MR-J4 - Instruction Manual (Supplementary 400V) SH (NA) - 030119-A (02.13)
MR-J4 - Instruction Manual (Supplementary 400V) SH (NA) - 030119-A (02.13)
MR-J4 - Instruction Manual (Supplementary 400V) SH (NA) - 030119-A (02.13)
MR-J4-_A4(-RJ) MR-J4_B4(-RJ)
SERVO AMPLIFIER
MR-J4-A4 MR-J4-B4
MODEL INSTRUCTIONMANUAL
MODEL
CODE 1CW812
To use the equipment correctly, do not attempt to install, operate, maintain, or inspect the equipment until
you have read through this Instruction Manual, Installation guide, and appended documents carefully. Do not
use the equipment until you have a full knowledge of the equipment, safety information and instructions.
In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
Note that the CAUTION level may lead to a serious consequence according to conditions.
Please follow the instructions of both levels because they are important to personnel safety.
What must not be done and what must be done are indicated by the following diagrammatic symbols.
Indicates what must not be done. For example, "No Fire" is indicated by .
In this Instruction Manual, instructions at a lower level than the above, instructions for other functions, and so
on are classified into "POINT".
After reading this Instruction Manual, keep it accessible to the operator.
A- 1
1. To prevent electric shock, note the following
WARNING
Before wiring or inspection, turn off the power and wait for 15 minutes or more until the charge lamp
turns off. Then, confirm that the voltage between P+ and N- is safe with a voltage tester and others.
Otherwise, an electric shock may occur. In addition, when confirming whether the charge lamp is off or
not, always confirm it from the front of the servo amplifier.
Ground the servo amplifier and servo motor securely.
Any person who is involved in wiring and inspection should be fully competent to do the work.
Do not attempt to wire the servo amplifier and servo motor until they have been installed. Otherwise, it
may cause an electric shock.
Do not operate switches with wet hands. Otherwise, it may cause an electric shock.
The cables should not be damaged, stressed, loaded, or pinched. Otherwise, it may cause an electric
shock.
During power-on or operation, do not open the front cover of the servo amplifier. Otherwise, it may cause
an electric shock.
Do not operate the servo amplifier with the front cover removed. High-voltage terminals and charging
area are exposed and you may get an electric shock.
Except for wiring and periodic inspection, do not remove the front cover of the servo amplifier even if the
power is off. The servo amplifier is charged and you may get an electric shock.
To prevent an electric shock, always connect the protective earth (PE) terminal (marked ) of the servo
amplifier to the protective earth (PE) of the cabinet.
When using an earth-leakage current breaker (RCD), select the type B.
To avoid an electric shock, insulate the connections of the power supply terminals.
A- 2
3. To prevent injury, note the following
CAUTION
Only the voltage specified in the Instruction Manual should be applied to each terminal. Otherwise, a
burst, damage, etc. may occur.
Connect cables to the correct terminals. Otherwise, a burst, damage, etc. may occur.
Ensure that polarity (+/-) is correct. Otherwise, a burst, damage, etc. may occur.
The servo amplifier heat sink, regenerative resistor, servo motor, etc. may be hot while power is on or for
some time after power-off. Take safety measures, e.g. provide covers, to avoid accidentally touching the
parts (cables, etc.) by hand.
4. Additional instructions
The following instructions should also be fully noted. Incorrect handling may cause a malfunction, injury,
electric shock, etc.
When the product has been stored for an extended period of time, contact your local sales office.
When handling the servo amplifier, be careful about the edged parts such as corners of the servo
amplifier.
The servo amplifier must be installed in a metal cabinet.
A- 3
CAUTION
When you disinfect or protect wooden packing from insects, take measures except by fumigation.
Fumigating the servo amplifier or packing the servo amplifier with fumigated wooden packing can cause
a malfunction of the servo amplifier due to halogen materials (such as fluorine, chlorine, bromine, and
iodine) which are contained in fumigant.
The servo amplifier must not be used with parts which contain halogen-series flame retardant materials
(such as bromine) under coexisting conditions.
(2) Wiring
CAUTION
Wire the equipment correctly and securely. Otherwise, the servo motor may operate unexpectedly.
Do not install a power capacitor, surge killer, or radio noise filter (optional FR-BIF-H) on the servo
amplifier output side.
To avoid a malfunction, connect the wires to the correct phase terminals (U, V, and W) of the servo
amplifier and servo motor.
Connect the servo amplifier power output (U, V, and W) to the servo motor power input (U, V, and W)
directly. Do not let a magnetic contactor, etc. intervene. Otherwise, it may cause a malfunction.
Servo amplifier Servo motor Servo amplifier Servo motor
U U
U U
V V
V M V M
W W
W W
The surge absorbing diode installed to the DC relay for control output should be fitted in the specified
direction. Otherwise, the emergency stop and other protective circuits may not operate.
Servo amplifier Servo amplifier
24 V DC 24 V DC
DOCOM DOCOM
Control output RA
Control output RA
signal signal
For sink output interface For source output interface
When the cable is not tightened enough to the terminal block, the cable or terminal block may generate
heat because of the poor contact. Be sure to tighten the cable with specified torque.
Connecting a servo motor of the wrong axis to U, V, W, or CN2 of the servo amplifier may cause a
malfunction.
A- 4
(4) Usage
CAUTION
When it is assumed that a hazardous condition may occur due to a power failure or product malfunction,
use a servo motor with an external brake to prevent the condition.
Do not disassemble, repair, or modify the equipment.
Before resetting an alarm, make sure that the run signal of the servo amplifier is off in order to prevent a
sudden restart. Otherwise, it may cause an accident.
Use a noise filter, etc. to minimize the influence of electromagnetic interference. Electromagnetic
interference may be given to the electronic equipment used near the servo amplifier.
Burning or breaking a servo amplifier may cause a toxic gas. Do not burn or break it.
Use the servo amplifier with the specified servo motor.
The electromagnetic brake on the servo motor is designed to hold the motor shaft and should not be
used for ordinary braking.
For such reasons as service life and mechanical structure (e.g. where a ball screw and the servo motor
are coupled via a timing belt), the electromagnetic brake may not hold the motor shaft. To ensure safety,
install a stopper on the machine side.
Servo motor
RA
B 24 V DC
Electromagnetic brake
When any alarm has occurred, eliminate its cause, ensure safety, and deactivate the alarm before
restarting operation.
Provide an adequate protection to prevent unexpected restart after an instantaneous power failure.
A- 5
(7) General instruction
To illustrate details, the equipment in the diagrams of this Instruction Manual may have been drawn
without covers and safety guards. When the equipment is operated, the covers and safety guards must
be installed as specified. Operation must be performed in accordance with this Instruction Manual.
DISPOSAL OF WASTE
Please dispose a servo amplifier, battery (primary battery) and other options according to your local laws and
regulations.
EEP-ROM life
The number of write times to the EEP-ROM, which stores parameter settings, etc., is limited to 100,000. If
the total number of the following operations exceeds 100,000, the servo amplifier may malfunction when the
EEP-ROM reaches the end of its useful life.
Write to the EEP-ROM due to parameter setting changes
Write to the EEP-ROM due to device changes
You must have this Instruction Manual and the following manuals to use this servo. Ensure to prepare
them to use the servo safely.
Relevant manuals
A- 6
This Instruction Manual does not describe the following items. These items are the same as those for MR-
J4-_A(-RJ) or MR-J4-_B(-RJ) servo amplifier. For details of the items, refer to each chapter/section of the
detailed explanation field.
Model Item Detailed explanation
MR-J4-_A4(-RJ) Normal gain adjustment MR-J4-_A(-RJ) Servo Amplifier Instruction Manual
chapter 6
Special adjustment functions (except MR-J4-_A(-RJ) Servo Amplifier Instruction Manual
"Compliance with SEMI-F47 standard") (Note) chapter 7
Absolute position detection system MR-J4-_A(-RJ) Servo Amplifier Instruction Manual
chapter 12
Using STO function MR-J4-_A(-RJ) Servo Amplifier Instruction Manual
chapter 13
Communication function MR-J4-_A(-RJ) Servo Amplifier Instruction Manual
chapter 14
MR-J4-_B4(-RJ) Normal gain adjustment MR-J4-_B(-RJ) Servo Amplifier Instruction Manual
chapter 6
Special adjustment functions (except MR-J4-_B(-RJ) Servo Amplifier Instruction Manual
"Compliance with SEMI-F47 standard") (Note) chapter 7
Absolute position detection system MR-J4-_B(-RJ) Servo Amplifier Instruction Manual
chapter 12
Using STO function MR-J4-_B(-RJ) Servo Amplifier Instruction Manual
chapter 13
Using fully closed loop system MR-J4-_B(-RJ) Servo Amplifier Instruction Manual
chapter 16
Wires mentioned in this Instruction Manual are selected based on the ambient temperature of 40 ˚C.
A- 7
MEMO
A- 8
CONTENTS
2. INSTALLATION 2- 1 to 2- 4
3.1 MR-J4-_A4(-RJ)................................................................................................................................. 3- 3
3.1.1 Input power supply circuit............................................................................................................ 3- 3
3.1.2 Explanation of power supply system........................................................................................... 3- 7
3.2 MR-J4-_B4(-RJ)................................................................................................................................ 3-11
3.2.1 Input power supply circuit........................................................................................................... 3-11
3.2.2 Explanation of power supply system.......................................................................................... 3-15
5. PARAMETERS 5- 1 to 5-26
5.1 MR-J4-_A4(-RJ)................................................................................................................................. 5- 1
5.1.1 Parameter list .............................................................................................................................. 5- 1
5.1.2 Detailed list of parameters.......................................................................................................... 5-10
5.2 MR-J4-_B4(-RJ)................................................................................................................................ 5-14
5.2.1 Parameter list ............................................................................................................................. 5-14
5.2.2 Detailed list of parameters.......................................................................................................... 5-23
6. TROUBLESHOOTING 6- 1 to 6-16
6.1 MR-J4-_A4(-RJ)................................................................................................................................. 6- 1
6.1.1 Alarm and warning list ................................................................................................................. 6- 1
6.2 MR-J4-_B4(-RJ)................................................................................................................................. 6- 9
6.2.1 Alarm and warning list ................................................................................................................. 6- 9
1
6.2.2 Troubleshooting at power on...................................................................................................... 6-15
7. DIMENSIONS 7- 1 to 7-16
7.1 MR-J4-_A4(-RJ)................................................................................................................................. 7- 2
7.2 MR-J4-_B4(-RJ)................................................................................................................................. 7- 9
8. CHARACTERISTICS 8- 1 to 8- 8
2
APPENDIX App.- 1 to App.-22
3
MEMO
4
1. FUNCTIONS AND CONFIGURATION
The items in the following table are the same as those for MR-J4-_A(-RJ) or MR-J4-_B(-RJ) servo amplifier.
For details of the items, refer to each chapter/section of the detailed explanation field.
Model Item Detailed explanation
MR-J4-_A4(-RJ) Summary MR-J4-_A(-RJ) Servo Amplifier Instruction Manual
section 1.1
Function list MR-J4-_A(-RJ) Servo Amplifier Instruction Manual
section 1.5
Removal and reinstallation of the front cover MR-J4-_A(-RJ) Servo Amplifier Instruction Manual
section 1.7.2
MR-J4-_B4(-RJ) Summary MR-J4-_B(-RJ) Servo Amplifier Instruction Manual
section 1.1
Function list MR-J4-_B(-RJ) Servo Amplifier Instruction Manual
section 1.5
Removal and reinstallation of the front cover MR-J4-_B(-RJ) Servo Amplifier Instruction Manual
section 1.7.2
In MELSERVO-J4 series, servo amplifiers with CN2L connector are also available as MR-J4-_A4-RJ and
MR-J4-_B4-RJ.
By using CN2L connector, an A/B/Z-phase differential output type external encoder can be connected to the
servo amplifier. In a fully closed loop system, a four-wire type external encoder is connectable as well. The
following table indicates the communication method of the external encoder compatible with MR-J4-_A4/MR-
J4-_B4 and MR-J4-_A4-RJ/MR-J4-_B4-RJ servo amplifiers.
1- 1
1. FUNCTIONS AND CONFIGURATION
POINT
The diagram shows for MR-J4-A4-RJ as an example. MR-J4-_A4 servo
amplifier does not have CN2L connector.
1- 2
1. FUNCTIONS AND CONFIGURATION
CN2
Overcurrent
amplifier detection protection detection
Encoder
Position Virtual
command Step-
encoder down
input Model Model circuit
position speed
control control
Virtual
motor
CN4 MR-BAT6V1SET
External encoder
CN2L
(Note 4)
A/D USB RS-422 D/A
I/F
CN1 CN5 CN3 CN6
DI/O control
Analog •Servo-on
•Input command pulse. Personal
(2 channels) •Start computer Controller Analog monitor
•Malfunction, etc USB RS-422 (2 channels)
1- 3
1. FUNCTIONS AND CONFIGURATION
(2) MR-J4-500A4(-RJ)/MR-J4-700A4(-RJ)
(Note 4)
Power factor
improving Regenerative
DC reactor option
RA B1
L11 Control
+ circuit 24 V DC B Electromagnetic
brake
L21 power
supply STO B2
circuit
STO
CN8
CN2
Overcurrent
amplifier detection protection detection
Encoder
Position Virtual
command Step-
encoder down
input Model Model circuit
position speed
control control
Virtual
motor
CN4 MR-BAT6V1SET
External encoder
CN2L
(Note 3)
A/D USB RS-422 D/A
I/F
CN1 CN5 CN3 CN6
DI/O control
Analog •Servo-on Personal
•Input command pulse.
(2 channels) •Start computer Controller Analog monitor
•Malfunction, etc USB RS-422 (2 channels)
1- 4
1. FUNCTIONS AND CONFIGURATION
(3) MR-J4-11KA4(-RJ)/MR-J4-15KA4(-RJ)/MR-J4-22KA4(-RJ)
(Note 5) External
Power factor regenerative resistor
improving or (Note 4)
DC reactor regenerative option External
dynamic brake
(optional)
Servo amplifier P3 P4 (Note 2) P+ C N- Servo motor
Diode
Thyristor
stack
MCCB MC L1 U U
(Note 1) U
V V
L2 Current
Power + Regene- M
supply detector
L3
U U
rative W W
TR
Charge
lamp
Cooling fan
RA B1
L11 Control
+ circuit 24 V DC B Electromagnetic
brake
L21 power
supply STO B2
circuit
STO
CN8
CN2
Overcurrent
amplifier detection protection detection
Encoder
Position Virtual
command encoder Step-
down
input Model Model circuit
position speed
control control
Virtual
motor
CN4 MR-BAT6V1SET
External encoder
CN2L
(Note 3)
A/D USB RS-422 D/A
I/F
CN1 CN5 CN3 CN6
DI/O control
Analog •Servo-on Personal
•Input command pulse.
(2 channels) •Start computer Controller Analog monitor
•Malfunction, etc USB RS-422 (2 channels)
1- 5
1. FUNCTIONS AND CONFIGURATION
POINT
The diagram shows for MR-J4-B4-RJ as an example. MR-J4-_B4 servo
amplifier does not have CN2L connector.
1- 6
1. FUNCTIONS AND CONFIGURATION
CN2
Overcurrent
amplifier detection protection detection
Encoder
Position Virtual
command encoder Step-
down
input Model Model circuit
position speed
control control
Virtual
motor
CN4 MR-BAT6V1SET
External encoder
CN2L
(Note 4)
USB D/A
IF Control
1- 7
1. FUNCTIONS AND CONFIGURATION
(2) MR-J4-500B4(-RJ)/MR-J4-700B4(-RJ)
(Note 4)
Power factor
improving Regenerative
DC reactor option
RA B1
L11 Control
+ circuit 24 V DC B Electromagnetic
brake
L21 power
supply STO B2
circuit
STO
CN8
CN2
Overcurrent
amplifier detection protection detection
Encoder
Position Virtual
command encoder Step-
down
input Model Model circuit
position speed
control control
Virtual
motor
CN4 MR-BAT6V1SET
External encoder
CN2L
(Note 3)
USB D/A
IF Control
1- 8
1. FUNCTIONS AND CONFIGURATION
(3) MR-J4-11KB4(-RJ)/MR-J4-15KB4(-RJ)/MR-J4-22KB4(-RJ)
(Note 5) External
Power factor regenerative resistor
improving or (Note 4)
DC reactor regenerative option External
dynamic brake
(optional)
Servo amplifier P3 P4 (Note 2) P+ C N- Servo motor
Diode
Thyristor
stack
MCCB MC L1 U U
(Note 1) U
V V
L2 Current
Power + Regene- M
supply detector
L3
U U
rative W W
TR
Charge
lamp
Cooling fan
RA B1
L11 Control
+ circuit 24 V DC B Electromagnetic
brake
L21 power
supply STO B2
circuit
STO
CN8
CN2
Overcurrent
amplifier detection protection detection
Encoder
Position Virtual
command encoder Step-
down
input Model Model circuit
position speed
control control
Virtual
motor
CN4 MR-BAT6V1SET
External encoder
CN2L
(Note 3)
USB D/A
IF Control
1- 9
1. FUNCTIONS AND CONFIGURATION
1 - 10
1. FUNCTIONS AND CONFIGURATION
Note 1. 0.5 A is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of
I/O points.
2. Test pulse is a signal which instantaneously turns off a signal to the servo amplifier at a constant period for external circuit to
self-diagnose.
3. Except for the terminal block.
4. 1 Mpps or lower commands are supported in the initial setting. When inputting commands between 1 Mpps and 4 Mpps,
change the setting in [Pr. PA13].
5. MR-J4-A4 servo amplifier is compatible only with two-wire type. MR-J4-A4-RJ servo amplifier is compatible with two-wire type,
four-wire type, and A/B/Z-phase differential output type. Refer to table 1.1 for details.
6. Use an external dynamic brake for this servo amplifier. Failure to do so will cause an accident because the servo motor does
not stop immediately but coasts at emergency stop. Ensure the safety in the entire equipment.
1 - 11
1. FUNCTIONS AND CONFIGURATION
1 - 12
1. FUNCTIONS AND CONFIGURATION
Note 1. 0.3 A is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of
I/O points.
2. Test pulse is a signal which instantaneously turns off a signal to the servo amplifier at a constant period for external circuit to
self-diagnose.
3. Except for the terminal block.
4. MR-J4-B4 servo amplifier is compatible only with two-wire type. MR-J4-B4-RJ servo amplifier is compatible with two-wire type,
four-wire type, and A/B/Z-phase differential output type. Refer to table 1.1 for details.
5. The communication cycle depends on the controller specifications and the number of axes connected.
6. Use an external dynamic brake for this servo amplifier. Failure to do so will cause an accident because the servo motor does
not stop immediately but coasts at emergency stop. Ensure the safety in the entire equipment.
1 - 13
1. FUNCTIONS AND CONFIGURATION
(2) Model
The following describes what each block of a model name indicates.
Special specifications
Series Symbol Special specifications
None Standard
Fully closed loop control four-wire
-RJ type/load-side encoder A/B/Z-phase
input compatible
-PX Without regenerative resistor (Note)
MR-J4-_4-RJ without regenerative
-RZ resistor (Note)
Corresponding
Symbol Corresponding
A General-purpose interface
B SSCNET Ⅲ/H
Rated output
Symbol Rated output [kW]
60 0.6
100 1
200 2
350 3.5
500 5
700 7
11K 11
15K 15
22K 22
1.5 Structure
1 - 14
1. FUNCTIONS AND CONFIGURATION
1 - 15
1. FUNCTIONS AND CONFIGURATION
(b) MR-J4-350A4(-RJ)
Detailed
The broken line area is the same as No. Name/Application
MR-J4-200A4(-RJ) or less. explanation
Main circuit power supply connector (CNP1)
(1) Section 3.1
Connect the input power supply.
(2) Rating plate Section 1.4
Control circuit power supply connector (CNP2)
(1)
(3) Connect the control circuit power supply and
(7) regenerative option. Section 3.1
Servo motor power output connector (CNP3)
(4)
Connect the servo motor.
Charge lamp
(3) (5) When the main circuit is charged, this will light.
While this lamp is lit, do not reconnect the cables.
Protective earth (PE) terminal
(2) (6) Section 3.1
Grounding terminal
Side
Battery holder
MR-J4-_A
(4) (7) Install the battery for absolute position data
section 12.4
backup.
(5)
(6)
1 - 16
1. FUNCTIONS AND CONFIGURATION
(c) MR-J4-500A4(-RJ)
POINT
The servo amplifier is shown without the front cover. For removal of the front
cover, refer to section 1.7.2 of "MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual".
(2)
(7)
Note. Lines for slots around the battery holder are omitted from the illustration.
1 - 17
1. FUNCTIONS AND CONFIGURATION
(d) MR-J4-700A4(-RJ)
POINT
The servo amplifier is shown without the front cover. For removal of the front
cover, refer to section 1.7.2 of "MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual".
(2)
(4)
(3)
Note. Lines for slots around the battery holder are omitted from the illustration.
1 - 18
1. FUNCTIONS AND CONFIGURATION
(e) MR-J4-11KA4(-RJ)/MR-J4-15KA4(-RJ)
POINT
The servo amplifier is shown without the front cover. For removal of the front
cover, refer to section 1.7.2 of "MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual".
(4)
(1)
Note. Lines for slots around the battery holder are omitted from the illustration.
1 - 19
1. FUNCTIONS AND CONFIGURATION
(f) MR-J4-22KA4(-RJ)
POINT
The servo amplifier is shown without the front cover. For removal of the front
cover, refer to section 1.7.2 of "MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual".
(1)
(4)
Note. Lines for slots around the battery holder are omitted from the illustration.
1 - 20
1. FUNCTIONS AND CONFIGURATION
1 - 21
1. FUNCTIONS AND CONFIGURATION
(b) MR-J4-350B4(-RJ)
Detailed
The broken line area is the same as No. Name/Application
MR-J4-200B4(-RJ) or less. explanation
Main circuit power supply connector (CNP1)
(1) Section 3.2
Connect the input power supply.
(2) Rating plate Section 1.4
Control circuit power supply connector (CNP2)
(1)
(3) Connect the control circuit power supply and
(7) regenerative option. Section 3.2
Servo motor power output connector (CNP3)
(4)
Connect the servo motor.
Charge lamp
(3) (5) When the main circuit is charged, this will light.
While this lamp is lit, do not reconnect the cables.
Protective earth (PE) terminal
(2) (6) Section 3.2
Side Grounding terminal
Battery holder
MR-J4-_B
(4) (7) Install the battery for absolute position data
section 12.4
backup.
(5)
(6)
1 - 22
1. FUNCTIONS AND CONFIGURATION
(c) MR-J4-500B4(-RJ)
POINT
The servo amplifier is shown without the front cover. For removal of the front
cover, refer to section 1.7.2 of "MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual".
Detailed
The broken line area is the same as No. Name/Application
MR-J4-200B4(-RJ) or less. explanation
Control circuit terminal block (TE2)
(1)
Used to connect the control circuit power supply.
Section 3.2
Main circuit terminal block (TE1)
(2)
(6) Connect the input power supply.
Battery holder
MR-J4-_B
(3) Install the battery for absolute position data
section 12.4
(3) backup.
(Note) (4) Rating plate Section 1.4
Regenerative option/power factor improving
reactor terminal block (TE3)
(5) Section 3.2
Used to connect a regenerative option and a
(4) power factor improving DC reactor.
Charge lamp
(6) When the main circuit is charged, this will light.
While this lamp is lit, do not reconnect the cables.
(5) Protective earth (PE) terminal
(7) Section 3.2
(1) Grounding terminal
(2)
(7)
Note. Lines for slots around the battery holder are omitted from the illustration.
1 - 23
1. FUNCTIONS AND CONFIGURATION
(d) MR-J4-700B4(-RJ)
POINT
The servo amplifier is shown without the front cover. For removal of the front
cover, refer to section 1.7.2 of "MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual".
Detailed
The broken line area is the same as No. Name/Application
MR-J4-200B4(-RJ) or less. explanation
Power factor improving reactor terminal block
(1) (TE3)
Used to connect the DC reactor.
Main circuit terminal block (TE1)
(2) Used to connect the input power supply,
Section 3.2
regenerative option, and servo motor.
(7)
Control circuit terminal block (TE2)
(3)
(6) Used to connect the control circuit power supply.
Protective earth (PE) terminal
(5) (4)
Grounding terminal
(Note)
Battery holder
MR-J4-_B
(5) Install the battery for absolute position data
section 12.4
backup.
(6) Rating plate Section 1.4
Charge lamp
(7) When the main circuit is charged, this will light.
While this lamp is lit, do not reconnect the cables.
(1)
(2)
(4)
(3)
Note. Lines for slots around the battery holder are omitted from the illustration.
1 - 24
1. FUNCTIONS AND CONFIGURATION
(e) MR-J4-11KB4(-RJ)/MR-J4-15KB4(-RJ)
POINT
The servo amplifier is shown without the front cover. For removal of the front
cover, refer to section 1.7.2 of "MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual".
Detailed
The broken line area is the same as No. Name/Application
MR-J4-200B4(-RJ) or less. explanation
Power factor improving reactor terminal block
(TE1-2)
(1)
Used to connect a power factor improving DC
reactor and a regenerative option.
Main circuit terminal block (TE1-1)
(7) (2) Used to connect the input power supply and servo Section 3.2
motor.
Control circuit terminal block (TE2)
(3)
Used to connect the control circuit power supply.
(6)
Protective earth (PE) terminal
(4)
Grounding terminal
Battery holder
MR-J4-_B
(5) Install the battery for absolute position data
section 12.4
(5) backup.
(Note) (6) Rating plate Section 1.4
Charge lamp
(2)
(7) When the main circuit is charged, this will light.
While this lamp is lit, do not reconnect the cables.
(3)
(4)
(1)
Note. Lines for slots around the battery holder are omitted from the illustration.
1 - 25
1. FUNCTIONS AND CONFIGURATION
(f) MR-J4-22KB4(-RJ)
POINT
The servo amplifier is shown without the front cover. For removal of the front
cover, refer to section 1.7.2 of "MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual".
