The Voltage Transformer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
The Current Transformer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Instrument Transformer Correction Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Ratio Correction Factor and Related Terms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Combined Ratio Correction Factor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
Phase Angle Correction Factor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
Transformer Correction Factor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
Final Correction Factor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
The Nominal Instrument Transformer Ratio. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Summary of Basic Instrument Transformer Relationships. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Compensating Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Application of Correction Factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
When Correction Factors Should Be Applied. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
Determining the Meter Adjustment in Percent Registration to Correct for Instrument
Transformer Errors—Calculations Based on Tables 10-2 and 10-3. . . . . . . . . . . . . . . . . . . . . 183
Overall Percent Error Caused by the Instrument Transformers Alone. . . . . . . . . . . . . . . . . . . . 185 xiii
Determining the Overall Percent Error by Adding the Percent Errors Caused by
Instrument Transformers and the Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
A Graphical Method of Determining the Percent Error Caused by the Instrument
CONTENTS
Transformers and the Required Compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
Application of Instrument Transformer and Watthour Standard Corrections in One Step
to a Three-Phase, Three-Stator, Four-Wire, Wye Metering Installation. . . . . . . . . . . . . . . . . 188
Application of Instrument Transformer and Watthour Standard Corrections in One Step
to a Three-Phase, Two-Stator, Three-Wire, Delta Metering Installation. . . . . . . . . . . . . . . . . 191
Summary of Basic Formulas for Applying Instrument Transformer Corrections. . . . . . . . . . . . 193
Individual Stator Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Burden Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
Voltage Transformer Burdens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
Current Transformer Burdens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Polyphase Burdens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
The Circle, or Farber, Method for Determination of Voltage Transformer Accuracy. . . . . . . . . 196
IEEE Standard Accuracy Classes for Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
High-Accuracy Instrument Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
Types of Instrument Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Current Transformers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Voltage Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Application Types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
Construction Types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
Voltage Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
Coupling Capacitive Voltage Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
Autotransformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
Current Transformers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
Selection and Application of Instrument Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
Voltage Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
Current Transformers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
Free Standing Current Transformers and Instrumentation Equipment Ratings . . . . . . . . . . . . 209
Relay Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Transformer Installation Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Current Transformer Secondaries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Precautions in Routing Secondary Leads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Instrument Transformer Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Voltage Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Current Transformers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Verification of Instrument Transformer Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
Visual Wire Tracing and Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
Wire Tracing with Instruments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
Interchanging Voltage Leads. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
Phasor Analysis of Voltages and Currents from Secondary Measurements. . . . . . . . . . . . . . . . 219
Instrument Transformer Test Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
Safety Precautions in Testing Instrument Transformers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
Insulation Tests. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
Polarity Tests. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
Tests to Verify the Marked Ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
Testing Current Transformers for Shorted Turns with a Heavy Burden. . . . . . . . . . . . . . . . . . . 222
Tests to Determine Ratio and Phase Angle. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Testing Current Transformers for Abnormal Admittance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
Testing Current Transformers for Abnormal Burden. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
Instrument Transformer Comparators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
Method. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
Precautions in Testing Instrument Transformers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
xiv Alternate Method of Testing Current Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
Traditional or Conventional Method. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
Modeling Concept as an Alternate Test Method. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
Measurement of Secondary Winding Resistance and Excitation Curve. . . . . . . . . . . . . . . . . . . 230
HANDBOOK FOR ELECTRICITY METERING
CHAPTER 11
THE WATTHOUR METER. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
The Generic Watthour Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
The Two-Wire Single-Phase Meter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
The Three-Wire Single-Phase Meter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
Multi-Element (Multi-Stator) Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
Polyphase Metering Today . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
Blondel’s Theorem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
Three-Wire Network Service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
Three-Wire, Three-Phase Delta Service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
Four-Wire, Three-Phase Wye Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
Four-Wire, Three-Phase Delta Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
Two-Element (Two-Stator), Three-Current Sensor Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260
Multi-Element (Multi-Stator) Meter Applications with Voltage Instrument Transformers . . . 260
Electromechanical Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262
The Motor in an Electromechanical Single-Stator AC Meter. . . . . . . . . . . . . . . . . . . . . . . . . . . 262
The Permanent Magnet or Magnetic Brake. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
Compensations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269
Anti-Creep Holes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273
Frequency Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273
Waveform. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 274
Meter Registers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275
Meter Rotor Bearings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275
Mechanical Construction of the Meter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275
Polyphase Electromechanical Meter Characteristics and Compensations. . . . . . . . . . . . . . . . . 277
Driving and Damping Torques. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 277
Individual-Stator Performance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 277
Current Damping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 278
Imbalanced Loads. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 278
Interference Between Stators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 278
Interference Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279
Design Considerations to Reduce Interference. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279
Multi-Stator Meter Adjustments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279
Solid-State Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281 xv
Evolution of Solid-State Metering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281
Current Sensing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
Voltage Sensing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 284
CONTENTS
Multiplication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 284
CHAPTER 12
ELECTRICITY METER TESTING AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . 291
Reference Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291
Simultaneous Multifunction Autoranging Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
Single-Function Autoranging Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
Single-Function Manual Ranging Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293
Rotating Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
Test Loading Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 295
Customer’s Load. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 295
Synthesized Loading. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 295
Phantom Loading. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 296
Resistance Load. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297
Voltage Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 298
Sensors, Counters, and Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 299
Basic Induction-Type Watthour Meter Test, Single-Stator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
Step 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
Step 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
Step 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
Step 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302
Step 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
Step 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
Step 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
Step 8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
Induction-Type Meter Adjustments, Single-Stator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
Full-Load Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
Light-Load Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
Lag Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 304
Multi-Stator, Induction-Type Meter Tests and Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 304
Electronic Meter Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305
Meter Test Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
Meter Timing and Speed Measurement Methods. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
Photoelectric Counters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
Optical Coupler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
Electricity Meter Test Fixtures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
Shop Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308
Procedure Variations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308
Single-Stator Meters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308
Multi-Stator Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309
Multi-Function Meters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310
Calibrating Constants. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310
Testing On Customers’ Premises Field Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310
Customer Relations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310
Safety Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310
Procedure Preliminary to Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311
Field Meter Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
Field Test Procedure, Single-Stator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
Field Test Procedure, Multi-Stator Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313
Instrument Transformer Meters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314
Test Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314
xvi Network Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315
Three-Phase, Four-Wire Delta, Two-Stator Meters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315
Three-Phase, Four-Wire Delta, Three-Stator Meters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316
Three-Phase, Four-Wire Wye, Three-Stator Meters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316
HANDBOOK FOR ELECTRICITY METERING
CHAPTER 13
DEMAND METERS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 319
Why Demand Is Metered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 319
Maximum Average Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320
Maximum Average Kilovoltamperes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321
General Classes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 322
Mechanical—Meter and Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 322
Integrating Type of Demand Meters—Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 322
Integrating Type of Demand Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 323
Mechanical Meter and Electronic Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 324
Electronic Demand Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 324
Electronic Time-of-Use Demand Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 329
Electronic Demand Meters with Time-of-Use and Interval Recorder . . . . . . . . . . . . . . . . . . . . 330
Electronic Meter and Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 330
Theory of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 330
Kilovar or Kilovarampere Demand Meter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 331
Coincidental Demand Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332
Methodologies in Determining Demand. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332
CHAPTER 14
DEMAND METER TESTING AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 335
Mechanical Demand Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 335
Principle of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 335
Mechanical Meter with Electronic Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338
Principle of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339
Electronic Demand Register with Time-of-Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 340
Principle of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 340
Test Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 340
Solid-State Pulse Recorders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 341
Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 341
Electronic Meter and Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 341
Principle of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 342
Test Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 342
CHAPTER 15
KILOVAR AND KILOVOLTAMPERE METERING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 345
Background . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346
Phasor Relationships . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 347
Voltampere Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 348
Electronic kVA Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 349
How Should Apparent Energy Be Measured? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 350 xvii
The Alternative Positions for “Correct Measurement”. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 350
Vectorial Versus Arithmetic kVA Calculation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 350
Delta Services: VA Metering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 352
CONTENTS
Electronic Multiquadrant Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 352
CHAPTER 16
SPECIAL METERING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357
Compensated Metering for Transformer and Line Losses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357
Why Is Compensation Desired?. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357
What Is Compensation Metering?. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357
Transformer Losses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 358
Line Loss Compensations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 358
Transformer Loss Tests. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 358
Transformer Loss Model. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 358
Bidirectional Energy Flow. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 359
No Energy Flow. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 359
Meter Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 360
Transformers with Taps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 360
Transformer Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 361
Loss Compensation Methods. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 361
Solid-State Compensation Meters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 363
Loss Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 363
Alternative Compensation Scenarios . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 370
Totalization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 374
Combining Input Circuits—CTs and/or VTs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 375
Parallel Current-Transformer Secondaries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 375
Parallel Current-Transformer Primaries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376
Multi-Stator Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376
On-Site Pulse Totalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376
Pulse Totalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376
Pulse Initiators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376
Totalizing Relays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 380
Multi-Channel Pulse Recorders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 380
Pulse Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 381
Notes on Pulse Totalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 382
Totalization Through Translation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 383
Metering Time-Controlled Loads. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 383
CHAPTER 17
METER READING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 385
How to Read a Watthour Meter and Electromechanical Meters . . . . . . . . . . . . . . . . . . . . . . . . . . 386
Register Constants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 386
Meters with Electronic Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 388
Demand Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 388
Indicating Demand Meters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 388
Electronic Demand Register Meter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 390
Sealing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 391
Recording Demand Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 391
Automatic Retrieval of Data from Solid-State Recorders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 391
Remote Meter Reading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 391
Migration from Manual Meter Reading to AMR and AMI . . . . . . . . . . . . . . . . . . . . . . . . . . . . 391
Automated Meter Reading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 391
Advanced Metering Infrastructure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 392
xviii CHAPTER 18
METER WIRING DIAGRAMS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 393
Chapter Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 393
HANDBOOK FOR ELECTRICITY METERING
CHAPTER 19
THE CUSTOMERS’ PREMISES, SERVICE, AND INSTALLATIONS . . . . . . . . . . . . . . . . . 435
The Customer’s Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 435
The Service Conductor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 435
The Service Entrance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 435
Classes of Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 436
How to Distinguish between Three-Wire Network and Three-Wire, Single-Phase Services. . . . 436
To Distinguish between Four-Wire Delta and Four-Wire Wye Service . . . . . . . . . . . . . . . . . . . 437
Overhead Service to Low Houses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 437
Circuit Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 437
Surge Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 437
Fuses and Circuit Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 437
Time-Delay Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 438
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 438
Residential Wiring Grounds. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 438
Identification of Grounded Conductor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 438
Conductor Identification by Color. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 439
Meter Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 440
Connection Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 440
Wrong Meter in the Socket Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 442
The Neutral Wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 443
What Happens if the Neutral Is Broken?. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 443
Network Neutral. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 444
Meter Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 444
Indoor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 444
Outdoor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 444
Selection of Meter Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 444
Meter Sockets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 445
Circuit-Closing Devices and Bypasses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 446
Meter Installation and Removal Socket Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 446
Socket Adapters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 447
Bottom-Connected Meters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 447
Outdoor Installations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 448
Installation of Meters with Instrument Transformers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 448
Inactive and Locked-Out Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 448 xix
Test Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 449
Instrument Transformer Metering in Metalclad Switchgear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 449
Pole-Top Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 450
CONTENTS
Good Practices For Metering Personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 450
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 452
CHAPTER 20
THE STANDARDS LABORATORY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 453
Standardization and National Metrology Laboratories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 454
Standard Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 454
Primary Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 454
Primary Transfer Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455
Secondary Standard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
Primary Watthour Standard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 457
Portable Working Standard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 457
Voltage and Current Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 458
Digital Multimeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 459
The Chain of Standardization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 459
Test Accuracy (Uncertainty) Ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 460
Standard Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 461
Accuracy (Uncertainty). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 461
Repeatability. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 461
Stability. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 461
Uncertainty. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 461
Traceability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 461
Functionality. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 461
Random (Type A) and Systematic (Type B) Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 462
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 462
Laboratory Intercomparison . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 462
Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 463
Laboratory Location and Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 463
Laboratory Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 463
CHAPTER 21
STANDARDS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 465
Introduction—What Are Standards? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 465
Who Develops Standards? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 466
American National Standards Institute . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 466
Institute of Electrical and Electronic Engineers—Standards Association . . . . . . . . . . . . . . . . . . 467
International Electrotechnical Commission. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 467
National Electric Manufacturers Association. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 468
Underwriters Laboratories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 468
Standard Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 468
Summary of Current Standards Development and Harmonization on National and
International Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 472
International Electrotechnical Commission. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 472
International Organization for Legal Metrology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 472
Measurement Canada. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 473
Underwriters Laboratories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 473
Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 474
INDEX. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 475
xx LIST OF FIGURES
Chapter 3: Mathematics for Metering (A Brief Review)
HANDBOOK FOR ELECTRICITY METERING
CONTENTS
Figure 5-9. Logic Circuit and Truth Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Figure 5-10. NOT Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Figure 5-11. AND Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Figure 5-12. OR Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Figure 5-13. NAND Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Figure 5-14. NOR Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Figure 5-15. Logic Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Figure 5-16. J–K Flip-Flop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Figure 5-17. Block Diagram of Meter Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Chapter 6: Service Switch
Figure 6-1. Paging Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Figure 6-2. AMI Mesh Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Figure 6-3. Electromechanical Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Chapter 7: Communications
Figure 7-1a. AMR Modules Installed “Under Glass” in Electromechanical Meters . . . . . . . . . . . . 114
Figure 7-1b. AMR Modules are “Built In” to Electronic Meters . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Figure 7-1c. Example of a Handheld Reader . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Figure 7-2. Multiple Communications Ports from a Single Substation Meter . . . . . . . . . . . . . . . . 120
Figure 7-3. Ethernet or Modem Gateways . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Figure 7-4. Host/Client Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Figure 7-5. Utility Managed Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Figure 7-6. Consumer Managed Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Chapter 8: The Smart Grid
Figure 8-1. National Institute of Standards and Technology (NIST) Smart Grid Framework . . . . 129
Chapter 9: Instruments
Figure 9-1. The Basic Structure of All Digital Instruments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Figure 9-2. Illustration of a Signal Sampled at 16 Times the Fundamental Frequency . . . . . . . . . 135
Figure 9-3. Illustration of a Signal Sampled at 3 Times the Fundamental Frequency . . . . . . . . . . 135
Figure 9-4. An Analog, Handheld Multimeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Figure 9-5. An Early Digital, Handheld Multimeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Figure 9-6. A Modern Digital, Handheld Multimeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Figure 9-7. A Clamp-on Current Probe for Use with a Multimeter . . . . . . . . . . . . . . . . . . . . . . . . 139
Figure 9-8. Use of a Ratio Tester . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Figure 9-9. TESCO 1044A 20A Analog Burden Tester . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Figure 9-10. UTEC 585 Digital Burden Tester . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Figure 9-11. A Typical Burden Tester Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Figure 9-12. Admittance Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Figure 9-13. Radian Research UTEC 505 Transformer Analyzer . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Figure 9-14. Spinlab 5000 Bird Dog Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Figure 9-15. Radian Research RR-DS/sm Meter Disk Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Figure 9-16. TESCO 1037-STND Optical Pickup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Figure 9-17. Radian Research RR-KYZ Pulse Input Adaptor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Figure 9-18. TESCO 995A Click Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Figure 9-19. TESCO Safety Test Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Figure 9-20. Brooks Meter Test Jack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Figure 9-21. TESCO 2200 Field Interface Kit and Socket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Figure 9-22. Radian Research RB-10 Bantam Lite . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Figure 9-23. TESCO 630 Field Test Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Figure 9-24. Spinlab 6000 Bird Dog Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Figure 9-25. Probewell MT-1/NT3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
xxii Figure 9-26. Powermetrix 4300 Field Tester . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Figure 9-27. A Typical Metering Installation (Only One Phase Shown) . . . . . . . . . . . . . . . . . . . . 147
Figure 9-28. Sample Vector Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Figure 9-29. Powermetrix PowerMaster 7302 Meter Site Analyzer . . . . . . . . . . . . . . . . . . . . . . . . . 148
HANDBOOK FOR ELECTRICITY METERING
CONTENTS
Figure 10-39. Equivalent Circuit of a CT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
Figure 10-40. Vector Diagram for the Equivalent Circuit of the CT . . . . . . . . . . . . . . . . . . . . . . . 229
Figure 10-41. Schematic Diagram of Optical Current and Voltage Sensors . . . . . . . . . . . . . . . . . 232
Figure 10-42. 72 kV Magneto-Optic Current Transducers at Sub-station . . . . . . . . . . . . . . . . . . . 233
Figure 10-43. 362 kV Optical Metering Units at Sub-station . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
Figure 10-44. 123 kV Optical Metering Unit Prototype . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
Figure 10-45. Flexible Optical Current Sensor Installed on a Power Transformer . . . . . . . . . . . . . 234
Figure 10-46. Optical Current Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Figure 10-47. Polarimetric Optical Current Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
Figure 10-48. Interferometric Current Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
Figure 10-49. Schematic Diagrams of Three Different Optical Voltage Sensor Techniques . . . . . . 238
Chapter 11: The Watthour Meter
Figure 11-1. Diagram Used in Proof of Blondel’s Theorem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
Figure 11-2. Two-Stator Meter on Three-Wire Network Service . . . . . . . . . . . . . . . . . . . . . . . . . . 251
Figure 11-3. Two-Stator Meter on Three-Phase, Three-Wire Delta Service . . . . . . . . . . . . . . . . . . 252
Figure 11-4. Three-Stator Meter on a Three-Phase, Four-Wire Wye Service . . . . . . . . . . . . . . . . . 254
Figure 11-5. Two-Stator, Three-Current-Coil Meter on Three-Phase, Four-Wire Wye Service . . . . 255
Figure 11-6. Error Curves for Equal Voltage and Current Imbalance in One Phase and for
Three Possible Locations of Z Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
Figure 11-7. Two-Stator Meter Used with Three-Current Transformers on a Three-Phase,
Four-Wire Wye Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
Figure 11-8. Three-Stator Meter on a Three-Phase, Four-Wire Delta Service . . . . . . . . . . . . . . . . . 259
Figure 11-9. Two-Stator, Three-Current-Coil Meter on a Four-Wire Delta Service . . . . . . . . . . . . 260
Figure 11-10. Wye-Circuit Voltage Transformer Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
Figure 11-11. Basic Parts of a Watthour Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
Figure 11-12. Basic Electromagnet (for Two-Wire Meter) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
Figure 11-13. Effect of a Current-Carrying Conductor in an External Magnetic Field . . . . . . . . . 264
Figure 11-14. Schematic Diagram of a Three-Wire, Single-Phase Induction
Watthour Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 264
Figure 11-15. Flux Relationships and Disk Eddy Currents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265
Figure 11-16. Voltage and Current Flux Wave Forms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266
Figure 11-17. Factors of Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269
Figure 11-18. Simplified Diagram of Magnetic Circuit of Current Element for
Overload Compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270
Figure 11-19. Overload, Voltage, and Class 2 Temperature Compensations . . . . . . . . . . . . . . . . . 271
Figure 11-20. Heavy-Load Accuracy Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 271
Figure 11-21. Light-Load Performance Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 272
Figure 11-22. Voltage Characteristic Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 272
Figure 11-23. Temperature Characteristic Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273
Figure 11-24. Frequency Curve of Modern Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 274
Figure 11-25. Clock-Type (Top) and Cyclometer-Type Meter Registers . . . . . . . . . . . . . . . . . . . . . 275
Figure 11-26. Methods of Shunting Voltage-Coil Air Gap for Torque-Balancing
Adjustment in Multi-Stator Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 280
Figure 11-27. Solid-State Watt/Watthour Transducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281
Figure 11-28. Functional Block Diagram Watt/Watthour Transducer . . . . . . . . . . . . . . . . . . . . . . 282
Figure 11-29. Hall Effect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 284
Figure 11-30. Time-Division Multiplication Waveforms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285
Figure 11-31. Hall Effect Applied to Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286
Figure 11-32. Transconductance Multiplier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286
Figure 11-33. Transconductance Multiplier Applied to Metering . . . . . . . . . . . . . . . . . . . . . . . . . . 287
Figure 11-34. Digital Multiplier Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 288
Figure 11-35. Variations on Digital Multiplier Designs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 288
Figure 11-36. Solid-State Three-Function Meter Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . 289
xxiv Chapter 12: Electricity Meter Testing and Maintenance
Figure 12-1. The Radian Research Model RD-21 Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
Figure 12-2. Block Diagram of the RD-21 Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293
HANDBOOK FOR ELECTRICITY METERING
CONTENTS
Figure 16-10. One-Line Diagram of Metering Specifications for Three
Single-Phase Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 372
Figure 16-11. Example of Parameter Listing for Combining Three
Single-Phase Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 372
Figure 16-12. One-Line Diagram of Metering Specifications for Three Winding
Tertiary Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373
Figure 16-13. Simplified Connection Diagram for Parallel-Connected,
Current-Transformer Secondaries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 375
Figure 16-14. Simplified Diagrams Illustrating Basic Two- and Three-Wire Pulse Circuits . . . . . . 377
Figure 16-15. Simplified Diagram for a Load Pulse Isolation Relay . . . . . . . . . . . . . . . . . . . . . . . . 382
Chapter 17: Meter Reading
Figure 17-1. Conventional Five-Pointer Kilowatthour Dial . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 386
Figure 17-3. Kilowatthour Register Showing Reading of 0562 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 387
Figure 17-2. Conventional Four-Pointer Kilowatthour Dial with Overlapping Circles . . . . . . . . . 387
Figure 17-4. Kilowatthour Register Showing Reading of 2198 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 387
Figure 17-5. Electronic Display, All-Segments Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 388
Figure 17-6. Electronic Display, with Prompts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 388
Figure 17-7. Watthour Demand Register, Indicating Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 389
Figure 17-8. Watthour Demand Scales Showing Various Subdivision Values . . . . . . . . . . . . . . . . 389
Figure 17-9. Watthour Demand Register, Non-Cumulative Dial Type . . . . . . . . . . . . . . . . . . . . . 390
Chapter 18: Meter Wiring Diagrams
Figure 18-1. Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 394
Figure 18-2. Single Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 399
Figure 18-3. Polyphase Self-Contained—2-Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 400
Figure 18-4. Polyphase Self-Contained—3-Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 401
Figure 18-5. Polyphase Transformer-Rated—2-Element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 402
Figure 18-6. Polyphase Transformer-Rated—2-Element, 4-Wire Delta Services . . . . . . . . . . . . . . . 403
Figure 18-7. Polyphase Transformer Rated—2-Element, 4-Wire Wye Services . . . . . . . . . . . . . . . . 404
Figure 18-8. Polyphase Transformer Rated—3-Element, 4-Wire Services . . . . . . . . . . . . . . . . . . . . 405
Figure 18-9. Single Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 406
Figure 18-10. Self-Contained 2-Element Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 407
Figure 18-11. Self-Contained 3-Element Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 408
Figure 18-12. Transformer-Rated, 2-Element Meters, 3-Wire and 4-Wire Delta . . . . . . . . . . . . . . 409
Figure 18-13. Transformer-Rated, 2-Element Meters, 4-Wire Wye . . . . . . . . . . . . . . . . . . . . . . . . 410
Figure 18-14. Transformer-Rated, 3-Element Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 411
Figure 1. 2S Meter Internals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 412
Figure 2. 2S Meter Application Schematic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 413
Figure 3. Single-Phase, 3-Wire Vector Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 414
Figure 4. 2S Errors at PF 5 1.0. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 415
Figure 5. 4-Wire Wye Metering Using 2 Stator Meters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 417
Figure 6. 4-Wire Wye Metering Using 2.5 Stator Meters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 417
Figure 7. 4-Wire Delta Metering Using 2 Stator Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 420
Figure 8. 4-Wire Delta Metering Using 2.5 Stator Meters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 420
Figure 18-15. Current and Voltage Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 423
Figure 18-16. Current Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 424
Figure 18-17. One Window Type Current Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 425
Figure 18-18. Three-Wire Network Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 426
Figure 18-19. Three-Phase, Three-Wire Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 427
Figure 18-20. Three-Phase, Three-Wire Delta Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 428
Figure 18-21. Current Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 429
Figure 18-22. Current and Voltage Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 430
xxvi Figure 18-23. Current and Voltage Transformers and Typical Test Switch . . . . . . . . . . . . . . . . . . . 431
Figure 18-24. Two Window Type Current Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 432
Figure 18-25. Self-Contained . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 433
Figure 18-26. Current Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 434
HANDBOOK FOR ELECTRICITY METERING
LIST OF TABLES
Chapter 3: Mathematics for Metering (A Brief Review)
Table 3–1. Signs of the Functions of Angles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Table 3–2. Powers of Ten . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Table 3-3. Relationship of Registration, Percent Error, and Correction Factor . . . . . . . . . . . . . . . . 52
Chapter 4: Electrical Circuits
Table 4-1. Application Frequencies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Table 4-2. Polar and Rectangular Representation of Impedance of Circuit Elements . . . . . . . . . . . 75
Table 4-3. Polar and Rectangular Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Table 4-4. Polar and Rectangular Representation of Currents in Parallel Circuits . . . . . . . . . . . . . 77
Table 4-5. Formulas for Single-Phase AC Series Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Chapter 9: Instruments xxvii
Table 9-1. Approximate Errors in Calculating the RMS Value of a Sine Wave . . . . . . . . . . . . . . . 136
Table 9-2. Common Representation Formats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
CONTENTS
Chapter 10: Instrument Transformers
Table 10-1. Definitions of Instrument Transformer Ratio, Ratio Correction Factor, and
Related Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Table 10-2. Phase Angle Correction Factors (PACFs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
Table 10-2 (continued). Phase Angle Correction Factors (PACFs) . . . . . . . . . . . . . . . . . . . . . . . . 179
Table 10-3. Phase Angle Correction Factors (PACFs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Table 10-3 (continued). Phase Angle Correction Factors (PACFs) . . . . . . . . . . . . . . . . . . . . . . . . 181
Table 10-4. Summary of Fundamental Relations for Single-Phase Metering Installations
Involving Instrument Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
Table 10-5. Maximum Percent Errors for Combinations of 0.3% IEEE Accuracy Class
Instrument Transformers under IEEE-Specified Conditions of Burden, and
Load Power Factors between 1.00 and 0.6 Lag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
Table 10-6. Calculation of Meter Accuracy Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
Table 10-7. Average Ratio and Phase Angle Calculation Sheet for Polyphase Installations . . . . . . 189
Table 10-8. Watthour Meter Test, Combined Error Calculation Sheet for Three-Stator,
Three-Phase Meters Tested Three-Phase Using Three Watthour Standards or
Single-Phase Series Using One Watthour Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
Table 10-9. Watthour Meter Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Table 10-10. Watthour Meter Test, Combined Error Calculation Sheet for Two-Stator,
Three-Phase Meters Tested Three Phase Using Two Watthour Standards . . . . . . . . . . . . . . . . . 192
Table 10-11. Summary of Basic Formulas for Applying Instrument Transformer Corrections . . . 193
Table 10-12. Methods of Expressing Burdens of Instrument Transformers . . . . . . . . . . . . . . . . . . 195
Table 10-13. IEEE Accuracy Classes for Voltage Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
Table 10-14. IEEE Standard Burdens for Voltage Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
Table 10-15. IEEE Accuracy Classes for Metering Current Transformers . . . . . . . . . . . . . . . . . . . . 200
Table 10-16. IEEE Standard Burdens for Current Transformers with
5 Ampere* Secondaries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
Table 10-17. Standard Burdens for Current Transformers Supplying Electronic Meters
and Instrumentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Chapter 12: Electricity Meter Testing and Maintenance
Table 12-1. Calibrating Constants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311
Chapter 16: Special Metering
Table 16-1. Copper-Loss Multipliers for Common Transformer Taps with
Low-Voltage Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 360
Chapter 18: Meter Wiring Diagrams
Table 18-1. Attributes of Socket Form Designations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395
Table 18-2. Attributes of Bottom Connected Form Designations . . . . . . . . . . . . . . . . . . . . . . . . . 396
Table 18-3. Application of Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 397
Table 18-4. Phasor Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 398
Table 1. Common Non-Blondel Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 413
Table 2. Errors Under Various 2S Application Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 416
Table 3. Errors Under Various 4-Wire Wye Non-Blondel Applications . . . . . . . . . . . . . . . . . . . 418
Table 4. Errors Under Various 4-Wire Delta Non-Blondel Applications . . . . . . . . . . . . . . . . . . 421
Chapter 19: The Customers’ Premises, Service, and Installations
Table 19-1. Common Installation Mistakes and Resulting Registration Errors . . . . . . . . . . . . . . . 443
xxviii LIST OF ACRONYMS
%LoL ������������������������������� percent loss of life
HANDBOOK FOR ELECTRICITY METERING
A �������������������������������������� ampere
A/D �������������������������������� analog-to-digital
AC ������������������������������������ alternating current
AEIC ������������������������������� American Energy Innovation Council
AHJ ��������������������������������� authority having jurisdiction
AMI ��������������������������������� advanced metering infrastructure
AMR �������������������������������� automated meter reading
ANSI �������������������������������� American National Standards Institute
API ����������������������������������� application programming interface
ARRA ������������������������������ American Recovery and Reinvestment Act
ASIC �������������������������������� application specific integrated circuit
AT24 �������������������������������� average 24 hour ambient temperature
BIL ����������������������������������� basic impulse insulation level
BPL ��������������������������������� broadband over power line
BTU ���������������������������������� British Thermal Unit
CCVT ������������������������������� coupling capacitor voltage transformer
CDPD ������������������������������ cellular digital packet data
CEP ��������������������������������� cycloaliphatic epoxy
CMIL ������������������������������� circular mil
COMTRADE ������������������� Common Format for Transient Data Exchange
CPR ���������������������������������� cardiopulmonary resuscitation
CPU �������������������������������� central processing unit
CRC �������������������������������� cyclic redundancy check
CT ������������������������������������ current transformer
CTR ���������������������������������� current transformer ratio
CVT ��������������������������������� capacitive voltage transformers
DA ����������������������������������� distribution automation
DC ����������������������������������� direct current
DLMS/COSEM ��������������� Device Language Message Specification/Companion Specification for
Energy Metering
DNP ������������������������������� distributed network protocol
DNP ������������������������������� distributed network protocol
DOE ��������������������������������� U.S. Department of Energy
DPF ���������������������������������� displacement power factor
DRAM ���������������������������� dynamic RAM
DSP ��������������������������������� digital signal processors
EDL ���������������������������������� exchange data language
EEI ���������������������������������� Edison Electric Institute
EEPROM ������������������������� electrically -erasable programmable read only memory
EISA 2007 ������������������������ Energy Independence and Security Act
EMF ��������������������������������� electromotive force
EMS ��������������������������������� energy management systems
EMU ������������������������������� electromagnetic unit
EOI ��������������������������������� end-of-interval indicator
EPDM ����������������������������� ethylene-propylene-diene-monomer
EPROM ���������������������������� erasable programmable read only memory
EPSEM ���������������������������� extended PSEM xxix
ES ������������������������������������ enterprise systems
EV ����������������������������������� electric vehicle
CONTENTS
F ��������������������������������������� farad
Faa ���������������������������������� aging acceleration factor
FAT ����������������������������������� first article testing
FCF ��������������������������������� final correction factor
Feqa �������������������������������� equivalent aging factor of insulation
FERC �������������������������������� Federal Energy Regulatory Commission
FLC ���������������������������������� function limiting control
FLW �������������������������������� full load watt losses
FTP ���������������������������������� file transfer process
GB ���������������������������������� gigabyte
GFCI ������������������������������� ground fault circuit interrupter
GP ����������������������������������� HomePlug Green PHY
GPS ���������������������������������� global positioning system
H �������������������������������������� henries
HAN �������������������������������� home area network
HES ��������������������������������� head end system
hp ������������������������������������ horsepower
HST ��������������������������������� hottest spot temperature
HTTP ������������������������������� hypertext transfer protocol
HVDC ������������������������������ high-voltage direct current
Hz ������������������������������������ hertz
IC ������������������������������������ integrated circuit
IEC ����������������������������������� International Electrotechnical Commission
IED ��������������������������������� intelligent electronic devices
IEEE ��������������������������������� Institute of Electrical and Electronics Engineers
IEEE-SA ���������������������������� IEEE Standards Association
IP ������������������������������������ internet protocol
ISM ��������������������������������� industrial, scientific, and medical band
IT ������������������������������������� instrument transformer; also information technology
JWG ��������������������������������� joint working groups
KCL ���������������������������������� Kirchhoff’s Current Law
Ke ������������������������������������� KYZ output constant
Kh ������������������������������������� watthour meter constant
kHz ���������������������������������� kiloHertz
Km ����������������������������������� mass memory constant
Kr ������������������������������������ register constant
Kt ������������������������������������ test constant
kVA ���������������������������������� kilovoltampere
kVAh �������������������������������� kilovoltampere hours
kVAR �������������������������������� kilovoltamperes reactive
kVARh ������������������������������ kilovoltampere reactive hours
KVL ���������������������������������� Kirchhoff’s Voltage Law
kW ����������������������������������� kilowatts
kWh ��������������������������������� kilowatthours
KYZ ���������������������������������� pulse initiator output
LAN �������������������������������� local area network
xxx LC ����������������������������������� loss compensation
LCD ��������������������������������� liquid crystal display
LED ���������������������������������� light emitting diode
HANDBOOK FOR ELECTRICITY METERING
CONTENTS
Rr ������������������������������������ watthour meter register ratio
RTU ��������������������������������� remote terminal unit
SCADA ����������������������������� supervisory control and data acquisition
SE ������������������������������������ service entrance
SEP ���������������������������������� Smart Energy Profile
SEP2 ��������������������������������� Smart Energy Profile 2.0
SMMAA ��������������������������� Smart Meter Manufacturers’ Association of America
SRAM ������������������������������ static RAM
TA ������������������������������������ test ampere
TC ������������������������������������ technical committee
TCF ��������������������������������� transformer correction factor
TCP ��������������������������������� transmission control protocol
TCP/IP ���������������������������� transmission control protocol/internet protocol
TDL ���������������������������������� task description language; also table definition language
TDM �������������������������������� time-division-multiplier
THD �������������������������������� total harmonic distortion
TOU ��������������������������������� time-of-use
TPE ���������������������������������� thermoplastic elastomers
TWACS ��������������������������� two-way automatic communications system
UART ������������������������������ universal asynchronous receiver and transmitter
UL ������������������������������������ Underwriters Laboratories
UOM ������������������������������ unit of measure
V �������������������������������������� ohm
V �������������������������������������� volt
VA ������������������������������������ voltampere
VAh ���������������������������������� voltampere hours
VAR ���������������������������������� voltamperes reactive
VARh �������������������������������� voltampere reactive hours
VPN �������������������������������� virtual private network
VT ������������������������������������ voltage transformer
VTR ���������������������������������� voltage transformer ratio
W ������������������������������������� watt
WAN ������������������������������� wide area network
WG ���������������������������������� working group
Wh ����������������������������������� watthour
XML ��������������������������������� extensible markup language
ZSE ��������������������������������� ZigBee Smart Energy 1.x
µF ������������������������������������� microfarad
Chapter 1
Introduction to the
Meter Department
The Electric Utility and the Community
THE ELECTRIC COMPANY and the community which it serves are permanently interdependent. An
electric company, by the nature of its business, cannot pick up its generating plant, transmission, or
distribution system and move to a different community. It is firmly rooted where it is located. Its prog-
ress depends to a large extent upon the progress of the area it serves, as well as upon the respect and
active support of its customers. It makes good sense for the electric company to work cordially and
cooperatively with its customers toward the improvement of economic and civic conditions. Because
of this, the meter reader or meter technician must be aware that they represent the “Company”when
calling on a customer’s home or business.
What the electric company sells and/or delivers has become essential to the point that loss of
electric power causes more than inconvenience; it can mean real hardship, even tragedy. In addition,
large quantities of electricity cannot be produced and stored and so must be immediately available in
sufficient quantities upon demand. What this means is that we sell and/or deliver not only the com-
modity of electric energy but also a very valuable service.
The service performed by the electric company and its employees should be such that every mem-
ber of the company and the community can be proud of it.
1
2 of all test equipment must be traceable to the basic and legal standards of electrical measurement
maintained by the National Institute of Standards and Technology (NIST). Quality of workmanship
and adherence to procedures must be consistently maintained at a level which will achieve this desired
accuracy. Poor workmanship or deviation from procedures can have a serious effect on the customer
Handbook for Electricity Metering
and the company. Standards, procedures, and instructions are essential to ensure uniformity of opera-
tions and to prevent errors, as well as for overall safety and economy.
Customer Contacts
Due to the electric company’s place in the community and since members of the meter department
may frequently meet customers face-to-face, it is important that all meter personnel exemplify those
qualities of integrity and courtesy which generate confidence in the company. Day-to-day contacts
with customers provide these employees with exceptional opportunities to serve as goodwill ambas-
sadors and may earn public appreciation for the services that they and their company perform. To
achieve this appreciation, employees must demonstrate a sincere desire to be helpful and show high
ethical standards in the performance of their work.
However, in many companies, the increase in outdoor meters as well as the implementation of
automated meter reading systems has resulted in a decrease in the meetings between customers and
company employees. Therefore, every effort should be made to make a good first impression with the
customer through any available area of customer contact.
First impressions are often lasting impressions. It is desirable that meter personnel look their best
so that a good image of the company they represent will be left in the customer’s mind. Neatness and
cleanliness are of utmost importance. The little things which customers notice may have considerable
influence on the company’s reputation.
Visits to a customer’s premises for meter reading, testing, or for other reasons, afford opportuni-
ties for personnel to demonstrate the company’s interest in the customer’s welfare. Courteous consid-
eration of every request will create satisfaction and appreciation of the efforts made by the company to
render good service to its customers.
Please note, however, that customers should be referred to the appropriate department or per-
son for answers to all questions on rates, billing, or any other matter which is outside the meter
employee’s area of expertise. Promises requiring action beyond the employee’s own capability should
be avoided. In practically all cases, assurance that any request will be conveyed to the proper party will
satisfy the customer.
Upon entering a customer’s premises, meter personnel should make their presence and busi-
ness known and should cheerfully present their identification card, badge, or other credentials
when requested. All work done on customers’ premises should be planned carefully and carried out
promptly. While on customers’ premises, conversations between company personnel should only be
about the work at hand and should not be argumentative.
If utility personnel notice any unusual conditions on the customer’s premises or in the immedi-
ate vicinity which might affect safety, the company’s system, or the customer’s electric service, utility
personnel should report the conditions promptly to their immediate supervisors.
Telephone conversations with customers, like premise visits, can go a long way toward express-
ing the company’s interest in the customer. Phone conversations should always be conducted with
patience, intelligence, and understanding, and in a courteous tone of voice.
Meter Security
As the cost of electricity rises, so does the temptation to violate the security of metering equipment for
the purpose of energy theft. Therefore, the meter employee must be aware of the various techniques
of energy theft and be constantly on the lookout for such violations. Since meter security systems vary
throughout the industry, it is necessary for meter employees to familiarize themselves with their com-
pany’s policy for securing meters and associated devices. Incidents of tampering should be reported
immediately and in accordance with company instructions, taking care to preserve all evidence and to
submit complete, well documented reports.
Circumstantial evidence of tampering should not be interpreted as guilt until all evidence has
been examined by those designated to do so. Therefore, courtesy toward all customers, even in strained
circumstances, will speak well for you, your department, and your company.
Meter security begins with the seal that secures the glass cover to the base of the meter. This
seal is applied without a tool and offers no interference when installing the meter. After the meter
is installed, a seal must be applied to secure the meter mounting device, whether that device is the
ring-type or ringless. Ring-type sockets are secured by sealing the ring that holds the meter in place.
Ringless sockets are secured by installing the socket cover after the meter is in place, then sealing the
cover hasp.
The demand reset mechanism also needs to be secured with a seal to prevent undetected tamper-
ing. It should be sealed each time the demand is reset. If a different color seal is used each reading
cycle, there is assurance that the demand was reset at the end of the last cycle.
To be sure your company’s sealing program maintains its integrity, seals should be treated as
security items. Only authorized personnel should have access to seals, and they should not be left
where unauthorized people would come in contact with them.
The most important part of the sealing procedure is the follow-up. Every time the meter is read,
the seal should be inspected both visually and physically. This seal should be tugged on and visually
inspected to make sure it has not been tampered with and that it is the proper seal for that meter.
Evidence of tampering should be reported immediately.
4 There are a wide variety of seals. Some require tools for installation, while others do not. Some are
all metal, some all plastic, and some a combination of both. Whatever seal is used, however, it should
offer the following benefits:
Handbook for Electricity Metering
Safety
Safety is a full-time business and requires the hard work and full cooperation of every meter employee.
Safety procedures are measures which, if followed, will enable personnel to work without injury to
themselves or others and without damage to property.
Simply issuing safety procedures or rules does not guarantee safe work practices or produce good
safety records. Meter employees must learn the safety rules of their company, apply them daily, and
become safety-minded.
Meter personnel owe it to themselves, their families, and their company to do each step of every
job the safe way. Careful planning of every job is essential. Nothing should be taken for granted.
The meter employee must take responsibility for his/her own safety. Constant awareness of safety is
needed, coupled with training, experience, and knowledge.
Some common safety rules are:
• Horseplay and practical jokes are dangerous. Work safely, consider each act, and do nothing to
cause an accident.
• Knowledge of safe practices and methods, first aid, and cardiopulmonary resuscitation (CPR) is
a must for meter personnel.
• Beware of your surroundings and alert to unsafe conditions.
• Report unsafe conditions or defective equipment to your immediate supervisor without delay.
• Treat injuries immediately.
• Report all accidents as prescribed by company safety rules.
• Complete a job hazard analysis when appropriate before beginning a job. Re-assess when some-
thing unexpected happens during the job.
• Exercise general care and orderliness in performance of work.
• The right way is the safe way. Do not take short cuts.
• Study the job! Plan ahead! Prevent accidents!
• Select the right tools for the job and use them properly.
• Keep tools in good working order.
• Use personal protective equipment when appropriate.
• Use the appropriately-rated category of clothing for protection from arc flash incidents.
• Exercise good housekeeping at all times.
• Handle material with care. Lift and carry properly.
• Respect secondary voltage. It can be fatal.
• Never substitute assumptions for facts.
• Be knowledgeable about the safe operation of automotive vehicles.
Chapter 2
Common Terms
Used In Metering
THE FOLLOWING DEFINITIONS are to be considered as practical, common understandings. In order
to keep the explanations as clear and simple as possible, occasional departures from exact definitions
have been permitted. The explanations given are intended to be useful for meter personnel rather than
for scientists. For additional definitions, see the current version of American National Standards Insti-
tute (ANSI) C12.1 Code for Electricity Metering, Definitions Section, and ANSI/Industry of Electrical
and Electronics Engineers (IEEE) 100-1988, Standard Dictionary of Electrical and Electronics Terms.
A-Base
See Bottom-Connected Meter.
Accuracy
The extent to which a given measurement agrees with the defined value.
Advanced Metering Infrastructure (AMI)
AMI is the communications hardware, software, and associated system and data management software
that creates a network between advanced meters and utility business systems. It allows for the collec-
tion and distribution of information to the utility and its customers, as well as to other parties (e.g.,
competitive retail providers).
Also, according to FERC, advanced metering is a metering system that records customer consump-
tion (and possibly other parameters) hourly or more frequently and that provides for daily or more
frequent transmittal of measurements over a communication network to a central collection point.
Alternate Display
A display sequence usually containing constants and diagnostic information.
Ammeter
An instrument to measure current flow, usually indicating amperes. Where indication is in mill
amperes, the instrument may be called a milliammeter.
Ampere
The practical unit of electric current. One ampere is the current caused to flow through a resistance of
1 ohm by 1 volt.
Ampere-Hour
The average quantity of electric current flowing in a circuit for one hour.
Ampere-Turn
A unit of magneto motive force equal to that produced by one ampere flowing in a single turn of wire.
5
6 AMI Communication Module
A physical hardware device that enables two-way and end-to-end communications capabilities between
an end device (such as a meter) and the utility. AMI communication modules service layers 4-1 of the
Open System Interconnection (OSI) 7-layer protocol stack.
Handbook for Electricity Metering
The bypass feature refers to a load-rated current path built into the meter socket in
parallel with the meter. The normal condition of the bypass is open, so all load cur-
rent flows through the meter. When closed, the bypass shunts load current around
the meter. This allows the meter to be removed for testing or replacement without
interrupting service to the customer. The bypass is not rated for breaking load. It
must not be opened under load except when a meter is in place. Bypass sockets are
useful for commercial and industrial customers whose loads do not require CTs or
VTs. An additional feature of the bypass mechanism is that it provides clamping
pressure at its jaws to secure the meter blades. The bypass releases the pressure on the
meter blades in the abnormal, or closed, position, facilitating the removal or insertion of the meter.
Calibration
Comparison of the indication of the instrument under test, or registration of meter under test, with
an appropriate standard.
Capacitance
That property of an electric circuit which allows storage of energy and exists whenever two conductors
are in close proximity to each other but are separated by an insulator or dielectric material. When
direct voltage is impressed on the conductors, a current flows momentarily while energy is being stored
in the dielectric material, but stops when electrical equilibrium is reached. With an alternating volt-
age between the conductors, the capacitive energy is transferred to and from the dielectric materials,
resulting in an alternating current flow in the circuit.
Capacitive Reactance
Reactance due to capacitance, which is expressed in ohms. The capacitive reactance varies indirectly
with frequency.
Catastrophic Failure, a.k.a. Fatal Failure
A failure that results in temporary or permanent disruption of communication, corruption of protocol,
corruption of data, unexpected manipulation of data, delivery of wrong data, unexpected data format,
or incorrect placement of data within transported record. The assessment is performed by a reference
implementation (a test that is based upon the registered end device table data model).
Central Station
Control equipment, typically a computer system, which communicates with metering and load control
devices. The equipment may also interpret and process data, accept input from other sources, and
prepare reports.
Certified Meter Type
A metering device which is tested and certified to meet the certification testing as specified in the
standard for a specific meter type. It includes any optional circuit boards, devices, or modules enclosed
within the meter cover as part of the certified meter type.
Circuit, Three-Wire
A metallic circuit formed by three conductors insulated from each other. See Three-Wire System.
Circuit, Two-Wire
A metallic circuit formed by two adjacent conductors insulated from each other. When serving domes-
tic loads, one of these wires is usually grounded.
Circuit Breaker
A device, other than a fuse, designed to open a circuit when an overload or short circuit occurs.
The circuit breaker may be reset after the conditions which caused the breaker to open have been
corrected.
Circular Mil
The area of a circle whose diameter is one mil (1/1000 inches) or approximately 0.7854 millionths of
a square inch. The area of a circle in circular mils is equal to the square of its diameter in mils.
Class Amperes 9
The maximum continuous current at which a meter can operate without exceeding its rated accuracy
limits. Typical self-contained meters are Class 200, Class 320, or Class 400; meters for use with cur-
rent transformers are Class 10 or Class 20.
Creepage Distance
Shortest distance measured over the surface of insulation between conductive parts.
CT VT Ratio or CT VT
A factor representing the product of the current transformer ratio and the voltage transformer ratio.
Also called the dial constant.
Example:
If a meter is connected to 7200:120 volt VTs (60:1) and 400:5 amp CTs (80:1), the CT VT ratio
is 60 80 4800.
A meter installation may have CTs and no VTs in which case the CT VT ratio is just the CT ratio
(expressed as equivalent ratio to 1). For a transformer rated meter, the meter multiplier equals the CT
VT Ratio. For modern electronic transformer rated meters, the demand multiplier also equals the CT
VT Ratio.
Current Circuit
Internal connections of the meter and part of the measuring element through which flows the current
of the circuit to which the meter is connected.
Current Coil
The coil of a watthour meter through which a magnetic field is produced that is proportional to the
amount of current being drawn by the customer.
Current Transformer
An instrument transformer designed for the measurement or control of current. Its primary winding,
which may be a single turn or bus bar, is connected in series with the load. It is normally used to
reduce primary current by a known ratio to within the range of a connected measuring device.
Current Transformer (CT)
A high accuracy transformer that converts load current to another (usually smaller) value by some
fixed ratio. The industry refers to a CT in terms of its nameplate primary current as a ratio to five
amps secondary current. (e.g., 400:5). A CT is not necessarily limited to this nameplate current. See
Rating Factor. Also see Bar, Window, and Wound-type CTs.
Current Transformer, Continuous Thermal Current Rating Factor
The factor by which the rated primary current is multiplied to obtain the maximum allowable primary
current based on the maximum permissible temperature rise on a continuous basis.
Current Transformer Phase Angle
The angle between the current leaving the identified secondary terminal and the current entering the
identified primary terminal. This angle is considered positive when the secondary current leads the
primary current.
Customer Alert
A switching output used to indicate events or conditions.
Cutout
A means of disconnecting an electric circuit. The cutout generally consists of a fuse block and latching
device or switch.
Cycle
One complete set of positive and negative values of an alternating current or voltage. These values
repeat themselves at regular intervals (see Hertz).
Damping of an Instrument 11
A term which denotes the manner in which a pointer settles to its steady indication after a change
in the value of the measured quantity. Two general classes of damped motion are distinguished as
follows:
Demand Delay
The programmable amount of time before demand calculations are restarted after a power outage. Also
called Cold Load Pickup and Demand Forgiveness.
Demand Deviation
The difference between the indicated or recorded demand and the true demand, expressed as a per-
centage of the full scale value of the demand meter or demand register.
Demand Energy
The rate of energy usage averaged over some period of time (typically fifteen minutes). Commonly
expressed as Kilowatthours per Hour Kilowatts. For further explanation, see Demand and Demand
Metering.
Demand Factor
The ratio of the maximum demand to the connected load.
Demand Interval (Block-Interval Demand Meter)
The specified interval of time in which a demand measurement is based. Intervals such as 10, 15, or
60 minutes are commonly specified.
Demand Interval Deviation
The difference between the measured demand interval and the specified demand interval, expressed as
a percentage of the specified demand interval.
Demand Interval—Rolling (RDI)
An interval of time, the beginning of which progresses in steps of sub-intervals and where the interval
length is equal to an integer multiple of sub-intervals.
Demand Interval Synchronization
Physical linking of meters to synchronize the demand intervals of all meters. Also called Demand
Timing Pulse.
Demand—Maximum
The highest demand measured over a selected period of time.
Demand Meter
A metering device that indicates or records the demand, maximum demand, or both. Since demand
involves both an electrical factor and a time factor, mechanisms responsive to each of these factors
are required, as well as an indicating or recording mechanism. These mechanisms may be separate or
structurally combined with one another.
Demand Meter, Indicating
A demand meter equipped with a readout that indicates demand, maximum demand, or both.
Demand Meter, Integrating (Block-Interval)
A meter that integrates power or a related quantity over a fixed time interval and indicates or records
the average.
Demand Meter, Lagged
A meter that indicates demand by means of thermal or mechanical devices having an approximately
exponential response.
Demand Meter, Time Characteristic (Thermal or Lagged-Demand Meter)
The nominal time required for 90% of the final indication, with constant load suddenly applied. The
time characteristic of lagged-demand meters describes the exponential response of the meter to the
applied load. The response of the lagged-demand meter to the load is continuous and independent of
selected discrete time intervals.
Demand Meter, Timing Deviation 13
The difference between the elapsed time indicated by the timing element and the true elapsed time,
expressed as a percent of the true elapsed time.
by utilities such as electric, water, and transportation companies. For more information, see
www.dnp.org.
Diversity
A result of variation in time of use of connected electrical equipment so that the total maximum
demand is less than the sum of the maximum demands of the individual units.
Eddy Currents
Those currents that result from voltages which are introduced in a conducting material by a variation
of magnetic flux through the material.
Effective Resistance
Equal to watts divided by the square of the effective value of current.
Effective Value (Root-Mean-Square Value)
The effective value of a periodic quantity is the square root of the average of the squares of the instan-
taneous value of the quantity taken throughout one period. This value is also called the root-mean-
square value and is the value normally reported by alternating current instruments.
Electrical Degree
The 360th part of one complete alternating current cycle.
Electricity Meter
A device that measures and records the summation of an electrical quantity over a period of time.
Electromagnet
A magnet whose magnetic field is produced by an electric current. A common form of electromagnet
is a coil of wire wound on a laminated iron core, such as the voltage coil of a watthour meter stator.
Electromechanical Meter
A meter in which currents in fixed coils react with the currents induced in the conducting moving
element, generally a disk(s), which causes their movement proportional to the energy to be measured.
Also called induction watthour meter.
Electromotive Force (EMF)
The force which produces an electric current in a circuit. The common unit of electromotive force is
the volt.
Electronic Storage Register
An electronic circuit where data is stored for display and/or retrieval.
Element
A combination of a voltage-sensing unit and a current-sensing unit which provides an output pro-
portional to the quantities measured. Electricity meters normally include 1, 1½, 2, 2½, or 3 elements.
The 2½-element meter refers to 2-stator 4-wire wye meter as described in section A.2.7.2. The three-
wire element is a single element using the sum of two current circuits and one potential circuit. For
example, if one input signal is voltage and the other input signal is current, then the output is power
(watts). Also known as stator.
Embedded Coil
A coil in close proximity to, and nested within, a current circuit loop of a meter used to measure the
strength of a magnetic field and develop a voltage proportional to the flow of current.
Embedded System
A microcomputer system including microprocessor, memory, power supply, and supporting input and
output devices, usually designed for a dedicated application.
End Device
The closest device to the sensor or control point within a metering application communication system
which is compliant with the Utility Industry End Device Data Tables (ANSI C12.19-2008, Sec. 3.30).
End-of-Interval Indicator (EOI) 15
An indicator for the end of the demand interval for non-rolling (block)—interval demand, or the end
of the sub-interval for rolling-interval demand.
As its name implies, a multiform meter can take the place of multiple forms from this list. Two com-
mon multiform meters are Form 15/16 and Form 8/9.
The form number will sometimes be followed by an alphabetic suffix, such as Form 9S or Form
5A. The ‘S’ refers to a socket-base meter, while the ‘A’ refers to an A-base meter. See Meter Bases.
Full Load
A current level for testing the accuracy of a watthour meter, typically indicated on a meter by the
abbreviation “TA,” for test amps.
Function Limiting Control (FLC)
ANSI C12.19 Function Limiting Control Tables (X0/X1, where X is the decade number 0-204).
Galvanometer
An instrument for indicating a small electric current.
Gear Ratio
The number of revolutions of the rotating element of a meter compared to one revolution of the first
dial pointer.
Ground
A conducting connection, whether intentional or accidental, between an electric circuit or equipment
and earth.
Ground Return Circuit
A current in which the earth is utilized to complete the circuit.
Grounding Conductor
A conductor used to connect any equipment device or wiring system with a grounding electrode or
electrodes.
Grounding Electrode
A conductor embedded in the earth which has conductors connected to it to maintain a ground
potential and to dissipate current into the earth.
Head-end
An application associated with both one-way and two-way metering and end point systems that
provides some of the following features:
1. Manages the communication network for meters and end points.
2. Manages the collection of data.
3. Allows operators of the system to extract data and send commands to meters and end points.
4. Supplies metering and associated data to enterprise systems, such as a Mobile Device Manage-
ment (MDM).
Henry 17
The practical unit of inductance. The millihenry is commonly encountered. The common unit of
inductance is the millihenry.
Inductive Reactance
Reactance due to inductance expressed in ohms. The inductive reactance varies directly with the
frequency.
Instrument Transformer
A transformer that reproduces in its secondary circuit in a definite and known proportion the voltage
or current of its primary circuit with the phase relation substantially preserved.
Instrument Transformer (IT)
General name for the family of CTs and VTs used in metering and relaying.
Instrument Transformer, Accuracy Class
The limits of transformer correction factor in terms of percent error that have been established to
cover specific performance ranges for line power factor conditions between 1.0 and 0.6 lag.
Instrument Transformer, Accuracy Rating for Metering
The accuracy class together with the standard burden for which the accuracy class applies.
Instrument Transformer, Burden
The impedance of the circuit connected to the secondary winding. For voltage transformers it is con-
venient to express the burden in terms of the equivalent voltamperes and power factor at its specified
voltage and frequency.
Instrument Transformer, Correction Factor
The factor by which the reading of a wattmeter or the registration of a watthour meter must be multi-
plied to correct for the effects of the error in ratio and the phase angle of the instrument transformer.
This factor is the product of the ratio and phase angle correction factors for the existing conditions of
operation.
Instrument Transformer, Marked Ratio
The ratio of the rated primary value to the rated secondary value as stated on the transformer’s
nameplate.
Instrument Transformer, Phase Angle
The angle between the current or voltage leaving the identified secondary terminal and the current or
voltage entering the identified primary terminal. This angle is considered positive when the secondary
circuit or voltage leads the primary current or voltage.
Instrument Transformer, Phase Angle Correction Factor
The factor by which the reading of a wattmeter or the registration of a watthour meter, operated
from the secondary of a current transformer, or a voltage transformer, or both, must be multiplied
to correct for the effect of phase displacement of secondary current, or voltage, or both, with respect
to primary values. This factor equals the ratio of true power factor to apparent power factor and is a
function of the phase angle of the instrument transformer as well as the power factor of the primary
circuit being measured.
Instrument Transformer, Ratio Correction Factor
The factor by which the marked ratio of a current transformer or a voltage transformer must be
multiplied to obtain the true ratio. This factor is expressed as the ratio of true ratio to marked ratio. If
both the current transformer and the voltage transformer are used in conjunction with a wattmeter or
watthour meter, the resultant ratio correction factor is the product of the individual ratio correction
factors.
Instrument Transformer, True Ratio
The ratio of the magnitude of the primary quantity (voltage or current) to the magnitude of the cor-
responding secondary quantity.
Interface
The means for transmitting information between the meter or register and peripheral equipment.
Interval Data 19
Some meters are capable of generating periodic data, typically kWH (and kVARh, if applicable).
The data is synchronized to the 15 minute intervals that the meter uses for measuring demand. A
meter can send this data as pulses to a customer or to an external device or can save the data in its
That portion of the design of a watthour meter which provides favorable performance and accuracy
over a wide range of loads. In modern, self-contained meters, this load range extends from load cur-
rents under 10% of the rated meter test amperes to 667% of the test amperes for class 200 meters.
Load Control
A procedure for turning off portions of customers’ loads based on predetermined time schedules,
system demand thresholds, or other circumstances.
Load Factor
The ratio of average load over a designated time period to the maximum demand occurring in that
period.
Load Profile
The recording, storage, and analysis of consumption, demand, and other sensory data over a period of
time, using ANSI C12.19 load profile tables from Decade 6 (Standard Tables 60–69).
Loading Transformer
A transformer of low secondary voltage, usually provided with means for obtaining various definite
values of current, whereby the current circuit of the device under test and of the test standard can be
energized.
Loss Compensation
A means for correcting the reading of a meter when the metering point and point of service are physi-
cally separated, resulting in measurable losses, including iron core and I2R losses in conductors and
transformers. These losses may be added to, or subtracted from, the meter registration.
Magnetic
A region of magnetic influence surrounding a magnet or a conductor carrying electric current.
Magneto Motive Force
The force which produces magnetic flux. The magneto motive force resulting from a current is directly
proportional to the current.
Manufacturer (Supplied) Tables
Tables defined by the manufacturer of the C12.19 meter. Manufacturer table descriptions shall use
table description syntax. These tables shall be available and readable and used for configuration, setup,
and data storage of component data and only for processes not already fully or partially covered by
ANSI C12.19.
Mega
A prefix meaning one million of a specified unit (megawatt, megohm). 1 megohm 1,000,000 ohms.
Memory
Electronic devices which store digital information such as computer instructions and data.
(a) Volatile memory can be written to and read from repeatedly. Random access memory (RAM)
requires uninterrupted power to retain its contents.
(b) Non-volatile memory, also known as Read Only Memory (ROM), is able to retain informa-
tion in the absence of power. ROMs are programmed, may only be read repeatedly, and are
typically used to store firmware in dedicated systems.
Meter
A device that measures the amount of electrical, gas, or water utility commodities supplied, generated,
or consumed. Some or all values measured by these meters may be used for the purpose of billing.
Meter, Excess
A meter that records, either exclusively or separately, that portion of the energy consumption taken at
a demand in excess of a predetermined demand.
Meter Bases 21
Meters are manufactured in several physical configurations, the most common of which is the socket-
base meter. The socket-base meter has blade terminals on the back that plug into corresponding jaw
terminals in the meter socket. Another configuration is the A-base meter, in which the typical round
A prefix meaning one thousandth part of a specified unit (milliampere, millihenry, millivolt).
1 millivolt 0.001 volt.
Modbus
A serial communication protocol originally published by Modicon® for use with its programmable
logic controllers (PLCs). It has become a de facto standard protocol in industry, commonly used to
interconnect industrial electronic devices. Modbus is often used to connect a master computer with
a remote terminal unit (RTU) in supervisory control and data acquisition (SCADA) systems. Modbus
supports serial and transmission control protocol (TCP), or Ethernet, connections. For more informa-
tion, see www.modbus.org.
Modem
An internal or external device used to modulate/demodulate (or transfer) electronic data between two
locations.
Multiform Meter
Recent designs of electronic meters are of a type known as multiform. This refers to the meter’s
wide-range voltage capability (a single meter can operate on circuits from less than 120 volts up to
277 volts) and its ability to operate on multiple wiring configurations known as meter forms. For
example, one multiform meter can be used on 120/208 volt 4-wire wye, 120/240 volt 4-wire delta,
and 277/480 volt 4-wire wye services. The remaining options for the meter are whether it needs to
be transformer rated (Form 8/9) or self-contained (Form 15/16), whether or not it needs to measure
reactive power, and how it should be programmed.
Multi-Function Meter
A meter that displays more than one electricity-related quantity. Typically an electronic meter.
Multi-Rate Meter
An energy meter provided with a number of registers, each becoming operative at specified time
intervals corresponding to different tariff rates.
National Electrical Code (NEC)
A regulation covering the electric wiring systems on the customer’s premises, particularly in regard to
safety. The code represents the consensus of expert opinion as to the practical method and materials
of electrical equipment installation to provide for the safety of people and property.
Net Metering
A method of metering that might be used at meter points where power is expected to flow in either
direction. That is, where we expect to deliver power to the customer at times as well as receive power
at other times. Examples include (1) a conventional customer who installs sufficient generation that it
can feed power back into APC’s system, or (2) a system interconnect meter point (e.g., a transmission
intertie) where power flow can be in either direction. The net meter “sees” both received and delivered
quantities but does not register them separately. Instead, it treats a delivered quantity as a positive
value and a received quantity as a negative value and sums the two to create the net value. This net
value is the only one saved by the meter.
Net metering allows a customer to net the energy produced by its generating facility against the
energy received from its electric service provider. The power flow measurement performed by net
metering is |delivered|—|received|.
Contrast this to bi-directional metering.
Normal Mode
The operating mode of the register usually displaying the billing data.
Ohm
The practical unit of electrical resistance. It is the resistance which allows one ampere to flow when
the impressed electromotive force is one volt.
Ohm’s Law 23
Ohm’s Law states that the current which flows in an electrical circuit is directly proportional to the
electromotive force impressed on the circuit and inversely proportional to the resistance in a direct
current circuit or the impedance in an alternating current circuit.
Phasor (Vector)
A quantity which has magnitude, direction, and time relationship. Phasors are used to represent
sinusoidal voltages and currents by plotting on rectangular coordinates. If the phasors were allowed
to rotate about the origin and a plot was made of ordinates against rotation time, the instantaneous
sinusoidal wave form would be represented by the phasor.
Phasor Diagram
A phasor diagram contains two or more phasors drawn to scale showing the relative magnitude and
phase or time relationships among the various voltages and currents.
Photoelectric Tester (or Counter)
A device used in the shop testing of meters to compare the revolutions of a watthour meter standard
with a meter under test. The device receives pulses from a photoelectric pickup which is actuated by
the anti-creep holes in the meter disk or the black spots on the disk. These pulses are used to control
the standard meter revolutions on an accuracy indicator by means of various relay and electronic
circuits.
Ping Relative to AMI
Ping relative to AMI is a head-end administration utility used to test the reachability of an end point,
typically the meter. The PING utility confirms reachability of the end point with a minimum of data
transport information.
Polarity
The relative direction of current or voltage in a circuit at a given instant in time.
Polarity marks on CTs and VTs indicate a relationship between the primary and secondary wind-
ings of the transformers. On a CT, when current enters the primary polarity terminal, a secondary
current in phase with the primary will leave the secondary polarity terminal. On a VT, when a primary
voltage is applied from the polarity to the non-polarity terminal, a voltage in phase with the primary
will be produced on the secondary from polarity to non-polarity terminal. Wiring diagrams indicate
polarity marks for both CTs and VTs. Incorrect wiring with respect to polarity marks can result in
reverse flow or incorrect registration in single-phase and three-phase meters.
Potential Transformer (PT)
See Voltage Transformer.
Power, Active
The time average of the instantaneous power over one period of the wave. For sinusoidal quantities
in a two-wire circuit, it is the product of the voltage, the current, and the cosine of the phase angle
between them. For nonsinusoidal quantities, it is the sum of all the harmonic components, each
determined as above. In a polyphase circuit, it is the sum of the active powers of the individual phases.
Power, Apparent
The product of the root-mean-square current and root-mean-square voltage for any waveform. For
sinusoidal quantities, apparent power is the square root of the sum of the squares of the active and
reactive powers.
Power, Reactive
For sinusoidal quantities in a two-wire circuit, reactive power is the product of the voltage, the cur-
rent, and the sine of the phase angle between them with the current taken as reference. With non-
sinusoidal quantities, it is the sum of all the harmonic components, each determined as above. In a
polyphase circuit, it is the sum of the reactive powers of the individual phases.
Power Factor
The ratio of the active power to the apparent power.
Power Line Carrier
A type of communication where data may be transmitted through existing electrical power lines.
Precision 25
The repeatability of measurement data, customarily expressed in terms of standard deviation.
Pre-Wired Socket
Self-Contained Meter
A watthour meter that is connected directly to the supply voltage and is in series with the customer
loads; a meter designed for installation directly in a customer’s service circuit. The meter is connected
such that full service current passes through it and full service voltage is applied across its terminals.
Typical self-contained meters operate at 120, 240, or 277 volts and as high as 480 amps continuous
rating. The most common of these is the Class 200, 120/240 volt, single-phase, 3-wire meter used on
most residences. Also see Transformer Rated Meter.
Service
The conductors and equipment for delivering electric energy from a street distribution system to, and
including, the service equipment of the premises served.
Service Conductors
The conductors which extend from a street distribution system, transformers on private property, or
a private generating plant outside the building served, to the point of connection with the service
equipment.
Service Drop
That portion of the overhead service conductors between the last pole or other aerial support and the
first point of attachment to the building or structure.
Service Entrance (SE) Cable
A service entrance cable usually consists of two conductors with conventional insulation laid parallel
with a third stranded bare neutral conductor (which may or may not be insulated). The final covering
is a flame retarding and waterproof braid. ASE cable is a variant of the SE cable in which a flat steel
strip is inserted between the neutral conductor and the outside braid.
Service Entrance Conductors
For an overhead service, that portion of the service conductors which connect the service drop to the
service equipment. The service entrance conductors for an underground service are that portion of the
service conductors between the terminal box located on either the inside or outside building wall, or
the point of entrance in the building if no terminal box is installed, and the service equipment.
Service Equipment
The necessary equipment, usually consisting of one or more circuit breakers or switches and fuses, and
their accessories, intended to constitute the main control and means of disconnecting the load from
the supply source.
Shaft Reduction (Spindle Reduction, First Reduction)
The gear reduction between the shaft or spindle of the rotating element and the first gear of the
register.
Shop, Meter
A place where meters are inspected, repaired, tested, and adjusted.
Short Circuit
A fault in an electric circuit, instrument, or utilization equipment such that the current follows a
lower resistance by-pass instead of its intended course.
Simulated Meter
A meter cover, base, and jumper bars constructed to represent the thermal characteristics of a specific
class of watthour meter to be used in the testing of a meter socket and in determining the empirical
temperature rise of the test meter at continuous ampere rating.
Socket (Trough)
The mounting device consisting of jaws, connectors, and enclosure for socket-type meters. A mounting
device may be a single socket or a trough. The socket may have a cast or drawn enclosure, the trough
an assembled enclosure which may be extensible to accommodate more than one mounting unit.
Socket-Connected Meter 29
A meter having a socket-type of connection terminal assembly. Also referred to as an S-base electricity
meter.
A test made during the period that the meter is in service. It may be made on the customer’s premises
without removing the meter from its mounting, or by removing the meter for test either on the
premises or in a laboratory or meter shop.
Test—Accuracy—Referee
A test made by or in the presence of one or more representatives of a regulatory body or other impar-
tial agency.
Test—Accuracy—Request
A test made at the request of a customer.
Test Amperes (TA)
The load current specified by the manufacturer for the main calibration adjustment and the current
level used as a base for measuring registration accuracy. Typical TA for a Class 200 meter is 30 amps
and for a Class 20 meter is 5 amps.
Test—Approval
A test of one or more meters or other items under various controlled conditions to ascertain the
item’s compliance with the appropriate standard.
Test Mode
A separately-activated sequence that saves billing data while displaying test data. It reactivates the
billing data to the register when the normal mode is resumed.
Test Output
An output signal, optical, mechanical, or electrical, which provides a means to check calibration level
and verify operation of the meter.
Test—Switch
A device that can be opened to isolate a watthour meter from the voltage and current supplying it so
that tests or maintenance can be performed.
Testing, Periodic Sample
A testing method which conforms to acceptable testing practices whereby a meter is tested on a regular
reoccurring schedule based on either characteristics of the meter/meter type or service.
Testing, Statistical Sample
A testing method which conforms to accepted principles of statistical sampling based on either the
variables or attributes method. The following expressions are associated with statistical sample testing:
(a) Method of Attributes—A statistical sample testing method in which only the percent of
meters tested found outside certain accuracy limits is used for determining the quality or
accuracy of the entire group of meters.
(b) Method of Variables—A statistical sample testing method in which the accuracy of each
meter tested is used in the total results for determining the quality or accuracy of the entire
group of meters.
(c) Bar X—A mathematical term used to indicate the average accuracy of a group of meters
tested.
(d) Sigma—A mathematical term used to indicate the dispersion of the test results about the
average accuracy (Bar X) of a group of meters tested.
Thermocouple
A pair of dissimilar conductors so joined that two junctions are formed. An electromotive force is
developed by the thermoelectric effect when the two junctions are at different temperatures.
Thermoelectric Effect (Seebeck Effect)
One in which an electromotive force results from a difference of temperature between two junctions
of dissimilar metals in the same circuit.
Thermoelectric Laws 31
(1) The thermoelectromotive force is, for the same pair of metals, proportional through a consid-
erable range of temperature to the excess of temperature of the junction over the rest of the
Totalizing
A device used to receive and sum pulses from two or more sources for proportional transmission to
either another totalizing relay or to a receiver.
Transducer
A device to receive energy from one system and supply energy, of either the same or a different kind,
to another system, in such a manner that the desired characteristics of the energy input appear at the
output.
Transformer
An electric device without moving parts which transfers energy from one circuit to one or more other
circuits by means of electromagnetic fields. The name implies, unless otherwise described, that there is
complete electrical isolation among all windings of a transformer, in contrast to an auto-transformer.
Transformer—Loss Compensation
A method that adds to or subtracts from the meter registration to compensate for predetermined iron
and/or copper losses of transformers and transmission lines.
Transformer-Rated Meter
A watthour meter that requires external instrument transformer(s) to isolate or step-down the cur-
rent and, possibly, the voltage. This meter is designed to operate with reduced levels of current (and
sometimes voltage) that are directly proportional to the service current and voltage. The transformer-
rated meter is isolated from the current (and voltage) levels present in the customer’s service. Typical
transformer-rated meters operate at 120, 240, or 277 volts and 0–10 or 0–20 amps. Also see Self-
Contained Meter.
Transformer Ratio
A ratio that expresses the fixed relationship between the primary and secondary windings of a
transformer.
Translation
The term translation originally referred to the computerized process of reading meter interval data
recorded on magnetic tape and converting it to energy and demand information. The computer that
performs this function is known as the translator. In addition, the translator provides high levels of
data security and validation and manages the scheduling of automatic remote meter data downloads.
Today, most recording is done in solid state memory. When tape cartridges had to previously be
mailed to a central location for translation, faster means of retrieving the recorded data are now used,
including:
• Direct telephone communications between the translator and the meter.
• Downloading the meter data into a laptop computer and transferring the data to the translator
via modem.
• Downloading to a laptop and transferring the data via computer network.
Another form of translation is offered via software that can download interval data (remotely or via
direct connection) from various meters and generate load profiles, usage reports, and estimated bills.
Refer to the listing on Interval Data for the many uses of translated information.
Transocket
A high-capacity meter socket combining the advantages of a CT meter installation with the simplicity
of a self-contained meter socket. It contains current transformers and factory-installed meter wiring to
a socket for a standard transformer-rated meter.
Unit of Measure (UOM)
The unit of measure provides a method for describing a billing/trade quantity or selecting data source
attributes. Some of the attributes include the physical quantity measured, the time base used for
averaging, the scaling constants, direction of flow, method of measurement, and harmonic component
indication.
Upgrade/Upgrade Process 33
The series of communication steps required to replace or modify the existing operating firmware of a
meter and/or its associated communication and metrology components. The upgrade process does not
require the removal of the meter and/or its associated communication and metrology components
37
38 which simplifies to
ITotal 2 I1 2 I3 5 I2
The preceding example illustrates another general rule which states that any complete term may be
Handbook for Electricity Metering
shifted from one side of an equation to the other by changing its sign. This must be a complete term
or the equation is no longer true. In the example, the 1I1 and 1I3 terms were shifted from the right to
left side, where they then became negative.
To summarize:
If x 5 2y, and C is any constant except zero, then the following equations are also true:
x 1 C 5 2y 1 C
x 2 C 5 2y 2 C
Cx 5 2Cy
—x 5—2y
C C
Parentheses
In an expression such as IR1 1 IR2 1 IR3, the subscripts 1, 2, and 3 after the symbol R indicate that
R does not necessarily have the same value in each term. Since the symbol I does not have subscripts,
it does have the same value in each term. Such a series can be written I(R1 1 R2 1 R3), which means
that the total quantity inside the parentheses is to be multiplied by I.
The equation V 5 IR1 1 IR2 1 IR3 states that the voltage across three resistors in series is equal to
the sum of the products of the current times each of the resistances. If V, R1, R2, and R3 are all known
and the value of I is wanted, the equation may be rearranged as follows:
V 5 IR1 1 IR2 1 IR3
V 5 I(R1 1 R2 1 R3)
Dividing both sides by (R1 1 R2 1 R3) gives
V
———————————— 5 I
(R1 1 R2 1 R3)
When removing parentheses, pay attention to the laws of signs. These laws are summarized as
follows:
a 3 b 5 ab
a 3 (2b) 5 2ab
2a 3 b 5 2ab
2a 3 (2b) 5 ab
No sign before a term implies a 1 sign.
A minus sign before a parenthetical expression is equivalent to multiplication by 21 and means
that all signs within the parentheses must be changed when the parentheses are removed.
The Graph
A graph is a pictorial representation of the relationship between the magnitudes of two quantities. A
graph may represent a mathematical equation, or the relationship between the quantities may be such
that it cannot be expressed by a simple equation.
An example of a graph which may be used in metering is the calibration curve for an indicating
instrument. Figure 3-1 shows a typical graph of voltmeter corrections. When the voltmeter reads 120
volts, reference to the correction curve shows that, at this point (marked X in Figure 3-1), the correc-
tion to be applied is 11 volt and the true voltage is 121 volts. With a scale reading of 100 volts, the
correction is 10.5 volts, shown by , and the true voltage is 100.5. With a scale reading of 70 volts,
the correction is 20.5 volts, shown by , to give 69.5 true volts.
The sine wave has important applications in alternating-current circuit theory. The equation of
a sine wave, y 5 sin x, is shown graphically in Figure 3-2. The x quantity is commonly expressed in
angular degrees or radians and the y values, which are plotted on the graph, are the sine values of
39
the corresponding angles. Thus, for any particular angular value, it is possible to use the graph to
determine its sine. For example, the sine of 30 degrees is equal to 0.5, as shown by the dotted lines on
Figure 3-2.
the solution of alternating-current problems requiring the use of trigonometric functions, the follow-
ing tabulation of their definitions and relationships will be useful.
In the right triangle shown in Figure 3-3, side a is opposite angle A; side b is adjacent to angle A;
side a is adjacent to angle B; and side b is opposite angle B. The ratios between the length of the sides
of the triangle determine the trigonometric functions of the angle A.
By definition, the ratios are named:
a opposite
— 5 —————–——— 5 sine A or sin A
c hypotenuse
b adjacent
— 5 —————–——— 5 cosine A or cos A
c hypotenuse
a opposite
— 5 —————–——— 5 tangent A or tan A
b adjacent
Similarly:
a
b b 3 a — c sin A
cos A 5 — 5 ————— 5 —— 5 —————
a tan
c c 3 a — A
b
a
a — c sin A
tan A 5 — 5 —— 5 —————
b — b cos A
c
While —a is the sine of A, it is also the cosine of B, since a is adjacent to angle B. Therefore, it will
c
be seen that:
sin A 5 cos B
cos A 5 sin B
Numerical values for the functions of every angle are computed from the ratios of the sides of a
right triangle containing that angle. In a right triangle, which is a triangle containing one right (90°)
angle, the sum of the other two angles must equal 90°, since the sum of the three angles of any
triangle must be 180°. Also, the sum of the squares of the two shorter sides must equal the square of
the longer side, or hypotenuse (the side opposite the 90° angle). Regardless of the values which may
be assigned to the sides of a right triangle, the ratio of any two sides for any given angle is always the
same.
The functions of 30° and 60° may be derived from Figure 3-4. The triangle ABC of Figure 3-4
is equilateral (all sides equal). Therefore, it is also equiangular (all angles equal), so that each angle
equals 60°.
If a line is drawn from the midpoint of the base to the vertex as shown, then b9 5 ½ and angle
B9 5 30°. In the triangle AB9C9:
1
—
b9 2 1
sin 30° 5 cos 60° 5 —— 5 — 5 — 5 0.500
c 1 2
1
1 2 —
a9 12 2(—2
) 23 1
cos 30° 5 sin 60° 5 —— 5 ————————— 5 ———— 5 —
3 5 0.866
c 1 1 2
b9
—c— b9 1/2
sin 30° 1
tan 30° 5 —————— 5 —— 5 — 5 ————— 5 ———— 5 0.577
cos 30° a9 a9 — 1
3 3
—c— 2
41
c a
side opposite
angle A
b
side adjacent angle B
Figure 3-3. The Right Triangle. Figure 3-4. Functions of 30° and 60°.
The functions of 45° may be derived from Figure 3-5. In this triangle, a 5 b 5 1, and
c 5
a2 1
b2 5 2. From geometry, angle A must equal angle B, or half of 90°, which is 45°.
1 2
sin A 5 sin B 5 sin 45° 5 ———— 5 ———— 5 0.707
2 2
1 2
cos A 5 cos B 5 cos 45° 5———— 5 ———— 5 0.707
2 2
1
tan A 5 tan B 5 tan 45° 5 —— 5 1 5 1.000
1
To determine the functions of an angle greater than 90° and less than 180°, subtract the given
angle from 180° and refer to a table of functions. For an angle greater than 180° and less than 270°,
subtract 180° from the angle and refer to the table. For an angle greater than 270° and less than
360°, subtract the angle from 360° and refer to the table.
The algebraic sign of the functions of all angles between 0 and 90° is positive (1); beyond 90°
the signs can be determined from Table 3-1.
From the preceding formulas, it is evident that if two sides of a right triangle are known, the third
side as well as the angles can be calculated. Also, if one side and either angle A or B are known, the
other sides and angle can be calculated.
Example 1:
To find a, given c and b: a 5
c2 2
b2
To find a, given c and A: a 5 c 3 sin A
a
To find b, given a and A: b 5 ———
tan A
a or cos21 a/c
To find B, given a and c: B 5 angle whose cosine is —
c
In electric circuits with single non-distorted frequencies, the voltamperes, watts, and voltampere
reactives (VARs) are in proportion to the sides of a right triangle and may be represented as shown in
Figure 3-6. Trigonometry may also be used to calculate these quantities.
watts
Power factor 5 cosine of phase angle θ 5 ——————————
voltamperes
Example 2:
Voltmeter reads 120, ammeter 5, wattmeter 300.
300 5 0.5
pf 5 ———
600
Power factor 5 50%
In the above example, a lagging or leading power factor is not specified because it is unknown
whether the load is inductive or capacitive. If the load is inductive, the power factor is lagging, and if
the load is capacitive, the power factor is leading. This topic is covered in more detail in Chapter 4.