Detailed
The broken line area is the same as No. Name/Application
MR-J4-200B4(-RJ) or less. explanation
Power factor improving reactor terminal block
(TE1-2)
(1)
Used to connect a power factor improving DC
reactor and a regenerative option.
(7) Main circuit terminal block (TE1-1)
(2) Used to connect the input power supply and servo Section 3.2
(5) motor.
(Note)
Control circuit terminal block (TE2)
(3)
Used to connect the control circuit power supply.
(6) Protective earth (PE) terminal
(4)
Grounding terminal
Battery holder
MR-J4-_B
(5) Install the battery for absolute position data
section 12.4
backup.
(6) Rating plate Section 1.4
(2) Charge lamp
(7) When the main circuit is charged, this will light.
While this lamp is lit, do not reconnect the cables.
(3)
(1)
(4)
Note. Lines for slots around the battery holder are omitted from the illustration.
1 - 26
1. FUNCTIONS AND CONFIGURATION
POINT
Equipment other than the servo amplifier and servo motor are optional or
recommended products.
CN6
Analog monitor
(Note 3)
Magnetic CN3
contactor Personal computer and others
(MC)
(Note 1) CN8 To safety relay or
MR-J3-D05 safety
logic unit
L21
Servo motor
1 - 27
1. FUNCTIONS AND CONFIGURATION
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. Refer to section 1.2.1 for the power supply specification.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop
deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn
off the magnetic contactor.
4. This is for MR-J4-_A4-RJ servo amplifier. MR-J4-_A4 servo amplifier does not have CN2L connector. When using MR-J4-_A4-
RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector.
Refer to Table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
1 - 28
1. FUNCTIONS AND CONFIGURATION
(2) MR-J4-350A4(-RJ)
RS T
(Note 2)
Power supply
Molded-case Personal
circuit breaker computer
(MCCB) MR Configurator2
CN5
(Note 3)
Magnetic
contactor CN6
(MC) Analog monitor
(Note 1) CN3
Personal computer and others
CN8 To safety relay or
MR-J3-D05 safety
logic unit
Line noise filter
(FR-BSF01)
CN1
L21
Servo motor
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. Refer to section 1.2.1 for the power supply specification.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop
deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn
off the magnetic contactor.
4. This is for MR-J4-_A4-RJ servo amplifier. MR-J4-_A4 servo amplifier does not have CN2L connector. When using MR-J4-_A4-
RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector.
Refer to Table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
1 - 29
1. FUNCTIONS AND CONFIGURATION
(3) MR-J4-500A4(-RJ)
RS T
(Note 2)
Power supply
Molded-case
circuit breaker
(MCCB)
Personal
computer
MR Configurator2
CN5
(Note 3)
Magnetic
contactor
(MC)
(Note 1) CN6
Power factor Analog monitor
improving DC
reactor CN3
(FR-HEL-H) Personal computer and others
Line noise filter P3 CN8 To safety relay or
(FR-BSF01) MR-J3-D05 safety
logic unit
P4
CN1
CN2L (Note 4)
CN4
Battery
L21
L3 L11
L2
L1
U V W
P+ C
Regenerative
option
Servo motor
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. Refer to section 1.2.1 for the power supply specification.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop
deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn
off the magnetic contactor.
4. This is for MR-J4-_A4-RJ servo amplifier. MR-J4-_A4 servo amplifier does not have CN2L connector. When using MR-J4-_A4-
RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector.
Refer to Table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
1 - 30
1. FUNCTIONS AND CONFIGURATION
(4) MR-J4-700A4(-RJ)
RS T
(Note 2)
Power supply Personal
computer
Molded-case MR Configurator2
circuit breaker CN5
(MCCB)
CN6
(Note 3) Analog monitor
Magnetic
contactor CN3
(MC) Personal computer and others
(Note 1) CN8 To safety relay or
MR-J3-D05 safety
logic unit
P4
L3
L2
L1
U V W
P+ C
Regenerative
option
Servo motor
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. Refer to section 1.2.1 for the power supply specification.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop
deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn
off the magnetic contactor.
4. This is for MR-J4-_A4-RJ servo amplifier. MR-J4-_A4 servo amplifier does not have CN2L connector. When using MR-J4-_A4-
RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector.
Refer to Table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
1 - 31
1. FUNCTIONS AND CONFIGURATION
(5) MR-J4-11KA4(-RJ)/MR-J4-15KA4(-RJ)
Personal
computer
RS T MR Configurator2
(Note 2) CN5
Power supply
Molded-case
circuit breaker
(MCCB)
CN6
Analog monitor
CN3
Personal computer and others
(Note 3)
Magnetic CN8 To safety relay or
contactor MR-J3-D05 safety
(MC) logic unit
(Note 1)
CN1
L3
L2
L1
U V W
Power factor
improving DC
reactor
(FR-HEL-H)
P3
P4
P+ C
Regenerative
option
Servo motor
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. Refer to section 1.2.1 for the power supply specification.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop
deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn
off the magnetic contactor.
4. This is for MR-J4-_A4-RJ servo amplifier. MR-J4-_A4 servo amplifier does not have CN2L connector. When using MR-J4-_A4-
RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector.
Refer to Table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
1 - 32
1. FUNCTIONS AND CONFIGURATION
(6) MR-J4-22KA4(-RJ)
Personal
computer
MR Configurator2
RS T CN5
(Note 2)
Power supply
Molded-case
circuit breaker
(MCCB)
CN6
Analog monitor
CN3
Personal computer and others
L3
L2
L1
Power factor
improving DC U V W
reactor
(FR-HEL-H)
P3
P4
P+ C
Regenerative
option
Servo motor
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. Refer to section 1.2.1 for the power supply specification.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop
deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn
off the magnetic contactor.
4. This is for MR-J4-_A4-RJ servo amplifier. MR-J4-_A4 servo amplifier does not have CN2L connector. When using MR-J4-_A4-
RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector.
Refer to Table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
1 - 33
1. FUNCTIONS AND CONFIGURATION
Molded-case Personal
circuit breaker computer
(MCCB) MR Configurator2
CN5
(Note 3)
Magnetic
contactor
(MC)
(Note 1) CN3 Junction terminal
block
L1
CN1B Next servo amplifier
L2
CN1A or cap
L3
U
Power factor P3 CN2
improving DC V
reactor
(FR-HEL-H) P4 CN2L (Note 4)
W
P+ CN4
Regenerative Battery
option
C
L11
L21
Servo motor
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. Refer to section 1.2.2 for the power supply specification.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop
deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn
off the magnetic contactor.
4. This is for MR-J4-_B4-RJ servo amplifier. MR-J4-_B4 servo amplifier does not have CN2L connector. When using MR-J4-_B4-
RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector.
Refer to Table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
1 - 34
1. FUNCTIONS AND CONFIGURATION
(2) MR-J4-350B4(-RJ)
RS T
(Note 2)
Power supply
Molded-case
circuit breaker Personal
(MCCB) computer
MR Configurator2
CN5
(Note 3)
Magnetic
contactor
(MC)
(Note 1) CN3 Junction terminal
block
L1
CN1B Next servo amplifier
L2
CN1A or cap
L3
L21
Servo motor
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. Refer to section 1.2.2 for the power supply specification.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop
deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn
off the magnetic contactor.
4. This is for MR-J4-_B4-RJ servo amplifier. MR-J4-_B4 servo amplifier does not have CN2L connector. When using MR-J4-_B4-
RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector.
Refer to Table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
1 - 35
1. FUNCTIONS AND CONFIGURATION
(3) MR-J4-500B4(-RJ)
RS T
(Note 2)
Power supply Personal
computer
Molded-case MR Configurator2
circuit breaker CN5
(MCCB)
(Note 3)
Magnetic
contactor CN3 Junction terminal
(MC) block
(Note 1)
Power factor
improving DC To safety relay or
reactor CN8
MR-J3-D05 safety
(FR-HEL-H) logic unit
P3
Line noise filter CN1A Servo system controller
(FR-BSF01) or previous servo
amplifier CN1B
P4
CN1B Next servo amplifier
CN1A or cap
CN2
CN2L (Note 4)
CN4
Battery
L21
L3 L11
L2
L1
U V W
P+ C
Regenerative
option
Servo motor
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. Refer to section 1.2.2 for the power supply specification.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop
deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn
off the magnetic contactor.
4. This is for MR-J4-_B4-RJ servo amplifier. MR-J4-_B4 servo amplifier does not have CN2L connector. When using MR-J4-_B4-
RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector.
Refer to Table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
1 - 36
1. FUNCTIONS AND CONFIGURATION
(4) MR-J4-700B4(-RJ)
Personal
computer
MR Configurator2
RS T CN5
(Note 2)
Power supply
Molded-case
circuit breaker
(MCCB)
CN2
L21
L11 CN2L (Note 4)
Power factor CN4
improving DC Battery
reactor
(FR-HEL-H)
P3
P4
L3
L2
L1
U V W
P+ C
Regenerative
option
Servo motor
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. Refer to section 1.2.2 for the power supply specification.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop
deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn
off the magnetic contactor.
4. This is for MR-J4-_B4-RJ servo amplifier. MR-J4-_B4 servo amplifier does not have CN2L connector. When using MR-J4-_B4-
RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector.
Refer to Table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
1 - 37
1. FUNCTIONS AND CONFIGURATION
(5) MR-J4-11K4B(-RJ)/MR-J4-15K4B(-RJ)
Personal
computer
MR Configurator2
RS T CN5
(Note 2)
Power supply
Molded-case
circuit breaker
(MCCB)
CN2
L21 CN2L (Note 4)
L11 CN4
Battery
L3
L2
L1
U V W
Power factor
improving DC
reactor
(FR-HEL-H)
P3
P4
P+ C
Regenerative
option
Servo motor
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. Refer to section 1.2.2 for the power supply specification.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop
deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn
off the magnetic contactor.
4. This is for MR-J4-_B4-RJ servo amplifier. MR-J4-_B4 servo amplifier does not have CN2L connector. When using MR-J4-_B4-
RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector.
Refer to Table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
1 - 38
1. FUNCTIONS AND CONFIGURATION
(6) MR-J4-22K4B(-RJ)
Personal
computer
MR Configurator2
CN5
RS T
(Note 2)
Power supply
Molded-case
circuit breaker CN3 Junction terminal
(MCCB) block
CN2
Line noise filter
(FR-BLF) CN2L (Note 4)
CN4
Battery
L21
L11
L3
L2
L1
U V W
Power factor
improving DC
reactor
(FR-HEL-H)
P3
P4 P+ C
Regenerative
option
Servo motor
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. Refer to section 1.2.2 for the power supply specification.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop
deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn
off the magnetic contactor.
4. This is for MR-J4-_B4-RJ servo amplifier. MR-J4-_B4 servo amplifier does not have CN2L connector. When using MR-J4-_B4-
RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector.
Refer to Table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
1 - 39
1. FUNCTIONS AND CONFIGURATION
MEMO
1 - 40
2. INSTALLATION
2. INSTALLATION
2- 1
2. INSTALLATION
The items in the following table are the same as those for MR-J4-_A(-RJ) or MR-J4-_B(-RJ) servo amplifier.
For details of the items, refer to each chapter/section of the detailed explanation field.
Model Item Detailed explanation
MR-J4-_A4(-RJ) Keep out foreign materials MR-J4-_A(-RJ) Servo Amplifier Instruction Manual
section 2.2
Encoder cable stress MR-J4-_A(-RJ) Servo Amplifier Instruction Manual
section 2.3
Inspection items MR-J4-_A(-RJ) Servo Amplifier Instruction Manual
section 2.4
Parts having service lives MR-J4-_A(-RJ) Servo Amplifier Instruction Manual
section 2.5
MR-J4-_B4(-RJ) Keep out foreign materials MR-J4-_B(-RJ) Servo Amplifier Instruction Manual
section 2.2
Encoder cable stress MR-J4-_B(-RJ) Servo Amplifier Instruction Manual
section 2.3
SSCNET III cable laying MR-J4-_B(-RJ) Servo Amplifier Instruction Manual
section 2.4
Inspection items MR-J4-_B(-RJ) Servo Amplifier Instruction Manual
section 2.5
Parts having service lives MR-J4-_B(-RJ) Servo Amplifier Instruction Manual
section 2.6
40 mm or more
Servo amplifier Wiring allowance
80 mm
or more
10 mm 10 mm
or more or more Top
Bottom
40 mm or more
(Note)
Note. For 11 kW to 22 kW servo amplifiers, the clearance between the bottom and ground will be 120 mm or more.
2- 2
2. INSTALLATION
100 mm or more
10 mm or more
Top
30 mm 30 mm
or more or more
Bottom
40 mm or more
(Note)
Note. For 11 kW to 22 kW servo amplifiers, the clearance between the bottom and ground
will be 120 mm or more.
(2) Others
When using heat generating equipment such as the regenerative option, install them with full
consideration of heat generation so that the servo amplifier is not affected.
Install the servo amplifier on a perpendicular wall in the correct vertical direction.
2- 3
2. INSTALLATION
MEMO
2- 4
3. SIGNALS AND WIRING
Any person who is involved in wiring should be fully competent to do the work.
Before wiring, turn off the power and wait for 15 minutes or more until the charge
lamp turns off. Then, confirm that the voltage between P+ and N- is safe with a
voltage tester and others. Otherwise, an electric shock may occur. In addition,
when confirming whether the charge lamp is off or not, always confirm it from the
front of the servo amplifier.
WARNING Ground the servo amplifier and servo motor securely.
Do not attempt to wire the servo amplifier and servo motor until they have been
installed. Otherwise, it may cause an electric shock.
The cables should not be damaged, stressed, loaded, or pinched. Otherwise, it
may cause an electric shock.
To avoid an electric shock, insulate the connections of the power supply
terminals.
Wire the equipment correctly and securely. Otherwise, the servo motor may
operate unexpectedly, resulting in injury.
Connect cables to the correct terminals. Otherwise, a burst, damage, etc. may
occur.
Ensure that polarity (+/-) is correct. Otherwise, a burst, damage, etc. may occur.
The surge absorbing diode installed to the DC relay for control output should be
fitted in the specified direction. Otherwise, the emergency stop and other
protective circuits may not operate.
Servo amplifier Servo amplifier
24 V DC 24 V DC
DOCOM DOCOM
Control output RA
Control output RA
signal signal
CAUTION For sink output interface For source output interface
3- 1
3. SIGNALS AND WIRING
Connect the servo amplifier power output (U, V, and W) to the servo motor power
input (U, V, and W) directly. Do not let a magnetic contactor, etc. intervene.
Otherwise, it may cause a malfunction.
Servo amplifier Servo motor Servo amplifier Servo motor
CAUTION U
U
U
U
V V
V M V M
W W
W W
POINT
When you use a linear servo motor, replace the following left words to the right
words.
Load to motor inertia ratio → Load mass
Torque → Thrust
(Servo motor) speed → (Linear servo motor) speed
The items in the following table are the same as those for MR-J4-_A(-RJ) or MR-J4-_B(-RJ) servo amplifier.
For details of the items, refer to each chapter/section of the detailed explanation field.
Model Item Detailed explanation
MR-J4-_A4(-RJ) I/O signal connection example MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 3.2
Connector and pin assignment MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 3.4
Signal (device) explanations MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 3.5
Detailed explanation of signals MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 3.6
Forced stop deceleration function MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 3.7
Alarm occurrence timing chart MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 3.8
Interface MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 3.9
Servo motor with an electromagnetic brake MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 3.10
Grounding MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 3.11
MR-J4-_B4(-RJ) I/O signal connection example MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 3.2
Connector and pin assignment MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 3.4
Signal (device) explanations MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 3.5
Forced stop deceleration function MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 3.6
Alarm occurrence timing chart MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 3.7
Interface MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 3.8
SSCNET III cable connection MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 3.9
Servo motor with an electromagnetic brake MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 3.10
Grounding MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 3.11
3- 2
3. SIGNALS AND WIRING
3.1 MR-J4-_A4(-RJ)
Always connect a magnetic contactor between the power supply and the main
circuit power supply (L1, L2, and L3) of the servo amplifier, in order to configure a
circuit that shuts down the power supply on the side of the servo amplifier’s power
supply. If a magnetic contactor is not connected, continuous flow of a large
current may cause a fire when the servo amplifier malfunctions.
Use ALM (Malfunction) to switch main circuit power supply off. Not doing so may
cause a fire when a regenerative transistor malfunctions or the like may overheat
the regenerative resistor.
CAUTION Check the servo amplifier model, and then input proper voltage to the servo
amplifier power supply. If input voltage exceeds the upper limit, the servo amplifier
will break down.
The servo amplifier has a built-in surge absorber (varistor) to reduce noise and to
suppress lightning surge. The varistor can break down due to its aged
deterioration. To prevent a fire, use a molded-case circuit breaker or fuse for input
power supply.
Connecting a servo motor for different axis to U, V, W, or CN2 of the servo
amplifier may cause a malfunction.
POINT
EM2 has the same function as EM1 in the torque control mode.
Configure the wirings so that the main circuit power supply is shut off and SON (Servo-on) is turned off after
deceleration to a stop due to an alarm occurring, enabled servo forced stop, etc. A molded-case circuit
breaker (MCCB) must be used with the input cables of the main circuit power supply.
3- 3
3. SIGNALS AND WIRING
MC
Emergency stop switch SK
(Note 11)
Step-down
transformer Servo amplifier Servo motor
CNP1
(Note 6) (Note 10)
MCCB N- CNP3
MC (Note 5)
L1 U U
3-phase Motor
380 V AC or L2 V V
480 V AC M
L3 W W
P3
(Note 9) (Note 1)
P4
CNP2
P+
(Note 2) C
D (Note 10)
CN2 (Note 3) Encoder
L11 Encoder cable
L21
(Note 7)
Main circuit power supply CN1
Forced stop 2 EM2 CN1
(Note 4) 24 V DC (Note 12)
Servo-on SON DOCOM
(Note 4)
DICOM ALM RA1 Malfunction
24 V DC (Note 12)
CN8
(Note 8)
Short-circuit connector
(Packed with the servo amplifier)
Note 1. Always connect between P3 and P4 terminals. (factory-wired) When using the power factor improving DC reactor, refer to
section 9.8. Use either the power factor improving DC reactor or the power factor improving AC reactor.
2. Always connect between P+ and D terminals. (factory-wired) When using the regenerative option, refer to section 9.2.
3. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "Servo Motor Instruction
Manual (Vol. 3)".
4. This diagram is for sink I/O interface. For source I/O interface, refer to section 3.9.3 in MR-J4-_A(-RJ) Servo Amplifier
Instruction Manual.
5. For connecting servo motor power wires, refer to "Servo Motor Instruction Manual (Vol. 3)".
6. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of
contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that
may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not
required, slow the time to turn off the magnetic contactor.
7. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo
amplifier.
8. When not using the STO function, attach the short-circuit connector came with a servo amplifier.
9. When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit breaker. (Refer
to section 9.7.)
10. Connecting a servo motor for different axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
11. Stepdown transformer is required when the coil voltage of the magnetic contactor is 200 V class.
12. The illustration of the 24 V DC power supply is divided between input signal and output signal for convinence. However,
they can be configured by one.
3- 4
3. SIGNALS AND WIRING
(2) MR-J4-500A4(-RJ)/MR-J4-700A4(-RJ)
Malfunction OFF
RA1 ON
MC
MC
(Note 11) Emergency stop switch SK
Step-down
transformer Servo amplifier Servo motor
(Note 6)
MCCB MC
L1 (Note 10)
3-phase (Note 5)
380 V AC or L2 Built-in U U
480 V AC regenerative Motor
L3 resistor V V
M
(Note 2) P+ W W
(Note 9) C
L11
L21
N- (Note 10)
CN2 (Note 3) Encoder
P3 Encoder cable
(Note 1)
P4
(Note 7)
Main circuit power supply CN1
Forced stop 2 EM2 CN1
(Note 4) DC 24 V (Note 12)
Servo-on SON DOCOM
Note 1. Always connect between P3 and P4 terminals. (factory-wired) When using the power factor improving DC reactor, refer to
section 9.8. Use either the power factor improving DC reactor or the power factor improving AC reactor.
2. When using the regenerative option, refer to section 9.2.
3. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "Servo Motor Instruction
Manual (Vol. 3)".
4. This diagram is for sink I/O interface. For source I/O interface, refer to section 3.9.3 in MR-J4-_A(-RJ) Servo Amplifier
Instruction Manual.
5. For connecting servo motor power wires, refer to "Servo Motor Instruction Manual (Vol. 3)".
6. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of
contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that
may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not
required, slow the time to turn off the magnetic contactor.
7. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo
amplifier.
8. When not using the STO function, attach the short-circuit connector came with a servo amplifier.
9. When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit breaker. (Refer
to section 9.7.)
10. Connecting a servo motor for different axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
11. Stepdown transformer is required when the coil voltage of the magnetic contactor is 200 V class.
12. The illustration of the 24 V DC power supply is divided between input signal and output signal for convinence. However,
they can be configured by one.
3- 5
3. SIGNALS AND WIRING
MC
(Note 13)
Emergency stop switch SK Cooling fan
(Note 11)
Step-down power supply
transformer External
Servo amplifier dynamic brake Servo motor
(Note 6)
MCCB MC (optional)
(Note 15)
L1
3-phase (Note 10)
380 V AC or L2 U U
480 V AC Motor
L3 V V MCCB
M
P+ W W
(Note 5)
(Note 9) C
Regenerative
resistor
(Note 2)
L11
L21
N- (Note 10)
CN2 (Note 3) Encoder
P3 Encoder cable
(Note 1)
P4
BU
BV
BW
Cooling fan (Note 12)
(Note 7)
Main circuit power supply CN1
Forced stop 2 EM2 CN1
(Note 4) 24 V DC (Note 14)
Servo-on SON DOCOM
(Note 4)
DICOM ALM RA1 Malfunction
24 V DC (Note 14)
CN8
(Note 8)
Short-circuit connector
(Packed with the servo amplifier)
Note 1. Always connect between P3 and P4 terminals. (factory-wired) When using the power factor improving DC reactor, refer to
section 9.8. Use either the power factor improving DC reactor or the power factor improving AC reactor.
2. When using the regenerative resistor, refer to section 9.2.
3. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "Servo Motor Instruction Manual
(Vol. 3)".
4. This diagram is for sink I/O interface. For source I/O interface, refer to section 3.9.3 in MR-J4-_A(-RJ) Servo Amplifier
Instruction Manual.
5. For connecting servo motor power wires, refer to "Servo Motor Instruction Manual (Vol. 3)".
6. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of
contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may
cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not
required, slow the time to turn off the magnetic contactor.
7. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo
amplifier.
8. When not using the STO function, attach the short-circuit connector came with a servo amplifier.
9. When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit breaker. (Refer to
section 9.7.)
10. Connecting a servo motor for different axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
11. Stepdown transformer is required when the coil voltage of the magnetic contactor is 200 V class.
12. Only HG-JR22K1M4 servo motor is equipped with a cooling fan.
13. For the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)".
14. The illustration of the 24 V DC power supply is divided between input signal and output signal for convinence. However, they
can be configured by one.
15. Use an external dynamic brake for this servo amplifier. Failure to do so will cause an accident because the servo motor does
not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the
safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to section 6.1.1.
3- 6
3. SIGNALS AND WIRING
POINT
For the layout of connector and terminal block, refer to chapter 7 DIMENSIONS.
Connection target
Symbol Description
(application)
Supply the following power to L1, L2, and L3.
Servo amplifier
Main circuit power MR-J4-60A4(-RJ) to MR-J4-22KA4(-RJ)
L1/L2/L3 Power
supply
3-phase 380 V AC to 480 V AC,
L1/L2/L3
50 Hz/60 Hz
When not using the power factor improving DC reactor, connect P3 and P4. (factory-
Power factor wired)
P3/P4 improving DC When using the power factor improving DC reactor, disconnect P3 and P4, and
reactor connect the power factor improving DC reactor to P3 and P4.
Refer to section 9.8 for details.
1) MR-J4-350A4(-RJ) or less
When using a servo amplifier built-in regenerative resistor, connect P+ and D.
(factory-wired)
When using a regenerative option, disconnect P+ and D, and connect the
regenerative option to P+ and C.
2) MR-J4-500A4(-RJ) to MR-J4-22KA4(-RJ)
Regenerative
P+/C/D MR-J4-500A4(-RJ) to MR-J4-22KA4(-RJ) do not have D.
option
When using a servo amplifier built-in regenerative resistor, connect P+ and C.
(factory-wired)
When using a regenerative option, disconnect wires of P+ and C for the built-in
regenerative resistor. And then connect wires of the regenerative option to P+
and C.
Refer to section 9.2 to 9.5 for details.
Supply the following power to L11 and L21.
Connect them to the servo motor power supply (U, V, and W). Connect the servo
Servo motor amplifier power output (U, V, and W) to the servo motor power input (U, V, and W)
U/V/W
power output directly. Do not let a magnetic contactor, etc. intervene. Otherwise, it may cause a
malfunction.
Power This terminal is used for a power regenerative converter, power regenerative
regenerative common converter, and brake unit.
converter Refer to section 9.3 to 9.5 for details.
N- Power
regenerative
common converter
Brake unit
Protective earth Connect it to the grounding terminal of the servo motor and to the protective earth
(PE) (PE) of the cabinet for grounding.
3- 7
3. SIGNALS AND WIRING
POINT
A voltage, output signal, etc. of analog monitor output may be irregular at power-
on.
2) Switch on the control circuit power supply (L11 and L21) simultaneously with the main circuit
power supply or before switching on the main circuit power supply. If the main circuit power
supply is not on, the display shows the corresponding warning. However, by switching on the
main circuit power supply, the warning disappears and the servo amplifier will operate properly.
3) The servo amplifier receives the SON (Servo-on) 2.5 s to 3.5 s after the main circuit power supply
is switched on. Therefore, when SON (Servo-on) is switched on simultaneously with the main
circuit power supply, the base circuit will switch on in about 2.5 s to 3.5 s, and the RD (Ready) will
switch on in further about 5 ms, making the servo amplifier ready to operate. (Refer to (b) in this
section.)
4) When RES (Reset) is switched on, the base circuit is shut off and the servo motor shaft coasts.
Note. This time period is longer when detecting magnetic pole for the linear servo motor.
3- 8
3. SIGNALS AND WIRING
POINT
For the wire sizes used for wiring, refer to section 9.6.
MR-J4-500A4(-RJ) or more do not have these connectors.
Use the servo amplifier power supply connector for wiring CNP1, CNP2, and CNP3.
(a) Connector
Servo amplifier
(Note)
CNP1
CNP2
CNP3
3- 9
3. SIGNALS AND WIRING
Stripped length
You can also use a ferrule to connect with the connectors. The following shows references to
select ferrules according to wire sizes.
Ferrule model (Phoenix Contact) Crimp terminal
Servo amplifier Wire size
For 1 cable For 2 cables (Phoenix Contact)
MR-J4-60A4(-RJ) to AWG 16 AI1.5-10BK AI-TWIN2×1.5-10BK
CRIMPFOX-ZA3
MR-J4-350A4(-RJ) AWG 14 AI2.5-10BU
2) Inserting wire
Insert the open tool as follows and push down it to open the spring. While the open tool is pushed
down, insert the stripped wire into the wire insertion hole. Check the insertion depth so that the
cable insulator does not get caught by the spring.
Release the open tool to fix the wire. Pull the wire lightly to confirm that the wire is surely
connected.
The following shows a connection example of the CNP3 connector for 3.5 kW.
3 - 10
3. SIGNALS AND WIRING
3.2 MR-J4-_B4(-RJ)
Always connect a magnetic contactor between the power supply and the main
circuit power supply (L1, L2, and L3) of the servo amplifier, in order to configure a
circuit that shuts down the power supply on the side of the servo amplifier’s power
supply. If a magnetic contactor is not connected, continuous flow of a large
current may cause a fire when the servo amplifier malfunctions.
Use ALM (Malfunction) to switch main circuit power supply off. Not doing so may
cause a fire when a regenerative transistor malfunctions or the like may overheat
the regenerative resistor.
CAUTION Check the servo amplifier model, and then input proper voltage to the servo
amplifier power supply. If input voltage exceeds the upper limit, the servo amplifier
will break down.
The servo amplifier has a built-in surge absorber (varistor) to reduce noise and to
suppress lightning surge. The varistor can break down due to its aged
deterioration. To prevent a fire, use a molded-case circuit breaker or fuse for input
power supply.
Connecting a servo motor for different axis to U, V, W, or CN2 of the servo
amplifier may cause a malfunction.
POINT
Even if alarm has occurred, do not switch off the control circuit power supply.
When the control circuit power supply has been switched off, optical module
does not operate, and optical transmission of SSCNET III/H communication is
interrupted. Therefore, the next axis servo amplifier displays "AA" at the indicator
and turns into base circuit shut-off. The servo motor stops with starting dynamic
brake.
EM2 has the same function as EM1 in the torque control mode.
Configure the wiring so that the main circuit power supply is shut off and the servo-on command turned off
after deceleration to a stop due to an alarm occurring, an enabled servo forced stop, or an enabled controller
forced stop. A molded-case circuit breaker (MCCB) must be used with the input cables of the main circuit
power supply.
3 - 11
3. SIGNALS AND WIRING
MC
Emergency stop switch SK
(Note 12)
Step-down
transformer Servo amplifier Servo motor
CNP1
(Note 11)
(Note 7) N-
MCCB MC CNP3 (Note 6)
L1 U U
3-phase Motor
380 V AC or L2 V V
480 V AC M
L3 W W
P3
(Note 10) (Note 1)
P4
CNP2
P+
(Note 2) C
(Note 11)
D
CN2 (Note 3) Encoder
L11 Encoder cable
L21
(Note 8)
Main circuit power supply CN3 CN3 24 V DC (Note 13)
(Note 5) Forced stop 2 EM2 DOCOM
(Note 4)
DICOM ALM RA1 Malfunction (Note 5)
24 V DC (Note 13)
(Note 9) CN8
Short-circuit connector
(Packed with the servo amplifier)
Note 1. Always connect between P3 and P4 terminals. (factory-wired) When using the power factor improving DC reactor, refer to
section 9.8. Use either the power factor improving DC reactor or the power factor improving AC reactor.
2. Always connect between P+ and D terminals. (factory-wired) When using the regenerative option, refer to section 9.2.
3. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "Servo Motor Instruction
Manual (Vol. 3)".
4. If disabling ALM (Malfunction) output with the parameter, configure up the power supply circuit which switches off the
magnetic contactor after detection of alarm occurrence on the controller side.
5. This diagram is for sink I/O interface. For source I/O interface, refer to section 3.8.3 in MR-J4-_B(-RJ) Servo Amplifier
Instruction Manual.
6. For connecting servo motor power wires, refer to "Servo Motor Instruction Manual (Vol. 3)".
7. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of
contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that
may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not
required, slow the time to turn off the magnetic contactor.
8. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo
amplifier.
9. When not using the STO function, attach the short-circuit connector came with a servo amplifier.
10. When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit breaker. (Refer
to section 9.7.)
11. Connecting a servo motor for different axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
12. Stepdown transformer is required when the coil voltage of the magnetic contactor is 200 V class.
13. The illustration of the 24 V DC power supply is divided between input signal and output signal for convinence. However,
they can be configured by one.
3 - 12
3. SIGNALS AND WIRING
(2) MR-J4-500B4(-RJ)/MR-J4-700B4(-RJ)
(Note 4)
Malfunction OFF
RA1 ON
MC
MC
Emergency stop switch SK
(Note 12)
Step-down
transformer Servo amplifier Servo motor
(Note 7)
MCCB MC
L1 (Note 11)
3-phase (Note 6)
380 V AC or L2 Built-in U U
480 V AC regenerative Motor
L3 resistor V V
M
(Note 2) P+ W W
(Note 10) C
L11
L21
(Note 11)
N-
CN2 (Note 3) Encoder
P3 Encoder cable
(Note 1)
P4
(Note 8)
Main circuit power supply CN3 CN3 24 V DC (Note 13)
(Note 5) Forced stop 2 EM2 DOCOM
Note 1. Always connect between P3 and P4 terminals. (factory-wired) When using the power factor improving DC reactor, refer to
section 9.8. Use either the power factor improving DC reactor or the power factor improving AC reactor.
2. When using the regenerative option, refer to section 9.2.
3. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "Servo Motor Instruction
Manual (Vol. 3)".
4. If disabling ALM (Malfunction) output with the parameter, configure up the power supply circuit which switches off the
magnetic contactor after detection of alarm occurrence on the controller side.
5. This diagram is for sink I/O interface. For source I/O interface, refer to section 3.8.3 in MR-J4-_B(-RJ) Servo Amplifier
Instruction Manual.
6. For connecting servo motor power wires, refer to "Servo Motor Instruction Manual (Vol. 3)".
7. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of
contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that
may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not
required, slow the time to turn off the magnetic contactor.
8. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo
amplifier.
9. When not using the STO function, attach the short-circuit connector came with a servo amplifier.
10. When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit breaker. (Refer
to section 9.7.)
11. Connecting a servo motor for different axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
12. Stepdown transformer is required when the coil voltage of the magnetic contactor is 200 V class.
13. The illustration of the 24 V DC power supply is divided between input signal and output signal for convinence. However,
they can be configured by one.
3 - 13
3. SIGNALS AND WIRING
MC
(Note 14)
(Note 12) Emergency stop switch SK Cooling fan
Step-down power supply
transformer External
Servo amplifier dynamic brake Servo motor
(Note 7)
MCCB MC (optional)
L1 (Note 16)
3-phase (Note 11)
380 V AC or L2 U U
480 V AC Motor
L3 V V MCCB
M
P+ W W
(Note 6)
(Note 10) C
Regenerative
resistor
(Note 2)
L11
L21
(Note 11)
N-
CN2 (Note 3) Encoder
P3 Encoder cable
(Note 1)
P4
BU
BV
BW
Cooling fan (Note 13)
(Note 8)
Main circuit power supply CN3 CN3 24 V DC (Note 15)
(Note 5) Forced stop 2 EM2 DOCOM
Note 1. Always connect between P3 and P4 terminals. (factory-wired) When using the power factor improving DC reactor, refer to
section 9.8. Use either the power factor improving DC reactor or the power factor improving AC reactor.
2. When using the regenerative resistor, refer to section 9.2.
3. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "Servo Motor Instruction Manual
(Vol. 3)".
4. If disabling ALM (Malfunction) output with the parameter, configure up the power supply circuit which switches off the magnetic
contactor after detection of alarm occurrence on the controller side.
5. This diagram is for sink I/O interface. For source I/O interface, refer to section 3.8.3 in MR-J4-_B(-RJ) Servo Amplifier
Instruction Manual.
6. For connecting servo motor power wires, refer to "Servo Motor Instruction Manual (Vol. 3)".
7. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of
contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may
cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not
required, slow the time to turn off the magnetic contactor.
8. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo
amplifier.
9. When not using the STO function, attach the short-circuit connector came with a servo amplifier.
10. When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit breaker. (Refer to
section 9.7.)
11. Connecting a servo motor for different axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
12. Stepdown transformer is required for coil voltage of magnetic contactor more than 200 V class servo amplifiers.
13. Only HG-JR22K1M4 servo motor is equipped with a cooling fan.
14. For the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)".
15. The illustration of the 24 V DC power supply is divided between input signal and output signal for convinence. However, they
can be configured by one.
16. Use an external dynamic brake for this servo amplifier. Failure to do so will cause an accident because the servo motor does
not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the
safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to section 6.2.1.
3 - 14
3. SIGNALS AND WIRING
POINT
For the layout of connector and terminal block, refer to chapter 7 DIMENSIONS.
Connection target
Symbol Description
(application)
Supply the following power to L1, L2, and L3.
Servo amplifier
Main circuit power MR-J4-60B4(-RJ) to MR-J4-22KB4(-RJ)
L1/L2/L3 Power
supply
3-phase 380 V AC to 480 V AC,
L1/L2/L3
50 Hz/60 Hz
When not using the power factor improving DC reactor, connect P3 and P4. (factory-
Power factor wired)
P3/P4 improving DC When using the power factor improving DC reactor, disconnect P3 and P4, and
reactor connect the power factor improving DC reactor to P3 and P4.
Refer to section 9.8 for details.
1) MR-J4-350B4(-RJ) or less
When using a servo amplifier built-in regenerative resistor, connect P+ and D.
(factory-wired)
When using a regenerative option, disconnect P+ and D, and connect the
regenerative option to P+ and C.
2) MR-J4-500B4(-RJ) to MR-J4-22KB4(-RJ)
Regenerative
P+/C/D MR-J4-500B4(-RJ) to MR-J4-22KB4(-RJ) do not have D.
option
When using a servo amplifier built-in regenerative resistor, connect P+ and C.
(factory-wired)
When using a regenerative option, disconnect wires of P+ and C for the built-in
regenerative resistor. And then connect wires of the regenerative option to P+
and C.
Refer to section 9.2 to 9.5 for details.
Supply the following power to L11 and L21.
Connect them to the servo motor power supply (U, V, and W). Connect the servo
Servo motor amplifier power output (U, V, and W) to the servo motor power input (U, V, and W)
U/V/W
power output directly. Do not let a magnetic contactor, etc. intervene. Otherwise, it may cause a
malfunction.
Power This terminal is used for a power regenerative converter, power regenerative
regenerative common converter, and brake unit.
converter Refer to section 9.3 to 9.5 for details.
N- Power
regenerative
common converter
Brake unit
Protective earth Connect it to the grounding terminal of the servo motor and to the protective earth
(PE) (PE) of the cabinet for grounding.
3 - 15
3. SIGNALS AND WIRING
POINT
A voltage, output signal, etc. of analog monitor output may be irregular at power-
on.
2) Switch on the control circuit power supply (L11 and L21) simultaneously with the main circuit
power supply or before switching on the main circuit power supply. If the control circuit power
supply is turned on with the main circuit power supply off, and then the servo-on command is
transmitted, [AL. E9 Main circuit off warning] will occur. Turning on the main circuit power supply
stops the warning and starts the normal operation.
3) The servo amplifier receives the servo-on command within 3 s to 4 s after the main circuit power
supply is switched on.
(Refer to (2) of this section.)
Note. This time period is longer when detecting magnetic pole for the linear servo motor.
3 - 16
3. SIGNALS AND WIRING
POINT
For the wire sizes used for wiring, refer to section 9.6.
MR-J4-500B4(-RJ) or more do not have these connectors.
Use the servo amplifier power supply connector for wiring CNP1, CNP2, and CNP3.
(a) Connector
Servo amplifier
(Note)
CNP1
CNP2
CNP3
3 - 17
3. SIGNALS AND WIRING
Stripped length
You can also use a ferrule to connect with the connectors. The following shows references to
select ferrules according to wire sizes.
Ferrule model (Phoenix Contact) Crimping tool
Servo amplifier Wire size
For 1 cable For 2 cables (Phoenix Contact)
MR-J4-60B4(-RJ) to AWG 16 AI1.5-10BK AI-TWIN2×1.5-10BK
CRIMPFOX-ZA3
MR-J4-350B4(-RJ) AWG 14 AI2.5-10BU
2) Inserting wire
Insert the open tool as follows and push down it to open the spring. While the open tool is pushed
down, insert the stripped wire into the wire insertion hole. Check the insertion depth so that the
cable insulator does not get caught by the spring.
Release the open tool to fix the wire. Pull the wire lightly to confirm that the wire is surely
connected.
The following shows a connection example of the CNP3 connector for 3.5 kW.
3 - 18
4. STARTUP (WIRING CHECK)
Do not operate the switches with wet hands. Otherwise, it may cause an electric
WARNING shock.
Before starting operation, check the parameters. Improper settings may cause
some machines to operate unexpectedly.
The servo amplifier heat sink, regenerative resistor, servo motor, etc. may be hot
CAUTION while power is on or for some time after power-off. Take safety measures, e.g.
provide covers, to avoid accidentally touching the parts (cables, etc.) by hand.
During operation, never touch the rotor of the servo motor. Otherwise, it may
cause injury.
The items in the following table are the same as those for MR-J4-_A(-RJ) or MR-J4-_B(-RJ) servo amplifier.
For details of the items, refer to each chapter/section of the detailed explanation field.
Model Item Detailed explanation
MR-J4-_A4(-RJ) Switching power on for the first time MR-J4-_A(-RJ) Servo Amplifier Instruction
(expect wiring check) Manual section 4.1
Startup in position control mode MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 4.2
Startup in speed control mode MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 4.3
Startup in torque control mode MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 4.4
Display and operation sections MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 4.5
MR-J4-_B4(-RJ) Switching power on for the first time MR-J4-_B(-RJ) Servo Amplifier Instruction
(expect wiring check) Manual section 4.1
Startup MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 4.2
Switch setting and display of the servo MR-J4-_B(-RJ) Servo Amplifier Instruction
amplifier Manual section 4.3
Test operation MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 4.4
Test operation mode MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 4.5
4- 1
4. STARTUP (WIRING CHECK)
Before switching on the main circuit and control circuit power supplies, check the following items.
(b) The power supplied to the servo amplifier should not be connected to the power outputs (U, V, and
W). Doing so will fail the connected servo amplifier and servo motor.
(c) The grounding terminal of the servo motor is connected to the PE terminal of the servo amplifier.
Servo amplifier Servo motor
(d) The CN2 connector of the servo amplifier should be connected to the encoder of the servo motor
securely using the encoder cable.
P3
P4
4- 2
4. STARTUP (WIRING CHECK)
(b) When you use a regenerative option for 5 kW or more servo amplifiers
The lead wire of built-in regenerative resistor connected to P+ terminal and C terminal should not
be connected.
The regenerative option should be connected to P+ terminal and C terminal.
A twisted cable should be used when wiring is over 5 m and under 10 m. (Refer to section 9.2.4.)
(c) When you use a brake unit and power regenerative converter for 5 kW or more servo amplifiers
The lead wire of built-in regenerative resistor connected to P+ terminal and C terminal should not
be connected.
Brake unit, power regenerative converter should be connected to P+ terminal and N- terminal.
(Refer to section 9.3 to 9.4.)
(d) When you use a power regenerative common converter for 11 kW or more servo amplifiers
Power regenerative common converter should be connected to P4 terminal and N- terminal.
(Refer to section 9.5.)
(e) The power factor improving DC reactor should be connected between P3 and P4. (Refer to section
9.8.)
Servo amplifier
Power factor improving
DC reactor
P3
(Note)
P4
(2) A voltage exceeding 24 V DC is not applied to the pins of the CN1/CN3 connector.
SD
4- 3
4. STARTUP (WIRING CHECK)
MEMO
4- 4
5. PARAMETERS
5. PARAMETERS
5.1 MR-J4-_A4(-RJ)
POINT
To enable a parameter whose symbol is preceded by *, cycle the power after
setting it.
The symbols in the control mode column mean as follows.
P: Position control mode
S: Speed control mode
T: Torque control mode
Read the MR-J4-_A(-RJ) Servo Amplifier Instruction Manual for the parameters with "MR-J4-_A" in the
detailed explanation field.
T
Standard
Full.
Lin.
S
value explanation
5- 1
5. PARAMETERS
Operation Control
mode mode
Initial Detailed
No. Symbol Name Unit
T
Standard
Full.
Lin.
S
value explanation
T
Standard
Lin.
S
Full.
value explanation
PB01 FILT Adaptive tuning mode (adaptive filter II) 0000h MR-J4-_A
PB02 VRFT Vibration suppression control tuning mode (advanced vibration 0000h
suppression control II)
PB03 PST Position command acceleration/deceleration time constant (position 0 [ms]
smoothing)
PB04 FFC Feed forward gain 0 [%]
PB05 For manufacturer setting 500
PB06 GD2 Load to motor inertia ratio/load to motor mass ratio 7.00 [Multiplier] MR-J4-_A
PB07 PG1 Model loop gain 15.0 [rad/s]
PB08 PG2 Position loop gain 37.0 [rad/s]
PB09 VG2 Speed loop gain 823 [rad/s]
PB10 VIC Speed integral compensation 33.7 [ms]
PB11 VDC Speed differential compensation 980
PB12 OVA Overshoot amount compensation 0 [%]
PB13 NH1 Machine resonance suppression filter 1 4500 [Hz]
PB14 NHQ1 Notch shape selection 1 0000h
PB15 NH2 Machine resonance suppression filter 2 4500 [Hz]
PB16 NHQ2 Notch shape selection 2 0000h
PB17 NHF Shaft resonance suppression filter 0000h
PB18 LPF Low-pass filter setting 3141 [rad/s]
PB19 VRF11 Vibration suppression control 1 - Vibration frequency 100.0 [Hz]
PB20 VRF12 Vibration suppression control 1 - Resonance frequency 100.0 [Hz]
PB21 VRF13 Vibration suppression control 1 - Vibration frequency damping 0.00
PB22 VRF14 Vibration suppression control 1 - Resonance frequency damping 0.00
PB23 VFBF Low-pass filter selection 0000h
PB24 *MVS Slight vibration suppression control 0000h
PB25 *BOP1 Function selection B-1 0000h
PB26 *CDP Gain switching function 0000h
PB27 CDL Gain switching condition 10 [kpps]/
[pulse]/
[r/min]
PB28 CDT Gain switching time constant 1 [ms]
PB29 GD2B Load to motor inertia ratio/load to motor mass ratio after gain 7.00 [Multiplier]
switching
PB30 PG2B Position loop gain after gain switching 0.0 [rad/s]
PB31 VG2B Speed loop gain after gain switching 0 [rad/s]
PB32 VICB Speed integral compensation after gain switching 0.0 [ms]
PB33 VRF1B Vibration suppression control 1 - Vibration frequency after gain 0.0 [Hz]
switching
5- 2
5. PARAMETERS
Operation Control
mode mode
Initial Detailed
No. Symbol Name Unit
T
Standard
Full.
Lin.
S
value explanation
PB34 VRF2B Vibration suppression control 1 - Resonance frequency after gain 0.0 [Hz] MR-J4-_A
switching
PB35 VRF3B Vibration suppression control 1 - Vibration frequency damping after 0.00
gain switching
PB36 VRF4B Vibration suppression control 1 - Resonance frequency damping 0.00
after gain switching
PB37 For manufacturer setting 1600
PB38 0.00
PB39 0.00
PB40 0.00
PB41 0000h
PB42 0000h
PB43 0000h
PB44 0.00
PB45 CNHF Command notch filter 0000h MR-J4-_A
PB46 NH3 Machine resonance suppression filter 3 4500 [Hz]
PB47 NHQ3 Notch shape selection 3 0000h
PB48 NH4 Machine resonance suppression filter 4 4500 [Hz]
PB49 NHQ4 Notch shape selection 4 0000h
PB50 NH5 Machine resonance suppression filter 5 4500 [Hz]
PB51 NHQ5 Notch shape selection 5 0000h
PB52 VRF21 Vibration suppression control 2 - Vibration frequency 100.0 [Hz]
PB53 VRF22 Vibration suppression control 2 - Resonance frequency 100.0 [Hz]
PB54 VRF23 Vibration suppression control 2 - Vibration frequency damping 0.00
PB55 VRF24 Vibration suppression control 2 - Resonance frequency damping 0.00
PB56 VRF21B Vibration suppression control 2 - Vibration frequency after gain 0.0 [Hz]
switching
PB57 VRF22B Vibration suppression control 2 - Resonance frequency after gain 0.0 [Hz]
switching
PB58 VRF23B Vibration suppression control 2 - Vibration frequency damping after 0.00
gain switching
PB59 VRF24B Vibration suppression control 2 - Resonance frequency damping 0.00
after gain switching
PB60 PG1B Model loop gain after gain switching 0.0 [rad/s]
PB61 For manufacturer setting 0.0
PB62 0000h
PB63 0000h
PB64 0000h
Full.
Lin.
value explanation
5- 3
5. PARAMETERS
Operation Control
mode mode
Initial Detailed
No. Symbol Name Unit
T
Standard
Full.
Lin.
S
value explanation
5- 4
5. PARAMETERS
Operation Control
mode mode
Initial Detailed
No. Symbol Name Unit
T
Standard
Full.
Lin.
S
value explanation
Full.
Lin.
S
value explanation
5- 5
5. PARAMETERS
Operation Control
mode mode
Initial Detailed
No. Symbol Name Unit
T
Standard
Full.
Lin.
S
value explanation
T
Standard
Full.
Lin.
value S explanation
5- 6
5. PARAMETERS
Operation Control
mode mode
Initial Detailed
No. Symbol Name Unit
T
Standard
Full.
Lin.
S
value explanation
5- 7
5. PARAMETERS
T
Standard
Lin.
S
Full.
value explanation
5- 8
5. PARAMETERS
T
Standard
Lin.
S
Full.
value explanation
5- 9
5. PARAMETERS
POINT
"x" in the "Setting digit" columns means which digit to set a value.
5 - 10
5. PARAMETERS
Initial Control
No./symbol/ Setting
Function value mode
name digit
[unit] P S T
PA18 When you use a linear servo motor, select its model from [Pr. PA17] and [Pr. PA18]. 0000h
*MTY Set this and [Pr. PA17] at a time.
Servo motor Refer to the table of [Pr. PA17] for settings.
type setting
5 - 11
5. PARAMETERS
Standard
Lin.
Full.
00 (Linear) servo motor speed
(±8 V/max. speed)
01 Torque or thrust
(±8 V/max. torque or max. thrust) (Note 3)
02 (Linear) servo motor speed
(+8V/max. speed)
03 Torque or thrust
(+8 V/max. torque or max. thrust) (Note 3)
04 Current command (±8 V/max. current command)
05 Command pulse frequency (±10 V/±4 Mpps)
06 Servo motor-side droop pulses (±10 V/100 pulses) (Note
2)
07 Servo motor-side droop pulses (±10 V/1000 pulses) (Note
2)
08 Servo motor-side droop pulses (±10 V/10000 pulses)
(Note 2)
09 Servo motor-side droop pulses (±10 V/100000 pulses)
(Note 2)
0A Feedback position (±10 V/1 Mpulses) (Note 2)
0B Feedback position (±10 V/10 Mpulses) (Note 2)
0C Feedback position (±10 V/100 Mpulses) (Note 2)
0D Bus voltage (+8 V/800 V)
0E Speed command 2 (±8 V/max. speed)
10 Load-side droop pulses (±10 V/100 pulses) (Note 2)
11 Load-side droop pulses (±10 V/1000 pulses) (Note 2)
12 Load-side droop pulses (±10 V/10000 pulses) (Note 2)
13 Load-side droop pulses (±10 V/100000 pulses) (Note 2)
14 Load-side droop pulses (±10 V/1 Mpulses) (Note 2)
15 Servo motor-side/load-side position deviation
(±10 V/100000 pulses)
16 Servo motor-side/load-side speed deviation
(±8 V/max. speed)
17 Encoder inside temperature (±10 V/±128 ˚C)
Note 1. Items with ○ are available for each operation mode.
Standard: Standard (semi closed loop system) use of the rotary servo motor
Full.: Fully closed loop system use of the rotary servo motor
Lin.: Linear servo motor use
2. Encoder pulse unit
3. 8 V is outputted at the maximum torque. However, when [Pr. PA11] and [Pr. PA12]
are set to limit torque, 8 V is outputted at the torque highly limited.
5 - 12
5. PARAMETERS
Initial Control
No./symbol/ Setting
Function value mode
name digit
[unit] P S T
PC15 __xx Analog monitor 2 output selection 01h
MOD2 Select a signal to output to MO2 (Analog monitor 2). Refer to appendix 3.1 (3) for
Analog detection point of output selection.
monitor 2 Refer to [Pr. PC14] for settings.
output _x__ For manufacturer setting 0h
x___ 0h
5 - 13
5. PARAMETERS
5.2 MR-J4-_B4(-RJ)
POINT
When you connect the amplifier to a servo system controller, servo parameter
values of the servo system controller will be written to each parameter.