From Figure 3-6:
VARS VARhours
Tangent of phase angle: tan θ 5 ————— 5 —————————
watts watthours
Example 3: 43
If the VARhour meter reads 3733 and the watthour meter reads 9395, what is the average power
factor?
watts 5
(volt amp)2 2 (VARs)2
To find power factor, given VARs and voltamperes:
VARs
Power factor 5 cosine of angle whose sine 5 ——————
voltamp
To find VARs, given power factor and watts:
θ 5 angle whose cosine equals the power factor
VARs 5 watts 3 tan θ
To find voltamperes, given power factor and VARs:
θ 5 angle whose cosine equals the power factor
VARs
voltamperes 5 ————
sin θ
Scientific Notation
Scientific notation is a form of mathematical shorthand. It is a method of indicating a number that
has a large number of zeroes before or after the decimal point and is based on the theory of expo-
nents. Some powers of ten are shown in Table 3-2.
Any number may be expressed as a power of ten by applying the following rules:
1. To express a decimal fraction as a whole number times a power of ten, move the decimal point
to the right and count the number of places back to the original position of the decimal point.
The number of places moved is the correct negative power of ten.
Example 4:
0.00756 5 7.56 3 103
0.000095 5 9.5 3 105
0.866 5 86.6 3 102
0.0866 5 86.6 3 103
Example 5:
746. 5 7.46 3 102
95. 5 9.5 3 101
866. 5 86.6 3 101
8,660. 5 8.66 3 103
Complex Numbers
Complex numbers are a special extension of our real number system. All complex numbers can be
represented as points in the complex plane, as shown in Figure 3-7. The real axis, horizontal from left
to right, can only represent real numbers. The j, or imaginary axis, vertical from bottom to top, can
only represent imaginary numbers. For all other complex numbers having a real part and an imaginary
part, we can plot their coordinates in the complex plane as shown.
To subtract the same two complex numbers, subtract the real parts and the imaginary parts
separately.
j or Imaginary axis
jy 5 j1 •
z 5 1 1 j1 5 x 1 jy 5 (1,1)
or Real axis
Figure 3-7. Complex Number z 5 1 1 j1 Represented by a Single Point in the Complex Plane.
Example 7: 45
If z1 5 2 1 j3 and z2 5 25 2 j4, then find z1 2 z2.
Solution:
Example 8:
If z1 5 a 1 jb 5 7 1 j1 and z2 5 c 1 jd 5 23 1 j8, then find z1 z2.
Solution:
z1z2 5 (7 1 j1)(23 1 j8) 5 221 1 j56 2 j3 1 j28
5 221 2 8 1 j56 2 j3
5 229 1 j53
Example 9:
If z 5 0 1 jb, then what is z2?
Solution:
z2 5 z?z 5 (0 1 jb)(0 1 jb) 5 0 1 0 1 0 1 j2b2 5 2b2.
j or Imaginary axis
• z 5 1 1 j1 5 x 1 yj 5 (1,1)
Real axis
•
z* 5 1 2 j1 5 x 2 jy 5 (1,21)
z* 5 24 2 j(25) 5 24 1 j5
Example 11:
What is the conjugate of z 5 12?
Solution:
Since z 5 12 is the same as z 5 12 1 j0, then z* 5 12 2 j0 5 12. Thus, the conjugate of a
complex number with no imaginary part is just that number.
Example 12:
What do we get if we compute the product of z and its conjugate z*?
Solution:
If z 5 x 1 jy and z* 5 x 2 jy, then zz* 5 (x 1 jy)(x 2 jy) 5 x2 2 jxy 1 jyx 2 j2y2
zz* 5 x2 1 y2 since the second and third terms cancel each other and j2 5 21.
z1
(
a 1 jb
—— 5 ————–
z2 c 1 jd )(————–
c jd )
c jd
j or Imaginary axis
z 5 1 1 j1 5 |z| /_θ_ 5
2 /_45
__
jy 5 j1 |z|
θ
Real axis
x51
Example 14:
Write the imaginary number z 5 j in polar form.
Solution:
Since z 5 j 5 21 5 0 1 j1, then |z| 5 12) 5 1. What is the angle θ?
(02 1
It is the inverse tangent of the imaginary part divided by the real part of z. That is,
θ 5 tan21 (1/0). What angle does θ make with the positive real axis? What is the angle from the
positive real axis to the positive imaginary axis? We must move through the angle of 90°. Thus,
z 5 j 5 21 5 0 1 j1 5 1 / _90°.
___
j or Imaginary axis
θ
Real axis
x50
j or Imaginary axis
Real axis
x 5 21 θ 5 2180°
Example 16:
Write the imaginary number z 5 1 in polar form.
Solution:
Since z 5 1 5 1 1 j0, then |z| 5 [(1)2
1 0
2
] 5 1. What is the angle θ? It is the inverse
tangent of the imaginary part divided by the real part of z. That is, θ 5 tan21 (0/1). What angle
does θ make with the positive real axis? What is the angle from the positive real axis to the
positive real axis? We must move through the angle of 0°. Thus, z 5 1 5 1 1 j0 5 1 / _0°.
__
(See Figure 3-9d.)
j or Imaginary axis
jy 5 j0
θ 5 0°
Real axis
x51
z1z2 5 |z1||z2|/
_(θ1 1 θ2)
Example 17:
Let z1 5 2 1 j3 and z2 5 24 2 j5. Find the product z1z2.
Solution:
Convert z1 and z2 to polar form.
|z1| 5
(22 1
32) 5
13 3.61
The angle of z1 is θ1 5 tan21 (3/2) 5 56.3°. |z2| 5 2(25
[(24)
1 )2] 5 41 6.40.
The angle of z2 is θ2 5 tan ( /24) 5 231.3°.
21 25
When finding the arc-tangent or inverse tangent of an angle (i.e., tan21θ), most calculators will
return a “principal” angle between 290° and 190°. Thus, as long as a complex number is in quad-
rant I or IV, no adjustment is ever necessary. However, if the complex number is in quadrants II or III,
the 180° adjustment may be necessary.
For instance, in the above example, the use of a calculator in determining the angle θ2 will result
in θ2 5 51.3°. However, the complex number z2 is in quadrant III. When x , 0 and y , 0, the num-
ber is in quadrant III and the angle must lie between 180° and 270°. To determine the correct angle
in quadrant III from the angle the calculator returned, add 180°. Thus, 51.3° 1 180° 5 231.3°.
Example 18:
Let z1 5 2 1 j3 and z2 5 24 2 j5. Find z1/z2.
Solution:
First convert from rectangular to polar:
13
z1 5 32 /
22 1 _ta
__n_2_— 5 3.61 /
_56.
_____
3°
2
1 24
z2 5
(24)
2
(25
1 )
2
/_t_a_n_2_——
25
5 6.40 /
_23
_____
1.
_3
z1 3.61
—— 5 ———
z2 6.40
/_(56.3° 2 231.3°) 5 0.56 /_2____ 5 20.56 2 j0.05
_175°
Note that this is the same result as obtained in Example 13. The answer for both examples is the
same, but the calculation in polar coordinates is much easier to perform.
50 Example 19:
Let z1 5 2 2 j6 and z2 5 5 /30°. Find z1z2.
____
Solution:
Handbook for Electricity Metering
When multiplying or dividing two complex numbers, both of them should be in polar form. In
this example, the first number is not in polar form but the second is. First, convert z1 to polar
form.
z1 5 6.32 /_271.5
_____ ° or 6.32 /
___ _288.4°
____
Both are correct. Next, multiply the magnitudes and add the phase angles.
z1z2 5 (6.32)(5) /
_(288.44° 1 30°) 5 31.62 /
_318.4
___
______
3° (or 241.6°) 5 23.66 2j20.98
Example 20:
What is z1/z2?
Solution:
Divide the magnitudes and subtract the phase angles. Then,
z1/z2 5 (6.32)/(5) /_(288.4° 2 30°) 5 1.26 /
_258.4
___
__
____
°
Example 21:
Given three complex numbers, z1 5 6 2 j2, z2 5 7/___ and z3 5 10 /
_15°, _2.2°.
___
(a) Find |z1z2|.
Solution:
|z1z2| 5 |(6 2 j2)(7/___ 5 |(6.32 /
_15°)| ______)(7/
_218.4° _15°)|
___ 5
|(6.32)(7)|/
_(218.4 1 15)5 44.2 /
_23.
___4
__
When adding or subtracting complex numbers, the rectangular form should be used because the
real and imaginary parts can be added and subtracted separately. When multiplying or dividing com-
plex numbers, the polar form should be used because the magnitudes are multiplied or divided and
the angles are added or subtracted.
To understand and analyze alternating current circuits, it is mandatory to master the mathematics 51
of complex numbers. When analyzing these circuits, the various techniques require changes between
rectangular and polar format. Tables 3-1 and 3-2 provide examples of how the mathematics of this
chapter relate to the representation of electrical components and circuit variables. The analysis of
10.80
Percent registration 5 ————— 3 100 5 99.4%
10.87
It is frequently easier to mentally calculate the percent error of the meter and then to add it
algebraically to 100% to determine the percent registration of the meter.
Ro 2 R
Percent error 5 —————— 3 100
R
52 Using the same values as in the preceding example, then,
10.80210.87
Percent error 5 —————————— 3 100 5 20.6%, and
10.87
Handbook for Electricity Metering
The percent error of the rotating standard is calculated and applied to the indicated percent of
meter registration to determine the true percent meter registration.
Percent meter registration 5 indicated percent meter registration 1 percent standard error. The
percent standard error is added to the apparent percent registration of the meter under test if the
percent standard error is positive and subtracted if negative. Then, for this example,
Percent standard error 5 99.5% 2 100% 5 20.5%
Referring to computations made earlier, if a rotating standard with a 20.5% error is used, then
percent registration of the meter is 99.4% 2 0.5% 5 98.9%. Use this method when the percent error
does not exceed 3%.
36.00 3 100
Percent registration 5 —————————— 5 99.4%
36.23
The correction for instrument error may be applied similarly to the correction for rotating stan-
dards, where P equals the observed reading of the wattmeter.
Assume the observed reading of a wattmeter is 7,200 watts and true watts are 7,236. Then the
wattmeter indicates:
7,200
————— 5 99.5% of true watts.
7,236
This percent indication may be used for A in the formula:
kh 3 r 3 3,600 3 A
Percent registration 5 ————————————————
P3S
If the preceding meter had been a direct-current meter, the test could have been made with a
voltmeter and ammeter.
Assume an observed ammeter reading of 30 amperes and true current is 30.2 amperes. Then:
30
Percent indication 5 ———— 3 100 5 99.3%
30.2
Assume an observed voltmeter reading of a 240 volts, and true voltage is 239.5 volts. Then:
240
Percent indication 5 ————— 3 100 5 100.2%
239.5
Indicated watts 5 240 3 30 5 7,200 watts
Actual watts 5 239.5 3 30.2 5 7,233 watts
7,200
Percent indication 5 ————— 3 100 5 99.5%
7,233
Again, the 99.5% calculated could be used for A in the formula, the same as the 99.5% obtained
as the percent indication of the wattmeter.
In either case, the percent registration is the sum of the apparent percent indication and the
percent error. The percent registration 5 99.4% 1 (20.5%) 5 98.9%.
54 Register Formulas and Their Applications
Rr 5 register ratio
Kh 5 watthour constant
Handbook for Electricity Metering
Rs 5 gear reduction between worm or spur gear on disk shaft and meshing gear wheel
of register
Kr 5 register constant
Rg 5 gear ratio 5 Rr 3 Rs
CTR 5 current transformer ratio
VTR 5 voltage transformer ratio
TR 5 transformer ratio (CTR 3 VTR)
PKh 5 primary watthour constant 5 Kh 3 TR
Example 25:
Self-contained meter, Kh 5 7.2, 100 teeth on first wheel or register, 1 pitch worm on shaft,
register constant 10.
To find the register ratio:
10,000 3 Kr 10,000 3 10
Rr 5 —————————— 5 —————————— 5 1388/9
Kh 3 Rs 3 TR 7.2 3 100 3 1
To check the register constant:
Kh 3 Rr 3 Rs 3 TR 7. 2 3 1388/9 3 10 0 3 1
Kr 5 —————————————— 5 ——————————————————— 5 10
10,000 10,000
To determine the gear reduction:
Rg 5 Rr 3 Rs
100 1,250
Rg 5 1388/9 3 ———— 5 ————— 3 100 5 13,8888/9
1 9
Example 26:
Transformer-rated meter installed with 400/5 (80/1) current transformer ratio (CTR), register
constant (Kr) 100, Kh 5 1.8, 100 teeth on first wheel, 2 pitch worm on shaft.
10,000 3 Kr 10,000 3 Kr 10,000 3 100
Rr 5 ————————— 5 ———————————— 5 —————————————— 5 1388/9
PKh 3 Rs (Kh 3 TR) 3 Rs 100
(1.8 3 80) 3 ———
2
PKh 3 Rr 3 Rs (Kh 3 TR) 3 Rr 3 Rs
Kr 5 ——————————— 5 ————————————————
10,000 10,000
100
(1.8 3 80) 3 1388/9 3 ———
2 5 100
5 —————————————————————
10,000
100 1,250
Rg 5 1388/9 3 ———— 5 ————— 3 50 5 6,9444/9
2 9
Example 27:
Transformer-rated meter installed with 50/5 (10/1) CTR, 14,400/120 (120/1) voltage trans-
former ratio (VTR), register constant (Kr) 1,000, Kh 5 0.6, and 100 teeth on first wheel, with
1 pitch worm on shaft.
10,000 3 1,000
Rr 5 ————————————————— 5 1388/9
0.6 3 10 3 120 3 100
0.6 3 10 3 120 3 1388/9 3 100
Kr 5 ———————————————————————— 5 1,000
10,000
1,250
Rg 5 1388/9 3 100 5 ————— 3 100 5 13,8888/9
9
Chapter 4
Electrical Circuits
Direct Current
Introduction To Direct current Electric Circuits
DIRECT CURRENT (DC) electric circuits are those where the applied voltage and current do not
change with time; they are constant or fixed values. An example of a DC electric circuit is one which
contains a battery and other passive components. Examples include flashlights and the starting circuits
on cars.
Direct current distribution systems do not exist in the United States. However, high-voltage DC
(HVDC) transmission systems do exist; the Pacific Intertie (i.e., the DC transmission line between the
Pacific Northwest and California) and the multiple connections between Texas and the remainder of
the United States are examples. However, it is important to understand DC electric circuits as direct
current circuit analysis techniques are basic to all types of electric circuit problems. The methods for
DC electric circuits can be directly applied to alternating current (AC) electric circuits.
55
56 V Volts
I 5 — 5 ———— 5 Amperes (A)
R Ohms
V Volts
Handbook for Electricity Metering
Electrical Circuits
terminal of the battery, moves through the wires to the lamp, and then back to the negative post of
the battery. The current measurement at the positive terminal of the battery is equal to the current
measurement at the negative post. In other words, there is no current lost in the circuit. G. R. Kirch-
hoff (1824–87), a German physicist, discovered this principle in the late 1800s.
Kirchhoff’s Current Law (KCL) can be stated in three ways:
1. The sum of the currents leaving a junction of conductors is zero at all times.
2. The sum of the currents entering a junction of conductors is zero at all times.
3. The sum of the currents entering a junction of conductors is equal to the sum of the currents
leaving the junction of conductors.
If this were not so, current would col-
lect at the junction. In the flashlight circuit
shown in Figure 4-1, it is obvious that the
current flowing into the junction of the
wire and lamp terminal are equal.
This simple circuit is fairly obvious.
However, this principle provides a way to
analyze more complicated circuits. In Fig-
ure 4-2, two more lights have been added
to the circuit that was shown in Figure 4-1.
There are two junctions of conductors or
nodes. If a negative value is arbitrarily
assigned to current flowing into a node
and a positive value to current flowing out Figure 4-1. Flashlight Circuit.
from the node, the following equation can
be written:
2I1 I2 I3 I4 0
This principle can be used to solve complex circuits.
NODE 1
NODE 2
VLamp VSource
Figure 4-3. Flashlight Circuit. Subtracting VLamp from both sides yields:
0 VSource VLamp
The work generated by the batteries is equal to the light and heat emanated from the light bulb,
and is necessary to sustain the current flow in the circuit. Another way to represent the light bulb is
by showing it as a resistance to the work that the battery wants to do. The circuit can then be redrawn
in figurative terms, as in Figure 4-4.
0 VSource VLamp
Using Ohm’s Law, the current can be determined in the circuit.
VSource ILamp RLamp VLamp
Substituting: 3V 0.5 A
3 V I 6 ➞ I Lamp
—— Lamp 6
Example 5:
Determine the current and voltages IS, IX, IY, V1, V2, and V3 for the circuit shown in Figure 4-5.
Solution:
Step 1: Arbitrarily assign directions for the currents in the circuit. In this case, IS is coming
into Node 1, while IX and IY are assumed out of Node 1.
Step 2: Assign voltage polarity markings (i.e., , ) to each circuit element which is not a
voltage source. Voltage sources have their own polarity markings. Note that the passive
sign convention states that current always enters the positive terminal of a circuit
element.
RLamp 5 6
VSource 5 3 V
Electrical Circuits
0 VS V1 V2 V3 and 0 V4 VS
or
VS V1 V2 V3 and VS V4
Since each equation has a single unknown, it is possible to solve for the unknown
currents IX and IY.
VS 12
IX —— —— 2 A
R4 6
VS R1IY R2IY R3IY (R1 R2 R3) IY
VS 12 12
IY ——————————— —–—————— —— 2 A
(R1 R2 R3) 123 6
Step 5: Knowing two of the three currents at Node 1 leaves only one unknown, IS. Kirchhoff’s
Current Law can now be applied:
0 IS IX IY or IS IX IY
Substituting and solving for IS:
IS 2 2 4 A
Step 6: Solve for the voltage drops V1, V2, and V3 by using Ohm’s Law.
VS R1 IY 1 2 2 V
V2 R2 IY 2 2 4 V
V3 R3 IY 3 2 6 V
Resistances in a DC circuit can be connected in series, in parallel, in series-parallel, or as a net-
work of series and parallel circuits. In all cases, the equivalent resistance, REQ, seen by the source, is
the total effect of all the resistances in a circuit opposing the source current flow.
R1 5 1
R2 5 2
R3 5 3
R4 5 6
Vs 5 12 V
Rule 2. The input or source voltage to a series circuit is equal to the sum of the voltage drops
across all resistances in the circuit by KVL.
Rule 3. Since resistances in series are added, in a series circuit the equivalent resistance is equal
to the sum of the individual resistances.
Use Ohm’s Law to identify whether or not two resistors are “in series.” A resistor is a two-terminal
electric circuit component, so its behavior is modeled by and subject to Ohm’s Law. If two resistors are
in series, they will share only one of their terminals, and no other conductors will exist at that junc-
tion (Figure 4-6).
A series circuit consisting of three resistors is shown in Figure 4-7. Per Rule 1, the current I
through the voltage source and three resistors will be the same. Per Rule 2, the total voltage drops
across the 10, 20, and 30 resistors must equal the source voltage. Per Rule 3, the three series resis-
tors can be replaced with one resistor having a value equal to their sum.
Example 5:
Step 1. Find the total or equivalent resistance of the circuit.
REQ RTOTAL R1 R2 R3
REQ 10 20 30 60
Step 2. Use Ohm’s Law to find the current I passing through all circuit elements.
VS 120
I ——— ——— 2 A
REQ 60
5
R1 R2 REQ 5 R1 1 R2
Electrical Circuits
VR IR2 (2)(20) 40 V
VR IR3 (2)(30) 60 V
VS VR VR VR 20 V 40 V 60 V 120 V
R1 R2 5
R1 3 R2
REQ ———— R1 || R2
R1 1 R2
R1 5 10
R2 5 20
R3 5 60
Vs 5 120 V
Find the common denominator for the fractions in REQ. Since 60 is divisible by 20 and 10, the
common denominator is 60. The above equation becomes
1 1 60
REQ ——————————— —— —— 6
1 3 6
—— —— —— 10
—— 10
60 60 60 60
Step 2. Use Ohm’s Law to find the current I supplying the one equivalent resistor.
VS 12
I ——— 5 —— 5 2 A
REQ 6
Step 3. Use Ohm’s Law to find the current through each resistor and then verify that the sum
of all currents equals the total in Step 2.
VS 12
IR1 ——— 5 —— 5 1.2 A
R1 10
VS 12
IR2 ——— 5 —— 5 .6 A
R2 20
VS 12
IR ——— 5 —— 5 .2 A
R3 60
I IR1 IR2 IR3 1.2 A .6 A .2 A 2.0 A
Electrical Circuits
1 1 1 5
REQ,BC —————— ————— — — 5 2.5
2
—— —1—
1 1
—1 —1 2
—
R2 R3 5 5 5
The equivalent resistance of two resistors in parallel having the same value will always equal
one-half their original value. For the DE circuit:
1 1 1 1
REQ,DE —————— —————— —————— —— 5 5
—— —1—
1 1 1
— 1 —— 5 1
—— 1 —— 6
——
R4 R5 6 30 30 30 30
The original circuit in Figure 4-9a is equivalent to Figure 4-9b, which contains resistances in
series.
Step 2. Find the total or equivalent resistance of the circuit in Figure 4-9b.
REQ RTOTAL R1 REQ,BC REQ,DE R6
REQ 10 2.5 5 20 37.5
Step 3. Use Ohm’s Law to find the current I passing through all circuit elements.
VS 120
I ——— 5 ——— 5 3.2 A
REQ 37.5
Step 4. Use Ohm’s Law to find the voltage drop across each resistor and then verify that the
sum of all voltage drops equals the source voltage.
VR IR1 (3.2)(10) 32 V
VREQ,BC IREQ,BC (3.2)(2.5) 8 V
VREQ,DE IREQ,DE (3.2)(5) 16 V
VR IR6 (3.2)(20) 64 V
VS VR1 VREQ,BC VREQ,DE VR6 32 V 8 V 16 V 64 V 120 V
The equivalent resistance of a series–parallel circuit equals the equivalent resistances of each
group or branch of parallel resistances, added to the resistances connected in series. Determining the
equivalent resistance of a series–parallel circuit can be simplified if, by inspection, it can be determined
which resistances are connected in parallel and which resistances are connected in series.
(produced). If voltage across a circuit component and the current through that element are known,
the power into or out of that component is determined by multiplying voltage and current.
Using Ohm’s Law, substitute for voltage, V IR, or current, I V/R, to get the following
formulas:
P I2 R ——V2
R
Power is measured in watts or kilowatts (kW); one kilowatt equals 1000 watts. Energy is defined as
work done or power used over time.
Work
Energy, E (Joules) ————— Time P T Work
Time
Electrical Circuits
Figure 4.10a. Edison System— Figure 4.10b. Edison System—
Currents and Voltages Balanced Current in Neutral Flowing from the
and Balanced Load. Generator with Imbalanced Load.
V V 2
P
Resistance: R— ——
I P I2
Voltage: VIR— P 5 P3 R
I
Power: P V I I 2 R ——V2
R
E P T V I T I2 R T V ——T
2
Energy:
R
where T is time and E is energy with units of joules or watthours.
subtract 90° from the angle to convert it to a cosine function. In AC electric circuits, voltages and
currents are no longer fixed, constant values of time v(t) V and i(t) I. They instead take on a
specific form where the functions change value as a function of time (t).
v(t) Vp cos(2ft v) V
i(t) Ip cos(2ft i) A
Sinusoidal time-domain functions are completely described by their peak amplitude, frequency,
and phase angle. The peak value, magnitude, or amplitude of the voltage and current are Vp and Ip,
respectively. If the magnitude of the sinusoidal function is negative, it is made positive by adding or
subtracting 180° from the cosine function’s argument (the argument appears in the parentheses in
the two equations above).
The sinusoids repeat with a period T (in seconds), which determines their fundamental frequency
f. The phase angles v and i allow the sinusoidal functions to shift left and right along the time axis.
The phase is related to an arbitrary time reference when using a mathematical description, but with
AC circuits, what is of interest are the relative phases of the various sinusoidal voltages and currents,
which is often referenced to a particular voltage.
Example 9:
A sinusoidal function repeats itself every 21.6 milliseconds (ms). Its peak-to-peak value is
20 milliamps (mA). The waveform does not have a shift associated with it. Express this sinusoid
in the standard form.
Solution:
The period, T, is given as 21.6 ms. Since f 1/T, the frequency of the sinusoid is
1
/21.6 103 46.3 hertz (Hz). The peak value of the sinusoidal function is one-half
the given peak-to-peak value, or 20 mA/2 10 mA. The phase angle is given as 0°.
Thus, i(t) 10 cos(246.3t 0°) mA.
FUNDAMENTAL FREQUENCY
A cycle consists of one complete pattern of change of the AC wave, which is the period from any
point on an AC wave to the next point of the same magnitude and location at which the wave pattern
begins to repeat itself. See Figure 4-11.
If the usual alternating voltage or current is plotted against time, it produces the curve in Fig-
ure 4-11. A single cycle covers a definite period of time and is completed in 360°. This period of time
Electrical Circuits
The frequency in Hz is f 1/T. In the previous equations for v(t) and i(t), can be substituted
for 2f, to obtain the angular frequency having units of radians per second. Since f 1/T, then
2/T.
v(t) Vp cos(t v) V
i(t) Ip cos(t i) A
The mathematical argument of the cosine and sine functions should be expressed in radians or
degrees. However, the phase angle, v or i, is usually expressed in degrees.
A sinusoidal voltage can be assigned a value in three ways:
1. By the maximum (Vmax) or peak value (Vp). This value is used in insulation stress calculations.
2. By the average value (Vavg), which is equal to the average value of v for the positive or negative
half of the cycle. This value is often used in rectification problems. The average value of a cosine
waveform over one period is zero—in one period, there is just as much area above the x-axis as
there is below.
3. By the root-mean-square (Vrms) or the effective value (Veff). The term Vrms is generally used.
In electricity, the effective value of an alternating current is that value of current which gives
the same heating effect in a given resistor as the same value of direct current. Unless another
description is specified, when alternating currents or voltages are mentioned, it is always the
root-mean-square (rms) value that is meant.
PHASORS
If two sine waves of the same frequency do not coincide with respect to time, they are said to be out
of phase with each other. In Figure 4-12, the current waveform, I, is ° out of phase with the voltage
waveform. As shown, it is behind or lagging the voltage waveform by the angle . It reaches its peak
value at ° after the voltage waveform reaches its peak. The trigonometric cosine of this angle between
the voltage and current is the displacement power factor of the circuit.
Application Frequency
Direct current 0 Hz
Standard AC power (Europe influenced parts of the world) 50 Hz
Standard AC power (USA influenced parts of the world) 60 Hz
Audio sound 16 to 16,000 Hz
AM radio broadcasts 535 to 1,605 kHz
FM radio broadcasts 88 to 108 MHz
Television (Channels 2–13) 55 to 216 MHz
Communication satellites 5 GHz
68
Handbook for Electricity Metering
Example 10:
Calculate the displacement power factor if the voltage v(t) and current i(t) are
v(t)
2 226 cos(260t 0°) V
i(t)
2 15.6 cos(260t 2 34.1°) A
Solution:
Take the phase angle of the voltage and subtract the phase angle of the current to obtain the
displacement power factor angle pf, 0° 2 (34.1°) 34.1°. The power factor is lagging.
Example 11:
The angle between the voltage v(t) and current i(t) is 25.5°. The voltage is leading the current.
What is the displacement power factor?
Solution:
The cosine of 25.5° is 0.903. Since the voltage is leading the current, or the current is behind
the voltage, then the displacement power factor is lagging.
Electrical Circuits
The phasor’s length is defined either as the peak or rms value of the sine wave of the current or
voltage. The phase angle indicates the position of the phasor relative to a previously defined reference
phasor. The reference phasor is usually the phase A line-to-neutral voltage having an angle of 0°.
Since power equipment is normally specified by its rms quantities, all magnitudes are assumed to be
rms in the remainder of this chapter. As such, if v(t) or i(t) are given by their peak or maximum
amplitude, it will be necessary to convert them to their rms values by dividing by 2.
One method of phasor notation is I Irms /__°, meaning the phasor I is at an angle of ° counter-
clockwise from the positive x-axis (Figure 4-14).
Example 12:
What are the phasors representing 6 cos(t 30°) and 5 sin(t 10°)?
Solution:
The first is 6/_30°
_____
_18__ 6/____
__0° _ or 6/_210°
150° ____. The second must first be converted from a sine
function to a cosine function by subtracting 90°. Therefore, 5/_10°
_______ 90° 5/_100°
____ ______.
Example 13:
If the phasor VS 8.00 /_38.7°
______ V, what is vs(t)?
Solution:
The answer is vs(t) 8.00 cos(t 38.7°) V.
Phasors representing currents or voltages can be resolved into vertical and horizontal components
(Figure 4-14). Because phasors are complex numbers written in polar form, the methods presented in
Chapter 3 can be used to perform addition, subtraction, multiplication, and division.
INDUCTANCE
Any conductor which is carrying current is cut by the flux of its own field when the current changes
in value. A voltage is thereby induced in the conductor, which, by Lenz’s Law, opposes the change in
current in the conductor. If the current is decreasing, the polarity of the induced voltage attempts to
maintain the current; if the current is increasing, the induced voltage tends to keep the current down.
The amount of induced voltage depends upon the change in the number of flux lines cutting the
conductor, which, in turn, depends upon the rate of change of current in the conductor. The propor-
tionality factor between the induced voltage and the rate of change of current is the inductance, L, of
the circuit.
Electrical Circuits
rent passes through zero. At this instant of zero magnitude but maximum change, there is maximum
induced voltage and the voltage wave is at its peak value. When the current reaches its peak value, the
rate of change of current is zero and the induced voltage is zero. As shown in Figure 4-17, the current
wave lags the voltage wave by 90°.
When two inductors are in series, they may be replaced by a single equivalent inductor so they
become similar to a resistor. When L1 is in series with L2, then LEQ L1 L2. Similarly, inductors in
parallel add like resistors in parallel,
1 L1L2
LEQ L1 || L2 ————— —————
1
— — 1 L 1 L2
L1 L2
CAPACITANCE
Electric current flow is generally considered to be a movement of negative charges, or electrons, in a
conductor. In conducting materials, some of the electrons are loosely attached to the atoms so that
when a voltage is applied to a closed circuit, these electrons are separated from the atoms and their
movement constitutes a current flow.
The electrons in an insulator are much more firmly bonded to the atoms than in they would
be in a conductor. When a voltage is applied to an insulator, the electrons seek to leave the atoms
but cannot do so. However, the electrons are displaced by an amount dependent upon the force
applied, which is the voltage difference. When voltage changes, the displacement also changes. When
this electron motion takes place, a displacement current flows through the dielectric and there is a
charging-current flow throughout the entire circuit.
Consider the circuit shown in Figure 4-18a, which has a small insulating gap between the ends of
the wires. When the switch is closed, there is no continuous current flow in the circuit. However, for
a short time, a very small current may be measured with an extremely sensitive instrument. Elec-
trons move through the circuit to build up an electrical charge across the gap, which is equal to the
impressed voltage VS. Once the charge has been established there is no further electron movement.
If, instead of a small gap, the area is enlarged by connecting plates to each of the conductors, as
in Figure 4-18b, the current required to raise the charge to a given level is increased because a greater
movement of electrons is required. Such devices, consisting of large conducting areas separated by thin
insulating materials such as air, mica, glass, etc., are called capacitors. Any two conductors separated
by insulation constitute a capacitor, but normally the capacitance effect is negligible unless the com-
ponents and their arrangement have been specifically designed to provide capacitance.
The capacitance, C, is a function of the physical characteristics of the capacitor, such as the plate
area, the distance, and the type of insulation between the plates. Capacitance is expressed in Farads. A
more common, smaller unit is the microFarad (µF), which is one-millionth of a farad (F).
Capacitors may be connected in parallel or in series. The total capacitance of capacitors connected
in parallel is the sum of the individual capacitances.
CEQ C1 C2 C3
For a series connection, the net capacitance is found by a formula similar to that for parallel
resistances.
1 C1 C 2
CEQ ————— ——————
1 —
— 1 C1 C2
C1 C2
In a DC circuit, current flows through a capacitor only when the voltage across it changes. In an
AC circuit, the voltage is continually changing and current flows through a capacitor as long as the
alternating voltage is applied. The current magnitude is proportional to the rate of change of voltage.
With a sinusoidal voltage, the maximum rate of change occurs when the voltage crosses zero, which is
the instant when the peak value of current occurs. When the voltage is at its peak, its rate of change
is zero and the current magnitude is zero. Therefore, there is a 90° phase displacement between cur-
rent and voltage in a capacitor. When the rate of change of voltage is positive, the current must be in
the positive direction to supply the increasing positive charge. Therefore, the current leads the voltage
in a capacitor, as shown in Figure 4-19.
The current-limiting effect of a capacitor, its reactance, is dependent on capacitance and fre-
quency. Charging current increases with increasing capacitance, so, with a given voltage, the reactance
must be inversely proportional to capacitance. Rate of change of voltage is proportional to frequency,
hence charging current is also proportional to frequency and reactance is inversely proportional.
Capacitive reactance may be calculated from the following equation:
Electrical Circuits
Capacitive reactance causes leading current and a leading power factor while inductive reactance
causes lagging current and a lagging power factor. Capacitors are often used to balance some of the
inductive reactance (e.g., motors and transformers) of a circuit and therefore to increase the circuit
power factor. They are also used to balance some of the inductive voltage drop in a circuit and there-
fore increase the available voltage.
IMPEDANCE
In alternating currents, there are three
quantities that limit or impede the flow of
current: resistance, R; inductive reactance,
XL; and capacitive reactance, XC. Each of
these quantities is a specific part of a more
generic quantity called impedance. Imped-
ance, Z, is the ratio of the phasor voltage
divided by the phasor current through the
circuit of interest.
V Figure 4-20. Example Schematic.
Z—
I
Ohm’s Law restated for AC circuits is V Z I. Note that Z is not a phasor. Since each variable in
the equation is a complex number, the following equations are true:
Vrms
|Z| ——— and Z 5 pf 5 V 2 I
Irms
Because the impedance Z in AC circuits is like R in DC circuits, combining impedances in paral-
lel and impedances in series is identical to combining resistors in parallel and resistors in series. For
impedances in series
ZEQ Z1 Z2 Z3 ••• ZN
and for impedances in parallel
1
ZEQ ————————————————————
1 1
— — — 1 ••• —
1
Z1 Z 2 Z1 ZN
74 The impedance associated with R, L, or C can be defined. The impedance of a resistor is:
VR
Z —— R j0 R
IR
Handbook for Electricity Metering
In a series RLC circuit, the equivalent impedance, ZEQ, and its magnitude, |ZEQ|, as seen by the
source is:
ZEQ R j(XL XC)
|ZEQ|
R2
(X
L XC)2
By definition, XC is a negative number.
Impedance may also be represented by impedance triangles (Figure 4–21).
From these triangles, other trigonometric relationships between Z, R, and X can be obtained. See
Table 4-2.
The various components of the impedance Z determine not only the amount of current flowing in
a circuit, but also the phase relationship between the voltage and the current: Z pf V I.
If the circuit has only resistance, R, the current is in phase with the voltage and the circuit is said
to have a unity displacement power factor.
If the inductive reactance, XL, exceeds the capacitive reactance, |XC|, in a series circuit, the current
lags the voltage and the circuit has a lagging displacement power factor.
75
Electrical Circuits
Figure 4-21. Impedance Triangles for a Series Circuit.
If the capacitive reactance, |XC|, exceeds the inductive reactance, XL, in a series circuit, the current
leads the voltage and the circuit has a leading displacement power factor.
If the inductive reactance, XL, and the capacitive reactance, |XC|, are equal in a series circuit, the
circuit is said to be in resonance, and the current flow is limited only by the resistance and the circuit
power factor is unity.
where cos Z cos pf cos(V I) and is equal to the displacement power factor of the circuit. The
units of P are watts.
In sinusoidal AC circuits, the reactive or imaginary power represents the power that is circulating
every quarter cycle of the line frequency between the magnetic and electrical circuits of the system.
This power is not directly consumed, although it will lead to additional line and equipment losses. It is
calculated as:
Electrical Circuits
are also VA. The apparent power is a measure of the operating limits in electrical equipment such as
transformers, motors, and generators.
The relationship between P, Q, and |S| is best shown by the power triangle, Figure 4-22.
Mathematically:
S P jQL for an inductive load having a lagging power factor
S P jQC for a capacitive load having a leading power factor
For the two cases above,
Vrms
2
QC I2rms XC ———
XC
Vrms
2
QL Irms
2
XL ———
XL
78
Handbook for Electricity Metering
When a circuit is capacitive (i.e., leading power factor), then Q is negative or less than zero since XC
is negative. When a circuit is inductive (i.e., lagging power factor), then Q is positive or greater than
zero. Using trigonometry, many other expressions can be written from Figure 4-22. For example, the
displacement power factor can be written as:
The measured power factor is DPF P/|S| 2920/3530 0.828. Since the item is a
motor, assume lagging as opposed to leading. A DPF of 0.828 corresponds to a phase angle of
cos1(0.828) 34.1°. The reactive power can be calculated by rearranging the above formula for
the apparent power.
Q
|S|2
2
P2 0)
(353
2
0
2 (292
)2 1980 VARs
The percent efficiency of a motor is
Poutput Poutput
5 [ ———— ] 3 100 5 [ ————— ] 3 100
Pinput VrmsIrms
The motor has a mechanical output of 3 hp. Since there are 746 watts per hp, the power output of the
motor is 3 746 or 2,238 watts.
Therefore, the efficiency, , of the motor is 79
2,238 watts
————————
2,920 watts
100 76.6%
Electrical Circuits
TRANSFORMERS
Transformers operate on the principle of induction in which energy is transferred between electric and
magnetic circuits. Because energy is alternately stored to and delivered from these magnetic circuits,
current alternates and power circulates in the electrical circuits.
It is the influence of the magnetic circuit on the electric circuit with which it is associated that
causes the major differences between the AC circuit and the DC circuit.
Transformers are indispensable in AC power distribution systems. Their applications range from
power conversion to small transducer applications, and they utilize a mixture of magnetic and electri-
cal properties. A transformer requires alternating current to perform its function as a “transforming”
mechanism. It is primarily used to change voltage and current levels to values more usable or measur-
able. It typically consists of two windings or inductors that are magnetically coupled by a core of
magnetic material. The input winding or coil is called the “primary” and the output winding or coil is
called the “secondary.” The secondary usually delivers power to a load or a measurable quantity to a
metering or monitoring device.
The ideal transformer has no electric or magnetic losses of any kind. Figure 4-23 illustrates an
ideal two-winding, shell-type transformer. This device works only when AC voltage and current are
applied to the primary, and appears as a short circuit to DC voltage and current. This property allows
the device to isolate the secondary from the primary and vice-versa for DC voltage and current. With
AC voltage applied to the primary, a magnetic field is generated in the core. This magnetic field or flux
flow in the core is analogous to current flowing in a circuit. As it flows through the core inside the
secondary winding, a voltage is induced into this winding. The magnitude of this induced voltage is
proportional to the turns ratio of the transformer.
V1 N
—— ——1 Turns Ratio a
V2 N2
As in an electric circuit, work is required to move this flux. This magnetic form of work is called
magneto-motive force (mmf). The mmf is equal to the number of turns in the winding times the
current in the winding. The magnetic circuit of the ideal transformer is lossless, and, therefore, the
mmf or work required to overcome the core circuit is zero. The mmfs of the two windings are equal
and opposite in polarity.
I1 N2 1 1
N1 I1 N2 I2 or —— —— ———————— —
I2 N1 Turns Ratio a
In an ideal transformer, the secondary voltage times the turns ratio is directly proportional to the
primary voltage and the secondary current is inversely proportional to the primary current.
VP V1 VS V2 IP I1
IS I 2
IS
VP VS a and IP ——a
An ideal transformer also demonstrates conservation of power. The power into the ideal trans-
former will equal the power out of the ideal transformer.
SP VP IP
IS
Substituting from the formulas above SP (VS a)——
a
Reducing this equation SP VS IS SS
Polarity defines the convention of current flow in and out of a transformer and is determined
when the transformer is manufactured and is dictated by the placement of the windings on a core. It
is marked on the nameplate and sometimes on the primary and secondary terminals, as is the case of
an instrument transformer used for metering or relaying. In Figure 4-23, the polarity marking is signi-
fied by a dot marked at the top of each winding. The primary current flows into the terminal marked
with the polarity marking and out of the secondary terminal marked with the polarity marking.
80
Handbook for Electricity Metering
Unfortunately, the transformers built today have a variety of losses that encompass the magnetic
circuit and the electrical circuit. In a transformer designed to deliver power, these losses have been
quantified in two categories; no load and full load. As their names imply, they pertain to losses at each
of these two states of the unit. In transformers that are used to meter voltages and currents, these
losses are quite small and are sometimes compensated by the devices to which they feed.
HARMONIC FREQUENCIES
Ideally, alternating voltages and currents are sinusoidal functions having a single frequency f or . This
fundamental frequency, also known as the power frequency, is usually the lowest frequency compo-
nent in the system.
In reality, there are a number of effects within the power system that may cause the cosine wave
to become distorted or “polluted.” The terms distorted or polluted indicate that the voltage and cur-
rent no longer contain just the desired power frequency (50 or 60 Hz).
Any repeating AC waveform, no matter how distorted, may be represented by a combination of
waveforms of the fundamental frequency plus one or more harmonics. A harmonic is a frequency
which is an integer multiple of the power frequency, (h, h integer). In a 60 Hz system, examples
of harmonics of the power frequency would be 180 Hz, 300 Hz, 420 Hz, 660 Hz, 780 Hz, etc. These
higher frequencies are called the third, fifth, seventh, eleventh, and thirteenth harmonics of 60 Hz,
respectively. The relative magnitude of the fundamental waveform and the number, magnitude, and
phase displacement of the harmonic components determine the resultant waveform’s shape.
Figure 4-24 shows a voltage waveform composed of a 100 V fundamental 60 Hz waveform and a
20 volt third harmonic. This waveform contains 100% or one per-unit 60 Hz and a 20% or .02 per-
unit third-harmonic component. The third harmonic crosses the x-axis at the same instant in time as
the fundamental waveform. Harmonics can be displaced in time from the fundamental, depending on
circuit characteristics. Figure 4-24 shows the third harmonic 180° out of phase with the fundamental.
Electronic loads containing power semiconductor devices, which switch on and off to control the
flow of energy between the source and load, typically cause power system harmonics. This switching
on and off, hundreds to thousands of times every second, directly modulates the current and cor-
rupts the voltage. The current modulation causes voltage drops across the impedance of the lines and
distribution equipment, resulting in the voltage being modulated as well and high-frequency harmonic
components to be injected into the power system. Examples include variable-speed motor drives,
electronic lighting ballasts, and electronic equipment power supplies.
Electronic loads containing power semiconductor devices can cause dangerous resonance condi-
tions between the electronic load’s step-down transformer and the utility’s power factor correction
capacitors. Harmonics will cause additional heating in wiring and other equipment, and will not be
detected by most digital test meters unless they are true rms measuring devices. In addition, electrome-
chanical meters typically underregister the energy being absorbed by these electronic loads. In general,
solid-state meters do a better job of measuring the total energy being consumed by a customer’s
electronic load.
81
Electrical Circuits
Figure 4-24. Sine Wave with 20% Third Harmonic.
Note that Van Vbn Vcn Vln and Vab Vbc Vca Vll 3 Vln. Also, the line-to-line voltages
lead the line-to-neutral voltages by 30°. Assuming that the line-to-neutral phasors are rotating in the
counterclockwise direction, there is a positive or abc sequence.
If, however, the line-to-neutral voltages are rotating in the clockwise direction, there is a negative
or acb sequence. In this case, the following results:
Van Van /___
0°
Vbn Vbn /_240°
______
Vcn Vcn /_120°
______
82 and
Vab Van Vbn Vab /_30°
___
___
Vbc Vbn Vcn Vbc /_150°
______
Handbook for Electricity Metering
Note again that Van Vbn Vcn Vln and Vab Vbc Vca Vll 3 Vln. In this case, the line-
to-line voltages lag the line-to-neutral voltages by 30°.
The current flowing through a phase of a wye connected three-phase source will be identical to the
current flowing through that phase’s line impedance. That is, the current flowing through each phase
voltage is:
IaA Ina Ina /____
0°_
____
IbB Inb Inb /_120°
_______
____
IcC Inc Inc /_240°
________
___
The source currents are referenced to the phase A line-to-neutral source voltage. The angle corre-
sponds to the current angle as shown in Figure 4-26.
The currents flowing through a delta- (-) connected three-phase source will be related to the line
currents by 3 and 30° for abc or positive sequence and 3 and 30° for acb or negative sequence.
The positive-sequence current flowing through the -connected source phase voltages is:
1
Iba 5 ———— /____
30° (Ian /____
0° ____
1 )
3
1
Icb 5 ———— /____
30° (Ibn /____
120°
__1
____
)
3
1
Iac 5 ———— /____
30° (Icn /_240°
_____1
____
)
3
Knowing the line currents, it is possible to get the -connected source phase currents by shrinking
the magnitude by 3 and shifting 30°.
The negative-sequence current flowing through the -connected source phase voltages is:
1
Iba 5 ———— /____
30° (Ian /_0°
_______
1 )
3
Electrical Circuits
Figure 4-26. Balanced Three-Phase Four-Wire Wye Network Phasor Diagram.
1
Icb 5 ———— /____
30° (Ibn /____
240°
__1
____
)
3
1
Iac 5 ———— /____
30° (Icn /_120°
_____1
____
)
3
Knowing the line currents, it is possible to get the -connected source phase currents by shrinking
the magnitude by 3 and shifting 230°.
Again, note that VAN VBN VCN VLN and VAB VBC VCA VLL 3 VLN. However, in this
case, the line-to-line voltages lag the line-to-neutral voltages by 30°.
The current flowing through a phase of a wye-connected three-phase load will be identical to
the current flowing through that phase’s line impedance. The current flowing through each phase
voltage is
IAN IAN /___
0°_
___
IBN IBN /________
120° ____
ICN ICN /_240°
_______
____
The load currents are still referenced to the phase A line-to-neutral load voltage. The currents
flowing through a -connected three-phase load will be related to the line currents by 3 and 30°
for abc or positive sequence and 3 and 30° for acb or negative sequence. The positive-sequence
current flowing through the -connected load phase voltages is
1
IAB 5 ———— /____
30° (IAN/_0°
_______
1 )
3
1
IBC 5 ———— /____
30° (IBN/_2120°
__________
1 )
3
1
ICA 5 ———— /____
30° (ICN/_2240°
__________
1 )
3
If the line currents are known, it is possible to find the -connected load phase currents by
shrinking the magnitude by 3 and shifting 30°.
The negative-sequence current flowing through the -connected load phase voltages is
1
IAB 5 ———— /______ (IAN /____
230° 0° ____
1 ) 85
3
1
IBC 5 ———— /_230°
_____ (IBN /_2240°
Electrical Circuits
__________
1 )
3
1
ICA 5 ———— /_230°
_____ (ICN /_2120°
__________
1 )
3
If the line currents are known, it is possible to find the L-connected load phase currents by shrink-
ing the magnitude by 3 and shifting 30°.
|S3|
P3
2
Q
2
3
Power Triangle
In sinusoidal AC circuits, the power triangle is used to relate the three-phase active, real, or average
power P3 and the three-phase reactive or imaginary power Q3 to the three-phase complex power S3
having units of voltamperes. The complex power S3 is
3V rms
2
S3 3S 3VlnIline 3Irms
2
Z ————
Z
S3 3S |S3| /_ __pf |S3| /___
V I |S3| / Z
___
3VrmsIrms /___ __
V__ I 3VrmsIrms /___
Z 3VrmsIrms /_
__pf
3 VllIrms /___ I
__
V__ Z
3 VllIrms /___ 3 VllIrms /___pf
when written in terms of the voltage and current phasor magnitudes and phase angles. The magnitude
of the three-phase complex power S3, |S3|, is known as the three-phase apparent power and is the
product 3Vrms Irms
P3
2
Q
3 . It also has units of volt
2
amperes. The three-phase apparent power is a
measure of the operating limits in electrical equipment such as transformers, motors, and generators.
The relationship between P3, Q3, and |S3| is best shown by the power triangle, Figure 4-27.
Mathematically,
S3 P3 jQ3,L for an inductive load having a lagging power factor and
S3 P3 jQ3,C for an capacitive load having a leading power factor.
Electrical Circuits
3V rms
2
Q3,L 3Irms
2
XL ————
XL
When a circuit is capacitive (i.e., leading power factor), then Q3,C is negative or less than zero
since XC is negative. When a circuit is inductive (i.e., lagging power factor), then Q3,L is positive or
greater than zero. Using trigonometry, many other expressions can be written from Figure 4-27. For
example, the displacement power factor can be written as
Q3 P3 P3
DPF cos(V I) cos(Z) cos(pf) cos tan–1 ——— 5 ——— 5 —————
P3 |S3| 3VrmsIrms
For metering applications, the complex power S3 is not a measurable quantity. However, the
newer electronic meters can measure |S3| directly. The reactive power Q3 can be measured with care,
and then only for sinusoidal systems. In practice, measure |S3| and P3, and then compute Q3.
phase shift and is transparent to all electrical quantities. The following formulas apply for the voltage
magnitudes:
1 N N
|V2| 3 |V1| |V1| ——— ——1 |V4| |V2| ——1 |V4|
3 N2 N2
Electrical Circuits
sequence and is transparent to some electrical quantities. The following formulas apply:
V2 3 V3 ———
V2
5 V3 V1 ——1 V2
N
N2
3
Solid-State Electronics
This chapter deals with basic solid-state electronics as applied to modern metering devices. The
information contained here is intended as a review for metering personnel with a background in
electronics and as an introduction for those unfamiliar with the subject, with the intention of stimu-
lating further study.
In the study of solid-state electronics, it is necessary to understand the effects of combining
semiconductors of differing atomic structures. Therefore, the chapter begins with a discussion of the
atom to introduce the concept of current flow across the semiconductor junction. This chapter also
introduces digital electronics, including the microprocessor.
The Atom
Atomic structure is best demonstrated by the hydrogen atom, which is composed of a nucleus or
center core containing one proton and a single orbiting electron. As the electron revolves around the
nucleus, it is held in orbit by two counteracting forces. One of these forces is centrifugal force, which
tends to cause the electron to fly outward as it orbits. The second force is centripetal force, which
tends to pull the electron toward the nucleus and is caused by the mutual attraction between the posi-
tive nucleus and negative electron. At some given radius the two forces will exactly balance each other,
providing a stable path for the electron. By virtue of its motion, the electron in the hydrogen atom has
kinetic energy. Due to its position, it also has potential energy.
The total energy of the electron (kinetic plus potential) is the factor which determines the radius
of the electron orbit around the nucleus. The orbit shown in Figure 5-1 is the smallest possible orbit
that the hydrogen electron can have. For the electron to remain in this orbit, it must neither gain nor
lose energy.
The electron will remain in its lowest orbit until a sufficient amount of energy is available, at which
time the electron will accept the energy and jump to one of a series of permissible orbits. An electron
cannot exist in the space between permissible orbits or energy levels. Therefore, the electron will not
accept energy unless it is great enough to elevate the electron to one of the allowable energy levels.
Light and heat energy, as well as collisions with other particles, can cause the electron to jump orbit.
Once the electron has been elevated to an energy level higher than the lowest possible energy level,
the atom is said to be in an excited state. The electron will not remain in this excited condition for
more than a fraction of a second before it will radiate the excess energy and return to a lower energy
orbit.
An alternative would be for the electron to return to the lower level in two jumps; from the third
to the second, and then from the second to the first, emitting energy twice, once from each jump.
Each emission would have less energy than the original amount that had excited the electron to
begin with.
91
92 Although hydrogen has the simplest of all
atoms, the principles just developed also apply
to the atoms of more complex elements. In
an atom containing two or more electrons,
Handbook for Electricity Metering
Semiconductor Electronics
Any element can be categorized as a conductor, semiconductor, or insulator. Conductors are elements,
such as copper or silver, which will readily conduct electricity. Insulators (non-conductors) do not
conduct electricity to any great degree and are therefore used to prevent a flow of electricity. Rubber
and glass are good insulators. Material such as germanium and silicon are not good conductors, but
cannot be used as insulators, either, since their electrical characteristics fall between those of conduc-
tors and insulators. These are called semiconductors.
The electrical conductivity of matter is ultimately dependent upon the energy levels of the atoms
of which the material is constructed. In any solid material such as copper, the atoms which make
up the molecular structure are bound together in a crystal lattice which is a rigid structure of copper
atoms. Since the atoms of copper are firmly fixed in position within the lattice structure, they are
not free to migrate through the material and therefore cannot carry electricity through the conductor
without the application of external force. However, by ionization, electrons could be removed from
the influence of the parent atom and made to move through the copper lattice under the influence of
external forces. It is by virtue of the movement of these free electrons that electrical energy is trans-
ported within the copper material. Since copper is a good conductor, it must contain a vast number of
free electrons.
Solid-State Electronics
The quality and quantity of the impurity are carefully controlled by the doping process.
P–N Junction
Both N- and P-type semiconductor materials are electrically neutral. However, a block of semicon-
ductor material may be doped with impurities so as to make half the crystals N-type material and
the other half P-type material. A force will then exist across the thin junction of the N- and P-type
material. The force is an electro-chemical attraction by the P-type material for electrons in the N-type
material. Due to this force, electrons will leave the N-type material and enter the P-type material,
making the N-type material near to the junction positive with respect to the remainder of the N-type
material. Also, the P-type material near to the junction will be negative with respect to the remaining
P-type material.
After the initial movement of charges, further migration of electrons ceases due to the equalization
of electron concentration in the immediate vicinity of the junction. The charged areas on either side
of the junction constitute a potential barrier, or junction barrier, which prevents further current flow.
This area is also called a depletion region. The device thus formed is called a semiconductor diode.
Semiconductor Diode
The schematic symbol for the semiconductor diode is illustrated in Figure 5-4. The N-type material
section of the device is called the cathode and the P-type material section the anode. The device
permits electron current flow from anode to cathode and restricts electron current flow from cathode
to anode.
Figure 5-5 depicts a potential placed externally across the diode, positive on the anode with respect
to the cathode 5. This polarity of voltage (anode positive with respect to the cathode) is called forward
bias since it decreases the junction barrier and causes the device to conduct appreciable current.
However Figure 5-6 illustrates a reverse bias condition when
an anode is made negative with respect to the cathode.
Theoretically, no current flow should be possible with
reverse bias applied across the junction due to the increase
in the junction barrier.
However, since the block of semiconductor material
is not a perfect insulator, a very small reverse or leakage
current will flow. At normal operating temperatures, this
current may be neglected. Leakage current increases with
an increase in temperature. The characteristic curve of the
typical diode is shown in Figure 5-7. Excessive forward bias
results in a rapid increase of forward current and could
destroy the diode, while excess reverse bias could cause a
breakdown in the junction due to the stress of the electric
field. The reverse bias point at which breakdown occurs is
called the breakdown or avalanche voltage.
Some semiconductor diodes are made to operate in
the breakdown or avalanche region, the most common of
Figure 5-4. Semiconductor Diode Symbol.
which is the zener diode.
95
Solid-State Electronics
Figure 5-5. Semiconductor Diode with Forward Bias.
Transistors
By connecting two P–N junctions, either at their N sides or their P sides, and appropriately applying
forward bias to one junction while reverse biasing the other junction, an interesting phenomenon
occurs. The thin connecting section of material is the base, and the sections on either end of the junc-
tion are the emitter and collector, respectively. This device is shown in Figure 5-8. Reverse bias applied
to the base-collector junction causes a small reverse current, as shown in Figure 5-7 for a typical P–N
junction. By forward biasing the emitter-base junction, the base-collector junction is driven further
into the breakdown or avalanche region, resulting in a much larger collector current. If a small,
varying signal is applied between the emitter and base, the bias across the base-emitter junction can be
used to control the large current flow in the collector circuit, and, if the bias is reversed, current flow
ceases. This is the means for controlling a large current by varying a smaller one, which is the basis
for amplification.
96 Digital Electronics
While analog circuits operate on a continu-
ous range of signals, digital electronic circuits
Handbook for Electricity Metering
Memory Circuits
In digital electronics, logic elements are used to make decisions. The decisions are then stored in
memory elements whose basic building block is the flip-flop. A flip-flop is a one-bit circuit which
remembers 1’s and 0’s.
The logic diagram for a J–K flip-flop is shown in Figure 5-16. The truth table lists possible values
for the inputs J and K as well as for the output Q, which will appear after the next clock pulse. The
value of Q only changes each time a clock pulse appears. The new value of Q depends on the inputs
Solid-State Electronics
Figure 5-9. Logic Circuit and Truth Table.
Solid-State Electronics
Figure 5-16. J–K Flip-Flop.
J and K. If J and K are both 0, the output Q keeps the same value (0 or 1) that it had before the new
clock pulse. If J and K are both 1’s, the output Q changes to the opposite of the value it had before
the clock pulse. If J and K are 0 and 1, the output Q is set to 0, and if J and K are 1 and 0, the output
Q is set to 1. The other output Q is always the inverse of Q.
With AND, OR, NAND, and NOR circuits, the outputs change immediately when inputs change.
Flip-flop outputs change only when a clock pulse arrives, so a flip-flop is a memory circuit that
remembers the input status from the last clock pulse.
Most digital systems and all computers need to remember thousands of bits of information. Large
memories are made by integrating thousands of flip-flops onto a piece of silicon, forming a single
integrated circuit. Since most computers operate with 8-bit bytes, integrated circuits are designed to
store bytes by the millions.
Several construction techniques exist for memory circuits to satisfy different needs. The most
popular electronic memory types are Random Access Memory (RAM), Read Only Memory (ROM),
Programmable Read Only Memory (PROM), and flash. All forms of memory can be read over and
over again without changing the contents.
RAM is used for the temporary storage of data and for applications where information is stored
and retrieved quickly and frequently. A disadvantage of RAM is that all data is lost when power is
removed from the circuit. This memory is also called volatile memory and can be supported with
batteries (called battery back-up).
ROM is made at an integrated circuit factory to a set of specifications called a mask. This memory
can be programmed to perform like many individual gates or to store data which can be accessed as
needed. When making a masked ROM, permanent changes are made to the silicon inside the inte-
grated circuit (IC) package. Once a ROM is programmed at the factory, the contents of its memory
can never be rewritten. This memory is permanent and remains intact even when power is removed. It
is called non-volatile memory.
PROM stores information which cannot be rewritten. Therefore, PROMs can be programmed by
the user at the laboratory or manufacturing facility and installed in the electronics. Another form
of PROM can be erased by exposing the silicon through a glass window in the package to intense
ultra-violet light. It can then be reprogrammed again. This is called Erasable Programmable Read Only
Memory (EPROM). Electrically Erasable Programmable Read Only Memory (EEPROM) is erased and
written electrically. Another form of PROM is flash memory, which is faster and permits more erase/
write cycles than EEPROM. Flash memory is generally used when there is a requirement for a large
amount of non-volatile memory. PROM and flash are useful for applications where the data stored
might be changed periodically. The software programs stored in PROMs are sometimes called firmware.
MICROPROCESSORS
Microprocessors are small computers that get instructions and data from memory, perform arithmetic
and logical functions on the data, and store the results. The instructions are in a specific sequence,
specifically written for each application. Microprocessors typically operate on data organized in groups
100 of 8-, 16-, 32-, or 64-bits. Usually the data path used by the microprocessor defines the data path of
the memory in the circuit. For example, 8-bit microprocessors use memory circuits with 8-bit data
paths. A microprocessor also has an input-output system to control communications or discrete status
signals between itself and external devices. The input-output system supports both asynchronous and
Handbook for Electricity Metering
Solid-State Electronics
sometimes referred to as a network interface card (NIC).
Chip Sets and Application Specific Integrated Circuits (ASICs)
Chip sets are a collection of functions integrated onto one or more integrated circuits to scale down
the size and the cost of an electronic circuit card. It is common for a manufacturer to have a custom,
proprietary component fabricated to reach a higher level of integration and a lower cost point. These
components are referred to as ASICs. Each is custom-designed to perform a collection of tasks in a
small space and at the lowest possible production costs.
Many chip sets are incorporated in today’s solid-state electric meters. Examples are: metrology,
register, and display integrated on a single substrate. These are often referred to as “meter on a chip”
technology.
Register
The register is used to process values from the metrology, as well as enable additional functionality.
It performs the primary functions of the meter including energy, demand, time-of-use, and load
profile, and is comprised of a microprocessor connected to a non-volatile memory. The microprocessor
includes on-chip flash memory where the firmware resides. This memory is non-volatile, but is rewrit-
able to allow firmware upgrades in the shop or field. The microprocessor performs all the control,
calculation, communication, and data storage functions associated with the register function.
The microprocessor is connected to an off-chip non-volatile memory. This device stores all the
measurement data, including load profile and event/history logs.
In time-of-use (TOU)/load profile versions of the meter, the power to the register microproces-
sor is battery backed. This allows the microprocessor to directly perform the real-time clock function
(keeping accurate time and date through outages). The battery does not back the power to any other
component on the board. For demand-only functionality, the battery is not needed.
Metrology
The metrology is the core metering component of the device, used to measure and calculate energy
usage. It performs the direct sampling of the voltage and current waveforms and the raw processing of
these samples to compute all the energy quantities. It is comprised of a dedicated microprocessor and
several analog-to-digital (A/D) converters. Low-level signals proportional to the service voltages and
currents are connected to the analog inputs of the A/D converters. These converters, which are con-
tained in one package, simultaneously sample the signals and send the digital result to the micropro-
cessor multiple times per second. The microprocessor takes these samples, applies precision calibration
corrections, and computes all the fundamental quantities required for the specific meter configuration.
Periodically, metrology data is sent to the register processor. The metrology processor does not store
any data at power-down.
Figure 5-17 shows a block diagram of the major components of the metrology and communica-
tions systems.
Display
The display circuitry is contained on the main board of the meter and is mounted in the upper hous-
ing so that the liquid-crystal display (LCD) is exposed through a window in the housing. The LCD is
driven by an application-specific driver that keeps the information on the display clearly visible across
the widest possible temperature range. Sometimes the LCD driver is built into the microprocessor.
Transceiver Integrated Circuit (IC)
The transceivers (transmitter/receiver) in the meter facilitate radio frequency (RF) communications
between the meter and other devices such as in-home display, another meter, or a data aggregation
point. The transceiver resides within an integrated circuit (IC). The transceiver IC consists of an
analog circuit, a digital circuit, a microcontroller (microprocessor), and on-chip memories, and an
input-output system that supports both asynchronous and synchronous serial communications.
In the receiver path, the analog circuit filters pass only the signal that is intended for the meter,
converts the signal from radio frequency to the baseband frequency, and digitizes the signal from
analog to digital. The digital circuit performs many functions previously performed with analog
102
3 Current
Handbook for Electricity Metering
AC Sensors Load
Line
Option Connector
Comm Port
Sensors A/D Converter
DAP
DC to
Power Circuits Microprocessor
Supply LCD Controller
c omponents, such as filters, mixers, detectors, and demodulator. In the transmit path, the digital
circuit assembles the data to be transmitted into a packet then encodes the packet.
The analog circuit aggregates the digital data into analog signal, and then modulates the analog
signal from baseband into radio frequency for transmission. Since the modulation and demodulation
is done in the digital portion of the processor, which is controlled by the firmware, the same hardware
can be programmed to operate with different radio protocols. The media access control (MAC) func-
tions that are time critical and require extensive computation, such as cyclic redundancy check (CRC)
calculation, are also implemented using the digital circuits. The microcontroller manages the opera-
tion of the transceiver IC. The on-chip memories such as RAM and flash memory are used as either
temporary or permanent storage for data and software program (operation software, communication
software, and application software).
Communications Components
The main board supports communication to the register processor through two ports:
• Optical—an optical transmitter/receiver pair that are mounted on the main board so that they
are communicable through the American National Standards Institute (ANSI) optical port
on the front of the meter. Through this port, the meter can be configured, firmware can be
upgraded, and all of the meter’s data can be read.
• Auxiliary—a Universal Asynchronous Receiver and Transmitter (UART) is made available on the
option board connector. This port can be used by a third party communication module or other
option boards when installed “under the cover.”
Solid-State Electronics
2. RF mesh is an NIC module that must be installed in the electric meter, which establishes
connection between the meter, neighboring meters, and other network communication devices
typically installed on utility poles. The NIC card is a transceiver IC.
3. A PLC communications board is a transceiver IC that injects a signal over the power line
typically back to a communications device installed at a distribution transformer or in a
sub-station.
4. A cellular communications module can be installed in the electric meter, which establishes a
connection between the meter and the cellular system. The cellular communications board is a
transceiver IC.
5. Modbus/DNP is communications protocol that is typically used in a sub-station environment
utilizing an RS-232 or RS-485 connection from the meter to a remote terminal unit (RTU).
A Home Area Network (HAN) radio is a transceiver IC that is installed in the meter and enables two-
way low power short distance communication to devices inside the home.
Chapter 6
Service Switch
105
106 Service Switch
Network Operation
Features and Functionality Center
As deregulated markets and electric
Handbook for Electricity Metering
The methods and procedures for disconnection and reconnection will vary according to the operating
practices established by each utility to best suit their individual circumstances.
Pre-Payment
Pre-payment gives the customer the option to pay as you go for their electricity usage and allows the
utility to turn power on and off in response to this prepayment activity. Many customers may have
difficulty paying the higher monthly electric bills or may have a previous poor payment record, limit-
ing their ability to obtain electric service. The pre-pay option allows customers to pay at more frequent
intervals, providing these customers with another way to better manage their electric usage. There are
many methods for pre-payment services, including the use of home area networks (HAN) interfac- 107
ing with AMI networks, internet services, and advanced meters to monitor customer usage data and
automatically control the service switch.
Service Switch
Load Limiting
For some customers, it becomes necessary for the utility to limit the maximum amount of load cur-
rent well below the meter socket’s maximum limit. By configuring programmable limit values in the
meter software, the utility can set the meter to automatically disconnect service at specific amperage
and reconnect service after a set amount of elapsed time. This limit allows the customer to still oper-
ate a small number of necessary household appliances and heating and air conditioning without using
a large amount of power. The load limiting option provides utilities another option of service offering
for those customers who may not normally be able to regain service due to past payment history.
Utilities may also benefit from the practice of load limiting. During extreme periods of cold or hot
weather conditions, transformers may be stressed to overloaded capacities. Using the AMI and meter
data management systems, the utilities can identify the overloaded transformers which are likely to
fail. Targeting operation of the service switches specifically served by these transformers allows the
utilities a method to limit loads for certain customers during these emergencies.
Load Management
In cases where demand can overwhelm the generating capability of the system, e.g., due to severe
weather or generation failures, the ability to selectively disconnect power to a large number of custom-
ers may be necessary. In the past, this practice, known as a rolling brown-out or load shedding, would
be controlled at the feeder level, effectively shutting off entire sections of the distribution network
without regard to customer load priority. This created safety issues due to the indiscriminate discon-
nection of street lights, railroad crossings, customers on life-support systems, etc. Instead of discon-
necting power at the feeder level, the remote service switch enables electric utilities to disconnect
the customer load at the meter base. This allows the utility to precisely target and control the type of
load that remains on the grid, so that high priority customers such as hospitals, critical care centers,
certain water treatment facilities, gas distributions facilities, emergency broadcast facilities, and others
will be able to continue full operation. By shedding non-critical loads such as residential and small
commercial customers, the utility can ensure system frequency and service to life and safety critical
loads.
Other Benefits
Utilities may also receive other benefits from the universal deployment of AMI systems and meters
with remote service switch capabilities. Remote switch operation no longer requires the meter to be
removed from service when customers relocate and disconnect service. In addition, maintaining meter
inventories to accommodate the removal and installation of meters for customer relocations is no
longer needed.
Customer service is improved when service switch activation occurs almost as soon as the cus-
tomer’s request. Customers no longer need to wait for long periods of time to obtain electrical service
from the utility. Remote service switches also offer the ability for the customer to stop receiving
electrical service at a specific time of the day or week, allowing for more flexibility for the customer.
Remote service switch technology allows the utility to target disconnects early in the morning
before normal business hours. This alerts the customer before leaving their residence to the power
disconnect and gives the customer the option to restore power immediately, thereby not being without
power for the entire day.
Utilities see many benefits from not having to dispatch a field employee to a residence to take
action. Customer privacy is maintained and utility employees are not exposed to liabilities such as pets
at the premise, navigating around locked gates, traveling on busy roads, or dealing with disgruntled
customers.
108 Design Criteria for Internal Service Switches
Internal service switches contained in smart meters have several important requirements that affect
how service switches are designed and constructed.
Handbook for Electricity Metering
• The switch must efficiently conduct the rated current of the meter.
• The construction of the switch must fit within the confines of the American National Standards
Institute’s (ANSI) standard spacing and accommodate the current sensing method of the meter.
• The switch must maintain its performance over the rated life.
• The switch must safely withstand fault conditions to which the meter may be exposed.
Internal service switches have found widespread application in North American markets where the
majority of meters have a Class Load rating of 200A. Although feasible to construct, service switches
for 320A application are not yet in widespread use. Internal service switches do not have an applica-
tion in transformer-rated meter installations since they cannot interrupt the power delivered to the
consumer.
It is a design goal to minimize the power dissipated in an electricity meter. Wasted power con-
tributes to utility losses. Power is also lost in the form of heat inside the meter enclosure that must
be conducted or radiated to the external environment. Because meter enclosures are designed to be
weather-proof and protect against the possibility of exposure to electrically live parts, the enclosures
are typically sealed and made of non-conductive materials. This means that it is difficult to effectively
remove waste heat from a meter. Excessive temperatures can adversely affect the reliability and per-
formance of the meter. Therefore, maintaining a low electrical resistance in the current conductor
construction is essential.
Current is routed from the line-to-
load terminals of a meter by means of
an electrical conductor. In a traditional
watthour meter this has typically been
done by using a rigid conductor of appro-
priate gauge made of highly conductive
copper or aluminum or some combination
thereof. The problem is somewhat more
difficult in a meter with an internal service
switch. Since there must be some means
of interrupting the current, the efficiency
of the switching element itself must be
considered. While there are many means
of controlling current flow using semi-
conductor devices, as of the time of this
writing none of the available technologies
can meet the efficiency requirements of
a metering application in a cost effective
Figure 6-3. Electromechanical Relay. manner. Although research continues in
the area of alternative technologies, all
commercially available internal service
switches are presently based on electromechanical relay technology. An electromechanical relay funda-
mentally involves a moving conducting element, an electrical contact surface, and an actuator.
Moving Condcutors
A relay mechanism must include at least one moving conductor to open and close the switching
contact surfaces. The moving conductor may be constructed of either a rigid moving element with
contact surfaces mounted at both ends or of a flexible moving element with one fixed end and one
free moving end on which the contact surface is mounted. There are economic and performance
trade-offs associated with either approach. Typical copper or aluminum conductors used in bus-bars
and single strand wire are very highly conductive but they are not flexible. Wires or braids made of
highly stranded fine-gauge wire are both flexible and conductive but they are also relatively expensive.
Alternatively, conductors that are solid yet flexible must be alloyed with other materials in order to
obtain their springy mechanical properties and this generally results in a conductivity that may be only
80% to 90% that of electrical grade copper. The majority of service switch designs in use today employ 109
some type of flexible copper alloy conductor with a fixed end and a movable contact end. This conduc-
tor is sized to minimize the resistive losses. The fixed end is typically bonded to a rigid electrical grade
copper conductor to complete the current circuit through the meter.
Service Switch
In a switching application, the current must pass through one or more pairs of conductive contact
surfaces which are moved apart to interrupt the current flow or forced together to allow current to
flow. There are many considerations in contact design but the factors of efficiency, reliability, and cost
are predominant.
actuators
In order to open or close the service switch, there must be an actuating device. Since the switch may
remain in a given state for an extended period of time, it is desirable that the actuator not require any
energy to maintain its state. Energy must be applied to change the state of the switch, but when it is
in one state or the other it does not require additional energy. Such a mechanism is called bi-stable.
There are many ways to construct a bi-stable actuator. Common methods in use today include the
use of permanent magnets to latch the armature of a solenoid or rocking H-shaped mechanism, or by
the use of a machine such as an electric motor drive and cam. Some of the factors that influence the
design are the energy source available to drive the actuator and the ability to resist mechanical shock
or other outside influences.
In the field it is possible that the switch may be exposed to high-current electrical faults in the
metered premises. As mentioned earlier, a repulsive effect is generated between contact faces by the
current constriction in the contact asperities. Normally these magnetic forces are insignificant and
are overcome by the normal mechanical forces of the mechanism. At high fault currents (several
thousand amperes), these repulsive forces become significant and, if not accounted for in the design,
110 may force the switch contacts open. A very high energy level could be dissipated in an arc between the
contact faces if this happens, resulting in potential destruction of the contact and associated electri-
cal conductors. To prevent this, the internal service switch is carefully designed to balance the high
current magnetic forces to keep the contacts closed.
Handbook for Electricity Metering
Testing
Utility Acceptance Testing
Remote service switches are built as an integral part of a solid state watthour meter and are subject
to the individual utility’s receiving inspection testing process that watthour meters without a service
switch would go through. Depending on the inspection process, the service switch may or may not be
subject to a functional test.
For First Article Testing (FAT) processes, utilities should test and verify that all communication
methods for operating the service switch mechanism are working properly. Communication methods
may include the AMI communication network, communication through the meter’s optical port, or
any other optional method that the meter utilizes for operation of the switch.
The FAT process of the service switch should also include operation of the switch under the meter
test amp (TA) load condition.
The switch should also be tested to verify that closure operation is not allowed when the meter’s
programmed load side voltage threshold is exceeded.
Service Switch
the meter insulation test.
Tests Unique to Meters with Service Switches
In addition to the tests already specified in C12.1, C12.30 lists other tests specific to the service switch
such as cycling, continuous load current, close on fault, and load side voltage sensing.
The first such test is for cycling (an open and close of the switch contacts) of the switch. The test
specifies a number of cycles without any electrical load and a smaller number of cycles with a load.
The unloaded test is to prove the mechanical aspects of the switch, both the moving parts and the
electrical drive mechanism. The test with an electrical load is to prove the robustness of the electri-
cal contacts. Electrical contacts wear as a circuit is opened and closed. If the contacts wear out, the
electrical resistance increases and can cause excessive heat in the meter. To verify that the contacts are
still in good condition after the cycling test, a heat rise test is performed. The number of cycles speci-
fied in C12.30 is many more than the number of cycles expected in the meter’s service life.
The purpose of the Continuous Class Amp Test is to validate the continuous class amp rating of
the service switch in a given metering device. This test operates a metering device at room temperature
at maximum rated class amp continuously for a specified duration. The meter must still be accurate
and fully functional after this test.
Another test unique to service switch meters is the close on fault test. This test is similar to the
Through Fault test, but at the start of this test the switch is open and then the switch is closed into
the high current overload. As in the Through Fault test, after the test the meter is not required to be
functional; it is required to be safe.
The last unique test for meters with a service switch is to verify that an open switch will not
close when there is voltage on the load side. If the electrical service has been turned off with the
service switch in the meter, it would be possible for the customer to hook up an auxiliary source of
power. This could be from a neighbor’s electrical service, or, more probably, from an auxiliary genera-
tor. Because an auxiliary generator will not be phase locked to the utility voltage source, closing the
meter’s service switch may damage the generator and electrical loads. Meters are required to sense
the load side voltage and not close if a significant voltage is present. The meter’s switch will function
properly when the load side voltage is removed.
Chapter 7
Communications
Introduction—Communication Systems
The evolution of communication technologies and system advances have enabled advanced
metering services for the electric utility industry. The most basic of these advanced metering services
is the ability to read the meter remotely. Systems that perform this fundamental task are generally
referred to as Automated Meter Reading (AMR) systems. AMR systems have one-way communications
for meter reading with little or no other advanced functionality.
Further evolution has yielded meters and systems with even more advanced functionality,
including meters with the capability of recording interval data, recording power quality informa-
tion, recording bi-directional energy flow, integrating with an outage management system, providing
end-use customers access to meter data via Home Area Networks (HAN), and being connected and
disconnected by a remote service switch. Metering systems with this level of functionality are typically
referred to as Advanced Meter Infrastructure (AMI) systems.
113
114 The meters are polled by a handheld terminal or a vehicle-based collection unit, often referred to
as a “walk-by” or “drive-by” AMR solution, respectively. Both solutions allow for the mass collection
of meter readings from many meters simultaneously, thereby improving the overall efficiency of the
manual meter reading process.
Handbook for Electricity Metering
Daily, the readings are brought back to a central office and loaded into the utility’s billing system.
Depending on meter density, memory capacity, and the type of readings collected, handheld collection
units (walk-by) are typically capable of reading several hundred meters in a day. Mobile-based (drive-
by) units, on the other hand, improve meter reading efficiency to the thousands of meters read within
a single day. While the human meter reading process is limited to being performed during daylight
hours, mobile-based meter reading is not. Thus, some utilities utilizing the “drive-by” solution have
introduced a second and even a third shift for their meter reading functions.
Communications
Figure 7-1b. AMR Modules are “Built In” to Figure 7-1c. Example of a Handheld Reader.
Electronic Meters.
number is typically a toll-free number so there is no per-call or long distance cost for the customer.
Also, if the phone line is busy or the customer picks up the line during the middle of the meter’s
communication period, the meter hangs up immediately, releasing the phone line for the customer’s
use. The meter tries to call again at a later time.
The investment costs for a dial-in can be low and effective in remote and low density locations.
Dial-in systems generally rely on the customer’s telephone lines, which are vulnerable to interrup-
tion resulting from the customer either changing or even eliminating their phone number or service,
usually done without notifying the utility. Another consideration when utilizing in-bound telephone
technology is that customers are trending towards eliminating land lines, instead relying on their cell
phones for daily use.
Cellular Systems
Originally, cellular systems were implemented in the same manner as wired telephone systems, only
without a physical telephone connection to the meter. As the communication technology evolved from
an analog environment to a fully digital environment, cellular systems also evolved, utilizing more
standard digital computer protocols and methodologies.
Today, most utilities using a cellular system have established a Virtual Private Network (VPN) with
the cellular provider of choice. The VPN connection establishes a secure connection from the utility
through the cellular provider’s network to each meter within the system. With the VPN connection,
the utility’s information technology (IT) department can manage access to specific computers within
the company. In some cases, the collection of the data is performed by the provider and the VPN
connection is then used as the secure path to deliver the data. In either case, the meter itself contains
a cellular modem which allows it to connect to the service provider’s system. However, in lieu of a
telephone number, each cellular modem is assigned an IP address that connects with each meter.
An agreement between the cellular provider and the utility is required to establish a VPN con-
nection. Some utilities have agreements with multiple cellular providers, depending on their cellular
coverage. Each meter department must ensure that the cellular modems are compatible with the
cellular providers’ system where the meters are deployed.
Satellite Reading Systems
In some very remote locations, satellite communications are a more viable option for meter reading as
the area may not be practical for telephone or cellular service, meters may be spread too far apart for
radio frequency (RF) communication, or it may be a long distance to the nearest meter reader’s office.
This may lead to the choice of satellite communications for reading such meters. A ground based radio
is attached to the meter’s communications port. Throughout the day and night telecom satellites pass
over the meter’s location. When a connection is established, the data packets are sent as a high speed
burst into space and retransmitted by Low Earth Orbiting Satellites (LEOS) back to a Satellite Network
Operations Center (NOC). From the NOC, the data is transported to the utility, usually via a secure
File Transfer Process (FTP). Once received by the utility, the data is routed to load research or billing
systems as needed. It should be noted that due to the communication system, the utility meter reading
and programming system is not connected to the meter, so reprogramming or other “on-demand”
data that can typically be requested from a “network system” are not possible and require a field trip
to the meter site. This technology tends to be much more expensive than the host of other alternatives
and therefore is rarely used by utilities.
Communications
gies to determine the best fit for their requirements. With the passage of the American Recovery and
Reinvestment Act (ARRA) in 2009, federal funding was provided to accelerate AMI deployment. This
resulted in significant growth of AMI implementation and many utilities with mature AMR systems
began transitioning to AMI.
The major differences between AMI and AMR systems focuses on the following three areas:
a. The communications capabilities between each meter/device and the back office.
b. The amount and type of information provided by the system.
c. Advanced functionality available as a result of the additional communications and information
capabilities.