Setting may not be made to some parameters and their ranges depending on
the servo system controller model, servo amplifier software version, and MR
Configurator2 software version. For details, refer to the servo system controller
user's manual.
The parameter whose symbol is preceded by * is enabled with the following
conditions:
*: After setting the parameter, cycle the power or reset the controller.
**: After setting the parameter, cycle the power.
Abbreviations of operation modes indicate the followings.
Standard: Standard (semi closed loop system) use of the rotary servo motor
Full.: Fully closed loop system use of the rotary servo motor
Lin.: Linear servo motor use
Read the MR-J4-_B(-RJ) Servo Amplifier Instruction Manual for the parameters with "MR-J4-_B" in the
detailed explanation field.
Lin.
Full.
value explanation
5 - 14
5. PARAMETERS
Operation
mode
Initial Detailed
Standard
No. Symbol Name Unit
Lin.
Full.
value explanation
Standard
No. Symbol Name Unit
Lin.
Full.
value explanation
PB01 FILT Adaptive tuning mode (adaptive filter II) 0000h MR-J4-_B
PB02 VRFT Vibration suppression control tuning mode (advanced vibration 0000h
suppression control II)
PB03 TFBGN Torque feedback loop gain 18000 [rad/s]
PB04 FFC Feed forward gain 0 [%]
PB05 For manufacturer setting 500
PB06 GD2 Load to motor inertia ratio/load to motor mass ratio 7.00 [Multiplier] MR-J4-_B
PB07 PG1 Model loop gain 15.0 [rad/s]
PB08 PG2 Position loop gain 37.0 [rad/s]
PB09 VG2 Speed loop gain 823 [rad/s]
PB10 VIC Speed integral compensation 33.7 [ms]
PB11 VDC Speed differential compensation 980
PB12 OVA Overshoot amount compensation 0 [%]
PB13 NH1 Machine resonance suppression filter 1 4500 [Hz]
PB14 NHQ1 Notch shape selection 1 0000h
PB15 NH2 Machine resonance suppression filter 2 4500 [Hz]
PB16 NHQ2 Notch shape selection 2 0000h
PB17 NHF Shaft resonance suppression filter 0000h
PB18 LPF Low-pass filter setting 3141 [rad/s]
PB19 VRF11 Vibration suppression control 1 - Vibration frequency 100.0 [Hz]
PB20 VRF12 Vibration suppression control 1 - Resonance frequency 100.0 [Hz]
PB21 VRF13 Vibration suppression control 1 - Vibration frequency damping 0.00
PB22 VRF14 Vibration suppression control 1 - Resonance frequency damping 0.00
PB23 VFBF Low-pass filter selection 0000h
PB24 *MVS Slight vibration suppression control 0000h
PB25 For manufacturer setting 0000h
PB26 *CDP Gain switching function 0000h MR-J4-_B
PB27 CDL Gain switching condition 10 [kpps]/
[pulse]/
[r/min]
PB28 CDT Gain switching time constant 1 [ms]
PB29 GD2B Load to motor inertia ratio/load to motor mass ratio after gain 7.00 [Multiplier]
switching
PB30 PG2B Position loop gain after gain switching 0.0 [rad/s]
5 - 15
5. PARAMETERS
Operation
mode
Initial Detailed
Standard
No. Symbol Name Unit
Lin.
Full.
value explanation
PB31 VG2B Speed loop gain after gain switching 0 [rad/s] MR-J4-_B
PB32 VICB Speed integral compensation after gain switching 0.0 [ms]
PB33 VRF11B Vibration suppression control 1 - Vibration frequency after gain 0.0 [Hz]
switching
PB34 VRF12B Vibration suppression control 1 - Resonance frequency after 0.0 [Hz]
gain switching
PB35 VRF13B Vibration suppression control 1 - Vibration frequency damping 0.00
after gain switching
PB36 VRF14B Vibration suppression control 1 - Resonance frequency damping 0.00
after gain switching
PB37 For manufacturer setting 1600
PB38 0.00
PB39 0.00
PB40 0.00
PB41 0
PB42 0
PB43 0000h
PB44 0.00
PB45 CNHF Command notch filter 0000h Section
5.2.2
PB46 NH3 Machine resonance suppression filter 3 4500 [Hz] MR-J4-_B
PB47 NHQ3 Notch shape selection 3 0000h
PB48 NH4 Machine resonance suppression filter 4 4500 [Hz]
PB49 NHQ4 Notch shape selection 4 0000h
PB50 NH5 Machine resonance suppression filter 5 4500 [Hz]
PB51 NHQ5 Notch shape selection 5 0000h
PB52 VRF21 Vibration suppression control 2 - Vibration frequency 100.0 [Hz]
PB53 VRF22 Vibration suppression control 2 - Resonance frequency 100.0 [Hz]
PB54 VRF23 Vibration suppression control 2 - Vibration frequency damping 0.00
PB55 VRF24 Vibration suppression control 2 - Resonance frequency damping 0.00
PB56 VRF21B Vibration suppression control 2 - Vibration frequency after gain 0.0 [Hz]
switching
PB57 VRF22B Vibration suppression control 2 - Resonance frequency after 0.0 [Hz]
gain switching
PB58 VRF23B Vibration suppression control 2 - Vibration frequency damping 0.00
after gain switching
PB59 VRF24B Vibration suppression control 2 - Resonance frequency damping 0.00
after gain switching
PB60 PG1B Model loop gain after gain switching 0.0 [rad/s]
PB61 For manufacturer setting 0.0
PB62 0000h
PB63 0000h
PB64 0000h
5 - 16
5. PARAMETERS
Standard
No. Symbol Name Unit
Full.
Lin.
value explanation
5 - 17
5. PARAMETERS
Operation
mode
Initial Detailed
Standard
No. Symbol Name Unit
Lin.
Full.
value explanation
Standard
No. Symbol Name Unit
Lin.
Full.
value explanation
5 - 18
5. PARAMETERS
Operation
mode
Initial Detailed
Standard
No. Symbol Name Unit
Lin.
Full.
value explanation
Lin.
Full.
value explanation
5 - 19
5. PARAMETERS
Operation
mode
Initial Detailed
Standard
No. Symbol Name Unit
Lin.
Full.
value explanation
5 - 20
5. PARAMETERS
Standard
No. Symbol Name Unit
Full.
Lin.
value explanation
5 - 21
5. PARAMETERS
Standard
No. Symbol Name Unit
Full.
Lin.
value explanation
5 - 22
5. PARAMETERS
POINT
"x" in the "Setting digit" columns means which digit to set a value.
5 - 23
5. PARAMETERS
Initial
Setting
No. Symbol Name and function value
range
[unit]
PA02 **REG Regenerative option Refer to Name
Used to select the regenerative option. and function
Incorrect setting may cause the regenerative option to burn. column.
If a selected regenerative option is not for use with the servo amplifier, [AL. 37 Parameter
error] occurs.
Setting Initial
Explanation
digit value
__xx Regenerative option selection 00h
00: Regenerative option is not used.
For servo amplifier of 0.6 kW to 7 kW, built-in regenerative
resistor is used.
Supplied regenerative resistors or regenerative option is used
with the servo amplifier of 11 kW to 22 kW.
01: FR-RC-H/FR-CV-H/FR-BU2-H
When you use FR-RC-H, FR-CV-H, or FR-BU2-H, select "Mode
2 (_ _ _ 1)" of "Undervoltage alarm detection mode selection" in
[Pr. PC20].
80: MR-RB1H-4
81: MR-RB3M-4 (Cooling fan is required.)
82: MR-RB3G-4 (Cooling fan is required.)
83: MR-RB5G-4 (Cooling fan is required.)
84: MR-RB34-4 (Cooling fan is required.)
85: MR-RB54-4 (Cooling fan is required.)
91: MR-RB3U-4 (Cooling fan is required.)
92: MR-RB5U-4 (Cooling fan is required.)
FA: When the supplied regenerative resistors or the regenerative
option is cooled by the cooling fan to increase the ability with
the servo amplifier of 11 kW to 22 kW.
_x__ For manufacturer setting 0h
x___ 0h
5 - 24
5. PARAMETERS
Setting Initial
Explanation
digit value
__xx Analog monitor 1 output selection 00h
Refer to table 5.2 for settings.
_x__ For manufacturer setting 0h
x___ 0h
Standard
Full.
Lin.
00 (Linear) servo motor speed
(±8 V/max. speed)
01 Torque or thrust
(±8 V/max. torque or max. thrust)
02 (Linear) servo motor speed
(+8V/max. speed)
03 Torque or thrust
(+8 V/max. torque or max. thrust)
04 Current command (±8 V/max. current command)
05 Speed command (±8 V/max. speed)
06 Servo motor-side droop pulses (±10 V/100 pulses) (Note 2)
07 Servo motor-side droop pulses (±10 V/1000 pulses) (Note 2)
08 Servo motor-side droop pulses (±10 V/10000 pulses) (Note 2)
09 Servo motor-side droop pulses (±10 V/100000 pulses) (Note 2)
0A Feedback position (±10 V/1 Mpulses) (Note 2)
0B Feedback position (±10 V/10 Mpulses) (Note 2)
0C Feedback position (±10 V/100 Mpulses) (Note 2)
0D Bus voltage (+8 V/800 V)
0E Speed command 2 (±8 V/max. speed)
10 Load-side droop pulses (±10 V/100 pulses) (Note 2)
11 Load-side droop pulses (±10 V/1000 pulses) (Note 2)
12 Load-side droop pulses (±10 V/10000 pulses) (Note 2)
13 Load-side droop pulses (±10 V/100000 pulses) (Note 2)
14 Load-side droop pulses (±10 V/1 Mpulses) (Note 2)
15 Servo motor-side/load-side position deviation
(±10 V/100000 pulses)
16 Servo motor-side/load-side speed deviation
(±8 V/max. speed)
17 Encoder inside temperature (±10 V/±128 ˚C)
5 - 25
5. PARAMETERS
Initial
Setting
No. Symbol Name and function value
range
[unit]
PC10 MOD2 Analog monitor 2 output Refer to Name
Select a signal to output to MO2 (Analog monitor 2). Refer to appendix 3.2 (3) for detection and function
point of output selection. column.
Setting Initial
Explanation
digit value
__xx Analog monitor 2 output selection 01h
Refer to [Pr. PC09] for settings.
_x__ For manufacturer setting 0h
x___ 0h
5 - 26
6. TROUBLESHOOTING
6. TROUBLESHOOTING
POINT
Refer to "MELSERVO-J4 Servo Amplifier Instruction Manual (Troubleshooting)"
for details of alarms and warnings.
As soon as an alarm occurs, turn SON (Servo-on) off and interrupt the power.
6.1 MR-J4-_A4(-RJ)
When an error occurs during operation, the corresponding alarm or warning is displayed. When the alarm or
the warning occurs, refer to "MELSERVO-J4 Servo Amplifier Instruction Manual (Troubleshooting)" to
remove the failure. When an alarm occurs, ALM will turn off.
To output alarm codes, set [Pr. PD34] to "_ _ _ 1". Alarm codes are outputted by on/off of bit 0 to bit 2.
Warnings ([AL. 91] to [AL. F3]) do not have alarm codes. The alarm codes in the following table will be
outputted when they occur. The alarm codes will not be outputted in normal condition.
After its cause has been removed, the alarm can be deactivated in any of the methods marked ○ in the
alarm deactivation column. Warnings are automatically canceled after the cause of occurrence is removed.
For the alarms and warnings in which "SD" is written in the stop method column, the axis stops with the
dynamic brake after forced stop deceleration. For the alarms and warnings in which "DB" or "EDB" is written
in the stop method column, the servo motor stops with the dynamic brake without forced stop deceleration.
Operation
Alarm code Alarm deactivation
mode
Stop
off → on
Alarm reset
(RES)
Press the
"SET" button
Power
Standard
Full.
Lin.
on the current
alarm screen.
Detail method
No. CN1 CN1 CN1 Name Detail name
display (Note 2,
22 23 24 3)
(Bit 2) (Bit 1) (Bit 0)
10.1 EDB
power
10 0 1 0 Undervoltage
Voltage drop in the main circuit
10.2 SD
power
12.1 RAM error 1 DB
Memory error 1 12.2 RAM error 2 DB
12 0 0 0
(RAM) 12.4 RAM error 4 DB
12.5 RAM error 5 DB
13.1 Clock error 1 DB
13 0 0 0 Clock error
13.2 Clock error 2 DB
14.1 Control process error 1 DB
14.2 Control process error 2 DB
14.3 Control process error 3 DB
14.4 Control process error 4 DB
Control process 14.5 Control process error 5 DB
14 0 0 0
error 14.6 Control process error 6 DB
14.7 Control process error 7 DB
14.8 Control process error 8 DB
14.9 Control process error 9 DB
14.A Control process error 10 DB
Memory error 2 15.1 EEP-ROM error at power on DB
15 0 0 0
(EEP-ROM) 15.2 EEP-ROM error during operation DB
6- 1
6. TROUBLESHOOTING
Operation
Alarm code Alarm deactivation
mode
Stop
off → on
Alarm reset
(RES)
Press the
"SET" button
Power
Standard
Full.
Lin.
on the current
alarm screen.
Detail method
No. CN1 CN1 CN1 Name Detail name
display (Note 2,
22 23 24 3)
(Bit 2) (Bit 1) (Bit 0)
DB
less Receive data error 1
Encoder initial communication -
16.2 DB
Receive data error 2
Encoder initial communication -
16.3 DB
Receive data error 3
Encoder initial communication -
16.5 DB
Transmission data error 1
Encoder initial communication -
16.6 DB
Transmission data error 2
Encoder initial communication -
Encoder initial 16.7 DB
Transmission data error 3
16 1 1 0 communication error
1 Encoder initial communication -
16.A DB
Process error 1
Encoder initial communication -
16.B DB
Process error 2
Encoder initial communication -
16.C DB
Process error 3
Encoder initial communication -
16.D DB
Process error 4
Encoder initial communication -
16.E DB
Process error 5
Encoder initial communication -
16.F DB
Process error 6
17.1 Board error 1 DB
17 0 0 0 Board error 17.3 Board error 2 DB
17.4 Board error 3 DB
Memory error 3 19.1 FLASH-ROM error 1 DB
19 0 0 0
(FLASH-ROM) 19.2 FLASH-ROM error 2 DB
1A.1 Servo motor combination error DB
Servo motor
1A 1 1 0 Servo motor control mode
combination error 1A.2 DB
combination error
Encoder initial 1E.1 Encoder malfunction DB
1E 1 1 0 communication error
2 1E.2 Load-side encoder malfunction DB
Encoder initial 1F.1 Incompatible encoder DB
1F 1 1 0 communication error
3 1F.2 Incompatible load-side encoder DB
Encoder normal communication -
20.1 EDB
Receive data error 1
Encoder normal communication -
20.2 EDB
Receive data error 2
Encoder normal communication -
20.3 EDB
Receive data error 3
Encoder normal communication -
Encoder normal 20.5 EDB
Transmission data error 1
20 1 1 0 communication error
1 Encoder normal communication -
20.6 EDB
Transmission data error 2
Encoder normal communication -
20.7 EDB
Transmission data error 3
Encoder normal communication -
20.9 EDB
Receive data error 4
Encoder normal communication -
20.A EDB
Receive data error 5
21.1 Encoder data error 1 EDB
21.2 Encoder data update error EDB
Encoder normal 21.3 Encoder data waveform error EDB
21 1 1 0 communication error 21.4 Encoder non-signal error EDB
2 21.5 Encoder hardware error 1 EDB
21.6 Encoder hardware error 2 EDB
21.9 Encoder data error 2 EDB
6- 2
6. TROUBLESHOOTING
Operation
Alarm code Alarm deactivation
mode
Stop
off → on
Alarm reset
(RES)
Press the
"SET" button
Power
Standard
Full.
Lin.
on the current
alarm screen.
Detail method
No. CN1 CN1 CN1 Name Detail name
display (Note 2,
22 23 24 3)
(Bit 2) (Bit 1) (Bit 0)
24.1 DB
detection circuit
24 1 0 0 Main circuit error
Ground fault detected by software
24.2 DB
detection function
Absolute position Servo motor encoder - Absolute
25 1 1 0 25.1 DB
erased position erased
Initial magnetic pole detection -
27.1 DB
Abnormal termination
Initial magnetic pole detection -
27.2 DB
Time out error
Initial magnetic pole detection -
27.3 DB
Limit switch error
Initial magnetic pole Initial magnetic pole detection -
27 1 1 0 27.4 DB
detection error Estimated error
Initial magnetic pole detection -
27.5 DB
Position deviation error
Initial magnetic pole detection -
27.6 DB
Speed deviation error
Initial magnetic pole detection -
27.7 DB
Current error
Linear encoder error Linear encoder - Environment error
28 1 1 0 28.1 EDB
2 2
2A.1 Linear encoder error 1-1 EDB
2A.2 Linear encoder error 1-2 EDB
2A.3 Linear encoder error 1-3 EDB
Linear encoder error 2A.4 Linear encoder error 1-4 EDB
2A 1 1 0
1 2A.5 Linear encoder error 1-5 EDB
2A.6 Linear encoder error 1-6 EDB
2A.7 Linear encoder error 1-7 EDB
2A.8 Linear encoder error 1-8 EDB
Encoder counter 2B.1 Encoder counter error 1 EDB
2B 1 1 0
error 2B.2 Encoder counter error 2 EDB
6- 3
6. TROUBLESHOOTING
Operation
Alarm code Alarm deactivation
mode
Stop
off → on
Alarm reset
(RES)
Press the
"SET" button
Power
Standard
Full.
Lin.
on the current
alarm screen.
Detail method
No. CN1 CN1 CN1 Name Detail name
display (Note 2,
22 23 24 3)
(Bit 2) (Bit 1) (Bit 0)
42.1 EDB
deviation (Note 4) (Note 4)
Servo control error by speed
Servo control error 42.2 EDB
deviation (Note 4) (Note 4)
Servo control error by torque/thrust
42.3 EDB
deviation (Note 4) (Note 4)
42 1 1 0 Fully closed loop control error by
42.8 EDB
position deviation (Note 4) (Note 4)
Fully closed loop control error by
Fully closed loop 42.9 EDB
speed deviation (Note 4) (Note 4)
control error
Fully closed loop control error by
42.A position deviation during command EDB
(Note 4) (Note 4)
stop
Main circuit device
45 0 1 1 45.1 Main circuit device overheat error SD
overheat (Note 1) (Note 1) (Note 1) (Note 1)
Abnormal temperature of servo
46.1 SD
motor 1 (Note 1) (Note 1) (Note 1)
Abnormal temperature of servo
46.2 SD
motor 2 (Note 1) (Note 1) (Note 1)
Servo motor
46 0 1 1 46.3 Thermistor disconnected SD
overheat (Note 1) (Note 1) (Note 1) (Note 1)
Abnormal temperature of servo
46.5 DB
motor 3 (Note 1) (Note 1) (Note 1)
Abnormal temperature of servo
46.6 DB
motor 4 (Note 1) (Note 1) (Note 1)
47.1 Cooling fan stop error SD
47 0 1 1 Cooling fan error
47.2 Cooling fan speed reduction error SD
Thermal overload error 1 during
50.1 SD
operation (Note 1) (Note 1) (Note 1)
Thermal overload error 2 during
50.2 SD
operation (Note 1) (Note 1) (Note 1)
Thermal overload error 4 during
50.3 SD
operation (Note 1) (Note 1) (Note 1)
50 0 1 1 Overload 1 (Note 1)
Thermal overload error 1 during a
50.4 SD
stop (Note 1) (Note 1) (Note 1)
Thermal overload error 2 during a
50.5 SD
stop (Note 1) (Note 1) (Note 1)
Thermal overload error 4 during a
50.6 SD
stop (Note 1) (Note 1) (Note 1)
Thermal overload error 3 during
51.1 DB
operation (Note 1) (Note 1) (Note 1)
51 0 1 1 Overload 2 (Note 1)
Thermal overload error 3 during a
51.2 DB
stop (Note 1) (Note 1) (Note 1)
52.1 Excess droop pulse 1 SD
52.3 Excess droop pulse 2 SD
52 1 0 1 Error excessive
52.4 Error excessive during 0 torque limit SD
52.5 Excess droop pulse 3 EDB
54 0 1 1 Oscillation detection 54.1 Oscillation detection error EDB
56.2 Over speed during forced stop EDB
56 1 1 0 Forced stop error Estimated distance over during
56.3 EDB
forced stop
63.1 STO1 off DB
63 1 1 0 STO timing error
63.2 STO2 off DB
6- 4
6. TROUBLESHOOTING
Operation
Alarm code Alarm deactivation
mode
Stop
off → on
Alarm reset
(RES)
Press the
"SET" button
Power
Standard
Full.
Lin.
on the current
alarm screen.
Detail method
No. CN1 CN1 CN1 Name Detail name
display (Note 2,
22 23 24 3)
(Bit 2) (Bit 1) (Bit 0)
6- 5
6. TROUBLESHOOTING
Operation
Alarm code Alarm deactivation
mode
Stop
"SET" button
off → on
Alarm reset
(RES)
Press the
Power
Standard
Full.
Lin.
on the current
alarm screen.
Detail method
No. CN1 CN1 CN1 Name Detail name
display (Note 2,
22 23 24 3)
(Bit 2) (Bit 1) (Bit 0)
Note 1. Leave for about 30 minutes of cooling time after removing the cause of occurrence.
2. Stop method indicates as follows:
DB: Stops with dynamic brake. (Coasts for the servo amplifier without dynamic brake.)
EDB: Stops with electronic dynamic brake for 600 W or less servo amplifiers
Stops with dynamic brake for 700 W or more servo amplifiers
SD: Forced stop deceleration
3. This is applicable when [Pr. PA04] is set to the initial value. The stop system of SD can be changed to DB using [Pr. PA04].
4. Reset enable or disable can be selected using [Pr. PE03].
6- 6
6. TROUBLESHOOTING
Operation
mode
Stop
Standard
Full.
Lin.
Detail method
No. Name Detail name
display (Note 2,
3)
Servo amplifier
Warning
6- 7
6. TROUBLESHOOTING
Operation
mode
Stop
Standard
Full.
Lin.
Detail method
No. Name Detail name
display (Note 2,
3)
Note 1. Leave for about 30 minutes of cooling time after removing the cause of occurrence.
2. Stop method indicates as follows:
DB: Stops with dynamic brake. (Coasts for the servo amplifier without dynamic brake.)
SD: Forced stop deceleration
3. This is applicable when [Pr. PA04] is set to the initial value. The stop system of SD can be changed to DB using [Pr. PA04].
4. Quick stop or slow stop can be selected using [Pr. PD30].
6- 8
6. TROUBLESHOOTING
6.2 MR-J4-_B4(-RJ)
When an error occurs during operation, the corresponding alarm or warning is displayed. When the alarm or
the warning occurs, refer to "MELSERVO-J4 Servo Amplifier Instruction Manual (Troubleshooting)" to
remove the failure. When an alarm occurs, ALM will turn off.
After its cause has been removed, the alarm can be deactivated in any of the methods marked ○ in the
alarm deactivation column in the following table. Warnings are automatically canceled after the cause of
occurrence is removed.
For the alarms and warnings in which "SD" is written in the stop method column, the axis stops with the
dynamic brake after forced stop deceleration. For the alarms and warnings in which "DB" or "EDB" is written
in the stop method column, the servo motor stops with the dynamic brake without forced stop deceleration.
Operation
Alarm reset
Stop mode
Detail method
Error reset
CPU reset
off → on
Power
Standard
Lin.
Full.
No. Name Detail name
display (Note 4,
5)
10 Undervoltage
10.2 Voltage drop in the main circuit power SD
12.1 RAM error 1 DB
12.2 RAM error 2 DB
12 Memory error 1 (RAM) 12.3 RAM error 3 DB
12.4 RAM error 4 DB
12.5 RAM error 5 DB
13.1 Clock error 1 DB
13 Clock error
13.2 Clock error 2 DB
14.1 Control process error 1 DB
14.2 Control process error 2 DB
14.3 Control process error 3 DB
14.4 Control process error 4 DB
14.5 Control process error 5 DB
14 Control process error
14.6 Control process error 6 DB
14.7 Control process error 7 DB
14.8 Control process error 8 DB
14.9 Control process error 9 DB
14.A Control process error 10 DB
Memory error 2 15.1 EEP-ROM error at power on DB
15
(EEP-ROM) 15.2 EEP-ROM error during operation DB
16.1 Encoder initial communication - Receive data error 1 DB
16.2 Encoder initial communication - Receive data error 2 DB
16.3 Encoder initial communication - Receive data error 3 DB
Encoder initial communication - Transmission data
16.5 DB
error 1
Encoder initial communication - Transmission data
16.6 DB
error 2
Encoder initial
16 Encoder initial communication - Transmission data
communication error 1 16.7 DB
error 3
16.A Encoder initial communication - Process error 1 DB
16.B Encoder initial communication - Process error 2 DB
16.C Encoder initial communication - Process error 3 DB
16.D Encoder initial communication - Process error 4 DB
16.E Encoder initial communication - Process error 5 DB
16.F Encoder initial communication - Process error 6 DB
6- 9
6. TROUBLESHOOTING
Operation
Alarm reset
Stop mode
Detail method
Error reset
CPU reset
off → on
Power
Standard
Lin.
Full.
No. Name Detail name
display (Note 4,
5)
6 - 10
6. TROUBLESHOOTING
Operation
Alarm reset
Stop mode
Detail method
Error reset
CPU reset
off → on
Power
Standard
Lin.
Full.
No. Name Detail name
display (Note 4,
5)
Alarm
6 - 11
6. TROUBLESHOOTING
Operation
Alarm reset
Stop mode
Detail method
Error reset
CPU reset
off → on
Power
Standard
Lin.
Full.