AMI requires full two-way connection between each metering point and the back office system,
utilizing a fixed communication network. In an AMI system, meter data can be obtained upon a
calendar schedule or requested on demand. Furthermore, the AMI meter is capable of providing more
information than is typically available in an AMR system. In addition to basic billing information,
AMI also provides power quality information, alarm and event data, and power outage and voltage
information, all of which may be provided back to the utility in either a near or real-time manner.
The head-end system collects the data and transfers the appropriate consumption data to the utility’s
billing system. Where AMR can be adapted to a simple electromechanical meter to primarily retrieve
register reads, AMI requires an electronic meter platform that can be programmed with the advanced
functionality to act as both a billing and monitoring end-point.
Early communication devices required control circuit board components which were used for
switching, filtering, surge protection, etc., to be combined into a separate circuit board, often referred
to as a communications module. Power requirements for the communication module were extensive
and required a separate power supply from the meter. This arrangement is known as a modular meter
design. As technology advanced, the power requirements for the communication modules dropped so
that the metrology power supply would be sufficient to power the meter as well as communications.
This allowed for the integration of communications and metrology into one circuit board, resulting in
a common device, an integrated meter, with a reduced cost. Many manufacturers incorporate the AMI
communication device on the metrology board.
In addition to the communication module necessary to connect the meter to the utility, AMI
meters may also contain an additional communication device to communicate to a HAN.
All advanced metering systems rely on a fixed two-way communications network to relay the cus-
tomers’ meter information to the utility and commands from the utility to the meter. From telephone
modems and switched public networks to power line communications or carrier systems, RF transmis-
sion or cellular telephone service, a communication infrastructure must be developed and supported.
Additionally, these systems must have sufficient bandwidth capacity to allow the data to flow in either
direction. The time it takes for a message to travel from a host to a client, referred to as latency, is
a factor when considering uses of the communication infrastructure with critical alerts or messages.
Another network characteristic is throughput, which is the ability of a communication network to
handle the volume of data when there is a major outage or a load control event.
Some additional factors that need to be considered when designing an AMI system:
• Topography, i.e., whether the area is flat versus mountainous.
• Customer density, as urban areas have greater density but can also cause throughput concerns,
while rural areas can extend great distances for a minimal number of customers.
AMI systems generally employ PLC and RF technologies. There are two types of RF systems, mesh
systems and point-to-point systems.
enhanced communication protocols to achieve the full two-way communications required to provide
interval data and other value-added services.
A common feature of PLC systems is that they all must operate within the harsh constraints of
the power line as its communication medium.
Communications
tions. The head-end system then forwards the multi-meter data to a meter data management system
(MDMS) and other utility application programs.
A point-to-(multi) point system is self-healing, like a mesh network, to ensure that each meter
has multiple paths to a data collector. Typically, within a point-to-(multi) point system, there is a
limit to the number of meters that can talk to a data collector.
Hybrid Solutions
It should be noted that even though radio frequency (or wireless) systems are generally classified as
either a mesh or a point-to-(multi) point system, some system providers have introduced features
that use both technologies, creating a hybrid model. For example, in a point-to-(multi) point system,
there are usually specific metering locations which are not able to connect directly with any routers/
collectors within the system. In lieu of installing a dedicated data collector for that one location, a
mechanism can be introduced where a limited number of meter-to-meter, mesh-like, communications
can be put in place, thereby allowing the communications to work itself around the blockage. On the
other hand, most mesh networks are generally designed with a single data collection point for each
mesh node as its communications path to the home office, in much the same way as the point-to-
(multi) point system.
Communications Media
Given that the lifecycle of a substation is over 50 years and the monitoring and control equipment
is somewhat less, various generations of technologies must co-exist at times. Communications avail-
ability can range from none to full gigabyte (GB) Ethernet over fiber optic cable. Substation metering
must be capable of bridging the gap between communications upgrades. A few examples of media
requirements are:
• Optical ports for local connection
• On-board Public Switched Telephone Network (PSTN, a.k.a. POTS) modems
• Serial ports for local and remote communications
• On-board Ethernet network interface card supporting 10 megabyte (MB), 100MB, and even
1GB speeds for both RJ-45 (copper) and fiber optic connections
The physical requirements of this variety of connections and cables may cause substation meters to
be larger in size and more difficult to install and wire. Also, the complexity of configuring the meter’s
communication and managing security access increases.
Protocols
Data from substation meters can be used for many different applications, each requiring a different
set of data to be presented in a different level of detail. These differences gave rise to various protocols
120
Modem Ethernet PQ Monitoring
Billing System and Analysis
TCP/IP
Handbook for Electricity Metering
RS-485
Customer Service
Direct IRIG-B
Time Synch
RS-232
SCADA System
with which to communicate the data. Historically, each manufacturer created its own protocol to
transfer data between devices and between devices and remote systems. Over time, industry groups
have tried to create standard protocols for manufacturers to implement in order to reduce the con-
figuration and maintenance complexity for the end-user. Various interest groups within the industry
tackled different topics and data sets, leading to a variety of protocols that are application-specific and
even, in some cases, geographically specific. Early control applications used the Modbus protocol for
machine-to-machine communications. In fact, this practice is still prevalent today. The North Ameri-
can groups for SCADA communication created distributed network protocol (DNP), while the same
groups in Europe created International Electrotechnical Commission (IEC) 61870-5-101.
Neither of these protocols addressed the need for transmitting waveform data, thereby precipitat-
ing yet additional protocols targeting this specific requirement. For example, Common Format for
Transient Data Exchange (COMTRADE) was developed to transfer waveform and power quality data,
though some utilities preferred to use Power Quality Data Interchange Format (PQDIF). Revenue
metering data was addressed by neither COMTRADE nor PQDIF standards, but was addressed by
separate groups. In the IEC community, the Device Language Message Specification/Companion
Specification for Energy Metering (DLMS/COSEM) protocol was created, while the North American
groups worked to develop American National Standards Institute (ANSI) C12.19 and C12.22. In the
interim, some software companies created applications to use vendor-specific protocols to transfer
revenue data, thereby giving the end-user a multi-vendor tool for revenue data collection. As a result,
many substation meters must be capable of simultaneously supporting any or all of these protocols.
Access control
Allowing remote users to connect to a device improves operational efficiency but raises issues regarding
control of the integrity of the data and the device configuration. Substation meters must allow for the
control of the access rights for various users based on the application. In addition, substation revenue
metering configuration may be required to have an electronic sealing function such that no one can
change parameters that would impact revenue billing without regulatory approval. Other systems may
require read-only access to a restricted set of data. Substation meters must control both local and
remote communications access rights in a manageable way.
Communications
Ethernet Serial Serial
Communications to a Gateway
Meters can have linked communications to allow a group of meters to communicate over the same
network bus to a gateway and permitting communications to all the devices, which would allow a
system (e.g., SCADA, DCS, BAS, etc.) to communicate to all the devices on the bus as required. The
bus, typically RS-485, is able to allow 32 devices to communicate up to 4,000 feet. A gateway can
be created using an Ethernet connection (Ethergate) or a modem connection (modemgate) to the
485 loop.
Master
RS-485 or Ethernet
limited to, in-home displays, computers, energy management devices, security, entertainment devices,
load control devices, remote home management, distributed energy resources, thermostats, and smart
meters. home area networks can be wired or wireless.
There can be a variety of topologies for a hAn. one such configuration, called a utility Managed
network, is shown below in figure 7-5. The hAn may be as simple as the meter and an in-home
display. The customer may or may not have any input into the hAn.
A more complex configuration for a hAn is shown in figure 7-6, which can be called a Consumer
Managed network. All equipment below the consumer boundary is typically owned and controlled by
the home owner or end user. While the electric utility has input into the network, any decisions on
control of end devices are made by the customer (or even a third party if the appropriate permission is
granted by the consumer) either manually or by the programming of the home controller. The home
controller can be either built within a hAn device, such as a thermostat, or via software loaded onto
the consumer’s equipment.
Utility
Utility
Communications
Meter
Consumer Boundary
Consumer
Communications
Figure 7-6. Consumer Managed Network.
Ethernet requires dedicated wiring, (a dedicated wire to each device) it can be expensive, especially
when retrofitting existing locations. Also, not all energy-related devices are made with an Ethernet
interface and many energy-related HAN devices do not need as high a data rate as available through
an Ethernet connection. While wired networks are common in commercial settings, they are much
less common in residential applications.
There are other wired communications methods, such as RS-232 and RS-485 type connections
which, like Ethernet, utilize serial communications standards. RS-232 and RS-485 define only the
physical layer of the communications interface; they do not address any aspect of a protocol. Even
though RS-232 has been used for many years, its use is diminishing since it is used for primarily
point-to-point communications, while RS-485 can be used in multipoint applications. RS-485 is also
more common in industrial locations and can be configured in 4-wire (full duplex) or 2-wire (half
duplex) arrangements.
One example of a common application within the metering arena of an RS-485 connection is the
sharing of one telephone modem with many meters, each meter being equipped with an RS-485 wired
connection module.
Wireless
RF devices are much more common in residential applications because they have low installation costs
and are typically offered at a good price for the performance characteristics provided. A mature and
widely accepted standard for RF communications is Wi-Fi (IEEE 802.11). This standard, first published
in 1997, has been amended many times to add new capabilities. While there are inexpensive chip sets
available for integration into equipment, the power requirements of this communications technology
limits battery operation. Security within the communications was first implemented as IEEE 802.11i
and has been evolving over the years. The Wi-Fi Alliance industry group specifies their specific security
and operational characteristics to ensure interoperable implementations.
124 The most common wireless HAN protocol used in smart meters is ZigBee. Designed specifically
with low power consumption requirements and low data rate operation in mind, some product designs
can have battery life lasting several years. ZigBee is controlled by an industry alliance that defines
specifications and certifies product interoperability. It has developed a large base of manufacturers
Handbook for Electricity Metering
and a broad array of products. The packet-based protocol uses the IEEE 802.15.3 standard and allows
devices to communicate in a variety of network topologies. As with Wi-Fi, ZigBee also uses the indus-
trial, scientific, and medical (ISM) frequency bands. The maximum data rates depend on the specific
frequency band used and can be up to 250kbits/s. The advertised indoor range is up to 200 feet.
ZigBee allows for several levels of security, varying from none to full encryption and authentication.
There are a few other wireless communications that are much less common. Bluetooth is widely
used in short range communications, e.g., for a cell phone to headset wireless connection. However, it
has not gained a general acceptance in HAN applications because it has limited networking and range
capabilities. Bluetooth is based on the IEEE 802.15 standard.
Another low-power RF communications HAN technology is Z-wave. It is designed for low data
rate (up to 100kbits/s in the ISM band), secure communications, and status and monitoring. Many
products are available with this technology in the areas of security, remote home management, energy
conservation, home entertainment, and home comfort.
Power Line Communications (PLC)
Some home networks have been developed to use the existing home wiring as the communications
connection. A major advantage of PLC is that there is no need for additional wiring within the home
or facility to talk with alternating current devices. While power lines were not developed as a com-
munication path and are subject to a variety of noise sources, modern electronics can be made to use
this noisy path to make reliable communications through the selection of a less noisy frequency range,
spread spectrum techniques, and forward error correction coding.
One example of a PLC network is HomePlug, which is able to provide reliable communications
over existing house wiring. HomePlug is designed for high data rates to support video, but HomePlug
Green PHY (GP) was developed specifically for use in smart grid areas. It has a lower data rate (up
to 10Mbit/s), lower power, and lower cost, but is still compatible with other HomePlug networks. GP
uses AES-128 encryption to provide secure communications.
Another networking system (ANSI/CEA-790.1) that can use PLC as its communication network is
LonWorks. While LonWorks is more common as a HAN in Europe, it is also used in industrial control
in other locations, including the U.S. Using PLC, it has a low data rate (less than 10kbits/sec) but
uses the bandwidth efficiently.
Communications
IP-based networks. SEP2 will not replace ZSE, as both profiles continue to evolve for their particular niches.
Smart Energy was developed by an industry confederation, with domain experts from utilities,
service providers, meter vendors, appliance makers, consumer electronics manufacturers, and security
firms. In addition to the profile itself, this confederation also produced the test plan and certification
process that ensures interoperability among all devices that carry the Smart Energy label. While mil-
lions of SEP 1.x devices have been deployed already, SEP2 is in the later stage of development. ZigBee
and HomePlug both offer products with SEP certification.
all remote endpoints. This includes software and firmware upgrades to meters/endpoints and other
network components as well as the capability to operate service switches and collect data through
scheduled and on-demand reads.
Typical HESs employ an easy to navigate user interface referred to as an AMI dashboard to assist
the user in the operation of the AMI system functionality. Most user interfaces are equipped to
provide real-time network diagnostics and status information for quick analysis of particular devices.
A standard user interface provides quick access to key performance indicators, exceptions, and system
reports.
The conventional HES has the capability to track the installation of endpoint devices and sync
installation data with other systems (i.e., customer information system, meter asset systems), which
is particularly helpful during the initial deployment. The HES facilitates the deployment of network
devices and hardware in a seamless fashion. The AMI system should continuously monitor all end-
points and send alerts to the HES as diagnostic activities dictate.
One of the key features of the HES is the capability to provide current and exception reporting
of the key information at specific customer installation sites, including such information as power
quality, voltage, outage, high usage, and demand.
The HES also has the ability to securely provision the customer’s HAN devices through the AMI
network. The HES should support industry standards such as Web services application programming
interface (API) and IEC 61968 (Common Interface Model) standards to enable third party applica-
tions to interface with the AMI system.
A very necessary feature of the HES is the ability to process and log large numbers of meter outage
and restoration events and have the ability to report these occurrences to the utility outage manage-
ment system, distribution management system, and other applications.
Introduction
The smart grid is an environment of components, applications, and users networked together to
provide intelligence pertaining to the operation of the electric grid. Every user will have their own
definition of what the smart grid means to them and utilities will have a specific set of targeted
objectives as business reasons for deploying smart grid technologies. However, advanced metering is
a significant component of the smart grid, providing information for enhanced network operation,
distribution asset management, revenue billing, outage and restoration management, and a myriad of
other applications, some of which are still yet to be identified and applied.
20th Century
For all practical purposes, commercialization of electric power began early in the 20th century. With
the light bulb revolution and the promise of the electric motor, demand for electric power exploded,
sparking the rapid development of an effective distribution system. At first, small utility companies
provided power to local industrial plants and private communities. Some larger businesses even
generated their own power. Seeking greater efficiency and distribution, utility companies pooled their
resources, sharing transmission lines and quickly forming electrical networks called grids.
Technological improvements of the power system largely arose in the post–World War II era of the
1950s and 1960s. Nuclear power, computer controls, and other developments helped fine tune the
grid’s effectiveness and operability. However, even though today’s consumer electronics technology has
rapidly advanced, the national power grid has evolved little over the past 50 years.
Over this period, power grids grew and were eventually interconnected for economic and reliability
reasons. By the late 1960s, the electric grids of developed countries had become mature and highly
127
128 interconnected, with thousands of central generation power stations delivering power to major load
centers via high capacity power transmission and distribution lines. The topology of the 1960s grid
evolved from the economies of scale of existing generation technology consisting primarily of large
coal-, gas-, and oil-fired power stations in the 1 GW (1000 MW) to 3 GW scale. Even today, this
Handbook for Electricity Metering
topology is still cost-effective, due to efficiency improvements that can be cost-effectively added.
Power stations were located strategically to be close to either fossil fuel reserves (either the mines
or wells themselves) or, alternatively, to transportation centers such as rail, road, or port supply lines.
Siting of hydro-electric dams in mountain areas also strongly influenced the structure of the emerging
grid. Nuclear power plants were cited for availability of cooling water. Finally, fossil fuel–fired power
stations at the turn of the 20th century were polluting and were therefore located as far as economi-
cally possible from population centers. By the late 1960s, the electricity grid reached the overwhelm-
ing majority of the population of developed countries, with only outlying regional areas remaining
off-grid.
Through the 1970s to the 1990s, growing demand for electricity led to increasing numbers of
power stations. In some areas, the supply of electricity, especially at peak times, could not keep up
with the ever-increasing demand, resulting in poor power quality including blackouts, power cuts,
and brownouts. Increasingly, electricity was depended on as a major economic driver for industry,
heating, communication, lighting, and entertainment, and consumers demanded ever higher levels of
reliability. The goal of matching consumption to generation required meters which could measure the
time of day of the consumption in addition to the cumulative consumption. Automatic meter reading
devices and time-of-use (TOU) metering introduced in the 1970s were the beginning of a means of
matching the time differentiated cost of generation to a consumer’s consumption pattern, focusing on
the highest cost period of time.
Toward the end of the 20th century, electricity demand patterns were established with domestic
heating and air-conditioning leading to daily peaks which were met by an array of peaking power
generators that would only be turned on for short periods each day. The relatively low utilization of
these peaking generators (commonly, gas turbines were used due to their relatively lower capital cost
and faster start-up times), together with the necessary redundancy in the electricity grid, resulted in
high costs to the electricity companies, which were passed on in the form of increased tariffs.
21st Century
Since the early 21st century, opportunities to take advantage of improvements in electronic commu-
nication technology have moved the informational feedback mechanism of the electric grid to include
more proactive measures. Technological advancements within the metering arena, including the
introduction of advanced metering infrastructure, no longer force peak power prices to be averaged out
and passed on to all consumers equally. With the advent of real-time pricing structures, customers can
take advantage of monitoring their consumption in a more real-time manner and match their indi-
vidual lifestyles to the associated pricing considerations for the generation and delivery of electricity.
In parallel, growing concerns over environmental damage from fossil-fired power stations has led
to a desire to use large amounts of renewable energy. Dominant forms, such as wind power and solar
power, are highly variable, and so the need for more sophisticated control systems became apparent to
facilitate the connection of sources to the otherwise highly controllable grid. Power from photovoltaic
cells (and, to a lesser extent, wind turbines) has also significantly called into question the imperative
for large, centralized power stations. The rapidly falling costs point to a major change from the cen-
tralized grid topology to one that is highly distributed, with power being both generated and consumed
right at the limits of the grid. Finally, growing concern over terrorist attacks in some countries has led
to calls for a more robust energy grid that is less dependent on centralized power stations that were
perceived to be potential attack targets.
All the technologies developed over the last century were necessary foundations for building the
safer, more efficient, and more reliable electrical distribution network that will eventually become the
smart grid. With today’s technology, the power grid can become smarter by allowing two-way commu-
nication between the utility and individual customers. The constant sensing and real-time load moni-
toring along the transmission and distribution lines is what makes the grid smart. Like the Internet,
the smart grid will consist of load and event monitoring, computers, and automation controls working
together to respond digitally and efficiently to our quickly changing demand for electricity.
Definitions 129
What Makes a Grid “Smart?”
In short, the advanced technology that allows for two-way communication between utility grid com-
Advanced Meters
Advanced Meters and Advanced Metering Infrastructure
Since the inception of electricity deregulation and market-driven pricing, utilities have been look-
ing for a means to match consumer consumption with generation. Traditional electric meters only
measure total consumption and provide no information of when the energy was consumed at each
metered site. Advanced meters provide a way of measuring this site-specific information, allowing
price-setting agencies to introduce different prices for consumption based on the time of day and
season.
Advanced metering is defined as a metering system that records customer consumption (and
possibly other parameters) hourly or more frequently and provides for daily or more frequent trans-
mittal of measurements over a communication network to a central collection point. The terms
advanced metering and advanced metering infrastructure (AMI) are used interchangeably (Federal
Energy Regulatory Commission [FERC] 2006; http://www.ferc.gov/legal/staff-reports/12-08-demand
-response.pdf).
Smart Meters
The term smart meter is also used interchangeably with AMI and advanced meters. For example, in
2013, the Department of Energy (DOE) defines AMI and smart meters the same, as “Electricity meters
that use two-way communication to collect electricity usage and related information from customers
and to deliver information to customers” (DOE; http://www.smartgrid.gov/glossary).
Figure 8-1. National Institute of Standards and Technology (NIST) Smart Grid Framework.
130 Furthermore, the DOE breaks down the definition of smart meters between residential and com-
mercial/industrial as follows:
• Residential—A meter that records a customer’s electricity usage for time intervals of one hour
Handbook for Electricity Metering
or less, and can transmit that information to the utility without the need for a human meter
reader. Depending on the feature set, the meter may also notify the utility of a power outage,
provide pricing or other information to the customer, or allow the utility to remotely switch
electricity service on or off. (DOE; http://www.smartgrid.gov/glossary)
• Commercial/Industrial—A meter that records a commercial customer’s electricity usage for
time intervals of one hour or less, and can transmit that information to the utility without
the need for a human meter reader. Depending on the feature set, the meter may also notify
the utility of a power outage and provide pricing or other information to the customer. (DOE;
http://www.smartgrid.gov/glossary)
Additional Information
For more information, please reference the following websites:
• http://energy.gov/oe/technologydevelopment/smartgrid — Department of Energy Smart Grid
• http://www.nist.gov/smartgrid/ — NIST Smart Grid
• http://smmaa.org/ — Smart Meter Manufacturers’ Association of America (SMMAA)
• http://smartgridcc.org/ — Smart Grid Consumer Collaborative
• http://www.smartgrid.epri.com/Repository/Repository.aspx — EPRI Smart Grid Use Case
Repository
• http://www.sgiclearinghouse.org/ — Smart Grid Clearinghouse
Chapter 9
Instruments
ELECTRICAL MEASURING INSTRUMENTS are necessary because the nature of most electrical
phenomena is beyond the reach of our physical senses. Measurement of electrical quantities makes
possible the design, manufacture, and maintenance of the innumerable electrical devices now in use.
The main purpose of any electrical instrument is to measure and indicate the value of an electrical
quantity. The measurement may be indicated by a digital numeric value or by a pointer positioned on
a scale. Some instruments provide additional functionality by recording measured values over time.
This recording may be in the form of a physical indication on a moving chart, as maximum and
minimum values during a time frame, or as periodic data stored in electronic memory. Today almost
all instrumentation used in the metering industry is digital. There are a variety of general-purpose
instruments such as multimeters, as well as many specialized instruments like transformer testers,
communications testers, meter testers, and site analyzers.
133
134
HANDBOOK FOR ELECTRICITY METERING
• Signal processor—a computer chip which takes the raw data coming from the ADCs and com-
putes the parameters needed (voltage, amperage, power, VA, etc.).
• Display—a way to present the results to the user.
• Memory—a place to store data and, in more complex instruments, specific test processes.
• Comm—communications ports such as USB, serial, and Ethernet for communicating to other
devices, such as laptop computers.
The transducer, signal conditioning, and sometimes the ADC are often referred to as the “front end”
of the instrument. These are the analog sections of the device that are subject to temperature effects,
non-linearity, and other often difficult to characterize effects. Similarly, we refer to the signal proces-
sor and all of its associated peripherals as the “back end.” The back end is the digital section of the
instrument. The digital section is characterized by a different set of errors and behaviors. Here the
issues are related to computational concerns such as resolution, rounding, and algorithms.
TRANSDUCERS
Common transducers for current are shunts and current transformers (CT’s). These may be part of
the instrument or external to the instrument, like a clamp-on current probe. A shunt is a resistor spe-
cially constructed to allow the voltage across it to be accurately measured when current flows through
it according to Ohm’s Law (V IR). A shunt does not provide isolation of the current circuit. A
current transformer changes the level of the current precisely and provides isolation of the circuit. A
shunt resistor is still required to convert the secondary current of the CT to a voltage.
SIGNAL CONDITIONING
Signal conditioning circuits generally provide gain and or filtering of the signal. They may be com-
posed of discrete operational amplifiers (generally in high accuracy instruments) or be integrated into
a single large scale integrated circuit (IC) that has all of the analog and digital processing (like a hand
held multimeter).
ANALOG-TO-DIGITAL CONVERTER
An analog-to-digital converter converts an analog signal level into a numeric value. For alternating
current (AC) measurements, this process occurs many times during each cycle.
When the sampling frequency of the ADC is high compared to the frequency of the signal, the
signal can be measured accurately. Figure 9-2 shows a signal sampled at 16 times the fundamental fre-
quency. Provided the mathematics of the calculations are done with attention to detail—like frequency
determination and the effects of cycle by cycle computations—there is little difference in the accuracy
if the sampling frequency is at least 16 times the highest frequency in the AC signal. If the sampling
frequency is too low, then accurately computing the amplitude of the waveform becomes impossible.
135
INSTRUMENTS
Figure 9-2. Illustration of a Signal Sampled at 16 Times the Fundamental Frequency.
Figure 9-3 shows a signal sampled at about three times the fundamental frequency. While this does
satisfy Nyquist’s Theorem, it does not allow accurate computation of the signal amplitude in the time
domain.
The sampling frequency is not the only parameter of the ADC that effects accuracy. Other critical
parameters are listed below.
Resolution
Computer data is stored in binary format where each bit of the number can be either zero or one.
A 12 bit digital number can represent values from 0 to 4095, or a bipolar number from 2,048 to
2,047. A 20 bit digital number can represent values from 524,288 to 524,287. Table 9-1 shows
the approximate errors in calculating the RMS value of a sine wave as a function of ADC resolution
and percentage of full scale.
Precision
When making current measurements related to metering, an instrument may have to cover a range of
0.020 to 20 amps for a transformer-rated meter, or 0.2 to 320 amps for a self-contained meter. The
low end of these ranges are approximately 0.1% of full scale. For the ADC to have enough precision
136 Table 9-1. Approximate Errors in Calculating the RMS Value of a Sine Wave.
to cover the entire range, very high resolution is required. Most instruments approach this issue by
having multiple ranges (gains in the signal conditioning section). These ranges may be obvious (they
are selected on a dial on some multimeters) or set automatically by the instrument. A device might
have six ranges of 20 amps, 5 amps, 2 amps, 0.5 amps, 0.2 amps, and 0.5 amps paired with a 16 bit
ADC to achieve 0.01% precision throughout the full measurement range. Some modern devices use
as many as 16 ranges and some operate with only one using 24 bit converters.
Accuracy
So far we have only discussed precision of measurement, not accuracy. Your measurement cannot be
more accurate than its precision. The accuracy can be and often is much worse. For a measurement
to be accurate, it must be traceable to a national standard with a known uncertainty. When we say an
instrument is accurate to 0.01%, we generally mean that 95 percent of measurements made will fall
within 0.01% of the true value. The accuracy of an instrument is actually a statement of confidence
in the measurement taken with this instrument.
Building an accurate instrument is much harder than building high precision instruments.
Issues Affecting Accuracy
Linearity: Any of the sections of the front end may exhibit non-linearity. A CT usually has some
linearity effects at very low currents (lack of excitation) and at high currents (saturation). Amplifiers
may also exhibit some non-linearities. ADCs have two forms of non-linearity: (1) differential non-
linearity is when each bit of the ADC does not have the same value, and (2) integral non-linearity is
the overall deviation of the measured value from a straight line.
Gain: All of the front end components can exhibit gain errors. This means that every measurement
will be either slightly lower or slightly higher than is correct. The amount of error will be proportional
to the measured value as a percentage of full scale.
Offset: Amplifiers and ADCs can exhibit offset errors. In an offset error, zero is not zero. The amount
of the offset error is constant in absolute terms for all values.
Historically, gain and offset errors were minimized by adjustments in the signal conditioning
section of the instrument. These were manual adjustments that were difficult and time-consuming
to perform precisely. In modern digital instruments these errors are usually corrected in the signal
processing section through a calibration process which can also allow correction of non-linearity and
other more complex errors.
Temperature: A device may be accurate at one temperature, for example 23°C in a lab, but inaccu-
rate outside at 45°C on a hot, sunny day. The temperature performance of a device is usually specified
as a range of temperatures over which the instrument performs to a specification combined with a
temperature coefficient for calculating the performance outside of the range.
A typical specification might be:
0.05% accuracy from 0°C to 40°C
Temperature Coefficient of 0.008%/°C for T 0°C
Temperature Coefficient of 0.005%/°C for T 40°C
Based on this specification the maximum error at 20°C would be 0.05 20 0.008 0.21%. 137
Based on this specification the maximum error at 62°C would be 0.05 22 0.005 0.16%.
Other: There are other things which can affect measurement accuracy, such as magnetic fields, but
INSTRUMENTS
they are not usually important except in very high accuracy measurements.
Digital Signal Processing
In the last two decades tremendous advances in digital processing have been made. Today a processor
that can perform millions of calculations per second with high precision costs only a few dollars.
These advances have enabled the high accuracy instrumentation available today.
Just as there are issues of precision in the ADC, there are similar issues in the digital processor.
Digital processors also represent values as binary numbers. Common representation formats are
shown in Table 9-2. To get from the raw data collected from the ADC to an answer such as 120.23
volts RMS, there are thousands of calculations involved. Consider the simple process of calculating the
sum of squares that is part of the RMS process. If the ADC has 16 bit resolution, then the product of
two values may be up to 32 bits in size. When summing many of these values the sum can exceed the
range of a 32 bit value.
If a full scale sine wave is digitized by a 16 bit ADC with 64 samples per cycle, then the sum of
the squared values is 34,356,460,758, which exceeds the maximum value of a 32 bit integer by a fac-
tor of 34. In the past, people invented various mathematical tricks to make these calculations possible,
but one of the effects was always a loss of precision.
This problem is the reason the high-precision digital instruments were so difficult to create for so
long. It is only in the last decade that cheap processors that can do these calculations are available.
Processors like the ARM family that power smart phones and make video games possible now allow
straightforward calculations with full precision. Even advanced analyses using fast Fourier transform
algorithms (FFTs) can now be done on multiple signals simultaneously.
Safety
The last decade has seen dramatic recognition for the need for safety standards for instrumentation.
The introduction of the IEC 61010 Safety Standard in 1990 represented a major milestone in instru-
mentation safety. In the current version of 61010-031, there are four safety categories defined for
instruments. Two of these categories are of special interest to the metering community.
CAT I Objects not connected to power mains.
CAT II Objects connected to mains but not part of the mains themselves, i.e., an electrical appliance.
CAT III The main system of a building. This area starts at the secondary side of the meter.
CAT IV The primary side of the meter and all parts of the utility distribution system.
Since the differentiating factor for CAT III versus CAT IV is the current-supplying capability of the
circuit, conservative practice would suggest that CAT IV might be more appropriate for someone work-
ing directly at the secondary side of a self-contained meter.
138
HANDBOOK FOR ELECTRICITY METERING
Figure 9-4. An Analog, Handheld Multimeter. Figure 9-5. An Early Digital, Handheld Multimeter.
INSTRUMENTS
The multimeter cannot measure power or ratios.
When voltages are measured one probe is placed on the point
to be measured and the second probe is placed on the reference
point. The reference point is generally neutral, but may be an
energized conductor in some circumstances. The currents found in
metering circuits are generally too large to be measured by placing
the meter in series with the circuit. So for current measurements
with a multimeter, a clamp-on current probe is generally used (see
Figure 9-7). This clamps around a conductor and measures the
current flowing in the conductor. Figure 9-7. A Clamp-on Current
One issue sometimes encountered in the use of digital multi- Probe for Use With a Multimeter.
meters (DMM) is the issue of “phantom voltages.” A typical DMM
voltage input has an impedance of 20 megaohms or more. With
this high impedance, a meter may measure voltages that are really
not there in the high electric fields surrounding a meter. This issue can be solved by either using a
meter with low impedance or using a lead set with a resistor built in between the two inputs. Phantom
voltages disappear when even a modest load is placed on the circuit.
Transformer Testers
Some meter installations utilize instrument transformers to step-down the service potential and cur-
rents to a level which can be safely measured by the watthour meter. To ensure accuracy of the entire
system, some utilities may choose to test the CTs and potential transformers (PTs) for accuracy and
proper functionality. Instrument transformer testing devices include ratio testers, burden testers, and
admittance testers.
RATIO TESTER
A CT ratio tester measures both the current in the primary conductor and the current in the second-
ary loop, allowing the user to calculate the actual ratio and compare it against the specified ratio of
the CT. As stated earlier in this chapter, amp-meters must be placed in series with the current being
measured. Due to the complexities, difficulty, and safety concerns with opening the primary current
conductor, an inductive-type current clamp is typically used to measure the primary current (see
Figure 9-7 and associated text above). Also, due to safety concerns and convenience, the ratio tester’s
secondary inputs are typically connected in series with the secondary current loop via the safety test
switch. Some modern testers are designed to measure both currents as close to simultaneously as
possible, to minimize the effects of changing customer loads during the test. Modern testers also
automatically calculate the ratios.
Refer to Figure 9-8. In this example, the measured primary current is 160 A, and the measured
secondary current is 4 A.
160 A : 4 A 40:1 ratio
The nameplate ratio of current transformers is generally specified as a ratio to 5 amps, the typical
test amps used for transformer rated meters. Hence a transformer with a 40:1 ratio will be labeled as a
200:5 transformer.
BURDEN TESTER
A burden tester is used to check for various defects and issues in the CT and/or secondary loop. See
Figure 9-9 for an example of a Traditional Analog Burden tester typically used in the field and Figure
9-10 for a digital version of a burden tester also commonly used in the field. Current transformers
are rated to function properly within a specified secondary burden range, and a burden tester may be
employed to verify this functionality. A burden tester is essentially a multi-range ammeter and set of
multi-range burden resistors, typically 0.1, 0.2, 0.5, 1, 2, 4, and 8Ω, which are placed sequentially in
series with the meter.
140 Example:
HANDBOOK FOR ELECTRICITY METERING
Figure 9-9. TESCO 1044A 20A Analog Burden Tester. Figure 9-10. UTEC 585 Digital Burden Tester.
Figure 9-11 shows a typical burden tester applica- 141
tion. The burden tester responds to these common
defects:
Meter
INSTRUMENTS
1. When a current transformer is free of internal
defects, the sudden imposition of a second-
ary burden within the accuracy limits of the
transformer should not cause any great change OPEN
in ratio. Therefore, the current as indicated
on the ammeter should decrease only a few Test
percent when the switch is depressed and Switch
the burden is added. In a good transformer,
the main effect of the added burden should
be only a rise in the primary and secondary
voltage. However, when one or more turns
within the transformer are shorted, then an
appreciable part of the total available ampere-
turns are diverted into the short, and the
Burden
current to the watthour meter is less than the
Tester
total secondary current of the transformer.
If now the burden of the Field Test Set is
added in series with the watthour meter by
depressing the push button, the additional high
impedance in the meter circuit will divert still
more current into the shunt path provided by
Current
shorted turn or turns, and the meter current
Transformer (CT)
should decrease by a large amount. This would
immediately show on the burden tester amme-
Figure 9-11. A Typical Burden Tester Application.
ter as a sudden and large decrease in the meter
reading every time the switch is depressed.
2. A high resistance at any point in the second-
ary circuit is the equivalent of an added high burden. Aside from the heating effect at the point
of high resistance, this instrument will reveal the presence of such a defect because the current
transformer is now operating at a much higher flux density due to the increased voltage neces-
sary to force current through the hot spot in the wiring.
At high flux densities, the ratio of current transformer drops off, and the addition of the
extra burden in the burden tester will cause a greater change in the current than when the
current transformer is operating normally at low flux density.
ADMITTANCE TESTER*
Admittance testing checks for abnormal admittance by injecting an audio frequency into the second-
ary of an in-service transformer, and detecting the circuit admittance. Admittance (Y) is the inverse of
impedance (Z) and is typically shown as mS (millisiemens). (See Figure 9-12.)
Relaying or metering current transformers have very low error when operated within the specified
current and burden ratings. The circuit admittance of any particular current transformer installation
is nearly constant throughout the normal operating range, unless a fault condition develops. If the
admittance measurement shows a deviation from normal while in service, it is likely that the current
transformer will have: (1) an internal short (usually a shorted turn, whereas the Z in Figure 9-12 will
change); (2) an abnormal internal or external resistance (such as a high-resistance connection that
is loose or corroded, whereas the R in Figure 9-12 will increase); or (3) the current transformer is
operating under abnormal conditions (such as DC in the primary).
Serious faults are immediately obvious due to an abnormally high admittance reading, normally at
least 1.5 times the normal reading. Transformers with a wrong ratio, exampled as a connection to the
*Portions of this section were reproduced from “Application Note 1109A: Admittance Testing Verifies CT Installa-
tion Integrity.” Radian Research. http://radianresearch.com/app_notes/admittance_application_note.pdf 11-09.
142
HANDBOOK FOR ELECTRICITY METERING
wrong tap, will have readings substantially different than normal readings. The best way to establish
the “normal” reading is to record measurements during installation and at subsequent test intervals.
Admittance values depend on the transformer’s XL as seen in Figure 9-12. The XL value will encompass
the transformer core design, burden rating, ratio, etc., but additions due to non-fault conditions (such
as temperature, primary load, etc.) are small in comparison to the change caused by fault conditions.
In-service current transformers are usually tested in groups, a high admittance reading obtained on
one CT in the group strongly implies that a fault condition does exist. Admittance testing provides a
quick, noninvasive way to evaluate the CT installation integrity, with or without load, at the customer
site. Shorted turns, circuit shunts, minor deterioration in CT performance, defective watthour meter
current coils, defective test switches, shunting of primary, partial by-pass of primary current, and high
resistance connections are all easily detected from the admittance value.
The testing devices shown in Figures 9-13 and 9-14 are available as discrete units. However, they
are commonly integrated together in a multi-functional unit.
INSTRUMENTS
must meet its specified accuracy class. To ensure this, the meter must be tested and its percent regis-
tration calculated. A meter accuracy tester is employed in this task.
To execute a meter accuracy test (as detailed in Chapter 12, “Electricity Meter Testing and Mainte-
nance”), the meter accuracy tester must include five basic components.
1. Energy Reference Standard. An extremely accurate and stable instrument used to measure
and calculate various electrical parameters, such as volts, amperes, watthours, VARhours, and
Q-hours. A reference standard will also be traceable to NIST (see Chapter 20, “The Standards
Laboratory”).
2. Current Source. While some test methods utilize the actual customer load to apply current to
the meter and standard during the test, a current source can also be employed to apply specific
current levels appropriate for the test. Typical current sources have a maximum current output
of either 30 or 50 amps, and are powered from the potential source.
3. Potential Source. Like the test current, the potential applied to the meter and standard during
the test can also be the actual service potential. Alternatively, this voltage may be obtained via a
potential source.
4. Meter Calibrated Pulse Output Pickup, Meter Disk Rotation Sensor, or Timing “Snap”
Switch. Depending on the type of meter under test (electro-mechanical or solid state) and
the test method (older, manual, “snap-switch” style testing or sensor pick-up method), one of
many pulse pickups, sensors, or timing “snap” switches are employed to acquire the calibrated
pulses from the meter and control the timing of the test. Various types of sensors used are as
follows:
Figure 9-15. Radian Research RR-DS/sm Meter Figure 9-16. TESCO 1037-STND Optical Pickup.
Disk Sensor.
144
HANDBOOK FOR ELECTRICITY METERING
Figure 9-17. Radian Research RR-KYZ Pulse Figure 9-18. TESCO 995A Click Switch.
Input Adaptor.
5. Meter Interface. This is any device that allows the test current and potential to be applied to
the meter under test. Examples include:
a. Safety test switch (Figure 9-19)
b. Test adaptor (Figure 9-20)
c. Field interface kit and socket (Figure 9-21)
Figure 9-19. TESCO Safety Test Switch. Figure 9-20. Brooks Meter Test Jack.
145
INSTRUMENTS
Figure 9-21. TESCO 2200 Field Interface Kit and Socket.
ANSI C12.29 Field Testing Standard allows for field testing using three different methods: (1) the
test potential and current are both generated by the test equipment; (2) the service potential is used
for the test voltage, while the test current is generated by the test equipment; and (3) both service
voltage and service current are used for the test voltage and current. Examples of each of these three
types of field test equipment are shown in Figures 9-22 through 9-26 below
These components may be standalone or integrated into a single instrument. Additional features
may include enhanced safety features, auto-ranging potential inputs, voltage and current displays,
power factor selection switches, and reverse current controls.
Figure 9-22. Radian Research RB-10 Bantam Lite. Figure 9-23. TESCO 630 Field Test Kit.
146
HANDBOOK FOR ELECTRICITY METERING
Figure 9-24. Spinlab 6000 Bird Dog Plus. Figure 9-25. Probewell MT-1/NT3.
INSTRUMENTS
communication devices the utility has selected for their service territory.
Common features of communication testing protocol include, but are not limited to:
• Utilizes existing meter test boards, qualification boards, or warm-up sockets
• Will incorporate the use of barcode scanners to read the meter number, the communication
device number, and initiate the test—where possible
• Saves the test data for inclusion in the utility’s metering system of record
• Allows for a hard copy of the test
There are many different meter forms and applications. Confusion or simple human error can lead
to connections being made incorrectly. When this occurs in a polyphase circuit, the signals presented
to the meter are wrong. This always leads to a significant reduction in the power being metered. Take,
for example, the case of a 4-wire wye application with a 9S meter. On a 208 V service with 120 V
phase to neutral and 100 amps per phase at unity power factor we should measure 36 kW.
A simple error is to switch the B and C currents. With the same conditions the power measured is
zero. All revenue from this customer is lost.
Vector diagrams like those in Figure 9-28 are the best tool for understanding wiring errors. The
vector diagram shows the phase relationship between the voltages and currents as they are seen by the
meter. In the 9S case above, seeing the problem is easy. In all cases the meterman must know what
service he is dealing with. The Power Measurement Handbook† provides PF1 diagrams for most ser-
vices in chapter 4 for reference. Many modern test instruments also provide reference vector diagrams.
*This section is reproduced from the Power Measurement Handbook by permission of the author, William Hardy.
†William H. Hardy, Power Measurements Handbook, Power Measurements, Chapter 4, pp. 31–51.
148
HANDBOOK FOR ELECTRICITY METERING
A number of studies have shown that problems with CTs and their associated wiring make up
roughly 60% of problems associated with metering sites. When testing a CT in the field there is sel-
dom the opportunity to control the primary current and measure the secondary output as there would
be in the laboratory. Nonetheless, there are several very useful tests to perform. These are three widely
used approaches for field testing CTs: (1) ratio testing with applied burden, (2) output monitoring
with applied burden, and (3) admittance testing.
INSTRUMENTS
b) True RMS measurement
c) Harmonic analysis
2) Current Measurement (high accuracy direct connection)
a) Up to three signals simultaneously
b) True RMS measurement
c) Harmonic analysis
3) Current Measurement (high current using clamp-on probes)
a) Up to three phases simultaneously
i) As seen at meter
b) True RMS measurement
c) Harmonic analysis
4) Phase
a) Measurement of phase angles between all voltages and currents
b) Measurement of power factor
5) CT Testing
a) Measurement of ratio and phase shifts
b) Measurement under applied burden
c) Measurement of CT burden
6) Meter Testing
a) Accuracy testing using test pulse from meter
i) Active power
ii) Reactive power
iii) Apparent power
b) Multiple test modes
i) Customer load test
ii) Current load box, customer voltage
iii) Equipment supplied voltage and
current
clockwise from the phase A voltage, which is drawn horizontally to the right.
A quick glance at the phasor diagram for a site can tell the operator whether the meter connec-
tions are correct or perhaps miss-wired as in Figure 9-31. Note that the phase A voltage and current
are closely aligned but Vb is aligned with Ic and Vc is aligned with Ib. This is the signature of a meter
with phase B and phase C current circuits reverse wired.
Each meter application has an expected ideal vector diagram. By comparing the expected diagram
with the site’s diagram many problems can be detected. Many modern analyzers provide instant access
to the reference diagrams.
INSTRUMENTS
Figure 9-32. Sample Plot of Ratio Testing with Applied Burden.
BURDEN-ONLY TESTING
Sometimes it is not possible to access the primary side of the CT. In this situation the CT output as a
function of applied burden can still be measured. Under ideal conditions the current output of a CT
decreases as additional burden is applied. The curve in Figure 9-33 shows the nominal performance
for a burden class 0.5 CT as burden is applied. To achieve a measurement like this the primary current
must be very stable. This is often not the case, even over the very short time required to make all of
the measurements (typically several seconds). The data in Figure 9-34 show results when the primary
current is not stable.
Figure 9-33. Curve Indicating the Nominal Performance for a Burden Class.
Figure 9-34. Results of Burden-Only Testing when the Primary Current is Not Stable.
152 Applying additional burden should never cause the secondary output to increase, so when there
is a result like above it means that the primary current has been unstable. By repeating the test
several times, the meter technician can get a better idea of whether the CT looks generally healthy.
A burden-only test, like that in Figure 9-34, simply gives a general idea of the health of a CT. Some
HANDBOOK FOR ELECTRICITY METERING
analyzers may offer the option of repeating the measurement multiple times and averaging the data.
ADMITTANCE TESTING
Because admittance testing does not involve measuring the currents directly, it has historically not
been a feature of site analyzers. However, there is no reason this approach could not be included as a
feature by adding the appropriate circuitry. As mentioned above, admittance testing involves injecting
an audio frequency signal into a CT secondary and looking at the response.
PT TESTING
Accurate PT testing can be done using the ratio approach just as in CT testing. Similar accuracy
parallelograms are defined in IEEE C57. Historically there has been less trouble with PTs than with
CTs because many services of 600 V and below did not use PTs. However, with the advent of arc-flash
concerns, many more PTs are being used.
METER TESTING
Recent developments in test equipment have made meter testing in the field much easier and more
accurate. By testing a meter on-site the utility can save both time and money. It can also better
determine whether the meter is accurate under the actual customer conditions. One of the problems
today is that meters are type tested only under sinusoidal conditions, while in the real world loads can
be very non-sinusoidal.
There are three general approaches to testing meters in the field. Each has a specific purpose and
answers different questions.
Testing Using Test Set Supplied Voltage and Current
In this approach the test set provides both the test voltage and current. This allows the laboratory
type test results to be reproduced in the field. This type of testing is required by some Public Service
Commissions and answers the question, “Is the meter meeting its specifications under laboratory load
conditions?”
Testing is generally performed at the nominal service voltage and three different loads: (1) full
load at PF1.0 (full load for a Class 20 meter is 2.5 A), (2) light load at PF1.0 (light load for a
Class 20 meter is 0.25 A), and (3) full load at PF0.5 lagging. (See Figure 9-35.)
Figure 9-35. Sample Test Results Using Test Set Supplied Voltage and Current.
Testing Using Customer Voltage and Test Set Supplied Current 153
This is a compromise approach (compared to that above) based on the assumption that even with
non-sinusoidal current loads most voltage retains a nearly sinusoidal waveform. This allows the use of
customer voltage and only supply current from the test equipment. This is not always a good assump-
INSTRUMENTS
tion. If the purpose of performing the test is to reproduce the laboratory results, then the assumption
should be verified by measurement. Test points are generally the same as listed above.
Testing Using Customer Voltage and Current
The most fundamental reason for all testing is to verify that the customer is being billed correctly.
This can only be completely assured if it can be verified that the meter is operating correctly under the
conditions at the customer’s site. Today, test equipment is available that makes accurate measurements
under ALL test conditions. This allows a meter’s performance to be verified under the customer’s
specific conditions.
When a customer’s voltage and load is used, there is only one set of test conditions. A question
that is often raised is, “What are the requirements for a ‘valid’ test?” Any test that is within the speci-
fied operating range of the meter should be considered valid. For a Class 20 meter, that would mean
any load within the 100 mA to 20 A range would be valid. Voltages outside the operating range occur
very infrequently.
As shown in Figure 9-36, a field test typically includes a number of measurements made simulta-
neously. In addition to the information shown in the report, many test devices record vector diagrams,
waveforms for voltage and current, and full harmonic analysis. This suite of data allows not only a
determination of the meter’s accuracy but a complete analysis of the customer’s load.
Figure 9-36. Sample Results for a Field Test Using Customer Voltage and Current.
Note: Measurement of VA and VAR under non-sinusoidal conditions may lead to differences
between the standard and the meter under test. There is currently in the United States no legal defini-
tion of VA and VAR under non-sinusoidal conditions. The meter may be working according to the
manufacturer’s specifications, and the standard working perfectly, yet the two may not agree because
they are working with different definitions. A new version of C12.20 is in editorial review (June
2014). This version will address active energy measurement (WHrs) under non-sinusoidal conditions.
However, it will not address either VA or VAR under non-sinusoidal conditions.
Work on a new metering standard, C12.46, is currently under way. This standard is intended to
replace C12.1 and C12.20 with an integrated document following the outline of OIML IR-46. This
standard is expected to address watts, VA, and VAR under all conditions, including rapidly varying
conditions.
Chapter 10
Instrument Transformers
IT WOULD BE difficult and impractical to build self-contained meters to measure the energy in
high-voltage or high-current circuits. To provide adequate insulation and current-carrying capacity,
the physical size of the meters would have to be enormously increased. Such meters would be costly
to build and would expose the meter technician to the hazards of high voltage. The use of instrument
transformers makes the construction of such high-voltage or high-current meters unnecessary.
Instrument transformers are primarily used to insulate and thereby isolate the meters from the
high-voltage circuits, and to reduce the primary voltages and currents to usable sizes and standard
values that are easily metered with meters having a common secondary rating. The instrument trans-
formers deliver accurately known fractions of the primary voltages and currents to the meters. With
proper register ratios and multipliers, the readings of the meters can be made to indicate the primary
kilowatthours.
155
156 Hazardous Current Transformer (CT) Open-Circuiting
An energized current transformer (CT) with the secondary open-circuited can result in a high voltage
across the secondary terminals or conductors which may be hazardous to personnel or damaging to
equipment.
HANDBOOK FOR ELECTRICITY METERING
Indoor Transformer
A transformer which must be protected from weather.
Insulated-Neutral Terminal-Type Voltage Transformer
A transformer with the neutral line of the primary insulated from the case or base and connected to
a terminal with insulation for a lower voltage than the voltage that is required by the line terminal.
The neutral line may be connected to the case or mounting base in a manner which allows temporary
disconnection for dielectric testing.
Leakage Flux
Magnetic flux, produced by current in a transformer winding, which flows outside the windings.
Low Remanence Current Transformer
A transformer with a remanence less than 10% of maximum flux.
Multiple-Secondary Current Transformer
A transformer with one primary and two or more secondaries, each on separate magnetic circuits.
Multi-Ratio Current Transformer
A transformer with three or more ratios obtained by taps on the secondary winding.
Rated Current
The current in the primary upon which the performance specifications are based.
Rated Secondary Current
Rated current divided by the marked ratio.
Rated Secondary Voltage
Rated voltage divided by the marked ratio.
Rated Voltage
The primary voltage upon which the performance specifications of a voltage transformer are based.
Series-Parallel Primary Current Transformer
A transformer with two insulated primaries that can be connected in series or in parallel, and that
provide different rated currents.
Tapped-Secondary Current (Voltage) Transformer
A transformer with two ratios, obtained by a tap on the secondary winding.
Window-Type Current Transformer
A transformer with no primary winding, and a secondary winding insulated from, and permanently
assembled on, the core, providing a window through which the primary line conductor can pass.
Wound-Type Current Transformer
A transformer with a primary with one or more turns mechanically encircling the core. The primary
and secondary windings are insulated from each other and from the core and are assembled as an
integrated structure.
INSTRUMENT TRANSFORMERS
In Figure 10-1, the polarity markers are used to show the instantaneous direction of current flow in
the primary and secondary windings of the voltage transformer. They are so placed that when the
primary current IP is flowing into the marked primary terminal H1, the secondary current Is is at the
same instant flowing out of the marked secondary terminal X1. These markings enable the secondaries
of the voltage and current transformers to be connected to the meter with the proper phase relation-
ships. In the case of a single-stator meter installed with a voltage and a current transformer, reversal
of the secondaries from either transformer would cause the meter to run backward.
Secondary Burden
In Figure 10-1, the voltage coil of the meter draws a small current from the secondary winding and is
therefore a burden on the secondary winding. The burden of an instrument transformer is defined by
Institute of Electrical and Electronics Engineers (IEEE) Standard C57.13 as follows:
That property of the circuit connected to the secondary winding that determines the active and reactive
power at its secondary terminals.
The burden on a voltage transformer is usually expressed as the total volt amperes and power
factor of the secondary devices and leads at a specified voltage and frequency (normally 120 volts at
25 KV and below and 115 volts above 25 KV, 60 hertz [Hz]).
The burden imposed by the voltage sensors of an electronic (solid-state) meter is typically less
than 0.1 VA and may be considered insignificant. However, the solid-state meter’s power supply, which
is typically connected to phase A, may be significant enough for consideration as a voltage transformer
secondary burden.
Marked Ratio, Turn Ratio, True Ratio
The marked ratio of a voltage transformer is the ratio of primary voltage to secondary voltage as given
on the rating plate.
The turn ratio of a voltage transformer is the ratio of the number of turns in the primary winding
to that in the secondary winding.
The true ratio of a voltage transformer is the ratio of the root-mean-square (rms) primary voltage
to the rms secondary voltage under specified conditions.
In an ideal voltage transformer, the marked ratio, turn ratio, and true ratio would always be equal
and the reversed secondary voltage would always be in phase with the impressed primary voltage. It
must be strongly emphasized that this ideal voltage transformer does not exist. It has been assumed
that the ideal voltage transformer is 100% efficient, has no losses, and requires no magnetizing cur-
rent. This assumption is not true for any actual voltage transformer.
The concept of the ideal voltage transformer is, however, a useful fiction. Modern voltage trans-
formers, when supplying burdens which do not exceed their accuracy ratings, approach the fictional
ideal very closely. Most metering installations involving instrument transformers are set up on this
ideal basis and, in most cases, no corrections need be applied. Thus, in the example shown in Fig-
ure 10-1, it would normally be assumed that the meter voltage coil is always supplied with 1/20th of
the primary voltage. If this assumption is to be valid, the limitations of actual voltage transformers
must be clearly understood and care taken to see that they are used within these limitations.
The Actual Voltage Transformer—The Phasor Diagram
In the ideal voltage transformer, the secondary voltage is directly proportional to the ratio of turns and
opposite in phase to the impressed primary voltage. In an actual transformer, an exact proportionality
and phase relation is not possible because the exciting current necessary to magnetize the magnetic
core causes an impedance drop in the primary winding and the load current that is drawn by the
burden causes an impedance drop in both the primary and secondary windings.
Both of these currents produce an overall voltage drop in the transformer and introduce errors in
ratio and phase angle. The net result is that the secondary voltage is slightly different from that which
the ratio of turns would indicate and there is a small shift in the phase relationship, resulting in
the introduction of ratio and phase angle errors as compared to the performance of the ideal voltage
transformer.
158
HANDBOOK FOR ELECTRICITY METERING
INSTRUMENT TRANSFORMERS
IE
VP
The secondary current IS is determined by the secondary terminal voltage VS and the impedance
of the burden ZB. Theoretically, the true burden seen by a voltage transformer includes the leads RL in
series with the connected instruments. In practice, the effect of the leads on the total burden is very
VS
small and is neglected. I is equal to —— and lags V by a phase angle B, where cos B is the power factor
ZB
of the burden. This burden power factor should not be confused with the power factor of the load
being supplied by the primary circuit.
The voltage drop in the secondary winding is equal to ISZS where ZS is the impedance of this wind-
ing. This drop is the phasor sum of two components ISRS and ISXS, where RS and XS are the resistance
and reactance of the secondary winding. The voltage drop ISRS must be in phase with IS and the voltage
drop ISXS must lead IS by 90°. The induced secondary voltage ES is equal to the phasor sum of VS 1 ISZS
and VS is the phasor difference ES 2 ISZS.
IM is the magnetizing current required to supply the flux and is in phase with the flux. IW is the
current required to supply the hysteresis and eddy current losses in the core and leads IM by 90°. The
phasor sum of IM 1 IW is the exciting current IE. This would be the total primary current if there were
no burden on the secondary.
When a burden is connected to the secondary, the primary must also supply the reflected
I I
secondary current, —S . The total primary current IP is therefore the phasor sum of IE and 2—S .
n n
160 The voltage drop in the primary winding is equal to IPZP where ZP is the impedance of the primary
winding. This drop is the phasor sum of the two components IPRP and IPXP where RP and XP are the
resistance and the reactance of the primary winding. The voltage drop IPRP must be in phase with IP
and the drop IPXP must lead IP by 90°. The primary terminal voltage VP is equal to the phasor sum of
HANDBOOK FOR ELECTRICITY METERING
EP 1 IPZP.
The phasor 2VS is obtained by reversing the secondary voltage phasor VS. In practice this simply
amounts to reversing the connections to the secondary terminals. This reversal is automatically done
by the polarity markings and, if these are followed, the terminal voltage from the marked to the
unmarked secondary lead will be 2VS.
In Figure 10-3, note that the reversed secondary voltage phasor 2VS is not equal in magnitude
to the impressed primary voltage VP and that 2VS is out of phase with VP by the angle . In an ideal
voltage transformer of 1:1 ratio, 2VS would be equal to and in phase with VP. In the actual voltage
transformer, this difference represents errors in both ratio and phase angle.
True Ratio and Ratio Correction Factor
The true ratio of a voltage transformer is the ratio of the rms primary voltage to the rms secondary
voltage under specified conditions.
V
In the phasor diagram, Figure 10-3, the true ratio is —P . It is apparent that this is not equal to the
T VS
1:1 turn ratio —P upon which this diagram was based. In this case, VS is smaller in magnitude than VP
TS
as a result of the voltage drops in the transformer.
T
The turn ratio of a voltage transformer —P is built in at the time of construction and the marked
TS
ratio is indicated on the nameplate by the manufacturer. These ratios are fixed and permanent values
for a given transformer.
The true ratio of a voltage transformer is not a single fixed value since it depends upon the speci-
fied conditions of use. These conditions are secondary burden, primary voltage, frequency, and wave-
form. Under ordinary conditions, primary voltage, frequency, and waveform are practically constant
so that the true ratio is primarily dependent upon the secondary burden and the characteristics of the
particular voltage transformer.
The true ratio of a voltage transformer cannot be marked on the nameplate since it is not a
constant value but one that is variable and is affected by external conditions. The true ratio is deter-
mined by test for the specified conditions under which the voltage transformer is to be used. For most
practical applications where no corrections are to be applied, the true ratio is considered to be equal to
the marked ratio under specified IEEE standard accuracy tolerances and burdens.
Thus, it might be found that the true ratio of a voltage transformer having a marked ratio of 20:1
was 20.034:1 under the specified conditions. However, the true ratio is not usually written in this way
because this form is difficult to evaluate and inconvenient to use. The figure 20.034 may be broken
into two factors and written 20 3 1.0017, where 20 is the marked or nominal ratio of the voltage
transformer and is multiplied by the factor 1.0017.
This factor, by which the marked ratio must be multiplied to obtain the true ratio, is called the
ratio correction factor (RCF).
True Ratio 5 Marked Ratio 3 RCF
True Ratio
RCF 5 ——————————
Marked Ratio
Phase Angle
Figure 10-3 shows that the reversed secondary voltage 2VS is not in phase with the impressed primary
voltage VP. The angle between these two phasors is known as the phase angle of the voltage trans-
former and is usually expressed in minutes of arc. Sixty minutes of arc is equal to one degree.
In the ideal voltage transformer, the secondary voltage VS would be exactly 180° out of phase with
the impressed primary voltage VP. The polarity markings automatically correct for this 180° reversal.
The reversed secondary voltage 2VS, would therefore be in phase with the impressed primary VP and
the phase angle would be zero.
In the actual voltage transformer, the phase angle represents a phase shift between the primary
and secondary voltages in addition to the normal 180° shift. The 180° shift is corrected by the rever-
sal that occurs when the polarity markings are followed, but the phase angle remains. This uncor- 161
rected phase shift can cause errors in measurements when exact phase relations must be maintained.
The phase angle of an instrument transformer is defined by IEEE Standard C57.13 as the phase
displacement, in minutes, between the primary and secondary values. The phase angle of a voltage
INSTRUMENT TRANSFORMERS
transformer is designated by the Greek letter gamma () and is positive when the secondary voltage
from the identified to the unidentified terminal leads the corresponding primary voltage.
The phase angle of a voltage transformer is not a single fixed value but varies with burden, primary
voltage, frequency, and waveform. It results from the voltage drops within the transformer as shown
in Figure 10-3. Under ordinary conditions where voltage, frequency, and waveform are practically
constant, the phase angle is primarily dependent upon the secondary burden and the characteristics of
the particular voltage transformer.
Effects of Secondary Burden on Ratio and Phase Angle
Figure 10-3 shows that any change in the secondary current IS will change the relative magnitudes and
phase relations of the primary terminal voltage VP and the secondary terminal voltage VS. Since the
V
secondary current IS is a function of the burden impedance ZB the true ratio —P and the phase angle
VS
are affected by any change in burden. Figure 10-5 shows the metering accuracy curve of a voltage
transformer referenced to connected burden.
Effects of Primary Voltage on Ratio and Phase Angle
A change in primary voltage causes a nearly proportional increase or decrease in all of the other
voltages and currents shown in the phasor diagram in Figure 10-3. If this proportionality were exact,
no change in true ratio or phase angle would result from a change in voltage. However, the exciting
current IE is not strictly proportional to the primary voltage VP, but varies according to the saturation
curve of the magnetic core as shown in Figure 10-4. The change in exciting current for the normal
operating range of 90 to 110% of rated primary voltage is very nearly linear. Above 110% rated volt-
age the core is rapidly approaching saturation and the exciting current IE increases more rapidly than
the primary voltage VP. This could result in a change in true ratio and phase angle with voltage if the
transformer is operated at more than 110% of its rated voltage. The exact point of saturation depends
upon the particular design. Some voltage transformers may show greater changes with voltage than
others.
In the normal operating range, and even well below this range, the change of true ratio and phase
angle with voltage is very small with modern well-designed voltage transformers.
Exciting Current
in the burden reactance XB (see Figure 10-3). These two effects tend to cancel each other, but depend
upon the ratio of resistance to reactance in the transformer and the burden. In addition, the excit-
ing current IE decreases rapidly at higher frequencies and increases at lower frequencies. At lower
frequencies the core will saturate at voltages below the normal rating and large changes in ratio and
phase angle could occur. As a result, a small increase in frequency may have little effect, whereas a
small decrease may result in appreciable change in true ratio and phase angle. A drastic decrease in
frequency results in excessive exciting current and overheating of the voltage transformer.
Voltage transformers are normally designed for a single frequency, though they can be designed to
work satisfactorily for a small range of frequencies such as 50 to 60 Hz. In utility work, this frequency
is usually 60 Hz. Since power system frequency is closely regulated, the problem of varying frequency
does not normally arise.
Effects of Waveform on Ratio and Phase Angle
Since any distorted waveform of the impressed primary voltage may be considered equivalent to a mix-
ture of a sinusoidal voltage at the fundamental frequency and sinusoidal voltages at higher harmonic
frequencies, waveform distortion would also have an effect on the true ratio and phase angle.
If the burden is a magnetic core device requiring a large exciting current, this may result in a
waveform distortion in the secondary current IS. However, this error is included if the transformer is
tested with this burden. In testing voltage transformers, care must be used to avoid overloading the
primary voltage supply as this could produce a distorted primary voltage waveform.
Effects of Temperature on Ratio and Phase Angle
A change in temperature changes the resistance of the primary and secondary windings of the voltage
transformer. This results in only slight changes of ratio and phase angle as the voltage drops in the
Lagging
Burden
Phase Power
Angle Factor
Leading
Ratio Burden
Correction Power
Factor Factor
Figure 10-5. Characteristic Ratio and Phase Angle Curves for a Voltage Transformer at 60 Hertz, 120 Volts.
transformers are primarily reactive and the secondary current is determined by the impedance of the 163
burden. The change in accuracy is usually less than 0.1% for a 55°C change in temperature.
Effects of Secondary Lead Resistance on the Ratio and Phase Angle as Seen by the Meter
INSTRUMENT TRANSFORMERS
The true ratio and phase angle of a voltage transformer are defined in terms of the terminal voltages
VP and VS. The true secondary burden is defined in terms of the impedance connected to the secondary
terminals and therefore includes the secondary lead resistance RL as shown in Figure 10-2. The resis-
tance of the secondary leads RL is small compared to the impedance of the burden ZB so that ordinar-
ily the lead resistance does not change the secondary burden sufficiently to make any appreciable
difference in the ratio and phase angle at the voltage transformer terminals.
However, the meter is not connected directly to the secondary terminals, but at the end of the
secondary leads. The voltage at the meter terminals is the burden voltage VB as shown in Figure 10-2
and not the secondary terminal voltage VS; VB differs from VS by the phasor drop ISRL that occurs in
the leads (see Figures 10-3 and 10-6).
This voltage drop is in phase with the secondary current IS and therefore causes the burden volt-
age VB to be slightly different in magnitude and slightly shifted in phase relation with respect to the
secondary terminal voltage VS.
The effect of this line drop in terms of ratio correction factor and phase angle may be calculated
as shown in Figure 10-6. Values for a typical example have also been given to illustrate the use of
these equations. In this example, the ratio correction factor 1.0009 and the phase angle 11.7 minutes
due to the secondary lead resistance were small and could be ignored in all but the most exacting
applications. If a greater lead resistance or a heavier secondary burden had been assumed, then this
Example:
VS VS 120
RCFL 5 —— ——————— 5 —————————— 5 1.009
VB VS 2 ISRL cos B 120 2 (0.24)(0.5)(.866)
Example:
ISRL sin B (0.24)(0.5)(0.5)(3438)
L (min.) ——————— 3438 5 —————————— 5 11.7 Minutes
VS 120
Figure 10-6. Phasor Diagram and Calculation of the Ratio Correction Factor and Phase Angle Due to the
Secondary Lead Resistance Only (Applies to Voltage Transformer Secondary Leads).
164 effect would be much greater. For example, if the lead resistance RL was increased to one ohm and the
secondary current IS to one ampere at 0.866 burden power factor (B), then the ratio correction factor
and phase angle due to the leads would rise to 1.0073 and 114.3 minutes. Such an error should not
be ignored.
HANDBOOK FOR ELECTRICITY METERING
It should be emphasized that the effect of the secondary lead resistance, in causing a change in
apparent ratio and phase angle at the meter terminals, is a straight lead-drop problem and is not due
to the voltage transformer in any way. The effect would be exactly the same if an ideal voltage trans-
former were used.
In spite of the fact that this lead-drop effect is not due to the voltage transformer, it is sometimes
convenient to include this drop during the test of a voltage transformer by determining the apparent
ratio and phase angle between the primary terminals of the transformer and the terminals of the
V
burden of the end of the actual or simulated secondary leads. This apparent ratio —P and apparent
VB
phase angle (B) are indicated by the dashed-line phasors VB, 2VB, and ISRL on the phasor diagram,
Figure 10-3. This is the total RCF and phase angle that must be used to correct the readings of the
meter as both the transformer and lead-drop errors are included. Since the lead-drop is not caused by
the transformer, acceptance tests to determine if the transformers meet specifications must be made at
the transformer secondary terminals.
In actual practice, the ratio and phase angle errors due to secondary lead-drop are usually limited
to small values by strict limitations of allowable lead resistance and secondary burden. This lead-drop
is troublesome only in exceptional cases where long leads and heavy burdens are required. In case of
doubt, a calculation, using the formulas given in Figure 10-6, will quickly indicate the magnitude of
the error involved.
Effects of Common Secondary Leads on Ratio and Phase Angle as Seen by the Meter
In a polyphase circuit where two or three voltage transformers are used, it is the normal practice to
use one wire as the common neutral secondary lead for all of the voltage transformers.
This fact must be taken into account when measuring or calculating the effect of the lead-drop on
the ratio and phase angle at the meter. If three voltage transformers are connected in wye as shown
in Figure 10-25, the neutral secondary lead carries no current with a balanced burden. If two voltage
transformers are connected in open delta as shown in Figure 10-23, the neutral secondary carries 3
times the current of the other leads for a balanced burden on phases 1-2 and 2-3.
If, because of long secondary leads or heavy burdens, the lead-drop effect causes significant error,
then the use of a common secondary lead increases the difficulties of determining this effect by test
or calculation. Calculations must be made phasorially, taking into account the magnitude and phase
relation of the current in each secondary lead.
Polyphase Burdens
When the secondaries of two or three voltage transformers are used to supply interconnected poly-
phase burdens, it becomes difficult to determine the actual burden in each transformer. Calculations
of burden must be made phasorially and become exceedingly complex when several polyphase and
single-phase burdens are involved. Such calculations can be avoided by testing at the burden under
actual or simulated three-phase conditions. This is required only in the most exacting applications,
where corrections based on the actual burden must be applied. In most cases burdens are kept within
the ratings of the voltage transformers and no corrections are applied.
Methods of Compensating Voltage Transformers to Reduce Ratio and Phase Angle Errors
Voltage transformers are designed to have low exciting current and low internal impedance, which
reduces the ratio and phase angle errors. In addition, the turn ratio may be made slightly different
than the marked ratio in order to compensate the transformer for minimum error at a specific burden
instead of at zero burden. If the transformer is used with a burden approximating the design burden,
errors may be greatly reduced.
Permanence of Accuracy
The accuracy of a voltage transformer does not change appreciably with age. It may change due to
mechanical damage or to electrical stresses beyond those for which the transformer was designed.
THE CURRENT TRANSFORMER 165
The Ideal Current Transformer Connection Diagram
Figure 10-7 shows the connection diagram for an ideal current transformer. The primary winding is
INSTRUMENT TRANSFORMERS
connected in series with one of the high-voltage leads carrying the primary current, and the secondary
winding is connected to the current coil of the meter. When 600 amperes flow through the primary
winding of this current transformer, 5 amperes are developed in the secondary winding by transformer
action. This secondary current is passed through the current coil of the meter. Since there is no direct
connection between the primary and secondary windings, the insulation between these windings
isolates the meter from the voltage of the primary. One side of the secondary circuit is connected to
ground to provide protection from static charges and insulation failure.
Polarity
In Figure 10-7, the polarity markers are used to show the instantaneous direction of current flow in
the primary and secondary windings of the current transformer. They are so placed that when the
primary current IP is flowing into the marked primary terminal H1, the secondary current IS is at the
same instant flowing out of the marked secondary terminal X1. These markings enable the secondaries
of the current and voltage transformers to be connected to the meter with the proper phase relation-
ships. For example, in the case of a single-stator meter installed with a current and a voltage trans-
former, reversal of the secondaries from either transformer would cause the meter to run backward.
Secondary Burden
In Figure 10-7, the impedance of the current coil
of the meter and the resistance of the second-
ary leads causes a small voltage drop across the
secondary terminals of the current transformer
when the secondary current IS is flowing. The cur-
rent transformer must develop a small terminal
voltage VS to overcome this voltage drop in order
to maintain the secondary current. The imped-
ance of the meter and resistance of the secondary
leads is therefore a burden on the secondary
winding.
This burden may be expressed as the total
voltamperes and power factor of the second-
ary devices and leads at a specified current and
frequency (normally, 5 amperes and 60 Hz). It is
often more convenient to express current trans-
former burdens in terms of their total resistance
in ohms and inductance in millihenries, or as
total ohms impedance at a given power factor and
frequency.
While the basic definition of burden for a
current transformer and voltage transformer is
the same in terms of active and reactive power
supplied by the instrument transformer, the effect
of burden impedance is the reverse. Zero burden
on a voltage transformer is an open-circuit or
infinite impedance, while zero burden on a
current transformer is a short-circuit or zero
impedance.
The impedance of the current coil of the
meter in Figure 10-7 is very low so that the cur-
rent transformer is operated with what amounts
to a short circuit on its secondary winding. This Figure 10-7. The Ideal Current Transformer.
is the normal condition of operation for a current
transformer.
166 Marked Ratio, Turn Ratio, and True Ratio
The marked ratio of a current transformer is the ratio of primary current to secondary current as
given on the rating plate.
The turn ratio of a current transformer is the ratio of the number of turns in the secondary
HANDBOOK FOR ELECTRICITY METERING
winding to the number of turns in the primary winding. This is the opposite of a voltage transformer.
A voltage transformer that steps down the voltage has more turns on the primary than the secondary,
while a current transformer that steps down the current has more turns on the secondary than on the
primary.
The true ratio of a current transformer is the ratio of rms primary current to the rms secondary
current under specified conditions.
In an ideal current transformer, the marked ratio, turn ratio, and true ratio would always be equal
and the reversed secondary current would always be in phase with the impressed primary current. It
must be strongly emphasized that this ideal current transformer does not exist.
The concept of the ideal current transformer is a useful fiction. Modern current transformers
when supplying burdens which do not exceed their accuracy ratings, approach this fictional ideal very
closely. Most metering installations involving instrument transformers are set up on this ideal basis
and, in most cases, no corrections need be applied. In the example shown in Figure 10-7, it would
normally be assumed that the meter current coil is always supplied with 1/120 of the primary current.
If this assumption is to be valid, the limitations of actual current transformers must be clearly under-
stood and care taken to see that they are used within these limitations.
The Actual Current Transformer—The Phasor Diagram
In the ideal current transformer, the secondary current is inversely proportional to the ratio of turns
and opposite in phase to the impressed primary current. In reality, an exact inverse proportionality
and phase relation is not possible because part of the primary current must be used to excite the
core. The exciting current may be subtracted phasorially from the primary current to find the amount
remaining to supply secondary current. Therefore, the secondary current will be slightly different from
the value that the ratio of turns would indicate and there is a slight shift in the phase relationship.
This results in the introduction of ratio and phase angle errors as compared to the performance of the
“ideal” current transformer.
Figures 10-8 and 10-9 are the schematic and phasor diagrams of an actual current transformer.
The phasor diagram, Figure 10-9, is drawn for a transformer having a 1:1 turn ratio and the volt-
age drop and loss phasors have been greatly exaggerated so that they can be clearly separated on the
diagram.
Basically, the phasor diagram for a current transformer is similar to that for the voltage trans-
former. However, in the current transformer, the important phasors are the primary and secondary
current rather than the voltages.
INSTRUMENT TRANSFORMERS
5 Flux in Core XS 5 Reactance of Secondary
IM 5 Magnetizing Current RB 5 Resistance of Burden
IW 5 Core Loss Current XB 5 Reactance of Burden
IE 5 Exciting Current ZB 5 Impedance of Burden
EP 5 Voltage Required to Overcome Induced B 5 Phase Angle of Burden
Primary Voltage cos B 5 Power Factor of Burden
IP 5 Primary Current TP 5 Turns on Primary
ES 5 Induced Secondary Voltage TS 5 Turns on Secondary
VS 5 Secondary Terminal Voltage n 5 Turns Ratio 5 TS/TP
IS 5 Secondary Current IP/IS 5 True Ratio of Current Transformer
RS 5 Resistance of Secondary b 5 Phase Angle of Current Transformer
The operation of the current transformer may be explained briefly by means of the phasor dia-
gram, Figure 10-9, as follows:
The flux in the core induces a voltage ES in the secondary winding lagging the flux by 90°. A
E TS
voltage equal to —S , where n is the turn ratio —— , is also induced in the primary winding lagging
n TP E
by 90°. To overcome this induced voltage, a voltage E 5 —S , must be supplied in the primary.
n
Thus, EP must lead ES by 180° and therefore leads the flux by 90°.
The secondary current IS is determined by the secondary terminal voltage VS and the impedance
V
of the burden ZB. IS is equal to —S and lags VS by a phase angle B where cos B is the power factor of
ZB
the burden (this burden power factor should not be confused with the power factor of the load being
supplied by the primary circuit). The burden impedance ZB is made up of the burden resistance RB and
the burden reactance XB (see Figure 10-8). The burden resistance RB is equal to the sum of the meter
resistance RM and the secondary lead resistance RL. Since the total impedance of current transformer
burdens is very low, usually less than one ohm, the lead resistance RL is an appreciable part of the
burden and cannot be neglected. In many cases the resistance of the secondary leads may constitute
the greater part of the burden impedance.
The voltage drop in the secondary winding is equal to ISZS, where ZS is the impedance of this
winding. This drop is the phasor sum of the two components ISRS and ISXS, where RS and XS are the
resistance and reactance of the secondary winding. The voltage drop ISRS must be in phase with IS and
the voltage drop ISXS must lead IS by 90°. The induced secondary voltage ES is equal to the phasor sum
of VS 1 ISZS and VS is the phasor difference ES 2 ISZS.
IM is the magnetizing current required to supply the flux and is in phase with the flux. IW is the
current required to supply the hysteresis and eddy current losses in the core, and leads IM by 90°. The
phasor sum of IM 1 IW is the exciting current IE.
168 The primary must supply the reflected secondary current 2nIS. The total primary current IP is
therefore the phasor sum of IE and 2nIS.
With a low-impedance burden connected to the secondary winding, the impedance of the primary
winding is extremely low, since the reflected impedance of the secondary is approximately proportional
HANDBOOK FOR ELECTRICITY METERING
to the square of the turn ratio, and the primary winding of a step-down current transformer has fewer
turns than the secondary.
The primary current in the current transformer is determined by the load on the primary circuit of
the installation. The voltage drop in the primary winding is therefore very small, even with full-rated
current in the primary line, due to the low impedance of this winding. The induced secondary voltage
ES and the secondary terminal voltage VS are both small because the transformer is essentially short
E
circuited by the low-impedance burden. Therefore, the voltage EP required to overcome the voltage —S ,
n
induced in the primary is also very small.
IP
Since the true ratio of a current transformer is —, it is not ordinarily necessary to consider the
IS
primary voltage or the voltage drops in the primary, since they do not effect the value of either the
primary or secondary currents.
The phasor 2IS is obtained by reversing the secondary current phasor IS. In Figure 10-9, which is
for a 1:1 transformer, 2IS is coincident with 2nIS. This reversal is automatically done if the polarity
markings are followed.
Also note that the reversed secondary current phasor 2IS is not equal in magnitude to the
impressed primary current phasor IP and that 2IS is out of phase with IP by the angle beta, . In an
ideal current transformer of 1:1 ratio, 2IS would be equal to and in phase with IP. In the actual cur-
rent transformer, this difference represents errors in both ratio and phase angle.
True Ratio and Ratio Correction Factor
I
In the phasor diagram, Figure 10-9, the true ratio is —P. It is apparent that this is not equal to the
IS
TS
1:1 turn ratio —— upon which the diagram was based. IS in this case is smaller in magnitude than IP
TP
because part of the primary current IP is required to supply the exciting current IE.
TS
The turn ratio of a current transformer —— is built in at the time of construction and the marked
TP
ratio is indicated on the nameplate by the manufacturer. These ratios are fixed and permanent values
for a given transformer.
The true ratio of a current transformer is not a single fixed value since it depends upon the speci-
fied conditions of use. These conditions are secondary burden, primary current, frequency, and wave-
form. Under ordinary conditions, frequency and waveform are practically constant so that the true
ratio is primarily dependent upon the secondary burden, the primary current, and the characteristics
of the particular current transformer.
The true ratio of a current transformer cannot be marked on the nameplate since it is not a
constant value but a variable which is affected by external conditions. The true ratio is determined by
test for the specified conditions under which the current transformer is to be used. For most practical
applications, where no corrections are to be applied, the true ratio is considered to be equal to the
marked ratio under specified IEEE standard accuracy tolerances and burdens. Thus, it might be found
that the true ratio of a current transformer having the marked ratio of 120:1 was 119.796:1 under
the specified conditions. However, the true ratio is not usually written in this way because this form
is difficult to evaluate and inconvenient to use. The figure 119.796 may be broken into two factors
and written 120 3 0.9983. Note that 120 is the marked or nominal ratio of the current transformer
which is multiplied by the factor 0.9983.
This factor, by which the marked ratio must be multiplied to obtain the true ratio, is called the
ratio correction factor (RCF). It has exactly the same meaning when applied to the current trans-
former as previously given for the voltage transformer.
True Ratio
RCF 5 ——————————
Marked Ratio
Phase Angle 169
Figure 10-9 shows that the reversed secondary current IS is not in phase with the impressed primary
current IP. The angle beta () between these phasors is known as the phase angle of the current
transformer and is usually expressed in minutes of arc (60 minutes of arc is equal to one degree).
INSTRUMENT TRANSFORMERS
In the ideal current transformer, the secondary current IS would be exactly 180° out of phase with
the impressed primary current IP. The polarity markings automatically correct for this 180° reversal.
The reversed secondary current 2IS would therefore be in phase with the impressed primary current IP
and the phase angle would be zero.
In the actual current transformer, the phase angle represents a phase shift between the primary
and secondary currents in addition to the normal 180° phase shift. The 180° shift is corrected by
the reversal that occurs when the polarity markings are followed, but the phase angle remains.
This uncorrected phase shift can cause errors in measurements when exact phase relations must be
maintained.
The phase angle of a current transformer is designated by the Greek letter beta () and is positive
when the current leaving the identified secondary terminal leads the current entering the identified
primary terminal.
The phase angle of a current transformer is not a single fixed value, but varies with burden, pri-
mary current, frequency, and waveform. It results from the component of the primary current required
to supply the exciting current IE as shown in Figure 10-9. Under ordinary conditions where frequency
and waveform are practically constant, the phase angle is primarily dependent upon the secondary
burden, the primary current, and the characteristics of the particular current transformer.