No. Name Detail name
display (Note 4,
5)
Alarm
6 - 12
6. TROUBLESHOOTING
Operation
Alarm reset
Stop mode
Detail method
Error reset
CPU reset
off → on
Power
Standard
Lin.
Full.
No. Name Detail name
display (Note 4,
5)
71.1 EDB
error 1
Load-side encoder communication - Receive data
71.2 EDB
error 2
Load-side encoder communication - Receive data
71.3 EDB
error 3
Load-side encoder communication - Transmission
71.5 EDB
Load-side encoder normal data error 1
71
communication error 1 Load-side encoder communication - Transmission
71.6 EDB
data error 2
Load-side encoder communication - Transmission
71.7 EDB
data error 3
Load-side encoder communication - Transmission
71.9 EDB
data error 4
Load-side encoder communication - Transmission
71.A EDB
data error 5
72.1 Load-side encoder data error 1 EDB
72.2 Load-side encoder data update error EDB
72.3 Load-side encoder data waveform error EDB
Load-side encoder normal
72 72.4 Load-side encoder non-signal error EDB
communication error 2
72.5 Load-side encoder hardware error 1 EDB
72.6 Load-side encoder hardware error 2 EDB
72.9 Load-side encoder data error 2 EDB
USB communication time-
8A 8A.1 USB communication time-out error SD
out error
8E.1 USB communication receive error SD
8E.2 USB communication checksum error SD
8E USB communication error 8E.3 USB communication character error SD
8E.4 USB communication command error SD
8E.5 USB communication data number error SD
888 Watchdog 88._ Watchdog DB
Note 1. Leave for about 30 minutes of cooling time after removing the cause of occurrence.
2. In some controller communication status, the alarm factor may not be removed.
3. The alarm can be canceled by setting as follows:
For the fully closed loop control: set [Pr. PE03] to "1 _ _ _".
For the linear servo motor: set [Pr. PL04] to "1 _ _ _".
4. Stop method indicates as follows:
DB: Stops with dynamic brake. (Coasts for the servo amplifier without dynamic brake.)
EDB: Stops with electronic dynamic brake for 600 W or less servo amplifiers
Stops with dynamic brake for 700 W or more servo amplifiers
SD: Forced stop deceleration
5. This is applicable when [Pr. PA04] is set to the initial value. The stop system of SD can be changed to DB using [Pr. PA04].
6. This alarm occurs only in the J3 compatibility mode.
6 - 13
6. TROUBLESHOOTING
Operation
Stop mode
Detail method
Standard
Lin.
Full.
No. Name Detail name
display (Note 2,
3)
Note 1. Leave for about 30 minutes of cooling time after removing the cause of occurrence.
2. Stop method indicates as follows:
DB: Stops with dynamic brake. (Coasts for the servo amplifier without dynamic brake.)
SD: Decelerates to a stop
3. This is applicable when [Pr. PA04] is set to the initial value. The stop system of SD can be changed to DB using [Pr. PA04].
6 - 14
6. TROUBLESHOOTING
When the servo system does not boot and system error occurs at power on of the servo system controller,
improper boot of the servo amplifier might be the cause. Check the display of the servo amplifier, and take
actions according to this section.
Display Description Cause Checkpoint Action
AA Communication with the The power of the servo Check the power of the servo Switch on the power of the servo
servo system controller system controller was system controller. system controller.
has disconnected. turned off.
A SSCNET III cable was "AA" is displayed in the Replace the SSCNET III cable of
disconnected. corresponding axis and following the corresponding axis.
axes.
Check if the connectors (CNIA, Connect it correctly.
CNIB) are unplugged.
The power of the servo "AA" is displayed in the Check the power of the servo
amplifier was turned off. corresponding axis and following amplifier.
axes.
Replace the servo amplifier of the
corresponding axis.
Ab Initialization The control axis is Check if the disabling control axis Turn off the disabling control axis
communication with the disabled. switch (SW2-2) is on. switch (SW2-2).
servo system controller The setting of the axis Check that the other servo Set it correctly.
has not completed. No. is incorrect. amplifier is not assigned to the
same axis No.
Axis No. does not match Check the setting and axis No. of Set it correctly.
with the axis No. set to the servo system controller.
the servo system
controller.
Information about the Check the value set in Servo Set it correctly.
servo series has not set series (Pr.100) in the simple
in the simple motion motion module.
module.
Communication cycle Check the communication cycle Set it correctly.
does not match. at the servo system controller
side.
When using 8 axes or less: 0.222
ms
When using 16 axes or less:
0.444 ms
When using 32 axes or less:
0.888 ms
A SSCNET III cable was "Ab" is displayed in the Replace the SSCNET III cable of
disconnected. corresponding axis and following the corresponding axis.
axes.
Check if the connectors (CNIA, Connect it correctly.
CNIB) are unplugged.
The power of the servo "Ab" is displayed in an axis and Check the power of the servo
amplifier was turned off. the following axes. amplifier.
The servo amplifier is "Ab" is displayed in an axis and Replace the servo amplifier of the
malfunctioning. the following axes. corresponding axis.
b##. The system has been in Test operation mode has Test operation setting switch Turn off the test operation setting
(Note) the test operation mode. been enabled. (SW2-1) is turned on. switch (SW2-1).
off Operation mode for Operation mode for Check if all of the control axis Set the control axis setting
manufacturer setting is manufacturer setting is setting switches (SW2) are on. switches (SW2) correctly.
set. enabled.
6 - 15
6. TROUBLESHOOTING
MEMO
6 - 16
7. DIMENSIONS
7. DIMENSIONS
POINT
The dimensions shown are for MR-J4-_A4-RJ and MR-J4-_B4-RJ. MR-J4-_A4
and MR-J4-_B4 servo amplifiers do not have CN2L and CN7 connectors. The
dimensions for MR-J4-_A4 and MR-J4-_B4 servo amplifiers are the same as
those for MR-J4-_A4-RJ and MR-J4-_B4-RJ servo amplifiers except these
connectors.
7- 1
7. DIMENSIONS
7.1 MR-J4-_A4(-RJ)
(a) MR-J4-60A4(-RJ)/MR-J4-100A4(-RJ)
[Unit: mm]
60
φ6 mounting hole 12 Approx. 80 195
Lock knob
6
CNP1
CNP2
161
156
168
CNP3
6
PE
6
Approx. 21
12 42 Approx. 69.3
Approx. 38.5
With
MR-BAT6V1SET
L2
6
Approx. 60
L3
P3
P4
CNP2
Approx. 168
P+
156 ± 0.5
C
D
L11
L21 3-M5 screw
CNP3
U
Approx.
V
6
W 42 ± 0.3
PE Screw size: M4 Approx. 12 Approx. 6
Tightening torque: 1.2 [N•m] Mounting hole process drawing
7- 2
7. DIMENSIONS
(b) MR-J4-200A4(-RJ)
[Unit: mm]
90
85
φ6 mounting hole
45 Approx. 80 195
Lock knob
Exhaust
6
CNP1
CNP2
161
156
168
CNP3
6
PE Cooling fan
Approx. intake
6 Approx. 21
69.3
6 78 6
Approx. 38.5
With
MR-BAT6V1SET
Approx. 90
L2
6
L3
P3
P4
CNP2
Approx. 168
P+
156 ± 0.5
C
D
L11
L21 3-M5 screw
CNP3
U
Approx.
V
6
W
PE Approx. 6 78 ± 0.3 Approx. 6
Screw size: M4
Tightening torque: 1.2 [N•m] Mounting hole process drawing
7- 3
7. DIMENSIONS
(c) MR-J4-350A4(-RJ)
[Unit: mm]
7.5
Cooling fan exhaust
Approx. 73.5
CNP1
CNP2
250
235
CNP3
Approx. 69.3
With
MR-BAT6V1SET
7.5
6 Intake
Approx.
38.5
Approx.
34
P3 4-M5 screw
P4
CNP2
P+
C
D
Approx. 250
L11
235 ± 0.5
L21
CNP3
U
V
W
PE
Screw size: M4
Tightening torque: 1.2 [N•m]
Approx.
7.5
7- 4
7. DIMENSIONS
(d) MR-J4-500A4(-RJ)
[Unit: mm]
Approx. 73.5
TE2 TE3
TE1
With Intake PE
7.5
MR-BAT6V1SET
Built-in regenerative resistor
Approx.
38.5
4-M5 screw
PE Screw size: M4
Tightening torque: 1.2 [N•m]
Approx.
7- 5
7. DIMENSIONS
(e) MR-J4-700A4(-RJ)
[Unit: mm]
exhaust
300
285
With TE3
MR-BAT6V1SET
TE1
PE TE2
7.5
6 Intake
Screw size: M4
Tightening torque: 1.2 [N•m]
101
4-M5 screw
PE
TE3 Screw size: M4
Tightening torque: 1.2 [N•m]
PE Screw size: M4
Tightening torque: 1.2 [N•m]
Approx.
7.5
7- 6
7. DIMENSIONS
(f) MR-J4-11KA4(-RJ)/MR-J4-15KA4(-RJ)
[Unit: mm]
exhaust
400
380
PE
24.2 11
TE2 TE1-1
TE1-2
60 43
78.5
With 188 Intake 25.5 22.8
10
6
MR-BAT6V1SET 224.2 57.9
237.4 5 × 25.5 (= 127.5)
Approx. Approx.
139.5 39
4-M5 screw
PE
TE1-1 Screw size: M6
Tightening torque: 3.0 [N•m]
PE Screw size: M6
Tightening torque: 3.0 [N•m]
Approx.
10
7- 7
7. DIMENSIONS
(g) MR-J4-22KA4(-RJ)
[Unit: mm]
TE1-1
32.7 11
TE2 TE1-2
39.7
PE
Intake
40.5
12 188.5 22.8
26.8
12
With
MR-BAT6V1SET 223.4 59.9 127.5
235.4
Approx. Approx.
179 39
4-M10 screw
PE TE2 L11 L21
PE Screw size: M8
Tightening torque: 6.0 [N•m]
Approx.
7- 8
7. DIMENSIONS
7.2 MR-J4-_B4(-RJ)
(a) MR-J4-60B4(-RJ)/MR-J4-100B4(-RJ)
[Unit: mm]
60
φ6 mounting hole Approx. 80
12 195
Lock knob
6
CNP1
161
CNP2
156
168
CNP3
6
PE
6
Approx. 21
12 42 Approx. 69.3
Approx. 38.5
With
MR-BAT6V1SET
L2 Approx. 60
6
L3
P3
P4
CNP2
P+
Approx. 168
156 ± 0.5
C
D
L11
L21
3-M5 screw
CNP3
U
V
Approx.
W
6
42 ± 0.3
PE Screw size: M4
Tightening torque: 1.2 [N•m] Approx. 12 Approx. 6
7- 9
7. DIMENSIONS
(b) MR-J4-200B4(-RJ)
[Unit: mm]
90
85
φ6 mounting hole
45 Approx. 80 195
Lock knob
Exhaust
6
CNP1
CNP2
161
156
168
CNP3
6
PE Cooling fan
Approx. 21 Approx. intake
6 69.3
6 78 6
Approx. 38.5
With
MR-BAT6V1SET
L2 Approx. 90
6
L3
P3
P4
CNP2
Approx. 168
P+
156 ± 0.5
C
D
L11
L21
3-M5 screw
CNP3
U
Approx.
V
6
W
PE Screw size: M4 Approx. 6 78 ± 0.3 Approx. 6
Tightening torque: 1.2 [N•m]
Mounting hole process drawing
7 - 10
7. DIMENSIONS
(c) MR-J4-350B4(-RJ)
[Unit: mm]
7.5
Cooling fan exhaust
Approx. 73.5
CNP1
CNP2
250
235
CNP3
Approx. 69.3
With
MR-BAT6V1SET
Intake
7.5
6
Approx.
38.5
Approx.
34
P3
7.5
P4 4-M5 screw
CNP2
P+
C
D
L11
Approx. 250
235 ± 0.5
L21
CNP3
U
V
W
PE Screw size: M4
Tightening torque: 1.2 [N•m]
Approx.
7.5
7 - 11
7. DIMENSIONS
(d) MR-J4-500B4(-RJ)
[Unit: mm]
Approx. 28
Approx. 73.5
TE2 TE3
TE1
With Intake PE
7.5
MR-BAT6V1SET
Built-in regenerative resistor
Approx.
38.5
4-M5 screw
PE Screw size: M4
Tightening torque: 1.2 [N•m]
Approx.
7.5
7 - 12
7. DIMENSIONS
(e) MR-J4-700B4(-RJ)
[Unit: mm]
exhaust
300
285
TE3
With TE1
MR-BAT6V1SET TE2
PE
7.5
6 Intake
Screw size: M4
Tightening torque: 1.2 [N•m]
101
4-M5 screw
PE
TE3 Screw size: M4
Tightening torque: 1.2 [N•m]
PE Screw size: M4
Tightening torque: 1.2 [N•m]
Approx.
7 - 13
7. DIMENSIONS
(f) MR-J4-11KB4(-RJ)/MR-J4-15KB4(-RJ)
[Unit: mm]
24.2 11 PE
TE1-1
TE2
TE1-2
60 43
78.5
6 188 Intake 25.5 22.8
10
With
MR-BAT6V1SET 224.2 57.9
237.4 5 × 25.5 (= 127.5)
Approx. Approx.
139.5 39
4-M5 screw
PE
TE1-1 Screw size: M6
Tightening torque: 3.0 [N•m]
PE Screw size: M6
Tightening torque: 3.0 [N•m]
Approx.
10
7 - 14
7. DIMENSIONS
(g) MR-J4-22KB4(-RJ)
[Unit: mm]
exhaust
400
376
TE1-1
32.7 11
TE2 TE1-2
40
PE
25.5 22.8
40.5
188.5 Intake
26.5
12
12
With
MR-BAT6V1SET 223.4 59.9
235.4 5 × 25.5 (= 127.5)
Approx. Approx.
179 39
4-M10 screw
PE TE2 L11 L21
PE Screw size: M8
Tightening torque: 6.0 [N•m]
Approx.
12
7 - 15
7. DIMENSIONS
MEMO
7 - 16
8. CHARACTERISTICS
8. CHARACTERISTICS
The items in the following table are the same as those for MR-J4-_A(-RJ) or MR-J4-_B(-RJ) servo amplifier.
For details of the items, refer to each chapter/section of the detailed explanation field.
Model Item Detailed explanation
MR-J4-_A4(-RJ) Cable bending life MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 10.4
MR-J4-_B4(-RJ) Cable bending life MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 10.4
An electronic thermal is built in the servo amplifier to protect the servo motor, servo amplifier and servo
motor power wires from overloads.
[AL. 50 Overload 1] occurs if overload operation performed is above the electronic thermal protection curve
shown in fig. 8.1. [AL. 51 Overload 2] occurs if the maximum current is applied continuously for several
seconds due to machine collision, etc. Use the equipment on the left-side area of the continuous or broken
line in the graph.
For the system where the unbalanced torque occurs, such as a vertical axis system, it is recommended that
the unbalanced torque of the machine be kept at 70% or less of the motor's rated torque.
This servo amplifier has servo motor overload protective function. (The servo motor overload current (full
load current) is set on the basis of 120% rated current of the servo amplifier.)
The following table shows the combination of each servo motor and overload protective characteristics.
Rotary servo motor
HG-JR Graph of overload protection
HG-SR HG-JR (standard) (When the maximum torque is characteristics
400%)
534
524
734 534 Characteristics a
1024
1034
734
1524 1534
1034
2024 2034 Characteristics b
1534
3524 3534
2034
5024 5034 3534
Characteristics c
7024 7034 5034
9034
11K1M4
Characteristics d
15K1M4
22K1M4
8- 1
8. CHARACTERISTICS
Operating Operating
100 100
Operation time [s]
1 1
0.1 0.1
0 50 100 150 200 250 300 350 400 0 50 100 150 200 250 300 350 400
(Note 1, 2) Load ratio [%] (Note 1, 2) Load ratio [%]
Characteristics a Characteristics b
1000 10000
Operating
100 1000
Operation time [s]
Operating
Servo-lock
10 100
Servo-lock
1
10
0.1
0 50 100 150 200 250 300 350 400 1
0 50 100 150 200 250 300
(Note 1, 2) Load ratio [%]
(Note 1) Load ratio [%]
Characteristics c
Characteristics d
Note 1. If operation that generates torque more than 100% of the rating is performed with an abnormally high frequency in a servo
motor stop status (servo-lock status) or in a 30 r/min or less low-speed operation status, the servo amplifier may malfunction
regardless of the electronic thermal protection.
2. The operation time at the load ratio of 300% to 400% applies when the maximum torque of HG-JR servo motor is increased to
400%.
8- 2
8. CHARACTERISTICS
Table 8.1 Power supply capacity and generated loss per servo motor at rated output
(Note 2) Servo amplifier-generated heat [W]
(Note 1) At rated output
[Generated heat Area required
Power supply
Servo amplifier Servo motor in the cabinet for heat
capacity At rated output With servo-off 2
when dissipating dissipation [m ]
[kVA]
heat outside the
cabinet] (Note 3)
HG-SR524 1.0 40 18 0.8
MR-J4-60_4(-RJ)
HG-JR534 1.0 40 18 0.8
HG-SR1024 1.7 60 18 1.2
MR-J4-100_4(-RJ) HG-JR734 1.3 60 18 1.2
HG-JR1034 1.7 60 18 1.2
HG-SR1524 2.5 90 20 1.8
HG-SR2024 3.5 90 20 1.8
MR-J4-200_4(-RJ)
HG-JR1534 2.5 90 20 1.8
HG-JR2034 3.5 90 20 1.8
HG-SR3524 5.5 130 20 2.6
MR-J4-350_4(-RJ)
HG-JR3534 5.5 160 20 2.7
HG-SR5024 7.5 195 25 3.9
MR-J4-500_4(-RJ)
HG-JR5034 7.5 195 25 3.9
HG-SR7024 10 300 25 6.0
MR-J4-700_4(-RJ)
HG-JR7034 10 300 25 6.0
HG-JR9034 13 435 130 45 8.7
MR-J4-11K_4(-RJ)
HG-JR11K1M4 16 530 160 45 11.0
MR-J4-15K_4(-RJ) HG-JR15K1M4 22 640 195 45 13.0
MR-J4-22K_4(-RJ) HG-JR22K1M4 33 850 260 55 17.0
Note 1. Note that the power supply capacity will vary according to the power supply impedance. This value is applicable when
the power factor improving AC reactor or power factor improving DC reactor are not used.
2. Heat generated during regeneration is not included in the servo amplifier-generated heat. To calculate heat generated by
the regenerative option, refer to section 9.2.
3. This value is applicable when the servo amplifier is cooled by using the heat sink outside mounting attachment.
8- 3
8. CHARACTERISTICS
P
A= ·········································································································································· (8.1)
K • ΔT
When calculating the heat dissipation area with equation 8.1, assume that P is the sum of all losses
generated in the cabinet. Refer to table 8.1 for heat generated by the servo amplifier. "A" indicates the
effective area for heat dissipation, but if the cabinet is directly installed on an insulated wall, that extra
amount must be added to the cabinet's surface area. The required heat dissipation area will vary with
the conditions in the cabinet. If convection in the cabinet is poor and heat builds up, effective heat
dissipation will not be possible. Therefore, arrangement of the equipment in the cabinet and the use of a
cooling fan should be considered. Table 8.1 lists the cabinet dissipation area for each servo amplifier
(guideline) when the servo amplifier is operated at the ambient temperature of 40 ˚C under rated load.
Air flow
When air flows along the outer wall of the cabinet, effective heat exchange will be possible, because the
temperature slope inside and outside the cabinet will be steeper.
8- 4
8. CHARACTERISTICS
POINT
Do not use dynamic brake to stop in a normal operation as it is the function to
stop in emergency.
For a machine operating at the recommended load to motor inertia ratio or less,
the estimated number of usage times of the dynamic brake is 1000 times while
the machine decelerates from the rated speed to a stop once in 10 minutes.
Be sure to enable EM1 (Forced stop 1) after servo motor stops when using EM1
(Forced stop 1) frequently in other than emergency.
Servo motors for MR-J4 may have the different coasting distance from that of
the previous model.
The electronic dynamic brake operates in the initial state for the HG series servo
motors of 600 W or smaller capacity. The time constant "τ" for the electronic
dynamic brake will be shorter than that of normal dynamic brake. Therefore,
coasting distance will be longer than that of normal dynamic brake. For how to
set the electronic dynamic brake, refer to [Pr. PF09] and [Pr. PF15] (MR-J4-_A4)
or [Pr. PF06] and [Pr. PF12] (MR-J4-_B4).
Dynamic brake
time constant
V0
Machine speed
te Time
8- 5
8. CHARACTERISTICS
V0 JL
Lmax = • te + 1+ ··············································································································· (8.2)
60 JM
80 3524
constant [ms]
35
constant [ms]
60 30 22K1M4
25 15K1M4
2024 20
40 5024 15
1024 10
20 5
7024 0
1524 0 500 1000 1500 2000 2500 3000
0
0 500 1000 1500 2000 2500 3000 Speed [r/min]
Speed [r/min]
80 534
9034
60
1034
40 3534
5034
20
2034 1534
734
0
0 1000 2000 3000 4000 5000 6000
Speed [r/min]
HG-SR3000r/min series
8.3.2 Permissible load to motor inertia when the dynamic brake is used
Use the dynamic brake under the load to motor inertia ratio indicated in the following table. If the ratio is
higher than this value, the dynamic brake may burn. If there is a possibility that the ratio may exceed the
value, contact your local sales office.
The values of the permissible load to motor inertia ratio in the table are the values at the maximum rotation
speed of the servo motor. The value in the parenthesis shows the value at the rated speed.
8- 6
8. CHARACTERISTICS
Note. When the maximum torque is increased to 400%, the permissible load to motor inertia ratio at the maximum speed
of the servo motor is 25 times.
The following table indicates the inrush currents (reference data) that will flow when 480 V AC is applied at
the power supply capacity of 2500 kVA and the wiring length of 1 m.
Inrush currents (A0-P)
Servo amplifier Main circuit power supply Control circuit power supply
(L1, L2, and L3) (L11 and L21)
MR-J4-60_4(-RJ) 65 A
MR-J4-100_4(-RJ) (attenuated to approx. 5 A in 10 ms)
80 A 40 A to 50 A
MR-J4-200_4(-RJ) (Attenuated to approx. 0 A in 2 ms)
(attenuated to approx. 5 A in 10 ms)
100 A
MR-J4-350_4(-RJ)
(attenuated to approx. 20 A in 10 ms)
65 A
MR-J4-500_4(-RJ)
(attenuated to approx. 9 A in 20 ms) 41 A
68 A (attenuated to approx. 0 A in 3 ms)
MR-J4-700_4(-RJ)
(attenuated to approx. 34 A in 20 ms)
339 A
MR-J4-11K_4(-RJ)
(attenuated to approx. 10 A in 30 ms)
339 A 38 A
MR-J4-15K_4(-RJ)
(attenuated to approx. 15 A in 30 ms) (attenuated to approx. 1 A in 30 ms)
339 A
MR-J4-22K_4(-RJ)
(attenuated to approx. 20 A in 30 ms)
Since large inrush currents flow in the power supplies, always use molded-case circuit breakers and
magnetic contactors.
(Refer to section 9.7.)
When circuit protectors are used, it is recommended that the inertia delay type, which is not tripped by an
inrush current, be used.
8- 7
8. CHARACTERISTICS
MEMO
8- 8
9. OPTIONS AND PERIPHERAL EQUIPMENT
Before connecting any option or peripheral equipment, turn off the power and wait
for 15 minutes or more until the charge lamp turns off. Then, confirm that the
WARNING voltage between P+ and N- is safe with a voltage tester and others. Otherwise, an
electric shock may occur. In addition, when confirming whether the charge lamp is
off or not, always confirm it from the front of the servo amplifier.
POINT
We recommend using HIV wires to wire the servo amplifiers, options, and
peripheral equipment. Therefore, the recommended wire sizes may differ from
those used for the previous servo amplifiers.
The items in the following table are the same as those for MR-J4-_A(-RJ) or MR-J4-_B(-RJ) servo amplifier.
For details of the items, refer to each chapter/section of the detailed explanation field.
Model Item Detailed explanation
MR-J4-_A4(-RJ) MR-D05UDL3M-B STO cable MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 11.1.2
Junction terminal block MR-TB50 MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 11.6
MR Configurator2 MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 11.7
Battery MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 11.8
Relay (recommended) MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 11.13
External dynamic brake MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 11.17
Heat sink outside mounting attachment MR-J4-_A(-RJ) Servo Amplifier Instruction
(MR-J4ACN15K/MR-J3ACN) Manual section 11.18
MR-J4-_B4(-RJ) MR-D05UDL3M-B STO cable MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 11.1.2
SSCNET III cable MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 11.1.3
Junction terminal block PS7DW-20V14B-F MR-J4-_B(-RJ) Servo Amplifier Instruction
(recommended) Manual section 11.6
MR Configurator2 MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 11.7
Battery MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 11.8
Relay (recommended) MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 11.13
External dynamic brake MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 11.17
Heat sink outside mounting attachment MR-J4-_B(-RJ) Servo Amplifier Instruction
(MR-J4ACN15K/MR-J3ACN) Manual section 11.18
9- 1
9. OPTIONS AND PERIPHERAL EQUIPMENT
POINT
The IP rating indicated for cables and connectors is their protection against
ingress of dust and raindrops when they are connected to a servo amplifier or
servo motor. If the IP rating of the cable, connector, servo amplifier and servo
motor vary, the overall IP rating depends on the lowest IP rating of all
components.
Please purchase the cable and connector options indicated in this section.
Operation 3)
panel
Personal computer
2)
Servo amplifier 5)
Controller
1) (packed with the
servo amplifier) CN5 6)
CN6
(Note 1)
CNP1 Safety logic unit
CN3 MR-J3-D05
CN9
CN8 (Note 2) 7)
CNP2 CN10
CN1
CNP3
CN2
CN4
Refer to "Servo Motor Instruction Manual (Vol. 3)" for options for servo
motor power supply, electromagnetic brake, and encoder.