Effects of Secondary Burden on Ratio and Phase Angle
An increase of secondary burden, which for a current transformer means an increase in the burden
impedance ZB, requires an increase in the secondary voltage VS if the secondary current IS is to remain
the same. See Figure 10-9 (note that in a voltage transformer an increase of secondary burden requires
an increase in the secondary current if the secondary voltage is to remain the same). Increasing the
secondary current requires an increase in the induced secondary voltage ES which can only be pro-
duced by an increase in the flux .
To provide an increased flux, the magnetizing current IM must increase and the core loss current IW
also increases. This results in an increase in the exciting current IE. Thus, increasing the burden causes
an increase in the exciting current. Since the exciting current is the primary cause of the ratio and
phase angle errors in the current transformer, these errors are affected by any change in the secondary
burden.
Effect of Primary Current on Ratio and Phase Angle
Unlike the voltage transformer which operates at a practically constant primary voltage, the current
transformer must operate over a wide range of primary currents from zero to rated current, and
above rated current in special cases, such as the operation of protective relays. This means that with
a constant secondary burden, the flux in the core must vary over a wide range as the primary current
is changed. To produce this varying flux, the exciting current must also vary over a wide range. If the
flux varied in exact proportion with the exciting current IE then the changes in primary current
would not effect the ratio and phase angle. However, current transformers are designed to operate at
low flux densities in the core and under these conditions the flux is not directly proportional to the
exciting current. Figure 10-10 shows a typical exciting current curve for the magnetic core of a current
transformer.
The change of exciting current over the normal operating range from 10 to 100% rated primary
current is not a linear function of the primary current. The shape of the saturation curve for the
current transformer is actually similar to the curve for the voltage transformer, as seen in Figure 10-4,
but only an expanded portion of the lower end of the curve is shown in Figure 10-10. With normal
secondary burdens, saturation does not occur until the primary current reaches 5 to 20 times the
rated value. Thus, the saturation point is not shown in Figure 10-10.
Since the exciting current does not change in exact proportion to the primary current, the true
ratio and phase angle vary to some extent with the primary current. The ratio and phase angle errors
are usually greater at 10% primary current than at 100% primary current, though this depends upon
the burden and the compensation of the particular current transformer. Figure 10-11 shows typical
metering accuracy curves for a 0.3 Accuracy Class current transformer at IEEE standard burdens and
170
HANDBOOK FOR ELECTRICITY METERING
Flux in Core
or
Rated Primary
Current (IS) Normal Operating
Range
rated current ranging from 5 to 160%. Note that the typical current transformer ratio and phase
angle errors are very small at the lower burdens. Also, the current transformers are typically much
more accurate over a wider current range than is required by IEEE Accuracy Class 0.3 (at these lower
burdens), i.e., 0.3% maximum error at 100% rated current and 0.6% maximum error at 10% rated
current.
Effects of Frequency on Ratio and Phase Angle
The effect of frequency variation on the ratio and phase angle of a current transformer is less than
that on a voltage transformer primarily because of the low flux density. Current transformers may be
designed to have reasonable accuracy over a range from 25 to 133 Hz. There will, however, be some
slight variation with frequency in this range.
Effects of Waveform on Ratio and Phase Angle
Waveform distortion in the primary current may have slight effects on the ratio and phase angle but
in general such effects are negligible. Even a large amount of third harmonic in the primary current
wave is reasonably well reproduced in the secondary and causes little error. Higher harmonics could
cause errors but these are not normally present in sufficient magnitude to be significant.
Effects of Secondary Leads on Ratio and Phase Angle
In the current transformer, the secondary current IS must be the same in all parts of the secondary
circuit, including the burden, since it is a series circuit. Thus, the secondary current and, therefore,
the true ratio and phase angle, will be the same whether measured at the transformer or at the meter
at the end of the secondary leads. The only effect of the secondary leads is on the burden. With long
secondary leads, the leads may constitute the major portion of the secondary burden. In all cases, the
secondary leads must be included in all tests and calculations as part of the secondary burden.
Effects of Common Secondary Leads
In a polyphase circuit where two or three current transformers are used it is a common practice to use
one wire as the common secondary lead for all of the current transformers.
This fact must be taken into account when measuring or calculating the effect of the leads as part
of the secondary burden. If the current transformers are connected in wye as shown in Figure 10-28,
the neutral secondary lead carries no current if the primary load current is balanced. In this case, the
resistance of the common lead is not part of the burden on any of the current transformers. If the
two current transformers are connected open delta as shown in Figure 10-27 the common secondary
171
INSTRUMENT TRANSFORMERS
Phase Angle
Leading
Ratio Correction
Factor
Figure 10-11. Characteristic Ratio and Phase Angle Curves for a Typical Current Transformer at 60 Hertz.
lead carries a current whose magnitude is the same as the other leads under conditions of balanced
line currents and an open-delta burden as shown. However, the current in the common lead is not in
phase with the current in either of the other two leads. Thus, the lead resistance of the common lead
does not effect the burden on the two current transformers equally.
Figure 10-12 is a schematic and a phasor diagram of a two-stator polyphase meter whose current
elements are connected to two current transformers. If the lead resistance RL is an appreciable part of
the burden, the burden on the two current transformers is not the same because of the effect of the
common lead resistance. The effective burdens differ in both magnitude and phase. The burden on
one current transformer is V1I1 cos B1 and the other is V3I3 cos B3. The secondary currents I1 and I3
were assumed to be equal, but the terminal voltages V1 and V3 are not equal. In addition, the phase
angles of the two burdens B1 and B3 are not equal. Thus, the effect of the common secondary lead
resistance results in unequal burdens on the two current transformers even though the two elements
of the meter are identical.
If a burden of 2.1 VA at 0.60 power factor lagging and a lead resistance of 0.1 ohm (100 feet
of No. 10 wire) are assumed, the burdens on the two transformers would be 6.34 VA at 0.79 power
factor lagging on the current transformer in line 1 and 5.05 VA at 0.996 power factor leading on the
current transformer in line 3.
These small differences in burden would have little effect on the ratio and phase angle of a
modern current transformer. However, if a much longer common secondary lead with a resistance of
0.3 ohm or more is used, the effect might cause significant error unless appropriate corrections are
applied.
In most installations, the common lead resistance is kept low so that the resulting error is insig-
nificant. In the most accurate work, if long secondary leads must be used and exact corrections must
be applied, the current transformers can be tested under actual three-phase conditions. If the common
lead is eliminated by using separate return leads for each transformer, the calculations of burden are
simplified.
172
HANDBOOK FOR ELECTRICITY METERING
INSTRUMENT TRANSFORMERS
Instrument Transformer Correction Factor
RATIO CORRECTION FACTOR AND RELATED TERMS
The marked ratio, the true ratio, and the ratio correction factor have been defined and discussed. In
addition to the RCF, the terms percent ratio (or percent marked ratio), ratio error, and percent ratio
error are often used when stating the errors in ratio of instrument transformers. Though these four
terms are numerically different, they describe the same phenomenon. Table 10-1 defines these and
related terms with algebraic formulas which provide the means of converting one term to another. Of
the four, RCF is the only one defined in IEEE Standard C57.13 and is therefore the preferred term.
Example 1:
If RCF is 1.0027, the percent ratio is 100.27%, the ratio error is 10.0027, and the percent ratio
error is 10.27%.
If the RCF is 0.9973, the percent ratio is 99.73%, the ratio error is 20.0027, and the percent
ratio error is 20.27%.
Note that the proper sign, 1 or 2, must be used for the ratio error or the percent ratio error and
the word percent or a percent sign (%) must be used with the percent ratio and the percent ratio
error.
INSTRUMENT TRANSFORMERS
The secondary power WS measured by the meter is equal to the product of the secondary voltage
ES, the secondary current IS, and the power factor of the secondary circuit (cos 2):
WS 5 ESIS cos 2
The power factor of the secondary circuit (cos 2) is called the apparent power factor and dif-
fers from the primary power factor (cos ) because of the effect of the phase angles beta () and
gamma () of the current and voltage transformers, respectively.
If the instrument transformers had 1:1 ratios and no errors due to ratio, then the subscripts could
be omitted. For this condition:
WP 5 EI cos
WS 5 EI cos 2
In this special case, the primary power WP would be equal to the secondary power WS were it
not for the difference between cos and cos 2 which is due to the phase angles of the instrument
transformers.
The phase angle correction factor (PACF) is defined by IEEE as the ratio of the true power factor to
the measured power factor. It is a function of the phase angles of the instrument transformer and the
power factor of the primary circuit being measured.
Note that the phase angle correction factor is the factor that corrects for the phase displacement
of the secondary current or voltage, or both, due to the instrument transformer phase angles.
The measured watts or watthours in the secondary circuits of instrument transformers must be
multiplied by the phase angle correction factor and the true ratio to obtain the true primary watts or
watthours.
The combined phase angle correction factor (PACFK) is used when both current and voltage
transformers are involved. When current transformers only (no voltage transformers) are involved,
PACFI is used.
Therefore, for the special case of 1:1 ratio and no ratio errors:
WP 5 WS(PACFK)
and
W EI cos cos
PACFK 5 ——P 5 —————— 5 —————
WS EI cos 2 cos 2
The PACFK is therefore equal to the ratio of the true power factor (cos ) to the apparent power
factor (cos 2). This equation for the phase angle correction factor is not directly usable, since, in
general, cos 2, the apparent power factor, is known, but the exact value of the true power factor,
cos , is not.
The phasor diagram in Figure 10-13 shows that 5 2 1 2 . In this phasor diagram, all the
angles shown have a plus (1) sign and are positive. The secondary current and voltage phasors have
been drawn so that they lead their respective primary phasors. Therefore, and are both positive by
definition. The angles and 2 between the voltage and current phasors, are considered positive (1)
when the current phasors are lagging the voltage phasors (lagging power factor). Hence, and 2 are
both positive as drawn. Substituting 5 2 1 2 into the previous equation:
cos (2 1 2 )
PACFK 5 —————————————
cos 2
When a current transformer is used alone, PACFI may be determined by using the formula for
PACFK with the 2 term deleted.
If cos 2, , and are known, PACFK can now be calculated using trigonometric tables. Care must
be taken to use the proper signs for , , and , as previously noted.
176 Example 3:
Given:
cos 2 5 0.80 lag, 5 2139, 5 1109
Then: 2 5 cos21 0.80 5 36°529
HANDBOOK FOR ELECTRICITY METERING
5 2 1 2
5 (136°529) 1 (2139) 2 (1109) 5 36°299
cos 5 cos 36°299 5 0.804030
0.804030
PACFK 5 ——————— 5 1.0050
0.800000
This method of evaluating the PACF is straight forward but too time consuming for practical work.
Therefore, Tables 10-2 and 10-3 have been calculated by this method to give the PACF directly in
terms of the apparent power factor (cos 2) and the combined value of the phase angles ( 2 ).
Use of Tables 10-2 and 10-3 to Find the Phase Angle Correction Factor
In the example just given, cos 2 5 0.80 lagging and 2 5 (213 minutes) 2 (110 minutes) 5
223 minutes. Hence, Table 10-3 must be used as indicated by the heading “For Lagging Current When
2 is Negative.” At the intersection of the 0.80 power factor column and the 23 minute row, the
phase angle correction factor is 1.0050.
Two precautions are necessary when using these tables:
1. The algebraic signs of the phase angles and the minus sign in the formula must be carefully
observed when calculating 2 ;
2. Care must be used in selecting either Table 10-2 or 10-3 according to the notes heading these
tables regarding leading or lagging power factors and the resultant sign of 2 .
For an installation where a current transformer is used, but no voltage transformer is used:
cos (2 1 )
PACFI 5 —————————
cos 2
Tables 10-2 and 10-3 can still be used to find the phase angle correction factor using the value of
itself for 2 , since is not involved.
The PACFK depends upon the phase angles of the instrument transformers ( and ) and on
the apparent power factor of the load (cos 2). Thus, the phase angle correction factor varies with
the apparent power factor of the load. In actual practice, the difference between the apparent power
factor (cos 2) and the true power factor (cos ) is so small that for ordinary values of phase angle
either power factor can be used with Tables 10-2 and 10-3 to find the phase angle correction factor.
The value of 2 must be accurately known. Note in Tables 10-2 and 10-3 that the PACFK increases
rapidly at low power factors.
Tables 10-2 and 10-3 cover values of 2 from zero to one degree by minutes and from 0.05
to 1.00 power factor in steps of 0.05. Interpolation between values may be done but will rarely be
required with these tables. Values of 2 greater than 60 minutes are rarely encountered with
modern instrument transformers.
INSTRUMENT TRANSFORMERS
TCFE 5 RCFE 3 PACFE
When both current and voltage transformers are used, the PACF should be determined for the
combination in one step as previously shown and not calculated separately and combined. The product
of the two separate phase angle correction factors is not exactly equal to the true value of the overall
phase angle correction factor.
COMPENSATING ERRORS
The equation for the transformer correction factor (TCF 5 RCF 3 PACF) shows that for some values
of RCF and PACF, their product would be closer to one than either separately. For example, (1.0032)
(0.9970) 5 1.0002. Thus, under some conditions the overall effect of the error in ratio may be offset
by an opposite effect due to the phase angle.
This fact is used as a basis for the tolerance limits of the standard accuracy classifications of IEEE
Standard C57.13, where the specified tolerances of ratio and phase angle are interdependent. These
classifications are set up on the basis of a maximum overall tolerance in terms of TCF for power
factors from unity to 0.6 lagging. This is covered later under the subheading “IEEE Standard Accuracy
Classes for Metering.”
When a current and a voltage transformer are used, the combined ratio correction factor can be
improved by matching transformers with opposite ratio errors since RCFK 5 RCFE 3 RCFI.
To reduce the effect of phase angle errors, which are dependent upon 2 , current and voltage
transformers can be selected having phase angles of the same sign (i.e., both positive or both nega-
tive), thus reducing the overall phase angle error.
Current and voltage transformers are not usually matched to balance errors in this manner but
occasionally these methods may be useful.
HANDBOOK FOR ELECTRICITY METERING
178
For Lagging Current When (b 2 g) is Positive For Leading Current When (b 2 g) is Negative
(b 2 g) .05 .10 .15 .20 .25 .30 .35 .40 .45 .50 .55 .60 .65 .70 .75 .80 .85 .90 .95 .99 (b 2 g)
19 .9942 .9971 .9981 .9986 .9989 .9991 .9992 .9993 .9994 .9995 .9996 .9996 .9997 .9997 .9997 .9998 .9998 .9999 .9999 1.0000 I9
29 .9884 .9942 .9962 .9971 .9977 .9981 .9984 .9987 .9988 .9990 .9991 .9992 .9993 .9994 .9995 .9996 .9996 .9997 .9998 .9999 29
39 .9826 .9913 .9942 .9957 .9966 .9972 .9977 .9980 .9983 .9985 .9987 .9988 .9990 .9991 .9992 .9993 .9995 .9996 .9997 .9999 39
49 .9768 .9884 .9923 .9943 .9955 .9963 .9969 .9973 .9977 .9980 .9982 .9984 .9986 .9988 .9990 .9991 .9993 .9994 .9996 .9998 49
59 .9709 .9855 .9904 .9929 .9944 .9954 .9961 .9967 .9971 .9975 .9978 .9981 .9983 .9985 .9987 .9989 .9991 .9993 .9995 .9998 59
69 .9651 .9826 .9885 .9914 .9932 .9944 .9953 .9960 .9965 .9970 .9973 .9977 .9980 .9982 .9985 .9987 .9989 .9992 .9994 .9997 69
79 .9593 .9797 .9866 .9900 .9921 .9935 .9945 .9953 .9960 .9965 .9969 .9973 .9976 .9979 .9982 .9985 .9987 .9990 .9993 .9997 79
89 .9535 .9768 .9847 .9886 .9910 .9926 .9938 .9947 .9954 .9960 .9965 .9969 .9973 .9976 .9979 .9983 .9986 .9989 .9992 .9997 89
99 .9477 .9739 .9827 .9872 .9899 .9917 .9930 .9940 .9948 .9955 .9960 .9965 .9969 .9973 .9977 .9980 .9984 .9987 .9991 .9996 99
109 .9419 .9711 .9808 .9857 .9887 .9907 .9922 .9933 .9942 .9950 .9956 .9961 .9966 .9970 .9974 .9978 .9982 .9986 .9990 .9996 109
119 .9361 .9682 .9789 .9843 .9876 .9898 .9914 .9927 .9936 .9945 .9951 .9957 .9963 .9967 .9972 .9976 .9980 .9984 .9989 .9995 119
129 .9303 .9653 .9770 .9829 .9865 .9889 .9907 .9920 .9931 .9939 .9947 .9953 .9959 .9964 .9969 .9974 .9978 .9983 .9988 .9995 129
139 .9245 .9624 .9751 .9815 .9853 .9880 .9899 .9913 .9925 .9934 .9943 .9950 .9956 .9961 .9967 .9972 .9976 .9982 .9995 .9987 139
149 .9186 .9595 .9731 .9800 .9842 .9870 .9891 .9907 .9919 .9929 .9938 .9946 .9952 .9958 .9964 .9969 .9975 .9980 .9987 .9994 149
159 .9128 .9566 .9712 .9786 .9831 .9861 .9883 .9900 .9913 .9924 .9934 .9942 .9949 .9955 .9961 .9967 .9973 .9979 .9986 .9994 159
169 .9070 .9537 .9693 .9772 .9820 .9852 .9875 .9893 .9908 .9919 .9929 .9938 .9945 .9952 .9959 .9965 .9971 .9977 .9985 .9993 169
179 .9012 .9508 .9674 .9758 .9808 .9843 .9868 .9887 .9902 .9914 .9925 .9934 .9942 .9949 .9956 .9963 .9969 .9976 .9984 .9993 179
189 .8954 .9479 .9655 .9743 .9797 .9833 .9860 .9880 .9896 .9909 .9920 .9930 .9939 .9946 .9954 .9961 .9967 .9975 .9983 .9992 189
199 .8896 .9450 .9636 .9729 .9786 .9824 .9852 .9873 .9890 .9904 .9916 .9926 .9935 .9943 .9951 .9958 .9966 .9973 .9982 .9992 199
209 .8838 .9421 .9616 .9715 .9775 .9815 .9844 .9867 .9884 .9899 .9911 .9922 .9932 .9940 .9949 .9956 .9964 .9972 .9981 .9992 209
219 .8780 .9392 .9597 .9701 .9763 .9806 .9836 .9860 .9879 .9894 .9907 .9918 .9928 .9937 .9946 .9954 .9962 .9970 .9980 .9991 219
229 .8721 .9363 .9578 .9686 .9752 .9796 .9829 .9853 .9873 .9889 .9903 .9914 .9925 .9935 .9943 .9952 .9960 .9969 .9979 .9991 229
239 .8663 .9334 .9559 .9672 .9741 .9787 .9821 .9846 .9867 .9884 .9898 .9911 .9922 .9932 .9941 .9950 .9958 .9967 .9978 .9990 239
249 .8605 .9305 .9540 .9658 .9729 .9778 .9813 .9840 .9861 .9879 .9894 .9907 .9918 .9929 .9938 .9947 .9956 .9966 .9977 .9990 249
259 .8547 .9276 .9520 .9643 .9718 .9768 .9805 .9833 .9855 .9874 .9889 .9903 .9915 .9926 .9936 .9945 .9955 .9965 .9976 .9989 259
269 .8489 .9247 .9501 .9629 .9707 .9759 .9797 .9826 .9850 .9869 .9885 .9899 .9911 .9923 .9933 .9943 .9953 .9963 .9975 .9989 269
279 .8431 .9218 .9482 .9615 .9696 .9750 .9789 .9820 .9844 .9864 .9880 .9895 .9908 .9920 .9930 .9941 .9951 .9962 .9974 .9989 279
289 .8373 .9189 .9463 .9601 .9684 .9741 .9782 .9813 .9838 .9859 .9876 .9891 .9904 .9917 .9928 .9939 .9949 .9960 .9973 .9988 289
299 .8315 .9160 .9444 .9586 .9673 .9731 .9774 .9806 .9832 .9854 .9872 .9887 .9901 .9914 .9925 .9936 .9947 .9959 .9972 .9988 299
309 .8256 .9131 .9424 .9572 .9662 .9722 .9766 .9800 .9826 .9848 .9867 .9883 .9898 .9911 .9923 .9934 .9946 .9957 .9971 .9987 309
Table 10-2 (continued). Phase Angle Correction Factors (PACFs).
For Lagging Current When (b 2 g) is Positive For Leading Current When (b 2 g) is Negative
(b 2 g) .05 .10 .15 .20 .25 .30 .35 .40 .45 .50 .55 .60 .65 .70 .75 .80 .85 .90 .95 .99 (b 2 g)
319 .8198 .9102 .9405 .9558 .9650 .9713 .9758 .9793 .9821 .9843 .9863 .9879 .9894 .9908 .9920 .9932 .9944 .9956 .9970 .9987 319
329 .8140 .9073 .9386 .9544 .9639 .9704 .9750 .9786 .9815 .9838 .9858 .9875 .9891 .9905 .9917 .9930 .9942 .9954 .9969 .9986 329
339 .8082 .9044 .9367 .9529 .9628 .9694 .9743 .9780 .9809 .9833 .9854 .9872 .9887 .9902 .9915 .9928 .9940 .9953 .9968 .9986 339
349 .8024 .9015 .9348 .9515 .9616 .9685 .9735 .9773 .9803 .9828 .9849 .9868 .9884 .9899 .9912 .9925 .9938 .9952 .9967 .9985 349
359 .7966 .8986 .9328 .9501 .9605 .9676 .9727 .9766 .9797 .9823 .9845 .9864 .9880 .9896 .9910 .9923 .9936 .9950 .9966 .9985 359
369 .7908 .8958 .9309 .9486 .9594 .9666 .9719 .9760 .9792 .9818 .9840 .9860 .9877 .9893 .9907 .9921 .9935 .9949 .9965 .9985 369
379 .7850 .8929 .9290 .9472 .9583 .9657 .9711 .9753 .9786 .9813 .9836 .9856 .9874 .9890 .9905 .9919 .9933 .9947 .9964 .9984 379
389 .7791 .8900 .9271 .9458 .9571 .9648 .9704 .9746 .9780 .9808 .9832 .9852 .9870 .9887 .9902 .9916 .9931 .9946 .9963 .9984 389
399 .7733 .8871 .9252 .9444 .9560 .9639 .9696 .9739 .9774 .9803 .9827 .9848 .9867 .9884 .9899 .9914 .9929 .9944 .9962 .9983 399
409 .7675 .8842 .9232 .9429 .9549 .9629 .9688 .9733 .9768 .9798 .9823 .9844 .9863 .9881 .9897 .9912 .9927 .9943 .9961 .9983 409
419 .7617 .8813 .9213 .9415 .9537 .9620 .9680 .9726 .9763 .9793 .9818 .9840 .9860 .9878 .9894 .9910 .9925 .9942 .9960 .9982 419
429 .7559 .8784 .9194 .9401 .9526 .9611 .9672 .9719 .9757 .9788 .9814 .9836 .9856 .9875 .9892 .9908 .9924 .9940 .9959 .9982 429
439 .7501 .8755 .9175 .9386 .9515 .9601 .9664 .9713 .9751 .9783 .9809 .9832 .9853 .9872 .9889 .9905 .9922 .9939 .9958 .9981 439
449 .7443 .8726 .9156 .9372 .9503 .9592 .9657 .9706 .9745 .9778 .9805 .9829 .9850 .9869 .9886 .9903 .9920 .9937 .9957 .9981 449
459 .7384 .8697 .9136 .9358 .9492 .9583 .9649 .9699 .9739 .9772 .9800 .9825 .9846 .9866 .9884 .9901 .9918 .9936 .9956 .9980 459
469 .7326 .8668 .9117 .9344 .9481 .9547 .9641 .9693 .9734 .9767 .9796 .9821 .9843 .9863 .9881 .9899 .9916 .9934 .9955 .9980 469
479 .7268 .8639 .9098 .9329 .9470 .9564 .9633 .9686 .9728 .9762 .9791 .9817 .9839 .9860 .9878 .9897 .9914 .9933 .9954 .9980 479
489 .7210 .8610 .9079 .9315 .9458 .9555 .9625 .9679 .9722 .9757 .9787 .9813 .9836 .9857 .9876 .9894 .9912 .9931 .9953 .9979 489
499 .7152 .8581 .9060 .9301 .9447 .9546 .9618 .9672 .9716 .9752 .9783 .9809 .9832 .9854 .9873 .9892 .9911 .9930 .9952 .9979 499
509 .7094 .8552 .9040 .9286 .9436 .9356 .9610 .9666 .9710 .9747 .9778 .9805 .9829 .9851 .9871 .9890 .9909 .9929 .9951 .9978 509
519 .7036 .8523 .9021 .9272 .9424 .9527 .9602 .9659 .9705 .9742 .9774 .9801 .9825 .9848 .9868 .9888 .9907 .9927 .9950 .9978 519
529 .6978 .8494 .9002 .9258 .9143 .9518 .9594 .9652 .9699 .9737 .9769 .9797 .9822 .9845 .9865 .9885 .9905 .9926 .9949 .9977 529
539 .6919 .8465 .8983 .9244 .9402 .9509 .9586 .9646 .9693 .9732 .9765 .9793 .9819 .9842 .9863 .9883 .9903 .9924 .9948 .9977 539
549 .6861 .8436 .8963 .9229 .9390 .9499 .9578 .9639 .9687 .9727 .9760 .9789 .9815 .9839 .9860 .9881 .9901 .9923 .9947 .9976 549
559 .6803 .8407 .8944 .9215 .9379 .9490 .9571 .9632 .9681 .9722 .9756 .9785 .9812 .9836 .9858 .9879 .9900 .9921 .9946 .9976 559
569 .6745 .8378 .8925 .9201 .9368 .9481 .9563 .9625 .9675 .9717 .9751 .9781 .9808 .9832 .9855 .9877 .9898 .9920 .9945 .9975 569
579 .6687 .8349 .8906 .9186 .9536 .9471 .9555 .9619 .9670 .9711 .9747 .9778 .9805 .9829 .9852 .9874 .9896 .9918 .9944 .9975 579
589 .6629 .8320 .8887 .9172 .9345 .9462 .9547 .9612 .9664 .9706 .9742 .9774 .9801 .9826 .9850 .9872 .9894 .9917 .9943 .9975 589
599 .6571 .8291 .8867 .9158 .9334 .9453 .9539 .9605 .9658 .9701 .9738 .9770 .9798 .9823 .9847 .9870 .9892 .9915 .9942 .9974 599
609 .6512 .8262 .8848 .9143 .9323 .9444 .9531 .9599 .9652 .9696 .9733 .9766 .9794 .9820 .9845 .9868 .9890 .9914 .9941 .9974 609
179
INSTRUMENT TRANSFORMERS
HANDBOOK FOR ELECTRICITY METERING
180
For Lagging Current When (b 2 g) is Negative For Leading Current When (b 2 g) is Positive
(b 2 g) .05 .10 .15 .20 .25 .30 .35 .40 .45 .50 .55 .60 .65 .70 .75 .80 .85 .90 .95 .99 (b 2 g)
19 1.0058 1.0029 1.0019 1.0014 1.0011 1.0009 1.0008 1.0007 1.0006 1.0005 1.0004 1.0004 1.0003 1.0003 1.0003 1.0002 1.0002 1.0001 1.0001 1.0000 I9
29 1.0116 1.0058 1.0038 1.0028 1.0023 1.0018 1.0016 1.0013 1.0012 1.0010 1.0009 1.0008 1.0007 1.0006 1.0005 1.0004 1.0004 1.0003 1.0002 1.0001 29
39 1.0174 1.0087 1.0058 1.0043 1.0034 1.0028 1.0023 1.0020 1.0017 1.0015 1.0013 1.0012 1.0010 1.0009 1.0008 1.0007 1.0005 1.0004 1.0003 1.0001 39
49 1.0232 1.0116 1.0077 1.0057 1.0045 1.0037 1.0031 1.0027 1.0023 1.0020 1.0018 1.0016 1.0014 1.0012 1.0010 1.0009 1.0007 1.0006 1.0004 1.0002 49
59 1.0291 1.0145 1.0096 1.0071 1.0056 1.0046 1.0039 1.0033 1.0029 1.0025 1.0022 1.0019 1.0017 1.0015 1.0013 1.0011 1.0009 1.0007 1.0005 1.0002 59
69 1.0349 1.0174 1.0115 1.0085 1.0068 1.0055 1.0047 1.0040 1.0035 1.0030 1.0026 1.0023 1.0020 1.0018 1.0015 1.0013 1.0011 1.0008 1.0006 1.0002 69
79 1.0407 1.0203 1.0134 1.0100 1.0079 1.0065 1.0054 1.0047 1.0040 1.0035 1.0031 1.0027 1.0024 1.0021 1.0018 1.0015 1.0013 1.0010 1.0007 1.0003 79
89 1.0465 1.0232 1.0153 1.0114 1.0090 1.0074 1.0062 1.0053 1.0046 1.0040 1.0035 1.0031 1.0027 1.0024 1.0020 1.0017 1.0014 1.0011 1.0008 1.0003 89
99 1.0523 1.0260 1.0173 1.0128 1.0101 1.0083 1.0070 1.0060 1.0052 1.0045 1.0040 1.0035 1.0031 1.0027 1.0023 1.0020 1.0016 1.0013 1.0009 1.0004 99
109 1.0581 1.0289 1.0192 1.0142 1.0113 1.0092 1.0078 1.0067 1.0058 1.0050 1.0044 1.0039 1.0034 1.0030 1.0026 1.0022 1.0018 1.0014 1.0010 1.0004 109
119 1.0639 1.0318 1.0211 1.0157 1.0124 1.0102 1.0086 1.0073 1.0063 1.0055 1.0049 1.0043 1.0037 1.0033 1.0028 1.0024 1.0020 1.0015 1.0010 1.0005 119
129 1.0697 1.0347 1.0230 1.0171 1.0135 1.0111 1.0093 1.0080 1.0069 1.0060 1.0053 1.0046 1.0041 1.0036 1.0031 1.0026 1.0022 1.0017 1.0011 1.0005 129
139 1.0755 1.0376 1.0249 1.0185 1.0146 1.0120 1.0101 1.0087 1.0075 1.0065 1.0057 1.0050 1.0044 1.0039 1.0033 1.0028 1.0023 1.0018 1.0012 1.0005 139
149 1.0813 1.0405 1.0268 1.0199 1.0158 1.0129 1.0109 1.0093 1.0081 1.0070 1.0062 1.0054 1.0048 1.0041 1.0036 1.0030 1.0025 1.0020 1.0013 1.0006 149
159 1.0871 1.0434 1.0288 1.0214 1.0169 1.0139 1.0117 1.0100 1.0086 1.0075 1.0066 1.0058 1.0051 1.0044 1.0038 1.0033 1.0027 1.0021 1.0014 1.0006 159
169 1.0930 1.0463 1.0307 1.0228 1.0180 1.0148 1.0124 1.0107 1.0092 1.0081 1.0071 1.0062 1.0054 1.0047 1.0041 1.0035 1.0029 1.0022 1.0015 1.0007 169
179 1.0988 1.0492 1.0326 1.0242 1.0191 1.0157 1.0132 1.0113 1.0098 1.0086 1.0075 1.0066 1.0058 1.0050 1.0043 1.0037 1.0031 1.0024 1.0016 1.0007 179
189 1.1046 1.0521 1.0345 1.0256 1.0203 1.0166 1.0140 1.0120 1.0104 1.0091 1.0079 1.0070 1.0061 1.0053 1.0046 1.0039 1.0032 1.0025 1.0017 1.0007 189
199 1.1104 1.0550 1.0364 1.0271 1.0214 1.0176 1.0148 1.0126 1.0110 1.0096 1.0084 1.0074 1.0064 1.0056 1.0049 1.0041 1.0034 1.0027 1.0018 1.0008 199
209 1.1162 1.0579 1.0383 1.0285 1.0225 1.0185 1.0156 1.0133 1.0115 1.0101 1.0088 1.0077 1.0068 1.0059 1.0051 1.0043 1.0036 1.0028 1.0019 1.0008 209
219 1.1220 1.0608 1.0402 1.0299 1.0236 1.0194 1.0163 1.0140 1.0121 1.0106 1.0093 1.0081 1.0071 1.0062 1.0054 1.0046 1.0038 1.0029 1.0020 1.0009 219
229 1.1278 1.0637 1.0422 1.0313 1.0248 1.0203 1.0171 1.0146 1.0127 1.0111 1.0097 1.0085 1.0075 1.0065 1.0056 1.0048 1.0039 1.0031 1.0021 1.0009 229
239 1.1336 1.0665 1.0441 1.0328 1.0259 1.0213 1.0179 1.0153 1.0133 1.0116 1.0101 1.0089 1.0078 1.0068 1.0059 1.0050 1.0041 1.0032 1.0022 1.0009 239
249 1.1394 1.0694 1.0460 1.0342 1.0270 1.0222 1.0187 1.0160 1.0138 1.0121 1.0106 1.0093 1.0081 1.0071 1.0061 1.0052 1.0043 1.0034 1.0023 1.0010 249
259 1.1452 1.0723 1.0479 1.0356 1.0281 1.0231 1.0194 1.0166 1.0144 1.0126 1.0110 1.0097 1.0085 1.0074 1.0064 1.0054 1.0045 1.0035 1.0024 1.0010 259
269 1.1510 1.0752 1.0498 1.0370 1.0293 1.0240 1.0202 1.0173 1.0150 1.0131 1.0115 1.0101 1.0088 1.0077 1.0066 1.0056 1.0047 1.0036 1.0025 1.0010 269
279 1.1569 1.0781 1.0517 1.0384 1.0304 1.0249 1.0210 1.0180 1.0156 1.0136 1.0119 1.0104 1.0092 1.0080 1.0069 1.0059 1.0048 1.0038 1.0026 1.0011 279
289 1.1627 1.0810 1.0537 1.0399 1.0315 1.0259 1.0218 1.0186 1.0161 1.0141 1.0123 1.0108 1.0095 1.0083 1.0071 1.0061 1.0050 1.0039 1.0026 1.0011 289
299 1.1685 1.0839 1.0556 1.0413 1.0326 1.0268 1.0225 1.0193 1.0167 1.0146 1.0128 1.0112 1.0098 1.0086 1.0074 1.0063 1.0052 1.0040 1.0027 1.0012 299
309 1.1743 1.0868 1.0575 1.0427 1.0338 1.0277 1.0233 1.0200 1.0173 1.0151 1.0132 1.0116 1.0102 1.0089 1.0077 1.0065 1.0054 1.0042 1.0028 1.0012 309
Table 10-3 (continued). Phase Angle Correction Factors (PACFs).
For Lagging Current When (b 2 g) is Negative For Leading Current When (b 2 g) is Positive
(b 2 g) .05 .10 .15 .20 .25 .30 .35 .40 .45 .50 .55 .60 .65 .70 .75 .80 .85 .90 .95 .99 (b 2 g)
319 1.1801 1.0897 1.0594 1.0441 1.0349 1.0286 1.0241 1.0206 1.0179 1.0156 1.0137 1.0120 1.0105 1.0092 1.0079 1.0067 1.0055 1.0043 1.0029 1.0012 319
329 1.1859 1.0926 1.0613 1.0456 1.0360 1.0296 1.0249 1.0213 1.0184 1.0161 1.0141 1.0124 1.0108 1.0095 1.0082 1.0069 1.0057 1.0045 1.0030 1.0013 329
339 1.1917 1.0955 1.0632 1.0470 1.0371 1.0305 1.0256 1.0219 1.0190 1.0166 1.0145 1.0128 1.0112 1.0097 1.0084 1.0072 1.0059 1.0046 1.0031 1.0013 339
349 1.1975 1.0984 1.0651 1.0484 1.0383 1.0314 1.0264 1.0226 1.0196 1.0171 1.0150 1.0131 1.0115 1.0100 1.0087 1.0074 1.0061 1.0047 1.0032 1.0014 349
359 1.2033 1.1012 1.0671 1.0498 1.0394 1.0323 1.0272 1.0233 1.0202 1.0176 1.0154 1.0135 1.0119 1.0103 1.0089 1.0076 1.0063 1.0049 1.0033 1.0014 359
369 1.2091 1.1041 1.0690 1.0512 1.0405 1.0332 1.0280 1.0239 1.0207 1.0181 1.0158 1.0139 1.0122 1.0106 1.0092 1.0078 1.0064 1.0050 1.0034 1.0014 369
379 1.2149 1.1070 1.0709 1.0527 1.0416 1.0342 1.0287 1.0246 1.0213 1.0186 1.0163 1.0143 1.0125 1.0109 1.0094 1.0080 1.0066 1.0052 1.0035 1.0015 379
389 1.2207 1.1099 1.0728 1.0541 1.0427 1.0351 1.0295 1.0253 1.0219 1.0191 1.0167 1.0147 1.0129 1.0112 1.0097 1.0082 1.0068 1.0053 1.0036 1.0015 389
399 1.2265 1.1128 1.0747 1.0555 1.0439 1.0360 1.0303 1.0259 1.0224 1.0196 1.0172 1.0151 1.0132 1.0115 1.0099 1.0084 1.0070 1.0054 1.0037 1.0016 399
409 1.2323 1.1157 1.0766 1.0569 1.0450 1.0369 1.0311 1.0266 1.0230 1.0201 1.0176 1.0154 1.0135 1.0118 1.0102 1.0087 1.0071 1.0056 1.0038 1.0016 409
419 1.2382 1.1186 1.0785 1.0584 1.0461 1.0379 1.0318 1.0273 1.0236 1.0206 1.0180 1.0158 1.0139 1.0121 1.0104 1.0089 1.0073 1.0057 1.0038 1.0016 419
429 1.2440 1.1215 1.0805 1.0598 1.0472 1.0388 1.0326 1.0279 1.0242 1.0211 1.0185 1.0162 1.0142 1.0124 1.0107 1.0091 1.0075 1.0058 1.0039 1.0017 429
439 1.2498 1.1244 1.0824 1.0612 1.0484 1.0397 1.0334 1.0286 1.0247 1.0216 1.0189 1.0166 1.0145 1.0127 1.0110 1.0093 1.0077 1.0060 1.0040 1.0017 439
449 1.2556 1.1273 1.0843 1.0626 1.0495 1.0406 1.0342 1.0292 1.0253 1.0221 1.0194 1.0170 1.0149 1.0130 1.0112 1.0095 1.0079 1.0061 1.0041 1.0017 449
459 1.2614 1.1302 1.0862 1.0640 1.0506 1.0415 1.0349 1.0299 1.0259 1.0226 1.0198 1.0174 1.0152 1.0133 1.0115 1.0097 1.0080 1.0063 1.0042 1.0018 459
469 1.2672 1.1330 1.0881 1.0655 1.0517 1.0425 1.0357 1.0306 1.0265 1.0231 1.0202 1.0178 1.0156 1.0136 1.0117 1.0099 1.0082 1.0064 1.0043 1.0018 469
479 1.2730 1.1359 1.0900 1.0669 1.0529 1.0434 1.0365 1.0312 1.0270 1.0236 1.0207 1.0181 1.0159 1.0139 1.0120 1.0102 1.0084 1.0065 1.0044 1.0019 479
489 1.2788 1.1388 1.0919 1.0683 1.0540 1.0443 1.0373 1.0319 1.0276 1.0241 1.0211 1.0185 1.0162 1.0141 1.0122 1.0104 1.0086 1.0067 1.0045 1.0019 489
499 1.2846 1.1417 1.0938 1.0697 1.0551 1.0452 1.0380 1.0326 1.0282 1.0246 1.0215 1.0189 1.0166 1.0144 1.0125 1.0106 1.0087 1.0068 1.0046 1.0019 499
509 1.2904 1.1446 1.0958 1.0711 1.0562 1.0461 1.0388 1.0332 1.0288 1.0251 1.0220 1.0193 1.0169 1.0147 1.0127 1.0108 1.0089 1.0069 1.0047 1.0020 509
519 1.2962 1.1475 1.0977 1.0726 1.0573 1.0471 1.0396 1.0339 1.0293 1.0256 1.0224 1.0197 1.0172 1.0150 1.0130 1.0110 1.0091 1.0071 1.0048 1.0020 519
529 1.3020 1.1504 1.0996 1.0740 1.0585 1.0480 1.0404 1.0345 1.0299 1.0261 1.0229 1.0201 1.0176 1.0153 1.0132 1.0112 1.0093 1.0072 1.0049 1.0020 529
539 1.3078 1.1533 1.1015 1.0754 1.0596 1.0489 1.0411 1.0352 1.0305 1.0266 1.0233 1.0204 1.0179 1.0156 1.0135 1.0114 1.0094 1.0073 1.0049 1.0021 539
549 1.3136 1.1562 1.1034 1.0768 1.0607 1.0498 1.0419 1.0359 1.0310 1.0271 1.0237 1.0208 1.0182 1.0159 1.0137 1.0117 1.0096 1.0075 1.0050 1.0021 549
559 1.3194 1.1591 1.1053 1.0782 1.0618 1.0507 1.0427 1.0365 1.0316 1.0276 1.0242 1.0212 1.0186 1.0162 1.0140 1.0119 1.0098 1.0076 1.0051 1.0022 559
569 1.3252 1.1619 1.1072 1.0797 1.0630 1.0517 1.0435 1.0372 1.0322 1.0281 1.0246 1.0216 1.0189 1.0165 1.0142 1.0121 1.0100 1.0078 1.0052 1.0022 569
579 1.3310 1.1648 1.1091 1.0811 1.0641 1.0526 1.0442 1.0379 1.0328 1.0286 1.0250 1.0220 1.0192 1.0168 1.0145 1.0123 1.0101 1.0079 1.0053 1.0022 579
589 1.3368 1.1677 1.1111 1.0825 1.0652 1.0535 1.0450 1.0385 1.0333 1.0291 1.0255 1.0224 1.0196 1.0171 1.0147 1.0125 1.0103 1.0080 1.0054 1.0023 589
599 1.3427 1.1706 1.1130 1.0839 1.0663 1.0544 1.0458 1.0392 1.0339 1.0296 1.0259 1.0227 1.0199 1.0174 1.0150 1.0127 1.0105 1.0082 1.0055 1.0023 599
609 1.3485 1.1735 1.1149 1.0853 1.0674 1.0553 1.0466 1.0398 1.0345 1.0301 1.0263 1.0231 1.0203 1.0177 1.0152 1.0129 1.0107 1.0083 1.0056 1.0023 609
181
INSTRUMENT TRANSFORMERS
182 Application of Correction Factors
WHEN CORRECTION FACTORS SHOULD BE APPLIED
In most metering installations using instrument transformers, no corrections need be applied if
HANDBOOK FOR ELECTRICITY METERING
instrument transformers meeting IEEE Standard C57.13 accuracy specifications are used within the
burden and power factor limits of these specifications and the secondary leads are short enough so
they cause no appreciable error. Under such conditions, the error contributed by any single instrument
transformer should not exceed the IEEE standard accuracy class. Where both a current and a voltage
transformer are used, their combined error could theoretically reach the sum of the maximum errors
represented by the standard accuracy classes of the two transformers, but will, in most cases, be much
less. In polyphase metering, the total error is the weighted average of the combined errors of the
current and voltage transformer on each phase and can never be greater than the maximum errors
on the worst phase. For 0.3% Standard Accuracy Class transformers, the maximum errors, under the
IEEE-specified conditions, are summarized in Table 10-5.
These maximum errors would rarely occur in an actual combination of instrument transformers.
There is a good probability that the errors would be less than 0.3 to 0.5%, which would be acceptable
for most metering applications.
cos(2 1 2 )
WP 5 ESlS cos 2 3 NENI 3 (RCFE)(RCFI ) 3 ———————
cos 2
WP 5 WS 3 NK 3 RCFK 3 PACFK
WP 5 WS 3 NK 3 FCF
Primary Power 5 Secondary Power 3 Nominal Instrument Transformer Ratio 3 Final Correction Factor
See Figure 10-13 for the corresponding schematic and phasor diagrams.
Table 10-5. Maximum Percent Errors for Combinations of 0.3% IEEE Accuracy Class 183
Instrument Transformers under IEEE-Specified Conditions of Burden,
and Load Power Factors between 1.00 and 0.6 Lag.
INSTRUMENT TRANSFORMERS
Percent Error at 100% Load Percent Error at 10% Load
Special cases may arise that make the application of instrument transformer corrections necessary
or desirable. Such cases could be due to the use of older types of instrument transformers that do not
meet IEEE Standard C57.13 accuracy specifications, the necessity of using heavier burdens than speci-
fied by IEEE, the use of long secondary leads, power factor of the load below 0.6 lagging, power factor
of the load leading, and requirements for higher than normal accuracy for special installations, such
as large wholesale installations, interchange metering between power companies, or measurement of
total generator output during efficiency tests of power station generators and turbines.
The decision as to when instrument transformer corrections should be applied is a matter of policy
that must be decided by each utility company on the basis of both technical and economic consider-
ations. In general, most utilities do not apply instrument transformer corrections for routine work and
may or may not apply corrections in special cases.
If the meter is to be adjusted to compensate for the errors of the instrument transformers, great
care must be taken to make this adjustment in the proper direction. An error in the sign of the correc-
tion applied results in doubling the overall error instead of eliminating it. The best precaution against
this type of mistake is the use of prepared forms which are set up to show each step in the process.
With a well prepared form, correction factors can be applied easily. The actual field work may
involve nothing more than adding the percent error caused by the transformers to the percent error of
the meter.
The primary (overall) percent registration can be made 100.00% if the percent registration of the
meter is adjusted to 100 times the final correction factor.
If the meter in the preceding example were adjusted to 100.37% registration, then
100.37
Primary (overall) Percent Registration 5 ——————— 5 100.00%
1.0 037
Table 10-6 shows a standard form that can be used to determine the required meter adjustment by
this method. This method is particularly useful when meter tests are made with a fixed routine, such
as light-load, full-load, and inductive-load, made respectively with 10 and 100% rated current at 1.0
power factor and with 100% rated current at 0.5 power factor lagging.
This method is applicable to installations with current and voltage transformers, or to either, and
the calculations are simplified by using addition and subtraction for the multiplication of quantities
near unity, as previously explained. Ratio correction factors and phase angles are used directly and the
result is the accuracy performance to which the meter should be adjusted to compensate for instru-
ment transformer errors.
The ratio correction factors and phase angles are taken from test data on the instrument trans-
formers or from the manufacturers’ certificates. These values must be the values that apply at the
terminals of the meter and be based on the actual burdens. If long secondary leads are used from the
voltage transformer to the meter, the effect of the lead drop on the ratio and phase angle as seen at
the meter must be included. This can be determined by test or calculation as previously explained. If
the available instrument transformer data are not based on the actual burden, the desired value may
be determined by interpolation or calculation by methods to be explained later.
The appropriate ratio correction factors and phase angles are shown in Table 10-6. The phase angle
correction factor at unity power factor is 1.0000, within 0.02% or less, for all values of ( 2 ) up to
60 minutes. At 0.50 power factor lagging, the phase angle correction factor is read from Table 10-3 as
1.0050 for a value of ( 2 ) of 210 minutes. The operations indicated in Table 10-6 are performed
and the meter accuracy settings in percent registration are determined as shown. The bottom two
lines show the percent errors caused by the instrument transformers and the percent errors to which
the meter should be set to compensate. The meter is then adjusted to the desired tolerance of these
settings and the compensation has been accomplished.
The calculations in this table have been carried to 0.01%, as it is normal practice to use one more
place in calculations of this kind than is used in the final result. If the final overall accuracy of the
installation were to be reported, it would normally be rounded to the nearest 0.1%.
The same setup may be used when only a current transformer or a voltage transformer is used.
It is only necessary to enter zero under phase angle and 1.0000 under ratio correction factor in the
places where no transformer is used and make the additions and subtractions indicated. For polyphase
installations, when correction factors and phase angles are not widely divergent, the ratio correction
factors and phase angles for the current transformers for all phases may be respectively averaged and
Table 10-6. Calculation of Meter Accuracy Settings. 185
INSTRUMENT TRANSFORMERS
the average values of ratio correction factor and phase angle of the current and voltage transformers
used for the calculations.
Alternatively, calculations may be made on each stator using the ratio correction factors and phase
angles for the transformers connected to that stator. For precise work, where either voltage or current
transformer phase angles materially differ, this method is preferred.
This is the overall percent error of the installation including both meter and transformer errors.
To find the errors due to the transformers alone, assume that the meter is correct. Then, Indicated
Secondary Watthours 5 True Secondary Watthours, and substituting in the preceding equation:
Percent Error Caused by Instrument Transformer 5
(True Secondary Watthours) 2 (True Secondary Watthours)(FCF)
—————————————————————————————————————————————— 3 100
(True Secondary Watthours)(FCF)
1 2 FCF
Percent Error Caused by Instrument Transformer 5 —————— (100) 5 (1 2 FCF) 3 100
FCF
Where 5 means “is approximately equal to.”
The second or approximate form is the most convenient to use and will not be in error by more
than 0.01% for values of FCF between 0.9900 and 1.0100 or more than 0.02% for values of FCF
between 0.9800 and 1.0200.
Example 5:
Given FCF 5 0.9853
Percent Error Caused by Instrument Transformer 5
1 2 0.9853 (0.0147)(100)
————————— 3 100 5 —————————— 5 1.49% using the exact method.
0.9853 0.9853
Percent Error Caused by Instrument Transformer 5
(1 2 0.9853)100 5 0.0147 3 100 5 1.47% using the approximate method.
Note that the sign of the error will be minus for values of FCF greater than 1.
A form such as Table 10-6 can be used to determine the final correction factor from which the
percent error caused by the instrument transformers is determined, as shown on the next to bottom
line of the table.
INSTRUMENT TRANSFORMERS
Figure 10-14. Percent Error Calculation Chart for Effects of Instrument Transformer Ratio and Phase Angle.
center scale that represents the desired power factor. The proper half of the phase angle scale to be
used depends upon the load power factor and the sign of ( 2 ) and this is indicated in the headings
for this scale. The sign of the error caused by the instrument transformers and the sign of the percent
error of the required compensating meter adjustment is indicated in the blocks between the 100 and
95% power factor scales. The chart is designed to give percent errors for a current and voltage trans-
former combined, by using the RCFK and the combined phase angle ( 2 ).
To use the chart for an installation involving a current transformer only, use RCFI on the RCF
scale and in place of ( 2 ). For polyphase values, the percent errors may be determined separately
for each phase, or average values of RCFK and ( 2 ) may be used to obtain the total percent error
in one step. The chart is based on the approximate formula for the percent error caused by the instru-
ment transformer previously discussed. Thus, the results read from the chart may differ by a few
hundredths of a percent from the values computed from Tables 10-2 and 10-3.
188 Example 7:
For a load power factor 70%, lagging:
Current Transformer: RCFI 5 1.0043 5 112
HANDBOOK FOR ELECTRICITY METERING
One end of the straight edge is placed on the RCF scale at 1.0055 and the other end on the
lower half of the phase angle scale at 5. The straight edge then intercepts the 70% power factor
scale at 0.40% in the upper half of the chart. Therefore, the error caused by the instrument
transformers is 20.40% and the meter must be adjusted to 10.40% (fast) to compensate.
INSTRUMENT TRANSFORMERS
product of the average RCFK and the average PACFK gives the average final correction factor. The
percent error caused by the instrument transformers is equal to (1 2 FCF) 3 100. This is entered in
Column B. The values in Columns A and B are added algebraically and entered in the final column to
give the combined percent error caused by the instrument transform ers and the watthour standards.
If correction for the watthour standards is not desired, this can be omitted, in which case the
values in Column A would be zero.
The values in Column B could also be obtained directly from Table 10-7 and the chart shown in
Figure 10-14. This is a simpler but slightly less accurate method.
Table 10-9 is a watthour meter test form suitable for this method. The revolutions of the three
watthour standards for each test run are entered and added as shown. Where only one watthour
standard is used for a single-phase series test of a polyphase meter, its revolutions should be entered
directly in the column for the total revolutions. In this case, the preceding three columns are not
needed. The indicated percent error is computed from the total revolutions and entered as shown. The
190 Table 10-8. Watthour Meter Test, Combined Error Calculation Sheet for
Three-Stator, Three-Phase Meters Tested Three-Phase Using Three Watthour
Standards or Single-Phase Series Using One Watthour Standard.
HANDBOOK FOR ELECTRICITY METERING
percent error caused by the instrument transformers and watthour standards from the last column
of Table 10-8 is entered as shown in Table 10-9. This value, plus the percent error indicated, is equal
to the overall percent error. Only the values at 0.87 power factor have been shown on Table 10-9.
Values at other power factors would be obtained in the same manner. Meter adjustments are made as
required to reduce the overall percent error to the desired tolerances. Table 10-9 has been filled in to
show an “as left” curve at 0.87 power factor lagging, taken after all adjustments had been made. The
“as found” tests and adjustments would be on previous sheets and are not shown in Table 10-9.
This method is simple and fast in actual use as the corrections are precalculated before starting
the meter tests. The forms reduce the whole operation to simple bookkeeping and allow the calcula-
tions to be checked at any time. If only standard single-phase series tests are made on polyphase
meters, the forms shown in Tables 10-8 and 10-9 may be simplified to one column for the watthour
standard data.
Table 10-9. Watthour Meter Test. 191
INSTRUMENT TRANSFORMERS
INSTRUMENT TRANSFORMERS
clearly in the column headings and in the example shown in Table 10-10. The remaining columns of
Table 10-10 would be filled in similar to Table 10-8 using the three-phase power factor to determine
the PACFK.
The same form (Table 10-9) may be used for the watthour meter test as was used for the three-
stator meter, though using only two columns for the revolutions of the two watthour standards.
This method is quite satisfactory for the three-phase phantom load test using two watthour
standards, since balanced loads are applied. It can be used for a customer’s load test using two watt-
hour standards if the load on the circuit is reasonably balanced. For customers’ load tests with badly
imbalanced loads, this method cannot be used. In such cases the corrections must be applied to each
stator and watthour standard separately.
When only one watthour standard is used for a single-phase series test of a two-stator polyphase
meter, both stators operate during the test at the same single-phase power factor and it is not neces-
sary to use Table 10-10 at all. Rather, Table 10-8 is used and the watthour standard error entered
directly in Column A.
Cosines have been used in this calculation to make clear the phase angle errors possible. Similar
results may be obtained by use of PACF, Tables 10-2 and 10-3.
Burden Calculations
VOLTAGE TRANSFORMER BURDENS
The secondary burdens of voltage transformers are connected in parallel across the secondary of the
transformer. The voltampere burden is equal to — E2 where Z is the impedance.
Z
Usually voltage transformer burdens are expressed as voltamperes at a given power factor. To
calculate the total burden on the secondary of a voltage transformer, the burden of each device should
be divided into in-phase and quadrature-phase components and added (voltamperes cannot be added
directly unless they are all at the same power factor).
The in-phase component is:
Watts 5 (Voltamperes)(Cos ) 5 VA 3 PF
The quadrature-phase component is:
VARs 5 (Voltamperes)(Sin ) 5 PF)
(1 2 2
INSTRUMENT TRANSFORMERS
Total Burden Impedance (Z) 5
(Sum of stan
resices
)21m
(Suf
o ctan
reaces
)2
The voltampere burden on a current transformer is equal to I2Z. Burdens are usually computed at
5 amperes rated secondary current. It may be necessary to convert burdens stated in meter manuals at
2.5 amperes to 5.0 amperes.
When the burdens are expressed in voltamperes at a given power factor, the burden of each device
and the secondary conductors should be divided into in-phase and quadrature-phase components, and
added.
The in-phase component is:
Watts 5 (Voltamperes)(cos ) 5 VA 3 PF 5 I2R
The quadrature-phase component is:
VARs 5 (Voltamperes)(sin ) 5 VA
(1 2PF)
2
5 I2X
Where X is the inductive reactance, X 5 2fL, L is the inductance in henries, and f is the frequency in
hertz.
Total Voltamperes 5
(Total s)
Watt
2
1 VAR
(Total s)
2
Total Watts R
Power Factor of Combined Burden 5 Cos 5 ———————————— 5 ——
Total Voltamperes Z
The secondary lead resistance must be included in the burden calculations for current
transformers.
The basic formulas for burden calculations are summarized in Table 10-12 for both current and
voltage transformers.
POLYPHASE BURDENS
When the secondary burdens of instrument transformers are interconnected, as is often the case in
polyphase metering, no simple method of computing the bur dens on each transformer is applicable
to all cases. Such combinations of burden must be computed phasorially on the basis of the actual
circuit.
For wye-connected burdens on wye-connected instrument transformers, each transformer is
affected by the burden directly across its terminals from the polarity to the neutral secondary leads.
Thus, each transformer “sees” only the burden on its own phase and burdens are easily calculated. The
Voltage Transformers
Burden Expression Watts at 120 V VARs at 120 V, 60 Hz
VA 5 Voltamperes at 120 V, 60 Hz
VA 3 PF VA 3
(1 2
PF)2
PF 5 Burden power factor
Current Transformers
Burden Expression Watts at 5 A VARs at 5 A, 60 Hz
R 5 Resistance in ohms
25 3 R 9.43 3 L
L 5 Inductance in millihenries
Z 5 Inductance in ohms, 60 Hz
25 3 Z 3 PF 25 3 Z 3
(1 2
PF)2
PF 5 Burden power factor
VA 5 Voltamperes at 5 A, 60 Hz
VA 3 PF VA 3
(1 2
PF)2
PF 5 Burden power factor
196 same situation is true for an open-delta burden on transformers connected open delta. These are the
normal arrangements for metering burdens.
Unusual cases, such as wye-connected burdens on open-delta-connected instrument transformers,
delta-connected burdens, on wye-connected instrument transformers, and complex combinations of
HANDBOOK FOR ELECTRICITY METERING
single-phase and three-phase burdens must be analyzed individually. Since such analysis is complex,
this type of burden should be avoided in metering applications when possible.
1.006
1.005
1.004
1.003
1.002
RATIO CORRECTION FACTOR
1.001
1.000
0.999
0.997
0.995
0.994
230 225 220 215 210 25 0 15 110 115 120 125 130
PHASE ANGLE IN MINUTES
Figure 10-15a. Sample of Graph Paper Specifically Scaled for oltage Transformer Circle Diagram.
An example of the use of the circle method is shown in Figure 10-15b. The following data are test 197
results at 120 secondary volts for a 2400:120 volt voltage transformer:
At 0 voltampere burden, RCF 5 0.9979 and phase angle 5 12.0 minutes
INSTRUMENT TRANSFORMERS
At 50 voltamperes, 85% power factor burden, RCF 5 1.0040 and phase angle5 11.0 minute
Performance at other voltampere and power factor burdens can be plotted by making radii propor-
tional to voltamperes and angles equal to burden power factor angles.
1.008
1.007
1.006
1.005
1.004
RATIO CORRECTION FACTOR
1.003
1.002
1.001
1.000
0.999
0.998
0.997
0.996
230 225 220 215 210 25 0 15 110 115 120 125 130
PHASE ANGLE IN MINUTES
Figure 10-16a. Parallelograms Showing Graphical Equivalent of IEEE Accuracy Classes 0.3, 0.6, and 1.2 for
Current Transformers for Metering.
Note: The accuracy requirements for 100% rated current also apply at the continuous-thermal-current rating of the transformer.
for voltage transformers. Note that the inclination of the accuracy class parallelogram for voltage
transformers is opposite that of current transformers. The current transformer allowable TCF at 10%
current is double that at 100% current.
It has been shown that a TCF is not a constant but depends on the secondary burden. Hence, the
standard accuracy class is designated by the limiting percent error caused by the transformer followed
by the standard burden designation at which the transformer accuracy is determined. For a current
transformer the accuracy class may be written: 0.3 B-0.5, 0.6 B-1.8. This means that at burden B-0.5
the transformer would not affect the meter accuracy more than 6 0.3% at 100% rated current or
6 0.6% at 10% rated current, and at burden B-1.8 the transformer would not effect the meter accu-
racy more than 6 0.6% at 100% rated current or 6 1.2% at 10% rated current, when the power factor
of the metered load is between 0.6 and 1.0 lagging.
Likewise, the accuracy of a voltage transformer could be given as 0.3 X, 0.3 , 1.2 Z, with similar
meanings. Accuracy classes of voltage and current transformers are shown in Tables 10-13 and 10-15.
INSTRUMENT TRANSFORMERS
Figure 10-16b. Parallelograms Showing Graphical Equivalent of IEEE Accuracy Classes 0.3, 0.6, and 1.2 for
Voltage Transformers for Metering.
Note: The transformer characteristics shall lie within the limits of the parallelogram for all voltages between 90 and 110% of rated voltage.
The standard burdens for both voltage and current transformers are precisely defined by IEEE
Standard C57.13. Standard burdens and characteristics are given in Tables 10-14 and 10-16.
The use of the IEEE standard accuracy classifications permits the installation of instrument trans-
formers with reasonable assurance that errors will be held within known limits provided that burden
limitations are strictly followed and secondary connections introduce no additional error.
W 12.5 0.10
X 25. 0.70
M 35. 0.20
Y 75. 0.85
Z 200. 0.85
ZZ 400. 0.85
200 Table 10-15. IEEE Accuracy Classes for Metering Current Transformers.
Metering Burdens
*If a current transformer is rated at other than 5 amperes, ohmic burdens for specification and rating may be derived by multiplying the
resistance and inductance in the table by [5/(ampere rating)]2, the VA at rated current and the power factor remaining the same.
**These standard burden designations have no significance at frequencies other than 60 Hz.
(CTs) to maintain accuracy over a much wider range than for standard revenue metering
installations.
• Increasing cost of energy places additional emphasis on accurately metering large customers.
• High accuracy CTs’ extended range capability allows the use of fewer ratios. High accuracy CTs
extend their accuracy at a lower range of current while maintaining equivalent rating factors
compared to standard CTs. This extended range of the high accuracy CTs allows a reduction in
CT inventory by minimizing the different ratios of CTs that must be kept in inventory.
Design and material changes have resulted in making the cost and availability of high accuracy
instrument transformers of more interest to some users. Magnetic core material for high accuracy
instrument transformers is made of specialized steel with better magnetic properties than grain-
oriented electrical grade steel used for conventional instrument transformers, which results in better
accuracy. Non-conventional methods of compensation have enhanced performance at the lower
ranges of 1%–10% of rated current while permitting continuous duty to 400% of rated current.
In general, high accuracy current transformers should not be considered for use in protective relay-
ing applications. Cores produced from specialized steels have much lower saturating induction levels
than those of grain oriented silicon-iron steel. For example, nickel-iron will saturate at 33% that of
silicon-iron, while nanocrystalline amorphous steel saturates at about 50%. These levels will tremen-
dously decrease the CTs fault level capability. In some cases, high accuracy CTs may go into saturation
slightly above 500% rated current by design. In addition, if the CT winding has been compensated,
true errors above 500% may not be easily calculated.
IEEE Standard C57.13.6-2005 was developed to define two new accuracy classes and burdens for 201
current transformers and one new accuracy class for voltage transformers.
For CTs, accuracy class .15 and .15S are now defined. Figure 10-17 shows the limits for the .15
accuracy class and Figure 10-18 shows the limits for the .15S accuracy class. The .15 accuracy class
INSTRUMENT TRANSFORMERS
maintains .15% accuracy from 100% to maximum rated current and .3% accuracy down to 5% of
rated current. The .15S accuracy rating maintains an accuracy of .15% from 5% to maximum rated
current.
The standard defines one additional accuracy class for voltage transformers, .15, as shown in
Figure 10-19.
Several manufacturers currently provide an extended range high accuracy current transformer.
Figure 10-18 also shows the limits of accuracy of this CT. The accuracy of these units are .15% from
1% to maximum current rating. The 1% rating would be at a current of .05 amp, which is below the
.25 amp minimum test current for most revenue accuracy class 20 meters. The accuracy of the meter
is not well documented or normally tested below .25 amp.
Due to the extensive use of electronic meters and instrumentation, a significantly lower burden
may be present than for electromechanical meters or instrumentation. As a result, IEEE C57.13-2005
has added two additional standard burdens as listed in Table 10-17.
1.0045 20.45
1.003 20.30
1.0015 20.15
1.000 10
0.9985 10.15
0.997 10.30
0.9955 10.45
Figure 10-17. Limits for .15 Accuracy Class for Current Transformers for Metering.
202
1.0015 20.15%
HANDBOOK FOR ELECTRICITY METERING
1.0010 20.10%
1.0005 20.05%
1.0000 10%
0.9995 10.05%
0.9990 10.10%
0.9985 10.15%
Figure 10-18. Limits for .15S Accuracy Class for Current Transformers for Metering.
Burden E.04 is applicable for applications where the CTs are adjacent to the meter (within
10 feet).
From an application perspective, many existing CTs currently installed, as well as many produced
today that are rated 0.3 class, may inherently satisfy a class of 0.15 at lower burdens. This can be
evaluated if RCF and phase angle curves at lower burdens are readily available, and which provide
characteristics below 10% of rated current. Recertification of such CTs with performances verified to
5% of rated current and lower may be a viable option if the CTs are accessible. Use and calibration
should be in accordance with the utilities’ standard metering practices and/or policies.
INSTRUMENT TRANSFORMERS
1.0010 20.10%
1.0005 20.05%
1.0000 10%
0.9995 10.05%
0.9990 10.10%
0.9985 10.15%
Figure 10-19. Limits for .15 Accuracy Class for Voltage Transformers for Metering.
VOLTAGE TRANSFORMERS
Similarly, a voltage transformer reduces the voltage being measured to a highly accurate value that is
proportional to the line voltage and can be measured by the meter.
weather. This construction is generally limited to circuits of 25,000 volts (125 kV BIL) or less.
Typically, indoor voltage transformers are fused.
Outdoor
An outdoor instrument transformer is constructed for installations exposed to the weather.
Indoor-Outdoor
For circuits rated at 24 kV or above, common designs of instrument transformers are suitable for
either indoor or outdoor use. At lower voltages, units for outdoor use are provided with additional
protection, particularly against moisture. Spacings between high-voltage terminals and between these
terminals and ground are generally increased for outdoor types.
CONSTRUCTION TYPES
Both liquid filled and dry type construction is used for transformers rated 69 kV (350 kV BIL) and
lower. Above 69 kV liquid filled and gas filled, construction is used.
Butyl Rubber
Butyl rubber is used for the outside coating of instrument transformers. Butyl rubber has excellent
insulating properties and the ability to ensure exact dielectric clearances and geometries of the core-
coil assembly.
Cycloaliphatic Epoxy (CEP)
CEP is also used, due to its good resistance to degradation and tracking erosion as well as its ability to
withstand exposure to humidity, UV radiation, and outdoor pollutants.
Hydrophobic Cycloaliphatic Epoxy
Introduced in the 2000s, hydrophobic cycloaliphatic epoxy incorporated improved hydrophobic proper-
ties, causing water to bead up on the surface and remove conductive contaminants when the water
rolls off.
Dry Type
A dry type transformer’s core and coils are embedded in a body of material which serves as the
insulation, case, and bushings. This construction is usually employed for individual current or voltage
transformers.
The materials used to insulate and furnish mechanical support are rubbers, epoxies, thermoplastic
elastomers (TPE) and ethylene-propylene-diene-monomer (EPDM) as these materials are adaptable
to molding into the geometry of the transformer. Other plastics may be used, but their use is not
widespread.
The core and coils may be wrapped in layers of insulating paper or material and then inserted into
the transformer.
Compound Filled
In a compound filled construction, the core and coils are wrapped and inserted in the same manner
as in the dry type construction. The element is then mounted in the case and the case filled with a
compound with a high dielectric strength. These units are designed for voltages not exceeding 15 kV.
Liquid Filled
In the liquid filled construction, the core and coils are insulated and then mounted in a tank which is
filled with the insulating liquid.
Higher voltage transformers, in addition to the primary winding, often have two other windings,
a secondary and a tertiary, on a common core. Sometimes one or both windings have a tap allowing
multiple ratios.
Gas Filled
Sulfur hexafluoride gas SF6 is used to insulate the core and coils of instrument transformers in voltage
ranges above 69 kV. Insulating gas is used instead of liquid insulation and requires special coil insula-
tion and other precautions.
VOLTAGE TRANSFORMERS 205
Voltage transformers are made with various methods of winding. They are usually wound for single-
ratio at lower voltages and two ratios at higher voltages, particularly for substation applications.
INSTRUMENT TRANSFORMERS
For special purposes, taps may be taken off at various points on the secondary winding. While
these taps are usually marked, great care should be used in connecting such a transformer to ensure
that the proper tap is used.
CORRECTION FACTOR
1.0050
1.0025
1.00
.0075
260 250 240 230 220 210 0 110 120 130 140 150 160
TEMPERATURE (°C)
Figure 10-21. CCVT Correction Factor vs. Temperature for Mixed Dielectric Design.
The mixed dielectric design typically consist of kraft paper and polypropylene film dielectric layers,
impregnated with synthetic oil. The paper and film have dielectric properties that change in an oppos-
ing manner with regard to temperature, thus providing a relatively flat capacitance change over a wide
temperature range. This capacitance change is normally considered to be within the accuracy class
range of the unit.
All film designs use only polypropylene as the dielectric. As the temperature changes below the
freezing point, these designs tend to experience capacitance changes that may effect the accuracy
performance of the CCVT. When using these designs for revenue metering, the temperature response
of the CCVT should be investigated.
Older CCVTs using paper/mineral oil dielectrics can drift substantially over normal operating
temperatures and are generally not recommended for revenue metering.
AUTOTRANSFORMERS
An autotransformer is one having only one coil with taps brought out at the proper points in the coil
to give the voltages desired. Any portion of the coil may be used as the line-voltage connection and
any other portion as the load connection. The ratio of such a transformer is approximately:
Line voltage Number of turns used for line winding
————————— 5 ————————————————————————————
Load voltage Number of turns used for load winding
Autotransformers may be used for special purposes as in the phase-shifting transformers used
with VARhour meters. The widespread use of solid-state meters with VAR measurement capability has
significantly reduced the need for phase-shifting transformers.
CURRENT TRANSFORMERS
Wound (Wound Primary) Type
This type of CT has the primary and secondary windings completely insulated and permanently
assembled on the core. The primary is usually a multi-turn winding.
Three-Wire Transformers
The primary winding is in two equal sections, each of which is insulated from the other and to
ground so that the transformer can be used for measuring total power in the conventional three-wire,
single-phase power service. Three-wire transformers are used on low voltage only since it is difficult to
provide the necessary insulation between the two primary windings. Two two-wire CTs are commonly
used for three-wire metering.
Window Type
This type is similar in construction to the wound type except that the primary winding is omitted
and an opening is provided in the core through which a bus or primary conductor may be passed,
serving as the primary winding. Complete insulation for such a primary is not always provided by the 207
transformer.
By looping the primary conductor through the core, a number of different ratios may be obtained.
For instance, if a transformer had a ratio of 1,200:5 or 240:1 with a single turn, it would have a ratio
INSTRUMENT TRANSFORMERS
of 120:1 with two turns, 80:1 with three turns, etc. In other words, the ratio is:
Original Ratio
Ratio 5 ——————————
Turns
The number of turns in the primary is the number of times the conductor passes through the hole in
the core and not the number of times the cable passes some point on the outside.
Bar-Type
The bar-type is similar to the window type but has an insulated primary provided. The bar in bar-type
may be removable or fixed.
Window Type as a Three-Wire
This is done by passing one wire of a three-wire, single-phase service through the window in one
direction and the other line in the opposite direction. The ratio of the CT would be one-half the
marked ratio. For example, an 800:5 CT can be used to measure 400A on each leg. Some manufac-
tures provide a bar-type CT and label as a 400&400:5.
Dual Ratio
The series/parallel type has the primary divided into two sections and may be used as a dual ratio
transformer. A 200 3 400:5 CT has a ratio of 200:5 when the primary coils are connected in series
and 400:5 when connected in parallel.
The tapped secondary type, designated, for example, 200/400:5, provides the advantage of chang-
ing ratio without interrupting service.
Split-Core Type
The split-core type is convenient to install where the primary conductor cannot be broken or opened.
Part of the core is separable or hinged to permit its encircling a primary conductor or an uninsulated
conductor operating at a voltage within the voltage rating of the transformer. It has a secondary
winding completely insulated and permanently assembled on the core but does not have a primary
winding. It may or may not have insulation for a primary winding.
The exciting current of this type of CT may be relatively large as are the losses,ratio error, and
phase angle error.
Multi-Core
When it is necessary or desirable to operate two or more separate burdens from a single CT, a
complete secondary winding and magnetic circuit must be supplied for each burden and the indi-
vidual magnetic circuits linked by a common primary winding. A double-secondary CT is designated
200:5//5, for example.
Each secondary function is entirely independent of the other.
Miniature Transformers
These transformers are exceptionally small, no larger than a four inch cube, and are used in metering
low-voltage circuits. The typical continuous current rating factors are one, two, three, and four times
the nominal rating. Each type and ratio of CT may have a different rating factor.
With rated current in the primary, the open secondary voltage is low and may be considered non-
hazardous. Current transformers should never be open-circuited, even though miniature CTs may not
develop enough voltage before they saturate and damage themselves. An open circuit can cause the CT
to be magnetized, and in larger units can cause a failure as well as voltages in excess of 2,500 volts.
Bushing Type
This type has a secondary winding completely insulated and permanently assembled on a ring-type
core but does not have a primary winding or insulation for a primary winding. The circuit breaker or
power transformer bushing with its conductor or stud becomes the completely insulated single-turn
primary winding of the bushing type CT.
For metering application, considerable improvement in accuracy over the range of primary current
is obtained by using special core materials and compensated secondary windings. Bushing type CTs, at
208 ratings above 100 amperes may have accuracies within acceptable revenue metering limits. The burden
capability of these CTs is directly related to core cross-section and inversely related to ratio.
HANDBOOK FOR ELECTRICITY METERING
VOLTAGE TRANSFORMERS
Basic Impulse Insulation Level
The basic impulse insulation level (BIL) rating of a voltage transformer indicates the factory dielectric
test that the transformer insulation is capable of withstanding. The dielectric test values, minimum
creepage distances associated with each BIL, the appropriate BIL level for each primary voltage rating,
and conditions for transformer application are given in IEEE Standard C57.13. In a wye system with
voltage transformers connected line to grounded neutral, the transformer may be subjected to 1.73
times normal voltage during a ground fault. Hence the distinction among the various groups must be
maintained to avoid over-stressing transformer insulation.
Insulation must be de-rated when transformers are installed at altitudes greater than 3,300 feet
(1,000 meters) above sea level. See IEEE C57.13.
The BIL of voltage transformers should be coordinated with associated equip ment. In a substation
with a BIL level of 200 kV, it is considered poor practice to use voltage transformers of 150 kV BIL.
When deciding on the insulation level to be used, questions such as whether the power circuits are
overhead or under ground and adequacy of lightning arrester protection should be considered.
Thermal Rating
The thermal rating of a voltage transformer is the voltamperes that the transformer will carry continu-
ously at rated voltage and frequency without causing the specified temperature limits to be exceeded. It
has little, if anything, to do with the burdens at which accuracies are established. It must be remem-
bered that whether the transformer remains within its accuracy class depends upon the burden (load)
on the secondary.
CURRENT TRANSFORMERS
Basic Impulse Insulation Level
The Basic Impulse Insulation Level is a useful guide in selecting current transformers for installation
in critical locations. Current transformers should not be rated at a lower level than the other station
or service equipment.
Continuous Thermal Current Rating Factor
Current transformers may carry a thermal rating factor of 1.0, 1.33, 1.5, 2.0, 3.0, or 4.0. This means
that the nameplate current rating may be multiplied by the rating factor applicable to give the maxi-
mum current the transformers can carry continuously in an ambient temperature not exceeding 30°C.
High-voltage current transformers typically have a rating factor of 1.5. For altitudes above 3,300 feet
or 24 hour temperatures appreciably different from 30°C, refer to IEEE Standard C57.13.
The IEEE accuracy classifications for current transformers apply throughout the current range
defined by the continuous thermal current rating factor.
Short-Time Thermal Limit or Rating
The short-time thermal current limit of a current transformer is the rms, symmetrical primary current
that may be carried with the secondary winding short-circuited for a stated period, usually 1 second,
without exceeding a maximum specified temperature in any winding. When this current limit is
expressed as a rating, it is a number which represents how many times normal primary current.
Short-Time Mechanical Limit or Rating
This limit indicates the maximum current value (how many times normal primary current), for one
second, that the current transformer can stand without mechanical failure. The possible mechanical
failure is the distortion of the primary winding. Hence the bar-type or through-type has a practically
unlimited mechanical rating. It is often considered not an applicable rating for window or bushing
style CT’s, as damage to the transformer is dependent upon the support or bracing of the primary 209
conductor or bus work.
When indoor current transformers are in locations critical to public safety, it may be necessary
to use a higher rated transformer than the circuit requires to obtain the necessary mechanical and
INSTRUMENT TRANSFORMERS
thermal short-time ratings. Both of these short-time ratings should be matched to possible fault cur-
rents in the circuit.
• Percent Loss of Life (%LoL)—Equivalent aging in hours at reference hottest spot temperature
over a time period (usually 24 hours) multiplied by 100 and then divided by the total normal
insulation life (in hours) at the reference hottest spot temperature (110 C° for a 65 C° average
winding rise and 95 C° for a 55 C° average winding rise).
Formulas:
1. Feqa 5 (%LoL 3 NIL) / (24 hours 3 100)
24
2. Feqa 5 n51 (Faa(n) 3 t(n)) / 24
3. HST 5 (215000 / (LN(Faa) 2 (15000/368))) 2 273 [For 55 C° Rise]
4. Loading Factor (LF) 5 (((HST 2 AT24) 3 RF²) / 55) [For 55 C° Rise]
Calculated Loading Factors Based on the Conditions Listed Above:
1. For Normal Conditions:
• Feqa 5 (0.01 * 180,000) / (24 * 100) 5 0.75
• Faa 5 Feqa / 24 5 0.75/24 5 0.03125
• HST 5 (215000/(LN(0.03125) 2 (15000/368))) 2 273 5 66 C°
• For continuous operations the Load Factor must be calculated using C12.11 and C57.13
• LF 5 (((85 2 AT24) * RF²) / 55) (Reference C12.11 and C57.13 for continuous
operations)
• LF 5 0.95 (for average ambient temp 5 35 C°; RF 5 1.0)
2. For Long Term Emergency
• Feqa 5 (0.04 * 180,000) / (24 * 100) 5 3.0
• Faa 5 (F eqa 2 (20hrs * 0.03125)) / 4 hrs 5 0.59
• HST 5 (215000/(LN(0.59)2(15000/368))) 2 273 5 90 C°
• LF 5 (((HST 2 AT24) * RF²) / 55)
• LF 5 1.0 (for average ambient temp 5 35 C°; RF 5 1.0)
3. For a 12 Hour Emergency
• Feqa 5 (1.0 * 180,000) / (24 * 100) 5 75.0
• Faa 5 (Feqa 2 (12hrs * 0.03125)) / 12 hrs 5 6.22
• HST 5 (215000/(LN(6.22)2(15000/368))) 2 273 5 112 C°
• LF 5 (((HST 2 AT24) * RF²) / 55)
• LF 5 1.19 (for average ambient temp 5 35 C°; RF 5 1.0)
4. For a 1 Hour Emergency
• Feqa 5 (4.0 * 180,000) / (24 * 100) 5 300.0
• Faa 5 Feqa 2 (23hrs * 0.03125) 5 299.28
• HST 5 (215000/(LN(299.28)2(15000/368))) 2 273 5 155 C°
• LF 5 (((HST 2 AT24) * RF²) / 55)
• LF 5 1.48 (for average ambient temp 5 35 C°; RF 5 1.0)
INSTRUMENT TRANSFORMERS
ratings of the larger power apparatus.
RELAY APPLICATIONS
For relaying (system protection) applications, current transformers must meet requirements that differ
greatly from those of metering. Since relays operate under abnormal conditions, high-current charac-
teristics are important.
Current transformers for relaying service are given standard accuracy class ratings by letters and
numbers, such as T200 or C200, which describe their capabilities up to 20 times normal current
rating. The standard relay accuracy indicates the RCF will not exceed the 10% accuracy limits at loads
from one to 20 times nominal, and at the rated burden. The letters T and C indicate whether perfor-
mance is based on tests (T) or calculated (C).
The number 2 secondary lead is common to both transformers and carries the phasor sum of the
currents drawn by coils 1–2 and 3–2. This leads to some difficulty in very precise metering, particularly
if long secondary leads are used, as it is difficult to calculate the exact effect of this common lead
resistance. Generally, the common lead will not produce any significant error for watthour metering
and saves one wire.
Three-Phase, Three-Wire Delta with Four-Wire Secondary
Where long secondary leads are used and where correction factors are to be applied, the four-wire
secondary shown in Figure 10-24 is preferred.
INSTRUMENT TRANSFORMERS
Figure 10-24. Three-Phase, Three-Wire Open-Delta, Four-Wire Secondary.
phase angle measurements. In addition, such a small fuse may be mechanically weak and may fail due
to aging without any transformer failure.
If a primary fuse opens for any reason, the load will be incorrectly metered or not metered until
the fuse(s) is(are) replaced. Such incident causes error or lack of meter data for billing and settlement
purposes.
In many cases, circuit protective equipment is relied upon without the additional fusing of the
voltage transformer primaries. There are cases where primary fuses are used in metal enclosure equip-
ment. This is done to maintain equipment in service in the event of a voltage transformer failure.
On wye-connected voltage transformers, the neutral side of voltage transformers is not fused.
Secondary Fuses
The secondary leads of a voltage transformer are often fused, especially in high-voltage applications. The
secondary fuses protect the transformers from short circuits in the secondary wiring. Fuses and fuse clips
may introduce sufficient resistance in the circuit to cause metering errors. When corrosion is present
this effect may become serious. A voltage transformer is not normally subject to overload as its metering
burden is fixed at a value far below the thermal capacity of the transformer. Hence, the only value of the
fuses is short-circuit protection. The most likely chance of a short circuit is during test procedures and
normally the transformer can stand a momentary short without damage. When voltage transformers are
used for both metering and relay service, an accidental short will operate the relays and cause an inter-
ruption. In such cases the metering circuit can be fused after separation for relaying and metering have
been made. The individual utility’s standard practices will usually dictate what situations require voltage
transformer fusing.
Secondary fuses/fuse clips may suffer a soft failure (meaning increase resistance but not open).
Application of fuses will impact three goals of any metering point/service connection:
• Safety of installation 215
• Reliability of service connection
• Quality of energy measurement
INSTRUMENT TRANSFORMERS
Generally, secondary fuses would not be used when one dry type transformer is used for metering.
Effect of Secondary Lead Resistance, Length, and Size of Leads
The effect of secondary lead resistance in a voltage transformer circuit is to cause a voltage drop in the
leads so that the voltage at the meter is less than the voltage at the terminals of the transformer.
When the lead resistance exceeds a few tenths of an ohm, this voltage drop can cause errors equal
to or greater than the errors due to ratio and phase angle of the transformer.
Meters can be adjusted to compensate for these errors but most companies object to upsetting
meter calibrations to take care of secondary lead errors. This problem is avoided by limiting second-
ary lead lengths to, for example, a limit of not over 100 feet of No. 10 wire. When greater distances
are involved, either larger secondary conductors or meters adjacent to the transformers with contact
devices to transmit the intelligence to the station are used.
With normal watthour meter burdens the error due to the leads will usually be within acceptable
limits if the total lead resistance does not exceed 0.3 ohms. If the lead resistance is larger, or if heavy
burdens are used, calculations should be made to determine if corrections are necessary.
CURRENT TRANSFORMERS
Two-Wire, Single-Phase
Figure 10-26 shows the connec-
tions for one CT supplying single-
phase current to the current coil of
a meter. Again, the grounding of
the non-polarity secondary lead is
at one point only.
Three-Wire, Three-Phase
This connection is shown in Figure
10-27. The grounding of the com-
mon connection is at one point
only. The common lead carries the
phasor sum of the secondary cur-
rents in each transformer. To avoid
the problem of applying corrections Figure 10-26. Two-Wire, Single-Phase.
for the common lead resistance,
the connection shown in Figure
10-25, using four secondary leads,
is occasionally employed.
Four-Wire, Three-Phase with
Wye-Connected Secondaries
This connection is shown in Figure
10-28. The grounding of the com-
mon lead is at one point only. On
a balanced load the common lead
carries no current.
Four-Wire, Three-Phase with
Delta-Connected Secondaries
Figure 10-29 shows this connec-
tion which is sometimes used to
provide three-wire metering from
a four-wire system. It is often used
for indicating and graphic meters
and relays and sometimes for
watthour metering. The metering Figure 10-27. Three-Wire, Three-Phase, Three-Wire Secondary.
216
HANDBOOK FOR ELECTRICITY METERING
is theoretically correct only at balanced voltages, but on modern power systems the voltage is normally
balanced well enough to give acceptable accuracy for watthour metering. With delta-connected current
transformers, the secondary currents to the meter are displaced 30° from the primary line currents
and also increased by the square root of three ( 3 ) in magnitude due to the phasor addition. This
circuit is equivalent to the 2½-stator meter used by some companies. It permits the use of a standard
two-stator meter with none of the test complications that the 2½-stator meter involves.
Parallel Secondaries for Totalized Metering
The paralleling of CT secondaries for totalized metering is covered in Chapter 16, “Special Metering,”
under the “Totalization” section. That section outlines the details and precautions involved in this
method.
With the proper precautions, acceptable metering accuracy may be obtained. Without proper
consideration of all the factors involved, the errors may be excessive, particularly at low current values.
Grounding
It is standard practice to ground the non-polarity secondary lead of a CT. Grounding is a necessary
safety precaution for protection against static voltages and insulation failure. Normally, all metal cases
of instrument transformers should be grounded (local regulations may prohibit such grounding in
overhead construction). If grounded, the CT secondary circuit must be grounded in only one place.
In order to “provide the maximum protection to personnel and connected equipment,” IEEE Standard
C57.13.3, a Guide for the Grounding of Instrument Transformer Secondary Circuits and Cases, recom-
mends that this point of grounding be at the switchboard (or meter cabinet). When CT secondaries
are connected in parallel and grounded, there must be only one ground for the set of CTs and this
should be at the point where the secondary leads are paralleled at the meter. Additional grounds must
be avoided due to the indeterminate resistance and voltage gradients in the parallel ground path and
the resultant metering errors. On circuits of 250 volts or less, grounding of the CT secondary is not
necessarily required, but is a good practice for protection of personnel and equipment.
Number of Secondary Wires
The resistance of a CT secondary lead adds to the burden, but unless this added resistance causes the
total burden to exceed the burden rating of the transformer, it has a relatively small effect on the
transformer accuracy. For most installations, the common lead is used to save wire. For very precise
metering, separate return leads might be justified if the lead resistance is large.
217
INSTRUMENT TRANSFORMERS
Figure 10-29. Four-Wire, Three-Phase with Delta-Connected Secondaries.
INSTRUMENT TRANSFORMERS
work properly. If shorting clips in meter sockets are present, they should be tested to be sure that they
open when the meter is installed. This type of verification is most conveniently done on a new instal-
lation before the service is energized.
When the service is already energized, this wire tracing method requiring the removal of wires
from terminals may be impractical and unsafe.
INSULATION TESTS
The insulation of instrument transformers must be adequate to protect the meters and control appara-
tus as well as the operators and testers, from high-voltage circuits and to insure continuity of service.
The insulation tests should normally precede all other tests for reasons of safety.
When it is essential to determine the accuracy of instrument transformers removed from service
in order to confirm corrections of billing, it may be advisable to make accuracy tests with extreme
caution before any insulation test.
It is recognized that dielectric tests impose a severe stress on insulation and if applied frequently
will hasten breakdown. It is recommended that insulation tests made by the user should not exceed
75% of the IEEE standard factory test voltage. When dielectric field tests are made on a periodic basis,
it is recommended that the test voltage be limited to 65% of factory test values.
AC Applied Potential (Hi-Pot) Tests, 60 Hertz
The alternating-current test at 60 hertz should be made on each instrument transformer by the
manufacturer in accordance with IEEE standards. Similar tests may be made by the user. All insulation
tests for liquid-insulated transformers should be made with the transformer cases properly filled.
Hi-pot test sets with fault-current capacities below “Let Go” or “Threshold of Feeling” are a desir-
able safety precaution. When properly constructed, such equipment does not represent a fatal hazard
to the operator. Many small sets of this type are available commercially. These small test sets may
not supply the charging current necessary for over-potential tests on high-voltage current and voltage
transformers.
When high-potential testing equipment with larger fault-current capacity is used it must be
handled with all the safety precautions necessary for any other high-voltage power equipment. Such
equipment represents a fatal hazard to the operator. Some degree of protection from the hazards of
such equipment may be provided by the use of an enclosed test area protected by electrical interlocks
that automatically de-energize the equipment when the gate is opened.
The fundamental responsibility for safety lies with the operator who must use the utmost care to
de-energize the equipment before approaching the high-voltage terminals. The operator must never fall
into the bad habit of depending upon the interlocks as these could fail.
To protect the transformers being tested, some means should be provided in large-capacity hi-pot
equipment to prevent destructive surges and limit the current in case of breakdown. Impedance in the
form of choke coils is often used for this purpose.
When the hi-pot test voltage is very high, a spark gap may be used to prevent the accidental 221
application of voltage above the desired value. Resistors are used in series with the spark gap to limit
the current at breakdown and to damp high-frequency oscillation. The gap is set to a breakdown
value slightly higher than the desired test value before the transformer to be tested is connected. The
INSTRUMENT TRANSFORMERS
transformer under test is then connected across the gap and its resistors. Should the test voltage be
exceeded, the gap flashes over and prevents the voltage from rising further.
POLARITY TESTS
The marking of the leads should be carefully checked by a polarity test. Most methods, as well as the
instrumentation used in checking transformers for ratio and phase angle, automatically check polarity
at the same time. When such facilities are not available, the circuits shown in Figures 10-27 through
10-30 may be used to determine polarity.
Polarity Tests for Voltage Transformers
In Figure 10-30, Polarity Test, Voltage Transformer, voltage H2 to X2 is less than voltage H1 to H2 if
polarity is correct. The reliability of this method is diminished at high ratios.
For Figure 10-31, Polarity Test, Voltage Transformer, the standard voltage transformer must have
the same nominal ratio as the
unknown voltage transformer. The
voltmeter reads zero if polarity
is correct and twice the normal
secondary voltage if incorrect.
Polarity Tests for
Current Transformers
In Figure 10-32, Polarity Test,
Current Transformer, polarity
is correct if the ammeter reads
less when X2 secondary lead is
connected to the line side of the
ammeter than when the X2 lead is
connected to X1 (shorted secondary
circuit). CAUTION: Do not apply
primary current with the secondary
Figure 10-30. Polarity Test, Voltage Transformer.
open. The reliability of this method
is diminished at high ratios.
In Figure 10-33, Polarity Test,
Current Transformer, the standard
current transformer must have
the same nominal ratio as the
unknown current transformer. The
ammeter reads zero if the polarity
is correct and twice the normal
secondary current if incorrect.
CAUTION: Do not open the CTs’
secondary circuits with primary
current applied.
TESTS TO VERIFY
THE MARKED RATIO
Voltage Transformers
The marked ratio of a voltage
transformer may be verified at
Figure 10-31. Polarity Test, Voltage Transformer.
the time of the polar ity check
with either of the circuits shown
in Figures 10-27 or 10-28. In Figure 10-27, the voltage measured across H2 to X2 should be less than
the voltage across H1 to H2 by an amount equal to the H1 to H2 applied voltage divided by the marked
ratio. For example, if 120 V is applied to the primary H1 to H2 of a 2,400 to 120 V (20:1) transformer,
222
HANDBOOK FOR ELECTRICITY METERING
Standard Unknown
Figure 10-32. Polarity Test, Current Transformer. Figure 10-33. Polarity Test, Current Transformer.
then the H2 to X2 reading should be (120 2 120—— ), or 114 V. This method may be improved by using
20
two voltmeters so that the two voltages are read simultaneously.
In the circuit shown in Figure 10-28, the voltage will not be zero unless the unknown transformer
has the same ratio as the standard and this automatically verifies its ratio.
A third method that may be used is shown in Figure 10-33. The secondary voltages will be the
same if the ratios of the standard and the unknown are the same. If not, the ratio of the unknown is
equal to the ratio of the standard times the secondary voltage of the standard divided by the secondary
voltage of the unknown. Care must be used not to apply a primary voltage in excess of the rating of
either transformer.
The marked ratio of a voltage transformer may also be checked with a turn-ratio test set such as
the Biddle Model TTR.
Current Transformers
The marked ratio of a CT may be checked by measuring the primary and secondary currents directly
with ammeters. For large primary values, a standard current transformer must be used and the
secondary current of the standard is compared with the secondary current of the unknown CT when
their primaries are connected in series as shown in Figure 10-35. CAUTION: Do not open the CTs’
secondary circuits with primary current applied.
There are power system analyzers offered that will provide a reasonably accurate ratio check for
in-service CTs.
INSTRUMENT TRANSFORMERS
capacitors while comparative methods will require a standard instrument transformer of the same
nominal ratio whose exact ratio and phase angle have been previously determined.
Direct Methods
Direct methods are necessary for the determination of the ratio and phase angle of instrument trans-
formers in terms of the basic electrical standards. Such methods are used by the National Standards
Councils to calibrate their own standard instrument transformers which, in turn, are used to test
instrument transformer standards sent for certification.
Direct methods are simple in theory but involve so many practical difficulties that they are not
suitable for non-laboratory use.
Comparative Methods
When calibrated standard instrument transformers are available, the problems of testing instru-
ment transformers are greatly simplified since only a comparison of nearly equal secondary values is
involved.
Deflection Methods
Methods involving the use of indicating instruments connected to the secondary of the standard
and unknown transformers suffer from the accuracy limitations of the instruments used. Thus the
two-voltmeter or two-ammeter methods, Figures 10-34 and 10-35, are useful only as a rough check
of ratio. If two wattmeters are used, a rough check on phase angle may also be made, although this
involves considerable calculation after tests at 1.00 and 0.50 power factors. Accuracy may be some-
the test and compute the results. In addition, it imposes the small burden of a watthour standard
on the transformer under test which may not be desirable. Although this method requires extensive
calculations to determine ratio and phase angle correction factors to the degree of accuracy generally
required, it provides a rapid and convenient test method to determine whether transformers meet
established accuracy limits. In this case, readings are compared to tables of go and no-go limits with-
out extensive calculations. Some utility companies have adopted this method for testing the commonly
used 600 V class of transformers that are not involved in metering large blocks of power. Also, this
test confirms polarity and nominal ratio. See Figures 10-36 and 10-37.
Null Methods
Most modern methods of testing instrument transformers are null methods wherein the secondary
voltages or currents from the standard and the unknown (X) transformer are compared and their dif-
ferences balanced with suitable circuits to produce a zero or null reading on a detector. After balanc-
ing, the ratio and phase angle difference between the X-transformer and the standard transformer may
be read directly from the calibrated dials of the balancing equipment. With suitable equipment of this
type, tests for ratio and phase angle may be made rapidly and with a high degree of accuracy. Equip-
ment of this type is available commercially.
INSTRUMENT TRANSFORMERS
Figure 10-37. Current Transformer Test Circuit, Two-Watthour-Meter Method.
into the secondary of an in-service transformer, then measuring the admittance seen by that signal.
While any frequency between one and two kHz could be used, this tester uses 1580 Hz to reduce false
readings caused by harmonics of 60 Hz in the secondary.
Metering current transformers have very small errors, typically less than 0.3%, when operated
within their specified current and burden ratings. Therefore, the circuit admittance of a current
transformer is nearly constant throughout its normal operating range unless a fault develops. If
an admittance measurement shows deviation from normal while in service, it is likely the current
transformer has: (1) an internal short such as short-circuited turns; (2) an abnormal internal or
external resistance such as a high resistance joint; (3) the current transformer is being operated under
abnormal conditions, perhaps with a direct current (DC) component in the primary; or (4) the cur-
rent transformer has become magnetized. Most faults are immediately obvious because they produce a
high admittance reading, typically greater than 1.5 times a normal reading. Transformers with a wrong
ratio, such as those hooked to the wrong tap, will also have readings substantially different from
normal readings.
The best way to establish a normal admittance reading is to develop a history of measurements.
Admittance readings can be taken before installation, during initial field tests, and during subsequent
checks. Admittance values depend on fixed features such as core design, burden rating, and the turns
ratio. Changes to admittance which are caused by non-fault conditions are small when compared with
changes caused by fault conditions.
In-service CTs can be tested in groups and a high admittance reading by one transformer in the
group suggests a fault condition in that transformer. If all readings in the group are high the cause
could be a capacitive load on both sides of the current transformer, high system noise including
harmonics close to the test frequency, or the presence of DC in the primary.
226 TESTING CURRENT TRANSFORMERS FOR ABNORMAL BURDEN
The condition of a CT can be evaluated by measuring the burden of the transformer.
Current transformers are designed to supply a known current as dictated by the turns ratio into a
HANDBOOK FOR ELECTRICITY METERING
known burden, and to maintain a stated accuracy. The principle of a burden tester is to challenge the
capability of the CT to deliver a current into a known burden.
The total burden of the CT secondary loop includes the burden of the watthour meter current
coils, the mounting device, the test switch, connection resistances, and the loop wiring. When burden
is added which exceeds the design capacity of the CT, the transformer cannot supply the same level of
current to the increased burden, which results in a drop in the current transformer of loop current.
The tester shown in Figure 10-38
measures the burden of a current
transformer by adding a known
ohmic resistance in series with the
current transformer secondary loop
and comparing the total burden
including the known resistance with
the burden when the resistance is
not in the loop.
The magnitude of the current
change depends on several factors
and is not absolutely definable. The
operating level of current in the
CT secondary loop can be a signifi-
cant factor. Current transformers
operating at low currents are able
to support several times the burden
rating because at low currents the
flux density of the core is low, leav-
ing ample head room for additional
flux before saturation. Therefore,
to obtain accurate readings, these
burden tests are performed at full
rated secondary current. At the high
end of the current range, additional
burden quickly pushes the current
transformer out of its operating
range, resulting in significant drops
in operating current.
Form factor effects the burden
Figure 10-38. Instrument for Measuring Current Transformer capability of a current transformer.
Secondary Admittance and Burden. Transformers with high form factors
can support a burden greater than
the nameplate specifications. For
high form factor transformers, it is important to take measurements at full rated secondary current.
Other procedures for testing the burden of CTs are included in the IEEE C57.13 specification
Requirements for Instrument Transformers.
INSTRUMENT TRANSFORMERS
in the following diagram:
)
urrent (U
E)
nd ary C
(
Seco
nt
TUT
e
urr
C
b
or
a
Err
Ref. Std. Secondary Current (S)
“S” is the reference standard transformer secondary current and is measured directly. “U” is the
transformer under test (TUT) secondary current. “b” is the phase angle between the reference and
TUT secondary currents and is calculated. “E” is the error current of the TUT and is measured directly.
“a” is the angle between the reference standard secondary (“S”) and the error (“E”) and is measured
directly.
These quantities are related according to the following equations for RCF and b:
S S
RCF 5 — 5 —————————————————————
U [(E sin )2 1 (S 1 E cos a)2]1/2
E sin a
b 5 tan21 ——————————
(S 1 E cos )
————
sin b
1 ———— 2 1
cos b 2 1/2
E5
RCF RCF
sin b
5 sin21 ——‑‑‑‑‑‑——
E 3 RCF
The microprocessor-based comparator calculates RCF and b and then displays the results. The ANSI
accuracy class is also calculated and displayed.
Similar equations are used for the voltage comparator.
ary circuit. This resistance is then gradually reduced to zero and the current is reduced to zero. Avoid
opening the secondary circuit at any time during this procedure. A reactor in place of the resistor
reduces the possibility of re-magnetizing by accidentally open-circuiting during the procedure.
Today, equipment is available, such as the Transformer Analyzer shown in Figure 10-37, that not
only performs current transformer admittance and burden tests but also provides a safe and easy way
to demagnetize.
A current transformer can be magnetized by passing direct current through the windings, by surges
due to opening the primary under heavy load, or by accidental opening of the secondary with load
on the primary. Test circuits should provide for a gradual increase and decrease of primary current to
avoid surges.
Modern high-accuracy current transformers show relatively little change in accuracy due to
magnetization.
Ground Loops and Stray Ground Capacitance
In all instrument transformer testing, care must be taken to avoid ground loops and stray ground
capacitance that might cause errors. Usually only one primary and one secondary ground are used.
The location of these grounds must be carefully determined to avoid errors.
RCT
INSTRUMENT TRANSFORMERS
Ie
IXm IRm RB
X
Xm Rm EMF US B 5 arctan —B
RB
XB
P2 S2
Ie 5 Excitation Current
IS 5 Secondary Current
IP 5 Primary Current
Xm 5 Main Inductivity of the Core
Rm 5 Magnetic Losses of the Core
NP, NS 5 Amount of Turns of the Ideal Core
RCT 5 Ohmic Resistance of Secondary Turns
EMF 5 Electro-Motive Force — Secondary Core Voltage
US 5 Secondary Terminal Voltage
RB 5 Ohmic Part of Complex Burden
XB 5 Inductive Part of Complex Burden
B 5 Phase Angle of Burden
IS* RCT
Re
EMF Ie
US B IP
Is
Ie
Im
IRm
IXm
Figure 10-40. Vector Diagram for the Equivalent Circuit of the CT.
230 The benefit of this method is that these new CT testers only have to inject approximately 5A of
current and a known voltage into the secondary of the current transformer and measure the output
on the primary side of the CT. During the test, the CT tester measures the secondary resistance,
excitation curve, eddy and hysteresis losses, and the turn’s ratio (core ratio). Through its modeling
HANDBOOK FOR ELECTRICITY METERING
software, it calculates the current ratio error and phase displacement at desired burden and primary
current rating, a table of calculated data results are generated and charts, graphs, and selected param-
eters can be displayed, printed, or saved for analysis or reporting. All of this can be done automatically
without any operator intervention during test once initial setup is complete.
INSTRUMENT TRANSFORMERS
displacement can be calculated by factoring in the ohmic and inductive part of the complex burden
values to the original excitation data, where IB is the secondary current:
VCore 5 EMF 5 IB 3
(RCT
1 R
B)
2
X
1 B2
This shows how each selected primary and secondary burden can be evaluated from the excitation data
without having to add physical resistive and inductive burden components.
This method of applying low injection current into the secondary of the CT allows a safer environ-
ment and enables the unit to be made much smaller than the conventional primary injection systems
commonly used today, so its smaller size can be made portable and easily carried by field personnel to
travel to the location of the instrument transformers to perform field testing.
Accuracy
Accurate testing of instrument transformers requires adequate equipment and careful attention to
detail. Readability to 0.01% and 0.5 minute phase angle is easily possible with modern equipment,
but accuracy to this limit is much more difficult. For the greatest accuracy, the test equipment and
standard instrument transformers should be certified by the NIST or by a laboratory whose standard
accuracies are traceable to the NIST. With the greatest care, absolute accuracies in the order of 0.04%
and 1 to 3 minutes phase angle may be achieved.
applications. For example, a metering class current sensor can also measure fault currents in excess
of 50 kA and meet all protection accuracy requirements, creating the opportunity to share the output
of a single sensing system between metering and protection equipment and lowering total substation
costs.
Galvanic Isolation
As shown in Figure 10-41, an optical sensor typically has a sensing structure located at or near the
high voltage line. Optical fibers carry information about the measured voltage or current to ground
potential, through conduit, and into an secondary converter usually located in a control house.
There is no electrical connection between the high voltage equipment and the converter, resulting in
complete galvanic isolation between the high voltage line and the control room electronics. This factor
becomes increasingly important as measurement and control equipment for the power system becomes
more electronic. For these systems, the ability of optical sensors to disconnect the control room
electronics from the hazards presented by the power system in the form of voltage transients and open
secondaries is a major factor in increasing reliability and safety. A related benefit of galvanic isolation
is the lack of interaction between the sensor and the measured parameter. Issues such as ferro-
resonant conditions caused by the interaction of iron core devices and capacitance are non-existent
with optical designs. Likewise, electromagnetic interference effects such as crosstalk are reduced or
eliminated.
Wide Frequency Bandwidth
As power quality monitoring becomes increasingly important, the ability to accurately monitor har-
monic content up to the 100th harmonic is becoming more desirable. Available optical sensors with
signal bandwidths in excess of 5 kHz fulfill this requirement.
Unlike wound iron-core transformers, certain types of optical current sensors are also capable of
measuring DC currents, so they can be used for metering of DC inter-ties or for measuring other DC
or low-frequency currents such as geomagnetic-induced currents.
Accuracy Independent of Burden
The accuracy of optical sensors is less dependent or completely independent on burden and power fac-
tor. This makes calibration easier and simplifies the selection of secondary devices and wiring designs.
Small, Lightweight Form Factor
For most optical designs, the equipment is significantly smaller and lighter than could be achieved
with conventional wound iron-core insulation systems. The equipment requires less space in the
Current sensor
High voltage
insulator and
voltage sensor
INSTRUMENT TRANSFORMERS
of ownership. Figure 10-42
depicts an example of a retrofit
installation of optical current
sensors into a 72 kV genera-
tor substation. Figure 10-43
depicts an example of optical
voltage and current sensors
(combined units) installed in
a 362 kV sub-station. Figure
10-44 shows a 123 kV com-
bined unit and Figure 10-45
shows a flexible wraparound
fiber optical current sensor
retroactively installed around
a transformer bushing Optical
sensor elements, by virtue of
their small size and weight,
could be integrated into exist-
ing sub-station equipment such Figure 10-42. 72 kV Magneto-Optic Current Transducers at Sub-station.
as circuit breakers and switches.
Copper Wiring Cost Savings
The cost of copper has increased dramatically over the last decade, while the cost of optical cables
has dropped. With optical sensor systems, it is no longer necessary to run large amounts of copper
wire from the instrument transformers to the control house for the secondary connections. Instead, a
smaller number of fiber optic cables are used to connect the optical sensors to the secondary convert-
ers in the control room, which can result in significant cost savings.
current sensors, light remains within the fiber at all times, and the light makes
multiple trips around the conductor. There are several manufacturers of this
design, with a large number of equipment years of experience.
In the third class of sensors, known as hybrid optical current sensors and
Figure 10-44. 123 kV shown in Figure 10-46c, a conventional current transducer such as an iron
Optical Metering Unit core surrounds the conductor (an air-core Rogowski coil, resistive shunt, or
Prototype. other non-optical technology could also be used). For the case of an iron
core, a secondary coil on the core generates a current that is proportional to
the primary conductor current, in a manner identical to conventional current
transformers. The secondary current is locally digitized and subsequently transmitted in serial fashion
in an optical fiber that spans from the high voltage conductor to ground potential. Since electron-
ics are present at the high voltage conductor, electrical power must be supplied to the sensor head.
Commercial devices use a high power (.100 mW) infrared laser diode coupled into an optical fiber
to carry optical power from ground potential to the sensor head. Efficient gallium arsenide (GaAs)
photocells convert the received optical power into electrical power to energize the electronics in the
sensor head. The hybrid approach has been implemented for capacitor bank protection applications
with many equipment years of experience.
The exterior appearances of all three classes of current sensors are almost identical. A lightweight
(,100 pounds) sensor pod is located at the high voltage conductor, and one or more optical fibers are
brought from high voltage to ground using some form of post insulator, suspension insulator, or shed-
ded cable. In all three cases, an electronics chassis, usually located in the control house, supports the
generation and detection of the optical signals affiliated with one or more three-phase sets of sensors.
The current sensor interface chassis can have several output signals, including:
1. Low-voltage analog output representation of the primary current
2. Ampere-level current output representation of the primary current
3. International Electrotechnical Commission (IEC) 61850-9-2 digital output
The low voltage analog output can have various ratios, but many applications typically use a
2 Vrms or 4 Vrms output to represent nominal primary current. For example, an optical sensor with a
235
Optics
Block of glass
INSTRUMENT TRANSFORMERS
Light input
Transducer
PLD Optical Fibre
Filter DOIT
circuit
I1 I2
HV link
Interface Unit
Detecter
WDM
Decoder
coupler
Laser
(c) Hybrid
marked ratio of 2400A:2V would generate a 2 Vrms output voltage when 2400 Arms are carried in the
primary conductor.
The current output uses a transconductance amplifier to generate an output current. The output
current is usually specified in a manner identical to that found for conventional current transformers,
and both 1 amp and 5 amp nominal secondary currents are available. For example, an optical current
sensor with a marked ratio of 2400:1 provides an output current of 1 Arms when 2,400 Arms are
flowing through the primary conductor. Since the compliance voltage of the amplifier can be limited
through careful design, safety concerns surrounding open secondary windings of current transformers
can be completely eliminated.
Optical sensor manufacturers can provide multiple outputs with different ratios using one sensor.
For example, a single optical current sensor at high voltage can provide a low voltage analog output
of 2400A:2V for monitoring applications, a low voltage analog output of 2400A:0.2V for relaying or
protection applications, and a current output of 2400:1 for metering applications. Some manufactur-
ers can provide two current outputs (2400:1 and 100:1) for metering applications.
Also, most manufacturers allow the output ratio of the current sensor to be changed, meaning if
the load of the system changes over time and a different nominal current is required, the same current
sensor can be used (assuming its dynamic range and accuracy meets the new system requirements).
The IEC 61850-9-2 output utilizes a digital protocol where data is sampled at 80 samples per cycle
and multicast over a copper or fiber Ethernet network. Real values are transmitted as opposed to scaled
values, so there is less programming required in the meters or IED.
236 Sensing Mechanism In Optical Current Sensors
The bulk optic and all-fiber current sensors exploit the Faraday Effect and Ampere’s Law to provide
precision measurements of current. From basic electromagnetic theory, Ampere’s Law states that
HANDBOOK FOR ELECTRICITY METERING
→ →
i 5 H • dl
where i is the current enclosed by the loop integral and H is the magnetic field present in the region
of integration. Note that the path of integration does not matter, provided that it makes one or more
complete closed loops around the primary conductor. The magnetic field is generated by electrical
currents in the vicinity of the sensor. However, the integral is precisely equal to only the currents
enclosed by the integration path.
The Faraday Effect describes a change in the refractive index of a material when exposed to a
magnetic field. The change in refractive index causes the speed of light to be effected in the material.
This variation can be detected using either polarimetric or interferometric methods. With the polari-
metric approach shown in Figure 10-47, the Faraday Effect changes the polarization state of an optical
beam in proportion to the magnetic field parallel to the optical beam path. The total rotation of the
plane of polarization for linearly polarized light when the optical path encircles a conductor carrying
current I is 5 VNi, where N is the number of round trips traveled by the optical beam around the
encircled conductor, V is the Verdet constant of the material, and is the magnetic perme ability of
the material. The change in polarization is detected using a linear polarizer, resulting in a signal that
varies with the current.
With the interferometric approach, light traveling through the sensing material having one refrac-
tive index is interfered with another optical signal that experiences a different refractive index. In
Figure 10-48, the two optical signals have orthogonal polarization states as they make one round trip
through the fiber. When they interfere in the fiber polarizer, the optical phase shift between the two
interfering waves generates an intensity variation at the detector. The detected signal varies with the
strength of the applied magnetic field in the sensing fiber. By encircling the conductor with the optical
path, an output signal is created that varies with the strength of the current in the encircled conduc-
tor. Another benefit of the interferometric approach is that is allows the current sensor to accurately
measure DC current.
The optical path in the sensor material must follow a closed path about the conductor without
introducing unwanted linear optical birefringence (a variation in the refractive index of a material
Optical detector
Polarizer
Magnetic field
Sensing material
Intensity
Incident
polarized light
0 Magnetic field
INSTRUMENT TRANSFORMERS
linear polarizer and enters the main sensor block. At each corner of the sensor block a pair of mirrors
deflect the beam 90°. The complementary mirror pair is required to maintain the polarization state
of the light at each right angle bend in the sensor. After making a single round trip in the glass, the
beam is passed through a second polarizer and focused by a parabolic reflector or lens onto a receiving
optical fiber. A large hole in the middle of the block permits the passage of the conductor through the
optical loop formed in the sensor material. Precision machining of the block is required to maintain
accurate alignment between the two multimode fibers.
The all-fiber sensor uses the fiber itself as the Faraday material. Single mode fiber is used, and
strain-induced optical birefringence must be minimized or overwhelmed by other birefringence in
order to construct a useful sensor. This is accomplished by using finely annealed single mode fiber or
a deliberately twisted or spun single mode fiber. In all cases, the fiber must be carefully mounted in
strain-relieving packaging to avoid temperature or vibration effects. With this approach, incident light
can make many complete loops around the primary conductor, increasing the signal intensity at the
receiver electronics. The modulated light can be reflected from the end of the fiber, recombined with
the incident light in a coupler, or carried by a separate fiber. The fiber loop diameter can be adjusted to
match the application requirements. The ability to create multiple optical loops around the conductor
is important since the signal levels generated by useful Faraday materials are very small.
Fiber polarizer
50:50
LED coupler
PZT: Db
modulator
PD
SM fiber Current-carrying
sensing coil conductor
Lock-in
amplifier
Sensors
Sensor HV
Capacitor
Sensor
Figure 10-49. Schematic Diagrams of Three Different Optical Voltage Sensor Techniques.
rod. Light from an optical fiber travels inside the short crystalline rod and is subsequently collected by
a second optical fiber. A gas dielectric such as sulfur hexafluoride provides insulation around the two
rods. The glass rod and the crystalline rod form a capacitive divider to reduce the primary high volt-
age to a value that can be measured optically using the short crystalline rod. The two rods are placed
within a metallic pressure vessel to control the electric field distributions in the rods and contain the
high-pressure dielectric insulation gas. One manufacturer offers this type of voltage sensor. A small
number of equipment years have been accumulated using this approach.
In the third class, the distributed optical voltage sensor shown in Figure 10-49c, several optical
point sensors are placed between high voltage and ground in a shedded high voltage insulator. Optical
fibers carry light to and from the optical sensors. The vertical component of the electric field is mea-
sured at these points and the measurements are combined to estimate the potential difference between
high voltage and ground. A gas dielectric such as nitrogen provides insulation around the sensors. One
manufacturer offers this type of voltage sensor.
The exterior appearances of all three classes of voltage sensors are similar. A hollow insulating
column is located between the high voltage line and ground. The bottom of the column connects to
a metallic enclosure. For the electro-optic voltage sensor, the optical sensor is placed inside the center
of the insulator, and high voltage and ground electrodes are brought to the sensor from the ends of
the column. The metallic enclosure at the base provides a means of containing and protecting the
optical fiber connections and any monitoring equipment desired (typically a gas density alarm). The
capacitive divider optical sensor is mounted in a metallic housing located at the base of the insulator.
The distributed optical voltage sensor has optical sensors located along the inside of the column. The
metallic enclosure at the base provides a means of containing and protecting the optical fiber connec-
tions and any monitoring equipment desired. In the first two cases, the column is pressurized with
sulfur hexafluoride gas to ensure dielectric integrity. In the third case, the column is pressurized with
dry nitrogen to preserve accuracy.
In all three cases, an electronics chassis, usually located in the control house, supports the genera-
tion and detection of the optical signals affiliated with one or more three-phase sets of sensors.
The output of the voltage sensor interface chassis can have several output signals, including:
1. Low-voltage, low-burden analog output representation of the primary voltage
2. Higher-voltage, higher-burden analog output representation of the primary voltage
3. IEC 61850-9-2 digital output
The low-voltage analog output can have various ratios, but metering applications typically use a
4 Vrms output to represent nominal primary voltage. For example, an optical sensor with a marked
ratio of 16,600:1 generates a 4 Vrms output voltage when the primary conductor is at 66,400 Vrms
line to ground.
The higher-voltage output uses a voltage amplifier to generate an output voltage of 69 Vrms or
120 Vrms at rated primary voltage, with a burden capability of 10 VA 2 100 VA. The output voltage is
usually specified in a manner identical to that found for conventional voltage transformers, although
the output burdens are typically ,100 VA instead of the more common .100 VA burdens found 239
with conventional voltage transformers. For example, an optical voltage sensor with a marked ratio of
1000:1 provides an output voltage of 69 Vrms when the primary conductor is at 69,000 Vrms.
Optical sensor manufacturers can provide multiple outputs with different ratios using one sensing
INSTRUMENT TRANSFORMERS
column. For example, a single optical voltage sensor for use on a 115 kV three phase power line can
provide a low voltage analog output of 16,600:1 for monitoring, relaying, or protection applications,
and a higher voltage output with a ratio of 2900:1 for metering applications.
The IEC 61850-9-2 output utilizes a digital protocol where data is sampled at 80 samples per cycle
and multicast over a copper or fiber Ethernet network. Real values are transmitted as opposed to scaled
values, so there is less programming in the meters or intelligent electronic devices (IEDs), leading to
fewer mistakes.
C1
Vb–a 5 Vprimary ——————
C1 1 C 2
where C1 is the high voltage capacitor (,50 pF), C2 is the much larger low voltage capacitor, and C2
is assumed to be much larger than the capacitance of the Pockels cell. If the capacitors C1 and C2 are
stable and the electric field distribution in the region of the two capacitors is stable, then the resulting
optical signal is proportional to the primary high voltage. Normally the capacitive divider is located
in a grounded, metallic vessel to control the field distributions at the divider and provide dielectric
insulation using pressurized sulfur hexafluoride gas.
240 The distributed voltage sensor uses multiple Pockels cells to measure the electric field at different
locations along the high voltage insulator. Each Pockels cell measures a voltage drop that depends on
the electric field strength in the local region of the cell, the dielectric properties of the materials from
which the cell is fabricated, as well as the shape of the cell. This design is very sensitive to the shape
HANDBOOK FOR ELECTRICITY METERING
of the electric field distribution between high voltage and ground. Selecting the locations of the cells
and adding field-shaping resistors reduce the system’s sensitivity to the field distribution. With signal
processing to combine the sensor signals, a representation of the primary voltage is created.
INSTRUMENT TRANSFORMERS
tion in Northern Maine or Canada may have a primary current of 20 amps, an ambient temperature
of 250°C, and a wind velocity of 30 miles per hour (mph). Following this temperature cycle, the
electronics chassis can be temperature cycled while the sensor head is kept at a fixed temperature.
Typically, an industrial temperature range of 240°C to 170°C is used for this temperature cycle.
Compensation must be verified on every system and documented in the routine test report provided by
the manufacturer.
erroneous apparent power and active power readings will result. Depending on the algorithm used to
determine power factor, erroneous power factor readings may also result.
Some electronic meters calculate power quantities by multiplying the instantaneous voltage and
current and averaging over time, and separately calculate the voltage and current rms values. These
meters can provide correct power readings, but display erroneous voltage and current values, depend-
ing on the noise present on the voltage and current waveforms. This can lead to very confusing
situations.
The proposed standard IEEE 1459-2000 provides a way to describe the effect of noise on the
reported power flows measured by a meter that calculates rms values of voltage and current before
multiplying these values to calculate apparent power. Although specifically fashioned to quantify
harmonic and non-harmonic power flows on the power system, it is directly applicable to the case
at hand. The voltage and current waveforms have rms values V and I, with total harmonic distortion
levels defined by THDV 5 VH/V1 and THDI 5 IH/I1, where V1 and I1 are the fundamental (60 Hz)
voltage and current rms values, and VH and IH are the non-fundamental voltage and current rms
values, including all integer and non-integer harmonics (i.e., noise). The apparent power that results
(a single-phase analysis is used for simplicity) is
S2 5 (VI)2 5 S12 1 S12 5 S12 1 D12 1 DV2 1 SH2
where S is the total apparent power, S1 is the fundamental (60 Hz) apparent power, DI is the current
distortion power, DV is the voltage distortion power, SH 5 S1 (THDV)(THDI) is the harmonic apparent
power and SN is the non-fundamental apparent power. The distortion powers are given by DV 5 S1
THDV and DI 5 S1 THDI. For distortion-free current and voltage waveforms, DV 5 DI 5 SH 5 0 and the
apparent power S 5 S1, as expected.
When noise generated by the sensor is included but limited to THDV ,5% and THDI ,200%, then
the total apparent power S can be approximated by
S2 S12 [1 1 (THDV)2 1 (THDI)2]
Similarly, for THDV ,5%, THDI ,40%, and assuming that current waveform distortions dominate
over other sources of distortion, the power factor PF can be approximated by
PF1
PF ———————————
1 1 D
(TH
I)
2
INSTRUMENT TRANSFORMERS
200 kVrms primary voltage with no additional noise. Here, THDI 5 1/1 5 100% and
THDV 5 0%.
The reported apparent power will be 282 kVA, as compared with the true apparent power of
200 kVA.
As can be seen by these three examples, depending on the algorithm used in the meter, even very
high performance optical sensors may create metering errors. Since new electronic meter designs,
algorithms, and features are constantly being introduced, the best course of action for an optical
system user is to request the optical sensor system manufacturer to furnish type test results when the
optical sensor is operating with the user’s meter of choice. The tests should be conducted over the
full range of metered currents. If harmonic content is needed for power quality measurements, then
type test results for harmonic content should also be requested. Often, only the optical current sensor
needs to be verified with a particular meter, since optical voltage sensors have very small noise contri-
butions at rated primary voltage and metering usually does not occur when the primary voltage differs
appreciably (.20%) from nominal values. Alternatively, if resources are available, these type tests can
be performed at the user’s meter testing facilities.
INSTRUMENT TRANSFORMERS
Although usually considered a mundane component of a measurement system, the fiber optic cabling
between the sensor head and the interface electronics is crucial to long term reliability of an optical
sensor system. Cabling usually involves the fiber optic run between the control house and the location
in the substation where the optical sensor is installed, the fiber run up to the sensor elements, and
the connectors or splicing techniques used to connect the cable into the sensor head and the interface
electronics. Manufacturers usually supply the optical cable as part of the total system.
The telecommunications industry has provided very strict standards (known as Bellcore standards)
that, if followed, will ensure trouble-free fiber cable service. Some of the issues involved with fiber
cabling include:
1. Over long-term exposure to water and under tension, an optical fiber develops surface micro-
cracks that eventually cleave the fiber. Manufacturers usually recommend a fiber cable that can
be directly buried. This applies even when running fiber cable in conduit, as conduit cannot be
made waterproof.
2. A Kevlar®-armored fiber cable that is crush resistant and rodent proof is preferable for direct
bury applications.
3. Some commercial offerings include fiber cable cut to a user-specified length with the cable
pre-terminated with connectors. The connectors are protected by pulling sleeves. While being
handled, the ends of the fiber cable are extremely fragile. Training of installation personnel is
usually advisable to avoid costly time delays due to accidents (e.g., fiber cables can be pulled
through conduit much more easily if the connectors are snipped off first).
4. Some companies recommend splicing all outdoor fiber connections to avoid issues with con-
tamination over the life of the installation.
5. If the cable must be installed above ground, a metal conduit is highly preferred to provide
ultraviolet light shielding.
6. Fiber optic connectors must be kept meticulously clean. Cleaning kits are available from many
fiber optic supplies stores and are highly recommended.
7. Ports into which fiber connectors are inserted must be kept meticulously clean. If contaminated,
they are very difficult to clean without disassembling the equipment. To avoid this, a metal
conduit is recommended.
8. Optical sensor manufacturers use several different fiber sizes. In general, standard singlemode
fiber is the least expensive, followed by multimode fiber and polarization maintaining single
mode fiber. Multimode fiber is much more tolerant to mechanical misalignments than single
mode fiber.
9. Some manufacturers supply fiber that cannot be fusion spliced. For this type of fiber, one
manufacturer uses mechanical splices for field repairs.
Chapter 11
The Watthour Meter
A wattmeter and a watthour meter have roughly the same relationship to each other as do the
speedometer and the odometer of an automobile. A speedometer indicates miles per hour and an
odometer shows the total number of miles traveled. Similarly, a wattmeter indicates the instantaneous
consumption of watts and a watthour meter measures the total watthours that have been used. For
example, a watthour meter will indicate 1,000 watthours if connected for two hours in a circuit using
500 watts. Consumer loads may be constantly changing, so, to accurately measure watthours, it is
necessary to have a meter that will accumulate the instantaneous watts over time. Monthly energy
consumed is determined by subtracting the watthour reading at the end of the previous billing period
from the reading at the end of the current billing period. In the United States, meters are read on a
monthly basis at a minimum through an Automated Meter Reading (AMR) or Advanced Metering
Infrastructure (AMI) system and a monthly bill produced. At the time of installation, a new meter
starts with a register read of zero. Likewise, a previously used meter can be reset to zero, and at the
time of installation the installation form records the install read as zero. The meter continues to
increase in kilowatt hours (kWh) registered over time, and, once the maximum register read is accu-
mulated, the meter will roll over and return to all zeroes. This is determined by the number of digits
within the register of the meter. For example, a register with five digits would record to 99,999 kWh
and then roll over to zero.
247
248 The Two-Wire Single-Phase Meter
The two-wire meter is the simplest watthour meter and forms the basis for all other meters. The
service this meter is used to measure has one voltage which supplies the load and one current being
Handbook for Electricity Metering
used by the load. As such, the meter has one voltage sensor and one current sensor. Since the voltage
and current are changing with load conditions in real time, the voltage and current must be measured
in real time. Regardless of direct current (DC), alternating current (AC), or distorted waveforms, at
each instant in time the following equation is true:
Wattsi 5 Vi 3 Ii
If all of these instances watts are collected over time and watthours are computed. The equation for
this is:
i5T
Watthours 5 V 3I
i50
i i
The real quantities in the electrical system are current, voltage, and (real) power, and can be
defined for each instance in time. Most other quantities reflect some average effect or are a math-
ematical convenience to more easily understand what is happening on a macro scale. For example,
it is common to speak of meters in terms of root-mean-square (rms) voltages, rms currents, and
phase angles between these. However, in a real electrical system, the waveforms may be distorted
and dynamically changing as loads are switched in and out of the service. At one extreme, consider
an electricity meter on an oil pump. During the up stroke of the pump, significant power is drawn
from the service, and, during the down stroke, the pump motor turns into a generator. In between,
there are significant current distortions. If a revenue meter attempted to compute watts from the rms
voltage, rms current, and phase angle between these, the meter would not be very accurate. Therefore,
revenue meters measure watts in real-time and accumulate their effect to produce watthours. This
can be accomplished with magnetic fluxes within an electromechanical meter disk or with electronic
components.
Blondel’s Theorem
The theory of polyphase watthour metering was first set forth on a scientific basis in 1893 by engineer
and mathematician Andre E. Blondel. Blondel’s Theorem applies to the measurement of real power in
a polyphase system of any number of wires. The theorem is as follows:
If energy is supplied to any system of conductors through N wires, the total power in the system is given
by the algebraic sum of the readings of N wattmeters, so arranged that each of the N wires contains
one current coil, the corresponding voltage coil being connected between that wire and some common
point. If this common point is on one of the N wires, the measurement may be made by the use of N-1
wattmeters.
The receiving and generating circuits may be arranged in any desired manner and there are no restric-
tions as to balance among the voltages, currents, or power-factor values.
From this theorem it follows that a meter containing two elements or stators is necessary for a
three-wire, two- or three-phase circuit, and a meter with three stators for a four-wire, three-phase
circuit. Some deviations from this rule are commercially possible, but resultant metering accuracy,
which may be decreased, is dependent upon circuit conditions that are not under the control of the
meter technician. An example of such a deviation is the three-wire, single-stator meter.
The circuit shown in Figure 11-1 may be used to prove Blondel’s Theorem. Three watthour meters,
or wattmeters, have their voltage sensors connected to a common point D, which may differ in voltage
from the neutral point N of the load, by an amount equal to EN. The true instantaneous load power is:
WattsLoad 5 EAIA 1 EBIB 1 ECIC
Inspection of the circuit shows:
EA 5 E9A 1 EN
EB 5 E9B 1 EN
EC 5 E9C 1 EN
Substituting in the equation for total load power:
WattsLoad 5 (E9A 1 EN)IA 1 (E9B 1 EN)IB 1 (E9C 1 EN)IC
WattsLoad 5 E9AIA 1 E9BIB 1 E9CIC 1 EN(IA 1 IB 1 IC)
From Kirchhoff’s Law, IA 1 IB 1 IC 5 0, the last term in the preceding equation becomes zero, leaving
WattsLoad 5 E9AIA 1 E9BIB 1 E9CIC 5 W1 1 W2 1 W3
Thus, the three watthour meters correctly measure the true load power. If, instead of connecting the
three voltage coils at a common point removed from the supply system, the common point is placed
250
Handbook for Electricity Metering
on any one line, the voltage becomes zero on the meter connected in that line. If, for example, the
common point is on line C, E9C becomes zero and the preceding formula simplifies to:
WattsLoad 5 E9AIA 1 E9BIB 5 W1 1 W2
proving that one less metering unit than the number of lines will provide correct metering regardless
of load conditions.
The operations indicated in these equations have been performed in the phasor diagrams to obtain
I1A and I3C. Examination of the phasor diagram shows that for balanced loads the magnitude of the
line currents is equal to the magnitude of the phase currents times the 3.
The top element (stator) in Figure 11-3 has voltage EAB impressed and carries current I1A. These
two quantities have been circled in the phasor diagram and inspection of the diagram shows that for
the general case the angle between them is equal to 30° 1 . Therefore, the power measured by the
top element (stator) is EABI1Acos(30° 1 ) for any balanced-load power factor. Similarly, the bottom
element (stator) uses voltage ECB and current I3C. These phasors have also been circled on the diagram
and in this case the angle between them is 30° 2 . The bottom element (stator) power is then
ECBI3Ccos(30° 2 ) for balanced loads. The sum of these two expressions is the total metered power.
Total Meter Power = EABI1Acos(30° ) ECBI3Ccos(30° ) 253
Examination of the two expressions for power shows that even with a unity power factor load, the
meter currents are not in phase with their respective voltages. With a balanced unity power factor load
Since I1A 5
3 IPhase
Top Element 5 240 3
3 3 15 3 cos(30° 1 0°)
5 240 3
3 3 15 3 0.866 5 5,400 watts
Bottom Element 5 ECBI3Ccos(30° 2 °)
Since I3C 5
3 IPhase
Bottom Element 5 240 3
3 3 15 3 cos(30° 2 0°)
5 240 3
3 3 15 3 0.866 5 5,400 watts
Total Meter Power 5 Top Element 1 Bottom Element 5 5,400 1 5,400
5 10,800 watts 5 Total Load Power
When the balanced load power factor lags, the phase angles in the meter vary in accordance with
the 30° 6 expressions. When the load power factor reaches 50%, the magnitude of is 60°. The top
stator phase angle becomes 30° 1 5 90° and, since the cosine of 90° is zero, the torque from this
stator becomes zero at this load power factor. To illustrate, assume the same load current and voltage
used in the preceding example with 50% load power factor.
Total Load Power 5 3 3 240 3 15 3 0.5 5 5,400 watts
Top Element 5 240 3
3 3 15 3 cos(30° 1 60°)
5 240 3
3 3 15 3 0 5 0 watts
Bottom Element 5 240 3
3 3 15 3 cos(30° 2 60°)
5 240 3
3 3 15 3 0.866 5 5,400 watts
Total Meter Power 5 0 1 5,400 5 5,400 watts 5 Total Load Power
With lagging load power factors below 50%, the top element power reverses direction and the
resultant action of the two elements (stators) becomes a differential one, such that the power direc-
tion is that of the stronger element (stator). Since the bottom element (stator) power is always larger
than that of the top element (stator), the meter power is always in the forward direction, but with
proportionately lower power at power factors under 50%. Actually, on a balanced load the two ele-
ments (stators) operate over the following ranges of power factor angles when the system power factor
varies from unity to zero: the leading element (stator) from 30° lead to 60° lag, the lagging element
(stator) from 30° lag to 120° lag.
The expression for total meter power can be written as follows by inspection of the phasor
diagram:
Total Meter Power 5 EANIANcos 1 1 EBNIBNcos 2 1 ECNICNcos 3
which is the total power developed by the load.
If the loads are connected line-to-line, instead of line-to-neutral, the total load power will still
be the same as the total meter power, because it can be proven that any delta-connected load may be
replaced by an equivalent wye-connected load. Hence, there are no metering errors with imbalanced
load voltages of varying load currents or power factors.
Two-Element (Two-Stator), Three-Current Sensor Meter
For years, metering personnel have struggled with the cost of metering. Trade-offs can be made among
the accuracy of the metering, the assumptions about the service voltages and currents, and the cost of
the meter or the number of instrument transformers required. The two-element (two-stator), three-
current sensor meter is an example of a trade-off that many metering engineers have found accept-
able. This meter employs two elements (stators) with two voltage sensors and three current sensors. 255
Historically, an electromechanical meter of this type was less expensive than one with three voltage
sensors. In addition, in a service requiring external voltage instrument transformers, two voltage
transformers could be used instead of three. This could represent a significant equipment cost savings.
As an example, with a balanced line-to-neutral load from each of 15 amperes at 120 volts with a
lagging power factor of 86.6% the true load power is:
True Power 5 3 EPhaseIPhasecos [] 5 3 3 120 3 15 3 0.866 5 4676.4 watts
For 86.6% power factor the phase angle is 30°.
Metered Power 5 120 3 15 3 0.866 1 120 3 15 3 0.866 1 120 3 15 3
cos(60° 1 30°) 1 120 3 15cos(60° 2 30°)
5 2 3 120 3 15 3 0.866 1 120 3 15cos90° 1 120 3 15cos30°
5 2 3 120 3 15 3 0.866 1 120 3 15 3 0 1 120 3 15 3 0.866
5 3 3 120 3 15 3 0.866
5 4676.4 watts
A similar proof of correct metering may be developed for a polyphase power load connected to lines A,
B, and C.
A 2½-element (2½-stator) meter is in error when the voltages are not balanced in magnitude or
phase position. With imbalanced voltages, the amounts of any current imbalance and power-factor
values also have a bearing on the amount of metering error as well as where the voltage imbalance
occurs relative to the connection of the Z coil. The curves of Figure 11-6 are drawn for an assumed
equal voltage and current imbalance in one load phase and for the three possible locations of the
Z coil. Using the curves for an assumed voltage and current imbalance of 2% in Phase 1, the following
tabulation shows the variations in metering errors as the Z coil is moved.
However, if the voltages remain balanced, the 2½-element (2½-stator) meter will meter correctly
with current and power factor imbalance.
While this method of metering does not follow Blondel’s Theorem and is less accurate than
a three-element meter in cases of imbalanced voltages, many users find it acceptable for energy
measurement.
Since this service can be more accurately metered with a wide-voltage-range, electronic, three-
element meter, today’s electronic meter manufacturers do not offer this type of meter.
Two-Element (Two-Stator) Meter Used with
Three Current Transformers or Two Window Current Transformers
This method of metering a four-wire wye service uses a conventional two-element (two-stator), two-
current sensor meter with three-current transformers in the circuit. The circuit connections are shown
in Figure 11-7.
The component currents in each current sensor are indicated by the arrows on the circuit diagram.
In both elements (stators), the third line transformer current, I2B, is in opposition to the other line
transformer current. The phasor diagram shows how these components add to produce the total cur-
rent in each current sensor, IX and IY.
Before the component currents are added, the phasor diagram for this connection is similar to
that shown in Figure 11-5 for the 2½-element meter, showing that this method is electrically equiva-
lent to the 2½-element meter. The difference is that the third line current flows through an external
transformer and its current is combined in the meter’s two-current sensors rather than processing the
third line current in the meter directly.
An alternate to this approach is to use two current transformers with window openings through
the transformer cores. The window current transformers allow the line currents to be combined in
these external transformers rather than in the meter current sensors. In this approach, one service line
passes through one current transformer window and the second service line passes through the second
current transformer window. The third service line passes through each of the current transformer
windows in the opposite direction from the first two service lines.
These methods have the same accuracy limitations and errors as the 2½-element meter.
257
The phasor diagram of Figure 11-8 is drawn for a combined power and lighting load. To simplify
the diagram, the current phasors for the individual loads are not shown. Since this method follows
Blondel’s Theorem, it provides correct metering under any condition of voltage or load imbalance.
The advantages of using a three-element (three-stator) meter for this application are correct
registration under all conditions of voltage and increased meter capacity in lighting phases, an impor-
tant advantage when the load in these phases greatly exceeds that in the power phase. A disadvantage
of this metering is that to verify a meter’s accuracy in this service, polyphase test stations that can
apply different voltages to different elements are required. These were not readily available in the past,
and still may not be the common test station within today’s meter shop. Additionally, electromechani-
cal meters for this metering are difficult to produce. However, with today’s three-element electronic
meters and polyphase test stations, there really are no disadvantages to providing three-element elec-
tronic meters for this service. Most wide-voltage-range, three-element, electronic meter designs can be
qualified to work on this service using a polyphase test station, and then individual meter calibration
can be verified with 120 volts applied to all elements with no concern that the meter will not perform
accurately when the third element is powered at 208 volts.
260 TWO-ELEMENT (TWO-STATOR), THREE-CURRENT SENSOR METER
It is possible, as with the four-wire wye service, to meter a four-wire delta service with a two-element
(two-stator), three current sensor meter. This is shown in Figure 11-9. It is a compromise with
Handbook for Electricity Metering
Blondel’s Theorem which allows possible metering errors. Since this service can be more accurately
metered with a wide-voltage-range, electronic, three-element meter, today’s electronic meter manufac-
turers do not offer this type of meter.
(a)
(b)
(C)
third-harmonic current flow, thereby keeping the third-harmonic voltages at low values. If this path
were not present, the transformer voltages would be highly distorted by the excessive third-harmonic
voltages, potentially causing metering errors. Also, serious hazards to voltage transformer insulation
exist because of large increases in exciting current due to harmonic voltages. The four-wire wye circuit
may also be derived from a wye-wye distribution bank, wye auto-transformer, wye grounding bank, or
zig-zag transformer connections.
The circuit of Figure 11-10b is a delta-wye transformer bank with a three-wire secondary without
ground. If it is known that there is no possibility of an actual or unintended phantom ground in the
secondary circuit, it may be metered (as in any three-wire circuit) by a two-stator meter. Two voltage
transformers would be connected as shown using one of the lines for the common connection.
The three-wire wye secondary circuit with neutral grounded as shown in Figure 11-10c presents
a major metering problem. Since the secondary circuit is three-wire, it is possible to use a two-stator
meter. However, it is possible that this may not yield correct metering, since loads may be connected
from the unmetered line to ground and thereby fail to be metered. Also, loads connected from
metered lines to ground will not be measured correctly. For correct metering under all load conditions,
a three-stator meter or equivalent must be used. In this case, three voltage transformers connected
wye-wye would be used as shown. To limit third-harmonic effects, the neutral of the voltage trans-
formers must be connected to the neutral of the distribution bank by a low-impedance connection.
If the meter is located at the same substation as the distribution bank, a ground connection to the
station grounding grid may be sufficient or the two neutrals may be directly connected. If the metering
location is at a considerable distance from the distribution bank, it may not be possible to establish
a firm common ground. When the metering transformer neutral is left floating, the harmonic prob-
lem is again very serious. Harmonic voltages as large as 30% have been found in some instances. If
the voltage transformer neutral is grounded at the metering location to an isolated ground, other
problems exist. Differences in ground voltage under certain conditions can cause extremely hazardous
conditions at the meter and a high-resistance ground may not eliminate the harmonic errors. Because
of these conditions, many companies require that a neutral conductor be run between the distribution
and instrument voltage transformers.
Many other problems can arise in wye-circuit metering and the presence of harmonics and their
potential effects on the metering should always be considered. In metering transmission and distribu-
tion circuits, a thorough understanding of circuit connections is necessary. For example, the three-wire
wye connection with neutral ground is frequently encountered. With voltages in the order of 24,000
volts the designer is reasonably certain that customer loads will not be connected line-to-ground and
two-stator metering will be correct. However, this may not always be the case.
Electromechanical Metering
The electromechanical watthour meter consists of a motor whose torque is proportional to the active
power flowing through it, a magnetic brake to retard the speed of the motor in such a way that it is
proportional to power (by making the braking effect proportional to the speed of the rotor), and a
register that converts the number of revolutions of the motor through the gearing of the register and
displays these revolutions as kilowatthours (Figure 11-11). If the speed of the motor is proportional to
the power, the number of revolutions will be proportional to the energy.
The portion of the stator energized by the load current is known as the current coil and serves
the function of current sensor. For a Class 200 meter, the current coil usually consists of two or four
turns of wire equivalent to approximately 30,000 circular mils in size. The current coils are wound in
reverse directions on the two current poles for correct meter operation.
In 1884 Dr. Galileo Ferraris proved that torque could be produced electromagnetically by two
alternating-current fluxes which have a time displacement and a space displacement in the direc-
tion of proposed motion. The voltage coil is highly inductive, so the current through the voltage coil
(and hence the flux from it) lags almost 90° behind the line voltage. In modern meters, this angle is
between 80° and 85°. Although the current
coil has very few turns, it is wound on iron
and is therefore inductive. However, it is not
as inductive as the voltage coil. The power
factor of a modern meter current coil may be
0.5 to 0.7 or an angle of lag between 60° and
45°. The meter current coils have negligible
effect on the phase angle of the current
flowing through them as the current coil
impedance is extremely small in comparison
to the load impedance, which is connected in
series. The load voltage and load impedance
determine the phase position of the current
through the meter. With a unity-power-factor
load, the meter current will be in phase with
the meter voltage. Since current through the
voltage coil lags behind current through the
current coil, flux from the voltage coil reaches
the rotor after flux from the current coil and
a time displacement of fluxes exists. The sta-
tor is designed so that the current and voltage
windings supply fluxes that are displaced in
space. These two features combine to give the
time and space displacement that Dr. Ferraris
showed could be used to produce torque. Figure 11-12. Basic Electromagnet (for Two-Wire Meter).
264
Handbook for Electricity Metering
In order to understand why torque is produced, certain fundamental laws must be remembered.
They are:
1. A magnetic field exists around a current-carrying conductor.
2. Like magnetic poles repel each other and unlike poles attract each other.
3. An electromotive force (EMF) is induced in a conductor by electromagnetic action. This EMF is
proportional to the rate at which the conductor cuts magnetic lines of force. The induced EMF
lags 90° behind the flux that produces it.
4. If a conducting material lies in an alternating-current magnetic field, the constantly changing
or alternating magnetic lines of force induce EMFs in this material. Because of these EMFs,
eddy currents circulate through the material and produce magnetic fields of their own.
5. When a current is caused to flow through a conductor lying within a magnet ic field, a
mechanical force is set up which tends to move the current-carrying conductor out of the
magnetic field.
The reason for this effect can be seen
from Figure 11-12. In Figure 11-13a, a con-
ductor is indicated as carrying current from
above into the plane of the paper, which
establishes a magnetic field that is clockwise
in direction. Figure 11-13b indicates an
external magnetic field. When the current-
carrying conductor is moved into the external
field, as in Figure 11-13c, it reacts with the
external field and causes a crowding of the
flux lines on the left where the two fields are
additive. On the right, where the fields are
in opposition, the flux lines move apart. The
flux lines may be considered as elastic bands
acting on the conductor, causing a force that
tends to move the conductor to the right.
The rotor of the meter is an electrical
conductor in the form of a disk that is placed
between the pole faces of the stator as indi-
cated in Figure 11-14. The magnetic fluxes
Figure 11-14. Schematic Diagram of a Three-Wire,
from the stator pass through a portion of the
disk and, as the magnetic fields alternately
Single-Phase Induction Watthour Meter.
build up and collapse, induced EMFs in the
disk cause eddy currents that react with the alternating magnetic field, causing torque on the disk. The 265
disk is free to turn, so it rotates.
Figure 11-15 shows the flux relationships and disk eddy currents in a meter at various instants of
time during one cycle of supply voltage. It also indicates the space displacement that exists between
Time 1 Time 2
Time 3 Time 4
its rate of change is at maximum, giving the greatest disk eddy currents. Consideration in Figure 11-15
of the directions of the fluxes created by the disk eddy currents and the air-gap fluxes from the voltage
and current coils shows that, in accordance with Figure 11-13, a force is developed with direction of
the resultant torque as shown to the left.
In Figure 11-16, below the flux waveforms are enlarged views of the current and voltage poles and
disk, which show more clearly the flux interactions that produce disk torque. It is assumed that an
exact 90° phase relationship has been obtained between the two fluxes.
Time 1. The current coils are at the zero point of their flux curve and the rate of change of cur-
rent flux is maximum, giving disk eddy currents as shown for the two current poles. The voltage-coil
flux curve lags that of the current coil by 90°. Since this curve is below the zero line, the voltage coil
develops a south magnetic pole. Interaction of the disk eddy-current flux (in the central portion of the
disk) and the voltage-coil flux develops a force to the left in the disk according to the principle shown
in Figure 11-13. The return paths of the disk eddy currents shown in the outer portions of the disk are
too far removed from the voltage flux to have an appreciable effect on disk force.
Time 2. At this time, 90° after Time 1, the voltage-coil flux has reached zero. Its rate of change
is maximum, causing disk eddy currents as shown. The current-coil flux has reached its maximum.
North and south current poles are produced as indicated because the current coils are wound in
reverse directions on the two poles. Again, the interaction of flux produced by the disk eddy currents
with the current-coil flux creates disk force to the left.
Time 3. This point is similar to that at Time 1 and occurs 180° later. Here, the voltage flux curve
is above the zero line, producing a north pole. The current-coil flux has again reached zero, but its rate
of change is in the opposite direction so that the direction of disk eddy-current flow is reversed from
that shown at Time 2. Since both the voltage flux and disk eddy-current flux are reversed in direction,
the resultant disk force is still to the left.
Time 4. This point, 270° after Time 1, is similar to that at Time 2. Again, the direction of both
current-coil flux and disk eddy-current flux are reversed, giving resultant disk force to the left.
Time 5. At this time the cycle of change is completed, producing the identical conditions of
Time 1 360° later.
ADJUSTMENTS
On modern electromechanical, single-stator watthour meters there are two adjustments available for
utility testers to make the speed of the rotor agree with the watthour constant of the meter. They are
the full-load adjustment and the light-load adjustment.
268 Full-Load Adjustment
The eddy currents in the disk caused by the permanent magnets produce a retarding force on the
disk. In order to adjust the rotor speed to the proper number of revolutions per minute at a given (or
“rated”) voltage and current at unity power factor, the full-load adjustment is used.
Handbook for Electricity Metering
There are two methods of making the full-load adjustment. One is to change the position of the
permanent magnet. As the magnet moves further away from the center of the disk, the lever arm
becomes longer, increasing the retarding force. The rate at which the disk cuts the lines of flux from
the permanent magnet increases and this also increases the retarding force.
In modern electromechanical meters, the method of making the full-load adjustment is by varying
the amount of flux by means of a shunt, as flux tends to travel through the path of least reluctance.
Reluctance in a magnetic circuit is resistance to magnetic lines of force, or flux. By changing the
reluctance of the shunt, it is possible to vary the amount of flux that cuts the disk. This can be done
with a soft iron yoke used as a flux shunt, in which there is a movable iron screw. As the screw is
moved into the yoke, the reluctance of this path decreases and more lines of flux from the permanent
magnet flow through the yoke and less through the disk, so the disk is subject to less retarding force
and turns faster.
In either case, the retarding force is varied by the full-load adjustment and the rotor speed is
varied until it is correct. Normally the full-load adjustment is made at unity power factor and at the
voltage and test current (TA) shown on the nameplate of the watthour meter, but the effect of adjust-
ment is the same, in terms of percent, at all loads within the class range of the meter.
Light-Load Adjustment
With no current in the current coil, any lack of symmetry in the voltage coil flux could produce a
torque that might be either forward or reverse. Because electrical steels are not perfect conductors of
magnetic flux, the flux produced by the current coils is not exactly proportional to the current, so that
when a meter is carrying a small portion of its rated load it tends to run slower. A certain amount
of friction is caused by the disk shaft bearings and the register, which also tends to make the disk
rotate at a slower speed than it should with small load currents. To compensate for these tendencies,
a controlled driving torque, which is dependent upon the voltage, is added to the disk. This is done by
means of a plate (or shading pole loop) mounted close to the voltage pole in the path of the voltage
flux. As this plate is moved circumferentially with respect to the disk, the net driving torque is varied
and the disk rotation speed changes accordingly. The plate is so designed that it can be adjusted to
provide the necessary additional driving torque to make the disk revolve at the correct speed at 10%
of the TA current marked on the nameplate of the meter. This torque is present under all conditions
of loading. Since it is constant as long as applied voltage does not change, a change in the light-load
adjustment at 10% of test amperes will also change full-load registration, but will change it only one-
tenth as much as light-load registration is changed.
Inductive-Load or Power-Factor Adjustment
Modern meters use a fixed lag plate operating on voltage flux with the compensation permanently
made by the manufacturer at the factory. Such plates may be located on the voltage coil pole or may
form a single loop around both current poles. All modern meters leave the factories properly adjusted
and, once calibrated, this lag or power-factor adjustment seldom requires change regardless of the
method used.
Once the proper phase relationship between the load-current flux and the voltage flux is attained,
there will be no appreciable error at any power factor. If this adjustment is improperly made, an error
will be present at all power factors other than unity and it will increase as the power factor decreases.
This is calculated as follows:
Meter watts
% error 5 100 1 2 —————————
True watts
This can be developed into a formula which may be resolved into the following:
cos 2 cos ( 6 )
5 100 ——————————————
cos
where is the angle between the line current and voltage and is the angle of error between the line-
current flux and the voltage flux due to improper relation within the meter. This error is computed
without reference to errors of calibration at full load. Full-load errors are independent of those just 269
calculated and add to or subtract from them dependent upon their relative signs. The errors indicated,
while computed for lagging power factor, are also applicable for leading power factor. The sign of the
effect will change when going from a lagging power factor to a leading power factor. An improper lag
COMPENSATIONS
Several factors must be compensated to make the meter accurate for the variety of field conditions in
which it must operate. These compensations are built into the meter and provide corrections needed
to make the meter register accurately under conditions of overload, temperature variation, frequency
error, and voltage fluctuation.
Overload Compensation
The meter may be adjusted to record correctly at its nominal load. However, the current sensing
approach used in electromechanical meters is not perfect and, unless it is compensated, it will not
record correctly as loads increase up to the maximum load of the meter (class current). Because
electromagnetic steels are not perfect conductors of flux, the speed of rotation of the disk will tend
to be proportionately less at higher loads. Also, as load currents increase, the damping caused by the
interaction of the disk eddy currents with the fluxes that produce them also increases. This effect
becomes more visible at the higher overload currents of the meter. The voltage coil produces eddy cur-
rents which interact with the current-coil flux to drive the disk, but the interaction of the voltage-coil
eddy currents with the voltage-coil flux retards the disk. The voltage-coil flux is practically constant
regardless of load, so its retarding effect can be calibrated out of the meter. The fluxes produced by the
current coil will act with the current-coil eddy currents to retard rotation of the disk. At rated load
these self-damping effects are in the order of only 0.5% of the total damping. However, the retarding
action increases as the square of the current flux. This is true because the retarding force is a function
of the eddy currents multiplied by the flux and the eddy currents increase as the flux increases, so the
retarding force increases as the flux multiplied by itself.
Figure 11-17 shows the factors of accuracy for a meter with the typical load curve (6) of a model
compensated meter. To negate the retarding or dropping accuracy shown as curve 4, which would
result without overload compensation, a magnetic shunt is placed between but not touching the poles
of the current electromagnet and is held in place by non-magnetic spacers (see Figure 11-18). This
shunt has little effect below the point at which the accuracy curve of the meter would otherwise start
to drop, but as the load increases the shunt approaches saturation causing the current flux which cuts
the disk to increase at a greater ratio than the current. This causes an added increase in torque, which
counteracts the drop in the accuracy curve up to the point at which the shunt is saturated. Beyond
this point, which is usually beyond the maximum rated load of the meter, the accuracy curve drops
very rapidly.
Figure 11-18. Simplified Diagram of Magnetic Circuit of Current Element for Overload Compensation
Figure 11-19 shows another diagram of the magnetic circuit for overload compensation on the
current element. Other ways of minimizing the retarding effect are: (1) proper proportioning of
the voltage and current fluxes, so that the effective voltage-coil flux (about 4% of the total damping
flux) is proportionately higher than the effective current-coil flux; (2) by use of stronger permanent
magnets and lower disk speed; and (3) a design which gives the greatest driving torque while getting
the least damping effect from the electromagnets. Present-day meters will accurately register loads up
to 667% of the meter’s nominal rating. Figure 11-20 shows comparisons of the accuracy of modern
meters with that of those manufactured in 1920, 1940, and 1955.
At the same time that these improvements were being made, similar improvements were effected
in light-load performance as can be seen from the curves in Figure 11-21.
Voltage Compensation
Inaccuracies of registration in modern electromechanical meters over the usual range of voltage varia-
tions are very small. In a meter without voltage compensation, errors resulting from voltage change
are caused by:
1. The damping effect of the voltage flux;
2. Changes in the electromagnet characteristics due to changes in voltage; and
3. Changes in the effect of the light-load adjustment due to changes in voltage.
The damping effect of the voltage flux is similar to that of the current flux, with changes in effect
being proportional to the square of the voltage.
The errors caused by the characteristics of electromagnets are due to the failure of the magnetic
circuit to be linear under all conditions of flux density. In an electromagnet, the effective flux is not
equal to the total flux. The ratio between the effective and the total flux determines many of the
characteristics of the electromagnet. Improvements in the metals used have permitted a much closer
approach to the desired straightline properties of the magnetic circuit. Through use of saturable
271
magnetic shunts similar to those used in the current magnetic circuit, voltage flux is controlled and
the errors due to normal voltage variations are reduced to a negligible amount.
Since the light-load compensation is dependent only on voltage, a voltage change varies the
magnitude of this compensation and tends to cause error. Increasing voltage increases light-load driv-
ing torque so that a meter tends to over-register at light-load current under over-voltage conditions.
Good meter design, which maintains a high ratio of driving torque to light-load compensating torque,
reduces these errors to very small values.
ANTI-CREEP HOLES
Without anti-creep holes, the interaction of the voltage coil and the light-load adjustment might
provide enough torque to cause the disk to rotate very slowly when the meter was energized, but no
current flowing. This creep would generally be in a forward direction, because the light-load adjust-
ment is so designed that it helps overcome the effects of friction and compensates for imperfections
of the electromagnet steels. In order to prevent the disk from rotating continuously, two diametrically
opposed holes are cut into the disk, adding resistance to the flow of eddy currents caused by the
voltage flux. Earnshaw’s Theorem explains that a conductor in a flux field tends to move to a position
of least coupling between the conductor and the source of the flux field. As a result, the disk will tend
to stop at a position in which the anti-creep hole causes the greatest reduction in the eddy currents
(sometimes moving backward a portion of a revolution in order to stop in this position). A laminated
disk or one of varying thickness will also tend to stop in a position of least coupling.
FREQUENCY CHARACTERISTICS
Due to frequency stability of modern systems, variations in meter accuracy as a result of frequency
variations are negligible. As frequency is increased, the shunt coil reactance increases and its excit-
ing current decreases. The reactance of the eddy current paths in the disk is raised, thus limiting
cent registration at 50% power factor lagging will be higher than that for unity power factor. Because
of the stability of modern systems, specific frequency compensation is not required and in modern
meters frequency variation errors are kept to a minimum by proper design.
Figure 11-24 shows the effect of frequency variations on modern meters.
WAVEFORM
In determining the effects of harmonics on an electromechanical watthour meter’s performance, the
following facts are relevant:
1. An harmonic is a current or a voltage of a frequency that is an integral multiple of the fun-
damental frequency. For example, the third harmonic has a frequency of 180 hertz (Hz) in a
60 Hz system.
2. A distorted wave is a combination of fundamental and harmonic frequencies which, by analysis,
may be broken down into such frequencies.
3. Currents and voltages of different frequencies do not interact to produce torque. An harmonic
in the voltage wave will react only with the same harmonic in the current wave to produce
torque.
4. To produce torque, two fluxes with time and space displacement are necessary.
5. An harmonic present only in the voltage circuit may have a small effect on meter performance
due to the torque component produced by the light-load adjustment.
6. Minor damping effects of harmonics in either voltage or current elements are possible.
The magnetic shunt used for overload compensation can introduce harmonics in the current flux
which are not necessarily present in the load current, particularly at high loads. To a lesser extent,
this is also possible in the voltage flux. Unless extreme distortion of waveform exists, the errors due to
harmonics will not degrade meter accuracy beyond normal commercial limits. However, when working
with high accuracy watthour standards, the errors due to harmonics may be bothersome. All meters,
even when of the same manufacture and type, do not exhibit identical reactions to the same degree of
harmonics.
Waveform distortion and resulting meter inaccuracies may be caused by over-excited distribution
transformers and open-delta transformer banks. Some types of equipment, such as rectifiers and fluo-
rescent lamps, may also cause distortion of the waveform. Welders cause poor waveform and present a
continuing metering problem, but other factors may have greater influence on meter errors.
In extreme cases of distortion a separate analysis is necessary because each waveform has different
characteristics. The distorted wave should be resolved into the fundamental and the various harmonic
sine waves and then calculations can be made.
the cooler cover to act as the condenser under high-humidity operation. Therefore, meters should not
be stored outdoors without being energized.
The materials and coatings used to prevent corrosion are the best materials economically avail-
able during that period of manufacture. Present-day meters are made from high corrosion-resistant
aluminum, which has minimum contact with copper or brass materials. The steel laminations are
coated with paint. A plastic base, glass, or plastic cover, and stainless-steel (or other material) cover-
ing provide the meter with corrosion resistance. In the application of corrosion-resistant finishes,
consideration must be given to the particular function of the part in question, such as exposure to the
elements, wear resistance, and use as a current-carrying part.
There are a variety of processes that can be used to protect the metals within a meter. Iridite is
a chromate-dip finish that may be used on cadmium-plated steel parts. This process applies an oxide
coating and seals at the same time. One of the finishes applied to aluminum is anodizing. This finish
converts the surface to aluminum oxide, which is a very hard, corrosion-resistant finish. This protec-
tion may be further improved by applying a sealer that closes the pores in the oxide and prevents
the entrance of moisture. Another finish for aluminum is alodine, which is a complex chromate gel
applied to the surface and that seals the metal in one operation. When applied to aluminum, the
parts take on an iridescent finish. It may be used on parts such as the grid, register plates, and others
not subject to wear or abrasion.
The copper and copper-bearing alloys that carry current are tin-plated on contact surfaces, e.g.,
socket-meter bayonets. This not only gives protection against corrosion, but also improves contact
resistance.
Brass screws may be protected by a heavy nickel plating. Steel parts, such as register screws, may
also be nickel-plated.
For the protection of ferrous metals, such as voltage and current electromagnet laminations, these
parts may be immersed in a hot solution of phosphoric acid. This converts the surface to a hard iron
phosphite that is further hardened by a sealer, usually paint. The voltage and current laminations may
be sealed with several coats of paint.
Lightning and surge protection are provided by a combination of high insulation and surge levels
built into the voltage coil and current coil and the provision of a ground pin in calibrated proximity
to the current leads on the line side so that a lightning surge will jump the spark gap prior to enter-
ing the coils. The ground-pin gap is such as to cause a spark over at some voltage between 4,000
and 6,000 volts. The ground pin is attached to a strap in contact with the socket enclosure, which is
grounded. The factory testing consists of hi-potting of both voltage coils and current coils at about
7,000 volts. The voltage coil is exposed to a 10,000 volt surge of a 1.2 3 50 (crests in 1.2 micro
seconds, decays in 50 microseconds) wave shape to pick out any shorted turns in the windings. This
combination has proved very successful in allowing meters to withstand repeated lightning surges and
still allow continued accurate meter operation.
Present-day meters are built with permanent magnets that are practically unaffected by lightning
surges.
Two- or Three-Wire Electromechanical Meters
Some single-stator electromechanical meters are made so that by means of a very simple rearrange-
ment of internal connections the meter can be converted from the connections used on 120 volt
circuits to those needed for use on 240 volt circuits. Coil ends are brought to terminal boards and
usually the connections can be changed with a screwdriver. The basic theory, inherent accuracy, stabil-
ity of calibration, insulation, and other desirable features of modern watthour meters are unaffected
by the minor changes of internal connections. This meter has the advantage of not becoming obsolete
if the customer changes from 120 volt to 240 volt service.
The voltage coils are wound to give uniform flux distribution whether connected for 120 volt or
240 volt usage. A constant resistance-to-reactance ratio is maintained as the change is made; therefore
a constant phase-angle relationship exists and no readjustment of the lag compensation is necessary.
The Kh constant is the same for either connection, since one current coil is used for 120 volt
operation and two are used when the meter is connected for 240 volt operation. These meters are
of standard dimensions so they are interchangeable with other single-phase, 120 volt or 240 volt 277
standard-size meters. In general, changing internal connections has so little effect on calibration of
the meter that it may be considered negligible.