To CN2
Linear encoder
Note 1. Connectors for 3.5 kW or less. For 5 kW or more, it is a terminal block.
2. When not using the STO function, attach the short-circuit connector ( 8)) came with a servo amplifier.
9- 2
9. OPTIONS AND PERIPHERAL EQUIPMENT
Operation 3)
panel
Personal computer
2)
Servo amplifier 5)
Controller
1) (packed with the
1) servo amplifier) CN5 6)
CN6
(Note 1)
CNP1 Safety logic unit
CN3 MR-J3-D05
CN9
CN8 (Note 2) 7)
CNP2 CN10
CN1
CNP3
CN2
CN2L
CN4
Refer to "Servo Motor Instruction Manual (Vol. 3)" for options for servo
motor power supply, electromagnetic brake, and encoder.
Battery
To 24 V DC power supply
for electromagnetic brake Servo motor
To CN2
Linear encoder
9- 3
9. OPTIONS AND PERIPHERAL EQUIPMENT
9- 4
9. OPTIONS AND PERIPHERAL EQUIPMENT
2)3)4)
Servo amplifier 7) Servo amplifier
CN1B CN1B
CNP3
CN2 CN2
Cap
(packed with the
servo amplifier)
CN4 CN4
Refer to "Servo Motor Instruction Manual (Vol. 3)" for options for servo
motor power supply, electromagnetic brake, and encoder.
To CN2
Linear encoder
9- 5
9. OPTIONS AND PERIPHERAL EQUIPMENT
2) 3) 4)
Servo amplifier 7) Servo amplifier
CN1B CN1B
CNP3
CN2 CN2
Cap
CN2L CN2L (packed with the
servo amplifier)
CN4 CN4
Refer to "Servo Motor Instruction Manual (Vol. 3)" for options for servo
motor power supply, electromagnetic brake, and encoder.
To CN2
Linear encoder
9- 6
9. OPTIONS AND PERIPHERAL EQUIPMENT
9- 7
9. OPTIONS AND PERIPHERAL EQUIPMENT
Do not use servo amplifiers with regenerative options other than the combinations
CAUTION specified below.
Otherwise, it may cause a fire.
The power values in the table are resistor-generated powers and not rated powers.
Regenerative power [W]
(Note 1) (Note 1) (Note 1) (Note 1) (Note 1) (Note 1) (Note 1)
Servo amplifier Built-in MR-
MR- MR- MR- MR- MR- MR- MR-
regenerative RB1H-4
RB3M-4 RB3G-4 RB5G-4 RB34-4 RB54-4 RB3U-4 RB5U-4
resistor [82 Ω]
[120 Ω] [47 Ω] [47 Ω] [26 Ω] [26 Ω] [22 Ω] [22 Ω]
MR-J4-60_4(-RJ) 15 100 300
MR-J4-100_4(-RJ) 15 100 300
MR-J4-200_4(-RJ) 100 300 500
MR-J4-350_4(-RJ) 100 300 500
MR-J4-500_4(-RJ) 130 300 500
MR-J4-700_4(-RJ) 170 300 500
9- 8
9. OPTIONS AND PERIPHERAL EQUIPMENT
Time
Down
Unbalance torque
M t1 t2 t3 t4
tpsa1 tpsd1 tpsa2 tpsd2
Friction
torque 1)
(+)
(Power running)
Generated torque
2) 4) 8)
TF 5)
TU 6)
3)
(Regenerative) 7)
(-)
From the calculation results in 1) to 8), find the absolute value (Es) of the sum total of negative
energies.
9- 9
9. OPTIONS AND PERIPHERAL EQUIPMENT
Inverse efficiency (η): Efficiency including some efficiencies of the servo motor and servo amplifier
when rated (regenerative) torque is generated at rated speed. Since the efficiency varies
with the speed and generated torque, allow for about 10%.
Capacitor charging (Ec): Energy charged into the electrolytic capacitor in the servo amplifier
Subtract the capacitor charging from the result of multiplying the sum total of regenerative energies
by the inverse efficiency to calculate the energy consumed by the regenerative option.
ER [J] = η • Es - Ec
Calculate the power consumption of the regenerative option on the basis of single-cycle operation
period tf [s] to select the necessary regenerative option.
PR [W] = ER/tf
9 - 10
9. OPTIONS AND PERIPHERAL EQUIPMENT
The following shows equations of the linear servo motor thrust and energy at the driving pattern
above.
From the calculation results in 1) to 8), find the absolute value (Es) of the sum total of negative
energies.
ER [J] = η • Es - Ec
From the total of ER's whose subtraction results are positive and a 1-cycle period, the power
consumption of the regenerative option can be calculated with the following expression.
Select the regenerative option from the PR value. Regenerative option is not required when the
energy consumption is equal to or less than the built-in regenerative energy.
0 0
Selection of regenerative option
00: Regenerative option is not used.
For servo amplifier of 0.6 kW to 7 kW, built-in regenerative resistor is used.
Supplied regenerative resistors or regenerative option is used with the servo amplifier
of 11 kW to 22 kW.
01: FR-BU2-H/FR-RC-H/FR-CV-H
80: MR-RB1H-4
81: MR-RB3M-4 (Cooling fan is required.)
82: MR-RB3G-4 (Cooling fan is required.)
83: MR-RB5G-4 (Cooling fan is required.)
84: MR-RB34-4 (Cooling fan is required.)
85: MR-RB54-4 (Cooling fan is required.)
91: MR-RB3U-4 (Cooling fan is required.)
92: MR-RB5U-4 (Cooling fan is required.)
FA: When the supplied regenerative resistors or the regenerative option is cooled by the
cooling fan to increase the ability with the servo amplifier of 11 kW to 22 kW.
9 - 11
9. OPTIONS AND PERIPHERAL EQUIPMENT
POINT
MR-RB3M-4, MR-RB3G-4, MR-RB5G-4, MR-RB34-4, MR-RB54-4, MR-RB5K-4,
or MR-RB6K-4 is used, a cooling fan is required to cool it. The cooling fan
should be prepared by the customer.
For the wire sizes used for wiring, refer to section 9.6.
The regenerative option generates heat of 100 ˚C higher than the ambient temperature. Fully consider heat
dissipation, installation position, wires used, etc. before installing the option. For wiring, use flame-resistant
wires or make the wires flame-resistant and keep them away from the regenerative option. Always use
twisted cables of max. 5 m length for connection with the servo amplifier.
5 m or shorter
(Note 1)
Cooling fan
Note 1. When using the MR-RB3M-4, MR-RB3G-4, or MR-RB5G-4, forcibly cool it with a
3
cooling fan (92 × 92, minimum air flow: 1.0 m ).
2. Make up a sequence which will switch off the magnetic contactor when abnormal
heating occurs.
G3-G4 contact specifications
Maximum voltage: 120 V AC/DC
Maximum current: 0.5 A/4.8 V DC
Maximum capacity: 2.4 VA
9 - 12
9. OPTIONS AND PERIPHERAL EQUIPMENT
(2) MR-J4-500A4(-RJ)/MR-J4-700A4(-RJ)/MR-J4-500B4(-RJ)/MR-J4-700B4(-RJ)
Always remove the wiring (across P+ to C) of the servo amplifier built-in regenerative resistor and fit the
regenerative option across P+ to C. G3 and G4 are thermal sensor's terminals. Between G3 and G4 is
opened when the regenerative option overheats abnormally.
Always remove the wiring (across P+ to C) of the
servo amplifier built-in regenerative resistor.
Servo amplifier Regenerative option
P
P+
C
C
G3
(Note 2) G4
5 m or shorter
(Note 1)
Cooling fan
When using the regenerative option, remove the servo amplifier's built-in regenerative resistor wires
(across P+ to C), fit them back to back, and secure them to the frame with the accessory screw as
shown below.
Attached screw
9 - 13
9. OPTIONS AND PERIPHERAL EQUIPMENT
(3) MR-J4-11KA4(-RJ)/MR-J4-15KA4(-RJ)/MR-J4-22KA4(-RJ)/MR-J4-11KB4(-RJ)/MR-J4-15KB4(-RJ)/MR-
J4-22KB4(-RJ) (when using the supplied regenerative resistor)
When using the regenerative resistors supplied to the servo amplifier, the specified number of resistors
(4 or 5 resistors) must be connected in series. If they are connected in parallel or in less than the
specified number, the servo amplifier may become faulty and/or the regenerative resistors burn.
Install the resistors at intervals of about 70 mm. Cooling the resistors with two cooling fans (1.0 m3/min
or more, 92 mm × 92 mm) improves the regeneration capability. In this case, set "_ _ F A" in [Pr. PA02].
5 m or shorter
Servo amplifier
P+
(Note) C
Series connection
Cooling fan
Note. The number of resistors connected in series depends on the resistor type. The
thermal sensor is not mounted on the attached regenerative resistor. An abnormal
heating of resistor may be generated at a regenerative circuit failure. Install a thermal
sensor near the resistor and establish a protective circuit to shut off the main circuit
power supply when abnormal heating occurs. The detection level of the thermal
sensor varies according to the settings of the resistor. Set the thermal sensor in the
most appropriate position on your design basis, or use the thermal sensor built-in
regenerative option. (MR-RB5E, 5R, 9P, 9F, 5K-4, 6B-4, 60-4, or 6K-4)
9 - 14
9. OPTIONS AND PERIPHERAL EQUIPMENT
P+ P
C C
G3
(Note)
G4
Regenerative power
Regenerative Resistance [W]
Servo amplifier
option [Ω] Without With cooling
cooling fans fans
MR-J4-11KA4-PX
MR-J4-11KB4-PX
MR-RB5K-4 10 500 800
MR-J4-11KA4-RZ
MR-J4-11KB4-RZ
MR-J4-15KA4-PX
MR-J4-15KB4-PX
MR-J4-15KA4-RZ
MR-J4-15KB4-RZ
MR-RB6K-4 10 850 1300
MR-J4-22KA4-PX
MR-J4-22KB4-PX
MR-J4-22KA4-RZ
MR-J4-22KB4-RZ
9 - 15
9. OPTIONS AND PERIPHERAL EQUIPMENT
When using cooling fans, install them using the mounting holes provided in the bottom of the
regenerative option.
Top MR-RB5K-4/MR-RB6K-4
Bottom
TE1
Cooling fan × 2
(92 mm × 92 mm,
minimum air flow: 1.0 m3)
TE
Mounting screw 4-M3 G4 G3 C P
9.2.5 Dimensions
(1) MR-RB1H-4
[Unit: mm]
Terminal
G3
40
G4
36
P
15 φ6 mounting hole
C
6
Mounting screw
Screw size: M5
Tightening torque: 3.24 [N•m]
168
156
144
6 6 2
Approx. 24 149
173
9 - 16
9. OPTIONS AND PERIPHERAL EQUIPMENT
(2) MR-RB34-4/MR-RB3M-4/MR-RB3G-4/MR-RB3U-4
[Unit: mm]
Terminal block
Cooling fan mounting
screw (2-M4 screw) P
8.5
C
G3
125
82.5
150
142
G4
101.5 82.5
10 90 23 318
100 Mounting screw
341
Screw size: M6
Air intake Tightening torque: 5.4 [N•m]
Approx.
30
(3) MR-RB54-4/MR-RB5G-4/MR-RB5U-4
[Unit: mm]
Cooling fan mounting Terminal block
screw (2-M3 screw)
On opposite side P
7 × 14
12.5
Mounting screw
Air
82.5
350
2.3 7
12.5
9 - 17
9. OPTIONS AND PERIPHERAL EQUIPMENT
(4) MR-RB5K-4/MR-RB6K-4
[Unit: mm]
Terminal
2-φ10 mounting hole
10
G4 G3 C P
30
Terminal screw size: M5
Tightening torque: 2.0 [N•m]
Mounting screw
Screw size: M8
427
480
500
Tightening torque: 13.2 [N•m]
Regenerative Mass
option [kg]
MR-RB5K-4 10
MR-RB6K-4 11
43
10 2.3
10
15 230 15 197 15
260 215
15 230 15
Screw for mounting cooling fan
4-M3 screw
82.5
Approx. 42
82.5 82.5
[N•m]
Approx. φC GRZG400-2.5Ω
Approx. 2.4 10 5.5 39 M8 13.2 0.8
10 Approx. A
GRZG400-2.0Ω
1.6
40
9 - 18
9. OPTIONS AND PERIPHERAL EQUIPMENT
POINT
When a brake unit and a resistor unit are installed horizontally or diagonally, the
heat dissipation effect diminishes. Install them on a flat surface vertically.
The temperature of the resistor unit case will be higher than the ambient
temperature by 100 ˚C or over. Keep cables and flammable materials away from
the case.
Ambient temperature condition of the brake unit is between -10 ˚C and 50 ˚C.
Note that the condition is different from the ambient temperature condition of the
servo amplifier (between 0 ˚C and 55 ˚C).
Configure the circuit to shut down the power-supply with the alarm output of the
brake unit and the resistor unit under abnormal condition.
Use the brake unit with a combination indicated in section 9.3.1.
For executing a continuous regenerative operation, use FR-RC-H power
regenerative converter or FR-CV-H power regenerative common converter.
Brake unit and regenerative options (Regenerative resistor) cannot be used
simultaneously.
Connect the brake unit to the bus of the servo amplifier. As compared to the MR-RB regenerative option, the
brake unit can return larger power. Use the brake unit when the regenerative option cannot provide sufficient
regenerative capability.
When using the brake unit, set [Pr. PA02] to "_ _ 0 1".
When using the brake unit, always refer to the FR-BU2 Brake Unit Instruction Manual.
9 - 19
9. OPTIONS AND PERIPHERAL EQUIPMENT
9.3.1 Selection
Use a combination of servo amplifier, brake unit and resistor unit listed below.
Number of Permissible Resultant
Applicable servo
Brake unit Resistor unit connected continuous resistance
amplifier (Note 2)
units power [kW] [Ω]
400 V FR-BU2-H30K FR-BR-H30K 1 1.99 16 MR-J4-500_4(-RJ)
class MR-J4-700_4(-RJ)
MR-J4-11K_4(-RJ)
(Note 1)
FR-BU2-H55K FR-BR-H55K 1 3.91 8 MR-J4-11K_4(-RJ)
MR-J4-15K_4(-RJ)
MR-J4-22K_4(-RJ)
FR-BU2-H75K MT-BR5-H75K 1 7.5 6.5 MR-J4-22K_4(-RJ)
Note 1. When HG-JR11K1M4 servo motor is used, limit the torque during power running to 180% or less, or the servo
motor speed to 1800 r/min or less.
2. When the brake unit is selected by using the capacity selection software, a brake unit other than the combinations
listed may be shown. Refer to the combinations displayed on the capacity selection software for detailed
combinations.
9 - 20
9. OPTIONS AND PERIPHERAL EQUIPMENT
POINT
EM2 has the same function as EM1 in the torque control mode.
Connecting PR terminal of the brake unit to P+ terminal of the servo amplifier
results in brake unit malfunction. Always connect the PR terminal of the brake
unit to the PR terminal of the resistor unit.
MC
Emergency stop switch SK
Step-down
transformer Servo amplifier
(Note 9) CN1
MCCB MC 24 V DC (Note 12)
(Note 1) L1 46 DOCOM
Power L2
supply 47 DOCOM
L3
L11 48 ALM RA1
L21
(Note 11) FR-BR-H
(Note 5) TH1
P
TH2
(Note 10) PR
Main circuit power supply CN1
P3
EM2 42 (Note 3) FR-BU2-H
P4
SON 15 PR MSG
P+ P/+ SD
DICOM 20 (Note 4) A
(Note 7) N/-
24 V DC B
DICOM 21 N-
(Note 12) C
C BUE
(Note 6)
SD (Note 8)
(Note 2)
9 - 21
9. OPTIONS AND PERIPHERAL EQUIPMENT
MC
Emergency stop switch SK
Step-down
transformer Servo amplifier
(Note 9)
MCCB MC
(Note 1) L1
Power CN3 24 V DC (Note 12)
L2
supply L3 3 DOCOM
9 - 22
9. OPTIONS AND PERIPHERAL EQUIPMENT
MC
Emergency stop switch SK
Step-down
transformer
Servo amplifier
(Note 8)
CN1 24 V DC (Note 11)
MCCB MC
(Note 1) L1 46 DOCOM
Power L2
supply L3 47 DOCOM
L11 48 ALM RA1
L21
(Note 10) MT-BR5-H SK
(Note 4) TH1
P RA2
TH2
(Note 9) PR
Main circuit power supply CN1
P3
EM2 42 (Note 2) FR-BU2-H
P4
SON 15 PR MSG
P+ P/+ SD
DICOM 20 (Note 3) A
(Note 6) N/-
24 V DC B
DICOM 21 N-
(Note 11) C
BUE
(Note 5)
SD (Note 7)
9 - 23
9. OPTIONS AND PERIPHERAL EQUIPMENT
MC
Emergency stop switch SK
Step-down
transformer
Servo amplifier
(Note 8)
MCCB MC
(Note 1) L1
CN3 24 V DC (Note 11)
Power L2
supply 3 DOCOM
L3
L11 15 ALM RA1
MT-BR5-H SK
L21
(Note 4) TH1
(Note 10) P RA2
TH2
PR
(Note 9) P3
Main circuit power supply CN3
(Note 2) FR-BU2-H
P4
EM2 20
PR MSG
DICOM 5 P+ P/+ SD
(Note 3) A
24 V DC (Note 6) N/-
(Note 11) DICOM 10 B
N-
C
BUE
(Note 5)
SD (Note 7)
9 - 24
9. OPTIONS AND PERIPHERAL EQUIPMENT
(4) Wires
For the brake unit, HIV wire (600 V Grade heat-resistant polyvinyl chloride insulated wire) is
recommended.
POINT
Under tightening can cause a cable disconnection or malfunction. Over
tightening can cause a short circuit or malfunction due to damage to the screw
or the brake unit.
9 - 25
9. OPTIONS AND PERIPHERAL EQUIPMENT
POINT
Some crimp terminals may not be mounted depending on the size. Make sure to
use the recommended ones or equivalent ones.
Number of (Note 1)
Servo amplifier Brake unit connected Crimp terminal (Manufacturer) Applicable
units tool
400 V MR-J4-500_4(-RJ) FR-BU2-H30K 1 FVD5.5-S4 (JST) b
class MR-J4-700_4(-RJ) FR-BU2-H30K 1 FVD5.5-S4 (JST) b
MR-J4-11K_4(-RJ) FR-BU2-H30K 1 FVD5.5-6 (JST) b
FR-BU2-H55K 1 FVD5.5-6 (JST) b
MR-J4-15K_4(-RJ) FR-BU2-H55K 1 FVD5.5-6 (JST) b
MR-J4-22K_4(-RJ) FR-BU2-H55K 1 FVD5.5-8 (JST) b
FR-BU2-H75K 1 FVD14-8 (JST) a
Note 1. Symbols in the applicable tool field indicate applicable tools in (4)(b) of this section.
2. Coat the crimping part with an insulation tube.
9 - 26
9. OPTIONS AND PERIPHERAL EQUIPMENT
9.3.4 Dimensions
[Unit: mm]
FR-BU2-H30K
2-φ5 hole
(Screw size: M4)
5
118
128
Rating
plate
5 5
6 96 6 5 18.5 52 59
108 129.5
FR-BU2-H55K, FR-BU2-H75K
2-φ5 hole
(Screw size: M4)
5
118
128
Rating
plate
5
5
5
6 158 6 18.5 52 72
170 142.5
9 - 27
9. OPTIONS AND PERIPHERAL EQUIPMENT
[Unit: mm]
Approx.
H2
2-φC
D1
(Note)
H3 ± 1
H1 ± 3
H±5
Control circuit (Note)
terminal
Main circuit
terminal
Approx.
C C
H2
Approx. 35 W1 ± 1 Approx. 35
D±5
W±5
Note. Ventilation ports are provided on both sides and the top. The bottom is open.
Approximate
Resistor unit W W1 H H1 H2 H3 D D1 C
mass [kg]
400 V FR-BR-H30K 340 270 600 560 20 582 220 4 10 30
class FR-BR-H55K 480 410 700 620 40 670 450 3.2 12 70
[Unit’ mm]
Approximate
Resistor unit Resistance
mass [kg]
85
400 V
MT-BR5-H75K 6.5 Ω 70
NP class
800
M4
M6
30
40
85
193 189
37 60 10 21
480
510
75 300 75
9 - 28
9. OPTIONS AND PERIPHERAL EQUIPMENT
POINT
When using FR-RC-H, set [Pr. PA04] to "0 0 _ _" to enable EM1 (Forced stop
1).
When using FR-RC-H with MR-J4-_A4(-RJ), set [Pr. PA02] to "_ _ 0 1" and set [Pr. PC27] to "_ _ _ 1". When
using it with MR-J4-_B4(-RJ), set [Pr. PA02] to "_ _ 0 1" and set [Pr. PC20] to "_ _ _ 1".
(1) Selection
The converters can continuously return 75% of the nominal regenerative power. They are applied to the
servo amplifiers of the 5 kW to 22 kW.
Nominal
9 - 29
9. OPTIONS AND PERIPHERAL EQUIPMENT
POINT
In this configuration, only the STO function is supported. The forced stop
deceleration function is not available.
(Note 8)
(Note 8) Servo-on SON ALM RA Malfunction
(Note 3)
Step-down DICOM
transformer
24 V DC
(Note 9)
(Note 2)
P3 P4 N- C P+
(Note 4) 5 m or shorter
RD N/- P/+
Lady A
SE
B
RDY output B
C
C
R/L1 Alarm output
S/L2
T/L3
RX
R
SX (Note 1)
Phase detection
S terminals
TX
T
Power regenerative converter
FR-RC-H
FR-RC-H Operation
B C ALM ready
RA OFF
ON
MC
Forced stop 1 MC
SK
(Note 6)
9 - 30
9. OPTIONS AND PERIPHERAL EQUIPMENT
Note 1. When not using the phase detection terminals, fit the jumpers across RX-R, SX-S and TX-T. If the jumpers remain removed,
the FR-RC-H will not operate.
2. For the servo amplifier of 5 kW and 7 kW, always disconnect the lead wire of built-in regenerative resistor, which is connected
to P+ and C terminals. For the servo amplifier of 11 kW to 22 kW, do not connect a supplied regenerative resistor to the P+
and C terminals.
3. If disabling ALM (Malfunction) output with the parameter, configure up the power supply circuit which switches off the magnetic
contactor after detection of alarm occurrence on the controller side.
4. Always connect between P3 and P4 terminals. (factory-wired) Use either the power factor improving DC reactor or the power
factor improving AC reactor. When using the power factor improving DC reactor, refer to section 9.8.
5. For the power supply specifications, refer to section 1.2.1.
6. Set [Pr. PA04] to "0 0 _ _" to enable EM1 (Forced stop 1). Configure up the circuit which shuts off main circuit power with
external circuit at EM1 (Forced stop 1) off.
7. When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit breaker.
8. This diagram is for sink I/O interface. For source I/O interface, refer to section 3.9.3 in MR-J4-_A(-RJ) Servo Amplifier
Instruction Manual.
9. The illustration of the 24 V DC power supply is divided between input signal and output signal for convinence. However, they
can be configured by one.
(Note 2)
P3 P4 N- C P+
(Note 4) 5 m or shorter
RD N/- P/+
A
Lady SE
B
RDY output B
C
C
R/L1 Alarm output
S/L2
T/L3
RX
R
SX (Note 1)
Phase detection
S terminals
TX
T
Power regenerative converter
FR-RC-H
FR-RC-H Operation
ALM ready
B C RA OFF
ON
MC
Forced stop 1 MC
SK
(Note 6)
9 - 31
9. OPTIONS AND PERIPHERAL EQUIPMENT
Note 1. When not using the phase detection terminals, fit the jumpers across RX-R, SX-S and TX-T. If the jumpers remain removed,
the FR-RC-H will not operate.
2. For the servo amplifier of 5 kW and 7 kW, always disconnect the lead wire of built-in regenerative resistor, which is connected
to P+ and C terminals. For the servo amplifier of 11 kW to 22 kW, do not connect a supplied regenerative resistor to the P+
and C terminals.
3. If disabling ALM (Malfunction) output with the parameter, configure up the power supply circuit which switches off the magnetic
contactor after detection of alarm occurrence on the controller side.
4. Always connect between P3 and P4 terminals. (factory-wired) Use either the power factor improving DC reactor or the power
factor improving AC reactor. When using the power factor improving DC reactor, refer to section 9.8.
5. For the power supply specifications, refer to section 1.2.2.
6. Set [Pr. PA04] to "0 0 _ _" to enable EM1 (Forced stop 1). Configure up the circuit which shuts off main circuit power with
external circuit at EM1 (Forced stop 1) off.
7. When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit breaker.
8. This diagram is for sink I/O interface. For source I/O interface, refer to section 3.8.3 in MR-J4-_B(-RJ) Servo Amplifier
Instruction Manual.
9. The illustration of the 24 V DC power supply is divided between input signal and output signal for convinence. However, they
can be configured by one.
(3) Dimensions
2-φD hole Mounting foot (removable)
E
Mounting foot (movable)
Rating plate
Cooling fan
D F K
EE
AA
C
A
[Unit: mm]
Power regenerative Approximate
A AA B BA C D E EE K F
converter mass [kg]
FR-RC-H15K
340 270 600 582 195 10 10 8 3.2 90 31
FR-RC-H30K
FR-RC-H55K 480 410 700 670 250 12 15 15 3.2 135 55
9 - 32
9. OPTIONS AND PERIPHERAL EQUIPMENT
[Unit: mm]
Power regenerative
(AA) a b D AA BA
(2-φD hole) converter
FR-RC-H15K
330 562 10 270 582
FR-RC-H30K
FR-RC-H55K 470 642 12 410 670
(Mounting hole)
(BA)
9 - 33
9. OPTIONS AND PERIPHERAL EQUIPMENT
POINT
For details of the power regenerative common converter FR-CV-H, refer to the
FR-CV Installation Guide (IB(NA)0600075).