INDIVIDUAL-STATOR PERFORMANCE
In the simplest form of the polyphase meter with two stators driving a common moving element, the
meter performs as a single-phase meter if both elements are connected together on single-phase, e.g.,
with the current coils connected in series and the voltage coils in parallel. With this connection it
is, for all intents and purposes, a single-phase meter and has all the characteristics of a single-phase
meter. The fact that the two stators are coupled together on a single shaft makes no difference except
to average the characteristics of the individual stators.
278 The same will be true, with the exception of interference errors, when the meter is connected in a
polyphase circuit and the load is completely balanced. When the loads are not balanced, the polyphase
meter no longer performs as a single-phase meter. If only one stator is loaded, the polyphase meter
will tend to register fast. This is best illustrated by putting balanced loads on the two stators, checking
Handbook for Electricity Metering
the calibration, and then removing the load from one stator. The meter will register fast along the
load curve as compared to the speed curve on combined stators. This is due to the variation of the
overall damping torque caused by the change in the current damping component.
CURRENT DAMPING
Assume that a polyphase meter when operating at rated test-amperes has its damping components
in the following typical relationships: 96.7% from a permanent magnet, 2.8% from voltage at rated
voltage, and 0.5% from current at rated test-amperes.
When the load is taken off one stator, the driving torque drops 50%, but the total damping drops
more than 50% since the current damping on the unloaded stator is eliminated, whereas it was a part
of the total damping torque when both stators were loaded.
This characteristic changes with increasing load. For example, in a two-stator meter that runs
0.4% fast on a single stator at rated test-amperes as compared to the registration with balanced load
on both stators at rated test-amperes, the difference in registration between single and combined
stators may be as much as 3% at 300% rated test-amperes. This can be seen from the fact that the
current-damping component from the stator that is not loaded would be nine times as great at 300%
rated test-amperes as at 100% rated test-amperes. Therefore its elimination at 300% rated test-amperes
takes away 9 3 0.4 or about 3.6% from the total damping.
IMBALANCED LOADS
Due to the effect of current damping, if the stators are unequally loaded the registration will differ
from when the load is equally balanced or when the total load is carried by one stator. This is because
the overload compensation causes the torque curve to go up in direct proportion to the increase in
current damping on balanced loads. The departure from balanced-load performance, particularly for
heavy loads, will be in proportion to the amount of overload compensation in the meter.
For a five ampere, two-stator, polyphase meter with five amperes applied to each stator, the total
current damping will be proportional to (5 amperes)2 plus (5 amperes)2 or 50 current-damping
units. On the other hand, if 10 amperes is applied to one stator only, current damping will then be
proportional to (10 amperes)2 or 100 current-damping units. This is the same total energy and total
flux, but they are divided differently in the stators and consequently produce different current damp-
ing. The current-squared damping law applies only to current flux produced in a single stator and not
to the total currents in separate stators. In this case, the current damping of the single stator with
10 amperes is twice that of two elements with five amperes each.
If the load is imbalanced (eight amperes on one stator and two amperes on the other), the total
current damping is proportional to 82 plus 22 or 68 current-damping units as compared to 50 units
with 5 amperes on each stator.
INTERFERENCE TESTS
Comparative tests to evaluate interference effects in a watthour meter have been established within
the American National Standards Institute (ANSI) C12 standard.
Interference tests are not part of the usual meter calibration procedure and are not performed
in the meter shop. Since such tests are made to evaluate the manufacturer’s design of a particular
polyphase meter type, they are usually performed in the meter laboratory.
The specialized interference tests require the use of a two-phase power source with two-stator
meters and a three-phase source with three-stator meters. The test results do not give the specific
interference errors that will be obtained in actual service, but if the results are within the established
tolerances, assurance is obtained that the interference effects will not be excessive.
Torque-Balance Adjustment
For correct registration, the torque produced by each stator in a multi-stator electromechanical meter
must be the same when equal wattage is applied. A two-stator meter with one stator 5% fast and the
other stator 5% slow would show good performance with both stators connected in series-parallel for
a calibration test on single-phase loading. However, if this meter were used to measure polyphase loads
involving either low power factor or imbalance, the registration would be incorrect. To correct for this,
each stator should be calibrated and adjusted separately to ensure that each produces the same driving
torque. The full-load adjustment cannot be used because it has an equal effect on the performance
of all stators, so the torque-balance adjustment is provided for independently adjusting the torque of
each stator.
Since the torque developed by a single stator is dependent upon the amount of flux produced
by the electromagnet that passes through the disk, it follows that the torque for a given load can be
varied by any method that will change the flux through the disk. A convenient way to change this is
by providing a magnetic shunt in the air gap of the voltage-coil poles in the electromagnet. Moving
this shunt into or out of the air gap bypasses a greater or a lesser portion of the voltage flux from the
disk. This changes the disk driving torque through a narrow range. The adjustment obtained this way
is sufficient to equalize the torques of the individual stators in a polyphase meter.
Two methods used for torque balancing are shown in Figure 11-26. The first uses two steel screws
which can be turned into or out of the gaps in the voltage-coil iron just below the coil windings. The
second method uses a U-shaped soft iron wire that is inserted in the air gaps. This wire is attached to
a yoke carried on threaded studs which permits the magnetic shunt to be moved in and out of the air
gap. After these adjustments have been set so that the torques of all stators are alike, the other meter
adjustments can be made as for single-phase meters.
Interdependence of Adjustments
Another characteristic of the polyphase meter is that any change in a full-load or light-load adjust-
ment affects all stators alike. This does not apply to the power factor or torque balance adjustments.
The torques of the stators can be balanced at any unity power factor load value, but it is custom-
ary to make the balance adjustment at the rated test-ampere load. The balance of the individual stator
torques at other unity power factor load points will depend on how well the stator characteristics are
matched. Any divergence that may exist cannot be corrected or minimized by the light-load adjust-
ment or otherwise, except by attempting to select stators of the same characteristics. This is neither
practical nor important.
(a) (b)
Solid-State Meters
All watthour metering approaches require power to be measured and accumulated, and the results
stored and displayed. All approaches require that the voltage and current for each electrical phase
be sensed (or approximated) and for voltage and current for each electrical phase be multiplied, the
resultant power must be accumulated, and the accumulated watthours stored and displayed. Electro-
mechanical meters have evolved and all manufacturers use very similar approaches. The same cannot
be said for totally electronic meters.
Significant design variations occur in every electronic meter on the market. These variations even
occur within a given manufacturer’s product line. Ultimately, users or regulatory agencies determine if
design trade-offs are appropriate as determined by evaluation and qualification testing of each design.
cal, four-wire, wye meter. By the late 1980s, multiple manufacturers had totally electronic replacement
meters for all electromechanical polyphase meter services. These still tended to be more expensive than
the electromechanical meters, but provided more accuracy and greater functionality.
In 1992, polyphase metering changed dramatically with the introduction of a totally electronic
meter that was highly accurate and cost competitive with the electromechanical demand meter. In
addition, multiple service voltages and multiple service wirings could be handled with the same physi-
cal meter. In the mid-1990s, additional functionality, such as instrumentation and site diagnostics,
was added to the basic solid-state polyphase meter. Today, these features are the norm for polyphase
metering.
Also in the mid-1990s, a practical single-phase solid-state meter was introduced for practical time-
of-use and demand applications. By the late 1990s, other manufacturers had introduced more cost
effective solid-state meters for lower-end single-phase applications.
The Solid-State Watthour Meter Principle of Operation
A functional block diagram of an early watt/watthour transducer is shown in Figure 11-28. The watt
section is an electronic multiplier which uses the time-division-multiplier (TDM) principle to produce
a pulse train which combines pulse-width and pulse-amplitude modulation. The pulse initiator section
receives a DC current signal proportional to power from the watt section. Output pulses, propor-
tional to a convenient watthour-per-pulse rate, are fed from the KYZ output circuit to a register, tape
recorder, electronic pulse counter, or other pulse-operated device.
Solid-State Watthour Meter
A typical meter consists of two sections: the multiplier and the register. In an electromechanical meter
the multiplier consists of the voltage and current coils and the meter disk; the register consists of the
CURRENT SENSING
All currents must be reduced to a signal level that the electronics can process. The current sensor
needs to accurately reflect the current magnitude and phase angle over the expected environmental
and service variations. Because the current sensor measures the currents on lines that are at line
voltage, current sensors must be isolated from each other on systems with multiple line voltages. The
current sensor must also provide protection from power transients.
The most common current sensor circuits are typically current transformers. Transformers allow
the line voltages to be isolated from each other. A current transformer’s linearity is defined by the
magnetic material used for its core. Typically, a high permeability material is used to ensure a linear
performance, minimal phase shift, and immunity to external magnetic fields. Care must be taken
to ensure the material does not saturate under normal conditions. High permeability materials will
saturate with DC currents, but these are not normally present on an AC electrical system.
A current sensor similar to the current transformer is the mutual inductance current sensor. This
sensor uses air or a very low permeability material for the core because these materials are generally
inexpensive and will not saturate (as is the case with air) or require very high magnetic fluxes to cause
the material to saturate. They also tend to have acceptable DC immunity. The drawback to this sensor
is that it is more susceptible to external magnetic fields, it often has stability issues with time and
temperature, and it cannot supply much current. As such, it tends to have large phase shifts that vary
with sensor loading. Typically, a voltage is measured from the sensor instead of a current.
A common sensor used in two-wire meters (particularly in Europe) is the current shunt. This
sensor defines a geometry in the meter’s current conductor that causes part of the total current to
pass through a resistance so that a voltage will be developed that is proportional to the load current.
This voltage is then measured and represents the current. Because copper has a low resistance and a
very large temperature coefficient, a special material is used for the shunt. The main disadvantages of
this sensor are that it is not isolated from the line voltage and it is difficult to control the sensor’s
performance over a wide temperature range.
A current sensor can be produced using the Hall Effect. When a current flows through a material
which is in a magnetic field, a voltage appears across the material proportional to the product of the
current and the strength of the magnetic field (Figure 11-29). In Figure 11-29a there is no magnetic
field and no voltage appears across the material. In Figure 11-29b, the magnetic field perpendicular
to the path of the electrons displaces electrons toward the right side of the material. This produces
a voltage difference side-to-side across the material. The voltage is proportional to the strength of
the magnetic field and the amount of current flowing in the material. The Hall Effect device is usu-
ally inserted in a gap in a toroidal-shaped magnetic core. Because it measures the magnetic field of
the current through a conductor, there is electrical isolation in the current sensor. The Hall Effect
device can also be used for multiplication with the line voltage. Depending on the voltage measure-
ment approach, isolation may be lost. Historically, phase shift and temperature and frequency output
variations have been problems for Hall Effect devices, but there have been significant improvements in
the performance of meters using these sensors.
There are numerous variations of the above current sensors. Shunts can be combined with cur-
rent transformers. Compensating wirings can be used on a current transformer made with a low
284
Handbook for Electricity Metering
(a) (b)
permeability material. Generally, most of the performance issues related to a particular current sensor
technology can be compensated in the associated electronics. How these issues are addressed will be
unique to each meter design.
VOLTAGE SENSING
All voltages must be reduced to a signal level that the electronics can process. Like current sensing, the
reduced voltage needs to accurately reflect the voltage magnitude and phase angle over the expected
environmental and service variations. It must also provide protection from power transients.
Historically, the voltage reduction circuits were transformers. Transformers allow the line volt-
ages to be isolated from each other, but often have a limited operating range, have an intrinsic phase
shift that varies with frequency, and are relatively expensive. Most of today’s solid-state meters use
a resistor-divider network because of the reduced cost and a very wide dynamic operating range with
accurate reproduction of magnitude and phase angle. A drawback of this approach is that the designer
must use great care to ensure the meter operates properly over all defined services. Another is that the
electronics of the meter may have line voltage present in some services, which can represent a safety
and equipment issue for the meter technician.
MULTIPLICATION
Time-Division Multiplication
Time-division multiplication (TDM), also called mark-space-amplitude multiplication, is used in the
earliest commercial solid-state meters and many metering transducers and standards. It computes
power by using the common calculation of length times width to measure the area of a rectangle. The
TDM multiplier develops a series of pulses where the width of each pulse is proportional to input volt-
age and the height of each pulse is proportional to input current, or vise versa. The area of each pulse
is proportional to power. Power can be integrated over time to develop an output signal for energy.
Figure 11-30 is a block diagram of a TDM multiplier and the waveforms within the multiplier.
The signal from the voltage (or current) sensor is compared with a triangular wave with a mag-
nitude greater than the maximum of the input voltage signal. The frequency of the triangular wave
varies with each manufacturer, with values typically between 800 Hz and 10 kHz. The comparator
compares the input voltage with the reference voltage. For the positive half of the input voltage cycle,
if the reference voltage is greater than the input signal, the comparator output is negative; if the refer-
ence voltage is less than the input signal, the comparator output is positive. For the negative half of
the input voltage cycle, if the reference voltage is more negative than the input signal, the comparator
output is negative; if the reference voltage is less negative than the input signal, the comparator output
is positive. Figure 11-30b, graph C, illustrates these comparisons. Graph D shows the output from the
comparator, a signal with a fixed amplitude and a pulse width proportional to the input voltage.
The output from the comparator controls an electronic switch. When the comparator output is
positive, the switch is set to input 1. When comparator output is negative, the switch is set to input 2.
Signal from the current sensor (or voltage sensor) is applied to switch input 1, and the inverse of
that input is applied to switch input 2.
The output of the switch is shown on Figure 11-30b, graph F. The width of each shaded area is
proportional to the width of the switch control signal, which is proportional to the input voltage.
285
The height of each shaded area is proportional to the input current. The area of each shaded area is
proportional to power for that period of time. While there appears to be positive as well as negative
areas in the graph, the negative areas do not indicate power flow in the reverse direction.
The integrator and pulse generator convert power into energy measurements and the analog
information into digital data. The integrator sums individual areas, both positive and negative. When
the accumulated total exceeds a predetermined value, the predetermined value is subtracted from
the accumulated total and a pulse output is generated. The output of the pulse generator is sent to a
register for storage and display.
By passing output signal F through an electronic filter, a signal proportional to instantaneous
power can be produced. This waveform is labeled as signal H, and can be transmitted to a Supervisory
Control and Data Acquisition (SCADA) system for monitoring and control purposes.
A comparison of Figure 11-29 with Figure 11-30 shows that while several years have passed since
the watt/watthour transducer of Figure 11-29 was designed, the basic principles of TDM remain
unchanged. The significant changes in the two designs result from the trend toward smaller lower cost
components. In modern TDM multipliers, design variations among manufacturers include the fre-
quency used by the triangular reference waveform; the rate at which integrated data is converted into
pulses; the electronic components selected for the comparator, switch, and integrator; calibration and
adjustments made available; method for scaling down voltage and current inputs; power supplies; and
the technology used for the display.
Hall Effect Multiplication
The Hall Effect device can be used for current measurement and it can also be used for the multiplica-
tion of the voltage with the current signal. Figure 11-31 illustrates application of the Hall Effect to
metering. Current flows in the Hall Effect device based on line voltage across the device after a reduc-
ing resistor. Current in a conductor looped around the magnetic core creates a magnetic field. The
magnetic field flows around the core and through the Hall Effect device, perpendicular to the flow of
current.
The Hall Effect voltage is sensed by a differential amplifier and supplied to an integrator and pulse
generator. The integrator and pulse generator convert the power measured to an energy measurement,
286
Handbook for Electricity Metering
and convert analog information into digital data. The integrator calculates the area under the power
curve and stores accumulated data. When the accumulated total exceeds a predetermined value, the
predetermined value is subtracted from the accumulated total and a pulse output is sent to a register
for counting, storing, and displaying the measured data.
Transconductance Multiplier
The transconductance multiplier uses a differential amplifier, where bias current varies with an input
signal. The circuit is illustrated in Figure 11-32. In a metering application, input current is applied
to the emitter of both transistors through
resistor R1. Input voltage is applied across the
base of both transistors causing one transistor
to conduct more than the other transistor.
The current flow difference causes different
voltage drops across resistors R2 and R3.
Output voltage VOUT, is proportional to the
bias current multiplied by the input voltage.
Figure 11-33 illustrates application of
a transconductance amplifier for metering
purposes. Bias current is developed from
resistors R1, R2, and R3 connected across the
power line. Input voltage VIN is developed
from a secondary winding on a transformer
(in this example a toroid core), where the
primary winding carries line current. The
output signal is fed to an integrator and pulse
generator.
The integrator calculates the area beneath
Figure 11-32. Transconductance Multiplier the power curve. When the sum of several
areas exceeds a predetermined value, the
predetermined value is subtracted from the
integrated total and an output pulse generated. Output pulses are sent to a register for counting, stor-
ing, and display of the measured data.
Digital Multiplier
For all three multipliers described above, the analog voltage and current signals are multiplied and
the results are converted to digital format. With the digital multiplier, the voltage and current analog
inputs are immediately converted to digital equivalents, then multiplied using digital circuits.
An analog-to-digital converter measures the instantaneous value of the waveform and converts
each value to an equivalent digital word. An input sine wave, for example, can be sampled many
times within one cycle and a digital equivalent of each instantaneous value can be stored in memory.
Important specifications for analog-to-digital converters are: conversion time, the number of bits of
resolution, and linearity.
Modern analog-to-digital conversion times are typically in the range of 20 to 50 microseconds.
When the conversion time is short, changes to the input signal during the measuring window are
287
small, increasing the accuracy of the measurement. When the time for each conversion is short, more
samples can be taken during each cycle of the analog input, making the data collection process more
accurate.
When sampling a voltage or current signal, the sampling rate determines the accuracy with which
the signal is measured. The Nyquist Theorem states: when sampling an analog signal, to capture
sufficient information about that signal, the sampling rate must be at least twice the highest frequency
of interest in the analog signal. For example, if the highest frequency of interest in a signal is 60 Hz,
the signal must be sampled at least 120 times per second to get a valid representation of that signal. If
higher frequencies are of interest, a higher sampling rate must be used. For example, if measuring the
seventh harmonic which has a frequency of 420 Hz is of interest, the signal must be sampled at least
twice 420 or 840 times per second. Unfortunately, Nyquist is dealing with the presence of a frequency
in a stable waveform. The load currents may be considered stable over short time periods, but this is
very application dependent. To accurately reflect a changing current signal, a much higher sample rate
is required. The performance of a meter under these conditions is difficult to measure, because most
test equipment uses stable current signals for the test and is limited in its ability to deal with frequen-
cies other than the fundamental.
The sampling rate of solid-state meters varies by model and by manufacturer. Typical rates are 10s
to 100s of samples per 60 Hz cycle and per phase. Because two parameters, voltage and current, must
be measured, often multiple analog-to-digital converters are used. Because multiple phases must be
measured, the digital multiplier must process information at two to three times these sampling rates.
A three-phase meter taking two readings for each of three phases processes information at speeds over
15,000 new readings each second.
The number of bits of resolution determines the granularity of the measurement. For example, if a
2-bit analog-to-digital converter is used to convert an analog signal which varies from 0 to 110 volts,
the converter can output only four different digital values representing the input, or steps of 2.5 volts
each. If a 12-bit analog-to-digital converter is used to convert a signal varying from 0 to 110 volts,
the converter can output 4,096 different digital values, or steps of 2.44 millivolts each. In the second
example, a change of only 2.44 millivolts at the analog input will cause a one-bit change in the output
digital value. The resolution of analog-to-digital converters used in solid-state meters varies by model
and by manufacturer, depending on the accuracy of the application. Typical resolutions are 12 to 21
bits.
A block diagram of a digital multiplier in a power meter is shown in Figure 11-34. This example
shows two analog-to-digital converters although more could be used, especially in polyphase meters.
The input voltage and current signals are scaled down by their respective reduction circuits, then
applied to the analog-to-digital converters. The converter outputs are multiplied by the microprocessor,
with the results stored in memory along with an accumulating total of the results. When the accumu-
lated total reaches a predetermined value, that predetermined value is subtracted from the total and
one output pulse is generated. The output pulse indicates that one predetermined increment of power
has been measured. The pulse is sent to an electronic register for storage and display.
288
Handbook for Electricity Metering
Variations of digital multiplier designs are shown in Figure 11-35. The sample-andhold amplifiers
shown in Figure 11-35a allow the meter to measure voltage and current at the same instant, thus
eliminating time skew in taking two readings. The multiplexer shown in Figure 11-35b allows the
meter to switch one analog input at a time to one analog-to-digital converter. This approach elimi-
nates the cost of another analog-to-digital converter.
Reference Standard
The reference standard is also known as a watthour standard, an energy standard, or a standard meter.
The standard is actually a very accurate energy meter of substantially greater accuracy than the rev-
enue billing meter being tested (typically five times greater in accuracy). The standard is also extremely
stable with a known calibration history and accuracy that is traceable to the National Institute of
Standards and Technology (NIST) or some other nationally recognized metrology laboratory.
291
292
Sensor Port to Connect Pickups
4 Line x 16 Character
Back-lit LCD
HANDBOOK FOR ELECTRICITY METERING
There are different classifications of standards that relate to accuracy and application. Four types
of standards relate to the different generations of standards technology: rotating standards, single
function manual ranging standards, single function autoranging standards, and simultaneous multi-
function autoranging standards.
AUXILIARY INTERNAL
ELECTRONICALLY
INTEGRATING A/D
COMPENSATED POTENTIAL
CONVERTER FOR
TRANSFORMER WITH
VOLTAGE
AUTORANGING CURCUIT
ELECTRONICALLY
COMPENSATED CURRENT INTEGRATING A/D DIGITAL
TRANSFORMER WITH CONVERTER FOR SIGNAL REGISTER / LCO
AUTORANGING CURCUIT CURRENT PROCESSOR
INTERNAL
FREQUENCY
REFERENCE
The RM-10 and RM-11 standards use a pulse width modulation approach to measuring energy.
These second-generation electronic standards introduced a multitude of new features to the metering
industry.
Providing totally autoranging inputs for potential, current, and auxiliary power eliminated the
need for tap settings. A true watthour display with a Kh of one allows for easier calculations. A high-
resolution pulse output allows for shorter
test times. A display-gating feature greatly
improves safety by eliminating the need
for potential gating while also improving
accuracy. These standards also provide the
accuracy and stability required to conduct
a true test of an electronic meter. Although
still widely used, these standards do not
provide all of the functions required to
thoroughly test the new electronic revenue
billing meters.
Single-Function Manual
Ranging Standards
This can be referred to as first generation
electronic standards with the first products
appearing in the late 1970s. The most
common model is the SC-10 by Scientific
Columbus.
The SC-10 standard utilizes pulse
width modulation to calculate energy, thus
eliminating the induction-measuring ele-
ment of the rotating standard. The SC-10 Figure 12-3. The Radian Research Model RM-10 Standard.
is packaged to resemble rotating standards
294
AUXILARY AUXILARY
POWER POWER
HANDBOOK FOR ELECTRICITY METERING
Vrff Rref
POTENTIAL POTENTIAL
INPUT RANGING
CURRENT CURRENT
INPUT RANGING
Fref
for interchangeability while providing improvements over the rotating standards. The lack of moving
parts makes the need for leveling the standard unnecessary. The digital display reads in revolutions
while providing better resolution. It maintains manual voltage taps and current taps that simulate the
rotating standard. For testing operation, as with the Rotating Standard, tests are started and stopped by
closing and opening the voltage circuit with a snap switch. These standards are not widely used today
due to advancements in electronic revenue
billing meters. The revolution reading
display is not easily compatible with testing
an electronic meter and the accuracy and
stability are similar to the electronic meter
under test, not allowing for a true test of
accuracy.
Rotating Standards
Rotating standards have a rotating disk and
are also referred to as induction standards
or mechanical standards because the
measurement principle is based upon the
electromagnet. The most common model is
the IB-10 by General Electric.
Rotating standards have voltage taps
and current taps where the appropriate tap
to be used is based upon the amplitude of
the voltage and current test signals. Gener-
ally there are two voltage taps, rated at 120
and 240 volts, and four current taps with
Figure 12-5. The Scientific Columbus SC-10 Standard the most common rated at 1, 5, 15, and 50
amperes. The watthour constant (Kh) varies
depending upon which taps are used.
The normal procedure for using a rotating standard to test meters is to start and stop the standard
by applying and removing the test voltage by means of a snap switch.
By the nature of its design, a rotating standard requires proper handling when transporting and
in use to avoid damage. Although strong magnetic fields have little effect on rotating standards, they
295
Anti-Glare Window
Potential Terminals
Pointer Resetting Knob
Light-Load Adjustment
Potential Coil
should be kept away from heavy current carrying conductors, motors, transformers, or other like
apparatus. In addition, a rotating standard should be level if accuracy is to be maintained.
Rotating standards are not widely used due to their dated design relating to deficiencies in the
areas of accuracy, stability, functionality, and maintenance costs combined with parts availability.
CUSTOMER’S LOAD
When testing meters in service, the customer’s load itself may be used. Utilizing the customer’s load
while performing field meter tests eliminates the need for a loading device. This test procedure requires
less time as only one test at the available load current is performed. In addition, artificial registration
and or pulse counts do not have to be considered.
This type of testing has its limitations. The absence of load current will prohibit a test from being
performed. In addition, most metering standard procedures and manufacturers’ information recom-
mend meter testing be performed using three controlled load test points: full-load, light-load, and
power factor load. The full-load test point is identified as the meter’s test amp (TA) rating or can be
the associated current transformer secondary current rating. The light-load test point would then be
10% of the selected full-load current value. The customer’s loading does not satisfy these test points.
Other disadvantages include the fact that stable test conditions cannot be controlled or duplicated.
However, under certain conditions the test can still be valuable. For example, a standard such as the
Radian RD-20 or RD-21 can be used not only to test accuracy of the meter, but also to do harmonic
analysis of the customer’s load. This test also has the ability to test the accuracy of the meter under
customer load conditions if a true reference standard is being used to conduct such a test.
SYNTHESIZED LOADING
Synthesis is the latest technology applied to loading designs and is the most common and preferred
source for a majority of applications. Synthesized loading is actually a type of phantom loading
296 because it does not dissipate the full wattage of the test load. Synthesized loading is computer
controlled and allows for very precise conditions of current amplitude, frequency, phase angle, and
harmonics to be created and maintained throughout the test period. Imperfections associated with the
other loading approaches generally do not exist in a well-designed synthesized load.
HANDBOOK FOR ELECTRICITY METERING
PHANTOM LOADING
Phantom loading reduces the power in the current circuit by reducing the voltage across the load
connection. A phantom load is a small power transformer and an adjustable loading resistance. Test
connections apply service voltage, 120 or 240 volts, to the voltage coils of the meter and the stan-
dard. The current circuits of the standard and meter, which are isolated from the voltage circuit by
transformer action, are placed in the secondary of the low-voltage, phantom-load transformer, whose
primary is connected across the line. The regulating resistance of the phantom load is also in series
with the meter and standard current coils.
In this type of loading, although the current value is proper for the test being made, the voltage at
which this current is supplied is low and, hence, the power has been reduced below that necessary for
resistance testing. Assuming the phantom-load transformer is rated 240 to 12 volts and the regulating
resistor is adjusted to provide 15 amperes to the test circuit, the power of the secondary circuit would
be 15 3 12 5 180 watts. The current drawn from the secondary circuit is 15 amperes, but from the
source is: 15 3 ——12 5 0.75 amperes. With the low power requirements, a phantom load can be
240
constructed as a portable device.
The term phantom load is usually applied to the portable device that is used, particularly for
testing on customer premises. The same principle of a loading transformer with low-voltage resistance
units has been used in some test table designs. When the output voltage is lowered, the size of the
current regulating resistors in the secondary circuit is also reduced while still maintaining the desired
current magnitude.
When using phantom loads, the phase angle of the test circuit should not be ignored. Meter and
standard current coils have inductive reactance as well as resistance. Normally, the regulating resis-
tance is large enough to overcome any lagging effect caused by the reactance of the current coils and
loading transformer. However, if the regulating resistance is small, the current through the current
coils will lag the source voltage by some small angle. This change in phase angle may not be significant
at unity power factor tests, but may be of importance at 50% power factor tests. This occurs because
of the difference in values of cosines near zero and 60° angles. As an example, at 60° the cosine is
0.5 and at 61° it is 0.4848; at zero degrees the cosine is 1 and at 1° the cosine is 0.9998. A small
change in phase angle at unity power factor causes a much smaller change in cosine than a similar
phase angle change at 50% power factor. The phantom-load phase angle shift will increase rapidly
with increasing secondary burden above rated burden capacity. Furthermore, when a phantom-load
transformer is overloaded, the waveform of the output current may be seriously distorted. On the best
modern test boards, the loading transformers are designed to avoid these shortcomings.
When using a phantom load for testing a three-wire, single-stator meter, one end of the voltage
coil must be disconnected from the incoming current lead by means of the voltage link due to the
tying together of the current coils on the load side. If this is not done, the current test circuit will be
connected across full voltage, with resulting damage to meter coils and phantom load. The discon-
nected end of the voltage coil is connected to the correct voltage source in order to energize the coil at
full voltage.
RESISTANCE LOAD
Resistance load is adjustable to provide the various test currents desired. In the resistance-loading
method, the current coils of the meter under test, the standard, and the loading resistance are con-
nected in series. Thus, the current that is permitted to flow by the resistance passes through both the
meter and the standard.
The resistance type of loading device usually consists of a group of fixed resistances of various
values which can be connected in any one of several series-parallel networks to give the total resis-
tance which will allow the current flow required for the test. These loading devices are calibrated for
298 specified voltages and the switches
are generally marked to indicate the
current each allows to flow so that
currents can be obtained in steps from
HANDBOOK FOR ELECTRICITY METERING
Voltage Source
A steady voltage source is required, particularly when indicating instruments are used as reference
standards. When a standard is the reference, with the current circuits of the standard and of the
meter being tested in series and their voltage coils in parallel, minor fluctuations in voltage or current
have no significant effect on the test results. In this case, minor changes in source or load effects both
reference standard and meter in the same manner. This does not mean that wide and rapid changes in
source voltage should be tolerated. Harmonics do not have the same effect on all meters and wave-
form distortion should be avoided.
Early meter test boards required a three-wire, three-phase voltage source. The three-phase feature
provided a convenient way to obtain a 50% power factor, single-phase test load. The connections are
fundamental and in some form are used for all meter testing.
The preferred source connection is a closed-delta transformer bank. Both open-delta and wye con-
nections may contain unduly large harmonics and will not provide a waveform as close to a pure sine
POTENTIAL
SOURCE
RM-15
REMOTE
RESET
OPEN SWITCH
POTENTIAL
FORM 2S LINK
240V
3-WIRE
PHASE
CONTROL
JUMPER
AUXILIARY
POWER
80–600 VAC
CURRENT
SOURCE
REMOTE
RESET
CLOSED SWITCH
POTENTIAL
LINK
PHASE
CONTROL
AUXILIARY
POWER
80–600 VAC
CURRENT
SOURCE
(Isolated Outputs)
pulses has been counted the test is automatically stopped. An error calculation can then be made
based upon the reading on the display of the standard in association with other test variables. Some
counters, such as the Radian Research RM-110, have the ability to automatically calculate and display
the error of the meter under test.
Meters can also be tested from their KYZ output, and some meters emit an analog calibration
signal. These meters can generally be tested using the Scientific Columbus MicroJoule Standard or the
Radian Research RD-21 Standard.
STEP 1
Check meter number and meter rating. Record this data.
STEP 2
Check for creep. Creep may occur either backward or forward. When all load is removed, a meter disk
may rotate for part of a revolution before coming to rest. This is not creep. All measurements of the
amount of creep should be based upon at least one complete revolution for electromechanical meters
and a change of more than 61 least significant digit in 24 hours. Although only an unusually rapid
rate of creeping will result in an appreciable registration, as a matter of principle no meter in service
should be allowed to remain creeping or with a tendency to creep.
In most induction meters, creeping is prevented by two holes or slots cut in the disk on opposite
sides of the shaft. When either hole is near the pole of the voltage coil, forces set up by the alternat-
ing field tend to hold the disk in this position.
STEP 3
Connect the meter and take “as found” readings. The connections for testing are the current circuit
of the standard is connected in series with the loading device and current coil of the meter under test,
and the voltage circuit of the standard is connected in parallel with the voltage coil of the meter under
test. When setting up a standard for making a test, the place selected should be reasonably free from
301
RM-DS/f
RM-1N
RM-1S
RM-1H
RM-1N
RM-1S
STEP 4
Examine the original condition of meter. The principal features are:
a. Check that the disk is centered in both the permanent magnet gap and electromagnet gap.
b. Check that the magnet gap is clean.
c. Examine the mesh of the first register gear with the shaft worm or pinion. This mesh should
be between one-third and one-half the depth of the teeth. A deeper mesh may cause binding.
A slight amount of play is necessary. Where the pinion or worm is short, or where the worm is
cut concave to match the curvature of the worm wheel, the vertical position of the moving ele-
ment must be such that the center of the pinion or worm is level with the register wheel which
it engages.
STEP 5 303
Check the register ratio as marked on the register to determine if this ratio is correct for the type and
capacity of the meter. Also check the watthour constant (kh) for the meter type and rating with the
STEP 6
Make adjustments. Since the full-load adjustment effects all loads equally, this adjustment should be
made first. If, after adjustment at full-load, light-load performance is more than 1% slow, a cause
other than maladjustment of the light-load should be investigated. Such cause may be unusual friction
or dirt. If the meter is clean and the register mesh is correct, the meter bearings should be suspected.
Reference the bearing maintenance for suggestions.
Power factor adjustment of single-stator meters is usually limited to shop testing.
STEP 7
Record final readings.
STEP 8
Seal meter and return it to service or stock.
LIGHT-LOAD ADJUSTMENT
This adjustment is normally made at the nameplate rating of voltage and 10% of rated amperes or test
amperes. It is accomplished by varying the amount of light-load compensating torque.
This adjustment is changed by shifting a coil so that its position with respect to the voltage-coil
is changed. No torque is produced on the disk as long as the light-load coil is symmetrical with the
voltage-coil pole. When the light-load coil is shifted, a torque is produced in the disk that will tend to
turn the disk in the direction of the shift. The coil is essentially a short-circuited turn of large cross
section placed in the air gap above or below the disk so as to embrace part of the voltage-coil flux.
Maladjustment of this coil may result in creep. Effect of this torque on meter percentage registration
is inversely proportional to the test load, one-tenth as much effect is produced at heavy load as at 10%
load.
When a meter, after adjustment at full-load, is found inaccurate at light-load, the cause may be
some condition in the meter that should be removed rather than compensated for. In such cases the
tester should locate the trouble, making no adjustments unless the meter is still inaccurate after going
over all the parts and restoring them to proper condition.
304 LAG ADJUSTMENT
This adjustment is ordinarily made only in the shop. The flux established by the voltage coil of a meter
should lag the flux of the current coil by exactly 90° with unity power factor conditions for proper
HANDBOOK FOR ELECTRICITY METERING
metering accuracy with any load power factor. This flux relationship does not exist because of the
inherent resistance of the voltage coil. Compensation to obtain the correct relationship is by means of
a lag coil or plate on the voltage pole acting with another lag coil on the current poles.
If the compensation is obtained by means of a coil, the adjustment is made by soldering the
exposed pigtail ends of the coil so as to lengthen or shorten the overall length of the coil conductor to
change the resistance of the coil. If a lag plate is used, the adjustment consists of shifting the position
of the plate under the voltage pole radially with respect to the disk by means of an adjusting screw.
On some meters the lag adjustment is made by punching a lag plate during the manufacturers’ testing
and cannot readily be changed in the field.
The test to determine the lag or phase adjustment is generally made at 50% lagging power factor
with rated amperes and voltage applied. A 50% power factor is used because it can be obtained readily
from a polyphase circuit without auxiliary equipment.
In some meters, there is interdependence between the light-load and lagging power factor adjustments
so that a change in light-load in one stator may effect the lagging power factor performance of the
same stator. If more than one light-load adjuster is provided, it is good test practice when light-load
adjustment is required in a series-parallel test, particularly in field tests, to make equal changes with
each light-load adjuster.
The full-load adjustment on multi-stator meters, operating on the braking magnets, has an identi-
cal effect on all stators. Hence, it cannot be used for torque balance. One or more full-load adjusters
may be provided on multi-stator meters.
PHOTOELECTRIC COUNTERS
Modern test fixtures do not use a manual voltage switch for applying voltage to the standard meter. A
photoelectric counter that contains photoelectric devices and associated equipment for automatically
starting and stopping the standard watthour meter controls voltage. For this test method, a light beam
is directed through the anti-creep holes or reflected from the flag of the disk of the watthour meter
under test and illuminates a photodiode or transistor. This illumination causes pulses to be transmit-
ted to the control equipment where they are amplified and used to operate digital displays, which, in
turn, operate relays controlling the voltage circuit of the standard watthour meter. This is done in
accordance with a predetermined number of revolutions of the watthour meter disk.
It is important that the start/stop relays have exact or symmetrical reaction times. For this reason,
some designs use two relays for the start and stop functions, arranged in such a way that they both
pull-in to perform their function. Other designs use a single symmetrical reed relay controlled by zero
crossing switching circuits to close the relay at zero voltage and open it at zero current. This method of
zero crossing switching eliminates the need for arc suppression components used in standard designs
that, with time, can cause testing errors.
OPTICAL COUPLER
An optic coupler can either sense revolutions of a meter disk by sensing the black mark on the edge of
the disk or by sensing infrared light-emitting diode (LED) test pulses in a solid state meter.
These methods of shop testing and counting watthours eliminates the necessity of manually
counting the revolutions of a meter disk or solid state disk emulator and, since the starting and stop-
ping of the watthour standard is automatic, human errors are eliminated.
The ability to test the watthour accuracy of the solid-state meter is not the only concern. Solid-
state meters have functionality that far exceeds simply watthours. A single solid-state meter can record
forward and reverse power, forward and reverse reactive power, forward and reverse VAhours, voltage,
current, and more. A single meter can now take the place of many meters at certain customer loca-
tions. In addition to having better accuracy, this, of course, reduces the quantity of meters necessary to
install and maintain, translating into cost savings.
With new electronic test equipment, quality and accurate testing that provide flexibility and
convenience became available. New electronic test equipment has reasonably low power requirements.
It is no longer necessary to have a three-phase source to run the test equipment. Since the test equip-
ment is electronic, even true three-phase testing can be easily accomplished by simply plugging the test
equipment into a conventional 120VAC outlet. With this low power requirement, the test equipment
can be easily operated from a power inverter. Some utilities now make use of vans as mobile testing
laboratories.
Many utilities desire to conduct testing which is outside the normal American National Standards
Institute (ANSI) testing requirements for the utility. There are available standard production models of
electronic meter test equipment that will allow testing from 10 milliamps to 225 amps and with true
three-phase capability. The utility can run tests that previously were only able to be run by the meter
manufacturer.
Cost is obviously a big concern for most utilities. New electronic test equipment for shop, van,
and field-testing must provide not only quality and flexibility but also features which relate to savings
for the utility. Electronic test equipment is available that can have multiple test stations. Using one
computer, a single tester can operate more than one test station. The test stations are independent,
allowing the tester to test different meter forms at the same time, which increases throughput.
PROCEDURE VARIATIONS
Variations should be made based on the age and condition of the meters under test.
With manufacturers’ certified accuracy tests, new meters may not be tested at all before being
placed in service, or they may be sample tested, or completely tested. However, tests of new meters
seldom go beyond the step of taking the “as found” test if they are found to be within the established
accuracy limits.
Meters from service that are to be tested and returned to service are usually subjected to the entire
test procedure. Under certain conditions, it may be deemed advisable to take no further tests if the “as
found” test shows that the meter is operating satisfactorily.
Meters from service which are to be retired may have an “as found” test if local requirements
require it or the utility chooses to do so.
SINGLE-STATOR METERS
The following procedure for single-stator meters is typical for a complete shop test. All companies
may not use all of the steps listed, and the order given may be varied. Utilities that have an electronic
meter records system will reduce or eliminate the need to record meter data and initial set up of the
meter test. For most solid-state meters, Steps 3 and 5 are not required.
Step 1
a. Check nameplate for wire, phase, volts, and amperes.
b. Connect standard on proper voltage and current coils.
c. Open meter voltage link, if necessary.
d. Visually inspect the meter for any physical damage, overheating, or over voltage and current
damage.
e. Connect meter.
f. Check for creep by applying voltage only.
Step 2
a. Start “as found” test.
b. Record meter number, nameplate data, and reading.
c. Record “as found” test results. “As found” test load points are suggested as follows:
— Full-load at 100% of the current rating or test amperes of the meter; 100% power factor;
— Light-load at 10% of the current rating or test amperes of the meter; 100% power factor; 309
— Lagging power factor (if required) at 100% of the current rating or test amperes of the
meter; 50% power factor with lagging current.
MULTI-STATOR METERS
Multi-stator meters usually have two or three separate stators. Each stator should exhibit accurate
performance by itself as well as having good accuracy with all stators combined. This is evident with a
three-wire, three-phase circuit metered with a two-stator meter. With a balanced-load power factor of
86.6% lagging current, one meter stator is operating at unity power factor and the other at 50% power
factor, lagging current. This leads to the additional test adjustment of polyphase meters, balancing the
performance of the stators to provide the necessary separate stator accuracy.
The balance test is made by connecting all voltage coils in parallel and applying 100% of rated cur-
rent or test amperes of the meter to each current circuit, first at unity power factor and then at 50%
power factor, lagging current. Calibration of each stator is checked for both currents. In meters which
have current circuits which are common to more than one stator, such as the Z-circuit in two-stator,
four-wire wye circuit meters, the common current circuit is not energized during the balance test.
Accuracy limitations for this test are established in accordance with local requirements. If the
accuracies are not within the required limits, the following adjustments are made on electromechani-
cal polyphase meters. There are no adjustments on solid-state meters.
With unity power factor, the torque balance adjusters on the individual stators are used. This
additional adjuster allows adjustment of individual stator performance without changing the perfor-
mance of any other stator. Thus, the individual stator performances may be adjusted to agree within
the specified limits at unity power factor. In meters where the torque-balance adjustment is omitted
from one stator, the performance of the other stators is adjusted to match that of the first.
With 50% power factor, the usual lag adjustment on each stator is used. If the lag adjustment is a
fixed factory-made adjustment, the meter tester cannot easily change the lag balance. In meters where
the light-load and lag adjustments are not entirely independent in their effects, the meter tester must
remember that a change in light-load adjustment after establishing lag balance may have a detrimental
effect on such balance.
After the balance adjustments are made, the “as left” calibration is made by connecting all voltage
coils in parallel and all current coils in series and making tests at the usual light, heavy, and lagging
power factor loads. If adjustment is required on heavy load, the full-load braking magnet adjuster is
used, resulting in an equal effect on the performance of all stators. If lagging power factor adjustment
is required, equal changes are made with each lag adjuster to maintain as closely as possible proper lag
balance. Similarly, required light-load adjustment would be accomplished by equal changes on each
stator. However, on meters that have a light-load adjuster on only one stator, this procedure is not
possible.
310 MULTI-FUNCTION METERS
In addition to active energy (kWh), many solid-state meter types are capable of metering alternate
electrical quantities. The most common alternate quantities are apparent energy (kVAh) and reactive
HANDBOOK FOR ELECTRICITY METERING
energy (kVARh), also called 4 quadrant. These meters, in addition to visual indicators, usually also
have a test output signal that can be used to verify calibration. Because this test output signal can be
used for both active energy and alternate energy, there is a method for the user to select which quan-
tity will control the output signal. Common methods of control are a special command through the
optical communication port of the meter, or manually scrolling to a specific display quantity.
Like active energy, metering test points for alternate quantities are usually taken at test amperes,
light-load, and 50% power factor. When setting up to test reactive energy, power factor angles must be
changed by 90°. For example, to obtain the nameplate test output rate for kVARh, the meter must be
set for test amperes, test voltage, and a 90° angle between the voltage and current. Meter manufactur-
ers may have written documentation that states that reactive and apparent energy is as accurate as the
true power in watts as tested in the meter.
CALIBRATING CONSTANTS
In multi-coil meters, the value of one revolution of the meter disk (or equivalent disk revolution for
solid-state meters), the kh, varies with the test connections. The test kh is sometimes called the cali-
brating constant. When the same current passes through more than one full current coil (or current
sensor for a solid-state meter), the calibrating constant can be found by dividing the normal kh of the
meter by the number of current coils in the meter connected in series. Table 12-1 checks such calcula-
tions. Calibration constants for alternate energy quantities are usually the same as for active energy.
The calibrating constant will be one when using three element watthour standards such as the
Radian RM-11 when each meter element current circuit is isolated to one current circuit in the
standard.
CUSTOMER RELATIONS
On entering a customer’s premises to perform a meter test, testers should make their presence and
purpose known to someone on the premises. As employees of the utility company, the meter testers
can request access to the premises and the company meter. They must, however, recognize that they
represent the utility so must remain courteous and respectful.
It is important, however, that the tester not interrupt the customer’s service without notification.
Every precaution should be taken to avoid damaging the property of the customer and consent should
be obtained before making use of any furniture or equipment to assist in making the test. In case of
an accident resulting in damage to the customer’s property, a prompt report should be made to the
customer and to the company.
SAFETY PRECAUTIONS
It is important that the tester exercise all possible care to avoid accidents. In the interest of safety and
the tester’s well-being, the prohibitions and suggestions that follow should be continually in mind.
• Beware of dogs. If bitten, immediately go to a physician and then report the injury to your
supervisor.
• Exercise care when entering customer’s’ premises. Be on the lookout for nails, tripping hazards,
low beams, or other overhead projections.
• Carefully examine ladders, boxes, and supports expected to carry your weight before making use
of them.
• If the apparatus to be worked on is in a dangerous condition, or is so located as to be hazard-
ous, a complete report should be made to your supervisor and the location should be passed
without doing work.
Table 12-1. Calibrating Constants. 311
*In a single-stator, three-wire meter the individual current windings are half coils.
• Do not attempt to make connections until proper light is arranged. A flashlight should be used
until your portable lamp is connected.
• The use of matches or open flames on a customer’s premises is prohibited.
• Attention should be concentrated on the points where the tester is working; do not attempt to
do two things at once.
• Only one jumper should be connected at a time. Before connecting a jumper or a test lead,
be sure you know where the other end is. If necessary, tape it over or tie it in a safe location.
Having connected one end of the jumper, be sure that the final connection of the free end does
not create a short circuit. Always check with your voltage tester.
• All connections must be made securely to avoid possibility of their dropping or being pulled
away from original location.
• All wires, jumpers, test leads, instruments, and other equipment should be so placed that they
may not be run into or tripped over by people passing by.
• Use your voltage indicator to determine whether or not the meter, the meter box, or conduit are
alive to ground as a result of insulation failure.
• Every tester should be familiar with his or her company’s safety rules.
• Use personal protective equipment as required (work gloves, insulating gloves, safety glasses,
face shield, flame retardant clothing, etc.).
connections and possible hazards. When a connection is discovered which apparently was made
by an unauthorized person and which might influence meter registration, a report should be
made with a sketch of the connections as found. Do not alter such connections. Do not test
meter. Report conditions to your supervisor at the earliest opportunity. If hazardous conditions
are found, report them to your supervisor and defer test of this meter until the hazard has been
removed.
7. Check voltage and record unusual readings.
8. Note whether or not there is a grounding conductor.
9. Make sure that the grounded or neutral conductor of a two-wire service is properly connected
to the voltage and not to the current terminals of the watthour meter.
The first purpose of all field tests is to determine the actual accuracy condition of the meter “as
found,” the exact condition the meter is in at the time of test. To meet this requirement, the meter
must not be disturbed in a manner that would alter the normal operating condition existing before
start of test. The cover of the watthour meter is not removed until after completion of the “as found”
test.
Figure 12-19. Phasor Relations of Voltage and Currents in Lag Test of Multi-Stator Watthour Meter.
TEST PROCEDURE
With the meter disconnected from its instrument transformer, proceed to test as a self-contained
meter, with multi-stator meters connected with current coils in series and voltage coils in parallel.
Additional individual stator tests may also be required for stator balancing. Three-stator delta meters
present special problems.
When large loads are served from a delta power bank, power factor tests may be required and
should be made while testing individual stators rather than with the series-parallel connection. Lag-
ging power factor values should match the unity power factor performance values in each individual
stator so that proper balance is obtained under all conditions of loading. Since on delta circuits errors
in power factor balance effect meter performance on unity power factor loads, the tolerance for power
factor balance should be narrow.
With unusual loads it is sometimes desirable to make a running load test, which uses the cus-
tomer’s three-phase load instead of the phantom load.
Such tests require two standards for three-wire, three-phase meters and three standards for four- 315
wire meters, with a standard current coil in series with each meter current coil. The algebraic sum of
the standard registrations is used to determine meter performance. Figure 12-20 shows test connec-
tions for a running load test on a two-stator, three-wire meter.
NETWORK METERS
When meters are installed with current transformers but not with voltage trans formers, which is
often the case when customers are served from a 120/208 volt network, the test switch voltage blades
may present a hazard. The voltage supply to the meter is taken from a high-capacity power transformer
instead of from a low-capacity instrument transformer. As a result, an accidental short circuit of the
voltage conductors can result in a severe arc. Unfortunately, in many test switches the voltage switch
blades are live when open and protrude beyond the test switch barriers. When this is the case, an
insulated enclosure to cover the live switch blades will prevent accidents due to falling tools or contact
with other metallic objects.
Figure 12-20. Test Connections for Two-Stator, Three-Wire Meter Using Customer’s Load and Two Standards.
316 THREE-PHASE, FOUR-WIRE DELTA, THREE- STATOR METERS
This type of meter is unusual as compared with other meters, especially from a standpoint of test-
ing. Since it consists of one stator with a voltage rating of twice either of the other two stators and
HANDBOOK FOR ELECTRICITY METERING
a current rating of one-half of either of the other two stators, the usual method of series tests and
balance test cannot be used. The common practice is to calibrate each stator independently, although
the two like stators can be tested in series and also balanced against each other. Providing the correct
ratio current transformer and voltage transformer so that the higher voltage stator can be connected
essentially in series-parallel with the two lower voltage stators, a series test can be made. This requires
an accurate step-up voltage transformer and an accurate step-down current transformer. For more
detailed discussions, see manufacturers’ publications.
Meter Test By
Indicating Wattmeter
Load is applied to the meter
and watthours are measured by
means of indicating instruments
and timing devices, such as
stopwatches or chronographs.
The time is usually that required
for some convenient and prede-
termined number of revolutions
of the meter under test. The time
required for an integral number
of revolutions of the meter is
measured by a stopwatch and
the power, in true watts, during
Figure 12-21. Mobile Meter Testing Facility. the same period is measured by
means of indicating instruments. The ratio between the indicated or meter watthours and the true 317
watthours, as determined by the indicating instruments, multiplied by 100 is the percent registration
of the meter under test.
Meter Maintenance
CAUSES OF CREEPING
The causes of creeping may be classified as follows:
1. Incorrect light-load compensation
2. Vibration
3. Stray fields, either internal or external
4. Too high voltage, which has the same effect as overcompensation of light-load adjustment
5. The voltage circuit is connected on the load side of the meter
6. Short circuits in current coils
7. Mechanical disarrangement of the electromagnetic circuit of the meter. A high-resistance short
or ground in the customer’s circuit can cause a turning of the rotating element which may
be mistaken for creeping. Therefore, residence wiring should be isolated from the meter when
checking for creep.
If a short-circuit is present in the current coils it will probably be difficult to stop creeping. Volt-
ages being induced in the current coils by the voltage magnetic flux and resultant current low in the
shorted current coil turns cause the creeping, due to current coil shorts.
CAUSES OF INACCURACIES
There are multiple reasons why a meter may become inaccurate. For induction meters, this could
be caused by friction, bearing magnets, registers, and/or a failed coil. Friction can be caused by an
unleveled meter or foreign material. Proper disk position is created by the magnetic bearings, worn
parts, or foreign material. Registers in meters can become worn or misalignment can occur over time.
Demand Meters
KILOWATT DEMAND is the kilowatt load averaged over a specified interval of time. The meaning of
demand can be understood from a typical power curve as shown in Figure 13-1. In any one of the
time intervals shown, the area under the dotted line labeled demand is exactly equal to the area under
the power curve. Since energy is the product of power and time, both of these two areas represents the
energy consumed in the demand interval. The equivalence of the two areas shows that the demand for
the interval is that value of power which, if held constant over the interval, will account for the same
consumption of energy as the real power. It is then the average of the real power over the demand
interval.
The demand interval during which demand is measured may be any selected period but is typi-
cally 15 or 30 minutes. The demand period is determined by the billing tariff for a given utility’s rate
schedule.
Demand is typically explained in terms of power (kilowatts), but may also be expressed in kilovolt
amperes reactive (kVAR), kilovolt amperes (kVA), or other suitable units.
319
320
Power Curve
Handbook for Electricity Metering
Demand
2. Another factory (Figure 13-2b) uses the same number of kilowatt-hours of energy per month
but consumes all of it in a single eight-hour shift every day of the month. The average power is
therefore three times greater than for the pump plant and the rating (and size) of equipment
installed by the utility to furnish the factory with energy must also be about three times higher.
Costs rising from capital investment are a much greater factor in billing this consumer than in
billing the operator of the pump plant.
Demand is an indication of the capacity of equipment such as transformers, service wires, and
distribution lines required to furnish electricity to individual consumers. Kilowatt-hours or energy
per month is not a true indication of the rating of equipment the utility must install to supply a
particular maximum power requirement during the month without overheating or otherwise straining
its facilities. What is needed in this case is a measure of the maximum demand for power during the
month. The demand meter answers this need.
With the evolution of metering from a mechanical to a fully solid-state product, the manner and
methods used to measure demand have changed. When the concept of demand was first implemented,
kilowatt (kW) demand was the measure of choice, despite the fact that the true maximum stress that
utility equipment experiences is the maximum kilovolt amperes (kVA). The kVA takes into account
the real power watts, and the reactive power VARs, as one quantity. However, determining kVA in
a mechanical environment was more costly to measure as compared to kW demand, which can be
metered with a single device. With the introduction of electronic solid-state meters, the determination
of kVA demand has become more effective as it can be metered with a single device.
Demand Meters
1000
kWhs
Rated
Load
1000 kWhs
This method of measuring kW demand came about because the electromechanical meter could
only measure one quantity at a time, e.g., watthours. Measuring only real power to determine the
maximum demand the customer is using is only part of the real load. The full impact of load is actu-
ally derived from the maximum kilovoltamperes, kVA, demanded by the customer.
KVA
2 2
KVA = KW + KVAR KVAR
KW
Figure 13-3. Power Triangle.
322 The capacity of most electrical equipment is limited by the amount of heating it can stand. Heat-
ing depends on the apparent current flowing through the equipment by two components: the real
current and the reactive current. In addition, the maximum stress on the equipment not only depends
on the size of the load or the apparent current, but also on the length of time the current is main-
Handbook for Electricity Metering
tained. A momentary overload, such as the starting surge of a motor, will not cause a temperature rise
sufficient to break down insulation or otherwise damage any utility equipment. For this reason, the
utility does not use a momentary value of maximum kVA, but maximum average kVA over an interval
as a basis for billing.
General Classes
There are three basic types of demand registering meters in use:
1. Mechanical—meter and register
• Integrating type of demand meters
i. Indicator (pointer and dial)
ii. Cumulative
2. Mechanical meter and electronic register
• Electromechanical watthour meters with electronic demand register
i. Electronic demand registers with time-of-use (TOU)
ii. Electronic demand registers with TOU and internal data recorder
3. Electronic—meter and register
• Electronic watthour meter and electronic demand registers
i. Electronic demand registers with TOU
ii. Electronic demand registers with TOU and internal data recorder
All of these meters measure power so that the registered value is a measure of the load as it effects
heating and therefore the load-carrying capacity of the electric distribution equipment. The demand
meter’s main function is to provide billing and load information for use in pricing.
Demand Meters
Integrating Type of Demand Meter
Electromechanical Watthour and Demand Meter—Design Description
The electromechanical watthour and demand meter, as its name implies, combines an electromechani-
cal watthour meter and mechanical demand meter into a single unit.
In a mechanical watthour demand meter, the watthour disk shaft drives two devices:
1. The gears and dial pointers through which the revolutions of the rotor are summed as kilowat-
thours of energy
2. The gears and shafting, which, working in conjunction with a timing motor or a clock, sum the
revolutions of the rotor during each demand interval in terms of kilowatts of demand
These two devices, after their initial gearing to the disk shaft, are independent of each other and
are comprised of two separate registers. They are commonly combined physically and are referred to as
the watthour demand register.
Two types of mechanical watthour demand meters commonly in use are:
1. The indicating type. This type indicates only the maximum average demand for each month or
other period between resettings. Indicating demand meters are further segmented into either a
pointer or a dial register type.
2. The cumulative type. This type also indicates the maximum demand during the period between
resetting, and by means of the resetting operation, the maximum demand for the period that
just ended is transmitted to dials and added to the total of previous maximums.
The gears, dials, and pointers by which the disk rotations of a mechanical watthour demand meter
are translated into kilowatthours of energy are the same, in principle, as all mechanical watthour
meter registers.
The demand pointer-pusher or dials rotates a number of degrees proportional to energy utilization
of each demand interval. At the end of every demand interval, the timing mechanism performs two
operations:
1. It releases a clutch, mechanically breaking the connection between the meter rotor and the
pointer-pusher or recording mechanism.
2. It returns the pointer-pusher to the zero point.
Then the clutch is re-engaged and the summing-up process begins again. The process of returning
the pointer-pusher to zero at the end of each interval takes only a few seconds.
The timing mechanism may be actuated by voltage from the metered circuit, by voltage from a
separate circuit, or the mechanism may even be a spring-driven device.
Indicating Type (Pointer)
The maximum demand is indicated on the graduated scale by the sweep-hand pointer. During each
demand interval, the demand pointer-pusher advances proportionally to the kilowatt demand. If the
demand for a given interval is higher than any previous demand since the pointer was last reset, the
pointer-pusher pushes the pointer upscale to indicate the new maximum demand. The pointer is held
in this position by the friction pad. See Figure 13-4.
Indicating Type (Dial)
The dial type demand register uses an indicating type demand register mechanism in much the
same manner as the pointer type demand register. However, the demand reading is in dial form versus
a sweep-hand pointer scale. The dials return to zero when the monthly reset is performed. This type of
demand display has a better resolution than the pointer type due to a longer equivalent scale length
and is easier to read. See Figure 13-5.
Cumulative Type
The cumulative watthour demand meter goes one step further than the indicating watthour demand
meter. A pointer, moved across a scale by a pointer-pusher mechanism, preserves the maximum
demand until the meter is reset. The principle is the same as in the indicating meter but the pointer
324
Synchronous Timing Motor
Cam
Handbook for Electricity Metering
Plate
Geneva Reset Pin
Elapsed Time Gear to Motor Shaft 1
Indicator Kilowatt-Hour Mechanism
Gear Train Section Gear Tail
Transfer
Gear Transfer Worm Shaft 1
Gear
Clutch Spring
Clutch Lever Assembly
Sector Gear
Gear “A”
Pointer-Pusher Gear
Pointer-Pusher Screw
Shaft “A” Pointer Dog
Friction Pad
Pointer Shaft Pointer-Pusher
Clutch
Maximum Demand Pointer
and scale are much smaller. In addition, the cumulative type demand meter preserves a running total
of the maximum demands for consecutive months on small dials similar to watthour meter dials. The
maximum demand for each month is added to the previous maximums on the dials when the meter is
reset at the end of the month.
Except for the resetting device and the cumulative gear train, pointers, and dials, the cumulative
demand register is the same in principle and operation as the indicating demand register. See Figures
13-6 and 13-7.
Demand Meters
Timing Motor
Reset
Clutch Pin
Lever Sector Gear
Clutch Pivot
Hollow
Shaft
Shaft A
Clutch Spring
Gear A
Pointer
Pointer-
Friction Pad Dog Pointer-Pusher Screw
Timing Motor
Gear B Gear A
Dog
Gear C
Depressing Pins 2 Gear D
Pin
Pin 1
Resetting Screw
Resetting Shaft Pointer-Pusher
Knob Slots
Maximum Cork Faces
Demand
Indicator Gear E
Gear F
Cumulative
Demand Dials
Display Switch
End-of-Interval/
Demand Threshold
Output
Test Switch
Clock
DC Power
Power Fail
Clock Circuits
Power Supply Detector
50 / 60 Hz
•
AC Line Power
10
Demand Meters
9
11
7 13
5 14
6
3
2 VM-60 METER
1 8
4
12
15
3. Count and accumulate pulses for successive demand intervals and detect and store the value in
which power consumption was at its peak and, at the end of each interval, reset the count to
zero in preparation for the next interval.
Programming
Electronic registers may be pre-programmed with parameters such as:
1. The energy value of each input pulse
2. Demand interval length (for fixed or rolling calculations)
3. Type of demand display (maximum, cumulative, continuously accumulative)
4. Display format (how many digits and the decimal location)
5. Items to be displayed
6. The function of the output switch (e.g., pulse initiator, end-of-interval, demand threshold alert)
Making changes in software allows one hardware design to serve a variety of applications. Program
changes are analogous to a mechanical meter manufacturer selecting different gear ratios, dial scales,
and timing motor speeds.
New Functionality
With the introduction of digital processing into the mechanical watthour meter, new capabilities
and options have become available to utility personnel which impact how the demand is determined,
provided, and verified.
328 Rolling-Demand Capability
Rolling demand, also called sliding window, is a process by which intervals are divided into a fixed
number of subintervals. Instead of calculating demand at the completion of each interval period, the
calculation is performed at the end of each subinterval, at which time subsequent subintervals are
Handbook for Electricity Metering
totaled and averaged for the entire interval. Greater precision in determining the true peak demand
can be applied by utilizing the rolling demand capability of an electronic register. For example, in
the two curves shown in Figure 13-10, the kWh power consumption is the same, but the maximum
demand determined by the meter provides a truer picture of the customer’s peak load when the
Watts
Power
Maximum Demand
A B C Time
Interval Data (a)
Watts
Power
Maximum Demand
1 2 3 4 5 6 7 8 9 Time
P
Q
R
S
T
U
V
Demand Meters
Display Modes
Electronic demand registers display several types of information. The normal display mode presents
information needed on a regular basis such as data related to billing. An alternate mode can display
information useful to field technicians or shop personnel for verifying register program constants used
in the demand determination. A test mode provides information for testing, like demand run up.
Demand Forgiveness
Another feature that has been introduced with the advent of electronic registers is the concept of
demand forgiveness. Also referred to as power on demand delay timing, demand forgiveness is achieved
by delaying the start of the demand interval and, therefore, the demand measurement upon service
restoration after a power outage of a significant duration. Typically, when establishing this option the
utility must specify how long to wait after power is restored before beginning the demand calculation
and how long the power outage must be for the meter to trigger the demand forgiveness feature.
Output Signals
Most electronic demand registers are capable of providing output signals for communicating with
external monitoring and control equipment. These output signals are generally a relay closure activated
by the microprocessor. Outputs can include a pulse initiator output (KYZ), an end-of-interval signal,
and a demand threshold alert.
Demand Resolution
Many electronic registers provide resolution of one or more places to the right of the decimal point.
This increased resolution makes it possible to capture readings closer to the true demand. In most
cases, the improvement in resolution yields a higher reading. This is especially true with instrument
transformer rated services when billing constants are applied to all collected readings.
Improved Testability
Mechanical demand registers are tested by inputting enough meter disk revolutions, directly or from
a test board, to drive the demand pointer(s) to a point where the demand register is most accurate,
typically above 25% of full scale, within the time window of the register’s demand interval. If an
adjustment is required, the test is repeated, thereby resulting in several more demand intervals of time
to complete the test procedure.
Electronic demand registers are typically not adjusted or calibrated. If a register is defective, most
utilities simply replace the electronic module. However, if a test is required, it can be achieved by
simply injecting a few test pulses to verify the demand calculation, relying on the fact that the register
is counting pulses, and it is equally accurate across its entire scale. Registers which incorporate a test
mode may further assist in this verification.
The indicated demand values can be reset (zeroed) by a mechanism mounted on the meter cover
or by an accessory device, such as a portable reader programmer or internally generated self-read,
self-reset, feature.
Demand Meters
meter. All data values and program parameters are stored in nonvolatile memory, and a battery is not
required for data storage unless TOU and/or load profile is added to the meter as an option.
Due to the advanced functionality available within an electronic meter, it may actually be four
meters in one—demand, demand load profile, TOU, and TOU load profile—depending on how it is
configured and programmed. Like the electronic register, electronic meters can be programmed and
read through the meter’s optical port with a manufacturer’s software installed on a laptop computer.
The electronic meter may also include option boards for remote communications or pulse outputs.
Phasor (S)
Reactive (Q)
Apparent (U)
Active (P)
Distortion (D)
Demand Meters
read on time or late. The second peak should be configured conservatively to handle the cases when
the billing period is short either because it was read late last month and/or it is read early this month.
This is typically set to 18 or 19 days.
As an alternative to the self-read demand process, cycle insensitive demand meters provide greater
flexibility to read meters early or late without estimating bills. Meters can be moved to a different
route without reprogramming the calendar and only one calendar needs to be maintained for the
entire utility.
Demand Calculated From Interval Recording
With this optional method for determining demand, the utility collects the interval reads (15- or
30-minute intervals) either monthly or more frequently from remotely read interval recording meters.
Once the interval data has been retrieved, it can then be used (external from the meter) to calculate
the maximum demand. Meter Data Management Systems (MDMS) are often used for processing
interval data, calculating monthly peak demands. Many other determinates, such as TOU, can also be
determined using similar means. Even if 15-minute interval data is recorded and a 30-minute demand
period is required for billing, the processing engine (MDMS) can add multiple 15-minute blocks of
data into 30-minute intervals for calculating the maximum 30-minute billing demand.
Two other areas where interval data may be used in lieu of relying on the meter itself to perform
a calculation is when considering both a kVA and/or a coincidental peak demand determination. In
both cases, the raw data in the form of interval data must be available from the meter to perform the
calculation. This type of calculation is also typically performed by the utility’s MDMS or some other
internal system. In the case of kVA, interval data for both watthours and VAR hours must be avail-
able. However, in using this method for determining kVA, only the power triangle calculation may be
utilized. The arithmetic method of calculating kVA may only be utilized within the meter itself.
The primary difference between this methodology and the previous method discussed is that by
using interval data, the monthly peak demand determination is moved from the meter itself to an
external system/process. The configuration of the meter may, therefore, be simplified by just becoming
a source of the interval data and no longer be required to calculate the demand values. It also elimi-
nates the need for any type of demand reset command to be performed by the meter.
Daily Demand Readings
A hybrid approach between the traditional and interval data methods of determining demand is the
daily demand approach. This methodology requires remote communications to the specific demand
meter and primarily resolves when to send a demand reset command to the meter. All normal demand
calculations are performed within the meter. However, a demand reset is performed at the conclu-
sion of every communication session. If the communications with the meter occurs every day, then,
effectively, a series of daily demand readings are collected and stored within the utility billing process.
The billing system must then be set up to sort through all the demand values collected and choose the
highest value as the monthly peak demand for that billing period.
Accuracy Impacts in Determining Demand
Electronic watthour meters compute the product of voltage and current and integrate this product
over time to compute energy. The product of voltage and current is instantaneous power and varies
continuously with the power system AC waveform. Instantaneous power has little practical economic
value, so what is of interest is the average power supplied over some significant period of time. Elec-
tronic demand meters accomplish this function by measuring energy over a defined demand interval.
The reading provided is the average power (in watts) computed by dividing the interval energy by the
demand interval.
Although there are a number of ways to accomplish the computation of the product, at a basic
level, all methods require input signals proportional to system voltage and the delivered current. Volt-
age measurement is most commonly derived from a signal scaled through a resistive divider network.
It can also be derived from the output of a potential transformer. Voltage signals with an uncalibrated
accuracy of 2% are easily obtained. Current signals may be obtained by a number of methods and
334 may have typical uncalibrated accuracies of 65%. Since metrology function with a required accuracy
of 60.2% is not uncommon, it is necessary to provide a mechanism for the calibration of the system.
This can be accomplished by providing adjustments for gain and phase errors in each measurement
element. The corrections can be applied either to the voltage and current, or directly to the product
Handbook for Electricity Metering
depending on the computation method. Although physical calibration adjustments may be made, it is
more economical to provide computation adjustments through the use of calibration coefficients that
are programmed into the device at the time of manufacture.
In many cases the measurement quantities are computed by the means of digital signal process-
ing techniques. In this method the input signals must first be converted to digital samples. Once
the quantities are digitized, the results may be computed in the digital domain by an embedded
microprocessor or digital signal processing element in the meter. There are a number of methods for
digitization of signals in what is referred to as an analog to digital converter circuit. These methods
require the comparison of the input signal to a known accurate reference signal. The fundamental
inaccuracies of the reference are typically on the order of the meter’s stated accuracy and must also be
compensated for in calibration.
In order to integrate power accurately to measure energy, the meter must also have an accurate
time-base. Fortunately, an electronic time-base is easily and inexpensively derived by either using the
utility’s line frequency or by using quartz crystal oscillators. The uncalibrated accuracy of an inexpen-
sive oscillator is typically better than 0.005%. Since this is orders of magnitude greater than meter
accuracy, it is not normally a source of significant error.
Calibration of the watthour meter is normally performed to compensate for component toler-
ances, and the compensation is most commonly performed digitally with the compensating factors
stored in memory where they are not subject to inadvertent change or drift. Watthour meters provide
calibration outputs proportional to watthours that may be used to verify the device accuracy. Since an
accurate watthour measurement requires the same fundamental inputs as demand measurement, the
correct calibration of watthours ensures that associated demand measurement is equally precise.
Chapter 14
Demand Meter
Testing and Maintenance
There are various types of test procedures and maintenance suggestions for demand meters.
Principle of Operation
The demand gear train drives a pusher arm which advances the demand indicator in proportion to the
speed of the meter disk, which itself is proportional to the demand.
At the end of a predetermined interval, usually 15 or 30 minutes, the pusher arm is momentarily
disengaged from its gearing and returned to zero by a motor, a spring counter torque, or a gravity-
driven mechanism. The time interval during which the pusher arm is advanced is controlled by a
synchronous motor.
A test of a mechanical demand register must satisfy these three questions:
1. Is the advance of the indicator correct?
2. Does the reset operate correctly?
3. Is the time interval correct?
To make a clear distinction between the space interval covered by the advance of the indicator and
the demand interval controlled by the timing mechanism, the latter will be referred to as the “time
interval” in this chapter.
Advancing Mechanism
Since the pusher arm which advances the demand pointer is geared to the watthour meter shaft, the
accuracy of the demand indication is dependent upon the accuracy of the watthour meter. Therefore,
the watthour meter must be calibrated correctly if the demand indication is to be right. The register
ratio of the demand register must also be correct for the application.
The register gearing must not impose a heavy or variable load on the meter. In other words,
excessive register friction due to dirt or improper gear mesh must not exist. When demand meters are
335
336 located in areas with unusual dust, dirt, or fumes, it is standard practice to clean the demand register
thoroughly before reinstallation. It is also a good practice to ensure that all demand registers are
thoroughly cleaned as they come into the shop for routine tests.
Cleaning methods vary from the use of standard cleaning machines that utilize a cleaning solu-
Handbook for Electricity Metering
tion, a rinsing solution, and a drier, to more modern type of ultrasonic cleaner. The cleaning solu-
tions, if used, should be nontoxic and rinsing solutions should be acid free and not leave a film on the
cleaned parts. Carbon tetrachloride should never be used for cleaning purposes because of the cumula-
tive toxic effects that it may have.
After a register has been cleaned, a thorough examination should be made to detect faulty gears,
worn bearing holes, and insufficient or excessive end shake of the various shafts. Particular attention
should be given to worm gear assemblies because malformation of the gear edges can cause a jerky
advance of the succeeding gears.
Clutch
To permit reset of the pusher arm at the end of the demand interval and the reset of the maximum
demand indicator to zero at time of test, there is a clutch in the demand gear train between the meter
disk and the pusher arm.
The clutch usually consists of two flat disks with a felt washer in between which exerts the proper
amount of friction. Some registers employ a cam-operated arm to disengage the clutch during the
reset operation while others merely slip the clutch under full tension. While the adjustment of clutch
tension is not critical, it should be checked to determine that it falls within the recommended limits,
particularly if the register has been cleaned or disassembled for overhaul. Tension testing devices are
available.
The felt friction pads must be dry to ensure proper operation and should never be subjected to
cleaning fluids. If the register is to be put into a cleaning solution, the pads should be removed and
then replaced after the register is dry. In many cases, the pads can be removed without dismantling
the clutch assembly by slitting the pad radially with a very thin knife. New pads may be installed
similarly, making sure that the pads, after insertion, lie flat on the disks.
Resetting Mechanism
At the end of the demand interval, the pusher arm must be returned to zero. This requires that a
counter-torque be applied to the pusher-arm side of the clutch.
In various types of registers, the counter-torque is supplied by either a spring, a direct drive from
the timing motor, or gravity. In the spring-return type, the timing motor, in addition to driving the
interval gearing, winds up the return spring during the interval. At the end of the interval, a tripping
mechanism releases the spring energy to return the pusher arm to zero. In certain types of spring-
return mechanisms, the clutch is simultaneously disengaged, while in others the clutch is allowed
to slip but remain engaged. In the latter type, particular attention should be given to correct clutch
tension.
On direct-motor-drive reset registers, the timing motor disengages the clutch at the end of the
interval. Then, through cam and sector gear mechanisms, the pusher arm is returned to zero by the
motor.
The gravity type of return mechanism requires that either a clutch or the demand gearing be
disengaged at the end of the demand interval.
During operation of the reset mechanism, attention must be made to whether or not the pusher
arm returns exactly to zero and if the return to zero is smooth and within specified time limits for the
device.
An error in the zero setting will be reflected at all points on the scale. Most registers have an
adjustable zero stop for the maximum pointer which should be checked to see that the pointer is
exactly on zero. The pusher arm is provided with a micrometer screw adjustment for coordinating the
zero of the pusher arm with the maximum pointer zero position.
A sluggish return to zero may be the result of excessive friction or a decrease in the amount of
return power. For various types of registers, the return time, sometimes referred to as the out time,
varies from a fraction of a second to four seconds (for 15 minute interval registers). This out time
generally increases proportionally with the length of the time interval. On most registers, no adjust-
ment is provided to change the reset time, while some do have an adjustment in the cam mechanism.
Sluggishness is more pronounced and can be detected more readily in the spring-return and grav-
ity-return type of registers. In the spring-return type, a change in torque is possible, though a change
sufficient to effect malfunction is uncommon. In the gravity-return type, the weight is constant so 337
there cannot be a change in return force. Therefore, sluggishness can usually be attributed to excessive
friction due to dirt or gummy oil, maladjustment of the clutch, or a defective governor mechanism in
types where used. Examination of the register should indicate the maintenance required—either clean-
for any particular register, self-checking devices are available for most types. The register self-checking
consists of gearing mounted in a framework so the gear trains of the register are locked together
through the checker gearing. With the register energized, it will perform its normal function of reset-
ting the register and driving the demand gear train a definite number of revolutions per interval.
Most self-checking devices can be manually operated to run the register more quickly through a
demand interval. When operated manually, the checker should be run slowly during the reset cycle to
be sure the pusher arm is allowed to return to zero. The true reading may be calculated by counting
the number of revolutions of the first gear of the register for the demand interval:
kW 5 (Revolution of first gear per time interval) 3 10 (Register Ratio)
3 (Marked time interval, in hours)
Usually the self-checking devices are provided with two gear ratios to check two points on the
scale. This type of test verifies the gear train ratios only, and it is necessary to check the timing motor
to ensure the correct time interval.
Some timing motors can be checked for correct speed by use of a stroboscope light, others by
timing one of the slow-speed gears with an accurate stopwatch. The time interval may be checked
by timing the interval between two successive resets with an accurate device. It is recommended that
motors be checked at the voltage expected when placed into service.
Alternately, an overall test of a demand register can best be accomplished by a register-checking
device that simulates a watthour meter on a constant load. This consists of a synchronous motor
driving a shaft similar to a meter shaft for which the demand register was designed, and studs for
mounting the register. With the register motor and checker motor energized from the same source, the
register is allowed to operate through one or more complete intervals. Ignoring the demand multiplier,
the demand that should be indicated may be calculated as follows:
kW 5 (Revolution of first gear per time interval) 3 10 (Register Ratio)
3 (Marked time interval, in hours)
Revolutions of the first gear can be calculated for the time interval from the checker shaft speed
and the ratio of the first gear reduction. This type of checker is particularly adaptable to shop testing
when several such devices may be mounted on a test board. They are usually equipped with two or
more speed changes for checking different points on the demand scale. A correct indication verifies
that the time interval and the gear ratios are correct.
A manual test may be made on the gear train and zero setting by resetting the interval reset to
zero, then advancing the first gear a definite number of revolutions. The kilowatt indication is calcu-
lated by the same formula as for mechanical test devices. It is necessary to determine that the time
interval is correct.
Field tests on watthour demand meters may be made by connecting a field standard in series with
the watthour meter as for a regular watthour meter test. With a load applied to produce approximately
the desired demand indication, the field standard should be started at the instant of a demand interval
reset and stopped at the succeeding reset. The true kilowatts that should be indicated by the demand
register can be calculated as follows:
True kW 5 (Watthours recorded by standard) 3 N 3 60
1,000 3 (Time interval, in minutes)
a desired demand value is established to be run up on the meter. With the load applied to produce
approximately the desired demand indication, the standard should be started at the instant of a
demand interval reset and stopped at the succeeding reset. The true kilowatts that should be indicated
by the demand register can be calculated as follows:
True kW 5 (Watthours recorded by standard) 3 N 3 60
1,000 3 (Time interval, in minutes)
N 5 Number of full-current coils in series in the watthour meter
Principle of Operation
As with the electronic demand register, the electronic TOU register uses the same principle of optical
pickup to establish pulse information. The pulse information is analyzed by an on-board microproces-
sor. The pickup generates pulses directly from the disk rotation and is only as accurate as the base
meter.
Electronic TOU registers contain a microprocessor-based module with a program that is specific
to a particular billing rate schedule as established by the utility. Electronic TOU registers are capable
of measuring time-differentiated kilowatthours and time-differentiated integrated kilowatt demand.
The demand may take the form of block interval demand, cumulative demand, continuous cumulative
demand, or rolling demand.
The means of programming this type of register may be performed by either the manufacturer or
the utility via supplied software. Each method of programming provides the register with information
pertaining to the peak, shoulder-peak, and off-peak times; season change dates; daylight saving dates;
off-peak holidays; etc. Refer to the manufacturers’ instructions for more information.
Each electronic TOU register maintains an ongoing date and timekeeping function. During AC
power outages, the registers rely on battery backup. The register monitors the battery condition and
produces an error code on its digital display if the battery charge is not adequate. Monitoring of the
battery condition on a routine basis is advised to maintain proper operation of the register during
power outages. Manufacturers’ information provides insight as to when the register may require a new
battery or needs to be replaced.
Test Procedure
Periodic testing of the register switch times and special dates is recommended to ensure the correct
setup of the programming information. Some electronic registers have visual indications of the pres-
ent rate (peak, shoulder, off-peak). The manufacturers’ information may offer additional insight of
features that should be tested. Updates to any of the programs to be used with the electronic registers
should be verified completely before use in a billing situation.
Careful attention should be given to the manual demand resets performed for billing. Some
electronic TOU registers have a demand reset indication that appears on the digital display when a
correct billing reset has occurred. The manufacturers’ information booklet will give the specific reac-
tion identifying if a correct reset has occurred for each of their available registers.
Some electronic TOU registers may be tested utilizing its test mode function maintained within the
register. This feature disallows any load applied during a test to be applied to the customer’s bill.
A test voltage is only applied to the meter under test. If the register being tested is one of the types 341
that contain a test mode, that mode should be enabled. Visual inspection of the digital display is very
important to ensure all segments of the display are functioning properly.
The actual test of the demand portion of the register is performed by attaching a standard in
MAINTENANCE
Solid-state pulse recorders require very little maintenance. Most of these recorders are designed so that
the circuit board assemblies in the recorder can be easily replaced. Some recorders use rechargeable
batteries which should be checked periodically. Some recorders perform a self-check of the battery and
send a low-battery alarm to the device interrogating them. All batteries should be changed at intervals
less than the expected shelf life.
Planned replacements of solid-state pulse recorders as part of a maintenance program should be
made based on the estimated product life of solid-state electronics, which is usually 10 to 15 years.