Do not supply power to the main circuit power supply terminals (L1, L2, and L3)
of the servo amplifier. Doing so will fail the servo amplifier and FR-CV-H.
Connect the DC power supply between the FR-CV-H and servo amplifier with
correct polarity. Connection with incorrect polarity will fail the FR-CV-H and
servo amplifier.
Two or more FR-CV-H's cannot be installed to improve regeneration capability.
Two or more FR-CV-H's cannot be connected to the same DC power supply
line.
When using FR-CV-H, set [Pr. PA04] to "0 0 _ _" to enable EM1 (Forced stop 1).
When using FR-CV-H with MR-J4-_A4(-RJ), set [Pr. PA02] to "_ _ 0 1" and set [Pr. PC27] to "_ _ _ 1". When
using it with MR-J4-_B4(-RJ), set [Pr. PA02] to "_ _ 0 1" and set [Pr. PC20] to "_ _ _ 1".
(1) Model
Capacity
Symbol Capacity [kW]
22K 22
30K 30
37K 37
55K 55
(b) FR-CV-H capacity [W] ≥ Total of rated capacities [W] × 2 of servo amplifiers connected to FR-CV-H.
(c) The total of used servo motor rated currents should be equal to or less than the applicable current
[A] of the FR-CV-H.
(d) Among the servo amplifiers connected to the FR-CV-H, the servo amplifier of the maximum capacity
should be equal to or less than the maximum connectable capacity [W].
9 - 34
9. OPTIONS AND PERIPHERAL EQUIPMENT
When using the FR-CV-H, always install the dedicated stand-alone reactor (FR-CVL-H).
Power regenerative common Dedicated stand-alone
converter reactor
FR-CV-H22K(-AT) FR-CVL-H22K
FR-CV-H30K(-AT) FR-CVL-H30K
FR-CV-H37K FR-CVL-H37K
FR-CV-H55K FR-CVL-H55K
POINT
In this configuration, only the STO function is supported. The forced stop
deceleration function is not available.
T/MC1 (Note 1)
SD ALM RA2
RESET
RES
RDYB RA3 (Note 2)
SD
RDYA
(Note 1)
A (Note 1)
RA1 RA2 EM1 OFF RA1
ON
B (Note 2)
MC C RA3 SON
SON
RA1 (Note 4)
MC
EM1
(Note 3) EM1 (Note 1, 6)
RSO RES
SK
SE DICOM
24 V DC (Note 8)
Note 1. Configure a sequence that will shut off main circuit power in the following.
An alarm occurred at FR-CV-H or servo amplifier.
EM1 (Forced stop 1) is enabled.
2. For the servo amplifier, configure a sequence that will switch the servo-on after the FR-CV-H is ready.
3. For the FR-CV-H, the RSO signal turns off when it is put in a ready-to-operate status where the reset signal is input. Configure
a sequence that will make the servo inoperative when the RSO signal is on.
4. Configure a sequence that will make a stop with the forced stop input of the servo amplifier if an alarm occurs in the FR-CV-H.
5. When using FR-CV-H, always disconnect wiring between P3 and P4 terminals.
6. Set [Pr. PA04] to "0 0 _ _" to enable EM1 (Forced stop 1).
7. When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit breaker.
8. The illustration of the 24 V DC power supply is divided between input signal and output signal for convinence. However, they
can be configured by one.
9 - 35
9. OPTIONS AND PERIPHERAL EQUIPMENT
(Note 3)
RSO
(Note 1)
SE
RA1 RA2 EM1 OFF
ON
(Note 1)
A (Note 1, 6)
MC RA1
(Note 4) EM1
B RA1
EM1
MC
C DICOM
SK 24 V DC (Note 8)
Note 1. Configure a sequence that will shut off main circuit power in the following.
An alarm occurred at FR-CV-H or servo amplifier.
EM1 (Forced stop 1) is enabled.
2. For the servo amplifier, configure a sequence that will switch the servo-on after the FR-CV-H is ready.
3. For the FR-CV-H, the RSO signal turns off when it is put in a ready-to-operate status where the reset signal is input. Configure
a sequence that will make the servo inoperative when the RSO signal is on.
4. Configure a sequence that will make a stop with the emergency stop input of the servo system controller if an alarm occurs in
the FR-CV-H. When the servo system controller does not have an emergency stop input, use the forced stop input of the servo
amplifier to make a stop as shown in the diagram.
5. When using FR-CV-H, always disconnect wiring between P3 and P4 terminals.
6. Set [Pr. PA04] to "0 0 _ _" to enable EM1 (Forced stop 1).
7. When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit breaker.
8. The illustration of the 24 V DC power supply is divided between input signal and output signal for convinence. However, they
can be configured by one.
9 - 36
9. OPTIONS AND PERIPHERAL EQUIPMENT
POINT
Selection conditions of wire size is as follows.
Wire type: HIV wire (600 V grade heat-resistant polyvinyl chloride insulated
wire)
Construction condition: One wire is constructed in the air.
2) Grounding
For grounding, use the wire of the size equal to or greater than that indicated in the following
table, and make it as short as possible.
Power regenerative common Grounding wire size
2
converter [mm ]
FR-CV-H22K/FR-CV-H30K 8 (AWG 8)
FR-CV-H37K/FR-CV-H55K 14 (AWG 6)
9 - 37
9. OPTIONS AND PERIPHERAL EQUIPMENT
(b) The inputs/outputs (main circuits) of the FR-CV-H and servo amplifiers include high-frequency
components and may provide electromagnetic wave interference to communication equipment (such
as AM radios) used near them. In this case, interference can be reduced by installing the radio noise
filter (FR-BIF-H) or line noise filter (FR-BSF01, FR-BLF).
(c) The overall wiring length for connection of the DC power supply between the FR-CV-H and servo
amplifiers should be 5 m or less, and the wiring must be twisted.
(6) Specifications
Power regenerative common
converter FR-CV-H_
22K 30K 37K 55K
Item
Total of connectable servo amplifier
[kW] 11 15 185 27.5
capacities
Maximum servo amplifier capacity [kW] 11 15 15 22
Total of connectable servo
[A] 43 57 71 110
motor rated currents
Output
Note 1. This is the time when the protective function of the FR-CV is activated. The protective function of the
servo amplifier is activated in the time indicated in section 8.1.
2. The specified value is the power supply capacity of FR-CV-H. The total power supply capacities of
the connected servo amplifiers are actually required.
9 - 38
9. OPTIONS AND PERIPHERAL EQUIPMENT
POINT
To comply with the UL/CSA standard, use the wires shown in appendix 1 for
wiring. To comply with other standards, use a wire that is complied with each
standard.
Selection conditions of wire size is as follows.
Construction condition: One wire is constructed in the air.
Wire length: 30 m or less
The following diagram shows the wires used for wiring. Use the wires given in this section or equivalent.
1) Main circuit power supply lead
Servo amplifier
Power supply
L1 U
L2 V M
L3 W
2) Control circuit power supply lead
L11
L21 4) Servo motor power lead
Regenerative option
C
P+
9 - 39
9. OPTIONS AND PERIPHERAL EQUIPMENT
(1) When using the 600 V Grade heat-resistant polyvinyl chloride insulated wire (HIV wire)
Wire size selection examples for HIV wires are indicated below.
Note 1. Alphabets in the table indicate crimping tools. For crimp terminals and applicable tools, refer to (2)
in this section.
2. To connect these models to a terminal block, be sure to use the screws that come with the
terminal block.
3. The wire size shows applicable size of the servo amplifier connector and terminal block. For wires
connecting to the servo motor, refer to each servo amplifier instruction manual.
2
4. Be sure to use the size of 2 mm when corresponding to UL/CSA standard.
5. This is for connecting to the linear servo motor with natural cooling method.
6. This is for connecting to the linear servo motor with liquid cooling method.
Use wires (5)) of the following sizes with the power regenerative converter (FR-RC-H).
2
Model Wire [mm ]
FR-RC-H15K
FR-RC- H30K 14 (AWG6)
FR-RC- H55K
Note. Some crimp terminals may not be mounted depending on the size. Make sure to use the
recommended ones or equivalent ones.
9 - 40
9. OPTIONS AND PERIPHERAL EQUIPMENT
Note 1. When having the servo amplifier comply with the UL/CSA standard, refer to appendix 1.
2. Use a magnetic contactor with an operation delay time (interval between current being applied to
the coil until closure of contacts) of 80 ms or less.
Note. When having the servo amplifier comply with the UL/CSA standard, refer to appendix 1.
The following shows the advantages of using power factor improving DC reactor.
It improves the power factor by increasing the form factor of the servo amplifier's input current.
It decreases the power supply capacity.
The input power factor is improved to about 85%.
As compared to the power factor improving AC reactor (FR-HAL-H), it decreases the loss.
When connecting the power factor improving DC reactor to the servo amplifier, always disconnect P3 and
P4. If it remains connected, the effect of the power factor improving DC reactor is not produced.
When used, the power factor improving DC reactor generates heat. To release heat, therefore, leave a 10
cm or more clearance at each of the top and bottom, and a 5 cm or more clearance on each side.
9 - 41
9. OPTIONS AND PERIPHERAL EQUIPMENT
H ± 2.5
W1 D2 W1 D2
W ± 2.5 D1 ± 1 W ± 2.5 D1 ± 1
D or less
(D3)
P P1
H ± 2.5
6
W1 D2
W ± 2.5 D1 ± 1
Fig. 9.3
Servo amplifier
FR-HEL
P3
(Note 2)
P4
5 m or less
9 - 42
9. OPTIONS AND PERIPHERAL EQUIPMENT
9 - 43
9. OPTIONS AND PERIPHERAL EQUIPMENT
The following shows the advantages of using power factor improving AC reactor.
It improves the power factor by increasing the form factor of the servo amplifier's input current.
It decreases the power supply capacity.
The input power factor is improved to about 80%.
When using power factor improving reactors for two servo amplifiers or more, be sure to connect a power
factor improving reactor to each servo amplifier. If using only one power factor improving reactor, enough
improvement effect of phase factor cannot be obtained unless all servo amplifiers are operated.
4-d mounting hole (Note)
(φ5 groove)
R X S Y T Z
D or less
Servo amplifier
3-phase
400 V class
FR-HAL-H
MCCB MC R X
L1
3-phase S Y
380 V AC to L2
H±5
480 V AC T Z
L3
W1 D2
W ± 0.5 D1
Fig. 9.4
R X S Y T Z
R X S Y T Z
4-d mounting hole (Note)
4-d mounting hole (Note)
(φ6 groove)
(φ8 groove)
150 D or less
125 D or less
H±5
H±5
180
W1 D2
W1 D2
D1 W ± 0.5 D1
W ± 0.5
9 - 44
9. OPTIONS AND PERIPHERAL EQUIPMENT
Note. Maximum dimensions. The dimension varies depending on the input/output lines.
Noises are classified into external noises which enter the servo amplifier to cause it to malfunction and those
radiated by the servo amplifier to cause peripheral equipment to malfunction. Since the servo amplifier is an
electronic device which handles small signals, the following general noise reduction techniques are required.
Also, the servo amplifier can be a source of noise as its outputs are chopped by high carrier frequencies. If
peripheral equipment malfunction due to noises produced by the servo amplifier, noise suppression
measures must be taken. The measures will vary slightly with the routes of noise transmission.
(b) Reduction techniques for external noises that cause the servo amplifier to malfunction
If there are noise sources (such as a magnetic contactor, an electromagnetic brake, and many
relays which make a large amount of noise) near the servo amplifier and the servo amplifier may
malfunction, the following countermeasures are required.
Provide surge absorbers on the noise sources to suppress noises.
Attach data line filters to the signal cables.
Ground the shields of the encoder connecting cable and the control signal cables with cable clamp
fittings.
Although a surge absorber is built into the servo amplifier, to protect the servo amplifier and other
equipment against large exogenous noise and lightning surge, attaching a varistor to the power
input section of the equipment is recommended.
9 - 45
9. OPTIONS AND PERIPHERAL EQUIPMENT
(c) Techniques for noises radiated by the servo amplifier that cause peripheral equipment to malfunction
Noises produced by the servo amplifier are classified into those radiated from the cables connected
to the servo amplifier and its main circuits (input and output circuits), those induced
electromagnetically or statically by the signal cables of the peripheral equipment located near the
main circuit cables, and those transmitted through the power supply cables.
Static induction
Route 6)
noise
9 - 46
9. OPTIONS AND PERIPHERAL EQUIPMENT
5)
7) 7)
2)
7)
Sensor
power
1) supply
Servo
2)
amplifier
Instrument Receiver
3)
8)
6)
4) Sensor
3)
Servo motor M
Noise transmission
Suppression techniques
route
When measuring instruments, receivers, sensors, etc. which handle weak signals and may
malfunction due to noise and/or their signal cables are contained in a cabinet together with the servo
amplifier or run near the servo amplifier, such devices may malfunction due to noises transmitted
through the air. The following techniques are required.
1. Provide maximum clearance between easily affected devices and the servo amplifier.
1) 2) 3) 2. Provide maximum clearance between easily affected signal cables and the I/O cables of the servo
amplifier.
3. Avoid wiring the power lines (input/output lines of the servo amplifier) and signal lines side by side
or bundling them together.
4. Insert a line noise filter to the I/O cables or a radio noise filter on the input line.
5. Use shielded wires for the signal and power lines, or put the lines in separate metal conduits.
When the power lines and the signal lines are laid side by side or bundled together, magnetic
induction noise and static induction noise will be transmitted through the signal cables and
malfunction may occur. The following techniques are required.
1. Provide maximum clearance between easily affected devices and the servo amplifier.
4) 5) 6) 2. Provide maximum clearance between easily affected signal cables and the I/O cables of the servo
amplifier.
3. Avoid wiring the power lines (input/output lines of the servo amplifier) and signal lines side by side
or bundling them together.
4. Use shielded wires for the signal and power lines, or put the lines in separate metal conduits.
When the power supply of peripheral equipment is connected to the power supply of the servo
amplifier system, noises produced by the servo amplifier may be transmitted back through the power
7) supply cable and the devices may malfunction.The following techniques are required.
1. Install the radio noise filter (FR-BIF-H) on the power lines (Input lines) of the servo amplifier.
2. Install the line noise filter (FR-BSF01/FR-BLF) on the power lines of the servo amplifier.
When the cables of peripheral equipment are connected to the servo amplifier to make a closed loop
8) circuit, leakage current may flow to malfunction the peripheral equipment. If so, malfunction may be
prevented by disconnecting the grounding cable of the peripheral device.
9 - 47
9. OPTIONS AND PERIPHERAL EQUIPMENT
13 ± 1
80 150
TDK
30 ± 1
Product name Lot number
Outline drawing (ZCAT3035-1330)
MC
SK
Relay
Surge killer
Surge killer
Maximum current: Not less than twice the drive current of the relay or the
like. Diode
9 - 48
9. OPTIONS AND PERIPHERAL EQUIPMENT
cable
40
External conductor
Clamp section diagram
Dimensions
30
L or less 10
B ± 0.3
C
A
6
24 -0.2
0
35
3
24+ 00.3
7
(Note) M4 screw 6 22
35
11
Note. Screw hole for grounding. Connect it to the grounding plate of the cabinet.
9 - 49
9. OPTIONS AND PERIPHERAL EQUIPMENT
Approx. 22.5
of the filter rises as the number of passes increases, but generally
four passes would be appropriate. For the servo motor power
lines, passes must be four times or less. Do not pass the
11.25 ± 0.5
grounding wire through the filter. or the effect of the filter will drop. Approx. 65
Wind the wires by passing through the filter to satisfy the required
number of passes as shown in Example 1. If the wires are too φ33
thick to wind, use two or more filters to have the required number
of passes as shown in Example 2.
Approx. 65
Place the line noise filters as close to the servo amplifier as
possible for their best performance.
4.5
Example 1
MCCB MC Servo amplifier
Power L1
supply
L2 2
FR-BLF (for wire size 5.5 mm (AWG 10) or more))
Line noise L3
filter 7
(Number of turns: 4)
31.5
7
Example 2 130
MCCB MC 85
Power Servo amplifier
80
35
supply
L1
Line noise L2 160
2.3
filter L3 180
9 - 50
9. OPTIONS AND PERIPHERAL EQUIPMENT
Approx. 300
Terminal
block Servo amplifier
MCCB MC
L1
Power 29
supply L2
φ5
L3
42
hole
4
58 29 7
Radio noise
filter 44
MR-J4-500_4(-RJ) or more
Servo amplifier
MCCB MC
L1
Power L2
supply
L3
Radio noise
filter
9 - 51
9. OPTIONS AND PERIPHERAL EQUIPMENT
[Unit: mm]
D H T E (Note) L φd W
D T Model
Max. Max. Max. ±1.0 min. ±0.05 ±1.0
TND20V-102K 22.5 25.5 9.5 6.4 20 0.8 10.0
H
Note. For special purpose items for lead length (L), contact the manufacturer.
W E
L
9 - 52
9. OPTIONS AND PERIPHERAL EQUIPMENT
Rated sensitivity current ≥ 10 • {Ig1 + Ign + Iga + K • (Ig2 + Igm)} [mA]··············································· (9.1)
Ig1: Leakage current on the electric channel from the earth-leakage current breaker to the input
terminals of the servo amplifier (Found from Fig. 9.7.)
Ig2: Leakage current on the electric channel from the output terminals of the servo amplifier to the servo
motor (Found from Fig. 9.7.)
Ign: Leakage current when a filter is connected to the input side (4.4 mA per one FR-BIF-H)
Iga: Leakage current of the servo amplifier (Found from table 9.3.)
Igm: Leakage current of the servo motor (Found from table 9.2.)
120
Leakage current [mA]
100
80
60
40
20
0
2 5.5 14 38 100
3.5 8 22 60 150
30 80
Cable size [mm2]
Fig. 9.7 Example of leakage current per km (lg1, lg2) for CV cable run in metal conduit
9 - 53
9. OPTIONS AND PERIPHERAL EQUIPMENT
9 - 54
9. OPTIONS AND PERIPHERAL EQUIPMENT
NV
Servo amplifier
MR-J4-60A4 M Servo motor
HG-SR524
5
Ig1 = 20 • = 0.1 [mA]
1000
5
Ig2 = 20 • = 0.1 [mA]
1000
According to the result of calculation, use an earth-leakage current breaker having the rated sensitivity
current (Ig) of 4.0 mA or more.
An earth-leakage current breaker having Ig of 15 mA is used with the NV-SP/SW/CP/CW/HW series.
9 - 55
9. OPTIONS AND PERIPHERAL EQUIPMENT
It is recommended that one of the following filters be used to comply with EN EMC directive. Some EMC
filters have large in leakage current.
9 - 56
9. OPTIONS AND PERIPHERAL EQUIPMENT
(3) Dimensions
(a) EMC filter
TF3005C-TX/TX3020C-TX/TF3030C-TX
[Unit: mm]
125 ± 2
140 ± 1
155 ± 2
16 16
IN
290 ± 2 150 ± 2
332 ± 5 170 ± 5
9 - 57
9. OPTIONS AND PERIPHERAL EQUIPMENT
TF3040C-TX/TF3060C-TX
[Unit: mm]
3-M6 8-M M4 M4 3-M6
M6
Approx. 17
22 22
G±2
E±2
F±1
IN
C±2 K±2
B±5 Approx. J
A±5 H±5
Dimensions [mm]
Model
A B C D E F G H J K L M
TF3040C-TX R3.25 Length
438 412 390 100 175 160 145 200 (190) 180 (91.5)
TF3060C-TX 8 (for M6)
9 - 58
10. USING A LINEAR SERVO MOTOR
When using the linear servo motor, read "Linear Servo Motor Instruction Manual"
WARNING and "Linear Encoder Instruction Manual".
The items in the following table are the same as those for MR-J4-_A(-RJ) or MR-J4-_B(-RJ) servo amplifier.
For details of the items, refer to each chapter/section of the detailed explanation field.
Model Item Detailed explanation
MR-J4-_A4(-RJ) Functions and configuration MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 15.1
Operation and functions MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 15.3
How to replace servo amplifier without MR-J4-_A(-RJ) Servo Amplifier Instruction
magnetic pole detection Manual app. 10
MR-J4-_B4(-RJ) Functions and configuration MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 14.1
Operation and functions MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 14.3
How to replace servo amplifier without MR-J4-_B(-RJ) Servo Amplifier Instruction
magnetic pole detection Manual app. 8
Refer to [Pr. PA17 Servo motor series setting] and [Pr. PA18 Servo motor type setting] for setting the linear
servo motor.
10 - 1
10. USING A LINEAR SERVO MOTOR
Any person who is involved in wiring should be fully competent to do the work.
Before wiring, turn off the power and wait for 15 minutes or more until the charge
lamp turns off. Then, confirm that the voltage between P+ and N- is safe with a
voltage tester and others. Otherwise, an electric shock may occur. In addition,
when confirming whether the charge lamp is off or not, always confirm it from the
front of the servo amplifier.
WARNING Ground the servo amplifier and the linear servo motor securely.
Do not attempt to wire the servo amplifier and the linear servo motor until they
have been installed. Otherwise, it may cause an electric shock.
The cables should not be damaged, stressed, loaded, or pinched. Otherwise, it
may cause an electric shock.
To avoid an electric shock, insulate the connections of the power supply
terminals.
Wire the equipment correctly and securely. Otherwise, the linear servo motor may
operate unexpectedly, resulting in injury.
Connect cables to the correct terminals. Otherwise, a burst, damage, etc. may
occur.
Ensure that polarity (+/-) is correct. Otherwise, a burst, damage, etc. may occur.
The surge absorbing diode installed to the DC relay for control output should be
fitted in the specified direction. Otherwise, the emergency stop and other
protective circuits may not operate.
Servo amplifier Servo amplifier
24 V DC 24 V DC
DOCOM DOCOM
Control output RA
Control output RA
signal signal
For sink output interface For source output interface
10 - 2
10. USING A LINEAR SERVO MOTOR
Connecting a linear servo motor of the wrong axis to the U, V, W, or CN2 may
cause a malfunction.
Do not modify the equipment.
CAUTION The cables such as power wires deriving from the primary side cannot stand the
long-term bending action. Avoid the bending action by fixing the cables to the
moving part, etc. Also, use the cable that stands the long-term bending action for
the wiring to the servo amplifier.
This section does not describe the following items. For details of the items, refer to each section of the
detailed description field.
Model Item Detailed explanation
MR-J4-_A4 (-RJ) Input power supply circuit MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 3.1
Explanation of power supply system MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 3.3
Signal (device) explanations MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 3.5
Alarm occurrence timing chart MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 3.8
Interface MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 3.9
Grounding MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 3.11
Display and operation sections MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual section 4.5
MR-J4-_B4 (-RJ) Input power supply circuit MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 3.1
Explanation of power supply system MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 3.3
Signal (device) explanations MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 3.5
Alarm occurrence timing chart MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 3.7
Interface MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 3.8
SSCNET III cable connection MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 3.9
Grounding MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual section 3.11
Switch setting and display of the servo MR-J4-_B(-RJ) Servo Amplifier Instruction
amplifier Manual section 4.3
10 - 3
10. USING A LINEAR SERVO MOTOR
10.2 Characteristics
An electronic thermal is built in the servo amplifier to protect the linear servo motor, servo amplifier and
linear servo motor power wires from overloads.
[AL. 50 Overload 1] occurs if overload operation performed is above the electronic thermal protection curve
shown in fig. 10.1. [AL. 51 Overload 2] occurs if the maximum current is applied continuously for several
seconds due to machine collision, etc. Use the equipment on the left-side area of the continuous or broken
line in the graph.
This servo amplifier has solid-state linear servo motor overload protection. (The servo motor overload
current (full load current) is set on the basis of 120% rated current of the servo amplifier.)
1000 1000
100 100
Operating Operating
Operation time [s]
10 10 Servo-lock
Servo-lock
1 1
0.1 0.1
0 100 200 300 400 500 600 0 50 100 150 200 250 300
Load ratio [%] Load ratio [%]
10 - 4
10. USING A LINEAR SERVO MOTOR
Table 10.1 indicates servo amplifiers' power supply capacities and losses generated under rated load. For
thermal design of an enclosed type cabinet, use the values in the table in consideration for the worst
operating conditions. The actual amount of generated heat will be intermediate between values at rated
torque and servo-off according to the duty used during operation. When the linear servo motor is run at less
than the rated speed, the power supply capacity will be smaller than the value in the table, but the servo
amplifier's generated heat will not change.
Mounting a heat sink outside of the cabinet enables to reduce heat in the cabinet and design a compact
enclosed type cabinet.
Table 10.1 Power supply capacity and generated loss per linear servo motor at rated output
Power supply Servo amplifier-generated heat [W] Area required for
Linear servo motor Servo amplifier capacity [kVA] (Note 2) heat dissipation
(Note 1) At rated output With servo-off [m2]
LM-FP5H-60M-1SS0 MR-J4-22KB4(-RJ) 22 640 45 12.8
MR-J4-22KA4(-RJ)
Note 1. Note that the power supply capacity will vary according to the power supply impedance. This value is applicable when the
power factor improving AC reactor or power factor improving DC reactor are not used.
2. Heat generated during regeneration is not included in the servo amplifier-generated heat. To calculate heat generated by the
regenerative option, refer to section 9.2.
10 - 5
10. USING A LINEAR SERVO MOTOR
POINT
Do not use dynamic brake to stop in a normal operation as it is the function to
stop in emergency.
For a machine operating at the recommended load to motor mass ratio or less,
the estimated number of usage times of the dynamic brake is 1000 times while
the machine decelerates from the rated speed to a stop once in 10 minutes.
Be sure to enable EM1 (Forced stop 1) after the linear servo motor stops when
using EM1 (Forced stop 1) frequently in other than emergency.
The approximate coasting distance from when the dynamic break is activated until when the linear servo
motor stops can be calculated with the equation below.
10 - 6
10. USING A LINEAR SERVO MOTOR
10.2.4 Permissible load to motor mass ratio when the dynamic brake is used
Use the dynamic brake under the load to motor mass ratio indicated in the following table. If the ratio is
higher than this value, the dynamic brake may burn. If there is a possibility that the ratio may exceed the
value, contact your local sales office.
The values of the permissible load to motor mass ratio in the table are the values when the linear servo
motor is used at the maximum speed.
Permissible load to motor mass ratio
Linear servo motor
[Multiplier]
LM-F series 100
When actual speed does not reach the maximum speed of the servo motor, calculate the permissible load to
motor mass ratio at the time of using the dynamic brake by the following equation. (The upper limit is 300
times.)
Permissible load to motor mass ratio of the dynamic brake = Value in the table × (Servo motor maximum
speed2/Actual using speed2)
10 - 7
10. USING A LINEAR SERVO MOTOR
MEMO
10 - 8
APPENDIX
This appendix does not describe the following items. For details of the items, refer to each section of the
detailed description field.
Model Item Detailed explanation
MR-J4-_A4(-RJ) Peripheral equipment manufacturer (for MR-J4-_A(-RJ) Servo Amplifier Instruction
reference) Manual app. 1
Handling of AC servo amplifier batteries for MR-J4-_A(-RJ) Servo Amplifier Instruction
the United Nations Recommendations on the Manual app. 2
Transport of Dangerous Goods
Symbol for the new EU Battery Directive MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual app. 3
MR-J3-D05 Safety logic unit MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual app. 5
EC declaration of conformity MR-J4-_A(-RJ) Servo Amplifier Instruction
Manual app. 6
MR-J4-_B4(-RJ) Peripheral equipment manufacturer (for MR-J4-_B(-RJ) Servo Amplifier Instruction
reference) Manual app. 1
Handling of AC servo amplifier batteries for MR-J4-_B(-RJ) Servo Amplifier Instruction
the United Nations Recommendations on the Manual app. 2
Transport of Dangerous Goods
Symbol for the new EU Battery Directive MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual app. 3
MR-J3-D05 Safety logic unit MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual app. 5
EC declaration of conformity MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual app. 6
SSCNET III cable (SC-J3BUS_M-C) MR-J4-_B(-RJ) Servo Amplifier Instruction
manufactured by Mitsubishi Electric System & Manual app. 10
Service
J3 compatibility mode MR-J4-_B(-RJ) Servo Amplifier Instruction
Manual app. 12
This section explains safety of users and machine operators. Please read the section carefully before
mounting the equipment.
(2) A person who can access to operating manuals for the protective devices (e.g. light curtain) connected
to the safety control system.
A person who have read and familiarized himself/herself with the manuals.
App. - 1
APPENDIX
Always use the MR-J4 servo amplifiers within specifications (voltage, temperature, etc. Refer to section 1.2
for details.). Mitsubishi Electric Co. accepts no claims for liability if the equipment is used in any other way or
if modifications are made to the device, even in the context of mounting and installation.
It takes 15 minutes for capacitor discharging. Do not touch the unit and terminals
WARNING immediately after power off.
Note 1. To connect these models to a terminal block, be sure to use the screws that come with the terminal block.
2. Alphabets in the table indicate crimping tools. Refer to the following table for the crimp terminals and crimping tools.
3. Select wire sizes depending on the rated output of the servo motors. The values in the table are sizes based on rated output of
the servo amplifiers.
App. - 2
APPENDIX
Note. Some crimp terminals may not be mounted depending on the size. Make sure to use the
recommended ones or equivalent ones.
App. - 3
APPENDIX
(d) Grounding
To prevent an electric shock, always connect the protective earth (PE) terminal (marked ) of the
servo amplifier to the protective earth (PE) of the cabinet. Do not connect two grounding cables to
the same protective earth (PE) terminal. Always connect cables to the terminals one-to-one.
PE
terminals PE
terminals
If using an earth-leakage current breaker, always ground the protective earth (PE) terminal of the
servo amplifier to prevent an electric shock. Only an RCD (earth-leakage current breaker) of type B
can be used for the power supply side of the product.
(2) EU compliance
The MR-J4 servo amplifiers are designed to comply with the following directions to meet requirements
for mounting, using, and periodic technical inspections: Machinery directive (2006/42/EC), EMC directive
(2004/108/EC), and Low-voltage directive (2006/95/EC).
(a) Installation
The minimum cabinet size is 150% of each MR-J4 servo amplifier's volume. Also, design the cabinet
so that the ambient temperature in the cabinet is 55 ˚C or less. The servo amplifier must be installed
in a metal cabinet. Environment is open type (UL 50) and overvoltage category III. The servo
amplifier needs to be installed at or below of pollution degree 2. Use copper conductors only.
App. - 4
APPENDIX
App. 1.2.4 General cautions for safety protection and protective measures
Observe the following items to ensure proper use of the MELSERVO MR-J4 servo amplifiers.
(1) For safety components and installing systems, only qualified personnel and professional engineers
should perform.
(2) When mounting, installing, and using the MELSERVO MR-J4 servo amplifier, always observe standards
and directives applicable in the country.
(3) The item about noises of the test notices in the manuals should be observed.
(4) The MR-J4 servo amplifiers fulfill the requirements to conducted emissions at the main connections in
the frequency range from 150 kHz to 30 MHz. (Bases for the evaluation: Product standard IEC/EN
61800, adjustable speed electrical power drive systems, Part 3: EMC)
App. - 5
APPENDIX
(1) Be sure that all safety related switches, relays, sensors, etc., meet the required safety standards.
(2) Perform all risk assessments and safety level certification to the machine or the system as a whole.
(3) If the upper and lower power module in the servo amplifier are shorted and damaged simultaneously,
the servo motor may make a half revolution at a maximum.
(4) Only qualified personnel are authorized to install, start-up, repair or service the machines in which these
components are installed. Only trained engineers should install and operate the equipment. (ISO 13849-
1 Table F.1 No.5)
(5) Separate the wiring for safety function from other signal wirings. (ISO 13849-1 Table F.1 No.1)
(6) Protect the cables with appropriate ways (routing them in a cabinet, using a cable guard, etc.).
(7) Keep the required clearance/creepage distance depending on voltage you use.
Disposal of unusable or irreparable devices should always occur in accordance with the applicable country-
specific waste disposal regulations.
(Example: European Waste 16 02 14)
To transport lithium batteries, take actions to comply with the instructions and regulations such as the United
Nations (UN), the International Civil Aviation Organization (ICAO), and the International Maritime
Organization (IMO).
The battery options (MR-BAT6V1SET and MR-BAT6V1) are assembled batteries from lithium metal battery
CR17335A which are not subject to the dangerous goods (Class 9) of the UN Recommendations.
App. - 6
APPENDIX
The devices must be installed in the specified direction. Not doing so may cause
a malfunction.
CAUTION Mount the servo amplifier on a cabinet which meets IP54 in the correct vertical
direction to maintain pollution degree 2.
40 mm
or more 80 mm or longer
for wiring
Servo amplifier
10 mm or 10 mm or Servo amplifier
more more
40 mm
or more
(Note)
Bottom
Note. For 11 kW to 22 kW servo amplifiers, the clearance between the bottom and ground
will be 120 mm or more.
App. - 7
APPENDIX
Turn off the molded-case circuit breaker (MCCB) to avoid electrical shocks or
WARNING damages to the product before starting the installation or wiring.
The installation complies with IEC/EN 60204-1. The voltage supply to machines
must be 20 ms of immunity to instantaneous power failures as specified in
CAUTION IEC/EN 60204-1.
Connecting a servo motor of the wrong axis to U, V, W, or CN2_ of the servo
amplifier may cause a malfunction.
The following shows representative configuration diagram examples to conform to the IEC/EN/UL/CSA
standards.
(3-phase
400 V AC)
Servo amplifier
MCCB MC L1 L2 L3 P+
or fuse C
D
N-
L11
L21 CN8
STO
(Note) CN1
MCCB Controller
or fuse CN2 Encoder cable
PE
U/V/W/PE
Cabinet side
Machine side
Servo motor
Encoder
Note. When the wire sizes of L1 and L11 are the same, MCCB or fuse is not required.
The control circuit connectors described by rectangles are safely separated from the main circuits described
by circles.
The connected motors will be limited as follows.
(2) Using a servo motor complied with IEC60034-1 and Mitsubishi Electric encoder (OBA, OSA)
App. - 8
APPENDIX
The following shows MR-J4-60B4 signals as a typical example. Refer to section 3.4 of "MR-J4-_A(-RJ)
Servo Amplifier Instruction Manual" or "MR-J4-_B(-RJ) Servo Amplifier Instruction Manual" for other servo
amplifiers.
CN3
STO I/O signal 1 11
connector 2 12
CN8 LG LG
DI1 DI2
3 13
2 1 4 14
DOCOM MBR
MO1 MO2
5 15
4 3
6 16
STO1 STOCOM DICOM ALM
LA LAR
6 5 7 17
TOFB1 STO2 8 18
LB LBR
8 7 LZ LZR
9 19
TOFCOM TOFB2 10 20
INP DI3
DICOM EM2
Input device
Symbol Device Connector Pin No.
EM2 Forced stop 2 CN3 20
STOCOM Common terminal for input signals STO1/STO2 3
STO1 STO1 state input CN8 4
STO2 STO2 state input 5
Output device
Symbol Device Connector Pin No.
TOFCOM Common terminal for monitor output signal in STO state 8
TOFB1 Monitor output signal in STO1 state CN8 6
TOFB2 Monitor output signal in STO2 state 7
Power supply
Symbol Device Connector Pin No.
DICOM Digital I/F power supply input 5, 10
DOCOM Digital I/F common CN3 3
SD Shield Plate
App. - 9
APPENDIX
Do not perform insulation resistance test on the servo amplifier. Otherwise, it may
CAUTION cause a malfunction.
Do not disassemble and/or repair the equipment on customer side.
(1) Check for loose terminal block screws. Retighten any loose screws.
Tightening torque [N•m]
Servo amplifier
L1 L2 L3 N- P3 P4 P+ C L11 L21 U V W PE
MR-J4-60_4/MR-J4-100_4/
1.2
MR-J4-200_4/MR-J4-350_4
MR-J4-500_4 1.2 0.8 1.2
MR-J4-700_4 1.2 0.8 1.2
MR-J4-11K_4/MR-J4-15K_4 3.0 1.2 3.0
MR-J4-22K_4 6.0 1.2 6.0
(2) Check servo motor bearings, brake section, etc. for unusual noise.
(3) Check the cables and the like for scratches or cracks. Perform periodic inspection according to
operating conditions.
(4) Check that the connectors are securely connected to the servo motor.
(5) Check that the wires are not coming out from the connector.
(7) Check for unusual noise generated from the servo amplifier.
(8) Check the servo motor shaft and coupling for connection.
App. - 10
APPENDIX
Service lives of the following parts are listed below. However, the service life vary depending or operating
methods and environment. If any fault is found in the parts, they must be replaced immediately regardless of
their service lives. For parts replacement, please contact your local sales office.
Part name Life guideline
Smoothing capacitor (Note 3) 10 years
Number of power-on, forced stop and controller forced
Relay stop times: 100 000 times
Number of on and off for STO: 1,000,000 times
Cooling fan 10,000 hours to 30,000 hours (2 years to 3 years)
Rotary servo motor battery backup time Approximately 20,000 hours (equipment power supply:
(Note 1) off, ambient temperature: 20 ˚C)
(Note 2) Battery life 5 years from date of manufacture
Note 1. The data-holding time using a battery of MR-BAT6V1SET on condition that the power supply of
the servo amplifier is off. Replace the batteries within three years since the operation start
whether the power supply of the servo amplifier is on/off. If the battery is used out of
specification, [AL. 25 Absolute position erased] may occur.
2. Quality of the batteries degrades by the storage condition. The battery life is 5 years from the
production date regardless of the connection status.
3. The characteristic of smoothing capacitor is deteriorated due to ripple currents, etc. The life of
the capacitor greatly depends on ambient temperature and operating conditions. The capacitor
will reach the end of its life in 10 years of continuous operation in normal air-conditioned
environment (40 ˚C surrounding air temperature or less).
App. - 11
APPENDIX
When you keep or use it, please fulfill the following environment.
Item Environment
Operation [°C] 0 to 55 Class 3K3 (IEC/EN 60721-3-3)
Ambient
Transportation (Note) [°C] -20 to 65 Class 2K4 (IEC/EN 60721-3-2)
temperature
Storage (Note) [°C] -20 to 65 Class 1K4 (IEC/EN 60721-3-1)
Ambient Operation, transportation,
5% to 90 %RH
humidity storage
10 Hz to 57 Hz with constant deviation of 0.075 mm
2
Test values 57 Hz to 150 Hz with constant acceleration of 9.8 m/s (1 g) to IEC/EN 61800-5-1 (Test
Vibration Fc of IEC 60068-2-6)
2
load Operation 5.9 m/s (0.6 g)
Transportation (Note) Class 2M3 (IEC/EN 60721-3-2)
Storage Class 1M2 (IEC/EN 60721-3-2)
Pollution degree 2
Except terminal block IP20 (IEC/EN 60529) and fan finger guard
IP rating
Open type (UL 50)
Operation, storage 1000 m or less above sea level
Altitude
Transportation 10000 m or less above sea level
App. - 12
APPENDIX
App. - 13
APPENDIX
The following items must be satisfied by the initial test operation at least. The manufacturer/installer must
be responsible for checking the standards in the items.
Maintain and keep this checklist with related documents of machines to use this for periodic inspection.
1. Is it based on directive/standard applied to the machine? Yes [ ], No [ ]
2. Is directive/standard contained in Declaration of Conformity (DoC)? Yes [ ], No [ ]
3. Does the protection instrument conform to the category required? Yes [ ], No [ ]
4. Are electric shock protective measures (protection class) effective? Yes [ ], No [ ]
5. Is the STO function checked (test of all the shut-off wiring)? Yes [ ], No [ ]
Checking the items will not be instead of the first test operation or periodic inspection by professional
engineers.
POINT
A voltage of analog monitor output may be irregular at power-on.
(1) Setting
Change the following digits of [Pr. PC14] and [Pr. PC15].
[Pr. PC14]
0 0
Analog monitor 1 output selection
(the signal provided to the output across MO1 and LG)
[Pr. PC15]
0 0
Analog monitor 2 output selection
(the signal provided to the output across MO2 and LG)
[Pr. PC39] and [Pr. PC40] can be used to set the offset voltages to the analog output voltages. Setting
value is -9999 mV to 9999 mV.
Parameter Description Setting range [mV]
This is used to set the offset voltage of MO1 (Analog monitor
PC39
1).
-9999 to 9999
This is used to set the offset voltage of MO2 (Analog monitor
PC40
2).
App. - 14
APPENDIX
(2) Setting
POINT
When you use a linear servo motor, replace the following left words to the right
words.
(servo motor) speed [r/min] →(linear servo motor) speed [mm/s]
CCW direction →Positive direction
CW direction →Negative direction
Torque [N•m] →Thrust[N]
The servo amplifier is factory-set to output the servo motor speed to MO1 (Analog monitor 1) and the
torque to MO2 (Analog monitor 2). The setting can be changed by setting in [Pr. PC09] and [Pr. PC10]
as follows.
Refer to (3) for the detection point.
Setting Setting
Output item Description Output item Description
value value
00 Servo motor speed 01 Torque Power running in
CCW direction CCW direction
8 [V] 8 [V]
-8 [V] -8 [V]
CW direction Power running in
CW direction
-8 [V] -8 [V]
CW direction CW direction
06 Servo motor-side droop CCW direction 07 Servo motor-side droop CCW direction
10 [V] 10 [V]
pulses pulses
(Note 1, 3, 5, 6) (Note 1, 3, 5, 6)
(±10 V/100 pulses) 100 [pulse] (±10 V/1000 pulses) 1000 [pulse]
0 100 [pulse] 0 1000 [pulse]
08 Servo motor-side droop CCW direction 09 Servo motor-side droop CCW direction
10 [V] 10 [V]
pulses pulses
(Note 1, 3, 5, 6) (Note 1, 3, 5, 6)
(±10 V/10000 pulses) 10000 [pulse] (±10 V/100000 pulses) 100000 [pulse]
0 10000 [pulse] 0 100000 [pulse]
App. - 15
APPENDIX
Setting Setting
Output item Description Output item Description
value value
0A Feedback position CCW direction 0B Feedback position CCW direction
10 [V] 10 [V]
(Note 1, 2, 3) (Note 1, 2, 3)
(±10 V/1 Mpulses) (±10 V/10 Mpulses)
1 [Mpulse] 10 [Mpulse]
0 1 [Mpulse] 0 10 [Mpulse]
11 Load-side droop pulses CCW direction 12 Load-side droop pulses CCW direction
10 [V] 10 [V]
(Note 3, 4, 5, 6) (Note 3, 4, 5, 6)
(±10 V/1000 pulses) (±10 V/10000 pulses)
1000 [pulse] 10000 [pulse]
0 1000 [pulse] 0 10000 [pulse]
13 Load-side droop pulses CCW direction 14 Load-side droop pulses CCW direction
10 [V] 10 [V]
(Note 3, 4, 5, 6) (Note 3, 4, 5, 6)
(±10 V/100000 pulses) (±10 V/1 Mpulses)
100000 [pulse] 1 [Mpulse]
0 100000 [pulse] 0 1 [Mpulse]
-10 [V]
App. - 16
APPENDIX
Current
Speed encoder
Command + Position command + Speed + Current
pulse control control control PWM M Servo motor
- - -
Encoder inside
temperature
Current feedback
Encoder
Differen-
tiation
Position feedback
Home position
(CR input position)
(1) Setting
Change the following digits of [Pr. PC09] and [Pr. PC10].
[Pr. PC09]
0 0
Analog monitor 1 output selection
(the signal provided to the output across MO1 and LG)
[Pr. PC10]
0 0
Analog monitor 2 output selection
(the signal provided to the output across MO2 and LG)
[Pr. PC11] and [Pr. PC12] can be used to set the offset voltages to the analog output voltages. Setting
value is -999 mV to 999 mV.
Parameter Description Setting range [mV]
This is used to set the offset voltage of MO1 (Analog monitor
PC11
1).
-999 to 999
This is used to set the offset voltage of MO2 (Analog monitor
PC12
2).
App. - 17
APPENDIX
(2) Setting
POINT
When you use a linear servo motor, replace the following left words to the right
words.
(servo motor) speed [r/min] →(linear servo motor) speed [mm/s]
CCW direction →Positive direction
CW direction →Negative direction
Torque [N•m] →Thrust[N]
The servo amplifier is factory-set to output the servo motor speed to MO1 (Analog monitor 1) and the
torque to MO2 (Analog monitor 2). The setting can be changed by setting in [Pr. PC09] and [Pr. PC10]
as follows.
Refer to (3) for the detection point.
Setting Setting
Output item Description Output item Description
value value
00 Servo motor speed 01 Torque Power running in
CCW direction CCW direction
8 [V] 8 [V]
-8 [V] -8 [V]
CW direction Power running in
CW direction
-8 [V] -8 [V]
CW direction CW direction
06 Servo motor-side droop CCW direction 07 Servo motor-side droop CCW direction
10 [V] 10 [V]
pulses pulses
(Note 1, 3, 5, 6) (Note 1, 3, 5, 6)
(±10 V/100 pulses) 100 [pulse] (±10 V/1000 pulses) 1000 [pulse]
0 100 [pulse] 0 1000 [pulse]
08 Servo motor-side droop CCW direction 09 Servo motor-side droop CCW direction
10 [V] 10 [V]
pulses pulses
(Note 1, 3, 5, 6) (Note 1, 3, 5, 6)
(±10 V/10000 pulses) 10000 [pulse] (±10 V/100000 pulses) 100000 [pulse]
0 10000 [pulse] 0 100000 [pulse]
App. - 18
APPENDIX
Setting Setting
Output item Description Output item Description
value value
0A Feedback position CCW direction 0B Feedback position CCW direction
10 [V] 10 [V]
(Note 1, 2, 3) (Note 1, 2, 3)
(±10 V/1 Mpulses) (±10 V/10 Mpulses)
1 [Mpulse] 10 [Mpulse]
0 1 [Mpulse] 0 10 [Mpulse]
11 Load-side droop pulses CCW direction 12 Load-side droop pulses CCW direction
10 [V] 10 [V]
(Note 3, 4, 5, 6) (Note 3, 4, 5, 6)
(±10 V/1000 pulses) (±10 V/10000 pulses)
1000 [pulse] 10000 [pulse]
0 1000 [pulse] 0 10000 [pulse]
13 Load-side droop pulses CCW direction 14 Load-side droop pulses CCW direction
10 [V] 10 [V]
(Note 3, 4, 5, 6) (Note 3, 4, 5, 6)
(±10 V/10 Mpulses) (±10 V/1 Mpulses)
10 [Mpulse] 1 [Mpulse]
0 10 [Mpulse] 0 1 [Mpulse]
-10 [V]
App. - 19
APPENDIX
Differen- Current
tiation Speed encoder
Position command + Position command + Speed + Current
control control control PWM M Servo motor
received from a - - -
controller
Encoder inside
temperature
Current feedback
Encoder
Differen-
tiation
+
Feedback position - Servo motor
Torque
standard position(Note) speed
Feedback
position
Note. The feedback position is output based on the position data passed between servo system controller and servo amplifier. [Pr.
PC13] and [Pr. PC14] can set up the standard position of feedback position that is output to analog monitor in order to adjust the
output range of feedback position. The setting range is between -9999 pulses and 9999 pulses.
Standard position of feedback position = [Pr. PC14] setting value × 10000 + [Pr. PC13] setting value
App. - 20
APPENDIX
FBN
FBD
+ Semi closed loop Position feedback
+ -
Dual filter
Fully closed loop +
Servo motor-side
droop pulses
Servo motor-side feedback pulses
+ - (load-side encoder resolution unit)
Servo motor-side/load-side
Load-side speed deviation
droop pulses
Differen- +
tiation
-
Servo motor-side/load-side + Differen-
position deviation -
tiation
App. - 21
APPENDIX
POINT
The control circuit power supply of the servo amplifier can be possible to comply
with SEMI-F47. However, a back-up capacitor may be necessary for
instantaneous power failure in the main circuit power supply depending on the
power supply impedance and operating situation. Be sure to check them by
testing the entire equipment using actual machines.
Use a 3-phase for the input power supply of the servo amplifier.
The following explains the compliance with "SEMI-F47 semiconductor process equipment voltage sag
immunity test" of MR-J4 series.
Setting
Parameter Description
value
PA20 _1__ SEMI-F47 selection
PF25 200 Set the time [ms] of the [AL. 10.1 Voltage drop in the control circuit power]
occurrence.
(a) The voltage will drop in the control circuit power with "Rated voltage × 50% or less". 200 ms later,
[AL. 10.1 Voltage drop in the control circuit power] will occur.
(b) [AL. 10.2 Voltage drop in the main circuit power] will occur when bus voltage is as follows.
Servo amplifier Bus voltage which triggers alarm
MR-J4-60_4(-RJ)
to 380 V DC
MR-J4-22K_4(-RJ)
(c) MBR (Electromagnetic brake interlock) will turn off when [AL. 10.1 Voltage drop in the control circuit
power] occurs.
App. - 22
REVISIONS
*The manual number is given on the bottom left of the back cover.
Print Data *Manual Number Revision
Feb. 2013 SH(NA)030119-A First edition
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses.
Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
© 2013 MITSUBISHI ELECTRIC CORPORATION
Country/Region Sales office Tel/Fax
[Term]
The term of warranty for Product is twelve (12) months after your purchase or delivery of the Product to a place designated by you or
eighteen (18) months from the date of manufacture whichever comes first (“Warranty Period”). Warranty period for repaired Product
cannot exceed beyond the original warranty period before any repair work.
[Limitations]
(1) You are requested to conduct an initial failure diagnosis by yourself, as a general rule.
It can also be carried out by us or our service company upon your request and the actual cost will be charged. However, it will not be
charged if we are responsible for the cause of the failure.
(2) This limited warranty applies only when the condition, method, environment, etc. of use are in compliance with the terms and
conditions and instructions that are set forth in the instruction manual and user manual for the Product and the caution label affixed
to the Product.
(3) Even during the term of warranty, the repair cost will be charged on you in the following cases;
(i) a failure caused by your improper storing or handling, carelessness or negligence, etc., and a failure caused by your hardware
or software problem
(ii) a failure caused by any alteration, etc. to the Product made on your side without our approval
(iii) a failure which may be regarded as avoidable, if your equipment in which the Product is incorporated is equipped with a safety
device required by applicable laws and has any function or structure considered to be indispensable according to a common
sense in the industry
(iv) a failure which may be regarded as avoidable if consumable parts designated in the instruction manual, etc. are duly
maintained and replaced
(v) any replacement of consumable parts (battery, fan, smoothing capacitor, etc.)
(vi) a failure caused by external factors such as inevitable accidents, including without limitation fire and abnormal fluctuation of
voltage, and acts of God, including without limitation earthquake, lightning and natural disasters
(vii) a failure generated by an unforeseeable cause with a scientific technology that was not available at the time of the shipment of
the Product from our company
(viii) any other failures which we are not responsible for or which you acknowledge we are not responsible for
4. Exclusion of responsibility for compensation against loss of opportunity, secondary loss, etc.
Whether under or after the term of warranty, we assume no responsibility for any damages arisen from causes for which we are not
responsible, any losses of opportunity and/or profit incurred by you due to a failure of the Product, any damages, secondary
damages or compensation for accidents arisen under a specific circumstance that are foreseen or unforeseen by our company, any
damages to products other than the Product, and also compensation for any replacement work, readjustment, start-up test run of
local machines and the Product and any other operations conducted by you.
MR-J4-_A4(-RJ) MR-J4_B4(-RJ)
SERVO AMPLIFIER
MR-J4-A4 MR-J4-B4
MODEL INSTRUCTIONMANUAL
MODEL
CODE 1CW812