Principle of Operation
Handbook for Electricity Metering
In its simplest form, the electronic meter must duplicate the basic functionality of the mechanical
demand meter and its subsequent replacement, the hybrid electronic register, by providing a means for
recording consumption and the maximum demand. Various designs for the electronic meter perform
this basic function in essentially two different ways:
1. Processing of consumption data via pulse values
2. Direct measurement
In the first method, the metrology unit provides kilowatthour information to the register in the
form of pulses. The register then operates exactly in the same manner as the electronic demand
register.
The second method provides for a more direct measurement in that the basic units of current and
voltage are converted digitally and then sent to a microprocessor that provides all the data process-
ing functions, including the determination of consumption, determination of elapsed time, and the
demand calculation.
Depending on whether more advanced options are turned on, such as TOU, load profile, or kVA,
either type of unit described may or may not contain a battery to help maintain the meter’s time base.
As with the electronic register, the meter will typically monitor the battery condition and provide alerts
to its status if a battery is installed.
The method for performing the monthly demand reset may range from the manual reset via a
switch on the meter to one performed electronically via a handheld device or some alternative system
remotely. There are also conditions where the demand reset is not even necessary for determining the
monthly peak demand values.
Since there are no moving parts, all the features and options are controlled by the meter’s firm-
ware, software, or a combination of both. Therefore a test of the electronic meter must satisfy the
following the following questions:
1. Does the firmware and/or software match versions already validated by the utility?
2. Is the meter’s time interval correct?
3. Does the operation of the register function match expected results?
Test Procedure
Since all register functions are proportional to the kilowatthour measured via the metrology compo-
nent of the meter, it is important to perform an accuracy test on the meter. Any inaccuracy with the
kilowatthour measurement will be reflected into any values determined by the register (e.g., demand,
TOU, etc.). In addition, with only voltage applied to the meter, a visual inspection of the display
sequence is necessary to confirm that all segments of each display value are functioning properly.
For a type of device which processes pulse information, the steps for the electronic demand
register can be applied.
Alternately, for either type of device, a test comprising of running the meter in parallel with
a known standard for an equal period of time and measuring equivalent units of measure can be
applied. This type of test is sometimes referred to as a time run test and is typically performed in the
meter shop. Some electronic meters may be tested utilizing the test mode function within the meter.
This feature allows for test load to be applied to the meter without impacting the customer’s bill.
However, for shop testing, this feature may also be utilized to shorten the duration of the test, which
is typically set for at least one interval period.
Testing the electronic meter in this manner, especially with a static programming design, will
provide a level of confirmation that all components—the firmware/software, the time interval, and the
measurement determination—conform to the utility’s requirements. However, in some more advanced
meters, many utilities are going beyond an operational test of the meter, mainly due to the fact that it
is difficult to reproduce all the scenarios that may impact the measurement and value determination
by the device. These additional tests become more critical whenever changes are made to the meter’s
firmware and/or software. For example, one utility may program into the meter/register a holiday
schedule during which the peak and off-peak periods may respond differently than on a normal
weekday. The question arises of how a utility ensures that all of the specific holidays are included in 343
the register’s program.
To resolve the concern of the potential risk of incorrectly programmed devices being placed into
service, utilities have introduced some of the following actions:
345
346 less measuring components that need to be read, processed, computed, and, ultimately, billed to the
customer as part of their rate structure.
In three-phase systems, harmonic currents can add in the ground wire instead of canceling, result-
ing in grounding problems. The harmonic voltages produce larger eddy currents in magnetic materials,
Handbook for Electricity Metering
resulting in greater core losses and impacting equipment sizing. In historic metering equipment,
harmonics can also cause errors or may not be measured at all. Metering equipment, techniques, and
simplifying assumptions used to meter power were adequate because these harmonic loads were very
limited and any meter technology limitations had little impact.
Today and in the future, these harmonic loads must be carefully reviewed and new metering
technologies used as needed to accurately measure these values. In some cases, for historical reasons,
the older techniques must be emulated to achieve consistent results, although their validity is ques-
tionable. Some may believe that existing rates dictate that historical techniques be emulated. Others
may feel that applying newer metering techniques will cause commercial issues with their customers.
These issues require care to avoid measurement or other problems.
Background
Historic measurement techniques assumed all currents and voltages were perfect sine waves. Some
instruments and methods will be in error if the sine wave is distorted. The current required by induc-
tion motors, transformers, and other induction devices can be considered to be made up of two kinds:
magnetizing current and power-producing current.
Power-producing current, or working current, is that current which is converted into useful work.
The unit of measurement of the power produced is the watt or kilowatt.
Magnetizing current, which is also known as wattless, reactive, quadrature, or non-working
current, is that current which is required to produce the magnetic fields necessary for the operation of
induction devices. Without magnetizing current, energy could not flow through the core of a trans-
former or across the air gap of an induction motor. The unit of measure for magnetizing voltamperes
is the VAR or kiloVAR. The word VAR is derived from voltamperes reactive and is equal to the voltage
times the magnetizing current in amperes.
The total current is the current which would be read on an ammeter in the circuit. It is made up
of the magnetizing current and the power producing current which add phasorially (vectorially).
Phasor Relationships
In a single-phase circuit which contains only resistance, the current I is in phase with the voltage E.
See Figure 15-3a. In this ideal case, watts equal voltamperes.
When reactance (inductive or capacitive) is introduced into the circuit, the current is displaced or
shifted out of phase with the voltage by an angle , depending on the relative amounts of resistance
and reactance. Normally, the reactance is inductive and the current I lags the voltage E. See Figure
15-3(b). If the reactance is capacitive, the current will lead the voltage.
The current I in a two-wire circuit can be considered to be made up of two components: IW which
is in phase with E and which produces watts; and IV which is displaced 90° from E and produces
reactive voltamperes. By trigonometry:
IW 5 I cos
and IV 5 I sin
then:
E I cos 5 watts
and E I sin 5 VAR
Again by trigonometry, the cosine varies from zero for an angle of 90° to one for an angle of zero
degrees. As power factor improves, the displacement angle becomes smaller. When the power factor is
in unity, watts and voltamperes are equal to each other and reactive voltamperes equal zero.
Voltampere Metering
As previously stated, voltamperes is simply the product of the voltage and current without consider-
ation of the phase angle. This is shown in the following definition:
Voltamperes 5 |V|*|I|
Where the |V| is the rms value of the voltage and |I| is the rms value of the current. Note that
there is no mention of phase angle. This definition is accurate under all waveform conditions includ-
ing the presence of noise and harmonics on the line. Another method of calculating VA when the
waveform has 60 Hz only is to combine watts and VAR vectorially,
Voltamperes (vector) 5
watts
2
1
VA R2
This can be seen from the familiar power triangle illustrated in Figure 15-4.
This method of calculating VA is called Vector VA.
Use of Two Conventional Meters: Real and Reactive
Prior to the development of electronic meters capable of performing accurate measurement of appar-
ent energy, the approximate value of this quantity typically was measured by combining readings from
a real energy meter and a reactive 349
energy meter. For the billing time
period, kVAh is calculated vectorally
from the square root of the sum of
VAs2
VAR 5 2
Watts
350 Assuming that an adequate sampling and computation rate is used, the only drawback with using
this method is that the sign of the reactive energy is lost. This may or may not be a problem, depend-
ing upon the local practices and legislation for utility tariffs. In any case, more sophisticated electronic
meters can be used to provide alternate measurement methods to overcome this possible concern.
Handbook for Electricity Metering
Note that in the presence of harmonics, this quantity is not just VAR as historically defined, but a very
accurate value of
VARD
2
2
which includes the harmonic effects.
In this case, the VAR measurement of the primary (fundamental) frequency is distorted by the
inclusion of the harmonics. However, this is not viewed as a significant issue because VAR and distor-
tion power “D” affect the electrical system in a similar manner. Indeed, it can be argued that for the
purpose of determining system loads and billing for all of the inherent impacts of customer-induced
harmonics, this value is the preferred value to use.
2. Arithmetic Method
Using the arithmetic method and an “ideal” measuring device, we determine the kVA at each
moment during the measurement interval and integrate it over the time period of interest.
In this case, we know that for the first 15 minutes (.25 hours), the kVA 5 kW and we have
25 kWh or 25 kVAh metered in our ideal measurement device (100 kW .25 hours). Similarly,
for the next 15 minutes, we draw 25 kVARh and therefore, exactly 25 kVAh again.
Which is correct? Both! This illustrates how two “completely accurate” methods of measuring
apparent power and energy can result in dramatically different values. In this particular example, the
vectorial method returns a “correct” answer that is almost 30% lower than the arithmetic method!
Even so, it is useful to observe that the equipment capacity had best be set by the arithmetic measure-
ment result.
As there is no universally accepted correct way, meter manufacturers have provided metering
solutions enabling all utilities to obtain better and more accurate basic data, regardless of the local
requirements for power calculations.
Energy sold by the source may be defined as delivered. Energy purchased may be defined as received.
For any given voltage and current, VA is constant and an unsigned absolute quantity. For any given
phase angle
Watts 5 EI cos
VAR 5 EI sin
The signs—plus and minus—and directions—delivered and received—are for conventionally polar-
ized instrument transformer connections with respect to the power source.
Electronic multiple-function meters can measure the following quantities, or combinations of
quantities:
kWh, kW demand delivered Quadrants I and IV
kWh, kW demand received Quadrants II and III
kVAh, kVA demand delivered Quadrants I and IV
kVAh, kVA demand received Quadrants II and III
kVARh, kVAR demand active quantities delivered, PF lagging Quadrant I
kVARh, kVAR demand active quantities received, PF leading Quadrant II
kVARh, kVAR demand active quantities received, PF lagging Quadrant III
kVARh, kVAR demand active quantities delivered, PF leading Quadrant IV
The following combinations of reactive quantities are available on some meters as displayed
quantities or as non-displayed outputs. Consult the specifications of individual meter manufacturers.
kVARh and kVAR demand delivered Quadrant I plus II
kVARh and kVAR demand received Quadrant III plus IV
354 These two combined quadrant VAR quantities are equivalent to the performance of a rotating
detented VAR meter.
kVARh and kVAR demand delivered, net Quadrant I minus IV
Handbook for Electricity Metering
357
358 These meters operate with formulas, approved by meter engineers and/or regulatory agencies,
that add or subtract simulated losses to the metered load and record compensated meter readings, or
uncompensated readings, with simulated losses. The information for the derivation of the parameters
required to be programmed into these meters will be discussed in detail later in this chapter.
HANDBOOK FOR ELECTRICITY METERING
TRANSFORMER LOSSES
Transformer losses are typically viewed as load—or copper—losses, and no load—or iron—losses.
Losses in the transformer are caused by hysteresis, eddy currents, and load currents. Hysteresis losses
are derived from energy expended as the magnetic field within the transformer continually changes
intensity and direction. Hysteresis losses are a function of the metallurgical properties of the core
material. Eddy current losses are caused by energy expended by current, induced by the magnetic field,
and circulating within the transformer core. Eddy current losses can be minimized by building the
transformer core from electrically resistive steel formed into thin, insulated laminations. Load losses,
or I2R losses, are caused by current passing through the transformer windings and the resistance of
those windings. Transformer manufacturers will test transformers and provide data on load and no
load losses, excitation current, and percent impedance, all of which are values needed for internal
meter compensation and will be explained in more detail later in this chapter.
SPECIAL METERING
No-load loss kVA equals the rated transformer kVA times the percent of magnetizing current. Load
loss kVA equals the rated transformer kVA times the percent of impedance.
The power factor angle for no-load loss is the angle whose cosine equals the ratio of no-load loss
watts to no-load kVA. The power factor angle for load loss is the angle whose cosine equals the ratio
of load loss watts to kVA. Alternately, these expressions can be seen in Figure 16-1.
No-load loss VAR and load loss VAR are the products of their respective kVAs times the sines of
their respective power factor angles. The Power Triangle may also be used to determine VARs as they
equal the square root of VA2 minus watts2.
NO ENERGY FLOW
During periods when there is no energy flow, transformer losses still exist. Under no-load situations
such as this, the meter measures no energy delivered or received. However, the high voltage system is
still consuming watts and VARs to energize the customer’s transformer. A meter programmed to per-
form loss compensation will calculate no-load (core) losses even when it sees no current flow as long
as the meter still sees voltage. As such, the meter will continue to register these losses even with no
load flowing through the transformer. As a result, it is possible to see accumulation of kilowatt hours
(kWhs) and kilovolt amps reactive hours (kVARhs) during periods when the customer’s load and gen-
eration are zero. It should be noted that once loss compensation is enabled, most of today’s solid state
meters will have an option to either apply or ignore loss compensation during no load conditions. An
METER LOCATION
HANDBOOK FOR ELECTRICITY METERING
If installed on the low voltage side of the transformer, any meter compensated for transformer losses
should be connected ahead of the disconnection device so that, while the transformer is still energized,
it will continue to see voltage and register core losses (if applicable) under no load conditions. This is
typically the case for most types of construction since the metering voltage circuit (or metering voltage
transformer) is usually connected to the low-voltage bus.
Conductor losses on the low voltage side between the interconnection point and the metering
point should be considered in the compensation calculations. For short conductor lengths and rela-
tively large conductor sizes, these losses may be negligible. However, in other cases where there is some
distance between the interconnection and metering points, conductor losses may be significant and
therefore should be included in compensation calculations. Conductor losses are typically added to the
full load (copper or winding) losses of the transformer since both vary with the square of the current.
TRANSFORMER CONNECTIONS
SPECIAL METERING
The majority of transformer loss compensation situations involve either four-wire wye or three-wire
delta connections. Both of these are balanced conditions for which standard calculations require
no adjustments. For other transformer connections, consideration must be given to the relationship
existing between the load current through the power transformer winding and the current through the
metering current transformer. The connections of the power transformers may affect the copper loss
calculations for determination of the meter calibrations.
Open-Delta Connections
For open-delta connections, full load losses occur when the transformers are supplying 86.6% of the
sum of the kVA ratings of the two transformers. Therefore, if an open-delta bank was used, the value
of the full-load line current would be multiplied by 0.866 to determine the current in the transformer
windings at full-load transformer losses.
Scott Connections
In Scott connections used for three-phase to two-phase transformation, the teaser transformer is
connected to the 86.6% tap. The copper-loss multiplier for the teaser transformer is 1.077 or 0.808
as shown in Table 16-1, depending on whether the metering is on the two-phase or three-phase side.
For the main transformer, the copper-loss multiplier is 0.875 for metering on the three-phase side and
1.167 for metering on the two-phase side.
Three-Phase, Four-Wire Delta Connections
Three-phase, four-wire delta connections with a two-stator, 2½-element meter involve a special
feature. When final tests of the meters are made with stators in series, the percent loss to which the
transformer-loss compensator is adjusted applies to the stator connected to the two-wire current
transformer. The stator connected to the three-wire current transformer measures the vector sum of
the two currents displaced by 120°. For this stator, the percent of copper loss is multiplied by 1.155.
For operation in service, the loss increment will then be divided equally between the two stators.
Similarly, with the transformer-loss meter, the speed of the stator connected to the three-wire current
transformer should be increased by the relation:
52
1 to ———— 5 1 to 1.333 or 33.3%
4.332
Transformer Connection
Figure 16-2. Sample Transformer Cover Sheet With Key Data Elements Circled.
SOLID-STATE COMPENSATION METERS 363
Solid-State Compensation Meter
A solid-state meter with various compensation options for calculating and applying loss factors
SPECIAL METERING
to measured quantities is currently the primary method used when loss compensation is required.
Although solid-state meters compensate using the same modeling formulas as those utilized via older
methodologies, they differ markedly in their manner of operation. Instead of using resistances, tapped
transformers, and capacitors to modify currents and voltages, coefficients based on loss compensation
percentages and other site specific information are stored within the meter and accessed each time a
loss calculation is performed. Solid-state meters convert the current and voltage to digital inputs for
microprocessors, which then perform the mathematical operations to compute metered quantities
such as watts, VARs, volt amperes (VA), Q, etc. Using these measured voltage and current inputs along
with the stored compensation coefficients, a meter with loss compensation programming options
performs internal calculations based on defined algorithms to generate compensated metered values.
These compensated metered quantities can then be stored as part of typical billing data. They can be
displayed, can generate an energy pulse output, and be used as a trigger or alarm. Some meters are
also capable of measuring and displaying both compensated and uncompensated metered quantities at
the same time.
Derivation of Coefficients
Solid-state meters with loss compensation (LC) options may be programmed by the manufacturer
using loss compensation data provided by the meter purchaser. However, most frequently, the utility
meter engineer programs the LC percentages based on data unique to the equipment at each specific
metering site using software provided by the meter manufacturer. Because the LC coefficients are
programmed directly in the meter and impact the measurement calculation, depending on the direc-
tion of the load, applicable losses may either be added or subtracted from previous metered quantities.
The overlying goal of the utility meter engineer is to properly model the transformer loss param-
eters, line loss parameters, or some combination of both when introducing compensation into the
metering circuit. Depending on the type of solid state meter and its capability for calculating compen-
sation factors, a meter engineer may have to use different methods of deriving the appropriate loss
compensation coefficients. Therefore, it is important to fully understand the required meter parameters
and how those parameters are utilized within the meter in determining the compensation percentages.
Finally, it is important to note that any change in the original set of physical connections or
operational conditions will impact the compensation results and thus require a new set of compensa-
tion calculations to be performed.
LOSS CALCULATIONS
Determination of Losses
In order to determine the proper loss compensation parameters, first request from the manufacturer of
the transformers the following information:
• Lowest kVA rating
• No-load test results—watts (iron loss) at rated voltage with no load current (open circuit test)
• Full-load test results—watts (copper loss) that meets or exceeds 75°C at rated full-load current
• Rated voltage of transformer
• Voltage taps provided in the high-voltage and/or low-voltage side
If compensation based on either power factor or VARhour losses is to be considered as part of the
overall compensation model, the following additional information will also be required:
• Percent exciting current at rated voltage to full load current
• Percent impedance that meets or exceeds 75°C at full-load current
Figures 16-2 and 16-3 show a sample set of transformer data sheets with the required informa-
tion, listed above, highlighted.
Finally, information pertaining to operational criteria at the site such as the transformer connec-
tions, taps in use, and the length, size, and material of conductors from the low-voltage terminals of
the transformers to the metering point must be properly documented in order to apply any necessary
364
High and Low Voltages
with KVA Rating
HANDBOOK FOR ELECTRICITY METERING
Percent Impedance
Figure 16-3. Sample Transformer Data Sheet With Key Data Elements Circled.
transformer loss adjustment factors as well as to determine any possible line loss contribution to the 365
overall compensation model.
The impact of the line losses may be considered negligible, depending on the location of the
metering circuit relative to the transformer. However, the utility meter engineer may still want to
SPECIAL METERING
account for these losses, despite their negligible effect, in order to better model the physical loss
characteristics of the site.
The following is a list of any type of cable-related information that must be obtained from various
sources, including the cable manufacturer and/or the site engineer, in order to determine the line
losses resulting from the cables:
• Positive sequence impedance at continuous rated current
• Type of conductor(s)
• Number of conductors
• Length of cable from the metering point to the billing point
In some cases, depending on the type and configuration of cable (e.g., underground, submarine,
overhead, etc.), additional information may also be required from the manufacturer, such as the per
length cable capacitance between each conductor and its insulation shielding as well as the conductor
loss angle at maximum ambient temperature and rated voltage.
Loss Compensation Formulas
Calculations should be referred to either the high voltage circuit or to the low voltage circuit. Once
the choice is made, this convention should be maintained as a point of reference for all subsequent
calculations. The following formulas all use the high voltage circuit as its reference.
Meter test current is defined as the test current with metered current elements (coils) in series at
unity power factor.
Meter test voltage is defined as the test voltage with meter voltage elements (coils) in parallel at
unity power factor.
Rated transformer volts are dependent on the voltage connections to the meter and can be either
delta (line-to-line) or wye (line-to-neutral). For consistency purposes, the rated voltage values are typi-
cally expressed in terms of a line-to-neutral reference.
Three possible options are listed below for determining the meter’s test current. When calculating
loss percentages for a programmable meter, it is necessary to choose the meter test current formula
that matches the method prescribed by the manufacturer. For example, some meter types specify that
loss calculations be based on 50% of the meter’s class amps, while other types specify calculations be
based on meter’s test amps. Alternatively, some meter types allow the user to specify directly within
the meter a specific current value for its loss percentage calculations.
Meter test current1 5 Meter TA 3 K
Meter test current2 5 5 amperes (transformer rated) 3 K
Meter test current3 5 50% Class amps of meter 3 K
Where K 5 3 (three-element meter)
K5 2 (two-element meter)
K5 4 (2½-element meter)*
Transformer Test kVA
Transformer Test Amps 5 —————————————————————
3 Transformer Rated kV
Note: VTR 5 Voltage Transformer Ratio
CTR 5 Current Transformer Ratio
LWFe is defined as the watt losses due to iron (core-loss watts) determined by the equation:
(Meter Test Voltage 3 VTR)2
LWFe 5 No-load Test Watts 3 ————————————————————
(Rated Transformer Volts)2
LVFe is defined as the VAR losses due to iron (core-loss VAR) determined by the equation:
(Meter Test Voltage 3 VTR)4
LVFe 5 no-load VAR 3 ————————————————————
(Rated Transformer Volts)4
With no-load VAR being calculated as follows:
No-load VA Loss 5 (Transformer Percent Exciting Current/100) 3
(Transformer kVA Rating 3 1000)
No-Load VAR 5 SQRT((No-load VA Loss)2 — (No-Load Watts)2)
Alternately, the same equation may be represented as:
No-load VAR 5 No-load VA 3 Sin
Where is the angle between the no-load watts and no-load VA
LVCu is defined as the VAR losses due to copper determined by the equation:
(Meter Test Current 3 CTR)2
LVCu 5 Load VAR 3 ————————————————————
(Transformer Test Amps)2
With load VAR being calculated as follows:
Transformer Load VA Loss 5 (Transformer Percent Impedance/100)
3 (Transformer kVA Rating 3 1000)
Load VAR 5 SQRT((Load VA Loss)2 — (Load Watts Loss)2)
Alternately, the same equation may be represented as:
Load VAR 5 Load VA 3 Sin
Where is the angle between the load watts and load VA
%LWFe is defined as the percent iron watt loss (core loss) determined by the equation:
LWFe 3 100
%LWFe 5 ——————————————————————————————————————
Meter Test Current 3 Meter Test Voltage 3 CTR 3 VTR
%LWCu is defined as the percent copper watt loss (load loss) determined by the equation:
LWCu 3 100
%LWCu 5 ——————————————————————————————————————
Meter Test Current 3 Meter Test Voltage 3 CTR 3 VTR
%LVCu is defined as the percent copper VAR loss (load VAR) determined by the equation:
LVCu 3 100
%LVCu 5 ——————————————————————————————————————
Meter Test Current 3 Meter Test Voltage 3 CTR 3 VTR
%LVFe is defined as the percent iron VAR loss (core VAR) determined by the equation:
LVFe 3 100
%LVFe 5 ——————————————————————————————————————
Meter Test Current 3 Meter Test Voltage 3 CTR 3 VTR
Calculate %LWFe, %LWCu, %LVFe, and %LVCu for full load, single phase, and with unity power
factor.
If the test voltage remains constant:
%LWCu is proportional to test load (test amps)
%LWCu is inversely proportional to power factor
%LWFe is inversely proportional to test load (test amps)
%LWFe is inversely proportional to power factor 367
%LVCu is proportional to test load (test amps)
%LVCu is inversely proportional to power factor
%LVFe is inversely proportional to test load (test amps)
SPECIAL METERING
%LVFe is inversely proportional to power factor
These relationships permit light-load test and 50% power-factor-load test values which are derived
from full-load test values.
Application Example 1
Once all of the physical and electrical characteristics of the equipment and site are determined, it is
recommended that forms such as shown in Figure 16-5 be utilized for documentation purposes. By
using such forms to record and document all data from the applicable sources, procedures for deriving
the compensation values can be more easily and uniformly followed. The application of the solid state
meters may be better understood by the following steps as applied to a specific installation.
Equipment and Site Specifications
A single 15,000 kVA three-phase transformer bank is connected delta/wye. Metering on the low side
of the transformer at 13,279 volts will be by a three-phase four-wire solid-state meter utilizing three
1,200:5 ampere current transformers and three 14,400:120 volt voltage transformers. It is desired
to compensate the metering to record the load at the designated point of interconnection, which is
3.3 miles away from the physical metering location, on the 115,000 volt (high) side of the power
transformer, as shown in Figure 16-4, using a solid-state meter.
Calculation Methods—Iron and Copper Transformer Loss
Using the equipment and site information as documented on the form shown in Figure 16-5, the iron
and copper loss values can be calculated. The calculations and resultant iron and copper loss values for
both watts and VARS are shown in Figure 16-6. These values will be referenced in subsequent calcula-
tions in determining the percent loss compensation factors programmed into the meter. Throughout
the calculations shown in Figure 16-6, an empirical assumption is made that within small variations
of the rated voltage, iron watt losses vary as the square of the voltage and the iron VAR losses vary
approximately as the fourth power of the voltage.
Calculation Methods—Line Loss
The inclusion of line losses is fully dependent on the physical conditions at the metering site. Since,
in this example, the physical metering location is 3.3 miles from the intended point of interconnec-
tion, the utility meter engineer has decided that the impact of such line losses is significant enough to
Point of
Interconnection
Actual Meter
Location
14,400:120
1,200:5
Source
Load
3.3 miles
15,000 KVA
115 2 23Y / 13.2 KV
JOHN
Customer's DOE MFG. CO
Name or Station _____________________________________________________________
100 MARKET STREET
Address _____________________________________________________________________________
GENERAL
Power Transformer ELECTRIC
Data (Provided by): _____________________________________________________
GE
Make ________________________________________________________________________________
CLASS OA/FA/FOA THREE PHASE 60 Hz
Type ________________________________________________________________________________
691592
Serial Number _________________________________________________________________________
Rated kVA 15,000/20,000/25,000
____________________________________________________________________________
115,000/23,000
Rated Voltage _________________________________________________________________________
Tape Voltage FIXED HIGH SIDE TAP; LOW SIDE - 23,000 VOLT TAP
in Use ____________________________________________________________________
20,849
Fe Loss @ WATTS
100% Rated Voltage ___________________________________________________________
68,074
Cu Loss @ WATTS
Full Load ___________________________________________________________________
% Imp. @ 8.23
75° C _______________________________________________________________________
0.52
% Exciting Current _____________________________________________________________________
Connections: X
PRIMARY Delta WYE 3
Wire _____ X
SECONDARY Delta WYE 4
Wire _____
Instrument 1,200:5
Transofmer Ratio: CT __________ 14,400:120
VT __________
15,000,000
Transformer Test Amps at Full Load: ________________________ 5 376.5328 Amps
3 3 23,000 3 SQRT (3)
CABLE INFORMATION
OKONITE
Make ________________________________________________________________________________
Overhead ACSR
Type ________________________________________________________________________________
0.077452
Impedance 1 j 0.738273 per mile
per length ___________________________________________________________________
3.3 miles
Length ______________________________________________________________________________
3
Number of Conductors __________________________________________________________________
METER INFORMATION
SOLID STATE METER
Make ________________________________________________________________________________
DIGITAL
Type ________________________________________________________________________________
9F
Form/Base ___________________________________________________________________________
20
Class ________________________________________________________________________________
120
Rated Voltage _________________________________________________________________________
3
Number of Elements ____________________________________________________________________
Figure 16-5. Example of a Form for Collecting Equipment and Site Information.
369
TRANSFORMER LOSS CALCULATIONS
Iron Loss (No-Load VARS) Copper Loss (Load VARS)
SPECIAL METERING
VA 5 15,000,000 3 0.0052 5 78,000 VA 5 15,000,000 3 0.0823 5 1,234,500
20,849 68,074
Cos 5 ———— Cos 5 ————
78,000 1,234,500
5 Cos21 (0.2673) 5 1.3002 5 Cos21 (0.0551) 5 1.5156
Sin 5 0.9636 Sin 5 0.9985
VARs 5 78,000 3 0.9636 5 75,161.9531 VARs 5 1,234,500 3 0.9985 5 1,232,621.67
VAm 5 VA of Meter 5 (Meter Test Current 3 Meter Rated Voltage 3 CTR 3 VTR)
VAm 5 3 3 10 3 120 3 240 3 120 5 103,680,000 VA
Iron and Copper Loss Watts:
(Meter Rated Voltage 3 VTR)2
LWFe 5 Watt losses due to iron (core-loss watts) 5 No-Load Watts 3 ————————————————
(Rated Transformer Volts 4 SQRT(3))2
(120 3 120)2
LWFe 5 20,849 3 ————————— 5 24,517.4781 Watts
(23,000 4 SQRT(3))2
(50% Class Amps of Meter 3 CTR)2
LWCu 5 Watt losses due to copper (Load Loss watts) 5 Load Watts 3 ————————————————
(Transformer Test Amps)2
(10 3 240)2
LWCu 5 68,074 3 —————— 5 2,765,655.781 Watts
(376.5328)2
include as part of the overall compensation model. The calculations of the watt and VAR loss values
attributed to the 3.3 mile line length are shown in Figure 16-7.
The calculations in Figure 16-7 employ the fundamental concept that line loss is proportional to
the I 2 (amp squared) losses associated with the type of cable used for each conductor. Utilizing this
method of calculation thus neglects the admittance of the cable. In most cases, the admittance of the
cable is determined to be negligible. However, if considered, the admittance would only impact the
value of VAR loss. In the above example, the calculation of nominal primary amps is found using the
current transformer ratio and 50% current class of the meter. This current value was selected in this
370
LINE LOSS CALCULATIONS
Resistance per length 5 0.0774 ohms/mi Reactance per length 5 0.7738 ohms/mi
HANDBOOK FOR ELECTRICITY METERING
Total Resistance of Cable 5 Resistance per length 3 length of cable 3 number of conductors
Total Line Loss Watts 5 0.077452 3 3.3 3 3 5 0.7667
Total Reactance of Cable 5 Reactance per length 3 length of cable 3 number of conductors
Total Line Loss VARS 5 7.3089
Nominal Primary Amps 5 50% Class Amps of Meter 3 CTR 5 10 3 240 5 2400 amps
23,000
Primary Amps 5 2400 3 ———— 5 480 amps
115,000
example since it represents conditions approximating those that would be seen by the meter under
normal operating conditions.
Calculation Methods—Percent Loss Coefficients
The final step prior to entering the compensation values into the meter is to calculate the actual loss
percentages, as shown in Figures 16-8 and 16-9. Using the calculation results in our example as shown
in Figures 16-6 and 16-7, the percent loss factors to be entered into our meter are as follows:
Transformer Loss percentages:
Watts loss due to iron 5 0.0236%
Watt loss due to copper 5 2.6675%
VAR loss due to iron 5 0.10025%
VAR loss due to copper 5 48.3005%
Line Loss percentages:
Watts loss 5 0.1704%
VARS loss 5 1.624%
SPECIAL METERING
LWFe
%LWFe 5 Percent Iron Watt Loss (Core Loss) 5 ——— 3 100
VAm
LWCu
%LWCu 5 Percent Copper Watt Loss (Load Loss) 5 ——— 3 100
VAm
LVFe
% LVFe 5 Percent Iron VAR Loss (Core Loss) 5 ——— 3 100
VAm
LVCu
%LVCu 5 Percent Copper VAR Loss (Load Loss) 5 ——— 3 100
VAm
176,664.9139
%LLW 5 —————— 5 0.1704%
103,680.000
1,683,971.1821
%LLV 5 ——————— 5 1.6242%
103,680.000
Actual Meter
Location
500 MVA
Source Load
500 MVA
Figure 16-10. One-Line Diagram of Metering Specifications for Three Single-Phase ransformers.
always present, with or without load, as long as the transformer is energized and should be shared
between the two meters. Under normal operating conditions, the iron losses may be allocated equally
between the two solid state meters.
However, it should be pointed out that if the operating configuration of the system changes by, for
example, taking one of the secondary winding loads out of service, the iron loss coefficient for only
50% of total losses would be accounted by the remaining metered service due to the equal allocation
across both. Ultimately, the determination of how iron losses are allocated should be mutually agreed
upon by all stakeholders.
Calculation
Transformer Parameters 1X 2X 3X Parameters
VA Bank Rating 500,000,000 500,000,000 500,000,000 1,500,000,000 (Total)
Rated Primary Voltage 345,000 345,000 345,000 345,000
Secondary L-L Voltage 23,000 23,000 23,000 23,000
Secondary L-N Voltage 13,279 13,279 13,279 13,279
No-Load Watts 200,000 190,000 195,000 585,000 (Total)
Copper Loss Watts 590,000 595,000 600,000 1,785,000 (Total)
Percent Impedance 12 11.9 11.8 11.9 (Average)
Percent Excitation Current 0.06 0.058 0.059 0.059 (Average)
Primary Amps 12,551.1 12,551.1 12,551.1 37,653.28 (Total)
Figure 16-11. Example of Parameter Listing for Combining Three Single-Phase Transformers.
373
Point of
Interconnection Actual Meter
SPECIAL METERING
Location
4.16 kV
Single Core 15 MVA
Transformer Load 2
Source
Load 1
30 MVA 15 MVA
115 kV 23 kV
Actual Meter
Location
Figure 16-12. One-Line Diagram of Metering Specifications for Three Winding ertiary Transformers.
TOTALIZATION
Introduction
Totalization is the algebraic combination of like electrical quantities performed on a real time or
near time basis. The combination may be as simple as adding the kilowatthour usage of two or more
circuits or as complicated as solving an algebraic algorithm to determine the overall net usage for an
installation with multiple sources and loads.
Totalization is typically utilized when it is necessary to combine loads from multiple contributing
sources into a single load value. Revenue metering of customers who are served by two or more lines
and billed on coincident demand is one example where totalization would be advantageous. For any
true coincidental demand determination, totalization must be performed in either a real or near time
basis in order to reflect the true peak demand impact of that customer on the utility system (see
Chapter 13, Demand Meters, for a more detailed discussion on this topic). The simple addition of the
individual demand readings does not provide a true coincidential demand value.
In some cases, totalization is not necessary but is used to simplify meter reading and the subse-
quent accounting procedures. Under this type of scenario, monthly kilowatthour usage from multiple
meters is simply added together to determine the customer’s total consumption. Monthly consump-
tion values can be accurately added together as long as there is not any type of demand component on
the customer’s bill.
Finally, in some situations, the totalization process may become very complex, requiring an algo-
rithmic calculation to separate customer supplied load from utility supplied load. An example of such
a case is when a generation station’s service load determination for merchant generators may possibly
be supplied either from the utility or the merchant’s own generator, depending on the generator’s
status.
The manner in which totalization may be provided can be broken down into the following
methods:
• Combining input circuits—current transformers (CTs) and/or voltage transformers (VTs)
• Multi-stator metering
• On-site pulse totalization
• Totalization via translation
Of the four methods listed, examples of the first two may still exist within the industry, but they 375
have both been universally replaced by either of the last two methods. The on-site pulse totalization
and totalization via translation methods are less costly to implement and maintain, and use readily
available equipment that is generally more reliable over a longer period of time. The following are
SPECIAL METERING
descriptions of each of the four totalization methods.
Figure 16-13. Simplified Connection Diagram for Parallel-Connected, Current- ransformer Secondaries.
376 11. Low-voltage, low-burden-capability current transformers are not suited to this application
since the burden imposed on parallel secondaries may be very high.
12. Meter voltage is usually equipped with a throw-over relay to avoid loss of meter voltage in the
HANDBOOK FOR ELECTRICITY METERING
Multi-Stator Meters
Mechanical totalization is accomplished by combining, on one watthour meter shaft, the number
of stators necessary to properly meter all circuits involved. Its use is mostly relegated to mechanical
meters and dates back to the early 1950s as a method for utilities to reduce the number of meters,
and therefore the cost, required for this type of totalization. However, with the advent of pulse meter-
ing and now solid-state metering, it is doubtful that utility personnel will encounter such a device. If
additional details on the operation of a multi-stator meter in a totalization application are required,
please refer to previous editions of this Handbook or to the manufacturer’s literature.
PULSE INITIATORS
A pulse initiator is the mechanism, either mechanical or electrical, within the meter which generates a
pulse for each discrete amount of a metered quantity.
The pulse initiator can be a small switch or pair of switches mounted within the meter. It may
also be an electronic device. On a mechanical meter, the pulse initiator may consist of a light-sensitive
device positioned so as to receive reflections directly from the bottom of the disk or from reflective
vanes on a shaft driven from the disk. Whether the pulse initiator assembly is commonly geared to
the disk shaft or receives reflections from the disk itself, the number of pulses is directly proportional
to the number of disk revolutions. On a solid-state meter, the pulse output value can be set to any
value within the meter’s program. However, it is typically set to a value which is proportional to the
meter’s internal pulse multiplier in units of equivalent disk revolutions.
The output pulses are normally Form C closures, commonly known as KYZ or double-throw,
single-pole, or their electrical equivalent. Each closure is one pulse.
In some applications, Form A closures are used. A Form A closure can be obtained from a Form C
by using only either the KY or KZ contact and doubling the value of each pulse.
Since pulses are directly proportional to disk revolutions (or equivalent disk revolutions, as in
the case of a solid-state meter), a specific watthour value must be assigned to each pulse. If the ratio
between pulses and disk revolutions is 1:1, the watthour value of a pulse must be, and is, equal to the
primary watthour constant of the meter. Thus, in a receiving instrument which counts the number of
pulses, this count multiplied by the primary watthour constant gives the value of the energy measured.
It is important to note that in certain mechanical pulse receivers, one pulse is a latching and the next
an advancing pulse. There may be confusion regarding this type of device, since only half the pulses
are recorded. This chapter considers one closure of the pulse initiator as one pulse transmitted.
Regardless of the manner in which the pulses of a watthour meter are initiated, the value of the
pulse is in terms of energy and not of power. Before any time factor is introduced, the pulse has a
value in watthours rather than watts. In a pulse recorder or any translation system, the time channel, 377
in effect, divides the quantity of pulses received into recorded intervals, therefore creating a reading in
watts. This does not change the character of the value of the pulse as received. In this type of device,
the interval pulses, when multiplied by the appropriate constant, yields demand in kilowatts; the total
SPECIAL METERING
pulses, when multiplied by the appropriate constant, yields kilowatthours.
There are certain requirements in the design and operation of pulse initiators that should be kept
in mind when employing this type of telemetering. In any pulse system, the initiator is the only source
of information transmitted. Therefore, particularly when used for billing, the performance of the
mechanism generating the pulses must match the accuracy of the requirement. A pulse initiator free
from faults has the accuracy of the watthour meter in which it is installed. The final answer given by
the receiver cannot be more accurate than the initiating pulse.
To achieve the desired accuracy, good design of the pulse initiator, proper application, and a high
order of maintenance are necessary. The good design must be provided by the manufacturers. Proper
application by the utility’s meter engineer means matching the capabilities of the pulse initiator, the
communication channel, and the receiver.
It must be remembered that as the value in kilowatthours of each pulse is increased, the possible
dollar impact in the demand determination by a miscount of even one pulse becomes correspondingly
greater. However, the lower limits of pulse value and correspondingly greater rate of sending pulses is
determined by pulse initiator design and receiver capabilities.
Please note that this section has primarily addressed pulses in terms of watthour values. Electronic
meters provide a variety of measured quantities that can be associated with their own unique pulse
output. Therefore, the same concepts discussed in this chapter are also applicable to pulses represent-
ing other energy values, e.g., VARhours, VAhours, etc.
Characteristics of Pulse Initiators
The two basic output circuits of pulse initiators used for pulse metering of kilowatthours are the two
wire and the more common three wire, as shown in Figure 16-14.
The pulse initiator output circuit may be energized with alternating current (AC) or direct cur-
rent (DC). Direct current, in conjunction with polarized relays or electronic-type demand devices, is
Figure 16-14. Simplified Diagrams Illustrating Basic wo- and Three-Wire Pulse Circuits.
378 used where transmission over telephone lines is necessary. The polarized relay permits true three-wire
operation over a two-wire circuit. It is also used on long circuits to avoid the attenuation due to the
capacity effect of some communication cables.
Electronic pulse initiators of the mercury wetted relay or transistor switching types provide quick
HANDBOOK FOR ELECTRICITY METERING
make-break action in delivering pulses to the transmitting circuit. Electronic devices obtain all of the
advantages of the physical construction with none of the disadvantages associated with the mechani-
cal type of pulse initiator.
The output pulse circuits of pulse initiators are usually low power circuits. Most receivers, total-
izers, and pulse equipment designed for meter pulse applications are also low power devices and,
therefore, require no intermediary device. However, the installation must have interposing relays,
impedance correcting circuits, or a combination thereof to protect the pulse initiator where there are
long runs of connecting wire, multiple devices activated by one initiator, or devices having inductive or
capacitive input characteristics.
Types of Pulse Initiators
Mechanical pulse initiators with cam-and-leaf construction depend upon the meter disk for their
driving force.
Electronic pulse initiators may have a shuttered disk, which is an output shaft with reflective vanes
or reflective spots on the rotor of the meter, that work in conjunction with a light source to furnish
an input signal to an amplifier whose output is connected to the pulse transmitting circuit. Electronic
pulse initiators can be designed to permit a much greater number of output pulses per meter disk
revolution than cam-and-leaf devices.
Pulse initiators of hybrid mechanical meters with electronic registers are sometimes integrated
with their registers. The registers are not driven by direct gearing as with a mechanical device, but by
light or infrared reflections off the meter disk. The pulse initiator supplies output pulses, which are an
integral number of the pulses driving the register. Normally, the register pulse ratio is 12 pulses per
revolution. Output pulses can therefore be 12, 6, 4, 3, 2, or 1 pulse per revolution. The reciprocals
1/12, 1/6, 1/4, 1/3, 1/2, and 1/1 are known as the Pulse Multiplier (Mp) or Revolutions per Impulse
(R/I) of the initiator. The choice of Mp or R/I is made when programming the register.
Some meters with electronic registers have no provision for supplying output pulses. These meters
must be equipped with a separate pulse initiator board. Having a separate initiator has the advantage
of providing a redundant revolution-counting circuit which can serve as a check against the meter
registration.
Electronic meters that do not have a rotating disk may be configured to generate pulses based on
the quantity selected and the pulse weight entered within the meter’s program. These pulse outputs
may be chosen to indicate a quantity of energy identical to that quantity metered by one revolution of
the disk of an equivalent mechanical meter. This equivalent revolution pulse permits testing the meter
using conventional test procedures. The output pulse is usually programmable in terms of Ke, where Ke
is a discrete amount of the metered quantity per pulse, e.g., kilowatthours/pulse.
Maintenance of Pulse Initiators
Proper maintenance of mechanical pulse initiators requires correct adjustment of contacts for maxi-
mum tension, minimum resistance when closed, adequate clearance with contacts open, and low
friction loading on the meter rotor.
If the contact points become discolored or pitted, the points should be dressed with a burnishing
tool and then with paper until they are bright but not necessarily flat. If employed with discretion,
fine crocus cloth is sometimes useful. The use of a file on these points is bad practice and should be
avoided. If contacts require filing, they should be replaced as their service life will be limited. Small
pits in the contact points will not impair operation as long as the points are clean.
The same mesh conditions required for mechanical pulse initiators must be obtained for electron-
ics pulse initiators. However, friction due to mechanical make and break of contacts has been elimi-
nated in solid-state pulse initiators.
Fully solid-state pulse initiators with transistor-type switching typically do not require any type of
maintenance beyond simple replacement.
Kilowatthour and Kilowatt Constants
Meter pulse initiators normally have a three-wire pulse output. The wires are designated K, Y, and Z.
The pulse output is a series of alternating KY and KZ closures. Contact closure between K and Y is a
pulse as is closure between K and Z. Most initiators have break-before-make closures. The output can 379
be thought of as a single-pole, double-throw switch. Describing the output in relay terms is relevant
because many initiators have mechanical relay outputs. However, the current trend is toward solid-
state switches, with a dry output via Form C contacts.
SPECIAL METERING
Each pulse represents a distinct quantity of kilowatthour energy. The kilowatthour value of each
pulse is Ke.
Meter Kd is programmable in most solid-state meters and electronic registers which have KYZ
pulse outputs. The same multiplier can be derived for pulse initiator on electro-mechanical meters
using constants listed within manufacturer’s literature as either Pulses/Disk Revolutions (P/DR),
Revolutions/Impulse (R/I), or Revolutions per Pulse (Mp). All of these constants are either equivalents
or reciprocals of the particular constant, depending on the preference of the meter manufacturer.
Depending on the model and type, these constants are either programmable or must be specified
when purchased. Meter Ke equals Kh (watthours per revolution) 3 R/I (revolutions per pulse), divided
by 1,000.
The overall Ke, that is the effective Ke of pulses delivered to an end device by the output of the
pulse totalizer or relay, may be different from meter Ke. If the totalizer or any interposed relay has
an input/output ratio other than 1:1, the output Ke will equal the meter Ke times the product of the
input/output ratios.
If a two-wire device is operated by a three-wire pulse system, the value of each two-wire pulse will
be double the three-wire value.
For a particular demand interval, each pulse represents a distinct quantity of kilowatt demand.
If the demand interval is programmed into the pulse receiver, a demand indicator, pulse recorder,
translation system, or any other device, the value of the demand pulse Kd, is equal to the overall Ke
divided by the demand interval, expressed in hours.
Meter pulse systems determine demand by counting the total quantity of pulses accumulated over
a complete demand interval. Devices that operate on pulse rate, duration, or the times between pulses
might be erroneous, especially when pulse totalization is being performed.
The following gives the nomenclature, equations, and method of calculating the application of
pulse initiators.
Required data:
Maximum kW demand expected, e.g., kilowatts
Demand interval in hours
Pulse receiving capacity of demand meter per interval
Nomenclature:
kWh 5 kW 3 demand interval in hours
Pulse 5 The closing and opening of the circuit of a two-wire pulse system. The
alternate closing and opening of one side and then the other of a three-
wire system is equal to two pulses.
Ke 5 kWh/pulse, i.e., the energy
Mp 5 Meter disk revolutions per pulse
Ti 5 Demand interval in hours
Rp 5 Ratio of input pulses to output pulses for totalizing relay(s)
Np 5 Number of pulses required to advance receiver
Kd 5 Kilowatts per incoming pulse at receiver 5 (Ke 3 Rp) / Ti
Kh 5 Secondary watthour constant
Kilowatts divided by the pulse receiving capacity of the demand meter gives a possible value of Kd.
Obviously, no demand meter would intentionally be run to exactly full scale at the demand peak. Usu-
ally a choice of one-half to three-quarters of the maximum pulse capacity per interval of the receiver
is reasonable and will allow for load growth. Also, the choice should be such as to obtain convenient
values of Ke and Kd.
If revolutions per pulse is too small a fraction, the value of Ke must be increased and a lower scale
reading on the demand meter accepted.
380 kW Constants
Where Kd is the kilowatt value of the incoming pulse and where Ti equals the incoming demand
interval in hours,
HANDBOOK FOR ELECTRICITY METERING
Ke (final)
Kd 5 ———————
Ti
Kilowatt dial multiplier 5 Kd 3 kW ratio where the kW ratio equals the number of incoming
pulses to give a reading of 1 on the demand dial.
Available R/I, Mp, and other ratios are generally in the range of 1:10 to 10:1. Indicators which
operate on reflections off the meter disk are normally 2, 4, 6, 8, or 12 pulses per revolution. Ques-
tions concerning the availability of specific ratios should be referred to the meter manufacturer.
TOTALIZING RELAYS
When the totalization of more than two circuits is required on site, an intermediate totalizing relay
is generally necessary. This relay must be capable of adding pulses and, when required, subtracting
other pulses from the positive sum and retransmitting the algebraic sum to a receiving device. When
a totalizing relay with an input to output ratio other than 1:1 is used, the new output ratio must be
considered in adjusting the pulse value of the meter.
If, for example, a relay is used which has a 4:1 ratio, it is necessary to furnish four pulses to the
relay for every one that is retransmitted to the receiver. Pulse values for the meter must be in a 1:4
ratio to the values for the receiver. As an example, if the receiver pulse value was 38.4 kWh, it would
be 38.4/4 5 9.6 kWh at the meter.
Totalizing relays serve to combine pulses produced by two or more meters and to retransmit the
total over a single channel. Electronic types eliminate most of the problems of maintenance that are
associated with the older electromechanical mechanisms, but in no way relieve the situation of limit-
ing pulse rates to prevent overrun of the relays. Attention to pulse rates (pulses per minute) is espe-
cially important if several relays are cascaded to accommodate a large number of meters in a single
totalizing network.
The maximum pulse rate at which any relay can be operated is often limited by the receiver.
Electronic data logging receivers are capable of accepting very high pulse rates with very short time
duration per pulse, but many electromechanical receivers require relatively low rates and relatively long
pulses.
In electronic totalizing relays, all input circuits of a relay must be interrogated (scanned) in turn
and all pulses present must be output to the receiver before any channel can be again interrogated. A
limiting condition is pulses on all channels simultaneously, known as a burst condition.
For a multi-channel relay, the maximum input rate must be no greater than output rate divided
by the number of channels. For example, a seven-channel relay with a relay ratio of 1:1 and an
output rate of 56 pulses per minute has an effective input rate of eight pulses per minute per chan-
nel (56 4 7 5 8). In order to provide some safety margin, a rate of seven pulses per minute may be
utilized.
If the relay ratio is other than 1:1, this factor must also be considered. The formula used is output
rate times the ratio factor divided by the number of channels (56 3 4/7 5 32 for a four-to-one relay).
It must be kept in mind that the higher the output rate of the relay, the shorter the duration of
the pulses. This, too, can be a limiting factor for some receivers.
A general discussion of the electromagnetic type of totalizing relays can be found in Chapter 10 of
the 7th edition of this Handbook. For specific operating characteristics of modern totalizing relays, the
manufacturer’s literature should be consulted.
SPECIAL METERING
permit more days of data to be stored. Most meters allow at least 16 bit resolution or 65,535 pulses
per interval. The resolution of the data (per pulse) is controlled by this maximum pulses per interval
and the interval length or duration.
One useful memory design is the wrap-around type. Wrap-around memory overwrites the most
current data over the oldest data. The consequence of this type of memory is that the data is not
erased when the recorder is interrogated. These properties permit a certain level of redundancy in
data storage, in that the recorder will always retain the most recent amount of data depending on the
number of days that can be stored. The database at the translation site has all data up through the last
interrogation. The meter data can be reread if the communications introduced errors or if data stored
at the central computer is corrupted.
Data transmission can be by telephone, frame relay, fiber optic cable, packet radio, cable TV lines,
power line carrier, microwave, or other communication medium with the ability to transmit data
accurately. In the event the communication system fails, most solid-state recorders can be interrogated
by a portable reader or computer via an optical port. Each time there is communication between an
individual recorder and the central computer, the central computer runs a time check and may adjust
the time within the individual unit to match the system time. Each unit keeps time using the 60 Hz
power system as reference. In addition, each unit has a backup source for keeping time during power
outages.
When the communication system is telephone, packet radio, or other medium which is constantly
available, individual units can call or be called at frequent intervals. With more frequent interrogation,
problems can be discovered and solved promptly. Additionally, the units can be self-diagnostic, includ-
ing tamper detectors which initiate calls to report alarms.
PULSE ACCESSORIES
Auxiliary Relays
In some cases of totalization, it may be necessary to operate more than one device from the same
watthour meter pulse initiator or to operate an AC device and a DC circuit from the same pulse
source. Auxiliary relays may be used for this purpose. In general, such relays have a variety of combi-
nation of input and output circuits, each isolated from one another, in either a two-wire or three-wire
format. Relays are also available to convert two-wire pulses to three-wire and three-wire pulses to
two-wire.
Another auxiliary relay is the polarized relay—a direct current operated relay. It permits the use of
the two-wire circuit to transmit three-wire pulses. This is done by reversing the polarity of the direct
current applied to the relay coil. It is equivalent to using a positive pulse for one side of the three-wire
circuit and a negative pulse for the other.
Polarized relays are found to be necessary in the totalization and telemetering of pulses over some
distance. The features of these relays are the low current at which they operate, one to 20 milliamp
(mA) DC; the positive action upon polarity change, preventing stray currents from causing incorrect
operation; and the fact that the contacts for retransmitting consist of two sets which can be paralleled
or used to drive separate circuits. The polarized relay maintains a closed transmitting contact until the
opposite polarity is received. Polarized relays require only two wires between the source of pulses and
the relay, an obvious advantage for distance metering.
Load Pulse Isolation Relays
Often, metering pulses are provided to utility customers as a means of providing real time load data
to their energy management systems. The load pulses may be provided directly from the meter to the
customer’s energy management system. However, this direct connection may increase the risk of dam-
age to the meter, depending on what the customer does with their end of the pulse output cabling.
The solution many utilities have put in place is to utilize a load pulse isolation relay. The isolation
relay serves two purposes. The first is to create a convenient point of interconnection or a demarcation
between the customer and the utility. The second is that it provides a certain level of isolation between
the meter’s pulse output and the customer’s energy management system. In the case where a high
382
Meter Interface Enclosure
(For Load Pulse output options)
HANDBOOK FOR ELECTRICITY METERING
CUSTOMER / SUPPLIER
2-wire cable from energy
management system
voltage is inadvertently applied to the customer’s end of the pulse cabling, the isolation relay may be
damaged; however, the meter continues to perform its primary function—monthly billing. Figure 16-15
is an example of a wiring diagram for a typical isolation relay.
SPECIAL METERING
Totalization Through Translation
The use of recorded meter interval data provides a very flexible and popular method of totalization. It
requires that interval meter data be recorded and gathered from the meters into a computer system
(sometimes called a translation system or translator). This form of totalization requires no additional
hardware at the meter sites other than whatever communications equipment might be needed to
retrieve the interval data. It does not require the matching of current transformer ratios or service
voltages or careful manipulation of pulse multipliers, all of which are necessary with some other
methods of totalization. It also does not impose any physical proximity requirements on the meters or
services that are to be totalized. The meters can be located many miles apart, even at opposite corners
of a utility’s service territory.
The actual process of totalizing occurs after the fact using the meter interval data sets that are
retrieved and stored on the computer.
Energy—to determine totalized energy, the computer simply combines* the energies from each
meter source for the desired period.
Demand—to determine coincident demand, the computer combines* the individual consump-
tion value from each meter set, interval by interval, for the desired period to create a new
combined interval set. It then scans this new data set to select the peak or other desired value.
By its nature, this process does not make available any totalized values at the meter sites. This can
be a disadvantage in situations where totalized values are required by the customer. In these cases,
some other method must be used to provide totalized data to the customer, either in addition to or
instead of the interval data totalization method.
*Combining data: While the most common form of totalizing involves adding data from two constituent meters,
there can also be applications in which the data from one meter are subtracted from those of a second meter. Of
course, if more than two meters are involved in the totalization, the combinations can become more complex.
384 Air Conditioning Loads
Like water heating loads, air conditioning loads also lend themselves to utility load control applica-
tions when interrupted for short durations so as not to adversely affect customers during times of high
cost of generation and/or system peaking.
HANDBOOK FOR ELECTRICITY METERING
Meter Reading
FOR THE PAST 20 years, the process of reading of electric meters has changed more than it has in the
history of electric distribution. With the evolution of Automated Meter Reading (AMR) and the devel-
opment of the Advanced Metering Infrastructure (AMI) and smart meters, meter reading has been
increasingly automated and done remotely. The meter reading technology revolution will bring its own
challenges as more functionality of the meter system will require additional data and communications
with the utility smart grid. One fundamental will not change, and that is the requirement for accuracy
and timeliness in reading the metering systems. During this transition phase, the need still exists to
read meters manually and remotely.
The accurate reading of meters is an operation of major importance for any electric utility com-
pany, not only from a revenue standpoint but also in the promotion of strong customer relationships.
In the manual reading of meters, the meter reader makes many personal contacts with customers
and is often the only utility employee seen by the customer. With this in mind, most electrical utility
companies choose, for their meter reading personnel, employees who are conscientious and have the
natural attributes of friendliness and courtesy as well as a neat appearance.
A meter reader’s initial training course usually includes the fundamentals of good public relations,
familiarization with the types of metering equipment likely to be encountered, and thorough explana-
tions of the terms used in customer billing. It is important that meter readers be familiar enough with
their company’s organizational structure to be able to channel a customer’s requests and questions to
the proper departments.
Meter reading is carried out under a carefully planned program, and meter routes are arranged in
proper reading order. Readings are taken on a pre-arranged schedule to make the billing cycle practica-
ble and to provide an even flow of work for other operations, such as billing, auditing, and collecting.
To prevent undue annoyance to customers and to expedite the work, meter-reading records usually
contain notations showing the exact locations of meters, means of access, keys needed (if applicable),
and notes of any unusual conditions, such as physical hazards and/or dangerous pets.
If it is necessary to enter a customer’s premise, it is a good practice for readers to announce
themselves courteously and to produce proper identification when requested. Meter readers can be of
considerable help to the company in reporting irregularities, such as changes in customers, meters
without a reading record, vacant buildings, stopped meters, unsealed meters, unmetered service,
and any other condition that might adversely affect customer billing, safety, or the quality of service
rendered.
The principal duty of a meter reader is to obtain the meter readings and to make certain that these
readings are entered on the correct reading records by verifying addresses and meter numbers. A good
meter reader will enter the readings on mark sense cards or meter reading sheets in a clear, precise,
and legible manner.
385
386 How to Read a Watthour Meter and Electromechanical Meters
There are three styles of mechanical kilowatthour meter register types in general use. One has indi-
vidual dial circles as shown in Figure 17-1, another has interlocking dial circles as shown in Figure
HANDBOOK FOR ELECTRICITY METERING
REGISTER CONSTANTS
The register constant is also known as the dial constant, dial multiplier, or reading multiplier. It
represents the factor by which the register reading is multiplied to obtain the total registration.
METER READING
for customer billing. For small capacity
domestic meters, the register commonly
reacts directly in the billing units.
Changing the gearing between
the dial pointers and the disk shaft
introduces a constant. If the value of
this gearing is doubled, the speed of the
register pointers is halved and the read-
ing must be multiplied by two to obtain
the true value.
On modern high-capacity meters,
particularly with bi-monthly billing,
a four-dial register may not have the Figure 17-2. Conventional Four-Pointer Kilowatthour Dial
capacity to indicate the customer’s with Overlapping Circles.
consumption during the billing period
and the register may turn over. This
difficulty can usually be avoided by increasing the capacity of the register.
One way to increase register capacity is to add an extra dial at the left of the four dials commonly
used. This means that the capacity of the register is increased ten-fold and, instead of a maximum
reading of 9,999 kilowatthours, there is a maximum reading of 99,999 kilowatthours. Another solu-
tion is to change the register ratio or gearing and introduce a multiplying factor or constant of ten. In
this way, the capacity of the register is changed from 9,999 kilowatthours to 99,999 kilowatthours.
Many factors enter into the decision as to which method is used. Among these factors are the pro-
cedures and billing machines used by the billing group and whether they require major modification
to accept five-digit readings. On the other hand, constants other than one must be carefully controlled
and checked if errors are to be avoided.
Register constants are also introduced when meters are supplied from instrument transformers. If
the meters are supplied for use with instrument transformers of specified ratios, the register constant
is a multiple of ten, i.e., 10, 100, 1,000, etc. If transformer-rated meters are not supplied for specified
transformers, the register will read directly for the meter alone (considered as self-contained) and the
register constant will be the current-transformer ratio or the product of the ratios of the current and
potential transformers when both are used.
Meter manufacturers have recently made available demand registers with a scale and gear shifting
design that provides full-scale deflection at 50% and 100% of meter capacity. These registers provide
flexibility for future load growth with better reading accuracy at smaller loads.
Figure 17-3. Kilowatthour Register Showing Figure 17-4. Kilowatthour Register Showing
Reading of 0562. Reading of 2198.
388 Meters With Electronic Displays
Electronic meters or electromechanical meters with electronic registers use digital displays to indicate
power readings and other information. The display can show a series of readings, automatically step-
HANDBOOK FOR ELECTRICITY METERING
ping through each parameter at a programmed rate, five or ten seconds per step. This allows the meter
reader to record each reading by writing it on a meter card or by keying it into a handheld terminal.
In addition to measured values, the display can show time and date and perform an all-segments test
(Figure 17-5) to verify the proper operation of all display elements. Some electronic registers display
prompts such as “01” or “02” (Figure 17-6), which identify the parameters being displayed.
Demand Meters
Demand readings are usually measured in kilowatts, kilovoltamperes, or kiloVARs, with the quantity
measured being indicated on the dial face, the nameplate of the instrument, or an icon/identifier on
the electronic display. The demand device may be incorporated within a watthour meter or associated
with an auxiliary demand device connected to the meter. Demand readings consist of two types—
indicating or recording.
Figure 17-5. Electronic Display, All-Segments Tests. Figure 17-6. Electronic Display, with Prompts.
389
METER READING
Figure 17-7. Watthour Demand Register, Indicating Type.
Sweephand Type of Pointer Showing Maximum Demand, Plus a Sweephand Pusher Pointer,
Showing Current Demand (Thermal-Type Register)
How to Read—The maximum demand is read in the same manner as the mechanical-type register.
How to Reset—Unlike the mechanical register, the pusher pointer is not driven by a clutch in the
thermal-type register, but is directly attached to the moving element and must not be forced back to
zero. Therefore, it is customary to record the position of the maximum pointer, and then to reset the
maximum pointer back to, or slightly depressed beyond, the indication of the pusher pointer.
to operate a mechanism attached to the meter cover. The kilowatt demand for the billing period is
then automatically added to these dials and a record is made of the new readings. The dial pointers
are stationary between reading periods. A solid black index line equal in height to the demand dials is
used to denote the decimal point.
How to Reset—When resetting cumulative demand registers, which are motor operated, the reset
plunger must be firmly pushed against the reset knob until the knob starts to rotate. The plunger
should not be held against the knob for the completion of the accumulation because this may jam the
register. For a meter equipped with a reset lock device, the key is inserted, turned to the left one-eighth
of a turn and pushed forward, causing the plunger on the lock to push against the reset knob. When
the knob starts to rotate, the pressure on the key should be released and rotated back one-eighth of a
turn to its normal position and the key removed.
Dial-Type Pointers (Non-Cumulative)
How to Read—This register has three demand dials similar in appearance to the kilowatthour dials
(Figure 17-9). These dials are located at the bottom of the register and are read in the same manner as
the kilowatthour dials. The pointers are reset to zero after each reading. A solid black index line equal
in height to the demand dials is used to denote the decimal point.
How to Reset—The dial pointers are reset to zero by turning the reset lever approximately one-
fourth of a turn in a counterclockwise direction; then the lever is returned to its normal position.
METER READING
be returned for their salvage value and/or in the interest of cleanliness and safety at the customer’s
premise.
mitter. In other processes, there is either a one- or two-way connection from the office to the meter,
allowing the meter to be read upon request at any time.
THIS CHAPTER IS intended to provide the user with a reference to how to apply various different
meter forms to some of the more common wiring applications a user may encounter. This chapter
also provides precautions to be aware of when applying a specific form meter into an application
which does not meet Blondel’s Theorem.
Chapter Contents
Table Figure Page
393
394 Three-Phase Four-Wire Wye Circuit (Form 45S Meter) 18-24 421
Three-Phase Four-Wire Delta Circuit (Form 16S Meter) 18-25 422
Three-Phase Four-Wire Delta Circuit (Form 8S Meter) 18-26 423
A Simple Approach to the Analysis of Non-Blondel Metering Applications 424
HANDBOOK FOR ELECTRICITY METERING
Symbols used in this chapter are in accordance with American National Standards Institute
(ANSI) Y32.2 except where none are listed (see Figure 18-1).
Polarity Marks
Resistor
Ground
Link Terminal
Voltage Current Ground Self-Contained Phase Sequence
Switch Switch Strap Connection Block Indicator
1S 1 1 1 2-Wire SC 18-2
2S 1 2 1 3-Wire SC 18-2
3S 1 1 1 2-Wire TR 18-2
4S 1 2 1 3-Wire TR 18-2
5S 2 2 2 3-Wire TR 18-5
6S 2 3 2 4-Wire Wye TR 18-7
7S 2 3 2 4-Wire Wye TR 18-7
8S 2 3 2 4-Wire Delta TR 18-6
9S 3 3 3 4-Wire TR 18-8
10S 3 3 3 4-Wire TR 18-8
11S 3 3 3 4-Wire Delta TR 18-8
18S 2 2 2 3-Wire SC 18-3
13S 2 2 2 3-Wire SC 18-3
14S 2 3 2 4-Wire Wye SC 18-3
15S 2 3 2 4-Wire Delta SC 18-3
16S 3 3 3 4-Wire SC 18-4
17S 3 3 3 4-Wire Delta SC 18-4
24S 2 3 2 4-Wire Delta TR 18-6
25S 2 2 2 3-Wire SC 18-3
26S 2 2 2 3-Wire TR 18-5
29S 2 3 2 4-Wire Wye TR 18-7
32S 2 2 2 3-Wire SC 18-3
35S 2 2 2 3-Wire TR 18-5
36S 2 3 2 4-Wire Wye TR 18-7
39S 3 4 3 4-Wire TR 18-8
45S 2 2 3 3-Wire TR 18-5
46S 2 3 2 4-Wire Wye TR 18-7
56S 2 2 3 3-Wire TR 18-5
66S 2 2 2 3-Wire TR 18-5
76S 2 4 2 4-Wire Wye TR 18-7
While ANSI Form Designation does not specify TR or SC, the most common case is shown for clarity.
396 Table 18-2. Attributes of Bottom Connected Form Designations.
1A 1 1 1 2-Wire SC 18-9
2A 1 2 1 3-Wire SC 18-9
3A 1 1 1 2-Wire TR 18-9
4A 1 2 1 3-Wire TR 18-9
5A 2 2 2 3-Wire TR 18-18
6A 2 3 2 4-Wire Wye TR 18-13
8A 2 3 2 4-Wire Delta TR 18-18
9A 3 3 3 4-Wire TR 18-14
10A 3 3 3 4-Wire TR 18-14
11A 3 3 3 4-Wire Delta TR 18-14
18A 2 2 2 3-Wire SC 18-10
13A 2 2 2 3-Wire SC 18-10
14A 2 3 2 4-Wire Wye SC 18-10
15A 2 3 2 4-Wire Delta SC 18-10
16A 3 3 3 4-Wire SC 18-11
17A 3 3 3 4-Wire Delta SC 18-11
18A 2 4 2 5-Wire SC 18-11
29A 2 3 2 4-Wire Wye TR 18-13
35A 2 2 2 3-Wire TR 18-18
36A 2 3 2 4-Wire Wye TR 18-13
45A 2 2 3 3-Wire TR 18-18
46A 2 3 2 4-Wire Wye TR 18-13
48A 3 3 3 4-Wire TR 18-14
Application of Meters
Electromechanical meters and some solid-state meters are built with potential coils or potential
transformers. These meters may have limits on the voltages that a voltage coil can reliably measure.
More recent meters support a wide voltage range. These meters may have different voltages applied to
different voltage coils.
For example, modern FM 9 or FM16 meters may be applied to either 4-wire wye or 4-wire delta
services. This flexibility may not be present in earlier meter designs.
Switch board and panel meters are not covered by ANSI C12.10. Some manufacturers have marked
these meters with a form designation to represent the electrical connection of the meter; these nota-
tions may appear as “FM __” or “FM __Z.” The reference is generally to the equivalent socket meter
electrical connection.
Table 18-3 provides the power calculations and noted precautions when applying various form
meters for a given service application This table also lists some of the possible meter configurations for
given applications. The power formulas in Table 18-3 reference the phasor diagrams in Table 18-4.
Table 18-3. Application of Meters. 397
3-Phase 5, 45 Van * (Ia cos θa 2 Ib cos θb) 1 Vcn * Assumes balanced voltages on all
4-Wire Wye (Ic cos θc 2 Ib cos θb) 3 phases / Ib has to be reversed and
combined outside the meter
6, 7, 14, 29 Van * (Ia cos θa 1 Ib cos θb) 1 Vcn * Assumes balanced voltages on all
(Ic cos θc 1 Ib cos θb) 3 phases
46 Van * Ia cos θa 2 Van * Ib cos θb 1 Assumes balanced voltages on all
Vcn * Ic cos θc 2 Vcn * Ib cos θb 3 phases / Voltage polarities are
reversed in the meter for Ib
9, 10, 16, 39 Van * Ia cos θa 1 Vbn *Ib cos θb 1 Satisfies Blondel's Theorem
Vcn * Ic cos θc
3-Phase 5, 12, 13, 25, Vab * Ia cos (θa 1 30) 1 Vcb * Satisfies Blondel's Theorem
3-Wire Delta 26, 32, 35, 45, Ic cos (θc 2 30)
56, 66
3-Phase 8, 15, 24 Vab /2 * [Ia cos (θa 2 30) 1 Ib Assumes all 3-phase voltages are
4-Wire Delta cos (θb 1 30)] 1 Vcn * Ic cos θc balanced / Vcn 5 SQRT(Vcb² 2 Vbn²)
Van 5 Vbn 5 Vab /2
11, 17 Van * Ia cos (θa 2 30) 1 Vbn * Ib Van 5 Vab /2; Vbn 5 Vab /2;
cos (θb 1 30) 1 Vcn * Ic cos θc Vcn 5 SQRT(Vcb² 2 Vbn²)
Satisfies Blondel's Theorem
5, 26, 45, 56 Van * [Ia cos (θ 2 30) 2 Ib Assumes Van and Vbn voltages are
cos (θ 1 30)] 1 Vcn * Ic cos θc balanced / Ib has to be reversed and
combined outside the meter
Vcn 5 SQRT(Vcb² 2 Vbn²)
Van 5 Vbn 5 Vab /2
2-Phase 5, 12, 13, 25, Van * Ia cos θa 1 Vcn * Ic cos θc Voltage across line side terminals is 208
3-Wire Network 26, 32, 35, 45, volts. Satisfies Blondel's Theorem
56, 66
Ic
Ia B A Vcn
Van N
Ib
Ic
Ic Vcn
θc
Vcb
θa
Ic
Ia Vab
Van
N Ia
ABC Phase Sequence (CCW rotation)
CBA Phase Sequence (CW rotation) ABC Phase Sequence (CCW rotation)
CBA Phase Sequence (CW rotation)
Vac Van N
Van Vcn Ia
Ia N Ic
399
Internal Connections of Socket Meters
Front Views
Form 1A Form 2A
Single-Phase, Self-Contained 2-Wire Single Phase, Self-Contained 3-Wire
Single-Phase,
Form 3A Form 4A
Single-Phase, Transformer Rated 2-Wire Single-Phase, Transformer Rated 3-Wire
Form 3S
120 Volt One-Element
Two-Wire
Transformer-Rated
Socket Meter
Form 3S
240 Volt One-Element
Two-Wire
Transformer-Rated
Socket Meter
Form 12S
120–480 Volt
Two-Element
Three-Wire
Self-Contained
Socket Meter
Form 45S
120–480 Volt
Two-Element
Three-Wire
Transformer-Rated
Socket Meter
With Current
Transformers
Form 9S
120 Volt Three-Element
Four-Wire
Transformer-Rated
Socket Meter
Figure 18-23. Current and Voltage Transformers and Typical Test Switch.
421
Three-Phase, Four-Wire Wye Circuit
Form 16S
240 Volt Three-Element
Four-Wire
Self-Contained
Socket Meter
the Handbook for Electricity Metering. This section of Dr. Hardy’s book provides a useful explanation of
how to derive potential measurement errors when applying meter forms in applications which do not
satisfy Blondel’s Theorem.
Introduction
In North America a number of non-Blondel metering applications are very common. In fact
the most common metering scenario, the use of 2S meters to meter residential customers, is a non-
Blondel application. There is currently a movement to allow form 2S meters to be included under the
high accuracy metering standard, C12.20. Certainly 2S meters can be built which meet a 0.5% accu-
racy specification under balanced conditions. The question is what errors can we expect simply because
the meter does not meet the requirements of Blondel’s Theorem.
In addition to the residential 2S application there are a number of non-Blondel metering forms
used in commercial metering, and even more Blondel forms which are used in non-Blondel applica-
tions through creative use of PTs and CTs. In these commercial applications we may have an accuracy
class 0.2 meter used in an application where the “application dependent” errors are more than an
order of magnitude larger.
The various non-Blondel applications can be grouped by service type. There are five very common
configurations. Table 1 summarizes these applications.
In Figure 2 we see the form 2S meter installed in a typical residential 3-wire single-phase instal-
lation. The secondary side of the supply transformer is shown on the left. The secondary has a center
tap which is the Neutral conductor, N. This conductor is connected to the local earth ground. The
start and finish of this secondary winding have voltages Van and Vbn with respect to the Neutral. The
voltages Van and Vbn are connected to the meter blades 1 and 3 as shown. Under balanced voltage
conditions Van and Vbn are equal in magnitude and the angle between them is exactly 180°.
The challenge comes in calculating θ when the voltage and current appear at arbitrary angles. There is
a different and simpler approach available by couching the problem in a different way. This “vector”
approach is easier to apply and compute in more complex applications, AND provides a natural exten-
sion to the computation of → VA and→VAR.
If you have two vectors V and I then the dot product of the two vectors is:
→ →
V ? I 5 VIcos(θ) 5 Vx * Ix 1 Vy * Iy 2.0
By using the Cartesian representation in our calculations, the formulization becomes very straight
forward. All we need to remember is that:
Vx 5 Vcos(φv) Vy 5 Vsin(φv) 3.0
To calculate the power for a voltage V at a phase φv and a current I at a phase φI we have:
Power 5 VIcos(φv 2 φI) 5 Vcos(φv) * Icos(φI) 1 Vsin(φv) * Isin(φI) 5
Vx * I x 1 V y * I y 4.0
Now consider the issue of measuring power in a typical residential three-wire system. This can be
done with a Blondel compliant approach using a 12S or 25S meter, or in a non-Blondel method using
a 2S or 4S meter. The question is, what are the inherent inaccuracies with the non-Blondel approach?
Are the inherent errors significant in normal operation?
OBSERVATIONS
Unity power factor
• Unbalanced voltages cause no error if currents are balanced.
• Unbalanced currents cause no error if voltages are balanced.
• A 20% imbalance in voltage and current where I is proportional to V yields a 1% error.
• A 20% imbalance in V and a 50% imbalance in I yields a 2.5% error.
6.00%
5.00%
4.00% 5% | Imb
10% | Imb
% Error
20% | Imb
3.00%
40% | Imb
60% | Imb
2.00% 80% | Imb
100% | Imb
1.00%
0.00%
0% 1% 2% 3% 4% 5% 6% 7% 8% 9% 10%
% Voltage Imbalance
All balanced 0 0 120 0 100 0 120 180 100 180 24000 0.0 0.00%
Unbalanced voltages PF51 18% 0% 108 0 100 0 132 180 100 180 24000 0.0 0.00%
Unbalanced current PF51 0% 18% 120 0 90 0 120 180 110 180 24000 0.0 0.00%
Unbalanced V&I PF51 5% 18% 117 0 90 0 123 180 110 180 24060 260.0 20.25%
Unbalanced V&I PF51 8% 18% 110 0 90 0 120 180 110 180 23100 2100.0 20.43%
Unbalanced V&I PF51 8% 50% 110 0 50 0 120 180 100 180 17500 2250.0 21.43%
Unbalanced V&I PF51 18% 40% 108 0 75 0 132 180 125 180 24600 2600.0 22.44%
Unbalanced voltages PF1 PFa 5 PFb 18% 0% 108 0 100 30 132 180 100 210 20785 0.0 0.00%
Unbalanced current PF1 PFa 5 PFb 0% 18% 120 0 90 30 120 180 110 210 20785 0.0 0.00%
Unbalanced V&I PF1 PFa 5 PFb 18% 18% 108 0 90 30 132 180 110 210 20992 2207.8 20.99%
Unbalanced V&I PF1 PFa 5 PFb 18% 40% 108 0 75 30 132 180 125 210 21304 2519.6 22.44%
Unbalanced voltages PF1 PFa PFb 18% 0% 108 0 100 60 132 180 100 210 16832 2439.2 22.61%
Unbalanced current PF1 PFa PFb 0% 18% 120 0 90 60 120 180 110 210 16832 0.0 0.00%
Unbalanced V&I PF1 PFa PFb 18% 18% 108 0 90 60 132 180 110 210 17435 2603.2 23.46%
Unbalanced V&I PF1 PFa PFb 18% 40% 108 0 75 60 132 180 125 210 18339 2849.0 24.63%
Non-unity, equal power factors 429
• If both phases have the same power factor then the results are the same as for unity power
factor.
All balanced 0% 0% 120 0 100 0 120 120 100 120 120 240 100 240 36000 0 0.00%
Unbalanced voltages PF51 5% 25% 118 0 100 0 123 120 100 120 119 240 120 240 38380 450 1.17%
Unbalanced current PF51 5% 40% 118 0 100 0 123 120 80 120 119 240 120 240 35920 360 1.00%
Unbalanced voltages PF51 5% 71% 118 0 100 0 123 120 60 120 119 240 120 240 33460 270 0.81%
Unbalanced current PF51 5% 108% 118 0 100 0 123 120 40 120 119 240 120 240 31000 180 0.58%
Unbalanced V&I PF1 10% 0% 115 0 100 30 125 120 100 150 117 240 100 270 30917 866 2.80%
Unbalanced V&I PF1 10% 0% 115 0 100 60 125 120 100 180 117 240 100 300 17850 600 3.36%
Unbalanced V&I PF1 10% 0% 115 0 100 0 125 122 100 120 117 238 100 240 35685 1250 3.50%
Unbalanced V&I PF1 10% 73% 115 0 60 30 125 122 100 150 117 238 60 240 24028 1486 6.18%
Unbalanced V&I PF1 8% 71% 115 0 60 60 125 115 100 180 120 240 120 300 15933 2217 21.36%
Unbalanced V&I PF1 8% 40% 115 0 80 60 125 119 120 120 120 240 100 240 31598 898 2.84%
Unbalanced V&I PF1 8% 40% 115 0 80 30 125 120 120 150 120 240 100 210 31350 1039 3.31%
Unbalanced V&I PF1 10% 77% 125 0 80 60 117 125 120 150 115 245 60 270 23978 21469 26.12%
Analysis of 4-Wire Wye Metering 431
Using 2.5-Stator Meters (Forms 6S, 7S, 14S, 29S, 36S, 46S)
The 6S family of meters use the same computational approach as the 5S family, except that the differ-
OBSERVATIONS
• Absolute error is not affected by power factor, however the percent error can be much larger
because the absolute magnitude of the power is smaller.
• The larger the voltage unbalance the larger the error.
• If the phase B current is large, compared to phases A and C, then the percent error can be quite
large.
Figure 7. 4-Wire Delta Metering Using Figure 8. 4-Wire Delta Metering Using
2 Stator Meters. 2.5 Stator Meters.
OBSERVATIONS
• There is no error contribution from the phase C metering.
• Error contribution from phases A and B is identical to the 2S metering application.
Table 4. Errors Under Various 4-Wire Delta Non-Blondel Applications.
All balanced 0 0 120 0 100 0 120 180 100 180 20800 24000 0.0 0.00%
Unbalanced voltages PF51 20% 0% 108 0 100 0 132 180 100 180 20800 24000 0.0 0.00%
Unbalanced current PF51 0% 20% 120 0 90 0 120 180 110 180 20800 24000 0.0 0.00%
Unbalanced V&I PF51 20% 20% 108 0 90 0 132 180 110 180 20800 24240 2240.0 20.53%
Unbalanced V&I PF51 20% 50% 108 0 75 0 132 180 125 180 20800 24600 2600.0 21.32%
Unbalanced voltages PF1 PFa 5 PFb 20% 0% 108 0 100 30 132 180 100 210 10400 20785 0.0 0.00%
Unbalanced current PF1 PFa 5 PFb 0% 20% 120 0 90 30 120 180 110 210 10400 20785 0.0 0.00%
Unbalanced V&I PF1 PFa 5 PFb 20% 20% 108 0 90 30 132 180 110 210 10400 20992 2207.8 20.66%
Unbalanced V&I PF1 PFa 5 PFb 20% 50% 108 0 75 30 132 180 125 210 10400 21304 2519.6 21.64%
Unbalanced voltages PF1 PFa PFb 20% 0% 108 0 100 60 132 180 100 210 10400 16832 2439.2 21.61%
Unbalanced current PF1 PFa PFb 0% 20% 120 0 90 60 120 180 110 210 10400 16832 0.0 0.00%
Unbalanced V&I PF1 PFa PFb 20% 20% 108 0 90 60 132 180 110 210 10400 17435 2603.2 22.17%
Unbalanced V&I PF1 PFa PFb 20% 50% 108 0 75 60 132 180 125 210 10400 18339 2849.0 22.95%
433
then errors arising from the non-Blondel approach are generally less than 0.5%. With wider voltage
imbalance, non-unity power factors, and imbalanced currents, these errors can grow to several percent.
Considering the types of loads generally encountered, residential applications probably do not
suffer significant added metering error due to the non-Blondel nature of the 2S meter. However, there
are likely significant numbers of commercial and industrial applications where the dominant error in
the metering is the non-Blondel nature of the installed service.
Chapter Conclusion
This chapter focused on the application of electricity watt-hour meters to measure electrical quantities
for a given service type. The diagrams on internal connections for watt-hour meters and the associated
form numbers are in accordance with ANSI C12.10. For reference to legacy meter forms which may
not be included in this revision of the Handbook, readers are encouraged to reference prior editions of
the Handbook For Electricity Metering. The reader is also encouraged to reference the appropriate ANSI
standards associated with meter sockets, switches, and instrument transformers to provide additional
guidance when designing solutions to meter given service types.
Chapter 19
The Customers’ Premises,
Service, and Installations
When the utility provides service to the customer, it is important to consult the specific utility’s
service entrance requirements before starting any work. Requirements are not the same in each utility
and not following the local utility’s rules can be costly.
Two-wire service may be taken from a two-wire, three-wire, or four-wire distribution system.
One wire of the two-wire service is grounded by the utility near the transformer and by the electrical
contractor or customer at the customer’s service equipment.
Three-wire, single-phase service may be supplied from either a single-phase or a polyphase distri-
bution system. In this service, one conductor is normally grounded with the nominal voltage 240 V
between the ungrounded conductors and 120 V from each of the ungrounded conductors to the
grounded conductor. Some streetlight services are three-wire 480 V, 240 V from line to ground and
480 V from line to line.
Three-wire network service is supplied from a four-wire, wye distribution system. One line is
always grounded. The nominal voltage for this circuit is 208 V between the ungrounded conductors
and 120 V between each of the ungrounded conductors to the grounded conductor. Note that 208 V
is the phasor resultant, not the algebraic sum, of the two line-to-ground voltages.
Three-wire, three-phase service may be supplied from either a closed-delta or an open-delta trans-
former bank. The difference between these two connections is largely one of capacity. The output of an
open-delta bank is 58% of the output of a closed delta where the individual transformers are similar.
Four-wire, three-phase, delta service is often used for combined power and lighting. It is a delta
service, with one transformer center tapped to provide 120 V for lighting. The center tap must be
grounded. In this case, the voltage between any two phase wires is 240 V; between the grounded wire
and either of two phase wires is 120 V and between the grounded line and the third phase wire is
208 V. The transformer bank may be either open-delta or closed-delta.
Four-wire, three-phase, wye service is also used for combined power and lighting. Under balanced
load conditions, the grounded neutral does not carry current.
If the voltage from neutral to phase conductor is 120 V, the voltage between any two phase wires
is 208 V. Likewise, if the voltage from the neutral to the phase conductor is 277 V, the voltage between
any two phase wires is 480 V.
Primary service is service above 600 V. The customer might own the transformer, reducing the
service voltage from the primary level to the operating level requested by the customer. The metering
is done with instrument transformers, normally installed at the point where the customer facilities are
connected to the electric utility.
Since it is necessary to determine relatively small differences among voltages, this test requires a
voltmeter rather than a voltage tester.
Phase-Sequence Indicator 437
In a single-phase circuit, a rotating-disk phase-sequence indicator will give no indication of phases.
On either a three-wire network or a three-phase circuit, the disk will rotate.
Circuit Protection
Surge Protection
Surge protection is designed to protect circuits and connected equipment by providing a bypass to
ground when the supply circuit voltage rises above safe limits. Sometimes called lightning arrestors or
surge arrestors, surge protection devices have acquired an important role in the protection of meters
and the customers’ consumer electronics. Basic surge protection provides a path of least resistance
between each ungrounded line conductor and ground, dissipating much of the energy of a high energy
surge. Normal line voltages are not capable of conducting down this path to ground. In electronic
meters, metal oxide varistors (MOVs), some electronic components (i.e., resistors, fuses), or air gap
spacing on the circuit boards are often used as protection against lightning.
An example of simple protection is the spark gap arrestors of socket-type electromechanical
watthour meters. In this type of meter, there are two spark-gap pins protruding from the meter base.
When the meter is assembled, the current-coil leads are located near but not in contact with these
pins. If lightning or a system disturbance causes a sudden surge of high voltage that might break down
the meter insulation, an arc will be established across one or both spark air gaps. The surge will then
go through the pins to the stainless steel straps on the back of the base, into the socket, and then to
ground. The ears that are to the left and right of a meter socket are the connection to ground for the
contacts on the base of the meter.
Time-Delay Fuses
Many small motors have a starting inrush current several times the normal running current. This
inrush current is of such short duration that, although it may cause an annoying voltage dip, it does
not result in a serious fire hazard. The time-delay fuse or circuit breaker permits the passage of such
starting currents without opening. However, should this high current last for more than the normal
starting period of the motor, as might be the case if the motor stalled, the fuse or breaker will open
and clear the circuit. Time-delay fuses or circuit breakers will eliminate many “no-light” trouble calls
by reducing unnecessary circuit openings.
Grounding
A ground is a conducting connection between an electric circuit or equipment and the earth. Such a
connection may refer to the grounding of the neutral wire of a circuit or to the connection between
hardware such as meter sockets or switch cabinets and the earth.
When considering when and how to ground, considerations such as conditions of use and the
location of equipment have a bearing on the method of grounding. The NEC must also be consulted
for the most up-to-date rules on grounding.
connection errors.
Many connection errors can be self-corrected by the installation of an electronic meter. As
opposed to an electromechanical meter, an electronic Form 15 meter will meter properly if the lighting
and the high-leg are swapped whereas the electromechanical meter would have registered incorrectly.
When replacing an electromechanical meter with an electronic meter, a thorough analysis of the
socket and wiring must be performed to catch an existing connection error.
Connection Errors
With the current coil connected in the grounded service conductor, the meter may be partially or
completely by-passed. To correctly measure the power in a two-wire circuit, the current coil in the
watthour meter must carry all of the circuit’s load current. To accomplish this, the current coil
must be connected in series with the ungrounded line. See Figure 19-2. If the current coil is in the
ungrounded leg and the watthour meter has been installed incorrectly as shown in Figure 19-2 and a
ground occurred on the load side of the meter, there are two paths for current flow. The meter cur-
rent coil is effectively shunted by the ground path. The meter is bypassed and the energy used is, to a
considerable degree, unmetered and unbilled.
In Figure 19-3, the current coil is connected to the ground wire and the fuses are not blown. As a
result, the meter is registering forward without a load being used because the meter and the load wires
provide another path to the transformer for loads not properly on this meter. The amount of current
thus shunted will depend on the resistance of the neutral conductor. Due to numerous splices, the
resistance may be quite high, causing even more current to take the path through the meter.
The direction of rotation of the incorrectly wired meter will depend on the direction of current in
the neutral. If a three-wire load is taken from the same service as is shown in Figure 19-3 for Cus-
tomer C, any imbalance in the three-wire load will produce rotation in the incorrectly wired meter.
Similar precautions must be taken when connecting a three-wire meter. If the neutral instead of
an ungrounded line is connected to one of the meter coils, there is a variable error in the current
components and a constant error of 50% in the voltage, as 120 V instead of 240 V is applied to the
voltage coil.
A three-wire, single-phase meter installed on a two-wire circuit without alteration to fit the condi-
tions may have one current coil bypassed by the customer’s ground. Correct metering of a two-wire
circuit with a three-wire, single-phase meter can be found in the Handbook for Electricity Metering,
10th edition, “Metering Two-Wire Services with Three-Wire Meters,” page 465.
A three-wire, three-phase service is properly metered with a two-stator meter. However, if one of
the transformers has a center tap grounded, it is possible for energy to be consumed on this service
that would not pass through the current coils of the meter (Figure 19-4).
Figure 19-4. Wrong Connection for a Two-Stator, Three-Wire Meter on a Delta Bank with Grounded
Transformer Center Tap.
442 Other types of errors are possible, such as when load circuits are incorrectly connected at some
point on the source side of the meter. In multi-family buildings, incorrect connection of customer’s
service conductors can result in the registration of one customer’s use on their neighbor’s meter. It is
also possible that meters measure loads other than those for which they are intended, such as a meter
Handbook for Electricity Metering
Network Neutral
In the three-wire network circuit (two phase wires and neutral from wye-connected transformers),
the condition is somewhat different. Under balanced load conditions and with only phase-to-neutral
loads, the neutral wire carries the same magnitude of current as the phase wires.
If the neutral is broken in a network circuit, the customer loses the protection of the ground.
Appliances operating at 208 V will not be affected. Branch circuits operating at 120 V will normally be
dead, but currents may find a path to the other phase wire, thus putting 120 V lamps in a level lower
or higher than 120 V.
When the only ground that is lost is at the meter in a three phase meter, the meter is connected
properly and the required metered loads are grounded. There may be times when the ground connec-
tion at the meter is cut.
If the meter does not see ground, then metering errors in the three-phase meter could range from
0% to 50%, depending on how much of the loads are phase-to-ground versus phase-to-phase.
The ground connection at the meter should be checked with a voltmeter to a phase and then
the system neutral should be checked to the same phase. The voltages should be the same unless the
ground connection at the meter is broken. Calculating the percent of error would be impossible unless
the amount of usage phase-to-phase versus phase-to-ground can be determined.
Meter Location
Indoor
When meters are installed indoors, they should be located near the point of service entrance to avoid
long runs of unprotected or unmetered conductors. If the meter is in a partitioned basement, it should
be installed in the same area that the service enters.
Since meters must be read and sometimes tested in place, they should be mounted at a convenient
height, i.e., between three and six feet from the floor. In addition, since meter accessory equipment
may have to be changed as a result of changes in the customer’s load, space sufficient to permit such
changes must be provided.
The area in which meters are located should be free of corrosive fumes and excessive moisture.
Meters should not be installed near furnaces or water heaters, nor should they be mounted under
pipes that may drip. Also, the wall or panel on which the meter is mounted must be free of vibration.
Outdoor
Outdoor meters should not be mounted overhanging driveways or walks where they may either be
damaged by traffic or may cause accidents to pedestrians.
Although meters are temperature-compensated well, they should be installed out of direct sunlight,
i.e., the north side of the house if the service permits.
As in indoor metering, the height at which the meter is mounted must be convenient. However, in
areas where it snows, a height at least four feet above the ground is recommended.
Figure 19-8. Socket and Meter with Flexible Bypasses in Place also known as Horn Bypass.
Before installing the meter, the following tips and checks must be performed: 447
• Check that meter’s voltage clips are closed.
• Check the correctness of the electrician’s wiring to ensure that the grounded wire is connected
Socket Adapters
When modernization of customers’ services is taking place at the same time that a changeover from
bottom-connected to socket-type meters is being made, adapters which permit this replacement of
meter types may be considered. These adapters essentially give a socket meter a base which allows
for installation in a location designed for a bottom-connected meter. The adapter may be no more
than a low-cost shell to hold the socket meter with facilities for bringing out flexible leads to the
service switch, or it may be equipped with a standard terminal chamber similar to that of the bottom-
connected meter.
Socket adapters provide a wide range of functionality to the meter installation. Some of the
common types of socket adapter are socket-based surge arrestors, disconnect devices, ground-strap
adapters, and service transfer switch adapters.
Bottom-Connected Meters
The handling of A-type meters for installation or removal is different than what is required with
S-type meters. All line and load wires must be removed from the several meter terminals before the
meter can be lifted from its location. Unless the line wires can be deenergized by opening a service
switch, removing the main fuse, or cutting the energized wires at the weatherhead, these wires must be
handled carefully at all times.
Visually inspect the insulation of the wires before working on energized meters, as frayed wiring
could cause a shorting condition.
448 Connection screws must be tight and each wire tested by pulling and shaking it to ensure they are
not loose. Keep in mind that smaller wires can be cut off in the terminal hole by forcing the terminal
screws down.
Where a service interruption cannot be tolerated for a period long enough to remove and replace
Handbook for Electricity Metering
a meter, the use of jumpers is necessary. When test facilities are provided or, in certain types of service
installations, with line and load terminals available in the service equipment assembly, this is a simple
procedure with test links or with leads equipped with spring-clip terminals. When the meter is located
directly in the line, it is necessary to remove insulation from the line and load wires ahead of and
beyond the meter terminals. Jumpers are then attached to the bare spots.
Placing such jumpers calls for careful work. If there is any doubt as to where jumpers should be
connected, a voltage tester should be used. A jumper connected across a voltage difference is a short
circuit and will result in a flash.
Any bare spots must be properly taped after the job is completed.
When the meter is mounted above a test block, a change of meter is simple since the meter can be
bypassed and isolated by test-block links and jumpers. There are two different test-block connections.
In one, the test-block terminals are in the same sequence as the meter terminals and, to bypass the
meter, flexible jumpers are used to connect each of the line wires to the corresponding load wires. The
second arrangement is line-load, in which the test block link can be used to short adjacent terminals.
It is generally easy to distinguish one arrangement from the other, though a voltage tester should be
used if there is any doubt.
Often, a bottom-connected meter is mounted directly above the service switch which has test
connections involved. Since such test connections take many forms, the use of a voltage tester or
voltmeter is advisable.
Outdoor Installations
To adapt the bottom-connected meter to outdoor use, several types of meter enclosures have been
developed. These include the complete enclosure, generally with a window through which the meter
can be read; the semi-enclosure, in which the glass cover of the meter projects through a round open-
ing in the box cover; the “banjo box,” which provides a disconnect device and an enclosure for the
meter terminals; and conduit pull boxes modified to enclose the meter terminal block.
A conduit pull box with a single cover to enclose both the meter terminal chamber and pull box
is often designed so that it also encloses a disconnect feature. This permits separation of the meter
terminal chamber from a terminal block to which line and load wires are connected. With such
construction, the meter can be tested or changed without service interruption.
Test Switches
Test switches are generally used if meters are in the secondaries of instrument transformers. The
functions of the test switch are to short-circuit the current transformer secondaries and to isolate the
meter so that it may be tested or changed without hazard.
When the test switches are open, the current blades are grounded. The voltage blades, however,
may be live and are therefore a hazard. When both voltage and current transformers are used, the
low capacity of the voltage transformers limits the hazard to some degree, but when only current
transformers are used and the voltage connections are made directly to the line, the entire capacity
of the power transformer is behind this circuit and extreme care must be used. A screwdriver or even
a connector clip falling across these blades can cause a severe flash. Because of this danger, many
companies install low-current, high interrupting-capacity fuses in the voltage circuits of meters used
with current transformers. Another precaution that can be taken is to place insulating blocks over the
open voltage blades of the test switch.
Removing or replacing test switch covers must be done carefully. Some non-metallic covers have
metal end walls that can cause a phase-to-ground short.
When paralleled current transformers are used, it is necessary to make sure that the test switch
shorts the secondaries of all the connected current transformers before disturbing the meter leads.
to permit the installation of all necessary meters, instruments, auxiliary devices, or test facilities
of any type, whether they be front connected, back connected, surface mounted, or flush type.
5. The arrangements should be such that the secondary wiring may be installed in a manner to
facilitate checking of connections.
By following these specifications, control of all metering transformers and conductors rests with
the utility.
When extremely high-capacity current transformers are used, spacing of bus bars must be adequate
to avoid interference between individual transformers.
There are many advantages gained by mounting instrument transformers in the customer’s switch-
gear, e.g., protection, appearance, and, in many cases, economy.
There are also disadvantages, e.g., access to the instrument transformers when testing the meter,
liability if one of the transformers catches on fire and damages the switchgear, ensuring against
tampering, and ensuring that none of the current transformers have been shorted.
Pole-Top Metering
Pole-top location of instrument transformers is often necessary. Poles with distribution equipment
mounted on them that require maintenance are generally avoided for metering, since the reduction of
climbing space may present hazards to utility personnel.
Instrument transformers may either be mounted on crossarms or be put in place as pre-wired
units on cluster mounting brackets. These brackets are generally designed to allow sufficient free
climbing space and the transformers used are able to be installed in any position. For low-voltage
metering, window-type current transformers offer convenience and economy.
Meters may be located on the pole or the instrument transformer secondary may be extended to
a nearby building where a more suitable location may be found. In the latter case, an underground
secondary run is sometimes involved. Such a conduit or cable run coming down the pole and extend-
ing up the building wall may form a U-shape which will often collect water. When installing cable
or conduit, care must be taken to prevent this condition. The comments in Chapter 10, “Instrument
Transformers,” referring to the length of a secondary run should be consulted.
Since pole-top metering is generally distant from any extensive water piping system, other forms
of grounding must be employed. This is particularly true when meters are installed in an enclosure
on the pole, since the enclosure must be well grounded to protect the installer. To guard against high
ground resistance, it is good practice to bury the ground wire connecting multiple electrodes in a circle
around the pole so that the person working on the meter or enclosure is standing inside the ground-
ing network. All grounding in the area should be bonded together.
Grounding of instrument transformer cases must be in accordance with general utility practice.
The grounding practice determines whether secondary conductors are in metallic or non-metallic
enclosures.
Give the entire job a good once over before leaving it.
• Check the job in general for good workmanship and safety before leaving. Be sure the area
surrounding the meter is left clean and neat.
Meter employees are the utility in the eyes of many customers. They can make a good impression on
the customer by being neat in dress, accurate in work, and courteous at all times. Having equipment
and tools in good, clean condition will build the customer’s confidence in the utility and reassure the
customer of the employee’s skill. Sloppy dress, actions, and equipment leave a poor impression.
There are probably many other practices which are followed on local levels throughout the coun-
try, but if employees observe those listed, they will turn out a good job. Failure to follow any one of
these practices may result in extensive property damage, personal injury, outage of service, or a loss
of revenue. And, last but by no means least, it may impair that valuable asset to a public utility—good
customer relations.
Safety
Though this is the last section in this chapter, safety must be first and foremost in the technician’s
mind when performing meter work. Safety has no beginning or end—it must be continuous. Some
safety tips include:
• Park vehicles so they don’t need to be backed out when the job is complete.
• Wear all personal protective equipment (PPE) from the time you leaves the truck until you
return to it when the job is complete.
• Inspect all PPE and tools prior to use.
• Survey the job to determine test equipment or supplies will be staged.
• Determine an escape route in case of a flash or a fire and identify any trip hazards or uneven
ground.
• If the work area is cluttered, ask that it be cleaned up. A flash can catch nearby debris on fire.
• Don’t carry too much equipment at a time to the job site. If necessary, use a cart.
• Stage all equipment and tools before opening the meter enclosure so that a socket won’t be
exposed while going back to the truck for more tools.
• Do not carry anything in such a way as to block your eyesight.
• Take a deep breath and hold it while removing or installing a meter. If a flash occurs, a person’s
first reaction is to take a deep breath and inhale the fire and smoke.
• Perform a thorough inspection of the removed meter and the meter socket for signs of burning
or arching. Look for discoloration or melting of the conductors coming off the socket terminals
and notify the customer and your supervisor if such signs exist.
• Make sure all tools and equipment are picked up.
• Always leave the site safe.
• Even though the truck is parked so it doesn’t need to be backed up to exit the site, perform a
four-corner walk-around to ensure there are no dangers present.
Chapter 20
THE STANDARDS LABORATORY is part of the meter department but is often a separate division from
the meter shop. The scope of the standards laboratory may include only the certification of portable
watthour standards and other portable instruments, or it may be extensive and include such functions
as new product approval testing, acceptance testing of materials and apparatus, special investigations,
and research work. Regardless of the scope, the fundamental responsibility of the laboratory is to
obtain accurate measurements while maintaining traceability to national standards.
The basic functions of the standards laboratory are as follows:
1. Calibration and certification of working standards by comparison with secondary reference
standards.
2. Calibration and certification of secondary reference standards by comparison with primary
transfer standards.
3. Calibration of primary transfer standards with fundamental primary standards. If the primary
standards are maintained within the standards laboratory, the comparison is an internal func-
tion. For those electric utility companies that do not maintain primary standards, the calibra-
tion of transfer standards may be performed in another approved laboratory that maintains
traceability to national standards.
4. Calibration and certification of transfer standards directly to standards maintained by the
National Institute of Standards and Technology (NIST) or with an approved laboratory that
maintains direct traceability to NIST.
5. Intercomparison of primary standards. The direct current (DC) volt references, standard resis-
tors, time base, and associated equipment employed to calibrate the primary transfer standard
are the laboratory’s highest internal authority on the value of electric measuring units and
should be intercompared regularly to ensure the integrity of their measurement accuracies.
6. Regular calibration of primary standards. Primary standards are sent periodically for calibration
to NIST or to an approved laboratory that has its own primary standards regularly certified by
NIST.
7. Acceptance tests and determination of the characteristics of new types or designs of watthour
meters, watthour standards, portable instruments, instrument transformers, and other electric
measuring devices to determine their suitability for use by the electric utility company.
8. Special investigations relating to metering or measurement problems. Such investigations may
require extensive tests both in the laboratory and in the field under actual operating conditions.
9. In addition to these basic functions, the standards laboratory may include in its scope of opera-
tions the repair of electric instruments and related devices. Assistance may be given to other
sections of the electric utility company with electric measurements and tests.
453
454 Key instruments used in the standards laboratory:
1. Primary standards for DC voltage, resistance, and time
2. DC to alternating current (AC) primary transfer standards
HANDBOOK FOR ELECTRICITY METERING
Standard Types
An electricity reference standard is an instrument that measures electrical parameters and is accepted
as a basis for comparison. This acceptance is based upon its traceable accuracy and the criteria used
to define its accuracy. The standard is used as a comparison to measurement instruments of lesser
accuracy and therefore plays a key role in the standards laboratory.
Electric utility companies use reference standards to ensure the integrity of their revenue billing
system. Because consumers are charged a fee for the energy they use, it is important that the accuracy
of the revenue billing meters be maintained, documented, properly stored, and easily proven. The
various types of reference standards are the foundation of that responsibility. In addition, reference
standards are used to evaluate the performance of new metering products and to do approval testing
of those new products.
There are different types of standards designed for different applications.
PRIMARY STANDARDS
Primary standards are the basis for all measurements and consist of a DC voltage standard, a standard
resistor, and a time standard.
Zener-based DC reference standards (such as the Fluke Zener Reference model 732B) and the
Josephson Junction (such as the HYPRES model 2000) have effectively replaced the dated saturated
and unsaturated standard cells which are no longer manufactured. When using the Zener Reference
it is common to maintain a four-cell array of Zener References, as this provides for a good statisti-
cal group and offers redundancy should one fail. The Josephson Junction is maintained by some
National Metrology Institutes, such as NIST, but to this date is not commonly used by electric utility
laboratories.
Resistance standards (such as the Guildline model 9330/10k) are used as the primary reference
for the ohm. If the laboratory maintains tight temperature control, then the standard resistor can be
used at room temperature. Alternatively, for more precise ambient temperature control the standard
resistor can be maintained in a temperature controlled oil bath for maximum stability.
Time standards consist of crystal-based universal time/frequency counters (such as the Hewlett
Packard model 5334B) or global positioning systems (GPS) (such as the Arbiter Systems Satellite
Controlled Frequency Standard model 1083B). These two modern time standards have effectively 455
replaced the pendulum clock.
Primary standards are normally used to calibrate the primary transfer standard. The three funda-
mental calibrations performed on the primary transfer standard are DC voltage, DC current (using
OHMS
SECONDS
VOLTS WATTHOURS
Figure 20-2. The Radian Research Model RD-22 Primary Transfer Standard.
SECONDARY STANDARD
The secondary standard is also referred to as the working reference standard and is tested against the
primary transfer standard to ensure its accuracy. The role of the secondary standard is to test portable
working standards. Some electric utility laboratories may not use a secondary standard. Instead, they
may use the primary transfer standard in this role.
The Scientific Columbus model SC-60 and the Radian Research model RM-11 were very popular
secondary standards. The Radian Research model RD-21 is a modern secondary reference standard
with accuracy of 0.02% that applies to all measurement functions across the entire operating range
of the product, and includes the variables of stability, power factor, traceability uncertainty, and
test system errors. The RD-21 provides simultaneous measurements of multiple functions including
watthours, VARhours, VAhours, Q-hours, volts, amps, watts, VAR, VA, millivolt-hours, milliamp-hours,
volt-squared-hours, amp-squared-hours, phase angle, power factor, and frequency. The wide auto-
ranging voltage input of 30 to 600 volts and wide auto-ranging current input of 0.05 to 120 amps
have effectively eliminated the need for external transformers historically used to isolate the reference
standard from the standard under test. These external transformers added unnecessary error to the test
system. The RD-21 can accurately sense and measure the exact voltage and current test signals being
applied to the standard under test, as well as analyze distorted waveforms up to the 50th harmonic
order, allowing for testing of harmonic analyzing instruments (see Figure 20-4).
Normally a quantity of three of these standards would be used together as a standard bank. The
use of three improves repeatability of measurements and ensures measurement integrity.
457
External Primary
Internal
Electronically
Compensated Integrating A/D
Transformer with Converter
Auto-ranging for Voltage
Circuit
External
Primary Reference
Internal
(Time/
Frequency
Frequency)
Reference
Figure 20-3. Block Diagram of the RD-22 Interfaced with Primary References for a DC to AC Accuracy Transfer.
There are sourcing standards available such as the Radian Research RS-933, that replaced the RS-
703A. The RS-933 is used by many electric utility companies as a secondary working standard because
it is a complete system capable of collecting data from multiple standards being tested simultaneously
and then displaying and saving the test results.
Figure 20-4. Radian Research Model RD-21 Figure 20-5. Radian Research Model RD-20
Portable Reference Standard. Portable Working Standard.
It has its accuracy tested against a secondary working standard. Electric utility companies typically
test their portable working standards monthly, quarterly, or bi-annually, and it may be found as the
reference in meter shop test bench and field test kits. The Scientific Columbus model SC-10 and the
Radian Research model RM-10 were very popular portable working standards. The Radian Research
model RD-20 is a modern portable working standard with accuracy of 0.05% that applies to all
measurement functions across the entire operating range of the product and includes the variables of
stability, power factor, traceability uncertainty, and test system errors (see Figure 20-5).
The RD-20 provides simultaneous measurements of multiple functions, including watthours,
VARhours, VAhours, Q-hours, volts, amps, watts, VAR, VA, millivolt-hours, milliamp-hours, volt-
squared-hours, amp-squared-hours, phase angle, power factor, and frequency. The wide auto-ranging
voltage input of 60 to 600 volts and wide auto-ranging current input of 0.05 to 120 amps allow for
simple operation in the field. The RD-20 can also analyze distorted waveforms up to the 50th har-
monic order allowing for customer load analysis in the field.
Digital Multimeter
The digital multimeter has effectively replaced the role
of the potentiometer and resistance bridge methods in
the standards laboratory. The 8½-digit multimeter is
used as the key instrument for performing intercompari-
sons of primary standards. The Hewlett Packard model
3458A is a common laboratory multimeter.
Radian RS-933
Radian RD-22 (X3)
Computer Controlled
Multimeasurement
AC Voltage and
Transfer Standard
Current Source
External Primary
Reference Units Under Test
(Time/Frequency)
Figure 20-7. Block Diagram of the Radian Research RD-22 and RS-933 Test System.
460
Intrinsic
Volt
HANDBOOK FOR ELECTRICITY METERING
NIST
Intrinsic
Ohm GPS
Intrinsic
Volt Ohm
Second
Second
Fundamental
Digital
Primary
Multimeter
References
Portable
Working
Standard
primary watthour standard. However, it is important to note that Alternative B will not provide the
same degree of accuracy and certainty of measurements. Note 1 of Figure 20-8 points out that some
manufacturers, such as Radian Research, have a complete metrology laboratory and maintain all of the
necessary instruments, including both DC and AC, for traceability to NIST. These laboratories provide
certification and calibration services to the electric utility industry. Some electric utility companies
choose Alternative B and utilize a metrology laboratory, such as Radian Research, for their traceability
to NIST.
The particular standards laboratory approach used will vary among electric utility companies and
may depend upon factors such as size of the utility and the accompanying description of its laboratory
responsibilities.
Therefore, certification of instruments may be obtained from sources other than NIST, such as
manufacturers or other laboratories having primary standards certified by NIST. In all cases, the
calibration of the equipment used to establish the watthour should be traceable to NIST.
Standard Attributes
A reference standard, regardless of its type or classification, has certain attributes by which it is classi-
fied. These attributes are generally listed in the manufacturer’s specifications for a given model of stan-
dard. They are accuracy, repeatability, stability, calibration uncertainty, traceability, and functionality.
ACCURACY (UNCERTAINTY)
The term accuracy is a measure of the degree to which a measurement or calibration approaches the
true value. However, in reality there is always some uncertainty associated with the ability to deter-
mine how close to true we really are. Therefore, the term accuracy is slowly being replaced by the term
uncertainty. A measurement may be comprised of type A uncertainty components and type B uncer-
tainty. A type A uncertainty might be gained from statistical means, e.g., the standard deviation of a
group of measurements, whereas examples of type B uncertainties may be obtained from calibration
reports or the manufacturers’ specifications. Accuracy is often stated for a given temperature range and
should not be confused with what is often specified as operating range.
REPEATABILITY
Repeatability is also referred to as precision. This variable relates to the degree of self-consistency an
instrument has for the same given test parameters. Note that an instrument can have repeatability
without being accurate. Repeatability or precision is a measure of the degree of consistency in a series
of measurements.
STABILITY
Stability relates to an instrument’s drift over a designated period of time and refers to how consistent
the instrument’s measurement accuracy is over time. Stability is often measured in the short or long
term. Equipment datasheets would normally reference a time period for the long term but may also
provide an indication of its short term stability. Short term stability may be in minutes or hours and is
often used in a lab that conducts measurement transfers where the same measurement condition may
be repeated with a short period using the same device. This enables the lab to ignore certain compo-
nents of uncertainty to achieve tighter transfer uncertainties.
UNCERTAINTY
This variable refers to the degree of certainty that a given measurement and/or accuracy specifica-
tion is correct. This variable is applied so that those using the instrument (and therefore its accuracy
capabilities) can assess the reliability or certainty of the results. Uncertainty is often qualified by a
confidence interval, that is used to indicate the reliability of the estimated uncertainty.
TRACEABILITY
This variable refers to the accuracy path of a given instrument back to a national measurement
institute, NIST in the U.S. It is important that the accuracy of a given instrument be traceable back to
the highest available level with the shortest possible path.
FUNCTIONALITY
Functionality refers to the different types of measurements that the standard is capable of measuring
and therefore it has traceability for these measurements. The more measurement functions, the more
applications there are for the standard.
462 Random (Type A) and Systematic (Type B) Errors
Small residual errors are always present in any measurement. These errors may be divided into two
general types, random or systematic. Random errors occur without any apparent pattern in a series of
HANDBOOK FOR ELECTRICITY METERING
repeated measurements with the same equipment and can be detected through statistical analysis. The
standard deviation, sigma, of a series of measurements containing random errors is a good indication
of the precision of the measurement (the calculation and uses of the standard deviation are found in
books on statistical analysis).
Systematic errors are much more difficult to detect or analyze. These are errors that may be fixed
or may vary in a recognizable pattern. If variable, they may be detected as a systematic change in the
results of a series of repeated measurements. The pattern may be a trend in one direction with time,
a periodic function of time, or a function of temperature or some other variable. Systematic errors
which remain constant are the most troublesome of all, as they cannot be readily detected in a series
of repeated measurements.
Fixed systematic errors are detected and eliminated by making cross checks using a different
method, different equipment, or both. If the results agree, the probability of an undetected systematic
error is small, since it is unlikely that each test involved identical systematic errors. If the results do
not agree, systematic error is present in one or both measurements. Fixed systematic errors may be due
to an unknown change in the calibration of any piece of equipment, unknown voltage drops in test
circuits, unknown magnetic coupling between circuits, or innumerable other causes.
Calibration
Calibration is a comparison between two measurements, one of known magnitude or correctness
made or set with one device and another measurement made in as similar a way as possible with a
second device. Not all equipment has the same stability. To ensure the equipment is operating within
known tolerances the equipment requires periodic calibration. The interval between periodic calibra-
tion may be determined by a number of factors, including:
1. A process or procedure defined by the utility
2. A recommended interval of calibration specified by the equipment manufacturer
3. The device broke and required repair
The result of a calibration is a calibration report indicating the date and place the calibration took
place, the equipment used to perform the calibration and the calibration result(s) with a stated
measurement uncertainty. The calibration report is an important document and is evidence of a
calibration that should be reviewed carefully and stored in a safe place for future reference. Some labs
will produce two reports, as found (the status of the equipment on arrival to the lab) and as left (how
the equipment performed following any adjustment, repair, or updates).
Careful scrutiny of a calibration report will provide information that may determine the per-
formance of the device against the manufacturers’ claimed specifications. A calibration report with
test data significantly in tolerance using equipment with adequate test accuracy ratio indicates the
lab is proficient. Conversely, test data that is close to exceeding the manufacturer’s specification,
using equipment that has low (or equal) test accuracy ratio may be of little value in determining the
adequacy of the device being calibrated.
Equipment that requires routine calibration will have a calibration label attached indicating when
the last calibration took place and when the next calibration is due. These calibration due labels
should be inspected before use to ensure that the equipment is in compliance with the utility’s quality
operating procedures.
Laboratory Intercomparison
To eliminate the possibility of systematic errors and thereby establish confidence at each level of
standardization, suitable cross checks must be made. Much of this cross checking may be done
within a single laboratory if some alternate equipment is available. However, complete duplication
of all equipment is seldom economically feasible. To overcome equipment limitations, measurement
intercomparisons may be made with other laboratories. Two electric utility laboratories may easily
perform intercomparison of their watthour standards by carefully packaging and shipping calibrated
portable secondary reference standards from one laboratory to the other. The electric utility can also 463
use the certification and calibration services of a metrology laboratory such as the one maintained
by Radian Research in Lafayette, Indiana. Radian Research maintains all needed references traceable
to NIST. The standards should be rechecked upon return to the home laboratory to be sure they have
Resolution
Resolution refers to the number of significant digits that can be read from the display of a given
instrument. Resolution has no direct relationship to precision or accuracy. In high quality instruments,
the resolution is usually slightly greater than the precision of the instrument, and the precision, in
turn, usually exceeds the guaranteed accuracy. Instruments with a resolution which is in excess of
their precision or accuracy are misleading because they imply a higher degree of precision than actu-
ally exists.
The resolution of a portable watthour standard can be increased almost without limit by increas-
ing the time of the test run, but this does not increase the precision or the accuracy of the measure-
ment after the point is passed where resolution is the limiting factor.
Laboratory Operation
Successful operation of a standards laboratory requires the possession and maintenance of certified
standards of suitable types, highly trained laboratory personnel who understand the art and science of
accurate measurement, the availability of sufficient time and money for the regular program of peri-
odic standardization and intercomparison, and proper documentation. This documentation includes
defined and controlled procedures for the key laboratory activities of calibrations, certifications, cross
checks, and traceability. It is very important that records be appropriately maintained and accessible.
Chapter 21
Standards
1
Adopted from http://standards.ieee.org/develop/overview.html.
465
466 Who Develops Standards?
Over time, various standards development organizations have naturally emerged, each covering specific
areas of interest. Organizations responsible for the development of standards related to the metering
Handbook for Electricity Metering
industry include the ANSI, the Institute for Electrical and Electronics Engineers (IEEE), the Interna-
tional Electrotechnical Commission (IEC), and Underwriters Laboratories (UL).
ISO/IEC 7498-1, “Information Technology—Open Systems Interconnection—Basic Reference Model: The Basic
2
Standards
• ANSI C12.22—Protocol Specification for Interfacing to Data Communication Networks. This
standard extends the concepts of the ANSI C12.18, C12.19, and C12.21 standards to allow
transport of table data over any reliable networking communication system (see Figure 21-4).
Virginia, its 400-plus member companies manufacture a diverse set of products used in the generation,
transmission, distribution, and end use of electricity as well as medical diagnostic imaging. NEMA also
has an associate membership program for non-manufacturers such as industrial suppliers, wholesale
traders, associated enterprises (utilities and consultants), and associations. NEMA serves as the
Secretariat under ANSI to manage the C12 series of standards and ensure they are produced under the
ANSI rules.
With respect to metering, there are two relevant standards that NEMA has published in recent
years:
• NEMA C12.24 TR-2011—Definitions for Calculations of VA, VAh, VAR, and VARh for Polyphase
Electricity Meters. This technical report establishes names and mathematical definitions for the
voltampere (VA), voltampere hours (VAh), voltamperes reactive (VAR), and voltampere reac-
tive hours (VARh) formulae used by polyphase electricity meters. The mathematical definitions
assume static waveforms.
• NEMA SG-AMI 1—Requirements for Smart Meter Upgradeability. This standard defines require-
ments that include secure local and remote upgrades of smart meter: metrology, Advanced
Metering Infrastructure (AMI) applications, AMI communications, Home Area Network (HAN)
applications, and HAN communications.
Underwriters Laboratories
Underwriters Laboratories (UL) is a global independent safety science company with more than
a century of expertise innovating safety solutions from the public adoption of electricity to new
breakthroughs in sustainability, renewable energy, and nanotechnology (www.ul.com). Dedicated to
promoting safe living and working environments, UL helps safeguard people, products, and places,
facilitating trade, and provides peace of mind for consumers of products available on the market.
UL works with a diverse array of stakeholders, optimizing the supply chain for manufacturers, by
providing a broad range of services that support every stage of a product’s life cycle. UL works with
retailers and government entities by collaborating on standards that create a level playing field for all.
UL standards are used to assess products; test components, materials, systems, and performance; and
evaluate environmentally sustainable products, renewable energies, food and water products, recycling
systems, and other innovative technologies.
Examples of UL standards relevant to the meter socket industry include:
• UL 414—Requirements for meter sockets used for electricity metering. This standard focuses
on ensuring the compliance with National Electrical Code (NFPA 70) of meter sockets, test
switches, and metering/instrument transformer cabinets (Figures 21-2 and 21-6).
• UL50—Enclosures for Electrical Equipment. These requirements cover electrical equipment
enclosures for use in accordance with the National Electrical Code, NFPA 70. Specific applica-
tions covered by this standard include cabinets and cutout boxes and junction and pull boxes.
Specific applications not covered by this standard are junction boxes of the swimming pool type.
Standard Applications
It is often difficult to understand where exactly the numerous standards apply in the power system.
The following diagrams indicate where the most common of the standards apply to reference electric
service applications.
469
Standards
Figure 21-1. Applicable ANSI Standards for Typical Residential Meter.
Figure 21-2. Applicable ANSI and UL Standards for Solid-State Blondel Meter and Meter Sockets.
470
Handbook for Electricity Metering
Figure 21-3. Applicable ANSI Standards Associated with a Meter’s Optical Port and Data Interaction.
Figure 21-4. Applicable ANSI Standards for Associated Telephone Modems and Data Communications.
471
Standards
Figure 21-5. Applicable ANSI and IEEE Standards for Instrument Transformers.
Figure 21-6. Applicable ANSI and UL Standards for Metering Test Switches.
472 Summary of Current Standards Development and
Harmonization on National and International Levels
International Electrotechnical Commission
Handbook for Electricity Metering
There are many IEC metering standards that parallel those developed and used within the North
American (ANSI) market. The IEC is divided into technical committees (TCs), working groups (WGs),
project teams (PTs), and maintenance teams (MTs) that are focused on different individual topic areas
within each standard domain. There are also joint working groups (JWG) that are structured to permit
different TCs to work together, thereby allowing the pool of experts to collaborate while exercising
their particular expertise when developing and modifying the standards.
Technical Committee #13 (TC13) is devoted to electrical energy measurement and control. The
IEC divides the TC13 work on the standards into four major groups:
WG11: Electricity metering equipment requirements, type tests, and acceptance tests
WG13: Dependability3 of electricity metering equipment
WG14: Data exchange for meter reading, tariff, and load control4
WG15: Payment systems5
The metering type testing standards are divided into general requirements—those that every device is
expected to take into consideration—and particular requirements. However, the latter only apply if that
particular aspect (component or feature) is actually part of the meter. An example of the particular
requirements standard is shown through the distinction between electromechanical and static (elec-
tronic) meters, and then further by real and reactive energy, and then even further by accuracy class.
For example, there is a standard for static active energy meters and another for static reactive energy
meters, with different accuracy classes.
Very little technical input from the ANSI requirements is being considered by the IEC TC13 as
part of current modification efforts on their standards. The basic reason for this is that the underly-
ing service types, locations, and physical forms are completely different, lending to different testing
philosophies and expectations. An important difference between ANSI and IEC standards is that the
latter do not cover physical form factor elements such as connections, shape, mounting, etc. Those
may differ on a country-by-country basis, with much of the market adopting the specifications defined
by the German Standards Institute (Deutsches Institut für Normung, or DIN) standards.
Much as there are different cellular telephony standards in use around the world, there are
also metering communication differences. A centerpiece of the IEC metering protocol standards is
known as DLMS/COSEM, or device language message specification and the companion specification
for energy metering. The former is the generalized concept for abstract modeling of communication
entities while the latter sets the rules, based on existing standards, for data exchange with energy
meters. There is an associated user association (http://www.dlms.com/) which maintains an active
conformance testing process and list of compliant devices, an important differentiator from the ANSI
metering protocol standards.
3
The IEC defines dependability in TR62059-11 (2002) as “the collective term used to describe the availability
performance and its influencing factors: reliability performance, maintainability performance and maintenance
support performance.” The ANSI synonym for dependability is considered to be in-service performance.
4
This includes communications protocols and data modeling standards.
5
IEC nomenclature for what is also known as pre-payment metering.
The importance of the OIML work, as it ties to ANSI meters, is through this treaty relationship. 473
Starting with European Union legislation, known as the Measuring Instruments Directive,6 the OIML
derived a set of general requirements for electronic measuring instruments, published as a document
known as D11 (www.oiml.org/publications/D/D011-e04.pdf). From this set of requirements, inter-
Standards
national metrology experts developed what is known as international recommendation 46, or IR46,
which applies to electrical energy meters currently available for use. IR46 specifies the metrological
and technical requirements applicable to electricity meters subject to legal metrological controls. The
requirements outlined in IR46 are to be applied during type approval, verification, and re-verification.
They also apply to modifications that may be made to existing approved devices. However, the provi-
sions set out in IR46 apply only to active electrical energy meters. There is no existing OIML specifica-
tion for other meter types at the present time.
Since the meters certified to ANSI limits are used in several countries that are party to this treaty,
there are current considerations to move the entire suite of ANSI C12 standards toward the OIML
type of requirements and tests. This shift will represent a change for the vendors and, ultimately, the
utilities using their equipment due to differences in equipment testing philosophies and expectations
in a few key areas, touching on the fundamental design of electricity meters. An example of similar
but different specifications is how load (current) is defined with an example of completely different
requirements being the treatment of harmonics by OIML, which currently is not considered with the
ANSI standards.
Measurement Canada
Measurement Canada (MC) is responsible for ensuring the integrity and accuracy of measurement in
the Canadian marketplace. Measurement Canada:
• Develops and administers the laws and requirements governing measurement
• Evaluates, approves, and certifies measuring devices
• Investigates complaints of suspected inaccurate measurement
A notable difference in the relationship between Measurement Canada and the Canadian consum-
ers and NIST and the American consumers is that NIST maintains the equipment used to validate
accurate measurements (i.e., the national watthour) but has no law-making, approval, or investigative
authority.
From the standards standpoint, there are some different expectations and requirements for
Canada. Although meters that pass ANSI tests can usually meet Canadian requirements, formal
Canadian approval is required prior to use in Canada. A key difference in meter assessments is that
Measurement Canada is the sole authority for approving meters in Canada. Once a particular model
of meter is approved, no changes to the meter pattern are permitted without acceptance by Measure-
ment Canada. From the information standpoint, Measurement Canada approves specific versions of
meter firmware and meter programming configurations, and changes are permitted only when compli-
ant with Measurement Canada’s policies and requirements.
Underwriters Laboratories
In part, UL develops standards used to assess products by testing components, materials, systems, and
performance. For meter sockets, UL develops and maintains the type testing (safety) performance
standards used for certification. The community of experts in meter sockets participates in the devel-
opment of all the key standards for the devices in a loosely-collaborative fashion. Recent cooperative
projects include examining one of the ANSI C12.1 and UL414 tests as a cross industry team, recom-
mending changes to both standards to simplify and harmonize the testing of the two types of devices,
meters, and sockets.
6
“Directive 2004/22/EC of the European Parliament and of the Council of 31 March 2004 on measuring instru-
ments,” http://eur-lex.europa.eu/LexUriServ/LexUriServ.do?uri=OJ:L:2004:135:0001:0080:EN:PDF
474 Conclusion
The utility industry is facing a period of rapid technological change primarily driven in recent years
by the migration to an Advanced Metering System (AMS) or AMI networks and the installation of
Handbook for Electricity Metering
smart grid systems. As this technology continues to evolve, the advances in technology, functionality,
open system architectures, and added complexity around AMS networks dictates the need for more
product interoperability and compatibility along with the simplified product development of meters
and metering related equipment. Standards documents that establish the required specifications and
procedures including the additional needed communication protocols for the systems and networks
will be required to facilitate the necessary interoperability of these new systems and metering products.
Understandably, standards cannot be developed and maintained without the required help from
utility members, manufacturers, and other interested parties contributing their time, expertise, and
resources to this endeavor.
Index
475
476 Alternating current, transformers in (continued) Bridges, 7
248, 249, 256, 261, 262, 274, 283, 286, Kelvin, 7
292, 295–299, 310, 314–316, 319, 329, 333, Wheatstone, 7
346, 352, 353, 357–373, 375, 376, 383, 387, British thermal unit (BTU), 7
HANDBOOK FOR ELECTRICITY METERING
393, 394, 402–406, 409–411, 413, 419, 420, Burden, 7, 18, 139, 141, 142, 148–152, 155, 157–159,
423–426, 428–432, 434, 436, 440–442, 445, 161–163, 165–167, 169, 172, 183, 194, 195, 199,
447, 449, 450, 457, 463, 466–468 200, 202, 203, 222, 226, 229, 231, 232
Ammeter, 5, 42, 53, 140, 219, 221–223, 241, 346 calculation of, 190, 191
permanent magnet, 267 effect on instrument transformer ratio and phase
rectifier type, 439 angle, 183
Ampere, 5 methods of expressing
Ampere-hour, 5 polyphase, 160, 191
Ampere-turn, 5, 21, 140, 172 secondary, 9, 140, 152, 160–165, 168–170, 194,
Analog-to-Digital (A/D) converter, 101, 102, 133, 195, 197, 198, 231, 297
134, 286, 287, 288, 289, 293 standard, 18, 169, 198–201, 203
Angles. See Trigonometry; Phase angle Burden tester, 139–141, 226
ANSI standards, 6, 453–464 Bypass socket, 8
Anti-creep holes, 24, 273, 306
Artificial load. See Phantom load
ASE cable, 28 C
“As found” tests, 190, 300, 308, 312, 316, 462 Calibrating constant, 310, 311. See also Constants,
“As left” tests, 190, 309, 313, 316, 462 calibrating
Atom, structure of, 91, 92, 93 Calibration, 1, 8, 19, 29, 30, 34, 38, 101, 136, 138,
Automated meter reading (AMR), 1–3, 6, 15, 21, 29, 188, 202, 205, 232, 240, 243, 244, 259, 269,
113–115, 117, 118, 128, 247, 308, 332, 385, 391, 276–281, 285, 291, 299, 300, 305, 306, 309,
392 310, 334, 339, 373, 453, 458–463.
electronic meter reading, 22, 117, 243, 244, 256, See also Watthour meters, testing of
259, 260, 281, 282, 293, 294, 307, 308, Capacitance, 3, 8, 15, 26, 71–73, 205, 206, 228, 232,
330–332, 341, 342, 355, 440, 442, 447 239, 365, 439
handheld data entry terminals, 113, 115, 330, Capacitive reactance, 8, 26, 72–75
388 Chain of standardization, 459, 460
handheld terminals, automatic data entry, 114, Circuit breaker, 8, 61, 111, 155, 207, 438
115, 391 Circuits, 2, 3, 6, 8, 14, 17, 22, 24, 25, 32, 35, 37, 42,
network meter reading, 114 51, 55, 57, 59, 65, 66, 70, 73, 76, 79, 85, 86, 96,
power line system, 114 99–102, 134, 137–139, 141, 142, 147, 149, 150,
radio system, 114 152, 155, 156, 175, 204, 207, 208, 214, 216, 218,
Telephone Dial-In System, 115 220–222, 224, 227, 228, 248–250, 255, 261, 262,
Telephone Dial-Out System, 115 273, 276, 279, 281, 283, 284, 286, 287, 296,
retrieval of data, 1, 27 298, 299, 306, 309, 313, 314, 317, 329, 330,
Autotransformer, 6, 210 354, 355, 374–378, 380–382, 436–438, 442–444,
phase shifting, 26, 206, 331, 354 449, 451, 462, 463. See also Alternating current
Average power factor kilovolt amps (kVA), 6 circuits; Direct current circuits
delta, 16, 22, 81, 82, 84, 88, 89, 100, 164, 170,
171, 191, 193, 196, 211, 216, 251, 253, 254,
B 257, 260–262, 274, 289, 298, 299, 304, 311,
Balanced load, 7, 188, 194, 215, 251, 253, 255, 278, 313, 314, 352, 361, 365, 367, 393, 396, 436,
436, 443, 444 437, 439, 451
Bar X, 30 distribution, 1, 5, 25, 28, 55, 64, 79, 80, 83, 88,
Base load, 7 89, 103, 107, 113, 116–118, 125–128, 130,
Basic impulse insulation level (BIL), 7 131, 137–240, 243, 260, 262, 274, 276, 320,
Bi-directional metering, 7 322, 355, 358, 385, 392, 435–438, 450,
Binary digital logic, 96 466–468
Block interval demand register, 13 parallel, 37, 59, 61, 62, 63
Blondel’s Theorem, 3, 7, 248–251, 253, 255–257, 259, polyphase, 3, 23, 24, 102, 147, 164, 170, 171, 182,
260, 393, 412, 466 184, 187–190, 193, 195, 211, 219, 248, 249,
application of, 248, 249, 251, 255, 257, 260, 397, 256, 259, 260, 277–282, 287, 304, 306, 308,
466 309, 331, 332, 347, 352, 355, 393, 400–405,
Bottom-connected meter, 7 436, 442, 468. See also Polyphase
Braking magnets, 273, 305. See also Permanent protection of, 214, 437
magnets series, 76, 85
series-parallel, 59, 280, 297, 304, 305, 313, 314, Creep or creeping, 10, 24, 273, 300, 303, 306, 308, 477
316 309, 312, 313, 317
single-phase, 16, 24–26, 28, 65, 76, 81, 85, 106, Creepage distance, 10
164, 177, 188–193, 196, 206, 207, 211, 213, Cumulative demand register, 324, 337
INDEX
215, 219, 242, 248, 250, 277–280, 282, 298, Current
299, 304, 306, 313, 347, 352, 370, 413, 419, alternating, 2, 8–10, 14, 17, 19, 23, 26, 27, 31, 51,
420, 436–438, 441, 443, 444 55, 65, 67, 70, 79, 81, 124, 134, 248, 317,
three-phase, 16, 23–25, 64, 81–86, 106, 164, 331, 339, 355, 377, 454, 466, 467
171, 188, 191–193, 196, 219, 222, 234, 238, circuit, 10
249–251, 279, 287, 298, 299, 307, 309, coil, 10
313–315, 346, 352, 361, 367, 370, 436, 437, direct, 2, 17, 23, 31, 37, 55, 67, 70, 138, 225, 228,
441, 444, 451. See also Polyphase 248, 355, 377, 381, 453, 467
three-wire, 8, 31, 64, 65, 191, 206, 207, 211–213, electron, 92–94
215, 248, 250–252, 264, 276, 305, 315, 377, hole, 92, 93
393, 394, 414, 424–429, 432, 436, 441, 442 induced, 17
two-wire, 8, 215, 248, 250, 263, 393, 394, 423, lagging, 19, 73, 176, 178–181, 309
425, 440, 441 leading, 19, 73, 178–181
wye, 14, 16, 22, 81, 82, 84, 88, 89, 148, 164, 170, measurement of, 57, 148, 149, 241, 285
188, 195, 196, 208, 214, 250, 253, 254, 256, transformer, 10
260–262, 282, 298, 309, 311, 316, 352, 361, Currents, eddy, 15, 19, 73, 265–269, 273, 274, 278,
365, 367, 393, 396, 417, 419, 420, 436–438, 279
444. See also Polyphase Customer’s load, 143, 149, 153, 188, 193, 295, 312,
Circular mil, 8, 56 359, 439, 442–444, 446
Clamp-on current probe, 134, 139 Customer’s premises, 2, 22, 30, 291, 310, 311, 435,
Class amperes, 9 438, 450
Class designation, 9 testing on, 2, 3, 291, 310
Clearance, 9 Cutout, 10, 468
Clockwise rotation, 9 Cycle, 3, 10, 14, 19, 23, 66, 67, 69, 70, 76, 134, 137,
Clutch, demand meter, 323–325, 336, 337, 388, 389 235, 239, 241, 243, 265–267, 284, 286, 287,
Compensating metering. See Transformers, loss 331–333, 338, 349, 385, 468
compensation
Compensation of meters
overload, 269, 270, 274, 278 D
temperature, 29, 240, 272, 273 Damping, 11, 269, 270, 274, 277, 278, 303
voltage, 270 current magnet. See Magnets, damping
Compensator, loss, 357–361, 363, 367 of an instrument, 11
Complex numbers, 44–47, 49–51, 69 D’Arsonval, 463
calculations, 44–46, 49, 50 Dead-front, 11
polar form, 47, 49 Decade, 11
rectangular form, 44, 45, 50 Degree, electrical, 14
Conductor Delta service, 16, 22, 81, 82, 84, 88, 89, 100, 164,
current, 108, 139, 283 170, 171, 191, 193, 196, 211, 216, 251, 253, 254,
grounding, 16, 312, 439, 443 257, 260–262, 274, 289, 298, 299, 304, 311, 313,
losses, 9 314, 352, 361, 365, 367, 393, 396, 436, 437,
service, 435 439, 451. See also Polyphase
Connected load, 9, 12, 84, 85, 254, 262, 444 Demand, 9, 11–13, 319, 320, 322–333, 335, 337, 340,
Connection errors, 440 374, 379, 383, 388–391
Constants, 2, 5, 9, 32, 51, 230, 302, 315, 324, 329, aggregate, 11
379, 387 coincidental, 11, 332, 374
calibrating, 310, 311 cumulative, 324, 337, 340, 390
dial, 9, 10, 13, 386 interval, 12
kilowatthour, 303 maximum, 11–14, 20, 23, 31, 320–324, 328, 332,
KYZ output (Ke), 9 333, 335–337, 339, 342, 388–390
mass memory (Km), 9 rolling interval, 11
register. See Register constant sliding window, 11, 328
watthour. See Watthour constant threshold alert, 11, 327, 329
Copper loss, 360, 361, 363, 367, 369, 372, 373 totalized, 11, 216, 374–376, 383
Core loss, 9, 159, 167, 169, 366, 371 Demand constant, 12
Correction factor, 18, 51, 52, 160, 162–164, 168, 171, explanation of, 12
173–177, 182–186, 189, 197, 198, 200, 205, 206 Demand delay, 9, 12, 329
Counters, photoelectric, 306 Demand deviation, 12
478 Demand energy, 12 Disk. See Rotor
Demand meters, 12, 282, 320–324, 332, 333, 342, Display, 13
379, 388 Distributed network protocol (DNP), 14
application of, 151, 260, 413 Distribution circuits, 88, 89, 262, 436
HANDBOOK FOR ELECTRICITY METERING
classes of, 6, 9, 13, 15, 19, 20, 26, 28, 30, 106, Diversity, 14, 444
139, 152, 197, 200, 248, 249, 263, 272, 365, Driving torque, 29, 34, 35, 267, 268, 270, 271, 273,
369, 370, 445, 466 277–280, 304
cumulative type, 322–325, 337, 390 Dynamometer, 463
indicating type, 12, 215, 316, 322, 323, 325, 388
integrating, 12, 13, 322, 323
lagged, 12, 267, 274 E
maintenance of, 30, 119, 130, 143, 275, 291–317, Eddy currents, 9, 19, 73, 265–269, 273, 274, 278, 279,
335–343 346, 358
mechanical, 6, 10, 12, 21, 322–324, 326, 327, 329, Effective resistance, 14, 155, 273
330, 338, 339, 342, 376, 378, 386, 391 Effective value, 14, 17, 67
pulse-operated, 282, 326 Electrical degree, 14
electronic type, 2, 4, 6, 10, 21, 22, 26, 33, 78, Electrical service, 105, 107, 111, 248
87, 115, 117, 201, 203, 242–244, 248, 249, Electromagnet, 14, 127, 262, 263, 269, 270, 273, 276,
256–260, 281, 282, 293, 294, 299, 305, 279, 280, 294, 302
307, 308, 322, 326, 330–332, 341, 343, Electromechanical meter, 14
348–350, 355, 358, 360, 383, 385, 389, Electromotive force, 7, 14, 17, 22, 23, 30, 33, 55, 67,
397, 400, 402, 449, 453, 456, 462, 464, 264, 267
484, 490 Electronic digital instruments, 133
indicating type, 12, 215, 316, 322, 323, 325, 388 Electronics, solid-state, 91, 341
recording type, 12, 19, 323, 333, 388, 391 Element, 14
solid-state, 9, 19, 29, 65, 80, 101, 110, 144, Embedded coil, 14
153, 199, 206, 220, 281–284, 287, 289, Embedded system, 14
305–310, 317, 320, 321, 341, 357–359, End-of-interval indicator (EOI), 15
361, 363, 367, 368, 372, 376, 379, 391, Energy, 7, 8, 11–15, 17, 19–22, 25–29, 31–35, 55, 63,
396, 469 65, 70, 76, 79, 80
registers for, 3, 13, 322, 324, 326, 329, 335–337, Enterprise systems (ES), 15
339, 387, 390, 466. See also Registers Errors, See also Percent error
testing of, 153 random, 462
advancing mechanism, 335, 339, 388 systematic, 462, 463
clutch, 324, 325, 336, 388 Excess meter, 20
maximum demand pointer, 324, 337 Exchange data language (EDL), 15
mechanical registers, 335, 338, 389
procedures, 149, 291–317, 335–343
pulse-operated, 282, 326 F
resetting mechanism, 336 Farad, 15, 71
timing motor for, 323, 327, 336–338 Farber Method, 196
Demand register. See Registers Field, magnetic
Demand scales, 388, 389 stray, 15, 211, 227
Detent, 13 Firmware, 15
Detent metering, 13 First reduction, 28
Dial constant. See Constants, dial Flagging, 15
Digital, 133, 286 Force, electromotive, 7, 14, 17, 22, 23, 30, 33, 55, 67,
Digital display, 34, 294, 338–341 264, 267
Digital electronics, 91, 96 Form, 16
Digital instrument, 133 Friction, 55, 267, 268, 273, 275, 303, 313, 317, 323,
Digital multiplier, 286–289 335–337, 378
Direct current circuits Function limiting control (FLC), 16
formulas for, 65 Fuses
Kirchhoff’s Law for application of, 57, 59, 249, 251, time delay, 438
443
Ohm’s Law, 2, 23, 37, 55, 56, 58–64, 73, 76, 85,
134 G
Ohm’s Law for application of, 37, 55, 56, 59–64 Galvanometer, 7, 16
resistance connected in network Gear ratio
parallel, 59, 61–63, 71–73 checking, 338
series, 226 formulas of, 54
series-parallel, 59, 62, 63, 297, 304, 313, 316 Gear reduction, 28, 54, 338
three-wire Edison distribution system, 64, 65
Ground, 16 ratio, 173, 174 479
return circuit, 16 table of, 193
Grounding conductor current, 202, 206, 208
electrode, 16 actual, 166
INDEX
identification of, 312, 439 burden on, 195, 203
of electric circuits, 439 connections of, 215, 216
dangers due to open secondary of, 172
demagnetizing of, 228
H difficulties with low ampere-turn designs of, 172
Harmonics, 80, 170, 225, 242, 262, 274, 289, 296, effects of burden on ratio and phase angle of,
298, 299, 308, 345–350, 352, 354, 355, 455, 473 169
Head-end, 16 common secondary leads, 170–172
Henry, 17, 70 frequency on ratio and phase angle of, 170
Hertz, 17 primary current on ratio and phase angle of,
Hi-pot test, 220, 221 169, 170
History logger data, 17 secondary leads on ratio and phase angle of,
Home area network (HAN), 17 170
Homogeneous meter group, 17 waveform on ratio and phase angle of, 170
Horsepower, 17, 78 ideal, 165
Hot-wire instrument, 17 marked ratio of, 166
Hybrid meter, 17 permanence of accuracy, 173
phase angle of, 169
phasor diagram of, 166
I polarity of, 165
Impedance, 7, 17, 18, 23, 73–75, 80, 82–84, 117, 139, ratio correction factor of, 168
141, 151, 153, 155, 157, 159–165, 167–169, 172, secondary burden on, 165, 169
194, 195, 199, 200, 203, 220, 224, 243, 262, true ratio of, 166, 168
263, 330, 358, 359, 363–366, 368, 372, 378 turn ratio of, 166
in AC circuits, 17, 18, 23, 73–75, 82, 83, 139, optical current sensors, 233–237
141, 151, 153, 155, 161, 163–165, 168, 190, optical voltage sensors, 237–240
191, 195, 196, 199, 216, 259, 326, 354, 355, testing of, 151, 220–221
359–362, 374 AC hi-pot test, 216, 217
Inactive meters, 448 by comparative method, 219
Induced current, 17 by deflection method, 219, 220
Induced voltage, 17, 19, 69–71, 79, 158, 167, 230, 266 by direct method, 150, 223
Inductance, 3, 17, 18, 26, 69–71, 165, 195, 200, 203, by null method, 224
228, 283 for adequate insultation of, 220
mutual, 17, 283 for shorted term, 222
self, 17 to check polarity of, 221, 222
Inductive, 17, 18, 26, 67, 70, 71, 73–75, 77, 78, 83, to determine ratio and phase angle of, 221–223
86, 87, 184, 195, 229, 231, 263, 267, 268 type
reactance, 18, 70, 71, 73–75, 83, 195, 296 bar, 207
Instrument, digital, 133 bushing, 207
Instrument, hot-wire, 17 double ratio, 207
Instrument transformers, 18 miniature, 207
application of, 139, 188–193, 204, 208, 211 multi-core, 207
basic theory of, 156 split-core, 207
burden capability of, 208, 226, 238, 243 three-wire, 206, 207
burden on, 194, 195 window, 206, 207
calculation of, 193 wound, 152, 205, 206
definitions, 155, 156, 173 verification of connections of, 217–220
methods of expression, 186, 195 voltage, 203, 205, 208
polyphase, 164 actual, 152, 153, 160
standard, 150, 152, 177, 201, 209, 213 burden of, 152, 153, 194
calculation of meter accuracy settings, 196 connections of, 150, 211, 212, 213
compensating error of, 164, 177 effects of burden on ratio and phase angle of
connections of, 211, 217, 218 common secondary leads on ratio and phase
correction factors for, 173, 174, 176, 177 angle of, 164
application of, 182 frequency on ratio and phase angle of, 162
final, 177, 182–184, 186, 189 polyphase, 164
phase angle, 174–176 primary voltage on ratio and phase angle of,
tables of, 178–181 161
480 Instrument transformers, voltage (continued) kVA, 19
secondary leads on ratio and phase angle of, metering of, 345, 349, 350. See also KiloVAR and
161, 163, 164 kilovoltampere metering
temperature on ratio and phase angle of, 162, KYZ output, 19
HANDBOOK FOR ELECTRICITY METERING
163
waveform on ratio and phase angle of, 162
ideal, 152, 153 L
marked ratio of, 152, 153 Laboratory, 19, 27, 29, 30, 33, 99, 143, 148, 152, 153,
phase angle of, 160, 161 223, 231, 279, 291, 292, 453–455, 459, 460,
phasor diagram of, 152–155, 159 462, 463
polarity of, 152 Lag adjustments, 304, 309
ratio correction factor of, 160 Lagged demand meter, 12
selection of, 208 Lagging current, 19, 73, 176, 178–181, 309
true ratio of, 152, 160 Laminated core, 19
turn ratio of 152 Leading current, 19, 178–181
Instruments, indicating Lenz’s Law, 19, 69
ammeter. See Ammeter Light emitting diode (LED), 19, 345
current transformer field test set, 141, 144, 145, Light-load adjustment, 263, 267, 268, 270, 273, 274,
148, 158, 225 279, 280, 295, 303–305, 309, 317
maintenance on, 130, 317 Lightning arrester, 208
Megger, 308 Liquid crystal display (LCD), 19
ohmmeters, 218 Load
permanent-magnet, moving-coil type, 267 artificial, 19, 295. See also Phantom load
precision of, 101, 135–137, 282, 462, 463 balanced, 188, 194, 215, 251, 253, 255, 278, 436,
readability and resolution of, 133, 136–138, 231, 443, 444
293, 294, 323, 329, 463 compensation, 20, 271, 317
rectifier type, 27, 274, 439, 463 control, 20
scales of, 327 overload, 269, 270, 274, 278
stray fields influence on, 227, 317 factor, 20, 210
temperature influence on, 28–31, 108–110, 119, phantom, 19, 23, 188, 193, 296, 297, 312–314
134, 136, 138, 142, 162, 205, 206, 208–210, profile, 20
237, 239–241, 269, 271–273, 277, 283, 322, resistance, 297, 298
357, 365, 437, 444, 454, 461, 463 system, 20, 188, 350, 352
thermocouple type, 30 Loading transformer, 20, 296
voltmeter. See Voltmeter Location of meter, 360, 367, 372, 373, 444
wattmeter. See Wattmeter Locked-out meters, 448
Interference, 3, 232, 277–279, 450 Loss compensation, 20, 32, 357–361, 363, 365, 367
Interval demand, 12, 15, 19, 340 Losses, core, 9, 159, 167, 169, 366, 371
J M
Joule’s Law, 19 Magnetic, 9, 10, 14, 15, 17, 19, 20, 29, 32, 34, 65, 70,
73, 76, 79, 80, 109, 110, 137, 155–157, 161, 162,
169, 200, 207, 211, 218, 229, 230, 236, 239,
K 248, 262–271, 273–275, 277, 279, 280, 283, 285,
Kilo, 19, 43 294, 302, 304, 312, 317, 346, 358, 391, 462
KiloVAR and kilovoltampere metering, 331, 345–355 field, 10, 14, 15, 19, 70, 79, 236, 264, 265, 267,
electronic, 349, 350, 352–354 283, 285, 358
of four-wire, three-phase circuits, 347, 352 flux, 14, 17, 19, 20, 156, 218, 230, 268, 317
of three-wire, three phase, 352 Magnetism, 228
phase relations for, 346, 347 Magneto motive force, 20
phase sequence, 23, 313, 437 Magnets, 109, 263, 268, 270, 272, 273, 275, 276, 303,
theory of, 345 305, 317
KiloVAR demand, 11, 12 damping, 303
KiloVARhour, 33 permanent, 27, 109, 267, 268, 270, 272, 276–278,
Kilowatt, 7, 19, 26, 64, 247, 319, 320, 322, 323, 324, 302
329, 335, 337, 338, 339, 340, 346, 359, 378, retarding, 27, 263, 272, 295
379, 380, 383, 386, 390 Maintenance, 1, 30, 119, 120, 130, 133, 143, 231,
Kirchhoff’s Law, 2, 57, 59, 249, 251, 443 243, 247, 275, 291, 295, 303, 310, 317, 319, 335,
application of, 249, 443 337, 341, 377, 378, 380, 382, 450, 463, 467, 472
demand meters. See Demand meters, testing of N 481
instruments
National Electrical Code, 22, 435, 438, 439, 468
watthour meters. See Watthour meters,
National Institute of Standards and Technology, 2, 29,
maintenance of
INDEX
34, 129, 131, 143, 231, 291, 453–455, 457, 459,
Marked ratio of instrument transformers, 18, 156,
460, 461, 463, 472, 473
157, 160, 164, 166, 168, 173, 207, 221, 222, 223,
Net metering, 22
235, 238, 239
Network, 5, 6, 14, 16, 17, 25, 31, 32, 59, 82, 83,
Mathematics, 2, 37, 51, 55, 135
101–103, 105–107, 110, 114–129, 131, 146, 235,
Maximum average power, 320
239, 250, 251, 284, 315, 333, 380, 391–393,
Maximum demand, 11–14, 20, 23, 31, 320–325, 328,
397, 398, 426, 436, 437, 444, 447, 450, 467, 468
332, 333, 335–337, 339, 342, 388–390
Neutral wire, 31, 217, 257, 438, 443, 444
meters. See Demand meters
Null method, 224
Measurement of, 133–139, 149, 153, 174, 183, 219,
230, 249, 277, 345, 346, 348–350, 352, 354,
355, 357, 467 O
demand. See Demand meters
Ohm, 2, 5, 21–23, 33, 37, 55, 56, 58–64, 73, 76, 85,
watthours. See Watthour meters
138, 139, 150, 164, 167, 171, 215, 454, 459, 460
Mega, 20, 43, 371
Ohm’s Law, 2, 23, 37, 55, 56, 58–64, 73, 76, 85, 134
Megger, 308
Ohmmeters, 218
Memory circuits, 96, 99, 100
Optical port, 23, 102, 110, 126, 331, 381, 391, 465,
Meter accuracy, 143, 184, 185, 198, 219, 243, 273,
466, 470
274, 304, 309, 312, 334, 373, 374. See also
Optical probe, 23, 341, 391
Accuracy
Outdoor installations, 448
Meter bases, 21
Overload compensation, 269, 270, 274, 278
Meter bearing. See Bearings
Meter cable, 21
Meter data management system (MDMS), 21 P
Meter demand. See Demand meters
Padmount CT, 23
Meter department, 1, 2, 116, 451, 453, 463
Parallel circuit, 37, 61, 62, 63
Meter installation, 10, 32, 138, 313, 332, 442, 446,
Parallel-series circuit, 62, 63
447, 451
Peak load, 23, 328, 383, 384
Meter laboratory, 279
Percent error, 18, 23, 51–53, 183, 185–190, 193, 198,
Meter location, 360, 367, 372, 373, 444
312, 419
Meter multiplier, 21
Percent registration, 23, 51, 52, 53, 142, 183, 184,
Meter personnel, 1, 2, 3, 4, 5
193, 274, 302, 303, 312, 317, 373
Meter reading, 1, 2, 6, 11, 27, 35, 113–116, 128, 141,
Permanent magnets. See Magnets, permanent
247, 281, 308, 316, 332, 374, 385, 386, 391,
Phantom load, 19, 23, 188, 193, 296, 297, 312–314
392, 472
Phantom voltage, 23
Meter sequence, 21
Phase angle, 10, 18, 23, 24, 42, 43, 66–69, 78, 149,
Meter sockets, 219, 249, 422, 438, 445, 466, 468,
150, 157, 159–164, 166–172, 174–182, 184–189,
469, 473
191, 193, 194, 196, 197, 201–203, 207, 214, 215,
Meter testing, See Demand meter, testing of; Watthour
218, 219, 221, 223, 224, 226, 227, 229, 231,
meter, testing of
248, 250, 253, 256, 263, 274, 278, 279, 283,
Meter watthour. See Watthour meters
284, 291, 292, 296, 297, 313, 348, 353, 355,
Metering computations, 51
375, 443, 455, 456, 458
Method, Farber, 196
Phase angle correction factor, 18, 174, 175, 176, 177,
Micro, 7, 21, 43, 245
182, 184
Microprocessor, 14, 91, 100–102, 138, 148, 226, 227,
Phase rotation, 219, 451
281, 287, 329, 334, 339, 340, 342, 391
Phase sequence, 23
Mil, 8, 22, 56
Phase shifter, 23
Milli, 22, 43, 292
Phase-shifting transformer, 24
Modbus, 22
Phasor, 24, 68, 69, 73, 76, 83, 86, 150, 157–161, 163,
Modem, 22
164, 166–168, 171, 174, 175, 177, 182, 212, 213,
Multiform meter, 22
215–217, 219, 251–256, 259, 314, 331, 347, 348,
Multi-function meter, 22
393, 396, 398, 436
Multiplier, digital, 286, 287, 288, 289
Photoelectric tester, 24
Multi-rate meter, 22
Polarity, 24, 58, 69, 79, 94, 157, 160, 161, 165, 168,
Multi-stator, VARhour meters. See Watthour meters,
169, 195, 211, 215, 216, 218–222, 224, 381, 394
multi-stator
Pole-top metering, 450
Mutual inductance, See Inductance, mutual
482 Polyphase, 3, 23, 24, 147, 164, 170, 171, 182, 184, Reactor, 26, 205, 228, 394
187–190, 193, 195, 211, 219, 248, 249, 256, 259, Reading of meters. See Meter, reading of
260, 277–282, 287, 304, 306, 308, 309, 347, Readability of instruments, 231
352, 355, 436, 442, 468 Rectifier, 27
HANDBOOK FOR ELECTRICITY METERING
Q S
Q-hour meter, 26 Safety, 2–4, 22, 106, 107, 111, 137–139, 144, 145,
Quadergy, 26 209, 213, 215, 216, 218, 220, 232, 235, 284,
Quadrants, 41, 49, 352, 353, 354 293, 310–312, 314, 380, 385, 391, 439, 452,
465–468, 473
Scales, instrument, 327, 388, 389, 452
R Scientific notation, 43
Random errors, 462 Scott connections, 361
Rating factor, 26 SE cable, 28
Ratio correction factors. See Instrument transformers, Secure metering, 28
ratio correction factors of Self-contained meter, 28
Ratio gear. See Gear ratio Self-inductance, 17
Ratio, marked. See Instrument transformers, current Series circuit. See Direct current circuits
and voltage Series-parallel. See Direct current circuits
Ratio, register. See Register, ratio Service, 1, 2, 6–8, 13, 20–23, 28–33, 35, 101,
Ratio, true. See Instrument transformers, current and 105–111, 113, 116, 117, 120, 125, 126, 130, 131,
voltage 139, 141–143, 145–147, 152, 205–208, 211, 214,
Ratio, turn. See Instrument transformers, current and 215, 219, 220, 222, 224, 225, 243–245, 248,
voltage 250–260, 276, 277, 279, 282–284, 291, 295, 296,
Reactance, 8, 17, 18, 26, 70–75, 83, 159, 160, 162, 299, 300, 303, 304, 308–313, 316, 319, 320,
167, 195, 205, 273, 274, 276, 296, 347, 358, 370 329, 331, 332, 338, 339, 343, 347, 352, 361,
Reactiformer, 26 372–374, 378, 383–385, 396, 412, 417, 419, 422,
Reactive power. See VARs 435–445, 447–452, 466, 468, 472
Reactive voltamperes, 26, 347, 348, See also VARs conductors, 28
drop, 28 Time standard, 454 483
equipment, 28 Timebase, 31
service entrance (SE) cable, 28 Time-delay fuses, 438
service entrance conductors, 28 Time-division multiplication, 283–285
INDEX
Shaft reduction, 28, 303, 315 Time-of-use metering, 31
Short circuit, 8, 23, 28, 79, 111, 165, 214, 311, 315, Torque balance adjustment, 279, 280
317, 358, 437, 438, 448 Torque, driving, 29, 31, 34, 35
Simulated meter, 28 Total harmonic distortion (THD), 32
Sine waves, 67, 274, 346, 463 Totalization, 11, 19, 32, 216, 374–376, 379–383
Single-phase, 16, 24–26, 28, 31, 76, 78, 81, 85, 106, Totalizing relay, 32, 379, 380
164, 177, 182, 188–193, 196, 206, 207, 211, 213, Transconductance multiplier, 286, 287
215, 219, 242, 248, 250, 264, 277–280, 282, Transducer, 32
298, 299, 304, 306, 313, 346, 347, 352, 370, Transformer, 6, 7, 9, 10, 16, 18, 20–26, 28, 32, 33,
372, 393, 398, 406, 412–414, 419, 420, 423–425, 35, 54, 79, 80, 87–89, 103, 108, 131, 133–135,
436–438, 440–444 139–142, 150, 155–177, 182–188, 191, 193–201,
Socket, 3, 8, 16, 21, 23, 25, 27–29, 32, 34, 107, 138, 203–209, 211, 213–228, 230, 233, 234, 240, 241,
144, 147, 249, 276, 312, 393, 395, 396, 399–405, 243, 244, 248, 249, 256, 261, 262, 274, 283,
423–427, 429–434, 437, 440, 442, 443, 445–449, 286, 292, 295–299, 310, 314–316, 319, 329, 333,
452, 465, 466, 468 346, 352, 353, 357–373, 375, 376, 383, 387, 393,
Socket-connected meter, 29 394, 402–406, 409–411, 413, 419, 420, 423–426,
Solid-state electronics, 29, 91 428–432, 434, 436, 440–442, 445, 447, 449,
Special metering, 216, 357 450, 457, 463, 466–468
Speed, 80, 100, 116, 118, 122, 148, 188, 192, 236, coupling-capacitor voltage (CCVT), 9
262, 267–270, 273, 275, 277, 278, 303, 306, 316, current (CT), 7, 10, 21, 23–26, 32, 35, 134, 136,
317, 335, 338, 339, 345, 361, 387 139, 141, 142, 148–152, 156, 173, 200,
Standard burden, 18, 198, 200 206, 207, 209–211, 215–217, 219, 222, 224,
Standard cells, 454 226–228, 230, 315, 413, 419
Standard resistors, 223, 453 loss compensation, 32, 134, 169
Standards, 1, 2, 3, 5, 15, 19, 29, 33, 35, 53, 56, 102, voltage (VT), 7, 10, 21, 24, 25, 33, 173, 315, 368
108, 110, 120, 123, 125, 126, 129, 137, 143, Transformer ratio, 32, 173, 177, 182, 183, 187, 365,
155, 188–190, 192, 193, 211, 220, 223, 224, 228, 369
240, 245, 274, 279, 284, 291–295, 298, 306, Transocket, 32
307, 310, 315, 394, 422, 435, 445, 453–463, Trigonometric functions, 40, 414
465–474 Trigonometry, 42, 78, 87, 347, 348
Stray fields, 211, 227, 317 Two-wire meter, 248, 263, 277, 441
Sub-metering, 29
Switchboard-mount meter, 29
Synchronism, 29 V
Systematic errors, 462, 463 Value, effective, 14
VARhour, 33, 43, 206, 363, 457
VARs, 33, 42, 43, 78, 194, 195, 289, 292, 320, 331,
T 352, 353, 355, 359, 363, 369, 370, 371, 373
Table definition language (TDL), 29 Volt, 33
Temperature compensation, 29, 240, 272, 273 Voltampere, 26, 33, 42, 194, 195, 197, 347, 348, 371,
Terms and definitions, 5 468
Test switch, 25, 139, 142, 144, 149, 150, 219, 226, Voltmeter, 23, 38, 39, 42, 53, 219, 221, 223, 388,
314, 315, 326, 394, 431, 449 436, 437, 439, 444, 448
Test tables, 306
Tests and testing, 1, 2, 8, 16, 19, 23, 24, 28, 30,
33–35, 110, 111, 133, 134, 138–153, 156, 162, W
164, 170, 183, 184, 188, 190–193, 211, 213, Watt, 33
219–228, 231, 240, 243, 249, 276, 279, 281, 282, Watthour constant, 9, 34
291, 292, 294–317, 326, 329, 335–342, 361, 365, equation of, 275
366, 368, 369, 373, 374, 378, 388, 394, 431, use, in precent registration calculations, 52, 54, 376
449, 450, 453, 454, 456, 459–461, 463, 465, in testing watthour meter registers, 302, 303
466, 471–473 in testing watthour meters, 267, 294, 302
periodic sample, 30 Watthour meters
statistical sample, 30 basic current range, 29
Thermocouple, instrument, 30 basic reference standards, 33
Thermoelectric effect, 30 basic voltage range, 29
Thermoelectric laws, 31 bottom-connected, 33
Three-wire system, 8, 31, 379, 414, 438 calibration, 34
484 Watthour meters (continued) lag adjustment, 265, 304, 309
class designation, 34 light-load adjustment, 157, 184, 263, 267,
detachable (socket-mounted), 34 268, 270–274, 279, 281, 295, 303–305,
field standard, 34 309, 310, 313, 317
HANDBOOK FOR ELECTRICITY METERING